G61MPV series units are high−efficiency multi−position
(upflow, downflow, horizontal right and left) gas furnaces
manufactured with Lennox Duralok Plust heat exchang-
ers formed of an aluminized steel primary with a stainless
steel secondary condensing coil. G61MPV units are available in heating capacities of 44,000 to 132,000 Btuh
(13.0.0 to 38.6 kW) and cooling applications from 2 to 5
tons (7.0 kW to 17.5 kW). Refer to Engineering Handbook
for proper sizing.
Units are factory equipped for use with natural gas. Kits are
available for conversion to LPG operation. G61MPV model
units are equipped with the two−stage variable speed integrated SureLight® control. All G61MPV units meet the California Nitrogen Oxides (NO
sonal Efficiency requirements. All units use a redundant gas
valve to assure safety shut−off as required by C.S.A.
) Standards and California Sea-
x
G61MPV
All specifications in this manual are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommendations only and do not constitute code.
VII Wiring and Sequence of OperationPage 71. . . . . .
VIII Field Wiring and Jumper SettingPage 86. . . . . . . .
IX Control Board TroubleshootingPage 91. . . . . . . . . .
IMPORTANT
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a qualified installer, service agency
or the gas supplier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect switch(es). Unit may have multiple
power supplies.
WARNING
Sharp edges.
Be careful when servicing unit to avoid sharp edges
which may result in personal injury.
NOTE − Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non−weatherized furnaces.
Gas
Heating
Performance
High Fire
ModelNo.G61MPV
−60C−090
Input− Btuh88,000
G61MPV
−60C−091
G61MPV
−60C−110
G61MPV
−60C−111
G61MPV
−60D−135
88,000110,000110,000132,000
Output− Btuh81,00084,00099,000103,000122,000
Temperature rise range − _F40 − 7040 − 7050 − 8050 − 8065 − 95
NOTE − Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non−weatherized furnaces.
Page 2
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
p
Di
t
Applications
p
Kit
B" Width ModelsC" Width ModelsD" Width Models
FILTER KITS
1
Air Filter and
Rack Kit
EZ Filter Base
Horizontal (end)Size of filter − in.87L96 − 18 x 25 x 187L97 − 20 x 25 x 187L98 − 25 x 25 x 1
Side Return
Single44J2244J2244J22
Ten Pack66K6366K6366K63
Size of filter − in.16 x 25 x 116 x 25 x 116 x 25 x 1
SignatureStatt Home Comfort Control81M2781M2781M27
TERMINATION KITS − See Installation Instructions for specific venting information.
2
Termination
Concentric
Kits
rect Ven
Applications
Wall − Close Couple
Only
Close Couple WTK 2 in.30G28− − −− − −
2
Termination
s − Direct or
Non−Direct Vent
2
Roof Termination Flashing Kit − Direct or Non−Direct
Roof2 in.15F7515F75
Wall − Wall Ring Kit2 in.15F7415F74
Vent − Contains two flashings.
1
Cleanable polyurethane frame type filter.
2
Kits contain enough parts for two, non−direct vent installations.
3
Non−direct vent only.
2 in.71M8069M29− − −
3 in.− − −60L4660L46
2 in.22G44− − −− − −
3 in.44J4044J4044J40
3 in.81J2081J2081J20
− − −
3
15F74
44J4144J4144J41
GAS HEAT ACCESSORIES
High Altitude
Orifice Kit
Input
Natural Gas
Only
7501−10,000 ft.2001−4500 ft.4501−7500 ft. 7501−10,000 ft.0−7500 ft.7501−10,000 ft.0−7500 ft.
−04559M17− − −− − −− − −59M1359M1459M8759M87
−07059M17− − −− − −56M2359M1359M1459M8759M87
−07159M1775M2275M2256M2159M1359M1459M8759M87
−09059M17− − −75M2256M2159M1359M1459M8759M87
−090
(036C−9
and
later
models)
59M17− − −24W5124W4959M1359M1459M8759M87
−09147M8226W8526W8526W8659M1359M1459M8759M87
−11059M17− − −56M2375M2259M1359M1459M8759M87
−11147M8256M2256M2256M2359M1359M1459M8759M87
−13559M17− − −56M9356M9359M1359M1459M8759M87
1
High Altitude Orifice Kit is required and must be ordered separately for applications from 7501 to 10,000 ft.
