The HS26 is a high efficiency residential split−system con
densing unit which features a scroll compressor. Early
model HS26 units (−261,−311,−411, and −461) are available
in sizes ranging from 2 through 3−1/2 tons. Late model
HS26 units (−018, −024, −030, −036, −042, −048 and −060)
are available in sizes ranging from 1−1/2 through 5 tons.
The series is designed for use with an expansion valve in
the indoor unit.This manual is divided into sections which
discuss the major components, refrigerant system, charg
ing procedure, maintenance and operation sequence. In
formation in this manual covers both early and late model
HS26 units.
All specifications in this manual are subject to change.
UNIT
HS26
EARLY/LATE
MODEL SERIES
Litho U.S.A.
Late ModelHS26 shown
SPECIFICATIONS (Early Model)
Model No.HS26−261HS26−311HS26−411HS26−461
Face area (sq.ft.)
Outdoor
Coil
Condenser
Fan
HCFC−22 (charge furnished)
Liquid line connection
Suction line connection
*Refrigerant charge sufficient for 25 ft. (7.6 m) length of refrigerant lines.
outer / inner
Tube diameter (in.)
No. of Rows
Fins per inch
Diameter (in.)
No. of Blades
Motor hp
Cfm
RPM
Watts
11.8/5.415.9/5.515.9/15.321.6/20.8
3/83/83/83/8
1.361.362.02.0
20202020
24242424
3333
1/61/61/61/6
3150315030003230
820820820820
210210230205
7lbs. 11oz.8lbs. 1oz.9lbs. 0oz.11lbs. 3oz.
3/83/83/83/8
3/43/43/411/8
ELECTRICAL DATA (Early Model)
Model No.
Line voltage data − 60hz./1 phase
Rated load amps
Compressor
Condenser
Fan Motor
Max fuse or c.b. size (amps)
*Minimum circuit ampacity
*Refer to National Electrical Code Manual to determine wire, fuse and disconnect size requirements.
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage
Power factor
Locked rotor amps
Full load amps
Locked rotor amps
HS26−261HS26−311HS26−411HS26−461
208/230V208/230V208/230V208/230V
11.613.518.020
.96.96.96.97
62.576.090.5107
1.11.11.11.1
2.02.02.02.0
25304045
15.618.023.626.1
Page 1
1996 Lennox Industries Inc.
Net face area
Condenser
Coil
Cond
Condenser Coil
Condenser Coil
Coil
SPECIFICATIONS (Late Model)
Model No.HS26018HS26024HS26030HS26036HS26042HS26048HS26060
Rec. max. fuse or circuit breaker size (amps)15203035204025
*Minimum circuit ampacity13141821.31423.616.4
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
Full load amps0.81.11.11.11.11.11.1
Locked rotor amps1.62.02.02.02.02.02.0
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
3ph
208/230v
1ph
208/230v
3ph
ELECTRICAL DATA (Late Model)
Model No.HS26048HS26060
Line voltage data 60hz
Rated load amps23.713.57.428.817.49.0
CompressorPower factor.97.87.87.97.85.85
Locked rotor amps1299949.516912362
Condenser Coil
Fan Motor
Rec. max. fuse or circuit breaker size (amps)503015604020
*Minimum circuit ampacity31.418.610.437.723.512.4
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
Full load amps1.71.71.11.71.71.1
Locked rotor amps3.13.12.23.13.12.2
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
Page 2
DISCHARGE
SUCTION
SCROLL COMPRESSOR
SCROLL FORM
CROSS−SECTION OF SCROLLS
DISCHARGE
DISCHARGE
PRESSURE
FIGURE 2
STATIONARY SCROLL
SUCTION
Early Model HS26
Compressor shown
FIGURE 1
I−APPLICATION
All major components (indoor blower and coil) must be
matched according to Lennox recommendations for the
compressor to be covered under warranty. Refer to the
Engineering Handbook for approved system matchups. A
misapplied system will cause erratic operation and can re
sult in early compressor failure.
II−SCROLL COMPRESSOR
The scroll compressor design is simple, efficient and re
quires few moving parts. A cutaway diagram of the scroll
compressor is shown in figure 1.The scrolls are located in
the top of the compressor can and the motor is located just
below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered
around the unique spiral shape of the scroll and its inherent
properties. Figure 2 shows the basic scroll form. Two iden
tical scrolls are mated together forming concentric spiral
shapes (figure 3 ). One scroll remains stationary, while the
other is allowed to orbit" (figure 4). Note that the orbiting
scroll does not rotate or turn but merely orbits" the station
ary scroll.
