Lennox HSXA12-018, HSXA12-024, HSXA12-030, HSXA12-048, HSXA12-036 Installation Instructions Manual

...
Page 1
INSTALLATION
©2002 Lennox Industries Inc.
Dallas, Texas
HSXA12 Outdoor Unit
INSTRUCTIONS
HSXA12 Series Units
CONDENSING UNITS
504,540M 04/04
Supersedes 12/03
Table of Contents
HSXA12 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping And Packing List 1. . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Existing Line Set & Indoor Coil 5. . . . . . . . . . .
Refrigerant Metering Device 11. . . . . . . . . . . . . . . . . . . .
Manifold Gauge Set 11. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−up 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 18. . . . . . . . . . . . . . . . . . . . . . . . . .
HSXA12 Check Points 19. . . . . . . . . . . . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
General Information
Litho U.S.A.
Shipping and Packing List
1 − Assembled HSXA12 outdoor unit 1 − Liquid line filter drier (approved for use with R410A
systems) 1 − Fixed orifice refrigerant metering device Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with R22 must be flushed.
04/04
*2P0404*
These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities having jurisdiction before installation.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
504,540M
Page 1
*P504540M*
Page 2
Unit Dimensions − inches (mm)
HSXA12-018
HSXA12-036
INLET
AIR
INLET AIR
INLET AIR
Top View
C
INLET
AIR
LIQUID LINE
CONNECTION
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
COIL DRAIN OUTLETS
(Around perimeter of base)
VAPOR LINE
CONNECTION
4-3/8 (111 )
6-3/8 (162)
OUTDOOR
COIL FAN
COMPRESSOR
4-3/8 (111 )
COMPRESSOR
6-3/8 (162)
Top View Base Section
C
DISCHARGE AIR
4-3/8 (111 )
4-3/8 (111 )
4-3/8 (111 )
4-3/8 (111 )
Side View
HSXA12-018 HSXA12-024
HSXA12-030 HSXA12-036 HSXA12-042 HSXA12-048
HSXA12-060
B
A
ELECTRICAL
INLETS
VAPOR &
LIQUID LINE
CONNECTION
2-3/4 (70)
2 (51)
3/4
(19)
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
Model No. A B C
in. 25 24-1/4 24-1/4
mm 635 616 616
in. 33 32-1/4 24-1/4
mm 838 819 616
in. 29 28−1/4 28−1/4
mm 737 718 718
Side View
Page 2
Page 3
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Sharp sheet metal edges can cause injury. When installing the unit, avoid accidental contact with sharp edges.
Refer to unit dimensions for sizing mounting slab, plat­forms or supports. Refer to figure 1 for installation clear­ances.
Installation Clearances
36
(914 mm)
36
(914 mm)
36*
(914 mm)
*NOTE − A service clearance of 30" (762 mm) must be main­tained on one of the sides adjacent to the control box. Clear­ance to one of the other three sides must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained between two units. NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
Figure 1
Slab Mounting
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground will not collect around the unit. See figure 2. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1524 mm). Refer to roof mounting section for barrier construction if unit must face prevailing winter winds.
Slab Mounting At Ground Level
structure
discharge air
36*
(914 mm)
Roof Mounting
Install unit at a minimum of 4 inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either red­wood or steel supports are recommended.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Unit must be grounded in accordance with national and local codes. ELECTRIC SHOCK HAZARD. Can cause injury or death.
1 − Install line voltage power supply to unit from a properly
sized disconnect switch.
2 − Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us ing a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 4 for field wiring diagram.
NOTE − A complete unit wiring diagram is located in side the unit control box cover.
3 − Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4 − Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit. See figure 3.
Mounting slab must slope away from building.
Figure 2
ground level
Page 3
Page 4
Thermostat Designations
Thermostat Indoor Unit
R
W1
power
heat
R
W
NOTE − see unit wiring diagram for
power supply connections.
