Lennox HSXA15, HSXA15-030, HSXA15-024, HSXA15-042, HSXA15-036 Installation Instructions Manual

...
INSTALLATION
2001 Lennox Industries Inc.
Dallas, Texas
HSXA15 Outdoor Unit
provided filter drier will void the warranty.
INSTRUCTIONS
HSXA15 SERIES UNITS
CONDENSING UNITS
504,668M 02/04
Supersedes 12/02
Table of Contents
HSXA15 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting The Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Existing Line Set & Indoor Coil 6. . . . . . . . . . .
Manifold Gauge Set 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 13. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 13. . . . . . . . . . . . . .
Retain These Instructions
For Future Reference
Litho U.S.A.
Shipping & Packing List
1 − Assembled HSXA15 outdoor unit 1 − Filter/Drier (approved for use with R410A systems) 1 − Expansion valve (approved for use with R410A) 2 − Grommets (for liquid and suction lines) 1 − Bushing (for low voltage wiring)
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
02/04
*2P0204*
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
504,668M
Page 1
*P504668M*
Unit Dimensions – Inches (mm)
HSXA15
Outdoor Unit
AIRINLET
INLET
COMPRESSOR
AIR
AIRINLET
C
4
(102)
E
2
(51)
B
JJ
H
4-7/8 (22)
G
ELECTRICAL
INLETS
VAPOR LINE
INLET
A
LIQUID
LINE INLET
H
2
(51)
4-1/2 (114)
2-3/4 (70)
D
1-3/8
(35)
2-9/16
(65)
4
(102)
TOP VIEW
DISCHARGE AIR
F
SIDE VIEWACCESS VIEW
Model No. A B C D E F G H J
HSXA15-024
HSXA15-030, HSXA15-036, HSXA15-042
HSXA15-048
HSXA15-060
in. 27-7/8 25-7/8 29-7/8 12-1/4 22-7/16 14-7/16 22-1/8 2-7/8 5-1/2 mm 708 657 759 311 570 367 562 73 140
in. 30-7/8 32-1/8 34-1/16 12-3/4 26-5/8 18-5/8 28-1/8 3-7/8 7-1/2
mm 784 816 865 324 676 473 718 98 191
in. 34−7/8 32-1/8 34-1/16 13-3/4 26-5/8 18-5/8 28-1/8 3-7/8 7-1/2 mm 886 816 865 349 676 473 718 98 191 in. 40-7/8 32-1/8 34-1/16 19-3/4 26-5/8 18-5/8 28-1/8 3-7/8 7-1/2 mm 1038 816 865 502 676 473 718 98 191
6-1/16
(154)
Page 2
Parts Arrangement
CONDENSER FAN
(NOT SHOWN)
TOP OF CABINET
RUN CAPACITOR
GROUND LUG
CONTACTOR
COMPRESSOR POWER
TERMINALS
HIGH PRESSURE
SWITCH
Figure 1
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Sharp sheet metal edges can cause injury. When installing the unit, avoid accidental contact with sharp edges.
Refer to unit dimensions for sizing mounting slab, plat­forms or supports. Refer to figure 2 for installation clear­ances.
VAPOR VALVE
AND GAUGE PORT
LIQUID LINE
SERVICE VALVE
AND GAUGE
COMPRESSOR
LOW PRESSURE
SWITCH
Installation Clearances
NOTE − A service access clearance of 30" (762 mm) must be maintained in front of the service access panel. Clearance to one side must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
36"
(914 mm)
Figure 2
PORT
*36"
(914 mm)
*36"
(914 mm)
36"
(914 mm)
Page 3
A − Slab Mounting
When you install the unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground will not collect around the unit. See figure 3. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m). Refer to the next section (roof mounting) for barrier construction if the unit must face prevailing winter winds.
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m)
slope tolerance away
from building structure
ground level
Slab Mounting
discharge air
building
structure
mounting
slab
Figure 3
B − Roof Mounting
Install unit at a minimum of 4 inches above surface of the roof. Care must be taken to ensure weight of unit is properly distrib­uted over roof joists and rafters. Either redwood or steel sup­ports are recommended.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Unit must be grounded in accordance with national and local codes. ELECTRIC SHOCK HAZARD. Can cause injury or death.