High Altitude Pressure Switch Kit
ORDER TWO EACH
Page 3
LPG/Propane Kit
LPG/Propane to
Natural Gas Kit
1
7501−10,000 ft.
BLOWER DATA
ADJUST"
Stc
Positions
BLOWER DATA
G61MPV−36B−045 BLOWER PERFORMANCE (less filter)
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 442 cfm.
G61MPV−36B−045 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
G61MPV−36B−070 BLOWER PERFORMANCE (less filter)
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
G61MPV−36B−070 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
G61MPV−36B−071 BLOWER PERFORMANCE (less filter)
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
G61MPV−36B−071 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1709011 0135160180195215240100120140165190210235255275
Tap 2115
Tap 3205230265295325355380410425290320350380415440465490480
Tap 4220250290325360390425455455310345375410445475500525515
COOL"
Speed
Tap 1557090110130145165185200145170195220245270295320345
Tap 27 0
Tap 39 0105130150170195220240260265300340375415440465490505
Tap 4110130155180205230250270295360390425460495515540560535
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1607595115135155175195215759511 5140160180200220240
Tap 28 0
Tap 3150170200225250275300325350210235260285315345375405425
Tap 4165190220250280310335360385230260290325355380405430435
COOL"
Speed
Tap 14560809511 513015016518511 0130155180205225245265285
Tap 26 0
Tap 37 085105130150170190215235205230260290320350380410420
Tap 48 0100125150170195215240260260290320355390415440470480
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
Speed
Tap 15065851001201401551751957090105125145165185205215
Tap 26 5
Tap 3105125150180205225245265290145170195225255270290305325
Tap 4115135165190215240260285310160185215240270290310330350
COOL"
Speed
Tap 1405570851001201351551707595120140165185205225245
Tap 24 5
Tap 35 57090110130150165185205140165190215245265290315340
Tap 46075100120140165185205225180205235265295320345365390
G61MPV−36C−090 BLOWER PERFORMANCE (less filter)
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 479 cfm.
G61MPV−36C−090 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
G61MPV−60C−090 BLOWER PERFORMANCE (less filter)
Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side.
0 through 0.80 in. w.g. External Static Pressure Range
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm.
HEAT speed position.
G61MPV−60C−090 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Jumper Speed
First StageSecond Stage
00.10.20.30.40.50.60.70.800.10.20.30.40.50.60.70.8
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
G61MPV−60C−090 BLOWER PERFORMANCE (less filter)
Side Return Air with Optional RAB Return Air Base
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm.
G61MPV−60C−090 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
G61MPV−60C−090 BLOWER PERFORMANCE (less filter)
Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in
order to maintain proper air velocity across the filter.
0 through 0.80 in. w.g. External Static Pressure Range
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm.
HEAT speed position.
G61MPV−60C−090 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Jumper Speed
First StageSecond Stage
00.10.20.30.40.50.60.70.800.10.20.30.40.50.60.70.8
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
G61MPV−60C−091 BLOWER PERFORMANCE (less filter)
Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side.
0 through 1.00 in. w.g. External Static Pressure Range
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
HEAT speed position.
G61MPV−60C−091 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Tap 3 145165190215235260280305325385410440470495535570605630
Tap 4 190215240265290315345370395485520555590625660700735765
Speed Switch Positions
1
4
1
4
Page 11
BLOWER DATA
ADJUST"
Stc
Positions
G61MPV−60C−091 BLOWER PERFORMANCE (less filter)
Side Return Air with Optional RAB Return Air Base
0 through 1.00 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
G61MPV−60C−091 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1 210235265295325350380405435265295330365400425450480500
Tap 2 270
Tap 3 430455490520550580610645675530656600640675700730755775
Tap 4 525560600635675710750790825680725775820870905935970995
COOL"
Speed
Tap 1 145165185210230255275295315353380410440470500530555580
Tap 2 175
Tap 3 230260285315345370395420450640680725765810840870905890
Tap 4 335365390415445470500525560855885915940970970965965935
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1 160185210235260280305325355195225255285320345365390420
Tap 2 205
Tap 3 325350375400430455475500530415445475505540570605635665
Tap 4 410445475510545575605640670505545585625660700740780815
COOL"
Speed
Tap 1 105125150170195220240261280260285315345375400420445475
Tap 2 135
Tap 3 175200225250275305330360375475515555595635665695730760
Tap 4 235260290320350375405430460625665705750790815840865855
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
Speed
Tap 1 120140165190215235260285305150170195220245270295320345
Tap 2 145
Tap 3 230255285315345370395420445310335365390415445470495520
Tap 4 280315350385420450480515540385415445480515545580610640
COOL"
Speed
Tap 1 85100120140160180195215235195220245270295315335360385
Tap 2 100
Tap 3 140155180200225245265285305375400430455485520555590620
Tap 4 180205230255280305330355380450480515545580610645675705
G61MPV−60C−091 BLOWER PERFORMANCE (less filter)
Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in
order to maintain proper air velocity across the filter.