TIPS SEALED BY
DISCHARGE PRESSURE
ORBITING SCROLL
FIGURE 3
The counterclockwise orbiting scroll draws gas into the out
er crescent shaped gas pocket created by the two scrolls
(figure 4 − 1). The centrifugal action of the orbiting scroll
seals off the flanks of the scrolls (figure 4 − 2). As the orbiting
motion continues, the gas is forced toward the center of the
scroll and the gas pocket becomes compressed (figure 4
−3). When the compressed gas reaches the center, it is dis
charged vertically into a chamber and discharge port in the
top of the compressor (figure1). The discharge pressure
forcing down on the top scroll helps seal off the upper and
lower edges (tips) of the scrolls (figure 3 ). During a single
orbit, several pockets of gas are compressed simultaneous
ly providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid re
turn. If liquid enters the scrolls, the orbiting scroll is allowed
to separate from the stationary scroll. The liquid is worked
toward the center of the scroll and is discharged. If the
compressor is replaced, conventional Lennox cleanup
practices must be used.
Due to its efficiency, the scroll compressor is capable of
drawing a much deeper vacuum than reciprocating com
pressors. Deep vacuum operation can cause internal fu
site arcing resulting in damaged internal parts and will re
sult in compressor failure. Never use a scroll compressor
for evacuating or pumping−down" the system. This type of
damage can be detected and will result in denial of warran
ty claims.
NOTE − During operation, the head of a scroll compressor
may be hot since it is in constant contact with discharge
gas.
Page 3
SUCTION
POCKET
HOW A SCROLL WORKS
MOVEMENT OF ORBIT
SUCTION
ORBITING
SCROLL
SUCTION
INTERMEDIATE
PRESSURE
GAS
CRESCENT
SHAPED GAS
POCKET
12
FLANKS
STATIONARY SCROLL
SUCTION
SEALED BY
CENTRIFUGAL
FORCE
SUCTION
34
HIGH
PRESSURE
GAS
FIGURE4
III−UNIT COMPONENTS
A−Transformer
The contactor coil, time delay and temperature sensor
are all energized by 24VAC supplied by the indoor unit.
All other controls in the outdoor unit are powered by line
voltage. Refer to unit wiring diagram. The HS26 is not
equipped with an internal line voltage to 24V transform
er.
B−Contactor
The compressor is energized by a contactor located in the
control box. Early model units use single−pole contactors.Late
model single−phase units use single pole and two−pole con
tactors. See wiring diagrams for specific unit. Late model
three−phase units use three−pole contactors. The contactor is
energized by indoor thermostat terminal Y when thermostat
demand is present.
DISCHARGE
POCKET
CAUTION
Some HS26 units use single−pole contactors. One
leg of the compressor, capacitor and condenser
fan are connected to line voltage at all times. Po
tential exists for electrical shock resulting in inju
ry or death. Remove all power at disconnect be
fore servicing
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during unit instal
lation and service to protect the unit’s electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the unit, the control and the technician at the
same electrostatic potential. Neutralize electro
static charge by touching hand and all tools on an
unpainted unit surface before performing any
service procedure.
Page 4
C−TD1−1 Time Delay (Early Models)
Some early model HS26 units are equipped with a Lennox−
built TD1−1 time delay located in the control box (figure 5).
The time delay is electrically connected between thermostat
terminal Y and the compressor contactor. On initial thermo
stat demand, the compressor contactor is delayed for 8.5
seconds. At the end of the delay, the compressor is allowed
to energize. When thermostat demand is satisfied, the time
delay opens the circuit to the compressor contactor coil and
the compressor is de−energized.
The time delay performs no other functions. Without the
delay it would be possible to short cycle the compressor. A
scroll compressor, when short cycled, can run backward if
head pressure is still high. It does not harm a scroll com
pressor to run backward, but it could cause a nuisance trip
of safety limits (internal overload). For this reason, if a
TD1−1 delay should fail, it must be replaced. Do not bypass
the control.
D−TOC Timed Off Control
(Early and Late Models)
Some early and all late model HS26 units are equipped with
a TOC, timed off control.The TOC is located in the control
box (figure 6). The time delay is electrically connected be
tween thermostat terminal Y and the compressor contactor.
Between cycles, the compressor contactor is delayed for 5
minutes + 2 minutes. At the end of the delay, the compres
sor is allowed to energize. When thermostat demand is sat
isfied, the time delay opens the circuit to the compressor
contactor coil and the compressor is de−energized. Without
the time delay it would be possible to short cycle the com
pressor. A scroll compressor, when short cycled, can run
backward if head pressure is still high. It does not harm a
scroll compressor to run backward, but it could cause a nui
sance tripout of safety limits. For this reason, if a TOC fails it
must be replaced.
DANGER
DO NOT ATTEMPT TO REPAIR THE TD1−1 OR THE
TOC CONTROL. UNSAFE OPERATION WILL RE
SULT. IF THE CONTROL IS FOUND TO BE INOP
ERATIVE, SIMPLY REPLACE IT.
