Lennox G61MPV-36C-090, G61MPV-36B-070, G61MPV-36B-071, G61MPV-60C-091, G61MPV-60C-110 Installation Instructions Manual

...
Page 1
Page 1
01/11
*2P0111*
506506−01
*P506506-01*
E 2011 Lennox Industries Inc.
Dallas, Texas, USA
HOMEOWNER FOR FUTURE REFERENCE
INSTALLATION INSTRUCTIONS
G61MPV SERIES UNITS
GAS UNITS
506506−01 01/2011
Supersedes 07/2010
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G61MPV Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as Construction Heater 5. . . . . . . . . . .
General 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 6. . . . . . . . . . . . .
Installation − Setting Equipment 9. . . . . . . . . . . . . . . . . .
Filters 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe & Fittings Specifications 16. . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 19. . . . . . . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 20. . . . . . . . . . . . . . . . . . . . .
Venting Practices 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board 45. . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 56. . . . . . . . . . . . . . . . . . . . . .
High Altitude Information 57. . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 59. . . . . . . . . . . . . . . . . . . . . . . .
Service 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ignition Control Board Diagnostic Codes 63. . . . . . . . .
Troubleshooting 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Pipe Sizing Worksheet 70. . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 71. . . . . . . . . . . . . .
WHAT TO DO IF YOU SMELL GAS:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
WARNING
D Leave the building immediately.
Litho U.S.A.
Page 2
Page 2
G61MPV Unit Dimensions − inches (mm)
*Bottom Return
Air Opening
*Bottom Return
Air Opening
ELECTRICAL INLET
(Either Side)
SUPPLY AIR
OPENING
AIR FLOW
FRONT VIEW SIDE VIEW
TOP VIEW
A
B 9/16 (14)
C
3/4 (19)
3/4 (19)
28−1/2
(724)
19−7/16
(494)
23−1/2
(597) 4−1/4 (108)
11−5/8 (295)
Right
9−3/4 (248)
Left
4−7/8 (124) Right
2−1/4 (57) Left
40
(1016)
4
(102)
1−15/16 (49)
23
(584)
14**
(356)
9/16
(14)
16
(406)
14−3/4
(375)
5/8 (16)
23-3/4 (603)
25 (635)
GAS PIPING INLET
(Either Side)
EXHAUST AIR OUTLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
2−1/2
(64)
18-3/4 (476)
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
*OPTIONAL
RETURN CUTOUT
(Either Side)
1
Optional External Side Return Air Filter Kit is not for use
with the optional RAB Return Air Base.
*60C and 60D size units installed in upflow applications that require air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. Required to maintain proper air velocity.
2. Single side return air with optional RAB Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
one side return air.
Refer to Engineering Handbook for additional information.
**Consider sizing requirements for optional IAQ equip­ment before cutting side return opening.
COMBUSTION AIR INTAKE
(Either Side)
6−1/2 (165)
4−1/8 (103)
6−1/2 (165)
6−3/4 (171)
5−1/2 (140)
3−1/8
(79)
Model No.
A B C
in. mm in. mm in. mm
G61MPV−36B−045 G61MPV−36B−070 G61MPV−36B−071
17−1/2 446 16−3/8 416 16 406
G61MPV−36C−090 G61MPV−60C−090 G61MPV−60C−091 G61MPV−60C−110 G61MPV−60C−111
21 533 19−7/8 505 19−1/2 495
G61MPV−60D−135 24−1/2 622 23−3/8 546 23 584
Page 3
Page 3
G61MPV Parts Arrangement
FIGURE 1
TOP CAP
CABINET
BURNER BOX
ASSEMBLY
SIGHT
GLASS
DuralokPlus
TM
HEAT EXCHANGER
ASSEMBLY
CONDENSER COIL
DOOR
INTERLOCK
SWITCH
COLD HEADER
(COLLECTOR)
BOX
COMBUSTION AIR
INDUCER
BLOWER
ACCESS
PANEL
BURNER ACCESS
PANEL
FLUE
COLLAR
COMBUSTION
AIR PRESSURE
PROVE SWITCHES*
PRIMARY LIMIT
WARM HEADER
(COLLECTOR)
BOX
GAS VALVE
AND MANIFOLD
SECONDARY
LIMITS (2)
POWER CHOKE
(5 Ton Only)
BLOWER MOTOR
TRANSFORMER
*G61MPV−36B−045
units are equipped
with two switches.
Two−Stage, Variable Speed
Integrated Control
CIRCUIT
BREAKER
Page 4
Page 4
G61MPV Gas Furnace
The G61MPV category IV gas furnace is equipped with a two−stage, variable speed integrated control. This control ensures compatibility with Lennox’ Harmony III zone con­trol system, as well as a thermostat which provides humid­ity control. Each G61MPV is shipped ready for installation in the upflow, downflow, horizontal left air discharge or horizontal right air discharge position. The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in upflow ap­plications with bottom return air. The bottom panel must also be removed and discarded in all downflow or horizon­tal applications.
The furnace is equipped for installation in natural gas ap­plications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
The G61MPV can be installed as either a Direct Vent or a Non−Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination.
FIGURE 2
DIRECT VENT INSTALLATION NON−DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
CONDENSATE
DRAIN
EXHAUST OUTLET
G61MPV
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
G61MPV
CONDENSATE
DRAIN
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G61MPV unit 1 − Bag assembly containing the following:
3 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 2 − 2" diameter vent / intake plugs
1 − 3" diameter cabinet plug (intake) 1 − 2" diameter debris screen 1 − Logo sticker (for use in downflow applications)
NOTE − G61MPV−60C−110 and G61MPV−60C−111 units also include a 2" diameter PVC street elbow, which is shipped on the blower deck in the heating compartment. G61MPV−60D−135 units are shipped with a 3" to 2" PVC reducing elbow.
Canadian Installations Only − Replace the provided 2" street elbow shipped with the G61MPV−60C−110 and G61MPV−60C−111 units with 2" street elbow Y0162. Re­place the provided 3" X 2" reducing elbow shipped with the G61MPV−60D−135 units with 3" X 2" reducing elbow 40W22. Y0162 and 40W22 meet B149 vent requirements.
The following items may also be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Safety Information
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
G61MPV units are CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
In the USA, installation of gas furnaces must conform with lo­cal building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
Page 5
Page 5
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
In order to ensure proper unit operation in non−direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figures 8, 13 and 17. Acces­sibility and service clearances must take precedence over fire protection clearances.
NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code or CSA B149 standard.
NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation.
This G61MPV furnace may be used as a high−static unit heater. The G61MPV may also be installed in an aircraft hangar in accordance with the Standard for Aircraft Han­gars (ANSI/NFPA No. 408−1990).
Installation in parking structures must be in accordance with the Standard for Parking Structures (ANSI/NFPA No. 88A−1991). Installation in repair garages must be in accor­dance with the Standard for Repair Garages (ANSI/NFPA No. 88B−1991).
This G61MPV furnace must be installed so that its electri­cal components are protected from water.
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air
from entering the furnace. If the damper is manually oper­ated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit­tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The G61MPV furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms.
This furnace design has not been CSA certified for installa­tion in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of G61MPV units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
G61MPV units may be used for heating of buildings or structures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
Page 6
Page 6
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a G61MPV furnace:
Place the furnace as close to the center of the air dis­tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
When the furnace is installed in non−direct vent applica­tions, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
When the furnace is installed in non−direct vent applica­tions, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insu­lated space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
CAUTION
G61MPV unit should not be installed in areas normal­ly subject to freezing temperatures.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
If the G61MPV is installed as a Non−Direct Vent Fur­nace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De−icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, ap­pliance vents, chimneys, and fireplaces force additional
Page 7
Page 7
air that could be used for combustion out of the house. Unless outside air is brought into the house for combus­tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a po­tentially dangerous situation.
In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install G61MPV furnaces to ensure effi­cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI− Z223.1/NFPA 54). This reprinted material is not the com­plete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Canada, refer to the standard CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliance will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex­haust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm
2
) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm
2
). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 3.
FIGURE 3
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
OPENINGS
(To Adjacent
Unconfined
Space)
NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm
2
per .29kW) per hour of the total input
rating of all equipment in the enclosure, but not less than 100 square inches (64516mm.
2).
G61MPV
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED EX-
HAUST PIPE (ALTER-
NATE LOCATION)
Page 8
Page 8
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a mini­mum free area of 1 square inch per 4,000 Btu (645mm
2
per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a mini­mum free area of 1 square inch per 2,000 Btu (645mm
2
per .59kW) per total input rating of all equipment in the en­closure (See figure 4).