0 through 1.00 in. w.g. External Static Pressure Range
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
HEAT speed position.
G61MPV−60C−091 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Tap 3 145165185210235255275300320375400430460490525560595620
Tap 4 190215240265290320345375400475510545575610645680715745
Speed Switch Positions
1
4
1
4
Page 13
BLOWER DATA
ADJUST"
Stc
Jumper
Speed
G61MPV−60C−110 BLOWER PERFORMANCE (less filter)
Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side.
0 through 0.80 in. w.g. External Static Pressure Range
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm.
HEAT speed position.
G61MPV−60C−110 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Speed
Positions
0.10.20.30.40.50.60.70.800.10.20.30.40.50.60.70.8
0
First Stage
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
G61MPV−60C−110 BLOWER PERFORMANCE (less filter)
Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in
order to maintain proper air velocity across the filter.
0 through 0.80 in. w.g. External Static Pressure Range
Factory default jumper setting.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm.
HEAT speed position.
G61MPV−60C−110 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
First StageSecond Stage
Speed
Positions
r
0.10.20.30.40.50.60.70.800.10.20.30.40.50.60.70.8
0
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
G61MPV−60C−110 BLOWER PERFORMANCE (less filter)
Side Return Air with Optional RAB Return Air Base
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm.
G61MPV−60C−110 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
G61MPV−60C−111 BLOWER PERFORMANCE (less filter)
Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side.
0 through 1.00 in. w.g. External Static Pressure Range
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
HEAT speed position.
G61MPV−60C−111 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Tap 3 115135160185205230250270295305335370405440470505540570
Tap 4 155175205230260285310335360425460495530570595625655690
Speed Switch Positions
1
4
1
4
Page 17
BLOWER DATA
ADJUST"
Stc
Positions
G61MPV−60C−111 BLOWER PERFORMANCE (less filter)
Side Return Air with Optional RAB Return Air Base
0 through 1.00 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
G61MPV−60C−111 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1 165190225255290320355385410210245280320355385410440470
Tap 2 210
Tap 3 385415445475505535570600625490520560595630660690720745
Tap 4 490525565600640680720760790620660705750795835870910945
COOL"
Speed
Tap 1 115130155180205225250270290310335365390415445470500525
Tap 2 145
Tap 3 180210240270300330355380405530570615655700735775810845
Tap 4 265295325360390420450480510715750795835875900930960960
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1 140160185205230255285310340155185215250280310340365395
Tap 2 175
Tap 3 295320350380405430455485505360390425460490520550585610
Tap 4 375405445480515545580610640460495540580620660700740770
COOL"
Speed
Tap 1 85105130150175190210225250200230260295325355385410440
Tap 2 105
Tap 3 135160185210235260280305330425455490525560590620650685
Tap 4 180210240270300330355385415545580615651690730770810835
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
Speed
Tap 1 105125150170195220240265285135155175200225250275300325
Tap 2 135
Tap 3 210230255280305335365395420275300325350375400430455485
Tap 4 265295325355390425465500530350380410440475510545580610
COOL"
Speed
Tap 1 7085105120140160180205220150170195220250275300325350
Tap 2 85
Tap 3 110130150175195215235255280300330360395430460495530560
Tap 4 145170195220245270295320345395425455490525550580605635
G61MPV−60C−111 BLOWER PERFORMANCE (less filter)
Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in
order to maintain proper air velocity across the filter.
0 through 1.00 in. w.g. External Static Pressure Range
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm.
HEAT speed position.
