Lennox HPXA15-024, HPXA15-036, HPXA15, HPXA15-030, HPXA15-048 Installation Instructions Manual

...
INSTALLATION
2002 Lennox Industries Inc.
Dallas, Texas
HPXA15 outdoor units use R410A which is an ozone friendly HFC refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the Lennox Engineering Handbook. HPXA15 outdoor units are de­signed for use in expansion valve (TXV) systems only. They are not designed to be used with other refrigerant flow control devices. An expansion valve approved for use with R410A has been shipped with the unit and must be installed prior to operating the unit.
Shipping and Packing List
INSTRUCTIONS
HPXA15 SERIES UNITS
HEAT PUMP UNITS
504,713M 02/04
Supersedes 12/02
Table of Contents
HPXA15 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Existing Line Set & Indoor Coil 10. . . . . . . . . .
Manifold Gauge Set 12. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HPXA15 Check Points 21. . . . . . . . . . . . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with R22 must be flushed.
Litho U.S.A.
1 − Assembled HPXA15 outdoor unit
2 − Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
02/04
*2P0204*
Page 1
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
504,713M
*P504713M*
Dimensions −− Inches (mm)
HPXA15-030
HPXA15-048
inlet
air
inlet
air
compressor
inlet air
Top View
B
inlets
electrical
C
coil drain outlets
(around perimeter
of base)
discharge air
vapor
line inlet
A
4-1/2 (114)
H
liquid
D
2-9/16
(65)
line inlet
K
J
4-7/8 (22)
2
(51)
K
J
G
2
(51)
2-3/4
(70)
1-3/8
(35)
4
(102)
F
E
Side ViewService Access
Model No. A B C D E F G H J K
HPXA15-024
HPXA15-030 HPXA15-036
HPXA15-042
HPXA15-048 HPXA15−060
in. 27-7/8 25-7/8 29-7/8 12-1/4 22-7/16 14-7/16 22-1/8 16-3/4 2-7/8 5-1/2
mm 708 657 759 311 570 367 562 425 730 140
in. 30-7/8 32-1/8 34-1/16 12-3/4 26-5/8 18-5/8 28-1/8 17-1/4 3-7/8 7-1/2
mm 784 816 865 324 676 473 718 438 98 191
in. 34-7/8 32-1/8 34-1/16 13-3/4 26-5/8 18-5/8 28-1/8 18-1/4 3-7/8 7-1/2
mm 886 816 865 349 676 473 718 464 98 191
in. 44-7/8 32-1/8 34-1/16 14-1/4 26-5/8 18-5/8 28-1/8 18-3/4 3-7/8 7-1/2
mm 1140 816 865 362 676 473 718 476 98 191
4
(102)
6-1/16
(154)
Page 2
Parts Arrangement
dual capacitor
high pressure
switch
filter/drier
expansion valve
with internal check valve
defrost
thermostat
distributor
compressor
terminal box
defrost control/timed−off control
compressor
crankcase
heater
contactor
ground lug
sensing bulb
vapor line
service valve
and gauge port
liquid line
service valve
and gauge port
crankcase heater
thermostat
(2−1/2 through
5−ton units)
reversing valve
and solenoid
muffler
Figure 1
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Sharp sheet metal edges can cause injury. When installing the unit, avoid accidental contact with sharp edges.
These units operate under a wide range of weather condi­tions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be positioned to give adequate clearances for sufficient airflow and servic­ing. A minimum clearance of 24 inches (610 mm) between multiple units must be maintained. Refer to figure 2 for in­stallation clearances.
1 − Place a sound−absorbing material, such as Isomode,
under the unit if it will be installed in a location or posi­tion that will transmit sound or vibration to the living area or adjacent buildings.
2 − Mount unit high enough above ground or roof to allow
adequate drainage of defrost water and prevent ice build−up.
3 − In heavy snow areas, do not locate unit where drifting
will occur. The unit base should be elevated above the depth of average snows.
NOTE − Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a sup­port frame is constructed, it must not block drain holes in unit base.
