Lennox HPXA19 Unit Information

Corp. 0302−L2
Service Literature
Revised 07−2006
HPXA19 SERIES UNITS
The HPXA19 is a high efficiency residential split−system heat pump unit, which features a two−step scroll compres­sor and R410A refrigerant. HPXA19 units are available in 2, 3 (−036 and −038 models), 4 and 5 ton sizes. The series includes the HPXA19−038, a 3 ton unit equipped with a vari­able speed condenser fan motor. The series is designed for use with an expansion valve only (approved for use with R410A) in the indoor unit.This manual is divided into sec­tions which discuss the major components, refrigerant sys­tem, charging procedure, maintenance and operation se­quence. Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change.
IMPORTANT
Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.
HPXA19
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of (CFC’s and HFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration my be levied for noncompliance.
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications / Electrical Data 2. . . . . . . . . . . . . . . . . .
I Application 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Unit Components 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
III Refrigerant System 16. . . . . . . . . . . . . . . . . . . . . . . . . .
DANGER
Shock Hazard Remove all power at disconnect be-
fore removing access panel. HPXA19 units use single-pole con­tactors. Potential exists for electrical shock resulting in injury or death. Line voltage exists at all components (even when unit is not in operation).
IV Charging 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V Service and Recovery 22. . . . . . . . . . . . . . . . . . . . . . . .
VI Maintenance 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII Diagrams and Operating Sequence 23. . . . . . . . . . .
Page 1
© 2003 Lennox Industries Inc.
SPECIFICATIONS
p
g
Kit
g
General Data
Connections (sweat)
Refrigerant
Outdoor
Netfacearea sq. ft. (m2) − Outer Coil 16.04 (1.49) 16.04 (1.49) 24.06 (2.24) 24.06 (2.24) 24.06 (2.24)
Nominal Tonnage (kW) 2 (7.0)
Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line o.d. − in. (mm) 7/8 (22.2)
1
Coil
Tubediameter − in. (mm) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52)
Outdoor
Diameter in.(mm) and no. of blades 24 (610) − 3 24 (610) − 3 24 (610) − 4 24 (610) − 4 24 (610) − 4
Fan
Shipping Data − lbs. (kg) 1 package 261 (118) 262 (119) 316 (143) 318 (144) 340 (154)
Model No. HPXA19−024 HPXA19−036 HPXA19−038 HPXA19−048 HPXA19−060
3 (10.6) 3 (10.6) 4 (14.1) 5 (17.6)
7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 1−1/8 (28.5)
R−410A furnished 10 lbs. 4 oz.
(4.65 kg)
Inner Coil 15.56 (1.45)
11 lbs. 0 oz.
(5.00 kg)
13 lbs. 15 oz.
(6.32 kg)
12 lbs. 14 oz.
(5.84 kg)
14 lbs. 6 oz.
(6.52 kg)
15.56 (1.45) 23.33 (2.17) 23.33 (2.17) 23.33 (2.17)
Number of rows 2 2 2 2 2
Fins per inch (m) 22 22 22 22 22
Motor hp (W) 1/10 (74.8)
Cfm (L/s) 3159 (1485) 3159 (1485) 3135 (1480) first−stage
Rpm 825 825 700 first−stage
Watts 170 170 105 first−stage
1/10 (74.8) 1/3 (249) 1/4 (187) 1/4 (187)
3600 (1700) second−stage
820 second−stage
150 second−stage
3900 (1840) 4200 (1980)
820 820
300 350
ELECTRICAL DATA
Electrical Data
Compressor
Outdoor Coil Fan Motor
3
Maximum overcurrent protection (amps) 20 35 40 45 60
Line voltage data − 60hz 208/230V−1ph 208/230V−1ph 208/230V−1ph 208/230V−1ph 208/230V−1ph
2
Minimum circuit ampacity 13.7 22.1 23.7 28.2 33.8
Rated load amps 10.3 16.7 16.7 21.2 25.7
Locked rotor amps 52 82 82 96 118
Power factor 0.99 0.98 0.98 0.99 0.99
Full load amps 0.8 0.8 2.8 1.7 1.7
Locked rotor amps 2
2 Not Applicable 3.1 3.1
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Hard Start Kit Factory
Installed
Compressor Low Ambient Cut−off 45F08 45F08 45F08 45F08 45F08
Freezestat
3/8 in. tubing 93G35 93G35 93G35 93G35 93G35
1/2 in. tubing 39H29 39H29 39H29 39H29 39H29
5/8 in. tubing 50A93 50A93 50A93 50A93 50A93
3
Indoor Blower Speed Relay Kit 40K58 40K58 40K58 40K58 40K58
Low Ambient Kit 54M89 54M89 68M04 54M89 54M89
Mild Weather Kit 33M07 33M07 33M07 33M07 33M07
Monitor Kit − Service Light 76F53 76F53 76F53 76F53 76F53
Mounting Base
Outdoor Thermostat Kit
Part No. − Catalog No. MB2−L (69J07) MB2−L (69J07) MB2−L (69J07) MB2−L (69J07) MB2−L (69J07)
Net Weight 15 lbs. (7 kg)
Thermostat 56A87 56A87 56A87 56A87 56A87
Mounting Box − US 31461
Canada 33A09 33A09 33A09 33A09 33A09
Refrigerant Line Set
15 ft. (4.6 m) length L15−65−15 L15−65−15 L15−65−15 L15−65−15 Field Fabricate
30 ft. (9 m) length L15−65−30
40 ft. (12 m) length L15−65−40 L15−65−40 L15−65−40 L15−65−40 Field Fabricate
50 ft. (15 m) length L15−65−50 L15−65−50 L15−65−50 L15−65−50 Field Fabricate
SignatureStatt Programmable Thermostat 51M28 51M28 51M28 51M28 51M28
Time Delay Relay Kit 58M81 58M81 58M81 58M81 58M81
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. (4.6 m) length of refrigerant lines.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
3
HACR type breaker or fuse.
10J42 10J42 81J69 81J69
15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg)
31461 31461 31461 31461
L15−65−30 L15−65−30 L15−65−30 Field Fabricate
Page 2
I−APPLICATION
All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the En­gineering Handbook for approved system matchups. A misapplied system will cause erratic operation and can re­sult in early compressor failure.
II−Unit Components
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
A−Two−Stage Scroll Compressor (B1)
TWO−STAGE MODULATED SCROLL
slider ring
solenoid actuator coil
FIGURE 1
The scroll compressor design is simple, efficient and re­quires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 1.The scrolls are located in the top of the compressor can and the motor is located just below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 2 shows the basic scroll form. Two iden­tical scrolls are mated together forming concentric spiral shapes (figure 3). One scroll remains stationary, while the other is allowed to orbit" (figure 4). Note that the orbiting scroll does not rotate or turn but merely orbits" the station­ary scroll.
SCROLL FORM
FIGURE 2
CROSS−SECTION OF SCROLLS
DISCHARGE PRESSURE
TIPS SEALED BY
DISCHARGE PRESSURE
DISCHARGE
STATIONARY
SCROLL
SUCTION
ORBITING SCROLL
FIGURE 3
The counterclockwise orbiting scroll draws gas into the out­er crescent shaped gas pocket created by the two scrolls (figure 4 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 4 − 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 4
−3). When the compressed gas reaches the center, it is dis­charged vertically into a chamber and discharge port in the top of the compressor (figure1). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 3). During a single or­bit, several pockets of gas are compressed simultaneously providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid re­turn. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating com­pressors. Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in compressor failure. This type of damage can be detected and will result in denial of warranty claims. The scroll com­pressor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig.
