This manual contains information pertaining to
GHR32−1 through −6 model units. GHR32 series units
are high−efficiency horizontal or down flow gas furnaces
manufactured with Lennox DuralokPlust aluminized and
stainless steel clamshell-type heat exchangers. GHR32Q
units are available in heating input capacities of 50,000 to
120,000 Btuh (14.7 to 35.2 kW) and cooling applications
from 2 through 5 tons (7.0 through 17.6 kW). GHR32V units
are available in heating capacities of 75,000 and 100,000 Btuh
(22.0 and 29.3 kW) and 3 and 5 tons (10.5 and 17.5) for cooling. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is
available for conversion to LPG operation. GHR32−1
through −4 units are equipped with the Lennox SureLight
silicon nitride ignition system. GHR32−5 units are
equipped with the two stage (V models will have the variable speed control) integrated control board. Each
GHR32 unit meets the California Nitrogen Oxides (NOx)
Standards and California Seasonal Efficiency requirements. The gas valve is redundant to assure safety
shut−off as required by A.G.A. and C.G.A.
The heat exchanger, burners and manifold assembly can be
removed for inspection and service. The maintenance section
gives a detailed description on how this is done.
Information contained in this manual is intended for
use by qualified service technicians only. All specifica-
tions are subject to change. Procedures outlined in this
manual are presented as a recommendation only and do
not supersede or replace local or state codes.
LPG/Propane kit59L81 (−1 and −2 models) 11M57 (−3 and later models)
Down-Flow Additive Base32K5232K53
Horizontal Support Frame Kit Ship. Wt. − lbs. (kg.)56J18 18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits60G77 − For 1 1/2 inch (38 mm) venting
Roof
Vent/
Intake
Kits
Twinning Kit15L38 (all models)
Condensate Drain Heat Cable26K68 6 ft. (1.8 m) 26K69 24 ft. (7.3 m) 26K70 50 ft. (15.2 m)
Heat Cable Tape39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Determine from venting tables proper intake and exhaust pipe size and termination kit required.
Cleanable polyurethane frame type filter.
For 3 inch (76 mm) ventingNot Available44J40 (close couple) 81J20 (WTK close couple)
ple)
33K97 − For 2 inch
(51 mm) venting
60L46 − For 3 inch
(76 mm) venting
Not Available
HIGH ALTITUDE
No gas pressure adjustment is needed when operating from 0 to 4500 ft. (0 to 1372m). See table below for correct manifold
pressure and prove switch for altitudes greater than 4500 ft. (1372m).
Horizontal Support Frame Kit Ship. Wt. − lbs. (kg.)56J18 18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits60G77 − For 1 1/2 inch (38 mm) venting33K97 − For 2 inch (51 mm) venting
Roof
Termination
Vent/
Intake
Kits
Condensate Drain Heat Cable26K68 6 ft. (1.8 m) 26K69 24 ft. (7.3 m) 26K70 50 ft. (15.2 m)
Heat Cable Tape39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Determine from venting tables proper intake and exhaust pipe size and termination kit required.
Cleanable polyurethane frame type filter.
Kits
Wall
Termination
Kits
For 2 inch (51 mm) venting15F75
For 3 inch (76 mm) venting44J41
15F74 (ring kit)
For 2 inch (51 mm) venting
30G79 (WTKX close couple w/ extension riser)
For 3 inch (76 mm) venting44J40 (close couple) 81J20 (WTK close couple)
22G44 (close couple)
30G28 (WTK Close Couple)
22G44 (close couple)
Page 4
15F74 (ring kit)
BLOWER PERFORMANCE DATA −1 through −3 V MODELS
p
Jumper
g
g
Setting
ADJUST
Jumper
s
Positions
ADJUST
Jumper
s
Positions
GHR32V3-75 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 875 cfm (415 L/s) for all positions.
GHR32V5−100 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP3−1 Blower Control Factory SettingsADJUST − NORM
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 1100 cfm (520 L/s) for all positions.
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
Heat Speed 3
VSP Jumper Speed Positions
HIGH" Speed (Cool)HEAT" Speed
106
0
500
107
505 113 0 535
0
127
105
0
5
129
600
0
500 112 0 530 940 445 995 470
610
109
515 117 5 555
0
Heat Speed 1
VSP Jumper Speed Positions
BLOWER PERFORMANCE DATA −4 V MODELS
Heat Speed − 3
Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low SpeedHigh Speed
COOL"
Low SpeedHigh Speed
Heat Speed − 2
Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low SpeedHigh Speed
COOL"
Low SpeedHigh Speed
Page 5
128
605
5
109
515 118 0 555
5
133
630
0
GHR32V3−75−5 Blower Motor Performance
Adjust
Jumper
g
Adjust"
Jumper
g
Adj
"
Jumper
Jumper
g
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 875
cfm (415 L/s) for all positions.
Heating
GHR32V5−100/125−5 Blower Motor Performance
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 1100
cfm (520 L/s) for all positions.
Heating
Page 6
GHR32Q−5 PARTS IDENTIFICATION
(Downflow Application Shown)
CONTROL VOLTAGE
CIRCUIT BREAKER
CONTROL TRANSFORMER
CONTROL BOX COVER
DOOR INTERLOCK SWITCH
COLD END HEADER
(COLLECTOR) BOX
COMBUSTION AIR
BLOWER MOUNTING
COMBUSTION
AIR INDUCER
EXHAUST TEE
PATCH PLATE
WITH BARBED
FITTING
BURNER BOX
COVER
FLAME SIGHT
GLASS
FLAME SENSOR
INTAKE AIR
GASKET
BRACKET
FRESH AIR
INTAKE FITTING
IGNITOR
SURELIGHT TWO−STAGE
INTEGRATED CONTROL
CORBELS
BURNER BOX
TOP
BURNER BOX
ASSEMBLY
ORIFICE
GAS VALVE
AND MANIFOLD
FIGURE 1
SUPPLY AIR
BLOWER
TOP CAP
CONTROL
BOX
GASKET
PRIMARY LIMIT
AUTO−RESET
(ALTERNATE STYLES)
BURNER BOX
GASKET
FLAME ROLL−OUT SWITCH
(MANUAL RESET)
SECONDARY LIMIT
AUTO−RESET
(Located on Backside
of Blower Wrapper)
CABINET
COMBUSTION AIR
PROVING (PRES-
SURE) SWITCH
HOT END HEADER
(COLLECTOR) BOX
CONDENSER
COIL
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
CONDENSATE
TRAP
BACK FILTER
CLIP
FLUE
COLLAR
CONDENSATE
COLLAR
TM
Page 7
I−UNIT COMPONENTS
GHR32 unit components are shown in figure 1. The combustion air blower, gas valve and burners can be accessed
by removing the burner access panel. The blower and control box can be accessed by removing the blower access
door.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
WARNING
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch
A−Make-Up Box (Figure 2)
WARNING
Unit must be grounded in accordance with national
and local codes. Electric Shock Hazaed.
Can cause injury or death.
A field make−up box (see figure 2) is provided for line voltage
wiring. Line voltage wiring to unit is done through the J96 jack
from the field make−up box to plug P96 from the control box.
The box may be installed inside or outside the unit (see figures
3 and 4) and may be installed on the unit left or right side.
MAKE-UP BOX
POWER ENTRY KNOCKOUT
BOX
UNIT
GROUND
JACK J96
Box may be installed inside or outside unit.
