Lennox HPXA16-024, HPXA16-048, HPXA16 -060, HPXA16-036 Installation Instructions Manual

INSTALLATION
2006 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a qualified installer or service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of refrigerant (CFC’s, HFC’s, and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycl­ing or reclaiming must be followed. Fines and/or in­carceration may be levied for noncompliance.
INSTRUCTIONS
HPXA16 Series Units
HEAT PUMP UNITS
504,954M 08/06 Supersedes 03/06
Table of Contents
HPXA16 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 2. . . . . . . . . . . . . . . . . . . . . . . .
General Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Metering Device 8. . . . . . . . . . . . . . . . . . . .
Flushing Existing Line Set & Indoor Coil 8. . . . . . . . . .
Manifold Gauge Set 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Charging 12. . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 21. . . . . . . . . . . . . . . . . . . . . . . . . .
Check Points 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Information:
Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Operation 24. . . . . . . . . . . . . . . . . . . . . . . . . .
HPXA16 Outdoor Unit
Lennox HPXA16 outdoor units use HFC−410A refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the Lennox Engineering Handbook. Elite® Series HPXA16 outdoor units are designed for use in check expansion valve (CTXV) systems only and must not be used with other refrigerant flow control devices.
See Lennox Engineering Handbook list of indoor expan­sion valve kits (ordered separately).
Litho U.S.A.
08/06 504,954M
*2P0806* *P504954M*
Page 1
Shipping and Packing List
Check unit for shipping damage. Consult last carrier imme­diately if damage is found.
1 − Assembled HPXA16 outdoor unit 2 − Grommets (for liquid and vapor lines)
General Information
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
Table 1
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Unit Dimensions − inches (mm)
Model A B C
HPXA16−024, −036 30-7/8 (784) 12-3/4 (324) 17-1/4 (438)
HPXA16−048, −060 44-7/8 (1140) 14-1/4 (362 18-3/4 (476)
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, main­tenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
INLET AIR
(51)
INLET
AIR
COMPRESSOR
INLET AIR
Coil drain outlets (around perimeter of base)
Top View
ELECTRICAL
INLETS
32-1/8 (816) 34-1/16 (865)
VAPOR
LINE INLET
4-1/2
A
(114)
C
2-9/16
(65)
DISCHARGE AIR
B
2-3/4 (70)
4-7/8 (124)
7−1/2 (191)
3-7/8
(98)
(51)
18-5/8 (473)
2
LIQUID
LINE INLET
1-3/8
(35)
4
(102)
26−5/8 (676)
4
(102)
6-1/16
(154)
7−1/2
3-7/8
(191)
2
(98)
28-1/8 (718)
Side ViewService Access
504954M 08/06
Page 2
Parts Arrangement
RUN CAPACITOR
START CAPACITOR
(−024 UNIT ONLY)
DEFROST CONTROL
CHARGE COMPENSATOR
(−048 UNITS)
TXV/CHECK VALVE
DISCHARGE LINE
COMPRESSOR TERMINAL PLUG
VAPOR LINE
LOW PRESSURE SWITCH
DISCHARGE TEMPERATURE
SENSOR
HIGH PRESSURE SWITCH
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CONTACTOR
VAPOR VALVE AND GAUGE PORT
TWO−STAGE COMPRESSOR
FILTER DRIER
Figure 1
Installation Clearances
as noted
These units operate under a wide range of weather condi­tions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be positioned to give adequate clearances for sufficient airflow and servic­ing. Refer to figure 2 for installation clearances.
1. Place a sound−absorbing material, such as Isomode, under the unit if it will be installed in a location or posi­tion that will transmit sound or vibration to the living area or adjacent buildings.
2. Mount unit high enough above ground or roof to allow adequate drainage of defrost water and prevent ice build−up.
3. In heavy snow areas, do not locate unit where drifting will occur. The unit base should be elevated above the depth of average snows.
NOTE − Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a sup­port frame is constructed, it must not block drain holes in unit base.
Page 3
30"
(762 mm)
NOTE − A service access clearance of 30" (762 mm) must be main­tained in front of the service access panel. Clearance to one side must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (305 mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
as noted
as noted
Figure 2
4. When installed in areas where low ambient tempera­tures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil.
5. Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit.
HPXA16 SERIES
Slab Mounting
color coded, temperature
When installing unit at grade level, top of slab should be high enough above the grade so that water from higher ground will not collect around unit. See figure 3. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m). This will prevent ice build−up under unit during a defrost cycle. Re­fer to roof mounting section for barrier construction if unit must face prevailing winter winds.
Slab Mounting
discharge air
2 DEGREES OR 2 IN. PER 5 FOOT (51 MM PER 1.5 M) SLOPE TOLERANCE AWAY FROM BUILDING STRUCTURE
ground level
building
structure
mounting
slab
Figure 3
Roof Mounting
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. See figure 4. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
Rooftop Wind Barrier Construction
prevailing winter
winds
wind barrier
inlet air
inlet air
24" (610 mm)
inlet air
Figure 4
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Electric Shock Hazard. Can cause in­jury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all compo­nents when unit is not in operation on units with single-pole contactors. Dis­connect all remote electric power sup­plies before opening access panel. Unit may have multiple power sup­plies.
1. Install line voltage power supply to unit from a properly sized disconnect switch.
2. Ground unit at unit disconnect switch or to an earth ground.
NOTE − Connect conduit to the unit using a proper conduit fitting. Units are approved for use only with copper conductors. Refer to figure 5 for high voltage field wiring diagram. A complete unit wiring diagram is located on the back side of the unit’s access panel.
Typical Field Wiring Diagram
GND
READ
WARNING
AND NOTE
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE − For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size.
