HSXA15 outdoor units use R410A which is an ozone friendly HFC refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the Lennox Engineering Handbook. HSXA15 outdoor units are designed for
use in expansion valve systems only. They are not designed
to be used with other refrigerant flow control devices. An expansion valve and filter drier approved for use with R410A
have been shipped with the unit. These components must
be installed prior to unit operation. Failure to install the
1 − Assembled HSXA15 outdoor unit
1 − Filter/Drier (approved for use with R410A systems)
1 − Expansion valve (approved for use with R410A)
2 − Grommets (for liquid and suction lines)
1 − Bushing (for low voltage wiring)
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.
IMPORTANT
This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook. Coils
previously charged with HCFC−22 must be flushed.
02/04
*2P0204*
General Information
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
WARNING
This product and/or the indoor unit it is matched with
may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to
cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
In order to avoid injury, take proper precaution when
lifting heavy objects.
CAUTION
Sharp sheet metal edges can cause injury. When
installing the unit, avoid accidental contact with
sharp edges.
Refer to unit dimensions for sizing mounting slab, platforms or supports. Refer to figure 2 for installation clearances.
VAPOR VALVE
AND GAUGE PORT
LIQUID LINE
SERVICE VALVE
AND GAUGE
COMPRESSOR
LOW PRESSURE
SWITCH
Installation Clearances
NOTE − A service access
clearance of 30" (762 mm)
must be maintained in front
of the service access panel.
Clearance to one side must
be 36" (914 mm). Clearance
to one of the remaining two
sides may be 12" (304 mm)
and the final side may be 6"
(152 mm).
NOTE − A clearance of 24" (610 mm)
must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top
of unit. Maximum soffit overhang is 36" (914 mm).
36"
(914 mm)
Figure 2
PORT
*36"
(914 mm)
*36"
(914 mm)
36"
(914 mm)
Page 3
A − Slab Mounting
When you install the unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground will not collect around the unit. See figure 3.
Slab should have a slope tolerance away from the building
of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m). Refer
to the next section (roof mounting) for barrier construction if
the unit must face prevailing winter winds.
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m)
slope tolerance away
from building structure
ground level
Slab Mounting
discharge air
building
structure
mounting
slab
Figure 3
B − Roof Mounting
Install unit at a minimum of 4 inches above surface of the roof.
Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
WARNING
Unit must be grounded in accordance with national
and local codes.
ELECTRIC SHOCK HAZARD.
Can cause injury or death.
1 − Install line voltage power supply to unit from a properly
sized disconnect switch.
2 − Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box us
ing a proper conduit fitting.
NOTE − Units are approved for use only with copper
conductors.
24V, Class II circuit connections are made in the low
voltage junction box. Refer to figure 4 for field wiring
diagram.
NOTE − A complete unit wiring diagram is located in
side the unit control box cover.
3 − Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.
4 − Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit. See figure 5.
Page 4
(LEADLESS)
Outdoor Unit
Field Wiring Diagram
YELLOW
Thermostat Designations
ThermostatIndoor Unit
R
W1
Y
G
C
power
heat
cooling
indoor blower
common
R
W
Y
G
C
Figure 4
NOTE − see unit wiring diagram for
power supply connections.
Outdoor Unit
Y1 Outdoor Unit
C Outdoor Unit
NOTE − If the indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent).
Figure 5
Page 5
Refrigerant Piping
Model
If the HSXA15 unit is being installed with a new indoor coil
and line set, the connections should be made as outlined in
this section. If an existing line set and/or indoor coil (used
with mineral oil) is going to be used to complete the
HSXA15 system, refer to the following section which includes flushing procedures.
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, nonflare) series line sets as shown in table 1 or use field-fabricated refrigerant lines. Refer to Refrigerant Piping Guide
(Corp. 9351−L9) for proper size, type, and application of
field−fabricated lines. Valve sizes are also listed in table 1.
Table 1
Refrigerant Line Sets
Model
No.
−024
−030
−036
−042
−048
−060
Valve Field Size
Connections
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in.
