Lennox GHR32Q, GHR32V Unit Information

Service Literature
GHR32Q/V SERIES UNITS
Units are factory equipped for use with natural gas. A kit is available for conversion to LPG operation. GHR32−1 through −4 units are equipped with the Lennox SureLight silicon nitride ignition system. GHR32−5 units are equipped with the two stage (V models will have the vari­able speed control) integrated control board. Each GHR32 unit meets the California Nitrogen Oxides (NOx) Standards and California Seasonal Efficiency require­ments. The gas valve is redundant to assure safety shut−off as required by A.G.A. and C.G.A.
The heat exchanger, burners and manifold assembly can be removed for inspection and service. The maintenance section gives a detailed description on how this is done.
Information contained in this manual is intended for use by qualified service technicians only. All specifica-
tions are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
TABLE OF CONTENTS
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Q Models 2. . . . . . . . . . . . . . . . . . . . . . . .
Blower performance Q Models 3. . . . . . . . . . . . . . . . . .
Specifications V Models 4. . . . . . . . . . . . . . . . . . . . . . . .
Blower performance V Models 5. . . . . . . . . . . . . . . . . . .
Parts Arrangement 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
I Unit Components 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Placement and Installation 41. . . . . . . . . . . . . . . . . . . .
III Start Up 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating System Service Checks 47. . . . . . . . . . . . . .
V Typical Operating Characteristics 49. . . . . . . . . . . . . .
VI Maintenance 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32Q/V
Corp. 0001−L2
Revised 08−2004
DOWN FLOW
POSITION
GHR32Q MODEL SHOWN
VII Wiring Diagram and Sequence of Operation 54. . . .
GHR32Q−1 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32Q−3 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32Q−5 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−1 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−3 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−4 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−5 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII Operating Flow Charts 65. . . . . . . . . . . . . . . . . . . . . .
IX Troubleshooting 76. . . . . . . . . . . . . . . . . . . . . . . . . . . .
X Blower Control Board Jumper Summary 87. . . . . . . .
Page 1
© 2000 Lennox Industries Inc.
Litho U.S.A.
SPECIFICATIONS GHR32Q MODELS
I
(kW)
O
(kW)
Temperature rise
Blower wheel nominal
Nominal cooling
Intake
Kit
()
()
()
10.0 (2.49)
10.0 (2.49)
10.0 (2.49)
Kit #67K27
Model No. GHR32Q2/3-50 GHR32Q3-75 GHR32Q4/5-100 GHR32Q4/5-120
nput  Btuh
utput  Btuh
A.F.U.E. 90.0%
California Seasonal Efficiency 83.7% 83.9% 85.3% 84.0%
Exhaust pipe connection (PVC) diameter  in. (mm) 2 (51)
Intake pipe connection (PVC) diameter  in. (mm) 2 (51)
Condensate drain connection (PVC)  in. (mm) 1/2 (12.7)
Temperature rise range  _F (_C)
High static certified by (A.G.A./C.G.A.)  in wg. (Pa) .50 (125)
Gas Piping Size I.P.S.  in. (mm) 1/2 (12.7)
Blower wheel nominal
diameter x width
Number and size of filters − in. (mm) (1) 14 x 25 x 1 (356 x 635 x 25) (1) 20 x 25 x 1 (508 x 635 x 25)
Blower motor output  hp (W) 1/3 (249) 1/2 (373) 3/4 (560)
Nominal cooling
that can be added
Shipping weight  lbs. (kg) 1 package 147 (67) 155 (70) 196 (89) 205 (93)
Electrical characteristics 120 volts  60 hertz  1 phase (less than 12 amps)
High Fire 50,000 (14.7) 72,000 (21.1) 100,000 (29.3) 118,000 (34.6)
Low Fire 34,000 (10.0) 51,000 (14.9) 68,000 (19.9) 81,600 (23.9)
High Fire 47,000 (13.8) 67,000 (19.6) 93,000 (27.2) 111,000 (32.5)
Low Fire 31,600 (9.3) 47,000 (13.8) 63,000 (18.4) 75,900 (22.2)
High Fire 30 − 60 (17 − 33) 40 − 70 (22 − 39) 45 − 75 (25 − 42)
Low Fire 25 − 55 (14 − 31) 35 − 65 (20 − 36) 40 − 70 (22 − 39)
in. 10 x 8 11-1/2 x 9
mm 254 x 203 292 x 229
Tons 2 to 3 2 to 3.5 3.5 to 5
kW 7.0 to 10.6 7.0 to 12.3 12.3 to 17.6
Optional Accessories (Must Be Ordered Extra)
LPG/Propane kit 59L81 (−1 and −2 models) 11M57 (−3 and later models)
Down-Flow Additive Base 32K52 32K53
Horizontal Support Frame Kit  Ship. Wt. − lbs. (kg.) 56J18  18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits 60G77 − For 1 1/2 inch (38 mm) venting
Roof
Vent/
Intake
Kits
Twinning Kit 15L38 (all models)
Condensate Drain Heat Cable 26K68 6 ft. (1.8 m)  26K69 24 ft. (7.3 m)  26K70 50 ft. (15.2 m)
Heat Cable Tape 39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.Determine from venting tables proper intake and exhaust pipe size and termination kit required.Cleanable polyurethane frame type filter.
Termination
Kits
Wall
Termination
s
For 2 inch (51 mm) venting 15F75 Not Available
For 3 inch (76 mm) venting Not Available 44J41
For 2 inch (51 mm) venting
15F74 (ring kit) − 22G44 (close couple) − 30G28 (WTK Close Cou-
30G79 (WTKX close couple with extension riser)
For 3 inch (76 mm) venting Not Available 44J40 (close couple)  81J20 (WTK close couple)
ple)
33K97 − For 2 inch
(51 mm) venting
60L46 − For 3 inch
(76 mm) venting
Not Available
HIGH ALTITUDE
No gas pressure adjustment is needed when operating from 0 to 4500 ft. (0 to 1372m). See table below for correct manifold pressure and prove switch for altitudes greater than 4500 ft. (1372m).
Model No. Prove Switch
GHR32−50 nat no change 3.5 (0.87) 3.5 (0.87) 3.5 (0.87)
GHR32−75 nat
GHR32−100 nat
GHR32−120 L.P.
GHR32−50 L.P.
GHR32−75 L.P.
GHR32−100 L.P.
HGR32−120 L.P.
Kit #67K27 3.4 (0.85) 3.3 (0.82) 3.2 (0.80)
no change
Manifold Pressure (outlet) in. w.g. (kPa)
4501 to 5500 ft.
(1373 to 1676m)
10.0 (2.49) 10.0 (2.49) 10.0 (2.49)
9.6 (2.39) 9.3 (2.31) 9.0 (2.24)
5501 to 6500 ft.
(1677 to 1981m)
6501 to 7500 ft.