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
The scroll compressors in all HPXA19 model units are de­signed for use with R410A refrigerant and operation at high pressures. Compressors are shipped from the factory with 3MA (32MMMA) P.O.E. oil. See electrical section in this manual for compressor specifications.
Page 3
TWO−STAGE OPERATION
The two−stage scroll compressor operates like any stan-
dard scroll compressor with the exception the two−stage
compressor modulates between first stage (low capacity
approximately 67%) and second stage (high capacity).
Modulation occurs when gas is bypassed through bypass
ports (figure 5 bypass ports open) in the first suction pock-
et. This bypassing of gas allows the compressor to operate
on first stage (low capacity) if thermostat demand allows.
Indoor thermostat setting will determine first or second
HOW A SCROLL WORKS
MOVEMENT OF ORBIT
SUCTION
ORBITING
SUCTION
POCKET
SCROLL
stage operation. The compressor will operate on first−stage until demand is satisfied or the indoor temperature reaches the thermostat set point calling for second−stage.
Second−stage (high capacity) is achieved by blocking the bypass ports (figure 5 bypass ports closed) with a slider ring. The slider ring begins in the open position and is con­trolled by a 24VDC internal solenoid. On a Y2 call the inter- nal solenoid closes the slider ring, blocking the bypass ports and bringing the compressor to high capacity. Two− stage modulation can occur during a single thermostat de­mand as the motor runs continuously while the compressor modulates from first−stage to second− stage.
SUCTION
INTERMEDIATE
PRESSURE
GAS
CRESCENT
SHAPED GAS
POCKET
3
12
FLANKS
SUCTION
STATIONARY SCROLL
SEALED BY
CENTRIFUGAL
FORCE
SUCTION
4
HIGH
PRESSURE
GAS
FIGURE 4
TWO−STAGE MODULATION
Bypass Ports
Closed
High Capacity
DISCHARGE
POCKET
Bypass Ports
Open
Low Capacity
FIGURE 5
Page 4
INTERNAL SOLENOID (L34)
Procedure
The internal unloader solenoid controls the two−stage op­eration of the compressor by shifting a slide ring mecha­nism to open two by−pass ports in the first compression pocket of the scrolls in the compressor. The internal sole­noid is activated by a 24 volt direct current solenoid coil. The coil power requires 20VAC. The internal wires from the solenoid in the compressor are routed to a 2 pin fusite con­nection on the side of the compressor shell. The external electrical connection is made to the compressor with a molded plug assembly. This plug contains a full wave recti­fier that converts 24 volt AC into 24 volt DC power to power the unloader solenoid. Refer to unit diagram for internal cir­cuitry view of plug.
If it is suspect the unloader is not operating properly, check the following
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper air­flow over coils, and correct system refrigerant charge. All components in the system must be func­tioning proper to correctly perform compressor modulation operational check. (Accurate measure­ments are critical to this test as indoor system load­ing and outdoor ambient can affect variations be­tween low and high capacity readings).
STEP 1 Confirm low to high capacity compressor operation
Tools required
Refrigeration gauge set
Digital volt/amp meter
Electronic temperature thermometer
On-off toggle switch
1. Turn main power "OFF" to outdoor unit.
2. Adjust room thermostat set point above (heating op­eration on heat pump) or below (cooling operation) the room temperature 5ºF.
3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch "OFF" and install switch in series with Y2 wire from room thermostat.
5. Cycle main power "ON."
6. Allow pressures and temperatures to stabilize be­fore taking any measured reading (may take up to 10 minutes).
NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).
7. Record all of the readings for the Y1 demand on table 1.
8. Close switch to energize Y2 demand.
9. Allow pressures and temperatures to stabilize be­fore taking any measured reading (this may take up to 10 minutes).
10. Record all of the readings of Y2 demand on table
1.
NOTE − On new installations or installations that have shut down for an extended period of time, if the com­pressor does not cycle from low stage to high stage on the first attempt, it may be necessary to recycle the com­pressor back down to low stage and back up to high stage a few times in order to get the bypass seals to properly seat
Compare Y1 readings with Y2 readings in table 1. Some readings should be higher, lower or the same. If the readings follow what table 1 specifies, the compressor is operating and shifting to high capacity as designed. If the readings do not follow what table 1 specifies, continue to step 2 to determine if problem is with external solenoid plug power.
Page 5
TABLE 1
Compressor Operation
Unit Readings
Y1 −
1st-Stage
Expected Results
Compressor
Voltage Same Amperage Higher
Condenser Fan motor
Amperage Same or Higher
Temperature
Ambient Same Outdoor Coil Discharge Air Higher in Cooling
Lower in Heating
Compressor Discharge Line Higher Indoor Return Air Same Indoor Coil Discharge Air Lower in Cooling
Higher in Heating
Pressures
Suction (Vapor) Lower Liquid Higher
Y2 −
2nd-Stage
STEP 2 Confirm DC voltage output on compressor solenoid plug
A − Compressor solenoid plug WITH built in full wave−
rectifier (LSOM I) that converts 24 volt AC into 24 volt DC power. See Table 1 for units equipped with the LSOM I.
1. Shut power off to outdoor unit.
2. Supply 24 volts AC control voltage to the wire ends of the full wave rectifier plug. Listen for a click" as the solenoid is energized. See figure 6.
apply 24vac
meter
compressor
fusite
terminals
rectifier plug leads
solenoid fusite
terminals
compressor
FIGURE 6
3. Unplug the full wave rectifier plug from the fusite connection on the compressor.
4. Turn the low voltage power back onto the unit. Sup­ply 24VAC to the wires of the full wave rectifier plug. Set volt meter to DC volts and measure the DC voltage at the female connector end of the full wave rectifier plug. The DC voltage reading should be 1.5 to 3 volts lower than the input voltage to the plug wire leads. (EX: Input voltage is 24VAC output voltage is 22VDC). See figure 7.
rectifier plug leads
apply 24vac
compressor
fusite
terminals
compressor
solenoid
fusite
terminals
meter
FIGURE 7
If the above checks verify that the solenoid plug is pro­viding power to cycle into high capacity operation, con­tinue to step 3 to determine if problem is with solenoid coil in compressor
Page 6
STEP 3 Confirm internal unloader solenoid has prop­er resistance
1. Shut all power off to unit (main and low voltage)
2. Unplug the molded plug from the compressor sole­noid 2−pin fusite.
3. Using a volt meter set on the 200 ohm scale
Replace the Compressor under these conditions:
Bad Solenoid
a. Measure the resistance at the 2−pin fusite. The resist­ance should be 32 to 60 ohms depending on compressor temperature. If no resist ancereplace compressor.
b. Measure the resistance from each fusite pin to ground. There should not be continuity to ground. If so­lenoid coil is grounded, replace compressor.
Good Solenoid
a. Seals not shifting, replace compressor b. Slider ring not shifting, replace compressor.
B−Contactor (K1)
The compressor is energized by a contactor located in the control box. All XP19 units are single phase and use single− pole contactors.
C−Low Pressure Switch (S87)
The XP19 is equipped with an auto−reset low pressure switch which is located on the suction line. The switch shuts off the compressor when the suction pressure falls below the factory setting. This switch is ignored during the first 90 seconds of compressor start up, during defrost operation, 90 seconds after defrost operation, during test mode and when the outdoor temperature drops below 15°F.
The switch closes when it is exposed to 55 psig and opens at 25 psig. It is not adjustable.
D−High Pressure Switch (S4)
E−Capacitor (C12)
The compressor in XP19−024, −036, −048 and −060 units
use a permanent split capacitor (see unit wiring diagram).