Figure 5
NOTE − For proper voltages, select thermostat wire gauge per the following chart:
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
3. Install room thermostat (ordered separately) on an in­side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figures 6 through 8.
NOTE − 24V, Class II circuit connections are made in the low voltage junction box.
color−coded, temperature rating 35ºC minimum
L2 L1
208−
230/
60/1
504954M 08/06
Page 4
HPXA16 Outdoor Unit and Blower Unit
Thermostat Designations
(Some connections may not apply. Refer to specific thermostat and indoor unit.)
Outdoor Unit Indoor Unit TB1
Defrost Board
Y2
OUT
R
Y1
C
W1
O
Y2
R
W3
W2
Y1
G
C
W1
O
Y2
A2 Thermostat
R
Y1
G
C
W1
O
Y2
HPXA16 Outdoor Unit and CB31MV/CB32MV
Thermostat Designations
(Some connections may not apply. Refer to specific thermostat and indoor unit.)
Outdoor Unit
Defrost
W1
Board
Y2
OUT
Y2
R
Y1
C
O
CB31MV / CBX32MV TB1
DS
R
W3
W2
Y1
G
C
W1
O
Y2
SignatureStat A2 Thermostat
D
R
H
L
Y1
G
C
W2
O
W1
Y2
RT− 14
Figure 6
Figure 7
HPXA16 Wiring Diagram
Figure 8
Page 5
BLUE WIRE
Y2 OUT
DEFROST BOARD DETAIL
Shipped as shown above with terminal crimped to blue wire; use terminal or cut off terminal and splice blue wire with Y2 wire to indoor unit.
WITH CRIMPED
TERMINAL
HPXA16 SERIES
Refrigerant Piping
If the HPXA16 unit is being installed with a new indoor coil and line set, the refrigerant connections should be made as outlined in this section. If an existing line set and/or in­door coil is going to be used to complete the HPXA16 sys­tem, refer to the following section which includes flushing procedures.
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 2 or use field-fabri­cated refrigerant lines. Valve sizes are also listed in table 2.
Refrigerant Connections − HPXA16 Matched with New Indoor Coil and Line Set
If an existing indoor coil which was equipped with an RFCI metering device is being replaced, the liquid line must also be replaced prior to the installation of the HPXA16 unit.
Table 2
Refrigerant Line Sets
Field Connections
Mod­el
−024
−036
−048
−060 3/8 in.
Liquid Line
3/8 in. (10 mm)
(10 mm)
Vapor Line
7/8 in (22 mm)
1−1/8 in. (29 mm)
Recommended Line Set
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
7/8 in (22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
1. PlacementBe aware some localities are adopting sound ordinances based on how noisy the unit is at the neighbors’ home, not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a bed­room window. Glass has a very high level of sound transmission. Figure 9 shows how to place the outdoor unit and line set.
Outside Unit Placement and Installation
Install unit away from windows
Two 90° elbows installed in line set will reduce line set vibration.
NOTE − Units are designed for line sets of up to fifty feet (15m).
Installing Refrigerant Line
Pay close attention to line set isolation during installation of any heat pump or a/c system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent noises. Also, consider the following when placing and installing a high−efficiency outdoor unit:
Refrigerant Line Sets: Transition From Vertical To Horizontal
ANCHORED
HEAVY NYLON
WIRE TIE
WALL STUD
Strap Liquid Line To Va­por Line
Figure 9
2. Line Set IsolationThe following illustrations dem­onstrate procedures which ensure proper refrigerant line set isolation. Figure 10 shows how to make a tran­sition from horizontal to vertical. Figure 11 shows how to install line sets on vertical runs. Figure 12 shows how to install line sets on horizontal runs.
AUTOMOTIVE
MUFFLER-TYPE
HANGER
WALL STUD
Strap Liquid Line To Vapor Line
METAL
SLEEVE
504954M 08/06
VAPOR LINE − WRAPPED IN ARMAFLEX
LIQUID LINE
Figure 10
Page 6
METAL
SLEEVE
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
NOTE − Similar installation practices should be used if line set is to be installed on exterior of outside wall.
IMPORTANT - Refrigerant lines must not contact wall.
LIQUID LINEVAPOR LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
VAPOR LINE WRAPPED
IMPORTANT! Refrigerant lines must not contact structure.
WOOD BLOCK
BETWEEN STUDS
WITH ARMAFLEX
OUTSIDE WALL
OUTSIDE WALL
LIQUID
LINE
PVC PIPE
FIBERGLASS
INSULATION
Refrigerant Line Sets: Installing Horizontal Runs
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
STRAPPING MATERIAL (Around vapor line only)
CAULK
8 feet
FLOOR JOIST OR ROOF RAFTER
METAL SLEEVE
Figure 11
8 feet
WIRE TIE (Around vapor line only)
TAPE OR WIRE TIE
FLOOR JOIST OR ROOF RAFTER
SLEEVE
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line.
TAPE OR WIRE TIE
Figure 12
Page 7
HPXA16 SERIES
Isolation Grommets
Locate the provided isolation grommets. Use a knife to slit the webbing on each grommet. Slide larger grommet onto vapor line and smaller grommet onto liquid line. Insert grommets into mullion to isolate refrigerant lines from sheet metal edges.
WARNING
Polyol ester (POE) oils used with HFC−410A refrig­erant absorb moisture very quickly. It is very im­portant that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Brazing Connection Procedure
1. The end of the refrigerant line must be cut square and its internal shape must remain round. The line must be free of nicks or dents and must be deburred (I.D. and O.D.)
2. Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the sys­tem.
3. Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing). Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to protect them during brazing. Braze the line set to the service valve.
4. Quench the joint with water or a wet cloth to prevent heat damage to the valve core and opening port.
NOTE − The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, seal­ing and rigidity.