Installation Clearances
*36"
NOTE − A service access clearance of 30" (762 mm) must be maintained in front of the service access panel. Clearance to one side must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
36"
(914 mm)
(914 mm)
*36"
(914 mm)
36"
(914 mm)
Figure 2
4 − When installed in areas where low ambient tempera-
tures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil.
Page 3
5 − Locate unit away from overhanging roof lines which
would allow water or ice to drop on, or in front of, coil or into unit.
Slab Mounting
When installing unit at grade level, top of slab should be high enough above the grade so that water from higher ground will not collect around unit. See figure 3. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m). This will prevent ice build−up under unit during a defrost cycle. Refer to roof mounting section for barrier construction if unit must face prevailing winter winds.
Rooftop Application
Wind Barrier Construction
prevailing winter winds
wind barrier
inlet air
(610 mm)
INLET
AIR
24"
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m)
slope tolerance away
from building structure
ground level
Slab Mounting
discharge air
building
structure
mounting
slab
Figure 3
Roof Mounting
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. See figure 3. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
inlet air
Figure 4
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Unit must be grounded in accordance with national and local codes. ELECTRIC SHOCK HAZARD. Can cause injury or death.
1 −Install line voltage power supply to unit from a properly
sized disconnect switch.
2 −Ground unit at unit disconnect switch or to an earth
ground.
Page 4
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us ing a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 5 for field wiring diagram.
NOTE − A complete unit wiring diagram is located in
Typical Field Wiring Diagram
side the unit control box cover.
3 − Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4 − Install voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit. See figures 6 and 7.
Figure 5
Page 5
Outdoor Unit and Blower Unit
Thermostat Designations
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
R
C
1st. stage aux. heat
W1
G
O
Y1
Indoor
Unit
power
common common
indoor blower
reversing valve
compressor
R
C
W1
W2
W3
G
power
1st. stage aux. heat
Outdoor
Unit
R
C
W1
O
Y1
Figure 6
Outdoor Unit and Blower Unit
Thermostat Designations
(with auxiliary heat)
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
R
C
emergency heat
E
W1
1st. stage aux. heat
indoor blower
G
reversing valve
O
compressor
Y1
Indoor
Unit
power
common common
R
C
em.
heat rly
W1
1st. stage aux. heat
W2
W3
G
Outdoor
power
outdoor t’stat
Unit
R
C
W1
O
Y1
Figure 7
Refrigerant Piping
If the HPXA15 unit is being installed with a new indoor coil and line set, the refrigerant connections should be made as outlined in this section.
If an existing line set and/or indoor coil is going to be used to complete the HPXA15 system, refer to the following sec­tion which includes flushing procedures.
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 1 or use field-fabri­cated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351−L9) for proper size, type, and application of field−fabricated lines. Valve sizes are also listed in table 1.
Refrigerant Connections
HPXA15 Matched with New Indoor Coil and Line Set
If an existing indoor coil which was equipped with an RFCI metering device is being replaced, the liquid line must also be replaced prior to the installation of the HPXA15 unit.
Table 1
Refrigerant Line Sets
Valve Field Size
Connections
Model
−024
−030
−036
−042
−048
−060
Liquid
Line
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
Vapor
Line
3/4 in.
19 mm
7/8 in.
22 mm
1−1/8 in.
29 mm
NOTE − Units are designed for line sets of up to 50 feet (15 m). For applications longer than 50 feet, consult the Len­nox Refrigerant Piping Guide (Corp. 9351−L9). Select line set diameters from table 1 to ensure that oil returns to the compressor.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Closer attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high−efficiency outdoor unit:
Recommended Line Set
Liquid
Line
3/8 in.
10 mm
3/8 in.
10 mm
3/8 in.
10 mm
Vapor
Line
3/4 in.
19 mm
7/8 in.
22 mm
1−1/8 in.
29 mm
15 ft. − 50 ft.
4.6 m − 15 m
15 ft. − 50 ft.
4.6 m − 15 m
L15
Line Sets
L15−41
L15−65
Field
Fabricated
Page 6
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from the adjacent property not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmis­sion.
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line set isolation. Figure 8 shows how to install line sets on vertical runs. Figure 9 shows how to install line sets on horizontal runs. Figure 10 shows how to make a transi­tion from horizontal to vertical. Finally, figure 11 shows how to place the outdoor unit and line set.