(1982 to 2286m)
Page 2
BLOWER PERFORMANCE DATA Q MODELS
External Static
External Static
External Static
External Static
GHR32Q2/3-50 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 1480 700 640 1330 630 520 1070 505 435 900 425 355 .10 25 1430 675 615 1290 610 500 1050 495 420 880 415 346 .20 50 1380 650 595 1240 585 480 1040 490 400 870 410 330 .30 75 1320 625 570 1200 565 455 1010 475 380 850 400 320 .40 100 1260 595 545 1140 540 430 980 460 370 820 385 300 .50 125 1200 565 520 1080 510 410 930 440 320 790 375 280 .60 150 1100 520 500 1000 470 385 860 405 300 740 350 265 .70 175 1000 470 470 890 420 370 750 355 290 660 310 250 .80 200 800 380 440 700 330 340 590 280 280 550 260 240
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium-Low Low
GHR32Q3-75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 1650 780 720 1540 725 585 1450 685 540 1230 580 450 .10 25 1590 750 660 1490 705 550 1400 660 505 1200 565 420 .20 50 1520 715 645 1430 675 520 1350 635 485 1170 550 405 .30 75 1440 680 630 1370 645 490 1300 615 450 1130 535 390 .40 100 1370 645 610 1300 615 470 1240 585 430 1090 515 370 .50 125 1300 615 590 1240 585 450 1170 550 410 1040 490 330 .60 150 1210 570 560 1170 550 430 1100 520 375 970 460 320 .70 175 1120 530 540 1080 510 410 1020 480 350 890 420 280 .80 200 1020 480 515 980 460 380 900 425 325 750 355 260 .90 225 880 415 500 820 385 350 750 355 300 600 285 240
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium-Low Low
GHR32Q4/5-100 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 2530 1195 1360 2300 1085 1210 2030 960 1050 1780 840 885 1540 725 745 .10 25 2460 1160 1290 2250 1060 1140 2010 950 1010 1760 830 850 1530 720 730 .20 50 2380 1125 1270 2200 1040 1100 1990 940 990 1740 820 830 1520 715 720 .30 75 2310 1090 1250 2150 1015 1080 1950 920 970 1720 810 805 1510 715 710 .40 100 2250 1060 1200 2090 985 1060 1910 900 950 1690 800 790 1500 710 690 .50 125 2180 1030 1150 2020 955 1020 1870 880 910 1660 785 780 1480 700 670 .60 150 2100 990 1100 1960 925 980 1810 855 870 1620 765 760 1430 675 650 .70 175 2010 950 1070 1880 885 940 1750 825 855 1570 740 730 1380 650 630 .80 200 1910 900 1040 1800 850 920 1680 795 840 1500 710 710 1320 625 615 .90 225 1800 850 1010 1700 800 890 1580 745 800 1420 670 690 1240 585 600
1.00 250 1700 800 980 1600 755 870 1500 710 780 1320 625 670 1120 530 590
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium Medium-Low Low
Air Volume and Motor Watts at Specific Blower Taps
Air Volume and Motor Watts at Specific Blower Taps
Air Volume and Motor Watts at Specific Blower Taps
GHR32Q4/5-120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 2400 1135 1250 2270 1070 1140 2060 970 1010 1800 850 860 1560 735 720 .10 25 2350 111 0 1220 2220 1050 1100 2040 965 980 1780 840 830 1550 730 705 .20 50 2290 1080 1200 2170 1025 1080 2000 945 960 1750 825 815 1540 725 685 .30 75 2220 1050 1180 2120 1000 1060 1960 925 940 1720 810 800 1520 715 675 .40 100 2150 1015 1130 2050 965 1020 1900 895 920 1680 795 770 1500 710 660 .50 125 2080 980 1100 1980 935 980 1850 875 880 1640 775 750 1460 690 650 .60 150 2000 945 1050 1910 900 940 1780 840 840 1590 750 720 1420 670 630 .70 175 1900 895 1010 1830 865 920 1710 805 810 1530 720 690 1380 650 610 .80 200 1800 850 980 1740 820 900 1630 770 790 1460 690 675 1320 625 595 .90 225 1700 800 960 1630 770 860 1540 725 770 1380 650 660 1250 590 580
1.00 250 1600 755 940 1530 720 840 1430 675 750 1300 615 640 1150 545 560
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium Medium-Low Low
Air Volume and Motor Watts at Specific Blower Taps
Page 3
SPECIFICATIONS GHR32V MODELS
Temperature rise
Blower wheel nominal
g
Nominal cooling
Vent/
Kits
Model No. GHR32V3-75 GHR32V5-100
High Fire 72,000 (21.1) 100,000 (29.3)
Input  Btuh (kW)
Output  Btuh (kW)
A.F.U.E. 90.0% 90.0%
California Seasonal Efficiency 83.9 85.3
Exhaust pipe connection (PVC) diameter  in. (mm) 2 (51)
Intake pipe connection (PVC) diameter  in. (mm) 2 (51)
Condensate drain connection (PVC)  in. (mm) 1/2 (12.7)
Low Fire 51,000 (14.9) 68,000 (19.9)
High Fire 67,000 (19.6) 93,000 (27.2)
Low Fire 47,000 (13.8) 63,000 (18.4)
Te mperature rise range  _F (_C)
High static certified by (A.G.A./C.G.A.)  in wg. (Pa) .80 (200)
Gas Piping Size I.P.S.  in. (mm) 1/2 (12.7)
Blower wheel nominal
diameter x width
Blower motor output  hp (W) 1/2 (373) 1 (746)
Number and size of filters − in. (mm) (1) 14 x 25 x 1 (356 x 635 x 25) (1) 20 x 25 x 1 ( 508 x 635 x 25)
Nominal coolin
that can be added
Shipping weight  lbs. (kg) 1 package 160 (73) 201 (91)
Electrical characteristics 120 volts  60 hertz  1 phase (less than 12 amps)
High Fire 40 − 70 (22 − 39)
Low Fire 35 − 65 (19 − 36)
in. 10 x 8 11-1/2 x 9
mm 254 x 203 292 x 229
Tons 2 to 3.5 3.5 to 5
kW 7.0 to 12.3 12.3 to 17.6
Optional Accessories (Must Be Ordered Extra)
LPG/Propane kit 59L81
Down-Flow Additive Base 32K52 32K53
Horizontal Support Frame Kit  Ship. Wt. − lbs. (kg.) 56J18  18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits 60G77 − For 1 1/2 inch (38 mm) venting 33K97 − For 2 inch (51 mm) venting
Roof
Termination
Vent/
Intake
Kits
Condensate Drain Heat Cable 26K68 6 ft. (1.8 m)  26K69 24 ft. (7.3 m)  26K70 50 ft. (15.2 m)
Heat Cable Tape 39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.Determine from venting tables proper intake and exhaust pipe size and termination kit required.Cleanable polyurethane frame type filter.
Kits
Wall
Termination
Kits
For 2 inch (51 mm) venting 15F75
For 3 inch (76 mm) venting 44J41
15F74 (ring kit)
For 2 inch (51 mm) venting
30G79 (WTKX close couple w/ extension riser)
For 3 inch (76 mm) venting 44J40 (close couple)  81J20 (WTK close couple)
22G44 (close couple)
30G28 (WTK Close Couple)
22G44 (close couple)
Page 4
15F74 (ring kit)
BLOWER PERFORMANCE DATA −1 through −3 V MODELS
p
Jumper
g
g
Setting
ADJUST
Jumper
s
Positions
ADJUST
Jumper
s
Positions
GHR32V3-75 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP2−1 Blower Control Low Speed  3 Factory Settings High Speed  4
ADJUST"
Jum
Setting
NORM 875 415 940 445 985 465
minus 15%
less motor
speed
NOTE  The effect of static pressure and filter resistance is included in the air volumes listed.
(Cool, Low Heat Or Continuous Fan)
er
1 2 3 4 1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
750 355 795 375 850 400 915 430 900 425 940 445
LOW" Speed
GHR32V5-100 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP2−1 Blower Control Low Speed  2 Factory Settings High Speed  4
ADJUST"
Jumper
Settin
NORM 1100 520 1260 595 1445 680 1635 770 1670 790 1960 925 2165 1020 2285 1075 1640 775 1825 860 2150 1015 2315 1090
minus 15%
less motor
speed
NOTE  The effect of static pressure and filter resistance is included in the air volumes listed.
LOW" Speed (Cool Or Continuous Fan) HIGH" Speed (Cool) HEAT" Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
935 440 1015 480 1195 565 1355 640 1335 630 1495 705 1690 800 1800 850 1360 640 1465 690 1770 835 1905 900
GHR32V3-75 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP3−1 Blower Control Factory Settings ADJUST − NORM
ADJUST"
Jumper
Positions
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
NORM (Normal) 875 415 940 445 985 465 1060 500 1090 515 1175 555 1285 605 1330 630
" (Minus) 15% 750 355 795 375 850 400 915 430 940 445 995 470 1095 515 1180 555
ADJUST"
Jumper
Position
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
NORM (Normal) 875 415 940 445 985 465 1060 500 1070 505 1130 535 1270 600 1290 610
" (Minus) 15% 750 355 795 375 850 400 915 430 900 425 940 445 1055 500 1120 530
15% lower motor speed than NORM jumper setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 875 cfm (415 L/s) for all positions.
GHR32V5−100 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP3−1 Blower Control Factory Settings ADJUST − NORM
ADJUST"
Jumper
Positions
NORM (Normal) 1100 520 1260 595 1445 680 1635 770 1640 775 1825 860 2150 1015 2315 1090
" (Minus) 15% 935 440 1015 480 1195 565 1355 640 1360 640 1465 690 1770 835 1905 900
ADJUST"
Jumper
Position
NORM (Normal) 1100 520 1260 595 1445 680 1635 770 1670 790 1960 925 2165 1020 2285 1075
" (Minus) 15% 935 440 1015 480 1195 565 1355 640 1335 630 1495 705 1690 800 1800 850
15% lower motor speed than NORM jumper setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 1100 cfm (520 L/s) for all positions.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Heat Speed  3
VSP Jumper Speed Positions
HIGH" Speed (Cool) HEAT" Speed
106
0
500
107
505 113 0 535
0
127
105
0
5
129
600
0
500 112 0 530 940 445 995 470
610
109
515 117 5 555
0
Heat Speed  1
VSP Jumper Speed Positions
BLOWER PERFORMANCE DATA −4 V MODELS
Heat Speed − 3 Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low Speed High Speed
COOL"
Low Speed High Speed
Heat Speed − 2 Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low Speed High Speed
COOL"
Low Speed High Speed
Page 5
128
605
5
109
515 118 0 555
5
133
630
0
GHR32V3−75−5 Blower Motor Performance
Adjust
Jumper
g
Adjust"
Jumper
g
Adj
"
Jumper
Jumper
g
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
"
Jumper
Setting
Norm 875 415 940 445 985 465 1060 500 1070 505 1130 535 1270 600 1290 610
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
750 355 795 375 850 400 915 430 900 425 940 445 1055 500 1120 530
Low High
Cooling
Blower Speed Adjustment Settings (Switches 7 and 8)
 Jumper
Setting
"
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Low High
Norm 945 446 1025 484 1125 531 1270 599 1080 510 1172 533 1286 607 1452 685
803 379 871 411 956 451 1080 510 918 433 996 470 1093 516 1234 582
15% lower motor speed than NORM switch setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 875 cfm (415 L/s) for all positions.
