Lennox G61MPVT-36B-070, G61MPVT-60C-090, G61MPVT-60C-110, G61MPVT-60D-135 Installation Instructions Manual

Page 1
INSTALLATION
E 2006 Lennox Industries Inc.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INSTRUCTIONS
G61MPVT SERIES UNITS
GAS UNITS
505,187M 06/2009
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G61MPVT Parts Arrangement 3. . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation − Setting Equipment 5. . . . . . . . . . . . . . . . . .
Filters 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe & Fittings Specifications 10. . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 11. . . . . . . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 12. . . . . . . . . . . . . . . . . . . . .
Venting Practices 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board 27. . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 35. . . . . . . . . . . . . . . . . . . . . .
Manifold Pressure & High Altitude Information 35. . . .
Other Unit Adjustments 36. . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 37. . . . . . . . . . . . . . . . .
Service 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Requirements 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 41. . . . . . . . . . . .
Ignition Control Board Diagnostic Codes 44. . . . . . . . .
Troubleshooting 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Pipe Sizing Worksheet 51. . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 52. . . . . . . . . . . . . .
Litho U.S.A.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
06/09
*2P0609*
WARNING
FIRE OR EXPLOSION HAZARD.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately. D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
Page 1
505,187M
*P505187M*
Page 2
G61MPVT Unit Dimensions − mm
*60C and 60D size units installed in upflow applications that require air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. Required to maintain proper air velocity.
2. Single side return
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
Refer to Engineering Handbook for additional information.
**Consider sizing requirements for optional IAQ equip­ment before cutting side return opening.
one side return air.
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
SUPPLY AIR
OPENING
603
635
TOP VIEW
19
A
B
14
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
40
(1016)
295 Right
248 Left
165
103
124 Right
57 Left
140
171
165
79
724
COMBUSTION AIR INTAKE
(Either Side)
EXHAUST AIR OUTLET
(Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
ELECTRICAL INLET
(Either Side)
64
AIR FLOW
C
*Bottom Return
Air Opening
19
375
16
406
476
RECEPTACLE
102
IEC
108
584
*OPTIONAL
RETURN CUTOUT
(Either Side)
597
*Bottom Return
Air Opening
FRONT VIEW SIDE VIEW
378
14
356**
49
Model No.
G61MPVT−36B−070 446 416 406
G61MPVT−60C−090 G61MPVT−60C−110
G61MPVT−60D−135 622 594 584
A B C
mm mm mm
533 454 495
Page 2
Page 3
G61MPVT Parts Arrangement
BURNER BOX
ASSEMBLY
GAS VALVE
AND MANIFOLD
FLUE
COLLAR
TOP CAP
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
CABINET
COMBUSTION
AIR PRESSURE
PROVE SWITCHES
COMBUSTION AIR
INDUCER
BURNER ACCESS
PANEL
BLOWER
ACCESS
PANEL
SIGHT
GLASS
DOOR
INTERLOCK
SWITCH
Two−Stage, Variable Speed
Integrated Control Board
WARM HEADER
(COLLECTOR)
BOX
CONDENSER COIL
PRIMARY LIMIT
COLD HEADER
(COLLECTOR)
BOX
SECONDARY
LIMITS (2)
BLOWER MOTOR
TRANSFORMER
CONTROL BOX
FIGURE 1
Page 3
Page 4
G61MPVT Gas Furnace
The G61MPVT gas furnace is equipped with a two−stage, variable speed integrated control. This control ensures compatibility with a thermostat which provides humidity control. Each G61MPVT is shipped ready for installation in the upflow, downflow, horizontal left air discharge or horizontal right air discharge position. The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in upflow ap­plications with bottom return air. The bottom panel must also be removed and discarded in all downflow or horizon­tal applications.
The furnace is equipped for installation in natural gas ap­plications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
All G61MPVT models can be installed as a Direct Vent gas central furnace. G61MPVT−070, −090 and −110 mod­els can be installed as a Non−Direct Vent gas central fur­nace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination.
DIRECT VENT INSTALLATION NON−DIRECT VENT
COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
EXHAUST OUTLET
INSTALLATION
EXHAUST OUTLET
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G61MPVT unit 1 − Bag assembly containing the following:
3 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 2 − 2" diameter vent / intake plugs 1 − 3" diameter cabinet plug (intake) 2 − 2" diameter debris screen
1 − Bag assembly containing the following:
1− 50 hertz power wiring harness
NOTE − G61MPVT−60C−110 and −60D−135 units also in­clude two 50mm to 80mm diameter ABS street elbows and two 80mm to 50mm ABS reducing elbows, which are shipped on the blower deck in the heating compartment.
The following items may also be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Safety Information
CONDENSATE
DRAIN
G61MPVT
FIGURE 2
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
G61MPVT
CONDENSATE
DRAIN
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Page 4
Page 5
Installation − Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
Upflow Applications
The G61MPVT gas furnace can be installed as shipped in the upflow position. Refer to figure 3 for clearances.
Installation Clearances
Top
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [610 mm (24 inches) at unit front]. The unit must be level from front to back and side
to side.
NOTE − G61MPVT−36B units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must
be removed before the furnace is placed into opera­tion. After the bolt and washer have been removed, the rig-
id leg will not touch the blower housing.
NOTE − G61MPVT−60D−135 units are equipped with a shipping pad under the blower housing. Remove the ship­ping pad prior to operation.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figures 3, 9 and 6.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
Left Side
Bottom (Floor)
Top/Plenum 25 mm (1 in.)
*Front 0
Back 0
Sides 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 610 mm (24 inch­es). Maintain a minimum of 610 mm (24 inches) for front service access. Allow proper clearances to accommodate condensate trap and vent pipe installation. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
Right Side
FIGURE 3
Return Air −− Upflow Units
NOTE − G61MPVT−135 models are not approved for installation in upflow air discharge applications.
Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 850 L/s (1800 cfm) are required with 60C or 60D models in an upflow applica­tion, the following return air options are available:
1 − Return air from single side with transition which will ac-
commodate508 x 635 x 25 mm (20 x 25 x 1 in.) air filter. (Required to maintain proper air velocity.) See figure 4.
2 − Return air from single side.
3 − Return air from bottom.
4 − Return air from both sides.
Page 5
Page 6
5 − Return air from bottom and one side.
Refer to Engineering Handbook for additional information.
G61MPVT applications which include side return air and a condensate trap installed on the same side of the cabinet require either a return air base or field−fabri­cated transition to accommodate an optional IAQ ac­cessory taller than 368mm (14.5 inches).
Side Return Air
(with transition and filter)
508mm X635mm X 25mm
(20" X 25" X 1")
Air Filter
Return
Air
Plenum
Horizontal Applications
G61MPVT furnaces, with the exception of the G61MPVT−60D−135, can be installed in horizontal applica­tions with either right− or left−hand air discharge. The G61MPVT−60D−135 can only be installed in horizontal ap­plications with right−hand air discharge.
Refer to figure 6 for clearances in horizontal applications.
Horizontal Application
Installation Clearances
Right−Hand Discharge
Top
Left End Right End
Bottom (Floor)**
Left−Hand Discharge
Top
Left End Right End
Transition
FIGURE 4
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 5.
Removing the Bottom Panel
Screw
Bottom Cap
Bottom Panel
Bottom (Floor)**
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 610 mm (24 inch­es). Maintain a minimum of 610mm (24 inches) for front service ac­cess. **A 140mm (5−1/2) service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 6
This furnace may be installed in either a roof space or un­der floor. Install the furnace on a field−fabricated raised platform, as shown in figure 7. The unit must be supported at both ends and beneath the blower deck to prevent sag­ging.
NOTE − In horizontal applications, the unit must be lev­el side−to−side. The unit may be tilted back−to−front a maximum of 25mm (1 inch) to ensure proper draining of the heat exchanger. The heat exchanger coil will not
drain properly if the unit is tilted backward.
FIGURE 5
Page 6
Page 7
TYPICAL HORIZONTAL ROOF SPACE INSTALLATION (FORCED AIR FURNACE)
INTAKE PIPE
NOTE − Condensate trap and
condensate line must be
protected by self−regulating
heating cable and insulation
when run through unconditioned
spaces.
CONDENSATE LINE
FIGURE 7
Platform Installation of Horizontal Unit in Roof Space
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 6.
2 − Construct a raised wooden frame and cover frame
with a plywood sheet. Provide a service platform for unit. A drain pan is also recommended.
EXHAUST PIPE
INTAKE
PIPE
GAS
CONNECTOR
RAISED PLATFORM
SERVICE PLATFORM
EXHAUST
PIPE
3 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
4 − Set unit in drain pan (if used) as shown in figure 7. Unit
must be level to ensure proper coil drainage. Leave 140mm (5−1/2 inches) for service clearance below unit for condensate trap.
5 − Continue with exhaust, condensate and intake piping
installation according to instructions.
Platform Installation of Horizontal
Unit Installed Under Floor
1 − Select location for unit, keeping in mind service and
other clearances.
EVAPORATOR COIL
FIGURE 8
2 − After positioning cement blocks, mount support frame
on top of blocks and install unit. Unit must be level to ensure proper heat exchanger coil drainage. Leave 140mm (5−1/2 inches) for service clearance) for con­densate trap.
3 − Install exhaust and intake piping according to informa-
tion given in following section.
Page 7
Page 8
Return Air −− Horizontal Applications
Return air may be brought in only through the end of a fur­nace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 5.
Downflow Applications
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling cabi­net. Do not drag the unit across the floor in the down-
flow position. Flange damage will result. Refer to figure 9 for clearances in downflow applica­tions.
Downflow Application Installation Clearances
Top
Left Side
Right Side
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Model No.
B Cabinet (445mm) 19 − 3/4 502 16 − 5/8 422
C Cabinet (533mm) 19 − 3/4 502 20−1/8 511
D Cabinet (622mm) 19 − 3/4 502 23 − 5/8 600
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Front to Rear Side to Side
in. mm in. mm
Installation on Combustible Flooring
1 − When unit is installed on a combustible floor, an addi-
tive base must be installed between the furnace and the floor. The base must be ordered separately for the following cabinet sizes:
D B cabinet 445mm − # 11M60 D C cabinet 533mm − # 11M61 D D cabinet 622mm − # 11M62
See table 2 for opening size to cut in floor.