1 − Install line voltage power supply to unit from a properly
sized disconnect switch.
2 − Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us ing a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 4 for field wiring diagram.
NOTE − A complete unit wiring diagram is located in side the unit control box cover.
3 − Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4 − Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit. See figure 5.
Page 4
(LEADLESS)
Outdoor Unit
Field Wiring Diagram
YELLOW
Thermostat Designations
Thermostat Indoor Unit
R
W1
Y
G
C
power
heat
cooling
indoor blower
common
R
W
Y
G
C
Figure 4
NOTE − see unit wiring diagram for
power supply connections.
Outdoor Unit
Y1 Outdoor Unit
C Outdoor Unit
NOTE − If the indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent).
Figure 5
Page 5
Refrigerant Piping
Model
If the HSXA15 unit is being installed with a new indoor coil and line set, the connections should be made as outlined in this section. If an existing line set and/or indoor coil (used with mineral oil) is going to be used to complete the HSXA15 system, refer to the following section which in­cludes flushing procedures.
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 1 or use field-fabri­cated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351−L9) for proper size, type, and application of field−fabricated lines. Valve sizes are also listed in table 1.
Table 1
Refrigerant Line Sets
Model
No.
−024
−030
−036
−042
−048
−060
Valve Field Size
Connections
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in. (29 mm)
(4.6 m − 15 m)
(4.6 m − 15 m)
L15
Line Sets
L15−41
15 ft. − 50 ft.
L15−65
15 ft. − 50 ft.
Field
Fabricated
NOTE − Units are designed for line sets of up to fifty feet (15 m). For applications longer than fifty feet, consult the Lennox Refrig­erant Piping Guide (Corp. 9351−L9). Select line set diameters from table 1 to ensure that oil returns to the compressor.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Closer attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high−efficiency outdoor unit:
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from the adjacent property not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmis­sion.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line set isolation. Figure 6 shows how to install line sets on vertical runs. Figure 7 shows how to install line sets on horizontal runs. Figure 8 shows how to make a transition from horizontal to vertical. Finally, figure 9 shows how to place the outdoor unit and line set.
Page 6
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall.
Outside Wall
Wood Block
Between Studs
Liquid Line
Vapor Line
(wrapped with Armaflex)
Outside Wall
IMPORTANT - Refrigerant
lines must not contact wall.
Liquid LineVapor Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Caulk
PVC Pipe
Fiberglass
Insulation
IMPORTANT - Refrigerant
lines must not contact
structure.
Strap
Sleeve
Figure 6
Page 7
Installing Horizontal Runs
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Floor Joist or
Roof Rafter
Refrigerant Line Sets:
Wire Tie
(around vapor line only)
8 feet
Tape or Wire Tie
8 feet
Strapping Material (around vapor line only)
Tape or Wire Tie
Metal Sleeve
Floor Joist or Roof Rafter
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line.
Figure 7
Page 8
Refrigerant Line Sets:
Transition From Vertical To Horizontal
Anchored Heavy
Nylon Wire Tie
Wall Stud
Metal
Sleeve
Vapor Line
Wrapped in
Armaflex
Strap Liquid Line
To Vapor Line
Liquid Line
Figure 8
Automotive
Muffler-Type
Hanger
Wall Stud
Metal
Sleeve
Strap Liquid Line
To Vapor Line
Liquid Line
Vapor Line
Wrapped in
Armaflex
Outside Unit Placement and Installation
Install unit away from windows.
Two 90° elbows installed in line set will reduce line set vibration.
Figure 9
Page 9
Refrigerant Connections
HSXA15 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced, the liquid line must also be replaced prior to the installation of the HSXA15 unit.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building.
WARNING
Polyol ester (POE) oils used with R410A refrigerant
absorb moisture very quickly. It is very important
that the refrigerant system be kept closed as much
as possible. DO NOT remove line set caps or ser-
vice valve stub caps until you are ready to make
connections.