Outside Wall
Wood Block
Between Studs
Liquid Line
Vapor Line
(wrapped with Armaflex)
Outside Wall
IMPORTANT - Refrigerant
lines must not contact wall.
Liquid LineVapor Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Caulk
PVC Pipe
Fiberglass
Insulation
IMPORTANT - Refrigerant
lines must not contact
structure.
Strap
Sleeve
Figure 8
Page 7
Installing Horizontal Runs
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Floor Joist or
Roof Rafter
Refrigerant Line Sets:
Wire Tie
(around vapor line only)
8 feet
Tape or Wire Tie
8 feet
Strapping Material (around vapor line only)
Tape or Wire Tie
Metal Sleeve
Floor Joist or Roof Rafter
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line.
Figure 9
Page 8
Refrigerant Line Sets:
Transition From Vertical To Horizontal
Anchored Heavy
Nylon Wire Tie
Wall Stud
Metal
Sleeve
Muffler-Type
Wall Stud
Strap Liquid Line
To Vapor Line
Vapor Line
Wrapped in
Armaflex
Liquid Line
Figure 10
Outside Unit Placement and Installation
Automotive
Hanger
Metal
Sleeve
Strap Liquid Line
To Vapor Line
Liquid Line
Vapor Line
Wrapped in
Armaflex
Install unit away from windows.
Two 90° elbows installed in line set will reduce line set vibration.
Figure 11
Page 9
Isolation Grommets
Locate the provided isolation grommets. Use a knife to slit the webbing on each grommet. Slide larger grommet onto vapor line and smaller grommet onto liquid line. Insert grommets into mullion to isolate refrigerant lines from sheet metal edges.
Metering Device Installation
distributor
expansion
valve
o−ring
WARNING
Polyol ester (POE) oils used with R410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or ser­vice valve stub caps until you are ready to make connections.
Brazing Connection Procedure
1 − The end of the refrigerant line must be cut square and
its internal shape must remain round. The line must be free of nicks or dents and must be deburred (I.D. and O.D.)
2 − Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the sys­tem.
3 − Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel braz­ing). Wrap a wet cloth around the valve body and the copper tube stub. Remove light maroon washers from service valves and shield light maroon stickers in order to protect them during brazing. Braze the line set to the service valve.
4 − Quench the joint with water or a wet cloth to prevent
heat damage to the valve core and opening port.
IMPORTANT − The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity.
Refrigerant Metering Device
HPXA15 units are used in check expansion valve systems only. See the Lennox Engineering Handbook for approved TXV match-ups and application information.
Check expansion valves equipped with Chatleff fittings are available from Lennox. Refer to the Engineering Handbook for applicable expansion valves for use with specific match-ups.
If you install a check expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before installing the check expansion valve.
See figure 1 for installation of the check expansion valve.
o−ring
strainer
liquid line
stub
Figure 1
IMPORTANT
Failure to remove RFC orifice when installing an ex­pansion valve on the indoor coil will result in improp­er operation and damage to the system.
Flushing Existing Line Set & Indoor Coil
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suc­tion tubing being pressurized. App­plication of a brazing torch while pres­surized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbra­zing.
IMPORTANT
If this unit is being matched with an approved line set or indoor coil that was previously charged with R22 refrigerant, or if it is being matched with a coil that was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with R410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the thermal expansion valve, reducing system performance and capacity. Failure to properly flush the system per the instruc­tions below will void the warranty.
CAUTION
This procedure should not be performed on sys­tems which contain contaminants (Example: com­pressor burn out).
Page 10
Required Equipment
You will need the following equipment in order to flush the existing line set and indoor coil: two clean R22 recovery bottles, an oilless recovery machine with a pump down fea­ture, and two sets of gauges (one for use with R22 and one for use with the R410A).
Flushing Procedure
1 − Remove existing R22 refrigerant using the appropri-
ate procedure below.
