Lennox HPXA12 Series, HPXA12-018, HPXA12-024, HPXA12-030, HPXA12-036 Unit Information

...
Corp. 0208−L3
Service Literature
Revised 09−2004
HPXA12 SERIES UNITS
The HPXA12 is a high efficiency residential split−system heat pump unit, which features a scroll compressor and R410A refrigerant. HPXA12 units are available in sizes ranging from 1 1/2 through 5 tons. The series is designed for use with an expansion valve only (approved for use with R410A) in the indoor unit.This manual is divided into sec­tions which discuss the major components, refrigerant sys­tem, charging procedure, maintenance and operation se­quence. Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change.
IMPORTANT
Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.
HPXA12
WARNING
Warranty will be voided if covered equipment is re­moved from original installation site. Warranty will not cover damage or defect resulting from: Flood, wind, lightning, or installation and opera­tion in a corrosive atmosphere (chlorine, fluorine, salt, recycled waste water, urine, fertilizers, or oth­er damaging chemicals).
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon­nect switch(es). Unit may have multiple power supplies.
TABLE OF CONTENTS
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications / Electrical 2. . . . . . . . . . . . . . . . . . . . . . . .
I Unit Information 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Unit Components 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
III Refrigerant System 13. . . . . . . . . . . . . . . . . . . . . . . . . .
IV Charging 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V Service and Recovery 19. . . . . . . . . . . . . . . . . . . . . . . .
VI Maintenance 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII Wiring Diagram and Operating Sequence 20. . . . . .
Page 1
©2002 Lennox Industries Inc.
SPECIFICATIONS single phase
Fan
Net face area
Kit
M
General Data
Connections (sweat)
Refrigerant (R410A) furnished 7 lbs. 5 oz. (3.31 kg) 6 lbs. 12 oz. (3.06
Outdoor Coil Fan
Outdoor Coil
Shipping Data lbs. (kg) 1 package 160 (73) 160 (73) 176 (80) 181 (82)
Diameter − in. (mm) & no. of blades
Net face area
sq. ft. (m2)
Tube diameter − in. (mm) & no. of rows
Nominal Tonnage (kW) 1.5 (5.3) 2 (7.0) 2.5 (8.8) 3 (10.6)
Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line o.d. − in. (mm) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) 7/8 (22.2)
Model No. HPXA12−018 HPXA12−024 HPXA12−030 HPXA12−036
Motor hp (W)
Cfm (L/s)
Rpm
Watts
Outer coil
Inner coil
Fins per inch (m)
18 (457) − 3
1/6 (124)
2500 (1180)
1100
200
15.21 (1.41)
5.44 (0.51)
5/16 (8) − 1.37
18 (709)
kg)
18 (457) − 3 18 (457) − 4 18 (457) − 4
1/6 (124) 1/6 (124) 1/6 (124)
2500 (1180) 2450 (1155) 2450 (1155)
1100 1100 1100
200 200 200
15.21 (1.41) 15.21 (1.41) 15.21 (1.41)
5.44 (0.51) 14.50 (1.35) 14.50 (1.35)
5/16 (8) − 1.37 5/16 (8) − 2 5/16 (8) − 2
18 (709) 18 (709) 18 (709)
7 lbs. 12 oz. (3.51
kg)
8 lbs. 15 oz. (4.1 kg)
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Monitor (Canada Only) 45F08 45F08 45F08 45F08
Hail Guards 17L73 17L73 17L73 17L73
Mild Ambient Kit (LB-101122) 32M08 32M08 32M08 32M08
Monitor Kit (Canada Only) 76F53 76F53 76F53 76F53
Outdoor Thermostat Kit
Plastic
ounting
Base
Refrigerant Line Set
Unit Stand-Off Kit 94J45 94J45 94J45 94J45
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.Refrigerant charge is sufficient for 15 ft. (4.5 m) length line set.