(29 mm)
Recommended Line Set
Liquid
Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Vapor
Line
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in.
(29 mm)
(4.6 m − 15 m)
(4.6 m − 15 m)
L15
Line Sets
L15−41
15 ft. − 50 ft.
L15−65
15 ft. − 50 ft.
Field
Fabricated
NOTE − Units are designed for line sets of up to fifty feet (15 m).
For applications longer than fifty feet, consult the Lennox Refrigerant Piping Guide (Corp. 9351−L9). Select line set diameters
from table 1 to ensure that oil returns to the compressor.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is
important to properly isolate the refrigerant lines to prevent
unnecessary vibration. Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound. As a result, more
energy or vibration can be expected. Closer attention to
line set isolation must be observed.
Following are some points to consider when placing and
installing a high−efficiency outdoor unit:
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmission.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line
set isolation. Figure 6 shows how to install line sets on
vertical runs. Figure 7 shows how to install line sets on
horizontal runs. Figure 8 shows how to make a transition
from horizontal to vertical. Finally, figure 9 shows how to
place the outdoor unit and line set.
Page 6
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE - Similar installation practices should be used if
line set is to be installed on exterior of outside wall.
Outside Wall
Wood Block
Between Studs
Liquid Line
Vapor Line
(wrapped with Armaflex)
Outside Wall
IMPORTANT - Refrigerant
lines must not contact wall.
Liquid LineVapor Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Caulk
PVC Pipe
Fiberglass
Insulation
IMPORTANT - Refrigerant
lines must not contact
structure.
Strap
Sleeve
Figure 6
Page 7
Installing Horizontal Runs
To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.
Floor Joist or
Roof Rafter
Refrigerant Line Sets:
Wire Tie
(around vapor line only)
8 feet
Tape or Wire Tie
8 feet
Strapping Material (around vapor line only)
Tape or Wire Tie
Metal Sleeve
Floor Joist or Roof Rafter
Strap the vapor line to the joist or rafter at 8 ft.
intervals then strap the liquid line to the vapor line.
Figure 7
Page 8
Refrigerant Line Sets:
Transition From Vertical To Horizontal
Anchored Heavy
Nylon Wire Tie
Wall
Stud
Metal
Sleeve
Vapor Line
Wrapped in
Armaflex
Strap Liquid Line
To Vapor Line
Liquid Line
Figure 8
Automotive
Muffler-Type
Hanger
Wall
Stud
Metal
Sleeve
Strap Liquid Line
To Vapor Line
Liquid Line
Vapor Line
Wrapped in
Armaflex
Outside Unit Placement and Installation
Install unit away from windows.
Two 90° elbows
installed in line set
will reduce line set
vibration.
Figure 9
Page 9
Refrigerant Connections
HSXA15 Matched with New Indoor Coil and Line Set
If an existing indoor coil that was equipped with an
RFCI metering device is being replaced, the liquid line
must also be replaced prior to the installation of the
HSXA15 unit.
If refrigerant lines are routed through a wall, seal and isolate
the opening so vibration is not transmitted to the building.
WARNING
Polyol ester (POE) oils used with R410A refrigerant
absorb moisture very quickly. It is very important
that the refrigerant system be kept closed as much
as possible. DO NOT remove line set caps or ser-
vice valve stub caps until you are ready to make
connections.
Flushing Existing Line Set & Indoor Coil
IMPORTANT
If this unit is being matched with an approved line
set or indoor coil which was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol
ester (POE) oils are used in Lennox units charged
with R410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the thermal expansion valve, reducing system performance and capacity.
Failure to properly flush the system per the instructions below will void the warranty.
Brazing Connection Procedure
1 − Cut ends of the refrigerant lines square (free from nicks
or dents). Debur the ends. The pipe must remain
round, do not pinch end of the line.
2 − Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the system.
3 − Use silver alloy brazing rods (5 or 6 percent silver alloy
for copper−to−copper brazing or 45 percent silver alloy
for copper−to−brass or copper−to−steel brazing) which
are rated for use with R410A refrigerant. Wrap a wet
cloth around the valve body and the copper tube stub.
