Lennox GCS16-240, GCS16-120, GCS16-072, GCS16-090, GCS16-180 User's Information Manual

...
Page 1
See unit nameplate for manufacturer and address.
504,502M 8/2002
Supersedes 10/2001
AWARNING 150, 180,
GCS16-072, 090,
(6, 7-1/2, 10, 12-1/2, 15, 20 TON)
UNITS
READ ALL INSTRUCTIONS IN THIS MANUAL
AND RETAIN FOR FUTURE REFERENCE
FBR113270
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
Installation and service must be per- formed by a qualified installer, ser- vice agency or the gas supplier.
GCS16-090, 120, 150 SHOWN
-&WARNING
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Extinguish any open flames.
Do not touch any electrical switch; do not
use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas suppli-
er's instructions.
If you cannot reach your gas supplier, call
the fire department.
TeChnical
blications
Lithe U.S.A.
G_)2002
08/02
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIll
504,502M
IIIllllllllllllllllllllllllllHIIIIIIIIlllll
Page 2
CONDENSER FAN
(2 ON -120 & -150 UNITS)
CONDENSER
FILTERS (4)
EVAPORATOR
COIL
HEAT EXCHANGERTUBES
COMBUSTION AIR
INDUCER
COIL
CONTROLBOX_
SIDE POWER ENTRY
(-072, -090 UNITS)
COMPRESSORS
(10N-072UNITS)
CONDENSER FANS (2)
FILTERS (6)
FRONT POWER ENTRY
(-120 & -150 UNITS)
EVAPORATOR COIL
FLUE BOX
COVER
GAS VALVE
BURNERS
CONDENSATE DRAIN
BOTTOM POWER ENTRY
BLOWER MOTOR (Requires additionalfield-installed kit;
refer to "Electrical Connections" section)
HEAT EXCHANGERTUBES
COMBUSTION
AIRINDUCER
CONDENSER COIL
CONTROL
COMPRESSORS(3)
COVER
IGNITION CONTROL
GAS VALVE
CONDENSATE DRAIN
BLOWER MOTOR
POWER ENTRY
BOTTOM POWER ENTRY
Page 1
Page 3
, ,WARNING
-
Keep gas heat section clear and free of combustible materials, gasoline and other flammable vapors and
liquids,
.
Inspect return air duct to ensure duct is sealed to the curb external to the unit,
-
Inspect physical support of unit to guarantee that it is sound without sagging, cracks, or gaps around base, On downflow units, seal between base and support
must also be checked to make sure it is tight,
-
Do notobstruct air flow around unit, Unit must receive an unobstructed flow of combustion and ventilating air.
,&,WARNING
,&IMPORTANT
A,WARNING
,&,CAUTION
,&WARNING
,&WARNING
,&WARNING
FOR YOUR SAFETY READ BEFORE LIGHTING BEFORE LIGHTING smell all around the furnace area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor,
Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire
or explosion.
,&,WARNING
Page 2
Page 4
,WARNING
This unit is equipped with an automatic spark ignition system. There is no pilot. In case of a safety shutdown,
move thermostat switch to OFF and return the thermostat switch to HEAT to reset ignition control. See figure 1. For
units which have electronic temperature control devices, shut off the main disconnect and return it to the on position
to reset the ignition control.
HEAT I!! lil COOL
/_ THERMOSTAT .
50 60 70 80
10 15 20 2530
\\\\'_\\\"III1"////'1111
I II I
7- Turn the knob on the gas valve counterclockwise41_
to "ON". Do not force.
8- Close or replace the heat section access panel. 9- Turn on all electrical power to furnace.
10- Set thermostat to desired setting. 11- The combustion air inducer will start. The burners will
light within 40 seconds.
12- If the furnace does not light the first time (gas line not
fully purged), it will attempt up to two more ignitions before locking out.
WHITE RODGERS 36C76 GAS VALVE
STAGE2 MANIFOLD
INLET
PRESSURE
PRESSURE ADJUSTMENT
SCREW UNDER CAP
MANIFOLD
PRESSURE
TAP_SIDE)
FAN ON HEAT OFF COOL
I
FIGURE 1
A-Placing Unit In Operation
,WARNING
Gas Valve Operation for White Rodgers 36C (figure 2) and Honeywell VR8305Q (figure 3)
1- Set thermostat to lowest setting.
2- Turn off all electrical power to furnace.
3- This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by hand.
4- Open or remove the heat section access panel.
5- Turn the knob on the gas valve clockwise 4_ to
"OFF". Depress 36C knob slightly. Do not force.
6- Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions. If you do not smell gas, go to the next step.
Page 3
FIGURE 2
HONEYWELL VR8305Q SERIES GAS VALVE
HIGH FIRE ADJUSTMENT
ADJUSTMENT
LOW FIRE
MANIFOLD
PRESSURE
TAP
,
PRESSURE I(( _ _ 4'''_t_" ,
TAP L._._=Vi oF_/
Gas valve knob is shown in OFF position,
FIGURE 3
13- If lockout occurs, repeat steps 1 through 10. 14- If the furnace will not operate, follow the instructions
"Turning Off Gas to Furnace" and call your service technician or gas supplier.