The capacitor is located inside the unit control box. Ratings
are on capacitor side.
F−Condenser Fan with Variable Speed Motor(B4)
The variable speed condenser fan motor (figure 14) used in all
units is a three-phase, electronically controlled d.c. brushless
motor (controller converts single phase a.c. to three phase
d.c.), with a permanent-magnet-type rotor, manufactured by
GE. Because this motor has a permanent magnet rotor it does
not need brushes like conventional D.C. motors. The motors
consist of a control module and motor . Internal components
are shown in figure 15. The stator windings are split into three
poles which are electrically connected to the controller. This ar-
rangement allows motor windings to be turned on and off in
sequence by the controller.
The controller is primarily an a.c. to d.c. converter. Con-
verted d.c. power is used to drive the motor. The control-
ler contains a microprocessor which monitors varying
conditions inside the motor (such as motor workload).
G−Contactor (K1)
The compressor is energized by a contactor located in the control box. All HPXA19 units are single phase and use single− pole contactors.
H−Low Pressure Switch (S87)
IMPORTANT
Pressure switch settings for R410A refrigerant will be significantly higher than units with R22.
An auto-reset, single-pole/single-throw high pressure switch is located in the liquid line. This switch shuts off the compres­sor when liquid line pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 640 + ure 13 for switch location.
10 psi and close at 448 + 10 psi. See fig-
Page 7
The HPXA19 is equipped with an auto−reset low pressure switch which is located on the suction line. The switch shuts off the compressor when the suction pressure falls below the factory setting. This switch is ignored during the first 90 seconds of compressor start up, during defrost operation, 90 seconds after defrost operation, during test mode and when the outdoor temperature drops below 15°F.
The switch closes when it is exposed to 55 psig and opens at 25 psig. It is not adjustable.
I−High Pressure Switch (S4)
IMPORTANT
Pressure switch settings for R410A refrigerant will be significantly higher than units with R22.
An auto-reset, single-pole/single-throw high pressure switch is located in the liquid line. This switch shuts off the compres­sor when liquid line pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 640 + ure 13 for switch location.
J−Low Ambient Thermostat (S23)
Second−stage low ambient thermostat S23 (figure 8) is a SPST thermostat located in the compressor compartment. The control uses a cap-tube sensor to monitor the tempera­ture inside the compressor compartment. The cap-tube sensor is coiled adjacent to the control.
Temperature Sensor
(Cap-Tube)
10 psi and close at 448 + 10 psi. See fig-
(Second−Stage)
Low Ambient Thermostat S23
Regional climatic conditions may require the control to be ad­justed to a different setting. The adjustment screw is located on the control. A hole cut into the bottom shelf of the control box provides access to the control from the compressor compartment. See figure 9.
Adjusting Low Ambient Thermostat
Adjustment screw can be reached by inserting a screw­driver through the slot in control box.
Turn screw clockwise to increase
switchover temperature.
FIGURE 9
Figure 10 shows the adjustment range of the control. Turn adjustment screw clockwise to raise the switchover tem­perature and counterclockwise to lower the switchover temperature.
Low Ambient Thermostat
49
adjustment
screw
FIGURE 8
S23 continually monitors the temperature inside the com­pressor compartment. When compressor compartment temperature drops below the control setpoint, the control closes. When the control closes, the contacts shunt across Y1 and Y2 inside the unit. When Y1 heating demand is present and S23 is closed, the compressor will run in high capacity. The compressor will operate in high capacity mode anytime there is a Y1 heating call from indoor ther­mostat, until the units control box warms and S23 opens.
S23 has field adjustable setpoints. Temperature differential (difference between cut-in and cut-out) is fixed and cannot be adjusted. Table 2 shows S23 control setpoints. The con­trol is factory set to close at 40+ and reset at 50+
2°F on a temperature rise.
2°F on a temperature drop
TABLE 2
Control Setpoints
Low Ambient Thermostat
Adjustable Range
Cut-In
(Close on Temperature Drop)
Cut-Out
(Open on Temperature Rise)
Factory
Setting
40+2°F 37+2°F 55+2°F
50+2°F 47+2°F 65+2°F
Min. Max.
43
*40
37
55
FIGURE 10
K−Reversing Valve (L1)
A refrigerant reversing valve with an electromechanical so­lenoid is used to reverse refrigerant flow during unit opera­tion. The reversing valve is energized during cooling de­mand and during defrost.
L−Transformer (T46)
Transformer T46 is located in the control box and is ener­gized any time the compressor is operating.
M−Solenoid Relay (K195)
Relay K195 is N.O. SPDT relay located in the control box. On a Y2 call K195−1 closes allowing AC voltage from (T46) to the two pin full wave rectifier plug (D4).
N−Rectifier Plug (D4)
D4 is a molded assembly that plugs into the compressor. On a Y2 call D4 converts 24 volts AC to 24 volts DC. The DC voltage energizes solenoid L34, allowing the com­pressor to operate at full capacity.
Page 8
O−Discharge Line Thermostat (S5)
S5 is an automatic reset SPST N.C. switch which opens on temperature rise. S5 is located on the discharge line and wired in series with S4 high pressure switch on the defrost control board. When discharge line temperature rises to
8°F the switch opens and shuts down the compres-
275° + sor. The switch resets when discharge line temperature drops to 225° +
11°F.
P−Dual Capacitor (C12)
The compressor and fan in HPXA19−024, −036, −048 and
−060 units use permanent split capacitor motors. A single dual" capacitor is used for both the fan motor and the com­pressor (see unit wiring diagram). The two sides (fan and compressor) of the capacitor have different mfd ratings and may change with each compressor. The capacitor is located inside the unit control box.
Q−Condenser Fan Motor (B4)
HPXA19−024, −036, −048 and −060 units use single−phase PSC fan motors which require a run capacitor. The FAN" side of the dual capacitor is used for this purpose. In all units, the outdoor fan is controlled by the compressor con­tactor. See ELECTRICAL DATA and SPECIFICATIONS section for more information. See figure 11 if condenser fan motor replacement is necessary. Rain shield location is critical on the condenser fan assembly. Two shields are used in unison to prevent moisture from entering the motor bearings. Installing the shields to close to the bearing hub will create noise and may affect operation. Installing too far away will allow moisture to enter the bearing, resulting in motor failure. See figure 12.
"A" SEE TABLE 3
Condenser fan and motor
FIGURE
11
TABLE 3
HPXA19 UNIT "A" DIM. + 1/8"
−024, −036 1 1/16"
−038
−048
−060
RAIN SHIELD LOCATION
(See figure 14 for HPXA19−038)
Critical Dimension
plastic
shield
fiber shield
FIGURE 12
FAN GUARD
Wiring
Drip loop
1 3/16"
1/4" (.250)
run capacitor
start capacitor
(−024 unit only)
system
operation monitor
defrost control
charge compensator (−038 and −048 units)
TXV/check valve
discharge line
compressor terminal plug
vapor line
low pressure switch
discharge temperature
thermostat
HPXA19 PARTS ARRANGEMENT
outdoor fan
(variable speed
on 038 units)
contactor
vapor valve
and
gauge port
two−stage compressor
filter drier
high pressure switch
FIGURE 13
Page 9
R−Condenser Fan with Variable Speed Motor(B4) (−038 only)
The variable speed condenser fan motor (figure 14) used in all HPXA19−038 units is a three-phase, electronically controlled d.c. brushless motor (controller converts single phase a.c. to three phase d.c.), with a permanent-magnet-type rotor, manufactured by GE. Because this motor has a permanent magnet rotor it does not need brushes like conventional D.C. motors. The motors consist of a control module and motor . Internal components are shown in figure 15. The stator wind­ings are split into three poles which are electrically connected to the controller. This arrangement allows motor windings to be turned on and off in sequence by the controller.
