The HPXA19 is a high efficiency residential split−system
heat pump unit, which features a two−step scroll compressor and R410A refrigerant. HPXA19 units are available in
2, 3 (−036 and −038 models), 4 and 5 ton sizes. The series
includes the HPXA19−038, a 3 ton unit equipped with a variable speed condenser fan motor. The series is designed for
use with an expansion valve only (approved for use with
R410A) in the indoor unit.This manual is divided into sections which discuss the major components, refrigerant system, charging procedure, maintenance and operation sequence.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are
subject to change.
IMPORTANT
Operating pressures of this R410A unit are higher
than pressures in R22 units. Always use service
equipment rated for R410A.
HPXA19
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of (CFC’s and HFC’s) as of July 1, 1992. Approved
methods of recovery, recycling or reclaiming must
be followed. Fines and/or incarceration my be levied
for noncompliance.
fore removing access panel.
HPXA19 units use single-pole contactors. Potential exists for electrical
shock resulting in injury or death.
Line voltage exists at all components
(even when unit is not in operation).
All major components (indoor blower and coil) must be
matched according to Lennox recommendations for the
compressor to be covered under warranty. Refer to the Engineering Handbook for approved system matchups. A
misapplied system will cause erratic operation and can result in early compressor failure.
II−Unit Components
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during unit installation and service to protect the unit’s electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the unit, the control and the technician at the
same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an
unpainted unit surface before performing any
service procedure.
A−Two−Stage Scroll Compressor (B1)
TWO−STAGE MODULATED SCROLL
slider ring
solenoid actuator coil
FIGURE 1
The scroll compressor design is simple, efficient and requires few moving parts. A cutaway diagram of the scroll
compressor is shown in figure 1.The scrolls are located in
the top of the compressor can and the motor is located just
below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered
around the unique spiral shape of the scroll and its inherent
properties. Figure 2 shows the basic scroll form. Two identical scrolls are mated together forming concentric spiral
shapes (figure 3). One scroll remains stationary, while the
other is allowed to orbit" (figure 4). Note that the orbiting
scroll does not rotate or turn but merely orbits" the stationary scroll.
SCROLL FORM
FIGURE 2
CROSS−SECTION OF SCROLLS
DISCHARGE
PRESSURE
TIPS SEALED BY
DISCHARGE PRESSURE
DISCHARGE
STATIONARY
SCROLL
SUCTION
ORBITING SCROLL
FIGURE 3
The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls
(figure 4 − 1). The centrifugal action of the orbiting scroll
seals off the flanks of the scrolls (figure 4 − 2). As the orbiting
motion continues, the gas is forced toward the center of the
scroll and the gas pocket becomes compressed (figure 4
−3). When the compressed gas reaches the center, it is discharged vertically into a chamber and discharge port in the
top of the compressor (figure1). The discharge pressure
forcing down on the top scroll helps seal off the upper and
lower edges (tips) of the scrolls (figure 3). During a single orbit, several pockets of gas are compressed simultaneously
providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid return. If liquid enters the scrolls, the orbiting scroll is allowed
to separate from the stationary scroll. The liquid is worked
toward the center of the scroll and is discharged.
Due to its efficiency, the scroll compressor is capable of
drawing a much deeper vacuum than reciprocating compressors. Deep vacuum operation can cause internal fusite
arcing resulting in damaged internal parts and will result in
compressor failure. This type of damage can be detected
and will result in denial of warranty claims. The scroll compressor can be used to pump down refrigerant as long as
the pressure is not reduced below 7 psig.
NOTE − During operation, the head of a scroll compressor
may be hot since it is in constant contact with discharge
gas.
The scroll compressors in all HPXA19 model units are designed for use with R410A refrigerant and operation at high
pressures. Compressors are shipped from the factory with
3MA (32MMMA) P.O.E. oil. See electrical section in this
manual for compressor specifications.
Page 3
TWO−STAGE OPERATION
The two−stage scroll compressor operates like any stan-
dard scroll compressor with the exception the two−stage
compressor modulates between first stage (low capacity
approximately 67%) and second stage (high capacity).
Modulation occurs when gas is bypassed through bypass
ports (figure 5 bypass ports open) in the first suction pock-
et. This bypassing of gas allows the compressor to operate
on first stage (low capacity) if thermostat demand allows.
Indoor thermostat setting will determine first or second
HOW A SCROLL WORKS
MOVEMENT OF ORBIT
SUCTION
ORBITING
SUCTION
POCKET
SCROLL
stage operation. The compressor will operate on first−stage
until demand is satisfied or the indoor temperature reaches
the thermostat set point calling for second−stage.
Second−stage (high capacity) is achieved by blocking the
bypass ports (figure 5 bypass ports closed) with a slider
ring. The slider ring begins in the open position and is controlled by a 24VDC internal solenoid. On a Y2 call the inter-
nal solenoid closes the slider ring, blocking the bypass
ports and bringing the compressor to high capacity. Two−
stage modulation can occur during a single thermostat demand as the motor runs continuously while the compressor
modulates from first−stage to second− stage.
SUCTION
INTERMEDIATE
PRESSURE
GAS
CRESCENT
SHAPED GAS
POCKET
3
12
FLANKS
SUCTION
STATIONARY SCROLL
SEALED BY
CENTRIFUGAL
FORCE
SUCTION
4
HIGH
PRESSURE
GAS
FIGURE 4
TWO−STAGE MODULATION
Bypass Ports
Closed
High Capacity
DISCHARGE
POCKET
Bypass Ports
Open
Low Capacity
FIGURE 5
Page 4
INTERNAL SOLENOID (L34)
Procedure
The internal unloader solenoid controls the two−stage operation of the compressor by shifting a slide ring mechanism to open two by−pass ports in the first compression
pocket of the scrolls in the compressor. The internal solenoid is activated by a 24 volt direct current solenoid coil.
The coil power requires 20VAC. The internal wires from the
solenoid in the compressor are routed to a 2 pin fusite connection on the side of the compressor shell. The external
electrical connection is made to the compressor with a
molded plug assembly. This plug contains a full wave rectifier that converts 24 volt AC into 24 volt DC power to power
the unloader solenoid. Refer to unit diagram for internal circuitry view of plug.
If it is suspect the unloader is not operating properly, check
the following
IMPORTANT
This performance check is ONLY valid on systems
that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant
charge. All components in the system must be functioning proper to correctly perform compressor
modulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).
STEP 1 Confirm low to high capacity compressor
operation
Tools required
Refrigeration gauge set
Digital volt/amp meter
Electronic temperature thermometer
On-off toggle switch
1. Turn main power "OFF" to outdoor unit.
2. Adjust room thermostat set point above (heating operation on heat pump) or below (cooling operation) the
room temperature 5ºF.
3. Remove control access panel. Install refrigeration
gauges on unit. Attach the amp meter to the common
(black wire) wire of the compressor harness. Attach
thermometer to discharge line as close as possible to
the compressor.
