Lennox HPXA19 Unit Information

Corp. 0302−L2
Service Literature
Revised 07−2006
HPXA19 SERIES UNITS
The HPXA19 is a high efficiency residential split−system heat pump unit, which features a two−step scroll compres­sor and R410A refrigerant. HPXA19 units are available in 2, 3 (−036 and −038 models), 4 and 5 ton sizes. The series includes the HPXA19−038, a 3 ton unit equipped with a vari­able speed condenser fan motor. The series is designed for use with an expansion valve only (approved for use with R410A) in the indoor unit.This manual is divided into sec­tions which discuss the major components, refrigerant sys­tem, charging procedure, maintenance and operation se­quence. Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change.
IMPORTANT
Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.
HPXA19
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of (CFC’s and HFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration my be levied for noncompliance.
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications / Electrical Data 2. . . . . . . . . . . . . . . . . .
I Application 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Unit Components 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
III Refrigerant System 16. . . . . . . . . . . . . . . . . . . . . . . . . .
DANGER
Shock Hazard Remove all power at disconnect be-
fore removing access panel. HPXA19 units use single-pole con­tactors. Potential exists for electrical shock resulting in injury or death. Line voltage exists at all components (even when unit is not in operation).
IV Charging 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V Service and Recovery 22. . . . . . . . . . . . . . . . . . . . . . . .
VI Maintenance 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII Diagrams and Operating Sequence 23. . . . . . . . . . .
Page 1
© 2003 Lennox Industries Inc.
SPECIFICATIONS
p
g
Kit
g
General Data
Connections (sweat)
Refrigerant
Outdoor
Netfacearea sq. ft. (m2) − Outer Coil 16.04 (1.49) 16.04 (1.49) 24.06 (2.24) 24.06 (2.24) 24.06 (2.24)
Nominal Tonnage (kW) 2 (7.0)
Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line o.d. − in. (mm) 7/8 (22.2)
1
Coil
Tubediameter − in. (mm) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52) 5/16 (0.52)
Outdoor
Diameter in.(mm) and no. of blades 24 (610) − 3 24 (610) − 3 24 (610) − 4 24 (610) − 4 24 (610) − 4
Fan
Shipping Data − lbs. (kg) 1 package 261 (118) 262 (119) 316 (143) 318 (144) 340 (154)
Model No. HPXA19−024 HPXA19−036 HPXA19−038 HPXA19−048 HPXA19−060
3 (10.6) 3 (10.6) 4 (14.1) 5 (17.6)
7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 1−1/8 (28.5)
R−410A furnished 10 lbs. 4 oz.
(4.65 kg)
Inner Coil 15.56 (1.45)
11 lbs. 0 oz.
(5.00 kg)
13 lbs. 15 oz.
(6.32 kg)
12 lbs. 14 oz.
(5.84 kg)
14 lbs. 6 oz.
(6.52 kg)
15.56 (1.45) 23.33 (2.17) 23.33 (2.17) 23.33 (2.17)
Number of rows 2 2 2 2 2
Fins per inch (m) 22 22 22 22 22
Motor hp (W) 1/10 (74.8)
Cfm (L/s) 3159 (1485) 3159 (1485) 3135 (1480) first−stage
Rpm 825 825 700 first−stage
Watts 170 170 105 first−stage
1/10 (74.8) 1/3 (249) 1/4 (187) 1/4 (187)
3600 (1700) second−stage
820 second−stage
150 second−stage
3900 (1840) 4200 (1980)
820 820
300 350
ELECTRICAL DATA
Electrical Data
Compressor
Outdoor Coil Fan Motor
3
Maximum overcurrent protection (amps) 20 35 40 45 60
Line voltage data − 60hz 208/230V−1ph 208/230V−1ph 208/230V−1ph 208/230V−1ph 208/230V−1ph
2
Minimum circuit ampacity 13.7 22.1 23.7 28.2 33.8
Rated load amps 10.3 16.7 16.7 21.2 25.7
Locked rotor amps 52 82 82 96 118
Power factor 0.99 0.98 0.98 0.99 0.99
Full load amps 0.8 0.8 2.8 1.7 1.7
Locked rotor amps 2
2 Not Applicable 3.1 3.1
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Hard Start Kit Factory
Installed
Compressor Low Ambient Cut−off 45F08 45F08 45F08 45F08 45F08
Freezestat
3/8 in. tubing 93G35 93G35 93G35 93G35 93G35
1/2 in. tubing 39H29 39H29 39H29 39H29 39H29
5/8 in. tubing 50A93 50A93 50A93 50A93 50A93
3
Indoor Blower Speed Relay Kit 40K58 40K58 40K58 40K58 40K58
Low Ambient Kit 54M89 54M89 68M04 54M89 54M89
Mild Weather Kit 33M07 33M07 33M07 33M07 33M07
Monitor Kit − Service Light 76F53 76F53 76F53 76F53 76F53
Mounting Base
Outdoor Thermostat Kit
Part No. − Catalog No. MB2−L (69J07) MB2−L (69J07) MB2−L (69J07) MB2−L (69J07) MB2−L (69J07)
Net Weight 15 lbs. (7 kg)
Thermostat 56A87 56A87 56A87 56A87 56A87
Mounting Box − US 31461
Canada 33A09 33A09 33A09 33A09 33A09