FIGURE 2
120V LINE VOLTAGE
PIGTAIL CONNECTIONS
COVER
J96
BUSHING
P96
FIGURE 3
EXTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
BUSHING
J96
(Shown with
accessory
wire connected)
P96
FIGURE 4
An accessory (brown) output wire is provided with the makeup box. The wire provides a 120V connection for optional accessories such as electronic air cleaner or humidifier. If
used, the wire is field installed in J96 jack plug by inserting the
pin of the brown wire into the open socket of the jack. See figure 5. 120V accessories rated up to 4 amps total may be connected to this wire. The neutral
leg of the accessory is connected to the neutral white wire
in the make-up box. The acces-
INSTALLING BROWN
ACCESSORY WIRE TO J96
WHITE
NEUTRAL
BROWN
sory terminal is energized
whenever the indoor blower is
in operation.
BLACK
J96
FIGURE 5
Page 8
B−Control Box (Figure 6)
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CIRCUIT BREAKER CB8
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s
electronic controls. Precautions will help to avoid
control exposure to electrostatic discharge by
putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all
tools on an unpainted unit surface, such as the
gas valve or blower deck, before performing any
service procedure.
GHR32−1 through −4 CONTROL BOX
TWO−STAGE
CONTROL
CIRCUIT
BREAKER
TRANSFORMER
FIGURE 6
Unit transformer (T1), circuit breaker (CB8), SureLight
control (A92), VSP−2 control (A24) and Two−stage control
(A86) are located in the control box. In addition, a door interlock switch (S51) is located in the control box. Jackplugs
and a snap-off" terminal strip allow the control box to be
easily removed for blower service.
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage 24 volt section of the unit. Transformers on
all models are rated 40VA with a 120V primary and a 24V
secondary.
2. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated 3 amps at 32V. If the current exceeds this limit the breaker will trip and all unit operation will
shut down. The breaker can be manually reset by pressing the
button on the face (figure 7).
VSP−2
CONTROL
(v models only)
SURELIGHT
CONTROL
DOOR INTERLOCK
SWITCH
PRESS TO RESET
FIGURE 7
3.Door Interlock Switch (S51)
A door interlock switch rated 14 amps at 125VAC is located
on the control box. The switch is wired in series with line
voltage. When the blower door is removed the unit will shut
down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
4. SureLight Ignition System A92
All GHR32−1 through −4 units are equipped with the Lennox SureLight ignition system. The system consists of ignitor (figure 8) and ignition control board (figure 9 and
table 3 ). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The SureLight
integrated board controls all major furnace operations.
Table 1 and 2 show jack plug terminal designations. shows
control board terminations. The board also features two
LED lights for troubleshooting and two accessory terminals rated at (1) one amp. See table 4 for troubleshooting
diagnostic codes. Units equipped with the SureLight
board can be used with either electronic or electro−mechanical thermostats without modification. The SureLight
ignitor is made of durable silicon nitride. Ignitor longevity
is also enhanced by voltage ramping by the control board.
The board finds the lowest ignitor temperature which will
successfully light the burner, thus increasing the life of the
ignitor.
NOTE − Do not remove blower access panel to read
Surelight LED lights. A sight glass is provided on the
access panel for viewing.
Page 9
13/32’
SURELIGHT IGNITOR
MEASUREMENT IS TO I.D.
5/8"
OF RETENTION RING
FRONT VIEW
TABLE 1
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN #FUNCTION
1Ignitor
2
3
4
Combustion Air Blower Line Voltage
5
6
Combustion Air Blower Neutral
Not Used
Ignitor Neutral
Not Used
TABLE 2
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
5/16"
TOP VIEW
FIGURE 8
SURELIGHT INTEGRATED CONTROL BOARD
GHR32−1 through −4 units
PIN #FUNCTION
1Primary Limit In
2
3
4
5
6
Pressure Switch and Primary Limit Out
7
8
9
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Not Used
Roll Out Switch In
Ground
TABLE 3
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
TERMINAL DESIGNATIONS
Blower − Cooling Speed (Line Volt)
Blower − Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
FIGURE 9
Page 10
TABLE 4
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1LED #2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASHON
OFFSLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASHOFF
ONSLOW FLASH
ON
ON
OFF
FAST FLASHSLOW FLASH
SLOW FLASHFAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Limit must close within 3 minutes or board goes
Watchguard pressure switch − 5 minutes. Pressure switch open or has opened 5
times during a single call for heat; OR: Blocked inlet/exhaust vent; OR: Conden-
sate line blocked; OR: Pressure switch closed prior to activation of combustion
Watchguard 60 minute delay − burners fail to ignite.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .61 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
into one hour limit Watchguard.
air blower.
Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.21 microAmps
a−Electronic Ignition Figures 12 and 13
On a call for heat the SureLight control monitors the combustion air blower pressure switch. The control will not begin the heating cycle if the pressure switch is closed (by−
passed). Once the pressure switch is determined to be
open, the combustion air blower is energized. When the
differential in the pressure switch is great enough, the pressure switch closes and a 15−second pre−purge begins. If
the pressure switch is not proven within 2−1/2 minutes, the
control goes into Watchguard−Pressure Switch mode for a
5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. Units with control 97L48: ignitor stays energized during the trial or until flame is
sensed. Units with control 56L83: ignitor stays energized
for the first second of the 4−second trial. If ignition is not
The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
b−Fan Time Control Q Models Only
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 10.
proved during the 4−second period, the control (97L48 or
56L83) will try four more times with an inter purge and
warm−up time between trials of 35 seconds. After a total of
five trials for ignition (including the initial trial), the control
FAN-OFF TIME ADJUSTMENT
60sec.90sec.120sec.180sec.
goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence
again.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 10
Page 11
c−Flame Sensor
ЙЙЙЙЙЙЙЙЙ
A flame sensor is located on the left side of the burner support. See figure 11. The sensor is mounted on a bracket in
the burner support and the tip protrudes into the flame envelope of the left−most burner. The sensor is fastened to
burner supports and can be removed for service without removing any part of the burners. During operation, flame is
sensed by current passed through the flame and sensing
electrode. The SureLight control allows the gas valve to remain open as long as flame signal is sensed.
SENSOR
3/8"
IGNITOR
FIGURE 11
NOTE − The GHR32 furnace contains electronic components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
5. Two−Stage Control (A86)
All GHR32−1 through −4 units are equipped with a two−
stage control board. Two different boards have been used.
Boards 43K9001 and 29M9201 (figure 14) are identical,
except the 9 pin connector on 43K9001 is replaced by two
relays with quick connect terminals on board 29M9201.
The two−stage board acts as a go between from the indoor
thermostat to the SureLight ignition board. The board can
be utilized in three modes: with a SINGLE−STAGE thermostat, a TWO−STAGE thermostat or with a second−stage
(high fire) delay called W2 TIMED. The two−stage board is
equipped with a jumper (see figure 14) which changes operating modes and a jumper which adjusts second−stage
heat delay during W2 TIMED mode.
NOTE−The mode of operation jumper on the two−stage
control board is factory set in the TWO−STAGE" position.
While in the single−stage thermostat mode (one−stage
jumper setting), the unit will always operate on second−
stage heat. The combustion air blower (B6) will operate on
high speed and indoor blower (B3) will operate on heating
speed. While in the two−stage thermostat mode the unit will
operate on first−stage heat (low fire). The combustion air
blower (B6) and indoor blower will operate on low speed.
The unit will switch to second−stage heat (high fire) on call
from the indoor thermostat W2. While in the W2 TIMED
mode (factory setting 8 minutes) the unit will fire on first−
stage heat (low fire) with the combustion air blower (B6)
and indoor blower (B3) operating on low speed. After a set
time delay the unit switches to second−stage heat (high
fire). The combustion air blower and indoor blower also
switch to second−stage heat mode.