The controller is primarily an a.c. to d.c. converter. Con­verted d.c. power is used to drive the motor. The control­ler contains a microprocessor which monitors varying conditions inside the motor (such as motor workload).
The controller uses sensing devices to know what position the rotor is in at any given time. By sensing the position of the rotor and then switching the motor windings on and off in sequence, the rotor shaft turns the blower.
motor speed and allows the motor to compensate for varying load conditions as sensed by the controller. In this case, the controller monitors the static workload on the motor and var­ies motor rpm in order to maintain constant airflow (cfm).
Motor rpm is continually adjusted internally to maintain constant static pressure against the fan blade. The control­ler monitors the static work load on the motor and motor amp-draw to determine the amount of rpm adjustment. Blower rpm is adjusted internally to maintain a constant cfm. The amount of adjustment is determined by the incre­mental taps which are used and the amount of motor load­ing sensed internally. The motor constantly adjusts rpm to maintain a specified cfm.
Initial Power Up
When line voltage is applied to the motor, there will be a large inrush of power lasting less than 1/4 second. This in­rush charges a bank of DC filter capacitors inside the con­troller. If the disconnect switch is bounced when the discon­nect is closed, the disconnect contacts may become welded. Try not to bounce the disconnect switch when ap­plying power to the unit.
VARIABLE SPEED CONDENSER FAN MOTOR
RED
YELLOW
BLACK
RED
BLUE
motor
control module
FIGURE 14
BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 15
Internal Operation
The condenser fan motor is a variable speed motor with RPM settings at 700 (Y1) and 820 (Y2). The variation in speed is accomplished each time the controller switches a stator wind­ing (figure14) on and off, it is called a pulse." The length of time each pulse stays on is called the pulse width." By vary­ing the pulse width the controller varies motor speed (called pulse-width modulation"). This allows for precise control of
The DC filter capacitors inside the controller are connected electrically to the speed tap wires. The capacitors take approximately 5 minutes to discharge when the disconnect is opened. For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempting to service motor.
DANGER
Disconnect power from unit and wait at least five minutes to allow capacitors to discharge before attempting to ser­vice motor. Failure to wait may cause personal injury or death.
Motor Start-Up
At start-up, the motor may gently rock back and forth for a moment. This is normal. During this time the electronic controller is determining the exact position of the rotor. Once the motor begins turning, the controller slowly eases the motor up to speed (this is called soft-start"). The motor may take as long as 10-15 seconds to reach full speed. If the motor does not reach 200rpm within 13 seconds, the motor shuts down. Then the motor will im­mediately attempt a restart. The shutdown feature pro­vides protection in case of a frozen bearing or blocked fan blade. The motor may attempt to start eight times. If the motor does not start after the eighth try, the controller locks out. Reset controller by momentarily turning off power to unit.
Page 10
Rain shield location is critical on the condenser fan assem­bly. Installing the shields to close to the bearing hub will create noise and may affect operation. Installing too far away will allow moisture to enter the bearing resulting in motor failure. See figure 16 .
S−Filter Drier
A filter drier designed for all HPXA19 model units is factory
installed in the liquid line. The filter drier is designed to re-
move moisture and foreign matter, which can lead to com-
pressor failure.
RAIN SHIELD LOCATION
(−038 only)
3"
Critical
Dimension
plastic
shield
fiber shield
FIGURE 16
Troubleshooting
If first or second stage thermostat call for cool is present and the variable speed condenser fan motor does not ener­gize, check voltage at the breaker box. If voltage is present do the following and reference figure 17.
1− Check for 240 volts between the compressor RED wi-
res.
2− Initiate a first stage call for cool. Check for 24 volts be-
tween the fan motor YELLOW wire and fan motor BLACK wire.
3− Initiate a second stage call for cool. Check for 24 volts
between the fan motor YELLOW wire and fan motor BLACK wire, then check for 24 volts between the fan motor BLUE wire and fan motor BLACK.
4− Repeat steps 1 through 3 with a HEAT call.
Moisture and / or Acid Check
Because POE oils absorb moisture, the dryness of the
system must be verified any time the refrigerant sys-
tem is exposed to open air. A compressor oil sample
must be taken to determine if excessive moisture has been
introduced to the oil. Table 4 lists kits available from Lennox
to check POE oils.
If oil sample taken from a system that has been exposed to
open air does not test in the dry color range, the filter drier
MUST be replaced.
IMPORTANT
Replacement filter drier MUST be approved for R410A refrigerant and POE application.
Foreign Matter Check
It is recommended that a liquid line filter drier be replaced
when the pressure drop across the filter drier is greater
than 4 psig.
T−Accumulator (HPXA19−060 only)
ALL 5 ton HPXA19 units are equipped with an accumulator.
The purpose of the accumulator is to trap and evaporate all
liquid refrigerant returning to the compressor.
1st Stage (low capacity − 700 rpm)
RED
B4
RED
YELLOW
BLUE
BLACK
common
Y1
Y2
240V
240V
24V
0V
24V
2nd Stage (High capacity − 820 rpm)
RED
B4
RED
YELLOW
BLUE
BLACK
common
Y1
Y2
240V
240V
24V
24V
24V
FIGURE 17
U−Charge Compensator
HPXA19−038 and −048 series units are equipped with a
charge compensator located in the vapor line between the
reversing valve and outdoor coil manifold. The compensa-
tor is used to collect and store excess refrigerant in the
heating mode. Figure 18 shows operation of the charge
compensator.
In heating mode, the vapor line passing through the charge
compensator tank is cooler than the liquid line. Excess re-
frigerant (condensed liquid) from the indoor coil is trapped
by the compensator. The vapor line is cooler than the liquid
line so liquid migrates from the liquid line to the compensa-
tor tank where it is stored. In cooling mode, the vapor line
passing through the charge compensator tank is hotter
than the liquid line. Stored liquid is boiled and forced back
into the liquid line for circulation.
Page 11
TABLE 4
KIT CONTENTS TUBE SHELF LIFE
10N46 − Refrigerant Analysis Checkmate−RT700
10N45 − Acid Test Tubes Checkmate−RT750A (three pack)
10N44 − Moisture Test Tubes
74N40 − Easy Oil Test Tubes
74N39 − Acid Test Kit Sporlan One Shot − TA−1
Checkmate − RT751 Tubes (three pack)
Checkmate − RT752C Tubes (three pack)
2 − 3 years @ room temperature. 3+ years refrigerated
6 − 12 months @ room temperature. 2 years refrigerated
2 − 3 years @ room temperature. 3+ years refrigerated
CHARGE COMPENSATOR OPERATION
COOLING MODE
Vapor Line
(To Outdoor Coil)
Compensator Tank
During cooling mode, the va­por line is hotter than the liq­uid line. Stored liquid is heated (boiled) and forced back into circulation.
Stored Liquid
To Liquid Line
To be Circulated
Through Indoor Coil
Vapor Line
(From Compressor Discharge Port)
HEATING MODE
Vapor Line
(From Outdoor Coil)
Compensator Tank
During heating mode, the va­por line is cooler than the liq­uid line. Excess refrigerant is forced into the charge com­pensator where it condenses and collects.