Flushing Existing Line Set & Indoor Coil
IMPORTANT
If this unit is being matched with an approved line set or indoor coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to instal­lation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with R410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the thermal expansion valve, reduc­ing system performance and capacity. Failure to properly flush the system per the instruc­tions below will void the warranty.
Brazing Connection Procedure
1 − Cut ends of the refrigerant lines square (free from nicks
or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2 − Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the sys­tem.
3 − Use silver alloy brazing rods (5 or 6 percent silver alloy
for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing) which are rated for use with R410A refrigerant. Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to protect them during brazing. Braze the line set to the service valve.
4 − Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during braz­ing. Wrap another wet cloth underneath the valve body to protect the base paint.
NOTE − The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity.
5 − Install the provided thermal expansion valve (ap-
proved for use with R410A refrigerant) in the liquid line at the indoor coil.
6 − Install the provided filter drier (approved for use with
R410A refrigerant) in the liquid line as close as pos­sible to the expansion device. Do not leave the filter
drier uncapped for more than 10 to 15 minutes prior to brazing, evacuation and leak testing. Polyol ester oils used in this system absorb mois­ture quickly. Failure to install the filter drier will void the warranty.
CAUTION
This procedure should not be performed on sys­tems which contain contaminants (Example: com­pressor burn out).
Required Equipment
You will need the following equipment in order to flush the existing line set and indoor coil: two clean HCFC−22 recov­ery bottles, an oilless recovery machine with a pump down feature, and two sets of gauges (one for use with HCFC−22 and one for use with the R410A).
Flushing Procedure
1 − Remove existing HCFC−22 refrigerant using the ap-
propriate procedure below.
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational AND you plan to use the existing HCFC−22 refrig­erant to flush the system – Disconnect all power to
the existing outdoor unit. Connect to the existing unit, a clean recovery cylinder and the recovery machine according to the instructions provided with the recov­ery machine. Remove all HCFC−22 refrigerant from the existing system. Refer to gauges after shutdown to confirm that the entire system is completely void of re­frigerant. Disconnect the liquid and vapor lines from the existing outdoor unit.
If the existing outdoor unit is equipped with manu­al shut−off valves AND you plan to use NEW HCFC−22 refrigerant to flush the system – Start the
existing HCFC−22 system in the cooling mode and close the liquid line valve. Pump all of the existing HCFC−22 refrigerant back into the outdoor unit. (It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.) When the low side system pressures reach 0 psig, close the va-
Page 10
por line valve. Disconnect all power to the existing out­door unit. Refer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and vapor lines from the existing outdoor unit.
2 − Remove the existing outdoor unit. Set the new R410A
unit and follow the brazing connection procedure which begins on the previous page to make line set connections. DO NOT install provided R410A
check/expansion valve at this time.
Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this time.
Flushing Connections
Inverted HCFC−22 Cylinder
(Contains clean HCFC−22 to be
used for flushing)
3 − Remove the existing refrigerant flow control orifice or
thermal expansion valve before continuing with flush­ing procedures. The existing devices are not ap­proved for use with R410A refrigerant and may pre­vent proper flushing. Use a field−provided fitting to re­connect the lines.
IMPORTANT
The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that pre­viously charged the system. Check the charge in the flushing cylinder before proceeding.
Existing
Indoor Coil
RECOVERY
CYLINDER
EXISTING VAPOR LINE
EXISTING LIQUID LINE
VAPOR LINE
SERVICE VALVE
LIQUID LINE
SERVICE VALVE
TANK RETURN
INLET
DISCHARGE
RECOVERY MACHINE
Figure 10
HSXA15 UNIT
NOTE − The inverted HCFC−22 cylinder must contain at least the same amount of refrigerant as was recovered from the ex­isting system.
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
HIGH
CLOSEDOPENED
Page 11
4 − Remove the pressure tap valve cores from the
HSXA15 unit’s service valves. Connect an HCFC−22 cylinder with clean refrigerant to the vapor service valve. Connect the HCFC−22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set.