SureLight Control Ignition Sequence Board 56L8301
15
ON
OFF
DEMAND
CAB
IGNITOR
GAS VALVE
INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −PurgeIgnitor WarmupTrial for
341
35
Ignition
38
Blower On"
Delay
FIGURE 12
SureLight Control Ignition Sequence Board 97L4801
15
ON
OFF
DEMAND
CAB
IGNITOR
GAS VALVE
INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −PurgeIgnitor Warmup
341
Trial for
Ignition
38
Blower On"
Delay
FIGURE 13
5 SEC80
Post
Purge
5 SEC80
Post
Purge
Page 12
MODE OF
OPERATION
JUMPER
TWO−STAGE CONTROL BOARD
G32(V) −1 through −4 units
W2 TIMED
DELAY JUMPER
6.VSP2−1 Blower Control Board (A24)
−1 through −3 V Models only
GHR32V−1 through −3 units are equipped with a variable
speed motor that is capable of maintaining a specified CFM
throughout the external static range. The unit uses the
VSP2−1 variable speed control board, located in the blower compartment, which controls the blower speed and
provides diagnostic LEDs. The control has a non−adjustable, factory preset ON" fan timing delay and an adjustable
OFF" fan timing delay (see figure 17).
The VSP2−1 also senses limit trip condition and turns on the
blower. The GHR32 primary limit switch is located in the
middle of the vestibule wall and the secondary limit switch is
located int ehblower compartment. When excess heat is
sensed in the heat exchanger, or blower compartment,
the respective switch will open and interrupt the current to
the gas valve, while at the same time the VSP2−1 energizes
the blower on heating speed. The limit automatically resets
when the unit temperature returns to normal and the blower is
de−energized.
FIGURE 14
HIGH SPEED
SELECTOR PINS
(COOLING ONLY)
LOW SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG
(BOARD TO VARIOUS
POINTS IN FURNACE)
Diagnostic LEDs located on the VSP2−1 control board are provided to aid in identifying the unit’s mode of operation. Certain
scenarios will arise depending on the jumper positions. Refer
to figure 15 for identification.
VSP2−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP
2
HIGHLOWADJUSTHEAT
270
1
2
3
4
DS4
CFM
210
90
150
JP
1
1
1
2
3
4
HTG.
BLOWER
12
1
2
3
4
HEAT
DS2
TEST
−
+
NORM
DS3
ON/OFF
HI/LOW
DS1
JP46
13 PIN PLUG
(BOARD TO MOTOR)
HEATING SPEED
SELECTOR PINS
See table 5 for VSP2
factory settings
OPERATIONAL
SELECTOR PINS
(Affects both heating and
cooling modes)
DIAGNOSTIC
DS LEDS
FAN OFF"
TIMING PINS
FIGURE 15
Page 13
IMPORTANT
24 VAC half wave rectified (DC pulse), when measured with a meter, may appear as a lower or higher
voltage depending on the make of the meter. Rather
than attempting to measure the output voltage of the
VSP2 board, see GHR32 BLOWER & VSP2 BLOWER
CONTROL BOARD TROUBLESHOOTING FLOW
CHART in the TROUBLESHOOTING section of this
manual.
VSP2−1 BLOWER CONTROL BOARD (A24)
1
J46
HIGHLOWADJUSTHEAT
1
2
3
4
HTG.
BLOWER
1
2
3
4
HEAT
DS3
TEST
−
+
NORM
HI/LOW
1
2
3
4
DS4
Diagnostic LED Lights
a − DS3 ON/OFF"
ON/OFF−DS3 indicates there is a demand for the blower mo-
tor to run. When the ON/OFF LED−DS3 is lit, a demand is being sent to the motor. In heating mode only, there is a 45 second fan ON" delay in energizing ON/OFF LED−DS3.
The light will not go off until adjustable fan OFF" delay
has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1 &
HEAT LED−DS2 are off, the motor will operate in low
speed.
b − DS2 HEAT"
If HEAT LED−DS2 is on, the blower is running in the heat
speed according to the HEAT" jumper setting. The HEAT
LED−DS2 comes on instantaneous and switches off when
the call for heat is satisfied.
NOTE−When the blower is in OFF" delay mode, the motor runs at low speed, therefore the HEAT LED−DS2 is off. It
switches off when the call for heat is satisfied.
c − DS1 HI/LOW"
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control.
PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output.
PIN 13 - 24V - Input 24 VAC power for the VSP2-1.
PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 1 - Heat - Heat speed input signal to the ICM2 motor.
PIN 4 - High Tap - High Speed programming input.
PIN 5 - Low Tap - Low speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 8 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common.
PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
DS1
270
CFM
210
90
150
HIGH/LOW LED−DS1 indicates whether the blower is operating in high or low speed. When the light is off, the blower is running in low speed according to the LOW" jumper
setting. When HIGH/LOW LED−DS1 is on, the blower is op-
erating in high speed according to the HIGH" jumper setting.
d − DS4 CFM"
CFM LED−DS4 indicates the CFM the unit is operating,
according to the jumper settings. The light flashes once
for approximately every 100 CFM. For example, if the unit
is operating at 1000 CFM, CFM LED−DS4 will flash 10
times. If the CFM is 2050, CFM LED−DS4 will flash 20 full
times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes
place when the control is communicating with the motor between cycles. This is normal operation.
The appropriate speed according to application and CFM
need is selected by moving jumper pins.
Page 14
VOLTAGES INTO VSP2−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0 volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage) if CCB
is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP2−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx.
34 volts
0 volts
Voltage across J46 pins 8 and 9 to 3, is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pins 8 and 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
24VAC Half-Rectified (DC Pulse)
a voltage of 0−25VDC should be present.
@ 60Hz.
FIGURE 16
NOTE−On Harmony II zoning applications in the heating
mode, the highest speed obtainable is the same as the highest
cooling speed selection. Also, the heating speed (heat jumper
position) is only used when the primary limit has been tripped.
In non−zoning applications, refer to the section on the VSP2−1
control.
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
not operable. Notice in the GHR32V5−100 table, that the
normal adjustment setting for heat speed position #3 is
2150 CFM (1015L/s). After the adjustment setting has been
determined, c hose th e re main ing speed jumper settings
from those offered in the table.
The TEST pin is available to bypass the VSP2−1 control and
run the motor at approximately 70% to test that the moto r i s
operational. This is beneficial primarily in troubleshooting. G must be energized for motor to run.
b−HEATING BLOWER"
IMPORTANT
Before changing jumper setting, make sure the
motor has completely stopped. Any jumper setting change will not take place while the motor
is running.
To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and conditions associated with each one. Refer to figure 15 for identification.
After the CFM for each application has been determined, the
jumper settings must be adjusted to reflect those given in
the tables in the blower performance section. Using the tables,
determine which row of CFM volumes most closely
matches the desired CFM. Once a specific row has been
chosen (NORMAL or −), CFM volumes from other rows
cannot be used. Below are the descriptions of each of the
jumper selections.
Refer to table 5 for factory settings. Refer to the blower performance tables for the approximate air volume for each setting.
VSP2−1 FACTORY SETTINGS
MODELHIGHLOWADJUSTHEAT
GHR32V−75−
1, −2, −3 units
GHR32V−100
−1, −2, −3
units
a−ADJUST"
The ADJUST pins allow the motor to run at normal speed or
approximately 15% lower than normal speed. The blower
performance tables give two rows (NORMAL and −) with
their respective CFM volumes. The + adjustment setting i s
TABLE 5
43NORM2
42NORM1
For GHRV32 units, place the HEATING BLOWER jumper
across the second and third pins (position #2).
