Lennox HS27-024, HS27-042, HS27 Series, HS27-030, HS27-036 Installation Instructions Manual

INSTALLATION
2000 Lennox Industries Inc.
Dallas, Texas, USA
HS27 outdoor units are designed for expansion valve sys­tems only. They are not designed for RFC systems. Refer to Lennox engineering handbook for expansion valve kits which must be ordered separately.
Shipping & Packing List
1 − Assembled HS27 outdoor unit
2 − Grommets (for liquid and vapor lines)
1 − Bushing (for low voltage wiring)
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarcera­tion may be levied for noncompliance.
INSTRUCTIONS
HS27 SERIES UNITS
CONDENSING UNITS
504,669M 02/04
Supersedes 12/02
Table of Contents
HS27 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Metering Device 9. . . . . . . . . . . . . . . . . . . . .
Manifold Gauge Set 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 14. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−up & Performance Check List 15. . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
Litho U.S.A.
02/04
*2P0204*
Page 1
504,669M
*P504669M*
Unit Dimensions − inches (mm)
HS27-024
HS27-036
airinlet
inlet
COMPRESSOR
air
2
(51)
3-7/8
(98)
32-1/8 (816)
7-1/2
(191)
4-7/8 (22)
28-1/8 (714)
HS27-024 HS27-030
HS27-036 HS27-042
7-1/2 (191)
electrical
3-7/8
(98)
(51)
inlets
vapor line
inlet
A
liquid
line inlet
4-1/2 (114)
B
2-3/4 (70)
2
1-3/8
(35)
DISCHARGE AIR
2-9/16
(65)
4
(102)
Top View
34-1/16 (865)
18-5/8
(473)
26-5/8 (676)
Side ViewAccess View
Model No. A B
in. 30-7/8 12-3/4
mm 784 324
in. 40-7/8 19-3/4
mm 1038 502
airinlet
4
(102)
6-1/16
(154)
Page 2
Parts Arrangement
outdoor fan (not shown)
top of cabinet
run capacitor
ground lug
contactor
terminal box
high pressure
switch
Figure 1
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
Refer to unit dimensions for sizing mounting slab, platform­s, or supports. Refer to figure 2 for installation clearances.
vapor valve
and gauge port
liquid line
service valve
and gauge port
compressor
low pressure
switch
Installation Clearances
NOTE − A service access clearance of 30" (762 mm) must be maintained in front of the service access panel. Clearance to one side must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
36"
(914 mm)
*36"
(914 mm)
*36"
(914 mm)
36"
(914 mm)
Figure 2
Page 3
A − Slab Mounting
When you install the unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground will not collect around the unit. See figure 3. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m)
slope tolerance away
from building structure
ground level
Slab Mounting
discharge air
building
structure
mounting
slab
Figure 3
B − Roof Mounting
Install unit at a minimum of 4 inches above surface of the roof. Care must be taken to ensure weight of unit is properly distrib­uted over roof joists and rafters. Either redwood or steel sup­ports are recommended.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Unit must be grounded in accordance with national and local codes. Electric Shock Hazard. Can cause injury or death.
1. Install line voltage power supply to unit from a properly sized disconnect switch.
2. Ground unit at unit disconnect switch or to an earth ground.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us ing a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 4 for field wiring diagram.
NOTE − A complete unit wiring diagram is located in side the unit control box cover.
3. Install room thermostat (ordered separately) on an in­side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figure 5.
Page 4
(LEADLESS)
Outdoor Unit
Field Wiring Diagram
YELLOW
Thermostat Designations
Thermostat Furnace
R
W1
Y
G
C
power
heat
cooling
indoor blower
common
R
W
Y
G
C
Figure 4
NOTE − see unit wiring diagram for
power supply connections.
Outdoor Unit
Y1 Outdoor Unit
C Outdoor Unit
NOTE − If the indoor unit is not equipped with blower relay, it must be field−provided and installed (P−8−3251 or equivalent).
Figure 5
Page 5
Loading...
+ 11 hidden pages