Lennox G1N80BU, GIN80BT, GIN80BR, CG80UB, CG80RB Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
®
G1N80BU, GIN80BR, GIN80BT, CG80UB, CG80RB, & CG80TB
80% Gas-Fired Furnace
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
W ARNING
Do not store combustible materials, including gasoline and other flammable vapors and liquids, near the furnace, vent pipe, or warm air ducts. The homeowner should be cau­tioned that the furnace area must not be used as a broom closet or for any other storage purposes. Such uses may result in actions that could cause property damage, personal injury, or death.
SAFETY ................................................. 2
INSTALLATION ...................................... 2
START-UP ............................................ 14
OPERATION ........................................ 15
MAINTENANCE................................... 16
T ABLE OF CONTENTS
CONTROL SYSTEM DIAGNOSTICS .. 18
W ARNING
REPAIR PARTS ................................... 18
This furnace is not approved for installation in a mobile home. Do not install this furnace in a
WIRING DIAGRAMS ............................ 19
mobile home. Installation in a mobile home could result in actions that could cause prop­erty damage, personal injury, or death.
A Lennox International Company
Manufactured By
A.A.C.
421 Monroe Street
®
IMPORT ANT
The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition) and the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; CSA B149.1 (latest edition) Natural Gas and Propane Installation Codes and the Canadian Electrical Code Part 1, CSA
22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances (including plumbing or wastewater codes), or local gas utility requirements. Local authorities having jurisdiction should be con­sulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
# 45464K003 Page 1
IMPORT ANT SAFETY INFORMATION
The following is a list of safety rules and precautions that must be followed when installing this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the Location section on page 3 of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in the Combustion and Ventilation Air section beginning on page 4 of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in Venting beginning on page 6 of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions, as specified in Gas Supply and Piping beginning on page 12 of these instructions.
6. Always install furnace to operate within the furnace’s
intended temperature rise range with a duct system
which has an external static pressure within the allowable range, as specified in Temperature Rise on page 16 of these instructions. See furnace rating plate.
7. When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See Circulating Air Supply on page 8 of these instructions.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in the Loca- tion section on page 3 of these instructions.
9. The furnace is not to be used for temporary heating of buildings or structures under construction as specified on page 4 of these instructions.
In the State of Massachusetts:
This product must be installed by a licensed Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not exceed 36". When lever­type gas shutoffs are used, they shall be T-handle type.
INSTALLATION
These instructions must be placed on or near the furnace in a conspicuous place.
This furnace is design certified by CSA International as a Category I furnace using air from inside the structure for combustion. The combustion system is fan-assisted, which means it is equipped with an integral mechanical means to draw products of combustion through the heat exchanger.
G1N80BT and CG80TB models may be installed as upflow or horizontal furnaces. G1N80BR and CG80RB models may be installed as counterflow (downflow) or horizontal
furnaces. When installed horizontally, the installer must install a sheet metal screw to retain the upper door as shown in Figure 1.
G1N80BU and CG80UB models must be installed only as upflow furnaces.
Never install any furnace on its back.
Horizontal Installations
Figure 1
# 45464K003Page 2
Inspection of Shipment
tenibaC
htdiW
sediS tnorF kcaB tneV
wolfriA
LotR RotL
poT mottoB poT mottoB
5.4108106
232
013
2
5.71 0 81 0 622
2
0 1 2
2
0.1208106210 10
5.42 0 81 0 621 0 1 0
tenibaC
htdiW
sediS tnorF kcaB tneV
wolfriA
LotR RotL
poT mottoB poT mottoB
5.411810621313
1
0
5.71 1 81 0 621 2
2
2
2
0
0.1218106210 10
This furnace is shipped in one package, completely assembled and wired. The thermostat is shipped in a
separate carton when ordered.
Minimum Clearances to Combustibles
(all measurements in inches)
Upflow and Counterflow Installations
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on
the carriers freight bill. Damage claims should be filed with
the carrier immediately. Claims of shortages should be filed with the seller within 5 days.
Check the rating plate for correct model number, type of gas, and input.
Clearances
All servicing and cleaning of the furnace can be performed from the front. If installed in a closet or utility room, provide 18" clearance in front for service if the door to the room is not in line with the front of the furnace.
All models are suitable for installation at reduced clear­ances to combustibles as noted in the tables in Figure 2. Where servicing clearances are greater than clearances to combustibles, servicing clearances take precedence.
G1N80BU, G1N80BT, CG80UB, and CG80TB models, and horizontally installed G1N80BR and CG80RB models may be installed on wood flooring, but shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
tenibaC
htdiW
5.414
5.71 4
0.124
5.42 4
tnorF kcaB poT tneV
1
01623
1
0 1 6
1
016210
1
0 1 6
Horizontal Installations
(G1N80BR and CG80RB models)
Horizontal Installations
(G1N80BT and CG80TB models)
2
2
tfeL thgiR
3
3
2
0 0
sediS
0
0
G1N80BR and CG80RB models installed as counterflow (downflow) units may be installed on combustible flooring provided a special combustible floor base is used. Refer to
the Counterflow (Downflow) Installations section begin-
ning on page 10 for more information on using the special base assembly.
