Lennox HS26, HS26-311, HS26-261, HS26-461, HS26-018 Series Manual

...
SERVICE
INFORMATION
Corp. 9622−L12
Revised 04−2002
HS26 SERIES UNITS
The HS26 is a high efficiency residential split−system con densing unit which features a scroll compressor. Early model HS26 units (−261,−311,−411, and −461) are available in sizes ranging from 2 through 3−1/2 tons. Late model HS26 units (−018, −024, −030, −036, −042, −048 and −060) are available in sizes ranging from 1−1/2 through 5 tons. The series is designed for use with an expansion valve in the indoor unit.This manual is divided into sections which discuss the major components, refrigerant system, charg ing procedure, maintenance and operation sequence. In formation in this manual covers both early and late model HS26 units.
All specifications in this manual are subject to change.
UNIT
HS26
Litho U.S.A.
Late Model HS26 shown
SPECIFICATIONS (Early Model)
Model No. HS26−261 HS26−311 HS26−411 HS26−461
Face area (sq.ft.)
Outdoor
Coil
Condenser
Fan
HCFC−22 (charge furnished) Liquid line connection Suction line connection
*Refrigerant charge sufficient for 25 ft. (7.6 m) length of refrigerant lines.
outer / inner Tube diameter (in.)
No. of Rows Fins per inch
Diameter (in.) No. of Blades
Motor hp Cfm RPM
Watts
11.8/5.4 15.9/5.5 15.9/15.3 21.6/20.8
3/8 3/8 3/8 3/8
1.36 1.36 2.0 2.0
20 20 20 20 24 24 24 24
3333
1/6 1/6 1/6 1/6
3150 3150 3000 3230
820 820 820 820 210 210 230 205
7lbs. 11oz. 8lbs. 1oz. 9lbs. 0oz. 11lbs. 3oz.
3/8 3/8 3/8 3/8 3/4 3/4 3/4 11/8
ELECTRICAL DATA (Early Model)
Model No.
Line voltage data − 60hz./1 phase
Rated load amps
Compressor
Condenser Fan Motor
Max fuse or c.b. size (amps) *Minimum circuit ampacity
*Refer to National Electrical Code Manual to determine wire, fuse and disconnect size requirements. NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage
Power factor Locked rotor amps
Full load amps Locked rotor amps
HS26−261 HS26−311 HS26−411 HS26−461
208/230V 208/230V 208/230V 208/230V
11.6 13.5 18.0 20
.96 .96 .96 .97
62.5 76.0 90.5 107
1.1 1.1 1.1 1.1
2.0 2.0 2.0 2.0
25 30 40 45
15.6 18.0 23.6 26.1
Page 1
1996 Lennox Industries Inc.
Net face area
Condenser
Coil
Cond
Condenser Coil
Condenser Coil
Coil
SPECIFICATIONS (Late Model)
Model No. HS26018 HS26024 HS26030 HS26036 HS26042 HS26048 HS26060
Net face area  sq. ft. (m2)
Tube diameter  in. (mm) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9)
No. of rows 1.48 1.48 1.36 1.86 1.86 1.75 2
Fins per inch (m) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866)
Outer coil 11.9 (1.11) 11.9 (1.11) 16.0 (1.59) 16.0 (1.59) 16.0 (1.59) 18.2 (1.69) 21.6 (2.01)
Inner coil 5.5 (0.51) 5.5 (0.51) 5.6 (0.52) 13.3 (1.24) 13.3 (1.24) 13.3 (1.24) 20.8 (1.93)
Dia. − in. (mm) no. of blades 20 (508) − 4 20 (508) − 4 24 (610) − 3 24 (610) − 3 24 (610) − 3
Motor hp (W) 1/10 (75) 1/6 (124) 1/6 (124) 1/6 (124) 1/6 (124) 1/4 (187) 1/4 (187)
enser
Fan Cfm (L/s) 2500 (1180) 2450 (1155) 3150 (1485) 3150 (1485) 3000 (1415) 3900 (1840) 4200 (1980)
Rpm 825 825 825 825 825 820 820
Watts 160 210 225 225 230 310 350
*Refrigerant  HCFC22 charge furnished
Liquid line (o.d.)  in. (mm) sweat 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Suction line (o.d.) in.  (mm) sweat 5/8 (16) 3/4 (19) 3/4 (19) 3/4 (19) 7/8 (22.2) 7/8 (22.2) 11/8 (28.6)
Shipping weight  lbs. (kg) 1 package 177 (80) 185 (84) 192 (87) 221 (100) 231 (105) 274 (124) 308 (140)
*Refrigerant charge sufficient for 25 ft. (7.6 m) length of refrigerant lines.
4 lbs. 1 oz.
(1.84 kg)
4 lbs. 1 oz.
(1.84 kg)
5 lbs. 1 oz.
(2.30 kg)
5 lbs. 13 oz.
(2.64 kg)
6 lbs. 11 oz.
(3.03 kg)
24 (610) 424 (610) 
7 lbs. 5 oz.
(3.32 kg)
4
10 lbs. 8 oz.
