Lennox iComfort S30 Installation And Setup Manual

iComfort® S30
Ultra Smart Thermostat
Installation and Setup Guide
507536-05 5/2018
2018© Lennox Industries Inc.
Dallas, Texas, USA
2
Table of Contents
Shipping and Packing List ........................................................................ 3
Operating and Storage Environment, Electrical and Dimensions ........ 3
Installation Recommendations ................................................................ 3
Smart Hub Installation, External Components, LEDs and Terminals ... 3
Installation .............................................................................................. 3
External Components ............................................................................. 4
Push Button Functions ........................................................................... 4
LED Indicators ........................................................................................ 5
Terminals ................................................................................................ 5
Mag-Mount LED and Installation .............................................................. 5
Installation .............................................................................................. 5
LED Indicators ........................................................................................ 6
HD Display Components and Installation ............................................... 7
Installation .............................................................................................. 7
External Components ............................................................................. 8
Connecting Low Voltage Wiring ............................................................... 8
Control Wiring Requirements.................................................................. 8
Discharge Air Temperature Sensor (DATS) ............................................ 8
Outdoor Air Temperature Sensor (OATS) .............................................. 8
Reducing Electrical Noise on Communication Bus - Indoor,
outdoor, S30 Smart Hub and Optional PureAir S. .................................. 8
Wiring Diagrams ................................................................................... 10
Electric Heat Conguration for iComfort Air Handlers ........................ 15
Commissioning and Service (Using the Mobile Setup Application) ... 15
Mobile Device Operating System Requirements .................................. 15
Establishing a Direct Wireless Connection to the Smart Hub ............... 16
Service .................................................................................................. 16
Alternative Method ................................................................................ 17
Multiple Smart Hubs ............................................................................. 17
Restarting Smart Hub ........................................................................... 17
Commissioning (Using the HD Display) ................................................ 17
Boot-up Screen ..................................................................................... 17
Low Battery Status ............................................................................... 17
Apple HomeKit Wi-Fi Accessory Conguration .................................... 18
Dealer Info and Language Selection .................................................... 18
Warning Screen .................................................................................... 18
General Information .............................................................................. 18
Equipment Found Screen ..................................................................... 18
Non-Communicating Equipment ........................................................... 18
Reminders ............................................................................................ 19
iHarmony Zoning .................................................................................. 19
Commissioning Completion .................................................................. 19
Dealer Control Center ............................................................................. 20
Equipment Parameters ......................................................................... 21
Tests ..................................................................................................... 38
Diagnostics ........................................................................................... 38
Installation Report ................................................................................. 38
Information ............................................................................................ 38
Dehumidication Settings ...................................................................... 39
Dehumidication Setting Options ......................................................... 39
Overcooling .......................................................................................... 39
Dehumidication Set Point ................................................................... 39
Advanced Dehumidication Descriptions ............................................. 39
Displaying Outdoor Temperature (Sensor) and Indoor Humidity
on the Home Screen ................................................................................ 41
Displaying the Outdoor Sensor Temperature on the Home Screen ..... 41
Displaying the Indoor Humidity on the Home Screen ........................... 41
System Congurations ........................................................................... 41
Complete iComfort Systems — Furnace and Air Conditioner .............. 41
Complete iComfort Systems — Furnace and HP Unit
(Dual-Fuel) ............................................................................................ 42
Complete iComfort Systems — Air Handler and Air Conditioner .......... 42
Complete iComfort Systems — Air Handler and Heat Pump Unit ........ 43
Partial iComfort System — iComfort Furnace and Lennox
Conventional Air Conditioner ................................................................ 43
Partial iComfort System — iComfort Furnace and Lennox
Conventional Heat Pump Unit (Dual-Fuel) ........................................... 44
Partial iComfort System — iComfort Air Handler and Lennox
Conventional Air Conditioner ................................................................ 44
Partial iComfort System — iComfort Air Handler and Lennox
Conventional Heat Pump Unit .............................................................. 45
Partial iComfort System — iComfort Equipment Interface Module ....... 45
G71MPP or SLP98 Furnace Setting Adjustments................................. 46
Wi-Fi Connection ..................................................................................... 46
Performance Reports .............................................................................. 47
Replacement Parts .................................................................................. 48
Replacement Indoor and Outdoor Communicating Controls ............. 48
Mobile Applications ................................................................................. 48
Notications (Alert Codes) ..................................................................... 48
3
Alert Code Types .................................................................................. 48
Soft Disable .......................................................................................... 49
Installation Checklist............................................................................... 75
Electrical Troubleshooting ..................................................................... 76
Overview ............................................................................................... 76
Denitions ............................................................................................. 76
Testing .................................................................................................. 76
Index ......................................................................................................... 78
Shipping and Packing List
Quantity Description
1 iComfort S30 ultra smart thermostat includes a Smart Hub, HD Display, Mag-
Mount and optional use wall plate. 4 Mounting screws (#6 X 1.25” pan head) 4 Wall anchors (alligator anged solid wall anchors) 1 Installation and setup guide 1 User guide 1 Warranty certicate
NOTE: Due to Lennox’ ongoing commitment to quality, features and options
are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service
must be performed by a qualied installer and servicing agency.
Operating and Storage Environment, Electrical and Dimensions
• Operating Temperature is -40°F to 175°F (-40 to 79°C)
• Shipping and storage temperature range is -40°F to 185°F (-40°C to 85°C)
• Operating humidity range is 10% to 90% non-condensing at 104°F (40°C)
• Storage humidity range is 5% to 95% non-condensing at 104°F (40°C)
• S30 Smart Hub Power Input: 24VAC, 1AMP at 60Hz.
• S30 Smart Hub DC Power Output: 12VDC (to Mag-Mount/HD Display)
• Dimensions (H x W x D): » Mag-Mount: 3-1/4” x 3-1/4” x 1/2” (83 x 83 x 13 mm) » HD Display: 5” x 7-1/2” x 1” (127 x 19 x 25 mm) » S30 Smart Hub: 4-1/2 x 4-/2 x 1-1/2” (114 x 114 x 38 mm) - antenna
length is 7-1/4” (184 mm)
Installation Recommendations
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a li censed professional HVAC installer (or equivalent) or a service agency.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
Before beginning installation, note the type of equipment, number of stages, and any accessories being installed.
Do
Read this entire document, noting which procedures pertain to your specic equipment and system requirements.
• Make sure that all wiring conforms to local and national building and electrical codes and ordinances.
Do Not
• Install on voltages higher than 30VAC.
• Short (jumper) across terminals on the gas valve or at the system controls to test installation. This will damage the thermostat and void the warranty.
• Exceed 300 feet (91 meters) run when using 18 #AWG thermostat wire or larger.
• Allow power load from any thermostat connection to be more than 1 AMP.
Smart Hub Installation, External Components, LEDs and Terminals
InstallatIon
1. Things to consider when installing the Smart Hub:
• Install near the indoor unit such that there is a direct path to the approximate location of the home Wi-Fi access point (the signal is not blocked by the indoor unit or duct work, for example).
• Can be attached to a vertical surface such as a wall stud or roof truss
web, or to a horizontal surface such as a oor or ceiling joist, or a roof
rafter.
• Smart Hub antenna should be positioned such that it is roughly vertical, no matter the orientation of the Smart Hub, itself.
• Do not install the Smart Hub on the indoor unit, duct work, or other equipment that could induce vibration in the Smart Hub
4
• Do not install the Smart Hub on or near large metal objects. This could adversely affect the range and directional coverage of the Smart Hub Wi-Fi signal.
• If the Smart Hub MUST be installed on a metal object, orientate the antenna perpendicular to the metal surface.
• In all cases, the Smart Hub antenna orientation may need to be adjusted to obtain best Wi-Fi results.
2. Use the following procedure outlined in “Figure 1. Smart Hub Installation” to install the Smart Hub controller.
1/4”
STRIP 1/4” INSULATION FROM END OF EACH CONTROL WIRE
A
B
D
USE SMART HUB AS TEMPLATE TO MARK DESIRED MOUNTING LOCATIONS ON WALL OR STUD.
CAUTION: DO NOT OVERTIGHTEN LOWER MOUNTING SCREW, MAY DAMAGE SMART HUB.
SECURE SMART-HUB TO WALL WITH FIELD-PROVIDED FASTENERS
RAER
TNORF
KEYHOLE
THROUGH-HOLE
C
MAKE CONNECTIONS TO SMART HUB USING WIRING DIAGRAMS PROVIDED
PUSH SPRING-LOADED LEVER IN AND INSERT WIRE THROUGH HOLE LOCATED ON BOTTOM SIDE OF CONNECTOR. RELEASE LEVER TO SECURE WIRE.
SMART HUB WIRE
CONNECTORS
18-GAUGE THERMOSTAT WIRE
Figure 1. Smart Hub Installation
3. For low voltage wiring connections use diagrams in section titled
“Connecting Low Voltage Wiring” on page 8.
ExtErnal ComponEnts
System Status LED
System Commissioning Status LED
USB Port
Dealer commissioning and manual reboot button
T
erminal Connection Access Cover
Antenna
Figure 2. Smart Hub Indicators and External Components
push Button FunCtIons
The Smart Hub push button switch has two primarily functions.
Rebooting: Press and hold the button for ve seconds to reboot the Smart Hub.
Commissioning: Quickly press and release the button to start the process of creating a direct network connection between the Smart Hub and mobile device running the iComfort Mobile Setup application.
5
The push button has a LED associated with it that indicates the status of the Smart Hub commissioning state (see “Table 1. LED Indicators”).
lED InDICators
Table 1. LED Indicators
System Status LED
LED Color Status Description
Green
System is nor­mal
A solid green LED indicates no system errors are detected. System operating as designed.
Red HVAC Fault System has critical alert which needs attention.
Amber Wi-Fi Error
Blinking amber LED indicates either Wi-Fi is not connected, no Wi-Fi is within range, or and Wi-Fi hardware error. Could also indicate intermittent Wi-Fi connection.
Magenta Thermostat Error
Blinking magenta LED indicates either Mag-Mount or HD display not connected.
Cyan HVAC Error Indoor unit is not connected or unable to communicate.
Commissioning Status LED
Blue
System is normal
No mobile device is directly connected using Wi-Fi to the Smart Hub.
Green
Blinking green LED indicates the commissioning button has been activated and the Smart Hub is waiting for a connection with a mobile device.
Green A solid green LED indicates a mobile device is connected to the Smart Hub.
• If multiple errors are present, the system status LED will display each active error for one second on and one second off and then display the next error if present.
• The system will continue to cycle through all active errors.
• System status errors are displayed in the following priority: HVAC , thermostat and then Wi-Fi.
tErmInals
Table 2. Terminal Designations
Terminal Designation Description Terminal Color
R 24VAC input Red I+ RSBUS I+ Yellow I- RSBUS I- Green C 24VAC return Black
ACC1*
Accessory 1 and 2 (FOR FUTURE USE)
Orange
ACC2* White
+ 12VDC output Blue
- 12VDC return Black
A Communications bus A Yellow
Table 2. Terminal Designations
Terminal Designation Description Terminal Color
B Communications bus B Green
* ACC1 and ACC2 are for future use. DO NOT USE.
Mag-Mount LED and Installation
CAUTION
Magnets located in this product have far-reaching and strong magnetic elds.
They could damage TVs and laptops, computer hard drives, credit and ATM cards, data storage media, mechanical watches, hearing aids and speakers.
Keep HD Display and Mag-Mount away from devices and objects that could
be damaged by strong magnetic elds.
InstallatIon
A
ccess Cover
Mag-Mount without
access cover installed.
Wall Plate
(Use is optional)
Use the following procedure for installation of the Mag-Mount where existing thermostat wiring does not exist:
1. Unpack the HD Display and Mag-Mount (wall base).
2. Determine the best location to install Mag-Mount. Ideal location should be
located away from outside wall, direct sunlight or discharge air vents.
3. Cut or drill a small hole for thermostat wiring.
3/8” (10 mm)
Diameter Hole
4. Pull about three inches of thermostat wire through the opening and remove the outer thermostat wire jacket.
6
Seal wire hole in wall to prevent
cold or hot air from affecting temperature
sensor in display.
IMPORTANT
Seal wire hole in wall to prevent cold or hot air from affecting temperature sensor in HD Display.
5. Strip 1/4” (7 mm) insulation from end of each wire.
1/4”
6. Use a level to align either the mag-mount or wall plate on wall horizontally.
7. Remove cover from mag-mount by inserting a at-head screwdriver into
the slot on each side of the mag-mount. Give it a gentle twist to separate the two sections.
Slot
Slot
8. Use Mag-Mount as a template to mark the desired mounting hole locations on the wall.
Use either the Mag-Mount or wall plate as a template to mark the desired mounting hole locations on the wall.
9. Drill 3/16” (5 mm) holes at marked locations on the wall for anchors. Then
insert wall anchors into holes until ush with the wall.
Drill Holes
Insert in hole until flush with wall.
WARNING
DO NOT over-tighten mounting screws. Doing so my distort the mag-mount plastic housing and cause connection issues when installed the HD display.
10. Secure mag-mount to wall or through wall-plate to wall with provided #6 x
1.25” pan-head screws (4).
11. Connect thermostat wiring to Mag-Mount terminals referencing provided wiring diagrams in this guide.
12. Reinstall access cover.
NOTE: Verify that the Mag-Mount access cover is reinstalled correctly to the
Mag-Mount base. The access cover must be ush with the base or
could cause power or communication issues.
lED InDICators
1. A blue LED is visible on the front of the Mag-Mount when it is connected, power applied, and the HD Display has not been installed (see following illustration). The blue LED is also visible through the top vent of the Mag­Mount near the top-left corner when the HD Display is installed.
7
System Status LED
System Commissioning Status LED
Mag-Mount
COMM
A
BUS
B
12VDC
+ -
Blue LED Location
Smart Hub
Table 3. Communication Error Troubleshooting
(Mag-Mount to Smart Hub)
Possible Connection Issues
Mag-Mount LED Condition
(HD Display Removed)
S30 Smart Hub - System Status LED
One communication wire at either the Mag­Mount or Smart Hub COMM BUS A or B termi­nals is disconnected.
Steady Blue
Flashing Magenta LED
Both communication wires – at either the Mag­Mount or Smart Hub COMM BUS A or B are disconnected.
Flashing Blue
Flashing Magenta LED
Both communication wires – at either the Mag-Mount or Smart Hub COMM BUS A or B terminals are reversed.
Flashing Blue
Flashing Magenta LED
Power wires at either the Smart Hub or Mag­Mount 12VDC + and - terminals are disconnect­ed.
Off
Flashing Magenta LED.
If terminals are connected correctly, then check HD Display mounting to Mag-Mount. HD Display may not be secured correctly to Mag-Mount.
LED not visible when HD Display is installed.
Flashing Magenta LED.
HD Display screen may be either blank or a message indicat­ing iComfort cannot communicate with the equipment.
HD Display Components and Installation
InstallatIon
1. Hold the HD Display by the edges, line it up with the Mag-Mount (horizontal position), and move the HD Display toward the Mag-Mount.
2. When the magnets in the Mag-Mount attract the HD Display, guide it toward the Mag-Mount and let the magnets pull it into place.
3. Lightly press on the sides of the HD Display to verify it is completely seated on the Mag-Mount.
4. To remove the HD Display from the Mag-Mount, rotate the HD Display right or left (clockwise or counter-clockwise) at least 30 degrees to disengage the plastic hooks and then pull it straight off of the Mag-Mount
WARNING
Failure to rotate the HD Display before pulling it off of the Mag-Mount may loosen the dry wall anchors or pull the Mag-Mount off of the wall due to the increased forced required to separate the HD Display from the Mag-Mount when it is not rotated.
NOTE: If the HD Display is removed from the Mag-Mount base, the HD Display
will shut down and will not be able to communicate with the system. System can be controlled from mobile devices or consumer/dealer web portals once registration has been completed.
5. Do not remove the label covering the HD Display screen until after power is applied to the system.
CAUTION
1) Battery may need to charge before operation. Once the display is connected, instructions may appear within 15 seconds with further detail.
2) TO AVOID BREAKING THE GLASS DISPLAY a. Do not apply force directly to the glass display b. Holding the display horizontally i. Center the display cavity on the base ii. Press both sides equally until the snaps engage
3) AVOID EXCESSIVE FORCE TO THE CLASS DISPLAY
8
ExtErnal ComponEnts
• Proximity sensor - Detects a person approaching the HD Display. If the HD Display is in Screen Saver mode and the Proximity Sensor setting is enabled, the proximity sensor takes the HD Display out of screen saver mode automatically and returns to the home screen when someone approaches.
• Power button - Turns off the HD Display when pressed and held for about
ve (5) seconds.
• microSD card slot - Not functional, for future use.
• Micro USB connector - Not functional, for future use.
Proximity Sensor
Power Button
microSD Slot
Micro USB Connector
Figure 3. HD Display Components
Connecting Low Voltage Wiring
The following diagrams in this section illustrates the basic Lennox control wiring for all compatible components.
Control WIrIng rEquIrEmEnts
The following is the wiring specication requirements for installation of this
system.
• iComfort wiring size is 18 #AWG.
• Thermostat does not required shielded cable wiring.
• Maximum total length of all connections combined is 1500 feet (457 meters).
• Maximum length between components is 300 feet (90 meters).
DIsChargE aIr tEmpEraturE sEnsor (Dats)
Installation of discharge air temperature sensor (DATS) (88K38) must comply with the following requirements:
• Installed downstream of the heat exchanger or electric heat elements.
It must be placed in free airow, where other accessories (such as humidiers, UV lights, etc.) will not interfere with its accuracy.
• Wiring distance between the integrated furnace and air handler controls or damper control module and the discharge air sensor must not exceed 10 feet (3 meters) when wired with 18 #AWG thermostat wire.
• DATS is highly recommended for all systems that include a modulating
outdoor unit in order to provided more precise dehumidication operation.
outDoor aIr tEmpEraturE sEnsor (oats)
The optional outdoor air (temperature) sensor (OAS) (X2658) wiring distance to the iComfort S30 should not exceed 150 feet (45 meters) when wired with minimum 22 #AWG (recommend 18 #AWG) dedicated 2-conductor thermostat cable. Installation of OAS must comply with the following requirements:
• Sensor wiring must be run to avoid touching or being close to high voltage wiring and light ballast.
• Choose a protected outdoor location away from direct sunlight or other heat sources (usually on the north side of the building).
• Ensure that water will neither collect on, nor wash over the sensor.
• Do not locate the sensor near driveways or similar heat-absorbing masses
which may reect stored heat energy onto the sensor and send inaccurate
information to the thermostat.
Locate the sensor away from attic and soft vents, or furnace venting pipes.
• Do not locate the sensor directly above an air conditioner or heat pump.
rEDuCIng ElECtrICal noIsE on CommunICatIon Bus - InDoor, outDoor, s30 smart huB anD optIonal purEaIr S.
Communicating systems requires four thermostat wires between the Mag­Mount and Smart Hub. Four wires are also used between the Smart Hub and indoor/outdoor units as well. When a thermostat cable with more than four wires is used, the extra wires must be properly connected to avoid electrical noise. The wires must not be left disconnected.
• Use wire nuts to bundle the unused wires at each end of the cable. A single wire should then be connected to the indoor unit end of the wire bundle and attached to the “C” terminals as shown in “Figure 4. Thermostat Wire Termination in Communicating Systems (Electrical Noise)”.
• Keep all communication wiring as far away from the house electrical wiring and large electrical appliances as possible. Recommended minimal distance is 15 feet (5 meters).
9
Unused wires
Unused wires
12VDC
+ -
COM
BUS
A B
12VDC
+ -
COM
BUS
A B
Single wire
to bundle
wire to indoor
terminal “C”.
Single wire to indoor unit terminal “C”.
Unused wires
Single wire
to terminal “C”.
Indoor Unit Controller
Outdoor Unit
Smart Hub
Mag-Mount
R i+ I- C
Figure 4. Thermostat Wire Termination in Communicating Systems (Electrical Noise)
Unused wires
Single wire
to terminal “C”.
Indoor Unit Controller
PureAir S
Figure 5. Thermostat Wire Termination in Communicating Systems (Electrical Noise) - Optional PureAir S
10
WIrIng DIagrams
The following diagrams are typical low voltage wiring connections for various
system congurations.
iComfort Indoor Unit
S30 Smart Hub
C
i+
i-
R
S30
Mag-Mount
12VDC
+ -
COM
BUS
A B
COM
BUS
B A
12VDC
- +
ACC1 ACC2
iComfort Outdoor Unit
OATS (Optional)
DATS (Optional)
Figure 6. iComfort System
24VAC 1- or 2-Stage
Heat Pump
iComfort
Air Handler
SETUP NOTES:
CUT Y1-Y2 ON-BOARD
MUNICATING)
CUT R-O ON-BOARD LINK FOR OUTDOOR HEAT
MUNICATING)
COM
BUS
B A
12VDC
- +
12VDC
+ -
COM
BUS
A B
S30
Mag-Mount
S30 Smart
Hub
ACC1
ACC2
DATS (Optional)
OATS (Optional)
Figure 7. iComfort System with Non-Communicating Heat Pump
24VAC Outdoor Unit
(1 - or 2-Stage Air Conditioner)
SETUP NOTE:
CUT Y1-Y2 ON-BOARD LINK FOR 2-STAGE OUTDOOR UNITS (NON-COMMUNICATING)
COM
BUS
B A
12VDC
- +
12VDC
+ -
COM
BUS
A B
S30 Smart-Hub
S30
Mag-Mount
ACC1
ACC2
iComfort Indoor Unit
DATS (Optional)
OATS (Optional)
Figure 8. iComfort System with Non-Communicating Air Conditioner
24VAC 1- or 2-Stage
Indoor Unit
EIM
iComfort
Outdoor Unit
COM
BUS
B A
12VDC
- +
12VDC
+ -
COM
BUS
A B
S30
Mag-Mount
S30 Smart Hub
If jumber is present between
R and W2 on indoor unit terminals then
removed it. Installed jumper
may cause erroneous Alert Code 125.
ACC1
ACC2
Figure 9. iComfort System with Equipment Interface Module,
Non-Communicating Indoor Unit and Communicating Outdoor Unit
11
DATS (Required)
OATS (Optional)
IN-ZONE
THERMOSTATS
PWR D+ D­C
PWR
D+
D-
C
PWR D+ D­C
See iHarmony Installation instruction for damper connection information.
INDOOR
DOOR” ON DAMPER CONTROL MODULE TO CONNECT TO THE INDOOR UNIT.
PWR
D+
D-
C
iComfort Indoor
Unit
TSTAT
IHARMONY ZONING
SYSTEM
To Smart
Hub
To indoor unit
To iHarmony
If unable to connect two wires to indoor unit terminals then pigtail wiring as exampled here.
COM
BUS
B A
12VDC
- +
12VDC
+ -
COM
BUS
A B
S30 Smart Hub
S30
Mag-Mount
DATS
UP TO THREE
IN-ZONE
THERMOSTATS
ARE SUPPORTED
ACC1
ACC2
iComfort Outdoor
Unit
Figure 10. iComfort System with iHarmony Zoning System
12
+- AB ODT
FLOAT
Switch
DH DH
Gh Rf Cf Gs YW
HVAC EQUIP
.
DH
C
G R
NC NO
NC
NO
SPDT RELAY
f
C
s
G h
G W
fR
HVAC EQUIP
DH
NC
AUXILIARY DEHUMIDIFIER MODELS HCWHD-090
AND HCWHD-135
NOTE: HCWHD-065 IS NOT COMPATIBLE
AUXILIARY DEHUMIDIFIER MODELS HCWHD3-070 AND HCWHD-095
ICOMFORT
INDOOR
UNIT
12VDC
- +
12VDC
+ -
COM
BUS
B A
COM
BUS
A B
ICOMFORT
INDOOR
UNIT
COM
BUS
B A
12VDC
- +
12VDC
+ -
COM
BUS
A B
S30 MAG
MOUNT
S30 SMART
HUB
AUXILIARY DEHUMIDIFIER
S30 SMART
HUB
S30 MAG
MOUNT
ACC1 ACC2
Figure 11. iComfort System with Auxiliary Dehumidier Accessory
13
SLP98 & G71MPP FURNACE (IFC) OR AIR
HANDLER (AHC)
NOTE: 24V UV LIGHT APPLICATIONS
IN AN ICOMFORT
®
SYSTEM, NEITHER FURNACE NOR AIR HANDLER
CATIONS. AN ADDITIONAL TRANSFORMER FOR UV LIGHT APPLICATIONS IS REQUIRED. UV LIGHT WIRING CONNECTIONS ARE INDEPENDENT OF HVAC SYSTEM OPERATION; SEE UV LIGHT INSTALLATION INSTRUCTIONS.
NOTE: ICOMFORT
®
SENSES HUMIDITY & CONTROLS 24V “H” OUTPUT (& 120V “H” OUTPUT) TO CYCLE HUMIDIFIER BASED ON DEMAND. NO OTHER CONTROL OR HUMIDISTAT REQUIRED.
OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH HUMIDIFIER (IF NOT
FORT OUTDOOR UNITS). (SEE OAS NOTES)
SL280, EL296 FURNACE
48G96 Relay
GND
IN
ICOMFORT
®
OUTDOOR UNIT
SMART HUB
FOR SL280 & EL296, SEE HUMIDIFIER DIAGRAM BELOW
(BOTTOM RIGHT)
120VAC<-------HUMIDIFIER CONNECTIONS------> 24VAC
SMART
HUB
CHARGE AIR SENSOR
(SEE DAS NOTES)
OPTIONAL OUTDOOR
AIR SENSOR (SEE OAS
NOTES)
A
i+
B
-
A
i+
B
-
HD
DISPLAY
Mag-Mount
12VDC
+ -
COM
BUS
A B
12VDC
- +
COM
BUS
B A
ERV/HRV 3 AND 5
ACC1
ACC2
Figure 12. iComfort System with Humidier Accessory
14
LVCS VENTILATION CONTROL
SYSTEM
26L56 CURRENT SENSING RELAY KIT.
