Lennox G61MPVT-36B-070, G61MPVT-60C-090, G61MPVT-60C-110, G61MPVT-60D-135 Installation Instructions Manual

INSTALLATION
E 2006 Lennox Industries Inc.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INSTRUCTIONS
G61MPVT SERIES UNITS
GAS UNITS
505,187M 06/2009
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G61MPVT Parts Arrangement 3. . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation − Setting Equipment 5. . . . . . . . . . . . . . . . . .
Filters 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe & Fittings Specifications 10. . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 11. . . . . . . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 12. . . . . . . . . . . . . . . . . . . . .
Venting Practices 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board 27. . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 35. . . . . . . . . . . . . . . . . . . . . .
Manifold Pressure & High Altitude Information 35. . . .
Other Unit Adjustments 36. . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 37. . . . . . . . . . . . . . . . .
Service 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Requirements 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 41. . . . . . . . . . . .
Ignition Control Board Diagnostic Codes 44. . . . . . . . .
Troubleshooting 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Pipe Sizing Worksheet 51. . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 52. . . . . . . . . . . . . .
Litho U.S.A.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
06/09
*2P0609*
WARNING
FIRE OR EXPLOSION HAZARD.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately. D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
Page 1
505,187M
*P505187M*
G61MPVT Unit Dimensions − mm
*60C and 60D size units installed in upflow applications that require air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. Required to maintain proper air velocity.
2. Single side return
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
Refer to Engineering Handbook for additional information.
**Consider sizing requirements for optional IAQ equip­ment before cutting side return opening.
one side return air.
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
SUPPLY AIR
OPENING
603
635
TOP VIEW
19
A
B
14
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
40
(1016)
295 Right
248 Left
165
103
124 Right
57 Left
140
171
165
79
724
COMBUSTION AIR INTAKE
(Either Side)
EXHAUST AIR OUTLET
(Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
ELECTRICAL INLET
(Either Side)
64
AIR FLOW
C
*Bottom Return
Air Opening
19
375
16
406
476
RECEPTACLE
102
IEC
108
584
*OPTIONAL
RETURN CUTOUT
(Either Side)
597
*Bottom Return
Air Opening
FRONT VIEW SIDE VIEW
378
14
356**
49
Model No.
G61MPVT−36B−070 446 416 406
G61MPVT−60C−090 G61MPVT−60C−110
G61MPVT−60D−135 622 594 584
A B C
mm mm mm
533 454 495
Page 2
G61MPVT Parts Arrangement
BURNER BOX
ASSEMBLY
GAS VALVE
AND MANIFOLD
FLUE
COLLAR
TOP CAP
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
CABINET
COMBUSTION
AIR PRESSURE
PROVE SWITCHES
COMBUSTION AIR
INDUCER
BURNER ACCESS
PANEL
BLOWER
ACCESS
PANEL
SIGHT
GLASS
DOOR
INTERLOCK
SWITCH
Two−Stage, Variable Speed
Integrated Control Board
WARM HEADER
(COLLECTOR)
BOX
CONDENSER COIL
PRIMARY LIMIT
COLD HEADER
(COLLECTOR)
BOX
SECONDARY
LIMITS (2)
BLOWER MOTOR
TRANSFORMER
CONTROL BOX
FIGURE 1
Page 3
G61MPVT Gas Furnace
The G61MPVT gas furnace is equipped with a two−stage, variable speed integrated control. This control ensures compatibility with a thermostat which provides humidity control. Each G61MPVT is shipped ready for installation in the upflow, downflow, horizontal left air discharge or horizontal right air discharge position. The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in upflow ap­plications with bottom return air. The bottom panel must also be removed and discarded in all downflow or horizon­tal applications.
The furnace is equipped for installation in natural gas ap­plications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
All G61MPVT models can be installed as a Direct Vent gas central furnace. G61MPVT−070, −090 and −110 mod­els can be installed as a Non−Direct Vent gas central fur­nace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination.
DIRECT VENT INSTALLATION NON−DIRECT VENT
COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
EXHAUST OUTLET
INSTALLATION
EXHAUST OUTLET
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G61MPVT unit 1 − Bag assembly containing the following:
3 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 2 − 2" diameter vent / intake plugs 1 − 3" diameter cabinet plug (intake) 2 − 2" diameter debris screen
1 − Bag assembly containing the following:
1− 50 hertz power wiring harness
NOTE − G61MPVT−60C−110 and −60D−135 units also in­clude two 50mm to 80mm diameter ABS street elbows and two 80mm to 50mm ABS reducing elbows, which are shipped on the blower deck in the heating compartment.