(4.76 kg)
ELECTRICAL DATA (Late Model)
Model No. HS26018 HS26024 HS26030 HS26036 HS26042
Line voltage data  60hz
Rated load amps 8.4 10.3 13.5 16.0 10.3 18.0 12.5
Compressor Power factor 0.97 0.96 0.96 0.96 0.82 0.94 0.82
Locked rotor amps 47 56 72.5 88 77 104 88
Condenser Coil
Fan Motor
Rec. max. fuse or circuit breaker size (amps) 15 20 30 35 20 40 25
*Minimum circuit ampacity 13 14 18 21.3 14 23.6 16.4
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
Full load amps 0.8 1.1 1.1 1.1 1.1 1.1 1.1
Locked rotor amps 1.6 2.0 2.0 2.0 2.0 2.0 2.0
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
3ph
208/230v
1ph
208/230v
3ph
ELECTRICAL DATA (Late Model)
Model No. HS26048 HS26060
Line voltage data  60hz
Rated load amps 23.7 13.5 7.4 28.8 17.4 9.0
Compressor Power factor .97 .87 .87 .97 .85 .85
Locked rotor amps 129 99 49.5 169 123 62
Condenser Coil
Fan Motor
Rec. max. fuse or circuit breaker size (amps) 50 30 15 60 40 20
*Minimum circuit ampacity 31.4 18.6 10.4 37.7 23.5 12.4
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
Full load amps 1.7 1.7 1.1 1.7 1.7 1.1
Locked rotor amps 3.1 3.1 2.2 3.1 3.1 2.2
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
Page 2
DISCHARGE
SUCTION

SCROLL COMPRESSOR

SCROLL FORM
CROSS−SECTION OF SCROLLS
DISCHARGE
DISCHARGE PRESSURE
FIGURE 2
STATIONARY SCROLL
SUCTION
Early Model HS26 Compressor shown
FIGURE 1
I−APPLICATION
All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the Engineering Handbook for approved system matchups. A misapplied system will cause erratic operation and can re sult in early compressor failure.
II−SCROLL COMPRESSOR
The scroll compressor design is simple, efficient and re quires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 1.The scrolls are located in the top of the compressor can and the motor is located just below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 2 shows the basic scroll form. Two iden tical scrolls are mated together forming concentric spiral shapes (figure 3 ). One scroll remains stationary, while the other is allowed to orbit" (figure 4). Note that the orbiting scroll does not rotate or turn but merely orbits" the station ary scroll.
TIPS SEALED BY DISCHARGE PRESSURE
ORBITING SCROLL
FIGURE 3
The counterclockwise orbiting scroll draws gas into the out er crescent shaped gas pocket created by the two scrolls (figure 4 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 4 − 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 4
−3). When the compressed gas reaches the center, it is dis charged vertically into a chamber and discharge port in the top of the compressor (figure1). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 3 ). During a single orbit, several pockets of gas are compressed simultaneous ly providing smooth continuous compression. The scroll compressor is tolerant to the effects of liquid re turn. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. If the compressor is replaced, conventional Lennox cleanup practices must be used. Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating com pressors. Deep vacuum operation can cause internal fu site arcing resulting in damaged internal parts and will re sult in compressor failure. Never use a scroll compressor for evacuating or pumping−down" the system. This type of damage can be detected and will result in denial of warran ty claims.
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
Page 3
SUCTION
POCKET
HOW A SCROLL WORKS
MOVEMENT OF ORBIT
SUCTION
ORBITING
SCROLL
SUCTION
INTERMEDIATE
PRESSURE
GAS
CRESCENT
SHAPED GAS
POCKET
12
FLANKS
STATIONARY SCROLL
SUCTION
SEALED BY
CENTRIFUGAL
FORCE
SUCTION
34
HIGH
PRESSURE
GAS
FIGURE4
III−UNIT COMPONENTS A−Transformer
The contactor coil, time delay and temperature sensor are all energized by 24VAC supplied by the indoor unit. All other controls in the outdoor unit are powered by line voltage. Refer to unit wiring diagram. The HS26 is not equipped with an internal line voltage to 24V transform er.
B−Contactor
The compressor is energized by a contactor located in the control box. Early model units use single−pole contactors.Late model single−phase units use single pole and two−pole con tactors. See wiring diagrams for specific unit. Late model three−phase units use three−pole contactors. The contactor is energized by indoor thermostat terminal Y when thermostat demand is present.
DISCHARGE
POCKET
CAUTION
Some HS26 units use single−pole contactors. One leg of the compressor, capacitor and condenser fan are connected to line voltage at all times. Po tential exists for electrical shock resulting in inju ry or death. Remove all power at disconnect be fore servicing
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
Page 4
C−TD1−1 Time Delay (Early Models)
Some early model HS26 units are equipped with a Lennox− built TD1−1 time delay located in the control box (figure 5). The time delay is electrically connected between thermostat terminal Y and the compressor contactor. On initial thermo stat demand, the compressor contactor is delayed for 8.5 seconds. At the end of the delay, the compressor is allowed to energize. When thermostat demand is satisfied, the time delay opens the circuit to the compressor contactor coil and the compressor is de−energized.
The time delay performs no other functions. Without the delay it would be possible to short cycle the compressor. A scroll compressor, when short cycled, can run backward if head pressure is still high. It does not harm a scroll com pressor to run backward, but it could cause a nuisance trip of safety limits (internal overload). For this reason, if a TD1−1 delay should fail, it must be replaced. Do not bypass the control.