Excess Refrigerant
To be Condensed and Stored
as Liquid
Vapor Line
(To Compressor Suction Port)
FIGURE 18
V−Lennox System Operation Monitor (A132)
The Lennox system operation monitor (LSOM) is a 24 volt powered module wired directly to the indoor unit . See diag­nostic module A132 on wiring diagram and figure 19. The LSOM is located in the control box and is used to trouble shoot problems in the system. The module has three LED’s for troubleshooting: GREEN indicates power status, YEL­LOW indicates an abnormal condition and RED indicates thermostat demand, but compressor not operating. See table 5 for troubleshooting codes.
IMPORTANT
The LSOM is not a safety component and cannot shut down or control the HPXA19. The LSOM is a monitoring device only.
W−Crankcase Heater (HR1)
Compressors in all units are equipped with a 70 watt belly­band type crankcase heater. HR1 prevents liquid from ac­cumulating in the compressor. HR1 is controlled by the crankcaseheater thermostat.
X− Crankcase heater Thermostat (S40)
Thermostat S40 controls the crankcase heater in all units. S40 is located on the liquid line. When liquid line tempera­ture drops below 50° F the thermostat S40 closes energizing HR1. The thermostat will open, de−energizing HR1 once liq­uid line temperature reaches 70° F .
System Operation Monitor
LE D
Y
C
R
LED’s
FIGURE 19
Y−Defrost System
The demand defrost controller uses basic differential tem­perature means to detect when the system performs poor­ly because of ice build−up on the outdoor coil. The control­ler also uses self−calibrating" principles to calibrate itself when the system starts and after every time the system defrosts. The control board has the following compo­nents: defrost relays, anti−short cycle timed−off control, pressure switch/safety control, 5−trip lockout circuit, test mode pins, ambient and coil temperature sensors, field selectable termination temperature pins, and a field low voltage connection terminal strip. See figure 20.
The control monitors ambient temperature, outdoor coil temperature and total run time to determine when a de­frost cycle is required. Two temperature probes are per­manently attached to the control. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation. See figure 21 for coil sensor location. The ambient temperature sensor is located in the PVC tube next to the filter drier.
NOTE − The logic of the demand defrost board accurately measures the performance of the system as frost accumu­lates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
Page 12
TABLE 5
System Operation Monitor LED Troubleshooting Codes
Status LED
Green Power" Module has power. 24VAC control power is present at the module terminal.
Red Trip"
Yellow Alert"
Flash Code 1 (Does not apply to heat pump or to two−stage split systems)
Yellow Alert"
Flash Code 2
Yellow Alert"
Flash Code 3
Yellow Alert"
Flash Code 4
Yellow Alert"
Flash Code 5
Status LED Description
Thermostat demand signal Y1 is present, but the com­pressor is not running. Heat pump only−Trip light will be on during defrost board 5 minute delay with Y thermo­stat call.
Long Run Time
Compressor is running ex­tremely long run cycles
System Pressure Trip
Discharge or suction pres­sure out of limits or compres­sor overloaded
Short Cycling
Compressor is running only briefly
Locked Rotor
Open Circuit
Status LED Troubleshooting Information
1
Compressor protector is open.
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low pressure switch open if present in the system.
6
Compressor contactor has failed to close.
1
Low refrigerant charge.
2
Evaporator blower is not running.
3
Evaporator coil is frozen.
4
Faulty metering device.
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning.
1
High head pressure.
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
4
Return air duct has substantial leakage.
5
If low pressure switch is present, check Flash Code 1 information.
1
Thermostat demand signal is intermittent.
2
Time delay relay or control board is defective.
3
If high pressure switch is present, check Flash Code 2 information.
4
If low pressure switch is present, check Flash Code 1 information.
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at disconnect is low).
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambient temperature.
7
Compressor windings are damaged.
1
Yellow Alert"
Flash Code 6
Yellow Alert"
Flash Code 7
Yellow Alert"
Flash Code 8
Yellow Alert"
Flash Code 9
Open Start Circuit
Current only in run circuit
Open Run Circuit
Current only in start circuit
Welded Contactor
Compressor always runs
Low Voltage
Control circuit < 17VAC
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
3
Compressor start winding is damaged.
1
Open circ uit in compress or start wiring or connections.
2
Compressor start winding is damaged.
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to module.
1
Control circuit transformer is overloaded
2
Low line voltage (contact utility if voltage at disconnect is low.)
Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated.
TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation.
Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on.
Page 13
Component Locations Will
Vary With Board Manufacture
pressure
switch circuit
connections
reversing valve
connections
coil
sensor
COIL SENSOR LOCATION
HPXA19−036/−048/−060
Coil sensor should be on
the 5th hairpin from the
bottom on the outside loop.
HPXA19−024
Coil sensor should be on the
6th hairpin from the top on
the outside loop.
DELAY
Y2
FIGURE 20
HPXA19−038
Coil sensor should be on
the 8th hairpin down from
the top on the outside loop.
FIGURE 21
r
defrost board
test pins
diagnostic LEDs
24V terminal
strip connections
Y2
field select
temperature pins
ambient
sensor
The temperature probes cannot be removed from the con­trol. The control and the attached probes MUST be re­placed as a unit. Do not attempt to cut or splice probe wires.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the diagnos­tic condition. See table 6.
HI−PS/LO−PS Terminals
High pressure switch (S4) is factory wired into the defrost board HI−PS terminals. When (S4) trips, the defrost board will cycle off the compressor and the strike counter in the board will count one strike. Low pressure switch (S87) is factory wired into the defrost board LO−PS terminals. When (S87) trips, the defrost board will cycle off the compressor and the strike counter in the board will count one strike. (S87) is ignored during certain conditions:
During the defrost cycle and 90 seconds after the
termination of defrost
When the average ambient sensor temperature is
below 15 F (−9)
For 90 seconds following the start up of the
compressor
During "Test" mode
5−Strike Lockout Feature
The internal control logic of the board counts the pres-
sure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be
reset by cycling OFF the 24−volt power to the control board or by shorting the TEST pins. All timer functions (run times) will also be reset.
If a pressure switch or discharge line thermostat switch
opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.
DELAY" Option
The defrost board has a field selectable function to reduce occasional noise that may occur while the unit is cycling in and out of defrost mode. When a jumper is installed on the DELAY" pins, the compressor will cycle off for 30 seconds going in and out of defrost mode.
NOTE − 30 second off cycle is not functional when jumpering TEST" pins.
Page 14
LED 1 LED 2 Condition Possible Cause(s) Solution
prope
2
Improper refrigerant charge
pp , p
pp g p
leaks. Replace metering device
OFF OFF Power problem
ON ON Coil sensor problem
OFF ON Ambient sensor problem
FLASH FLASH Normal operation
ON OFF
ON FLASH
FLASH ON
ALTERNATING
FLASH
The demand defrost control board initiates a defrost cycle based on either frost detection or time. Frost Detection − If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds
the maximum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature defrost system.
Time − If 6 hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
Actuation − When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s). Calibration success depends on stable system temperatures during the 20−minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run time. Once the defrost board is calibrated, it will use demand defrost logic to initiate a defrost cycle. A demand defrost system initiates defrost when the difference be­tween the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
Termination − The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 34 minutes of run time.
Test Mode − When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the Test" pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation. The jumper will initiate one cycle per test.
Operational Description
The defrost control board has three basic operational modes: normal, defrost, and calibration.
The demand defrost board monitors the O line, to deter­mine the system operating mode (heat/cool), outdoor am­bient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the W1 (auxiliary heat) line. The unit will stay in this mode until either the coil sen­sor temperature is above the selected termination temper­ature, the defrost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default termination temperature will be 100°F.) If the room
ALTERNATING
FLASH
Normal Mode
Defrost Mode
TABLE 6
Defrost Control Board Diagnostic (5 strike)
1
No power (24V) to board terminals
R & C.