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational AND you plan to use the existing R22 refrigerant to flush the system −− Disconnect all power to the exist-
ing outdoor unit. Connect the existing unit, a clean re­covery cylinder and the recovery machine according to the instructions provided with the recovery ma­chine. Remove all R22 refrigerant from the existing system. Refer to gauges after shutdown to confirm that the entire system is completely void of refrigerant. Disconnect the liquid and vapor lines from the existing outdoor unit.
If the existing outdoor unit is equipped with manu­al shut−off valves AND you plan to use NEW R22 refrigerant to flush the system −− Start the existing
R22 system in the cooling mode and close the liquid line valve. Pump all of the existing R22 refrigerant back into the outdoor unit. (It may be necessary to by­pass the low pressure switches to ensure complete re-
frigerant evacuation.) When the low side system pres­sures reach 0 psig, close the vapor line valve. Disconnect all power to the existing outdoor unit. Re­fer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and vapor lines from the existing outdoor unit.
2 − Remove the existing outdoor unit. Set the new R410A
unit and follow the brazing connection procedure which begins on the previous page to make line set connections. DO NOT install provided R410A
check/expansion valve at this time.
Make low voltage and line voltage connections to the new outdoor unit. DO NOT turn on power to the unit
or open the outdoor unit service valves at this time.
3 − Remove the existing refrigerant flow control orifice or
thermal expansion/check valve before continuing with flushing procedures. The existing devices are not ap­proved for use with R410A refrigerant and may pre­vent proper flushing. Use a field−provided fitting to re­connect the lines.
IMPORTANT
The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that pre­viously charged the system. Check the charge in the flushing cylinder before proceeding.
Existing
Indoor Coil
RECOVERY
CYLINDER
Flushing Connections
Inverted R22 Cylinder
(Contains clean R22 to
be used for flushing)
EXISTING VAPOR LINE
EXISTING LIQUID LINE
VAPOR LINE
SERVICE VALVE
LIQUID LINE
SERVICE VALVE
TANK RETURN
INLET
DISCHARGE
Recovery Machine
Figure 12
LOW
PRESSURE
HPXA15 Unit
GAUGE MANIFOLD
NOTE − The inverted R22 cylinder must con­tain at least the same amount of refrigerant as was recovered from the existing system.
HIGH
PRESSURE
CLOSEDOPENED
Page 11
4 − Remove the pressure tap valve cores from the
HPXA15 unit’s service valves. Connect an R22 cylin­der with clean refrigerant to the vapor service valve. Connect the R22 gauge set to the liquid line valve and connect a recovery machine with an empty recovery tank to the gauge set.
5 − Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex­isting system line set and indoor coil.
6 − Invert the cylinder of clean R22 and open its valve to
allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
7 − After all of the liquid refrigerant has been recovered,
switch the recovery machine to vapor recovery so that all of the R22 vapor is recovered.
NOTE − A single system flush should remove all of the mineral oil from the existing refrigerant lines and in­door coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush. Each time the system
is flushed, you must allow the recovery machine to pull a vacuum on the system at the end of the procedure.
8 − Close the valve on the inverted R22 drum and the
gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
9 − Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery ma­chine, gauges and R22 refrigerant drum. Reinstall pressure tap valve cores into HPXA15 service valves.
10 −Install the provided check/expansion valve (approved
for use with R410A refrigerant) in the liquid line at the indoor coil.
Manifold Gauge Set
Manifold gauge sets used with systems charged with R410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
Service Valves
Access the liquid line and vapor line service valves (figures 13 and 14) and gauge ports are used for leak testing, eva­cuating, charging and checking charge. See table 1 for torque requirements.
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
Table 1
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 N M
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 N M
IMPORTANT
Service valves are closed to the outdoor unit and open to line set connections. Do not open the valves until refrigerant lines have been leak tested and evacuated. All precautions should be exercised to keep the system free from dirt, moisture and air.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench. 2 − Connect gauge to the service port. 3 − When testing is complete, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
To Open Service Valve:
1 − Remove stem cap with an adjustable wrench. 2 − Using service wrench and hex head extension, back
the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace stem cap and tighten it firmly. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Service Valve:
1 − Remove stem cap with an adjustable wrench. 2 − Using service wrench and hex head extension, turn
stem clockwise to seat valve. Tighten it firmly.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
Vapor Line (Ball Type) Valve
Vapor line service valves function the same way as the oth­er valves, the difference is in the construction. These valves are not rebuildable. If a valve has failed, you must replace it. A ball valve valve is illustrated in figure 14. The ball valve is equipped with a service port with a factory− installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak− free seal.