Remove light maroon washers from service valves and
shield light maroon stickers in order to protect them
during brazing. Braze the line set to the service valve.
4 − Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during brazing. Wrap another wet cloth underneath the valve body
to protect the base paint.
NOTE − The tube end must stay bottomed in the fitting
during final assembly to ensure proper seating, sealing
and rigidity.
5 − Install the provided thermal expansion valve (ap-
proved for use with R410A refrigerant) in the liquid line
at the indoor coil.
6 − Install the provided filter drier (approved for use with
R410A refrigerant) in the liquid line as close as possible to the expansion device. Do not leave the filter
drier uncapped for more than 10 to 15 minutes
prior to brazing, evacuation and leak testing.
Polyol ester oils used in this system absorb moisture quickly. Failure to install the filter drier will
void the warranty.
CAUTION
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
Required Equipment
You will need the following equipment in order to flush the
existing line set and indoor coil: two clean HCFC−22 recovery bottles, an oilless recovery machine with a pump down
feature, and two sets of gauges (one for use with HCFC−22
and one for use with the R410A).
Flushing Procedure
1 − Remove existing HCFC−22 refrigerant using the ap-
propriate procedure below.
If the existing outdoor unit is not equipped with
shut−off valves, or if the unit is not operational
AND you plan to use the existing HCFC−22 refrigerant to flush the system – Disconnect all power to
the existing outdoor unit. Connect to the existing unit,
a clean recovery cylinder and the recovery machine
according to the instructions provided with the recovery machine. Remove all HCFC−22 refrigerant from
the existing system. Refer to gauges after shutdown to
confirm that the entire system is completely void of refrigerant. Disconnect the liquid and vapor lines from
the existing outdoor unit.
If the existing outdoor unit is equipped with manual shut−off valves AND you plan to use NEW
HCFC−22 refrigerant to flush the system – Start the
existing HCFC−22 system in the cooling mode and
close the liquid line valve. Pump all of the existing
HCFC−22 refrigerant back into the outdoor unit. (It may
be necessary to bypass the low pressure switches to
ensure complete refrigerant evacuation.) When the
low side system pressures reach 0 psig, close the va-
Page 10
por line valve. Disconnect all power to the existing outdoor unit. Refer to gauges after shutdown to confirm
that the valves are not allowing refrigerant to flow back
into the low side of the system. Disconnect the liquid
and vapor lines from the existing outdoor unit.
2 − Remove the existing outdoor unit. Set the new R410A
unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. DO NOT install provided R410A
check/expansion valve at this time.
Make low voltage and line voltage connections to the
new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this time.
Flushing Connections
Inverted HCFC−22 Cylinder
(Contains clean HCFC−22 to be
used for flushing)
3 − Remove the existing refrigerant flow control orifice or
thermal expansion valve before continuing with flushing procedures. The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing. Use a field−provided fitting to reconnect the lines.
IMPORTANT
The line set and indoor coil must be flushed with at
least the same amount of clean refrigerant that previously charged the system. Check the charge in
the flushing cylinder before proceeding.
Existing
Indoor Coil
RECOVERY
CYLINDER
EXISTING VAPOR LINE
EXISTING LIQUID LINE
VAPOR LINE
SERVICE VALVE
LIQUID LINE
SERVICE VALVE
TANK RETURN
INLET
DISCHARGE
RECOVERY MACHINE
Figure 10
HSXA15 UNIT
NOTE − The inverted HCFC−22
cylinder must contain at least
the same amount of refrigerant
as was recovered from the existing system.
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
HIGH
CLOSEDOPENED
Page 11
4 − Remove the pressure tap valve cores from the
HSXA15 unit’s service valves. Connect an HCFC−22
cylinder with clean refrigerant to the vapor service
valve. Connect the HCFC−22 gauge set to the liquid
line valve and connect a recovery machine with an
empty recovery tank to the gauge set.
5 − Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the existing system line set and indoor coil.