Outdoor Unit
Y
G
C
NOTE − If the indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent).
cooling
indoor blower
common
Y
G
C
Y1 Outdoor Unit
C Outdoor Unit
Figure 3
Typical Field Wiring Diagram
*
*
*
*May be optional
Figure 4
Page 4
Page 5
Refrigerant Piping
If the HSXA12 unit is being installed with an indoor coil and line set, make the refrigerant connections as outlined in this section. If an existing line set and/or indoor coil is going to be used to complete the HSXA12 system, refer to this sec­tion, as well as the flushing section which follows. Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 1 or use field-fabri­cated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351−L9) for proper size, type, and application of field−fabricated lines. Valve sizes are also listed in table 1.
Refrigerant Line Connections
HSXA12 Matched with New Indoor Coil and Line Set If the HSXA12 is being used with an existing indoor coil which was equipped with a liquid line which served as a metering device (RFCI), the liquid line must be re­placed prior to the installation of the HSXA12 unit.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building.
Table 1
Refrigerant Line Sets
Model
Valve Field Size
Connections
Liquid
Line
Vapor
Line
Recommended Line Set
Liquid
Line
Vapor
Line
L15
Line Sets
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Closer attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high−efficiency outdoor unit:
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from the adjacent property not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmis­sion.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line set isolation. Figure 5 shows how to install line sets on vertical runs. Figure 6 shows how to install line sets on horizontal runs. Figure 7 shows how to make a transition from horizontal to vertical. Finally, figure 8 shows how to place the outdoor unit and line set.
L15−26
15 ft. − 50 ft.
(4.6 m − 15 m)
L15−41
15 ft. − 50 ft.
(4.6 m − 15 m)
L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)
Field
Fabricated
−018
024
−030
−036
−042
−048
−060
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
5/8 in.
(16 mm)
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in. (29 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
5/8 in.
(19 mm)
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in. (29 mm)
NOTE − Units are designed for line sets of up to fifty feet (15 m). For applications longer than fifty feet, consult the Len­nox Refrigerant Piping Guide (Corp. 9351−L9). Select line set diameters from table 1 to ensure that oil returns to the compressor.
Page 5
Page 6
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall.
Outside Wall
Wood Block
Between Studs
Liquid Line
Vapor Line
(wrapped with Armaflex)
Outside Wall
IMPORTANT - Refrigerant
lines must not contact wall.
Liquid LineVapor Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Caulk
PVC Pipe
Fiberglass
Insulation
IMPORTANT - Refrigerant
lines must not contact
structure.
Strap
Sleeve
Figure 5
Page 6
Page 7
Installing Horizontal Runs
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Floor Joist or
Roof Rafter
Refrigerant Line Sets:
Wire Tie
(around vapor line only)
8 feet
Tape or Wire Tie
8 feet
Strapping Material (around vapor line only)
Tape or Wire Tie
Metal Sleeve
Floor Joist or Roof Rafter
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line.
Figure 6
Page 7
Page 8
Refrigerant Line Sets:
Transition From Vertical To Horizontal
Anchored Heavy
Nylon Wire Tie
Wall Stud
Metal
Sleeve
Vapor Line
Wrapped in
Armaflex
Strap Liquid Line
To Vapor Line
Liquid Line
Figure 7
Automotive
Muffler-Type
Hanger
Wall Stud
Metal
Sleeve
Strap Liquid Line
To Vapor Line
Liquid Line
Vapor Line
Wrapped in
Armaflex
Outside Unit Placement and Installation
Install unit away from windows.
Two 90° elbows installed in line set will reduce line set vibration.
Figure 8
Page 8
Page 9
WARNING
Polyol ester (POE) oils used with R410A refrigerant
absorb moisture very quickly. It is very important
that the refrigerant system be kept closed as much
as possible. DO NOT remove line set caps or ser-
vice valve stub caps until you are ready to make
connections.
Brazing Connection Procedure
1 − Cut ends of the refrigerant lines square (free from nicks
or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2 − Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the sys­tem.
3 − Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel braz­ing) which are rated for use with R410A refrigerant. Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to pro­tect them during brazing. Braze the line set to the ser­vice valve.
4 − Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during braz­ing. Wrap another wet cloth underneath the valve body to protect the base paint.
Quench the joints with a wet cloth to prevent possible heat damage to the valve core and opening port.
NOTE − The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity.