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 610mm (24 inches). Maintain a minimum of 610mm (24 inches) for front service ac­cess. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional additive base is installed between the furnace and the com­bustible floor.
FIGURE 9
Installation on Non−Combustible Flooring
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
CAUTION
The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma­terial other than wood flooring.
TABLE 2
ADDITIVE BASE FLOOR OPENING SIZE
Model
B Cabinet (445mm)
C Cabinet (533mm)
D Cabinet (622mm)
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 − Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
22 559 22 − 3/4 578
22 559 25 − 3/4 654
Page 8
Page 9
G61MPVT UNIT
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
SUPPLY AIR PLENUM
PROPERLY
SIZED FLOOR
OPENING
ADDITIVE BASE
FIGURE 10
Installation on Cooling Cabinet
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position.The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 11 or 12).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
Side View
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
FIGURE 11
CABINET
SECURE FROM
INSIDE CABINET
Side View
SIDE PANEL
FIGURE 12
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended minimum filter sizes.
A filter must be in place when the unit is operating.
NOTE − In upflow applications where side return air fil­ter is installed on same side as the condensate trap, fil­ter rack must be installed beyond condensate trap to avoid interference.
TABLE 3
Furnace
Cabinet Size
445mm 406 X 635 X 25 (1) 406 X 635 X 25 (1)
533mm 406 X 635 X 25 (1) 508 X 635 X 25 (1)
622mm 406 X 635 X 25 (2) 610 X 635 X 25 (1)
Side Return Bottom Return
Filter Size −− mm
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Operation of this furnace in heating mode (indoor blower operating at selected heating speed) with an exter­nal static pressure which exceeds 200 Pa (0.8 inches w.c.) may result in erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed. If present, this ac­cess panel must always be in place when the furnace is op­erating and it must not allow leaks into the supply air duct system.
Return Air Plenum
Return air must not be drawn from a room where this furnace, or any other gas appliance (ie., a water heat­er), is installed. When return air is drawn from a room, a
negative pressure is created in the room. If a gas ap­pliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and
Page 9
Page 10
into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe and fittings to be Pressure Pipe, Class E / Class 12 / Schedule 40 or equivalent
All pipe, fittings, primer and solvent cement must conform
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
Outdoor Ex­haust Accel-
erator
(Dia. X
Length)
40mm X
305mm
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
UNIT
MODEL
−070
−090
−110
−135
VENT
PIPE
DIA.
(in.)
50mm 1.2
80mm 2.4
100mm 4.3
50mm
80mm
100mm
80mm
100mm
80mm
100mm
*Requires field−provided and installed 40mm exhaust accelerator.
Outdoor Ex-
haust Accel-
erator
(Dia. X
Length)
50mm X
305mm
Not
Allowed
Not
Allowed
Not
Allowed
0.3
0.6
1.2
0.6
1.2
1.8
3.0
Concentric
(1−1/2")
71M80 60M29 60L46 22G44 44J40 15F74
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
TABLE 4
Vent Pipe Length Equivalency (meters)
40mm
Kit
3.6
7.3
12.8
Not
Not
Not
Not
Not
Not
Not
with Australian standards. The solvent shall be free flow­ing and contain no lumps, undissolved particles or any for­eign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
Table 4 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when sizing vent pipe. All Lennox vent terminations are PVC or ABS.
50mm (2")
Concentric
Kit
Not
Allowed
Not
Allowed
Not
Allowed
.9 .9
1.8 1.8
3.7 3.7
1.8 1.8
3.7 3.7
Not
Allowed
Not
Allowed
**Requires field−provided and installed 50mm exhaust accelerator.
80mm (3") Concentric
Kit
Not
Allowed
Not
Allowed
Not
Allowed
4.6
7.6
50mm (2")
Wall Plate
Kit
1.2 1.2* 1.2
2.4 2.4* 2.4
4.3 4.3* 4.3
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
80mm (3")
Wall Plate
Kit
0.3 0.3**
0.6 0.6**
1.2 1.2**
0.6 0.6
1.2 1.2
1.8
3.0
50mm (2")
Wall Ring
Kit
Not
Allowed
Not
Allowed
Page 10
Page 11
Vent Piping Guidelines
G61MPVT furnaces, with the exception of the G61MPVT−60D−135, can be installed as either a Non−Di­rect Vent or a Direct Vent gas central furnace. The G61MPVT−60D−135 can only be installed as a Direct Vent (two pipe) gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −− Size pipe according to tables 5 and 6. Table 5 lists the mini­mum equivalent vent pipe lengths permitted. Table 6 lists the maximum equivalent pipe lengths permitted.
Maximum vent length is defined as:
Total length (linear meters) of pipe,
Plus Equivalent length (meters) of fittings, Plus Equivalent length (meters) of termination. NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 7.
NOTE − The exhaust pipe should be offset a minimum of 305mm (12 inches) to avoid the possibility of water droplets being released from the exhaust termination. The mini­mum exhaust vent length is 4.5m (15 feet). Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 305mm (12−inch) vertical offset.
Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 1.5m (5 feet ) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to .76m (2.5 feet) of vent pipe of the same diameter.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox for assistance in sizing vent pipe in these applications.
NOTE − The flue collar on all models is sized to accommo­date 50mm Schedule 40 / Class 12 / Class E pressure pipe. When vent pipe which is larger than 50mm must be used in an upflow application, a 50mm elbow must be ap­plied at the flue collar in order to properly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine acceptable vent lengths. Assign an equivalent meter value to this elbow according to the larger size pipe being used. Contact Lennox for more information concerning sizing of vent systems which include multiple pipe sizes.
305mm Min.
Upflow and Downflow Application
Rooftop Termination
305mm Min.
Horizontal Application
Rooftop Termination
Exhaust Pipe Offset
305mm Min.
Upflow and Downflow Application
Side Wall Termination
305mm Min.
Horizontal Application
Side Wall Termination
FIGURE 13
Page 11
Page 12
Use the following steps to correctly size vent pipe diameter.
Refer to Vent Pipe Size Determination Worksheet on page 52.
1 − Determine the vent termination and its corresponding
equivalent meter value per table 6.
2 − Determine the number of 90° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent meters of vent pipe.
3 − Determine the number of 45° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent meters of vent pipe.
4 − Determine the length of straight pipe required.
5 − Add the total equivalent meters calculated in steps 1
through 4 and compare that length to the maximum values given in table 6 for the proposed vent pipe di­ameter. If the total equivalent length required exceeds the maximum equivalent length listed in the appropri­ate table, evaluate the next larger size pipe.
TABLE 5
MINIMUM VENT PIPE LENGTHS
G61MPVT
MODEL
070, 090
110***
135***
*Any approved termination may be added to the minimum equivalent length listed.
**G61MPVT−60C−110 and G61MPVT−60D−135 must have 90° street ell (sup­plied) installed directly into unit flue colla and 50mm to 80mm reducer (sup­plied) must be installed on the 50mm ell. NOTE − All 90° elbows used in configuration of vent, must be sweep el-
bows.
MIN. EQUIV.
VENT LENGTH
4.5m*
EXAMPLE
1.5m plus 2 elbows of 50mm or 80mm diameter pipe
1.5m plus 2 elbows of 80mm diameter pipe
1.5m plus 2 elbows of 80mm diameter pipe
TABLE 6
MAXIMUM VENT PIPE LENGTHS
MAXIMUM EQUIVALENT VENT
ALTITUDE
0 − 610m
611 −1372m
n/a −− Not allowed. *G61MPVT−60C−110 and G61MPVT−60D−135 must have 90° street ell (sup-
plied) installed directly into unit flue colla and 50mm to 80mm reducer (sup­plied) must be installed on the 50mm ell. NOTE − All 90° elbows used in configuration of vent, must be sweep el-
bows.
G61MPVT
MODEL
070 12.2 16.1 44
090 4.5 12.2 34.5 110* n/a 12.2 30 135* n/a 7.6 20
070 7.6 10 27.5
090 n/a 7.6 21.5 110* n/a 7.6 18.7 135* n/a n/a n/a
LENGTH METERS
50mm
dia.
80mm
dia.
100mm
dia.
IMPORTANT
The G61MPVT unit is not suitable for use at eleva­tions over 610m.
Joint Cementing Procedure
All cementing of joints should be done according to the relevant local authority.
WARNING
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply liberal coat of PVC primer for PVC or
ABS cleaner for ABS to inside socket surface of fitting and male end of pipe to depth of fitting socket.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn pipe 1/4 turn during as­sembly (but not after pipe is fully inserted) to distribute cement evenly.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Page 12
Page 13
Venting Practices
1 − Use recommended piping materials for exhaust piping
(Class E / Class 12 / Schedule 40).
2 − Secure all joints so that they are gas-tight using ap-
proved cement.
downflow positions. Exhaust piping exits from the top of the unit in horizontal air discharge applications. Glue the field−provided exhaust vent pipe (or provided street ell or reducing ell in upflow or downflow applica­tions) to the flue collar. Refer to pipe and fittings speci­fications and gluing procedures.
Suspend piping using hangers at a minimum of every
1.52m (5 feet) for Schedule 40 vent pipe. A suitable hanger can be fabricated by using metal or plastic strapping or a large wire tie.
3 − In areas where piping
penetrates joists or interi­or walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
4 − Isolate piping at the point where it exits the outside wall
or roof in order to prevent transmission of vibration to the structure.
5 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
Exhaust Piping (Figures 15 and 16)
NOTE − Two 50mm diameter street ells and two 80mm to 50mm reducers are contained in a bag assembly strapped to the blower deck of 60C−110 and 60D−135 units. The street ells must be flue collar. See figure 15. The 80mm to 50mm reducers must be glued to the street ells in upflow or downflow
applications.
1 − Choose the appropriate side for venting in upflow or
glued directly into the unit
STRAPPING
(metal, plastic
or large wire
ties)
FIGURE 14
IMPORTANT
Exhaust piping and condensate trap must be installed on the same side of the unit in upflow and dowflow applications.