Page 12
Liquid Service Valve (Valve Open)
Insert Hex
Wrench Here
Field Side
Schrader
Valve
Service Port
Cap
Service Port
Liquid Service Valve (Valve Closed)
Field Side
Service
Port
Service Port
Cap
Schrader Valve Open
To Line Set When Valve Is
Closed (Front Seated)
Vapor Line (Ball Type) Service Valve
Use Adjustable Wrench
To open: rotate stem counter-clockwise 90°.
To close: rotate stem clockwise 90°.
Schrader
valve
service
port
field side
(shown open)
Figure 13
(Valve Open)
service port
cap
ball
Figure 14
Stem Cap
Unit Side
Stem Cap
Insert Hex
Wrench Here
(Valve Front
Seated)
Unit Side
unit side
stem
stem cap
Leak Testing
After the line set has been connected to the indoor and out­door units, the line set connections and indoor unit must be checked for leaks.
WARNING
Refrigerant can be harmful if it is inhaled. Refriger­ant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Danger of explosion: Can cause equipment damage, injury or death. Never use oxygen to pressurize a re­frigeration or air conditioning system. Oxygen will explode on contact with oil and could cause personal injury.
WARNING
Danger of explosion: Can cause equipment damage, injury or death. When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Using an Electronic Leak Detector
1 − Connect a cylinder of R410A to the center port of the
manifold gauge set.
2 − With both manifold valves closed, open the valve on
the R410A cylinder (vapor only).
3 − Open the high pressure side of the manifold to allow
the R410A into the line set and indoor unit. Weigh in a trace amount of R410A . [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the R410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
Page 13
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck.
IMPORTANT
Leak detector must be capable of sensing HFC re­frigerant.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 10,000 microns.
1 − Connect the manifold gauge set to the service valve
ports as follows:
low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start vacuum pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin­der with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use com­pressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of R410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R410A cylinder and remove the manifold gauge set.
Start−Up
IMPORTANT
If unit is equipped with crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1 − Rotate fan to check for frozen bearings or binding. 2 − Inspect all factory− and field-installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves (counterclockwise) to release refrigerant charge (contained in outdoor unit) into the system.
4 − Replace stem caps and secure finger tight, then tight-
en an additional (1/6) one-sixth of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition has been corrected.
6 − Set the thermostat for a cooling demand, turn on power
to indoor blower unit and close the outdoor unit discon­nect to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Page 14
Charging
This system is charged with R410A refrigerant which oper­ates at much higher pressures than R22. The check/ex­pansion valve provided with the unit is approved for use with R410A. Do not replace it with a valve designed for use with R22. This unit is NOT approved for use with coils which include metering orifices or capillary tubes.
Processing Procedure
The unit is factory−charged with the amount of R410A re­frigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.6 m) line set. For varying lengths of line set, refer to table 2 for refrigerant charge adjustment.
Table 2
Liquid Line Set
Diameter
3/8 in.
(10 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Oz. per 5 ft. (grams per 1.5 m) adjust
from 15 ft. (4.6 m) line set*
3 ounces per 5 feet
(85g per 1.5 m)
IMPORTANT
Mineral oils are not compatible with R410A. If oil must be added, it must be a polyol ester oil.
The compressor is charged with sufficient polyol ester oil for line set lengths up to 50 feet (15.2 m). Do not add any more than 7 oz. of oil.If oil must be added to the compressor in the field, Copeland has approved Mobil EALt Arctic 22CC and ICI EMKARATEt RL32CF.
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the out­door ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1 − Close manifold gauge set valves. Connect manifold
gauge set to service valves as shown in figure 16: low pressure gauge to vapor valve service port high pressure gauge to liquid valve service port
Connect the center manifold hose to an upright cylin­der of R410A .
2 − Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in the cooling cycle.
3 − Use a digital thermometer to record the outdoor ambi-
ent temperature.