When W1 is energized, the LOW jumper selections are activated. The HEAT jumper selections are activated when
W2 is energized.
NOTE−In Harmony II zoning applications, HEATING
BLOWER jumper must be in position #2.
c−HEAT"
The HEAT jumper is used to set the blower speed to ob-
tain the required CFM as outlined in HEAT SPEED in the
blower performance tables.
The HEAT jumper selections are activated with a call for
second-stage heating (W2).
d−HIGH"
The HIGH jumper is used to determine the CFM during
cooling speed. These jumper selections are activated
when G and DS terminals are energized.
e−LOW"
The LOW jumper is used to determine CFM during low
speed cooling. These jumper selections are activated
when G is energized. The LOW jumper may also be used for
low speed heating. See the HEAT" section for details.
f−FAN OFF"
Fan OFF" timings (time that the blower operates after the
heat demand has been satisfied) are determined by the arrangement of a jumper on the VSP2−1 board. See figure
17. To adjust fan OFF" timings, gently disconnect the
jumper and reposition it across pins corresponding with the
new timing. Fan OFF" time is adjustable from 90 to 330
seconds. The control has a non−adjustable, factory preset
on" fan timing (45 seconds).
WARNING − MAKE SURE TO DISCONNECT POWER
BEFORE CHANGING FAN OFF" TIMINGS.
Page 15
FAN-OFF TIME ADJUSTMENT
NOTEIf fan OFF" time is too low, residual heat in heat
exchanger may cause primary limit S10 to trip resulting
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from VSP2−1 and select
one of the other pin combinations to
achieve the desired time.
in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Table 6 outlines the operation of the variable speed motor
in relation to specific modes of operation. Some informa-
270
15090
210
Leave jumper off to achieve
330 second fan−off timing.
TIMING PINS (seconds)
Fan-off timing is factory
set at 90 seconds
tion has been repeated from the previous section to provide
an example. Refer to each diagnostic LED or jumper settings
section for more information.
FIGURE 17
TABLE 6
VSP2−1 GHR32−1 through −3 units OPERATION
HEATING MODECOOLING MODE
UNITS WITH
SINGLE−STAGE HEATING
NON−ZONED
APPLICATIONS
Using a single−stage thermostat with
one−stage" heating, the HEAT LED−
DS2 is lit when the thermostat calls for
heat. The ON/OFF LED−DS3 is lit after
110 seconds (65 seconds pre−purge
and 45 seconds fan ON" time) from
the time a call for heat is made. This indicates the blower is operating in heating speed.
Using a single−stage thermostat with
W2 TIMED," and W1 calling, the ON/
OFF LED−DS3 is lit to indicate the
blower is operating on low speed.
When the HEAT LED−DS2 is lit, the
blower is operating in heating speed,
and second−stage (W2) heating is calling.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the zoning system to the terminal strip’s DS
terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the
blower is operating.
NOTE−In Harmony II zoning applications, HTG. BLOWER jumper must be
in position #2.
NOTE: For zone applications with Harmony, remove the wire from the pin #3 of the J73 terminal on the VSP control board, insulate the
end, and secure it to prevent from shorting.
Using a two−stage thermostat with
first−stage (W1) calling, the ON/OFF
LED−DS3 is lit to indicate the blower is
operating in low speed.
When the ON/OFF LED−DS3 and
HEAT LED−DS2 are lit, the blower is
operating in heating speed and second−stage (W2) heating is calling.
HEAT LED−DS2 is lit with a call for heat
from the thermostat. ON/OFF LED−
DS3 is lit after 110 seconds from the
time a call for heat is made.
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the zoning system to the terminal strip’s DS
terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the
blower is operating.
NOTE−In Harmony II zoning applications, HTG. BLOWER jumper must be
in position #2.
UNITS WITH
TWO−STAGE HEATING
NON−ZONED
APPLICATIONS
HARMONY ZONED
APPLICATIONS
UNITS WITH SINGLE−
SPEED COMPRESSOR
NON−ZONED
APPLICATIONS
The terminals DS and Y must be
jumpered together. With a call for
cooling, terminals G, Y and DS on the
unit control board are energized from
the thermostat. HI/LOW LED−DS1
and ON/OFF LED−DS3 are lit to indicate the blower is operating on high
speed.
NOTEY and DS are factory jumpered for single−stage cooling, non−
zoned applications.
NOTEFor low speed during single−
stage cooling remove jumper from Y
to DS.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the
zoning system to the terminal strip’s
DS terminal. HI/LOW LED−DS1 andON/OFF LED−DS3 are lit to indicate
the blower is operating.
UNITS WITH TWO−SPEED
COMPRESSOR
NON−ZONED
APPLICATIONS
The ON/OFF LED−DS3 is lit to indicate
the blower is operating in first stage
cooling. This LED is energized on
when a 24VAC thermostat demand is
supplied to the control (terminal G" on
the control board terminal strip).
In second stage, the ON/OFF LED−
DS3 and HI/LOW LED−DS1 are lit to
indicate the blower is operating on
high speed (24VAC is supplied to the
unit terminal strip Y2 from Y2 on the
thermostat).
NOTE Jumper must be moved from
Y1 to Y2 In two−speed, non−zoned applications.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the zoning system to the terminal strip’s DS
terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the
blower is operating.
Page 16
7.VSP3−1 Blower Control Board (A24)
GHR32V−4 Units
GHR32V−4 units are equipped with a variable speed motor
that is capable of maintaining a specified CFM throughout
the external static range. The unit uses the VSP3−1 variable speed control board, located in the blower compartment, which controls the blower speed and provides
diagnostic LEDs. The control has both a non−adjustable,
factory preset ON" fan timing delay and an adjustable OFF"
fan timing delay (see figure 17).
VSP3−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP2
DELAY PROFILE
SELECTOR PINS
(COOLING ONLY)
DELAYCOOLADJUSTHEAT
1
2
3
4
The VSP3−1 also senses limit trip condition and turns on the
blower. The GHR32V limit switch is located in the middle of the
vestibule wall. When excess heat is sensed in the hea t exchanger, the limit switch will open and interrupt the current
to the gas valve, while at the same time the VSP3−1 energizes
the blower on heating speed. The limit automatically resets
when the unit temperature returns to normal and the blower is
de−energized.
Diagnostic LEDs located on the VSP3−1 control board are provided to aid in identifying the unit’s mode of operation. Certain
scenarios will arise depending on the jumper positions. Refer
to figure 18 for identification.
JP46
13 PIN PLUG
(BOARD TO MOTOR)
1
2
3
4
TEST
−
+
NORM
1
2
3
4
HEATING SPEED
SELECTOR PINS
See table 7 for VSP3−1
factory settings
COOL SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG
(BOARD TO VARIOUS
POINTS IN FURNACE)
JP1
1
HTG.
BLOWER
12
HEAT
DS2
ON/OFF
FIGURE 18
DS3
HI/LOW
DS1
270
210
150
DS4
CFM
OPERATIONAL
SELECTOR PINS
(Affects both heating
and cooling modes)
DIAGNOSTIC
DS LEDS
90
FAN OFF"
TIMING PINS
Page 17
VSP3−1 BLOWER CONTROL BOARD (A24)
1
J46
DELAYCOOLADJUSTHEAT
1
2
3
4
HTG.
BLOWER
1
2
3
4
HEAT
DS3
TEST
−
+
NORM
HI/LOW
1
2
3
4
DS4
IMPORTANT
24 VAC half wave rectified (DC pulse), when
measured with a meter, may appear as a lower
or higher voltage depending on the make of the
meter. Rather than attempting to measure the
output voltage of A24, see GHR32V BLOWER &
VSP3 BLOWER CONTROL BOARD TROUBLESHOOTING FLOW CHART in the TROUBLESHOOTING section of this manual.