If you install a expansion valve with an indoor coil that
includes a fixed orifice, remove the orifice before the
expansion valve is installed.
Metering Device Installation
distributor
o−ring
expansion
valve
6 − Invert the cylinder of clean HCFC−22 and open its
valve to allow liquid refrigerant to flow into the system
through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the
indoor coil before it enters the recovery machine.
7 − After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that
all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull a vacuum on the system.
NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush. Each time the system
is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.
8 − Close the valve on the inverted HCFC−22 drum and
the gauge set valves. Pump the remaining refrigerant
out of the recovery machine and turn the machine off.
9 − Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery machine, gauges and HCFC−22 refrigerant drum. Reinstall pressure tap valve cores into HSXA15 service
valves.
10 −Install the provided expansion valve (approved for use
with R410A refrigerant) in the liquid line at the indoor
coil.
Refrigerant Metering Devices
Use HSXA15 units in TXV systems systems. See the Len-
nox Engineering Handbook for approved TXV match-ups
and application information.
o−ring
strainer
liquid line
stub
Figure 11
Manifold Gauge Set
Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures. The gauges should be rated
for use with pressures of 0 − 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to 500
psi. Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating.
Service Valves
The liquid line and vapor line service valves (figure 12) and
gauge ports are used for leak testing, evacuating, charging
and checking charge. See table 2 for torque requirements
Each valve is equipped with a service port which has a factory−installed Schrader valve. A service port cap protects
the Schrader valve from contamination and serves as the
primary leak seal.
Table 2
Torque Requirements
PartRecommended Torque
Service valve cap8 ft.− lb.11 N M
Sheet metal screws16 in.− lb.2 NM
Machine screws #1028 in.− lb.3 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 N M
Expansion Valve Systems
Expansion valves equipped with either Chatleff or flare
type fittings are available from Lennox. Refer to the Engineering Handbook for expansion valves for use with specific match−ups. See figure 11 for installation of the expansion
valve.
To Access Schrader Port:
1 − Remove access panel.
2 − Remove service port cap with an adjustable wrench.
3 − Connect gauge to the service port.
4 − When testing is complete, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
Page 12
To Open Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as possible.
NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
WARNING
Service Valve
(Valve Closed)
service
port
to outdoor coil
service
port cap
Schrader valve open
to line set when valve is
closed (front seated)
wrench here
(valve front seated)
stem cap
insert hex
to indoor coil
Service Valve
insert hex
wrench here
to outdoor coil
service port
cap
(Valve Open)
service
port
Schrader
valve
stem cap
to indoor coil
Figure 12
To Close Service Valve:
1 − Remove the stem cap with an adjustable wrench.
2 − Use a service wrench with a hex−head extension to
turn the stem clockwise to seat the valve. Tighten it
firmly.
NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Leak Testing
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks.
Danger of explosion: Can cause
equipment damage, injury or death.
Never use oxygen to pressurize a refrigeration or air conditioning system.
Oxygen will explode on contact with
oil and could cause personal injury.
WARNING
Danger of explosion: Can cause equipment damage,
injury or death. When using a high pressure gas
such as dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).
Using an Electronic Leak Detector
1 − Connect the high pressure hose of the manifold gauge
set to the vapor valve service port. (Normally, the high
pressure hose is connected to the liquid line port, however, connecting it to the vapor port helps to protect the
manifold gauge set from damage caused by high pressure.)
2 − With both manifold valves closed, connect the cylinder
of R410A refrigerant to the center port of the manifold
gauge set. Open the valve on the R410A cylinder (vapor only).
3 − Open the high pressure side of the manifold to allow
R410A into the line set and indoor unit. Weigh in a trace
amount of R410A. [A trace amount is a maximum of 2
ounces (57 g) refrigerant or 3 pounds (31 kPa) pressure.] Close the valve on the R410A cylinder and the
valve on the high pressure side of the manifold gauge
set. Disconnect R410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Adjust nitrogen pressure to 150 psig (1034 kPa). Open
the valve on the high side of the manifold gauge set in
order to pressurize the line set and the indoor coil.