FIGURE 4
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
OUTLET
AIR
INLET
AIR
VENTILATION
LOUVERS
(For unheated
crawl space)
G61MPV
ROOF TERMINATED
EXHAUST PIPE
VENTILATION LOUVERS
(Each end of attic)
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indi­rectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See figures 4 and 5. When communicat­ing with the outdoors through horizontal ducts, each open­ing shall have a minimum free area of 1 square inch (645 mm
2
) per 2,000 Btu (.56 kW) per total input rating of all
equipment in the enclosure. See figure 6.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
FIGURE 5
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per hour
of the total input rating of all equipment in the enclosure.
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12" above
bottom)
G61MPV
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FIGURE 6
G61MPV
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
OUTLET AIR
INLET AIR
NOTE−Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm
2
per .59kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
Page 9
Page 9
Installation − Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from front to back and side
to side.
The unit may be tilted slightly (maximum 1/2 in.) from back to front to aid in the draining of the heat exchanger. See figure 7.
NOTE − G61MPV−36B and −36C units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and
washer must be removed before the furnace is placed into operation. After the bolt and washer have been re-
moved, the rigid leg will not touch the blower housing.
NOTE − G61MPV−60D−135 units are equipped with a ship­ping pad under the blower housing. Remove the shipping pad prior to operation.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figures 8, 13 and 17.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
FIGURE 7
SETTING EQUIPMENT
UPFLOW APPLICATION DOWNFLOW APPLICATION
HORIZONTAL APPLICATION
FRONT VIEW
SIDE VIEW
FRONT VIEW
END VIEW
FRONT VIEW
SIDE VIEW
AIR FLOW
AIR FLOW
AIR FLOW
UNIT
FRONT
AIR FLOW
AIR FLOW
UNIT
FRONT
UNIT
FRONT
1/2"
max.
1/2"
max.
1/2"
max.
UNIT MUST BE LEVEL SIDE−TO−SIDE IN ALL APPLICATIONS.
UNIT SHOULD BE LEVEL FROM LEFT TO RIGHT BUT MAY BE
TILTED SLIGHTLY (MAX. 1/2") FROM BACK TO FRONT TO AID IN THE DRAINING OF THE HEAT EXCHANGER.
Page 10
Page 10
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
Upflow Applications
The G61MPV gas furnace can be installed as shipped in the upflow position. Refer to figure 8 for clearances.
Installation Clearances
Top
Bottom (Floor)
Left Side
Right Side
Top/Plenum 1 in. (25 mm)
*Front 0
Back 0
Sides 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. Allow proper clearances to accommodate condensate trap and vent pipe installation. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 8
Return Air −− Upflow Units
Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 1800 cfm (850 L/s) are required with 60C or 60D models in an upflow applica­tion, the following return air options are available:
1 − Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. (Required to maintain proper air velocity.) See figure 9.
2 − Return air from single side with optional RAB Return
Air Base. See figure 11.
3 − Return air from bottom.
4 − Return air from both sides.
5 − Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
G61MPV applications which include side return air and a condensate trap installed on the same side of the cabinet require either a return air base or field−fabri­cated transition to accommodate an optional IAQ ac­cessory taller than 14.5".
Side Return Air
(with transition and filter)
FIGURE 9
Return Air
Plenum
Transition
20" X 25" X 1"
(508mm X635mm X 25mm)
Air Filter
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 10.
Page 11
Page 11
Removing the Bottom Panel
FIGURE 10
Screw
Bottom Panel
Bottom Cap
Optional Return Air Base
(Upflow Applications Only −− For use with B, C and D cabinets only)
FIGURE 11
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Unit side return air
Opening
FRONT VIEW
SIDE VIEW
27−5/8 (702)
4
(102)
1
23 (584)
Overall
(Maximum)
OPTIONAL RAB
RETURN AIR BASE
23 (584)
7−1/4 (184)
7/8
(22)
3/4
(19)
1
22−7−16
(570)
Overall
(Maximum)
SIDE RETURN
AIR OPENINGS
(Either Side)
FURNACE
FRONT
14
(356)
AIR FLOW
5−5/8 (143)
1
Minimum 11 (279)
2
Maximum
14 (356)
21 (533) RAB−C (98M58)
24−1/2 (622) RAB−D (98M59)
17−1/2 (446) RAB−B (98M60)
Page 12
Page 12
Setting an Upflow Unit
When the side return air inlets are used in an upflow ap­plication, it may be necessary to install leveling bolts on the bottom of the furnace. Use field−supplied corrosion−resist­ant 5/16 inch machine bolts (4) and nuts (8). See figure 12.
NOTE − The maximum length of the bolt is 1−1/2 inches.
1 − Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace’s bottom. See fig­ure 12 for the correct location of the holes. Drill through the bottom panel and the bottom flange of the cabinet.
2 − Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole. A flat washer may be added between the nut and the bot­tom of the unit.
3 − Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the nut and the bottom of the unit.
4 − Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement.
NOTE − The unit may be tilted back−to−front a maximum of 1". This will ensure proper draining of the heat exchanger.
FIGURE 12
1−3/4
(44)
1−3/4
(44)
3/8
(10)
1−3/4 (44)
3/8
(10)
3/8
(10)
3/8
(10)
1−3/4
(44)
Leveling Bolt Installation
Leveling Bolt
Locations
Leveling Bolt
Locations
Inches (mm)
Furnace Front
Furnace
Bottom
Downflow Applications
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling cabi­net. Do not drag the unit across the floor in the down-
flow position. Flange damage will result.
After unit has been properly set in place, position provided logo over existing logo and affix sticker on front panel.
Refer to figure 13 for clearances in downflow applica­tions.
Downflow Application Installation Clearances
Top
Bottom
Left Side
Right Side
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional additive base is installed between the furnace and the com­bustible floor.
FIGURE 13
Installation on Non−Combustible Flooring
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Model No.
Front to Rear Side to Side
in. mm in. mm
B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422
C Cabinet (21") 19 − 3/4 502 20−1/8 511
D Cabinet (24.5") 19 − 3/4 502 23 − 5/8 600
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Page 13
Page 13
Installation on Combustible Flooring
1 − When unit is installed on a combustible floor, an addi-
tive base must be installed between the furnace and the floor. The base must be ordered separately. See table 2 for opening size to cut in floor.
CAUTION
The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma­terial other than wood flooring.
TABLE 2
ADDITIVE BASE FLOOR OPENING SIZE
Cabinet
Width
Catalog Number
Front to Rear Side to Side
in. mm in. mm
B Cabinet
(17.5")
11M60
22 559 18 − 3/4 476
C Cabinet
(21")
11M61
22 559 22 − 3/4 578
D Cabinet
(24.5")
11M62
22 559 25 − 3/4 654
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 − Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
G61MPV UNIT
SUPPLY AIR PLENUM
ADDITIVE BASE
PROPERLY
SIZED FLOOR
OPENING
FIGURE 14
Installation on Cooling Coil Cabinet
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position.The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 15 or 16).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
FIGURE 15
SECURE FROM
OUTSIDE CABINET
PLENUM
(Field Provided)
SEALING STRIP (Field Provided)
Side View
CABINET
SIDE PANEL
SECURE FROM
INSIDE CABINET
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
Side View
CABINET
SIDE PANEL
FIGURE 16
Horizontal Applications
The G61MPV furnace can be installed in horizontal ap­plications with either right− or left−hand air discharge.
The G61MPV may also be installed as a unit heater. Either suspend the furnace as shown in figure 18, or install the furnace on a field−fabricated raised platform. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
Refer to figure 17 for clearances in horizontal applications.
Page 14
Page 14
Horizontal Application
Installation Clearances
Top
Left End Right End
Right−Hand Discharge
Left−Hand Discharge
Top
Bottom (Floor)**
Bottom (Floor)**
Left End Right End
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. **A 5−1/2 service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 17
Suspended Installation of Horizontal Unit
NOTE − If unit is suspended in attic or crawl space, horizon­tal support kit (Cat No. 56J18 ordered separately) must be used to ensure proper unit support and coil drainage.
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
2 − Provide service platform in front of unit.
3 − If unit is installed above finished space, fabricate a
drain pan fitted with a 1/2 inch or 3/4 inch N.P.T. fitting.
4 − Using 3/8 inch rods and support frame kit or field−fabri-
cated supports, fabricate suspension hangers, keep­ing in mind front service access clearances.
5 − Mount unit on support frame as shown in figure 18.
6 − Continue with exhaust, condensate and intake line
piping instructions.
7 − If unit is suspended above finished space, hang the
field−provided drain pan below the support frame as shown in figure 18. Leave 5−1/2 inches for service clearance below unit for condensate trap.
8 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner. If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
FIGURE 18
BLOWER ACCESS PANEL
3/8 in. RODS
SUPPORT FRAME
INTAKE/EXHAUST
CONNECTION
TYPICAL HORIZONTAL CEILING APPLICATION
DRAIN PAN
(to protect finished space)
Platform Installation of Horizontal Unit
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
2 − Construct a raised wooden frame and cover frame
with a plywood sheet. Provide a service platform in front of unit. If unit is installed above finished space, fabricate a drain pan to be installed under unit. When installing the unit in a crawl space, a proper sup­port platform may be created using cement blocks and the horizontal support frame kit (ordered separately, Lennox part number 56J18). Position the support frame on top of the blocks and install the unit on the frame. Leave 5−1/2 inches for service clearance for condensate trap.