Metering Device Installation
O−RING
DISTRIBUTOR
NOTE − If necessary, remove HCFC−22 flow control device (fixed orifice/check expansion valve) from existing line set before installing HFC−410A approved expansion valve and o−ring.
EXPANSION VALVE & O−RING (See NOTE)
STRAINER
LIQUID LINE STUB
Figure 13
IMPORTANT
Failure to remove a fixed orifice when installing an expansion valve on the indoor coil will result in im­proper operation and damage to the system.
Flushing Existing Line Set & Indoor Coil
NOTE − If the indoor unit line and set are new, skip this sec­tion and go on to the Manifold Gauge Set section.
WARNING
Danger of fire. Bleeding the refriger­ant charge from only the high side may result in the low side shell and suction tubing being pressurized. Ap­plication of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before un­brazing.
Refrigerant Metering Device
HPXA16 units may be used in check expansion valve (CTXV) systems only. See indoor coil installation instruc­tions and the Lennox engineering handbook for approved HFC−410A TXV match−ups and application information.
NOTE − HFC−410A systems will not operate properly with an HCFC−22 valve.
Check Expansion Valve Systems
Check expansion valves equipped with either Chatleff or flare−type fittings are available from Lennox. Refer to the Engineering Handbook for applicable expansion valves for use with specific match-ups.
If you install a check expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the check expansion valve is installed. See figure 13 for instal­lation of the check expansion valve.
504954M 08/06
IMPORTANT
If this unit is being matched with an approved line set or indoor coil which was previously charged with HCFC−22 refrigerant, or if it is being matched with a coil which was manufactured before Janu­ary of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps.
Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual min­eral oil can act as an insulator, preventing proper heat transfer. It can also clog the check expansion valve, reducing system performance and capacity.
Failure to properly flush the system per the in­structions below will void the warranty.
Page 8
IMPORTANT
The Environmental Protection Agency prohibits the intentional venting of HFC refrigerants during main­tenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or re­claiming must be followed.
CAUTION
This procedure should not be performed on sys­tems which contain contaminants (Example: com­pressor burn out).
Required Equipment
You will need the following equipment in order to flush the existing line set and indoor coil: two clean HCFC−22 recov­ery bottles, an oilless recovery machine with a pump down feature, and two sets of gauges (one for use with HCFC−22 and one for use with the HFC−410A).
Flushing Procedure
1. Remove existing HCFC−22 refrigerant using the ap­propriate procedure below.
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational AND you plan to use the existing HCFC−22 refrig­erant to flush the system −
Disconnect all power to the existing outdoor unit.Connect to the existing unit, a clean recovery cyl-
inder and the recovery machine according to the instructions provided with the recovery machine.
Remove all HCFC−22 refrigerant from the existing
system. Check gauges after shutdown to confirm that the entire system is completely void of refrig­erant.
Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.
If the existing outdoor unit is equipped with manual shut−off valves AND you plan to use NEW HCFC−22 refrigerant to flush the system
Start the existing HCFC−22 system in the cooling
mode and close the liquid line valve.
Pump all of the existing HCFC−22 refrigerant back
into the outdoor unit. (It may be necessary to by­pass the low pressure switches to ensure com­plete refrigerant evacuation.)
When the low side system pressures reach 0 psig,
close the vapor line valve.
Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.
2. Remove the existing outdoor unit. Set the new HFC−410A unit and follow the brazing connection pro­cedure (see page 8) to make line set connections. DO NOT install metering device at this time.
3. Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this time.
IMPORTANT
The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
4. Remove the existing refrigerant flow control orifice or thermal expansion/check valve before continuing with flushing procedures. The existing devices are not ap­proved for use with HFC−410A refrigerant and may prevent proper flushing. Use a field−provided fitting to reconnect the lines.
EXISTING
INDOOR COIL
RECOVERY CYLINDER
Inverted HCFC−22 Cylin­der (Contains clean HCFC−22 to be used for flushing)
EXISTING VAPOR LINE
EXISTING LIQUID LINE
Flushing Connections
VAPOR LINE
SERVICE VALVE
LIQUID LINE
SERVICE VALVE
Tank Return
Inlet
Discharge
RECOVERY MACHINE
Figure 14
Page 9
Low
Pressure
HPXA16
UNIT
NOTE − The inverted HCFC−22 cyl­inder must contain at least the same amount of refrigerant as was recovered from the existing sys­tem.
GAUGE MANIFOLD
High
Pressure
ClosedOpened
HPXA16 SERIES
5. Remove the pressure tap valve cores from the HPXA16 unit’s service valves. Connect an HCFC−22 cylinder with clean refrigerant to the vapor service valve. Connect the HCFC−22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set.
6. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex­isting system line set and indoor coil.
7. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
8. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered.
NOTE − A single system flush should remove all of the mineral oil from the existing refrigerant lines and in­door coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system
is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure.
9. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
10. Use dry nitrogen to break the vacuum on the refriger­ant lines and indoor coil before removing the recovery machine, gauges and HCFC−22 refrigerant drum. Re­install pressure tap valve cores into HPXA16 service valves.
11. Install the provided check expansion valve (approved for use with HFC−410A refrigerant) in the liquid line at the indoor coil.
Manifold Gauge Set
Manifold gauge sets used with systems charged with HFC−410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
Service Valves
The liquid line and vapor line service valves (figures 15 and
16) and gauge ports are used for leak testing, evacuating,
charging, and checking charge. See table for torque requi­rements.