2
Board failure.
1
Coil temperature outside of sensor
range.
2
Faulty sensor wiring connections at
board or poor sensor contact on coil.
3
Sensor failure.
1
Ambient temperature outside of
sensor range.
2
Faulty sensor wiring connections at
board or sensor.
3
Sensor failure.
Unit operating normally or in standby mode.
5−Strike pressure lockout (Short test pins or reset 24V power to board to override lockout)
Low pressure switch circuit open during Y1 demand
High pressure switch or discharge thermostat switch circuit open during Y1 demand
5−minute delay (Jumper test pins to over­ride delay)
Demand Defrost Operation
1
Restricted air flow over indoor or
outdoor coil.
2
Im
3
tion.
4
Poor contact between coil sensor
and coil.
Thermostat demand for cooling or heat pump operation. Unit operating in 5−minute anti−short−cycle mode.
r refrigerant charge.
Improper metering device opera-
thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the se­lected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by time and the coil temperature did not remain above 35°F (2°C) for 4 minutes, the control will go into the 34−minute Time/Temperature mode.
The board is considered uncalibrated when power is ap­plied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to en­sure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
Page 15
1
Check control transformer power
(24V).
2
If power is available and LED(s) are
unlit, replace board and all sensors.
1
Sensor function will resume when coil temperature is between −20°F and 110°F.
2
Check sensor wiring connections at
board and sensor contact on coil.
3
Replace board and all sensors.
1
Sensor function will resume when coil temperature is between −20°F and 110°F.
2
Check sensor wiring connections at
board and sensor.
3
Replace board and all sensors.
None required.
1
Remove any blockages or restric-
tions. Check outdoor fan motor for proper operation.
2
.
Check approach, superheat & sub-
cooling temperatures.
3
Check system pressures. Repair
4
Make sure that sensor is properly
positioned on coil and that firm con­tact is established. Refer to service manual for proper placement.
None required.
Calibration Mode
.
Z−Start Capacitor (C7) −024 model only
All 2 ton HPXA19 units are equipped with a start capacitor (C7). The capacitor is located in the control box and wired in parallel with the compressor side of the dual capacitor. C7 is de−energized by potential relay K31 when the com­pressor nears full speed.
AA−Potential Relay (K31) −024 model only
III−REFRIGERANT SYSTEM
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections). Use Lennox L15 series line sets as shown in table 7. Separate liquid and suction service ports are provided at the service valves for connection of gauge manifold during charging procedure. Figure 22 shows HPXA19 refrigerant flow and gauge manifold connections.
All 2 ton HPXA19 units are equipped with potential relay K31, which controls the operation of the starting circuit. The relay is located inside the control box and is normally closed when contactor K1 is de−energized. When K1 is en­ergized the compressor begins start up. K31 remains closed closed during start up and capacitor C7 remains in the circuit. When the compressor reaches 75% of its speed, K31 is energized, de−energizing capacitor C7.
HPXA19 COOLING CYCLE
(Showing Gauge Manifold Connections)
OUTDOOR UNIT
DISTRIBUTOR
EXPANSION/
CHECK VALVE
LOW
PRESSURE
HIGH
PRESSURE
BIFLOW
FILTER / DRIER
MUFFLER
OUTDOOR
COIL
Model
−024,− 036
−038
−048
−060
Valve Field Size
Connections
Liquid
Line
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
REVERSING VALVE
Vapor
Line
7/8 in.
22 mm
7/8 in.
22 mm
1−1/8 in.
29 mm
1−1/8 in.
29 mm
TABLE 7
Recommended Line Set
Liquid
Line
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
DIRECTION OF REFRIGERANT FLOW.
REFRIGERANT WILL FLOW IN OPPOSITE
DIRECTION IN HEATING CYCLE.
Vapor
Line
7/8 in.
19 mm
15 ft. − 50 ft.
4.6 m − 15 m
7/8 in.
22 mm
7/8 in.
22 mm
15 ft. − 50 ft.
4.6 m − 15 m
15 ft. − 50 ft.
4.6 m − 15 m
1−1/8 in.
29 mm
NOTE − ARROWS INDICATE
INDOOR UNIT
Fabricated
L15
Line Sets
L15−65
L15−65
L15−65
Field
GAUGE MANIFOLD
TO
R410A
DRUM
LIQUID
LINE
SERVICE
PORT
COMPRESSOR
SUCTION SERVICE
PORT
NOTE−Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use suction gauge port to measure suction pressure during charging.
FIGURE 22
Page 16
VAPOR
LINE
VALV E
EXPANSION/CHECK
VALV E
INDOOR
COIL
A−Service Valves
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale min). Fully in­sert the wrench into the valve stem recess. Service valve stems are factory torqued (from 9 ft lbs for small valves, to 25 ft lbs for large valves) to prevent refrigerant loss during ship­ping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
Access the liquid line and vapor line service valves (figures 23 and 24) and gauge ports are used for leak testing, eva­cuating, charging and checking charge. See table 8 for torque requirements.
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
TABLE 8
Part Recommended Torque
To Close Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Using service wrench and hex head extension, turn
stem clockwise to seat valve. Tighten it firmly.
NOTE − Use a 3/16" hex head extension for liquid line size.
3 − Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
Vapor Line (Ball Type) Valve
Vapor line service valves function the same way as the oth­er valves, the difference is in the construction. These valves are not rebuildable. If a valve has failed, you must replace it. A ball valve valve is illustrated in figure 24.
The ball valve is equipped with a service port with a factory− installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak− free seal.
Liquid Line Service Valve
(Valve Closed)
service
port cap
service port
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
IMPORTANT
Service valves are closed to the outdoor unit and open to line set connections. Do not open the valves until refrigerant lines have been leak tested and evacuated. All precautions should be exercised to keep the system free from dirt, moisture and air.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench. 2 − Connect gauge to the service port. 3 − When testing is complete, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
To Open Service Valve:
1 − Remove stem cap with an adjustable wrench. 2 − Using service wrench and hex head extension, back
the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for liquid line size.
3 − Replace stem cap and tighten it firmly. Tighten finger
tight, then tighten an additional 1/6 turn.
insert hex
wrench here
stem cap
Liquid Line Service Valve
(Valve Open)
service
port cap
schrader
valve
stem
cap
Service Port Is Open
To Line Set When Valve Is
Closed (Front Seated)
insert hex
wrench here
FIGURE 23
to
indoor coil
to outdoor coil
service port
to
indoor coil
to outdoor coil
(valve front seated)
Page 17
Vapor Line (Ball Type) Service Valve
(Valve Open)
To open: rotate stem counter-clockwise 90°.
Schrader
valve
service
port
field side
Use Adjustable Wrench
To close: rotate stem clockwise 90°.
service port
ball
(shown open)
cap
unit side
stem cap
stem
FIGURE 24
IV−CHARGING
Units are factory charged with the amount of R410A refrig­erant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15 ft. (4.6m) line set. For varying lengths of line set, refer to table 9 for refrigerant charge adjustment.
TABLE 9
Liquid Line Set
Diameter
3/8 in.
(10mm)
Ozs. per 5 ft. (grams per 1.5m) adjust
from 15 ft. (4.6m) line set*
3 ounces per 5 feet
(85g per 1.5m)
*If line length is greater than 15 ft. (4.6m), add this amount. If line length is less than 15 ft. (4.6), subtract this amount.
A−Leak Testing
After the line set has been connected to the indoor and out­door units, the line set connections and indoor unit must be checked for leaks.