4 − When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68F (20C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
5 − The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate charg­ing procedure.
Weighing in the Charge TXV Systems –
Outdoor Temp < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been re­paired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other proce­dures outlined below.
Subcooling Method
Outdoor Temp. < 65°F (18°C)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the out­door coil to achieve pressures in the 325−375 psig (2240−2585 kPa) range. These higher pressures are nec­essary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liq­uid pressure is in the 325−375 psig (2240−2585 kPa) range. See figure 15.
Blocking Outdoor Coil
Outdoor coil should be
blocked one side
at a time with cardboard
or plastic sheet until proper
testing pressures
are reached.
cardboard or plastic sheet
Figure 15
1 − With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature. 2 − At the same time, record the liquid line pressure reading. 3 − Use a temperature/pressure chart for R410A to deter-
mine the saturation temperature for the liquid line pres-
sure reading. See table 6.
4 − Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature − Liquid line tem-
perature = Subcooling)
5 − Compare the subcooling value with those in table 3. If
subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant. Be aware of the R410A refrigerant cylinder. It
Page 15
will be light maroon−colored. Refrigerant should be added through the vapor line valve in the liquid state.
Some R410A cylinders are equipped with a dip tube that allows you to draw liquid refrigerant from the bottom of the cylinder without turning the cyl­inder upside−down. The cylinder will be marked if it is equipped with a dip tube.
Table 3
Subcooling Values for Charging
Model Number
HPXA15−024 5 ± 1 (2.8 ± .5)
HPXA15−030 8± 1 (7.4 ± .5)
HPXA15−036 5.5 ± 1 (3 ± .5)
HPXA15−042 4.5 ± 1 (2.5 ± .5)
HPXA15−048 2.5 ± 1 (1.4 ± .5)
HPXA15−060 6 ± 1 (3.3 ± .5)
Conversion Temp. − Liquid Line Temp. °F (°C)
Subcooling Values
Charging Using Normal Operating Pressures
and the Approach Method
Outdoor Temp. >
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 5, Normal Operating Pressures." Minor varia­tions in these pressures may be expected due to differ­ences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
65F (18C)
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer used to check out-
door ambient temperature to check liquid line tempera-
ture. Verify the unit charge using the approach method. 5 − The difference between the ambient and liquid temper-
atures should match values given in table 4. If the val-
ues don’t agree with the those in table 4, add refriger-
ant to lower the approach temperature or recover
refrigerant from the system to increase the approach
temperature.
Table 4
Approach Values for Charging
Model Number
HPXA15−024 13 ± 1 (7.2 ± .5)
HPXA15−030 7 ± 1 (3.9 ± .5)
HPXA15−036 11 ± 1 (6.1 ± .5)
HPXA15−042 12.5 ± 1 (6.9 ± .5)
HPXA15−048 10 ± 1 (5.6 ± .5)
HPXA15−060 11.5 ± 1 (6.5 ± .5)
Liquid Line Temp. − Outdoor Ambient °F (°C)
Approach Temperature
IMPORTANT
Use table 5 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging/Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
Page 16
DEFROST THERMOSTAT
)
)
EXPANSION/
CHECK VALVE
LOW
PRESSURE
HIGH
PRESSURE
HPXA15 Cooling Cycle
(Showing Gauge Manifold Connections)
OUTDOOR UNIT
DISTRIBUTOR
REVERSING VALVE
BIFLOW
FILTER /
DRIER
MUFFLER
OUTDOOR
COIL
NOTE − ARROWS INDICATE
DIRECTION OF REFRIGERANT
FLOW
INDOOR UNIT
GAUGE MANIFOLD
TO
R410A
DRUM
LIQUID
LINE
SERVICE
PORT
COMPRESSOR
NOTE−Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines
VAPOR
SERVICE
PORT
VAPOR
LINE
VALV E
EXPANSION/CHECK
VALV E
INDOOR
COIL
and indoor coil. Use vapor gauge port to measure vapor pressure during charging.