The following items may also be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Safety Information
CONDENSATE
DRAIN
G61MPVT
FIGURE 2
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
G61MPVT
CONDENSATE
DRAIN
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Page 4
Installation − Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
Upflow Applications
The G61MPVT gas furnace can be installed as shipped in the upflow position. Refer to figure 3 for clearances.
Installation Clearances
Top
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [610 mm (24 inches) at unit front]. The unit must be level from front to back and side
to side.
NOTE − G61MPVT−36B units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must
be removed before the furnace is placed into opera­tion. After the bolt and washer have been removed, the rig-
id leg will not touch the blower housing.
NOTE − G61MPVT−60D−135 units are equipped with a shipping pad under the blower housing. Remove the ship­ping pad prior to operation.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figures 3, 9 and 6.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
Left Side
Bottom (Floor)
Top/Plenum 25 mm (1 in.)
*Front 0
Back 0
Sides 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 610 mm (24 inch­es). Maintain a minimum of 610 mm (24 inches) for front service access. Allow proper clearances to accommodate condensate trap and vent pipe installation. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
Right Side
FIGURE 3
Return Air −− Upflow Units
NOTE − G61MPVT−135 models are not approved for installation in upflow air discharge applications.
Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 850 L/s (1800 cfm) are required with 60C or 60D models in an upflow applica­tion, the following return air options are available:
1 − Return air from single side with transition which will ac-
commodate508 x 635 x 25 mm (20 x 25 x 1 in.) air filter. (Required to maintain proper air velocity.) See figure 4.
2 − Return air from single side.
3 − Return air from bottom.
4 − Return air from both sides.
Page 5
5 − Return air from bottom and one side.
Refer to Engineering Handbook for additional information.
G61MPVT applications which include side return air and a condensate trap installed on the same side of the cabinet require either a return air base or field−fabri­cated transition to accommodate an optional IAQ ac­cessory taller than 368mm (14.5 inches).
Side Return Air
(with transition and filter)
508mm X635mm X 25mm
(20" X 25" X 1")
Air Filter
Return
Air
Plenum
Horizontal Applications
G61MPVT furnaces, with the exception of the G61MPVT−60D−135, can be installed in horizontal applica­tions with either right− or left−hand air discharge. The G61MPVT−60D−135 can only be installed in horizontal ap­plications with right−hand air discharge.
Refer to figure 6 for clearances in horizontal applications.
Horizontal Application
Installation Clearances
Right−Hand Discharge
Top
Left End Right End
Bottom (Floor)**
Left−Hand Discharge
Top
Left End Right End
Transition
FIGURE 4
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 5.
Removing the Bottom Panel
Screw
Bottom Cap
Bottom Panel
Bottom (Floor)**
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 610 mm (24 inch­es). Maintain a minimum of 610mm (24 inches) for front service ac­cess. **A 140mm (5−1/2) service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 6
This furnace may be installed in either a roof space or un­der floor. Install the furnace on a field−fabricated raised platform, as shown in figure 7. The unit must be supported at both ends and beneath the blower deck to prevent sag­ging.
NOTE − In horizontal applications, the unit must be lev­el side−to−side. The unit may be tilted back−to−front a maximum of 25mm (1 inch) to ensure proper draining of the heat exchanger. The heat exchanger coil will not
drain properly if the unit is tilted backward.
FIGURE 5
Page 6
TYPICAL HORIZONTAL ROOF SPACE INSTALLATION (FORCED AIR FURNACE)
INTAKE PIPE
NOTE − Condensate trap and
condensate line must be
protected by self−regulating
heating cable and insulation
when run through unconditioned
spaces.
CONDENSATE LINE
FIGURE 7
Platform Installation of Horizontal Unit in Roof Space
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 6.
2 − Construct a raised wooden frame and cover frame
with a plywood sheet. Provide a service platform for unit. A drain pan is also recommended.
EXHAUST PIPE
INTAKE
PIPE
GAS
CONNECTOR
RAISED PLATFORM
SERVICE PLATFORM
EXHAUST
PIPE
3 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
4 − Set unit in drain pan (if used) as shown in figure 7. Unit
must be level to ensure proper coil drainage. Leave 140mm (5−1/2 inches) for service clearance below unit for condensate trap.