3 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner. If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
Page 15
Page 15
4 − Set unit in drain pan as shown in figure 19. Leave 5−1/2
inches for service clearance below unit for condensate trap.
5 − Continue with exhaust, condensate and intake piping
installation according to instructions.
INTAKE PIPE
*GAS
CONNECTOR
SERVICE PLATFORM
RAISED
PLATFORM
CONDENSATE LINE
*Gas connector may be used for Canadian installation if accept­able by local authority having jurisdiction.
EXHAUST PIPE
FIGURE 19
G61MPV Installed in Unit Heater Applications
The G61MPV may also be installed as a unit heater. Either suspend the furnace from roof rafters or floor joists, as shown in figure 18, or install the furnace on a field−fabri­cated raised platform, as shown in figure 19. The unit must be supported at both ends and beneath the blower deck to prevent sagging. The condensate trap must be installed where it can be serviced at a later date.
Unit Heater Discharge Duct Guidelines
A field−fabricated and installed discharge air duct and grille cabinet is suitable for use with the G61MPV heater. Keep the following items in mind when constructing the cabinet.
1 − Outer dimensions of cabinet should match those of the
unit heater, so the duct/grille cabinet installs flush with the unit heater cabinet. See figure 20.
2 − Flange both ends of duct/grille cabinet so that screws
can be used to secure cabinet to discharge end of unit heater.
3 − To ensure proper operation, the duct/grille cabinet
must be at least 18 inches long.
4 − Use #10−16 x 1/2 inch sheet metal screws to secure
duct/grille cabinet to unit, taking care not to damage in­ternal components of unit heater when drilling holes or installing screws. See figure 20.
5 − Use adjustable, double−deflection grille(s) to distribute
discharge air. Adjust static pressure to be in the 0.06 inch to 0.10 inch w.c. range.
FIGURE 20
18 in.
MIN.
NOTE − When installing duct/grille cabinet, take care not to damage internal unit
heater components when drilling holes or installing screws.
DRAIN PAN
(to protect
finished
space)
Return Air −− Horizontal Applications
Return air may be brought in only through the end of a fur­nace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 10.
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended filter sizes.
A filter must be in place whenever the unit is operating.
NOTE − In upflow applications where side return air fil­ter is installed on same side as the condensate trap, fil­ter rack must be installed beyond condensate trap to avoid interference.
TABLE 3
Furnace
Cabinet Width
Filter Size
Side Return Bottom Return
17−1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24−1/2" 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Page 16
Page 16
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Operation of this furnace in heating mode (indoor blower operating at selected heating speed) with an exter­nal static pressure which exceeds 0.8 inches w.c. may re­sult in erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (by reflected light) of the heat exchanger for leaks after the furnace is installed. If present, this access panel must al­ways be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled ap­pliance (i.e., water heater), or carbon monoxide− producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pres­sure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan­dards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that ad-
versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica­tion, or separation that cannot be removed by stirring. Re­fer to the table 4 below for approved piping and fitting materials.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
TABLE 4
PIPING AND FITTINGS SPECIFICATIONS
PIPE & FITTING MATERIAL
ASTM
SPECIFICATION
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
D2661
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
D2665
PRIMER & SOLVENT CEMENT
ASTM
SPECIFICATION
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
D2564, D2235, F493
ABS to PVC or CPVC Transition Solvent Cement
D3138
CANADA PIPE & FITTING & SOLVENT
CEMENT
MARKING
PVC & CPVC Pipe and Fittings
ULCS636
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
Page 17
Page 17
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alter­nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi­als. Use transition solvent cement when bonding ABS to ei­ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers. Uni­formly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fit­ting and male end of pipe to depth of fitting socket.
Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap­pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex­haust) system. When bonding the vent system to the fur­nace, use ULC S636 approved One−Step Transition Ce­ment to bond the pipe to the flue collar, or to bond the 90° elbow or reducing 90° elbow to the flue collar. In addi­tion, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 5 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when siz­ing vent pipe. All Lennox vent terminations are PVC.
Page 18
Page 18
TABLE 5
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
UNIT
MODEL
VENT
PIPE DIA.
(in.)
Vent Pipe Length Equivalency (feet)
Outdoor Exhaust
Accelera-
tor
(Dia. X
Length)
Outdoor Exhaust Acceler-
ator
(Dia. X
Length)
1−1/2"
Concentric
Kit
2"
Concentric
Kit
3"
Concen-
tric Kit
2" Wall
Plate Kit
3" Wall
Plate Kit
2" Wall
Ring
Kit
Flush Mount
Termination
1−1/2" X
12"
2" X 12"
71M80
or
44W92
69M29
or
44W92
60L46
or
44W93
22G44
or
30G28
44J40
or
81J20
15F74
51W11
with
1−1/2
accelera-
tor
51W11 without
1−1/2" ac-
celerator
36B−045
2 4
Not
Allowed
12
Not
Allowed
Not
Allowed
4 4* 4 4
Not
Allowed
2−1/2 5
Not
Allowed
15
Not
Allowed
Not
Allowed
5 5* 5 7****
Not
Allowed
3 7
Not
Allowed
21
Not
Allowed
Not
Allowed
7 7* 7 7
Not
Allowed
4 14
Not
Allowed
42
Not
Allowed
Not
Allowed
14 14* 14
Not
Allowed
Not
Allowed
36B−070 36B−071
2 4
Not
Allowed
12
Not
Allowed
Not
Allowed
4 4* 4 4
Not
Allowed
2−1/2 5
Not
Allowed
15
Not
Allowed
Not
Allowed
5 5* 5 7****
Not
Allowed
3 8
Not
Allowed
24
Not
Allowed
Not
Allowed
8 8* 8 8
Not
Allowed
4 14
Not
Allowed
42
Not
Allowed
Not
Allowed
14 14* 14
Not
Allowed
Not
Allowed
36B−091
60C−090
2
Not
Allowed
1
Not
Allowed
3 3
Not
Allowed
1 1** 4
Not
Allowed
2−1/2
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2** 7****
Not
Allowed
3
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2** 8
Not
Allowed
4
Not
Allowed
4
Not
Allowed
12 12
Not
Allowed
4 4**
Not
Allowed
Not
Allowed
60C−110 60C−111
2
Not
Allowed
1
Not
Allowed
3 3
Not
Allowed
1 1**
Not
Allowed
1
2−1/2
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2***
Not
Allowed
4****
3
Not
Allowed
2
Not
Allowed
6 6
Not
Allowed
2 2***
Not
Allowed
7
4
Not
Allowed
4
Not
Allowed
12 12
Not
Allowed
4 4***
Not
Allowed
Not
Allowed
60D−135
3
Not
Allowed
6
Not
Allowed
Not
Allowed
15
Not
Allowed
6 6***
Not
Allowed
7
4
Not
Allowed
10
Not
Allowed
Not
Allowed
25
Not
Allowed
10 10***
Not
Allowed
Not
Allowed
*Requires field−provided and installed 1−1/2" exhaust accelerator. **Requires field−provided and installed 2" exhaust accelerator. ***For use only in non−direct vent applications, when snow riser is not required. Re­quires field−provided and installed 2" exhaust accelerator. **** Requires field−provided and installed 2"−2−1/2" coupling on G61MPV−36B−045, G61MPV−36B−070, 071, G61MPV−36B−090,091 and G61MPV−60C−110 furnaces
 Termination kits 44W92, 44W93, 30G28 & 81J20 are ULC−636 approved for Cana­dian Installation.
 The 44W92 Concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the G61MPV−36B−045, G61MPV−36B−070 & 071 furnaces.
Page 19
Page 19
Vent Piping Guidelines
The G61MPV can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −− Size pipe according to tables 6 and 7. Table 6 lists the mini­mum equivalent vent pipe lengths permitted. Table 7 lists the maximum equivalent pipe lengths permitted.
Maximum vent length is defined as:
Total length (linear feet) of pipe,
Plus Equivalent length (feet) of fittings, Plus Equivalent length (feet) of termination. NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8.
NOTE − The exhaust pipe should be offset a minimum of 12 inches to avoid the possibility of water droplets being re­leased from the exhaust termination. The minimum ex­haust vent length is 15 ft. Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 12−inch vertical offset. See fig­ure 21.
Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 5 feet (1.52m) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to 2.5 feet (.76m) of vent pipe of the same diameter.
NOTE − On G61MPV−071, −091 and −111 units, sweep el­bows must be used for all 90° elbows in the venting system when 2", 2−1/2" or 3" vent pipe is used. On G61MPV−135, sweep elbows must be used for all 90° el­bows in the venting system when 3" vent pipe is used. Sweep elbows are recommended for use in vent sys­tems of other G61MPV units.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assis­tance in sizing vent pipe in these applications.