Refrigerant Line Set
15 ft. (4.6 m) length L15−65−15 L15−65−15 L15−65−15 L15−65−15 Field Fabricate
30 ft. (9 m) length L15−65−30
40 ft. (12 m) length L15−65−40 L15−65−40 L15−65−40 L15−65−40 Field Fabricate
50 ft. (15 m) length L15−65−50 L15−65−50 L15−65−50 L15−65−50 Field Fabricate
SignatureStatt Programmable Thermostat 51M28 51M28 51M28 51M28 51M28
Time Delay Relay Kit 58M81 58M81 58M81 58M81 58M81
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 15 ft. (4.6 m) length of refrigerant lines.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
3
HACR type breaker or fuse.
10J42 10J42 81J69 81J69
15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg)
31461 31461 31461 31461
L15−65−30 L15−65−30 L15−65−30 Field Fabricate
Page 2
I−APPLICATION
All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the En­gineering Handbook for approved system matchups. A misapplied system will cause erratic operation and can re­sult in early compressor failure.
II−Unit Components
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
A−Two−Stage Scroll Compressor (B1)
TWO−STAGE MODULATED SCROLL
slider ring
solenoid actuator coil
FIGURE 1
The scroll compressor design is simple, efficient and re­quires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 1.The scrolls are located in the top of the compressor can and the motor is located just below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 2 shows the basic scroll form. Two iden­tical scrolls are mated together forming concentric spiral shapes (figure 3). One scroll remains stationary, while the other is allowed to orbit" (figure 4). Note that the orbiting scroll does not rotate or turn but merely orbits" the station­ary scroll.
SCROLL FORM
FIGURE 2
CROSS−SECTION OF SCROLLS
DISCHARGE PRESSURE
TIPS SEALED BY
DISCHARGE PRESSURE
DISCHARGE
STATIONARY
SCROLL
SUCTION
ORBITING SCROLL
FIGURE 3
The counterclockwise orbiting scroll draws gas into the out­er crescent shaped gas pocket created by the two scrolls (figure 4 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 4 − 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 4
−3). When the compressed gas reaches the center, it is dis­charged vertically into a chamber and discharge port in the top of the compressor (figure1). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 3). During a single or­bit, several pockets of gas are compressed simultaneously providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid re­turn. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating com­pressors. Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in compressor failure. This type of damage can be detected and will result in denial of warranty claims. The scroll com­pressor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig.
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
The scroll compressors in all HPXA19 model units are de­signed for use with R410A refrigerant and operation at high pressures. Compressors are shipped from the factory with 3MA (32MMMA) P.O.E. oil. See electrical section in this manual for compressor specifications.
Page 3
TWO−STAGE OPERATION
The two−stage scroll compressor operates like any stan-
dard scroll compressor with the exception the two−stage
compressor modulates between first stage (low capacity
approximately 67%) and second stage (high capacity).
Modulation occurs when gas is bypassed through bypass
ports (figure 5 bypass ports open) in the first suction pock-
et. This bypassing of gas allows the compressor to operate
on first stage (low capacity) if thermostat demand allows.
Indoor thermostat setting will determine first or second
HOW A SCROLL WORKS
MOVEMENT OF ORBIT
SUCTION
ORBITING
SUCTION
POCKET
SCROLL
stage operation. The compressor will operate on first−stage until demand is satisfied or the indoor temperature reaches the thermostat set point calling for second−stage.
Second−stage (high capacity) is achieved by blocking the bypass ports (figure 5 bypass ports closed) with a slider ring. The slider ring begins in the open position and is con­trolled by a 24VDC internal solenoid. On a Y2 call the inter- nal solenoid closes the slider ring, blocking the bypass ports and bringing the compressor to high capacity. Two− stage modulation can occur during a single thermostat de­mand as the motor runs continuously while the compressor modulates from first−stage to second− stage.