WARNING
Refrigerant can be harmful if inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning can lead to injury or death.
WARNING
Danger of explosion! When using a high pressure gas such
as dry nitrogen to pressurize a refrig­erant or air conditioning system, use a regulator that can control the pres­sure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and / or an explosion, that can re­sult in personal injury or death.
Using an Electronic Leak Detector
1 − Connect a cylinder of R410A to the center port of the
manifold gauge set.
2 − With both manifold valves closed, open the valve on
the R410A cylinder (vapor only).
3 − Open the high pressure side of the manifold to allow
the R410A into the line set and indoor unit. Weigh in a trace amount of R410A . [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the R410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck.
IMPORTANT
Leak detector must be capable of sensing HFC re­frigerant.
B−Evacuating
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
Page 18
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 23,000 microns.
1 − Connect the manifold gauge set to the service valve
ports as follows:
low pressure gauge to vapor line service valvehigh pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start vacuum pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin­der with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use com­pressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of R410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R410A cylinder and remove the manifold gauge set.
C−Charging
This system is charged with R410A refrigerant which oper­ates at much higher pressures than R22. The check/ex­pansion valve provided with the unit is approved for use with R410A. Do not replace it with a valve designed for use with R22. This unit is NOT approved for use with coils which include metering orifices or capillary tubes.
Processing Procedure
The unit is factory−charged with the amount of R410A re­frigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.6m) line set. For varying lengths of line set, refer to table 9 for refrigerant charge adjustment. .
IMPORTANT
Mineral oils are not compatible with R410A. If oil must be added, it must be a polyol ester oil.
It is desirable to charge the system in the cooling cycle if weather conditions permit. However, if the unit must be charged in the heating season, one of the following proce­dures must be followed to ensure proper system charge.
Weighing in the Charge TXV Systems –
Outdoor Temp. < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been re­paired.
1 − Recover the refrigerant from the unit. 2 − Conduct a leak check, then evacuate as previously
outlined. 3 − Weigh in the unit nameplate charge. If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other proce­dures outlined below.
Subcooling Method
Outdoor Temp. < 65°F (18°C)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the out­door coil to achieve pressures in the 325−375 psig (2240−2585 kPa) range. These higher pressures are nec­essary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liq­uid pressure is in the 325−375 psig (2240−2585 kPa) range. Figure 25 shows a four sided unit for example..
Page 19
Blocking Outdoor Coil
Outdoor coil should be
blocked one side
at a time with cardboard
or plastic sheet until proper
testing pressures
are reached.
cardboard or plastic sheet
FIGURE 25
1 − With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.
2 − At the same time, record the liquid line pressure reading.
3 − Use a temperature/pressure chart for R410A to deter-
mine the saturation temperature for the liquid line pres-
sure reading. See table 14.
4 − Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature − Liquid line tem-
perature = Subcooling)
5 − Compare the subcooling value with those in table 10. If
subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant. Be aware of the R410A refrigerant cylinder. It
will be light maroon−colored. Refrigerant should be
added through the vapor line valve in the liquid state.
Some R410A cylinders are equipped with a dip
tube that allows you to draw liquid refrigerant from
the bottom of the cylinder without turning the cyl-
inder upside−down. The cylinder will be marked if it
is equipped with a dip tube.
TABLE 10
2nd stage High Capacity
Model Number
HPXA19−024 11.0 + 1 (6 + .5)
HPXA19−036 8.5 + 1 (4.7 + .5)
HPXA19−038 10.5 + 1 (5.8 + .5)
HPXA19−048 7.5 + 1 (4.1 + .5)
HPXA19−060 7.0 + 1 (3.9 + .5)
Conversion Temp. − Liquid Line Temp. °F (°C)
Subcooling Values
Charging Using Normal Operating Pressures
and the Approach Method
Outdoor Temp. >
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
tables 12 and 13, Normal Operating Pressures." Mi­nor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the sys­tem. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer used to check out-
door ambient temperature to check liquid line tempera­ture. Verify the unit charge using the approach method.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 11. If the val­ues don’t agree with the those in table 11, add refriger­ant to lower the approach temperature or recover re­frigerant from the system to increase the approach temperature.
TABLE 11
2nd Stage High Capacity
Model Number
HPXA19−024 4.0 + 1 (2.2 + .5)
HPXA19−036 7.0 + 1 (3.9 + .5)
HPXA19−038 4.0 + 1 (2.2 + .5)
HPXA19−048 8.0 + 1 (4.4 + .5)
HPXA19−060 10.0 + 1 (5.6 + .5)
Liquid Line Temp. − Outdoor Ambient °F (°C)
65F (18C)
Approach Temperature
IMPORTANT
Use table 12 and table 13 as a general guide when performing maintenance checks. This is not a proce­dure for charging the unit (Refer to Charging/Check­ing Charge section). Minor variations in these pres­sures may be expected due to differences in installa­tions. Significant differences could mean that the system is not properly charged or that a problem ex­ists with some component in the system.
Page 20
NORMAL OPERATING PRESSURES
Outdoor Coil
)
Outdoor Coil
p
)
Coil
Coil
(Liquid ±10 and Vapor ±5 psig)
Outdoor Coil
Entering Air
Temp. °F (°C
65 (18.3) 217 143 227
75 (23.9) 250 145 262
85 (29.4) 291 147 305
95 (35.0) 336 149 352
105 (40.6) 386 151 403
115 (49.0) 440 153 458
HPXA19−024 HPXA19−036 HPXA19−038 HPXA19−048 HPXA19−060
Liquid Vapor Liquid
Second Stage (High Capacity)
Outdoor Coil
Entering Air Tem
65 (18.3) 222 143 244
75 (23.9) 256 145 282
85 (29.4) 302 145 325
95 (35.0) 349 147 377
105 (40.6) 403 149 428
115 (49.0) 464 152 488
. °F (°C
HPXA19−024 HPXA19−036 HPXA19−038 HPXA19−048 HPXA19−060
Liquid Vapor Liquid
TABLE 12
COOLING OPERATION
First Stage (Low Capacity)
Vapor
142
145
146
148
152
155
Vapor
136
139
142
144
146
148
Liquid Vapor Liquid Vapor Liquid Vapor
222 142 222 140 225 140
255 145 258 143 259 142
295 146 298 145 293 146
343 148 343 147 356 147
390 153 402 147 408 147
446 156 452 152 455 151
Liquid Vapor Liquid Vapor Liquid Vapor
231 133 232 134 249 126
263 139 266 136 289 134
305 142 309 139 330 140
354 145 359 142 378 143
403 147 410 144 433 146
461 149 468 147 492 149
Outdoor
Coil
Entering
Air
40 (4.4) 321 99 296
50 (10) 340 120 310
Outdoor
Entering
Air Temp.
20 (−7.0) 273 68 277
30 (−1.0) 296 80 296
40 (4.4) 321 95 321
50 (10) 341 11 5 341
HPXA19−024 HPXA19−036 HPXA19−038 HPXA19−048 HPXA19−060
Liquid Vapor Liquid
HPXA19−024 HPXA19−036 HPXA19−038 HPXA19−048 HPXA19−060
Liquid Vapor Liquid
TABLE 13
NORMAL OPERATING PRESSURES
HEATING OPERATION
(Liquid ±10 and Vapor ±5 psig)
First Stage (Low Capacity)
Vapor
95
112
Liquid Vapor Liquid Vapor Liquid Vapor
308 97 315 97 319 93
323 116 330 114 335 111
Second Stage (High Capacity)
Vapor
60
74
88
104
Liquid Vapor Liquid Vapor Liquid Vapor
288 59 294 60 300 57
308 74 303 75 312 70
316 90 314 90 323 83
330 108 325 106 339 97
Page 21
Table 14
R410A Temperature/Pressure Chart
Temperature°FPressure
Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 195.5 93 286.5 124 440.2 155 645.0
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Page 22
V−SERVICE AND RECOVERY
VI−MAINTENANCE
WARNING
WARNING
Polyol ester (POE) oils used with R410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or ser­vice valve stub caps until you are ready to make connections.