FIGURE 21
Exhaust Pipe Offset
*12" Min.
*12" Min.
*12" Min.
12" Min.
Upflow and Downflow Application
Rooftop Termination
Upflow and Downflow Application
Side Wall Termination
Horizontal Application
Rooftop Termination
Horizontal Application
Side Wall Termination
*A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage
Page 20
Page 20
NOTE − The flue collar on all models is sized to accommo­date 2" Schedule 40 flue pipe. When vent pipe which is larger than 2" must be used in an upflow application, a 2" elbow must be applied at the flue collar in order to proper­ly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine ac­ceptable vent lengths. Assign an equivalent feet value to this elbow according to the larger size pipe being used. Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.
Use the following steps to correctly size vent pipe diameter.
Refer to Vent Pipe Size Determination Worksheet on page 65.
1 − Determine the vent termination and its corresponding
equivalent feet value according to table 5.
2 − Determine the number of 90° elbows required for both
indoor and outdoor (e.g. snow riser) use. Calculate the corresponding equivalent feet of vent pipe.
3 − Determine the number of 45° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent feet of vent pipe.
4 − Determine the length of straight pipe required.
5 − Add the total equivalent feet calculated in steps 1
through 4 and compare that length to the maximum values given in table 7 for the proposed vent pipe di­ameter. If the total equivalent length required exceeds the maximum equivalent length listed in the appropri­ate table, evaluate the next larger size pipe.
IMPORTANT
Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze−ups and may block the terminations.
TABLE 6
MINIMUM VENT PIPE LENGTHS
G61MPV
MODEL
MIN. EQUIV.
VENT LENGTH
EXAMPLE
045, 070, 071, 090,
091
15 ft.*
5 ft. plus 2 elbows of 2", 2−1/2", 3"
or 4" diameter pipe
110
5 ft. plus 2 elbows of 2−1/2" 3" or 4"
diameter pipe
135***
5 ft. plus 2 elbows of 3" or 4"
diameter pipe
*Any approved termination may be added to the minimum equivalent length listed.
**G61MPV−60C−110 and −111 must have 90° street ell (supplied or field re­placement Canadian kit) installed directly into unit flue collar.
***G61MPV−60D−135 must have 3" to 2" reducing ell (supplied or field replace­ment Canadian kit) installed directly into unit flue collar.
TABLE 7
MAXIMUM VENT PIPE LENGTHS
ALTITUDE
G61MPV
MODEL
MAXIMUM EQUIVALENT VENT
LENGTH FEET
2"
PIPE
2−1/2"
PIPE
3"
PIPE4"PIPE
0 − 4500
(0 − 1371 m)
045 59 65 77 234 070 59 65 78 214
071† 59 65 78 214
090 26 42 72 204
091† 26 42 72 204
110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 61 160
4501−7500
(1372−2286 m)
045 59 65 77 234 070 59 65 78 214
071† 59 65 78 214
090 26 42 72 204
091† 26 42 72 204
110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 46 160
7501 − 10000
(2287 − 3048 m)
045 59 65 77 234 070 59 65 78 214
071† 59 65 78 214
090 26 42 72 204
091† 26 42 72 204
110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 46 160
n/a −− Not allowed. *G61MPV−60C−110 and −111 must have 90° street ell (supplied or field replace-
ment Canadian kit) installed directly into unit flue collar. **G61MPV−60D−135 must have 3" to 2" reducing ell (supplied or field replace-
ment Canadian kit) installed directly into unit flue collar.
†On G61MPV−071, −091 and −111 units, sweep elbows must be used for all 90° elbows in the venting system when 2", 2−1/2" or 3" vent pipe is used. Sweep elbows are recommended for use in vent sys­tems of other G61MPV units.
‡On G61MPV−60D−135 units, sweep elbows must be used for all 90° el­bows in the vent system when 3" vent pipe is used.
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
WARNING
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
Page 21
Page 21
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
NOTE − Furnace flue collar and air inlet fitting are both made of ABS material. Usetransition solvent cement when bonding ABS to either PVC or CPVC, refer to the procedure specified in ASTM D3138..
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur­ing assembly (but not after pipe is fully inserted) to dis­tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Venting Practices
The thickness of construction through which vent pipes may be installed is 24" (610mm) maximum and 3/4" (19mm) minimum. If a G61MPV furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
1 − Use recommended piping materials for exhaust pip-
ing.
2 − Secure all joints so that they are gas-tight using ap-
proved cement. Suspend piping using hangers at a minimum of every 5
feet (1.52m) for schedule 40 PVC and every 3 feet (.91m) for ABS−DWV, PVC− DWV, SPR−21 PVC, and SDR−26 PVC piping. A suit­able hanger can be fabri­cated by using metal or plastic strapping or a large wire tie.
3 − In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
4 − Isolate piping at the point where it exits the outside wall
or roof in order to prevent transmission of vibration to the structure.
5 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
Exhaust Piping (Figures 23 and 24)
NOTE − A 2" diameter PVC street ell is located on the blower deck of 60C−110 and 60C−111 units. In upflow or downflow applications the street ell must be
glued us­ing transition solvent cement directly into the unit flue col­lar. See figure 23. A 3" to 2" PVC reducing ell is located on the blower deck of the 60D−135 units. In upflow or downflow applications, the reducing ell must be
glued using transition solvent cement directly into the unit flue collar.
1 − Choose the appropriate side for venting in upflow or
downflow positions. Exhaust piping exits from the top of the unit in horizontal air discharge applications. Glue the field−provided exhaust vent pipe (or provided street ell or reducing ell in upflow or downflow applica­tions) to the flue collar. All PVC cement joints should be made according to the specifications outlined in ASTM D 2855. Refer to pipe and fittings specifications and gluing procedures.
IMPORTANT
Exhaust piping and condensate trap must be installed on the same side of the unit in upflow and dowflow applications or use alternate drain kit 76M20.
2 − All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage. Horizontal runs of exhaust piping must be supported ev­ery 5 feet (1.52m) using hangers.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
3 − On the opposite side of the cabinet, glue the provided
2" ABS vent plug into the unused ABS flue collar with ABS or all purpose solvent cement.
4 − Route piping to outside of structure. Continue with
installation following instructions given in piping ter­mination section.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
FIGURE 22
STRAPPING
(metal, plastic
or large wire
ties)
Page 22
Page 22
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
IN UPFLOW OR DOWNFLOW DIRECT OR NON−DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
FIGURE 23
VENT PLUG
(Must be
glued in
place)
PLUG
PLUG
CONDENSATE
TRAP
(Must be installed
on same side as
exhaust piping)
PLUG
G61MPV−110, −111,
−135 with
3" OR 4" vent pipe
2"
G61MPV−070,
−071, −090, −091
with 2−1/2", 3", or
4" vent pipe
TRANSITION
(use only if 4"
pipe is
required)
4"
2"
2" max
length
2−1/2", 3", OR
4"
TRANSITION
2"
2"
G61MPV−110,
−111 with
2−1/2", 3", OR 4"
vent pipe
*2"
TRANSITION
2−1/2",
3", OR
4"
2"
2"
or
45°
MAX
45°
MAX
SIDE VIEW
*2" diameter street elbow provided.
** Street elbow may be used on −045, −070, 071, −090, −091.
3" to 2" REDUCING ELBOW
(provided)
**
2" max
length
FIGURE 24
TYPICAL EXHAUST PIPE CONNECTIONS
HORIZONTAL DIRECT OR
NONDIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
2"
2"
2"
*2"
2−1/2", 3", OR
4"
DO NOT transition from smaller to larger pipe size in horizontal runs of exhaust pipe.
TRANSITION
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
−60C−110*
−60C−111*
−60D−135*
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
*Limit pipe length to 2" in −110, −111,
−135 applications.
Intake Piping
The G61MPV furnace may be installed in either direct vent or non−direct vent applications. In non−direct vent applica- tions, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be consid­ered and guidelines listed in Combustion, Dilution and Ven­tilation Air section must be followed.
The G61MPV unit is designed for either left−side or right− side air intake connections in either upflow or downflow ap­plications. In horizontal applications, air intake must be brought in through the top. Intake air piping is independent of exhaust piping.
Follow the next four steps when installing the unit in direct vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct vent applications.
1 − Use transition solvent cement to connect PVC pipe to
the ABS slip connector located on the side of the burn­er box.
2 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired. A pilot indentation is pro­vided in the slip connector to assist in locating and starting the fastener.
3 − Glue the provided 2" ABS plug into the unused ABS air
intake connector on the opposite side of the cabinet with ABS all pupose cement.
4 − Route piping to outside of structure. Continue with
installation following instructions given in general guide lines for piping terminations and in intake and exhaust piping terminations for direct vent sections. Refer to figure 25 for pipe sizes.