Heating
GHR32V5−100/125−5 Blower Motor Performance
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
"
ust
Jumper
Setting
Norm 1100 520 1260 595 1445 680 1635 770 1670 790 1960 925 2165 1020 2285 1075
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
935 440 1015 480 1195 565 1355 640 1335 630 1495 705 1690 800 1800 850
Low High
Cooling
Blower Speed Adjustment Settings (Switches 7 and 8)
"
Adjust"
Setting
Norm 1100 520 1260 595 1445 680 1635 770 1640 775 1825 860 2150 1015 2315 1090
1* 2 3 4 1* 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
935 440 1015 480 1195 565 1355 640 1360 640 1465 690 1770 835 1905 900
Low High
15% lower motor speed than NORM switch setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 1100 cfm (520 L/s) for all positions.
Heating
Page 6
GHR32Q−5 PARTS IDENTIFICATION
(Downflow Application Shown)
CONTROL VOLTAGE
CIRCUIT BREAKER
CONTROL TRANSFORMER
CONTROL BOX COVER
DOOR INTERLOCK SWITCH
COLD END HEADER
(COLLECTOR) BOX
COMBUSTION AIR
BLOWER MOUNTING
COMBUSTION
AIR INDUCER
EXHAUST TEE
PATCH PLATE
WITH BARBED
FITTING
BURNER BOX
COVER
FLAME SIGHT
GLASS
FLAME SENSOR
INTAKE AIR
GASKET
BRACKET
FRESH AIR
INTAKE FITTING
IGNITOR
SURELIGHT TWO−STAGE
INTEGRATED CONTROL
CORBELS
BURNER BOX
TOP
BURNER BOX
ASSEMBLY
ORIFICE
GAS VALVE
AND MANIFOLD
FIGURE 1
SUPPLY AIR
BLOWER
TOP CAP
CONTROL
BOX
GASKET
PRIMARY LIMIT
AUTO−RESET
(ALTERNATE STYLES)
BURNER BOX
GASKET
FLAME ROLL−OUT SWITCH
(MANUAL RESET)
SECONDARY LIMIT
AUTO−RESET
(Located on Backside
of Blower Wrapper)
CABINET
COMBUSTION AIR
PROVING (PRES-
SURE) SWITCH
HOT END HEADER
(COLLECTOR) BOX
CONDENSER
COIL
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
CONDENSATE
TRAP
BACK FILTER
CLIP
FLUE
COLLAR
CONDENSATE
COLLAR
TM
Page 7
I−UNIT COMPONENTS
GHR32 unit components are shown in figure 1. The com­bustion air blower, gas valve and burners can be accessed by removing the burner access panel. The blower and con­trol box can be accessed by removing the blower access door.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
WARNING
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch
A−Make-Up Box (Figure 2)
WARNING
Unit must be grounded in accordance with national and local codes. Electric Shock Hazaed. Can cause injury or death.
A field make−up box (see figure 2) is provided for line voltage wiring. Line voltage wiring to unit is done through the J96 jack from the field make−up box to plug P96 from the control box. The box may be installed inside or outside the unit (see figures 3 and 4) and may be installed on the unit left or right side.
MAKE-UP BOX
POWER ENTRY KNOCKOUT
BOX
UNIT
GROUND
JACK J96
Box may be installed inside or outside unit.
FIGURE 2
120V LINE VOLTAGE
PIGTAIL CONNECTIONS
COVER
J96
BUSHING
P96
FIGURE 3
EXTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
BUSHING
J96
(Shown with
accessory
wire connected)
P96
FIGURE 4
An accessory (brown) output wire is provided with the make­up box. The wire provides a 120V connection for optional ac­cessories such as electronic air cleaner or humidifier. If used, the wire is field installed in J96 jack plug by inserting the pin of the brown wire into the open socket of the jack. See fig­ure 5. 120V accessories rated up to 4 amps total may be con­nected to this wire. The neutral leg of the accessory is con­nected to the neutral white wire in the make-up box. The acces-
INSTALLING BROWN
ACCESSORY WIRE TO J96
WHITE
NEUTRAL
BROWN
sory terminal is energized whenever the indoor blower is in operation.
BLACK
J96
FIGURE 5
Page 8
B−Control Box (Figure 6)
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CIRCUIT BREAKER CB8
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the techni­cian at the same electrostatic potential. Neutral­ize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
GHR32−1 through −4 CONTROL BOX
TWO−STAGE
CONTROL
CIRCUIT
BREAKER
TRANSFORMER
FIGURE 6
Unit transformer (T1), circuit breaker (CB8), SureLight control (A92), VSP−2 control (A24) and Two−stage control (A86) are located in the control box. In addition, a door in­terlock switch (S51) is located in the control box. Jackplugs and a snap-off" terminal strip allow the control box to be easily removed for blower service.
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage 24 volt section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V secondary.
2. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the transformer (T1). The breaker is rated 3 amps at 32V. If the current ex­ceeds this limit the breaker will trip and all unit operation will shut down. The breaker can be manually reset by pressing the button on the face (figure 7).
VSP−2
CONTROL
(v models only)
SURELIGHT
CONTROL
DOOR INTERLOCK
SWITCH
PRESS TO RESET
FIGURE 7
3.Door Interlock Switch (S51)
A door interlock switch rated 14 amps at 125VAC is located on the control box. The switch is wired in series with line voltage. When the blower door is removed the unit will shut down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
4. SureLight Ignition System A92
All GHR32−1 through −4 units are equipped with the Len­nox SureLight ignition system. The system consists of ig­nitor (figure 8) and ignition control board (figure 9 and table 3 ). The board and ignitor work in combination to en­sure furnace ignition and ignitor durability. The SureLight integrated board controls all major furnace operations. Table 1 and 2 show jack plug terminal designations. shows control board terminations. The board also features two LED lights for troubleshooting and two accessory termi­nals rated at (1) one amp. See table 4 for troubleshooting diagnostic codes. Units equipped with the SureLight board can be used with either electronic or electro−me­chanical thermostats without modification. The SureLight ignitor is made of durable silicon nitride. Ignitor longevity is also enhanced by voltage ramping by the control board. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor.
NOTE − Do not remove blower access panel to read Surelight LED lights. A sight glass is provided on the access panel for viewing.
Page 9
13/32’
SURELIGHT IGNITOR
MEASUREMENT IS TO I.D.
5/8"
OF RETENTION RING
FRONT VIEW
TABLE 1
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Ignitor
2
3
4
Combustion Air Blower Line Voltage
5
6
Combustion Air Blower Neutral
Not Used
Ignitor Neutral
Not Used
TABLE 2
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
5/16"
TOP VIEW
FIGURE 8
SURELIGHT INTEGRATED CONTROL BOARD
GHR32−1 through −4 units
PIN # FUNCTION
1 Primary Limit In
2
3
4
5
6
Pressure Switch and Primary Limit Out
7
8
9
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Not Used
Roll Out Switch In
Ground
TABLE 3
ACB COOL ACB HEAT PARK ACB LOW ACC TX HOT HTG ACC NEUTRALS 24VAC HOT 24VAC RTN FLAME SENSE
TERMINAL DESIGNATIONS
Blower − Cooling Speed (Line Volt) Blower − Heating Speed (Line Volt) Alternate Blower Speeds (Dead) Continuous Low Speed Blower Accessory Terminal (Line Volt) 120VAC Hot to Transformer 120VAC Hot Input Heat Only Accessory (Line Volt) 120VAC Neutrals 24VAC Hot from Transformer 24VAC Return from Transformer Flame Sense Terminal
FIGURE 9
Page 10
TABLE 4
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1 LED #2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASH ON
OFF SLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASH OFF
ON SLOW FLASH
ON ON
OFF
FAST FLASH SLOW FLASH
SLOW FLASH FAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Limit must close within 3 minutes or board goes
Watchguard pressure switch − 5 minutes. Pressure switch open or has opened 5 times during a single call for heat; OR: Blocked inlet/exhaust vent; OR: Conden-
sate line blocked; OR: Pressure switch closed prior to activation of combustion
Watchguard 60 minute delay − burners fail to ignite.
Flame sensed without gas valve energized.
Rollout switch open. OR: 9 pin connector improperly attached.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .61 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
into one hour limit Watchguard.
air blower.
Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.21 microAmps
a−Electronic Ignition Figures 12 and 13
On a call for heat the SureLight control monitors the com­bustion air blower pressure switch. The control will not be­gin the heating cycle if the pressure switch is closed (by− passed). Once the pressure switch is determined to be open, the combustion air blower is energized. When the differential in the pressure switch is great enough, the pres­sure switch closes and a 15−second pre−purge begins. If the pressure switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. Units with control 97L48: ig­nitor stays energized during the trial or until flame is sensed. Units with control 56L83: ignitor stays energized for the first second of the 4−second trial. If ignition is not
The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
b−Fan Time Control Q Models Only
The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 10.
proved during the 4−second period, the control (97L48 or 56L83) will try four more times with an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control
FAN-OFF TIME ADJUSTMENT
60sec. 90sec. 120sec. 180sec.
goes into Watchguard−Flame Failure mode. After a 60−min­ute reset period, the control will begin the ignition sequence again.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 10
Page 11
c−Flame Sensor
ЙЙЙЙЙЙЙЙЙ
A flame sensor is located on the left side of the burner sup­port. See figure 11. The sensor is mounted on a bracket in the burner support and the tip protrudes into the flame en­velope of the left−most burner. The sensor is fastened to burner supports and can be removed for service without re­moving any part of the burners. During operation, flame is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve to re­main open as long as flame signal is sensed.