4. Turn toggle switch "OFF" and install switch in series
with Y2 wire from room thermostat.
5. Cycle main power "ON."
6. Allow pressures and temperatures to stabilize before taking any measured reading (may take up to 10
minutes).
NOTE − Block outdoor coil to maintain a minimum of 375
psig during testing).
7. Record all of the readings for the Y1 demand on
table 1.
8. Close switch to energize Y2 demand.
9. Allow pressures and temperatures to stabilize before taking any measured reading (this may take up to
10 minutes).
10. Record all of the readings of Y2 demand on table
1.
NOTE − On new installations or installations that have
shut down for an extended period of time, if the compressor does not cycle from low stage to high stage on
the first attempt, it may be necessary to recycle the compressor back down to low stage and back up to high
stage a few times in order to get the bypass seals to
properly seat
Compare Y1 readings with Y2 readings in table 1. Some
readings should be higher, lower or the same. If the
readings follow what table 1 specifies, the compressor is
operating and shifting to high capacity as designed. If the
readings do not follow what table 1 specifies, continue to
step 2 to determine if problem is with external solenoid
plug power.
Page 5
TABLE 1
Compressor Operation
Unit Readings
Y1 −
1st-Stage
Expected Results
Compressor
VoltageSame
AmperageHigher
Condenser Fan motor
AmperageSame or Higher
Temperature
AmbientSame
Outdoor Coil Discharge AirHigher in Cooling
STEP 2 Confirm DC voltage output on compressor
solenoid plug
A − Compressor solenoid plug WITH built in full wave−
rectifier (LSOM I) that converts 24 volt AC into 24 volt
DC power. See Table 1 for units equipped with the
LSOM I.
1. Shut power off to outdoor unit.
2. Supply 24 volts AC control voltage to the wire ends
of the full wave rectifier plug. Listen for a click" as the
solenoid is energized. See figure 6.
apply 24vac
meter
compressor
fusite
terminals
rectifier plug leads
solenoid fusite
terminals
compressor
FIGURE 6
3. Unplug the full wave rectifier plug from the fusite
connection on the compressor.
4. Turn the low voltage power back onto the unit. Supply 24VAC to the wires of the full wave rectifier plug. Set
volt meter to DC volts and measure the DC voltage at
the female connector end of the full wave rectifier plug.
The DC voltage reading should be 1.5 to 3 volts lower
than the input voltage to the plug wire leads. (EX: Input
voltage is 24VAC output voltage is 22VDC).
See figure 7.
rectifier plug leads
apply 24vac
compressor
fusite
terminals
compressor
solenoid
fusite
terminals
meter
FIGURE 7
If the above checks verify that the solenoid plug is providing power to cycle into high capacity operation, continue to step 3 to determine if problem is with solenoid
coil in compressor
Page 6
STEP 3 Confirm internal unloader solenoid has proper resistance
1. Shut all power off to unit (main and low voltage)
2. Unplug the molded plug from the compressor solenoid 2−pin fusite.
3. Using a volt meter set on the 200 ohm scale
Replace the Compressor under these conditions:
Bad Solenoid
a. Measure the resistance at the 2−pin fusite. The resistance should be 32 to 60 ohms depending on compressor
temperature. If no resist ancereplace compressor.
b. Measure the resistance from each fusite pin to
ground. There should not be continuity to ground. If solenoid coil is grounded, replace compressor.
Good Solenoid
a. Seals not shifting, replace compressor
b. Slider ring not shifting, replace compressor.
B−Contactor (K1)
The compressor is energized by a contactor located in the
control box. All XP19 units are single phase and use single−
pole contactors.
C−Low Pressure Switch (S87)
The XP19 is equipped with an auto−reset low pressure
switch which is located on the suction line. The switch shuts
off the compressor when the suction pressure falls below
the factory setting. This switch is ignored during the first 90
seconds of compressor start up, during defrost operation,
90 seconds after defrost operation, during test mode and
when the outdoor temperature drops below 15°F.
The switch closes when it is exposed to 55 psig and opens
at 25 psig. It is not adjustable.
D−High Pressure Switch (S4)
E−Capacitor (C12)
The compressor in XP19−024, −036, −048 and −060 units
use a permanent split capacitor (see unit wiring diagram).
The capacitor is located inside the unit control box. Ratings
are on capacitor side.
F−Condenser Fan with
Variable Speed Motor(B4)
The variable speed condenser fan motor (figure 14) used in all
units is a three-phase, electronically controlled d.c. brushless
motor (controller converts single phase a.c. to three phase
d.c.), with a permanent-magnet-type rotor, manufactured by
GE. Because this motor has a permanent magnet rotor it does
not need brushes like conventional D.C. motors. The motors
consist of a control module and motor . Internal components
are shown in figure 15. The stator windings are split into three
poles which are electrically connected to the controller. This ar-
rangement allows motor windings to be turned on and off in
sequence by the controller.
The controller is primarily an a.c. to d.c. converter. Con-
verted d.c. power is used to drive the motor. The control-
ler contains a microprocessor which monitors varying
conditions inside the motor (such as motor workload).
G−Contactor (K1)
The compressor is energized by a contactor located in the
control box. All HPXA19 units are single phase and use single−
pole contactors.
H−Low Pressure Switch (S87)
IMPORTANT
Pressure switch settings for R410A refrigerant will
be significantly higher than units with R22.
An auto-reset, single-pole/single-throw high pressure switch
is located in the liquid line. This switch shuts off the compressor when liquid line pressure rises above the factory setting.
The switch is normally closed and is permanently adjusted to
trip (open) at 640 +
ure 13 for switch location.
10 psi and close at 448 + 10 psi. See fig-
Page 7
The HPXA19 is equipped with an auto−reset low pressure
switch which is located on the suction line. The switch shuts
off the compressor when the suction pressure falls below
the factory setting. This switch is ignored during the first 90
seconds of compressor start up, during defrost operation,
90 seconds after defrost operation, during test mode and
when the outdoor temperature drops below 15°F.
The switch closes when it is exposed to 55 psig and opens
at 25 psig. It is not adjustable.
I−High Pressure Switch (S4)
IMPORTANT
Pressure switch settings for R410A refrigerant will
be significantly higher than units with R22.
An auto-reset, single-pole/single-throw high pressure switch
is located in the liquid line. This switch shuts off the compressor when liquid line pressure rises above the factory setting.
The switch is normally closed and is permanently adjusted to
trip (open) at 640 +
ure 13 for switch location.
J−Low Ambient Thermostat (S23)
Second−stage low ambient thermostat S23 (figure 8) is a
SPST thermostat located in the compressor compartment.
The control uses a cap-tube sensor to monitor the temperature inside the compressor compartment. The cap-tube
sensor is coiled adjacent to the control.