Page 23
Page 23
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
FIGURE 25
PLUG
(Must be
glued in
place)
*Limit pipe length to 4" in
−110, −111, −135 applications.
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
−60C−110*
−60C−111*
−36B−045
−36B−070
−36C−071
−36C−090
−60C−090
−60C−091
−60C−110*
−60C−111*
−60D−135*
*2"
TRANSITION
2−1/2",
3" OR
4
2
2
2
2−1/2",
3" OR
4
TRANSITION
2
2
2
FIGURE 26
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL DIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
*Limit pipe length to 4" in
−110, −111, −135 applications.
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
−60C−110
−60C−111
−60D−135*
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
−60C−110
−60C−111
−36B−045
−36B−070
−36B−071
−36C−090
−60C−090
−60C−091
2”
2”
2”
TRANSITION
2”
21/2”,
3” OR 4”
2”
*2”
TRANSITION
21/2”,
3” OR 4”
Follow the next three steps when installing the unit in Non­Direct Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors.
FIGURE 27
PLUG
(Must be
glued in
place)
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR HORIZONTAL NON−DIRECT
VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
6 in. Max.
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE − Debris screen and elbow may be rotated, so that screen may be positioned to face forward, backward or downward.
Page 24
Page 24
TYPICAL AIR INTAKE PIPE CONNECTIONS
DOWNFLOW NONDIRECT VENT APPLICATIONS
(RightHand Exit in Downflow Applications Shown)
FIGURE 28
PLUG
(Must be
glued in
place)
6 in. Max.
PLUG
(Must be
glued in
place)
Downflow Additive Flloor Base
18 in.
Downflow
Evaporator
Coil
2"
2" SWEEP
ELL
2" SWEEP ELL
INTAKE DEBRIS
SCREEN
(Provided)
INTAKE DEBRIS
SCREEN
(Provided)
NOTE − Debris screen and sweep ell may be rotated, so that screen may be positioned to face forward, backward or to the side.
1 − Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in figures 27 and 28. Maintain a minimum clearance of 3" (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed either downward or straight out. Use 2" pipe and fittings only and make sure that the air intake does not extend more than 6" beyond the G61MPV cabinet.
The air intake connector must not be located near the floor. To avoid this complication in downflow applications which do not include a downflow
evaporator coil, the intake air routing should be modi-
fied as shown in figure 28.
2 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired. A pilot indentation is pro­vided in the slip connector to assist in locating and starting the fastener.
3 − Glue the provided 2" ABS plug into the unused ABS air
intake connector on the opposite side of the cabinet with ABS or all purpose solvent cement.
Page 25
Page 25
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the out­doors. The G61MPV is then classified as a non-direct vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the out­doors. The G61MPV is then classified as a direct vent, Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current CSA−B149 Natural Gas and Propane Installation Codes in Canada for details.
Position termination according to location given in figure 29 or 30. In addition, position termination so it is free from any obstructions and 12" above the average snow accumula­tion.
At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of a condensing unit because the condensate can damage the painted coating.
NOTE − If winter design temperature is below 32°F (0°C), exhaust piping should be insulated with 1/2" (13mm), Ar­maflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to out­side air; exterior exhaust pipe should be insulated with 1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or equivalent may be neces­sary. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect insulation from deterioration. Exhaust pipe insulation may not be necessary in some specific applications. NOTE − During extremely cold temperatures, below approximately 20°F (6.7°C), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze−ups. Heating cable installation kit is avail­able from Lennox. See Condensate Piping section for part numbers.
IMPORTANT
Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze−ups and may block the terminations.
IMPORTANT
For Canadian Installations Only: In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).
Page 26
Page 26
FIGURE 29
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
* 12"
* Equal to or greater than soffit depth.
*
* 3 feet (.9m)
* 12"
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
 A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
 Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
7 feet (2.1m)
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner * No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*12 inches (305mm)
**
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the re­quirements of the gas supplier and these installation instructions."
Page 27
Page 27
FIGURE 30
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
* 12"
*
*
* 7 feet (2.1m)
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clear­ance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."
 A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
 Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
* 12"
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* Equal to or greater than soffit depth * Equal to or greater than soffit depth
* No minimum to outside corner
* No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
*
*12 inches (305mm)
Page 28
Page 28
Details of Intake and Exhaust Piping Terminations for Direct Vent Installation
NOTE − In Direct Vent installations, combustion air is tak­en from outdoors and flue gases are discharged to out­doors.
NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building ma­terial, a corrosion−resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See figure 35.
Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 31 through 43 show typical termina­tions.
1 − Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.
2 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il­lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina­tions.
3 − On roof terminations, the intake piping should termi-
nate straight down using two 90° elbows (See figure
31).
4 − Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust pip­ing at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.
NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.
FIGURE 31
UNCONDITIONED
ATTIC SPACE
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
SIZE TERMINATION
PIPE PER TABLE 8.
3"(76mm) MAX.
12" (305mm) ABOVE
AVERAGE SNOW ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
8" (203mm) MIN
Inches(mm)
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 32
FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
See venting table 7 for maximum venting lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
12" (508MM) 12" (508MM)
6" (152MM) 6" (152MM)
8" (203MM) 8" (203MM)
12" (305MM) 20" (508MM)
6" (152MM) 6" (152MM)
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C
SIZE TERMINATION
PER TABLE 8
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
STRAIGHT
APPPLICATION
B
C
A
D
* WALL
SUPPORT
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
EXTENDED
APPLICATION
A
Page 29
Page 29
FIGURE 33
FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
See venting table 7 for maximum venting lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (508MM) 12" (508MM)
6" (152MM) 6" (152MM)
6" (152MM)
12" (305MM) 20" (508MM)
6" (152MM) 6" (152MM)
6" (152MM)
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C
SIZE TERMINATION
PER TABLE 8
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
STRAIGHT
APPPLICATION
B
C
D
* WALL
SUPPORT
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
EXTENDED
APPLICATION
A
A
TABLE 8
EXHAUST PIPE TERMINATION SIZE REDUCTION
G61MPV
MODEL
Exhaust Pipe Size
Termination
Pipe Size
045, 070, 071
2" (51mm), 2−1/2" (64mm),
3" (76mm) or 4" (102mm)
1−1/2" (38mm)
090, 091 2" (51mm) 110, 111 2" (51mm)
135
3" (76mm) or 4" (102mm)
2" (51mm)
5 − On field supplied terminations for side wall exit, ex-
haust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. Intake piping should be as short as possible. See figures 32 and 33.
6 − On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8" and a minimum distance of 6" with a termination elbow. See figures 32 and 33.
7 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob­structions, piping must be supported every 24" (610mm) as shown in figures 32 and 33. In addition, close coupled wall termination kits must be extended for use in this application. See figures 41 and 42. When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated with pipe sized per table 8.The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.
8 − Based on the recommendation of the manufacturer, a
multiple furnace installation may use a group of up to four terminations assembled together horizontally, as shown in figure 38.
FIGURE 34
2" EXTENSION FOR 2" PVC PIPE1" EXTENSION FOR 3" PVC PIPE
1−1/2" ACCELERATOR
(all −045, −070 and −090 units)
FURNACE EXHAUST
PIPE
FURNACE
INTAKE
PIPE
4’’
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT SIDE
FLUSH−MOUNT SIDE WALL TERMINATION
51W11
Page 30
Page 30
C
A
E
D
B
A
B
D
D
B
C
A
C
12"
1
1
2
2
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A− Clearance above
grade or average snow
accumulation
B−Horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Exhaust pipe length
E−Wall support distance
from top of each pipe
(intake/exhaust)
12" (508MM) Min.
12" (508MM) Min.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min. 16" (405 MM) Max.
6" (152MM) Max.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min. 20" (508MM) Max.
6" (152MM) Max.
TABLE 9
FIGURE 35
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommende­d. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
Front View of
Intake and Exhaust
Intake
Exhaust
3
Intake
Exhaust
Page 31
Page 31
FIGURE 36
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
Minimum
Above Average
Snow
Accumulation
SHEET METAL STRAP
(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)
FLASHING
(Not Furnished)
CLAMP
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
INTAKE
1 1/2" (38mm) accelerator
provided on 71M80 &
44W92 kits for
G61MPV−36B−045,
36B−070 & 36B−071
12” (305mm)
12" (305mm) Min.
above grade or
average snow ac-
cumulation.
FIGURE 37
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
INTAKE
AIR
EXHAUST
AIR
INTAKE
AIR
INTAKE
AIR
EXHAUST
AIR
OUTSIDE
WALL
GRADE
CLAMP
(Not Furnished)
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE
SIZE TO TERMINATION
1 1/2" (38mm) accelerator
provided on 71M80 &
44W92 kits for
G61MPV−36B−045,
36B−070 & 36B−071
FIGURE 38
EXHAUST
VENT
INTAKE
AIR
5−1/2"
(140mm)
Front View
12"
(305mm)
5"
(127mm)
18" MAX.