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage
Part No. − Catalog Number MB2-S (69J06) MB2-S (69J06) MB2-S (69J06) MB2-S (69J06)
Suction/Vapor Line o.d. − in. (mm) 3/4 (19) 3/4 (19) 3/4 (19) 7/8 (22.2)
Liquid Line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Thermostat 56A87 56A87 56A87 56A87
Mounting Box − US 31461 31461 31461 31461
Canada 33A29 33A29 33A29 33A29
Net Weight 6 lbs. (3 kg) 6 lbs. (3 kg) 6 lbs. (3 kg) 6 lbs. (3 kg)
30 ft. (9 m) length L15−41−30 L15−41−30 L15−41−30 L15−65−30
40 ft. (12 m) length L15−41−40 L15−41−40 L15−41−40 L15−65−40
50 ft. (15 m) length L15−41−50 L15−41−50 L15−41−50 L15−65−50
Page 2
SPECIFICATIONS single phase Cont.
Fan
Net face area
Kit
M
g
p
General Data
Connections (sweat)
Refrigerant (R410A) furnished 9 lb. 2 oz. (4.13 kg) 11 lbs. 5 oz. (5.12 kg) 11 lbs. 3 oz. (5.06 kg)
Outdoor Coil
Outdoor Coil
Shipping Data lbs. (kg) 1 package 190 (86) 244 (111) 244 (111)
Diameter − in. (mm) & no. of blades 18 (457) − 4 22 (559) − 4 22 (559) − 4
Net face area
sq. ft. (m2)
Tube diameter − in. (mm) & no. of rows 5/16 (8) − 2 5/16 (8) − 2 5/16 (8) − 2
Nominal Tonnage (kW) 3.5 (12.3) 4 (14.1) 5 (17.6)
Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line o.d. − in. (mm) 7/8 (22.2) 7/8 (22.2) 1−1/8 (28.6)
Model No. HPXA12−042 HPXA12−048 HPXA12−060
Motor hp (W) 1/3 (249) 1/3 (249) 1/3 (249)
Cfm (L/s) 2930 (1385) 3890 (1835) 3890 (1835)
Rpm 1100 1085 1085
Watts 310 375 375
Outer coil 15.21 (1.41) 21.11 (1.96) 21.11 (1.96)
Inner coil 14.50 (1.35) 20.31 (1.89) 20.31 (1.89)
Fins per inch (m) 22 (860) 22 (860) 22 (860)
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Monitor (Canada Only) 45F08 45F08 45F08
Hail Guards 17L73 17L74 17L74
Mild Ambient Kit (LB-101122) 32M08 32M08 32M08
Monitor Kit (Canada Only) 76F53 76F53 76F53
Outdoor Thermostat
Plastic
ounting
Base
Refrigerant Line Set
Unit Stand-Off Kit 94J45 94J45 94J45
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.Refrigerant charge is sufficient for 20 ft. (6.1 m) length line set.
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage
Part No. − Catalog Number MB2-S (69J06) MB2-L (69J07) MB2-L (69J07)
Suction/Vapor Line o.d. − in. (mm) 7/8 (22.2) 7/8 (22.2) 1−1/8 (28.5)
Liquid Line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Thermostat 56A87 56A87 56A87
Mounting Box − US 31461 31461 31461
Canada 33A29 33A29 33A29
Net Weight 6 lbs. (3 kg) 15 lbs. (7 kg) 15 lbs. (7 kg)
30 ft. (9 m) length L15−65−30 L15−65−30 Field Fabricate
40 ft. (12 m) length L15−65−40 L15−65−40 Field Fabricate
50 ft. (15 m) length L15−65−50 L15−65−50 Field Fabricate
ELECTRICAL DATA
Model No. HPXA12−018 HPXA12−024 HPXA12−030 HPXA12−036 HPXA12−042 HPXA12−048 HPXA12−060
Line voltage data − 60 hz − 1 phase 208/230v 208/230v 208/230v 208/230v 208/230v 208/230v 208/230v
Recommended maximum fuse or circuit breaker size (amps)
{Minimum circuit ampacity 14.0 18.0 20.0 20.4 25.9 30.8 36.4
Compressor
Outdoor Coil
Fan Motor
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
Rated load amps 10.3 13.5 15.1 15.4 19.2 23.1 27.6
Power factor .98 .98 .98 .98 .99 .99 .99