Location
All models are suitable for closet or utility room installation. The furnace must be installed so that electrical compo­nents are protected from water.
The furnace is suitable for installation in buildings con­structed on-site. The furnace should be centralized in respect to the heat distribution system as much as practicable. When installed in a utility room, the door should be wide enough to allow the largest part of the furnace to enter, or permit the replacement of another appliance, such as a water heater.
A gas-fired furnace for installation in a residential garage must be installed so the burner(s) and the ignition source are located not less than 18" above the floor. The furnace is to be located or protected to avoid physical damage by vehicles.
# 45464K003 Page 3
1
May be 2" when Type B-1 vent pipe is used.
2
May be 1" when Type B-1 vent pipe is used.
3
Where values greater than 0 are shown, may be 0" when Type B-1 vent pipe is used.
Figure 2
G1N80BR, G1N80BT, CG80RB, and CG80TB models installed in the horizontal position are approved for attic
installations. If the furnace is to be installed in an attic
or other insulated space, it must be kept free and clear of insulating materials. When a furnace is installed in conjunction with an evaporator coil in an attic or above a finished ceiling where condensate overflow could result in property damage, a drain pan should be provided under the units as specified by most local building codes.
G1N80BR, G1N80BT, CG80RB, and CG80TB models may be installed as suspended units in the horizontal position. These furnaces are not designed for direct attachment of suspension rods to the furnace casing.
However, in a building of unusually tight construction, additional outdoor air should be provided.
Confined Space
The suspending means must be field fabricated, and
should consist of two “cradles” made by attaching two rods
to a length of angle iron or suitable gage steel. Locate the cradles so that they are as close as possible to the ends of the furnace (this will provide access for removal of major components such as the blower assembly). Provide enough clearance between the suspension rods and the furnace to allow removal of access panels.
CAUTION
Do not use the furnace as a heater in a building under construction. The furnace can be severely damaged due to the abnormal environment caused by construction. Chlo­rides from sources such as paint, stain, or varnish; tile and counter cements; adhesives; and foam insulation are abundant in a struc­ture under construction and can be highly corrosive. Low return air temperature can cause condensation in the furnace and other damage that can shorten the life of the unit.
A confined space is defined as a space whose volume is
less than 50 cubic feet per 1000 BTU per hour of the combined input rating of all appliances installed in that
space.
Confined Space Installation/Air from Inside Structure
If the furnace is installed in a confined space within the building and combustion air is taken from a heated space, the combustion air and ventilating air must enter and leave the space through two permanent openings of equal area. One opening shall be located within 12" of the ceiling and the other within 12" of the floor, each having a free area of 1 square inch per 1000 BTU/HR of total input rating of all appliances within the space and not less than 100 square inches each (see Figure 3).
Equipment in Confined Space
All Air From Inside
Chimney or Gas Vent
Water
Heater
Combustion and Ventilation Air
Adequate provisions for combustion air and ventilation of
furnace must be made. Refer to Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z223.1/NFPA54 (latest edition), Sections 7.2,
7.3, or 7.4 of CSA B149.1 Natural Gas and Propane Installation Codes (latest editions), or applicable provi­sions of the local building codes.
WARNING
Air openings in the front of the furnace must be kept free of obstructions. Any obstruction may cause improper operation that can result in a fire hazard or carbon monoxide injury.
Unconfined Space
An unconfined space is defined as a space whose volume
is more than 50 cubic feet per 1000 BTU per hour of the combined input rating of all appliances installed in that
space. When a furnace is installed in an unconfined space
in a building, it can be assumed that the infiltration will be sufficient to supply the required air. If the furnace is installed in a ventilated attic or crawl space, it is assumed that the infiltration is sufficient to supply the required air.
Openings
Furnace
Note: Each opening shall have a free area of at least one square
inch per 1000 BTU per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches.
Figure 3
Confined Space Installation/Air from Outside Structure
If air from outside is brought in for combustion, the confined space shall be provided with two permanent openings. One opening shall be within 12" of the ceiling and one opening within 12" of the floor. Several methods can be used to bring the outside air in through these openings. The openings shall open directly or by ducts with the outdoors, through spaces (crawl space or attic) that freely open to the out­doors, or indirectly through vertical ducts (see Figures 4 and
5). If any of these methods are used, each opening shall
have a free area of 1 square inch per 4000 BTU/HR of the total input rating of all appliances within the enclosure.