Page 5
Turning Off Gas to Furnace
-
If using an electromechanical thermostat, set to the lowest setting.
2-
Before performing any service, turn off all electrical power to the furnace.
&CAUTION
3- Open or remove the heat section access panel.
4- Turn the knob on the gas valve clockwise _1_ to
"OFF". Depress 36C knob slightly. Do not force.
5- Replace heat section access panel.
The combustion air pressure switch checks the combustion air inducer operation before allowing power
to the ignition controller. Ignition controller will not operate if blower is obstructed.
Under normal operating conditions, the combustion air blower wheel should be inspected prior to heating
season. With power supply disconnected, the condition of the blower wheel can be determined by removing the
vent cap assembly and looking through the exhaust vent. Remove any deposits of debris from vent cap assembly before reinstalling it on unit. If cleaning
combustion air inducer is necessary, contact a qualified service technician. See figure 4 and 5.
To maintain efficiency and longevity, your equipment must be serviced yearly by a qualified service technician. Failure to provide proof of service can void warranty.
GAS HEAT SECTION - 072,090
._OMBUSTION _-- _,IRINDUCER
COMBUSTION AIR LOUVERS
MANUALKNOB
GAS VALVE --_
VENT
CAP
O
BURNERS /
FIGURE 4
GAS HEAT SECTION - 120, 150, 180, 240
I
&WARNING
&WARNING
The primary air is permanently set for normal operation. The flame will be basically blue with some clear yellow
streaking in the end of the flame. Inspect burner flame periodically during heating season using inspection port
provided on the burner access panel.
Page 4
;OMBUSTION . _IRINDUCER
COMBUSTION AIR LOUVERS
MANUALKNOB
GAS VALVE --_
VENT CAP
O
BURNERS _
FIGURE 5
A-Servicing Filter
GCS16 units are equipped with pleated 2" throwaway-type filters, Filters should be checked monthly and replaced when necessary with filters of like kind and size. Take note of air flow direction marking on
filter frame when reinstalling filters. See figure 6,
NOTE--Filters must be U.L,C, approved or equivalent for use in Canada,
Page 6
Unit Qty.
TABLE 1
FILTER SIZE
Filter Size - inches (mm)
To keep your heating and cooling system in peak operating condition year after year, contact a qualified service technician about a regular maintenance program.
072, 090 4
120
150
180, 240 6
B-Blower Motor
16 X 20 X 2 (406 X 508 X 51)
2
16 X 20 X 2 (406 X 508 X 51)
2
16 X 25 X 2 (406 X 635 X 51)
2
20 X 20 X 2 (508 X 508 X 51)
2
20 X 25 X 2 (508 X 635 X 51)
18 X 24 X 2 (457 X 610 X 51)
Blower motor is prelubricated. No further lubrication is required.
Contact a qualified service technician if the unit is inoperative. Before calling, always check the following
to be sure service is required:
1- Be sure electrical disconnect switches are ON.
2- Check room thermostat for proper setting.
3- Replace any blown fuses or reset circuit breakers.
4- Gas valve(s) should be ON for heating cycle.
5- Air filters should not be plugged, limiting air flow.
6- Make sure all access panels are in place.
FILTER REMOVAL
(Four Filters On -072, 090, 120 & 150 Units)
FIGURE 6
The following repair parts are available. When ordering parts, include the complete model number listed on either the
CSA International rating plate (e.g. GCS16-240-375-1Y) or the U.L.C.S.A. rating plate (e.g. CHA16-240-1 G)
Heat Section Parts
Heat Exchanger Combustion Air Inducer
Burner Assembly Ignition Lead
Ignition Control (A3)
Sensor Lead Combination Gas Valve Flue Baffle
Limit Control (S10) CAB Proving Switch (s18)
Auxiliary Limit Control (S21)
Burner Manifold Assembly Main Burner Orifices
Ignition Electrode Assembly Hi Heat Delay (DL3)
Rollout Switch (S47)
Cooling Parts Compressor High Pressure Switch (S4, S7)
Condenser Fan Motor Condenser Fan Blade
Cond, Fan Run Capacitors (C1, C2) Freezestat (S49, S50)
Cond, Fan Mount, Bracket Fan Grille
Blower Wheel Expansion Valve Distributor
Expansion Valve Indoor Blower Motor
Electrical Control Parts
Compressor Contactor (K1, K2) Transformer (Control) T1
Blower Contactor (K3) Limit, Blower Relay (K20)
Capacitor CAB (C3) Transformer (T3) (575/460V only)
Combustion Air Inducer Relay (K13)
Firestat Switches (S74, S75)
Blower Delay (K25) Low Amb. Pressure Sw. (S11, S84) Condenser Fan Contactor (K10) Reversing Valve
Crankcase Heater Relay (K191)
Page 5
Loading...