5 − Install the provided fixed orifice (or thermal expan-
sion valve which is sold separately and approved for use with R410A refrigerant) in the liquid line at the
indoor coil.
6 − Install the provided filter drier (approved for use with
R410A refrigerant) in the liquid line as close as pos­sible to the expansion device. Do not leave the filter
drier uncapped for more than 10 to 15 minutes prior to brazing, evacuation, and leak testing. Polyol ester oils used in this system absorb mois­ture quickly. Failure to install the filter drier will void the warranty.
Flushing Existing Line Set & Indoor Coil
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suc­tion tubing being pressurized. App­plication of a brazing torch while pres­surized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbra­zing.
IMPORTANT
If this unit is being matched with an approved line set or indoor coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to instal­lation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with R410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instruc­tions below will void the warranty.
CAUTION
This procedure should not be performed on sys­tems which contain contaminants (Example: com­pressor burn out).
Required Equipment
You will need the following equipment in order to flush the existing line set and indoor coil: two clean R22 recovery bottles, an oilless recovery machine that has a pump down feature, and two sets of gauges (one for use with R22 and one for use with the R410A).
Flushing Procedure
1 − Remove existing R22 refrigerant using the appropri-
ate procedure below.
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational AND you plan to use the existing R22 refrigerant to flush the system − Disconnect all power to the ex-
isting outdoor unit. Connect to the existing unit, a
Page 9
Page 10
clean recovery cylinder and the recovery machine according to the instructions provided with the recov­ery machine. Remove all R22 refrigerant from the ex­isting system. Refer to gauges after shutdown to con­firm that the entire system is completely void of refrig­erant. Disconnect the liquid and vapor lines from the existing outdoor unit.
If the existing outdoor unit is equipped with manual shut−off valves AND you plan to use NEW R22 refrigerant to flush the system Start the exist-
ing R22 system in the cooling mode and close the liq­uid line valve. Pump all of the existing R22 refrigerant back into the outdoor unit. (It may be necessary to by­pass the low pressure switches to ensure complete refrigerant evacuation.) When the low side system pressures reach 0 psig, close the vapor line valve. Disconnect all power to the existing outdoor unit. Re­fer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and vapor lines from the existing outdoor unit.
Flushing Connections
2 − Remove the existing outdoor unit. Set the new R410A
unit and follow the brazing connection procedure which begins on the previous page to make line set connections. DO NOT install the provided fixed ori-
fice yet.
Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this time.
3 − Remove the existing refrigerant flow control orifice or
thermal expansion valve before continuing with flush­ing procedures. The existing devices are not ap­proved for use with R410A refrigerant and may pre­vent proper flushing. Use a field−provided fitting to re­connect the lines.
IMPORTANT
The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that pre­viously charged the system. Check the charge in the flushing cylinder before proceeding.
Existing
Indoor Coil
RECOVERY CYLINDER
Inverted R22 Cylinder
(Contains clean R22 to
be used for flushing)
Existing Vapor Line
Existing Liquid Line
Vapor Line
Service Valve
Liquid Line
Service Valve
Tank Return
Inlet
Discharge
RECOVERY MACHINE
Figure 9
Low
Pressure
HSXA12
Unit
NOTE − The inverted R22 cylin­der must contain at least the same amount of refrigerant as was recovered from the existing system.
GAUGE MANIFOLD
High
Pressure
ClosedOpened
Page 10
Page 11
4 − Remove the pressure tap valve cores from the
HSXA12 unit’s service valves. Connect an R22 cylin­der with clean refrigerant to the vapor service valve. Connect the R22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set.
5 − Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex­isting system line set and indoor coil.
6 − Invert the cylinder of clean R22 and open its valve to
allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
7 − After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that all of the R22 vapor is recovered. Allow the recovery machine to pull a vacuum on the system.
NOTE − A single system flush should remove all of the mineral oil from the existing refrigerant lines and in­door coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system
is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure.
8 − Close the valve on the inverted R22 drum and the
gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
9 − Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery ma­chine, gauges and R22 refrigerant drum. Reinstall pressure tap valve cores into HSXA12 service valves.
10 −Install the provided fixed orifice in the liquid line at the
indoor coil.