Temperature Sensor
(Cap-Tube)
10 psi and close at 448 + 10 psi. See fig-
(Second−Stage)
Low Ambient Thermostat S23
Regional climatic conditions may require the control to be adjusted to a different setting. The adjustment screw is located
on the control. A hole cut into the bottom shelf of the control
box provides access to the control from the compressor
compartment. See figure 9.
Adjusting Low Ambient Thermostat
Adjustment screw can be
reached by inserting a screwdriver through the slot in control
box.
Turn screw clockwise to increase
switchover temperature.
FIGURE 9
Figure 10 shows the adjustment range of the control. Turn
adjustment screw clockwise to raise the switchover temperature and counterclockwise to lower the switchover
temperature.
Low Ambient Thermostat
49
adjustment
screw
FIGURE 8
S23 continually monitors the temperature inside the compressor compartment. When compressor compartment
temperature drops below the control setpoint, the control
closes. When the control closes, the contacts shunt across
Y1 and Y2 inside the unit. When Y1 heating demand is
present and S23 is closed, the compressor will run in high
capacity. The compressor will operate in high capacity
mode anytime there is a Y1 heating call from indoor thermostat, until the units control box warms and S23 opens.
S23 has field adjustable setpoints. Temperature differential
(difference between cut-in and cut-out) is fixed and cannot
be adjusted. Table 2 shows S23 control setpoints. The control is factory set to close at 40+
and reset at 50+
2°F on a temperature rise.
2°F on a temperature drop
TABLE 2
Control Setpoints
Low Ambient Thermostat
Adjustable Range
Cut-In
(Close on Temperature Drop)
Cut-Out
(Open on Temperature Rise)
Factory
Setting
40+2°F37+2°F 55+2°F
50+2°F47+2°F 65+2°F
Min.Max.
43
*40
37
55
FIGURE 10
K−Reversing Valve (L1)
A refrigerant reversing valve with an electromechanical solenoid is used to reverse refrigerant flow during unit operation. The reversing valve is energized during cooling demand and during defrost.
L−Transformer (T46)
Transformer T46 is located in the control box and is energized any time the compressor is operating.
M−Solenoid Relay (K195)
Relay K195 is N.O. SPDT relay located in the control box.
On a Y2 call K195−1 closes allowing AC voltage from
(T46) to the two pin full wave rectifier plug (D4).
N−Rectifier Plug (D4)
D4 is a molded assembly that plugs into the compressor.
On a Y2 call D4 converts 24 volts AC to 24 volts DC. The
DC voltage energizes solenoid L34, allowing the compressor to operate at full capacity.
Page 8
O−Discharge Line Thermostat (S5)
S5 is an automatic reset SPST N.C. switch which opens on
temperature rise. S5 is located on the discharge line and
wired in series with S4 high pressure switch on the defrost
control board. When discharge line temperature rises to
8°F the switch opens and shuts down the compres-
275° +
sor. The switch resets when discharge line temperature
drops to 225° +
11°F.
P−Dual Capacitor (C12)
The compressor and fan in HPXA19−024, −036, −048 and
−060 units use permanent split capacitor motors. A single
dual" capacitor is used for both the fan motor and the compressor (see unit wiring diagram). The two sides (fan and
compressor) of the capacitor have different mfd ratings and
may change with each compressor. The capacitor is located
inside the unit control box.
Q−Condenser Fan Motor (B4)
HPXA19−024, −036, −048 and −060 units use single−phase
PSC fan motors which require a run capacitor. The FAN"
side of the dual capacitor is used for this purpose. In all
units, the outdoor fan is controlled by the compressor contactor. See ELECTRICAL DATA and SPECIFICATIONS
section for more information. See figure 11 if condenser fan
motor replacement is necessary. Rain shield location is
critical on the condenser fan assembly. Two shields are
used in unison to prevent moisture from entering the motor
bearings. Installing the shields to close to the bearing hub
will create noise and may affect operation. Installing too far
away will allow moisture to enter the bearing, resulting in
motor failure. See figure 12.
"A" SEE TABLE 3
Condenser fan
and motor
FIGURE
11
TABLE 3
HPXA19 UNIT"A" DIM. + 1/8"
−024, −0361 1/16"
−038
−048
−060
RAIN SHIELD LOCATION
(See figure 14 for HPXA19−038)
Critical Dimension
plastic
shield
fiber
shield
FIGURE 12
FAN
GUARD
Wiring
Drip loop
1 3/16"
1/4" (.250)
run capacitor
start capacitor
(−024 unit only)
system
operation monitor
defrost control
charge compensator
(−038 and −048 units)
TXV/check valve
discharge line
compressor terminal plug
vapor line
low pressure switch
discharge temperature
thermostat
HPXA19 PARTS ARRANGEMENT
outdoor fan
(variable speed
on 038 units)
contactor
vapor valve
and
gauge port
two−stage compressor
filter drier
high pressure switch
FIGURE 13
Page 9
R−Condenser Fan with
Variable Speed Motor(B4)
(−038 only)
The variable speed condenser fan motor (figure 14) used in all
HPXA19−038 units is a three-phase, electronically controlled
d.c. brushless motor (controller converts single phase a.c. to
three phase d.c.), with a permanent-magnet-type rotor,
manufactured by GE. Because this motor has a permanent
magnet rotor it does not need brushes like conventional D.C.
motors. The motors consist of a control module and motor .
Internal components are shown in figure 15. The stator windings are split into three poles which are electrically connected
to the controller. This arrangement allows motor windings to be
turned on and off in sequence by the controller.
The controller is primarily an a.c. to d.c. converter. Converted d.c. power is used to drive the motor. The controller contains a microprocessor which monitors varying
conditions inside the motor (such as motor workload).
The controller uses sensing devices to know what position
the rotor is in at any given time. By sensing the position of
the rotor and then switching the motor windings on and off
in sequence, the rotor shaft turns the blower.
motor speed and allows the motor to compensate for varying
load conditions as sensed by the controller. In this case, the
controller monitors the static workload on the motor and varies motor rpm in order to maintain constant airflow (cfm).
Motor rpm is continually adjusted internally to maintain
constant static pressure against the fan blade. The controller monitors the static work load on the motor and motor
amp-draw to determine the amount of rpm adjustment.
Blower rpm is adjusted internally to maintain a constant
cfm. The amount of adjustment is determined by the incremental taps which are used and the amount of motor loading sensed internally. The motor constantly adjusts rpm to
maintain a specified cfm.
Initial Power Up
When line voltage is applied to the motor, there will be a
large inrush of power lasting less than 1/4 second. This inrush charges a bank of DC filter capacitors inside the controller. If the disconnect switch is bounced when the disconnect is closed, the disconnect contacts may become
welded. Try not to bounce the disconnect switch when applying power to the unit.