5 − Continue with exhaust, condensate and intake piping
installation according to instructions.
Platform Installation of Horizontal
Unit Installed Under Floor
1 − Select location for unit, keeping in mind service and
other clearances.
EVAPORATOR COIL
FIGURE 8
2 − After positioning cement blocks, mount support frame
on top of blocks and install unit. Unit must be level to ensure proper heat exchanger coil drainage. Leave 140mm (5−1/2 inches) for service clearance) for con­densate trap.
3 − Install exhaust and intake piping according to informa-
tion given in following section.
Page 7
Return Air −− Horizontal Applications
Return air may be brought in only through the end of a fur­nace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 5.
Downflow Applications
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling cabi­net. Do not drag the unit across the floor in the down-
flow position. Flange damage will result. Refer to figure 9 for clearances in downflow applica­tions.
Downflow Application Installation Clearances
Top
Left Side
Right Side
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Model No.
B Cabinet (445mm) 19 − 3/4 502 16 − 5/8 422
C Cabinet (533mm) 19 − 3/4 502 20−1/8 511
D Cabinet (622mm) 19 − 3/4 502 23 − 5/8 600
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Front to Rear Side to Side
in. mm in. mm
Installation on Combustible Flooring
1 − When unit is installed on a combustible floor, an addi-
tive base must be installed between the furnace and the floor. The base must be ordered separately for the following cabinet sizes:
D B cabinet 445mm − # 11M60 D C cabinet 533mm − # 11M61 D D cabinet 622mm − # 11M62
See table 2 for opening size to cut in floor.
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 610mm (24 inches). Maintain a minimum of 610mm (24 inches) for front service ac­cess. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional additive base is installed between the furnace and the com­bustible floor.
FIGURE 9
Installation on Non−Combustible Flooring
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
CAUTION
The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma­terial other than wood flooring.
TABLE 2
ADDITIVE BASE FLOOR OPENING SIZE
Model
B Cabinet (445mm)
C Cabinet (533mm)
D Cabinet (622mm)
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 − Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
22 559 22 − 3/4 578
22 559 25 − 3/4 654
Page 8
G61MPVT UNIT
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
SUPPLY AIR PLENUM
PROPERLY
SIZED FLOOR
OPENING
ADDITIVE BASE
FIGURE 10
Installation on Cooling Cabinet
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position.The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 11 or 12).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
Side View
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
FIGURE 11
CABINET
SECURE FROM
INSIDE CABINET
Side View
SIDE PANEL
FIGURE 12
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended minimum filter sizes.
A filter must be in place when the unit is operating.
NOTE − In upflow applications where side return air fil­ter is installed on same side as the condensate trap, fil­ter rack must be installed beyond condensate trap to avoid interference.
TABLE 3
Furnace
Cabinet Size
445mm 406 X 635 X 25 (1) 406 X 635 X 25 (1)
533mm 406 X 635 X 25 (1) 508 X 635 X 25 (1)
622mm 406 X 635 X 25 (2) 610 X 635 X 25 (1)
Side Return Bottom Return
Filter Size −− mm
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Operation of this furnace in heating mode (indoor blower operating at selected heating speed) with an exter­nal static pressure which exceeds 200 Pa (0.8 inches w.c.) may result in erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed. If present, this ac­cess panel must always be in place when the furnace is op­erating and it must not allow leaks into the supply air duct system.
Return Air Plenum
Return air must not be drawn from a room where this furnace, or any other gas appliance (ie., a water heat­er), is installed. When return air is drawn from a room, a
negative pressure is created in the room. If a gas ap­pliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and
Page 9
into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe and fittings to be Pressure Pipe, Class E / Class 12 / Schedule 40 or equivalent
All pipe, fittings, primer and solvent cement must conform
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
Outdoor Ex­haust Accel-
erator
(Dia. X
Length)
40mm X
305mm
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
UNIT
MODEL
−070
−090
−110
−135
VENT
PIPE
DIA.
(in.)
50mm 1.2
80mm 2.4
100mm 4.3
50mm
80mm
100mm
80mm
100mm
80mm
100mm
*Requires field−provided and installed 40mm exhaust accelerator.