2 − All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 6mm (1/4") drop for each 305mm (12 inches) of horizontal run is mandatory for drainage. Horizontal runs of exhaust piping must be sup­ported every 1.5m (5 feet) using hangers.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
3 − On the opposite side of the cabinet, glue the provided
50mm vent plug into the unused flue collar.
4 − Route piping to outside of structure. Continue with
installation following instructions given in piping ter­mination section.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
Page 13
Page 14
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
IN UPFLOW OR DOWNFLOW DIRECT OR NON−DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
80mm
PLUG
VENT PLUG
(Must be
glued in
place)
PLUG
*50mm diameter street elbow provided.
**80mm diameter reducing elbow provided.
***Limit pipe length to 50mm.
PLUG
50mm
CONDENSATE
TRAP
(Must be installed
on same side as
exhaust piping)
50mm
50mm
FIGURE 15
TYPICAL EXHAUST PIPE CONNECTIONS
HORIZONTAL DIRECT OR
NONDIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
*Limit pipe length to 50mm in G61MPVT−110 and −135 applications.
DO NOT transition from smaller to larger pipe size in horizontal runs.
80mm
TRANSITION
50mm
50mm
50mm
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110* G61MPVT−60D−135*
50mm
G61MPVT−36B−070 G61MPVT−60C−090
FIGURE 16
TRANSITION
50mm
50mm
50mm
80mm
TRANSITION
50mm***
50mm*
G61MPVT−110
with
80mm vent pipe
G61MPVT−070
or 090 with 80mm
vent pipe
80mm
80mm**
G61MPVT−135
with
80mm vent pipe
Intake Piping
G61MPVT furnaces, with the exception of the G61MPVT−60D−135, can be installed as either a Non−Di­rect Vent or a Direct Vent gas central furnace. The G61MPVT−60D−135 can only be installed as a Direct Vent (two pipe) gas central furnace. In non−direct vent ap-
plications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
The G61MPVT unit is designed for either left−side or right− side air intake connections in either upflow or downflow ap­plications. In horizontal applications, air intake must be brought in through the top. Intake air piping is independent of exhaust piping.
Follow the next four steps when installing the unit in direct vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors.
1 − Cement intake piping in slip connector located on the
side of the burner box.
2 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired. A pilot indentation is pro­vided in the slip connector to assist in locating and starting the fastener.
3 − Glue the provided 50mm plug into the unused air intake
connector on the opposite side of the cabinet.
4 − Route piping to outside of structure. Continue with
installation following instructions given in general guide lines for piping terminations and in intake and exhaust piping terminations for direct vent sections. Refer to figure 17 for pipe sizes.
Page 14
Page 15
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
50mm
PLUG
(Must be
glued in
place)
50mm
50mm
G61MPVT−36B−070 G61MPVT−60C−090
FIGURE 17
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL DIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
80mm
TRANSITION
80mm
50mm*
50mm*
TRANSITION
50mm*
50mm
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110*
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110* G61MPVT−60D−135*
*Limit pipe length to 50mm in G61MPVT−110 and −135 applications.
Follow the next three steps when installing the unit in Non­Direct Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors.
*Limit pipe length to 50mm in G61MPVT−110 and −135 applications.
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110*
G61MPVT−36B−070 G61MPVT−60C−090 G61MPVT−60C−110* G61MPVT−60D−135*
50mm
G61MPVT−36B−070 G61MPVT−60C−090
50mm*
50mm*
TRANSITION
50mm*
TRANSITION
50mm
50mm
80mm
80mm
50mm
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR HORIZONTAL NON−DIRECT
(RightHand Exit in Upflow Application Shown)
PLUG
(Must be
glued in
place)
NOTE − Debris screen and elbow may be rotated, so that screen may be positioned to face forward, backward or downward.
VENT APPLICATIONS
156mm Max.
INTAKE
DEBRIS
SCREEN
(Provided)
FIGURE 18
FIGURE 19
Page 15
Page 16
TYPICAL AIR INTAKE PIPE CONNECTIONS
DOWNFLOW NONDIRECT VENT APPLICATIONS
(RightHand Exit in Downflow Applications Shown)
50mm
SWEEP
ELL
INTAKE
DEBRIS
SCREEN
(Provided)
PLUG
(Must be
glued in
place)
150mm Max.
INTAKE DEBRIS
SCREEN
(Provided)
Downflow
Evaporator
Coil
FIGURE 20
1 − Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in figures 19 and 20. Maintain a minimum clearance of 76mm (3 inches) around the air intake opening. The air intake opening (with the protective screen) should always be directed either downward or straight out. Use 50mm pipe and fittings only and make sure that the air intake does not extend more than 156mm (6inches) beyond the G61MPVT cabinet.
The air intake connector must not be located near the floor. To avoid this complication in downflow applications which do not include a downflow evaporator coil, the intake air routing should be modi-
fied as shown in figure 20.
2 − Use a sheet metal screw to secure the intake pipe to the
connector, if desired. A pilot indentation is provided in the slip connector to assist in locating and starting the fasten­er.
3 − Glue the provided 50mm plug into the unused air intake
connector on the opposite side of the cabinet.
PLUG
(Must be
glued in
place)
NOTE − Debris screen and sweep ell may be rotated, so that screen may be positioned to face forward, backward or to the side.
50mm
50mm SWEEP ELL
Downflow Additive Flloor Base
438mm
Testing for Proper Venting and Sufficient Combustion Air
(Non−Direct Vent Applications Only)
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monox­ide poisoning or death. The following steps shall be followed for each ap­pliance connected to the venting system being placed into operation, while all other appliances con­nected to the venting system are not in operation.
After the G61MPVT gas furnace has been started, the fol­lowing test should be conducted to ensure proper venting and sufficient combustion air has been provided to the G61MPVT, as well as to other gas-fired appliances which are separately vented. The test should be conducted while all appliances (both in operation and those not in op­eration) are connected to the venting system being tested.
Page 16
Page 17
If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section.
1 − Seal any unused openings in the venting system. 2 − Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re­striction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − To the extent that it is practical, close all building doors
and windows and all doors between the space in which the appliances connected to the venting system are lo-
cated and other spaces of the building. 4 − Close fireplace dampers. 5 − Turn on clothes dryers and any appliances not con-
nected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. 6 − Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously. 7 − Test for spillage of flue gases at the draft hood relief
opening after 5 minutes of main burner operation. Use
the flame of match or candle, or smoke from a ciga-
rette, cigar. 8 − If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make-up air must be provided. 9 − After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their previous
condition of use.
General Guidelines for Vent Terminations for Non-Direct Vent Installations.
In Non-Direct Vent applications, combustion air is taken
from indoors and the flue gases are discharged to the out­doors. The G61MPVT is then classified as a non-direct vent gas furnace. In Non-Direct Vent applications, the vent termination is limited by local building codes.
Position termination end according to location given in fig­ure 21. In addition, position termination end so it is free from any obstructions and above the level of snow accu­mulation (where applicable). The termination should be at least 305mm (12 inches) from any opening through which flue products could enter the building.
At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 1.8m (6 feet) of a condensing unit because the condensate can damage the painted coating.
NOTE − If winter design temperature is below 0°C (32°F), exhaust piping should be insulated with 13mm (1/2 inch), Armaflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to out­side air; exterior exhaust pipe should be insulated with 13mm (1/2 inch) Armaflex or equivalent. In extreme cold climate areas, 19mm (3/4 inch) Armaflex or equivalent may be necessary. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect insulation from dete­rioration. Exhaust pipe insulation may not be necessary in some specific applications.
NOTE − During extremely cold temperatures, below approximately −6.7°C (20°F), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze−ups. Heating cable installation kit is avail­able from Lennox.
Page 17
Page 18
VENT TERMINATION CLEARANCES
(AS 5601)
G61MPVT VENT TERMINATION
AIR INLET OF OTHER APPLIANCE
C
less than 10 ft (3.048M)
D
D
E
F
A − Clearance above ground level − 305mm. B − Clearance horizontally to window or door that may be
opened − 305mm minimum for appliances up to 150Mj/h; Clearance vertically below a window that may be opened − 1000mm minimum for appliances up to 150Mj/h.
C − Clearance below eaves, balconies and other projections −
305mm.
D − Clearance to electric meters, gas meters, regulators and re-
lief equipment1000mm minimum.
FIGURE 21
Details of Intake and Exhaust Piping Terminations for Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.
Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In at­tic or closet installations, vertical termination through the roof is preferred. Figures 22 through 25 show typical ter­minations. 1 − Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.
2 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il­lustrations). Maximum separation is 76mm (3 inches) on roof terminations and 152mm (6 inches) on side wall terminations.
E − Clearance to non−mechanical air supply inlet or outlet
300mm minimum horizontal and 1000mm minimum verti­cally for appliances up to 150Mj/h;
F − Clearance to mechanical air supply inlet including a spa
blower −− 1000mm minimum.
G − Do not point terminations into recessed areas such as win-
dow wells, stairwells or alcoves.
H − Do not position terminations directly above a walkway.
3 − If necessary, install a field−provided transition to adapt
larger vent pipe size to termination pipe size.
4 − On roof terminations, the intake piping should termi-
nate straight down using two 90° elbows (See figure
22).
5 − Exhaust piping must terminate straight out or up as
shown. In rooftop applications, a reducer may be re­quired on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 7.
NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.
6 − On field supplied terminations for side wall exits, ex-
haust piping should extend a maximum of 305mm (12 inches) beyond the outside wall unless supported. In­take piping should be as short as possible.
Page 18
Page 19
7 − On field supplied terminations, a minimum separation
distance between the end of the exhaust pipe and the
end of the intake pipe is 203mm (8 inches).
TABLE 7
EXHAUST PIPE TERMINATION SIZE REDUCTION
G61MPVT
MODEL
070 50 or 80mm 40mm 090 50 or 80mm 50mm 110 80mm 50mm* 135 80mm 50mm*
*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.
203 mm MIN
80mm or
50mm PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
Exhaust Pipe Size Termination Pipe Size
76mm MAX.