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control.
PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output.
PIN 13 - 24V - Input 24 VAC power for the VSP2-1.
PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 4 - Delay Tap - Delay profile programming input.
PIN 5 - Cooling blower speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor with CCB1 and
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common.
PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
PIN 1 - Not Used.
PIN 8 - NOT USED
HARMONY only
DS1
270
CFM
210
90
150
Diagnostic LED Lights
DS3 ON/OFF
ON/OFF−DS3 indicates there is a demand for the blower
motor to run. When the ON/OFF LED−DS3 is lit, a demand
is being sent to the motor. In heating mode only, there is a
45−second fan ON" delay in energizing ON/OFF LED−
DS3. Light will not go off until adjustable fan OFF" delay
has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1
& HEAT LED−DS2 are off, the motor will operate in low
speed (heating).
DS2 HEAT
If HEAT LED−DS2 is on, the blower is running in second−
stage heat speed according to the HEAT" jumper setting.
In heating mode only, there is a 45 second delay in energizing HEAT LED−DS2. Light will not go off until adjustable fan
OFF" delay has expired.
DS1 HI/LOW
HIGH/LOW LED−DS1 indicates the blower is operating in
the cooling mode.
DS4 CFM
CFM LED−DS4 indicates the CFM the blower is providing,
according to the jumper settings.
VOLTAGES INTO VSP3−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0
volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage)
if CCB is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP3−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx.
34 volts
0
volts
Voltage across J46 pin 9 to 3 is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pin 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
a voltage of 0−25VDC should be present.
24VAC Half-Rectified (DC
FIGURE 19
Pulse)
@ 60Hz.
Page 18
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
IMPORTANT
Before changing jumper setting, make sure the
motor has completely stopped. Any jumper setting change will not take place while the motor
is running.
To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and conditions associated with each one. Refer to figure 18 for identification.
After the CFM for each application has been determined, the
jumper settings must be adjusted to reflect those given in
the blower performance tables. Using the tables, determine
which row of CFM volumes most closely matches the
desired CFM. Once a specific row has been chosen
(NORMAL or −), CFM volumes from other rows cannot be
used. Below are the descriptions of each of the jumper
selections.
Refer to table 7 for factory settings.
TABLE 7
VSP FACTORY SETTINGS FOR GHR32V−4 UNITS
MODEL DELAYCOOLADJUST HEAT
GHR32V3−7544NORM3
GHR32V5−10044NORM2
NOTE − In Harmony II zoning applications in the heating mode,
the highest cooling speed selected is the highest blower speed
obtainable. Also, the fan−only speed is used when the primary limit has been tripped. In non−zoning applications, refer to the section
on the VSP3−1 control.
ADJUST
The ADJUST pins allow the motor to run at normal speed
or approximately 15% lower than normal speed. The blower performance tables two rows (NORMAL and −) with their
respective CFM volumes. The + adjustment setting is not
operable. Notice that the normal adjustment setting for
heat speed position #3 is 2150 CFM (1015 L/s) . After the
adjustment setting has been determined, choose the remainder speed jumper settings from those in the table.
The TEST pin is available to bypass the VSP3−1 control and
run the motor at approximately 70% to test that the motor is
operational. This is beneficial primarily in troubleshooting. G
must be energized for motor to run.
HTG. BLOWER
For GHR32V−4 units only, place the HTG. BLOWER jumper across the second and third pins (position #2).
NOTE − In Harmony II zoning applications, HTG. BLOWER
jumper must be in position #2.
HEAT
The HEAT jumper is used to set the blower speed to obtain
the required CFM as outlined in HEAT SPEED section of
the blower performance tables. The HEAT jumper selec-
tions are activated with a call for first−stage heating (W1)
and second−stage heating (W2).
DELAY
The DELAY jumper is used to set the specific motor fan
mode of operation during cooling. Depending on the application, one of four fan options may be chosen by moving
the jumper to the appropriate set of pins.
Options 1, 2, 3, or 4 will have an increased dehumidification
effect on the system. Option 1 will have the least effect and
option 4 will have the greatest effect.
#1 PIN JUMPERED
A − Motor runs at 100% until demand is satisfied.
B − Once demand is met, motor ramps down to off.
AB
100% CFM
COOLING
DEMAND
OFFOFF
#2 PIN JUMPERED
A − Motor runs at 82% for approximately 7−1/2 minutes.
B − If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
C − Once demand is met, motor ramps down to off.
C
OFF
OFF
A
7 1/2 MIN
82%CFM
B
100% CFM
COOLING DEMAND
#3 PIN JUMPERED
A − Motor runs at 50% for 1/2 minute.
B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor ramps down to off.
CD
100% CFM
OFF
OFF
A
1/2 MIN
50% CFM
B
7 1/2 MIN
82% CFM
COOLING DEMAND
Page 19
#4 PIN JUMPERED
A − Motor runs at 50% for 1/2 minute.
B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor runs at 50% for 1/2 min-
ute.
E − Motor ramps down to off.
CD
100%
CFM
1/2 MIN
50% CFM
E
OFF
OFF
A
1/2 MIN
50% CFM
B
7 1/2 MIN
82% CFM
COOLING DEMAND
COOL
The cool jumper is used to set the blower speed to obtain
the required CFM as outlined in the blower performance
tables.
VSP Operation
Table 8 outlines the operation of the variable speed motor
in relation to specific modes of operation. See table 9 for
GHR32V with CCB1 and a two speed outdoor unit. Some
information has been repeated from the previous section to
provide an example. Refer to each diagnostic LED or jumper settings section for more information.
Heating ModeCooling Mode
Units With
Single−Stage Heating
Non−Zoned Applications
Using a single−stage thermostat
with "one−stage" heating, the HEAT
LED−DS2 is lit when the thermostat
calls for heat. The ON/OFF LED−
DS3 is lit after 110 seconds (65 seconds prepurge and 45 seconds fan
"ON" time) from the time a call for
heat is made. This indicates the
blower is operating in high speed
heat.
Using a single−stage thermostat
with "W2 TIMED" and W1 calling,
the ON/OFF LED−DS3 is lit to indicate the blower is operating on low
speed heat.
When HEAT LED−DS2 is lit, the
blower is operating in high speed
heat and second−stage (W2) is calling.
Harmony Zoned Applications
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal
strip’s DS terminal. HI/LOW LED−
DS1 and ON/OFF LED−DS3 are lit
to indicate the blower is operating.
Note − In Harmony II zoning applications, HTG BLOWER jumper
must be in position #2.
GHR32V−4 Units with VSP3−1
TABLE 8
Units With
Two−Stage Heating
Non−Zoned Applications
Using a two−stage thermostat with
first−stage (W1) calling, the ON/OFF LED−DS3 is lit to indicate the
blower is operating in low speed
heat.
When the ON/OFF LED−DS3 andHEAT LED−DS2 are lit, the blower
is operating in high speed heat and
second−stage (W2) is calling.
HEAT LED−DS2 is lit with a call for
heat from the thermostat. ON/OFF
LED−DS3 is after 110 seconds from
the time a call for heat is made.
Harmony Zoned Application
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal
strip’s DS terminal. HI/LOW LED−
DS1 and ON/OFF LED−DS3 are lit
to indicate the blower is operating.
Note − In Harmony II zoning applications, HTG BLOWER jumper must
be in position #2.