Front-Seated Liquid Line Service Valve
(Valve Shown Closed)
Insert hex wrench here
CAP
STEM
CAP
(Valve Shown Open)
insert hex wrench here
CAP
STEM
CAP
Service port Is open to line set when valve is closed (front seated)
SERVICE PORT
To indoor coil
To outdoor coil
SERVICE PORT
To indoor coil
To outdoor coil
Figure 15
Ball−Type Vapor Valve (Valve Closed)
STEM
USE ADJUSTABLE WRENCH
TO OPEN: ROTATE STEM COUNTER-CLOCKWISE 90°. TO CLOSE: ROTATE STEM CLOCKWISE 90°.
TO INDOOR COIL
CAP
STEM
SERVICE PORT
SCHRADER VALVE
TO OUTDOOR COIL
BALL (SHOWN CLOSED)
SERVICE PORT CAP
Figure 16
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
504954M 08/06
Page 10
IMPORTANT
Service valves are closed to the outdoor unit and open to line set connections. Do not open until re­frigerant lines have been leak tested and evacuated. All precautions should be exercised in keeping the system free from dirt, moisture and air.
To Access Schrader Port:
1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap. Re­place the stem cap. Tighten finger tight; then torque per table 1 (Page 2).
To Open Front-Seated Service Valves:
1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap. Tighten finger tight; then torque per table 1 (Page 2).
To Close Front-Seated Service Valves:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly.
3. Replace the stem cap. Tighten finger tight; then torque per table 1 (Page 2).
Ball-Type Service Valve (Vapor Line)
Ball-type service valves function the same way as the oth­er valves; the difference is in the construction. These valves are not rebuildable. If a valve has failed, you must replace it. A ball valve is illustrated in figure 16.
The ball valve is equipped with a service port with a factory− installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak− free seal.
Leak Testing
After the line set has been connected to the indoor and out­door units, the line set connections and indoor unit must be checked for leaks.
WARNING
Refrigerant can be harmful if it is inhaled. Refriger­ant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrig­eration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to
13.8 kPa).
Using an Electronic Leak Detector
1. Connect a cylinder of HFC−410A to the center port of the manifold gauge set.
2. With both manifold valves closed, open the valve on the HFC−410A cylinder (vapor only).
3. Open the high pressure side of the manifold to allow the HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A . [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure reg­ulating valve to the center port of the manifold gauge set.
5. Connect the manifold gauge set high pressure hose to the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6. Adjust the dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7. After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge dry nitrogen and HFC−410A mixture. Correct any leaks and recheck.
IMPORTANT
Leak detector must be capable of sensing HFC re­frigerant.
Page 11
HPXA16 SERIES
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 23,000 microns.
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to vapor line service valvehigh pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves; start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
WARNING
Danger of Equipment Damage! Avoid deep vacu­um operation. Do not use compressors to evacu­ate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void war­ranty.
7. Shut off the dry nitrogen cylinder and remove the man­ifold gauge hose from the cylinder. Open the manifold
gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vac­uum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the HFC−410A cylinder and remove the manifold gauge set.
Start−Up
IMPORTANT
If unit is equipped with crankcase heater, it should be energized 24 hours before unit start−up to pre­vent compressor damage as a result of slugging.
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory− and field-installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and vapor line service valves (counterclockwise) to re­lease refrigerant charge (contained in outdoor unit) into the system.
4. Replace stem caps and secure finger tight, then tight­en an additional (1/6) one-sixth of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on pow­er to indoor blower unit and close the outdoor unit dis­connect to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
Refrigerant Charging
This system is charged with HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The field−provided check expansion valve for the indoor unit must be approved for use with HFC−410A. This unit is NOT approved for use with coils which include metering orifices or capillary tubes.
Factory Charge
The unit is factory−charged with the amount of HFC−410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.6 m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment.
504954M 08/06
Page 12
EXPANSION/
CHECK VALVE
LOW
PRESSURE
HPXA16 Cooling Cycle (Showing Gauge Manifold Connections)
HUGH
PRESSURE
BIFLOW FILTER / DRIER
MUFFLER
DISTRIBUTOR
OUTDOOR
COIL
OUTDOOR UNIT
REVERSING VALVE
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
INDOOR UNIT
GAUGE MANIFOLD
TO HFC−410 A DRUM
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
LIQUID
LINE
SERVICE
PORT
COMPRESSOR
VAPOR SERVICE PORT
VAPOR LINE VALV E
EXPANSION/CHECK VALVE
Figure 17
Table 3
Refrigerant Charge per Line Set Lengths
Liquid Line Set Diameter
3/8 in. (9.5mm) 3 ounces per 5 feet (85 grams per 1.52 meter)
*Add the amount shown if line length is greater than 15’ (4.57m), sub­tract the amount shown if less than 15’.
Ounces per 5 feet (grams per 1.52 meter) adjust from 15 ft. (4.57m) line set*
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a polyol ester oil.
The compressor is charged with sufficient polyol ester oil for approved line set lengths.
Checking Charge
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter-
mined by the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1. Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service porthigh pressure gauge to liquid valve service port
Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A. See figure 17.
2. Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle.
3. Record outdoor ambient temperature using a digital thermometer.
4. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68F
Page 13
(20C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
5. The outdoor temperature will determine which charg­ing method to use. Proceed with whichever of the fol­lowing charging procedure deemed appropriate for the situation.
Charge Using the Weigh-in Method – Outdoor Temperature < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit.
1. Recover the refrigerant from the unit.
2. Conduct leak check; evacuate as previously outlined.
3. Weigh in the unit nameplate charge. If weighing facili­ties are not available or if charging the unit during warm weather, use one of the following procedures.
Charge Using the Subcooling Method – Outdoor Temperature < 65°F (18°C)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the out­door coil to achieve pressures in the 325−375 psig (2240−2585 kPa) range. These higher pressures are nec­essary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liq­uid pressure is in the 325−375 psig (2240−2585 kPa) range. See figure 18.