CONDENSER FAN
(NOT SHOWN)
TOP OF CABINET
DUAL CAPACITOR
THERMOMETER
WELL
COMPRESSOR
TEMPERATURE
SENSOR
HIGH
PRESSURE
SWITCH
COMPRESSOR
COMPRESSOR
TERMINAL BOX
HS26 UNIT COMPONENTS (EARLY MODEL)
TD−1 TIME DELAY
OR T.O.C. TIMED OFF
CONTROL
CONTACTOR
LIQUID LINE
SERVICE VALVE
AND GAUGE PORT
SUCTION
VALV E
AND GAUGE PORT
LOW PRES
SURE SWITCH
ACCUMULATOR
(411, 461 only
all others equipped
with suction muffler)
FIGURE 5
Page 5
CONDENSER FAN
(NOT SHOWN)
TOP OF CABINET
PARTS ARRANGEMENT FOR HS26 (LATE MODEL)
TIMED OFF CONTROL (TOC)
GROUND LUG
DUAL CAPACITOR
TERMINAL BOX
THERMOME
TER
WELL
HIGH PRESSURE
SWITCH
FIGURE 6
E−Compressor
Tables1 and 2 show the specifications for compressors
used in HS26 series units.
F−Compressor High Temperature Limit
(Early Models)
Each scroll compressor in the HS26−261, −311, −411, −461
is equipped with a compressor high temperature limit lo
cated on the outside top of the compressor. The sensor is a
SPST thermostat which opens when the discharge tem
perature exceeds 280_F + 8_F (138_C + 4.5_C) on a tem
perature rise. When the switch opens, the circuit to the
compressor contactor and the time delay is de−energized
and the unit shuts off. The switch automatically resets
when the compressor temperature drops below 130_F +
14_F. (54_C + 8_C)
The sensor can be accessed by prying off the snap plug on
top of the compressor (see figure 7). Make sure to securely
seal the limit after replacement. The limit pigtails are lo
cated inside the unit control box. Figure 8 shows the ar
rangement of compressor line voltage terminals and dis
charge sensor pigtails.
CONTACTOR
SUCTION VALVE
AND GAUGE PORT
LIQUID LINE
SERVICE VALVE
AND GAUGE
PORT
COMPRESSOR
LOW PRESSURE
SWITCH
Table 1 (Early Models)
HS 26
Unit
−261208/230162.511.628*
−311208/230176.013.528*
−411208/230190.518.034*
−461208/230110720.038*
*Shipped with conventional white oil (Sontex 200LT). 3GS oil may be
used if additional oil is required.
VacPhaseLRARLAOil fl.oz.
Table 2 (Late Models)
HS26
Unit
−018208/230147.08.438*
−024208/230156.010.330*
−030208/230172.513.530*
−036208/230188.016.042*
−042208/2301104.018.042*
−048208/2301129.023.753*
−060208/2301169.028.850*
−036208/230388.810.342*
−042208/230377.012.542*
−048208/230399.013.553*
−048460349.57.453*
−060208/2303123.017.453*
−060460362.09.053*
*Shipped with conventional white oil (Sontex 200LT). 3GS oil may be
used if additional oil is required.
VacPhaseLRARLAOil fl. oz.
Page 6
COMPRESSOR HIGH TEMPERATURE LIMIT CHANGEOUT (EARLY MODELS ONLY)
PLASTIC CAP
SEALANT
(BLUE)
PRONG
THERMAL
GREASE
(WHITE)
COMPRESSOR
GROMMET
LIMIT
(THERMOSTAT)
FIGURE 7
G−High/Low Pressure Switch
A manualreset singlepole singlethrow high pressure switch
located in the liquid line, shuts off the compressor when liquid
line pressure rises above the factory setting. The switch is nor
mally closed and is permanently adjusted to trip (open) at 410
+ 10 psi. See figure 5 or 6 for switch location
COMPRESSOR TERMINAL BOX
DISCHARGE TEMPERATURE
SENSOR WIRES
TO CONTROL BOX
(TO COMP. TERM. BOX IN
461 UNITS)
EARLY MODELS ONLY
COMPRESSOR
TERMINALS
C
S
R
WARNING
COMPRESSOR MUST BE GROUNDED. DO
NOT OPERATE WITHOUT PROTECTIVE COV
ER OVER TERMINALS. DISCONNECT ALL
POWER BEFORE REMOVING PROTECTIVE
COVER. DISCHARGE CAPACITORS BEFORE
SERVICING UNIT. COMPRESSOR WIRING DIA
GRAM IS FURNISHED INSIDE COMPRESSOR
TERMINAL BOX COVER. FAILURE TO FOL
LOW THESE PRECAUTIONS COULD CAUSE
ELECTRICAL SHOCK RESULTING IN INJURY
OR DEATH.