Locked rotor amps 51 61 72.5 83 104 134 158
Full load amps 1.1 1.1 1.1 1.1 1.9 1.9 1.9
Locked rotor amps 1.9 1.9 1.9 1.9 4.1 4.1 4.1
20 30 35 35 45 50 60
Page 3
SPECIFICATIONS three phase
Fan
Net face area
p
Kit
g
g
General Data
Connections (sweat)
1
Refrigerant (R410A) furnished 8 lbs. 15 oz. (4.1 kg) 11 lbs. 5 oz. (5.1 kg) 11 lbs. 3 oz. (5.1 kg)
Outdoor
Diameter − in. (mm) & no. of blades 18 (457) − 4 22 (559) − 4 22 (559) − 4
Nominal Tonnage (kW) 3 (10.6) 4 (14.1) 5 (17.6)
Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line o.d. − in. (mm) 7/8 (22.2) 7/8 (22.2) 1−1/8 (28.6)
Coil
Outdoor Coil
Net face area
sq. ft. (m2)
Tube diameter − in. (mm) & no. of rows 5/16 (8) − 2 5/16 (8) − 2 5/16 (8) − 2
Shipping Data 1 package − lbs. (kg) 181 (82) 244 (111) 244 (111)
ELECTRICAL DATA
Line voltage data − 60 hz − 3 phase 208/230V 460V 208/230V 460V 208/230V 460V
2
Maximum overcurrent protection (amps) 25 10 35 15 40 20
3
Minimum circuit ampacity 15.4 6.9 21.9 9.8 24.5 12.2
Compressor
Locked Rotor amps 77 35 91 46 137 62
Outdoor Coil
Fan Motor
Locked Rotor Amps 2.3 1 4.1 2.1 4.1 2.1
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Low Ambient Cut−Off 45F08 45F08 45F08
Compressor Sound Cover 69J03 69J03 69J03
Compressor Crankcase Heater 67K90 67K89 Factory Installed Factory Installed
Freezestat
Hail Guards 17L73 17L74 17L74
Low Ambient Kit 54M89 54M89 54M89
Mild Weather Kit 33M07 33M07 33M07
Monitor Kit − Service Light 76F53 76F53 76F53
Outdoor Thermostat Kit
Mounting Base
Refrigerant Line Set
Unit Stand-Off Kit 94J45 94J45 94J45
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge is sufficient for 15 ft. (4.6 m) length line set.
2
HACR tyoe circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Mounting Box − US 31461 31461 31461
15 ft. (4.6 m) length L15−65−15 L15−65−15 Field Fabricate
40 ft. (12 m) length L15−65−40 L15−65−40 Field Fabricate
50 ft. (15 m) length L15−65−50 L15−65−50 Field Fabricate
Model No. HPXA12−036 HPXA12−048 HPXA12−060
Motor hp (W) 1/6 (124) 1/3 (249) 1/3 (249)
Cfm (L/s) 2450 (1155) 3890 (1835) 3890 (1835)
Rpm 1100 1085 1085
Watts 200 375 375
Outer coil 15.21 (1.41) 21.11 (1.96) 21.11 (1.96)
Inner coil 14.50 (1.35) 20.31 (1.89) 20.31 (1.89)
Fins per inch (m) 18 (709) 22 (860) 22 (860)
Model No. HPXA12−036
Rated load amps
−233
11.5 5.1 16 7.1 18.1 9
HPXA12−036
−463
HPXA12−048
−233
HPXA12−048
−463
HPXA12−060
−233
HPXA12−060
Power Factor .98 .98 .99 .99 .99 .99
Full load amps
1 .55 1.9 .9 1.9 .9
3/8 in. tubing 93G35 93G35 93G35
1/2 in. tubing 39H29 39H29 39H29
5/8 in. tubing 50A93 50A93 50A93
Thermostat 56A87 56A87 56A87
Canada 33A09 33A09 33A09
Model (Catalog) No. MB2-S (69J06) MB2-L (69J07) MB2-L (69J07)
Net Weight 6 lbs. (3 kg) 15 lbs. (7 kg) 15 lbs. (7 kg)
30 ft. (9 m) length L15−65−30 L15−65−30 Field Fabricate
−463
Page 4
I − UNIT INFORMATION
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
All major components (indoor blower and coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the En­gineering Handbook for approved system matchups. A missapplied system will cause erratic operation and can re­sult in early compressor failure.