Blocking Outdoor Coil
Figure 18
VAPOR
SERVICE
PORT
INDOOR
COIL
*Outdoor coil should be blocked one side at a time with cardboard or plastic sheet until proper testing pressures are reached.
cardboard or plastic sheet
*Four−sided unit shown.
HPXA16 SERIES
1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital ther­mometer to record the liquid line temperature.
2. At the same time, record the liquid line pressure reading.
3. Use a temperature/pressure chart for HFC−410A to determine the saturation temperature for the liquid line pressure reading. See table 4.
Table 4
HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6 35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5 37 111.4 68 194.1 99 312.7 130 475.6 38 113.6 69 197.3 100 317.2 131 481.6 39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0 41 120.3 72 207.2 103 331.0 134 500.2 42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9 44 127.3 75 217.4 106 345.3 137 519.3 45 129.7 76 220.9 107 350.1 138 525.8 46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0 48 137.1 79 231.6 11 0 365.0 141 545.6 49 139.6 80 235.3 111 370.0 142 552.3 50 142.2 81 239.0 11 2 375.1 143 559.1 51 144.8 82 242.7 11 3 380.2 144 565.9 52 147.4 83 246.5 11 4 385.4 145 572.8 53 150.1 84 250.3 11 5 390.7 146 579.8 54 152.8 85 254.1 11 6 396.0 147 586.8 55 155.5 86 258.0 11 7 401.3 148 593.8 56 158.2 87 262.0 11 8 406.7 149 601.0 57 161.0 88 266.0 11 9 412.2 150 608.1 58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7 60 169.6 91 278.2 122 428.8 153 630.1 61 172.6 92 282.3 123 434.5 154 637.5 62 175.4 93 286.5 124 440.2 155 645.0
4. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine sub­cooling. (Saturation temperature − Liquid line tem-
perature = Subcooling)
5. Compare the subcooling value with those in table 5. If subcooling is greater than shown, recover some refrig­erant. If subcooling is less than shown, add some re-
frigerant. Be aware of the HFC−410A refrigerant cylin­der. It will be light maroon−colored. Refrigerant should be added through the vapor line valve in the liquid state.
NOTE − Some HFC−410A cylinders are equipped with a dip tube that allows you to draw liquid refrigerant from the bot­tom of the cylinder without turning the cylinder upside− down. The cylinder will be marked if it is equipped with a dip tube.
Table 5
Subcooling Values for Charging
Second Stage (High Capacity)
Model Number
HPXA16−024 11.0 + 1 (6 + .5)
HPXA16−036 8.5 + 1 (4.7 + .5)
HPXA16−048 7.5 + 1 (4.1 + .5)
HPXA16−060 7.0 + 1 (3.9 + .5)
Subcooling Values Conversion Temp. −
Liquid Line Temp. °F (°C)
Charge Using the Approach Method – Outdoor Temperature >
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best re­sults, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1. Record outdoor ambient temperature using a digital thermometer.
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in tables 6 and 7, Normal Operating Pressures."
65F (18C)
IMPORTANT
Use tables 6 & 7 as a general guide when performing maintenance checks. This is not a procedure for charging the unit.
Minor variations in these pressures may be ex­pected due to differences in installations. Signifi­cant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Continue to check adjusted charge using approach values.
504954M 08/06
Page 14
Table 6
°F (°C)**
°F (°C)**
HPXA16 Normal Operating Pressures
COOLING (Liquid ±10 & Vapor ±5 psig)*
°
°
**
65 (18.3) 217 143 227 142 222 140 225 140
75 (23.9) 250 145 262 145 258 143 259 142
85 (29.4) 291 147 305 146 298 145 293 146
95 (35.0) 336 149 352 148 343 147 356 147
105 (40.6) 386 151 403 152 402 147 408 147
115 (49.0) 440 153 458 155 452 152 455 151
65 (18.3) 222 143 244 136 232 134 249 126
75 (23.9) 256 145 282 139 266 136 289 134
85 (29.4) 302 145 325 142 309 139 330 140
95 (35.0) 349 147 377 144 359 142 378 143
105 (40.6) 403 149 428 146 410 144 433 146
115 (49.0) 464 152 488 148 468 147 492 149
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.
−024 −036 −048 −060
Liq Vap Liq Va p Liq Vap Liq Vap
First Stage (Low Capacity)
Second Stage (High Capacity)
Table 7
HPXA16 Normal Operating Pressures
HEATING (Liquid ±10 & Vapor ±5 psig)
°
°
**
40 (4.4) 321 99 296 95 315 97 319 93
50 (10) 340 120 310 11 2 330 114 335 111
Second Stage (High Capacity)
20 (−7.0) 273 68 277 60 294 60 300 57
30 (−1.0) 296 80 296 74 303 75 312 70
40 (4.4) 321 95 321 88 314 90 323 83
50 (10) 341 115 341 104 325 106 339 97
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.
4. Use the same digital thermometer used to check outdoor ambient temperature to check liquid line temperature. Verify the unit charge using the approach method.
−024 −036 −048 −060
Liq Vap Liq Vap Liq Vap Liq Vap
First Stage (Low Capacity)
5. The difference between the ambient and liquid temperatures should match values given in table 8. If the values don’t agree with the those in table 8, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
Table 8
Approach Values for Charging
Second Stage (High Capacity) Ap-
Model Number
HPXA16−024 4.0 + 1 (2.2 + .5)
HPXA16−036 7.0 + 1 (3.9 + .5)
HPXA16−048 8.0 + 1 (4.4 + .5)
HPXA16−060 10.0 + 1 (5.6 + .5)
proach Temperature Liquid Line Temp. −
Outdoor Ambient °F (°C)
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continu- ously.