DIRECT VENT ROOF TERMINATION KIT
SIZE TERMINATION PIPE PER TABLE 7.
UNCONDITIONED
ATTIC SPACE
13mm FOAM
INSULATION IN
UNCONDITIONED
SPACE
FIGURE 22
INTAKE
TERMINATION
EXHAUST
INTAKE
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
DIRECT VENT CONCENTRIC WALL TERMINATION
(71M80, 69M29 or 60L46)
above ground level.
EXHAUST
TERMINATION
305mm Min.
FIGURE 24
Details of Exhaust Piping Terminations for Non-Direct Vent Applications
Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre­ferred. Figure 25 shows a typical terminations.
1 − Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in table 7.The specified pipe size ensures proper veloc­ity required to move the exhaust gases away from the building.
2 − On field supplied terminations for side wall exits, ex-
haust piping should extend a maximum of 305mm (12 inches) beyond the outside wall, unless support is pro­vided in the horizontal section.
EXHAUST
TERMINATION
INTAKE
TERMINATION
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
(71M80, 69M29 or 60L46)
INTAKE
FIGURE 23
SIZE TERMINATION PIPE PER TABLE 7.
80mm or
50mm PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
NON−DIRECT VENT ROOF TERMINATION KIT
UNCONDITIONED
ATTIC SPACE
FIGURE 25
Page 19
Page 20
Condensate Piping
This unit is designed for either right- or left-side exit of con­densate piping in either upflow or downflow applications; however, it must be installed on the same side of the unit as the exhaust piping. In horizontal applications, the conden­sate trap should extend below the unit. A 140mm (5−1/2−inch) service clearance is required for the conden­sate trap. Refer to figure 26 for condensate trap locations.
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position)
Horizontal
left and
optional
downflow
Horizontal
right and
optional
downflow
3 − Glue the field−provided coupling or pipe to the trap.
Install a tee and vent pipe near the trap.
NOTE − The condensate trap drain stubs (both sides) have an outer diameter which will accept a standard 19mm (3/4") PVC coupling. The inner diameter of each stub will accept standard 13mm (1/2") diameter PVC pipe.
NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 32mmOD X 25mm ID (1−1/4" OD X 1" ID) and should be attached to the drain stubs on the trap using a hose clamp.
4 − Glue the field−provided drain line to the tee. Route the
drain line to an open drain. As an alternate, clear vinyl tubing may be used to drain condensate away from the trap. Secure the vinyl tubing to the drain stubs on the trap using a hose clamp. Do not overtighten the hose clamp. Condensate line must be sloped downward away from condensate trap to drain. If drain level is above con­densate trap, condensate pump must be used.
Optional
upflow
Optional
upflow
NOTE − In upflow applications where side return air filter is installed on same side as the conden­sate trap, filter rack must be installed beyond condensate trap to avoid interference.
FIGURE 26
1 − Determine which side condensate piping will exit the
unit. Remove plugs from the condensate collar at the appropriate location on the side of the unit.
NOTE − The condensate trap is factory−shipped with two rubber O−rings and two rubber clean−out caps installed. Check to make sure that these items are in place before installing the trap assem­bly.
2 − Install condensate trap onto the condensate collar.
Use provided HI/LO screws to secure two upper flanges of the trap to the collar. Use provided sheet metal screw to secure bottom trap flange to side of unit. See figure 27.
NOTE − In upflow and downflow applications, con­densate trap must be installed on the same side as exhaust piping.
CAUTION
Do not use copper tubing or existing copper condensate lines for drain line.
5 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit Start−Up section.
6 − Glue the provided cap onto the unused condensate
drain line stub.
CONDENSATE ASSEMBLY
HI/LO SCREWS
CAP
O−RINGS
SCREW
(DO NOT use power driver. Hand−tighten
using screw driver.)
NIPPLE
COUPLING
CLEAN−OUT ACCESS
CONDENSATE TRAP
FIGURE 27
VENT
NIPPLE
TEE
(both sides)
Page 20
Page 21
Gas Piping
CAUTION
DO NOT over−tighten when attaching pipe or fittings to gas valve. Damage may occur.
1 − Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
figures 29 and 30. 2 − When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be con-
sidered to avoid excessive pressure drop. Table 8 lists
recommended pipe sizes for typical applications.
NOTE − Use two wrenches when connecting gas pip­ing to avoid transferring torque to the manifold.
3 − Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or eleva-
tor shafts. Center gas line through piping hole. Gas
line should not touch side of unit. See figures 29 and
30.
4 − Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, ev-
ery 2.44 to 3.05m (8 to 10 feet), using suitable hangers
or straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate. 5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 34. 6 − In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by in-
staller) external to the unit. Union must be of the
ground joint type.
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
FIGURE 28
Leak Check
After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing gas lines using pressures in excess of 1/2 psig (3.48 kPa), gas valve must be disconnected and isolated. See figure 28. Gas valves can be dam­aged if subjected to pressures greater than 1/2 psig (3.48 kPa).
WARNING
Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.
FIRE OR EXPLOSION HAZARD
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­leum gases.
Upflow Application
Left Side Piping
(Standard)
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
FIGURE 29
FIELD
PROVIDED
AND INSTALLED
Page 21
Upflow Application
Right Side Piping
(Alternate)
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Page 22
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT UNION
DRIP LEG
Horizontal Applications
Possible Gas Piping Configerations
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Horizontal Application
Left−Side Air Discharge
Horizontal Application
Right−Side Air Discharge
FIGURE 30
TABLE 8
GAS PIPE CAPACITY − FT3/HR (kL/HR)
Nominal
Iron Pipe Size
−Inches(mm)
1/4
(6.35)
3/8
(9.53)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1−1/4
(31.75)
1−1/2
(38.1)
2
(50.8)
2−1/2
(63.5)
3
(76.2)
4
(101.6)
Internal
Diameter
−Inches(mm)
.364
(9.246)
.493
(12.522)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
43
(1.13)
95
(2.69)
175
(4.96)
360
(10.19)
680
(19.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
29
(.82)
65
(1.84)
120
(3.40)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
24
(.68)
52
(1.47)
97
(2.75)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Length of Pipe−Feet(m)
20
(.57)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
(.51)
(1.13)
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
18
40
73
16
(.45)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
8800
(249.18)
15
(.42)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
14
(.40)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
13
(.37)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
7200
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Page 22
Page 23
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
5 − Electrically ground the unit according to local codes.
NOTE − The G61MPVT furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
CAUTION
Electrostatic discharge can affect electronic com­ponents. Take precautions during furnace installa­tion and service to protect the furnace’s electronic controls. Precautions will help to avoid control ex­posure to electrostatic discharge by putting the fur­nace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an un­painted unit surface, such as the gas valve or blower deck, before performing any service procedure.
A power wiring harness is shipped with each G61MPVT furnace. An IEC receptacle is provided on the right side of the unit. Plug the harness into the IEC receptacle and into a properly sized wall plug.
Refer to figure 31 and table 9 for field wiring and figure 32 for schematic wiring diagram and troubleshooting.
1 − Ensure that power connection point is located with 2m
of furnace.
2 − Holes are on both sides of the furnace cabinet to facili-
tate thermostat wiring.
3 − Before connecting the thermostat wiring, check to
make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.
4 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wir­ing diagram shown in figure 31 and table 9. Use 18−gauge wire or larger that is suitable for Class II ra­ting for thermostat connections.
6 − One line voltage EAC" spade terminal is provided on
the furnace control board. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 33 for control board configuration. This terminal is energized when the indoor blower is operating.
7 − One line voltage HUM" spade terminal is provided on
the furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 33 for control board configuration. This terminal is energized in the heating mode when the combustion air inducer is oper­ating.
8 − Install the room thermostat according to the instruc-
tions provided with the thermostat. See table 9 for ther­mostat connections. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously at approximately 38% of the second−stage cooling speed when there is no cool­ing or heating demand.
2 − When the G61MPVT is running in the heating mode,
the indoor blower will run on the heating speed desig­nated by the positions of DIP switches 7 and 8.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed designated by the positions of DIP switches 3 and 4.
Page 23
Page 24
USE COPPER CONDUCTORS ONLY.
FIELD INSTALLED CLASS II 24V FIELD INSTALLED LINE VOLTAGE
TYPICAL G61MPVT FIELD WIRING DIAGRAM
FIGURE 31
Page 24
Page 25
Thermostat
Heat Staging
Jumper
TABLE 9
Field Wiring Applications
Jumper Settings (See figure 33)
W915
Two−Stage
Cooling
W914 Dehu­midification
W951
Heat Pumps
Wiring Connections
1Heat / 1 Cool
NOTE − Use heat staging jumper to set second−stage heat ON delay. No delay (None), 10 minutes, or 15 minutes.
2 Heat / 1 Cool
NOTE − Use heat staging jumper to set second−stage heat ON delay. No delay (None), 10 minutes, or 15 minutes.
15 Minutes Intact Intact Intact
10 Minutes Intact Intact Intact
S1
T’STAT
S1
T’STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
Page 25
Page 26
TYPICAL G61MPVT WIRING DIAGRAM
FIGURE 32
Page 26
Page 27
Integrated Control Board
TWO−STAGE, VARIABLE SPEED INTEGRATED CONTROL BOARD
HEAT
STAGING
DELAY
JUMPER
BLOWER
OFF
DELAY
JUMPER
DIAGNOSTIC
LED
BLOWER
OPERATION
DIP
SWITCHES
OPERATIONAL
LEDS
FIGURE 33
G61MPVT units are equipped with a two−stage, variable speed integrated control. This control manages ignition timing, heating mode fan off delays and indoor blower speeds based on selections made using the control dip switches and jumpers. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out. After one hour of con­tinuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and automatically reset the control to relight the furnace.
Heat Staging Jumper The heat staging jumper is factory−positioned in the
NONE position for use with a two−stage thermostat. If a single−stage thermostat is to be used, the jumper must be repositioned.
When the G61MPVT unit is used with single−stage ther­mostat −− The heat staging jumper is used to determine the
second stage on delay. The jumper may be positioned to
provide either a 10−minute or a 15−minute delay before sec­ond−stage heat is initiated.