VARIABLE SPEED CONDENSER FAN MOTOR
RED
YELLOW
BLACK
RED
BLUE
motor
control module
FIGURE 14
BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 15
Internal Operation
The condenser fan motor is a variable speed motor with RPM
settings at 700 (Y1) and 820 (Y2). The variation in speed is
accomplished each time the controller switches a stator winding (figure14) on and off, it is called a pulse." The length of
time each pulse stays on is called the pulse width." By varying the pulse width the controller varies motor speed (called
pulse-width modulation"). This allows for precise control of
The DC filter capacitors inside the controller are connected
electrically to the speed tap wires. The capacitors take
approximately 5 minutes to discharge when the disconnect
is opened. For this reason it is necessary to wait at least 5
minutes after turning off power to the unit before attempting
to service motor.
DANGER
Disconnect power from unit and wait at
least five minutes to allow capacitors
to discharge before attempting to service motor. Failure to wait may cause
personal injury or death.
Motor Start-Up
At start-up, the motor may gently rock back and forth for a
moment. This is normal. During this time the electronic
controller is determining the exact position of the rotor.
Once the motor begins turning, the controller slowly
eases the motor up to speed (this is called soft-start").
The motor may take as long as 10-15 seconds to reach
full speed. If the motor does not reach 200rpm within 13
seconds, the motor shuts down. Then the motor will immediately attempt a restart. The shutdown feature provides protection in case of a frozen bearing or blocked
fan blade. The motor may attempt to start eight times. If
the motor does not start after the eighth try, the controller
locks out. Reset controller by momentarily turning off
power to unit.
Page 10
Rain shield location is critical on the condenser fan assembly. Installing the shields to close to the bearing hub will
create noise and may affect operation. Installing too far
away will allow moisture to enter the bearing resulting in
motor failure. See figure 16 .
S−Filter Drier
A filter drier designed for all HPXA19 model units is factory
installed in the liquid line. The filter drier is designed to re-
move moisture and foreign matter, which can lead to com-
pressor failure.
RAIN SHIELD LOCATION
(−038 only)
3"
Critical
Dimension
plastic
shield
fiber
shield
FIGURE 16
Troubleshooting
If first or second stage thermostat call for cool is present
and the variable speed condenser fan motor does not energize, check voltage at the breaker box. If voltage is present
do the following and reference figure 17.
1− Check for 240 volts between the compressor RED wi-
res.
2− Initiate a first stage call for cool. Check for 24 volts be-
tween the fan motor YELLOW wire and fan motor
BLACK wire.
3− Initiate a second stage call for cool. Check for 24 volts
between the fan motor YELLOW wire and fan motor
BLACK wire, then check for 24 volts between the fan
motor BLUE wire and fan motor BLACK.
4− Repeat steps 1 through 3 with a HEAT call.
Moisture and / or Acid Check
Because POE oils absorb moisture, the dryness of the
system must be verified any time the refrigerant sys-
tem is exposed to open air. A compressor oil sample
must be taken to determine if excessive moisture has been
introduced to the oil. Table 4 lists kits available from Lennox
to check POE oils.
If oil sample taken from a system that has been exposed to
open air does not test in the dry color range, the filter drier
MUST be replaced.
IMPORTANT
Replacement filter drier MUST be approved for
R410A refrigerant and POE application.
Foreign Matter Check
It is recommended that a liquid line filter drier be replaced
when the pressure drop across the filter drier is greater
than 4 psig.
T−Accumulator (HPXA19−060 only)
ALL 5 ton HPXA19 units are equipped with an accumulator.
The purpose of the accumulator is to trap and evaporate all
liquid refrigerant returning to the compressor.
1st Stage (low capacity − 700 rpm)
RED
B4
RED
YELLOW
BLUE
BLACK
common
Y1
Y2
240V
240V
24V
0V
24V
2nd Stage (High capacity − 820 rpm)
RED
B4
RED
YELLOW
BLUE
BLACK
common
Y1
Y2
240V
240V
24V
24V
24V
FIGURE 17
U−Charge Compensator
HPXA19−038 and −048 series units are equipped with a
charge compensator located in the vapor line between the
reversing valve and outdoor coil manifold. The compensa-
tor is used to collect and store excess refrigerant in the
heating mode. Figure 18 shows operation of the charge
compensator.
In heating mode, the vapor line passing through the charge
compensator tank is cooler than the liquid line. Excess re-
frigerant (condensed liquid) from the indoor coil is trapped
by the compensator. The vapor line is cooler than the liquid
line so liquid migrates from the liquid line to the compensa-
tor tank where it is stored. In cooling mode, the vapor line
passing through the charge compensator tank is hotter
than the liquid line. Stored liquid is boiled and forced back
into the liquid line for circulation.
Page 11
TABLE 4
KITCONTENTSTUBE SHELF LIFE
10N46 − Refrigerant AnalysisCheckmate−RT700
10N45 − Acid Test TubesCheckmate−RT750A (three pack)
10N44 − Moisture Test Tubes
74N40 − Easy Oil Test Tubes
74N39 − Acid Test KitSporlan One Shot − TA−1
Checkmate − RT751 Tubes (three
pack)
Checkmate − RT752C Tubes (three
pack)
2 − 3 years @ room temperature. 3+
years refrigerated
6 − 12 months @ room temperature. 2
years refrigerated
2 − 3 years @ room temperature. 3+
years refrigerated
CHARGE COMPENSATOR OPERATION
COOLING MODE
Vapor Line
(To Outdoor Coil)
Compensator Tank
During cooling mode, the vapor line is hotter than the liquid line. Stored liquid is
heated (boiled) and forced
back into circulation.
Stored Liquid
To Liquid Line
To be Circulated
Through Indoor Coil
Vapor Line
(From Compressor Discharge Port)
HEATING MODE
Vapor Line
(From Outdoor Coil)
Compensator Tank
During heating mode, the vapor line is cooler than the liquid line. Excess refrigerant is
forced into the charge compensator where it condenses
and collects.
Excess Refrigerant
To be Condensed and Stored
as Liquid
Vapor Line
(To Compressor Suction Port)
FIGURE 18
V−Lennox System Operation Monitor (A132)
The Lennox system operation monitor (LSOM) is a 24 volt
powered module wired directly to the indoor unit . See diagnostic module A132 on wiring diagram and figure 19. The
LSOM is located in the control box and is used to trouble
shoot problems in the system. The module has three LED’s
for troubleshooting: GREEN indicates power status, YELLOW indicates an abnormal condition and RED indicates
thermostat demand, but compressor not operating. See
table 5 for troubleshooting codes.
IMPORTANT
The LSOM is not a safety component and cannot
shut down or control the HPXA19. The LSOM is a
monitoring device only.
W−Crankcase Heater (HR1)
Compressors in all units are equipped with a 70 watt bellyband type crankcase heater. HR1 prevents liquid from accumulating in the compressor. HR1 is controlled by the
crankcaseheater thermostat.