Thermostat Operation
Some indoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The thermostat is not included with the unit and must be purchased separately.
Emergency Heat (Amber Light)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit con­trol circuit is isolated from power and field-provided relays by­pass the outdoor thermostats. An amber indicating light si­multaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power out­age if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.
Filter Drier
The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with HFC−410A refrigerant.
Page 15
HPXA16 SERIES
Defrost System
Defrost System Description
The demand defrost controller measures differential tem­peratures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates" when the defrost system starts and after each system defrost cycle. The defrost control board com­ponents are shown in figure 19.
Defrost Control Board
Note − Component Locations Vary by Board Manufacturer.
TEST PINS
DEFROST
TERMINATION
PIN SETTINGS
SENSOR
PLUG IN
(COIL & AM-
BIENT
SENSORS)
DELAY
PINS
REVERSING
VALV E
PRESSURE
SWITCH CIR-
CUIT CONNEC-
TIONS
Figure 19
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a de­frost cycle is required. The coil temperature probe is de­signed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE − The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
Defrost Board Diagnostic LEDs
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 10 (on page 20).
LOW AMBIENT THERMOSTAT PINS
DIAGNOSTIC LEDS
24V TERMINAL STRIP CONNECTIONS
Defrost Board Pressure Switch Connections
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the defrost board on the LO−PS and HI−PS terminals, respectively.
Low Pressure Switch (LO−PS)When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the following conditions:
during the defrost cycle and 90 seconds after the ter-
mination of defrost
when the average ambient sensor temperature is be-
low 15° F (−9°C)
for 90 seconds following the start up of the compressor during "test" mode
High Pressure Switch (HI−PS)When the high pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike.
Defrost Board Pressure Switch Settings
High Pressure (auto reset) − trip at 590 psig; reset at 418
psig. Low Pressure (auto reset) − trip at 25 psig; reset at 55
psig.
Pressure Switch 5−Strike Lockout
The internal control logic of the board counts the pressure switch trips only while the Y1 (Input) line is active. If a pres­sure switch opens and closes four times during a Y1 (In­put), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the control board or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is en­gaged, a 5−minute short cycle will occur after the switch closes.
Defrost System Sensors
Sensors connect to the defrost board through a field-re­placeable harness assembly that plugs into the board (see figure 21). Through the sensors, the board detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. Figure 20 shows how the re­sistance varies as the temperature changes for both type of sensors. Sensor resistance values can be checked by ohming across pins shown shown in table 9.
504954M 08/06
Page 16
NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 9, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.
NOTE − Under certain ambient conditions, the internal cabinet temperature of the HPXA16−036 cabinet will affect the temperature that is sensed by the coil sen­sor. This can set up a condition where the defrost board may not initiate a defrost cycle. To overcome this issue, the coil sensor should be moved to the al­ternate location on the other side of the cabinet to the coil hairpin shown in figure 21.
Table 9
Sensor Temperature / Resistance Range
Pins/W ire Color
(Black)
(Brown)
(Yellow)
Sensor
Temperature Range °F (°C)
Resistance values range (ohms)
Outdoor −35 (−37) to 120 (48) 280,000 to 3750 3 & 4
Coil −35 (−37) to 120 (48) 280,000 to 3750 5 & 6
Discharge (if
24 (−4) to 350 (176) 41,000 to 103 1 & 2
applicable)
Note: Sensor resistance decreases as sensed temperature increases (see figure 20).
Ambient and Coil Sensor Discharge Sensor
100
TEMPERATURE (ºF)
5750
90
80
70
60
50
40
30
20
10
7450
9275
11775
15425
19975
26200
34375
46275
62700
0
10000 30000 50000 70000 90000 1000 2000 50004000 60003000
RESISTANCE (OHMS) RESISTANCE (OHMS)
85300
300
280
260
240
220
200
180
160
TEMPERATURE (ºF)
140
120
100
200
225
250
275
325
375
425
500
600
700
825
1000
Figure 20
Sensor Locations
DISCHARGE LINE SENSOR
ALTERNATE COIL SENSOR LOCATION.
AMBIENT SENSOR − (Inside PVC tube) Extend tip of plastic sensor just outside of plastic sleeve.
1175
1400
1700
2025
2500
3000
3750
4650
5825
HPXA16−036 ALTERNATE COIL SENSOR LOCATION
Figure 21
Page 17
COIL SENSOR DETAIL − Sensor clips on the return bend as shown, located on bends as follows:
HPXA16−024: 6th bend from top on outside column.
HPXA16−036*, −048, −060: 5th bend from bottom on outside column.
NOTE − DIAGRAMS ARE TYPICAL OF −024 AND −036 COIL; −048 & −060 COILS HAVE MORE COIL SURFACE AREA AND GREATER NUMBER OF BENDS. * − −036 MODEL HAS ALTERNATE LOCATION ON OPPOSITE SIDE AS SHOWN TO THE LEFT
HPXA16 SERIES
Defrost System Sensors
Ambient SensorThe ambient sensor considers out-
door temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sen­sor, the board will not perform demand defrost operation. The board will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Coil SensorThe coil temperature sensor considers out­door temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not perform demand or time/tem­perature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Discharge Line SensorIf the discharge line tempera­ture exceeds a temperature of 300°F (148°C) during com­pressor operation, the board will de−energize the compres­sor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti− short cycle delay has been satisfied. This sensor has two fault and lockout codes:
1. If the board recognizes five high discharge line tem­perature faults during a single (Y1) compressor de­mand, it reverts to a lockout mode and displays the ap­propriate code. This code detects shorted sensor or high discharge temperatures. (Code on board is Dis­charge Line Temperature Fault and Lockout").