D−TOC Timed Off Control (Early and Late Models)
Some early and all late model HS26 units are equipped with a TOC, timed off control.The TOC is located in the control box (figure 6). The time delay is electrically connected be tween thermostat terminal Y and the compressor contactor. Between cycles, the compressor contactor is delayed for 5 minutes + 2 minutes. At the end of the delay, the compres sor is allowed to energize. When thermostat demand is sat isfied, the time delay opens the circuit to the compressor contactor coil and the compressor is de−energized. Without the time delay it would be possible to short cycle the com pressor. A scroll compressor, when short cycled, can run backward if head pressure is still high. It does not harm a scroll compressor to run backward, but it could cause a nui sance tripout of safety limits. For this reason, if a TOC fails it must be replaced.
DANGER
DO NOT ATTEMPT TO REPAIR THE TD1−1 OR THE TOC CONTROL. UNSAFE OPERATION WILL RE SULT. IF THE CONTROL IS FOUND TO BE INOP ERATIVE, SIMPLY REPLACE IT.
CONDENSER FAN
(NOT SHOWN)
TOP OF CABINET
DUAL CAPACITOR
THERMOMETER
WELL
COMPRESSOR TEMPERATURE
SENSOR
HIGH
PRESSURE
SWITCH
COMPRESSOR
COMPRESSOR
TERMINAL BOX
HS26 UNIT COMPONENTS (EARLY MODEL)
TD−1 TIME DELAY OR T.O.C. TIMED OFF CONTROL
CONTACTOR
LIQUID LINE
SERVICE VALVE
AND GAUGE PORT
SUCTION
VALV E
AND GAUGE PORT
LOW PRES
SURE SWITCH
ACCUMULATOR (411, 461 only
all others equipped
with suction muffler)
FIGURE 5
Page 5
CONDENSER FAN
(NOT SHOWN)
TOP OF CABINET
PARTS ARRANGEMENT FOR HS26 (LATE MODEL)
TIMED OFF CONTROL (TOC)
GROUND LUG
DUAL CAPACITOR
TERMINAL BOX
THERMOME
TER
WELL
HIGH PRESSURE
SWITCH
FIGURE 6
E−Compressor
Tables1 and 2 show the specifications for compressors used in HS26 series units.
F−Compressor High Temperature Limit (Early Models)
Each scroll compressor in the HS26−261, −311, −411, −461 is equipped with a compressor high temperature limit lo cated on the outside top of the compressor. The sensor is a SPST thermostat which opens when the discharge tem perature exceeds 280_F + 8_F (138_C + 4.5_C) on a tem perature rise. When the switch opens, the circuit to the compressor contactor and the time delay is de−energized and the unit shuts off. The switch automatically resets when the compressor temperature drops below 130_F + 14_F. (54_C + 8_C)
The sensor can be accessed by prying off the snap plug on top of the compressor (see figure 7). Make sure to securely seal the limit after replacement. The limit pigtails are lo cated inside the unit control box. Figure 8 shows the ar rangement of compressor line voltage terminals and dis charge sensor pigtails.
CONTACTOR
SUCTION VALVE
AND GAUGE PORT
LIQUID LINE
SERVICE VALVE
AND GAUGE
PORT
COMPRESSOR
LOW PRESSURE
SWITCH
Table 1 (Early Models)
HS 26
Unit
−261 208/230 1 62.5 11.6 28*
−311 208/230 1 76.0 13.5 28*
−411 208/230 1 90.5 18.0 34*
−461 208/230 1 107 20.0 38*
*Shipped with conventional white oil (Sontex 200LT). 3GS oil may be used if additional oil is required.
Vac Phase LRA RLA Oil fl.oz.
Table 2 (Late Models)
HS26
Unit
−018 208/230 1 47.0 8.4 38*
−024 208/230 1 56.0 10.3 30*
−030 208/230 1 72.5 13.5 30*
−036 208/230 1 88.0 16.0 42*
−042 208/230 1 104.0 18.0 42*
−048 208/230 1 129.0 23.7 53*
−060 208/230 1 169.0 28.8 50*
−036 208/230 3 88.8 10.3 42*
−042 208/230 3 77.0 12.5 42*
−048 208/230 3 99.0 13.5 53*
−048 460 3 49.5 7.4 53*
−060 208/230 3 123.0 17.4 53*
−060 460 3 62.0 9.0 53*
*Shipped with conventional white oil (Sontex 200LT). 3GS oil may be used if additional oil is required.
Vac Phase LRA RLA Oil fl. oz.