Refrigerant Metering Device
may not be appropriately sized. Refer to the Engineering Handbook for specific orifice information.
Table 2
Fixed Orifice Drill Sizes
Unit Fixed Orifice Part # Drill Size
HSXA12−018 29M88 .05
HSXA12−024 42J43 .063
HSXA12−030 42J43 .063
HSXA12−036 42J47 .071
HSXA12−042 42J51 .078
HSXA12−048 29M93 .081
HSXA12−060 42J57 .090
Install the fixed orifice as shown in figure 10. Do not twist the cap tubes when loosening the seal nut from the orifice housing. Use a wrench to back up the distributor.
Metering Device Installation
orifice
(factory−installed)
distributor
valve OR orifice
o−ring
expansion valve (opt.)
o−ring
strainer
liquid line
stub
Figure 10
Expansion Valve Systems
Expansion valves equipped with Chatleff type fittings are available from Lennox. Refer to the Engineering Handbook for expansion valves for use with specific match−ups.
If you install an expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the expansion valve is installed.
HSXA12 units are applicable to either fixed orifice or an expansion valve system. See the indoor coil installation instructions and the Lennox Engineering Handbook for approved TXV and fixed orifice match−ups and application information. Table 1 lists the unit liquid and vapor line sizes and corresponding line sets.
Fixed Orifice Systems
HSXA12 units are shipped with a fixed orifice refrigerant metering device. Replace the existing indoor unit fixed ori­fice with the orifice supplied with the outdoor unit. Place the supplied fixed orifice sticker on the indoor cabinet after installation. See table 2 for the fixed orifice size for each unit. In nonstandard applications, the provided fixed orifice
IMPORTANT
Failure to remove a fixed orifice when installing an expansion valve to the indoor coil will result in im­proper operation and damage to the system.
Manifold Gauge Set
Manifold gauge sets used with systems charged with R410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
Page 11
Page 12
Service Valves
The liquid line and vapor line service valves (figures 11 and
12) and gauge ports are used for leak testing, evacuating, charging and checking charge. See table 3 for torque re­quirements.
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
Table 3
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 N M
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 N M
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench. 2 − Connect gauge to the service port. 3 − When testing is completed, replace service port cap.
Tighten finger tight, then tighten an additional 1/6 turn.
To Open Service Valve:
1 − Remove stem cap with an adjustable wrench. 2 − Use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
To Close Service Valve:
1 − Remove the stem cap with an adjustable wrench. 2 − Use a service wrench with a hex−head extension to
turn the stem clockwise to seat the valve. Tighten it firmly.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Service Valve
(Valve Closed)
service
port
to outdoor coil
service
port cap
Schrader valve open
to line set when valve is
closed (front seated)
wrench here
(valve front seated)
stem cap
insert hex
to indoor coil
Service Valve
insert hex
wrench here
to outdoor coil
service port
cap
(Valve Open)
service
port
Schrader
valve
stem cap
to indoor coil
Figure 11
Vapor Line (Ball Type) Service Valve
Vapor line service valves function the same way as the oth-
er valves; the difference is in the construction. These
valves are not rebuildable. If a valve has failed, you must
replace it. A ball valve is illustrated in figure 12.
The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−
free seal.
Page 12
Page 13
Ball Valve (Valve Open)
Use Adjustable Wrench
To open: rotate Stem Counter-clockwise 90°.
To close: rotate Stem Clockwise 90°.
stem cap
to outdoor coil
stem
ball
(shown open)
to indoor coil
service port
cap
service port
Schrader valve
Figure 12
Leak Testing
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks.
WARNING
2 − With both manifold valves closed, connect the cylinder
of R410A refrigerant. Open the valve on the R410A cyl­inder (vapor only).
3 − Open the high pressure side of the manifold to allow
R410A into the line set and indoor unit. Weigh in a trace amount of R410A. [A trace amount is a maximum of 2
ounces (57 g) refrigerant or 3 pounds (31 kPa) pres­sure]. Close the valve on the R410A cylinder and the
valve on the high pressure side of the manifold gauge set. Disconnect R410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6 − Adjust nitrogen pressure to 150 psig (1034 kPa). Open
the valve on the high side of the manifold gauge set in or­der to pressurize the line set and the indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck.