Units With
Single−speed Compressor
Non−Zoned Applications
Y1−DS and Y1−Y2 must be jumpered together. With a call for cooling, G, Y1, Y2 and DS on the unit
control board are energized from
the thermostat. HI/LOW LED−DS1
and ON/OFF LED−DS3 are lit to indicate a call for cooling.
Note − Y1 to DS and Y1 to Y2 are
factory jumpered for single−stage
cooling, non−zoned applications.
Harmony Zoned Application
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal strip’s DS terminal. HI/LOW
LED−DS1 and ON/OFF LED−DS3
are lit to indicate the blower is operating.
Units With
Two−speed Compressor
Non−Zoned Applications
Y1−DS must be jumpered together.
With a call for single−stage cooling,
G, Y1, and DS on the unit control
board are energized from the Thermostat. With a call for second−stage
cooling, G, Y1, Y2, and DS on the
unit control board are energized
from the thermostat. In both cases,
HI/LOW LED−DS1 and ON/OFF
LED−DS3 are lit to indicate a call for
cooling.
Note − Jumper Y1−Y2 must be removed for units with two−speed
compressor.
Harmony Zoned Application
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal
strip’s DS terminal. HI/LOW LED−
DS1 and ON/OFF LED−DS3 are lit
to indicate the blower is operating.
NOTE − For zone applications with Harmony, remove the wire from pin #2 and pin #13 of the J49 terminal at the motor and the wire
from pin #3 of the J73 terminal on the VSP control board, insulate the ends and secure to prevent shorting.
Page 20
TABLE 9
p
Normal operation
blower speed follow thermostat
removal during 1st
ifi
ill i
,
When humidity demand is satisfied
satisfied during
th
gpp
Call f
idit
g
Call for 1st stage
Call for 2nd stage
Reduced blower speed (dehumidifi-
mostat demand), slide switch is
GHR32V−4 UNITS WITH CCB1 & TWO−SPEED OUTDOOR UNIT OPERATING SEQUENCE
Operating SequenceSystem DemandSystem Response
System
Condition
Step
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
***Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Call for humidity
removal during 1st
stage thermostat
demand
Significant increase
in humidity during
thermostat demand.
Humidity demand
satisfied during
thermostat demand.
or hum
removal during 2nd
stage thermostat
demand
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase
in humidity
Humidity demand
satisfied between
thermostat demands
(unit off cycle).
y
1Y1Acceptable (None)Low
2Y2Acceptable (None)HighHIGH COOL
1Y1Acceptable (None)Low
2Y1
Demand
3
satisfied
4Y1Slightly over setpoint (1)High
1Y1Acceptable (None)Low
2Y1
1Y1Over SetpointHigh
2Y1
3NoneAcceptable (None)OffOff
4Y1Acceptable (None)Low
1Y2Acceptable (None)HighHIGH COOL
2Y2
3Y2Acceptable (None)HighHIGH COOL
1NoneSlightly over setpoint (1)OffOffDehumidification mode (high speed
2Y1Slightly over setpoint (1)Low
1NoneSlightly over setpoint (1)OffOff
2Y2Slightly over setpoint (1)High
1None
2Y1 or Y2
1NoneOver setpoint (1 or more)OffOff
2Y1 or Y2
Change to slightly
over setpoint (1)
Slightly over setpoint (1)OffOff
Change to significantly
over setpoint (2 or more)
Change to Acceptable
(None)
Change to slightly
over setpoint (1)
Significantly over setpoint
(2 or more)
Significantly over
setpoint (2 or more
Change to
acceptable (None)
Low
High
HighHIGH COOL
High
OffOff
High
HighHIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
Compressor demand and indoor
blower s
Dehumidification mode begins with
next thermostat demand, after initial
thermostat demand is satisfied.
If humidity increases significantly
over setpoint, or if slide switch is
moved sign
ately go into dehumidification mode
(in presence of thermostat demand).
When humidity demand is satisfied
blower immediately shifts to the
HIGH COOL CFM in order to hasten
e end of the cycle. Unit can only
shift out of high speed compressor
operation at beginning of next cycle.
Blower immediately changes speed
in response to thermostat demand.
compressor) begins with next ther-
mostat demand after initial demand is
Reduced blower speed (dehumidifi-
cation speed) begins immediately
If humidity increases significantly
over setpoint, or if slide switch is
moved, unit immediately goes into
dehumidification mode (in presence
While unit is not operating (no ther-
mostat demand), slide switch is
moved down and back up. Blower
and compressor operate at high
speed until next thermostat demand.
eed follow thermostat
demand
cantly, u nit w
satisfied.
with thermostat demand
of thermostat demand).
mmedi-
,
Note − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first thermostat heating demand.
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed
indefinitely. To reset, move humidity slide switch all the way down then back up to desired setpoint (with unit running)
** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5.
***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compressor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 21
8.Two Stage Integrated Control (A92)
GHR32Q−5 Units
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
All GHR32Q units are equipped with the Lennox two−
stage integrated SureLight control board. The system
consists of a ignition control board (figure 20 with control
terminal designations in tables 12, 13 and 14) and ignitor
(figure 8). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The board controls all major furnace operations. The board features two
LED lights, DS1 and DS2 for troubleshooting. The board
also has two accessory terminals rated at (1) one amp
each. See table 15 for troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heat cycle, SureLight control monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heating cycle
if the first stage prove switch is closed (by−passed). Likewise the control will not begin the second stage heating
cycle if the second stage prove switch is closed and will allow first stage heat only. However if the second stage prove
switch closes during the first stage pre−purge, the control
will still respond to second stage heat. Once the first stage
prove switch is determined to be open, the combustion air
inducer is energized on low (first stage) heat speed. When
the differential in the prove switch is great enough, the
prove switch closes and a 15−second pre−purge begins. If
the switch is not proven within 2−1/2 minutes, the control
goes into Watchguard−Pressure Switch mode for a 5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4−second period, the control will try four more times with
an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure
mode. After a 60−minute reset period, the control will begin
the ignition sequence again.
The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE
thermostat or TWO−STAGE thermostat. The thermostat
selection jumper E20, located just below dip switches 1
through 4 (figure 20), must be positioned for the particular
application. The jumper is factory set on TWO" for use
with a two−stage thermostat with two stage heat. Re−position jumper to SINGLE" for use with a single stage thermostat with two stage heat.
While in the single−stage thermostat mode (single jumper
setting), the burners will always fire on first−stage heat. The
combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a field selectable 10 or 15 minute delay (dip switch 3), the unit will
switch to second stage heat. While in the two−stage thermostat mode (two jumper setting) the burners will fire on
first−stage heat. The combustion air inducer will operate on
low speed and indoor blower will operate on low heat
speed. The unit will switch to second−stage heat on call
from the indoor thermostat. If there is a simultaneous call
for W1 and W2 (first and second stage heat) the unit will fire
on first stage heat and will switch to second stage heat after
30 seconds of operation. See Sequence of Operation flow
charts in the back of this manual for more detail.
Dip Switch Settings
Dip Switches 1 and 2 − Heating Fan off Delay − The fan on
time of 45 seconds is not adjustable. Fan off time (time that
the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches 1 and 2
located on the SureLight integrated control. The unit is
shipped with a factory fan off setting of 90 seconds. Fan off
time will affect comfort and is adjustable to satisfy individual
applications. For customized comfort, monitor the supply
air temperature once the heat demand is satisfied. Note the
supply air temperature at the instant the blower is de−energized. Adjust the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de−
energized. (Longer delay times allow for lower air
temperature, shorter delay times allow for higher air temperature). See table 10 for dip switch settings.