Page 6
COMPRESSOR HIGH TEMPERATURE LIMIT CHANGEOUT (EARLY MODELS ONLY)
PLASTIC CAP
SEALANT
(BLUE)
PRONG
THERMAL
GREASE
(WHITE)
COMPRESSOR
GROMMET
LIMIT
(THERMOSTAT)
FIGURE 7
G−High/Low Pressure Switch
A manualreset singlepole singlethrow high pressure switch located in the liquid line, shuts off the compressor when liquid line pressure rises above the factory setting. The switch is nor mally closed and is permanently adjusted to trip (open) at 410 + 10 psi. See figure 5 or 6 for switch location
COMPRESSOR TERMINAL BOX
DISCHARGE TEMPERATURE
SENSOR WIRES
TO CONTROL BOX
(TO COMP. TERM. BOX IN
461 UNITS)
EARLY MODELS ONLY
COMPRESSOR
TERMINALS
C
S
R
WARNING
COMPRESSOR MUST BE GROUNDED. DO NOT OPERATE WITHOUT PROTECTIVE COV ER OVER TERMINALS. DISCONNECT ALL POWER BEFORE REMOVING PROTECTIVE COVER. DISCHARGE CAPACITORS BEFORE SERVICING UNIT. COMPRESSOR WIRING DIA GRAM IS FURNISHED INSIDE COMPRESSOR TERMINAL BOX COVER. FAILURE TO FOL LOW THESE PRECAUTIONS COULD CAUSE ELECTRICAL SHOCK RESULTING IN INJURY OR DEATH.
FIGURE 8
Instructions
1 With power off, disconnect wiring to limit. 2 Dislodge limit/cap assembly from compressor. Plastic cap and silicone seal
will break away. Discard all pieces.
3 Remove thermostat and grommet from compressor. Thoroughly clean all
blue adhesive and white silicone thermal grease from compressor and the inside of the thermostat tube. Thermostat tube should be clean and free of debris.
4 Using Lennox kit 93G8601, dip end of thermostat into plastic bottle labeled
Silicone Thermal Grease G.E. #G641" and coat end of thermostat. Care fully insert thermostat/grommet assembly into thermostat tube of compres sor. Avoid contact with top of compressor.
5 Clean excess thermal grease from under cap lip and top lip of compressor
opening.
6 Install protector assembly as shown, feeding wire leads through channel
provided in cap.
7 Apply a bead of sealant around lip of cap at area shown in illustration and
into the thermostat tube area.
8 Install assembly as shown. Align wires to channel in compressor shell. Suf
ficient force is required to snap plastic cap into tube to engage all three
prongs. 9 Reconnect wiring. 10After completing thermostat replacement, discard remaining parts.
An autoreset singlepole singlethrow low pressure switch located in the suction line shuts off the compressor when suction pressure drops below the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 25 + 5 psi. The switch automatically resets when suction line pressure rises above 55 + 5 psi. See fig ure 5 or 6 for switch location.
H−Dual Capacitor
The compressor and fan in HS26 single−phase units use permanent split capacitor motors. A single dual" capacitor is used for both the fan motor and the compressor (see unit wiring diagram). The fan side of the capacitor and the com pressor side of the capacitor have different mfd ratings. The capacitor is located inside the unit control box (see figure 5 or 6). Tables 3 and 4 show the ratings of the dual capacitor.
TABLE 3 (Early Models)
HS26 DUAL CAPACITOR RATING
UNITS
HS26−261 5 30 370
HS26−311 5 35 370
HS26−411,−461 5 35 440
TABLE 4 (Late Models)
HS26 DUAL CAPACITOR RATING
UNITS FAN MFD HERM MFD VAC
HS26−018 4 30 370
HS26−024,−030 5 40 370
HS26−036 5 50 370
HS26−042 5 55 370
HS26−048 7.5 60 370
HS26−060 10 80 370
FAN
MFD
HERM MFD VA C
Page 7
I−Condenser Fan Motor
018
024
261
7/8"
030, 311, 036,
1−1/16"
048
060
1−3/16"
All units use single−phase PSC fan motors which require a run capacitor. The FAN" side of the dual capacitor is used for this purpose. The specifications tables on page 1 and 2 of this manual show the specifications of outdoor fans used in HS26s. In all units, the outdoor fan is controlled by the compressor contactor. See figure 9 if condenser fan motor replacement is necessary.
"A" SEE TABLE 5
Condenser fan and motor
FAN GUARD
Wiring
Drip loop
FIGURE 9
TABLE 5
HS26 UNIT "A" DIM. + 1/8" Fan Blade Ven
, −
, −
−030, −311, −036,
−411, −042, −461
,
"
"
1−3/4" Lau
1−1/2" Revcor
"
dor
Lau
Revcor
Lau
Revcor
Lau
Revcor
IV−REFRIGERANT SYSTEM A−Plumbing
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections). Use Lennox L10 or L15 series line sets as shown in table 6 or 7 for field− fabricated refrigerant lines. Refer to the piping section of the Lennox Service Unit Information Manual (SUI−803−L9) for proper size, type and application of field−fabricated lines. Separate discharge and suction service ports are provided at the compressor for connection of gauge manifold during charging procedure.
TABLE 6 (Early Models)
HS26
UNIT
−261, −311,
−411
−461
−511
−651
LIQUID
LINE
3/8 in.
(10 MM)
3/8 in.
(10 MM)
3/8 in.
(10 MM)
3/8 in.
(10 MM)
SUCTION
LINE
3/4 in.
(19 mm)
1−1/8 in.
(29 m)
7/8 in. (22 m)
1−1/8 in.
(29 m)
L10 LINE
SET
L10−41
20ft. − 50 ft.