IMPORTANT
Use recovery machine rated for R410 refrigerant.
If the HPXA19 system must be opened for any kind of ser­vice, such as compressor or filter drier replacement, you must take extra precautions to prevent moisture from en­tering the system. The following steps will help to minimize the amount of moisture that enters the system during re­covery of R410A.
1 − Use a regulator−equipped nitrogen cylinder to break
the system vacuum. Do not exceed 5 psi. The dry ni­trogen will fill the system, and will help purge any mois­ture.
2 − Remove the faulty component and quickly seal the
system (using tape or some other means) to prevent additional moisture from entering the system.
3 − Do not remove the tape until you are ready to install
new component. Quickly install the replacement com­ponent.
4 − Evacuate the system to remove any moisture and oth-
er non−condensables.
The HPXA19 system MUST be checked for moisture any time the sealed system is opened.
Any moisture not absorbed by the polyol ester oil can be re­moved by triple evacuation. Moisture that has been ab­sorbed by the compressor oil can be removed by replacing the filter drier.
IMPORTANT
Evacuation of system only will not remove mois­ture from oil. Filter drier must be replaced to elimi­nate moisture from POE oil.
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a quali­fied installer or service agency. At the beginning of each cooling or heating season, the system should be checked as follows:
Outdoor Unit
1 − Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2 − Outdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.
3 − Visually inspect all connecting lines, joints and coils for
evidence of oil leaks. 4 − Check all wiring for loose connections. 5 − Check for correct voltage at unit (unit operating). 6 − Check amp−draw on outdoor fan motor and compres-
sor (high and low capacity). 7 − Inspect drain holes in coil compartment base and
clean if necessary.
NOTE − If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil if necessary.
2 − Check connecting lines, joints and coil for evidence of
oil leaks.
3 − Check condensate line and clean if necessary.
Indoor Unit
1 − Clean or change filters. 2 - Lennox blower motors are prelubricated and permanent-
ly sealed. No more lubrication is needed.
3 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure. 4 − Belt Drive Blowers − Check belt for wear and proper
tension.
5 − Check all wiring for loose connections.
6 − Check for correct voltage at unit.
7 − Check amp−draw on blower motor.
Page 23
VII−DIAGRAM / OPERATING SEQUENCE
HPXA19−024, 036, −048 & −060
Page 24
Sequence of Operation HPXA19−024/060
First Stage Cool (low capacity)
Transformer from indoor unit supplies 24VAC power to the thermostat and outdoor unit controls.
1− Internal wiring energizes terminal O by cooling mode
selection, energizing the reversing valve. Cooling de­mand initiates at Y1 in the thermostat.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compres­sor contactor K1. HPXA19−024 − Compressor begins start up. Relay K31 remains closed during start up and capacitor C7 remains in the circuit. As compressor speeds up K31 is energized, de−energizing capacitor C7.
3− K1−1 N.O. closes energizing compressor B1 and out-
door fan motor B4. Transformer T46 is also energized.
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
Second Stage Cool (high capacity)
5− Second stage thermostat demand energizes solenoid
relay K195. K195−1 closes sending voltage to rectifier plug D4. D4 converts the AC voltage to DC voltage and energizes L34 unloader solenoid. L34 then closes the slider ring, allowing the compressor to operate at high capacity.
Heating
A− Ambient temperature ABOVE S23 low ambient thermostat setting. S23 remains open.
1− Internal wiring de−energizes terminal O by heating
mode selection, de−energizing the reversing valve. Heating demand initiates at Y1.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compres­sor contactor K1.
3− K1−1 N.O. closes, energizing compressor, outdoor fan
motor and transformer T46.
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
B− Ambient temperature BELOW S23 low ambient thermostat setting. S23 closes shunting Y1 and Y2.
1− Internal wiring de−energizes terminal O by heating
mode selection, de−energizing the reversing valve. Thermostat calls for heating demand.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compres­sor contactor K1.
3− K1−1 N.O. closes, energizing compressor, outdoor fan
motor and transformer T46.
4− Heat demand energizes solenoid relay K195. K195−1
closes sending voltage to rectifier plug D4. D4 con­verts the AC voltage to DC voltage and energizes L34 unloader solenoid. L34 then closes the slider ring, al­lowing the compressor to operate at full capacity.
Defrost Mode
When a defrost cycle is initiated, the control ener­gizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the W1" (auxiliary heat) line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination temperature, the de­frost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default termination temperature will be 100°F.) If the room thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the meth­ods mentioned above. If a defrost is terminated by time and the coil temperature did not remain above 35°F (2°C) for 4 minutes the control will go to the 34−minute Time/Temperature mode.
Page 25
HPXA19−038 with Variable Speed Motor
3
4
2
1
Page 26
Sequence of Operation HPXA19−038
First Stage Cool (low capacity)
Transformer from indoor unit supplies 24VAC power to the thermostat and outdoor unit controls.
1− Internal wiring energizes terminal O by cooling mode
selection, energizing the reversing valve. Cooling de­mand initiates at Y1in the thermostat.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compres­sor contactor K1.
3− K1−1 N.O. closes energizing compressor B1,trans-
former T46 and outdoor fan motor B4. Variable speed condenser fan motor operates on low speed (yellow tap).
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
Second Stage Cool (high Capacity)
5− Second stage thermostat demand energizes solenoid
relay K195. K195−1 closes sending voltage to rectifier plug D4. D4 converts the AC voltage to DC voltage and energizes L34 unloader solenoid. L34 then closes the slider ring, allowing the compressor to operate at full capacity. Variable speed condenser fan motor oper­ates on high speed (blue tap).
Heating
A− Ambient temperature ABOVE S23 low ambient thermostat setting. S23 remains open.
1− Internal wiring de−energizes terminal O by heating
mode selection, de−energizing the reversing valve. Heating demand initiates at Y1.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compres­sor contactor K1.
3− K1−1 N.O. closes, energizing compressor B1, trans-
former T46 and outdoor fan motor B4. Variable speed condenser fan motor operates on low speed (yellow tap).
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
B− Ambient temperature BELOW S23 low ambient setting. S23 closes shunting Y1 and Y2.
1− Internal wiring de−energizes terminal O by heating
mode selection, de−energizing the reversing valve. In­door thermostat calls for heating demand.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compres­sor contactor K1.
3− K1−1 N.O. closes, energizing compressor B1, trans-
former T46 and outdoor fan motor B4. Variable speed condenser fan motor operates on high speed (blue tap).
4− Heat demand energizes solenoid relay K195. K195−1
closes sending voltage to rectifier plug D4. D4 con­verts the AC voltage to DC voltage and energizes L34 unloader solenoid. L34 then closes the slider ring, al­lowing the compressor to operate at full capacity.
Defrost Mode
When a defrost cycle is initiated, the control ener­gizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the W1" (auxiliary heat) line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination temperature, the de­frost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default termination temperature will be 100°F.) If the room thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the meth­ods mentioned above. If a defrost is terminated by time and the coil temperature did not remain above 35°F (2°C) for 4 minutes, the control will go to the 34−minute Time/Temperature mode.
Page 27
Loading...