TABLE 10
Heating Fan Off Delay
Delay (Seconds)
60OffOff
90OffOn
120OnOff
180OnOn
Switch 3 − Second Stage Delay (Used with Single−Stage
Thermostat Only) −− This switch is used to determine the
second stage on delay when a single−stage thermostat is
being used. The switch is factory−set in the ON position,
which provides a 10−minute delay before second−stage
heat is initiated. If the switch is toggled to the OFF position,
Switch 1Switch 2
Page 22
it will provide a 15−minute delay before second−stage heat
is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE−stage thermostat use.
Switch 4 − Cooling Fan off Delay − The fan on delay time
of 2 seconds is not adjustable. Fan off time (time that the
blower operates after the cool demand has been satisfied)
can be adjusted by flipping dip switch 4. The unit is shipped
with a factory fan off setting of 45 seconds. Fan off time will
affect comfort and is adjustable to satisfy individual applications. See table 11 for cool fan off time settings.
TABLE 11
Cooling Fan Off Delay
Delay (Seconds)Switch 4
2Off
45On
Diagnostic LED’s (DS1 and DS2)
Two diagnostic LED’S are located on the two−stage integrated control board. See figure 20. These light flashes
correspond with the codes detailed in table 15.
Factory Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the
integrated control board terminal strip must be removed for
two−stage cooling.
TABLE 12
Integrated Control Board Terminals
120VAC Neutral
LINELine
XFMRTransformer
EACElectronic Air Cleaner
CIRCIndoor Blower
HUMHumidifier
120VAC Line
HUMHumidifier
XMFRTransformer
LINELine
PARKFor Unused Leads
COOLCooling Speed
EACElectronic Air Cleaner
HI HEATHigh Heat Speed
LO HEATLow Heat, Low Cool and Continuous Fan
Speed
TWO−STAGE INTEGRATED CONTROL BOARD
SWITCHES
SENSOR
FACTORY−
INSTALLED
JUMPER
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH(ES)FUNCTION
1 and 2Blower Off Delay (Heating Mode)
3Second Stage ON Delay (Single−stage t’stat)
4Blower Off Delay (Cooling Mode)
Diagnostic LEDs are labeled DS1 and DS2. See figure 20 for location of diagnostic LEDs.
DS1DS2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASHON
OFFSLOW FLASH
OFFFAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASHOFFFlame sensed without gas valve energized.
ONON
OFFON
FAST FLASHSLOW FLASHMain power polarity reversed. Switch line and neutral.
SLOW FLASHFAST FLASHLow flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation.
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes
or unit goes into 1 hour Watchguard.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;
OR lost flame sense 5 times in one heating cycle;
OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts.
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on
call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Minimum flame sense current = 0.17−0.22 microAmps.
Page 24
9.Two Stage Variable Speed Integrated
Control (A92) GHR32V−5 Units
All GHR32V−5 units are equipped with the Lennox two−
stage, variable speed integrated SureLight control board.
The system consists of a ignition / blower control board
(figure 21 with control terminal designations in tables 16
through 19) and ignitor (figure 8). The board and ignitor
work in combination to ensure furnace ignition and ignitor
durability. The SureLight integrated board controls all major furnace operations. The board features two LED lights,
DS1 and DS2 for troubleshooting and four LED lights
(DS3, DS6, DS7 and DS8) to show furnace status. The
board also has two accessory terminals rated at (1) one
amp each. See table 20 for status code and table 21 for
troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heating cycle, the SureLight control monitors the first stage and second stage combustion
air inducer prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by−
passed). Likewise the control will not begin the second
stage heating cycle if the second stage prove switch is
closed, and will allow first stage heat only. However if the
second stage prove switch closes during the first stage pre−
purge, the control WILL respond to second stage heat call.
Once the first stage prove switch is determined to be open,
the combustion air inducer is energized on low (first stage)
heat speed. When the differential in the prove switch is
great enough, the prove switch closes and a 15−second
pre−purge begins. If the switch is not proven within 2−1/2
minutes, the control goes into Watchguard−Pressure
Switch mode for a 5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4−second period, the control will try four more times with
an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure
mode. After a 60−minute reset period, the control will begin
the ignition sequence again.
The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE
thermostat or TWO−STAGE thermostat. The thermostat
selection jumper E20, located just below dip switches 1
through 3 (figure 21), must be positioned for the particular
application. The jumper is factory set on TWO" for use
with a two−stage thermostat with two stage heat. Re−position jumper to SINGLE" for use with a single stage thermostat with two stage heat.
While in the single−stage thermostat mode (single jumper
setting), the burners will always fire on first−stage heat. The
combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a field selectable 10 or 15 minute delay (dip switch 3), the unit will
switch to second stage heat. While in the two−stage thermostat mode (two jumper setting) the burners will fire on
first−stage heat. The combustion air inducer will operate on
low speed and indoor blower will operate on low heat
speed. The unit will switch to second−stage heat on call
from the indoor thermostat. If there is a simultaneous call
for W1 and W2 (first and second stage heat) the unit will fire
on first stage heat and switch to second stage heat after 30
seconds of operation. See Sequence of Operation flow
charts in the back of this manual for more detail.
TABLE 16
Two Stage Ignition / Blower Control Terminals
120VAC Neutral
LINELine 120VAC Neutral
XFMRTransformer 120VAC Neutral
EACElectronic Air Cleaner 120VAC Neutral
CIRCIndoor Blower 120VAC Neutral
HUMHumidifier 120VAC Neutral
120VAC Line
HUMHumidifier 120VAC Hot
XMFRTransformer 120VAC Hot
LINELine 120VAC Hot
CIRCIndoor Blower 120VAC Hot
EACElectronic Air Cleaner 120VAC Hot
TABLE 17
SureLight Board 5 Pin Terminal Designation
PIN #Function
1Ignitor
2Combustion Air Inducer High Speed
3Combustion Air Inducer Low Speed
4Combustion Air Inducer Neutral
5Ignitor Neutral
Page 25
TW0−STAGE, VARIABLE SPEED INTEGRATED
CONTROL BOARD
DIAGNOSTIC
LEDs
LEDs
DS8
DS7
ON−BOARD
JUMPER W914
(cut when CCB1 or
Harmony II are used)
FACTORY−
INSTALLED
DS3
JUMPER
16 PIN BLOWER
CONTROL TERMINALS
(cut when heat pump
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH FUNCTIONS
DIP SWITCH(ES)FUNCTION
1 and 2Blower Off Delay
3Second Stage ON Delay (Single−stage t’stat)
4Not used
5 and 6Cooling Mode Blower Speed
7 and 8Blower Speed Adjustment
DS3−ON indicates that the motor has a demand to operate. (This LED must be on in all
modes).
DS6−blinking indicates the airflow (CFM) demand in the motor. The air flow is determined by
counting blinks between two (2) second pauses. One blink equals roughly 100 CFM.
DS7−ON indicaties the DS to R" jumper has not been cut. When the jumper is cut the system
will be operating with LENNOX HARMONY IIt (See Harmony Installation Instructions) or
with the CCB1 Efficiency Plus control.
CCB1: When ON, a 24 VAC is being applied and when OFF, it has been removed. This on/off
operation varies the indoor blower’s performance so dehumidification can be enhanced.
TABLE 21
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 21 for location of diagnostic LEDs.
DS1DS2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASHON
OFFSLOW FLASH
OFFFAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASHOFFFlame sensed without gas valve energized.
ONON
OFFON
FAST FLASHSLOW FLASHMain power polarity reversed. Switch line and neutral.
SLOW FLASHFAST FLASHLow flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation.
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes
or unit goes into 1 hour Watchguard.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;
OR lost flame sense 5 times in one heating cycle;
OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts.