(6m − 15 m)
Field
Fabricated
L10−65 30 ft. − 50 ft. (9 m − 15m)
Field
Fabricated
L15 LINE
SET
L15 − 41 20 ft. − 50 ft. (6 m − 15 m)
Field
Fabricated
L15−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
TABLE 7 (Late Models)
HS26
UNIT
−018
−024 −030
−036
−042 −048
−060
NO SCHRADER
SERVICE PORT OPEN TO
LINE SET WHEN FRONT
SEATED AND CLOSED
LIQUID
LINE
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
LIQUID LINE SERVICE VALVE
TO
CONDENSER
COIL
SERVICE
PORT
CAP
(OFF) WHEN BACK
SEATED
SUCTION
LINE
5/8 in.
(16 mm)
3/4 in.
(19 mm)
7/8 in. (22 m)
1−1/8 in.
(29 m)
L10 LINE
SET
L10−26 20ft. − 50 ft. (6m − 15 m)
L10−41
20 ft. − 50 ft.
(6m − 15 m)
L10−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
TO LINE
SET
KNIFE EDGE SEAL
VALVE STEM
USE SERVICE
WRENCH
(PART #18P66,
54B64 or 12P95)
STEM CAP
L15 LINE
SET
L15 − 26 20 ft. − 50 ft. (6 m − 15 m)
L15−41
20 ft. − 50 ft.
(6m − 15m)
L15−65
30 ft. − 50 ft.
(9 m − 15m)
Field
Fabricated
IMPORTANT
A schrader valve is not provided on the liquid line service port. Valve must be backseated to turn off pressure to service port.
FIGURE 10
B−Service Valves (Early Models)
The liquid line and suction line service valves and gauge ports are accessible by removing the compressor access cover. Full service liquid and suction line valves are used.The service ports are used for leak testing, evacuat ing, charging and checking charge.
1 − Liquid Line Service Valve
A fullservice liquid line valve made by one of several manufacturers may be used. All liquid line service valves function the same way, differences are in construction. Valves are not rebuildable. If a valve has failed it must be replaced. The liquid line service valve is illustrated in figure
10.
Page 8
The valve is equipped with a service port. There is no schrader valve installed in the liquid line service port. A ser vice port cap is supplied to seal off the port.
The liquid line service valve is a front and back seating valve. When the valve is backseated, the service port is not open.The service port cap can be removed and gauge connections can be made.
To Access Service Port:
1− Remove the stem cap. Use a service wrench
(part #18P66, 54B64 or 12P95) to make sure the ser vice valve is backseated.
CAUTION
The service port cap is used to seal the liquid line service valve. Access to service port requires backseating the service valve to isolate the service port from the system. Failure to do so will cause refrigerant leakage.
2 − Suction Line (Seating Type) Service Valve
A full service nonbackseating suction line service valve is used on all early HS26 series units (except 461). Different manufacturers of valves may be used. All suction line service valves function the same way, differences are in construction.
Valves are not rebuildable. If a valve has failed it must be replaced. The suction line service valve is illustrated in figure 11.
The valve is equipped with a service port. A schrader valve is factory installed. A service port cap is supplied to protect the schrader valve from contamination and assure a leak free seal.
SUCTION LINE SERVICE VALVE (VALVE
INSERT HEX WRENCH
HERE (PART #49A71
(FROM INDOOR COIL)
AND
SERVICE WRENCH)
INLET
OPEN)
SNAP RING
KNIFE EDGE
SEAL
IMPORTANT
A schrader valve is not provided on the liquid line service port. Valve must be backseated to turn off pressure to service port.
2− Remove service port cap and connect high pressure
gauge to service port.
3− Using service wrench, open valve stem (one turn
clockwise) from backseated position.
4− When finished using port, backseat stem with service
wrench. Tighten firmly.
5− Replace service port and stem cap. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Off Service Port:
1− Using service wrench, backseat valve.
a − Turn stem counterclockwise. b − Tighten firmly, but do not overtighten.
To Open Liquid Line Service Valve:
1− Remove the stem cap with an adjustable wrench. 2− Using service wrench, backseat valve.
a − Turn stem counterclockwise until backseated. b − Tighten firmly, but do not overtighten.
3− Replace stem cap, finger tighten then tighten an addi
tional 1/6 turn.
To Close Liquid Line Service Valve:
1− Remove the stem cap with an adjustable wrench. 2− Turn the stem in clockwise with a service wrench to
front seat the valve. Tighten firmly.
3− Replace stem cap, finger tighten then tighten an addi
tional 1/6 turn.
SCHRADER VALVE
SERVICE
PORT
CAP
SERVICE PORT
STEM CAP
OUTLET
(TO
COMPRESSOR)
SUCTION LINE SERVICE VALVE (VALVE
SNAP RING
KNIFE EDGE SEAL
(FROM INDOOR COIL)
SCHRADER VALVE OPEN TO LINE SET
WHEN VALVE IS CLOSED
INLET
SERVICE PORT
SERVICE
PORT
CAP
(FRONT SEATED)
CLOSED)
FIGURE 11
STEM
CAP
INSERT
HEX WRENCH HERE
(PART #49A71 AND
SERVICE
WRENCH)
(VALVE
FRONT SEATED)
OUTLET
(TO
COMPRESSOR)
To Access Schrader Port:
1− Remove service port cap with an adjustable wrench. 2− Connect gauge to the service port. 3− When testing is completed, replace service port
cap. Tighten finger tight, then tighten an additional 1/6 turn.
To Open Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench. 2− Using service wrench and 5/16" hex head extension
(part #49A71) back the stem out counterclockwise until the valve stem just touches the retaining ring.