X− Crankcase heater Thermostat (S40)
Thermostat S40 controls the crankcase heater in all units.
S40 is located on the liquid line. When liquid line temperature drops below 50° F the thermostat S40 closes energizing
HR1. The thermostat will open, de−energizing HR1 once liquid line temperature reaches 70° F .
System Operation Monitor
LE
D
Y
C
R
LED’s
FIGURE 19
Y−Defrost System
The demand defrost controller uses basic differential temperature means to detect when the system performs poorly because of ice build−up on the outdoor coil. The controller also uses self−calibrating" principles to calibrate itself
when the system starts and after every time the system
defrosts. The control board has the following components: defrost relays, anti−short cycle timed−off control,
pressure switch/safety control, 5−trip lockout circuit, test
mode pins, ambient and coil temperature sensors, field
selectable termination temperature pins, and a field low
voltage connection terminal strip. See figure 20.
The control monitors ambient temperature, outdoor coil
temperature and total run time to determine when a defrost cycle is required. Two temperature probes are permanently attached to the control. The coil temperature
probe is designed with a spring clip to allow mounting to
the outside coil tubing. The location of the coil sensor is
important for proper defrost operation. See figure 21 for
coil sensor location. The ambient temperature sensor is
located in the PVC tube next to the filter drier.
NOTE − The logic of the demand defrost board accurately
measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into
longer running time between defrost cycles as more frost
accumulates on the outdoor coil before the board initiates
defrost cycles.
Page 12
TABLE 5
System Operation Monitor LED Troubleshooting Codes
Status LED
Green Power"Module has power.24VAC control power is present at the module terminal.
Red Trip"
Yellow Alert"
Flash Code 1
(Does not apply to heat
pump or to two−stage
split systems)
Yellow Alert"
Flash Code 2
Yellow Alert"
Flash Code 3
Yellow Alert"
Flash Code 4
Yellow Alert"
Flash Code 5
Status LED Description
Thermostat demand signal
Y1 is present, but the compressor is not running.
Heat pump only−Trip light will
be on during defrost board 5
minute delay with Y thermostat call.
Long Run Time
Compressor is running extremely long run cycles
System Pressure Trip
Discharge or suction pressure out of limits or compressor overloaded
Short Cycling
Compressor is
running
only briefly
Locked Rotor
Open Circuit
Status LED Troubleshooting Information
1
Compressor protector is open.
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low pressure switch open if present in the system.
6
Compressor contactor has failed to close.
1
Low refrigerant charge.
2
Evaporator blower is not running.
3
Evaporator coil is frozen.
4
Faulty metering device.
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning.
1
High head pressure.
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
4
Return air duct has substantial leakage.
5
If low pressure switch is present, check Flash Code 1 information.
1
Thermostat demand signal is intermittent.
2
Time delay relay or control board is defective.
3
If high pressure switch is present, check Flash Code 2 information.
4
If low pressure switch is present, check Flash Code 1 information.
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at disconnect is low).
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambient temperature.
7
Compressor windings are damaged.
1
Yellow Alert"
Flash Code 6
Yellow Alert"
Flash Code 7
Yellow Alert"
Flash Code 8
Yellow Alert"
Flash Code 9
Open Start Circuit
Current only in run circuit
Open Run Circuit
Current only in start circuit
Welded Contactor
Compressor always runs
Low Voltage
Control circuit < 17VAC
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
3
Compressor start winding is damaged.
1
Open circ uit in compress or start wiring or connections.
2
Compressor start winding is damaged.
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to module.
1
Control circuit transformer is overloaded
2
Low line voltage (contact utility if voltage at disconnect is low.)
Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated.
TRIP and ALERT LEDs flashing at the same time indicates that the control circuit voltage is too low for operation.
Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on.
Page 13
Component Locations Will
Vary With Board Manufacture
pressure
switch
circuit
connections
reversing valve
connections
coil
sensor
COIL SENSOR LOCATION
HPXA19−036/−048/−060
Coil sensor should be on
the 5th hairpin from the
bottom on the outside loop.
HPXA19−024
Coil sensor should be on the
6th hairpin from the top on
the outside loop.
DELAY
Y2
FIGURE 20
HPXA19−038
Coil sensor should be on
the 8th hairpin down from
the top on the outside loop.
FIGURE 21
r
defrost board
test pins
diagnostic LEDs
24V terminal
strip connections
Y2
field select
temperature pins
ambient
sensor
The temperature probes cannot be removed from the control. The control and the attached probes MUST be replaced as a unit. Do not attempt to cut or splice probe wires.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the diagnostic condition. See table 6.
HI−PS/LO−PS Terminals
High pressure switch (S4) is factory wired into the defrost
board HI−PS terminals. When (S4) trips, the defrost board
will cycle off the compressor and the strike counter in the
board will count one strike.
Low pressure switch (S87) is factory wired into the defrost
board LO−PS terminals. When (S87) trips, the defrost
board will cycle off the compressor and the strike counter
in the board will count one strike.
(S87) is ignored during certain conditions:
During the defrost cycle and 90 seconds after the
termination of defrost
When the average ambient sensor temperature is
below 15 F (−9)
For 90 seconds following the start up of the
compressor
During "Test" mode
5−Strike Lockout Feature
The internal control logic of the board counts the pres-
sure switch trips only while the Y1 (Input) line is active. If
a pressure switch opens and closes four times during a
Y1 (Input), the control logic will reset the pressure switch
trip counter to zero at the end of the Y1 (Input). If the
pressure switch opens for a fifth time during the current
Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be
reset by cycling OFF the 24−volt power to the control
board or by shorting the TEST pins. All timer functions
(run times) will also be reset.
If a pressure switch or discharge line thermostat switch
opens while the Y1 Out line is engaged, a 5−minute short
cycle will occur after the switch closes.
DELAY" Option
The defrost board has a field selectable function to reduce
occasional noise that may occur while the unit is cycling in
and out of defrost mode. When a jumper is installed on the
DELAY" pins, the compressor will cycle off for 30 seconds
going in and out of defrost mode.
NOTE − 30 second off cycle is not functional when
jumpering TEST" pins.
Page 14
LED 1LED 2ConditionPossible Cause(s)Solution
prope
2
Improper refrigerant charge
pp,p
ppgp
leaks. Replace metering device
OFFOFFPower problem
ONONCoil sensor problem
OFFONAmbient sensor problem
FLASHFLASHNormal operation
ONOFF
ONFLASH
FLASHON
ALTERNATING
FLASH
The demand defrost control board initiates a defrost cycle based on either frost detection or time.
Frost Detection − If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds
the maximum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature
defrost system.
Time − If 6 hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C),
the demand defrost control will initiate a defrost cycle.
Actuation − When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the
compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The control
will attempt to self−calibrate after this (and all other) defrost cycle(s). Calibration success depends on stable system temperatures during the 20−minute
calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run time. Once the
defrost board is calibrated, it will use demand defrost logic to initiate a defrost cycle. A demand defrost system initiates defrost when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor
run time has been logged since the last defrost cycle.