NOTE: PASS THE BLOWER MOTOR L1 WIRE THROUGH THE
RENT SENSING RELAY AS SHOWN.
SLP98 & G71MPP FURNACE (IFC) OR AIR HANDLER (AHC)
LVCS. SET CYCLE TIME TO 1 HOUR; SET VENTILATION TIME TO 60 MINUTES.
NOTE: USE THE ICOMFORT
®
S30 CIRCULATE FAN PERCENTAGE OF ON TIME TO CONTROL VENTILATION TIME.
SMART HUB
Mag-Mount
12
VDC
- +
COM
BUS
B A
12
VDC
+ -
COM
BUS
A B
ICOMFORT
FURNACE OR AIR
HANDLER
HEPA BYPA SS FILTER X2680 HEPA
INTERLOCK KIT
TOR COMMON WIRE THROUGH CURRENT LOOP.
SEE HEPA INTERLOCK KIT FOR INSTALLATION DETAILS
ICOMFORT
OUTDOOR AIR CONDITIONING OR HEAT PUMP
STANDARD 1 OR 2 STAGE AC OR HP UNIT
ICOMFORT FURNACE OR AIR HANDLER
ICOMFORT
FURNACE OR AIR
HANDLER
(POWER COMPANY INTERRUPTION SYSTEMS ARE WIRED SAME AS OVERFLOW SWITCH)
ICOMFORT
2-STAGE
FURNACE
CUT R-DS W914
DS
R
HVAC HEAT OR COOL CALL, OR THE FAN IS IN CONTINUOUS OPERATION, THE VENTILATION CONTROLLER WILL OPEN OA DAMPER TO VENTILATE IF THE OUTDOOR TEMPERATURE AND
TION CONTROLLER.
ACC1
ACC2
Figure 13. Optional Accessories
15
Electric Heat Conguration for iComfort Air Handlers
IMPORTANT
Prior to running the thermostat installer setup, electric heat must be manually
congured.
IMPORTANT
After electric heat strips are installed, the air handler control must be manually
congured to detect the number of electric heat sections. (See 506181-01 for complete conguration guide.
OUTDOOR
AIR SENSOR
HEAT
1234
COOL
1234
DELAY
1234
ADJUST
NORM + −
HUMIDIFICATION
SMART AUTO
EVENHEAT
1234
BLOWER
ONLY CFM
100
11 5
130
85
Y1−Y2
2−STAGE
COMPR
R−O
HEAT
PUMP
R−DS
DEHUM
OR
C
W1
W2
G
Y2
Y1
C
R
DH
H
L
O
DS
W3
FUSE3 AMP
XFMR 24V
24 VAC
COM
3
6
9
1
4
7
XFMR LINE
G
2
5
8
P8
L1
L2
L2 L1
INDOOR BLOWER POWER
EARTH
INDOOR BLOWER
SIGNAL
45 6
12 3
A92 INTEGRATED CONTROL
OUTDOOR UNIT
LINK
I +
I −
I +I −RC
I +I −RC
THERMOSTAT
HUMIDITROL
DH
DISCHARGE AIR SENSOR
HARMONY
PUSHBUTTON LED
Figure 14. Air Handler Control
This procedure is applicable only to the CBX32MV-XX-230-6-06 and higher
and all CBX40UHV models. This procedure is for conguring the heat strips so
that they will be detected by the thermostat:
• Power must be applied to the air handler but NOT to the Smart Hub.
• Disconnect any communication wiring between the Smart Hub and indoor unit prior to electric heat discovery.
• The air handler control must be in idle mode (decimal blinks at 1 Hertz—0.5 second ON, 0.5 second OFF to use the following procedure.
1. Select eld test mode—press and hold the push button until solid “–”
appears; release button. Display will blink.
2. Push and hold button and wait for the display LED to show “H” (capital H), then release the button.
3. The air handler control cycles the indoor blower motor “on” to the selected heat speed and stages the electric heat relays “on” and “off” to automatically detect the number of electric heat sections. The air handler control stores the number of electric heat sections, then automatically exits “Field Test Mode”.
4. The thermostat will now detect the heat strip information stored in the air handler control.
5. Turn off power and connect all low voltage wiring (power and communication to and from the Smart Hub).
6. After completing the commissioning of the system then check to see if you have electric heat or emergency heat.
Commissioning and Service (Using the Mobile Setup Application)
This application tool is used by dealers to commission a iComfort S30 ultra smart thermostat using a Wi-Fi enabled mobile device.
A temporary Smart Hub local network provides a means for a mobile device using the iComfort Mobile Setup application to directly communicate with the Smart Hub.
NOTE: The iComfort Mobile Setup application running on a mobile device
cannot connect to the Smart Hub through the Internet or home Wi-Fi network.
To use the iComfort Mobile Setup app, the mobile device must be:
• Wi-Fi capable
• Located in the home near the Smart Hub
NOTE: A router with Bonjour capabilities is required for this function. Check the
router features if the Smart Hub does not connect. Apple Bonjour® is an
implementation of Zero-conguration networking (Zeroconf), a group
of technologies that includes service discovery, address assignment, and host name resolution.
moBIlE DEvICE opEratIng systEm rEquIrEmEnts
The iComfort Mobile Setup application is available for both IOS 6.0 and higher (App Store) and Android 4.1 and higher (Google Play).
16
EstaBlIshIng a DIrECt WIrElEss ConnECtIon to thE smart huB
IMPORTANT
If the connection between the iComfort Mobile Setup application and Smart Hub is idle for three (3) minutes, the Smart Hub will auto-disconnect from the mobile device. Repeat procedures to reconnect.
1. Download and install the iComfort Mobile Setup application.
NOTE: It is recommend that when using the iComfort Mobile Setup application
to commission the system, remove the HD Display from the Mag­Mount before starting. Once commissioning is completed, reattach the HD Display to the Mag-Mount.
2. Go to the Smart Hub and press the commissioning button located on the side of the unit (see “Figure 2. Smart Hub Indicators and External Components” on page 4 for location of button).
3. The commissioning status LED will start blinking green for two minutes.
During this time the Smart Hub will broadcast its Wi-Fi identier (SSID).
4. Go to your mobile device’s Wi-Fi connection tool and locate the Smart
Hub Wi-Fi broadcast identier. A typical example of a identier (SSID) is
DIRECT-XY12-3456.
NOTE: Refer to your mobile device’s owners manual on how to use your Wi-Fi
Connection tool.
5. Connect to the Smart Hub by using the last eight digits of the Smart Hub SSID as the password. In this example, it would be XY123456).
6. Once the mobile device is connected to the Smart Hub, the commissioning Status LED will turn solid green.
7. Start the iComfort Mobile Setup application and make sure you are connected to the correct Smart Hub by checking the serial number.
8. Touch the remote-in tab on the iComfort Mobile Setup application home screen. This will take you to the commissioning screen.
9. You can use the information provided in “Commissioning (Using the HD Display)” on page 17 to complete the commissioning process using the iComfort Mobile Setup application.
10. If the system has not been commissioned it will go to commissioning screen automatically. If the system has already been commissioned it will go to dealer control center.
11. Once the commissioning is completed, exit the iComfort Mobile Setup application.
12. Go to the mobile device’s Wi-Fi tool and manually disconnect from the Smart Hub.
13. Once disconnected, the Smart Hub commissioning LED will change to solid blue.
14. Reinstall the HD Display on the Mag-Mount.
sErvICE
To use iComfort Mobile Setup application as a service tool, the commissioning of the system must have already been completed.
1. Download and install the iComfort Mobile Setup application if not already installed.
2. Go to the Smart Hub and press the commissioning button once.
3. The LED will start blinking green for two minutes. During this time the Smart
Hub will broadcast its Wi-Fi identier (SSID).
4. If this is the rst time connecting to the target Smart Hub then go to your
mobile device’s Wi-Fi connection tool and locate the Smart Hub Wi-Fi
broadcast identier. A typical example of a identier (SSID) is DIRECT-
XY12-3456.
5. If your mobile device had already connected previously to the target Smart Hub, then touch the applicable Smart Hub SSID on the list and skip to step
7.
NOTE: Refer to your mobile device’s owners manual on how to use our Wi-Fi
Connection tool.
6. Connect to the Smart Hub by using the last eight digits of the Smart Hub SSID as the password (XY123456) for example.
7. Once connected to the mobile device the Smart Hub commissioning LED will turn solid green.
8. Start the iComfort Mobile Setup application and make sure you are connected to the correct Smart Hub by checking the serial number.
9. Touch the remote-in tab on the iComfort Mobile Setup application home screen.
10. If the system has not been commissioned it will launch the commissioning screen. If the system has already been commissioned it will go to dealer control center.
11. Once servicing is completed, exit the iComfort Mobile Setup application.
12. Go to the mobile device’s Wi-Fi tool and manually disconnect from the
Smart Hub.
13. Once disconnected the Smart Hub LED will change to a solid blue.
17
altErnatIvE mEthoD
From the home screen, go to menu > settings > advanced settings > pair Smart Hub to iComfort dealer mobile application selection. It will auto connect to dealer application and start you at the dealer control center screen. The following screen will appear and show the status of the connection. Once connected the screen will automatically disappear.
view dealer dashboard
restart
pair Smart Hub to icomfort dealer mobile app
advanced settings
wi- local
smart away on
o
auto
Feels Like
fan
heat & cool
humidity
iHarmony zoning
notications
general
display
settings
advanced settin
gs
wi-
loca
l
s
mart
a
Feels
L
f
an
h
eat &
h
umid
i
Harm
o
notic
a
gener
a
d
ispla
y
s
ettings
viewdea
ler dashbo
ard
aw
ay
y
i
ke
e
c
oool
i
ty
o
ny
y
z
o
on
ati
ions
y
Connect to the Smart Hub from the dealer iComfort mobile app
now broadcasting...
stop
Figure 15. Pairing
multIplE smart huBs
Multiple Smart Hubs in a home can be assigned to a group (up to nine groups with up to eight (8) Smart Hubs in each group). All Smart Hubs in a group can communicate with other Smart Hubs in the same group over the home Wi-Fi network.
Default Group ID is 1. Range is 0 to 9. For example, seven Smart Hubs in a home can be divided up for example as 1
in Group 1 and six in Group 2 or 4 in Group 1 and 3 in Group 2. Smart Hubs in Group 1 will not be able to see or interact with the Smart Hubs in Group 2. This allows the intentional isolation of the Smart Hub for the master bedroom from the Smart Hub for the children’s area, for example.
NOTE: If a Smart Hub is set to Group 0, it will not communicate with other
Smart Hubs.
rEstartIng smart huB
Pressing the Smart Hub button for more than ve seconds will reboot the Smart
Hub.
Commissioning (Using the HD Display)
The following procedures are written for commissioning the system using the HD display interface.
When power is rst applied to the system all iComfort devices attached to the
system (air handler or furnace, outdoor unit or zoning control) will automatically
be congured using optimal factory default settings based on system type, capacity and other conguration considerations.
NOTE: If there is an PureAir S air purication system installed, during
commissioning the blower will turn on and run at three different CFM
settings for the PCO lter calibration to take place. This may be well in
advanced before the display is fully up and running. This is a normal process. The blower may run as long as 90 seconds at each CFM
setting to complete the lter calibration .
Boot-up sCrEEn
When power is applied to the system, the HD Display will display a welcome screen.
If there is an issue with communication between any components attached to the thermostat, a critical alert message will appear on the screen. The alert message will provide detail information concerning the possible cause. Once
the issue is corrected and power is restored to the system the rst screen in the
initial commissioning sequence will appear. Below is an example of a communication error message.
IComfort cannot communicate with the equipment
If problem persists, please contact your iComfort dealer at
1-800-555-8888
alert
IComfort is unable to connect to the Smart Hub device
For additional support, contact Lennox at
1-800-9-LENNOX or visit www.lennox.com/support
Figure 16. Communication Error Message Example
loW BattEry status
If a critical low battery screen is displayed, the system will automatically start charging the HD Display internal battery. On the screen the word “charging” will appear. Once “charging” disappears (typically 3 to 10 minutes) then the display will automatically start-up.
18
applE homEKIt WI-FI aCCEssory ConFIguratIon
A pop-up screen will appears providing instructions on how to connect the thermostat to the home Wi-Fi network using an Apple IOS device. If you wish to
use this method to congure the unit for Wi-Fi and Apple HomeKit, then refer to
the provided user guide for additional instructions. Otherwise, select cancel to proceed with the thermostat commissioning
procedures. There is an option to perform this task later on at the homeowners convenience.
NOTE: This procedure can only be accomplished using a Apple IOS device.
Figure 17. IOS Wi-Fi Accessory Conguration
DEalEr InFo anD languagE sElECtIon
The rst screen in the commissioning sequence is the dealer information
screen and language selection tool. Supported languages are English, French and Spanish. The drop-down selection tool is located in the upper right-hand corner of the screen.
Dealer ID and/or phone number can be added. Once the system is connected to the Internet, the remaining information will be populated automatically by the Lennox server based on the dealer ID or phone number entered. All information can be entered manually if desired however.
Information that can be manually entered is name, email website, dealer address which includes address 1, address 2, city, state and zip/postal code. Once completed touch continue.
WarnIng sCrEEn
If either the Dealer ID or phone number is NOT provided, a warning screen will appear. The warning screen will provide information on the limitation imposed on the system if this information is not provided. Touch no to return to the previous screen to complete the information requested or touch yes to continue.
gEnEral InFormatIon
On this screen general information needs to be veried or changed. Touch
any item to change its contents. A pop-up screen will appear that will allow the information to be added or changed.
1. Select country / region.
2. Select time and date which includes time, date, time zone and daylight
savings time (ON/OFF).
3. Temperature unit (Fahrenheit or Celsius).
4. Once completed touch continue.
EquIpmEnt FounD sCrEEn
This screen will display any iComfort equipment the system has detected (air handler, furnace, outdoor unit, PureAir S, Smart Hub and iHarmony zoning system during initial commissioning of the system.
NOTE: When a Lennox Equipment Interface Module (EIM) is used and
congured as either a furnace or air handler, then the component
would appear as either EIM-Furnace or EIM-Air Handler. When using a EIM the outdoor unit may be either a Lennox iComfort or any standard 24VAC non-communicating unit.
NOTE: Not all equipment may be visible from the equipment found system
screen. Touch and swipe up to access additional information (if applicable) listed at the bottom of the system box.
If non-communicating equipment needs to be added, it can be done so from this screen.
non-CommunICatIng EquIpmEnt
When selecting the non-communicating (24VAC) equipment icon a screen will appear listing equipment that can be added. When selecting an applicable component, a green check will appear next to the item. The capacity selection of the outdoor unit will also be displayed on the screen after selecting the applicable outdoor equipment type.
NOTE: A temporary dialog box will appear indicating: Updating - Wait while we
check for dependencies.
NOTE: Selecting an outdoor unit type only appears if a iComfort outdoor unit
is not detected by the system. Selections are one or two-stage heat pumps or air conditioners. Outdoor unit capacity will also have to be set.
Other equipment that can be added are humidiers and dehumidiers.
Once completed touch done which will display the equipment found screen. There the additional non-communicating equipment will now be displayed along with the iComfort equipment.
Once completed touch continue.
19
rEmInDErs
This screen allows you to set reminders as either disabled or 3, 6, 12 or 24
months and also custom by specic date. The other options on this screen is to
trigger the reminder event either by calendar or actual system run-time.
1. Reminders may be set for replace lter 1, replace lter 2, replace UV
bulb, replace humidier pad, PureAir™, PureAir S maintenance and maintenance reminder. Once a reminder is set for a specic item, touch
done to return to the previous screen. An “expires on date” will appear next to the item just set.
2. Once completed touch continue.
Iharmony ZonIng
This screen will only appear if the iHarmony® zoning system is detected. This screen allows you to rename each zone. You may use the preset names or any custom name you may desire. If zoning is not applicable, proceed to the next section.
1. Touch on any zone to rename it. A screen will display that list several
predened names that can be used which are master bedroom, guest
bedroom, kitchen, living room, media room, dining room, library or custom.
When a predene name is selected, a green check-mark will appear next
to the selected name.
2. When creating a custom name, touch custom, enter a name and touch back to return to the previous screen. A new unique zone name can be created for all four zones.
3. When completed, touch done to return to the zoning screen and verify the
new name is being used for the specic zone.
4. Once completed touch continue.
SET UP AIRFLOW PER ZONE
This screen will allow the installer to setup the airow per zone. The types of
circulation per zone are:
Blower Circulation Airow (gray) which includes total, assigned, minimum
and maximum airow.
Heating Circulation Airow (red) which includes total, assigned, minimum
and maximum airow.
Cooling Circulation Airow (blue) which includes total, assigned, minimum
and maximum airow.
1. Touch on the circled green arrow to touch a specic zone. The that zone
settings will expand to allow the installer to adjust CFMs for each circulation
airow type. Use the plus and minus buttons to adjust CFMs up and down.
2. Once completed touch to continue. The next screen that will appear is the Dealer Control Center.
CommIssIonIng ComplEtIon
Once commissioning is completed, the system will leave you at the Dealer Control Center. You can either touch exit to go to the main screen or perform
any function listed in the various categories displayed.
20
Dealer Control Center
This menu provides access for the installer or service technician to perform various functions. Advance equipment congurations, notications, tests, diagnostics,
installation reports and general information about the system.
dealer
control center
equipment
tests
notifications
information
diagnostics
exit
Use to make changes to equipment settings and add or remove
non-communicating equipment or accessories. In addition the reset all
equipment option is available. This will allow the installer to reset all
equipment and reconfigure.
Use to display
system notifications
Use to run test on
system components
Use to run diagnostics on system components
Use to display system information
Exit to Home
screen.
To navigate back to the dealer control center, touch on the Dave Lennox icon when available on the top left-hand side of the screen.
<
<
To navigate back to the previous screen, touch on the left arrow when available.
“Previous Screen Name”
installation
report
Used to display installation results.
NOTE: This report is not available until after exiting the dealer control center following the commissioning procedure. Exit and return to the dealer control center to view the installation report.
Figure 18. Dealer Control Center
21
EquIpmEnt paramEtErs
Selections listed in this section are dependent on system hardware conguration. Not all options listed in this section will be available.
NOTE: When changing the default settings for any parameter, there is a possibility that it will affect the settings for another parameter. If this happens, a pop-up
message will be displayed listing the other affected parameters and their new automatically set values.
The following is a complete list of all possible parameters listed under System. Parameters actually available are dependent on the Lennox communicating equipment type detected and non-communicating equipment added.
Table 4. Smart Hub Parameters
Parameter Description
About
This screen provides information concerning language supported, equipment type name, control software revision, model, control mode number, control serial number, control hardware revision, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, compatible devices list, application code memory size and micro-controller part number.
Auto Changeover
- Humidif. Deadband
Prevents the Humidication and Dehumidication settings from being closer together than 5% or greater than 10% (Dead-band).
Range is 5 to 10%. Default is 5%. Adjustments are in increments of 1%.
Auto Changeover -
Temp Deadband
Prevents the Heating and Cooling from being set closer together than 3ºF (1.67°C) or greater than 9ºF (5.0°C) (Dead- band). Range is 3 to 9°F (1.67 to 5.0°C). Default is 3°F (1.67°C). Adjustments are in increments of 1°F (0.56°C).
Auto Dehumidication
Overcooling Threshold
Adjustments are in increments of 1%. This value can automatically be affected by adjusting other parameters. One example would be when enabling Max Dehumidica­tion Overcooling.
Range is 0 - 10%. Default is 4%.
Aux Heating Activation
Threshold
This is an adjustment to hasten or delay the aux heat activation. This adjusts how far below the set point the temperature must fall with the HP at 100% before allowing electric heat to come on.
Range is 0 - 10°F (0.0 to 5.56°C) with increments of 0.25°F (0.14°C). The default setting is 2.5°F (0.83°C).
Denition/Dependencies:
Step Change versus Steady State Modes
• Outdoor temperature below the high balance point or with balance points disabled.
• Heat Pump demand above 95% for 10 minutes.
• Sixty (60) minute temperature rise prediction = less than this Parameter Setting (value)
Result:
The Heating Proportional Integral Algorithm (as set for less, normal, or more aggressive) will begin to stage on the electric heat to bring the space temperature up to set point.
Synopsis: The LOWER this parameter is set, the quicker the auxiliary heating will respond, in both step change mode and steady state mode.
Balance Point Control
If system is set up as dual fuel or heat pump with electric heat and a outdoor temperature sensor connected to Smart Hub, the low and high balance point settings will appear. The balance points feature requires that a sensed outdoor temperature is provided to the thermostat. The outdoor ambient temperature can be read from either a:
• Field-installed outdoor temperature sensor (X2658).
• iComfort heat pump. All iComfort heat pumps have a factory-installed outdoor temperature sensor. Options are enabled or disabled. Default is disabled. When enabled, both low and high balance points can be set.
High Balance
Point
This setting is used to prevent the furnace or electric heat from heating the structure. (Alert 19 - Minor - Notication only - The outdoor temperature is higher than the level
where the furnace or electric heat is programmed to heat the home.) Range is -17 to 75°F (-27.22 to 23.89°C). Default is 50°F (10.0°C). Adjustments are in increments of 1°F (0.56°C).
Low Balance
Point
Setting used to prevent the heat pump from heating the structure. (Alert 18 - Minor - Notication only - The outdoor temperature is below the level where the heat pump is
programmed to heat the home). Range is -20 to 72°F (-28.89 to 22.22°C). Default is 25°F (-3.89°C). Adjustments are in increments of 1°F (0.56°C).
NOTE: Dual-Fuel Applications (Communicating Systems Only) - Dual fuel applications, which include both a Heat Pump and a gas furnace, will provide multiple stages
of heating. For example, a two−stage heat pump would deliver two stages of heat. The gas furnace can add two to four more stages of heat.
22
Table 4. Smart Hub Parameters
Parameter Description
CFA Cooling
Discomfort Threshold
Default is ON. The purpose of this algorithm when set to ON is to detect systems with faults which are causing measurable loss of comfort and thus, need repair/service intervention.
The algorithm monitors the duration in which the indoor temperature is above the cool set point or below the heat set point and does not approach the set-point. When an issue is detected alarm 901 is activated.
Cooling Mode
Options are Normal and Comfort. Default is Normal. When changing to Comfort Mode, several parameters are automatically modied for optimal system operations. The
changed parameters are listed on the screen when set to Comfort.
Normal - This setting cools the home to the desired temperature setting. Once second-stage is activated by timer or differential, it will not stage down to rst-stage until the next cooling cycle demand.
• Comfort - This is when the system could automatically stage up or down based on the current load demand.
Cooling Prognostics
This algorithm will determine whether the unit will run out of capacity during the hottest time of summer. It will look back everyday a minimum of three days to see if there
is a pattern and compare it to the hottest day on record for that zip code before triggering an notication. It must see a pattern before it will trigger the notication. There
may be a component or components that will require attention. The sensitivity (threshold) selection options are OFF, LOW, MEDIUM, and HIGH. The default is HIGH. The alert code notication is 65545.
DAT Integral
Gain
(Lennox Modulating Outdoor Units Only)
The indicates how stable the system is attempting to reach the discharge air temperature set point. You may hear the compressor hunting (ramping up and down) adjust­ing to lower setting will correct.
Lennox advises not to make changes to this setting without rst contacting Lennox technical support or Lennox eld technical consultant.
Default is 3.0. Range is 1.0 to 15.0 in increments of 0.5.
DAT Offset
This parameter is only available when a Lennox modulating outdoor units is installed along with a discharge air temperature sensor (DATS) Installed is used. Default is 0.0°F (0.0°C). Range is -5.0°F to 5.0°F (-2.88 to 2.78°C) in increments of 0.5°F (0.28°C).
DAT Proportional
Gain
(Lennox Modulating Outdoor Units Only)
This is how the system attempts to reach the discharge air temperature set point.
Lennox advises not to make changes to this setting without rst contacting Lennox technical support or Lennox eld technical consultant.
Default is 3.0. Range is 1.0 to 15.0 in increments of 0.5.
Dew Point
Adjustment
These settings allow adjustments to the Dew Point setting for the home. Some homes may require an adjustment to help maintain comfort. If condensation is present on windows, set the adjustment lower, between -15% to -5%. If the home feels dry, set the adjustment upwards, between +5 to +15%.
Range is -15 to 15°F. Default is 0°F. Adjustments are in increments of 1°F.
Electric Heat Control Mode
(Single and Two-Stage Lennox iComfort Out­door Units Only)
In heat pump applications, the electric heat is staged to provide supplemental heat to meet desired comfort levels. When the electric heat section is used in applications that do not have a heat pump, the elements are staged to limit heat so that it meets heating demands only.
Options are Standard and EvenHeat. Default is Standard.
Electric Heat Stages During Defrost
Can increase or decrease the number of electric elements to come on during a call for defrost. (Thermostat will have a demand for heat.) Range is 0 to 5 electric heat stages. Default is 2. Adjustments are in increments of 1.
Equipment Name
A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces. Default name is subnet controller.
EvenHeat Discharge Temp
When in EvenHeat Control Mode, the thermostat will stage the electric heat sections to maintain a constant discharge air temperature. The system must have a DATS connected to the system to show this parameter.
NOTE: Not selectable on Lennox modulating outdoor units. Electric heat elements will be staged on by the demand of the thermostat.