G61MPV−60C−111 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Tap 3 115135155180205225245265290300330365395430465495530560
Tap 4 155180205235260285310340365415450485520555585610640675
Speed Switch Positions
1
4
1
4
Page 19
BLOWER DATA
ADJUST"
Stc
Positions
G61MPV−60D−135 BLOWER PERFORMANCE (less filter)
Bottom Return Air, Return Air from Both Sides or Return Air from Bottom and One Side.
0 through 0.80 in. w.g. External Static Pressure Range
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm.
HEAT speed position.
G61MPV−60D−135 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
G61MPV−60D−135 BLOWER PERFORMANCE (less filter)
Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in
order to maintain proper air velocity across the filter.
0 through 0.80 in. w.g. External Static Pressure Range
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm.
G61MPV−60D−135 BLOWER MOTOR WATTS
Motor Watts @ Various External Static Pressures − in. wg.
Jumper Speed
First StageSecond Stage
00.10.20.30.40.50.60.70.800.10.20.30.40.50.60.70.8
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
G61MPV−60D−135 BLOWER PERFORMANCE (less filter)
Side Return Air with Optional RAB Return Air Base
0 through 0.80 in. w.g. External Static Pressure Range
Switch
Positions
1
ADJUST"
Switch
Positions
1
1
Factory default jumper setting.
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm.
Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm.
G61MPV−60D−135 BLOWER MOTOR WATTS
Jumper Speed
+" (Plus) SETTING (Adjust" Jumper at +" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
NORM" (Normal) SETTING (Adjust" Jumper at NORM" Setting)
HEAT"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
COOL"
Speed
Tap 1
Tap 2
Tap 3
Tap 4
−" (Minus) SETTING (Adjust" Jumper at −" Setting)
HEAT"
G61MPV unit components are shown in figure 1. The gas
valve, combustion air inducer and burners can be accessed by removing the burner access panel. Electrical
components are in the control box (figure 2) found in the
blower section.
G61MPV units are factory equipped with a bottom return air
panel in place. The panel is designed to be field removed as
required for bottom air return. Markings are provided for side
return air and may be cut out in the field.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the transformer (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit operation will shutdown. The breaker can be manually reset
by pressing the button on the face. See figure 3.
CIRCUIT BREAKER CB8
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s
electronic controls. Precautions will help to avoid
control exposure to electrostatic discharge by
putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all
tools on an unpainted unit surface, such as the
gas valve or blower deck, before performing any
service procedure.
A−Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. Transformers on all
models are rated 40VA with a 120V primary and a 24V secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in series with line voltage. When the blower door is removed the
unit will shut down.
CONTROL BOX G61MPV
PRESS TO RESET
FIGURE 3
WARNING
Shock hazard.
Disconnect power before servicing. Integrated
Control Board is not field repairable. If control is
inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
4. Integrated Control Board (A92)
SureLight Board 49M59
G61MPV units are equipped with the Lennox two−stage,
variable speed integrated SureLight® control. The system consists of a ignition / blower control (figure 4 with
control terminal designations in tables 1 through 4) and ignitor (figure 12). The control and ignitor work in combination to ensure furnace ignition and ignitor durability. The
SureLight integrated board controls all major furnace operations. The control features two LED lights, (DS1 and
DS2) for troubleshooting and four LED lights (DS3, DS6,
DS7 and DS8) to show furnace status. The control also
has two accessory terminals rated at (1) one amp each.
See table 5 for status code and table 6 for troubleshooting
diagnostic codes.
DOOR INTERLOCK
SURELIGHT®
CONTROL
BOARD
SWITCH
FIGURE 2
CIRCUIT
BREAKER
TRANSFORMER
Electronic Ignition
At the beginning of the heat cycle the SureLight control
monitors the first stage and second stage combustion air
inducer prove switch. The control will not begin the heating
cycle if the first stage or second stage prove switch is
closed (jumpered). Likewise the control will not begin the
second stage heating cycle if the second stage prove
switch is closed, and will remain in first stage heat. However, if the second stage prove switch closes during the first
stage heat pre−purge, the control will allow second stage
heat. Once the first stage prove switch is determined to be
open, the combustion air inducer is energized on low (first
stage) heat speed. When the differential in the prove switch
is great enough, the prove switch closes and a 15−second
pre−purge begins. If the switch is not proven within 2−1/2
minutes, the control goes into Watchguard−Pressure
Switch mode for a 5−minute re−set period.