6 − After a few minutes, open a refrigerant port to check
that an adequate amount of refrigerant has been added for detection (refrigerant requirements will vary
with line lengths). Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck.
Page 13
IMPORTANT
Leak detector must be capable of sensing HFC re-
frigerant.
Evacuation
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper piping and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.
1 − Connect manifold gauge set to the service valve ports :
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to
determine if there is a rapid rise in absolute pressure.
A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.
WARNING
Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compressors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will
void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.
Start−Up
1 − Rotate fan to check for frozen bearings or binding.
2 − Inspect all factory− and field−installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.
4 − Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.
6 − Set the thermostat for a cooling demand. Turn on pow-
er to the indoor blower and close the outdoor unit disconnect switch to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Page 14
Charging
This system is charged with R410A refrigerant which operates at much higher pressures than HCFC−22. The expansion valve and liquid line filter drier provided with the unit
are approved for use with R410A. Do not replace them with
components designed for use with HCFC−22. This unit is
NOT approved for use with coils which include metering
orifices or capillary tubes.
Processing Procedure
Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 15
feet (4.6 m) line set. For varying lengths of line set, refer to
table 3 for refrigerant charge adjustment.
Table 3
Liquid Line Set
Diameter
5/16 in
(8 mm)
3/8 in.
(10 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount.
If line length is less than 15 ft. (4.6 m), subtract this amount.
Oz. per 5 ft. (grams per 1.5m) adjust
from 15 ft. (4.6 m) line set*
2 ounces per 5 feet
(57 g per 1.5 m)
3 ounces per 5 feet
(85 g per 1.5 m)
IMPORTANT
Mineral oils are not compatible with R410A. If oil
must be added, it must be a polyol ester oil.
The compressor is charged with sufficient polyol ester
oil for line set lengths up to 50 feet (15.2 m). If oil must
be added in the field, Copeland has approved Mobil
EALt Arctic 22CC and ICI EMKARATEt RL32CF for
use with these compressors.
If the system is void of refrigerant, clean the system using the procedure described below.
1 − Use nitrogen to pressurize the system and check for
leaks. Repair leaks, if possible.
2 − Evacuate the system to remove as much of the mois-
ture as possible.
3 − Use nitrogen to break the vacuum and install the pro-
vided filter drier in the system.
4 − Evacuate the system again. Then, weigh the appropri-
ate amount of R410A refrigerant (listed on unit nameplate) into the system.
5 − Monitor the system to determine the amount of mois-
ture remaining in the oil. Use test kit 10N46 to verify
that the moisture content is within the kit’s dry color
range. It may be necessary to replace the filter drier
several times to achieve the required dryness level. If
system dryness is not verified, the compressor will
fail in the future.
The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the
outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
1 − Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service port
high pressure gauge to liquid valve service port
Connect the center manifold hose to an upright cylinder of HCFC-22. Close manifold gauge set valves.
2 − Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in
the cooling cycle.
3 − Use a digital thermometer to record the outdoor ambi-
ent temperature.
4 − When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68F
(20C). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature.
5 − The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate charging procedure.
Weighing in the Charge Fixed Orifice or
TXV Systems – Outdoor Temp < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit. Do this after any leaks have been repaired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other procedures outlined below.
Charging Using Normal Operating Pressures
and the Approach Method
TXV Systems – Outdoor Temp. >
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 5, Normal Operating Pressures." Minor variations in these pressures may be expected due to differences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
65F (18C)
Page 15
listed indicate that the system is undercharged. Verify
Mod
Entering Air
pressures with the R410A refrigerant pressure chart in
table 6. Verify adjusted charge using the approach
method.
Approach Method
4 − Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid
line temperature.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 4. If the values don’t agree with the those in table 4, add refrigerant to lower the approach temperature, or recover refrigerant from the system to increase the approach
temperature.
NOTE − For best results, the same electronic thermometer
should be used to check both outdoor ambient and liquid line
temperatures.