Range is 85 to 130ºF (29.4 to 54.4ºC). Default is 85ºF (29.4ºC). Adjustments can be made in increments of 15ºF (8.4ºC) .
23
Table 4. Smart Hub Parameters
Parameter Description
Gas Heat Control Mode
(SLP98 only)
Options are Staged, Load Tracking Variable Capacity and Variable Capacity. Default is Staged.
Staged: Some furnaces can be congured to provide up to four stages of gas heat operation. When staged heating is chosen, the iComfort thermostat allows you to choose between 1, 2, 3 and 4 stages of heat. Single-stage heat: rst stage provides 100% of full capacity.
• Two-stage heat: First stage provides 70% of full capacity; 2nd stage provides 100% of full capacity.
• Three-stage heat: First stage provides 60% of full capacity; 2nd stage provides 80% of full capacity; third stage provides 100% of full capacity.
• Four-stage heat: First stage provides 35 or 40% of full capacity; second stage provides 60% of full capacity; third stage provides 80% of full capacity; fourth stage provides 100% of full capacity.
Load Tracking Variable Capacity: Load tracking variable capacity will smoothly track the load (sensible temperature changes) up and down and adjust the furnace heating rate both ways.
Variable Capacity: Variable capacity only tracks the load upward (rising temperature). Variable capacity uses the thermostat stage differentials but not stage timers.
Gas Heating
Activation Temp
Difference
(Lennox Modulating Heat Pumps)
When the system is dual-fuel and steady state while operating at full HP demand, this is the amount of °F (°C) below the set point that is allowed before allowing to switch to gas heat.
Range is 0.5 to 10°F (0.0 to -5.56°C). Default is 1.5°F (1.30°C). Adjustments are in increments of 0.5°F (0.14°C).
Heat Cool Stages Locked In
Heat Cool (H/C) Stages Lock in default is disabled (heat/cool stages are turned off separately). If changed to Enabled, heat/cool stages are turned off together. For non-variable speed systems only.
H/C Stages Locked = Enabled
H/C Stages Locked = Disabled
POINTS:
2nd stage ON
2nd stage
OFF
1st stage ON
1st stage
OFF
2nd stage ON
2nd stage
OFF
1st stage ON
1st stage
OFF
SP -1.5 SP -1.0 SP -0.5
SP
SP +1.5SP +1.0 0.2+ PS5.0+ PS
Stg1 Differential
Stg2 Differential
Stg2 Differential
Stg1 Differential
Cooling (1- and 2-Stages)
H/C Stages Locked = YES
H/C Stages Locked = NO
1st stage
ON
2nd stage
ON
1st stage
ON
2nd stage
ON
2nd stage OFF
1st stage OFF
1st stage OFF
2nd stage OFF
SP -1.5SP -1.0 SP -0.5
SP
SP +0.5SP -2.0
Stg1 Differential
Stg2 Differential
SP -2.5SP -3.0
Stg1 Differential
Stg2 Differential
POINTS:
Heating - Non-Heat Pump or Heat Pump w/o backup heat - 1 or 2 stages
24
Table 4. Smart Hub Parameters
Parameter Description
H/C Stages Locked = NO
H/C Stages Locked = YES
POINTS:
3rd stage
ON
1st stage
ON
2nd stage
ON
3rd stage
ON
1st stage
ON
2nd stage
ON
2nd stage
OFF 3rd stage OFF
SP -1.5 SP -1.0 SP -0.5
SP
S
P
SP -2.0
Stg1 Differential
Stg3 Differential
Stg2 Differential
SP -2.5SP -3.0SP -3.5
Stg1 Differential
Stg3 Differential
Stg2 Differential
Heating - Heat Pump with Electric - 3 Stage
(2 compressor / 1 backup OR 1 compressor / 2 backup)
H/C Stages Locked = Enabled
H/C Stages Locked = Disabled
3rd stage
ON
1st stage
ON
2nd stage
ON
4th stage
ON
3rd stage
ON
1st stage
ON
2nd stage
ON
4th stage
ON
Stg4 Differential
2nd stage
OFF 3rd stage OFF
4th stage OFF
5.0- PS0.1- PS5.1- PS:STNIOP SP S
P
SP -2.0
Stg1 Differential
Stg3 Differential
Stg2 Differential
SP -2.5SP -3.0SP -3.5
Stg1 Differential
Stg3 Differential
Stg2 Differential
Stg4 Differential
Heating - Heat Pump with Electric - 4 Stage (2 compressor / 2 backup)
H/C Stages Locked = Disabled
abled
2nd stage
ON
1st stage
ON
2nd stage OFF
1st stage OFF
SP -1.5 SP -1.0 SP -0.5
SP
SP +0.5SP -2.0
Stg1 Differential
SP -2.5SP -3.0
Stg2 Differential
POINTS:
Heating - Dual Fuel - 2 Stage (1 compressor / 1 backup)
25
Table 4. Smart Hub Parameters
Parameter Description
H/C Stages Locked = Disabled
H/C Stages Locked = Enabled
POINTS:
3rd stage
ON
1st stage
ON
2nd stage
ON
3rd stage
ON
1st stage
ON
2nd stage
ON
SP -1.5 SP -1.0 SP -0.5
SP
S
P
SP -2.0
Stg1 Differential
Stg3 Differential
Stg2 Differential
SP -2.5SP -3.0SP -3.5
Stg1 Differential
Stg3 Diff.
Stg2 Differential
3rd stage OFF
Heating - Dual Fuel - 3 Stage (1 compressor / 2 backup)
H/C Stages Locked = Disabled
H/C Stages Locked = Enabled
POINTS:
3rd stage
ON
1st stage
ON
2nd stage
ON
3rd stage
ON
1st stage
ON
2nd stage
ON
2nd stage OFF
SP -1.5 SP -1.0 SP -0.5
SP
S
P
SP -2.0
Stg1 Differential
Stg3 Differential
Stg2 Differential
SP -2.5SP -3.0SP -3.5
Stg1 Differential
Stg3 Differential
Stg2 Differential
Heating - Dual Fuel - 3 Stages (2 compressor / 1 backup)
Stg4 Diff.
H/C Stages Locked = Enabled
H/C Stages Locked = Disabled
3rd stage
ON
1st stage
ON
2nd stage
ON
4th stage
ON
3rd stage
ON
1st stage
ON
2nd stage
ON
4th stage
ON
Stg4 Differential
2nd stage OFF
4th stage OFF
5.0- PS0.1- PS5.1- PS:STNIOP SP S
P
SP -2.0
Stg1 Differential
Stg3 Differential
Stg2 Differential
SP -2.5SP -3.0SP -3.5
Stg1 Differential
Stg3 Differential
Stg2 Differential
Heating - Dual Fuel - 4 Stage (2 compressor / 2 backup)
26
Table 4. Smart Hub Parameters
Parameter Description
Group ID
Multiple Smart Hubs in a home can be assigned to a group (up to nine groups with up to eight Smart Hubs in each group). All Smart Hubs in a group can communicate with other Smart Hubs in the same group over the home Wi-Fi network.
If a Smart Hub is set to Group ID 0, there will be no connectivity with another Smart Hub. Default Group ID is 1. Valid range is 0 to 9.
HP Heating Lockout Time
The HP could not get a zone to progress 0.5 degrees towards the set point in 120 minutes (Alert Code 40 - Minor alert). System will switch to secondary heat source. (Electric heat or furnace in dual fuel applications). Transition back to Heat Pump normal operation when termination setting times out.
Range is 60 to 240 minutes. Default is 120 minutes. Adjustments are in increments of 30 minutes.
HP Heating Mode
(Lennox Modulating Heat Pumps Only)
Options are Normal and Comfort. Default is Normal. The normal setting heats the home to the desired temperature setting. Modify the heating comfort mode to limit mini­mum compressor speed to 60 – 70 percent range and/or adjust comfort mode CFM.
Normal is when the heat pump will heat the home will providing the highest efciency.
Comfort is when the heat pump will deliver warmer air for comfort, but sacrices on efciency.
Humiditrol Comfort
Adjust
Options are Maximum Overcooling, Midpoint Overcooling and Minimum Overcooling. Default is Maximum Overcooling.
• Maximum Overcooling: Indoor temperature > (greater than) two degrees above heating setpoint.
• Midpoint Overcooling: Indoor temperature > (greater than) HEAT setpoint + COOL setpoint / 2.
• Minimum Overcooling: Indoor temperature > (greater than) two degrees below cooling setpoint.
NOTE: XP20 and XP25 is not compatible with Humiditrol (EDA).
Humidity Reading Calibration
If it is determine that the actual humidity percentage being detected at the thermostat is off based on independent readings using other humidity reading devices, the display can be adjusted using this setting.
Range is -10.0 to 10.0%. Default is 0.0%.
Lock In 2nd Stage HP by Outdoor Temp
(Lennox Two-Stage Heat Pumps Only)
This accessory allows the unit to lock in second stage HP heating when the outdoor temperature goes below the jumper pin setting. Options are off, 40°F (4°C), 45°F (7°C), 50°F (10°C) and 55°F (13°C). Default is off.
Max Heat Setpoint
The highest temperature setting that the heat set point can be set on the thermostat. Default is 90.0F (32.33°C). Range is 60.0 to 90.0°F (15.56 to 32.22°C). Adjustable in increments of 1°F (0.56°C).
Max Humidication
Setpoint
Maximum allowed set point for humidication.
Range is 15 to 45%. Default is 45%. Adjustments are in increments of 1%.
Min Cool Setpoint
The lowest temperature setting that the cool set point can be set on the thermostat. Range is Range is 60.0 to 90.0°F (15.56 to 32.22°C). Default is 60°F (15.56°C). Ad­justments are in increments of 1°F (0.56°C).
Min
Dehumidication
Setpoint
Adjustable minimum dehumidication setting.
Range is 40 to 60%. Default is 40%. Adjustments are in increments of 1%.
Modulating Cooling Cycles Per Hour
(Lennox Modulating Outdoor Units Only)
This feature is activated when the structure BTU load is less than the minimum outdoor unit cooling capacity of the outdoor unit. The system will be cycled “ON” and “OFF” at the selected cycles per hour to maintain the settings of the thermostat. (This governs how many cycles per hour the system will try to run when it needs to run at less than minimum capacity).
Range is 3 to 6 cycles hours. Can be adjusted in increments of 0.5. Default is 4.
Understanding Modulating Step Change and Steady State PI Gains
Each of these terms has a multiplier (or gain) associated with it called the proportional gain and the integral gain respectively and affect responsiveness and stability
Standard is a moderate gain suitable for nearly all installations.
More Aggressive is a set of slightly higher gains that will make the system more responsive to changes, and will try harder to stay on the set point. This setting may cause some systems to oscillate.
Less Aggressive is a set of slightly lower gains that will make the system less responsive and help to stabilize an oscillating system by sacricing a small amount of time to set point.
None of the above options will cause the system to end a call if the demand for heating or cooling remains above the minimum capacity of the system since the algorithm is designed to nd the
demand that allows the system capacity to exactly match the house heating or cooling loss, creating a balance and constant temperature.
27
Table 4. Smart Hub Parameters
Parameter Description
Modulating Cooling Step Change PI Gain
(Lennox Modulating Outdoor Units)
Step change gains deal with set point changes and affects how fast the system reaches the next set point. Options are less aggressive, standard and more aggressive. Default is standard.
Modulating Cooling Steady State PI Gain
(Lennox Modulating Outdoor Units Only)
Steady state gain controls the demand when the system is not responding to a sensed temperature change away from the iComfort thermostat setting. Options are less aggressive, standard and more aggressive. Default is standard.
Modulating Gas Heating Cycles Per Hour
(SLP98V only)
Heat Pump heating capacity of the outdoor unit. The system will be cycled “ON” and “OFF” at the selected cycles per hour to maintain the settings of the thermostat. (This governs how many cycles per hour the system will try to run when it needs to run at less than minimum capacity).
Range is 4 to 10 cycles. Default is 6 cycles. Adjustments are in increments of 0.5 cycles.
Modulating Gas Heating Step Change PI Gain
(SLP98V only)
This is applicable to the SLP98V only. Step change gains deal with set point changes and affects how fast the system reaches the next set point (Example: Adjustment to the thermostat setting).
Options are less aggressive, standard and more aggressive. Default is standard. Recommend not changing this setting.
Modulating HP Heating Cycles Per Hour
(Lennox Modulating Heat Pumps)
This feature is activated when the structure BTU load is less than the minimum Heat Pump heating capacity of the outdoor unit. The system will be cycled “ON” and “OFF” at the selected cycles per hour to maintain the settings of the thermostat. (This governs how many cycles per hour the system will try to run when it needs to run at less than minimum capacity).
Range is 3 to 6 cycles. Default is 4 cycles. Adjustments are in increments of 0.5 cycles.
Modulating HP Heating Step Change PI Gain
(Lennox Modulating Heat Pumps)
Step change gains deal with set point changes and affects how fast the system reaches the next set point (Example: Schedule change or adjustment to the thermostat setting).
Options are less aggressive, standard and more aggressive. Default is standard. Recommend not changing this setting.
Modulating HP Heating Steady State PI Gain
(Lennox Modulating Heat Pumps)
Steady state gain controls the demand when the system is not responding to a sensed temperature change away from the thermostat setting. Options are less aggressive, standard and more aggressive. Default is standard. Recommend not changing this setting.
Number of Gas Heating Stages
(SLP98V only)
Number of selectable stages when Gas Heat Control Mode is set in “Staged” mode. Options are 1 through 4. Default is 4.
Outdoor Temperature Reading Calibration
This will allow for adjustment to the outdoor temperature display when the display temperature is off. Outdoor sensor is required. Range is -10 to 10°F (-5.56 to 5.56°C). Default is 0°F (0.0°C). Adjustments are in increments of 1°F. (0.56°C)
Reset Smart Hub Reset Smart Hub (erases Smart Hub settings and restarts installer setup).
Severe Weather Protection
(high and low temperature notication)
Options are enabled or disabled. Default is disabled. When enabled either the heat or freezing alert temperature setting will automatically generate a email notication to the homeowner that the
applicable condition exist and homeowner interaction is required.
NOTE: Notication is dependent on the thermostat having an active Wi-Fi connection and the user account has been setup and includes a valid email address.
Heat Alert
Temperature
This will notied the homeowner when the indoor temperature reaches the setting dened for this parameter.
Range is 80°F to 100°F (26.67 to 37.78°C) with a factory default of 90°F (32.22°C). Increments adjusted by 1.0°F (0.56°C).
28
Table 4. Smart Hub Parameters
Parameter Description
Freezing Alert
Temperature
This will notied the homeowner when the indoor temperature reaches the setting dened for this parameter.
Range is 30°F to 50°F (-1.11 to 10.0°C) with a factory default of 40°F 4.4°C). Increments adjusted by 1.0°F (0.56°C).
Single Setpoint Mode (SSP)
(Non-Zoning System Only) On the user screens this is referred to as Perfect Temp (Temperature). Options are enabled or disabled. Default is disabled. The Single Set Point (SSP) algorithm allows the user the set only one
temperature set point value rather than one value for heating and a different value for cooling. When zoning is present, the following SSP settings are not available. When enabled the following
parameters are automatically congured for optimal settings.
SSP Heating
Cancel Coast
Counter
Increment Slope
Range is 0 to 0.75°F (0.0 to 0.42°C). Default is 0.25°F (14°C). Adjustments are in increments of 0.125°F (0.07°C).
SSP Heating
Cancel Coast
Counter
Decrement
Slope
Range is 0.25 to 2°F (0.14 to 1.11°C). Default is 0.5°F (0.28°C). Adjustments are in increments of 0.125°F (0.07°C).
SSP Cooling
Cancel Coast
Counter
Increment Slope
Range is -0.75 to 0.0°F (-0.42 to 0.0°C). Default is -0.25°F (-0.14°C). Adjustments are in increments of 0.125°F (0.07°C).
SSP Cooling
Cancel Coast
Counter
Decrement
Slope
Range is -2.0 to -0.25°F (-1.11 to -0.14°C). Default is -0.5°F (-0.28°C). Adjustments are in increments of 0.125°F (0.07°C).
SSP Heating
Lockout Outdoor
Temp
When the outdoor temperature is above this setting, heating is not allowed if single set point is running. Range is 50 to 80°F (10.0 to 26.67°C). Default is 70°F (21.11°C). Adjustments are in increments of 1.0°F (0.56°C).
SSP Cooling
Lockout Outdoor
Temp
When the outdoor temperature is below this setting, cooling is not allowed if single set point is running. Range is 30 to 60°F (-1.11 to 15.56°C). Default is 40°F (4.44°C). Adjustments are in increments of 1.0°F.
Smart Alert
Enable
Options are disabled, conservative, medium and aggressive. Default is disabled.
• Disable - There is no monitoring of Smart Alert Enable.
• Conservative - The system will wait longer to display any Smart Alert Enable alarms. This options allow for a minimum chance for false alarms being shown.
• Medium (default) - Extensive testing by the Lennox development team to minimize the number of false alarms.
• Aggressive - Will shorten time to display any Smart Alert Enable alarms.
Smart Alert Enable function monitors:
• Thermostat set point setting
• Temperature reading
• Determine whether the system moving towards the desired temperature setting or is unable to achieve the desire temperature setting.
• Uses local climate design temperatures
• System run times.
NOTE: Smart Alert Enable feature is disabled in a zoning system.
NOTE: Depending on type of system (conventional heating/cooling or heat pump system) and optional equipment not all system settings will be displayed.
29
Table 4. Smart Hub Parameters
Parameter Description
Smooth Setback
Recovery (SSR)
When enabled, smooth set back begins recovery up to two hours before the programmed time so that the programmed temperature is reached at the corresponding
programmed event time. Assume 12°F (6.72°C) per hour for rst-stage gas/electric heating and 6°F (3.36°C) per hour for rst-stage compressor based heating or cooling.
With Smooth Set Back disabled, the system will start a recovery at the programmed time. Options are enabled or disabled. Default is enabled. The SSR set point calculation is as follows:
Current SSR CSP
Current Program CSPTarget Program CSP
Current SSR HSP
Current Program HSPTarget Program HSP
N
N
For New SSR HSP
For New SSR CSP
Where: CSP = Cool Set Point
HSP = Heat Set Point N = number of 30 second intervals to the target program set point Note: N = 240 when target program set point is 2 hours away (maximum recovery time)
Rules for SSR:
• SSR is enabled when both “Smooth Setback Recovery” is set to enabled (default) and the program schedule is turned on.
• SSR does NOT turn off stage delay timers.
• SSR will NOT change the dead band between heating and cooling modes.
• SSR will not overshoot the target set point.
• SSR will reset if the user updates the program schedule during the active SSR period
Stage Delay Timers
(First)
Enabled (default) setting: When enabled all stage delay timers (stages 2 through 6) are enabled and will serve to bring on additional stage(s) of cooling or heating on a timed basis (default 20 minutes)
Disabled setting: All stages delay timers are disabled. Heat/cool stages are changed based on temperature
NOTE: The second-stage delay timer (when stage timers is Enabled) is used for both HEATING and COOLING. However, if the system has a variable capacity furnace,
zoning or variable outdoor unit, all stage delay timer will be ignored.
Stage Delay Timers
(1 through 6)
Second through Sixth Stage Delay timer (where applicable) - If staged delay timers are “Enabled”, the default is 20 minutes but can be programmed from 5 to 120
minutes in 5-minute increments. If the rst stage fails to advance the ambient temperature toward the set point by 1.0°F (0.56°C) in the programmed delay time, then the
second stage is activated. However, if the system has a variable capacity furnace,
Stage Differentials
(1 through 6)
Number of stages in thermostat is dependent on equipment that is installed.
NOTE: Lennox variable capacity systems will stage electric heat but not on differentials. It will use the thermostat PI logic to stage the electric heat. If the system has a
variable capacity furnace or zoning all stage differentials will be ignored.
Temp Reading Calibration
Range is -5.0 to 5.0°F (-2.78 to -2.78°C). Default is 0.0°F (-0.0°C). If it is determine that the actual temperature being detected at the thermostat is off based on independent readings using other ambient temperature reading devices, the
display can be adjusted using this setting.
Temperature Control Mode
The Feels-Like feature factors in the outdoor temperature and indoor humidity for a more accurate control of the temperature in the home. Either an outdoor temperature sensor is used or Internet Weather is enabled for this feature to operate. Modifying this setting here will also change the feature status on the user settings screen.
Normal - This setting cools or heats the home to the desired temperature setting (Feels Like is OFF.
Comfort - This setting cools or heats the home to the desired temperature setting (Feels Like) is ON. When set to ON, other parameters are modied to optimal settings for this feature. Those setting changes will be listed on-screen when Comfort is enabled.
Default is Normal.
Wall Insulation Options are poor, average and good. Default is average.
30
Table 4. Smart Hub Parameters
Parameter Description
Zone 1 through 4 First Stage Differential
Differential is the temperature between when rst stage will cycle ON and cycle OFF. (Example: Zone 1 HD Display is set at 70°F (21°C) with a 1.0°F (0.56°C) differential.
Cooling Demand - cooling will cycle ON when the room temperature reaches 70.5°F (21.4°C) and cycle OFF when the room temperature is 69.5°F (20.8°C). Range is 0.5 to 3°F (0.28 to 1.67°C). Default is 1°F (0.56°C). Adjustments are in increments of 1°F (0.56°C).
NOTE: For Lennox Modulating Outdoor Units differentials are ignored.
Zone 1 through 4 Continuous Blower CFM
Minimum and maximum CFM will be dependent on system component congurations. These parameter values are automatically adjusted to the specic hardware cong­uration. See iHarmony zoning system installation instruction for minimum CFMs for specic indoor units.
Zones requesting the fan ON are only allowed while no other zone demand is present. The thermostat will sum all the zone continuous blower CFM requirements and send the command only after positioning the dampers and waiting for the damper close delay period to expire (30 seconds) Continuous blower demands are the lowest priority demands, all other conditioning demands will over-ride the continuous blower demand.
Range is 5 CFM to maximum of indoor unit. Default is dependent on tonnage of indoor unit. Adjustments are in increments of 5 CFM.
Zone 1 through 4 Cooling CFM
Minimum and maximum CFM will be dependent on system component congurations. These parameter values are automatically adjusted to the specic hardware cong­uration. See iHarmony zoning system installation instruction for minimum CFMs for specic indoor units.
Target cooling CFM for a specic zone. Range is 5 CFM to maximum of indoor unit. Default is dependent on tonnage of indoor unit. Adjustments are in increments of 5
CFM.
Zone 1 through 4 Heating CFM
Minimum and maximum CFM will be dependent on system component congurations. These parameter values are automatically adjusted to the specic hardware cong­uration (See table 9 in iHarmony installation instruction for minimum CFMs for specic indoor units).
Target heating CFM for a specic zone. Range is 5 to maximum of indoor unit. Default is dependent on tonnage of indoor unit. Adjustments are in increments of 5 CFM.
Adjustments are in increments of 5 CFM.
Zoning Anticipated Discharge Air
Temperature
Adjustment
This parameter setting compensates for a rapid change of the discharge air temperature due to fast changing conditions. It examines the change in the discharge air temperature for the previous two minutes and extrapolates or looks forward by the number of seconds set in the parameter and uses this as the DATS value for staging. This parameter setting helps prevent limit trip/frozen coil from occurring.
Range is 0 to 120 seconds. Default is 30 seconds. Adjustments are in increments of 5 seconds.
Zoning Gas
Heating DAT
Cooldown Target
At the end of a gas cycle, the Heat Blower Off-Delay may not be long enough to completely cool the heat exchanger. This may result in a primary limit trip then, or at the beginning of the next heat demand. This parameter allows the blower to run after a gas heat call ends until the discharge air temperature sensor (DATS) cools to the temperature set in the parameter. If the temperature is set too low this will cause the temperature in the room to overshoot.
Range is 80 to 90°F (26.67 - 32.22°C). Default is 85°F (29.44°C). Adjustments are in increments of 1°F (0.56°C).
Zoning Minimum Zone Run-Time
Range is 90 to 600 seconds. Default is 120 seconds. Adjustments are in increments of 30 seconds.
Zoning Supply
Air Temp Limit
for Cooling
In cooling mode, this setting sets the discharge air temperature low limit. Below this temperature, the cooling is turned off. Range is 35 to 45°F (1.67 - 7.22°C). Default is 40°F (4.44°C). Adjustments are in increments of 1°F (0.56°C).
Zoning Supply Air
Temp Limit for Gas
/ Electric Heating
In heating mode, this setting sets the target discharge air temperature. Range is 100 to 160°F (37.78 to 54.44°C). Default is 140°F (43.33°C). Adjustments are in increments of 5°F (2.78°C).
Zoning Target
Supply Air Temp
for Cooling
In cooling mode, this setting sets the target discharge air temperature. Range is 40 to 60°F (4.44 - 15.56°C). Default is 45°F (7.22°C). Adjustments are in increments of 1°F (0.56°C).
Zoning Target
Supply Air Temp
for HP Heating
In heat pump heating mode, this setting sets the target discharge air temperature. Range is 85 to 110°F (29.44 to 43.33°C). Default is 90°F (32.22°C). Adjustments are in increments of 1°F (0.56°C).
Zoning Target
Supply Air Temp for Gas/Electric
Heating
Default is 110°F. Range is 100°F to 130°F with 1 degree increment adjustable. In heating mode, this setting sets the target discharge air temperature.
31
Table 5. Heat Pump Parameters
Parameter Description
About
This screen provides information concerning language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating states, number of cooling stages, heating capacity by stage, cooling capacity by stage, control software revision, control model number, control serial number, control hardware revision, outdoor air temp sensor, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consump-
tion, line voltage average power consumption, line voltage peak power consumption, outdoor inverter model number, outdoor inverter rmware version, outdoor fan RPM prole, unit code, compatible devices list, application code memory size and micro-controller part number.