Figure 16
Table 5
Normal Operating Pressures
(Liquid ±10 and Vapor ±5 psig)
Cooling Operation
Outdoor Coil
Entering Air
Temp. °F (°C
65 (18.3) 252 131 233 141 216 136 240 133 228 137 231 124
75 (23.9) 291 133 272 142 276 138 281 135 265 139 269 126
85 (29.4) 337 135 314 143 298 139 325 137 304 141 315 127
95 (35.0) 371 140 360 146 359 141 372 138 348 142 370 133
105 (40.6) 421 142 413 148 400 143 428 142 405 145 415 136
Outdoor Coil
Entering Air
Temp. °F (°C
20 (−6.6) 288 60 270 67 234 62 340 65 313 60 245 55
30 (−1.1) 306 75 297 84 257 80 350 72 330 73 287 66
40 (4.4) 325 90 325 100 318 93 353 83 346 87 332 82
50 (10.0) 344 105 353 11 7 322 103 358 101 366 101 347 99
HPXA15−024 HPXA15−030 HPXA15−036 HPXA15−042 HPXA15−048 HPXA15−060
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Heating Operation
HPXA15−024 HPXA15−030 HPXA15−036 HPXA15−042 HPXA15−048 HPXA15−060
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Page 17
Table 6
R410A Temperature/Pressure Chart
Temperature°FPressure
Psig
32 100.8 63 178.5 94 290.8 125 445.9 33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5 36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8 40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5 43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4 47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1 51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8 55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4 59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 195.5 93 286.5 124 440.2 155 645.0
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Temperature°FPressure
Psig
Page 18
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
Filter Drier
The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with R410A refrigerant.
Thermostat Operation
Some outdoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The thermostat is not included with the unit and must be purchased separately.
Emergency Heat (Amber Light)
An emergency heat function is designed into some room ther­mostats. This feature is applicable when isolation of the out­door unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power out­age if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.
High Pressure Switch
The HPXA15 is equipped with an auto−reset high pressure switch which is located on the liquid line. The normally closed switch opens the compressor circuit when dis­charge pressure rises above 640 + 10 psig (4412 + 69 kPa). The switch automatically closes when discharge pressure falls below 448 + 10 psig (3089 + 69 kPa).
Defrost System
The defrost system includes two components:
a defrost thermostat a defrost control
Defrost Thermostat
The defrost thermostat is located on the liquid line be­tween the check/expansion valve and the distributor. When the defrost thermostat senses 42°F (5.5°C) or cool­er, its contacts close and send a signal to the defrost con­trol board to start the defrost timing. It also terminates de­frost when the liquid line warms up to 70°F (21°C).
Defrost Control
The defrost control board includes the combined func­tions of a time/temperature defrost control, defrost relay, time delay, diagnostic LEDs, and a terminal strip for field wiring connections. See figure 17.
The control provides automatic switching from normal heating operation to defrost mode and back. During com­pressor cycle (call for defrost), the control accumulates compressor run times at 30, 60, or 90 minute field adjust­able intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.
Defrost Control Timing Pins
Each timing pin selection provides a different accumu­lated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. See figure 17. The defrost timing jumper is factory−installed to provide a 90−minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90−minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jump­ered. If the jumper is in the TEST position at power-up, the
control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an addi­tional 5−second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not re­moved until after the additional 5−second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and reap­plied.
Time Delay
The timed−off delay is five minutes long. The delay helps protect the compressor from short−cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Pressure Switch Circuits
The defrost control includes two pressure switch circuits. The high pressure switch (S4) is factory−connected to the board’s HI PS terminals. The board also includes LO PS ter­minals to accommodate the addition of a field−provided low pressure or loss of charge pressure switch. See figure 17. This feature is available on all units.
During a single demand cycle, the defrost control will lock out the unit after the third time that the circuit is interrupted by any pressure switch that is wired to the control board. In addition, the diagnostic LEDs will indicate a locked out
Page 19
pressure switch after the third occurrence of an open pres­sure switch. See table 7. The unit will remain locked out un­til power is broken then remade to the control or until the jumper is applied to the TEST pins for 0.5 seconds.