Page 24
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4−second period, the control will try four more times with
an inter−purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard mode. After a
60−minute reset period, the control will begin the ignition
sequence again.
The SureLight control has an added feature that prolongs
the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on
successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
TWO−STAGE, VARIABLE SPEED INTEGRATED
CONTROL BOARD
DIAGNOSTIC
LEDs
DIP
SWITCHES
1 − 3
LEDs
DIP
SWITCHES
5 − 12
LED
The control can be utilized in two modes: SINGLE−STAGE
thermostat or TWO−STAGE thermostat. The thermostat
selection jumper E20, located just below dip switches 1
through 3 (figure 4), must be positioned for the particular
application. The jumper is factory set on TWO" for use
with a two−stage thermostat with two stage heat. Re−position jumper to SINGLE" for use with a single stage thermostat with two stage heat.
While in the single−stage thermostat mode (single jumper
setting), the burners will always fire on first−stage heat. The
combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a 10 minute recognition period, the unit will switch to second stage
heat. While in the two−stage thermostat mode (two jumper
setting) the burners will fire on first−stage heat. The combustion air inducer will operate on low speed and indoor
blower will operate on low heat speed. The unit will switch
to second−stage heat on call from the indoor thermostat. If
there is a simultaneous call for first and second stage heat,
the unit will fire an first stage heat and switch to second
stage heat after 30 seconds of operation. See Sequence of
Operation flow charts in the back of this manual for more
detail.
ON−BOARD
JUMPER W914
(cut when SignatureStat,
CCB1 or Harmony II are
used)
ON−BOARD
JUMPER W915
(cut when two−stage
cooling is used)
JUMPER W951
(cut when heat pump is
used with FM21)
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH FUNCTIONS
DIP SWITCH(ES)FUNCTION
1 and 2Blower Off Delay
3Second Stage ON Delay (Single−stage t’stat)
4Not used
5 and 6Cooling Mode Blower Speed
7 and 8Blower Speed Adjustment
YELLOWDS8−ON indicates the system is in HEAT mode.
DS3−ON indicates that the motor has a demand to operate. (This LED must be on in all
modes).
DS6−blinking indicates the airflow (CFM) demand in the motor. The air flow is determine by
counting blinks between two (2) second pauses. One blink equals approximatley 100 CFM.
DS7−ON indicaties the DS to R" jumper has not been cut. When the jumper is cut the system
will be operating with LENNOX HARMONY IIt (See Harmony Installation Instructions) or
with the CCB1 Efficiency Plus control.
CCB1: When ON, a 24 VAC is being applied and when OFF, it has been removed. This on/off
operation varies the indoor blower’s performance so dehumidification can be enhanced.
TABLE 6
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 4 for location of diagnostic LEDs.
DS1DS2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASHON
OFFSLOW FLASH
OFFFAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASHOFFFlame sensed without gas valve energized.
ONON
OFFON
FAST FLASHSLOW FLASHMain power polarity reversed. Switch line and neutral.
SLOW FLASHFAST FLASHLow flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation.
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary, backup secondary or rollout limit switch open. Limits must
close within 3 minutes or unit goes into 1 hour Watchguard.
Low prove switch open;
OR: Blocked inlet/exhaust vent;
OR: Low prove switch closed prior to activation of combustion air inducer.
High prove switch open;
OR: Blocked inlet/exhaust vent;
OR: High prove switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;
OR lost flame sense 5 times in one heating cycle;
OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts.
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on
call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Low flame sense current = 0.17−0.22 microAmps.
Page 27
Dip Switch Settings
Switches 1 and 2 −− Blower Off Delay −− The blower−on
delay of 45 seconds is not adjustable. The blower−off delay
(time that the blower operates after the heating demand
has been satisfied) can be adjusted by moving switches 1
and 2 on the integrated control board. The unit is shipped
from the factory with a blower−off delay of 90 seconds. The
blower off delay affects comfort and is adjustable to satisfy
individual applications. Adjust the blower off delay to
achieve a high fire supply air temperature between 90° and
110°F at the exact moment that the blower is de−energized.
Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures. The table below provides the blower off timings that
will result from different switch settings.