Automatic Max
Defrost
(Single and Two-Stage iComfort Heat Pumps)
When set to ON, the system will always run at MAX DEFROST when accumulated compressor off time is longer than 30 minutes and ambient temperature is less than 35°F (1.6°C).
When ambient sensor temperature is higher than 40°F (4.5°C) then defrost termination will be 90°F (32°C). This option has two settings, either ON or OFF. Default is OFF.
Compressor Shift
Delay ON / OFF
(Single and Two-Stage iComfort Outdoor Units)
The options are ON or OFF. By default it is set to ON.
• Shift Delay “OFF” - Compressor will not be cycled “OFF” going in and out of defrost.
• Shift Delay “ON” - Compressor will be cycled “OFF” going in and out of defrost.
Compressor Short Cycle Delay’
(Single and Two-Stage iComfort Outdoor Units)
This feature prevents the compressor from being short cycled any time the compressor is turned “OFF”. The range is 60 - 300 seconds. Default is 300 seconds and with an incremental adjustment of 60 seconds.
Defrost Termination Temp
(Single and Two-Stage iComfort Heat Pumps)
This is the temperature that defrost mode will be terminated. In dual fuel applications (furnace and heat pump), defrost tempering is automatically enabled and operates as follows:
• Furnace will run for 75 seconds ON then after 90 seconds OFF for two cycles.
After the rst two cycles, the furnace will run for 60 seconds ON then cycle OFF for 90 seconds.
• This cycle will be repeated unit the room thermostat is informed by the outdoor control that defrost has terminated. The range is 50 - 100°F (10.0 to 37.78°C). Default is 50°F (10.0°C) and with an incremental adjustment of 10°F (5.56°C).
Modulating - Both Furnace and Heat Pump are Modulating:
When the thermostat receives information that the heat pump has entered defrost the thermostat sends a minimum rate heating demand to the furnace. Then the thermostat terminates the minimum rate heating demand upon defrost completion or any time the heat pump stops. (i.e., pressure switch opens, mode switch changes, etc.)
Staged – Both Furnace and Heat Pump are Multi-Stage:
When the thermostat receives information that the heat pump has entered defrost the thermostat performs the following :
Sends a rst stage heating demand to the furnace.
After 75 seconds elapse from the time the rst stage demand was sent, the thermostat terminates the furnace heating demand.
After the furnace minimum off time has elapsed (90 seconds) from the time the previous heating termination, the thermostat starts rst stage furnace heat again by
sending the rst stage heating demand. This is the new adjustable gas heat delay setting for zoning.
• After 60 seconds elapse from the previous heating demand being sent, the thermostat terminates the furnace heating demand.
• Repeat steps 3 and 4 while defrost is active, terminating any running furnace heat demand when the HP indicates that defrost is no longer active or any time the heat pump stops. (i.e., pressure switch opens, mode switch changes, etc.)
NOTE: The on times above assume the minimum furnace ignition time of 35 seconds.
Dehum Airow Adjustment Adder
(Lennox Modulating Heat Pumps Only)
Dehumidication airow = HUMID Mode CFM table value for a given thermostat demand + dehumidication adjustment adder (High Normal Cooling Airow CFM x Dehumidication Airow Adjustment Adder in percentage.
Both these values are in the installer set up under dealer control center > equipment > heat pump. Range is 0 to 30%. Default is 28%.
NOTE: Deactivated in auxiliary dehumidication and enhanced dehumidication accessory (Humiditrol)
Equipment Name A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces.
High Normal
Cooling Airow
(Lennox Modulating Heat Pumps Only)
Thermostat values shown are defaults. This value can be adjusted up or down to meet each application requirements. The range is 450 - 2150 CFM. Default is dependent on unit capacity with an incremental adjustment of 25 CFM.
32
Table 5. Heat Pump Parameters
Parameter Description
Fan Cycling
(Single and Two-Stage iComfort Heat Pumps)
Options are ON or OFF. Default OFF.
High Normal HP
Heating Airow
(Lennox Modulating Heat Pumps Only)
Thermostat values shown are defaults. This value can be adjusted up or down to meet each application requirements. The range is 450 - 2150 CFM. Default is dependent on unit capacity with an incremental adjustment of 25 CFM.
Low Normal
Cooling Airow
(Lennox Modulating Heat Pumps Only)
Thermostat values shown are defaults. This value can be adjusted up or down to meet each application requirements. The range is 450 - 2150 CFM. Default is dependent on unit capacity with an incremental adjustment of 25 CFM.
Low Normal HP
Heating Airow
(Lennox Modulating Heat Pumps Only)
Thermostat values shown are defaults. This value can be adjusted up or down to meet each application requirements. The range is 450 - 2150 CFM. Default is dependent on unit capacity with incremental adjustment of 25 CFM.
Max Defrost by Weather
(Single and Two-Stage iComfort Heat Pumps)
Options are off and on. Default is off. When set to on, information from the default Internet weather source is used to determine when Max Defrost is used.
Reset Heat Pump Any installer modications under the heat pump tab will be reset back to the factory defaults if the reset heat pump option is used.
Table 6. Air Conditioner Parameters
Parameter Description
About
This screen provides information concerning language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of cooling stages, cooling capacity by stage, control software revision, control model number, control serial number, control hardware revision, outdoor air temp sensor, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, outdoor inverter model number, outdoor inverter rmware version, outdoor fan RPM prole, unit code, compatible devices list, applica­tion code memory size and micro-controller part number.
Compressor Short Cycle Delay
(Single and Two-Stage iComfort Outdoor Units)
This feature prevents the compressor from being short cycled any time the compressor is turned “OFF” The range is 60 - 300 seconds. Default is 300 seconds and with an incremental adjustment of 60 seconds.
Dehum Airow Adjustment Adder
(Lennox Modulating Air Conditioners Only)
Dehumidication airow = “HUMID” Mode CFM table value for a given thermostat demand + dehumidication adjustment adder (High Normal Cooling Airow CFM x Dehumidication Airow Adjustment Adder in percentage. Both these values are in the installer set up under System Device/Air Conditioner/High Normal Cooling Airow).
NOTE: Deactivated in auxiliary dehumidication and Enhanced Dehumidication Accessory (Humiditrol).
Equipment Name A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces.
High Normal
Cooling Airow
(Lennox Modulating Air Conditioners Only)
The range is 450 - 2150 CFM. Default is dependent on unit capacity with an incremental adjustment of 25 CFM. Thermostat values shown are defaults. This value can be adjusted up or down to meet each application requirements.
Low Normal
Cooling Airow
(Lennox Modulating Air Conditioners Only)
The range is 450 - 2150 CFM. Default is dependent on unit capacity with an incremental adjustment of 25 CFM. Thermostat values shown are defaults. This value can be adjusted up or down to meet each application requirements.
Reset Air
Conditioner
Any installer modications under the air conditioner tab will be reset back to the factory defaults if the reset air conditioner option is used.
33
Table 7. Air Handler Parameters
Parameter Description
About
Provides information concerning unit code, language support, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating states, heating capacity by stage, indoor blower CFM range, control software revision, control model number, control serial number, control hardware revision, discharge air temp sensor, outdoor air temp sensor, protocol revision number, device product level, factory installed transformer, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, compatible devices list, applicable code memory size, and micro-controller part number.
Airow Prole
- Cooling
Options are: 1 - No delays. 2 - ON: No delays; OFF: 45 sec delay. 3 - ON: 82% - 7-1/2 minutes; OFF: No delays.
4 - ON: 50% - 30 seconds at 82% - 7-1/2 minutes at 100% and nish cycle 50% / 30 seconds off.
Continuous Indoor
Blower Airow
Range of operation of the indoor blower during continuous blower operation. The range is 450 to 2150 CFM. Default is dependent on component match-up. Incremental adjustments are made in 5 CFM.
NOTE: All iComfort parameter default CFM values are based on Air Handler Control (AHC) DIP switch setting (non-communicating value) prior to power up. This
dip switch settings are use and calculated using CFM conversion tables. They are then rounded up to closest number on 25 CFM resolution. Any DIP switch changes made after power up are ignore.
Cooling Indoor Blower Off Delay
The range is 0 - 30 seconds. Default is 0 seconds with an incremental adjustment of 2 seconds.
Cooling Indoor Blower On Delay
The range is 0 - 10 seconds. Default is 2 seconds with an incremental adjustment of 1 second.
Electric Heating
Airow
Range of operation of the indoor blower during electric heat operation. The range is 1560 to 2150 CFM. Default is dependent on unit capacity with an incremental adjustment of 5 CFM.
Equipment Name A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces.
Heating Indoor Blower Off Delay
Heating Indoor Blower OFF Delay (Electric Heat only -Blower runs at continuous air CFM setting during delay timing period). The range is 0 - 10 seconds. Default is 10 seconds with an incremental adjustment of 1 second.
Heating Indoor Blower On Delay
The range is 0 - 5 seconds. Default is 0 seconds with an incremental adjustment of 1 second.
High Cooling
Airow
Range of operation of the indoor blower during high cooling operation. The range is 1560 to 2150 CFM. Default is based on cooling demand with an incremental adjustments of 25 CFM.
High HP Airow
Range of operation of the indoor blower during high heat pump operation.
Information below is example only and exact air ow range is dependent on equipment tonnage. Use your example and add adjustment increments of +/-25 CFM
Example: The range is 800 -1100 CFM. Default setting is depending on unit tonnage. Can be incrementally adjusted by 25 CFM.
HP Indoor Blower Off Delay
Heat Pump Indoor Blower OFF Delay (Heat Pump only - Blower runs at continuous air CFM setting during delay timing period). The range is 0 - 60 seconds. Default is 45 seconds with an incremental adjustment of 5 seconds.
HP Indoor Blower On Delay
The range is 0 - 30 seconds. Default is 0 seconds with an incremental adjustment of 5 seconds.
Low Cooling
Airow
Range of operation of the indoor blower during low cooling operation. The range is 450.0 to 2150 CFM. Default is based on cooling demand with an incremental adjustments of 25 CFM.
Low HP Airow
Range of operation of the indoor blower during low heat pump operation.
Information below is example only and exact air ow range is dependent on equipment tonnage. Use your example and add adjustment increments of +/-25 CFM.
Example: The range is 450 - 600 CFM. Default setting is depending on unit tonnage. Can be incrementally adjusted by 25 CFM.
Reset Air Handler Any installer modications under the air handler tab will be reset back to the factory defaults if the reset air handler option is used.
34
Table 8. Furnace Parameters
Parameter Description
About
This screen provides information on unit code, language supported, equipment type name, unit model number, unit serial number, unit nominal capacity, number of heating stages, heating capacity by stage, indoor blower CFM range, control software revision, control model number, control serial number, control hardware revision, discharge air temp sensor, outdoor air temp sensor, protocol revision number, device product level, factory installed transformer, 24VAC average power consumption, 24VAC peak power consumption, line voltage average power consumption, line voltage peak power consumption, compatible devices list, application code memory size and micro-controller part number.
Airow Prole
- Cooling
Options are:
A - ON: 50% - 30 seconds at 82% - 7-1/2 minutes at 100% and nish cycle 50% / 30 seconds off.
B - ON: 82% - 7-1/2 minutes at 100% and nish cycle off.
C - ON: 100% - No delays; OFF: 45 seconds. D - no delays.
Continuous Indoor
Blower Airow
The range is 450 - 2000 CFM with a default setting based on equipment type match-up. Adjustments are in increments of 5 CFM.
NOTE: All iComfort parameter default CFM values are based on Furnace Control (IFC) DIP switch setting (non-communicating value) prior to power up. This dip switch
settings are use and calculated using CFM conversion tables. They are then rounded up to closest number on 25 CFM resolution. Any DIP switch changes made after power up are ignore.
Cooling Indoor Blower Off Delay
The range is 0.0 - 30.0 seconds with a default setting base on equipment type match-up. Adjustment are increments of 10 seconds. Default is 0.0 seconds.
Cooling Indoor Blower On Delay
The range is 0.0 - 10.0 seconds with a default setting base on equipment type match-up. Adjustment are increments of 1 second. Default is 2.0 seconds.
Dehumidication Airow %
Range is 60.0 to 80.0%. Default is 70.0%
Equipment Name A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces.
Heating Indoor Blower Off Delay
The range is 60 - 180 seconds with a default setting base on equipment type match-up. Adjustment are increments of 10 seconds.
Heating Airow
Control Type
Options for this setting are xed CFM or xed DAT (discharge air temperature). Default is dependent on equipment type match-up.
Fixed CFM is selected as the Heating Airow Control Type (parameter default selection), the circulator will operate at a CFM that is linearly interpolated between Low Heating Airow and High Heating Airow based on the current IFC ring rate. For example, if the ring rate is 60% and Low Heating Airow and High Heating Airow
were set to 500 CFM and 900 CFM respectively (both parameter values are set during the IFC commission), the circulator will run at 297 CFM (= 500+ (900-500) *(60-
40)/(100-40)) – assuming 40% minimum re rate.
Fixed Discharge Air Temperature (DAT) control when selected as Heating Airow Control Type, the IFC will vary circulator at a CFM to maintain a set Discharge Air Temperature (DAT). For example if the ring rate is 60% and Low Heating DAT and High Heating DAT were set to 115°F (46°C) and 130°F (54.4°C) respectively (both
parameter values are set during the IFC commission), the IFC will control the circulator to maintain a DAT at 120°F (48.9°C) (115+ (130-115) *(60-40)/(100-40)) – as-
suming 40% minimum re rate.
When Fix DAT is enabled, the following parameters are available:
Low Heating Discharge Temp
Range is 105 to 135°F (43.44 to 60.0°C). Adjustable in increments of 5F (2.78°C). Default is 120°F (51.67°C).
High Heating Discharge Temp
Range is 115 to 145°F (48.89 to 65.56°C). Adjustable in increments of 5F (2.78°C). Default is 130°F (57.22°C).
Heating Indoor Blower On Delay
The range is 15 - 45 seconds with a default setting base on equipment type match-up. Adjustment are increments of 5 seconds.
High Cooling
Airow
Range of operation of the indoor blower during high cooling operation. The range is dependent of indoor unit model and size. Default is based on cooling demand with an Incremental adjustments of 25 CFM.
High Heating
Airow
Both range and default setting is based on equipment type match-up. Adjustments are in increments of 25 CFM. This value is automatically adjusted by the system
based on heating airow control type used.
High HP Airow Range is 800.0 to 1100.0 CFM. Default is 967.0 CFM.
HP Indoor Blower Off Delay
The range is 0.0 - 60.0 seconds with a default setting base on equipment type match-up. Adjustment are increments of 5 seconds. Default is 45.0 seconds.
35
Table 8. Furnace Parameters
Parameter Description
HP Indoor Blower On Delay
The range is 0.0 - 30.0 seconds with a default setting base on equipment type match-up. Adjustment are increments of 5 seconds. Default is 0.0 seconds.
Low Cooling
Airow
Range of operation of the indoor blower during low cooling operation. The range is dependent of indoor unit model and size. Default is based on cooling demand with an Incremental adjustments of 25 CFM.
Low Heating
Airow
Both range and default setting is based on equipment type match-up. Adjustments are in increments of 25 CFM. This value is automatically adjusted by the system
based on heating airow control type used.
Minimum Gas Heating Off Time
Default is 1.5 minutes. Range is 1.5 to 10 minutes. With increments of 0.5. This setting will help with the Alarm 250 limit tripping in zoning applications where a second zone calls immediately after the satisfying a gas heating call and there is still
residual heat in heat exchanger.
Reset Furnace Any installer modications under the furnace tab will be reset back to the factory defaults if the reset furnace option is used.
36
Table 9. Zoning Control Parameters
Parameter Description
About
This provides information on unit code, language supported, equipment type name, control software revision, control model number, control serial number, control hard­ware revision, protocol revision number, device product level, 24VAC average power consumption, 24VAC peak power consumption, compatible devices list, application code memory size, micro-controller part number, max number of zones, supported damper types, number of damper positions, zone temp sensor 1, zone temp sensor 2, zone temp sensor 3 and zone temp sensor 4.
Equipment Name A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces.
Zones 1 through 4 Temp Reading Calibration
Allows adjustment to temperature reading displayed on zone thermostat.
Reset Zoning Control
Any installer modications under the zoning control tab will be reset back to the factory defaults if the reset zoning control option is used.
Table 10. Thermostat (HD Display) Parameters
Parameter Description
About This screen provides information concerning model number, serial number, hardware revision, software revision, language support and equipment type name. Auto Brightness Options are on and off. Default is off.
Brightness Value The brightness range is 0 - 100. Default 80. Touch either the + or - button to increase or decrease the setting.
Display Air
Quality
Options are on and off. Default is off. Air Quality is displayed under the weather display. Touch the Weather icon on the home page to see the current air quality.
Display Indoor Humidity
Options are on and off. Default is off.
Display Outdoor Weather
Options are on and off. Default is off.
Outdoor Temperature Source
Options are off, Internet (AccuWeather) or sensor. Default is Internet (AccuWeather).
Proximity Control Options are ON and OFF. Default is OFF. Is used to wake-up the display from screen saver mode when motion near the HD Display is detected. Reset thermostat Resets the thermostat settings to factory default. Screen Locked Options are unlocked, partially locked and locked. Default is unlocked. Screen Saver Options are off, weather, power save and logo. Default is off.
Wide Setpoint
Options are ON and OFF. Default is OFF. This allows a wider low and high temperature. Normal range is 60 to 90°F (15.6 to 32.2°C) . When this parameter is set to ON, the range is 40 to 100°F (4.4 to 37.8°C). This feature can also be set through the user interface setting screen. From the home screen go to menu > settings > heat & cool (or it may be just heat or cool) > wider set-point range.
Table 11. Mag-Mount Parameters
Parameter Description
About This provides information on equipment type name, control hardware revision, control software revision, control serial number and control model number.
37
Table 12. PureAir S Parameters
Parameter Description Equipment PureAir Filter
Dirty Filter Detection and UV Life Detection
Default: ON. Options are either ON or OFF.
This parameter turns on and off the lter life and UV lamp life reporting. When set to off, the control will continue to calculate the remaining lter life through continu­ous sampling, but will not use lter tests to determine lter life. The control will:
Perform a lter calibration upon indication of a lter change regardless of the value of this parameter.
• Perform a UVA lamp calibration upon indication of a lamp change regardless of the value of this parameter.
• Calculate UVA lamp life remaining regardless of the value of this parameter.
Alarms 504 and 503 will not be sent while this parameter is set to “Off”
The Diagnostics screen on the thermostat will continue to show values for both lter life and UV lamp life regardless of the value of this parameter.
Max Air Filtered
between Tests
Default is 100%, Range is 50% to 100% Changes can be made in increments of 10%. This parameter:
Modies the amount of air that is allowed to pass through the lter after a valid % life determination before a lter test is initiated.
Expressed as a percentage of the cubic feet of air that would pass through the lter if the fan operated at continuous fan CFM for 30 days.
UV lamp operation detection
Default: ON. Options are either ON or OFF.
Filter Life Provides percentage of remaining lter life. This is for display purposes only and cannot be changed.
Last replacement
date for lter
Date last lter reset was accomplished. This is for display purposes only and cannot be changed
Purier life Provides percentage of remaining purier life. This is for display purposes only and cannot be changed
Last replacement
date for purier
Date last purier insert reset was accomplished. This is for display purposes only and cannot be changed
• reset PureAir S will reset all PureAir S parameters back to factory defaults.
reset purier will reset it to 100%. This is usually accomplished after the purier insert has been replaced.
reset lter will reset it to 100%. This is usually accomplished after the air lter has been replaced.
Table 13. Utilities
Parameter Description Restart Smart Hub Restarts the Smart Hub.
Re-congure
System
Re-congure HVAC system.
Reset HVAC
Equipment
Resets all HVAC equipment.
Factory Reset Thermostat
Resets thermostat to factory default settings.
Factory Reset Smart Hub
Resets Smart Hub parameters back to factory default.
38
Table 14. Service Alert Codes
Alert Code Description
3000 Filter 1
3001 Filter 2 3002 Humidier pad 3003 UV light 3004 Maintenance 3005 PureAir maintenance 4000 User Wi-Fi state change, disabled. 4001 Firmware download failed 4002 Image le download failed
tEsts
Verify Airow Per Zone is the rst screen to appear under this selection. If no zoning is installed, zone airow settings will be for zone 1 only. If zoning
equipment is detected by the system then zones 1 through 4 will be listed.
These screens allow for verication and modication of CFMs for blower,
heating and cooling circulation. Touch continue to proceed to the next screen. Select Test to Run is the next screen to appear. Depending on hardware
present, various tests are available. By default all items to be tested are
enabled. Selecting a specic test will un-check the item. When a specic set
of tests are completed the results will be displayed on the screen next to the tested item. Touch continue to proceed to the next set of test items. Once all tests are completed press done to return to the touch tests to run screen. Touch the left arrow at the top left side of screen to return to the Dealer Control Center.
DIagnostICs
This screen allows the installer to test all major communicating components of the system indoor unit (air handler or furnace), outdoor unit (air conditioner or heat pump) and zoning control (if applicable). Pressing the stop diagnostics button will pause the diagnostic function.
Touch the left arrow at the top left side of screen to return to the Dealer Control Center.
InstallatIon rEport
The overview screen provides information on dealer and customer information. Also included under day of install section is information on conditions at the time of installation. Information includes date, time indoor and outdoor temperatures and indoor humidity. Under equipment, system, indoor/outdoor and zoning
model number, serial number and rmware information is displayed.
Other menus items include system indoor and outdoor units and zoning control parameter settings.
NOTE: Installation Report is not available until after exiting the dealer control
center following commissioning. Return to the dealer control center from the home screen to view the installation report.
InFormatIon
The dealer information screen will appear. The next screen will be for dealer information. Here either the dealer ID or phone number can be added. Once the system is connected to the Internet, the remaining information is automatically populated. Not all information for this screen will be viewable. Touch and hold and then drag up to access the remaining information on the screen.
Information Required: Dealer ID and / or dealer phone number. Information that can be manually entered is name, email website, dealer address which includes address 1, address 2, city state and zip/postal code. Once completed, touch the left arrow at the top left side of screen to return to the Dealer Control Center.
IMPORTANT
Adding dealer information will ensure the thermostat is associated with your LennoxPros account when connecting to the Lennox server.
Warning Screen: If the dealer ID or phone number is not provided, a warning screen will appear. The warning screen will provided information on the limitation imposed on the system if this information is missing. Touch no to return to the above screen to complete the information requested or press yes to continue.
General Information
On this screen general information needs to be veried or changed. Touch
any item to change its contents. A pop-up screen will appear that will allow the information to be added or changed.
Information Required:
1. Select desired language (ENGLISH, FRANÇAIS or ESPAÑOL).
2. Select country / region.
3. Select time and date which includes time, date, time zone, daylight savings
time (ON/OFF)
4. Temperature unit (Fahrenheit or Celsius).
5. Once completed press continue.
39
Home Address
On this screen general information needs to be veried or changed. Touch any
line item to change its contents. Information to be added is address 1, address 2, state, city and zip/postal code.
Complete the requested information and press the continue button.
Dehumidication Settings
For rmware version 3.15 and later, all controls for dehumidication are listed
at menu > settings > humidity. Under Humidity Control, select dehumidify to enable dehumidication. By default it is disabled.
When dehumidify is enabled, the options are as follows and are dependent on equipment type and accessory installed.
DEhumIDIFICatIon sEttIng optIons
Normal — Recommend when the air outside is not too humid.
Max — » Single and Two-Stage Outdoor Units or Modulating outdoor units
without a Discharge Air Temperature Sensor (DATS) Installed. Recommend when outdoor air is excessively humid. May cool your home below the set temperature.
NOTE: Recommend use of discharge air temperature sensor (DATS) catalog
number 88K38 when modulating outdoor units are used.
» Modulating Outdoor Units with DATS installed. Recommended
when outdoor air is excessively humid. Adjusts cooling based on duct sensor data. May cool your home below the set temperature.
Climate IQ (Auto) — Automatically adjusts fan speeds and cooling power
based on local climate conditions, using Climate IQ technology. May cool your home below the set temperature.
ovErCoolIng
Slide bar adjust with a range of 0°F to 4°F (-17.8 to -15.5°C). Only available when Max or Climate IQ is selected.
DEhumIDIFICatIon sEt poInt
Slide bar adjust with a range of 40% to 60%.
aDvanCED DEhumIDIFICatIon DEsCrIptIons
See table 1 for detail information concerning system operations when using Normal, Max or Climate IQ settings.
40
Table 15. Dehumidication Control Modes of Operations
Mode of Operation
Option Description
Dehumidication
Only
Normal
Both Staged and Modulating Outdoor Units: Dehumidies while servicing a cooling demand and will not over cool. The overcooling slider is hidden from the user.
Modulating units use the “comfort” table to run the system, regardless of the presence of a discharge air temperature sensor (DATS).
Max
Staged Outdoor Unit:
If at the start or during a cooling call, the humidity is above the relative humidity set point then the unit dehumidies during the cooling demand. If at the time the cooling call terminates, the humidity demand is not satised, overcooling will occur up to the overcooling slider setting in an attempt to satisfy the dehumidica­tion demand. Once the room temperature reaches the over cooling set point. If the system still has a dehumidication demand, the system keeps using the over cooling set point as its operating cooling set point (will not wait for the temperature to rise to the normal cooling set point to run again) until the dehumidication demand is satised
Modulating Outdoor Unit:
These units work as like staged units and if a discharge air temperature sensor (DATS) sensor is installed, the DAT PI setting is used to control the compressor
speed to maintain a cold coil for optimized dehumidication. If a DATS is not installed, the system runs using the outdoor unit’s “comfort” tables during dehumidi­cation.