FIGURE 8
Instructions
1 With power off, disconnect wiring to limit.
2 Dislodge limit/cap assembly from compressor. Plastic cap and silicone seal
will break away. Discard all pieces.
3 Remove thermostat and grommet from compressor. Thoroughly clean all
blue adhesive and white silicone thermal grease from compressor and the
inside of the thermostat tube. Thermostat tube should be clean and free of
debris.
4 Using Lennox kit 93G8601, dip end of thermostat into plastic bottle labeled
Silicone Thermal Grease G.E. #G641" and coat end of thermostat. Care
fully insert thermostat/grommet assembly into thermostat tube of compres
sor. Avoid contact with top of compressor.
5 Clean excess thermal grease from under cap lip and top lip of compressor
opening.
6 Install protector assembly as shown, feeding wire leads through channel
provided in cap.
7 Apply a bead of sealant around lip of cap at area shown in illustration and
into the thermostat tube area.
8 Install assembly as shown. Align wires to channel in compressor shell. Suf
ficient force is required to snap plastic cap into tube to engage all three
An autoreset singlepole singlethrow low pressure switch
located in the suction line shuts off the compressor when
suction pressure drops below the factory setting. The
switch is normally closed and is permanently adjusted to
trip (open) at 25 + 5 psi. The switch automatically resets
when suction line pressure rises above 55 + 5 psi. See fig
ure 5 or 6 for switch location.
H−Dual Capacitor
The compressor and fan in HS26 single−phase units use
permanent split capacitor motors. A single dual" capacitor
is used for both the fan motor and the compressor (see unit
wiring diagram). The fan side of the capacitor and the com
pressor side of the capacitor have different mfd ratings. The
capacitor is located inside the unit control box (see figure 5
or 6). Tables 3 and 4 show the ratings of the dual capacitor.
TABLE 3 (Early Models)
HS26 DUAL CAPACITOR RATING
UNITS
HS26−261530370
HS26−311535370
HS26−411,−461535440
TABLE 4 (Late Models)
HS26 DUAL CAPACITOR RATING
UNITSFAN MFDHERM MFDVAC
HS26−018430370
HS26−024,−030540370
HS26−036550370
HS26−042555370
HS26−0487.560370
HS26−0601080370
FAN
MFD
HERM MFDVA C
Page 7
I−Condenser Fan Motor
018
024
261
7/8"
030,311,036,
1−1/16"
048
060
1−3/16"
All units use single−phase PSC fan motors which require a
run capacitor. The FAN" side of the dual capacitor is used
for this purpose. The specifications tables on page 1 and 2
of this manual show the specifications of outdoor fans used
in HS26s. In all units, the outdoor fan is controlled by the
compressor contactor. See figure 9 if condenser fan motor
replacement is necessary.
"A" SEE TABLE 5
Condenser fan
and motor
FAN
GUARD
Wiring
Drip loop
FIGURE 9
TABLE 5
HS26 UNIT"A" DIM. + 1/8"Fan Blade Ven
−
, −
, −
−030, −311, −036,
−411, −042, −461
,
"
"
1−3/4"Lau
−
−
1−1/2"Revcor
"
dor
Lau
Revcor
Lau
Revcor
Lau
Revcor
IV−REFRIGERANT SYSTEM
A−Plumbing
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (sweat connections). Use Lennox
L10 or L15 series line sets as shown in table 6 or 7 for field−
fabricated refrigerant lines. Refer to the piping section of
the Lennox Service Unit Information Manual (SUI−803−L9)
for proper size, type and application of field−fabricated
lines.
Separate discharge and suction service ports are provided
at the compressor for connection of gauge manifold during
charging procedure.
TABLE 6 (Early Models)
HS26
UNIT
−261, −311,
−411
−461
−511
−651
LIQUID
LINE
3/8 in.
(10 MM)
3/8 in.
(10 MM)
3/8 in.
(10 MM)
3/8 in.
(10 MM)
SUCTION
LINE
3/4 in.
(19 mm)
1−1/8 in.
(29 m)
7/8 in.
(22 m)
1−1/8 in.
(29 m)
L10 LINE
SET
L10−41
20ft. − 50 ft.
(6m − 15 m)
Field
Fabricated
L10−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
L15 LINE
SET
L15 − 41
20 ft. − 50 ft.
(6 m − 15 m)
Field
Fabricated
L15−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
TABLE 7 (Late Models)
HS26
UNIT
−018
−024 −030
−036
−042 −048
−060
NO SCHRADER
SERVICE PORT OPEN TO
LINE SET WHEN FRONT
SEATED AND CLOSED
LIQUID
LINE
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
LIQUID LINE SERVICE VALVE
TO
CONDENSER
COIL
SERVICE
PORT
CAP
(OFF) WHEN BACK
SEATED
SUCTION
LINE
5/8 in.