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on
call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Minimum flame sense current = 0.17−0.22 microAmps.
Page 27
Dip Switch Settings
Switches 1 and 2 − Blower Off Delay The blower−on delay
of 45 seconds is not adjustable. The blower−off delay (time
that the blower operates after the heating demand has
been satisfied) can be adjusted by moving switches 1 and 2
on the integrated control board. The unit is shipped from
the factory with a blower−off delay of 90 seconds. The
blower off delay affects comfort and is adjustable to satisfy
individual applications. Adjust the blower off delay to
achieve a supply air temperature between 90° and 110°F at
the exact moment that the blower is de−energized. Longer
off delay settings provide lower supply air temperatures;
shorter settings provide higher supply air temperatures.The table below provides the blower off timings that will
result from different switch settings.
TABLE 22
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 1Switch 2
60OffOff
90OffOn
120OnOff
180OnOn
Switch 3 − Second Stage Delay (Used with Single−Stage
Thermostat Only) This switch is used to determine the
second stage on delay when a single−stage thermostat is
being used. The switch is factory−set in the ON position,
which provides a 10−minute delay before second−stage
heat is initiated. If the switch is toggled to the OFF position,
it will provide a 15−minute delay before second−stage heat
is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE−stage thermostat use.
Switch 4 − Not used
Switches 5 and 6 − Cooling Mode Blower Speed
Switches 5 and 6 are used to select cooling blower motor
speed. The unit is shipped from the factory with the dip
switches positioned for high speed (4) indoor blower motor
operation during the cooling mode. The table below provides the cooling mode blower speeds that will result from
different switch settings. Refer to blower data tables at the
front of this manual for corresponding cfm values.
Cooling Mode Blower Speeds
TABLE 23
SpeedSwitch 5Switch 6
1 − LowOnOn
2 − Medium LowOffOn
3 − Medium HighOnOff
4 − High (Factory)OffOff
Switches 7 and 8 − Blower Speed Adjustment Switches
7 and 8 are used to select blower speed adjustment settings. The unit is shipped from the factory with the dip
switches positioned for NORMAL (no) adjustment. The dip
switches may be positioned to adjust the blower speed by
+10% or −10% to better suit the application. The table below provides blower speed adjustments that will result from
different switch settings. Refer to blower data tables at the
front of this manual for corresponding cfm values.
TABLE 24
Blower Speed Adjustment
AdjustmentSwitch 7Switch 8
+10% (approx.)OnOff
NORMAL (Factory)OffOff
−10% (approx.)OffOn
Switches 9 and 10 − Cooling Mode Blower Speed
Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramping may be used to enhance dehumidification performance. The switches are factory set at option A which has
the greatest effect on blower motor performance. The table
below provides the cooling mode blower speed ramping
options that will result from different switch settings. The
cooling mode blower speed ramping options are detailed
on the next page. See unit nameplate for manufacturing
date.
TABLE 25
Cooling Mode Blower Speed Ramping
Ramping OptionSwitch 9Switch 10
A (Factory)OffOff
BOnOff
COffOn
D*OnOn
*Only option for CCB1
Page 28
GHR32V units manufactured before April 2003
Ramping Option A (Factory Selection)
D Motor runs at 50% for 1/2 minute.
D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 1/2 min-
ute.
D Motor ramps down to off.
GHR32V units manufactured April 2003 and later
Ramping Option A (Factory Selection)
S Motor runs at 50% for 30 seconds.
S Motor then runs at 82% for approximately 7−1/2 min-
utes. If demand has not been satisfied after 7−1/2 minutes.
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 50% for 30 sec-
onds then −
S ramps down to stop.
OFF
1/2 MIN
50% CFM
7−1/2 MIN
82% CFM
COOLING DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
D Motor runs at 50% for 1/2 minute.
D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
1/2 MIN
50% CFM
7−1/2 MIN
82% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
D Motor runs at 82% for approximately 7−1/2 minutes.
D If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
7−1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COOLING DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes −
S motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 60 sec-
onds. Then,
S ramps down to stop.
OFF
100% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option D
D Motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
100% CFM
COOLING
DEMAND
Ramping Option D
S− Motor runs at 100% until demand is satisfied.
S− Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING
DEMAND
OFFOFF
Page 29
Switches 11 and 12 − Heating Mode Blower Speed
idi
Dehumidification mode begins when rela
satisfied between
d
lid
d
Switches 11 and 12 are used to select heating mode blower
motor speed. The unit is shipped from the factory with the
dip switches positioned for medium low (2) speed indoor
blower motor operation during the heating mode. The table
below provides the heating mode blower speeds that will
result from different switch settings. Refer to blower data
tables at the front of this manual for corresponding cfm values.
TABLE 26
Heating Mode Blower Speeds
SpeedSwitch 11Switch 12
1 − LowOnOn
2 − Medium Low
(Factory)
OffOn
3 − Medium HighOnOff
4 − HighOffOff
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and
R on the integrated control board, must be cut when the furnace is installed with either the Harmony II zone control
board or the CCB1 EfficiencyPlus humidity control. Refer to
table 27 for operation sequence in applications including a
GHR32V, CCB1 and single−speed outdoor unit. Table 28
gives the operation sequence in applications with a two−
speed outdoor unit.
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O
on the integrated control board, must be cut when the furnace is installed in applications which include a heat pump
unit and the FM21 FuelMaster control board.
Factory−Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the
integrated control board terminal strip must be removed if
two−stage cooling will be used.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two−stage, variable speed integrated control just to the left of the first bank
of dip switches. These lights’ flashes correspond with diagnostic codes detailed on in table 15.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate
operating status. The green ON/OFF LED is lit any time the
blower is operating. The green CFM LED indicates the
blower motor speed. Count the number of blinks between
the two−second pauses to determine the CFM. Each blink
represents approximately 100 CFM. The yellow HI/LO LED
is lit when the W914 (DS to R) jumper has not been clipped
for CCB1 or Harmony operation. The yellow HEAT LED is
lit when the indoor blower is operating at the HEATING
speed.
Table 27
Operating Sequence
GHR32V−5, CCB1 and Single−Speed Outdoor Unit
OPERATING MODESYSTEM DEMANDSYSTEM RESPONSE
System Condition
Normal operationY1
*Call for humidity
removal during
cooling demand
Dehumidification
demand satisfied
during cooling demand.
Call for cooling after
call for hum
removal.
Humidity demand
satisfied between
thermostat demands
(unit off cycle).
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first thermostat heating demand.
* Reduced blower speed is 77% of COOL for V3 units and 74% of COOL for the V5 units.
ty
Thermostat
Demand
Y1
Y1
None
Y1
NoneOver setpoint (1 or more)Off
Y1Change to acceptableCOOL
*Relative Humidity
(EfficiencyPlus Lights)
No demand. Humidity
level is acceptable
Humidity level rises
above setpoint. Demand
initiated.
Humidity level falls below
setpoint. No demand
Humidity level above set-
point. Demand initiated.
Humidity level above set-
point. Demand initiated.
Blower
CFM
(COOL)
COOL
77%/74%
of COOL
COOL
Off
77%/74%
of COOL
Comments
Compressor demand and indoor blower
speed controlled by thermostat demand.
Call for dehumidification initiated by CCB1
control. Indoor blower speed reduced by
CCB1 control.
When humidity demand is satisfied, blower speed immediately increases to the
COOL CFM to hasten the end of the cycle.
Dehumidification mode begins when relative humidity is greater than setpoint.
While unit is not operating (no thermostat
emand), s
back up. Blower operates at COOL CFM.
e switch is moved down an
Page 30
Loading...
+ 69 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.