SENSOR
3/8"
IGNITOR
FIGURE 11
NOTE − The GHR32 furnace contains electronic com­ponents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
5. Two−Stage Control (A86)
All GHR32−1 through −4 units are equipped with a two− stage control board. Two different boards have been used. Boards 43K9001 and 29M9201 (figure 14) are identical, except the 9 pin connector on 43K9001 is replaced by two relays with quick connect terminals on board 29M9201. The two−stage board acts as a go between from the indoor thermostat to the SureLight ignition board. The board can be utilized in three modes: with a SINGLE−STAGE thermo­stat, a TWO−STAGE thermostat or with a second−stage (high fire) delay called W2 TIMED. The two−stage board is equipped with a jumper (see figure 14) which changes op­erating modes and a jumper which adjusts second−stage heat delay during W2 TIMED mode.
NOTE−The mode of operation jumper on the two−stage control board is factory set in the TWO−STAGE" position.
While in the single−stage thermostat mode (one−stage jumper setting), the unit will always operate on second− stage heat. The combustion air blower (B6) will operate on high speed and indoor blower (B3) will operate on heating speed. While in the two−stage thermostat mode the unit will operate on first−stage heat (low fire). The combustion air blower (B6) and indoor blower will operate on low speed. The unit will switch to second−stage heat (high fire) on call from the indoor thermostat W2. While in the W2 TIMED mode (factory setting 8 minutes) the unit will fire on first− stage heat (low fire) with the combustion air blower (B6) and indoor blower (B3) operating on low speed. After a set time delay the unit switches to second−stage heat (high fire). The combustion air blower and indoor blower also switch to second−stage heat mode.
SureLight Control Ignition Sequence Board 56L8301
15
ON
OFF
DEMAND
CAB IGNITOR GAS VALVE INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −Purge Ignitor Warmup Trial for
341
35
Ignition
38
Blower On"
Delay
FIGURE 12
SureLight Control Ignition Sequence Board 97L4801
15
ON
OFF
DEMAND
CAB IGNITOR GAS VALVE INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −Purge Ignitor Warmup
341
Trial for Ignition
38
Blower On"
Delay
FIGURE 13
5 SEC80
Post
Purge
5 SEC80
Post
Purge
Page 12
MODE OF
OPERATION
JUMPER
TWO−STAGE CONTROL BOARD
G32(V) −1 through −4 units
W2 TIMED DELAY JUMPER
6.VSP2−1 Blower Control Board (A24)
−1 through −3 V Models only
GHR32V−1 through −3 units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. The unit uses the VSP2−1 variable speed control board, located in the blow­er compartment, which controls the blower speed and provides diagnostic LEDs. The control has a non−adjust­able, factory preset ON" fan timing delay and an adjustable OFF" fan timing delay (see figure 17).
The VSP2−1 also senses limit trip condition and turns on the blower. The GHR32 primary limit switch is located in the middle of the vestibule wall and the secondary limit switch is located int ehblower compartment. When excess heat is sensed in the heat exchanger, or blower compartment, the respective switch will open and interrupt the current to the gas valve, while at the same time the VSP2−1 energizes the blower on heating speed. The limit automatically resets when the unit temperature returns to normal and the blower is de−energized.
FIGURE 14
HIGH SPEED
SELECTOR PINS
(COOLING ONLY)
LOW SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG (BOARD TO VARIOUS POINTS IN FURNACE)
Diagnostic LEDs located on the VSP2−1 control board are pro­vided to aid in identifying the unit’s mode of operation. Certain scenarios will arise depending on the jumper positions. Refer to figure 15 for identification.
VSP2−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP 2
HIGH LOW ADJUST HEAT
270
1
2
3
4
DS4
CFM
210
90
150
JP 1
1
1
2
3
4
HTG.
BLOWER
12
1
2
3
4
HEAT
DS2
TEST
+
NORM
DS3
ON/OFF
HI/LOW
DS1
JP46
13 PIN PLUG
(BOARD TO MOTOR)
HEATING SPEED
SELECTOR PINS
See table 5 for VSP2
factory settings
OPERATIONAL
SELECTOR PINS
(Affects both heating and
cooling modes)
DIAGNOSTIC
DS LEDS
FAN OFF"
TIMING PINS
FIGURE 15
Page 13
IMPORTANT
24 VAC half wave rectified (DC pulse), when mea­sured with a meter, may appear as a lower or higher voltage depending on the make of the meter. Rather than attempting to measure the output voltage of the VSP2 board, see GHR32 BLOWER & VSP2 BLOWER CONTROL BOARD TROUBLESHOOTING FLOW CHART in the TROUBLESHOOTING section of this manual.
VSP2−1 BLOWER CONTROL BOARD (A24)
1
J46
HIGH LOW ADJUST HEAT
1 2 3 4
HTG.
BLOWER
1 2 3 4
HEAT
DS3
TEST
− + NORM
HI/LOW
1 2 3 4
DS4
Diagnostic LED Lights
a − DS3 ON/OFF"
ON/OFF−DS3 indicates there is a demand for the blower mo-
tor to run. When the ON/OFF LED−DS3 is lit, a demand is be­ing sent to the motor. In heating mode only, there is a 45 sec­ond fan ON" delay in energizing ON/OFF LED−DS3. The light will not go off until adjustable fan OFF" delay has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1 & HEAT LED−DS2 are off, the motor will operate in low speed.
b − DS2 HEAT"
If HEAT LED−DS2 is on, the blower is running in the heat speed according to the HEAT" jumper setting. The HEAT LED−DS2 comes on instantaneous and switches off when the call for heat is satisfied.
NOTE−When the blower is in OFF" delay mode, the mo­tor runs at low speed, therefore the HEAT LED−DS2 is off. It switches off when the call for heat is satisfied.
c − DS1 HI/LOW"
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control. PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output. PIN 13 - 24V - Input 24 VAC power for the VSP2-1. PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 1 - Heat - Heat speed input signal to the ICM2 motor.
PIN 4 - High Tap - High Speed programming input.
PIN 5 - Low Tap - Low speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 8 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common. PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
DS1
270
CFM
210
90
150
HIGH/LOW LED−DS1 indicates whether the blower is op­erating in high or low speed. When the light is off, the blow­er is running in low speed according to the LOW" jumper setting. When HIGH/LOW LED−DS1 is on, the blower is op- erating in high speed according to the HIGH" jumper set­ting.
d − DS4 CFM"
CFM LED−DS4 indicates the CFM the unit is operating,
according to the jumper settings. The light flashes once for approximately every 100 CFM. For example, if the unit is operating at 1000 CFM, CFM LED−DS4 will flash 10 times. If the CFM is 2050, CFM LED−DS4 will flash 20 full times plus one fast or half flash. At times the light may appear to flicker or glow. This takes place when the control is communicating with the motor be­tween cycles. This is normal operation.
The appropriate speed according to application and CFM need is selected by moving jumper pins.
Page 14
VOLTAGES INTO VSP2−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0 volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage) if CCB
is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP2−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx.
34 volts
0 volts
Voltage across J46 pins 8 and 9 to 3, is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pins 8 and 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
24VAC Half-Rectified (DC Pulse)
a voltage of 0−25VDC should be present.
@ 60Hz.
FIGURE 16
NOTE−On Harmony II zoning applications in the heating mode, the highest speed obtainable is the same as the highest cooling speed selection. Also, the heating speed (heat jumper position) is only used when the primary limit has been tripped. In non−zoning applications, refer to the section on the VSP2−1 control.
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
not operable. Notice in the GHR32V5−100 table, that the normal adjustment setting for heat speed position #3 is 2150 CFM (1015L/s). After the adjustment setting has been determined, c hose th e re main ing speed jumper settings from those offered in the table.
The TEST pin is available to bypass the VSP2−1 control and run the motor at approximately 70% to test that the moto r i s operational. This is beneficial primarily in troubleshoot­ing. G must be energized for motor to run.
b−HEATING BLOWER"
IMPORTANT
Before changing jumper setting, make sure the motor has completely stopped. Any jumper set­ting change will not take place while the motor is running.
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and condi­tions associated with each one. Refer to figure 15 for identifica­tion.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in the tables in the blower performance section. Using the tables, determine which row of CFM volumes most closely matches the desired CFM. Once a specific row has been chosen (NORMAL or −), CFM volumes from other rows cannot be used. Below are the descriptions of each of the jumper selections.
Refer to table 5 for factory settings. Refer to the blower perfor­mance tables for the approximate air volume for each setting.
VSP2−1 FACTORY SETTINGS
MODEL HIGH LOW ADJUST HEAT
GHR32V−75−
1, −2, −3 units
GHR32V−100
−1, −2, −3 units
a−ADJUST"
The ADJUST pins allow the motor to run at normal speed or approximately 15% lower than normal speed. The blower performance tables give two rows (NORMAL and −) with their respective CFM volumes. The + adjustment setting i s
TABLE 5
4 3 NORM 2
4 2 NORM 1
For GHRV32 units, place the HEATING BLOWER jumper across the second and third pins (position #2).