(457mm)
EXHAUST VENT
INTAKE
AIR
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
Inches (mm)
Side View
12" (305mm) Min.
above grade or
average snow ac-
cumulation.
optional intake elbow
FIGURE 39
1/2" (13mm) Foam Insulation
in Unconditioned Space
EXHAUST VENT
INTAKE AIR
OUTSIDE WALL
EXHAUST VENT
INTAKE
AIR
Front View
Top View
DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
6 (152mm) MIN.
SIZE
TERMINATION
PIPE PER
TABLE 8.
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
FIGURE 40
1/2" (13mm) Foam Insulation
in Unconditioned Space
EXHAUST VENT
INTAKE AIR
OUTSIDE WALL
EXHAUST VENT
INTAKE
AIR
Front View
Top View
DIRECT VENT WALL TERMINATION KIT
(22G44 or 44J40)
8" (206mm) MIN.
SIZE
TERMINATION
PIPE PER
TABLE 8.
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
Page 32
Page 32
FIGURE 41
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(Field Furnished)
5” (127 mm)
51/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
WALL SUPPORT*
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
6” (152 mm)
Maximum
If Intake and Exhaust Pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field fabricated piping must be installed.
8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe
between the end of the exhaust pipe and intake pipe
8” (203 mm) Min.
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
FIGURE 42
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(Field Furnished)
5” (127 mm)
51/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
WALL SUPPORT*
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada) 3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
6” (152 mm)
Maximum
If Intake and Exhaust Pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed.
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
6” (152 mm)
Minimum
6” (152 mm)
Minimum
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
Page 33
Page 33
G61MP DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver­tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 43
8" − 12"
(203mm − 305mm)
3" − 8" (76mm− 203mm)
3" − 8"
(76mm−
203mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
ALTERNATE
INTAKE PIPE
INTAKE PIPE
INSULATION (optional)
EXTERIOR
PORTION OF
CHIMNEY
INSULATE TO FORM
SEAL
SHEET
METAL TOP
PLATE
*SIZE TERMINATION
PIPE PER TABLE 8.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
Details of Exhaust Piping Terminations for Non-Direct Vent Applications
Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre­ferred. Figures 44 through 47 show typical terminations.
1 − Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in table 8.The specified pipe size ensures proper veloc­ity required to move the exhaust gases away from the building.
2 − On field supplied terminations for side wall exit, ex-
haust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. See figure 45.
FIGURE 44
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
UNCONDITIONED
ATTIC SPACE
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
SIZE TERMINATION PIPE PER TABLE 8.
1/2" (13mm) FOAM
INSULATION
FIGURE 45
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
PVC REDUCER
1/2" (13mm)
ARMAFLEX
INSULATION
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL TERMINATION KIT
SIZE TERMINATION
PIPE PER TABLE 8.
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
12" MIN.
(305mm)
Above Grade or
average snow accumulation
12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm)
3 − If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, pip­ing must be supported every 24 inches (610mm) as shown in figure 46. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.
Page 34
Page 34
FIGURE 46
12" (305mm)
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
UNCONDITIONED
SPACE
1/2" (13mm) FOAM
INSULATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
*WALL SUPPORT
OUTSIDE WALL
SIZE TER­MINATION
PIPE PER TABLE 8.
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
*Use wall support every 24" (610). Use two supports if extension is
greater than 24" but less than 48".
12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm)
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION
EXTENDED OR (15F74) WALL TERMINATION VENT PIPE
EXTENDED
6" (152mm)
Max
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver­tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 47
3" − 8" (76mm− 203mm)
3" − 8"
(76mm−
203mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
SIZE TERMINATION
PIPE PER TABLE 8.
G61MPV NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
Condensate Piping
This unit is designed for either right- or left-side exit of con­densate piping in either upflow or downflow applications; however, it must be installed on the same side of the unit as the exhaust piping. In horizontal applications, the conden­sate trap should extend below the unit. A 5−1/2" service clearance is required for the condensate trap. Refer to fig­ure 48 for condensate trap locations.
FIGURE 48
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position)
Horizontal
left and
optional
downflow
Horizontal
right and
optional
downflow
Optional
upflow
Optional
upflow
NOTE − In upflow applications where side return air filter is installed on same side as the conden­sate trap, filter rack must be installed beyond condensate trap to avoid interference.
1 − Determine which side condensate piping will exit the
unit. Remove plugs from the condensate collar at the appropriate location on the side of the unit.
NOTE − The condensate trap is factory−shipped with two rubber O−rings and two rubber clean−out caps installed. Check to make sure that these items are in place before installing the trap assembly.
2 − Install condensate trap onto the condensate collar.
Use provided HI/LO screws to secure two upper flanges of the trap to the collar. Use provided sheet metal screw to secure bottom trap flange to side of unit. DO NOT apply glue to secure condensate trap to cabinet. All other joints must be glued. See figure
49.
NOTE − In upflow and downflow applications, con­densate trap must be installed on the same side as exhaust piping.
CAUTION
DO NOT use a power driver to tighten screws which secure condensate trap to cabinet. Screws should be hand−tightened using a screw driver to avoid the possibility of damage to the trap assembly.
Page 35
Page 35
3 − The condensate trap provided with the unit is
manufactured using ABS material. Use ABS to PVC transition solvent cement to glue a field−provided PVC coupling or PVC pipe to the trap. Install a tee and vent pipe near the trap.
NOTE − The condensate trap drain stubs (both sides) have an outer diameter which will accept a standard 3/4" PVC coupling. The inner diameter of each stub will accept standard 1/2" diameter PVC pipe.
NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain stubs on the trap using a hose clamp.
4 − Glue the field−provided drain line to the tee. Route the
drain line to an open drain. As an alternate, clear vinyl tubing may be used to drain condensate away from the trap. Secure the vinyl tubing to the drain stubs on the trap using a hose clamp. Do not overtighten the hose clamp. Condensate line must be sloped downward away from condensate trap to drain. If drain level is above con­densate trap, condensate pump must be used. Con­densate drain line should be routed within the condi­tioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft. (15.2m) − kit no. 26K70.
CAUTION
Do not use copper tubing or existing copper condensate lines for drain line.
5 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit Start−Up section.
6 − Glue the provided cap onto the unused condensate
drain line stub.
FIGURE 49
CONDENSATE ASSEMBLY
COUPLING
CAP
CONDENSATE TRAP
NIPPLE
NIPPLE
TEE
VENT
CLEAN−OUT ACCESS
(both sides)
HI/LO SCREWS (DO NOT use power driver. Hand−tighten using screw driver.)
SCREW
O−RINGS
NOTE − Use screws to secure condensate trap to cabinet. DO NOT apply glue to this joint. All other joints must be glued.
Page 36
Page 36
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet.
WARNING
Do not exceed 600 in−lbs (50 ft−lbs) torque when at­taching the gas piping to the gas valve.
1 − Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into the gas valve from the side of the valve as shown in figures 51 and 52.
2 − When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be con­sidered to avoid excessive pressure drop. Table 10 lists recommended pipe sizes for typical applications.
NOTE − Use two wrenches when connecting gas pip­ing to avoid transferring torque to the manifold.
3 − Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or eleva­tor shafts. Center gas line through piping hole. Gas line should not touch side of unit. See figures 51 and
52.
4 − Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, ev­ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.
5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection. See figures 59 and 60.
6 − In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by in­staller) external to the unit. Union must be of the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­leum gases.
FIGURE 50
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8 NPT PLUG
Leak Check
After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing gas lines using pressures in excess of 1/2 psig (3.48 kPa), gas valve must be disconnected and isolated. See figure 50. Gas valves can be dam­aged if subjected to pressures greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.
GROUND
JOINT
UNION
AUTOMATIC
GAS VALVE (with manual
shut−off valve)
FIELD
PROVIDED
AND INSTALLED
Upflow Application
Left Side Piping
(Standard)
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALV E
Upflow Application
Right Side Piping
(Alternate)
FIGURE 51
Page 37
Page 37
GROUND
JOINT UNION
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT UNION
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALV E
Horizontal Applications
Possible Gas Piping Configurations
Horizontal Application
Left−Side Air Discharge
Horizontal Application
Right−Side Air Discharge
FIGURE 52
TABLE 10
GAS PIPE CAPACITY − FT3/HR (kL/HR)
Nominal
Iron Pipe Size
−Inches(mm)
Internal
Diameter
−Inches(mm)
Length of Pipe−Feet(m)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
100
(30.480)
1/4
(6.35)
.364
(9.246)
43
(1.13)
29
(.82)
24
(.68)
20
(.57)
18
(.51)
16
(.45)
15
(.42)
14
(.40)
13
(.37)
12
(.34)
3/8
(9.53)
.493
(12.522)
95
(2.69)
65
(1.84)
52
(1.47)
45
(1.27)
40
(1.13)
36
(1.02)
33
(.73)
31
(.88)
29
(.82)
27
(.76)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
1
(25.4)
1.049
(26.645)
680
(19.25)
465
(13.17)
375
(10.62)
320
(9.06)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
1−1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1−1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
2−1/2
(63.5)
2.469
(67.713)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95)
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3
(76.2)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
4
(101.6)
4.026
(102.260)
23000
(651.27)
15800
(447.39)
12800
(362.44)
10900
(308.64)
9700
(274.67)
8800
(249.18)
8100
(229.36)
7500
(212.37)
7200
(203.88)
6700
(189.72)
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Page 38
Page 38
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putt­ing the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostat­ic charge by touching hand and all tools on an un­painted unit surface, such as the gas valve or blower deck, before performing any service procedure.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Right Side
FIGURE 53
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Left side
FIGURE 54
The unit is equipped with a field make−up box. The make− up box may be moved to the right side of the furnace to fa­cilitate installation. If the make−up box is moved to the right side, the excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harn­ess to protect it from damage.