Refrigerant can be harmful if it is inhaled. Refriger-
ant must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
WARNING
Danger of explosion: Can cause equipment damage, injury or death. Never use oxygen to pressurize a re­frigeration or air conditioning system. Oxygen will explode on contact with oil and could cause personal injury.
WARNING
Danger of explosion: Can cause equipment damage,
injury or death. When using a high pressure gas
such as dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).
Using an Electronic Leak Detector
1 − Connect a cylinder of R410A to the center port of the
manifold gauge set.
IMPORTANT
Leak detector must be capable of sensing HFC re­frigerant.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 10,000 microns.
1 − Connect manifold gauge set to the service valve ports
as follows: low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2 − Connect micron gauge.
Page 13
Page 14
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin­der with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use com­pressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of R410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R410A cylinder and remove the manifold gauge set.
Start−Up
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1 − Rotate fan to check for frozen bearings or binding.
2 − Inspect all factory− and field−installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4 − Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6 − Set the thermostat for a cooling demand. Turn on pow-
er to the indoor blower and close the outdoor unit dis­connect switch to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Charging
This system is charged with R410A refrigerant which oper­ates at much higher pressures than R22. The provided liq­uid line filter drier is approved for use with R410A. Do not replace it with components designed for use with R22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.
Factory Charge
Units are factory charged with the amount of R410A refrig­erant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15 ft. (4.6 m) line set. For varying lengths of line set, refer to table 4 for refrigerant charge adjustment.
Table 4
Liquid Line Set
Diameter
3/8 in.
(10 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Oz. per 5 ft. (grams per 1.5 m) adjust
from 15 ft. (4.6 m) line set*
3 ounces per 5 feet
(85g per 1.5 m)
IMPORTANT
Mineral oils are not compatible with R410A. If oil must be added, it must be a polyol ester oil.
Page 14
Page 15
The compressor is charged with sufficient polyol ester oil for line set lengths up to 50 feet (15.2 m). If oil must be added to the compressor in the field, Copeland has approved Mobil EALt Arctic 22CC and ICI EMKA­RATEt RL32CF.
Units Delivered Void of Charge
If the system is void of refrigerant, clean the system us­ing the procedure described below.
1 − Use nitrogen to pressurize the system and check for
leaks. Repair leaks, if possible.
2 − Evacuate the system to remove as much of the mois-
ture as possible.
3 − Use nitrogen to break the vacuum and install the pro-
vided filter drier in the system.
4 − Evacuate the system again. Then, weigh the appropri-
ate amount of R410A refrigerant (listed on unit name­plate) into the system.
5 − Monitor the system to determine the amount of mois-
ture remaining in the oil. Use test kit 10N46 to verify that the moisture content is within the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If
system dryness is not verified, the compressor will fail in the future.
Checking Charge
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1 − Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service port high pressure gauge to liquid valve service port
Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R410A .
2 − Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in the cooling cycle.
3 − Use a digital thermometer to record the outdoor ambi-
ent temperature.
4 − When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68F (20C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
5 − The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate charg­ing procedure.
Weighing in the Charge Fixed Orifice or
TXV Systems – Outdoor Temp. < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been re­paired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other proce­dures outlined below.
Charging Using the Subcooling Method
Fixed Orifice Systems
Outdoor Temp. >
If you charge a fixed orifice system when the outdoor ambi­ent is 65F (18C) or above, use the subcooling method to charge the unit.
1 − With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature. 2 − At the same time, record the liquid line pressure reading. 3 − Use a temperature/pressure chart for R410A to deter-
mine the saturation temperature for the liquid line pres-
sure reading. See table 5.
4 − Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature − Liquid line tem-
perature = Subcooling)
5 − Compare the subcooling value with those in table 6. If
subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant.