Available only with Max and
Climate IQ
(Auto)
Staged Outdoor Unit:
At the end of a cooling call, if the humidity is above the set point by a certain amount (Basic to Precision Threshold parameter), then overcooling to the overcool-
ing slider setting occurs to satisfy the dehumidication demand. Once the room temperature reaches the overcooling set point, if the system still has a dehu­midication demand, the system keeps using the over cooling set point as its operating cooling set point (will not wait for the temperature to rise to the normal cooling set point to run again) until the dehumidication demand is satised.
Staged Outdoor Unit:
At the end of a cooling call, if the humidity is above the set point by a certain amount (Basic to Precision Threshold parameter), then overcooling to the overcool-
ing slider setting occurs to satisfy the dehumidication demand. Once the room temperature reaches the over cooling set point, if the system still has a dehu­midication demand, the system keeps using the over cooling set point as its operating cooling set point (will not wait for the temperature to rise to the normal cooling set point to run again) until the dehumidication demand is satised.
Modulating Outdoor Unit:
If at the start or during a cooling call, the humidity level is below the relative humidity set point by more than 10%, then the mode becomes “Dry” such that the blower CFM is increased to the “Dry” table setting.
• If a cooling call starts with the humidity level below the relative humidity setpoint, or if during a cooling call, the humidity level is between the dehumidify off
relative humidity point and the relative humidity set point -10, then standard cooling runs to satisfy the cooling demand, without any added dehumidication.
If at the start or during a cooling call, the humidity is above the relative humidity set point then the unit dehumidies during the cooling demand. If at the time the cooling call terminates, the humidity is above the Basic to Precision Threshold then overcooling will occur up to the slider setting in an attempt to satisfy the
dehumidication demand. Once the room temperature reaches the over cooling set point, if the system still has a dehumidication demand, the system keeps
using the over cooling set point as its operating cooling set point (does not wait for the temperature to rise to the normal cooling set point to run again) until the
dehumidication demand is satised.
The Basic to Precision Threshold is a parameter with the following properties: Denition: Relative humidity amount above the relative humidity set point where over cooling will occur to dehumidify. Default: 4, Min: 0, Max: 10, Inc: 1
• Modulating units use the “comfort” table to run the system, regardless of the presence of a DATS.
overcooling
0°F
0°F
4°F
2°F
48%
dehumification set−point
60%
40%
1 Modulating outdoor units are XC20, XP20, XC25 and XP25. NOTE - The above information is applicable only for non-zoning systems, in addition to thermostat using rmware version 3.15 or
later. There is no dehumidication capability in zoning systems.
41
Displaying Outdoor Temperature (Sensor) and Indoor Humidity on the
Home Screen
DIsplayIng thE outDoor sEnsor tEmpEraturE on thE homE sCrEEn
An outdoor temperature sensor is provided in all iComfort outdoor units. To display the outdoor temperature on the home screen of the HD Display, you can enable this feature under the dealer control center. Use the following procedure to enable the outdoor temperature sensor display
1. Touch menu and then touch settings.
2. Touch advanced settings and then touch view dealer control center.
3. Touch equipment and then touch thermostat.
4. Touch Outdoor Temperature and touch sensor.
5. Touch the back arrow (<) at the top left-hand of the screen to return to the
dealer control center.
6. Touch exit.
7. From the Home screen, touch menu and then touch settings.
8. Touch display and touch outdoor temperature.
9. Touch sensor to touch the outdoor sensor. Touch < display to return to
display screen. There under outdoor temperature it will indicate sensor.
10. Touch the home icon at the top left-hand corner of the screen to return to the home screen.
DIsplayIng thE InDoor humIDIty on thE homE sCrEEn
To enable the Indoor Humidity Display on the Home screen use the following procedure:
1. Touch menu and then touch settings.
2. Touch advanced settings and then touch view dealer control center.
3. Touch equipment and then touch thermostat.
4. Touch Display Indoor Humidity and touch the toggle switch to turn on.
5. Touch the back arrow (<) at the top left-hand of the screen to return to the
dealer control center.
6. Touch exit to return to the home screen.
System Congurations
ComplEtE IComFort systEms — FurnaCE anD aIr ConDItIonEr
An iComfort gas furnace (G71MPP, EL296V, SLP98 or SL280) with an iComfort air conditioner (SL18XC, XC17, XC20, XC21 or XC25 only) unit.
1. Wiring—See Communicating System and optional accessories wiring diagrams.
• Four-conductor thermostat wire between the HD Display, Smart-Hub
and gas furnace (R, i+, i-, C).
• Four-conductor thermostat wire from the integrated furnace control
(IFC) terminal strip to the iComfort air conditioner unit (R, i+, i-, C)
• Wiring as required for accessories.
2. DO NOT cut any option links on furnace control.
3. After the entire system is wired, power up the system; the thermostat will
check the system for installed communication devices.
4. During commissioning, you will end that process with the dealer control center screen. From there touch equipment to modied any system or
equipment settings.
5. From the equipment list, touch furnace. From this furnace screen you will
have access to the various airow settings. Set the system air volumes
according to the needs of the home.
6. When all CFM settings are complete, press the back arrow (<) at the top left-hand of the screen to return to the dealer control center. Touch tests to access the test section.
7. Here you will have another opportunity to adjust blower circulation, heating
and cooling circulation air ows. Use the plus or minus buttons to adjust
up or down the CFM settings. Once adjustments are completed, touch
continue.
8. Under the test to run, you may un-check any test not desired, or run all
tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
9. Once all tests are completed, touch done which will return you to the select test to run screen. If nish, touch the back arrow (<) at the top left-hand of
the screen to return to the dealer control center.
10. Touch exit to return to the home screen.
42
ComplEtE IComFort systEms — FurnaCE anD hp unIt (Dual-FuEl)
An iComfort gas furnace (G71MPP, EL296V, SLP98 or SL280) with an iComfort air conditioner (SL18XC, XC17, XC20, XC21 or XC25 only) unit.
1. Wiring—See Communicating System and optional accessories wiring diagrams.
• 4-conductor thermostat wire between the HD Display, Smart-Hub and
gas furnace (R, i+, i-, C).
• 4-conductor thermostat wire from the integrated furnace control (IFC)
terminal strip to the iComfort air conditioner unit (R, i+, i-, C)
• Wiring as required for accessories.
2. DO NOT cut any option links on furnace control.
3. After the entire system is wired, power up the system; the thermostat will
check the system for installed communication devices.
4. During commissioning, you will end that process with the dealer control center screen. From there touch equipment to modify any system or
equipment settings.
5. Select Balance Point Control and press edit. Use the down arrow to touch Enabled. A pop-up warning screen indicating that due to enabling Balance Point Control other related parameter values were automatically changed.
6. Complete Balance Point Control by editing the High and Low Balance Points. It is not necessary to change the defaults.
7. From the equipment list, press furnace. From this furnace screen you will
have access to the various airow settings. Set the system air volumes
according the needs of the home.
8. When all CFM settings are complete, touch the back arrow (<) at the top left-hand of the screen to return to the dealer control center. Touch tests to access the test section.
9. Here you will have another opportunity to adjust blower circulation, heating
and cooling circulation air ows. Use the plus or minus buttons to adjust
up or down the CFM settings. Once adjustments are completed, touch
continue.
10. Under the select test to run screen, you may un-check any test not
required, or run all tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
11. Once all tests are completed, touch done. This will return you to the touch
tests to run screen. If nish, touch the back arrow (<) at the top left-hand of
the screen to return to the dealer control center.
12. Touch exit to return to the home screen.
ComplEtE IComFort systEms — aIr hanDlEr anD aIr ConDItIonEr
An iComfort air handler (CBX32MV or CBX40UHV) with an iComfort air conditioner (SL18XC, XC17, XC20, XC21 or XC25).
IMPORTANT
Be sure to congure the air handler control so that heat strips (if used)
information will be detected by the thermostat. This must be done prior to powering up the system and control system.
1. Congure air handler control (AHC) for auxiliary heat strips if used.
2. Wiring—See Communicating System and optional accessories Wiring
diagrams.
• Four-conductor thermostat wire between the HD Display, Smart-Hub and gas furnace (R, i+, i-, C)
• Four-conductor thermostat wire from the integrated furnace control (IFC) terminal strip to the iComfort air conditioner unit (R, i+, i-, C)
• Wiring as required for accessories.
3. DO NOT cut any option link on air handler control.
4. After the entire system is wired, power up the system; the thermostat will
check the system for installed communication devices.
5. During commissioning, you will end that process with the dealer control center screen. From there touch equipment to modify any system or
equipment settings.
6. From the equipment list, touch air handler. From this air handler screen
you will have access to the various airow settings. Set the system air
volumes according to the needs of the home.
7. When all CFM settings are complete, touch the back arrow (<) at the top left-hand of the screen to return to the dealer control center.
8. Touch tests to access the test section.
9. Here you will have another opportunity to adjust blower circulation, heating
and cooling circulation air ows. Use the plus or minus buttons to adjust
up or down the CFM settings. Once adjustments are completed, press continue.
10. Under the select test to run screen, you may un-check any test not required, or run all tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
11. Once all tests are completed, press done. This will return you to the touch
tests to run screen. If nish, press the back arrow (<) at the top left-hand of
the screen to return to the dealer control center.
12. Touch exit to return to the home screen.
43
TIPS
If the thermostat’s select mode screen does not offer a choice for “emerg. heat” then it may be possible that the electric heat is not working or perhaps
the electric heat has not been congured.
Congure the electric heat as described “Electric Heat Conguration for
iComfort Air Handlers” on page 15, or for complete detail, see the air
handler installation instruction. After conrming that the electric heat has been congured correctly, recongure the iComfort system by going to menu >
system > advanced settings > view dealer control center > equipment > reset > re-congure system.
ComplEtE IComFort systEms — aIr hanDlEr anD hEat pump unIt
An iComfort air handler (CBX32MV or CBX40UHV) with an iComfort heat pump (SL18XP, XP17, XP17N, XP20, XP21, XP21N or XP25) unit.
IMPORTANT
Be sure to congure the air handler control so that heat strips (if used)
information will be detected by the thermostat. This must be done prior to powering up the system and control system.
1. Congure air handler control (AHC) for auxiliary heat strips if used.
2. Wiring—See Communicating System and optional accessories Wiring
diagrams.
• Four-conductor thermostat wire between the HD Display, Smart-Hub and gas furnace (R, i+, i-, C)
• Four-conductor thermostat wire from the integrated furnace control (IFC) terminal strip to the iComfort air conditioner unit (R, i+, i-, C)
• Wiring as required for accessories.
3. DO NOT cut any option link on air handler control.
4. After the entire system is wired, power up the system; the thermostat will
check the system for installed communication devices.
5. During commissioning you will end that process with the dealer control center screen. From there touch equipment to modied any system or
equipment settings.
6. Select Balance Point Control and touch edit. Use the down arrow to touch Enabled. A pop-up warning screen indicating that due to enabling Balance Point Control other related parameter values were automatically changed.
7. Complete Balance Point Control by editing the High and Low Balance Points. It is not necessary to change the defaults.
8. From the equipment list, touch air handler. From this air handler screen
you will have access to the various airow settings. Set the system air
volumes according to the needs of the home.
9. When all CFM settings are complete, touch the back arrow (<) at the top left-hand of the screen to return to the dealer control center. Touch tests to access the test section.
10. Here you will have the opportunity to adjust blower circulation, heating
and cooling circulation air ows. Use the plus or minus buttons to adjust
up or down the CFM settings. Once adjustments are completed, touch
continue.
11. Under the select test to run screen, you may un-check any test not
required, or run all tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
12. Once all tests are completed, touch done. This will return you to the select tests to run screen. If nish, touch the back arrow (<) at the top left-hand of the screen to return to the dealer control center.
13. Touch exit to return to the home screen.
partIal IComFort systEmIComFort FurnaCE anD lEnnox ConvEntIonal aIr ConDItIonEr
An iComfort furnace (G71MPP, EL296V, SLP98 and SL280) with a conventional non-communicating Lennox brand air conditioner.
1. Wiring—See Communicating System and optional accessories Wiring diagrams.
• 4-conductor thermostat wire between the HD Display, Smart-Hub and
gas furnace (R, i+, i-, C)
• Conventional thermostat wire with 2 to 4 conductors from the furnace
terminal strip to the air conditioner unit (Y1, C, & on some models, R & Y2).
• Wiring as required for accessories.
2. Cut option link 2-stage compr (Y1 to Y2, W915) on furnace control on two- stage Lennox brand conventional air conditioner units only.
3. After the entire system is wired, power up the system; the thermostat will check the system for installed communication devices.
4. During commissioning you will arrive at the equipment found screen. From there touch non-communicating equipment to add non-communicating equipment.
5. From the add/remove equipment screen, touch either 1 Stage A/C unit or 2 Stage A/C unit.
6. Touch done to return to the equipment found screen.
7. Touch continue to proceed to the next screen.
44
8. From the equipment list, touch Furnace. From this furnace screen you will
have access to the various airow settings. Set the system air volumes
according to the needs of the home.
9. Continue with the commissioning sequence. When the set up airow per zone screen appears you can adjust the blower, heating and cooling
circulation air ows per zone. When done, touch continue to proceed.
10. The dealer control center will appear. Touch tests to access the test
section.
11. Here you will have the opportunity to adjust blower circulation, heating and cooling circulation air ows. Use the plus or minus buttons to adjust up or down the CFM settings. Once adjustments are completed, press
continue.
12. Under the select test to run screen, you may un-check any tests not
required, or run all tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
13. Once all tests are completed, touch done. This will return you to the touch
tests to run screen. If nish, touch the back arrow (<) at the top left-hand of
the screen to return to the dealer control center.
14. Touch exit to return to the home screen.
TIPS
If the thermostat’s select mode screen has only heat only or off selections and no choice for cooling or heat/cool you must add the non-communicating air conditioning unit. Use the following procedures from the home screen to add a non-communicating air conditioner.
1. Select menu > settings > advance settings > view dealer control center > equipment.
2. Select either 1-Stage A/C or 2-Stage A/C. Touch the back arrow (<) at the
top left-hand of the screen to return to the dealer control center.
3. Touch exit to return to the home screen.
On two-stage air conditioners you must cut the W915 2 Stage Compr link on the furnace control
partIal IComFort systEmIComFort FurnaCE anD lEnnox ConvEntIonal hEat pump unIt (Dual-FuEl)
If using a conventional non-communicating heat pump unit in an iComfort dual­fuel system then a iComfort Equipment Interface Module must be used and set up as a communicating heat pump.
If the HD Display System Setting only shows “heat only“ or “off“ choices and does not offer a choice for “cooling” you must “Install” the non-communicating air conditioning unit (see procedures above).
For two-stage air conditioners you must cut the Y1-Y2 2-stage comp on-board clippable link on the air handler control.
partIal IComFort systEmIComFort aIr hanDlEr anD lEnnox ConvEntIonal aIr ConDItIonEr
An iComfort air handler (CBX32MV or CBX40UHV) with a conventional non­communicating Lennox brand air conditioner unit.
IMPORTANT
Be sure to congure the air handler control so that heat strips (if used)
information will be detected by the thermostat. This must be done prior to powering up the system and control system.
1. Congure air handler control (AHC) for auxiliary heat strips if used.
2. Wiring—See Communicating System and optional accessories wiring
diagrams:
• Four-conductor thermostat wire from the Smart Hub to the air handler (R, i+, i-, C).
• iComfort air handler to conventional Lennox brand air conditioner (5 – 8 wires). (Y1, Y2, C, R, W1,W2).
• Wiring as required for accessories.
3. On air handler control, when matched with conventional Lennox brand 2-stage air conditioner, cut the Y1-Y2 2-stage comp on-board clippable link.
4. On air handler control, remove jumper between W1 and W2 for two-stage electric heat only.
5. After the entire system is wired, power up the system; the thermostat will check the system for installed communication devices.
6. During commissioning you will arrive at the equipment found screen. From there touch non-communicating equipment to add non-communicating equipment.
7. From the add/remove equipment screen, touch either 1-Stage A/C unit or 2-Stage A/C unit.
8. Touch the done to return to the equipment found screen.
9. Touch continue to proceed to the next screen.
10. Continue with the installer setup sequence. When the set up airow per
zone screen appears you can adjust blower, heating and cooling circulation
air ows. When done, press continue to proceed.
11. The dealer control center will appear. Touch tests to access the test
section.
45
12. Here you will have another opportunity to adjust blower circulation, heating
and cooling circulation air ows. Use the plus or minus buttons to adjust
up or down the CFM settings. Once adjustments are completed, touch
continue.
13. Under the touch test to run screen, you may un-check any tests not
required, or run all tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
14. Once all test are completed, touch done. The will return you to the select
tests to run screen. If nish, touch the back arrow (<) at the top left-hand of the screen to return to the dealer control center.
15. Touch exit to return to the home screen.
TIPS
If the thermostat’s select mode screen does not offer a choice for “emerg. heat” then it may be possible that the electric heat is not working or perhaps
the electric heat has not been congured.
Congure the electric heat as described “Electric Heat Conguration for
iComfort Air Handlers” on page 15, or for complete detail, see the air
handler installation instruction. After conrming that the electric heat has been congured correctly, recongure the iComfort system by going to menu >
system > advanced settings > view dealer control center > equipment > reset > re-congure system.
partIal IComFort systEmIComFort aIr hanDlEr anD lEnnox ConvEntIonal hEat pump unIt
An iComfort air handler (CBX32MV or CBX40UHV) with a conventional non­communicating Lennox brand heat pump unit.
IMPORTANT
Be sure to congure the air handler control so that heat strips (if used)
information will be detected by the thermostat. This must be done prior to powering up the system and control system.
1. Congure air handler control (AHC) for auxiliary heat strips if used.
2. Wiring—See Communicating System and optional accessories wiring
diagrams.
• Four-conductor thermostat wire between the HD Display, Smart-Hub and gas air handler (R, i+, i-, C).
• Conventional thermostat wire with 5 to 6 conductors from iComfort air handler to conventional HP (5 – 8 wires). (Y1, C, R, W1, O, and on some models Y2).
• Wiring as required for accessories.
3. On air handler control:
• When matched with conventional Lennox brand 2-stage heat pump, cut the Y1-Y2 2-stage comp on-board clippable link.
• Remove jumper between W1 and W2 for two-stage electric heat only.
• Cut on-board R-O clippable link.
4. After the entire system is wired, energized the system and the thermostat will check the system for installed communication devices.
5. During commissioning you will arrive at the equipment found screen. From there touch non-communicating equipment to add non-communicating equipment.
6. From the add/remove equipment screen touch the Outdoor Unit Type from the device list (1-stage HP or 2-stage HP) and touch done to return to the equipment found screen.
7. Touch continue to proceed to the next screen.
8. Continue with the commissioning sequence until you reach the dealer control center. Touch equipment to continue.
9. Touch air handler from the list. From this air handler screen you will
have access to the various airow settings. Set the system air volumes according to the needs of the home. When all CFM settings are complete, touch the back button.
10. Test the system operation and conrm the system is electrically energized
and operational. Test the heat strips (when used) to insure the auxiliary stages operates as designed.
11. Touch done.
12. Exit the dealer control center by touching exit to return to the home
screen.
partIal IComFort systEmIComFort EquIpmEnt IntErFaCE moDulE
The iComfort Equipment Interface Module (EIM) can be congured in the
following setups:
• Thermostat, EIM with either a non-communicating (conventional) indoor unit
and iComfort outdoor unit.
• Thermostat, EIM with either a non-communicating (conventional) indoor unit
and outdoor unit.
• Thermostat, iComfort furnace, EIM and a non-communicating heat pump.
1. Wiring—See Communicating System and Optional Accessories Wiring diagrams.
• Four-conductor thermostat wire between the HD Display, Smart-Hub
and equipment interface module (R, i+, i-, C).
• Four-conductor thermostat wire from the Smart Hub to the iComfort
heat pump (R, i+, i-, C).
46
• Up to 8-conductor thermostat wire from the non-communicating furnace terminal strip to the equipment interface module (R, C, O, Y1, Y2, G, W1, W2 and W3).
• Wiring as required for accessories
2. DO NOT cut any option link on furnace control.
3. After the entire system is wired, power up the system; the thermostat will
check the system for installed communication devices.
4. During commissioning you will arrive at the equipment found screen. From there touch non-communicating equipment to add non-communicating equipment.
5. From the add/remove equipment screen, touch either 1-Stage A/C unit or 2-Stage A/C unit.
6. Touch the done to return to the equipment found screen. Touch continue to proceed to the next screen.
7. Continue with the commissioning sequence. When the set up airow per zone screen appears, you can adjust blower, heating and cooling
circulation air ows. When done, touch continue to proceed.
8. The dealer control center will appear next. Touch tests to access the test
section
9. Here you will have another opportunity to adjust blower circulation, heating
and cooling circulation air ows. Use the plus or minus buttons to adjust
up or down the CFM settings. Once adjustments are completed, press
continue.
10. Under the select test to run screen, you may un-check any tests not
required, or run all tests. Touch start tests to proceed. Once each test section is completed, touch continue to proceed to the next group of tests.
11. Once all test are completed, touch done. This will return you to the select tests to run screen. If nish, press the back arrow (<) at the top left-hand of the screen to return to the dealer control center.
12. Touch exit to return to the home screen.
G71MPP or SLP98 Furnace Setting Adjustments
If your thermostat is being used with either a G71MPP or SLP98 furnace and is set to variable-capacity mode of operation (the iComfort default with these units), the system’s settings for stage timers are ignored (even if shown enabled in the thermostat). The stage timer will be used on the cooling side for other cooling units except when modulating outdoor units are used. The
furnace software sets and controls the ring rates. The only other controlling
factor is the stage temperature differentials. In Load-Tracking Variable Capacity (default for these furnaces), both stage timers and temperature differentials are ignored.
Wi-Fi Connection
This is for connecting the thermostat to a secure home wireless network.
NOTE: A router with Bonjour capabilities is required for this function. Check
the router functions if Smart Hub do not connect. Apple Bonjour® is an
implementation of zero-conguration networking (Zeroconf), a group
of technologies that includes service discovery, address assignment, and host name resolution.
NOTE: Never use a home guest account. Never use an open router connection
(non-secure). Always use a secure connection physically located in the home where the thermostat is located.
Home Wi-Fi Access Point is Visible
1. Go to menu > settings > wi- ,
2. Slide the option to ON to enable Wi-Fi.
3. Wi-Fi network will show not connected. Press on not connected to
display a list of available access points.
4. Select a network will be displayed listing all detected networks within range. Select your home network by pressing on the network name.
NOTE: The thermostat can connect to a home wireless router that uses up to
32 characters in the access point name (visible or hidden).
5. When connecting to a secure home Wi-Fi network, a password will be requested. Enter your home Wi-Fi network password and press join to continue.
NOTE: If you wish to see the characters you are typing, check show password.
The thermostat will support up to a 63 character password. The password cannot contain the % or # symbols.
Home Wi-Fi Access Point is Hidden
1. Slide the option to ON to enable Wi-Fi.
2. Wi-Fi network will show not connected. Press on not connected.
3. Select other.
4. The “enter new network information” screen will appear. Enter the name of
the hidden network.
NOTE: The thermostat can connect to a home wireless outer that uses up to
32 characters in the access point name (visible or hidden).
5. Select Security. Options are: none, WEP, WPA and WPA2. If your home Wi-Fi connection is unsecured, then Wi-FI security must be enabled using WEP, WPA or WPA2 via the router before proceeding. Consult your router documentation on how to enable Wi-Fi security.
47
6. Once security type is selected, a password eld will appear. Enter the
password to access your home Wi-Fi network.
NOTE: If you wish to see the characters you are typing, check show password.
The thermostat will support up to a 63 character password.
7. Press join.
Whether connecting to a visible or hidden network, if successful, a check mark will appear above both the router and Internet icons.
HOME WI-FI
ROUTER
INTERNET
ACCESS
SERVER
CONNECTION
E30
THERMOSTAT
Figure 19. Connection Status
Troubleshooting Wi-Fi Connection
The following terminology is used in this troubleshooting section:
• Received Signal Strength Indication (RSSI). This indicates the signal strength of the Wi-Fi router being received by the scanning device (i.e., smart phone). So the higher the RSSI number (or less negative in some devices), the stronger the signal.
• Wireless networks supported by this system are:
» 802.11b is 2.4Ghz band (max 11 Mbit/s) » 802.11g is 2.4Ghz band (max 54 Mbit/s) » 802.11n is 2.4Ghz band (max 130 Mbit/s)
• Internet Protocol Address (IP address). This is an address assigned by your home router for each network device (e.g., computer, printer, thermostat).
Electromagnetic Interference Causing Poor Connectivity: Locate the Smart Hub and router away from other devices that could possibility interfere with wireless communications. Some examples of other devices that could interfere are:
• Microwave ovens
• Wireless cameras
• Portable phones and bases
• Baby monitors
• Wireless speakers
• Bluetooth devices
• Garage door openers
• Neighbor’s wireless devices
To eliminate a possible source of interference, temporally disable any devices and see if Wi-Fi performance has improved.
Received Signal Strength Indication (RSSI)
The ideal signal strength range for the thermostat is -1 to -69 RSSI. The signal strength can be viewed from the thermostat interface.
1. Press NETWORK SETTINGS; this screen shows a graphical view of buttons representing OPEN and SECURE wireless networks, along with button for adding a network.