5 − Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex­isting system line set and indoor coil.
If you install a expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the expansion valve is installed.
Metering Device Installation
distributor
o−ring
expansion
valve
6 − Invert the cylinder of clean HCFC−22 and open its
valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
7 − After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the re­covery machine to pull a vacuum on the system.
NOTE − A single system flush should remove all of the mineral oil from the existing refrigerant lines and in­door coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system
is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure.
8 − Close the valve on the inverted HCFC−22 drum and
the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
9 − Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery ma­chine, gauges and HCFC−22 refrigerant drum. Rein­stall pressure tap valve cores into HSXA15 service valves.
10 −Install the provided expansion valve (approved for use
with R410A refrigerant) in the liquid line at the indoor coil.
Refrigerant Metering Devices
Use HSXA15 units in TXV systems systems. See the Len- nox Engineering Handbook for approved TXV match-ups and application information.
o−ring
strainer
liquid line
stub
Figure 11
Manifold Gauge Set
Manifold gauge sets used with systems charged with R410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
Service Valves
The liquid line and vapor line service valves (figure 12) and gauge ports are used for leak testing, evacuating, charging and checking charge. See table 2 for torque requirements
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
Table 2
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 N M
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 N M
Expansion Valve Systems
Expansion valves equipped with either Chatleff or flare type fittings are available from Lennox. Refer to the Engi­neering Handbook for expansion valves for use with specif­ic match−ups. See figure 11 for installation of the expansion valve.
To Access Schrader Port:
1 − Remove access panel. 2 − Remove service port cap with an adjustable wrench. 3 − Connect gauge to the service port. 4 − When testing is complete, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
Page 12
To Open Service Valve:
1 − Remove stem cap with an adjustable wrench. 2 − Use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as pos­sible.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
WARNING
Refrigerant can be harmful if it is inhaled. Refriger­ant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Service Valve
(Valve Closed)
service
port
to outdoor coil
service
port cap
Schrader valve open
to line set when valve is
closed (front seated)
wrench here
(valve front seated)
stem cap
insert hex
to indoor coil
Service Valve
insert hex
wrench here
to outdoor coil
service port
cap
(Valve Open)
service
port
Schrader
valve
stem cap
to indoor coil
Figure 12
To Close Service Valve:
1 − Remove the stem cap with an adjustable wrench. 2 − Use a service wrench with a hex−head extension to
turn the stem clockwise to seat the valve. Tighten it firmly.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Leak Testing
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks.
Danger of explosion: Can cause equipment damage, injury or death. Never use oxygen to pressurize a re­frigeration or air conditioning system. Oxygen will explode on contact with oil and could cause personal injury.
WARNING
Danger of explosion: Can cause equipment damage, injury or death. When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Using an Electronic Leak Detector
1 − Connect the high pressure hose of the manifold gauge
set to the vapor valve service port. (Normally, the high
pressure hose is connected to the liquid line port, how­ever, connecting it to the vapor port helps to protect the manifold gauge set from damage caused by high pres­sure.)
2 − With both manifold valves closed, connect the cylinder
of R410A refrigerant to the center port of the manifold gauge set. Open the valve on the R410A cylinder (va­por only).
3 − Open the high pressure side of the manifold to allow
R410A into the line set and indoor unit. Weigh in a trace amount of R410A. [A trace amount is a maximum of 2
ounces (57 g) refrigerant or 3 pounds (31 kPa) pres­sure.] Close the valve on the R410A cylinder and the
valve on the high pressure side of the manifold gauge set. Disconnect R410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Adjust nitrogen pressure to 150 psig (1034 kPa). Open
the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor coil.
6 − After a few minutes, open a refrigerant port to check
that an adequate amount of refrigerant has been add­ed for detection (refrigerant requirements will vary with line lengths). Check all joints for leaks. Purge ni­trogen and R410A mixture. Correct any leaks and re­check.
Page 13
IMPORTANT
Leak detector must be capable of sensing HFC re-
frigerant.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.