2. If the board recognizes five temperature sensor range faults during a single (Y1) compressor demand, it re­verts to a lockout mode and displays the appropriate code. The board detects open sensor or out-of-tem­perature sensor range. This fault is detected by allow­ing the unit to run for 90 seconds before checking sen­sor resistance. If the sensor resistance is not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout. (Code on board is Discharge Sensor Fault and Lockout").
The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a ½" re­frigerant discharge line.
NOTE − Within a single room thermostat demand, if 5−strikes occur, the board will lockout the unit. Defrost board 24 volt power R" must be cycled OFF" or the TEST" pins on board must be shorted between 1 to 2 sec­onds to reset the board.
Second−Stage OperationIf the board receives a call for second−stage compressor operation Y2" in heating or cooling mode and the first-stage compressor output is ac­tive, the second-stage compressor solenoid output will be energized.
NOTE − Figure 8 on page 5 shows the correct Y2 field wir­ing.
If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock−in temperature, the second-stage com­pressor solenoid output will be energized without the Y2" input. If the jumper is not connected to one of the tempera­ture selection pins on P3 (40, 45, 50, 55°F), the default lock−in temperature of 40°F (4.5°C) will be used.
The board de−energizes the second-stage compressor so­lenoid output immediately when the Y2" signal is removed or the outdoor ambient temperature is 5°F above the se­lected compressor lock−in temperature, or the first-stage compressor output is de−energized for any reason.
Defrost Temperature Termination Shunt (Jumper) PinsThe defrost board selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C).
Delay Mode
The defrost board has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when jumpering the TEST pins.
Operational Description
The defrost control board has three basic operational modes: normal, defrost, and calibration.
Normal ModeThe demand defrost board monitors
the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil tem­perature (outdoor coil) and compressor run time to de­termine when a defrost cycle is required.
Calibration ModeThe board is considered uncali-
brated when power is applied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode.
Calibration of the board occurs after a defrost cycle to ensure that there is no ice on the coil. During calibra­tion, the temperature of both the coil and the ambient sensor are measured to establish the temperature dif­ferential which is required to allow a defrost cycle.
Defrost ModeThe following paragraphs provide a
detailed description of the defrost system operation.
Detailed Defrost System Operation
The demand defrost control board initiates a defrost cycle based on either frost detection or time.
Frost DetectionIf the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum dif­ference allowed by the control, a defrost cycle will be initi­ated.
IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer de­frost cycles than a time/temperature defrost system.
504954M 08/06
Page 18
TimeIf 6 hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil tem­perature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
ActuationWhen the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is be­low 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system tempera­tures during the 20−minute calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum differ­ence allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
TerminationThe defrost cycle ends when the coil tem­perature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated
after 34 minutes of run time.
Test Mode[NOTE − Coil sensor temperature must be below 35ºF before the defrost board will initiate a test" defrost.] When Y1 is energized and 24V power is
being applied to the board, a test cycle can be initiated by placing the termination temperature jumper across the Test" pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ig­nore the test pins and revert to normal operation. The jumper will initiate one cycle per test.
Enter the TEST" mode by placing a shunt (jumper) across the TEST" pins on the board after power−up. (The TEST" pins are ignored and the test function is locked out if the shunt is applied on the TEST" pins before power−up). Board timings are reduced, the low−pressure switch is ig­nored and the board will clear any active lockout condition.
Each test pin shorting will result in one test event. For each TEST" the shunt (jumper) must be removed for at least 1 second and reapplied. Refer to flow chart (figure
22) for TEST" operation.
Note: The Y1 input must be active (ON) and the O" room thermostat terminal into board must be inactive.
Defrost Board Diagnostics
See table 10 to determine defrost board operational condi­tions and to diagnose cause and solution to problems.
Short test pins for longer
than 1 second but less
than 2.0 seconds
Clear any short cycle lockout
and/or 5−strike fault lockout
function, if applicable. No
other functions will be executed and unit will
continue in the mode it was
operating.
Test pin short REMAINS in place for more than 5 seconds Test pins short REMOVED before a
The unit will return to Heat mode uncalibrated with defrost
timer set for 34 minutes. No further test mode operation will
be executed until the test short is removed and re applied.
Test Mode
Y1 Active (0" line inactive)
Short test pins for more than 2.0 seconds
Clear any short cycle lockout or 5−strike fault
lockout function, if applicable.
If in COOLING Mode If in HEATING Mode If in DEFROST Mode
No further test mode
operation will be
executed until the test
short is removed and
reapplied.
The controller will check for
ambient and coil faults (open or shorted). If a fault exists will remain in Heat Mode and no
further test mode operation will be executed until the test short
is removed and re applied. If
no fault exists
temperature is below 35ºF, the
unit will go into Defrost mode.
, the unit
and ambient
maximum of 5 seconds
The unit will remain in Defrost mode
until termination on time or temperature
The unit will terminate
defrost and enter Heat
Mode uncalibrated with
defrost timer set for 34 minute test. No further
test mode operation will
be executed until the test
short is removed and
reapplied.
Figure 22
Page 19
HPXA16 SERIES
Table 10
pp g g
pp
installed
3
Check
d
y
yp
eration, the board will de−energize the compressor contactor output (and the defrost
Defrost Control Board Diagnostic LEDs
DS2 Green
OFF OFF Power problem No power (24V) to board termi-
DS1 Red
Condition/Code Possible Cause(s) Solution
1
Check control transformer power (24V).
nals R & C or board failure.
2
If power is available to board and LED(s) do not light, replace board.