Page 9
DANGER
Do not attempt to backseat this valve. Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant. Personal injury and unit damage will result.
3− Replace stem cap and tighten firmly. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench. 2− Using service wrench and 5/16" hex head extension
(part #49A71) turn stem in clockwise to seat the valve. Tighten firmly, but do not overtighten.
3− Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
3 − Suction Line (Ball Type) Service Valve
A balltype full service valve is used on the early model HS26461 units. This valve is manufactured by Aeroquip. All suction line service valves function the same way, differences are in construction. Valves are not rebuildable. If a valve has failed it must be replaced. A ball valve is illustrated in figure 12.
The ball valve is equipped with a service port. A schrad er valve is factory installed. A service port cap is sup plied to protect the schrader valve from contamination and assure a leak free seal.
SUCTION LINE (BALL TYPE) SERVICE VALVE
(VALVE OPEN)
USE ADJUSTABLE WRENCH
ROTATE STEM CLOCKWISE 90_ TO CLOSE
ROTATE STEM COUNTERCLOCKWISE 90_ TO OPEN
OUTLET
(TO
COMPRESSOR)
STEM CAP
C−Service Valves (Late Models)
The liquid line and suction line service valves and gauge ports are accessible by removing the compressor access cover. Full service liquid and suction line valves are used. See figures13 and 14. The service ports are used for leak testing, evacuating, charging and checking charge. Ser vice valves have a factory installed schrader valve. A ser vice port cap is supplied to protect the schrader valve from contamination and assure a leak free seal. Valves are not rebuildable. If a valve has failed it must be replaced.
LIQUID LINE SERVICE VALVE ALL UNITS
VAPOR LINE SERVICE VALVE
−018, −024, −030, −036, −042, −048 (VALVE OPEN)
INSERT HEX
WRENCH HERE
OUTLET (TO
COMPRESSOR)
SERVICE
PORT
CAP
LIQUID/VAPOR LINE SERVICE
OUTLET (TO
COMPRESSOR)
SER VICE
PORT
SCHRADE
R
VALV E
VALV E
RETAINING RING
(VALVE CLOSED)
SERVICE
PORT
STEM CAP
INLET (TO
INDOOR COIL)
STEM CAP
INSERT HEX
WRENCH HERE
SERVICE
PORT
CAP
SCHRADE
R VALVE
FIGURE 12
STEM
SERVICE PORT
(FROM INDOOR COIL)
BALL
(SHOWN OPEN)
INLET
SERVICE
PORT CAP
SCHRADER VALVE OPEN
TO LINE SET WHEN VALVE
IS CLOSED (FRONT
SEATED)
FIGURE 13
(TO INDOOR COIL)
(VALVE FRONT
SEATED)
To Access Schrader Port:
1− Remove service port cap with an adjustable wrench.
2− Connect gauge to the service port.
3− When testing is completed, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
Page 10
INLET
To Open Liquid or Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench.
2− Using service wrench and 5/16" hex head extension
back the stem out counterclockwise until the valve stem just touches the retaining ring.
3− Replace stem cap and tighten finger tight, then tighten
an additional 1/6 turn.
DANGER
Do not attempt to backseat this valve. Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant. Personal injury and unit damage will result.
To Close Liquid or Suction Line Service Valve:
1− Remove stem cap with an adjustable wrench.
2−Using service wrench and 5/16" hex head extension, turn
stem clockwise to seat the valve. Tighten firmly, but do not overtighten.
3− Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
SUCTION LINE (BALL TYPE) SERVICE VALVE
HS26−060 MODEL ONLY
(VALVE OPEN)
USE ADJUSTABLE WRENCH
ROTATE STEM CLOCKWISE 90_ TO CLOSE
ROTATE STEM COUNTERCLOCKWISE 90_ TO OPEN
V−CHARGING
The unit is factory−charged with the amount of R22 refrig erant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 25 foot (7.6m) line set. For varying lengths of line set, refer to table 8 for refrigerant charge adjustment for both, early and late model HS26 units. A blank space is provided on the unit rating plate to list actual field charge.
TABLE 8
LIQUID LINE
SET DIAMETER
5/16 in. (8mm) 2 ounce per 5 ft. (60 ml per 1524 mm)
3/8 in. (10 mm) 3 ounce per 5 ft. (90 ml per 1524 mm)
If line set is greater than 25 ft. (7.6m) add this amount. If line set is less than 25 ft. (7.6m) subtract this amount.
Ounce per 5 ft. (ml per mm) adjust
from 25 ft. (7.6m) line set*
Units are designed for line sets up to 50 ft. (15m).Consult Len nox Refrigerant Piping Manual for line sets over 50 ft. (15m).
IMPORTANT
If line length is greater than 25 feet (7.6m), add this amount. If line length is less than 25feet ( 7.6m), subtract this amount.
A−Leak Testing
1− Attach gauge manifold and connect a drum of dry nitro
gen to center port of gauge manifold.
2− Add a small amount of refrigerant to the lines and
coil. Open high pressure valve on gauge manifold and pressurize line set and indoor coil to 150 psig (1034 kPa).