NOTE − The defrost control board ignores input from the low pressure switch terminals during the TEST mode, dur­ing the defrost cycle, during the 90−second start−up period, and for the first 90 seconds each time the reversing valve switches heat/cool modes. If the TEST pins are jumpered
and the 5−minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90−second start−up period.
Ambient Thermistor & Service Light Connection
The defrost control board provides terminal connections for the ambient thermistor and a service light. The thermis­tor compensates for changes in ambient temperature
which might cause thermostat droop. The service light thermostat provides a signal which activates the room ther­mostat service light during periods of inefficient operation.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the diagnosis.
Table 7
Defrost Control Board Diagnostic LED
Mode LED 1 LED 2
Normal operation / power to board
Board failure or no power Off Off
Board failure On On
High pressure switch open Flash On
Low pressure switch open On Flash
Pressure switch lockout On Off
Anti−short−cycle / 5−minute delay
Synchronized Flash with LED 2
Alternating Flash with LED 2
Synchronized Flash with LED 1
Alternating Flash with LED 1
Defrost Control Board
PRESSURE SWITCH
WIRING CONNECTIONS
High
Pressure
Switch
(Factory−wired)
Optional
Pressure
Switch (Field−provided and installed −−
jumper removed)
S4
S5
HIGH PRESSURE
SWITCH
TERMINALS
OPTIONAL
PRESSURE
SWITCH
TERMINALS
(Remove factory−
installed jumper
to install
pressure switch.)
DEFROST INTERVAL
TIMING PINS
DIAGNOSTIC
LEDs
SERVICE
LIGHT
TERMINALS
AMBIENT
THERMISTOR
TERMINALS
24V
TERMINAL
STRIP
Figure 17
Page 20
Maintenance
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a quali­fied installer or service agency. At the beginning of each cooling or heating season, the system should be checked as follows:
Outdoor Unit
1 − Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.
2 − Outdoor unit fan motor is prelubricated and sealed. No
further lubrication is needed.
3 − Visually inspect all connecting lines, joints and coils for
evidence of oil leaks. 4 − Check all wiring for loose connections. 5 − Check for correct voltage at unit (unit operating). 6 − Check amp−draw on outdoor fan motor.
Unit nameplate_______Actual_______. 7 − Inspect drain holes in coil compartment base and
clean if necessary.
NOTE − If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil if necessary.
2 − Check connecting lines, joints and coil for evidence of
oil leaks.
3 − Check condensate line and clean if necessary.
Indoor Unit
1 − Clean or change filters.
2 - Lennox blower motors are prelubricated and permanent-
ly sealed. No more lubrication is needed.
3 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4 − Belt Drive Blowers − Check belt for wear and proper
tension.
5 − Check all wiring for loose connections.
6 − Check for correct voltage at unit.
7 − Check amp−draw on blower motor.
Motor nameplate_______Actual_______.
Optional Accessories
Refer to the Engineering Handbook for optional accesso­ries that may apply to this unit. The following may or may not apply:
Loss of Charge Kit High Pressure Switc Kit Compressor Monitor Compressor Crankcase Heater Hail Guards Mounting Bases Timed Off Control Stand−off Kit Sound Cover Low Ambient Kit Monitor Kit
HPXA15 Check Points
Job Name
Job Location Installer
Unit Model No. Nameplate Voltage
Rated Load Ampacity Maximum Fuse or Circuit Breaker Electrical Connections Tight?
Indoor Blower RPM
Cooling
Liquid Line Pressure
Heating
Liquid Line Pressure Refrigerant Lines:
Service Valves Fully Opened?
Sequence of Operation
Heating Correct Cooling Correct
Leak Checked?
S.P. Drop Over Indoor (Dry)
Start−up and Performance Check List
Job No.
City
City
Serial No.
Compressor
Indoor Filter Clean?
Vapor Pressure
Vapor Pressure
Properly Insulated?
Service Valve Caps Tight?
Page 21
Voltage With Compressor Operating
Calibrated? Properly Set? Level?
Outdoor Fan
Outdoor Coil Entering Air Temp.
Refrigerant Charge Checked?
Refrigerant Charge Checked?
Date
State
State
Service Technician
Supply Voltage (Unit Off)
Outdoor Fan Checked?
Thermostat
Loading...