Refer to figure 55 and table 11 for field wiring and figure 58 for schematic wiring diagram and troubleshooting.
1 − The power supply wiring must meet Class I restric-
tions. Protected by either a fuse or circuit breaker, se­lect circuit protection and wire size according to unit nameplate.
NOTE − Unit nameplate states maximum current draw. Maximum Over−Current Protection allowed is 20AMP.
2 − Holes are on both sides of the furnace cabinet to facili-
tate wiring.
3 − Install a separate (properly sized) disconnect switch
near the furnace so that power can be turned off for servicing.
4 − Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.
5 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wir­ing diagram shown in figure 55 and table 11. Use 18−gauge wire or larger that is suitable for Class II ra­ting for thermostat connections.
NOTE − Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the G61MPV integrated control.
6 − Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.
NOTE − The G61MPV furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
7 − One line voltage EAC" 1/4" spade terminal is provided
on the furnace control board. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 56 for control board configuration. This terminal is energized when the indoor blower is operating.
8 − One line voltage HUM" 1/4" spade terminal is provided
on the furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the
Page 39
Page 39
provided neutral terminals. See figure 56 for control board configuration. This terminal is energized in the heating mode when the combustion air inducer is oper­ating.
9 − One 24V H" terminal is provided on the furnace control
board terminal block. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the C" terminal. See figure 56 for control board config­uration.
10 −Install the room thermostat according to the instruc-
tions provided with the thermostat. See table 11 for thermostat connections. If the furnace is being
matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously at approximately 38% of the second−stage cooling speed when there is no cool­ing or heating demand.
2 − When the G61MPV is running in the heating mode, the
indoor blower will run on the heating speed designated by the positions of DIP switches 11 and 12.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed designated by the positions of DIP switches 5 and 6.
TYPICAL G61MPV FIELD WIRING DIAGRAM
FIGURE 55
FIELD INSTALLED CLASS II 24V FIELD INSTALLED LINE VOLTAGE
USE COPPER CONDUCTORS ONLY.
Page 40
Page 40
TABLE 11
Field Wiring Applications
Thermostat
Dip Switch Settings and On Board Links (See figure 56)
Wiring Connections
DIP Switch 1
W915
Two−Stage
Cooling
W914 Dehu­midification or Harmony
IIIt
W951
Heat Pumps
1Heat / 1 Cool
NOTE − Use DIP switch 2 to set second−stage heat ON delay. OFF−10 minutes. ON−15 minutes.
ON Intact Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
EXISTING
W915 JUMPER
1 Heat / 2 Cool
NOTE − Use DIP switch 2 to set second−stage heat ON delay. OFF−10 minutes. ON−15 minutes.
ON Cut Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool with t’stat with humidity control
NOTE − Use DIP switch 2 to set second−stage heat ON delay. OFF−10 minutes. ON−15 minutes.
ON Cut Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 41
Page 41
TABLE 11
Field Wiring Applications (Continued)
Thermostat
Dip Switch Settings and On Board Links (See figure 56)
Wiring Connections
DIP Switch 1
W915
Two−Stage
Cooling
W914 Dehu­midification or Harmony
IIIt
W951
Heat Pumps
2 Heat / 2 Cool OFF Cut Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
2 Heat / 2 Cool with t’stat with humidity control
OFF Cut Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
2 Heat / 1 Cool OFF Intact Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
EXISTING
W915 JUMPER
Page 42
Page 42
TWO−STAGE, VARIABLE SPEED INTEGRATED CONTROL BOARD
FIGURE 56
THERMOSTAT CONNECTIONS (TB1)
1/4" QUICK CONNECT TERMINALS
DIP SWITCH FUNCTIONS
INDOOR
BLOWER DIP
SWITCHES
HEATING
DIP
SWITCHES
LEDs
ON−BOARD
JUMPERS
H= 24V HUMIDIFIER OUTPUT L= DO NOT USE 1= FUTURE USE
NEUTRALS= 120 VAC NEUTRAL
W914
W951
W915
HTG DIP SWITCH(ES) FUNCTION
5 and 6 Cooling Mode Blower Speed 7 and 8 Blower Speed Adjustment
9 and 10 Cooling Mode Blower Ramping Profile
11 and 12 Heating Mode Blower Speed
1 T’stat Heat Stages (single or two−stage) 2 Second Stage ON Delay (single−stage t’stat)
3 and 4 Heating Fan OFF Delay
INDOOR BLOWER
DIP SWITCH(ES)
FUNCTION
1 − 4
FUTURE USE
Page 43
Page 43
INTEGRATED CONTROL BOARD DIP SWITCH SETTINGS AND JUMPERS
FIGURE 57
Page 44
Page 44
TYPICAL G61MPV WIRING DIAGRAM
FIGURE 58
Page 45
Page 45
Integrated Control Board
G61MPV units are equipped with a two−stage, variable speed integrated control. This control manages ignition timing, heating mode fan off delays and indoor blower speeds based on selections made using the control dip switches and jumpers. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out. After one hour of con­tinuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and automatically reset the control to relight the furnace.
Heating Operation DIP Switch Settings −− Figure 57
Switch 1 −− Thermostat Selection −− This unit may be used
with either a single−stage or two−stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular application. The DIP switch is factory−positioned for use with a two− stage thermostat. If a single−stage thermostat is to be used, the DIP switch must be repositioned.
a − Select OFF" for two−stage heating operation con-
trolled by a two−stage heating thermostat (factory set­ting);
b − Select ON" for two−stage heating operation con-
trolled by a single−stage heating thermostat. This set­ting provides a timed delay before second−stage heat is initiated.
Switch 2 −− Second Stage Delay (Used with Single− Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage ther­mostat is being used. The switch is factory−set in the OFF position, which provides a 10−minute delay before second− stage heat is initiated. If the switch is toggled to the ON position, it will provide a 15−minute delay before second− stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE− stage thermostat use.
Switches 3 and 4 −− Blower−Off Delay −− The blower−on delay of 45 seconds is not adjustable. The blower−off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated control board. The unit is shipped from the factory with a blower−off delay of 90 seconds. The blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatu­res.Table 12 provides the blower off timings that will result from different switch settings.
TABLE 12
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3 Switch 4
60 Off On
90 Off Off 120 On Off 180 On On
Indoor Blower Operation DIP Switch Settings
−− Figure 57 Switches 5 and 6 −− Cooling Mode Blower Speed −−
Switches 5 and 6 are used to select cooling blower motor speed. The unit is shipped from the factory with the DIP switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below pro­vides the cooling mode blower speeds that will result from different switch settings. Refer to tables 17 through 28 for corresponding cfm values.
TABLE 13
Cooling Mode Blower Speeds
Speed
Switch 5 Switch 6
1 − Low On On
2 − Medium Low Off On
3 − Medium High On Off
4 − High (Factory) Off Off
Switches 7 and 8 −− Blower Speed Adjustment −−
Switches 7 and 8 are used to select blower speed adjust­ment settings. The unit is shipped from the factory with the DIP switches positioned for NORMAL (no) adjustment. The DIP switches may be positioned to adjust the blower speed by +10% or −10% to better suit the application. The table below provides blower speed adjustments that will re­sult from different switch settings. Refer to tables 17 through 28 for corresponding cfm values.
TABLE 14
Blower Speed Adjustment
Adjustment
Switch 7 Switch 8
+10% (approx.) On Off
NORMAL (Factory) Off Off
−10% (approx.) Off On
Switches 9 and 10 −− Cooling Mode Blower Speed Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramp­ing may be used to enhance dehumidification perfor­mance. The switches are factory set at option A which has the greatest effect on blower motor performance. Table 15 provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed on the next page.
NOTE − The off portion of the selected ramp profile only ap­plies during heat pump operation in dual fuel applications.