(16 mm)
3/4 in.
(19 mm)
7/8 in.
(22 m)
1−1/8 in.
(29 m)
L10 LINE
SET
L10−26
20ft. − 50 ft.
(6m − 15 m)
L10−41
20 ft. − 50 ft.
(6m − 15 m)
L10−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
TO LINE
SET
KNIFE EDGE SEAL
VALVE STEM
USE SERVICE
WRENCH
(PART #18P66,
54B64 or 12P95)
STEM CAP
L15 LINE
SET
L15 − 26
20 ft. − 50 ft.
(6 m − 15 m)
L15−41
20 ft. − 50 ft.
(6m − 15m)
L15−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
IMPORTANT
A schrader valve is not provided on the liquid line
service port. Valve must be backseated to turn off
pressure to service port.
FIGURE 10
B−Service Valves (Early Models)
The liquid line and suction line service valves and gauge
ports are accessible by removing the compressor access
cover. Full service liquid and suction line valves are
used.The service ports are used for leak testing, evacuat
ing, charging and checking charge.
1 − Liquid Line Service Valve
A fullservice liquid line valve made by one of several
manufacturers may be used. All liquid line service valves
function the same way, differences are in construction.
Valves are not rebuildable. If a valve has failed it must be
replaced. The liquid line service valve is illustrated in figure
10.
Page 8
The valve is equipped with a service port. There is no
schrader valve installed in the liquid line service port. A ser
vice port cap is supplied to seal off the port.
The liquid line service valve is a front and back seating
valve. When the valve is backseated, the service port is not
open.The service port cap can be removed and gauge
connections can be made.
To Access Service Port:
1− Remove the stem cap. Use a service wrench
(part #18P66, 54B64 or 12P95) to make sure the ser
vice valve is backseated.
CAUTION
The service port cap is used to seal the liquid
line service valve. Access to service port
requires backseating the service valve to
isolate the service port from the system. Failure
to do so will cause refrigerant leakage.
2 − Suction Line (Seating Type) Service Valve
A full service nonbackseating suction line service valve is
used on all early HS26 series units (except 461). Different
manufacturers of valves may be used. All suction line service
valves function the same way, differences are in construction.
Valves are not rebuildable. If a valve has failed it must be
replaced. The suction line service valve is illustrated in
figure 11.
The valve is equipped with a service port. A schrader
valve is factory installed. A service port cap is supplied
to protect the schrader valve from contamination and
assure a leak free seal.
SUCTION LINE SERVICE VALVE (VALVE
INSERT HEX WRENCH
HERE (PART #49A71
(FROM INDOOR COIL)
AND
SERVICE WRENCH)
INLET
OPEN)
SNAP RING
KNIFE
EDGE
SEAL
IMPORTANT
A schrader valve is not provided on the liquid line
service port. Valve must be backseated to turn off
pressure to service port.
2− Remove service port cap and connect high pressure
gauge to service port.
3− Using service wrench, open valve stem (one turn
clockwise) from backseated position.
4− When finished using port, backseat stem with service
wrench. Tighten firmly.
5− Replace service port and stem cap. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Off Service Port:
1− Using service wrench, backseat valve.
a − Turn stem counterclockwise.
b − Tighten firmly, but do not overtighten.
To Open Liquid Line Service Valve:
1− Remove the stem cap with an adjustable wrench.
2− Using service wrench, backseat valve.
a − Turn stem counterclockwise until backseated.
b − Tighten firmly, but do not overtighten.
3− Replace stem cap, finger tighten then tighten an addi
tional 1/6 turn.
To Close Liquid Line Service Valve:
1− Remove the stem cap with an adjustable wrench.
2− Turn the stem in clockwise with a service wrench to
front seat the valve. Tighten firmly.
3−Replace stem cap, finger tighten then tighten an addi
tional 1/6 turn.
SCHRADER VALVE
SERVICE
PORT
CAP
SERVICE PORT
STEM CAP
OUTLET
(TO
COMPRESSOR)
SUCTION LINE SERVICE VALVE (VALVE
SNAP RING
KNIFE EDGE SEAL
(FROM INDOOR COIL)
SCHRADER VALVE
OPEN TO LINE SET
WHEN VALVE IS CLOSED
INLET
SERVICE PORT
SERVICE
PORT
CAP
(FRONT SEATED)
CLOSED)
FIGURE 11
STEM
CAP
INSERT
HEX WRENCH HERE
(PART #49A71 AND
SERVICE
WRENCH)
(VALVE
FRONT SEATED)
OUTLET
(TO
COMPRESSOR)
To Access Schrader Port:
1− Remove service port cap with an adjustable wrench.
2− Connect gauge to the service port.
3− When testing is completed, replace service port
cap. Tighten finger tight, then tighten an additional
1/6 turn.