Blower−Off Delay Jumper −− The heating mode blower−on delay of 45 seconds is not adjustable. The heating mode blower−off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving blower−off delay jumper on the integrated control board. The unit is shipped from the factory with a blower−off delay of 90 seconds. The blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature be­tween 32° and 43°C (90° and 110°F) at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures. Settings of 60, 90, 120 and 180 seconds are available.
Page 27
Page 28
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and R on the integrated control board, must be cut when the fur­nace is installed with a thermostat which features humidity control.
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the fur­nace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the jumper is left intact, terminal O" will remain energized elim­inating the HEAT MODE in the heat pump.
On−Board Jumper W915
On−board jumper W915, which connects terminals Y1 and Y2 on the integrated control board, must be cut if two−stage cooling will be used. If the jumper is not cut the outdoor unit will operate in first−stage cooling only.
Status LEDs (HI/LO, CFM, ANI)
The green HI/LO LED indicates circulating blower speed in response to the DS signal. The LED is lit during normal blower operation and is off during a dehumidification de­mand.
The green CFM LED indicates the blower air flow. Count the number of blinks between the two−second pauses to determine the airf low. Each blink represents approximate­ly 50 L/s (100CFM).
The red ANI LED flashes diagnostic codes, which are de­tailed on page 43.
Indoor Fan Operation DIP Switch Settings
Switches 1 and 2 −− Blower Speed Adjustment −−
Switches 1 and 2 are used to select blower speed adjust­ment settings. The unit is shipped from the factory with the DIP switches positioned for NORMAL (no) adjustment. The DIP switches may be positioned to adjust the blower speed by +10% or −10% to better suit the application. The table below provides blower speed adjustments that will re­sult from different switch settings. Refer to tables 14 through NO TAG for corresponding cfm values.
TABLE 10
Blower Speed Adjustment
Adjustment
Switch 1 Switch 2
+10% (approx.) On Off
NORMAL (Factory) Off Off
−10% (approx.) Off On
Cooling Mode Blower Speeds
TABLE 11
Speed
Switch 3 Switch 4
1 − Low On On
2 − Medium Low Off On
3 − Medium High On Off
4 − High (Factory) Off Off
Switches 5 and 6 −− Cooling Mode Blower Speed Ramp­ing −− Switches 5 and 6 are used to select cooling mode
blower speed ramping options. Blower speed ramping may be used to enhance dehumidification performance. The switches are factory set at option A which has the greatest effect on blower motor performance. Table 12 provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed on the next page.
NOTE − The off portion of the selected ramp profile also ap­plies during heat pump operation in dual fuel applications.
TABLE 12
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 5 Switch 6
A (Factory) Off Off
B On Off C Off On D On On
Ramping Option A (Factory Selection)
D Motor runs at 50% for 30 seconds. D Motor then runs at 82% for approximately 7−1/2 minu-
tes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 30 sec-
onds then ramps down to stop.
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
Switches 3 and 4 −− Cooling Mode Blower Speed −−
Switches 3 and 4 are used to select cooling blower motor speed. The unit is shipped from the factory with the DIP switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below pro­vides the cooling mode blower speeds that will result from different switch settings. Refer to tables 14 through NO TAG for corresponding cfm values.
OFF
7 1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 45 sec-
onds then ramps down to stop.
Page 28
OFF
Page 29
Switches 7 and 8 −− Heating Mode Blower Speed −−
Switches 7 and 8 are used to select heating mode blower motor speed. The unit is shipped from the factory with the
OFF
100% CFM
DEMAND
100% CFM
45 SEC.
OFF
dip switches positioned for medium low (2) speed indoor blower motor operation during the heating mode. The table below provides the heating mode blower speeds that will result from different switch settings. Refer to tables 14
Ramping Option D
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
through NO TAG for corresponding L/s values.
TABLE 13
Heating Mode Blower Speeds
Speed
Switch 7 Switch 8
1 − Low On On
100% CFM
COOLING DEMAND
2 − Medium Low
(Factory)
OFFOFF
3 − Medium High On Off
4 − High Off Off
Off On
TABLE 14
G61MPVT−36B−070 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
Speed Switch Positions
ADJUST"
Switch
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
895 420 1025 485 1290 610 1340 630 1015 480 1190 560 1280 605 1395 660
NORM 820 385 940 445 1155 545 1210 570 930 440 1065 505 1155 545 1270 600
N/A
ADJUST"
Switch
Positions
+
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
820 385 930 440 1160 550 1210 570 730 345 815 385 865 410 935 440
NORM 760 360 865 410 1045 495 1090 515 680 320 755 355 795 375 855 405
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
N/A N/A 775 365 930 440 965 455 625 295 695 330 730 345 775 365
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
N/A 840 395 1020 480 1055 495 830 390 950 450 1010 475 1105 520
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
HEAT speed position.
Page 29
Page 30
TABLE 15
G61MPVT−60C−090 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
Speed Switch Positions
ADJUST"
Switch
Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1500 710 1675 790 1880 885 2090 985 1605 760 1710 805 1925 910 2165 1020
NORM 1355 640 1545 730 1720 810 1900 895 1440 680 1560 735 1755 825 1960 925
1194
ADJUST"
Switch
Positions
+
1360 640 1560 735 1730 815 1910 900 1105 520 1185 560 1355 640 1545 730
565 1365 645 1540 730 1695 800 1275 600 1380 650 1590 750 1755 830
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
NORM 1220 575 1405 665 1585 750 1740 820 995 470 1080 510 1205 570 1345 635
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1105 520 1235 585 1410 665 1570 740 890 420 960 455 1090 515 1215 575
HEAT speed position.
TABLE 16
G61MPVT−60C−090 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Switch
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1450 685 1640 775 1820 860 2055 970 1575 745 1690 795 1895 895 2135 1005
NORM 1320 625 1510 710 1700 800 1870 880 1405 665 1530 720 1735 820 1935 910
1165
ADJUST"
Switch
Positions
+
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1315 620 1510 715 1695 800 1875 885 1080 510 1160 545 1315 620 1490 705
NORM 1190 560 1365 645 1545 730 1715 810 985 465 1060 500 1185 560 1330 625
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1075 510 1205 570 1370 645 1520 715 865 410 930 440 1065 500 1185 560
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
550 1320 625 1500 705 1665 785 1250 590 1355 640 1560 735 1735 820
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
HEAT speed position.
Page 30
Page 31
TABLE 17
G61MPVT−60C−090 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return with optional RAB return air base
Speed Switch Positions
ADJUST"
Switch
Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1440 680 1630 770 1810 855 2015 950 1525 720 1655 780 1860 880 2100 990
NORM 1300 615 1485 700 1655 780 1830 865 1385 655 1500 710 1695 800 1905 900
1155
ADJUST"
Switch
Positions
+
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1320 625 1490 700 1665 785 1840 870 1060 500 1135 535 1285 605 1455 685
545 1310 620 1480 700 1640 775 1240 585 1320 625 1510 710 1695 800
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
NORM 1180 555 1345 635 1515 715 1680 795 960 455 1035 490 1165 550 1310 620
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1055 500 1180 560 1340 630 1490 705 865 405 920 435 1050 495 1165 550
HEAT speed position.
TABLE 18
G61MPVT−60C−110 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
Speed Switch Positions
ADJUST"
Switch
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1505 710 1710 805 1915 905 2130 1005 1625 770 1745 825 1990 940 2210 1045
NORM 1370 645 1565 740 1765 835 1945 920 1465 690 1580 745 1790 845 1995 940
1205
ADJUST"
Switch
Positions
+
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1370 645 1570 740 1760 830 1945 920 945 445 1020 480 1160 545 1300 615
NORM 1235 585 1420 670 1600 755 1780 840 840 395 910 430 1055 500 1180 555
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1105 525 1250 590 1420 670 1580 745 740 350 800 380 920 435 1045 495
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
570 1380 650 1565 740 1740 820 1290 610 1405 660 1605 760 1790 845
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
HEAT speed position.
Page 31
Page 32
TABLE 19
G61MPVT−60C−110 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Switch
Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1485 700 1675 790 1870 885 2080 980 1585 750 1700 800 1905 900 2135 1005
NORM 1350 637 1525 720 1725 815 1895 895 1435 680 1535 725 1740 820 1930 910
1175
ADJUST"
Switch
Positions
+
1325 625 1505 710 1695 800 1870 885 935 440 1025 485 1155 545 1285 605
555 1335 630 1505 710 1670 790 1280 605 1385 655 1570 740 1755 830
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
NORM 1195 565 1365 645 1550 730 1720 810 840 395 915 430 1050 495 1175 555
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1080 510 1205 570 1365 645 1530 720 750 355 800 380 925 435 1050 495
HEAT speed position.
TABLE 20
G61MPVT−60C−110 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air with optional RAB return base. −
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Switch
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1475 695 1670 790 1865 880 2070 980 1555 735 1685 795 1895 895 2130 1005
NORM 1345 635 1500 710 1695 800 1865 880 1415 670 1540 725 1735 820 1930 910
1180
ADJUST"
Switch
Positions
+
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1330 625 1510 715 1695 800 1875 885 1085 510 1155 545 1310 620 1475 695
NORM 1195 565 1375 650 1550 730 1725 815 955 450 1050 495 1185 560 1335 630
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1080 510 1210 570 1370 645 1520 715 850 400 920 435 1070 505 1195 565
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
555 1345 635 1510 710 1685 795 1245 590 1350 635 1545 730 1725 815
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
HEAT speed position.
Page 32
Page 33
TABLE 21
G61MPVT−60D−135 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom.
Speed Switch Positions
ADJUST"
Switch
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1505 710 1705 805 1900 900 2110 995 1615 760 1730 815 1945 920 2190 1035
NORM 1365 645 1550 730 1740 820 1920 905 1455 685 1580 745 1780 840 1985 935
1225
ADJUST"
Switch
Positions
+
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1385 655 1570 740 1760 830 1930 910 1135 535 1205 570 1365 645 1540 725
NORM 1250 590 1425 670 1595 755 1775 835 1025 485 1105 520 1235 580 1390 655
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
1135 535 1265 595 1430 675 1585 750 915 430 985 465 1115 525 1235 585
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
580 1380 650 1545 730 1720 810 1305 615 1400 660 1600 755 1780 840
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
HEAT speed position.