2. Select the access point that has already been established and connected. When selecting the info icon, a screen will appear which will display an option to forget the network and IP address assigned to the thermostat by your router, sub-net mask, router, DNS and RSSI. If the RSSI signal strength is anywhere between -9 to -69, then the signal strength is
sufcient. If outside this range, then either relocate the router closer to the
thermostat, add a repeater, or move the Smart Hub. Adjusting antenna on router and/or Smart Hub may resolve the issue.
Home Network ........................
IP address 192.168.1.4...............
subnet mask 255.255.255.0............
router
DNS
04-ISSR............................
i
forget this network
Figure 20. Verifying Signal Strength
Performance Reports
Performance reports are only available through either the consumer or dealer web portals.
• Homeowner access is available at www.myiComfort.com.
• Dealer access is available through the Dealer Dashboard at
www.LennoxPros.com.
More information concerning Performance Reports is available in the user guide.
48
Replacement Parts
The following thermostat component parts can be ordered:
Table 16. Replacement Parts
Catalog # Component Remarks
12X97 HD display Thermostat interface 15X98 Smart hub Control base 12X99 Mag-Mount Wall mount for HD Display 13X01 Wall plate Wall plate for Mag-Mount (use is optional)
Replacement Indoor and Outdoor Communicating Controls
These kits have been set up for replacement of the communicating controls.
Please note that control kits are unit-specic.
Table 17. Replacement Communicating Controls
Catalog #
Replacement Kit
Catalog #
SLP98 (rev. 01 or later) 15M50 SL280 (rev. 02 or later) 15T94 EL296 (rev. 01 or later) 15T94 CBA38MV 16B27 CBX40UHV (rev. 02 or later) and CBX32MV (rev. 06 or later) 16B27 XC21 (rev. 04 or later) and SL18XC 11H36 SL18XP, XP21 and XP21N 11H36 XP20 and XP25 14G30 XC20 and XC25 14G30
Mobile Applications
iComfort Thermostat App (Homeowner)
The free iComfort Thermostat app is available for use on iPhone® and iPad®,
Android™ devices.
Control cooling/heating temperatures, fan operation, set programs and set Away mode for multiple locations.
Also controls individual zone settings if system is equipped with the optional iHarmony® Zoning System.
iComfort Mobile Setup App (Installer)
Allows the installer to commission the system and remotely turn the system on and off during setup on any iPhone®, iPad® and Android™ device.
Apple, the Apple logo, iPhone and iPad are trademarks of Apple Inc. registered in the US and other countries.
Android is a trademark of Google Inc. Use of this trademark is subject to Google permission.
Notications (Alert Codes)
These screens provide information on active notications and previously cleared notications. When selecting either a cleared or active notication a brief description and alert code will be displayed. Notications are categorized
by system, indoor unit (air handler or furnace), outdoor unit (air conditioner or heat pump), zoning control (if installed) and thermostat.
alErt CoDE typEs
To expand a specication notication to access a more detail description of the
alert code, press the down arrow to expand the description.
Critical alerts are displayed on Home (user) screen, in the Homeowner alert
button, and in the Installer alert button. Critical means that a service call is needed to get the system running.
Minor and Moderate alerts are found only in the Installer alert button.
What does minor and moderate mean?
Minor is information only, helps Lennox interpret test results, understand
complicated behavior.
Moderate means that the system will likely recover on its own, no action
necessary.
Communication System: When communication controls are operating in a communication system, all jumper and link setting on controls are ignored. Jumpers and link setting are treated as defaults and would only be active if the system was converted to a non-communicating system.
49
soFt DIsaBlE
Soft disabling is when the iComfort® thermostat nds an unknown control on the S30 system communication bus. The thermostat sends the unknown control a message to go into soft disable mode until the component is properly
congured or removed.
The iComfort® thermostat will not show any code for a soft disabled control. When soft disabling occurs only the control that has been disabled will display the blinking LED status. Refer to the device’s installation and setup guide for further guidance.
Use the following procedure if a equipment interface module (EIM) is used and is displaying the soft disable code.
1. Conrm proper wiring between all devices such as thermostat and Smart
Hub.
2. Cycle power to the EIM.
3. Go to the menu > settings > advanced settings > view dealer control center. Touch proceed to continue.
4. Select equipment.
5. Touch reset.
6. Touch re-congure system.
7. Select conrm to continue.
8. The thermostat will reboot and start through the system commissioning
procedure.
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
10 Critical Thermostat
Unknown
Device
Detected -
DEVICE2
The thermostat when NOT in conguration mode has detected an unknown device. Typically the
thermostat will send a command to the unknown device and place the device into a soft disable state. The soft disable control will indicate so as follows:
• On air handler, furnace and outdoor controls, the soft-disabled state is displayed by double horizontal lines on seven-segment display.
• On the damper control module, the green LED will blink 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will blink 3 seconds on and 1 second off.
A new communicating device has been added to the system since the original conguration setup was completed.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
Clear alert code by reconguring
the system.
11 Critical Thermostat
Missing
DEVICE2
The thermostat cannot nd a previously installed system component.
• Check all system components (devices) connections to make sure they are iComfort­compatible.
• Cycle system power.
• If problem persists, then check all system components (devices) connections to make sure they are iComfort-compatible.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
Cycle system power, and If problem persists then clear by
reconguring the system.
50
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
12 Critical Thermostat
Incomplete
System
Thermostat did not nd an indoor unit. Make sure there is an iComfort indoor unit on the system.
• Check for voltage and missing component.
• Check R, i+, i- and C connections.
• Ohm wires for electrical continuity.
Cycle power to both indoor unit rst and then thermostat.
Verify that equipment interface module (if applicable) is congured as either an air handler or furnace when used with a non-communicating indoor unit.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
• Replace indoor unit control if there is no response.
Automatically clears when the system detects that the issue no longer exists.
13 Critical Thermostat
Duplicate
Comfort Sensor
ID
Thermostat found more than one outdoor unit, or more than one indoor unit, or more than one thermostat connected to the system. Thermostat will display the message “Too Many Devices of the Same Type”.
• Check wiring and remove duplicate equipment.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
Automatically clears when the system detects that the issue no longer exists.
14 Critical Thermostat
Too Many
Devices of the
Same Type
The thermostat found more than one thermostat, indoor or outdoor unit on the system.
• Check wiring and remove duplicate equipment.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
Automatically clears when the system detects that the issue no longer exists.
18 Minor Thermostat
Low Ambient
HP Heat
Lockout
The outside temperature is below the level where the heat pump is programmed to heat the home. The system will not use the heat pump to warm your home.
• Outdoor temperature is below the low balance point.
• Heat pump will not be used to service a heating demand.
This is a notication only alert
code. Will automatically clear once the outdoor temperature rises above the low balance point.
19 Minor Thermostat
High Ambient
Auxiliary Heat
Lockout
The outside temperature is higher than the level where the furnace or electric heat is pro­grammed to work. The system will only use the heat pump to warm your home.
This is a notication only alert code.
• Outdoor temperature is above the low balance point.
• Indoor unit (furnace or air handler) will not be used to service a heating demand.
Automatically clears when the system detects that the issue no longer exists.
29 Critical Thermostat
Over
Temperature
Protection
The thermostat is reading an indoor temperature that is higher than 90ºF (factory default). The thermostat will not allow any heating operation to begin until it senses an indoor temperature lower than 90ºF. Indoor temperature rose above 90ºF during a heating or cooling demand.
• Heating operation is not allowed.
• Check to ensure that heating equipment is not stuck ON (reversing valve, etc.)
• Check the accuracy of the thermostat temperature sensor.
• Select cooling system mode to cool the indoor space below 90ºF.
Automatically clears when the system detects that the issue no longer exists.
51
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
30 Moderate Thermostat
Low
Temperature
Protection
The thermostat will not allow any cooling operation to begin until it senses a temperature higher than 40ºF.
• Cooling operation is not allowed.
• Check to ensure that cooling equipment is not stuck ON.
• Check accuracy of the thermostat temperature sensor.
• Select heating system mode to heat the indoor space to above 40ºF.
Automatically clears when the system detects that the issue no longer exists.
31 Critical S30 Smart Hub
Lost
Communication
with DEVICE2
The applicable system component (indoor, equipment interface or damper control module or outdoor unit) has not communicated with thermostat for more than three minutes.
• Check connections and voltages.
• Ohm wires for electrical continuity.
If oat switch is installed on air handler drain pain, check condensate line to ensure it is not
clogged and tripping the oat switch connected in series with R terminal.
If fault persists, then cycle power.
Fault clears after communication is restored.
32 Moderate
S30, furnace, air handler or
outdoor unit
Asynchronous
Reset DEVICE2
The applicable system component (device) is resetting itself. This issue may occur during a
power outage or power uctuation in the system. If persistent or if it coincides with the system
operations then proceed with the following troubleshooting steps.
• Check the power connections.
• Check the amp draw at the transformer (the transformer maybe overloaded).
• Check 24VAC voltage at the system component (device).
• If the fault persists after checking the connections, replace the applicable control.
To clear the alert code, go to
menu > settings > advanced settings > view dealer control
center > notications and select the alert code and press the clear button.
34 Critical
Indoor or
outdoor unit
Must Program
Unit Capacity for DEVICE2
The thermostat does not know the capacity (tonnage) of the indoor or outdoor unit. The applica­ble system component is missing the programmed unit capacity.
• Remove power to thermostat before programming the unit control.
• Go to applicable unit control and program the unit capacity manually (see the unit installation
instruction for conguration instructions).
Once conguration is complete then reconnect thermostat wires.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
Automatically clears when the system detects that the issue no longer exists.
36 Critical Thermostat
Heating when
Not Requested
DEVICE2
The system has been heating for at least 15 minutes without a demand for heating.
• Run the system in diagnostic mode and verify that it matches actual equipment operation. Go to menu > settings > advance settings > dealer control center > diagnostics and press the start diagnostics button.
• Check for other alert codes that may be preventing the system from operating as expected.
• Check all heating equipment to determine cause of heating demand.
• Recycle power.
Automatically clears when the system detects that the issue no longer exists.
37 Critical Thermostat
Cooling when
not Requested
DEVICE2
The system has been cooling for at least 15 minutes, without a demand for cooling.
• Run the system in diagnostic mode and verify that it matches actual equipment operation. Go to menu > settings > advance settings > dealer control center > diagnostics and press the start diagnostics button.
• Check for other alert codes that may be preventing the system from operating as expected.
• Check all cooling equipment to determine cause of cooling demand.
• Recycle power.
Automatically clears when the system detects that the issue no longer exists.
52
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
38 Critical Thermostat
Not Heating
when
Requested
DEVICE2
The system has not been able to turn on the heating for more than 45 minutes.
• The system will go off-line for 60 minutes and will attempt to restart itself.
• Run the system in diagnostic mode and verify that it matches actual equipment operation. Go to menu > settings > advance settings > dealer control center > diagnostics and press the start diagnostics button
• Check for other alert codes that may be preventing the system from operating as expected.
• Check all heating equipment to determine cause.
• Recycle power.
Automatically clears when the system detects that the issue no longer exists.
39 Critical Thermostat
No Cooling
when
Requested
DEVICE2
The system has not been able to turn on the cooling for more than 45 minutes.
• The system will go off-line for 60 minutes and will attempt to restart itself.
• Run the system in diagnostic mode and verify that it matches actual equipment operation. Go to menu > settings > advance settings > dealer control center > diagnostics and press the start diagnostics button
• Check for other alert codes that may be preventing the system from operating as expected.
• Check all cooling equipment to determine cause.
• Recycle power.
This alert code will automatically clear when the system detects the issue no longer exists.
53
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
40 Minor
Heat pump,
furnace,
electric heat,
and iHarmony
HP Heating
Lockout.
The heat pump could not increase the room temperature 0.5°F towards the set point in 30 min­utes.
In order to use the gas furnace as a primary heating source (not defrost tempering) when the outdoor temperature is between the high and low balance points, the heat pump:
• Must be used for a minimum of 30 minutes and the temperature in the zone not increase by more than 0.5°F
• Has not gone into defrost in the 30 minute period.
The default for HP Heating Lockout Time default is 120 minutes and will lock the heat pump off when the outdoor temperature is above the high balance point. Selectable range is 60 to 240 minutes.
• Go to menu > settings > advance settings > dealer control center > equipment > Smart Hub and located HP Heating Lockout Time to verify the lockout time setting.
NOTE: HP Heating Lockout Time is only available in a zoning system.
If any single zone satises the aforementioned conditions, the heat pump is stopped and the gas
furnace is used to satisfy all heat calls for the next duration of the parameter heat pump lockout time. After the heat pump lock out is expired, the heat pump is once again used as the primary heat source.
• Run system and verify that the heat pump cannot raise the room temperature 0.5F in 30 minutes on the zone or zones.
Check air ow to the zones or zones.
• Check discharge air temperatures.
• Check calibration of room thermostat.
• Set the low balance point and high balance point as close together as possible. (This is 3°F difference – Example: Set high balance point at 40°F and low balance point would set at 37°F). Go to menu > settings > advance settings > dealer control center > equipment > Smart Hub and located Low and High Balance Points.
• When below the low balance point, the indoor unit will heat the home between the low and high balance point, the heat pump and furnace will heat the home. When the outdoor temperature is above the high balance point, the gas furnace is locked out and all the heat is provided by the heat pump.
Clears when heat pump comes out of HP Heating Lockout Time.
41 Moderate
Furnace, air
handler or
outdoor control
Component control has
been replaced.
This alert code will appear anytime a component control [Furnace, air handler, air conditioner or heat pump] is replaced in the system.
Must be cleared manually.
105 Critical
Thermostat,
furnace,
air handler,
outdoor unit,
equipment
interface,
PureAir S or
IHarmony
Communication
Problem
A system component has lost communication with the system. System component (device) is unable to communicate.
• This may indicate the existence of other active alert codes.
• In most cases errors are related to electrical noise. Verify that high voltage power is separated from the low voltage communication wires.
• Check for incorrectly wired or loose connections between system components (devices).
• Check for a high voltage source of noise close to the system.
Automatically clears when the system detects the issue no longer exists.
110 Critical Furnace
Low AC Line
Voltage
The component AC line voltage is too low. This alert code may appear during a brownout. It may also occur when line voltage is below its designed operating value.
• Check and correct the power line voltage.
Automatically clears when the system detects the issue no longer exists.
54
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
111 Critical Furnace
Line Polarity
Reversed
The unit is reporting that its power and neutral lines are reversed.
• Turn off the power to the system and correct the line power voltage wiring.
System resumes normal operation ve seconds after critical condition is recovered.
Automatically clears when the system detects the issue no longer exists.
112 Critical Furnace
No Ground Connection
The reporting component cannot nd earth ground. The thermostat will shut down the system.
• Provide proper earth ground to the equipment.
System resumes normal operation ve seconds after critical condition is recovered.
Automatically clears when the system detects the issue no longer exists.
113 Critical Furnace
High AC Line
Voltage
Line voltage high (voltage higher than nameplate rating).
• Provide power voltage within proper range.
System resumes normal operation ve seconds after critical condition is recovered.
Automatically clears when the system detects the issue no longer exists.
114
Moderate /
Critical
Furnace,
air handler,
equipment
interface or
IHarmony
AC Line
Frequency /
Distortion Prob
There is a frequency / distortion problem with the power to a specic system component. There is a frequency / distortion problem with the power to a specic system component.
• This alert code may indicate transformer overloading.
• Check the voltage and line power frequency.
• Check the generator operating frequency, if the system is running on back-up power.
• Correct voltage and frequency problems.
System will resume normal operation ve seconds after fault recovered.
• All applicable system component outputs are disabled – moderate condition.
• After 10 minutes, the priority condition is escalated – critical condition.
• Damper control module will operate in central mode only until proper voltage is restored or frequency distortion is resolved – moderate condition.
Automatically clears when the system detects the issue no longer exists.
115 Critical
Furnace,
air handler,
equipment
interface
module and
IHarmony
Low Secondary
(24VAC)
Voltage
24VAC power to a system component control is lower than the required range of 18 to 30VAC.
• Check and correct voltage.
• Check for additional power-robbing system components (devices) connected to system.
• This alert code may require the installation of an additional or larger VA transformer.
• Damper control module will operate in non-zone mode until proper voltage is restored.
Automatically clears when the system detects the issue no longer exists.
116 Critical
Furnace or Air
Handler
High Secondary
(24VAC) voltage
• Thermostat will display this code when 24VAC power is high (18 to 30 VAC).
• Will display Furnace or Air Handler High Secondary (24VAC) voltage.
Check and correct voltage. Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when control senses proper voltage.
117 Minor Furnace Poor Ground
The reporting unit has poor earth grounding.
• Provide proper grounding for the system component (device).
• Check for proper earth ground to the system.
Automatically clears 30 seconds after the issue is corrected.
120 Moderate
Thermostat,
furnace,
air handler,
outdoor unit,
equipment
interface,
PureAir S or
IHarmony
Unresponsive
DEVICE2.
There is a delay in the system component responding to the system. Typically this alert code does not cause any operational issues and will clear on its own.
• This alert code is usually caused by a delay in the outdoor unit responding to the thermostat.
• Check all wiring connections.
Automatically clears after an unresponsive system compo­nent (device) responds to any inquiry.
55
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
124 Critical
Thermostat,
furnace,
air handler,
outdoor unit,
equipment
interface,
PureAir S or
IHarmony
Active Subnet
Controller
Missing
The thermostat has lost communication with a system component for more than three minutes. System component has lost communication with the thermostat.
• Check the wiring connections.
• Ohm wires.
• Cycle power.
• Check voltage at component.
This alert code stops all associated system operations and waits for a heartbeat message from the system component that is not communicating.
Automatically clears after com­munication is re-established with applicable system component (device).
125 Critical
Thermostat,
furnace,
air handler,
outdoor unit,
equipment
interface,
PureAir S or
IHarmony
Control
Hardware
Problem
There is a hardware problem on a system component control. There is a control hardware prob­lem.
• Replace the control if the problem prevents operation and is persistent.
Damper control module will remain in non-zone mode (all dampers open) for ve minutes after priority condition no longer exist.
• Remove jumper if present on indoor unit between R and W2 if equipment interface module is in use.
• PureAir S jumper selector is missing
Automatically clears ve min­utes after the issue no longer exists.
126 Critical
Furnace, air
handler or
outdoor unit
Control Internal Communication
Prob
There is an internal hardware problem on the system component control.
• Typically the system component control will reset itself.
• Replace the system component (device) control if the problem prevents operation and is persistent.
Automatically clears 300 sec­onds after the issue no longer exists.
130 Moderate
Equipment
interface
module
Conguration
Jumper Missing
Conguration jumper missing on equipment interface module.
• Install the missing jumper.
NOTE: This is applicable in non-communicating applications only).
Automatically clears after the missing or incorrectly installed jumper is installed or correct­ed.
131 Critical
Thermostat,
furnace,
air handler,
outdoor unit,
equipment
interface,
PureAir S or
IHarmony
Corrupted
Control
Parameters
System component control parameters are corrupted.
• Replace the system component control if heating or cooling is not available.
• Go to menu > advance settings > view dealer control center > equipment and press reset all equipment. This will allow the system to auto-detect any iComfort components attached.
Will automatically clear when system component (device) passes memory self-test or system component control is replaced.
132 Critical
Air handler,
equipment
interface module ,
PureAir S or
IHarmony
Failed Flash
CRC Check
System component control software is corrupted.
• Recycle power.
• If failure re-occurs, replace the system component control.
Manual system power reset is required to recover from this alert code.
56
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
180 Critical
Furnace, air
handler or
equipment
interface
module
Outdoor
Temperature
Sensor Problem
The thermostat has found a problem with a system component’s outdoor temperature sensor. In normal operation after system component control recognizes sensors, the alarm will be sent if valid temperature reading is lost.
• Compare outdoor sensor resistance to temperature / resistance charts in unit installation instructions.
• Replace sensors pack if necessary.
At the beginning of (any) conguration, furnace, air-handler control or equipment interface module will detect the presence of the sensor(s).
• If detected (reading in range), appropriate feature will be set as ‘installed’ and shown in the ‘About’ screen.
Automatically clears upon
conguration, or sensing normal
values.
200 Critical Furnace
Rollout Limit Switch Open
The furnace roll out limit switch is open. Correct the cause of roll out trip.
• Reset roll out switch.
• Test the furnace operation.
Automatically clears after the fur­nace roll out switch is closed.
201 Critical
Furnace or air
handler
Indoor Blower
Motor Problem
Lost communication with indoor blower motor.
• Possible causes include power outage, brown-out, motor not powered, loose wiring, condensation on system component control without cover on breaker.
• Problem may be on system component control or motor side.
Automatically clears after com­munication is restored.
202 Critical
Furnace or air
handler
ID Blower Motor
& Unit Size
Mismatch
The unit size code for the indoor unit and the size of blower motor do not match. Incorrect appli­ance unit size code selected.
• Remove the thermostat from the system while applying power and reprogramming.
Check for proper conguring under unit size codes for furnace/air handler in conguration guide or in installation instructions.
Automatically clears after the correct match is detected follow­ing a reset.
203 Critical
Furnace or air
handler
Invalid Unit
Code
The unit size code for the indoor unit has not been selected.
• Remove the thermostat from the system while applying power and reprogramming.
Check for correct conguration. Unit size codes for furnace and air handler are listed in the
system component conguration guide or installation instruction.
Automatically clears after the correct match is detected follow­ing a reset.
204 Critical Furnace
Gas Valve
Problem
There is an issue with the furnace gas valve.
• Check gas valve operation and wiring.
Automatically clears after the issue is corrected.
205 Critical Furnace
Gas Valve relay Contact Closed
The furnace gas valve relay contact is closed.
• Check wiring on control and gas valve.
Automatically clears after the issue is corrected.
206 Critical Furnace
Gas Valve 2nd
Stage Relay
Failure
The furnace gas valve second-stage relay is faulty.
Furnace will operate on rst-stage for the remainder of the heating demand
• If unable to operate second-stage, replace furnace control.
Automatically clears after the issue is corrected.
207 Critical Furnace
HIS Sensed
Open
The furnace hot surface igniter is open.
• Measure the resistance of hot surface igniter.
Replace the igniter if it is not within the specied range found in furnace installation instruction.
Automatically clears after the issue is corrected.
57
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
223 Critical Furnace
Low Pressure
Switch Open
The furnace low pressure switch is open.
• Check pressure (inches w. c.) of the low pressure switch closing during a heat call.
• Measure operating pressure (inches w. c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
• Check for blocked cold end heater box or condensate drain and cracked hoses.
Automatically clears after the issue is corrected.
224 Critical Furnace
Low Pressure
Switch Stuck
Closed
The furnace low pressure switch is stuck closed.
• Check operation of low pressure switch to see if it is stuck closed for longer than 150 seconds during a heat call.
• Measure operating pressure (inches w. c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
Automatically clears after the issue is corrected.
225 Moderate Furnace
High Press.
Switch Failed to
Close
The furnace high pressure switch will not close.
• Check pressure (inches w. c.) of high pressure switch closing during a heat call.
• Measure operating pressure (inches w. c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
• Check for blocked cold end heater box or condensate drain and cracked hoses.
Automatically clears after the issue is corrected.
226 Critical Furnace
High Pressure
Switch Stuck
Closed
The furnace high pressure switch will not open.
• Check operation of high pressure switch closing during a heat call.
• Measure operating pressure (inches w. c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
Automatically clears after the issue is corrected.
227 Moderate Furnace
Lo Pressure
Switch Open in
Run Mode
The furnace low pressure switch is open while in run mode.
• Check pressure (inches w. c.) of low pressure switch closing during a heat call.
• Measure operating pressure (inches w.c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
• Check for blocked cold end heater box or condensate drain and cracked hoses.
Automatically clears after the issue is corrected.
228 Moderate Furnace
Inducer / Press.
Switch Calib.
Failure
The furnace control is not able to calibrate the pressure switch. Unable to perform pressure switch calibration.
• Check vent system and pressure switch wiring connections.
• Check the drain trap for blockage.
• Check for blocked cold end heater box or condensate drain and cracked hoses.
Automatically clears after a successful calibration.
229 Minor Furnace
Ignition on High
Fire
Furnace control switched to high re ignition because low re pressure switch did not close in
allowed time.
No action is required.
240 Moderate Furnace
Low Flame
Current - Run
Mode
The furnace ame current is low.
Check micro-amperes of the ame sensor using thermostat diagnostics.
Clean or replace the ame sensor.
• Measure voltage of neutral to ground to ensure good unit ground.
• Clean face of burner assembly.
Check for AC voltage from ame sensor electrode to ground.
Automatically clears after a proper micro-amp reading has been sensed.
58
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
241 Critical Furnace
Flame Out of
Sequence - Still
Present
The furnace ame is going out while the furnace is heating.
• Shut off gas.
• Check for a gas valve leak.
• Replace the gas valve if needed.
Check for low ame signal.
Automatically clears when a heat call ends successfully.
250 Moderate
Furnace and
iHarmony
Primary Limit
Switch Open
The furnace primary limit switch is open.
• If limit switch is not closed within three minutes, the unit will go into a 60 minute soft lockout (WatchGuard mode).
• Check for high gas pressure.
Low supply air due to being plugged or restriction in system (example: dirty air lter or blockage in duct work).
• Limit trips will place the iHarmony zoning system into non-zone mode.
Check for proper ring rate on furnace.
• Check for non-functioning zone dampers.
NOTE: Refer to S&A Note ACC-14-01 - iHarmony and SLP98 - Insufcient Zone Heating and
Alarm Code 250 Issues for corrective actions.
Automatically clears when a heat call ends successfully.