To Open Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench.
2− Using service wrench and 5/16" hex head extension
(part #49A71) back the stem out counterclockwise until
the valve stem just touches the retaining ring.
Page 9
DANGER
Do not attempt to backseat this valve. Attempts to
backseat this valve will cause snap ring to explode
from valve body under pressure of refrigerant.
Personal injury and unit damage will result.
3− Replace stem cap and tighten firmly. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench.
2− Using service wrench and 5/16" hex head extension
(part #49A71) turn stem in clockwise to seat the valve.
Tighten firmly, but do not overtighten.
3−Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
3 − Suction Line (Ball Type) Service Valve
A balltype full service valve is used on the early model
HS26461 units. This valve is manufactured by Aeroquip. All
suction line service valves function the same way, differences
are in construction. Valves are not rebuildable. If a valve
has failed it must be replaced. A ball valve is illustrated
in figure 12.
The ball valve is equipped with a service port. A schrad
er valve is factory installed. A service port cap is sup
plied to protect the schrader valve from contamination
and assure a leak free seal.
SUCTION LINE (BALL TYPE) SERVICE VALVE
(VALVE OPEN)
USE ADJUSTABLE WRENCH
ROTATE STEM CLOCKWISE 90_ TO CLOSE
ROTATE STEM COUNTERCLOCKWISE 90_ TO OPEN
OUTLET
(TO
COMPRESSOR)
STEM CAP
C−Service Valves (Late Models)
The liquid line and suction line service valves and gauge
ports are accessible by removing the compressor access
cover. Full service liquid and suction line valves are used.
See figures13 and 14. The service ports are used for leak
testing, evacuating, charging and checking charge. Ser
vice valves have a factory installed schrader valve. A ser
vice port cap is supplied to protect the schrader valve from
contamination and assure a leak free seal. Valves are not
rebuildable. If a valve has failed it must be replaced.
LIQUID LINE SERVICE VALVE ALL UNITS
VAPOR LINE SERVICE VALVE
−018, −024, −030, −036, −042, −048
(VALVE OPEN)
INSERT HEX
WRENCH HERE
OUTLET (TO
COMPRESSOR)
SERVICE
PORT
CAP
LIQUID/VAPOR LINE SERVICE
OUTLET (TO
COMPRESSOR)
SER
VICE
PORT
SCHRADE
R
VALV E
VALV E
RETAINING RING
(VALVE CLOSED)
SERVICE
PORT
STEM CAP
INLET (TO
INDOOR COIL)
STEM CAP
INSERT HEX
WRENCH HERE
SERVICE
PORT
CAP
SCHRADE
R VALVE
FIGURE 12
STEM
SERVICE PORT
(FROM INDOOR COIL)
BALL
(SHOWN OPEN)
INLET
SERVICE
PORT CAP
SCHRADER VALVE OPEN
TO LINE SET WHEN VALVE
IS CLOSED (FRONT
SEATED)
FIGURE 13
(TO INDOOR COIL)
(VALVE FRONT
SEATED)
To Access Schrader Port:
1− Remove service port cap with an adjustable wrench.
2− Connect gauge to the service port.
3− When testing is completed, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
Page 10
INLET
To Open Liquid or Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench.
2− Using service wrench and 5/16" hex head extension
back the stem out counterclockwise until the valve stem
just touches the retaining ring.
3− Replace stem cap and tighten finger tight, then tighten
an additional 1/6 turn.
DANGER
Do not attempt to backseat this valve. Attempts to
backseat this valve will cause snap ring to explode
from valve body under pressure of refrigerant.
Personal injury and unit damage will result.
To Close Liquid or Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench.
2−Using service wrench and 5/16" hex head extension, turn
stem clockwise to seat the valve. Tighten firmly, but do not
overtighten.
3− Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
SUCTION LINE (BALL TYPE) SERVICE VALVE
HS26−060 MODEL ONLY
(VALVE OPEN)
USE ADJUSTABLE WRENCH
ROTATE STEM CLOCKWISE 90_ TO CLOSE
ROTATE STEM COUNTERCLOCKWISE 90_ TO OPEN
V−CHARGING
The unit is factory−charged with the amount of R22 refrig
erant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 25
foot (7.6m) line set. For varying lengths of line set, refer to
table 8 for refrigerant charge adjustment for both, early and
late model HS26 units. A blank space is provided on the
unit rating plate to list actual field charge.
TABLE 8
LIQUID LINE
SET DIAMETER
5/16 in. (8mm)2 ounce per 5 ft. (60 ml per 1524 mm)
3/8 in. (10 mm)3 ounce per 5 ft. (90 ml per 1524 mm)
If line set is greater than 25 ft. (7.6m) add this amount. If line set is less
than 25 ft. (7.6m) subtract this amount.