Simultaneous SLOW Flash
Alternating SLOW Flash
Simultaneous FAST Flash
Alternating FAST Flash
Normal operation Unit operating normally or in
None required.
standby mode.
5−minute anti−short cycle delay
Initial power up, safety trip, end of room thermostat demand.
None required (Jumper TEST pins to override)
Ambient Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will re-
vert to time/temperature defrost operation. (System will still heat or cool).
Coil Sensor Problem Sensor being detected open or shorted or out of temperature range. Board will not
perform demand or time/temperature defrost operation. (System will still heat or cool).
ON ON Circuit Board Failure Indicates that board has internal component failure. Cycle 24 volt power to board. If
code does not clear, replace board.
FAULT & LOCKOUT CODES (Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
OFF SLOW
Low Pressure Fault
Flash
OFF ON Low Pressure LOCKOUT
SLOW
OFF High Pressure Fault
Flash
ON OFF High Pressure LOCKOUT
1
Restricted air flow over indoor or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device
or incorrect operation
of metering device.
4
Incorrect or improper sensor location or connection to sys­tem.
1
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach & sub­cooling temperatures.
3
4
system operating pressures an compare to unit charging charts. Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements.
SLOW
ON Discharge Line Tempera-
Flash
FAST
ON Discharge Line Tempera-
Flash
OFF Fast
Flash
Fast
OFF Discharge Sensor
Flash
This code detects shorted sensor or high discharge temperatures. If the discharge
ture Fault
line temperature exceeds a temperature of 300ºF (148ºC) during compressor op-
output if active). The compressor will remain off until the discharge temperature has
ture LOCKOUT
dropped below 225ºF (107ºC).
Discharge Sensor Fault The board detects open sensor or out of temperature sensor range. This fault is
detected by allowing the unit to run for 90 seconds before checking sensor resist­ance. If the sensor resistance is not within range after 90 seconds, the board will
LOCKOUT
count one fault. After 5 faults, the board will lockout.
504954M 08/06
Page 20
Maintenance
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Before the start of each heating and cooling season, the following service checks should be performed by a quali­fied service technician. First, turn off electrical power to the unit prior to performing unit maintenance.
Inspect and clean the outdoor and indoor coils. The
outdoor coil may be flushed with a water hose.
NOTE − It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks. Check wiring for loose connections. Check voltage at the indoor and outdoor units (with
units operating).
Check the amperage draw at the outdoor fan motor,
compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters. Check the refrigerant charge and gauge the system
pressures.
Check the condensate drain line for free and unob-
structed flow; clean, if necessary.
Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
Check drive belt for wear and proper tension.
NOTE − If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Re­fer to section on refrigerant charging in this instruction.
Optional Accessories
Refer to the Engineering Handbook for optional accesso­ries that may apply to this unit. The following may or may not apply:
Loss of charge kit High pressure switch kit Compressor monitor Compressor crankcase heater Hail guards Mounting bases Timed-off control Stand−off Kit Sound cover Low ambient kit Monitor kit Dave Lennox SignatureStat
Room Thermostat
Page 21
HPXA16 SERIES
Start−Up and Performance Check List
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage: 1st Stage 2nd Stage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
COOLING (2ND STAGE)
Liquid Line Pressure: Vapor Pressure: Refrigerant Charge Checked?
HEATING (2ND STAGE)
Liquid Line Pressure: Vapor Pressure: Refrigerant Charge Checked?
Vapor Pressure; 1st Stage: 2nd Stage:
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? Cooling Correct?
Calibrated?  Properly Set?  Level? 
THERMOSTAT
504954M 08/06
Page 22
2006 Lennox Industries Inc.
Dallas, Texas, USA
Homeowner Information − Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Ask your Lennox dealer to show you where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable filters should be replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter you need for your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the disconnect switch before performing any maintenance. The unit may have multiple power supplies.
3. Many indoor units are equipped with reusable foam fil­ters. These filters can be cleaned with a mild soap and water solution. Rinse the filter thoroughly and let it dry completely before it is returned to the unit or grille.
NOTE − The filter and all access panels must be in place any time the unit is in operation.
4. Some systems are equipped with an electronic air cleaner, designed to remove the majority of airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for main­tenance instructions.
5. Inspect and clean indoor coil. The indoor evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the in­side air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
HPXA16
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
Heat Pump Operation
Your new Lennox heat pump has several characteristics that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of consid­erably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a de- frost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the de­frost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
In case of extended power outage...
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging" during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the Emer­gency Heat" setting to obtain temporary heat without the risk of serious damage to the heat pump. In Emergency Heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up" period, the thermostat can be switched to the Heat" setting and nor­mal heat pump operation may resume.
Page 23
HPXA16 SERIES
Thermostat Operation − Thermostat Operation
Though your thermostat may vary somewhat from the de­scription below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature selec­tor levers: one for heating and one for cooling. Set the lev­ers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjust­ment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous in­door blower operation, regardless of whether the com­pressor or auxiliary heat are operating. This mode is re­quired when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto opera­tion. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain pre­determined comfort settings. Many heat pump thermo­stats are also equipped with an emergency heat mode which locks out heat pump operation and provides tempo­rary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which in-
dicates when the heat pump is operating in the emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room tem­perature.
Programmable Thermostats
Your Lennox system may be controlled by a program­mable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manu­al provided with your particular thermostat for operation details.
Preservice Check
If your system fails to operate, check the following before calling for service:
Check to see that all electrical disconnect switches are
ON.
Make sure the room thermostat temperature selector
is properly set.
Make sure the room thermostat system switch is prop-
erly set.
Replace any blown fuses, or reset circuit breakers. Make sure unit access panels are in place. Make sure air filter is clean. Locate unit model number and have it handy before
calling.
504954M 08/06
Page 24
Loading...