Outdoor Ex-
haust Accel-
erator
(Dia. X
Length)
50mm X
305mm
Not
Allowed
Not
Allowed
Not
Allowed
0.3
0.6
1.2
0.6
1.2
1.8
3.0
Concentric
(1−1/2")
71M80 60M29 60L46 22G44 44J40 15F74
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
TABLE 4
Vent Pipe Length Equivalency (meters)
40mm
Kit
3.6
7.3
12.8
Not
Not
Not
Not
Not
Not
Not
with Australian standards. The solvent shall be free flow­ing and contain no lumps, undissolved particles or any for­eign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
Table 4 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when sizing vent pipe. All Lennox vent terminations are PVC or ABS.
50mm (2")
Concentric
Kit
Not
Allowed
Not
Allowed
Not
Allowed
.9 .9
1.8 1.8
3.7 3.7
1.8 1.8
3.7 3.7
Not
Allowed
Not
Allowed
**Requires field−provided and installed 50mm exhaust accelerator.
80mm (3") Concentric
Kit
Not
Allowed
Not
Allowed
Not
Allowed
4.6
7.6
50mm (2")
Wall Plate
Kit
1.2 1.2* 1.2
2.4 2.4* 2.4
4.3 4.3* 4.3
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
80mm (3")
Wall Plate
Kit
0.3 0.3**
0.6 0.6**
1.2 1.2**
0.6 0.6
1.2 1.2
1.8
3.0
50mm (2")
Wall Ring
Kit
Not
Allowed
Not
Allowed
Page 10
Vent Piping Guidelines
G61MPVT furnaces, with the exception of the G61MPVT−60D−135, can be installed as either a Non−Di­rect Vent or a Direct Vent gas central furnace. The G61MPVT−60D−135 can only be installed as a Direct Vent (two pipe) gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −− Size pipe according to tables 5 and 6. Table 5 lists the mini­mum equivalent vent pipe lengths permitted. Table 6 lists the maximum equivalent pipe lengths permitted.
Maximum vent length is defined as:
Total length (linear meters) of pipe,
Plus Equivalent length (meters) of fittings, Plus Equivalent length (meters) of termination. NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 7.
NOTE − The exhaust pipe should be offset a minimum of 305mm (12 inches) to avoid the possibility of water droplets being released from the exhaust termination. The mini­mum exhaust vent length is 4.5m (15 feet). Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 305mm (12−inch) vertical offset.
Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 1.5m (5 feet ) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to .76m (2.5 feet) of vent pipe of the same diameter.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox for assistance in sizing vent pipe in these applications.
NOTE − The flue collar on all models is sized to accommo­date 50mm Schedule 40 / Class 12 / Class E pressure pipe. When vent pipe which is larger than 50mm must be used in an upflow application, a 50mm elbow must be ap­plied at the flue collar in order to properly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine acceptable vent lengths. Assign an equivalent meter value to this elbow according to the larger size pipe being used. Contact Lennox for more information concerning sizing of vent systems which include multiple pipe sizes.
305mm Min.
Upflow and Downflow Application
Rooftop Termination
305mm Min.
Horizontal Application
Rooftop Termination
Exhaust Pipe Offset
305mm Min.
Upflow and Downflow Application
Side Wall Termination
305mm Min.
Horizontal Application
Side Wall Termination
FIGURE 13
Page 11
Use the following steps to correctly size vent pipe diameter.
Refer to Vent Pipe Size Determination Worksheet on page 52.
1 − Determine the vent termination and its corresponding
equivalent meter value per table 6.
2 − Determine the number of 90° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent meters of vent pipe.
3 − Determine the number of 45° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent meters of vent pipe.
4 − Determine the length of straight pipe required.
5 − Add the total equivalent meters calculated in steps 1
through 4 and compare that length to the maximum values given in table 6 for the proposed vent pipe di­ameter. If the total equivalent length required exceeds the maximum equivalent length listed in the appropri­ate table, evaluate the next larger size pipe.
TABLE 5
MINIMUM VENT PIPE LENGTHS
G61MPVT
MODEL
070, 090
110***
135***
*Any approved termination may be added to the minimum equivalent length listed.
**G61MPVT−60C−110 and G61MPVT−60D−135 must have 90° street ell (sup­plied) installed directly into unit flue colla and 50mm to 80mm reducer (sup­plied) must be installed on the 50mm ell. NOTE − All 90° elbows used in configuration of vent, must be sweep el-
bows.
MIN. EQUIV.