When W1 is energized, the LOW jumper selections are ac­tivated. The HEAT jumper selections are activated when W2 is energized.
NOTE−In Harmony II zoning applications, HEATING BLOWER jumper must be in position #2.
c−HEAT"
The HEAT jumper is used to set the blower speed to ob- tain the required CFM as outlined in HEAT SPEED in the blower performance tables.
The HEAT jumper selections are activated with a call for second-stage heating (W2).
d−HIGH"
The HIGH jumper is used to determine the CFM during cooling speed. These jumper selections are activated when G and DS terminals are energized.
e−LOW"
The LOW jumper is used to determine CFM during low speed cooling. These jumper selections are activated when G is energized. The LOW jumper may also be used for low speed heating. See the HEAT" section for details.
f−FAN OFF"
Fan OFF" timings (time that the blower operates after the heat demand has been satisfied) are determined by the ar­rangement of a jumper on the VSP2−1 board. See figure
17. To adjust fan OFF" timings, gently disconnect the jumper and reposition it across pins corresponding with the new timing. Fan OFF" time is adjustable from 90 to 330 seconds. The control has a non−adjustable, factory preset on" fan timing (45 seconds).
WARNING − MAKE SURE TO DISCONNECT POWER BEFORE CHANGING FAN OFF" TIMINGS.
Page 15
FAN-OFF TIME ADJUSTMENT
NOTEIf fan OFF" time is too low, residual heat in heat exchanger may cause primary limit S10 to trip resulting
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from VSP2−1 and select
one of the other pin combinations to
achieve the desired time.
in frequent cycling of blower. If this occurs, adjust blow­er to longer time setting.
Table 6 outlines the operation of the variable speed motor in relation to specific modes of operation. Some informa-
270
150 90
210
Leave jumper off to achieve
330 second fan−off timing.
TIMING PINS (seconds)
Fan-off timing is factory
set at 90 seconds
tion has been repeated from the previous section to provide an example. Refer to each diagnostic LED or jumper settings section for more information.
FIGURE 17
TABLE 6
VSP2−1 GHR32−1 through −3 units OPERATION
HEATING MODE COOLING MODE
UNITS WITH
SINGLE−STAGE HEATING
NON−ZONED
APPLICATIONS
Using a single−stage thermostat with one−stage" heating, the HEAT LED− DS2 is lit when the thermostat calls for heat. The ON/OFF LED−DS3 is lit after 110 seconds (65 seconds pre−purge and 45 seconds fan ON" time) from the time a call for heat is made. This in­dicates the blower is operating in heat­ing speed.
Using a single−stage thermostat with W2 TIMED," and W1 calling, the ON/ OFF LED−DS3 is lit to indicate the blower is operating on low speed.
When the HEAT LED−DS2 is lit, the blower is operating in heating speed, and second−stage (W2) heating is call­ing.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zon­ing system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/ OFF LED−DS3 are lit to indicate the blower is operating.
NOTE−In Harmony II zoning applica­tions, HTG. BLOWER jumper must be in position #2.
NOTE: For zone applications with Harmony, remove the wire from the pin #3 of the J73 terminal on the VSP control board, insulate the end, and secure it to prevent from shorting.
Using a two−stage thermostat with first−stage (W1) calling, the ON/OFF LED−DS3 is lit to indicate the blower is operating in low speed.
When the ON/OFF LED−DS3 and HEAT LED−DS2 are lit, the blower is operating in heating speed and sec­ond−stage (W2) heating is calling.
HEAT LED−DS2 is lit with a call for heat from the thermostat. ON/OFF LED− DS3 is lit after 110 seconds from the time a call for heat is made.
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zon­ing system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/ OFF LED−DS3 are lit to indicate the blower is operating.
NOTE−In Harmony II zoning applica­tions, HTG. BLOWER jumper must be in position #2.
UNITS WITH
TWO−STAGE HEATING
NON−ZONED
APPLICATIONS
HARMONY ZONED
APPLICATIONS
UNITS WITH SINGLE−
SPEED COMPRESSOR
NON−ZONED
APPLICATIONS
The terminals DS and Y must be jumpered together. With a call for cooling, terminals G, Y and DS on the unit control board are energized from the thermostat. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indi­cate the blower is operating on high speed.
NOTEY and DS are factory jump­ered for single−stage cooling, non− zoned applications.
NOTEFor low speed during single− stage cooling remove jumper from Y to DS.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
UNITS WITH TWO−SPEED
COMPRESSOR
NON−ZONED
APPLICATIONS
The ON/OFF LED−DS3 is lit to indicate the blower is operating in first stage cooling. This LED is energized on when a 24VAC thermostat demand is supplied to the control (terminal G" on the control board terminal strip).
In second stage, the ON/OFF LED− DS3 and HI/LOW LED−DS1 are lit to indicate the blower is operating on high speed (24VAC is supplied to the unit terminal strip Y2 from Y2 on the thermostat).
NOTE Jumper must be moved from Y1 to Y2 In two−speed, non−zoned ap­plications.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zon­ing system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/ OFF LED−DS3 are lit to indicate the blower is operating.
Page 16
7.VSP3−1 Blower Control Board (A24) GHR32V−4 Units
GHR32V−4 units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. The unit uses the VSP3−1 vari­able speed control board, located in the blower compart­ment, which controls the blower speed and provides diagnostic LEDs. The control has both a non−adjustable, factory preset ON" fan timing delay and an adjustable OFF" fan timing delay (see figure 17).
VSP3−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP2
DELAY PROFILE SELECTOR PINS
(COOLING ONLY)
DELAY COOL ADJUST HEAT
1
2
3
4
The VSP3−1 also senses limit trip condition and turns on the blower. The GHR32V limit switch is located in the middle of the vestibule wall. When excess heat is sensed in the hea t ex­changer, the limit switch will open and interrupt the current to the gas valve, while at the same time the VSP3−1 energizes the blower on heating speed. The limit automatically resets when the unit temperature returns to normal and the blower is de−energized.
Diagnostic LEDs located on the VSP3−1 control board are pro­vided to aid in identifying the unit’s mode of operation. Certain scenarios will arise depending on the jumper positions. Refer to figure 18 for identification.
JP46
13 PIN PLUG
(BOARD TO MOTOR)
1
2
3
4
TEST
+
NORM
1
2
3
4
HEATING SPEED SELECTOR PINS
See table 7 for VSP3−1
factory settings
COOL SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG (BOARD TO VARIOUS POINTS IN FURNACE)
JP1
1
HTG.
BLOWER
12
HEAT
DS2
ON/OFF
FIGURE 18
DS3
HI/LOW
DS1
270
210
150
DS4
CFM
OPERATIONAL
SELECTOR PINS
(Affects both heating
and cooling modes)
DIAGNOSTIC
DS LEDS
90
FAN OFF"
TIMING PINS
Page 17
VSP3−1 BLOWER CONTROL BOARD (A24)
1
J46
DELAY COOL ADJUST HEAT
1 2 3 4
HTG.
BLOWER
1 2 3 4
HEAT
DS3
TEST
− + NORM
HI/LOW
1 2 3 4
DS4
IMPORTANT
24 VAC half wave rectified (DC pulse), when measured with a meter, may appear as a lower or higher voltage depending on the make of the meter. Rather than attempting to measure the output voltage of A24, see GHR32V BLOWER & VSP3 BLOWER CONTROL BOARD TROUBLE­SHOOTING FLOW CHART in the TROUBLE­SHOOTING section of this manual.
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control. PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output. PIN 13 - 24V - Input 24 VAC power for the VSP2-1. PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 4 - Delay Tap - Delay profile programming input.
PIN 5 - Cooling blower speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor with CCB1 and
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common. PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
PIN 1 - Not Used.
PIN 8 - NOT USED
HARMONY only
DS1
270
CFM
210
90
150
Diagnostic LED Lights
DS3 ON/OFF
ON/OFF−DS3 indicates there is a demand for the blower
motor to run. When the ON/OFF LED−DS3 is lit, a demand is being sent to the motor. In heating mode only, there is a 45−second fan ON" delay in energizing ON/OFF LED− DS3. Light will not go off until adjustable fan OFF" delay has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1 & HEAT LED−DS2 are off, the motor will operate in low speed (heating).
DS2 HEAT
If HEAT LED−DS2 is on, the blower is running in second− stage heat speed according to the HEAT" jumper setting. In heating mode only, there is a 45 second delay in energiz­ing HEAT LED−DS2. Light will not go off until adjustable fan OFF" delay has expired.
DS1 HI/LOW
HIGH/LOW LED−DS1 indicates the blower is operating in
the cooling mode.
DS4 CFM
CFM LED−DS4 indicates the CFM the blower is providing,
according to the jumper settings.
VOLTAGES INTO VSP3−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0
volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage) if CCB is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP3−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx. 34 volts
0
volts
Voltage across J46 pin 9 to 3 is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pin 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
a voltage of 0−25VDC should be present.
24VAC Half-Rectified (DC
FIGURE 19
Pulse)
@ 60Hz.
Page 18
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
IMPORTANT
Before changing jumper setting, make sure the motor has completely stopped. Any jumper set­ting change will not take place while the motor is running.