NOTE: If this issue occurred on an iHarmony zoning system,
the eld will need to manually
activate the zoning.
252 Moderate Furnace
Discharge Air
Temperature
High
The furnace discharge air-temperature is high.
Check temperature rise, air ow and input rate.
Check for dirty air lter(s).
Automatically clears when a heat call ends successfully.
270 Critical Furnace
WatchGuard ­Flame Failure
on Ignite
The furnace is in WatchGuard mode. The furnace igniter cannot turn on the ame. This is a ve
strike condition during a single demand.
Check for proper gas ow.
• Ensure that igniter is lighting burner.
Check ame sensor current.
Check for dirty lters.
• Check for blocked cold end heater box or condensate drain and cracked hoses.
Automatically clears on success­ful ignition.
271 Critical Furnace
WatchGuard
- Low Press
Switch Open
The furnace is in WatchGuard mode. The furnace low pressure switch is open. This is a ve
strike condition during a single demand.
• Check pressure (inches w. c.) of low pressure switch closing during a heat call.
• Measure operating pressure (inches w. c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
Automatically clears on success­ful ignition.
272 Critical Furnace
WatchGuard -
Lo Press Switch
Open Run
Mode
The furnace low pressure switch is open during run mode. The system will go into WatchGuard mode.
• Check operation of low pressure switch to see if it is stuck open during a heat call.
• Measure operating pressure (inches w. c.).
• Inspect vent and combustion air inducer for correct operation and restriction.
• Check for blocked cold end heater box or condensate drain and cracked hoses.
Automatically clears when a heat call ends successfully.
59
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
273 Critical Furnace
WatchGuard
- Flame fail in Run Mode
The furnace ame is going off during a heating cycle. The system will go into WatchGuard
mode.
Check micro-amperes of ame sensor using thermostat diagnostics.
• Clean or replace sensor.
• Measure voltage of neutral to ground to ensure good unit ground.
• Clean face of burner assembly.
Automatically clears when a heat call ends successfully.
274 Critical Furnace
WatchGuard -
Primary Limit
Switch Open
The furnace limit switch has been open for more than three minutes. The system will go into WatchGuard mode.
Check ring rate and air ow.
• Check for air blockage.
Automatically clears when a heat call ends successfully.
275 Critical Furnace
WatchGuard -
Flame Out of
Seq. No Flame
The furnace ame is out of sequence. The system will go into WatchGuard mode.
• Shut off gas.
• Check for gas valve leak.
Automatically clears on success­ful ignition.
276 Critical Furnace
WatchGuard
- Calibration Failure
The furnace is not able to calibrate or the high pressure switch opened or failed to close in run mode. The system will go into WatchGuard mode.
• Check vent system
• Check pressure switch wiring connections.
Automatically clears when the furnace calibrates itself success­fully.
290 Critical Furnace
Ignition Circuit
Problem
There is a problem with the furnace ignition circuit. The system will go into WatchGuard mode.
• Measure resistance of hot surface igniter.
Replace the hot surface igniter; it is not within specications.
• Measure voltage to igniter.
Automatically clears on success­ful ignition
291 Critical Furnace
Heat Airow
Restricted
Below Min
The heating airow is below the minimum required level. The system will go into WatchGuard
mode.
Check for dirty air lter(s) and other air ow restrictions.
• Check blower performance.
Automatically clears when a heat call ends successfully.
292 Critical
Furnace or air
handler
Indoor Blower
Motor Start
Problem
The indoor unit blower motor will not start. The system will go into WatchGuard mode.
• Indoor blower motor unable to start.
• This could be due to seized bearing, stuck wheel, and obstructions.
• Replace motor, motor module or wheel if assembly does not operate or meet performance standards.
Automatically clears after the indoor blower motor starts suc­cessfully.
294 Critical Furnace
Inducer Motor
Overcurrent
There is over current in the furnace inducer motor. The system will go into WatchGuard mode.
• Check combustion blower bearings, wiring and amps.
• Replace furnace inducer motor if it does not operate or does not meet performance standards.
Automatically clears after inducer motor current is sensed to be in­range after the ignition following either WatchGuard mode or unit reset.
295 Minor Furnace
Indoor Blower Over Temperature
The indoor blower motor is overheating. Indoor blower motor over temperature (motor tripped on internal protector).
• Check motor bearings and amps.
• Replace indoor blower motor if necessary.
• Check for high duct static.
Automatically clears after blower
demand is satised.
60
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
310 Moderate
Furnace and
air handler only
Discharge Air Temp Sensor
Problem
There is a discharge air temperature sensor issue.
• Compare discharge temperature sensor (DATS) resistance to temperature / resistance charts in system component installation instruction.
• Replace discharge air sensor if necessary.
NOTE: Conrm there is no short or open circuits in the iComfort thermostat connections to any
of the other components in the communication system.
NOTE: Issues with a DATS connected to a damper control module or equipment interface model
will not generate an alert code.
Automatically clears 30 seconds after condition is detected as recovered or after system restart.
311 Minor Furnace
Heat Rate
Reduced to
Match Airow
The heat ring rate has been reduced to match available airow (cutback mode). This is a warn-
ing only alert code.
Furnace blower in cutback mode due to restricted airow.
Reduce ring rate every 60 seconds to match available CFM.
Check air lter and duct system.
To clear, replace air lter if needed or repair or add additional ducting.
Two-stage controls will reduce ring rate to rst stage.
Automatically clears when a heating call nishes success­fully.
312 Minor
Furnace or air
handler
Reduced/
Airow-Indoor
Blower Cutback
The indoor blower cannot provide the requested CFM due to high static pressure. This is a warn­ing only alert code.
Possible restricted airow - Indoor blower is running at a reduced CFM (Cutback Mode).
• The variable speed motor has pre-set speed and torque limiters to protect the motor from damage caused by operating outside of design parameters (0 to 0.8” e.g. total external static pressure).
Check air lter and duct system.
To clear, replace air lter if needed or repair or add additional ducting.
Automatically clears after the current service demand is
satised.
313 Minor
Furnace, air handler and outdoor unit
Indoor/Outdoor
Unit Capacity
Mismatch
The indoor and outdoor unit capacities do not match. This is a warning only alert code.
Check for proper system component conguring in installation instructions.
The system will operate, but might not meet efciency and capacity parameters.
Automatically clears after com­missioning is complete.
344 Critical Furnace Relay Y1 Stuck
Link Relay Problem. Relay Y1 Failure
• Possible Y1 relay failure.
• All system operations will stop.
Automatically clears ve minutes
after Y1 input sensed OFF.
345 Critical
Air handler,
equipment
interface
module or heat
pump
Relay O Failure
The O relay on the system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize.
• Possible O relay / stage 1 failure.
• Pilot relay contacts did not close or the relay coil did not energize.
• Replace system component (device) control.
• If error is applicable to the XC25 or XP25, the outdoor control will need to be replaced.
Automatically clears after the fault recovered following reset.
346 Critical Air handler
HP Jumper Not
Removed
The heat pump conguration link is not cut on the air handler control.
Conguration link not cut on air handler control.
• Cut O to R.
• This is only applicable with non-communicating heat pump with communicating indoor unit.
Automatically clears when the system detects that the issue no longer exists.
61
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
347 Critical
Furnace, air
handler or
equipment
interface
module
Relay Y1
Failure
The Y1 relay on the applicable system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize.
• System operation will stop.
• Possible Y1 relay / stage 1 failure.
• Pilot relay contacts did not close or the relay coil did not energize;
• There is no input back to the applicable system component control.
Automatically clears after reset and Y1 input sensed.
348 Critical
Furnace or air
handler
Relay Y2
Failure
The Y2 relay on the applicable system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize.
• Possible Y2 relay / stage 2 failure.
• Furnace pilot relay contacts did not close or the relay coil did not energize
• No input back to furnace or air handler control.
Automatically clears when the system detects that the issue no longer exists.
349 Critical Furnace
IFC Error Check
Jumper O to R
The O to R link on the furnace needs to be restored.
Conguration link R to O needs to be restored.
• Repair cut link by hard-wiring the R to O terminals on the terminal strip.
• Only applicable in non-communicating mode.
Automatically clears when the system detects that the issue no longer exists.
350 Critical Air handler
Electric Heat
Not Congured
The air handler’s electric heat is not congured or incorrectly congured.
Heat call with no congured or incorrectly congured electric heat.
Check for proper conguring under Conguring Electric Heat Stages in the air handler
installation instructions. Smart Hub MUST be removed from the system before conguring
electric heat.
Automatically clears after elec­trical heat detection is success­ful.
351 Critical Air handler
Electric Heat
Stage 1
Problem
There is an issue with the air handler’s rst stage electric heat.
• Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize.
• Possible heat section / stage 1 failure.
Air handler will operate on HP rst stage for reminder of the heat call.
Automatically clears after fault recovered.
352 Critical Air handler
Electric Heat
Stage 2
Problem
There is a issue with the air handler’s second stage electric heat.
• Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize.
The air-handler will operate on rst stage electric heat until the issue is resolved.
Automatically clears after fault recovered.
353 Critical Air handler
Electric Heat
Stage 3
Problem
There is a issue with the air handler’s third stage electric heat.
• Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize.
The air-handler will operate on rst stage electric heat until the issue is resolved.
Automatically clears after fault recovered.
354 Critical Air handler
Electric Heat
Stage 4
Problem
There is a issue with the air handler’s fourth stage electric heat.
• Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize.
The air-handler will operate on rst stage electric heat until the issue is resolved.
Automatically clears after fault recovered.
62
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
355 Critical Air handler
Electric Heat
Stage 5
Problem
There is an issue with the air handler’s fth stage electric heat.
• Either the pilot relay contacts did not close or the relay coil in the electric heat section did not energize.
The air-handler will operate on rst stage electric heat until the issue is resolved.
Automatically clears after fault recovered.
370 Critical Furnace
Interlock Switch
Open
The furnace control has not received 24VAC power for two minutes or more on the DS terminal
• The system will not operate.
• Dealer has cut the W914 jumper (Dehum, Harmony III) on the Lennox Furnace Control.
• The thermostat monitors the DS terminal in the furnace for power and if the link has been cut then power will be lost to DS.
This alert code will clear when 24VAC is continuously sensed on DS terminal for a minimum of 10 seconds or on a power reset.
380
Moderate /
Critical
Equipment
interface
module
Interlock Relay
Failure
Interlock relay failure (furnace or air handler modes only).
• Interlock relay is energized, but input is not sensed after three seconds.
• There will be no heating or cooling due to this alert code – moderate condition.
De-energize interlock relay and energize after ve minutes if demand is still present – critical condition.
Automatically clears after fault recovered.
381
Moderate /
Critical
Equipment
interface
module
Interlock Relay
Stuck
Interlock relay stuck (furnace or air handler modes only).
• Interlock relay continuously sensed (with relay off).
• There is no heating and cooling operation – moderation condition.
• After 10 minutes if event still exist it will be escalated – critical condition.
Automatically clears 30 seconds after fault clears.
382 Moderate
Equipment
interface
module
Relay W1
Failure
Relay W1 failure (furnace or air handler modes only). W1 relay is energized but input is not sensed after three seconds.
Automatically clears when W1 relay input is sensed.
400 Critical Outdoor unit
Compressor
Internal
Overload
Tripped
The compressor internal overload has tripped.
• Thermostat demand Y1 is present; however compressor is not running.
• Check power to unit.
• This alert code is automatically cleared after current is sensed in both RUN and START sensors for at least two seconds or after service is removed, or after power reset.
Automatically clears when the system detects that the issue no longer exists.
401 Moderate Outdoor unit
Compressor
Long Run Cycle
Either the compressor ran for more than 18 hours continuously while attempting to cool the home during a single demand or the system refrigerant pressure is low.
• Alert code will not lockout system.
• If the two-stage outdoor unit has:
• An outdoor control with blinking LED lights then the unit will run in low speed;
• An outdoor control with a 7-segment display, the outdoor control will display alert code 401, but continue to run in high speed.
• If the outdoor unit is a heat pump, and the outdoor temperature is less than 65°F, alert code 401 is ignored.
• Also monitors low pressure switch trips.
Automatically clears after 30 consecutive normal run cycles or power reset.
402 Critical Outdoor unit
Outdoor
Unit System
Pressure Trip
• Either the discharge or suction pressure level is out-of-limits, or the compressor has overloaded.
• Check discharge or suction pressure.
Automatically clears after four consecutive normal compressor run cycles.
63
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
403 Moderate Outdoor unit
Compressor
Short-Cycling
The compressor ran for less than three minutes to satisfy a thermostat demand.
Automatically clears after four consecutive normal compressor run cycles.
404 Critical Outdoor unit
Compressor
Rotor Locked
The compressor rotor is locked up.
• Compressor rotor locked up due to run capacitor short.
• Bearings are seized.
• Excessive liquid refrigerant, etc. (NOTE: May need to install hard start kit).
Automatically clears after four consecutive normal run cycles or after power reset.
405 Critical Outdoor Unit
Compressor Open Circuit
The compressor circuit is open. Compressor circuit open (due to power disconnection - open fuse, etc.)
Automatically clears after one normal compressor run cycle.
406 Critical Outdoor unit
Compressor
Open Start
Circuit
The required amount of current is not passing through the START current transformer.
Automatically clears after current is sensed in START sensor, or after power reset.
407 Critical Outdoor unit
Compressor
Open Run
Circuit
The required amount of current is not passing through RUN current transformer.
Automatically clears after current is sensed in RUN sensor, one normal compressor run cycle, or after power reset
408 Critical Outdoor unit
Compressor
Contactor
Welded
The compressor is running continuously.
Automatically clears one normal compressor run cycle or after power reset.
409 Moderate
Furnace, air
handler or
outdoor unit
Compressor Voltage Low
The secondary voltage for the applicable system component has fallen below 18VAC.
• Secondary voltage is below 18VAC.
• If this continues for 10 minutes, the thermostat will turn off the applicable system component.
Automatically clears after voltage is detected as higher than 20VAC for two seconds or after power reset.
410 Moderate Outdoor unit
Open Low
Pressure Switch
Unit low pressure is below the required limit.
• Check operating pressures.
Low pressure switch opens at a specic pressure (system shuts down) and closes at a specic pressure (system restarts).
Automatically clears when the system detects that the issue no longer exists.
411 Critical Outdoor unit
Low Pressure
Switch Strikes
Lockout
The low pressure switch has opened ve times during one cooling or heating demand.
• Thermostat will shut down the outdoor unit.
Open low pressure switch error count reached ve strikes.
• Check system charge using both approach and sub-cooling methods.
• Reset by putting outdoor unit control in test mode or resetting low voltage power.
Automatically clears when the system detects that the issue no longer exists.
412 Moderate Outdoor unit
Open High
Pressure Switch
The unit high pressure is above the upper limit.
• System will shut down.
Conrm that the system is properly charged with refrigerant.
• Check condenser fan motor, expansion valve (if installed), indoor unit blower motor, stuck
reversing valve or clogged refrigerant lter.
Conrm that the outdoor unit is clean.
Automatically clears after the high pressure switch closes or a power reset
64
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
413 Critical Outdoor unit
Hi Pressure
Switch Strikes
Lockout
The high pressure switch has opened ve times during one cooling demand.
• Thermostat will shut down the outdoor unit.
Open high pressure switch error count reached ve strikes.
• Check system charge using superheat and sub-cooling temperatures.
• Check outdoor fan operation.
Check for dirt or debris blocking air ow to outdoor unit.
• Reset by putting outdoor unit control in test mode or resetting low voltage power.
Automatically clears when the system detects that the issue no longer exists.
414 Moderate Outdoor unit
High
Discharge Line
Temperature
The discharge line temperature is higher than the recommended upper limit of 279ºF.
• Discharge line temperature is greater than 279ºF.
Make sure coil is clean and airow unobstructed in and out of condenser.
• Check system operating pressures and compare to unit charging charts in installation manual.
Automatically clears after dis­charge temperature is less than 225ºF.
415 Critical Outdoor unit
Hi Discharge
Line Temp
Strikes Lockout
The discharge line temperature has been consistently higher than the recommended upper limit of 279ºF.
Discharge line high temperature error count reached ve strikes during a single demand.
Make sure coil is clean and airow unobstructed in and out of condenser.
• Check system charge using superheat and sub cooling temperatures.
• Reset by putting outdoor control in test mode or resetting low voltage power.
Correct issue and cycle power to the system.
416
Moderate /
Critical
Outdoor unit
Outdoor Coil
Sensor Faulty
The outdoor coil sensor is either open, short-circuited or the temperature is out of sensor range.
• Outdoor unit control will not perform demand or time / temperature defrost operation. (System will still heat or cool.)
• This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the control will display a moderate code.
• Advances from moderate to critical after ten (10) minutes.
• Plug-in sensor harness correctly. (Refer to Service and Application Note C-18-08)
• Check resistance of sensor to determine if it is open, shorted, out of temperature calibration or
out of ambient temperature range. Replace if out-of-specications.
Automatically clears when out­door unit control detects proper sensor readings.
If sensor is faulty and the system is reporting the condition as critical, replaced sensor. Reset power to clear alert code.
65
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
417
Moderate
/ Critical
Outdoor unit
Discharge
Sensor Faulty
SYSTEM DETECTION AND Operation:
The outdoor unit discharge line temperature sensor is either open, short-circuited or the temperature is out of sensor range.
• This fault is detected by allowing the unit to run for 90 seconds before checking discharge line sensor resistance.
• If the discharge sensor resistance is not within range after 90 second period, the control will display the priority condition as moderate.
• If the moderate condition continues for 10 minutes, the system changes the priority condition to critical.
POSSIBLE CAUSES:
• The applicable system component detects either an open, shorted or temperature out of range condition.
• Discharge sensor leads located in wrong pin positions in harness plug-in connector. Refer to the applicable unit installation and service procedure and locate the terminal descriptions table to verify cable harness assembly wiring pin positions are correct.
POSSIBLE SOLUTIONS:
• Check the resistance of the discharge sensor and compare to temperature resistance chart located in the applicable unit installation and service procedure. If sensor resistance is out of range then replace the discharge line temperature sensor.
• If discharge sensor wring leads are located in the wrong connector pin-out then order a replacement cable assembly.
Moderate - Automatically clears after fault signal condition is no longer present.
Critical - Power down the system component and either replace faulty sensor or cable as­sembly (whichever is applicable). Power up system component af­ter replacing the applicable part which will clear the alert code / priority condition.
418 Moderate
Equipment
interface module and outdoor unit
W Output
Hardware Fault
There is a faulty W output circuit.
• W terminal is energized while in cooling mode.
• Possible cause may be a stuck closed relay on the control, or something external to the control that is energizing W terminal when it should not be energized.
• Disconnect any wiring from the W terminal.
• If 24VAC is still present on the terminal, then it is a stuck relay.
• If 24VAC disappears, then there is a need to check any of the wires hooked up to the W terminal.
Automatically clears after fault signal is removed.
419 Critical
Equipment
interface module and outdoor unit
W Output
hardware Fault
Lockout
The W output has reported more than ve errors.
• The system will shut down the outdoor unit.
The W output (code E418) on the outdoor unit has reported more than ve strikes.
• Disconnect thermostat wire from W and verify there is no 24VAC on the W.
• If 24VAC is present, replace the outdoor control.
Automatically clears after power recycled.
420 Critical
Air handler
or equipment
interface
module
Defrost Out of
Control
The heat pump defrost cycle has taken more than 20 minutes to complete.
• Defrost cycle lasts longer than 20 minutes.
• Check heat pump operation.
• This is applicable only in communicating indoor unit with non-communicating heat pump.
Automatically clears when W1 signal is removed.
421 Critical
Equipment
interface module and outdoor unit
W External Mis-
wire Fault
The W output terminal on the outdoor unit is not wired correctly. Voltage sensed on W output terminal when Y1 out is deactivated.
Automatically clears once volt­age is not sensed on output or power is cycled.
66
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
422 Moderate Outdoor unit
Compressor
Top Cap Switch
Open
Compressor top cap switch exceeding thermal limit.
• Check condenser fan motor, TXV and indoor unit blower motor.
Check for stuck reversing valve or clogged refrigerant lter.
• XC/XP25: Check to ensure that one of the wires from the top cap switch has not been disconnected from one of the TP terminals on the outdoor control. Reconnect wire if disconnected.
• Check superheat and sub-cooling.
Automatically clears when error is corrected.
423
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter CT Circuit Problem
The inverter has detected a circuit issue.
• When this condition is detected the outdoor control will stop outdoor unit operations and start the anti-short cycle timer – moderate condition.
• Outdoor control will lockout unit after 10 strikes within an hour – critical condition.
• Inverter LEDs will blink code 40
• Refer to the unit service documentation for troubleshooting procedures.
A moderate alarm will clear automatically when the inverter detects the condition no longer exist and will send a clear alarm message.
To clear critical alarm discon­nect power to outdoor unit and restart.
424 Moderate Outdoor unit
OD Liquid Line
Sensor Faulty
The liquid line temperature sensor has malfunctioned.
• In normal operation after outdoor control recognizes sensors, the alert code will be sent if a valid temperature reading is lost.
• Compare liquid line sensor resistance to temperature / resistance charts in unit installation instructions.
• Replace sensor pack if necessary.
At the beginning of (any) conguration, furnace or air handler control will detect the presence of the sensor(s).
• If detected (reading in range), appropriate feature will be set as ‘installed’ and shown in the thermostat ‘About’ screen.
Automatically clears upon
conguration, or sensing normal
values.
425 Minor
Inverter based
outdoor unit*
Compressor
Speed
Limited by OD
Temperature
Outdoor control has increased minimum compressor speed to allow for proper oil return due to low ambient temperature.
• Outdoor ambient temperature is below system limit.
• Control will attempt to run at lowest allowed compressor speed to allow for proper oil return.
NOTE: Minimum speed adjustments start at 45°F and go up to 100% minimum at 17°F
Automatically clears when out­door ambient temperature rises
above limit for more than ve
minutes.
426 Critical
Inverter based
outdoor unit*
Excessive
Inverter Alarms
After 10 faults within 60 consecutive minutes, the control will lockout. Inverter will blink codes 12 to 14 and 53. These inverter codes do not count towards this lockout condition.
To clear disconnect power to outdoor control and restart
427
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter DC
Peak Fault
The inverter has detected a DC peak fault condition.
• If condition (55A or higher) is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle is initiated.
• If peak current (55A or higher) occurs 10 times within an hour, system will lockout – critical condition.
• Inverter LEDs will blink code 21.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear, disconnect and recon­nect power to outdoor control.
67
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
428
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
High Main Input
Current
The inverter has detected a high main input current condition.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle is initiated.
• If condition occurs 10 times within an hour, system will lockout – critical condition.
• Inverter LEDs will blink code 22.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear, disconnect power to outdoor unit and restart.
429
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
DC Link Low
Voltage
The inverter has detected a DC link low voltage condition.
• On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2- and 3-ton models, 250 VDC for 4- and 5-ton models within 30 seconds, the control will display a moderate code.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• An anti-short cycle timer is initiated. If condition occurs 10 times within a 60 consecutive minutes, system will lock out and display alert code 429 – critical condition.
• The outdoor control anti-short cycle timer will time out and the unit will recycle the demand.
• Replace outdoor inverter.
• Inverter LEDs will blink code 23.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Automatically clears when the system detects that the issue no longer exists.
430
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
Compressor
Startup Fail
Compressor start-up failure.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle is initiated.
• If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical condition.
• Inverter LEDs will blink code 26.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear, disconnect power to outdoor unit and restart.
431
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
PFC Fault
The inverter has detected a PFC circuit over-current condition.
• Error occurs when PFC detects an over current condition of 100A peak.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle timer is initiated.
• If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical condition.
• Inverter LEDs will blink code 27.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear, disconnect power to outdoor unit and restart.
432
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
DC Link High
Voltage
The inverter has detected a DC link high voltage condition.
• Error occurs when the DC link capacitor voltage is greater than 480VDC.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle timer is initiated.
• If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical condition.
• Inverter LEDs will blink code 28.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear, disconnect power to outdoor unit and restart.
68
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
433
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter Compressor Over-current
Compressor phase current is too high.
• Error occurs when compressor peak phase current is greater than 28A.
Inverter will issue code 14 rst and slow down to try to reduce the current.
• If the current remains high, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle timer is initiated.
• If condition occurs 5 times within 60 consecutive minutes, the system will lockout – critical condition.
• Inverter LEDs will blink code 29.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear alert code disconnect power to outdoor unit and restart.
434
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
Comm Error to
Main Control
Outdoor control has lost communications with the inverter for greater than three minutes.
• Outdoor control has lost communications with the inverter for greater than three minutes.
• Outdoor control will stop all compressor demands – moderate condition.
• Recycle power to the inverter by de-energizing the contactor for two minutes.
• If this occurs three times in one thermostat call, the outdoor unit will lock out and display alert code 434 – critical condition.
• Check for loose or disconnected electrical connections.
• Interruption of main power to inverter.
• Inverter LEDs will blink code 53.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Automatically clears when the system detects that the issue no longer exists.
435
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
EEPROM
Checksum fault
Inverter internal error.
• When this error occurs, the outdoor control will cycle power to the inverter by opening the contactor for two minutes – moderate condition.
• Outdoor control will cycle power to the inverter three times and then outdoor unit is locked out – critical condition.
• Inverter LEDs will blink code 60.
• Refer to the unit service documentation for detailed troubleshooting procedures.
To clear alert code disconnect power to outdoor unit and restart.
436
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
High Heat-Sink
Temperature
Inverter heat sink temperature exceeded limit.
• This occurs when the heat sink temperature exceeds the inverter limit. Inverter will issue
inverter alert code 13 rst and slow down to try to cool the heat sink.