A − Control Box (Figures 2 and 3)
HPXA12 units are not equipped with a 24V transformer. All 24 VAC controls are powered by the indoor unit. Refer to wiring diagram.
SINGLE PHASE UNIT CONTROL BOX
DUAL CAPACITOR
(C12)
COMPRESSOR
CONTACTOR
(K1)
DEFROST
GROUNDING
LUG
FIGURE 2
CONTROL
(A108)
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook.
II − UNIT COMPONENTS
Unit components are illustrated in figure 1.
OUTDOOR
FAN/MOTOR
HPXA12 UNIT COMPONENTS
CONTROL
BOX
SUCTION
MUFFLER
REVERSING
VALV E
THREE PHASE UNIT CONTROL BOX
RUN CAPACITOR
(C1)
OUTDOOR FAN
RELAY (K10)
460 VOLTAGE
COMPRESSOR
CONTACTOR
(K1)
GROUNDING
LUG
ONLY
DEFROST
CONTROL
(A108)
FIGURE 3
Electrical openings are provided under the control box cov­er. Field thermostat wiring is made to a 24V terminal strip located on the defrost control board located in the control box. See figure 4.
24V THERMOSTAT TERMINAL STRIP
COMPRESSOR
BI-FLOW
FILTER DRIER
FIGURE 1
CHECK/EXPANSION
VALV E
Page 5
Y2
CRW1OY1L
FIGURE 4
1 − Compressor Contactor K1
The compressor is energized by a contactor located in the control box. See figure 2. Single−pole contactors are used in single−phase HPXA12 series units and three pole con­tactors are used in HPXA12 three−phase units. K1 is ener­gized through the control board by the indoor thermostat terminal Y1 (24V) when thermostat demand is present.
DANGER
Electric Shock Hazard. May cause injury or death.
Line voltage is present at all compo­nents when unit is not in operation on units with single pole contactors. Disconnect all remote electrical power supplies before opening unit panel. Unit may have multiple power supplies.
2 − Outdoor Fan Relay K10 (460V units only)
Outdoor fan relay K10, used in 460V units only, is a SPST normally open relay. K10 is energized by contactor K1 which in turn energizes outdoor fan B4 in response to ther­mostat demand.
3 − Run Capacitor C1 (three phase only)
The fan in all three−phase units uses a single−phase perma­nent split capacitor motor. A single capacitor C1 is used for the fan motor. C1 is located inside the control box. See fig­ure 3. Fan motor nameplate will have capacitor ratings.
The demand defrost board uses basic differential temper­ature means to detect degradation of system performance due to ice build−up on the outdoor coil. Further, the control­ler uses self−calibrating" principles to calibrate itself when the system starts and after each time the system defrosts. The control board has defrost relays, anti−short cycle timed−off control, pressure switch/safety control, 3−strike lockout circuit, field test pins, ambient and coil tempera­ture sensors, field selectable termination temperature and a field low voltage connection terminal strip. The control monitors ambient temperature, outdoor coil temperature and total run time to determine when a de­frost cycle is required. Two temperature probes are per­manently attached to the control. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is im­portant for proper defrost operation. On HPXA12−018 &
−024 the sensor should located on the 4th hairpin bend from the bottom. HPXA12−030 through −060 units the sen­sor should located on the 6th hairpin bend from the bot­tom. See figure 5.
NOTE − The logic of the Demand Defrost Board provides accurate performance measurements of the system as FROST accumulates on the outdoor coil. This will translate into longer running time in the heating mode with FROST accumulations on the outdoor coil before the board initiates any defrost cycles.
COIL SENSOR LOCATION
4 − Dual Capacitor C12
The compressor and fan in single phase HPXA12 series units use permanent split capacitor motors. The capacitor is located inside the unit control box (see figure 2). A single dual" capaci­tor (C12) is used for both the fan motor and the compressor (see unit wiring diagram). The fan side and the compressor side of the capacitor have different MFD ratings. See side of capacitor for ratings.