Termination − The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the
defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 34 minutes of run time.
Test Mode − When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature
jumper across the Test" pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ignore the test pins
and revert to normal operation. The jumper will initiate one cycle per test.
Operational Description
The defrost control board has three basic operational
modes: normal, defrost, and calibration.
The demand defrost board monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and
compressor run time to determine when a defrost cycle is
required.
When a defrost cycle is initiated, the control energizes the
reversing valve solenoid and turns off the condenser fan.
The control will also put 24VAC on the W1 (auxiliary heat)
line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination temperature, the defrost time of 14 minutes has been completed,
or the room thermostat demand cycle has been satisfied.
(If the temperature select shunt is not installed, the default
termination temperature will be 100°F.) If the room
ALTERNATING
FLASH
Normal Mode
Defrost Mode
TABLE 6
Defrost Control Board Diagnostic (5 strike)
1
No power (24V) to board terminals
R & C.
2
Board failure.
1
Coil temperature outside of sensor
range.
2
Faulty sensor wiring connections at
board or poor sensor contact on coil.
3
Sensor failure.
1
Ambient temperature outside of
sensor range.
2
Faulty sensor wiring connections at
board or sensor.
3
Sensor failure.
Unit operating normally or in standby
mode.
5−Strike pressure lockout
(Short test pins or reset
24V power to board to
override lockout)
Low pressure switch circuit
open during Y1 demand
High pressure switch or
discharge thermostat
switch circuit open during
Y1 demand
5−minute delay
(Jumper test pins to override delay)
Demand Defrost Operation
1
Restricted air flow over indoor or
outdoor coil.
2
Im
3
tion.
4
Poor contact between coil sensor
and coil.
Thermostat demand for cooling or
heat pump operation. Unit operating
in 5−minute anti−short−cycle mode.
r refrigerant charge.
Improper metering device opera-
thermostat demand cycle terminates the cycle, the defrost
cycle will be held until the next room thermostat demand
cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue
the defrost cycle until the cycle is terminated in one of the
methods mentioned above. If a defrost is terminated by
time and the coil temperature did not remain above 35°F
(2°C) for 4 minutes, the control will go into the 34−minute
Time/Temperature mode.
The board is considered uncalibrated when power is applied to the board, after cool mode operation, or if the coil
temperature exceeds the termination temperature when it
is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the
temperature of both the coil and the ambient sensor are
measured to establish the temperature differential which is
required to allow a defrost cycle.
Page 15
1
Check control transformer power
(24V).
2
If power is available and LED(s) are
unlit, replace board and all sensors.
1
Sensor function will resume when
coil temperature is between −20°F
and 110°F.
2
Check sensor wiring connections at
board and sensor contact on coil.
3
Replace board and all sensors.
1
Sensor function will resume when
coil temperature is between −20°F
and 110°F.
2
Check sensor wiring connections at
board and sensor.
3
Replace board and all sensors.
None required.
1
Remove any blockages or restric-
tions. Check outdoor fan motor for
proper operation.
2
.
Check approach, superheat & sub-
cooling temperatures.
3
Check system pressures. Repair
4
Make sure that sensor is properly
positioned on coil and that firm contact is established. Refer to service
manual for proper placement.
None required.
Calibration Mode
.
Z−Start Capacitor (C7) −024 model only
All 2 ton HPXA19 units are equipped with a start capacitor
(C7). The capacitor is located in the control box and wired
in parallel with the compressor side of the dual capacitor.
C7 is de−energized by potential relay K31 when the compressor nears full speed.
AA−Potential Relay (K31) −024 model only
III−REFRIGERANT SYSTEM
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections). Use Lennox
L15 series line sets as shown in table 7.
Separate liquid and suction service ports are provided at
the service valves for connection of gauge manifold during
charging procedure. Figure 22 shows HPXA19 refrigerant
flow and gauge manifold connections.
All 2 ton HPXA19 units are equipped with potential relay
K31, which controls the operation of the starting circuit. The
relay is located inside the control box and is normally
closed when contactor K1 is de−energized. When K1 is energized the compressor begins start up. K31 remains
closed closed during start up and capacitor C7 remains in
the circuit. When the compressor reaches 75% of its
speed, K31 is energized, de−energizing capacitor C7.
HPXA19 COOLING CYCLE
(Showing Gauge Manifold Connections)
OUTDOOR UNIT
DISTRIBUTOR
EXPANSION/
CHECK VALVE
LOW
PRESSURE
HIGH
PRESSURE
BIFLOW
FILTER / DRIER
MUFFLER
OUTDOOR
COIL
Model
−024,−
036
−038
−048
−060
Valve Field Size
Connections
Liquid
Line
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
REVERSING VALVE
Vapor
Line
7/8 in.
22 mm
7/8 in.
22 mm
1−1/8 in.
29 mm
1−1/8 in.
29 mm
TABLE 7
Recommended Line Set
Liquid
Line
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
DIRECTION OF REFRIGERANT FLOW.
REFRIGERANT WILL FLOW IN OPPOSITE
DIRECTION IN HEATING CYCLE.
Vapor
Line
7/8 in.
19 mm
15 ft. − 50 ft.
4.6 m − 15 m
7/8 in.
22 mm
7/8 in.
22 mm
15 ft. − 50 ft.
4.6 m − 15 m
15 ft. − 50 ft.
4.6 m − 15 m
1−1/8 in.
29 mm
NOTE − ARROWS INDICATE
INDOOR UNIT
Fabricated
L15
Line Sets
L15−65
L15−65
L15−65
Field
GAUGE MANIFOLD
TO
R410A
DRUM
LIQUID
LINE
SERVICE
PORT
COMPRESSOR
SUCTION
SERVICE
PORT
NOTE−Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines
and indoor coil. Use suction gauge port to measure suction pressure during charging.
FIGURE 22
Page 16
VAPOR
LINE
VALV E
EXPANSION/CHECK
VALV E
INDOOR
COIL
A−Service Valves
IMPORTANT
Only use Allen wrenches of sufficient hardness
(50Rc − Rockwell Harness Scale min). Fully insert the wrench into the valve stem recess.
Service valve stems are factory torqued (from 9
ft lbs for small valves, to 25 ft lbs for large
valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated
at less than 50Rc risks rounding or breaking off
the wrench, or stripping the valve stem recess.
Access the liquid line and vapor line service valves (figures
23 and 24) and gauge ports are used for leak testing, evacuating, charging and checking charge. See table 8 for
torque requirements.
Each valve is equipped with a service port which has a factory−installed Schrader valve. A service port cap protects
the Schrader valve from contamination and serves as the
primary leak seal.
TABLE 8
PartRecommended Torque
To Close Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Using service wrench and hex head extension, turn
stem clockwise to seat valve. Tighten it firmly.