WARNING
OUTLET
(TO
COMPRESSOR)
SERVICE
PORT
CAP
SCHRADE
R VALVE
SERVICE PORT
FIGURE 14
STEM CAP
STEM
BALL
(SHOWN OPEN)
INLET
(FROM INDOOR COIL)
Danger of Explosion. Can cause injury, death and equipment damage. When using dry nitrogen, use a pres sure−reducing regulator, set at 150 psig (1034 kPa) or less to prevent excessive pressure.
3− Check lines and connections for leaks.
NOTEIf electronic leak detector is used, add a trace of re frigerant to nitrogen for detection by leak detector.
4− Release nitrogen pressure from the system, correct
any leaks and recheck.
B−Evacuating the System
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables such as water vapor, combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Page 11
1− Attach gauge manifold and connect vacuum pump
(with vacuum gauge) to center port of gauge man ifold. With both gauge manifold service valves open, start pump and evacuate evaporator and refrigerant lines.
IMPORTANT
A temperature vacuum gauge, mercury vacuum (U−tube), or thermocouple gauge should be used. The usual Bourdon tube gauges are not accurate enough in the vacuum range.
IMPORTANT
The compressor should never be used to evacu ate a refrigeration or air conditioning system.
CAUTION
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
2− Evacuate the system to an absolute pressure of
.92 inches of mercury, 23 mm of mercury, or 23,000 microns.
3− After system has been evacuated to an absolute
pressure of .92 inches of mercury, 23 mm of mercury, or 23,000 microns, close manifold valve to center port.
4− Stop vacuum pump and disconnect from gauge man
ifold. Attach a drum of dry nitrogen to center port of gauge manifold, open drum valve slightly to purge line, then break vacuum in system to 3 psig (20.7 kPa) pres sure by opening manifold high pressure valve to center port.
5− Close nitrogen drum valve, disconnect drum from
manifold center port and release nitrogen pressure from system.
6− Reconnect vacuum pump to manifold center port
hose. Evacuate the system to an absolute pressure less than .197 inches of mercury, 5 mm of mercury, or 5000 microns, then turn off vacuum pump. If the abso lute pressure rises above .197 inches of mercury, 5 mm of mercury, or 5000 microns within a 20−minute period after stopping vacuum pump, repeat step 6. If not, evacuation is complete. This evacuation procedure is adequate for a new installation with clean and dry lines. If excessive mois ture is present, the evacuation process may be re quired more than once.
7− After evacuation has been completed, close gauge
manifold service valves. Disconnect vacuum pump from manifold center port and connect refrigerant drum. Pressurize system slightly with refrigerant to break vacuum.
IMPORTANT
Use tables 9 and 10 as a general guide for perform ing maintenance checks. Table 9 is not a procedure for charging the system. Minor variations in these pressures may be expected due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system. Used prudently, tables 9 and 10 could serve as a useful service guide.
OUTDOOR
TEMP. (_F)
65 75
85 95
105
C−Charging
TABLE 9 (Early Models)
HS26−261 HS26−311 HS26−411
LIQ.
+ 10
PSIG PSIG
141 163 191 220 255
SUC.
+ 10
77 79 80 82 83
NORMAL OPERATING PRESSURES
LIQ.
+ 10
PSIG PSIG
140 160 186 216 254
SUC.
+ 10
69 74 78 80 81
LIQ.
+ 10
PSIG PSIG
Page 12
141 167 195
225 260
SUC.
+ 10
75 77 79
80 81
HS26−461
LIQ.
+ 10
PSIG PSIG
140 170 170 223 261
SUC.
+ 10
62 77 77 80 81
OUTDOOR TEMP. (_F)
65 75 85
95
105
TABLE 10 (Late Models)
NORMAL OPERATING PRESSURES
HS26−018 HS26−024 HS26−030 HS26−036 HS26−042 HS26−048 HS26−060
Liq.+
10 psig
142 167 194
223
256
Suct.+
5 psig
75 76 77
78
79
Liq.+
10 psig
143 168 196
226
260
Suct.+ 5 psig
Liq.+
10 psig
76 77 78
79
80
Suct.+
5 psig
139 163 191
223
255
Liq.+
10 psig
72 73 74
76
77
Suct.+ 5 psig
138 164 192
223
256
Liq.+
10 psig
70 71 72
73
75
Suct.+
5 psig
141 166 186
227
261
Liq.+
10 psig
74 75 76
78
79
Suct.+
5 psig
130 156 175
216
251
Liq.+
10 psig
71 72 73
75
77
171 196 225
232
251
Suct.+
5 psig
73 74 75
76
77
If the system is completely void of refrigerant, the recom mended and most accurate method of charging is to weigh the refrigerant into the unit according to the total amount shown on the unit nameplate. Also refer to the SPECIFI CATIONS tables on page 1 for early model HS26 units and page 2 for late model HS26 units.
If weighing facilities are not available or if unit is just low on charge, the following procedure applies.
The following procedures are intended as a general guide for use with expansion valve systems only. For best re sults, indoor temperature should be between 70 °F and 80 °F. Outdoor temperature should be 60 °F or above. Slight variations in charging temperature and pres sure should be expected. Large variations may indicate a need for further servicing.
APPROACH METHOD (TXV SYSTEMS)
(Ambient Temperature of 60_F [16_C] or Above)
1− Connect gauge manifold. Connect an upright HCFC22
drum to center port of gauge manifold.