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and condi­tions associated with each one. Refer to figure 18 for identifica­tion.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in the blower performance tables. Using the tables, determine which row of CFM volumes most closely matches the desired CFM. Once a specific row has been chosen (NORMAL or −), CFM volumes from other rows cannot be used. Below are the descriptions of each of the jumper selections.
Refer to table 7 for factory settings.
TABLE 7
VSP FACTORY SETTINGS FOR GHR32V−4 UNITS
MODEL DELAY COOL ADJUST HEAT
GHR32V3−75 4 4 NORM 3
GHR32V5−100 4 4 NORM 2
NOTE − In Harmony II zoning applications in the heating mode, the highest cooling speed selected is the highest blower speed obtainable. Also, the fan−only speed is used when the primary lim­it has been tripped. In non−zoning applications, refer to the section on the VSP3−1 control.
ADJUST
The ADJUST pins allow the motor to run at normal speed or approximately 15% lower than normal speed. The blow­er performance tables two rows (NORMAL and −) with their respective CFM volumes. The + adjustment setting is not operable. Notice that the normal adjustment setting for heat speed position #3 is 2150 CFM (1015 L/s) . After the adjustment setting has been determined, choose the re­mainder speed jumper settings from those in the table.
The TEST pin is available to bypass the VSP3−1 control and run the motor at approximately 70% to test that the motor is operational. This is beneficial primarily in troubleshooting. G must be energized for motor to run.
HTG. BLOWER
For GHR32V−4 units only, place the HTG. BLOWER jump­er across the second and third pins (position #2).
NOTE − In Harmony II zoning applications, HTG. BLOWER jumper must be in position #2.
HEAT
The HEAT jumper is used to set the blower speed to obtain the required CFM as outlined in HEAT SPEED section of the blower performance tables. The HEAT jumper selec- tions are activated with a call for first−stage heating (W1) and second−stage heating (W2).
DELAY
The DELAY jumper is used to set the specific motor fan mode of operation during cooling. Depending on the ap­plication, one of four fan options may be chosen by moving the jumper to the appropriate set of pins.
Options 1, 2, 3, or 4 will have an increased dehumidification effect on the system. Option 1 will have the least effect and option 4 will have the greatest effect.
#1 PIN JUMPERED
A − Motor runs at 100% until demand is satisfied. B − Once demand is met, motor ramps down to off.
A B
100% CFM
COOLING DEMAND
OFFOFF
#2 PIN JUMPERED
A − Motor runs at 82% for approximately 7−1/2 minutes. B − If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
C − Once demand is met, motor ramps down to off.
C
OFF
OFF
A
7 1/2 MIN
82%CFM
B
100% CFM
COOLING DEMAND
#3 PIN JUMPERED A − Motor runs at 50% for 1/2 minute. B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor ramps down to off.
C D
100% CFM
OFF
OFF
A
1/2 MIN 50% CFM
B
7 1/2 MIN 82% CFM
COOLING DEMAND
Page 19
#4 PIN JUMPERED A − Motor runs at 50% for 1/2 minute. B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor runs at 50% for 1/2 min-
ute.
E − Motor ramps down to off.
C D
100% CFM
1/2 MIN 50% CFM
E
OFF
OFF
A
1/2 MIN 50% CFM
B
7 1/2 MIN 82% CFM
COOLING DEMAND
COOL
The cool jumper is used to set the blower speed to obtain the required CFM as outlined in the blower performance tables.
VSP Operation
Table 8 outlines the operation of the variable speed motor in relation to specific modes of operation. See table 9 for GHR32V with CCB1 and a two speed outdoor unit. Some information has been repeated from the previous section to provide an example. Refer to each diagnostic LED or jump­er settings section for more information.
Heating Mode Cooling Mode
Units With
Single−Stage Heating
Non−Zoned Applications
Using a single−stage thermostat with "one−stage" heating, the HEAT LED−DS2 is lit when the thermostat calls for heat. The ON/OFF LED− DS3 is lit after 110 seconds (65 sec­onds prepurge and 45 seconds fan "ON" time) from the time a call for heat is made. This indicates the blower is operating in high speed heat.
Using a single−stage thermostat with "W2 TIMED" and W1 calling, the ON/OFF LED−DS3 is lit to indi­cate the blower is operating on low speed heat.
When HEAT LED−DS2 is lit, the blower is operating in high speed heat and second−stage (W2) is call­ing.
Harmony Zoned Applications
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED− DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
Note − In Harmony II zoning ap­plications, HTG BLOWER jumper must be in position #2.
GHR32V−4 Units with VSP3−1
TABLE 8
Units With
Two−Stage Heating
Non−Zoned Applications
Using a two−stage thermostat with first−stage (W1) calling, the ON/ OFF LED−DS3 is lit to indicate the blower is operating in low speed heat.
When the ON/OFF LED−DS3 and HEAT LED−DS2 are lit, the blower is operating in high speed heat and second−stage (W2) is calling.
HEAT LED−DS2 is lit with a call for heat from the thermostat. ON/OFF LED−DS3 is after 110 seconds from the time a call for heat is made.
Harmony Zoned Application
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED− DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
Note − In Harmony II zoning applica­tions, HTG BLOWER jumper must be in position #2.
Units With
Single−speed Compressor
Non−Zoned Applications
Y1−DS and Y1−Y2 must be jump­ered together. With a call for cool­ing, G, Y1, Y2 and DS on the unit control board are energized from the thermostat. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to in­dicate a call for cooling.
Note − Y1 to DS and Y1 to Y2 are factory jumpered for single−stage cooling, non−zoned applications.
Harmony Zoned Application
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the termi­nal strip’s DS terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the blower is oper­ating.
Units With
Two−speed Compressor
Non−Zoned Applications
Y1−DS must be jumpered together. With a call for single−stage cooling, G, Y1, and DS on the unit control board are energized from the Ther­mostat. With a call for second−stage cooling, G, Y1, Y2, and DS on the unit control board are energized from the thermostat. In both cases, HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate a call for cooling.
Note − Jumper Y1−Y2 must be re­moved for units with two−speed compressor.
Harmony Zoned Application
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED− DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
NOTE − For zone applications with Harmony, remove the wire from pin #2 and pin #13 of the J49 terminal at the motor and the wire from pin #3 of the J73 terminal on the VSP control board, insulate the ends and secure to prevent shorting.
Page 20
TABLE 9
p
Normal operation
blower speed follow thermostat
removal during 1st
ifi
ill i
,
When humidity demand is satisfied
satisfied during
th
gp p
Call f
idit
g
Call for 1st stage
Call for 2nd stage
Reduced blower speed (dehumidifi-
mostat demand), slide switch is
GHR32V−4 UNITS WITH CCB1 & TWO−SPEED OUTDOOR UNIT OPERATING SEQUENCE
Operating Sequence System Demand System Response
System
Condition
Step
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
***Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Call for humidity
removal during 1st
stage thermostat
demand
Significant increase
in humidity during
thermostat demand.
Humidity demand
satisfied during
thermostat demand.
or hum
removal during 2nd
stage thermostat
demand
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase
in humidity
Humidity demand satisfied between
thermostat demands
(unit off cycle).
y
1 Y1 Acceptable (None) Low
2 Y2 Acceptable (None) High HIGH COOL
1 Y1 Acceptable (None) Low
2 Y1
Demand
3
satisfied
4 Y1 Slightly over setpoint (1) High
1 Y1 Acceptable (None) Low
2 Y1
1 Y1 Over Setpoint High
2 Y1
3 None Acceptable (None) Off Off
4 Y1 Acceptable (None) Low
1 Y2 Acceptable (None) High HIGH COOL
2 Y2
3 Y2 Acceptable (None) High HIGH COOL
1 None Slightly over setpoint (1) Off Off Dehumidification mode (high speed
2 Y1 Slightly over setpoint (1) Low
1 None Slightly over setpoint (1) Off Off
2 Y2 Slightly over setpoint (1) High
1 None
2 Y1 or Y2
1 None Over setpoint (1 or more) Off Off
2 Y1 or Y2
Change to slightly
over setpoint (1)
Slightly over setpoint (1) Off Off
Change to significantly
over setpoint (2 or more)
Change to Acceptable
(None)
Change to slightly
over setpoint (1)
Significantly over setpoint
(2 or more)
Significantly over
setpoint (2 or more
Change to
acceptable (None)
Low
High
High HIGH COOL
High
Off Off
High
High HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
Compressor demand and indoor
blower s
Dehumidification mode begins with
next thermostat demand, after initial
thermostat demand is satisfied.
If humidity increases significantly
over setpoint, or if slide switch is
moved sign
ately go into dehumidification mode
(in presence of thermostat demand).
When humidity demand is satisfied
blower immediately shifts to the
HIGH COOL CFM in order to hasten
e end of the cycle. Unit can only
shift out of high speed compressor
operation at beginning of next cycle.
Blower immediately changes speed
in response to thermostat demand.
compressor) begins with next ther-
mostat demand after initial demand is
Reduced blower speed (dehumidifi-
cation speed) begins immediately
If humidity increases significantly
over setpoint, or if slide switch is
moved, unit immediately goes into
dehumidification mode (in presence
While unit is not operating (no ther-
mostat demand), slide switch is
moved down and back up. Blower
and compressor operate at high
speed until next thermostat demand.
eed follow thermostat
demand
cantly, u nit w
satisfied.
with thermostat demand
of thermostat demand).
mmedi-
,
Note − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther­mostat heating demand.