SUCTION
INTERMEDIATE
PRESSURE
GAS
CRESCENT
SHAPED GAS
POCKET
3
12
FLANKS
SUCTION
STATIONARY SCROLL
SEALED BY
CENTRIFUGAL
FORCE
SUCTION
4
HIGH
PRESSURE
GAS
FIGURE 4
TWO−STAGE MODULATION
Bypass Ports
Closed
High Capacity
DISCHARGE
POCKET
Bypass Ports
Open
Low Capacity
FIGURE 5
Page 4
INTERNAL SOLENOID (L34)
Procedure
The internal unloader solenoid controls the two−stage op­eration of the compressor by shifting a slide ring mecha­nism to open two by−pass ports in the first compression pocket of the scrolls in the compressor. The internal sole­noid is activated by a 24 volt direct current solenoid coil. The coil power requires 20VAC. The internal wires from the solenoid in the compressor are routed to a 2 pin fusite con­nection on the side of the compressor shell. The external electrical connection is made to the compressor with a molded plug assembly. This plug contains a full wave recti­fier that converts 24 volt AC into 24 volt DC power to power the unloader solenoid. Refer to unit diagram for internal cir­cuitry view of plug.
If it is suspect the unloader is not operating properly, check the following
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper air­flow over coils, and correct system refrigerant charge. All components in the system must be func­tioning proper to correctly perform compressor modulation operational check. (Accurate measure­ments are critical to this test as indoor system load­ing and outdoor ambient can affect variations be­tween low and high capacity readings).
STEP 1 Confirm low to high capacity compressor operation
Tools required
Refrigeration gauge set
Digital volt/amp meter
Electronic temperature thermometer
On-off toggle switch
1. Turn main power "OFF" to outdoor unit.
2. Adjust room thermostat set point above (heating op­eration on heat pump) or below (cooling operation) the room temperature 5ºF.
3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch "OFF" and install switch in series with Y2 wire from room thermostat.
5. Cycle main power "ON."
6. Allow pressures and temperatures to stabilize be­fore taking any measured reading (may take up to 10 minutes).
NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).
7. Record all of the readings for the Y1 demand on table 1.
8. Close switch to energize Y2 demand.
9. Allow pressures and temperatures to stabilize be­fore taking any measured reading (this may take up to 10 minutes).
10. Record all of the readings of Y2 demand on table
1.
NOTE − On new installations or installations that have shut down for an extended period of time, if the com­pressor does not cycle from low stage to high stage on the first attempt, it may be necessary to recycle the com­pressor back down to low stage and back up to high stage a few times in order to get the bypass seals to properly seat
Compare Y1 readings with Y2 readings in table 1. Some readings should be higher, lower or the same. If the readings follow what table 1 specifies, the compressor is operating and shifting to high capacity as designed. If the readings do not follow what table 1 specifies, continue to step 2 to determine if problem is with external solenoid plug power.
Page 5
TABLE 1
Compressor Operation
Unit Readings
Y1 −
1st-Stage
Expected Results
Compressor
Voltage Same Amperage Higher
Condenser Fan motor
Amperage Same or Higher
Temperature
Ambient Same Outdoor Coil Discharge Air Higher in Cooling
Lower in Heating
Compressor Discharge Line Higher Indoor Return Air Same Indoor Coil Discharge Air Lower in Cooling
Higher in Heating
Pressures
Suction (Vapor) Lower Liquid Higher
Y2 −
2nd-Stage
STEP 2 Confirm DC voltage output on compressor solenoid plug
A − Compressor solenoid plug WITH built in full wave−
rectifier (LSOM I) that converts 24 volt AC into 24 volt DC power. See Table 1 for units equipped with the LSOM I.
1. Shut power off to outdoor unit.
2. Supply 24 volts AC control voltage to the wire ends of the full wave rectifier plug. Listen for a click" as the solenoid is energized. See figure 6.
apply 24vac
meter
compressor
fusite
terminals
rectifier plug leads
solenoid fusite
terminals
compressor
FIGURE 6
3. Unplug the full wave rectifier plug from the fusite connection on the compressor.
4. Turn the low voltage power back onto the unit. Sup­ply 24VAC to the wires of the full wave rectifier plug. Set volt meter to DC volts and measure the DC voltage at the female connector end of the full wave rectifier plug. The DC voltage reading should be 1.5 to 3 volts lower than the input voltage to the plug wire leads. (EX: Input voltage is 24VAC output voltage is 22VDC). See figure 7.