TABLE 7
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 1Switch 2
60OffOff
90OffOn
120OnOff
180OnOn
Switch 3 −− Second Stage Delay (Used with Single−
Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the ON
position, which provides a 10−minute delay before second−
stage heat is initiated. If the switch is toggled to the OFF
position, it will provide a 15−minute delay before second−
stage heat is initiated. This switch is only activated when
the E20 thermostat selector jumper is positioned for
SINGLE−stage thermostat use.
Switch 4 −− Not used in G61MPV application.
Switches 5 and 6 −− Cooling Mode Blower Speed −−
Switches 5 and 6 are used to select second stage cooling
blower motor speed (first stage cooling speed is 70% of
second stage). The unit is shipped from the factory with the
dip switches positioned for high speed (4) indoor blower
motor operation during the cooling mode. The table below
provides the cooling mode blower speeds that will result
from different switch settings. Refer to blower data tables at
the front of this manual for corresponding cfm values.
TABLE 8
Cooling Mode Blower Speeds
Speed
Switch 5Switch 6
1 − LowOnOn
2 − Medium LowOffOn
3 − Medium HighOnOff
4 − High (Factory)OffOff
Switches 7 and 8 −− Blower Speed Adjustment −−
Switches 7 and 8 are used to select blower speed adjustment settings. The unit is shipped from the factory with the
dip switches positioned for NORMAL (no) adjustment. The
dip switches may be positioned to adjust the blower speed
by +10% or −10% to better suit the application. The table
below provides blower speed adjustments that will result
from different switch settings. Refer to blower data tables at
the front of this manual for corresponding cfm values.
TABLE 9
Blower Speed Adjustment
Adjustment
Switch 7Switch 8
+10% (approx.)OnOff
NORMAL (Factory)OffOff
−10% (approx.)OffOn
Switches 9 and 10 −− Cooling Mode Blower Speed
Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramping may be used to enhance dehumidification performance. The switches are factory set at option A which has
the greatest effect on blower motor performance. The table
below provides the cooling mode blower speed ramping
options that will result from different switch settings. The
cooling mode blower speed ramping options are detailed
below.
TABLE 10
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 9Switch 10
A (Factory)OffOff
BOnOff
COffOn
DOnOn
COOLING MODE RAMPING OPTIONS
Ramping Option A (Factory Selection)
SMotor runs at 50% for 30 seconds.
SMotor then runs at 82% for approximately 7−1/2 min-
utes. If demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.
SOnce demand is met, motor runs at 50% for 30 sec-
onds then ramps down to stop.
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COOLING DEMAND
Ramping Option B
SMotor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
SOnce demand is met, motor ramps down to stop.
7 1/2 MIN
OFF
82%CFM
COOLING DEMAND
100%
CFM
100% CFM
1/2 MIN
50% CFM
OFF
OFF
Page 28
Ramping Option C
SMotor runs at 100% until demand is satisfied.
SOnce demand is met, motor runs at 100% for 60 sec-
onds then ramps down to stop.
OFF
100% CFM
DEMAND
100% CFM
60 SEC.
OFF
Ramping Option D
SMotor runs at 100% until demand is satisfied.
SOnce demand is met, motor ramps down to stop.
100% CFM
COOLING
DEMAND
OFFOFF
Switches 11 and 12 −− Heating Mode Blower Speed −−
Switches 11 and 12 are used to select second stage heat-
ing mode blower motor speed (first stage heating blower
speed is 91% of second stage). The unit is shipped from the
factory with the dip switches positioned for medium low (2)
speed indoor blower motor operation during the heating
mode. The table below provides the heating mode blower
speeds that will result from different switch settings. Refer
to blower data tables at the front of this manual for corre-
sponding cfm values.
TABLE 11
Heating Mode Blower Speeds
Speed
Switch 11Switch 12
1 − LowOnOn
2 − Medium Low
(Factory)
OffOn
3 − Medium HighOnOff
4 − HighOffOff
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and
R on the integrated control board, must be cut when the furnace is installed with the Harmony II zone control board,
the CCB1 EfficiencyPlus humidity control or the Lennox
SignatureStat.t If the jumper is left intact the PMW signal
from the Harmony II control will be blocked and also lead to
control damage. The SignatureStat and CCB1 will not operate unless the jumper is cut. Refer to table 21 for operation sequence in applications including a G61MPV, CCB1
and single−speed outdoor unit. Table 22 gives the operation sequence in applications with a two−speed outdoor
unit. See table 23 for applications for a G61MVP, SignatureStat and single−speed outdoor unit and table 24 for applications with a two−speed outdoor unit.