Approach Temperature
Table 5
s
Page 16
Table 6
R410A Temperature/Pressure Chart
Temperature°FPressure
Psig
32100.863178.594290.8125445.9
33102.964181.695295.1126451.8
34105.065184.396299.4127457.6
35107.166187.797303.8128463.5
36109.267190.998308.2129469.5
37111.468194.199312.7130475.6
38113.669197.3100317.2131481.6
39115.870200.6101321.8132487.8
40118.071203.9102326.4133494.0
41120.372207.2103331.0134500.2
42122.673210.6104335.7135506.5
43125.074214.0105340.5136512.9
44127.375217.4106345.3137519.3
45129.776220.9107350.1138525.8
46132.277224.4108355.0139532.4
47134.678228.0109360.0140539.0
48137.179231.611 0365.0141545.6
49139.680235.3111370.0142552.3
50142.281239.011 2375.1143559.1
51144.882242.711 3380.2144565.9
52147.483246.511 4385.4145572.8
53150.184250.311 5390.7146579.8
54152.885254.111 6396.0147586.8
55155.586258.011 7401.3148593.8
56158.287262.011 8406.7149601.0
57161.088266.011 9412.2150608.1
58163.989270.0120417.7151615.4
59166.790274.1121423.2152622.7
60169.691278.2122428.8153630.1
61172.692282.3123434.5154637.5
62195.593286.5124440.2155645.0
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Temperature°FPressure
Psig
System Operation
The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch is
in the ON position, the indoor blower operates continuously.
High Pressure Switch
HSXA15 units are equipped with a high pressure switch
that is located in the liquid line of the compressor. The
switch (SPST, manual reset, normally closed) removes
power from the compressor when discharge pressure rises
above factory setting at 640 + 10 psi.
Low Pressure Switch
HSXA15 units are also equipped with a low pressure switch
that is located in the vapor line of the compressor. The
switch (SPST, auto−reset, normally closed) removes power
from the compressor when vapor line pressure drops below factory setting at 40 + 5 psi.
Page 17
Filter Drier
A filter drier is shipped with each HSXA15 unit. The filter drier must be field installed in the liquid line between the liquid
line service valve and the expansion valve. This filter drier
must be installed to ensure a clean, moisture−free system. A replacement filter drier is available as Lennox part
no. 37L5201.
Maintenance
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn
the electrical power to unit OFF at disconnect switch(es). Unit may have
multiple power supplies.
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:
1 − Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned
off before you clean the coil.
2 − Condenser fan motor is prelubricated and sealed. No
further lubrication is needed.
3 − Visually inspect connecting lines and coils for evidence
of oil leaks.
4 − Check wiring for loose connections.
5 − Check for correct voltage at unit (unit operating).
6 − Check amp−draw condenser fan motor.
Unit nameplate _________ Actual ____________ .
NOTE − If owner complains of insufficient cooling, the
unit should be gauged and refrigerant charge
checked. Refer to section on refrigerant charging in
this instruction.
Indoor Coil
1 − Clean coil, if necessary.
2 − Check connecting lines and coils for evidence of oil
leaks.
3 − Check condensate line and clean, if necessary.
Indoor Unit
1 − Clean or change filters.
2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
3 − Belt Drive Blowers − Check belt for wear and proper
tension.
4 − Check all wiring for loose connections
5 − Check for correct voltage at unit (blower operating).
6 − Check amp−draw on blower motor
Unit nameplate_________ Actual ____________.
Optional Accessories
Refer to the Engineering Handbook for optional accessories that may apply to this unit. The following may or may
not apply:
Loss of Charge Kit
High Pressure Switch Kit
Compressor Monitor
Compressor Crankcase Heater
Hail Guards
Mounting Bases
Timed Off Control
Stand−off Kit
Sound Cover
Low Ambient Kit
Start−Up & Performance Check List
Job Name
Job Location
Installer
Unit Model No.
Nameplate Voltage
Rated Load Ampacity
Maximum Fuse or Circuit Breaker
Electrical Connections Tight?