VENT LENGTH
4.5m*
EXAMPLE
1.5m plus 2 elbows of 50mm or 80mm diameter pipe
1.5m plus 2 elbows of 80mm diameter pipe
1.5m plus 2 elbows of 80mm diameter pipe
TABLE 6
MAXIMUM VENT PIPE LENGTHS
MAXIMUM EQUIVALENT VENT
ALTITUDE
0 − 610m
611 −1372m
n/a −− Not allowed. *G61MPVT−60C−110 and G61MPVT−60D−135 must have 90° street ell (sup-
plied) installed directly into unit flue colla and 50mm to 80mm reducer (sup­plied) must be installed on the 50mm ell. NOTE − All 90° elbows used in configuration of vent, must be sweep el-
bows.
G61MPVT
MODEL
070 12.2 16.1 44
090 4.5 12.2 34.5 110* n/a 12.2 30 135* n/a 7.6 20
070 7.6 10 27.5
090 n/a 7.6 21.5 110* n/a 7.6 18.7 135* n/a n/a n/a
LENGTH METERS
50mm
dia.
80mm
dia.
100mm
dia.
IMPORTANT
The G61MPVT unit is not suitable for use at eleva­tions over 610m.
Joint Cementing Procedure
All cementing of joints should be done according to the relevant local authority.
WARNING
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply liberal coat of PVC primer for PVC or
ABS cleaner for ABS to inside socket surface of fitting and male end of pipe to depth of fitting socket.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn pipe 1/4 turn during as­sembly (but not after pipe is fully inserted) to distribute cement evenly.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Page 12
Venting Practices
1 − Use recommended piping materials for exhaust piping
(Class E / Class 12 / Schedule 40).
2 − Secure all joints so that they are gas-tight using ap-
proved cement.
downflow positions. Exhaust piping exits from the top of the unit in horizontal air discharge applications. Glue the field−provided exhaust vent pipe (or provided street ell or reducing ell in upflow or downflow applica­tions) to the flue collar. Refer to pipe and fittings speci­fications and gluing procedures.
Suspend piping using hangers at a minimum of every
1.52m (5 feet) for Schedule 40 vent pipe. A suitable hanger can be fabricated by using metal or plastic strapping or a large wire tie.
3 − In areas where piping
penetrates joists or interi­or walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
4 − Isolate piping at the point where it exits the outside wall
or roof in order to prevent transmission of vibration to the structure.
5 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
Exhaust Piping (Figures 15 and 16)
NOTE − Two 50mm diameter street ells and two 80mm to 50mm reducers are contained in a bag assembly strapped to the blower deck of 60C−110 and 60D−135 units. The street ells must be flue collar. See figure 15. The 80mm to 50mm reducers must be glued to the street ells in upflow or downflow
applications.
1 − Choose the appropriate side for venting in upflow or
glued directly into the unit
STRAPPING
(metal, plastic
or large wire
ties)
FIGURE 14
IMPORTANT
Exhaust piping and condensate trap must be installed on the same side of the unit in upflow and dowflow applications.
2 − All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 6mm (1/4") drop for each 305mm (12 inches) of horizontal run is mandatory for drainage. Horizontal runs of exhaust piping must be sup­ported every 1.5m (5 feet) using hangers.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
3 − On the opposite side of the cabinet, glue the provided
50mm vent plug into the unused flue collar.
4 − Route piping to outside of structure. Continue with
installation following instructions given in piping ter­mination section.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
Page 13
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
IN UPFLOW OR DOWNFLOW DIRECT OR NON−DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
80mm
PLUG
VENT PLUG
(Must be
glued in
place)
PLUG
*50mm diameter street elbow provided.
**80mm diameter reducing elbow provided.
***Limit pipe length to 50mm.
PLUG
50mm
CONDENSATE
TRAP
(Must be installed
on same side as
exhaust piping)
50mm
50mm
FIGURE 15
TYPICAL EXHAUST PIPE CONNECTIONS
HORIZONTAL DIRECT OR
NONDIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
*Limit pipe length to 50mm in G61MPVT−110 and −135 applications.
DO NOT transition from smaller to larger pipe size in horizontal runs.