NOTE − Use a 3/16" hex head extension for liquid line
size.
3 − Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
Vapor Line (Ball Type) Valve
Vapor line service valves function the same way as the other valves, the difference is in the construction. These
valves are not rebuildable. If a valve has failed, you must
replace it. A ball valve valve is illustrated in figure 24.
The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−
free seal.
Liquid Line Service Valve
(Valve Closed)
service
port cap
service port
Service valve cap8 ft.− lb.11 NM
Sheet metal screws16 in.− lb.2 NM
Machine screws #1028 in.− lb.3 NM
Compressor bolts90 in.− lb.10 NM
Gauge port seal cap8 ft.− lb.11 NM
IMPORTANT
Service valves are closed to the outdoor unit and
open to line set connections. Do not open the valves
until refrigerant lines have been leak tested and
evacuated. All precautions should be exercised to
keep the system free from dirt, moisture and air.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench.
2 − Connect gauge to the service port.
3 − When testing is complete, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
To Open Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Using service wrench and hex head extension, back
the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for liquid line
size.
3 − Replace stem cap and tighten it firmly. Tighten finger
tight, then tighten an additional 1/6 turn.
insert hex
wrench here
stem cap
Liquid Line Service Valve
(Valve Open)
service
port cap
schrader
valve
stem
cap
Service Port Is Open
To Line Set When Valve Is
Closed (Front Seated)
insert hex
wrench here
FIGURE 23
to
indoor coil
to outdoor coil
service port
to
indoor coil
to outdoor coil
(valve front seated)
Page 17
Vapor Line (Ball Type) Service Valve
(Valve Open)
To open: rotate stem counter-clockwise 90°.
Schrader
valve
service
port
field side
Use Adjustable Wrench
To close: rotate stem clockwise 90°.
service port
ball
(shown open)
cap
unit side
stem cap
stem
FIGURE 24
IV−CHARGING
Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 15 ft.
(4.6m) line set. For varying lengths of line set, refer to table
9 for refrigerant charge adjustment.
TABLE 9
Liquid Line Set
Diameter
3/8 in.
(10mm)
Ozs. per 5 ft. (grams per 1.5m) adjust
from 15 ft. (4.6m) line set*
3 ounces per 5 feet
(85g per 1.5m)
*If line length is greater than 15 ft. (4.6m), add this amount.
If line length is less than 15 ft. (4.6), subtract this amount.
A−Leak Testing
After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be
checked for leaks.
WARNING
Refrigerant can be harmful if inhaled. Refrigerant
must be used and recovered responsibly. Failure
to follow this warning can lead to injury or death.
WARNING
Danger of explosion!
When using a high pressure gas such
as dry nitrogen to pressurize a refrigerant or air conditioning system, use
a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).
WARNING
Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire
and / or an explosion, that can result in personal injury or death.
Using an Electronic Leak Detector
1 − Connect a cylinder of R410A to the center port of the
manifold gauge set.
2 − With both manifold valves closed, open the valve on
the R410A cylinder (vapor only).
3 − Open the high pressure side of the manifold to allow
the R410A into the line set and indoor unit. Weigh in a
trace amount of R410A . [A trace amount is a maximum
of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.]
Close the valve on the R410A cylinder and the valve
on the high pressure side of the manifold gauge set.
Disconnect the R410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the manifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R410A
mixture. Correct any leaks and recheck.
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
B−Evacuating
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper piping and compressor parts.
Page 18
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 23,000 microns.
1 − Connect the manifold gauge set to the service valve
ports as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start vacuum pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to
determine if there is a rapid rise in absolute pressure.
A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.
WARNING
Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compressors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will
void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.
C−Charging
This system is charged with R410A refrigerant which operates at much higher pressures than R22. The check/expansion valve provided with the unit is approved for use
with R410A. Do not replace it with a valve designed for use
with R22. This unit is NOT approved for use with coils which
include metering orifices or capillary tubes.
Processing Procedure
The unit is factory−charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 15
foot (4.6m) line set. For varying lengths of line set, refer to
table 9 for refrigerant charge adjustment. .
IMPORTANT
Mineral oils are not compatible with R410A. If oil
must be added, it must be a polyol ester oil.
It is desirable to charge the system in the cooling cycle if
weather conditions permit. However, if the unit must be
charged in the heating season, one of the following procedures must be followed to ensure proper system charge.
Weighing in the Charge TXV Systems –
Outdoor Temp. < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit. Do this after any leaks have been repaired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other procedures outlined below.
Subcooling Method
Outdoor Temp. < 65°F (18°C)
When the outdoor ambient temperature is below 65°F
(18°C), use the subcooling method to charge the unit. It
may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 325−375 psig
(2240−2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of air
intake panels and move obstructions sideways until the liquid pressure is in the 325−375 psig (2240−2585 kPa) range.
Figure 25 shows a four sided unit for example..
Page 19
Blocking Outdoor Coil
Outdoor coil should be
blocked one side
at a time with cardboard
or plastic sheet until proper
testing pressures
are reached.
cardboard or
plastic sheet
FIGURE 25
1 − With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.
2 − At the same time, record the liquid line pressure reading.
3 − Use a temperature/pressure chart for R410A to deter-
mine the saturation temperature for the liquid line pres-
sure reading. See table 14.
4 − Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature − Liquid line tem-
perature = Subcooling)
5 − Compare the subcooling value with those in table 10. If
subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant. Be aware of the R410A refrigerant cylinder. It
will be light maroon−colored. Refrigerant should be
added through the vapor line valve in the liquid state.
Some R410A cylinders are equipped with a dip
tube that allows you to draw liquid refrigerant from
the bottom of the cylinder without turning the cyl-
inder upside−down. The cylinder will be marked if it
is equipped with a dip tube.
TABLE 10
2nd stage High Capacity
Model Number
HPXA19−02411.0 + 1 (6 + .5)
HPXA19−0368.5 + 1 (4.7 + .5)
HPXA19−03810.5 + 1 (5.8 + .5)
HPXA19−0487.5 + 1 (4.1 + .5)
HPXA19−0607.0 + 1 (3.9 + .5)
Conversion Temp. − Liquid Line Temp. °F (°C)
Subcooling Values
Charging Using Normal Operating Pressures
and the Approach Method
Outdoor Temp. >
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
tables 12 and 13, Normal Operating Pressures." Minor variations in these pressures may be expected due
to differences in installations. Significant differences
could mean that the system is not properly charged or
that a problem exists with some component in the system. Pressures higher than those listed indicate that
the system is overcharged. Pressures lower than
those listed indicate that the system is undercharged.
Verify adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer used to check out-
door ambient temperature to check liquid line temperature. Verify the unit charge using the approach method.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 11. If the values don’t agree with the those in table 11, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach
temperature.
