Lennox HP27 SERIES, HP27-030, HP27-036, HS27-024, HP27-042 Installation Instructions Manual

Page 1
504,712M
*P504712M*
06/04
*2P0604*
2002 Lennox Industries Inc.
Dallas, Texas, USA
HP27 Outdoor Unit
HP27 outdoor units are designed for expansion valve sys­tems only. They are not designed for RFC systems. Refer to Lennox engineering handbook for expansion valve kits which you must order separately.
Shipping & Packing List
1 − Assembled HP27 outdoor unit
2 − Grommets (for liquid and vapor lines)
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarcera­tion may be levied for noncompliance.
INSTALLATION INSTRUCTIONS
HP27 SERIES UNITS
HEAT PUMP UNITS
504,712M 06/04
Supersedes 12/03
Table of Contents
HP27 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Metering Device 10. . . . . . . . . . . . . . . . . . . .
Service Valves 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manifold Gauge Set 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HP27 Check Points 18. . . . . . . . . . . . . . . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
Litho U.S.A.
Page 2
Unit Dimensions − inches (mm)
2-3/4
(70)
COMPRESSOR
INLET
INLET
AIR
TOP VIEW
SIDE VIEW
SERVICE ACCESS
ELECTRICAL
INLETS
VAP OR
LINE INLET
DISCHARGE
AIR
COIL DRAIN
OUTLETS
(Around perimeter
of base)
4
(102)
B
1-3/8
(35)
LIQUID
LINE INLET
4
(102)
6-1/16
(154)
AIR
INLET
AIR
A
4-7/8 (22)
4-1/2 (114)
2-9/16
(65)
2
(51)
2
(51)
13-5/8
(473)
26-5/8
(676)
7-1/2 (191)
7-1/2 (191)
3-7/8
(98)
3-7/8
(98)
28-1/8 (714)
32−1/8
(816)
34-1/16
(865)
Model No. A B
HS27-024
in. 40-7/8 19-13/16
HS27-024
HP27-030
mm 1038 503
HP27-036
in. 44-7/8 14-1/4
HP27-036
HP27-042
mm 1140 362
Page 3
Parts Arrangement
Figure 1
HP27 UNIT COMPONENTS
CONTACTOR
DEFROST CONTROL/TIMED−OFF CONTROL
LIQUID LINE
SERVICE VALVE
AND GAUGE
PORT
VAPOR LINE
SERVICE VALVE
AND GAUGE
PORT
MUFFLER
EXPANSION VALVE
WITH
INTERNAL CHECK VALVE
REVERSING
VALV E
AND SOLENOID
BIFLOW
FILTER/DRIER
DUAL
CAPACITOR
DISTRIBUTOR
HIGH PRESSURE
SWITCH
GROUND LUG
DEFROST
THERMOSTAT
TXV
SENSING BULB −036,
−042 ONLY
VAPOR GAUGE
PORT
ACCUMULATOR
TXV
SENSING BULB
−024, −030 ONLY
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
The outdoor units operate under a wide range of weather conditions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be posi­tioned to give adequate clearances for sufficient airflow and servicing. A minimum clearance of 24inches (610 mm) between multiple units must be maintained. Refer to figure 2 for installation clearances.
1 − Place a sound−absorbing material, such as Isomode,
under the unit if you intend to install it in a location or a position that will transmit sound or vibration to the liv­ing area or adjacent buildings.
2 − Install the unit high enough above ground or roof to
prevent ice build−up and to allow adequate drainage of defrost water.
3 − In areas that receive heavy snow, do not locate the unit
where drifting will occur. Ensure that the unit base is elevated above the depth of average snows.
NOTE − Elevate the unit by constructing a frame using suitable materials. If you construct a support frame, it must not block drain holes in the base of the unit.
36"
(914 mm)
36"
(914 mm)
*36"
(914 mm)
*36"
(914 mm)
Installation Clearances
NOTE − A service access clearance of 30" (762 mm) must be maintained in front of the service access panel. Clearance to one side must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
Figure 2
Page 4
4 − When you install the unit in areas where low ambient
temperatures exist, locate the unit so winter prevailing winds do not blow directly into outdoor coil.
5 − Locate the unit away from overhanging roof lines
which would allow water or ice to drop on, or in front of, the coil or into the unit.
Slab Mounting
When installing the unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground will not collect around the unit. See figure 3. The slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m). This will prevent ice from building up under the unit dur­ing a defrost cycle. Refer to the roof mounting section for barrier construction if the unit must face prevailing winter winds.
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m)
slope tolerance away
from building structure
Slab Mounting
ground level
mounting
slab
building
structure
discharge air
Figure 3
Roof Mounting
If you are unable to mount the unit coil away from prevailing winter winds, construct a wind barrier. See figure 4. Size the barrier at least the same height and width as the out­door unit. Mount the barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
WIND BARRIER
INLET AIR
PREVAILING WINTER WINDS
Rooftop Application
Wind Barrier Construction
INLET AIR
INLET
AIR
Figure 4
24 in.
(610 mm)
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
Page 5
WARNING
Unit must be grounded in accordance with national and local codes. Electric Shock Hazard. Can cause injury or death.
1 − Install line voltage power supply to unit from a properly
sized disconnect switch.
2 − Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us ing a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 5 for field wiring diagram.
NOTE − A complete unit wiring diagram is located in side the unit control box cover.
3 − Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4 − Install voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit. See figures 6 and 7.
Typical Field Wiring Diagram
Figure 5
Page 6
R
C
W1
Y1
O
G
R
C
W1
W2
W3
G
reversing valve
Outdoor Unit and Blower Unit
Thermostat Designations
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
Indoor
Unit
R
C
W1
Y1
O
Outdoor
Unit
power
power
common common
1st. stage aux. heat
1st. stage aux. heat
indoor blower
compressor
Figure 6
R
C
W1
Y1
O
G
R
C
W1
W2
W3
G
Outdoor Unit and Blower Unit
Thermostat Designations
(with auxiliary heat)
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
Indoor
Unit
Outdoor
Unit
E
R
C
W1
Y1
O
reversing valve
indoor blower
compressor
power
power
common common
1st. stage aux. heat
1st. stage aux. heat
emergency heat
Figure 7
Refrigerant Piping
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 1 or use field-fabri­cated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351−L9) for proper size, type, and application of field−fabricated lines. Valve sizes are also listed in table 1.
Table 1
Refrigerant Line Set
s
Valve Field Size
Connections
Recommended Line Set
Model
Liquid
Line
Vapor
Line
Liquid
Line
Vapor
Line
L15
Line Sets
−024
−030
3/8 in.
9.5 mm
3/4 in.
19.1 mm
3/8 in.
9.5 mm
3/4 in.
19.1 mm
L15−41
15 ft.−50 ft.
4.6 m−15.2 m
−036
−042
3/8 in.
9.5 mm
7/8 in.
22.2 mm
3/8 in.
9.5 mm
7/8 in.
22.2 mm
L15−41
15 ft.−50 ft.
4.6 m−15.2 m
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Closer attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high−efficiency outdoor unit:
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from the adjacent property not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmis­sion.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line set isolation. Figure 8 shows how to install line sets on vertical runs. Figure 9 shows how to install line sets on horizontal runs. Figure 10 shows how to make a transi­tion from horizontal to vertical. Finally, figure 11 shows how to place the outdoor unit and line set.
Loading...
+ 12 hidden pages