Page 33
Page 34
Unit Start−Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been under­water. A flood−damaged furnace is extremely dan­gerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified ser­vice technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
The gas valve on the G61MPVT is equipped with a gas control knob. Use only your hand to turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
G61MPVT units are equipped with an automatic ignition system. Do not furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with this ignition system.
attempt to manually light burners on this
WARNING
Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch.
Priming Condensate Trap
The condensate trap should be primed with water prior to start−up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into op-
eration.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes.
4 − Adjust the thermostat to deactivate the heating de-
mand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al­low the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating de-
mand and again wait for the combustion air inducer to stop. At this point, the trap should be primed with suffi­cient water to ensure proper condensate drain opera­tion.
BEFORE LIGHTING the unit, smell all around the fur­nace area for gas. Be sure to smell next to the floor be­cause some gas is heavier than air and will settle on the floor.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figure 34)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit. 4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand. 5 − Remove the upper access panel. 6 − Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise
34.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.
HONEYWELL VR8205 SERIES GAS VALVE
HIGH FIRE
ADJUSTING SCREW
(under cap)
LOW FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE TAP
GAS VALVE SHOWN IN OFF POSITION
8 − Honeywell VR8205 Gas Valve − Turn knob on gas
valve counterclockwise 9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.
to OFF. Do not force. See figure
MANIFOLD
PRESSURE
TAP
FIGURE 34
to ON. Do not force.
Page 34
Page 35
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service techni­cian or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting. 2 − Turn off all electrical power to the unit if service is to be
performed. 3 − Remove the upper access panel. 4 − Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise
to OFF. Do not force.
5 − Replace the upper access panel.
Gas Pressure Adjustment
Gas Flow (Approximate)
1 − Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for one revolu­tions of gas through the meter.
TABLE 22
3
Gas Flow Rate (Ft.
Seconds for 1
Revolution
1/2 cu ft Dial 1 cu ft Dial
10 180 360 12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 113 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 38 75 50 36 72 52 35 69 54 33 67 56 32 64 58 31 62 60 30 60
2 − Compare the number of seconds and the gas meter
size in table 22 to determine the gas flow rate. Multiply the gas flow rate by the heating value to determine the unit input rate. If manifold pressure is correct and the unit input rate is incorrect, check gas orifices for proper size and restriction.
/Hr.)
Gas Meter Size
3 − Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.
Manifold Pressure Measurement & Adjustment
NOTE − Pressure test adapter kit (10L34) is available from Lennox to facilitate manifold pressure measurement.
1 − Connect test gauge to outlet tap on gas valve.
2 − Disconnect pressure sensing hose from barbed fitting
on gas valve. Use an obstruction to plug the hose.
3 − Start unit on low heat and allow 5 minutes for unit to
reach steady state.
4 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue.
5 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
23.
6 − Repeat steps 3, 4 and 5 on high heat.
NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
NOTE − During this test procedure, the unit will be overfir­ing:
D Operate unit only long enough to obtain accurate read-
ing to prevent overheating heat exchanger.
D Attempts to clock gas meter during this procedure will
be inaccurate. Measure gas flow rate only during nor­mal unit operation.
7 − When test is complete remove obstruction from hose
and return hose to barbed fitting on gas valve.
Manifold Pressure and High Altitude Information
The units are factory−ready for use with natural gas. If LP/ propane fuel use is required, a conversion kit must be installed.
NOTE − A natural to L.P. propane gas changeover kit is nec­essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
Refer to table 23 for proper gas conversion kits and high al­titude pressure switch kits at varying altitudes. Table 24 lists high fire manifold pressure settings at varying alti­tudes.
The combustion air pressure switches are factory−set and require no adjustment.
Page 35
Page 36
TABLE 23
Conversion Kit Requirements
for Models −070, −090, −110 and −135
High Altitude Pressure Switch Kit
Input
−070 56M23 44W48 44W48 44W49 44W49
−090 56M23 44W48 44W48 44W49 44W49
−110 75M22 44W48 44W48 44W49 44W49
−135 Not allowed 44W48 Not allowed 44W49 Not allowed
NOTE − Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0−4500 feet (0−1372 m). *Two pressure switch assemblies required per unit.
ORDER TWO EACH
611 − 1372 m 0 − 610 m 611 − 1372 m 0 − 610 m 611−1372 m
LPG/Propane Kit LPG/Propane to
Natural Gas Kit
TABLE 24
Manifold Pressure (Outlet) at High Fire − kPa
Fuel
Natural 0.87 0.80 0.75 0.70
2
LPG/Propane 2.49 2.29 2.12 2.02
1
High Altitude Pressure Switch Kits required for certain models, see Gas Heat Accessories table for order number.
2
LPG/Propane conversion kit required, see Gas Heat Accessories table for order number.
0−610
1
611−914
Other Unit Adjustments
Altitude − m
1
915−1219
Thermostat Heat Anticipation
1
1220−1372
Set the heat anticipator setting (if adjustable) according to
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits are located in the blower compartment, attached to the back side of the blow­er. These limits are factory set and require no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the burner box. If tripped, check for adequate combustion air before resetting.
Pressure Switches (Two or Four)
The pressure switches are located in the heating compart­ment on the combustion air inducer. These switches check for proper combustion air inducer operation before allow­ing ignition trial. The switches are factory−set and require no adjustment.
Back−Up Secondary Limit (090, 110 & 135 Models)
The back−up secondary limit is located on the combustion air inducer. This switch protects the plastic components from overheating due to indoor blower motor failure. If tripped, check for proper blower operation before resetting.
Temperature Rise
After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to do adjust the temperature rise may cause erratic limit operation.
the amp draw listed on the wiring diagram that is attached to the unit.
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the air ducts or structure.
Electronic Ignition
The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re­set device for ignition control lockout caused by ignition fail­ure. This type of lockout is usually due to low gas line pres­sure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat de­mand to the furnace and automatically reset the control to begin the ignition sequence.
Exhaust and Air Intake Pipe
1 − Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 − Are pressure switches closed? Obstructed exhaust
pipe will cause unit to shut off at pressure switches. Check exhaust pipe and termination for blockages.
3 − Reset manual flame rollout switches on burner box
cover.
Failure To Operate
If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse?
Page 36
Page 37
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lock out? If the unit locks out
again, call the service technician to inspect the unit for
blockages.
Heating Sequence of Operation
NOTE − The heat staging jumper on the control board is factory−set in the NONE (or no delay) position.
Applications Using a Two−Stage Thermostat
A − Heating Sequence −− Control Board Heat Staging Jumper in NONE Position (Factory Setting)
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be­gins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc­curs. At the same time, the control module sends a sig­nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener­gized on the low fire heating speed. The furnace will continue this operation as long as the thermostat has a first−stage heating demand.
5 − If second−stage heat is required, the thermostat sec-
ond−stage heat contacts close and send a signal to the integrated control.
6 − The integrated control energizes the combustion air
inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the the control receives a signal that the high−fire pressure switch is close, the high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.
7 − When the demand for high−fire (second stage) heat is
satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.
8 − When the thermostat demand for low−fire (first stage)
heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.
9 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Applications Using A Single−Stage Thermostat
B − Heating Sequence −− Control Board Heat Staging Jumper in Either 10−Minute or 15−Minute Stage Delay Position
NOTE − In these applications, two−stage heat will be initi­ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be­gins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc­curs. At the same time, the control module sends a sig­nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener­gized on the low−fire heating speed. The integrated control also initiates a second−stage on delay of either 10 minutes or 15 minutes.
5 − If the heating demand continues beyond the second−
stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the control receives a sig­nal the high−fire pressure switch is closed, the high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.
6 − When the thermostat heating demand is satisfied, the-
combustion air inducer begins a 5−second post−purge. The field−selected indoor blower off delay begins.
7 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Page 37
Page 38
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis­connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
All G61MPVT filters are installed external to the unit. Fil­ters should be inspected monthly. Clean or replace the fil­ters when necessary to ensure proper furnace operation. Table 3 lists recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage.
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassem­bling unit. Use papers or protective covering in front of fur­nace while removing heat exchanger assembly.
1 − Turn off electrical and gas supplies to the furnace. 2 − Remove the upper and lower furnace access panels.
3 − Mark all gas valve wires and disconnect them from
valve.
4 − Remove gas supply line connected to gas valve. Re-
move gas valve/manifold assembly.
5 − Remove sensor wire from sensor. Disconnect 2-pin
plug from the ignitor. 6 − Disconnect wires from flame roll−out switches. 7 − Remove burner box cover and remove four burner box
screws at the vestibule panel and remove burner box.
Set burner box assembly aside.
NOTE − G61MPVT−135 units are secured to the vesti-
bule panel by two additional screws. These screws
must be removed for servicing; however it is not nec-
essary to replace the screws.
NOTE − If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
8 − Loosen three clamps and remove flexible exhaust tee. 9 − Remove 3/8 inch rubber cap from condensate drain
plug and drain. Replace cap after draining. 10 − Disconnect condensate drain line from the conden-
sate trap. Remove condensate trap (it may be neces-
sary to cut drain pipe). Remove screws that secure
condensate collars to either side of the furnace and re-
move collars. Remove drain tubes from cold end
header collector box. 11 − Disconnect condensate drain tubing from flue collar.
Remove screws that secure both flue collars into
place. Remove flue collars. It may be necessary to cut
the exiting exhaust pipe for removal of the fittings. 12 − Mark and disconnect all combustion air pressure tub-
ing from cold end header collector box. 13 − Mark and remove wires from pressure switches. Re-
move pressure switches. Keep tubing attached to
pressure switches. 14 − Disconnect the 3-pin plug from the combustion air in-
ducer. Disconnect the two wires to the backup secon-
dary limit, if applicable. Remove four screws which se-
cure combustion air inducer to collector box. Remove
combustion air inducer assembly. Remove ground
wire from vest panel. 15 − Remove electrical junction box from the side of the fur-
nace. 16 − Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck. 17 − Remove the primary limit from the vestibule panel. 18 − Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger. 19 − Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as-
sembly to cabinet. Remove two screws from blower
rail which secure bottom heat exchanger flange. Re-
move heat exchanger from furnace cabinet.