# 45464K003Page 4
Equipment in Confined Space
All Air from Out side
(Inlet Air from Crawl Sp ace and
Outlet Air to V entilated Attic)
Equipment in Confined Space
All Air from Out side
(All Air Through Horizontal Ducts)
Chimney or Gas Vent
Furnace
Ventilation
Louvers
(For unheated
crawl space)
Note: The inlet and outlet air opening shall each have a free area of
at least one square inch per 4000 BTU per hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
(Each end of attic)
Outlet
Air
Inlet
Air
Water
Heater
Figure 4
Equipment in Confined Space
All Air from Out side
(All Air Through V entilated Attic)
Chimney or Gas Vent
Outlet Air
Furnace
Ventilation Louvers
(Each end of attic)
Inlet Air
(Ends 12”
above bottom)
Water
Heater
Chimney or Gas Vent
Water Heater
Outlet Air
Furnace
Inlet Air
Note: Each air duct opening shall have a free area of at least one
square inch per 2000 BTU per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the outdoors, each opening shall have a free area of at least one square inch per 4000 BTU per hour of the total input rating of all other equipment in the enclosure.
Figure 6
come from the outdoors by way of an attic, crawl space, air duct, or direct opening.
2. If indoor combustion air is used, there must be no exposure to the substances listed in item 5.
3. All provisions for indoor combustion air must meet the requirements for combustion air indicated in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition), and/or any applicable local codes. In Canada, see CSA B149.1, Natural Gas and Propane Installa­tion Codes (latest edition).
Note: The inlet and outlet air opening shall each have a free area of
at least one square inch per 4000 BTU per hour of the total input rating of all equipment in the enclosure.
Figure 5
Another option is to use horizontal combustion ducts (see Figure 6). If horizontal combustion ducts are run, 1 square inch per 2000 BTU/HR is required.
Contaminated Combustion Air
Excessive exposure to contaminated combustion air will result in safety and performance related problems. The recommended source of combustion air is outdoor air. However, the use of indoor air in most applications is acceptable if the following guidelines are followed:
1. If the furnace is installed in a confined space, it is recommended that the necessary combustion air
# 45464K003 Page 5
4. The following types of installation may require out­door air for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
5. Exposure to the following substances in the combustion
air supply may also require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine-based swimming pool chemicals
Water softening chemicals
Deicing salts or chemicals
Carbon tetrachloride
Halogen-type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Chlorinated laundry products
Hydrochloric acid
Venting
This furnace has a fan-assisted combustion system designed for vertical venting into a suitable chimney or listed gas vent, and is classified as a Category I furnace as shipped from the factory.
If this furnace is used to replace an existing furnace, it is possible that the existing venting system is not suitable for venting this furnace. Furthermore, the
existing venting system may have to be modified to properly vent any other gas appliance, such as a water heater, that remains connected to it. Carefully read the
Vertical Venting, Sidewall Venting, and Existing Vent Systems sections that follow to determine proper venting
practices for the installation.
vent connector is permissible only in conditioned
space. Use Doublewall Type B vent pipe through
unconditioned space such as attics and crawl spaces. The vent material used should be in accor-
dance with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 (latest edition) or the CSA B149.1, Natural Gas and Propane Installation Codes and local codes. Fan-assisted combustion system Category I furnaces shall not be vented into single wall metal vents.
4. The vent connector must have an upward slope toward the chimney on all horizontal runs of at least 1/4" per foot of horizontal run and should be supported by a sheet metal strap. The vent pipe connection must be secured to the induced draft blower outlet. A single screw is sufficient. On G1N80BR and CG80RB models, a hole in the door hook will allow access to the blower outlet without removing the door hook.
5. All vents passing through floors, ceilings, and walls must be firestopped according to the requirements of the National Fuel Gas Code (see Figure 7).
Installation shall be in accordance with Parts 7 and 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) and/or Section 7 and Appendix B of the CSA B149.1, Natural Gas and Propane Installation Codes (latest edition); local building codes; vent manufacturer instructions; and these instructions.
IMPORT ANT
For 100K, 125K, and 150K BTUH input models, the minimum vent connector diameter is 5". The transition from 4" diameter flue outlet to 5" diameter pipe must be made at the flue outlet.
Vertical Venting
Category I furnaces must be vented vertically or nearly vertically. Common venting and multistory venting are permitted when done in accordance with applicable codes, such as local and national codes.
The venting system should be designed in accordance with
the FAN columns in the venting tables in the latest editions
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes.
Vent Through Ceiling
Vent Through Floor
V ent Through W all
1. Consult local building codes for installation require­ments.
2. The vent connector should be as short as possible with the least number of elbows and angles to do the job.
3. It is recommended a minimum of 26 gauge galvanized flue pipe be used. Use of single-wall vent pipe for the
Figure 7
# 45464K003Page 6
Loading...
+ 14 hidden pages