Ounce per 5 ft. (ml per mm) adjust
from 25 ft. (7.6m) line set*
Units are designed for line sets up to 50 ft. (15m).Consult Len
nox Refrigerant Piping Manual for line sets over 50 ft. (15m).
IMPORTANT
If line length is greater than 25 feet (7.6m), add this
amount. If line length is less than 25feet ( 7.6m),
subtract this amount.
A−Leak Testing
1− Attach gauge manifold and connect a drum of dry nitro
gen to center port of gauge manifold.
2− Add a small amount of refrigerant to the lines and
coil. Open high pressure valve on gauge manifold
and pressurize line set and indoor coil to 150 psig
(1034 kPa).
WARNING
OUTLET
(TO
COMPRESSOR)
SERVICE
PORT
CAP
SCHRADE
R VALVE
SERVICE PORT
FIGURE 14
STEM CAP
STEM
BALL
(SHOWN OPEN)
INLET
(FROM INDOOR COIL)
Danger of Explosion.
Can cause injury, death and equipment
damage.
When using dry nitrogen, use a pres
sure−reducing regulator, set at 150 psig
(1034 kPa) or less to prevent excessive
pressure.
3− Check lines and connections for leaks.
NOTEIf electronic leak detector is used, add a trace of re
frigerant to nitrogen for detection by leak detector.
4− Release nitrogen pressure from the system, correct
any leaks and recheck.
B−Evacuating the System
Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Non−condensables such as water vapor, combine
with refrigerant to produce substances that corrode copper
piping and compressor parts.
Page 11
1− Attach gauge manifold and connect vacuum pump
(with vacuum gauge) to center port of gauge man
ifold. With both gauge manifold service valves open,
start pump and evacuate evaporator and refrigerant
lines.
IMPORTANT
A temperature vacuum gauge, mercury vacuum
(U−tube), or thermocouple gauge should be used.
The usual Bourdon tube gauges are not accurate
enough in the vacuum range.
IMPORTANT
The compressor should never be used to evacu
ate a refrigeration or air conditioning system.
CAUTION
Danger of Equipment Damage. Avoid deep vacuum
operation. Do not use compressors to evacuate a
system. Extremely low vacuums can cause internal
arcing and compressor failure. Damage caused by
deep vacuum operation will void warranty.
2− Evacuate the system to an absolute pressure of
.92 inches of mercury, 23 mm of mercury, or 23,000
microns.
3− After system has been evacuated to an absolute
pressure of .92 inches of mercury, 23 mm of mercury,
or 23,000 microns, close manifold valve to center
port.
4− Stop vacuum pump and disconnect from gauge man
ifold. Attach a drum of dry nitrogen to center port of
gauge manifold, open drum valve slightly to purge line,
then break vacuum in system to 3 psig (20.7 kPa) pres
sure by opening manifold high pressure valve to center
port.
5− Close nitrogen drum valve, disconnect drum from
manifold center port and release nitrogen pressure
from system.
6− Reconnect vacuum pump to manifold center port
hose. Evacuate the system to an absolute pressure
less than .197 inches of mercury, 5 mm of mercury, or
5000 microns, then turn off vacuum pump. If the abso
lute pressure rises above .197 inches of mercury, 5
mm of mercury, or 5000 microns within a 20−minute
period after stopping vacuum pump, repeat step 6. If
not, evacuation is complete.
This evacuation procedure is adequate for a new
installation with clean and dry lines. If excessive mois
ture is present, the evacuation process may be re
quired more than once.
7− After evacuation has been completed, close gauge
manifold service valves. Disconnect vacuum pump
from manifold center port and connect refrigerant
drum. Pressurize system slightly with refrigerant to
break vacuum.
IMPORTANT
Use tables 9 and 10 as a general guide for perform
ing maintenance checks. Table 9 is not a procedure
for charging the system. Minor variations in these
pressures may be expected due to differences in
installations. Significant deviations could mean that
the system is not properly charged or that a problem
exists with some component in the system. Used
prudently, tables 9 and 10 could serve as a useful
service guide.
If the system is completely void of refrigerant, the recom
mended and most accurate method of charging is to weigh
the refrigerant into the unit according to the total amount
shown on the unit nameplate. Also refer to the SPECIFI
CATIONS tables on page 1 for early model HS26 units and
page 2 for late model HS26 units.
If weighing facilities are not available or if unit is just low on
charge, the following procedure applies.
The following procedures are intended as a general guide
for use with expansion valve systems only. For best re
sults, indoor temperature should be between
70 °F and 80 °F. Outdoor temperature should be 60 °F or
above. Slight variations in charging temperature and pres
sure should be expected. Large variations may indicate a
need for further servicing.