IMPORTANT
The following procedure requires accurate read ings of ambient (outdoor) temperature, liquid tem perature and liquid pressure for proper charging. Use a thermometer with accuracy of +2 °F and a pressure gauge with accuracy of +5 PSIG.
2− Record outdoor air (ambient) temperature. 3− Operate indoor and outdoor units in cooling mode. Allow
units to run until system pressures stabilize.
4− Make sure thermometer well is filled with mineral oil be
fore checking liquid line temperature.
5− Place thermometer in well and read liquid line tempera
ture. Liquid line temperature should be a few degrees warmer than the outdoor air temperature. Tables 11 and 12 show how many degrees warmer the liquid line tem perature should be.
Add refrigerant to make the liquid line cooler. Recover refrigerant to make the liquid line warmer.
TABLE 11
APPROACH METHOD − EXPANSION VALVES SYSTEM
MODEL
H2−26−261,311 3 + 1 (1.6 + .5)
HS26−411 4 + 1 (2.2 + .5)
HS26−461 6 + 1 (3.3 + .5)
Liquid Line _F (_C) Warmer Than
Outside Ambient Temperature
TABLE 12
APPROACH METHOD − EXPANSION VALVES SYSTEMS
MODEL
HS26−036, 048 5 + 1 (2.8 + .5)
HS26−018, 030, 042, 060 8 + 1 (4.44 + .5)
HS26−024 9 + 1 (5+ .5)
Liquid Line _F (_C) Warmer Than
Outside Ambient Temperature
6− When unit is properly charged liquid line pressures
should approximate those in table 9 or table 10.
D−Oil Charge
Refer to Table 1 and 2 on page 6.
Page 13
VI−MAINTENANCE
B−Indoor Coil
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
At the beginning of each heating or cooling season, the system should be cleaned as follows:
A−Outdoor Unit
1− Clean and inspect condenser coil. (Coil may be
flushed with a water hose).
2− Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
IMPORTANT
If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge checked.
1− Clean coil if necessary.
2− Check connecting lines and coil for oil leaks.
3−Check condensate line and clean if necessary.
C−Indoor Unit
1− Clean or change filters.
2− Adjust blower cooling speed. Check static pressure drop
over coil to determine correct blower CFM. Refer to Len nox Engineering Handbook.
3− Belt Drive BlowersCheck condition/tension.
4− Check all wiring for loose connections.
5− Check for correct voltage at unit.
6− Check amp−draw on blower motor.
Unit nameplate_________Actual_________.
Page 14
VII−DIAGRAMS / OPERATING SEQUENCE A−Unit Diagram HS26−261/461−1P (Early Models)
UNIT DIAGRAM
2
3
1
4
Operation Sequence
1− WARNING−Early HS26 units use single−
pole contactors. Capacitor terminal COM," orange condenser fan wire and red R" compressor wire are all con nected to L2 at all times. Remove all power at disconnect before servicing.
2− Cooling demand energizes thermostat ter
minal Y. Voltage from terminal Y passes through discharge temperature sensor (compressor thermostat) and low pressure switch to energize time delay terminal 2.
3− Time delay action is at the beginning of a
thermostat demand. When energized, time delay TD1−1 delays 8.5 seconds before en ergizing TD1−1 terminal 3. When TD1−1 ter minal 3 is energized, the contactor coil is en ergized.
4− When compressor contactor is energized,
N.O. contactor contacts close to energize compressor terminal C" (black wire) and black condenser fan motor wire. Condens er fan and compressor immediately begin operating.
Page 15
B−Unit Diagram HS26−018/060−2P (Late Models)
Operation Sequence
1− Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure
switch and the timed off control (TOC), which energizes K1 compressor contactor coil (provided 5 minute
delay is satisfied). 2− K1−1 and K1−2 contacts close energizing B1 compressor and B4 outdoor fan. 3− When cooling demand is satisfied, K1−1 and K1−2 contacts open de−energizing compressor and outdoor fan.
Timed off control begins 5 minute off time.
Page 16
C−Unit Diagram HS26−018/060−3 & 4−P (Late Models)
Operation Sequence
1− Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure
switch and the timed off control (TOC), which energizes K1 compressor contactor coil (provided 5 minute
delay is satisfied). 2− K1−1 and K1−2 contacts close energizing B1 compressor and B4 outdoor fan. 3− When cooling demand is satisfied, K1−1 and K1−2 contacts open de−energizing compressor and outdoor fan.
Timed off control begins 5 minute off time.
Page 17
C−Unit Diagram HS26−036/060−1Y, −048/−060−1G Three−phase (Late Models)
Operation Sequence
1− Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure
switch and timed off control (T.O.C.), which energizes K1 compressor contactor coil (provided 5 minute delay
is satisfied.) 2− K1−1, K1−2 and K1−3 contacts close energizing B1 compressor and B4 outdoor fan. 3− When cooling demand is satisfied, K1−1, K1−2 and K1−3 contacts open de−energizing compressor and out
door fan. Timed off control begins 5 minute off time.
NOTE−Three−phase compressors must be phased correctly. Compressor noise will be significantly higher if phasing is incorrect. Compressor will operate backwards so unit will not provide cooling. Continued backward operation will cause compressor to cycle on internal protector.
Page 18
Loading...