80mm
TRANSITION
50mm
50mm
50mm
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110* G61MPVT−60D−135*
50mm
G61MPVT−36B−070 G61MPVT−60C−090
FIGURE 16
TRANSITION
50mm
50mm
50mm
80mm
TRANSITION
50mm***
50mm*
G61MPVT−110
with
80mm vent pipe
G61MPVT−070
or 090 with 80mm
vent pipe
80mm
80mm**
G61MPVT−135
with
80mm vent pipe
Intake Piping
G61MPVT furnaces, with the exception of the G61MPVT−60D−135, can be installed as either a Non−Di­rect Vent or a Direct Vent gas central furnace. The G61MPVT−60D−135 can only be installed as a Direct Vent (two pipe) gas central furnace. In non−direct vent ap-
plications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
The G61MPVT unit is designed for either left−side or right− side air intake connections in either upflow or downflow ap­plications. In horizontal applications, air intake must be brought in through the top. Intake air piping is independent of exhaust piping.
Follow the next four steps when installing the unit in direct vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors.
1 − Cement intake piping in slip connector located on the
side of the burner box.
2 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired. A pilot indentation is pro­vided in the slip connector to assist in locating and starting the fastener.
3 − Glue the provided 50mm plug into the unused air intake
connector on the opposite side of the cabinet.
4 − Route piping to outside of structure. Continue with
installation following instructions given in general guide lines for piping terminations and in intake and exhaust piping terminations for direct vent sections. Refer to figure 17 for pipe sizes.
Page 14
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
50mm
PLUG
(Must be
glued in
place)
50mm
50mm
G61MPVT−36B−070 G61MPVT−60C−090
FIGURE 17
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL DIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
80mm
TRANSITION
80mm
50mm*
50mm*
TRANSITION
50mm*
50mm
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110*
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110* G61MPVT−60D−135*
*Limit pipe length to 50mm in G61MPVT−110 and −135 applications.
Follow the next three steps when installing the unit in Non­Direct Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors.
*Limit pipe length to 50mm in G61MPVT−110 and −135 applications.
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110*
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110* G61MPVT−60D−135*
50mm
G61MPVT−36B−070 G61MPVT−60C−090
50mm*
50mm*
TRANSITION
50mm*
TRANSITION
50mm
50mm
80mm
80mm
50mm
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR HORIZONTAL NON−DIRECT
(RightHand Exit in Upflow Application Shown)
PLUG
(Must be
glued in
place)
NOTE − Debris screen and elbow may be rotated, so that screen may be positioned to face forward, backward or downward.
VENT APPLICATIONS
156mm Max.
INTAKE
DEBRIS
SCREEN
(Provided)
FIGURE 18
FIGURE 19
Page 15
TYPICAL AIR INTAKE PIPE CONNECTIONS
DOWNFLOW NONDIRECT VENT APPLICATIONS
(RightHand Exit in Downflow Applications Shown)
50mm
SWEEP
ELL
INTAKE
DEBRIS
SCREEN
(Provided)
PLUG
(Must be
glued in
place)
150mm Max.
INTAKE DEBRIS
SCREEN
(Provided)
Downflow
Evaporator
Coil
FIGURE 20
1 − Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in figures 19 and 20. Maintain a minimum clearance of 76mm (3 inches) around the air intake opening. The air intake opening (with the protective screen) should always be directed either downward or straight out. Use 50mm pipe and fittings only and make sure that the air intake does not extend more than 156mm (6inches) beyond the G61MPVT cabinet.
The air intake connector must not be located near the floor. To avoid this complication in downflow applications which do not include a downflow evaporator coil, the intake air routing should be modi-
fied as shown in figure 20.
2 − Use a sheet metal screw to secure the intake pipe to the
connector, if desired. A pilot indentation is provided in the slip connector to assist in locating and starting the fasten­er.
3 − Glue the provided 50mm plug into the unused air intake
connector on the opposite side of the cabinet.
PLUG
(Must be
glued in
place)
NOTE − Debris screen and sweep ell may be rotated, so that screen may be positioned to face forward, backward or to the side.
50mm
50mm SWEEP ELL
Downflow Additive Flloor Base
438mm
Testing for Proper Venting and Sufficient Combustion Air
(Non−Direct Vent Applications Only)
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monox­ide poisoning or death. The following steps shall be followed for each ap­pliance connected to the venting system being placed into operation, while all other appliances con­nected to the venting system are not in operation.
After the G61MPVT gas furnace has been started, the fol­lowing test should be conducted to ensure proper venting and sufficient combustion air has been provided to the G61MPVT, as well as to other gas-fired appliances which are separately vented. The test should be conducted while all appliances (both in operation and those not in op­eration) are connected to the venting system being tested.
Page 16
Loading...
+ 36 hidden pages