Page 38
Page 39
20 − Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 135°C
(275°F).
21 − Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire assembly.
22 − Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly are resting on the support located at the rear of the cabi­net. Remove the indoor blower to view this area through the blower opening.
23 − Re-secure the supporting screws along the vestibule
sides and bottom to the cabinet.
24 − Reinstall cabinet screws on front flange at blower
deck. 25 − Reinstall the primary limit on the vestibule panel. 26 − Route heating component wiring through hole in blow-
er deck and reinsert strain relief bushing. 27 − Reinstall electrical junction box. 28 − Reinstall the combustion air inducer. Reconnect the
3−pin plug to the wire harness. Reconnect the two
wires to the backup secondary limit, if applicable. 29 − Reinstall pressure switches and reconnect pressure
switch wiring. 30 − Carefully connect combustion air pressure switch
hosing from pressure switches to proper stubs on
cold end header collector box. 31 − Reinstall condensate collars on each side of the fur-
nace. Reconnect drain tubing to collector box. 32 − Reinstall condensate trap on same side as exhaust
pipe. Reconnect condensate drain line to the conden-
sate trap. 33 − Use securing screws to reinstall flue collars to either
side of the furnace. Reconnect exhaust piping and ex-
haust drain tubing. 34 − Replace flexible exhaust tee on combustion air induc-
er and flue collars. Secure using three existing hose
clamps. 35 − Reinstall burner box assembly in vestibule area. 36 − Reconnect flame roll−out switch wires. 37 − Reconnect sensor wire and reconnect 2−pin plug from
ignitor. 38 − Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
39 − Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve. 40 − Reinstall burner box cover. 41 − Reconnect wires to gas valve. 42 − Replace the blower compartment access panel. 43 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies. 44 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly. 45 − Replace heating compartment access panel.
Cleaning the Burner Assembly
1 − Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels. 2 − Mark all gas valve wires and disconnect them from the
valve. 3 − Disconnect the gas supply line from the gas valve. Re-
move gas valve/manifold assembly. 4 − Mark and disconnect sensor wire from the sensor. Dis-
connect 2-pin plug from the ignitor at the burner box. 5 − Remove burner box cover and remove four screws
which secure burner box assembly to vest panel. Re-
move burner box from the unit.
NOTE − G61MPVT−135 units are secured to the vesti-
bule panel by two additional screws. These screws
must be removed for servicing; however it is not nec-
essary to replace the screws.
6 − Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block-
age caused by foreign matter. Remove any blockage. 7 − Reconnect the sensor wire and reconnect the 2−pin
plug to the ignitor wiring harness. 8 − Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports. 9 − Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn-
er box cover. 10 − Reconnect the gas valve wires to the gas valve. 11 − Replace the blower compartment access panel. 12 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies. 13 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly. 14 − Replace heating compartment access panel.
Page 39
Page 40
Requirements
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
G61MPVT units are certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figures 3, 9 and 6. Accessibility and service clearances must take precedence over fire protection clear­ances.
NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 457mm (18 inches) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code or AS 5601 standard.
NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation.
This G61MPVT furnace must be installed so that its electri­cal components are protected from water.
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually oper­ated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes.
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 16°C (60°F) or an intermit­tent operation down to 13°C (55°F) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 29°C (85°F) dry bulb.
The G61MPVT furnace may be installed in alcoves, clos­ets, attics, basements, garages, and utility rooms. This fur­nace design has not been certified for installation in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Lennox does not recommend the use of G61MPVT units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
G61MPVT units may be used for heating of buildings or structures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 16°C (60°F) and
27°C (80°F) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a G61MPVT furnace:
Place the furnace as close to the center of the air dis­tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
When the furnace is installed in non−direct vent applica­tions, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
When the furnace is installed in non−direct vent applica­tions, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
Page 40
Page 41
When the furnace is installed in an attic or other insu­lated space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
CAUTION
G61MPVT unit should not be installed in areas nor­mally subject to freezing temperatures.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool.
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
If the G61MPVT is installed as a Non−Direct Vent Fur­nace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, ap­pliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combus− tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a po− tentially dangerous situation.
In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install G61MPVT furnaces to ensure effi­cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI− Z223.1/NFPA 54). This reprinted material is not the com­plete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Australia, refer to the standard AS 5601−2004 Gas Installation Code.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De−icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliance will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex­haust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Page 41
Page 42
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 1.42 m per .29 kW (50 cubic feet per 1,000Btu) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 1.42 m per .29 kW (50 cubic feet per 1,000Btu) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 645 mm
2
per .29 kW (1 square inch per 1,000Btu) per hour
of total input rating of all gas−fired equipment in the con­fined space. Each opening must be at least 64516 mm
3
(100 square inches). One opening shall be within 305 mm (12 inches) of the top of the enclosure and one opening within 305 mm (12 inches) of the bottom.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
3
TERMINATED EX-
HAUST PIPE (ALTER-
NATE LOCATION)
NOTE − Each opening shall have a free area of at least 645mm .29kW (one square inch per 1,000 Btu) per hour of the total input rat­ing of all equipment in the enclosure, but not less than 64516mm. (100 square inches).
G61MPV
T
(To Adjacent
Unconfined
Space)
FIGURE 35
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 305mm (12 inches) of the top of the enclosure and one within 305mm (12 inches) of the bottom. These openings must commu­nicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall
2
have a minimum free area of 645mm
per 1.17kW (1 square inch per 4,000 Btu) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall
2
have a minimum free area of 645mm
per .59kW (1 square inch per 2,000 Btu) per total input rating of all equipment in the enclosure.
2
2
per
2
Page 42
Page 43
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 75mm (3 inches). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
OUTLET
AIR
G61MPVT
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12" above
bottom)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
VENTILATION
LOUVERS
(For unheated
crawl space)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least 645mm
G61MPV
INLET
T
AIR
2
per 1.17kW (one square inch per 4,000 Btu) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 36
NOTE−The inlet and outlet air openings shall each have a free area of at least 645mm
2
per 1.17kW (one square inch per 4,000 Btu) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 37
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−Each air duct opening shall have a free area of at least
2
645mm
per .59kW (one square inch per 2,000 Btu) per hour of the
G61MPVT
INLET AIR
total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings com­municate directly with the outdoors, each opening shall have a free area of at least 645mm
2
per 1.17kW (one square inch per 4,000 Btu) per hour of the total input rating of all other equipment in the enclosure.
FIGURE 38
Page 43
Page 44
Ignition Control Board Diagnostic Codes (Red LED)
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
Pulse A 1/4 second flash followed by four seconds of off time.
Heartbeat Constant 1/2 second bright and 1/2 second dim cycles.
X + Y
Pulse Power on − Standby.
Heartbeat Normal operation − signaled when heating demand initiated at thermostat.
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four seconds, then repeats.
FLAME CODES
1 + 2 Low flame current −− run mode.
1 + 3 Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3 Low pressure switch failed open.
2 + 4 Low pressure switch failed closed.
2 + 5 High pressure switch failed open.
2 + 6 High pressure switch failed closed.
2 + 7 Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1 Limit switch open.
WATCHGUARD CODES
4 + 1 Watchguard −− Exceeded maximum number of retries.
4 + 2 Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3 Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5 Watchguard −− Limit remained open longer than three minutes.
4 + 6
4 + 7 Ignitor circuit fault −− Failed ignitor or triggering circuitry.
4 + 8 Low line voltage.
Watchguard −− Flame sensed out of sequence; flame signal gone.
HARD LOCKOUT CODES
5 + 1 Hard lockout −− Rollout circuit open or previously opened.
5 + 2 Control failed self check, internal error (control will restart if error recovers).
5 + 3 No Earth ground (control will restart if error recovers).
5 + 4 Reversed line voltage polarity (control will restart if the error recovers).
5 + 6 Low secondary (24VAC) voltage.
Page 44
Page 45
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
CONTROL SELF−CHECK OKAY?
NO
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.)
NO
POLARITY OKAY?
YES
IS THERE A
PROPER GROUND?
YES
A
NORMAL OPERATION:
STATUS LED −− PULSE
B
THERMOSTAT CALLS FOR HEAT:
STATUS LED −− HEARTBEAT
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
ROLLOUT SWITCH CLOSED?
YES
FIRST (LOW) STAGE PRESSURE SWITCH
CONTACTS OPEN?
YES
SECOND (HIGH) STAGE PRESSURE SWITCH
CONTACTS OPEN?
YES
NO
NO
NO
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
INDOOR BLOWER ON. HAS PRIMARY OR
SECONDARY LIMIT RESET WITHIN 3 MINUTES?
NO
NO
NO
60−MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
POLARITY REVERSED.
STATUS ERROR CODE 5 + 4.
STATUS ERROR CODE 5 + 3.
COMBUSTION AIR INDUCER OFF.
STATUS ERROR CODE 3 + 1.
NO
STATUS ERROR CODE 4 + 5.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1.
STATUS ERROR CODE 2 + 4
YES
NO
YES
TWO−STAGE OR SINGLE−STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
STATUS LED −− HEARTBEAT
CONTINUED ON NEXT PAGE
COMBUSTION AIR INDUCER OFF.
GAS VALVE OFF.
INDOOR BLOWER OFF.
CONTROL WILL NOT ATTEMPT SECOND−STAGE
OPERATION DURING THIS HEAT DEMAND.
FIRST−STAGE OPERATION WILL BE ATTEMPTED.
STATUS ERROR CODE 2 + 6.
Page 45
Page 46
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
THERMOSTAT CALLS FOR HEAT
STATUS LED − HEARTBEAT
(Refer to box A on previous page)
FIRST−STAGE (LOW FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
YES
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED FIRST−STAGE
PRESSURE SWITCH (or 15 SECOND
INTER−PURGE PERIOD.)