1 − Connect manifold gauge set to the service valve ports :
low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin­der with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use com­pressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of R410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R410A cylinder and remove the manifold gauge set.
Start−Up
1 − Rotate fan to check for frozen bearings or binding.
2 − Inspect all factory− and field−installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4 − Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6 − Set the thermostat for a cooling demand. Turn on pow-
er to the indoor blower and close the outdoor unit dis­connect switch to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Page 14
Charging
This system is charged with R410A refrigerant which oper­ates at much higher pressures than HCFC−22. The expan­sion valve and liquid line filter drier provided with the unit are approved for use with R410A. Do not replace them with components designed for use with HCFC−22. This unit is NOT approved for use with coils which include metering orifices or capillary tubes.
Processing Procedure
Units are factory charged with the amount of R410A refrig­erant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15 feet (4.6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment.
Table 3
Liquid Line Set
Diameter
5/16 in
(8 mm)
3/8 in.
(10 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Oz. per 5 ft. (grams per 1.5m) adjust
from 15 ft. (4.6 m) line set*
2 ounces per 5 feet
(57 g per 1.5 m)
3 ounces per 5 feet
(85 g per 1.5 m)
IMPORTANT
Mineral oils are not compatible with R410A. If oil must be added, it must be a polyol ester oil.
The compressor is charged with sufficient polyol ester oil for line set lengths up to 50 feet (15.2 m). If oil must be added in the field, Copeland has approved Mobil EALt Arctic 22CC and ICI EMKARATEt RL32CF for use with these compressors.
If the system is void of refrigerant, clean the system us­ing the procedure described below.
1 − Use nitrogen to pressurize the system and check for
leaks. Repair leaks, if possible.
2 − Evacuate the system to remove as much of the mois-
ture as possible.
3 − Use nitrogen to break the vacuum and install the pro-
vided filter drier in the system.
4 − Evacuate the system again. Then, weigh the appropri-
ate amount of R410A refrigerant (listed on unit name­plate) into the system.
5 − Monitor the system to determine the amount of mois-
ture remaining in the oil. Use test kit 10N46 to verify that the moisture content is within the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If
system dryness is not verified, the compressor will fail in the future.
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1 − Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service port high pressure gauge to liquid valve service port
Connect the center manifold hose to an upright cylin­der of HCFC-22. Close manifold gauge set valves.
2 − Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in the cooling cycle.
3 − Use a digital thermometer to record the outdoor ambi-
ent temperature.
4 − When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68F (20C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
5 − The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate charg­ing procedure.
Weighing in the Charge Fixed Orifice or
TXV Systems – Outdoor Temp < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been re­paired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other proce­dures outlined below.
Charging Using Normal Operating Pressures
and the Approach Method
TXV Systems – Outdoor Temp. >
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 5, Normal Operating Pressures." Minor varia­tions in these pressures may be expected due to differ­ences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those
65F (18C)
Page 15
listed indicate that the system is undercharged. Verify
Mod
Entering Air
pressures with the R410A refrigerant pressure chart in table 6. Verify adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid line temperature.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 4. If the val­ues don’t agree with the those in table 4, add refriger­ant to lower the approach temperature, or recover re­frigerant from the system to increase the approach temperature.
Normal Operating Pressure
(Liquid ±10 and Vapor ±5 psig)
TXV
Outdoor Coil
e
Temp. °F (°C)
Entering Air
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
HSXA15−024 HSXA15−030 HSXA15−036 HSXA15−042 HSXA15−048 HSXA15−060
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
239 129 232 130 235 128 241 131 226 130 240 130
278 131 271 132 276 130 282 133 266 132 279 132
321 133 314 135 320 132 326 135 310 135 321 135
368 135 360 137 367 134 373 137 356 137 368 137
420 138 412 140 421 137 424 139 407 139 418 140
Table 4
Model Number
HSXA15−024 8 ± 1 (4.5 ± .5) HSXA15−030 8 ± 1 (4.5 ± .5)
HSXA15−036 6 ± 1 (3.3 ± .5)
HSXA15−042 9 ± 1 (5 ± .5)
HSXA15−048 8 ± 1 (4.5 ± .5)
HSXA15−060 12 ± 1 (6.7 ± .5)
Liquid Line Temp. − Outdoor Ambient °F (°C)
NOTE − For best results, the same electronic thermometer should be used to check both outdoor ambient and liquid line temperatures.