rectifier plug leads
apply 24vac
compressor
fusite
terminals
compressor
solenoid
fusite
terminals
meter
FIGURE 7
If the above checks verify that the solenoid plug is pro­viding power to cycle into high capacity operation, con­tinue to step 3 to determine if problem is with solenoid coil in compressor
Page 6
STEP 3 Confirm internal unloader solenoid has prop­er resistance
1. Shut all power off to unit (main and low voltage)
2. Unplug the molded plug from the compressor sole­noid 2−pin fusite.
3. Using a volt meter set on the 200 ohm scale
Replace the Compressor under these conditions:
Bad Solenoid
a. Measure the resistance at the 2−pin fusite. The resist­ance should be 32 to 60 ohms depending on compressor temperature. If no resist ancereplace compressor.
b. Measure the resistance from each fusite pin to ground. There should not be continuity to ground. If so­lenoid coil is grounded, replace compressor.
Good Solenoid
a. Seals not shifting, replace compressor b. Slider ring not shifting, replace compressor.
B−Contactor (K1)
The compressor is energized by a contactor located in the control box. All XP19 units are single phase and use single− pole contactors.
C−Low Pressure Switch (S87)
The XP19 is equipped with an auto−reset low pressure switch which is located on the suction line. The switch shuts off the compressor when the suction pressure falls below the factory setting. This switch is ignored during the first 90 seconds of compressor start up, during defrost operation, 90 seconds after defrost operation, during test mode and when the outdoor temperature drops below 15°F.
The switch closes when it is exposed to 55 psig and opens at 25 psig. It is not adjustable.
D−High Pressure Switch (S4)
E−Capacitor (C12)
The compressor in XP19−024, −036, −048 and −060 units
use a permanent split capacitor (see unit wiring diagram).
The capacitor is located inside the unit control box. Ratings
are on capacitor side.
F−Condenser Fan with Variable Speed Motor(B4)
The variable speed condenser fan motor (figure 14) used in all
units is a three-phase, electronically controlled d.c. brushless
motor (controller converts single phase a.c. to three phase
d.c.), with a permanent-magnet-type rotor, manufactured by
GE. Because this motor has a permanent magnet rotor it does
not need brushes like conventional D.C. motors. The motors
consist of a control module and motor . Internal components
are shown in figure 15. The stator windings are split into three
poles which are electrically connected to the controller. This ar-
rangement allows motor windings to be turned on and off in
sequence by the controller.
The controller is primarily an a.c. to d.c. converter. Con-
verted d.c. power is used to drive the motor. The control-
ler contains a microprocessor which monitors varying
conditions inside the motor (such as motor workload).
G−Contactor (K1)
The compressor is energized by a contactor located in the control box. All HPXA19 units are single phase and use single− pole contactors.
H−Low Pressure Switch (S87)
IMPORTANT
Pressure switch settings for R410A refrigerant will be significantly higher than units with R22.
An auto-reset, single-pole/single-throw high pressure switch is located in the liquid line. This switch shuts off the compres­sor when liquid line pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 640 + ure 13 for switch location.
10 psi and close at 448 + 10 psi. See fig-
Page 7
The HPXA19 is equipped with an auto−reset low pressure switch which is located on the suction line. The switch shuts off the compressor when the suction pressure falls below the factory setting. This switch is ignored during the first 90 seconds of compressor start up, during defrost operation, 90 seconds after defrost operation, during test mode and when the outdoor temperature drops below 15°F.
The switch closes when it is exposed to 55 psig and opens at 25 psig. It is not adjustable.
I−High Pressure Switch (S4)
IMPORTANT
Pressure switch settings for R410A refrigerant will be significantly higher than units with R22.
An auto-reset, single-pole/single-throw high pressure switch is located in the liquid line. This switch shuts off the compres­sor when liquid line pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 640 + ure 13 for switch location.
J−Low Ambient Thermostat (S23)
Second−stage low ambient thermostat S23 (figure 8) is a SPST thermostat located in the compressor compartment. The control uses a cap-tube sensor to monitor the tempera­ture inside the compressor compartment. The cap-tube sensor is coiled adjacent to the control.
Temperature Sensor
(Cap-Tube)
10 psi and close at 448 + 10 psi. See fig-
(Second−Stage)
Low Ambient Thermostat S23
Regional climatic conditions may require the control to be ad­justed to a different setting. The adjustment screw is located on the control. A hole cut into the bottom shelf of the control box provides access to the control from the compressor compartment. See figure 9.