STATUS LED −− HEARTBEAT.
IGNITOR WARM−UP (20 SECONDS)
STATUS LED −− HEARTBEAT.
YES
IS IGNITOR INTACT AND CONNECTED?
YES
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
YES
4−SECOND FLAME STABILIZATION PERIOD.
NO
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
STATUS ERROR CODE 2 + 3.
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED
OR RECONNECTED.
STATUS ERROR CODE 4 + 7.
IS VOLTAGE ABOVE 90 VOLTS?
NO
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95
VOLTS. STATUS ERROR CODE 4 + 8.
YES
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.20 microamps)
FLAME PRESENT?
YES
CONTINUED ON NEXT PAGE
NO
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
STATUS LED −− HEARTBEAT.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
STATUS ERROR CODE 4 + 1.
IS 60−MINUTE RESET PERIOD COMPLETE?
YES
HAS CONTROL RESET IGNITION SEQUENCE
FOUR (4) TIMES?
WATCHGUARD MODE.
STATUS ERROR CODE 4 + 3.
NO
YES
NO
Page 46
Page 47
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
FLAME SIGNAL ABOVE
(u1.40 microamps)
YES
SINGLE−STAGE THERMOSTAT MODE
(Heat staging jumper on 10 or 15 minutes)
YES
START SECOND−STAGE ON DELAY
(10 OR 15 MINUTES).
STATUS LED −− HEARTBEAT
ROLLOUT SWITCHES CLOSED?
NO
YES
TWO STAGE THERMOSTAT MODE
(Heat staging jumper on NONE)
45−SECOND INDOOR BLOWER ON DELAY BEGINS.
YES
NO
THERMOSTAT CALLS FOR HEAT.
STATUS LED −− HEARTBEAT.
SEE BOX A.
LOW FLAME SIGNAL
(Does not affect control operation)
STATUS ERROR CODE 1 + 2.
YES
STATUS LED −− HEARTBEAT.
YES
PRIMARY & SECONDARY LIMIT SWITCHES
CLOSED?
NO
YES
FIRST−STAGE (LOW FIRE)
PRESSURE SWITCH CLOSED?
YES
NO
FIRST−STAGE HEAT DEMAND SATISFIED?
YES
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
STATUS LED −− PULSE
SECOND−STAGE HEAT DEMAND.
SECOND−STAGE HEAT DEMAND REQUIRED?
YES
SECOND STAGE PRESSURE SWITCH CLOSED?
ABNORMAL FLASH CODE.
NOTE − IF SECOND−STAGE PRESSURE SWITCH
WAS ORIGINALLY FOUND CLOSED,
ABNORMAL CODE WILL FLASH.
NO
SECOND−STAGE BEGINS.
STATUS LED −− HEARTBEAT.
YES
SECOND−STAGE COMBUSTION AIR INDUCER
ON. SECOND−STAGE GAS VALVE ON. HIGH
HEAT INDOOR BLOWER SPEED ON.
STATUS LED −− HEARTBEAT.
YES
SECOND−STAGE PRESSURE SWITCH CLOSED
IN LESS THAN TEN (10) SECONDS?
STATUS LED −− HEARTBEAT
YES
CONTINUED ON NEXT PAGE
YES
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
YES
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS
UNTIL ROLLOUT SWITCH IS RESET AND MAIN
POWER IS INTERRUPTED OR THERMOSTAT
IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
(Indoor blower on low speed during 3−minute period)
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
IS 60−MINUTE RESET PERIOD COMPLETE?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF AFTER DELAY.
STATUS ERROR CODE 2 + 3. CONTROL RESTARTS
IGNITION SEQUENCE IF PRESSURE SWITCH
SECOND−STAGE PRESSURE SWITCH CLOSED
RETURNS TO FIRST−STAGE HEAT MODE WHICH CONTINUES UNTIL SECOND−STAGE PRESSURE
SWITCH CAN BE PROVEN or HEAT DEMAND IS
SATISFIED. FIVE (5) MINUTE WAIT PERIOD
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS
CONTINUES FIRST−STAGE HEATING DEMAND.
WILL NOT REATTEMPT SECOND−STAGE
INDOOR BLOWER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 3 + 1.
HAS PRIMARY OR SECONDARY LIMIT
SWITCH CLOSED WITHIN 3 MINUTES?
NO
LIMIT SWITCH WATCHGUARD MODE.
INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5
CLOSES WITHIN 2−1/2 MINUTES.
AT BEGINNING OF HEAT DEMAND?
STATUS ERROR CODE 2 + 6.
SECOND STAGE HEAT DEMAND
STATUS LED −− HEARTBEAT.
NO
MADE FOR SECOND−STAGE HEAT?
YES
HEATING DEMAND.
STATUS ERROR CODE 2 + 5.
YES
YES
YES
NO
Page 47
Page 48
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
NORMAL OPERATION.
SEE BOX A
SECOND−STAGE (HIGH FIRE) HEAT
PRESSURE SWITCH CLOSED?
YES
HEAT DEMAND SATISFIED? STATUS LED −− HEARTBEAT.
YES
SINGLE−STAGE THERMOSTAT MODE
(Heat staging jumper on 10− or 15−minutes)
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5−SECOND
LOW SPEED POST PURGE PERIOD,
INDOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
STATUS LED −− HEARTBEAT.
FIRST−STAGE CONTINUES UNTIL SECOND−
NO
YES
TWO STAGE THERMOSTAT MODE?
(Heat staging jumper on NONE)
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
STATUS LED −− HEARTBEAT.
STAGE PRESSURE SWITCH CAN BE PROVEN
or HEAT DEMAND IS SATISFIED. A FIVE (5)
MINUTE WAIT PERIOD IS INITIATED BEFORE
YES
THERMOSTAT CALLS FOR HEAT.
RETURN TO FIRST−STAGE HEAT MODE.
RETRY. WERE 5 ATTEMPTS MADE FOR
FIRST−STAGE HEAT DEMAND SATISFIED?
SEE BOX B
SECOND−STAGE HEAT?
NO
SEE BOX C
NO
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST−
STATUS LED −− HEARTBEAT.
SECOND STAGE HEAT
DEMAND SASTISFIED?
STATUS LED −− HEARTBEAT.
YES
STAGE OPERATION.
YES
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY. STATUS LED −− PULSE.
FIRST STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5−SECOND LOW SPEED POST−
PURGE PERIOD. INDOOR BLOWER OFF.
DELAY INITIATED ON LOW HEAT SPEED.
STATUS LED −− PULSE.
YES
Page 48
Page 49
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
POWER ON
YES
IS POLARITY REVERSED?
NO
CONTROL WILL CONTINUE TO CALL FOR COOLING
SIGNAL POLARITY REVERSED.
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.
IS THERE
PROPER GROUND?
YES
THERMOSTAT CALLS FOR FIRST−STAGE COOL.
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
INDOOR BLOWER ENERGIZED ON FIRST STAGE
COOL SPEED AFTER 2 SECOND DELAY.
FIRST−STAGE DEMAND FOR COOL SATISFIED?
NO
THERMOSTAT CALLS FOR SECOND−STAGE COOL.
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
NO
YES
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 3.
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
INDOOR BLOWER DE−ENERGIZED AFTER 45−SECOND
DELAY.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL .
Page 49
Page 50
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
YES YES
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
AFTER 45−SECOND DELAY, INDOOR BLOWER
YES
SWITCHES TO LOW HEAT SPEED.
YES
FIRST−STAGE COOL DEMAND SATISFIED?
NO
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
SECOND STAGE COOL DEMAND SATISFIED?
YES
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
FIRST−STAGE HEAT DEMAND SATISFIED.
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECONDS.
YES
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
YES
Page 50
Page 51
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the nameplate −− Example: G61MPVT−36B−070−01.
Cabinet Parts
Upper access panel Blower access panel Top Cap
Control Panel Parts
Transformer Integrated control board Door interlock switch Circuit Breaker
Blower Parts
Blower wheel Motor Motor mounting frame Blower housing cutoff plate
Vent Pipe Sizing Worksheet
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Proposed vent pipe size : ______
Termination kit catalog number : _____________ Vent pipe equivalency value from table 6 : ______
Total number of 90° elbows required (indoors and outdoors) ______ X 1.5 = ______ equivalent meters of pipe
Total number of 45° elbows required (indoors and outdoors) ______ X .76 = ______ equivalent meters of pipe
Linear feet of straight pipe required : ______
Add equivalent meters of vent pipe listed in steps 2 through 5.
Heating Parts
Flame Sensor
Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure switches Ignitor Primary limit control Secondary limit control Flame rollout switches Combustion air inducer auxiliary limit
Equivalent Meters
TOTAL
If the total is equal to, or less than, the allowable maximum given in table 6, the proposed pipe size is acceptable. If the total exceeds the maximum allowed vent pipe length, repeat the process above using the next larger diameter pipe until an acceptable total is achieved.
NOTE − In Direct Vent systems, total the equivalent length of either the exhaust OR intake piping run, depending upon which will be LONGER. Intake and exhaust pipe diameter must be the same size and must be terminated in the same pressure zone. Intake and exhaust pipe should be roughly the same length.
Page 51
Page 52
G61MPVT Start−Up & Performance Check List
Job Name
Job Location
Installer Unit Model No. Serial No.
Job No.
City
City Technician
Date
State
State
Heating Section
Electrical Connections Tight? Supply Voltage
Blower Motor Amps
Fuel Type: Natural Gas?
Furnace Btu Input
Line Pressure
Regulator Pressure Flue Connections Tight? Condensate Connections Tight? Combustion Gas Tested? Fan Control Setting
(45 Seconds Fixed On)
Fan Control Off Setting Filter Clean & Secure?
w.c. − Nat.:
CO
LP/Propane Gas?
2
Blower Motor H.P.
Gas Piping Connections Tight & Leak−Tested?
w.c. − LP/Propane
Proper Draft?
CO
Temperature Rise
Vent Clear?
Thermostat
Calibrated? Heat Anticipator Properly Set? Level?
Page 52
Loading...