Approach Temperature
Table 5
s
Page 16
Table 6
R410A Temperature/Pressure Chart
Temperature°FPressure
Psig
32 100.8 63 178.5 94 290.8 125 445.9
33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 11 0 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 11 2 375.1 143 559.1
51 144.8 82 242.7 11 3 380.2 144 565.9
52 147.4 83 246.5 11 4 385.4 145 572.8
53 150.1 84 250.3 11 5 390.7 146 579.8
54 152.8 85 254.1 11 6 396.0 147 586.8
55 155.5 86 258.0 11 7 401.3 148 593.8
56 158.2 87 262.0 11 8 406.7 149 601.0
57 161.0 88 266.0 11 9 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 195.5 93 286.5 124 440.2 155 645.0
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Temperature°FPressure
Psig
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
High Pressure Switch
HSXA15 units are equipped with a high pressure switch that is located in the liquid line of the compressor. The switch (SPST, manual reset, normally closed) removes power from the compressor when discharge pressure rises above factory setting at 640 + 10 psi.
Low Pressure Switch
HSXA15 units are also equipped with a low pressure switch that is located in the vapor line of the compressor. The switch (SPST, auto−reset, normally closed) removes power from the compressor when vapor line pressure drops be­low factory setting at 40 + 5 psi.
Page 17
Filter Drier
A filter drier is shipped with each HSXA15 unit. The filter dri­er must be field installed in the liquid line between the liquid line service valve and the expansion valve. This filter drier
must be installed to ensure a clean, moisture−free sys­tem. A replacement filter drier is available as Lennox part
no. 37L5201.
Maintenance
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
1 − Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned off before you clean the coil.
2 − Condenser fan motor is prelubricated and sealed. No
further lubrication is needed.
3 − Visually inspect connecting lines and coils for evidence
of oil leaks.
4 − Check wiring for loose connections.
5 − Check for correct voltage at unit (unit operating).
6 − Check amp−draw condenser fan motor.
Unit nameplate _________ Actual ____________ .
NOTE − If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil, if necessary.
2 − Check connecting lines and coils for evidence of oil
leaks.
3 − Check condensate line and clean, if necessary.
Indoor Unit
1 − Clean or change filters.
2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3 − Belt Drive Blowers − Check belt for wear and proper
tension.
4 − Check all wiring for loose connections
5 − Check for correct voltage at unit (blower operating).
6 − Check amp−draw on blower motor
Unit nameplate_________ Actual ____________.
Optional Accessories
Refer to the Engineering Handbook for optional accesso­ries that may apply to this unit. The following may or may not apply:
Loss of Charge Kit High Pressure Switch Kit Compressor Monitor Compressor Crankcase Heater Hail Guards Mounting Bases Timed Off Control Stand−off Kit Sound Cover Low Ambient Kit
Start−Up & Performance Check List
Job Name
Job Location Installer
Unit Model No. Nameplate Voltage
Rated Load Ampacity Maximum Fuse or Circuit Breaker Electrical Connections Tight?
Indoor Blower RPM Discharge Pressure Refrigerant Lines:
Service Valves Fully Opened?
Voltage With Compressor Operating
Leak Checked?
S.P. Drop Over Indoor (Dry)
Vapor Pressure
Start−up and Performance Check List
Job No.
City
City
Serial No.
Compressor
Indoor Filter Clean?
Properly Insulated?
Service Valve Caps Tight?
Calibrated? Properly Set?
Page 18
Outdoor Fan
Outdoor Coil Entering Air Temp.
Refrigerant Charge Checked?
Date
State
State
Service Technician
Supply Voltage (Unit Off)
Outdoor Fan Checked?
Thermostat
Level?
Loading...