• If temperature remains high, outdoor unit will stop both compressor and fan – moderate condition.
• Anti- short cycle is initiated.
If condition occurs ve times within an hour, system will lockout – critical condition.
• The screws that hold the inverter to the inverter board were loose causing poor contact between these two components.
• Tighten screws that hold the heat sink to the inverter control board.
NOTE: Wait ve minutes for all capacitors to discharge before checking screws.
• Inverter LEDs will blink code 62.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Moderate condition will auto­matically clear when the inverter sends an alarm clear mes­sage.
Critical condition is cleared by disconnecting power to the out­door unit and restart.
69
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
437
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
Heat-Sink temp
Sensor Fault
Heat sink temperature sensor fault has occurred (temperature less than 4ºF or greater than 264ºF after 10 minutes of operation).
• When the temperature sensor detects a temperature less than 4ºF or greater than 264ºF after 10 minutes of operation.
• Outdoor unit will stop both compressor and fan – moderate condition.
• Anti-short cycle is initiated.
If condition occurs ve times within an hour, system will lockout – critical condition.
• Inverter LEDs will blink code 65.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Moderate priority condition will automatically clear when the inverter sends an alarm clear message.
Critical priority condition can be cleared by disconnecting and reconnecting power to outdoor unit to restart.
438
Moderate /
Critical
Inverter based
outdoor unit*
OD Inverter
PFC Input
Overcurrent
The inverter has detected a PFC circuit over-current condition.
• The inverter has detected a power factor correction (PFC) over current condition. This may be caused by a high load condition, high pressure, or outdoor fan failure.
• Outdoor control will display the code when the inverter has detected the error – moderate condition.
• After three minutes, the inverter will reset and the compressor will resume operation.
• If the error condition occurs 10 times within a 60 minute rolling time period, the outdoor unit control will lock out operation of the outdoor unit – critical condition.
• Possible issue is system running at high pressures.
• Check for high pressure trips or other alert codes in thermostat and outdoor control.
• Inverter LEDs will blink code 73.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Moderate priority condition is automatically cleared when the inverter sends a clear mes­sage.
Critical priority condition will automatically clear when inverter is power cycled.
439 Moderate
Inverter based
outdoor unit*
OD Inverter
Compressor
Slowdown
- High Input Current
Compressor slowdown due to high input current.
• Input current is approaching a high limit.
• Compressor speed will automatically slow down. The outdoor control will continue sending the inverter speed demanded by the thermostat.
• The outdoor control will set indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz.
• Inverter LEDs will blink code 12.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Automatically clears when the condition no longer exists.
440 Moderate
Inverter based
outdoor unit*
OD Inverter
Compressor
Slowdown -
High Heat-Sink
temperature
Compressor slowdown due to high heat sink temperature.
• Heat sink temperature is approaching limit.
• The compressor speed automatically slows to reduce heat sink temperature.
• The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz.
• Feedback from supplier tear down of inverter indicates that the screws that hold the inverter to the inverter board were loose causing poor contact between these two components.
• Tighten screws that hold the heat sink to the inverter control board.
NOTE: Wait ve minutes for all capacitors to discharge before checking screws.
• Inverter LEDs will blink code 13.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Automatically clears when the condition no longer exists.
70
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
441 Moderate
Inverter based
outdoor unit*
OD Inverter
Compressor
Slowdown
- High
Compressor
Current
Compressor slowdown due to high compressor current.
• Compressor slowdown due to high compressor current.
• Compressor current is approaching limit.
• The compressor speed automatically slows.
• The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz.
• Possible issue is system running at high pressures.
• Check for high pressure trips or other alert codes in thermostat and outdoor control.
• Inverter LEDs will blink code 14.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Automatically clears when the condition no longer exists.
442 Critical Outdoor unit
Compressor
Top Cap Switch
Strike Lockout
The top cap switch has opened ve times within one hour. As a result, the outdoor unit is locked
out.
This condition occurs when compressor thermal protection sensor opens ve times within one hour.
• Outdoor unit will stop.
To clear, disconnect power to outdoor unit and restart.
443 Critical Outdoor unit
MUC Unit Code
to Inverter
Model Mismatch
Incorrect appliance unit size code selected.
Check for proper conguring under unit size code used for outdoor unit (see unit conguration guide or in installation instructions).
• If replacing inverter, verify inverter model matches unit size.
• Remove the thermostat from the system while applying power and reprogramming.
Automatically clears after the correct match is detected follow­ing a power reset.
500
Minor
(Escalated
to Critical
after alarm
persists for
15 minutes)
PureAir S
Diff Press
Sensor Fault
Pressure sensor reports a fault for more than 5 minutes, or does not respond for more than 5 minutes.
Device will not perform any pressure reading calculations until fault is recovered. Remaining lter
life display will indicate “-“ while fault exists.
Automatically clears 30 seconds after fault is recovered.
501
Minor
(Escalated
to Critical after alarm persists for
15 minutes)
PureAir S
UV Sensor
Fault
UV sensor reports a fault for more than 5 minutes or UV sensor does not respond for more than 5 minutes.
Device will not perform any UV lamp life remaining calculations until fault has recovered. Life remaining display shall indicate “-“ while fault exists.
Automatically clears 30 seconds after fault is recovered.
502 Critical PureAir S UV Lamp Off
The light is determined to be off when the last three last light intensities measurements are below the set threshold.
Light is determined on after 1 set
of ve samples are above the set
threshold.
503 Moderate PureAir S Filter life at 10% Filter life remaining determined to be <=10%, but greater than 0% None
504 Critical PureAir S Filter Life at 0% Filter life remaining determined to be 0% None
505 Moderate PureAir S
PureAir Model
Selection Changed
Model Selection jumper has changed positions.
Jumper repositioned back to original jumper position or system rebooted.
71
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
506 Critical PureAir S
UV Lamp Life at 0%
UV Lamp Life at 0% None
532 Moderate IHarmony
Zoning
Pressure Switch
Opened (High
Pressure)
Zoning Pressure Switch Opened (high pressure)
Compressor pressure is above the specied limit.
• Compressor is turned off.
• Zoning will be restored once the high pressure switch closes.
Automatically clears after compressor pressure is within limits.
542
Moderate/
Critical
iHarmony Zone
Sensor
Zone 1
Temperature
Sensor Problem
• Zone temperature sensor reading out of range.
Open or short zone temperature sensor detected for more than ve second.
• Damper control module will operate in non-zone mode (all dampers open) – moderate condition.
• If after 10 minutes the condition does not change, the priority code is change to critical. System will continue to operate in non-zone mode.
Automatically clears 30 seconds after condition no longer exist.
543
Moderate/
Critical
iHarmony Zone
Sensor
Zone 2
Temperature
Sensor Problem
544
Moderate/
Critical
iHarmony Zone
Sensor
Zone 3
Temperature
Sensor Problem
545
Moderate/
Critical
iHarmony Zone
Sensor
Zone 4
Temperature
Sensor Problem
546 Critical
iHarmony Zone
Sensor
Memory Error
Zone Sensor EEPROM error (Power ON). System shall restore everything to Energy save De­fault and operate.
Zone sensor will have to be replace.
547 Critical
iHarmony Zone
Sensor
Memory Error
Zone Sensor EEPROM error (Operating). System shall operate in normal mode operation until power off. The reading for humidity will not be valid. This message indicates hum sensor is not working correctly.
Zone sensor will have to be replace.
548 Critical
iHarmony Zone
Sensor
Humidity
Sensor Error
Zone Sensor - Hum sensor error (without humidier or dehumidier): sensor reads out of range
0% to 100%
Zone sensor will have to be replace if it does not auto correct itself.
549 Reminder
iHarmony Zone
Sensor
User Editable Zone Sensor custom reminder1. Displayed in notication screen.
Pressing done button will clear the reminder or pressing remind later on pop-up screen will ex­tend the duration.
550 Reminder
iHarmony Zone
Sensor
User Editable Zone Sensor custom reminder2. Displayed in notication screen.
594
Moderate /
Critical
Equipment
interface
module
Pre-Coil Air
temp Sensor
Problem
Pre-coil discharge air temperature sensor problem (dual-fuel mode only). Advances from moder­ate to critical after ten (10) minutes.
• Interlock relay energized, but input not sensed after three seconds.
• No heating and cooling operations.
De-energize interlock relay and re-energized ve minutes later if demand is still present.
Alarm clears ve minutes after
fault clears.
600 Minor Outdoor unit
Load Shed
Event
Compressor has been cycled OFF on utility load shedding.
• Load shedding function provides a method for a local utility company to limit the maximum power level usage of the outdoor unit.
• The feature is activated by applying 24VAC power across the L and C terminals on the outdoor control.
Automatically clears when L terminal is inactive.
72
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
601 Minor Heat Pump
OD Unit Low
Ambient
Operational
Lockout
• This is a low ambient protection feature.
• Outdoor unit has been lock out (will not run) due to low ambient conditions.
• Outdoor unit will not operate when the outdoor ambient is at or below 4°F (-15.6°C).
• If the unit is satisfying a demand (running) and the outdoor ambient drops below 4°F ( -15.6°C),
the unit will continue to operate until the demand has been satised or the outdoor ambient
drops to 15°F ( -9.4°C) which will result in the unit being locked out (shut down).
Automatically clears when low temperature condition no longer exists.
610 Critical Thermostat
Low Room
Temperature
Detected
This alert will automatically notied the user that a low room temperature condition exist. A
notication is displayed on the HD Display and email notication sent to homeowner and dealer.
• The freeze alert protection parameter range is 30°F to 50°F (-1.11 to 10.0°C). Default is 40°F (4.44°C).
NOTE: Notication is dependent on the thermostat having a active Wi-Fi connection and the
user account has been setup and includes a valid email address.
Automatically clears when condi­tion is resolved.
611 Critical Thermostat
High Room
Temperature
Detected
This alert will automatically notied the user that a high room temperature condition exist.
A notication is displayed on the HD Display and email notication sent to homeowner and
dealer.
• The heat alert protection parameter range is 80°F to 100°F (26.67 to 37.78°C). Default is 90°F (32.22°C).
NOTE: Notication is dependent on the thermostat having a active Wi-Fi connection and the
user account has been setup and includes a valid email address.
Automatically clears when condi­tion is resolved.
700 Critical
S30 HD
Display Unit or
Mag-Mount
Comfort Sensor
Temp Sensor
Problem
The temperature sensor in the HD Display is not working properly.
• Run reset all under Dealer Control Center.
• Try removing display from mag-mount and reattaching.
• If issue persist, then replace either the HD Display or Mag-Mount.
Automatically clears when the system detects that the issue no longer exists.
701 Moderate Thermostat
The thermostat
is reading
indoor
temperatures
above the pre-
programmed
limit.
• Run reset all under Dealer Control Center.
• Cool thermostat
• Adjust set point.
• Replace HD Display or mag-mount, if needed.
Automatically clears when the system detects that the issue no longer exists.
702 Moderate Thermostat
703 Moderate
S30 Mag-
Mount
Automatically clears when the system detects that the issue no longer exists.
704 Moderate
S30 Mag-
Mount
• Run reset all under Dealer Control Center.
• Replace mag-mount, if needed.
Automatically clears when the system detects that the issue no longer exists.
705 Moderate
S30 Mag-
Mount
• Run reset all under Dealer Control Center.
• Replace mag-mount, if needed.
Automatically clears when the system detects that the issue no longer exists.
900 Moderate S30 System
Temperature
Control Problem
Something is causing the system not to be able to reach set point. Check for dirty coil, low refrig­erant or verify the system is not under size for the application.
Automatically clears when the system detects that the issue no longer exists.
73
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
901 Moderate S30 System
Temperature
Control Problem
This indicates the system is not running in optimized efciency. There may be a component or
component that will require attention. Alert will be a moderate when ON, which will be the default setting. If turned off, this alert will be
a minor.
Automatically clears when the system detects that the issue no longer exists.
65537 Critical Thermostat
Missing Mag-
Mount Base
• Base not detected for more than 30 seconds.
• Amber LED is displayed on Smart Hub.
• Mount and wire Mag-Mount before powering up Smart Hub.
Automatically clears once is detected for two seconds.
65538 Minor Thermostat
Missing Mag-
Mount Base
• Base not detected for less than 30 seconds.
• Amber LED is displayed on Smart Hub.
• Mount and wire Mag-Mount before powering up Smart Hub.
Automatically clears once is detected for two seconds.
65539 Critical Thermostat
Missing HD
Wall Display
• HD Wall Display not detected for more than 30 seconds.
• Solid blue LED will appear on Mag-Mount if powered.
• Blinking blue LED will appear if not communicating with Smart Hub.
Typically the thermostat will send a command to the unknown device and place it in a soft disable state.
The iComfort control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines on seven-segment display.
• On the damper control module, the green LED will blink 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will blink 3 seconds on and 1 second off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear the soft disable state then replace control.
Automatically clears once is detected for two seconds.
65540 Minor Thermostat
Missing HD
Wall Display
• HD Wall Display not detected for less than 30 seconds.
• Solid blue LED will appear on Mag-Mount if powered.
• Blinking blue LED will appear if not communicating with Smart Hub.
Typically the thermostat will send a command to the unknown device and place it in a soft disable state.
The iComfort control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines on seven-segment display.
• On the damper control module, the green LED will blink 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will blink 3 seconds on and 1 second off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear the soft disable state then replace control.
Automatically clears once is detected for two seconds.
74
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
65541 Minor Thermostat Download-failed
Download for rmware failed.
Typically the thermostat will send a command to the unknown device and place it in a soft disable state.
The iComfort control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines on seven-segment display.
• On the damper control module, the green LED will blink 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will blink 3 seconds on and 1 second off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear the soft disable state then replace control.
Not applicable.
65542 Minor Thermostat
Hash
verication
failed
Has verication failed. Update failed.
• Solid blue LED will appear on Mag-Mount if powered.
• Blinking blue LED will appear if not communicating with Smart Hub.
Typically the thermostat will send a command to the unknown device and place it in a soft disable state.
The iComfort control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines on seven-segment display.
• On the damper control module, the green LED will blink 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will blink 3 seconds on and 1 second off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear the soft disable state then replace control.
Not applicable. Automatically clears once is
detected for two seconds.
65543 Info Thermostat
Firmware
updated
When new rmware has been successfully updated to the thermostat.
Typically the thermostat will send a command to the unknown device and place it in a soft disable state.
The iComfort control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines on seven-segment display.
• On the damper control module, the green LED will blink 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will blink 3 seconds on and 1 second off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear the soft disable state then replace control.
Clears automatically after suc­cessfully update.
65544 Critical Thermostat
Too many
siblings
The system is limited to no more than ve (5) Smart Hubs in a local Wi-Fi network.
Once the system detects that
only ve or less Smart Hubs
are detected on the network will the alert code automatically clears.
75
Table 18. Alert Codes and Troubleshooting
Initial notication of critical alerts will pop up on the home screen and will be listed under notication menu. Minor and moderate alerts are found only under the notication menu.
* Current Lennox modulating outdoor units are XC20, XP20, XC25 and XP25.
Alert
Code
Priority
Condition
Applicable
System
Component(s)
Actual
Displayed Alert
Text
Component or System Operational State and Troubleshooting Tip How to clear alert code
65545 Minor S30 System
Cooling
Prognostics
Alert (capacity
alert)
This indicates the system is not running cooling mode in optimized efciency. There may be a
component or components that will require attention.
NOTE: Currently this is a minor alert and will not generate an email notication to the dealer
or homeowner. Parameter settings for this feature are hidden for the software version
3.2 release. The information will be used for data collection only and sent to the Lennox server.
This algorithm will determine whether the unit will run out of capacity during the hottest time of summer. It will look back everyday a minimum of three days to see if there is a pattern and compare it to the hottest day on record for that zip code before triggering an alert. It must see a pattern before it will trigger the alert.
The system will continue to count the number occurrences within a 24 hours period where system demand is not achieved. Will clear once cooling demand is achieved.
Installation Checklist
Smart Hub Checks: YES NO
1
Is the Smart Hub properly mounted to either a wall stud or wall? (Do not mount on equipment or ductwork)
2
Is communication status LED (green) visible? When LED is active it indicates that 24VAC is present at the Smart Hub. It also indicates communication is active between Smart Hub, Mag-Mount and HD Display.
3
Are all terminal wiring properly connected and tight?
4
When required, is either or both the discharge (DATS) and outdoor (OAS) air sensors properly connected and isolated when used?
Mag-Mount Checks: YES NO
1
Are all terminal wiring properly connected and tight?
2
Is the solid blue LED visible when the HD Display is removed? This indicates all wiring is correct. Blinking blue LED indicates the A and B communication wires are reversed.
3
Is the solid blue LED not visible when the HD Display is removed? This usually indicates 12VDC to + and - is not present at the Mag-Mount terminals.
HD Display Checks: YES NO
1
Is the HD Display properly placed and connected to Mag-Mount? When properly connected, the Mag-Mount blue LED will be off.
2
Is the screen blank after initial power-up? The HD Display may take up to three minutes before anything appears on the screen due to a HD Display low battery condition. HD Display battery charging only occurs when connected to the Mag-Mount.
System Checks YES NO
1
Is the Wi-Fi connected?
2
Can the homeowner access the consumer portal (www.myicomfort.com) from either a PC or tablet?
3
Has the homeowner downloaded the Lennox Thermostat application from either Google Play or IOS App Store to their mobile devices?
4
Is the Lennox Dealer account number or your main shop phone number been added to the dealer information screen?
5
If applicable, has the air handler’s electric heat strips been commissioned? If not, commissioning of heat strips must be performed.
6
Has a complete system test been run? If not, from the HD Display home screen go to settings > advance settings > view dealer control center > and select tests.
76
Electrical Troubleshooting
ovErvIEW
The purpose of the service and application note is to address electrical troubleshooting of various connections between iComfort equipment and the applicable expected voltages. Applicable controls are thermostats, Lennox iComfort Equipment Interface Module (EIM) and iHarmony (DCM) and all iComfort Air Handler, Furnaces and Outdoor Units. Use these voltages to:
• Resolve double dashes on in-zone sensors.
• Determine whether the wire is bad or the device is faulty.
• Determine which wire is bad in the bundle.
• Resolve “missing outdoor unit”.
Resolve “can’t nd iComfort indoor unit”.
DEFInItIons
Naked = control has no wires on it at all
Loaded = voltage from c to i- / i+ when all four wires are on
Landed = voltage from c to i- / i+ without r wired on board
Transformer voltage is specic and best with three decimal places. For example 28.316
» Thousandths always bounces and is okay. » Hundredths can bounce but not wide range » Tenths should never bounce
1. If it does almost every time it is a oat switch that is breaking r to the
thermostat
2. Complaint of system waiting
3. History of active alarm codes 105 and 120.
4. Codes not related to equipment
5. Blank screens
6. Wi-Fi will not stay connected.
tEstIng
Table 19. Various Equipment
C to i+ and i­Terminals
Naked Loaded Landed
Gas Furnace (IFC) 2.84 2.615 1.9
Air Handlers - CBX32MV and CBX40UHV (AHC)
2.44 2.5 1.7
Equipment Interface Module
2.44 2.4 1.7
Outdoor Unit with IFC 0 2.615 1.9
Outdoor Unit
with AHC
0 2.45 1.7
Table 20. DCM C to i+ and i- Terminals
DCM C to i+ and i- Terminals
Naked Loaded Landed
DCM with IFC N/A 2.615 1.9
DCM with AHC N/A 2.45 1.7
Table 21. DCM C to D+, D- and PWR Terminals
DCM C to D+, D- and PWR Terminals
Naked Loaded Landed
DCM with IFC
C to d- 2.5 2.497 1.8 C to d+ 2.5 2.497 1.8 C to pwr 12.43 12.43 N/A
NOTE: IFC d-/d+ will be .1vdc lower than i-/i+
Table 22. DCM C to D+, D- and PWR Terminals
DCM C to D+, D- and PWR Terminals
Naked Loaded Landed
DCM with AHC
C to d- 2.4 2.4 1.7 C to d+ 2.4 2.4 1.7
C to pwr 12.43 12.43 N/A
NOTE: IFC d-/d+ will be .1vdc lower than i-/i+
77
78
Index
A
Advanced Dehumidication Descriptions 39
Airow Prole - Cooling 33, 34
Alert Codes and Troubleshooting 49 Apple HomeKit 18 Auto Brightness 36 Auto Changeover
Humidif. Deadband 21 Temp Deadband 21
Auto Dehumidication Overcooling Threshold 21
Automatic Max Defrost 31 Aux Heating Activation Threshold 21
B
Balance Point Control 21 Boot-up Screen 17 Brightness Value 36
C
Commissioning
Using the HD Display 17 Using the Mobile Setup App 15
Compressor Shift Delay ON / OFF 31 Compressor Short Cycle Delay 31, 32
Continuous Indoor Blower Airow 33, 34
Cooling Indoor Blower
Off Delay 33, 34 On Delay 33, 34
Cooling Mode 22 Cooling Prognostics 22
D
Dealer Control Center 20 Defrost Termination Temp 31
Dehumidication
Airow % 34 Airow Adjustment Adder 31, 32
Set Point 39 Setting Options 39
Dew Point Adjustment 22 Diagnostics 38 Dimensions 3 Discharge Air Sensor (DATS) 8
Integral Gain 22 Offset 22 Proportional Gain 22
Display
Air Quality 36 Indoor Humidity 36 Outdoor Weather 36
E
Electrical
Specications 3
Troubleshooting 76
Electric Heat
Airow 33
Control Mode 22 Stages During Defrost 22
Equipment Found Screen 18 Equipment Name
Air Conditioner 32 Air Handler 33 Furnace 34 Heat Pump 31 Smart Hub 22 Zoning Control 36
EvenHeat Discharge Temp 22
F
Factory Reset
Smart Hub 37 Thermostat 37
Fan Cycling 32 Freezing Alert Temperature 28
G
Gas Heat Control Mode (SLP98 only) 23 Gas Heating Activation Temp Difference 23 Group ID 26
H
HD Display 7
External Components 8 Installation 7
Heat / Cool Stages Locked In 23
Heating Airow Control Type 34
Heating Indoor Blower
Off Delay 33, 34 On Delay 33, 34
High
Balance Point 21
Cooling Airow 33, 34 Heating Airow 34 HP Airow 33, 34 Normal Cooling Airow 31, 32 Normal HP Heating Airow 32
HP
Blower On Delay 35 Heating Lockout Time 26 Heating Mode 26 Indoor Blower Off Delay 33, 34 Indoor Blower On Delay 33
Humiditrol Comfort Adjust 26 Humidity Reading Calibration 26
I
iHarmony Zoning 19
79
Information 38 Installation
Checklist 75 Recommendations 3 Report 38
L
Lock In 2nd Stage HP by Outdoor Temp 26 Low
Balance Point 21 Battery Status 17
Cooling Airow 33, 35 Heating Airow 35 HP Airow 33 Normal Cooling Airow 32 Normal HP Heating Airow 32
Low Voltage Wiring 8
M
Mag-Mount 5
Control Wiring Requirements 8 Installation 5 LED 5
Max
Defrost by Weather 32 Heat Setpoint 26
Humidication Setpoint 26
Min
Cool Setpoint 26
Dehumidication Setpoint 26
Modulating
Cooling Cycles Per Hour 26 Cooling Steady State PI Gain 27 Cooling Step Change PI Gain 27 Gas Heating Cycles Per Hour (SLP98V only) 27 Gas Heating Steady State PI Gain (SLP98V
only) 27
Gas Heating Step Change PI Gain (SLP98V
only) 27
HP Heating Cycles Per Hour 27
HP Heating Steady State PI Gain 27 HP Heating Step Change PI Gain 27
N
Number of Gas Heating Stages 27
O
Operating Environment 3 Outdoor Air Sensor 8 Outdoor Temperature
Calibration 27 Reading Calibration 21 Source 36
Overcooling 39
P
Perfect Temp 28 Proximity Control 36 PureAir Wiring Diagram 9
R
Received Signal Strength Indication (RSSI) 47
Re-congure System 37
Reset
Air Conditioner 32 Air Handler 33 Furnace 35 Heat Pump 32 HVAC Equipment 37 Smart Hub 27 Thermostat 36 Zoning Control 36
S
Screen Locked 36 Screen Saver 36 Smart Alert Enable 28 Smart Hub
Control Wiring Requirements 8
Group ID 26 Installation 3 LEDs 5 Multiple Devices 17, 26 Parameters 21 Push Button 4 Restart 17, 37 Terminals 5
Smooth Setback Recovery (SSR) 29 Soft Disable 49 Stage
Delay Timers 29 Differentials 29
T
Temperature Control Mode 29 Temp Reading Calibration 29 Terminal Designations 5 Troubleshooting Wi-Fi Connection 47
W
Wall Insulation 29 Warning Screen 18 Wide Setpoint 36 Wi-Fi 46
Accessory Conguration (WAC) 18
Access Point Hidden 46 Setting Up Connection 46 Signal Strength Indicator 47 Troubleshooting 47 Visible Access Point 46
Wiring Diagrams 10
Z
Zone 1 through 4
Continuous Blower CFM 30 Cooling CFM 30 Heating CFM 30 Temp Reading Calibration 36
80
Zoning
Anticipated Discharge Air Temperature Adjustment 30 Continuous Blower CFM 30 Gas Heating DAT Cool Down Target 30 Minimum Zone Run-Time 30 Supply Air Temp Limit for Cooling 30 Supply Air Temp Limit for Gas / Electric Heating 30 Target Supply Air Temp for Cooling 30 Target Supply Air Temp for HP Heating 30
Zoning Target Supply Air Temp for Gas/Electric Heating 30
Loading...