APPROACH METHOD (TXV SYSTEMS)
(Ambient Temperature of 60_F [16_C] or Above)
1− Connect gauge manifold. Connect an upright HCFC22
drum to center port of gauge manifold.
IMPORTANT
The following procedure requires accurate read
ings of ambient (outdoor) temperature, liquid tem
perature and liquid pressure for proper charging.
Use a thermometer with accuracy of +2 °F and a
pressure gauge with accuracy of +5 PSIG.
2− Record outdoor air (ambient) temperature.
3− Operate indoor and outdoor units in cooling mode. Allow
units to run until system pressures stabilize.
4− Make sure thermometer well is filled with mineral oil be
fore checking liquid line temperature.
5− Place thermometer in well and read liquid line tempera
ture. Liquid line temperature should be a few degrees
warmer than the outdoor air temperature. Tables 11 and
12 show how many degrees warmer the liquid line tem
perature should be.
Add refrigerant to make the liquid line cooler.
Recover refrigerant to make the liquid line warmer.
TABLE 11
APPROACH METHOD − EXPANSION VALVES SYSTEM
MODEL
H2−26−261,3113 + 1 (1.6 + .5)
HS26−4114 + 1 (2.2 + .5)
HS26−4616 + 1 (3.3 + .5)
Liquid Line _F (_C) Warmer Than
Outside Ambient Temperature
TABLE 12
APPROACH METHOD − EXPANSION VALVES SYSTEMS
MODEL
HS26−036, 0485 + 1 (2.8 + .5)
HS26−018, 030, 042, 0608 + 1 (4.44 + .5)
HS26−0249 + 1 (5+ .5)
Liquid Line _F (_C) Warmer Than
Outside Ambient Temperature
6− When unit is properly charged liquid line pressures
should approximate those in table 9 or table 10.
D−Oil Charge
Refer to Table 1 and 2 on page 6.
Page 13
VI−MAINTENANCE
B−Indoor Coil
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
At the beginning of each heating or cooling season, the
system should be cleaned as follows:
A−Outdoor Unit
1− Clean and inspect condenser coil. (Coil may be
flushed with a water hose).
2− Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
IMPORTANT
If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge
checked.
1− Clean coil if necessary.
2− Check connecting lines and coil for oil leaks.
3−Check condensate line and clean if necessary.
C−Indoor Unit
1− Clean or change filters.
2− Adjust blower cooling speed. Check static pressure drop
over coil to determine correct blower CFM. Refer to Len
nox Engineering Handbook.
pole contactors. Capacitor terminal
COM," orange condenser fan wire and
red R" compressor wire are all con
nected to L2 at all times. Remove all
power at disconnect before servicing.
2− Cooling demand energizes thermostat ter
minal Y. Voltage from terminal Y passes
through discharge temperature sensor
(compressor thermostat) and low pressure
switch to energize time delay terminal 2.
3− Time delay action is at the beginning of a
thermostat demand. When energized, time
delay TD1−1 delays 8.5 seconds before en
ergizing TD1−1 terminal 3. When TD1−1 ter
minal 3 is energized, the contactor coil is en
ergized.
4− When compressor contactor is energized,
N.O. contactor contacts close to energize
compressor terminal C" (black wire) and
black condenser fan motor wire. Condens
er fan and compressor immediately begin
operating.
Page 15
B−Unit Diagram HS26−018/060−2P (Late Models)
Operation Sequence
1−Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure
switch and the timed off control (TOC), which energizes K1 compressor contactor coil (provided 5 minute
delay is satisfied).
2−K1−1 and K1−2 contacts close energizing B1 compressor and B4 outdoor fan.
3−When cooling demand is satisfied, K1−1 and K1−2 contacts open de−energizing compressor and outdoor fan.
Timed off control begins 5 minute off time.
Page 16
C−Unit Diagram HS26−018/060−3 & 4−P (Late Models)
Operation Sequence
1−Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure
switch and the timed off control (TOC), which energizes K1 compressor contactor coil (provided 5 minute
delay is satisfied).
2−K1−1 and K1−2 contacts close energizing B1 compressor and B4 outdoor fan.
3−When cooling demand is satisfied, K1−1 and K1−2 contacts open de−energizing compressor and outdoor fan.
1−Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure
switch and timed off control (T.O.C.), which energizes K1 compressor contactor coil (provided 5 minute delay
is satisfied.)
2−K1−1, K1−2 and K1−3 contacts close energizing B1 compressor and B4 outdoor fan.
3−When cooling demand is satisfied, K1−1, K1−2 and K1−3 contacts open de−energizing compressor and out
door fan. Timed off control begins 5 minute off time.
NOTE−Three−phase compressors must be phased correctly. Compressor noise will be significantly higher if phasing is
incorrect. Compressor will operate backwards so unit will not provide cooling. Continued backward operation will cause
compressor to cycle on internal protector.
Page 18
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.