Adjusting Low Ambient Thermostat
Adjustment screw can be reached by inserting a screw­driver through the slot in control box.
Turn screw clockwise to increase
switchover temperature.
FIGURE 9
Figure 10 shows the adjustment range of the control. Turn adjustment screw clockwise to raise the switchover tem­perature and counterclockwise to lower the switchover temperature.
Low Ambient Thermostat
49
adjustment
screw
FIGURE 8
S23 continually monitors the temperature inside the com­pressor compartment. When compressor compartment temperature drops below the control setpoint, the control closes. When the control closes, the contacts shunt across Y1 and Y2 inside the unit. When Y1 heating demand is present and S23 is closed, the compressor will run in high capacity. The compressor will operate in high capacity mode anytime there is a Y1 heating call from indoor ther­mostat, until the units control box warms and S23 opens.
S23 has field adjustable setpoints. Temperature differential (difference between cut-in and cut-out) is fixed and cannot be adjusted. Table 2 shows S23 control setpoints. The con­trol is factory set to close at 40+ and reset at 50+
2°F on a temperature rise.
2°F on a temperature drop
TABLE 2
Control Setpoints
Low Ambient Thermostat
Adjustable Range
Cut-In
(Close on Temperature Drop)
Cut-Out
(Open on Temperature Rise)
Factory
Setting
40+2°F 37+2°F 55+2°F
50+2°F 47+2°F 65+2°F
Min. Max.
43
*40
37
55
FIGURE 10
K−Reversing Valve (L1)
A refrigerant reversing valve with an electromechanical so­lenoid is used to reverse refrigerant flow during unit opera­tion. The reversing valve is energized during cooling de­mand and during defrost.
L−Transformer (T46)
Transformer T46 is located in the control box and is ener­gized any time the compressor is operating.
M−Solenoid Relay (K195)
Relay K195 is N.O. SPDT relay located in the control box. On a Y2 call K195−1 closes allowing AC voltage from (T46) to the two pin full wave rectifier plug (D4).
N−Rectifier Plug (D4)
D4 is a molded assembly that plugs into the compressor. On a Y2 call D4 converts 24 volts AC to 24 volts DC. The DC voltage energizes solenoid L34, allowing the com­pressor to operate at full capacity.
Page 8
O−Discharge Line Thermostat (S5)
S5 is an automatic reset SPST N.C. switch which opens on temperature rise. S5 is located on the discharge line and wired in series with S4 high pressure switch on the defrost control board. When discharge line temperature rises to
8°F the switch opens and shuts down the compres-
275° + sor. The switch resets when discharge line temperature drops to 225° +
11°F.
P−Dual Capacitor (C12)
The compressor and fan in HPXA19−024, −036, −048 and
−060 units use permanent split capacitor motors. A single dual" capacitor is used for both the fan motor and the com­pressor (see unit wiring diagram). The two sides (fan and compressor) of the capacitor have different mfd ratings and may change with each compressor. The capacitor is located inside the unit control box.
Q−Condenser Fan Motor (B4)
HPXA19−024, −036, −048 and −060 units use single−phase PSC fan motors which require a run capacitor. The FAN" side of the dual capacitor is used for this purpose. In all units, the outdoor fan is controlled by the compressor con­tactor. See ELECTRICAL DATA and SPECIFICATIONS section for more information. See figure 11 if condenser fan motor replacement is necessary. Rain shield location is critical on the condenser fan assembly. Two shields are used in unison to prevent moisture from entering the motor bearings. Installing the shields to close to the bearing hub will create noise and may affect operation. Installing too far away will allow moisture to enter the bearing, resulting in motor failure. See figure 12.
"A" SEE TABLE 3
Condenser fan and motor
FIGURE
11
TABLE 3
HPXA19 UNIT "A" DIM. + 1/8"
−024, −036 1 1/16"
−038
−048
−060
RAIN SHIELD LOCATION
(See figure 14 for HPXA19−038)
Critical Dimension
plastic
shield
fiber shield
FIGURE 12
FAN GUARD
Wiring
Drip loop
1 3/16"
1/4" (.250)
run capacitor
start capacitor
(−024 unit only)
system
operation monitor
defrost control
charge compensator (−038 and −048 units)
TXV/check valve
discharge line
compressor terminal plug
vapor line
low pressure switch
discharge temperature
thermostat
HPXA19 PARTS ARRANGEMENT
outdoor fan
(variable speed
on 038 units)
contactor
vapor valve
and
gauge port
two−stage compressor
filter drier
high pressure switch
FIGURE 13
Page 9
Loading...
+ 18 hidden pages