TABLE 11
2nd Stage High Capacity
Model Number
HPXA19−0244.0 + 1 (2.2 + .5)
HPXA19−0367.0 + 1 (3.9 + .5)
HPXA19−0384.0 + 1 (2.2 + .5)
HPXA19−0488.0 + 1 (4.4 + .5)
HPXA19−06010.0 + 1 (5.6 + .5)
Liquid Line Temp. − Outdoor Ambient °F (°C)
65F (18C)
Approach Temperature
IMPORTANT
Use table 12 and table 13 as a general guide when
performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging/Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the
system is not properly charged or that a problem exists with some component in the system.
Polyol ester (POE) oils used with R410A refrigerant
absorb moisture very quickly. It is very important
that the refrigerant system be kept closed as much
as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make
connections.
IMPORTANT
Use recovery machine rated for R410 refrigerant.
If the HPXA19 system must be opened for any kind of service, such as compressor or filter drier replacement, you
must take extra precautions to prevent moisture from entering the system. The following steps will help to minimize
the amount of moisture that enters the system during recovery of R410A.
1 − Use a regulator−equipped nitrogen cylinder to break
the system vacuum. Do not exceed 5 psi. The dry nitrogen will fill the system, and will help purge any moisture.
2 − Remove the faulty component and quickly seal the
system (using tape or some other means) to prevent
additional moisture from entering the system.
3 − Do not remove the tape until you are ready to install
new component. Quickly install the replacement component.
4 − Evacuate the system to remove any moisture and oth-
er non−condensables.
The HPXA19 system MUST be checked for moisture
any time the sealed system is opened.
Any moisture not absorbed by the polyol ester oil can be removed by triple evacuation. Moisture that has been absorbed by the compressor oil can be removed by replacing
the filter drier.
IMPORTANT
Evacuation of system only will not remove moisture from oil. Filter drier must be replaced to eliminate moisture from POE oil.
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn
the electrical power to unit OFF at disconnect switch(es). Unit may have
multiple power supplies.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each
cooling or heating season, the system should be checked
as follows:
Outdoor Unit
1 − Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2 − Outdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.
3 − Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4 − Check all wiring for loose connections.
5 − Check for correct voltage at unit (unit operating).
6 − Check amp−draw on outdoor fan motor and compres-
sor (high and low capacity).
7 − Inspect drain holes in coil compartment base and
clean if necessary.
NOTE − If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer to
section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil if necessary.
2 − Check connecting lines, joints and coil for evidence of
oil leaks.
3 − Check condensate line and clean if necessary.
Indoor Unit
1 − Clean or change filters.
2 - Lennox blower motors are prelubricated and permanent-
ly sealed. No more lubrication is needed.
3 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
4 − Belt Drive Blowers − Check belt for wear and proper
tension.
5 − Check all wiring for loose connections.
6 − Check for correct voltage at unit.
7 − Check amp−draw on blower motor.
Page 23
VII−DIAGRAM / OPERATING SEQUENCE
HPXA19−024, 036, −048 & −060
Page 24
Sequence of Operation HPXA19−024/060
First Stage Cool (low capacity)
Transformer from indoor unit supplies 24VAC power to
the thermostat and outdoor unit controls.
1− Internal wiring energizes terminal O by cooling mode
selection, energizing the reversing valve. Cooling demand initiates at Y1 in the thermostat.
2− 24VAC passes through high pressure switch S4 and
discharge thermostat switch S5 energizing compressor contactor K1.
HPXA19−024 − Compressor begins start up. Relay
K31 remains closed during start up and capacitor
C7 remains in the circuit. As compressor speeds up
K31 is energized, de−energizing capacitor C7.
3− K1−1 N.O. closes energizing compressor B1 and out-
door fan motor B4. Transformer T46 is also energized.
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
Second Stage Cool (high capacity)
5− Second stage thermostat demand energizes solenoid
relay K195. K195−1 closes sending voltage to rectifier
plug D4. D4 converts the AC voltage to DC voltage and
energizes L34 unloader solenoid. L34 then closes the
slider ring, allowing the compressor to operate at high
capacity.
closes sending voltage to rectifier plug D4. D4 converts the AC voltage to DC voltage and energizes L34
unloader solenoid. L34 then closes the slider ring, allowing the compressor to operate at full capacity.
Defrost Mode
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the
condenser fan. The control will also put 24VAC on
the W1" (auxiliary heat) line. The unit will stay in this
mode until either the coil sensor temperature is
above the selected termination temperature, the defrost time of 14 minutes has been completed, or the
room thermostat demand cycle has been satisfied.
(If the temperature select shunt is not installed, the
default termination temperature will be 100°F.) If the
room thermostat demand cycle terminates the
cycle, the defrost cycle will be held until the next
room thermostat demand cycle. If the coil sensor
temperature is still below the selected termination
temperature, the control will continue the defrost
cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by
time and the coil temperature did not remain above
35°F (2°C) for 4 minutes the control will go to the
34−minute Time/Temperature mode.
Page 25
HPXA19−038 with Variable Speed Motor
3
4
2
1
Page 26
Sequence of Operation HPXA19−038
First Stage Cool (low capacity)
Transformer from indoor unit supplies 24VAC power to
the thermostat and outdoor unit controls.
1− Internal wiring energizes terminal O by cooling mode
selection, energizing the reversing valve. Cooling demand initiates at Y1in the thermostat.
2− 24VAC passes through high pressure switch S4 and
former T46 and outdoor fan motor B4. Variable speed
condenser fan motor operates on low speed (yellow
tap).
4− Solenoid L34 is NOT energized. The slider ring re-
mains open limiting compressor to low capacity.
Second Stage Cool (high Capacity)
5− Second stage thermostat demand energizes solenoid
relay K195. K195−1 closes sending voltage to rectifier
plug D4. D4 converts the AC voltage to DC voltage and
energizes L34 unloader solenoid. L34 then closes the
slider ring, allowing the compressor to operate at full
capacity. Variable speed condenser fan motor operates on high speed (blue tap).
closes sending voltage to rectifier plug D4. D4 converts the AC voltage to DC voltage and energizes L34
unloader solenoid. L34 then closes the slider ring, allowing the compressor to operate at full capacity.
Defrost Mode
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the
condenser fan. The control will also put 24VAC on
the W1" (auxiliary heat) line. The unit will stay in this
mode until either the coil sensor temperature is
above the selected termination temperature, the defrost time of 14 minutes has been completed, or the
room thermostat demand cycle has been satisfied.
(If the temperature select shunt is not installed, the
default termination temperature will be 100°F.) If the
room thermostat demand cycle terminates the
cycle, the defrost cycle will be held until the next
room thermostat demand cycle. If the coil sensor
temperature is still below the selected termination
temperature, the control will continue the defrost
cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by
time and the coil temperature did not remain above
35°F (2°C) for 4 minutes, the control will go to the
34−minute Time/Temperature mode.
Page 27
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.