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed indefinitely. To reset, move humidity slide switch all the way down then back up to desired setpoint (with unit running) ** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5. ***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compres­sor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 21
8.Two Stage Integrated Control (A92) GHR32Q−5 Units
DANGER
Shock hazard.
Disconnect power before servicing. Control is not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
All GHR32Q units are equipped with the Lennox two− stage integrated SureLight control board. The system consists of a ignition control board (figure 20 with control terminal designations in tables 12, 13 and 14) and ignitor (figure 8). The board and ignitor work in combination to en­sure furnace ignition and ignitor durability. The board con­trols all major furnace operations. The board features two LED lights, DS1 and DS2 for troubleshooting. The board also has two accessory terminals rated at (1) one amp each. See table 15 for troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heat cycle, SureLight control mon­itors the first stage and second stage combustion air induc­er prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by−passed). Like­wise the control will not begin the second stage heating cycle if the second stage prove switch is closed and will al­low first stage heat only. However if the second stage prove switch closes during the first stage pre−purge, the control will still respond to second stage heat. Once the first stage prove switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−min­ute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. The ignitor energizes during the trial until flame is sensed. If ignition is not proved during the 4−second period, the control will try four more times with an inter purge and warm−up time between trials of 35 sec­onds. After a total of five trials for ignition (including the ini­tial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE thermostat or TWO−STAGE thermostat. The thermostat selection jumper E20, located just below dip switches 1 through 4 (figure 20), must be positioned for the particular application. The jumper is factory set on TWO" for use with a two−stage thermostat with two stage heat. Re−posi­tion jumper to SINGLE" for use with a single stage thermo­stat with two stage heat. While in the single−stage thermostat mode (single jumper setting), the burners will always fire on first−stage heat. The combustion air inducer will operate on low speed and in­door blower will operate on low heat speed. After a field se­lectable 10 or 15 minute delay (dip switch 3), the unit will switch to second stage heat. While in the two−stage ther­mostat mode (two jumper setting) the burners will fire on first−stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second−stage heat on call from the indoor thermostat. If there is a simultaneous call for W1 and W2 (first and second stage heat) the unit will fire on first stage heat and will switch to second stage heat after 30 seconds of operation. See Sequence of Operation flow charts in the back of this manual for more detail.
Dip Switch Settings
Dip Switches 1 and 2 − Heating Fan off Delay − The fan on
time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satis­fied) can be adjusted by flipping the dip switches 1 and 2 located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. For customized comfort, monitor the supply air temperature once the heat demand is satisfied. Note the supply air temperature at the instant the blower is de−ener­gized. Adjust the fan−off delay to achieve a supply air tem­perature between 90° − 110° at the instant the blower is de− energized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher air tem­perature). See table 10 for dip switch settings.
TABLE 10
Heating Fan Off Delay
Delay (Seconds)
60 Off Off
90 Off On 120 On Off 180 On On
Switch 3 − Second Stage Delay (Used with Single−Stage Thermostat Only) −− This switch is used to determine the
second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the ON position, which provides a 10−minute delay before second−stage heat is initiated. If the switch is toggled to the OFF position,
Switch 1 Switch 2
Page 22
it will provide a 15−minute delay before second−stage heat is initiated. This switch is only activated when the thermo­stat selector jumper is positioned for SINGLE−stage ther­mostat use.
Switch 4 − Cooling Fan off Delay − The fan on delay time of 2 seconds is not adjustable. Fan off time (time that the blower operates after the cool demand has been satisfied) can be adjusted by flipping dip switch 4. The unit is shipped with a factory fan off setting of 45 seconds. Fan off time will affect comfort and is adjustable to satisfy individual ap­plications. See table 11 for cool fan off time settings.
TABLE 11
Cooling Fan Off Delay
Delay (Seconds) Switch 4
2 Off
45 On
Diagnostic LED’s (DS1 and DS2)
Two diagnostic LED’S are located on the two−stage inte­grated control board. See figure 20. These light flashes correspond with the codes detailed in table 15.
Factory Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the integrated control board terminal strip must be removed for two−stage cooling.
TABLE 12
Integrated Control Board Terminals
120VAC Neutral
LINE Line
XFMR Transformer
EAC Electronic Air Cleaner
CIRC Indoor Blower
HUM Humidifier
120VAC Line
HUM Humidifier
XMFR Transformer
LINE Line
PARK For Unused Leads
COOL Cooling Speed
EAC Electronic Air Cleaner
HI HEAT High Heat Speed
LO HEAT Low Heat, Low Cool and Continuous Fan
Speed
TWO−STAGE INTEGRATED CONTROL BOARD
SWITCHES
SENSOR
FACTORY−
INSTALLED
JUMPER
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH(ES) FUNCTION
1 and 2 Blower Off Delay (Heating Mode)
3 Second Stage ON Delay (Single−stage t’stat) 4 Blower Off Delay (Cooling Mode)
FIGURE 20
LEDs
DIP
1 − 4
Page 23
TABLE 13
ONONON
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
Integrated Control Board 5 Pin Terminal
PIN # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
Integrated Control Board 12Pin Terminal
PIN # Function
1 Gas Valve 2nd Stage (High Fire)
2 Second Stage Prove Switch
3 Not Used
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve 1st stage (Low Fire)
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Out
12 1st Stage Prove Switch
TABLE 14
TABLE 15
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 20 for location of diagnostic LEDs.
DS1 DS2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH ON
OFF SLOW FLASH
OFF FAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH OFF Flame sensed without gas valve energized.
ON ON
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation. Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes or unit goes into 1 hour Watchguard. Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes; OR lost flame sense 5 times in one heating cycle; OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts. (If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Minimum flame sense current = 0.17−0.22 microAmps.
Page 24
9.Two Stage Variable Speed Integrated Control (A92) GHR32V−5 Units
All GHR32V−5 units are equipped with the Lennox two− stage, variable speed integrated SureLight control board. The system consists of a ignition / blower control board (figure 21 with control terminal designations in tables 16 through 19) and ignitor (figure 8). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The SureLight integrated board controls all ma­jor furnace operations. The board features two LED lights, DS1 and DS2 for troubleshooting and four LED lights (DS3, DS6, DS7 and DS8) to show furnace status. The board also has two accessory terminals rated at (1) one amp each. See table 20 for status code and table 21 for troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heating cycle, the SureLight con­trol monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heat­ing cycle if the first stage prove switch is closed (by− passed). Likewise the control will not begin the second stage heating cycle if the second stage prove switch is closed, and will allow first stage heat only. However if the second stage prove switch closes during the first stage pre− purge, the control WILL respond to second stage heat call. Once the first stage prove switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. The ignitor energizes during the trial until flame is sensed. If ignition is not proved during the 4−second period, the control will try four more times with an inter purge and warm−up time between trials of 35 sec­onds. After a total of five trials for ignition (including the ini­tial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE thermostat or TWO−STAGE thermostat. The thermostat selection jumper E20, located just below dip switches 1 through 3 (figure 21), must be positioned for the particular application. The jumper is factory set on TWO" for use with a two−stage thermostat with two stage heat. Re−posi­tion jumper to SINGLE" for use with a single stage thermo­stat with two stage heat. While in the single−stage thermostat mode (single jumper setting), the burners will always fire on first−stage heat. The combustion air inducer will operate on low speed and in­door blower will operate on low heat speed. After a field se­lectable 10 or 15 minute delay (dip switch 3), the unit will switch to second stage heat. While in the two−stage ther­mostat mode (two jumper setting) the burners will fire on first−stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second−stage heat on call from the indoor thermostat. If there is a simultaneous call for W1 and W2 (first and second stage heat) the unit will fire on first stage heat and switch to second stage heat after 30 seconds of operation. See Sequence of Operation flow charts in the back of this manual for more detail.