65F (18C))
Page 15
Page 16
Table 5
Outdoor
R410A Temperature/Pressure Chart
Temperature°FPressure
Psig
32 100.8 63 178.5 94 290.8 125 445.9
33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 11 2 375.1 143 559.1
51 144.8 82 242.7 11 3 380.2 144 565.9
52 147.4 83 246.5 11 4 385.4 145 572.8
53 150.1 84 250.3 11 5 390.7 146 579.8
54 152.8 85 254.1 11 6 396.0 147 586.8
55 155.5 86 258.0 11 7 401.3 148 593.8
56 158.2 87 262.0 11 8 406.7 149 601.0
57 161.0 88 266.0 11 9 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 195.5 93 286.5 124 440.2 155 645.0
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Subcooling Values for Fixed Orifice Systems
Outdoor
Temp. °F (°C)
65 (18) 13 (7.2) 13 (7.2) 16 (8.9) 12 (6.7) 11 (6.4) 14 (7.8) 13 (7.2) 70 (21) 12 (6.7) 11 (6.1) 15 (8.3) 11 (6.1) 10 (5.6) 13 (7.2) 12 (6.7) 75 (24) 11 (6.1) 10 (5.6) 14 (7.8) 10 (5.6) 9 (5) 12 (6.7) 11 (6.1) 80 (27) 9 (5) 9 (5) 13 (7.2) 9 (5) 8 (4.5) 11 (6.1) 10 (5.6) 85 (29) 8 (4.5) 7 (3.9) 12 (6.7) 8 (4.5) 7 (3.9) 10 (5.6) 10 (5.6) 90 (32) 6 (3.3) 6 (3.3) 10 (5.6) 7 (3.9) 6 (3.3) 9 (5) 9 (5)
95 (35) 5 (2.8) 5 (2.8) 9 (5) 6 (3.3) 6 (3.3) 8 (4.5) 8 (4.5) 100 (38) 5 (2.8) 4 (2.2) 8 (4.5) 5 (2.8) 5 (2.8) 7 (3.9) 7 (3.9) 105 (41) 4 (2.2) 4 (2.2) 7 (3.9) 4 (2.2) 4 (2.2) 7 (3.9) 6 (3.3) 110 (43) 3 (1.7) 3 (1.7) 6 (3.3) 4 (2.2) 3 (1.7) 6 (3.3) 6 (3.3) 115 (45) 2 (1.1) 3 (1.7) 5 (2.8) 3 (1.7) 3 (1.7) 6 (3.3) 5 (2.8)
−018 −024 −030 −036 −042 −048 −060
Table 6
Liquid Subcooling [± 1°F (.6°C)]
Page 16
Page 17
Approach Method and
Mode
Normal Operating Pressures
TXV Systems – Outdoor Temp. >
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 8, Normal Operating Pressures." Minor varia­tions in these pressures may be expected due to differ­ences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid line temperature.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 7. If the val­ues don’t agree with the those in table 7, add refriger­ant to lower the approach temperature, or recover re-
65F (18C)
frigerant from the system to increase the approach temperature. Be aware of the R410A refrigerant cylinder. It will be rose−colored. Refrigerant should be added through the vapor valve in the liquid state. Some R410A cylinders
are equipped with a dip tube which allows you to draw liquid refrigerant from the bottom of the cylin­der without turning the cylinder upside−down. The cylinder will be marked if it is equipped with a dip tube.
Table 7
HSXA12 Approach Values
Model No.
−018 10 (5.6)
−024 12 (6.7)
−030 13 (7.2)
−036 12 (6.7)
−042 11 (6.1)
−048 13 (7.2)
−060 14 (7.8)
Approach Temperature
Liquid Line −
Outdoor Ambient °F (°C)
IMPORTANT
Use table 8 to perform maintenance checks. Table 8 is not a procedure for charging the system. Minor variations in these pressures may be due to differ­ences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Table 8
Normal Operating Pressures In psig (liquid +/− 10 and vapor +/− 5 PSIG)*
Out. Coil
Mode
fixed orifice
TXV
Entering Air
Temp.
