Page 13
Start−Up
Cooling Start−Up
IMPORTANT
If unit is equipped with crankcase heater, it should be
energized 24 hours before unit start−up to prevent
compressor damage as a result of slugging.
1 − Rotate fan to check for frozen bearings or binding.
2 − Inspect all factory− and field-installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves (counterclockwise) to release
refrigerant charge (contained in outdoor unit) into the
system.
4 − Replace stem caps and secure finger tight, then tight-
en an additional (1/6) one-sixth of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the
power company has been consulted and the voltage
condition has been corrected.
6 − Set the thermostat for a cooling demand, turn on power
to indoor blower unit and close the outdoor unit disconnect to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Manifold Gauge Set
When checking the unit charge, use a manifold gauge set
equipped with low loss" hoses. Do not use a manifold
gauge set that has anything other than a low loss" hose.
Charging
The unit is factory−charged with the amount of HCFC−22 refrigerant that is indicated on the unit rating plate. This
charge is based on a matching indoor coil and outdoor coil
with a 15 foot (4.6 m) line set. For varying lengths of line set,
refer to table 3 for refrigerant charge adjustment.
Table 3
Liquid Line
Set Diameter
Oz. per 5 ft. (g per 1.5 m) adjust
from 15 ft. (4.6 m) line set*
3/8 in.
(9.5 mm)
3 ounces per 5 ft. (88.05 g per 1.5 m)
*If line set length is greater than 15 ft. (4.6 m), add this amount. If line set
length is less than 15 ft. (4.6 m), subtract this amount.
The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
1 − Close manifold gauge set valves. Connect manifold
gauge set to service valves as shown in figure 16.
low pressure gauge to vapor valve service port
high pressure gauge to liquid valve service port
Connect the center manifold hose to an upright cylinder of HCFC−22.
2 − Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in
the cooling cycle.
3 − Use a digital thermometer to record the outdoor ambi-
ent temperature.
4 − When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68F
(20C). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature.
5 − The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate charging procedure.
Weighing in the Charge TXV Systems –
Outdoor Temp < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit. Do this after any leaks have been repaired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other procedures outlined below.
Subcooling Method
Outdoor Temp. < 65°F (18°C)
When the outdoor ambient temperature is below 65°F
(18°C), use the subcooling method to charge the unit. It
may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 200−250 psig
(1379−1724 kPa) range. These higher pressures are nec-