TABLE 16
Two Stage Ignition / Blower Control Terminals
120VAC Neutral
LINE Line 120VAC Neutral
XFMR Transformer 120VAC Neutral
EAC Electronic Air Cleaner 120VAC Neutral
CIRC Indoor Blower 120VAC Neutral
HUM Humidifier 120VAC Neutral
120VAC Line
HUM Humidifier 120VAC Hot
XMFR Transformer 120VAC Hot
LINE Line 120VAC Hot
CIRC Indoor Blower 120VAC Hot
EAC Electronic Air Cleaner 120VAC Hot
TABLE 17
SureLight Board 5 Pin Terminal Designation
PIN # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
Page 25
TW0−STAGE, VARIABLE SPEED INTEGRATED
CONTROL BOARD
DIAGNOSTIC
LEDs
LEDs
DS8
DS7
ON−BOARD
JUMPER W914
(cut when CCB1 or
Harmony II are used)
FACTORY−
INSTALLED
DS3
JUMPER
16 PIN BLOWER
CONTROL TERMINALS
(cut when heat pump
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH FUNCTIONS
DIP SWITCH(ES) FUNCTION
1 and 2 Blower Off Delay
3 Second Stage ON Delay (Single−stage t’stat)
4 Not used 5 and 6 Cooling Mode Blower Speed 7 and 8 Blower Speed Adjustment
9 and 10 Cooling Mode Blower Ramping Profile
11 and 12 Heating Mode Blower Speed
SWITCHES
SWITCHES
ON−BOARD
JUMPER W951
is used with FM21)
DIP
1 − 3
E20
JUMPER
DIP
5 − 12
LED DS6
TABLE 18
SureLight Board 12Pin Terminal Designation
PIN # Function
1 Gas Valve 2nd. Stage (High Fire)
2 Second Stage Pressure Switch
3 Not Used
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve 1st. Stage (Low Fire)
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Out
12 1st Stage Pressure Switch
TABLE 19
SureLight Board 16 Pin Blower Control Terminals
PIN # Function
1 Ground
2 Low Heat Speed
3 Ground
4 DELAY" Dip Switch Selection
5 COOL" Dip Switch Selection
6 Y1" Signal
7 ADJUST" Dip Switch Selection
8 Ground
9 O" From Thermostat
10 DS" Output Signal
11 HEAT" Dip Switch Selection
12 24 VAC
13 HIGH HEAT Speed
14 Y2" Signal
15 G"
16 CFM LED
FIGURE 21
Page 26
TABLE 20
ONONON
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
STATUS CODES
STATUS LED COLOR FUNCTION
DS3
ON / OFF ’
DS6
CFM"
DS7
HI / LO"
DS8
HEAT"
GREEN
GREEN
YELLOW
YELLOW DS8−ON indicates the sytem is in HEAT mode.
DS3−ON indicates that the motor has a demand to operate. (This LED must be on in all modes).
DS6−blinking indicates the airflow (CFM) demand in the motor. The air flow is determined by counting blinks between two (2) second pauses. One blink equals roughly 100 CFM.
DS7−ON indicaties the DS to R" jumper has not been cut. When the jumper is cut the system will be operating with LENNOX HARMONY IIt (See Harmony Installation Instructions) or with the CCB1 Efficiency Plus control. CCB1: When ON, a 24 VAC is being applied and when OFF, it has been removed. This on/off operation varies the indoor blower’s performance so dehumidification can be enhanced.
TABLE 21
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 21 for location of diagnostic LEDs.
DS1 DS2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH ON
OFF SLOW FLASH
OFF FAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH OFF Flame sensed without gas valve energized.
ON ON
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation. Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes or unit goes into 1 hour Watchguard. Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes; OR lost flame sense 5 times in one heating cycle; OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts. (If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Minimum flame sense current = 0.17−0.22 microAmps.
Page 27
Dip Switch Settings Switches 1 and 2 − Blower Off Delay The blower−on delay
of 45 seconds is not adjustable. The blower−off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 1 and 2 on the integrated control board. The unit is shipped from the factory with a blower−off delay of 90 seconds. The blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatu­res.The table below provides the blower off timings that will result from different switch settings.
TABLE 22
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 1 Switch 2
60 Off Off
90 Off On 120 On Off 180 On On
Switch 3 − Second Stage Delay (Used with Single−Stage Thermostat Only) This switch is used to determine the
second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the ON position, which provides a 10−minute delay before second−stage heat is initiated. If the switch is toggled to the OFF position, it will provide a 15−minute delay before second−stage heat is initiated. This switch is only activated when the thermo­stat selector jumper is positioned for SINGLE−stage ther­mostat use.
Switch 4 − Not used
Switches 5 and 6 − Cooling Mode Blower Speed
Switches 5 and 6 are used to select cooling blower motor speed. The unit is shipped from the factory with the dip switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below pro­vides the cooling mode blower speeds that will result from different switch settings. Refer to blower data tables at the front of this manual for corresponding cfm values.
Cooling Mode Blower Speeds
TABLE 23
Speed Switch 5 Switch 6
1 − Low On On
2 − Medium Low Off On
3 − Medium High On Off
4 − High (Factory) Off Off
Switches 7 and 8 − Blower Speed Adjustment Switches 7 and 8 are used to select blower speed adjustment set­tings. The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or −10% to better suit the application. The table be­low provides blower speed adjustments that will result from different switch settings. Refer to blower data tables at the front of this manual for corresponding cfm values.
TABLE 24
Blower Speed Adjustment
Adjustment Switch 7 Switch 8
+10% (approx.) On Off
NORMAL (Factory) Off Off
−10% (approx.) Off On
Switches 9 and 10 − Cooling Mode Blower Speed Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramp­ing may be used to enhance dehumidification perfor­mance. The switches are factory set at option A which has the greatest effect on blower motor performance. The table below provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed on the next page. See unit nameplate for manufacturing date.
TABLE 25
Cooling Mode Blower Speed Ramping
Ramping Option Switch 9 Switch 10
A (Factory) Off Off
B On Off C Off On
D* On On
*Only option for CCB1
Page 28
GHR32V units manufactured before April 2003
Ramping Option A (Factory Selection)
D Motor runs at 50% for 1/2 minute. D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 1/2 min-
ute.
D Motor ramps down to off.
GHR32V units manufactured April 2003 and later
Ramping Option A (Factory Selection)
S Motor runs at 50% for 30 seconds. S Motor then runs at 82% for approximately 7−1/2 min-
utes. If demand has not been satisfied after 7−1/2 min­utes.
S Motor runs at 100% until demand is satisfied. S Once demand is met, motor runs at 50% for 30 sec-
onds then −
S ramps down to stop.
OFF
1/2 MIN 50% CFM
7−1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
D Motor runs at 50% for 1/2 minute. D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
1/2 MIN 50% CFM
7−1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
D Motor runs at 82% for approximately 7−1/2 minutes. D If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
7−1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes −
S motor runs at 100% until demand is satisfied. S Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN 82%CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 60 sec-
onds. Then,
S ramps down to stop.
OFF
100% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option D
D Motor runs at 100% until demand is satisfied. D Once demand is met, motor ramps down to off.
100% CFM
COOLING DEMAND
Ramping Option D
SMotor runs at 100% until demand is satisfied.
SOnce demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING DEMAND
OFFOFF
Page 29
Switches 11 and 12 − Heating Mode Blower Speed
idi
Dehumidification mode begins when rela
satisfied between
d
lid
d
Switches 11 and 12 are used to select heating mode blower motor speed. The unit is shipped from the factory with the dip switches positioned for medium low (2) speed indoor blower motor operation during the heating mode. The table below provides the heating mode blower speeds that will result from different switch settings. Refer to blower data tables at the front of this manual for corresponding cfm val­ues.
TABLE 26
Heating Mode Blower Speeds
Speed Switch 11 Switch 12
1 − Low On On
2 − Medium Low
(Factory)
Off On
3 − Medium High On Off
4 − High Off Off
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and R on the integrated control board, must be cut when the fur­nace is installed with either the Harmony II zone control board or the CCB1 EfficiencyPlus humidity control. Refer to table 27 for operation sequence in applications including a GHR32V, CCB1 and single−speed outdoor unit. Table 28 gives the operation sequence in applications with a two− speed outdoor unit.
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the fur­nace is installed in applications which include a heat pump unit and the FM21 FuelMaster control board.
Factory−Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the integrated control board terminal strip must be removed if two−stage cooling will be used.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two−stage, vari­able speed integrated control just to the left of the first bank of dip switches. These lights’ flashes correspond with diag­nostic codes detailed on in table 15.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate operating status. The green ON/OFF LED is lit any time the blower is operating. The green CFM LED indicates the blower motor speed. Count the number of blinks between the two−second pauses to determine the CFM. Each blink represents approximately 100 CFM. The yellow HI/LO LED is lit when the W914 (DS to R) jumper has not been clipped for CCB1 or Harmony operation. The yellow HEAT LED is lit when the indoor blower is operating at the HEATING speed.
Table 27
Operating Sequence
GHR32V−5, CCB1 and Single−Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System Condition
Normal operation Y1
*Call for humidity
removal during
cooling demand Dehumidification demand satisfied
during cooling demand.
Call for cooling after
call for hum
removal.
Humidity demand satisfied between
thermostat demands
(unit off cycle).
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther­mostat heating demand. * Reduced blower speed is 77% of COOL for V3 units and 74% of COOL for the V5 units.
ty
Thermostat
Demand
Y1
Y1
None
Y1
None Over setpoint (1 or more) Off
Y1 Change to acceptable COOL
*Relative Humidity
(EfficiencyPlus Lights)
No demand. Humidity
level is acceptable
Humidity level rises
above setpoint. Demand
initiated.
Humidity level falls below
setpoint. No demand
Humidity level above set-
point. Demand initiated.
Humidity level above set-
point. Demand initiated.
Blower
CFM
(COOL)
COOL
77%/74% of COOL
COOL
Off
77%/74%
of COOL
Comments
Compressor demand and indoor blower speed controlled by thermostat demand.
Call for dehumidification initiated by CCB1 control. Indoor blower speed reduced by CCB1 control. When humidity demand is satisfied, blow­er speed immediately increases to the COOL CFM to hasten the end of the cycle.
Dehumidification mode begins when rela­tive humidity is greater than setpoint.
While unit is not operating (no thermostat
emand), s
back up. Blower operates at COOL CFM.
e switch is moved down an
Page 30
Loading...
+ 69 hidden pages