°F (°C)
65 (18.3) 238 123 261 131 261 128 268 130 254 121 270 124 280 121
75 (23.9) 275 131 300 135 300 133 308 134 296 128 311 130 332 126
85 (29.4) 317 136 343 139 343 138 351 138 340 133 356 134 379 130
95 (35.0) 362 141 391 143 387 141 398 142 389 138 404 139 427 135
105 (40.6) 410 144 441 147 434 145 447 146 440 142 456 143 479 140
65 (18.3) 234 133 256 134 256 137 264 135 256 124 269 131 262 121
75 (23.9) 270 135 298 137 296 139 305 138 296 127 312 133 304 127
85 (29.4) 312 137 344 140 339 141 349 139 341 133 357 135 349 132
95 (35.0) 361 138 394 142 384 144 396 140 389 136 406 137 397 136
105 (40.6) 409 141 448 143 432 146 446 143 440 140 460 140 449 140
*These are typical pressures only. Indoor indoor match up, indoor air quality, and indoor load will cause the pressures to vary.
−018 −024 −030 −036 −042 −048 −060
LIQ SUC LIQ SUC LIQ SUC LIQ SUC LIQ SUC LIQ SUC LIQ SUC
Page 17
Page 18
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
Compressor Time Delay (TD1)
A compressor time delay is used to prevent compressor short cycling and to prevent the compressor from running backwards. When there is demand for a cooling cycle, the control delays compressor operation for about 5 minutes (+ 2 minutes). Do not bypass the control.
High Pressure Switch
HSXA12 units are equipped with a high pressure switch that is located in the liquid line of the compressor. The switch (SPST, manual reset, normally closed) removes power from the compressor when discharge pressure rises above factory setting at 640 + 10 psi.
Low Pressure Switch
HSXA12 units are also equipped with a low pressure switch that is located in the vapor line of the compressor. The switch (SPST, auto−reset, normally closed) removes power from the compressor when vapor line pressure drops be­low factory setting at 40 + 5 psi.
Filter Drier
A filter drier is shipped with each HSXA12 unit. The filter drier must be field installed in the liquid line between the liquid line service valve and the expansion valve. This fil-
ter drier must be installed to ensure a clean, moisture− free system. Failure to install the filter drier will void the warranty. A replacement filter drier is available as
from Lennox.
1 − Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Ensure the power is turned off before you clean the coil.
2 − Outdoor fan motor is prelubricated and sealed. No fur-
ther lubrication is needed.
3 − Visually inspect connecting lines and coils for evidence
of oil leaks.
4 − Check wiring for loose connections.
5 − Check for correct voltage at unit (unit operating).
6 − Check amp−draw outdoor fan motor.
Unit nameplate _________ Actual ____________ .
NOTE − If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil, if necessary.
2 − Check connecting lines and coils for evidence of oil
leaks.
3 − Check condensate line and clean, if necessary.
Indoor Unit
1 − Clean or change filters.
2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3 − Belt Drive Blowers − Check belt for wear and proper
tension.
4 − Check all wiring for loose connections
5 − Check for correct voltage at unit (blower operating). 6 − Check amp−draw on blower motor
Unit nameplate_________ Actual ____________.
Maintenance
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Optional Accessories
Refer to the Engineering Handbook for optional accesso­ries that may apply to this unit. The following may or may not apply:
Loss of Charge Kit High Pressure Switch Kit Compressor Monitor Compressor Crankcase Heater Hail Guards Mounting Bases Timed Off Control Stand−off Kit Sound Cover Low Ambient Kit
Page 18
Page 19
HSXA12 Check Points
Job Name
Job Location
Installer
Unit Model No.
Nameplate Voltage
Rated Load Ampacity
Maximum Fuse or Circuit Breaker
Electrical Connections Tight?
Indoor Blower RPM
Discharge Pressure
Refrigerant Lines:
Service Valves Fully Opened?
Voltage With Compressor Operating
Leak Checked?
Start−up and Performance Check List
Job No.
City
City
Serial No.
Compressor
Indoor Filter Clean?
S.P. Drop Over Indoor (Dry)
Vapor Pressure
Properly Insulated?
Service Valve Caps Tight?
Calibrated? Properly Set?
Date
State
State
Service Technician
Outdoor Fan
Supply Voltage (Unit Off)
Outdoor Coil Entering Air Temp.
Refrigerant Charge Checked?
Outdoor Fan Checked?
Thermostat
Level?
Page 19
Loading...