5 − Demand Defrost System
Boards 60L3901, 46M8201, 56M8501
The HPXA12 will be equipped with one of three model de­frost boards. Differences are minimal:
Three strike lock out feature (60L3901) Five strike out feature (46M8201, 56M8501) Terminal T" for ambient sensor (60L3901) Terminal Y2" for 2nd stage thermostat input (46M8201,
56M8501). DELAY" pins (56M8501)
On HPXA12−030 /
On HPXA12−018,
−024 units,clip the coil sensor clip on the 4th bend from the bottom
The temperature probes cannot be detached from the con­trol. The control and the attached probes MUST be re­placed as a unit. Do not attempt to cut or splice probe wires.
−060 units,clip the coil sensor clip on the 6th bend from the bottom
FIGURE 5
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition. See table 1.
Page 6
HI−PS/LO−PS Terminals
High pressure switch (S4) is factory wired into the defrost board HI−PS terminals. When (S4) trips, the defrost board will cycle off the compressor and the strike counter in the board will count one strike.
Low pressure switch (S87) is factory wired into the defrost board LO−PS terminals. When (S87) trips, the defrost board will cycle off the compressor and the strike counter in the board will count one strike. (S87) is ignored during certain conditions:
During the defrost cycle and 90 seconds after the
termination of defrost
When the average ambient sensor temperature is
below 15 F (−9)
For 90 seconds following the start up of the
compressor
During "Test" mode
3−Strike Lockout Feature (Board 60L3901)
The internal control logic of the board counts the pres-
sure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes twice during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a third time during the current Y1 (Input), the control will enter a lockout condition.
The 3−strike pressure switch lockout condition can be re-
set by cycling OFF the 24−volt power supply to the con­trol board or by shorting the TEST pins. All timer func­tions (run times) will also be reset.
If a pressure switch becomes open while the Y1 Out line
is engaged, a 5 minute short cycle will occur after the switch closes.
5−Strike Lockout Feature (Boards 46M8201, 56M8501)
The internal control logic of the board counts the pres-
sure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes 4 times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be re-
set by cycling OFF the 24−volt power supply to the con­trol board or by shorting the TEST pins. All timer func­tions (run times) will also be reset.
If a pressure switch becomes open while the Y1 Out line
is engaged, a 5 minute short cycle will occur after the switch closes.
Operational Description
The demand defrost board has three basic operational modes: Normal, Defrost, and Calibration.
Normal Mode
The demand defrost board monitors the O" line, to deter­mine the system operating mode (heat/cool), outdoor ambi­ent temperature, coil temperature (outdoor coil) and com­pressor run time to determine when a defrost cycle is re­quired.
Defrost Mode
When a defrost cycle is initiated, the control energizes the reversing valve solenoid and turns off the condenser fan. The control will also put 24VAC on the W1" (auxiliary heat) line. The unit will stay in this mode until either the coil sensor temperature is above the selected termination tempera­ture, the defrost time of 14 minutes has been completed, or the room thermostat demand cycle has been satisfied. (If the temperature select shunt is not installed, the default ter­mination temperature will be 100°F.) If the room thermostat demand cycle terminates the cycle, the defrost cycle will be held until the next room thermostat demand cycle. If the coil sensor temperature is still below the selected termination temperature, the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned above. If a defrost is terminated by time and the coil temper­ature did not remain above 35°F (2°C) for 4 minutes, the control will go to the 34−minute Time/Temperature mode.
DELAY" PINS
The 56M8501 defrost board has a field selectable function to reduce occasional noise that may occur while the unit is cycling in and out of defrost mode. When a jumper is installed on the DELAY" pins, the compressor will cycle off for 30 seconds going in and out of defrost mode. Units are shipped with jumper installed on DELAY" pins.
NOTE − 30 second off cycle is not functional when jumpering TEST" pins.
Calibration Mode
The board is considered uncalibrated when power is ap­plied to the board, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode. Calibration of the board occurs after a de­frost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish a temperature differential required to allow a defrost cycle.
Page 7
Loading...
+ 16 hidden pages