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O
on the integrated control board, must be cut when the furnace is installed in applications which include a heat pump
unit and the FM21 FuelMaster control board. If the jumper
is left intact, terminal "O" will remain energized eliminating
the HEAT MODE in the heat pump.
On−Board Jumper W915
On−board jumper W915, which connects terminals Y1 and
Y2 on the integrated control board, must be cut if two−stage
cooling will be used. If the jumper is not cut the outdoor unit
will operate in first−stage cooling only.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two−stage, variable speed integrated control just to the left of the first bank
of dip switches. These flashing lights correspond with diagnostic codes detailed on page 52.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate
operating status. The green ON/OFF LED is lit any time the
blower is operating. The green CFM LED indicates the
blower motor speed. Count the number of blinks between
the two−second pauses to determine the CFM. Each blink
represents approximately 100 CFM. The yellow HI/LO LED
is lit when the W914 (DS to R) jumper has not
been clipped
for SignatuteStat, CCB1 or Harmony operation. The yellow
HEAT LED is lit when the indoor blower is operating at the
HEATING speed.
Page 29
WARNING
Shock hazard.
Disconnect power before servicing. Integrated
Control Board is not field repairable. If control is
inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
5. Integrated Control Board(A92)
SureLight Board 100870
G61MPV −7 and later units are equipped with the Lennox
two−stage, variable speed integrated SureLight control
board. The system consists of a ignition / blower control
board (figures 5 and 6) with control pin designations in
tables 12, 13 and 14 and ignitor (figure 13). The board and
ignitor work in combination to ensure furnace ignition and
ignitor durability. The SureLight integrated board controls
all major furnace operations. The board features a red LED
light, for furnace status and troubleshooting. The LED
flashes in X" + Y" codes. For example using table 15 under PRESSURE SWITCH CODES", if the red LED
flashes 2 times, then off for 2 seconds then flashes 3
times, the low pressure switch is failed open. Two green
LEDs show indoor blower status and CFM. See Page 35
for more detail. The board also has two 120 volt accessory terminals rated at (1) one amp each. In addition there is
a 24 volt accessory terminal located on TB1.
Electronic Ignition
At the beginning of the heat cycle the SureLight control
monitors the first stage and second stage combustion air
inducer prove switch. The control will not begin the heating
cycle if the first stage prove switch is closed (by−passed).
Likewise the control will not begin the second stage heating
cycle if the second stage prove switch is closed, and will remain in first stage heat. However, if the second stage prove
switch closes during the first stage heat pre−purge, the control will allow second stage heat. Once the first stage prove
switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the
differential in the prove switch is great enough, the prove
switch closes and a 15−second pre−purge begins. If the
switch is not proven within 2−1/2 minutes, the control goes
into Watchguard−Pressure Switch mode for a 5−minute re−
set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4−second period, the control will try four more times with
an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure
mode. After a 60−minute reset period, the control will begin
the ignition sequence again.
NOTE − Board 100870 provides a regulated 95 volts
the ignitor.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE
thermostat or TWO−STAGE thermostat. The thermostat
selection is made using a dip switch (figure 4) and must be
positioned for the particular application. The dip switch is
factory set on TWO" for use with a two−stage thermostat
with two stage heat. Re−position dip switch to SINGLE" for
use with a single stage thermostat with two stage heat.
While in the single−stage thermostat mode (single dip
switch setting), the burners will always fire on first−stage
heat. The combustion air inducer will operate on low speed
and indoor blower will operate on low heat speed. After a
factory default 10 minute recognition period, the unit will
switch to second stage heat. While in the two−stage thermostat mode (two dip switch setting) the burners will fire on
first−stage heat. The combustion air inducer will operate on
low speed and indoor blower will operate on low heat
speed. The unit will switch to second−stage heat on call
from the indoor thermostat. If there is a simultaneous call
for first and second stage heat, the unit will fire an first stage
heat and switch to second stage heat after 30 seconds of
operation. See Sequence of Operation flow charts in the
back of this manual for more detail.
Page 30
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.