Page 46
Page 46
TABLE 15
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 9 Switch 10
A (Factory) Off Off
B On Off C Off On D On On
Ramping Option A (Factory Selection)
D Motor runs at 50% for 30 seconds. D Motor then runs at 82% for approximately 7−1/2 minu-
tes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 30 sec-
onds then ramps down to stop.
OFF
OFF
1/2 MIN 50% CFM
COOLING DEMAND
7 1/2 MIN 82% CFM
100% CFM
1/2 MIN 50% CFM
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFF
OFF
82%CFM
100% CFM
COOLING DEMAND
7 1/2 MIN
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 45 sec-
onds then ramps down to stop.
OFF
OFF
100% CFM
100% CFM
DEMAND
45 SEC.
Ramping Option D
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING DEMAND
Switches 11 and 12 −− Heating Mode Blower Speed −−
Switches 11 and 12 are used to select heating mode blower motor speed. The unit is shipped from the factory with the dip switches positioned for medium low (2) speed indoor blower motor operation during the heating mode. The table below provides the heating mode blower speeds that will result from different switch settings. Refer to tables 17 through 28 for corresponding cfm values.
TABLE 16
Heating Mode Blower Speeds
Speed
Switch 11 Switch 12
1 − Low On On
2 − Medium Low
(Factory)
Off On
3 − Medium High On Off
4 − High Off Off
On−Board Jumper W914 −− Figure 57
On−board jumper W914, which connects terminals DS and R on the integrated control board, must be cut when the fur­nace is installed with either the Harmony IIIt zone control board or a thermostat which features humidity control. If the jumper is left intact the PMW signal from the Harmony III control will be blocked and also lead to control damage. Refer to table 29 for operation sequence in applications in­cluding G61MPV, a thermostat which features humidity control and a single−speed outdoor unit. Table 30 gives the operation sequence in applications with a two−speed out­door unit.
On−Board Jumper W951 −− Figure 57
On−board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the fur­nace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the jumper is left intact, terminal O" will remain energized elim­inating the HEAT MODE in the heat pump.
On−Board Jumper W915 −− Figure 57
On−board jumper W915, which connects terminals Y1 and Y2 on the integrated control board, must be cut if two−stage cooling will be used. If the jumper is not cut the outdoor unit will operate in second−stage cooling only.
LEDs (SPEED, CFM, STATUS, E−COM) −− Figure 56
The green SPEED LED indicates circulating blower speed in response to the DS signal. The LED is lit during normal blower operation and is off during a dehumidification de­mand. In Harmony III applications, the brightness of the LED indicates the requested blower speed.
The green CFM LED indicates the blower air flow. Count the number of blinks between the two−second pauses to determine the CFM. Each blink represents approximately 100 CFM.
The STATUS LED flashes diagnostic codes, which are de­tailed on page 43.
The green E−COM LED indicates that the control is receiv­ing and processing commands and inputs. The LED may flash rapidly or may display a single flash, depending upon the activity.
Page 47
Page 47
TABLE 17
G61MPV−36B−045 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
915 430 1070 505 1320 625 1370 645 1055 500 1235 580 1330 625 1420 670
NORM 830 395 965 455 1205 570 1255 590 945 445 100 520 1185 560 1295 610
740
350 860 405 1055 500 1095 515 840 395 970 460 1050 495 1150 540
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
830 390 970 460 1210 570 1255 590 720 340 820 385 890 420 970 455
NORM 755 355 880 415 1080 510 1120 530 665 310 745 350 795 375 875 410
690 325 795 375 950 450 995 470 610 290 685 325 725 340 785 370
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 442 cfm (210 L/s).
TABLE 18
G61MPV−36B−070 and G61MPV−36B−071 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
895 420 1025 485 1290 610 1340 630 1015 480 1190 560 1280 605 1395 660
NORM 820 385 940 445 1155 545 1210 570 930 440 1065 505 1155 545 1270 600
N/A
N/A 840 395 1020 480 1055 495 830 390 950 450 1010 475 1105 520
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
820 385 930 440 1160 550 1210 570 730 345 815 385 865 410 935 440
NORM 760 360 865 410 1045 495 1090 515 680 320 755 355 795 375 855 405
N/A N/A 775 365 930 440 965 455 625 295 695 330 730 345 775 365
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 458 cfm (215 L/s).
Page 48
Page 48
TABLE 19
G61MPV−36C−090 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
N/A N/A 1040 490 1285 605 1340 630 1020 480 1185 560 1275 600 1395 660
NORM N/A N/A 915 430 1150 540 1200 565 905 430 1060 500 1145 540 1270 600
N/A
N/A N/A N/A 1020 480 1055 495 800 380 925 435 1010 475 1100 520
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
N/A N/A 940 445 1160 550 1210 570 705 335 790 375 845 400 920 435
NORM N/A N/A 840 395 1040 490 1075 510 650 305 730 345 770 365 830 395
N/A N/A N/A N/A 915 430 945 445 600 285 670 315 705 330 750 355
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 479 cfm (225 L/s).
TABLE 20
G61MPV−60C−090 and G61MPV−60C−091 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1500 710 1675 790 1880 885 2090 985 1605 760 1710 805 1925 910 2165 1020
NORM 1355 640 1545 730 1720 810 1900 895 1440 680 1560 735 1755 825 1960 925
1194
565 1365 645 1540 730 1695 800 1275 600 1380 650 1590 750 1755 830
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1360 640 1560 735 1730 815 1910 900 1105 520 1185 560 1355 640 1545 730
NORM 1220 575 1405 665 1585 750 1740 820 995 470 1080 510 1205 570 1345 635
1105 520 1235 585 1410 665 1570 740 890 420 960 455 1090 515 1215 575
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm (210 L/s).
Page 49
Page 49
TABLE 21
G61MPV−60C−090 and G61MPV−60C−091 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1450 685 1640 775 1820 860 2055 970 1575 745 1690 795 1895 895 2135 1005
NORM 1320 625 1510 710 1700 800 1870 880 1405 665 1530 720 1735 820 1935 910
1165
550 1320 625 1500 705 1665 785 1250 590 1355 640 1560 735 1735 820
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1315 620 1510 715 1695 800 1875 885 1080 510 1160 545 1315 620 1490 705
NORM 1190 560 1365 645 1545 730 1715 810 985 465 1060 500 1185 560 1330 625
1075 510 1205 570 1370 645 1520 715 865 410 930 440 1065 500 1185 560
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm (210 L/s).
TABLE 22
G61MPV−60C−090 and G61MPV−60C−091 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return with optional RAB return air base
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1440 680 1630 770 1810 855 2015 950 1525 720 1655 780 1860 880 2100 990
NORM 1300 615 1485 700 1655 780 1830 865 1385 655 1500 710 1695 800 1905 900
1155
545 1310 620 1480 700 1640 775 1240 585 1320 625 1510 710 1695 800
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1320 625 1490 700 1665 785 1840 870 1060 500 1135 535 1285 605 1455 685
NORM 1180 555 1345 635 1515 715 1680 795 960 455 1035 490 1165 550 1310 620
1055 500 1180 560 1340 630 1490 705 865 405 920 435 1050 495 1165 550
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 449 cfm (210 L/s).
Page 50
Page 50
TABLE 23
G61MPV−60C−110 and G61MPV−60C−111 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1505 710 1710 805 1915 905 2130 1005 1625 770 1745 825 1990 940 2210 1045
NORM 1370 645 1565 740 1765 835 1945 920 1465 690 1580 745 1790 845 1995 940
1205
570 1380 650 1565 740 1740 820 1290 610 1405 660 1605 760 1790 845
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1370 645 1570 740 1760 830 1945 920 945 445 1020 480 1160 545 1300 615
NORM 1235 585 1420 670 1600 755 1780 840 840 395 910 430 1055 500 1180 555
1105 525 1250 590 1420 670 1580 745 740 350 800 380 920 435 1045 495
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm (220 L/s).
TABLE 24
G61MPV−60C−110 and G61MPV−60C−111 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1485 700 1675 790 1870 885 2080 980 1585 750 1700 800 1905 900 2135 1005
NORM 1350 637 1525 720 1725 815 1895 895 1435 680 1535 725 1740 820 1930 910
1175
555 1335 630 1505 710 1670 790 1280 605 1385 655 1570 740 1755 830
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1325 625 1505 710 1695 800 1870 885 935 440 1025 485 1155 545 1285 605
NORM 1195 565 1365 645 1550 730 1720 810 840 395 915 430 1050 495 1175 555
1080 510 1205 570 1365 645 1530 720 750 355 800 380 925 435 1050 495
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm (220 L/s).
Page 51
Page 51
TABLE 25
G61MPV−60C−110 and G61MPV−60C−111 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air with optional RAB return base. −
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1475 695 1670 790 1865 880 2070 980 1555 735 1685 795 1895 895 2130 1005
NORM 1345 635 1500 710 1695 800 1865 880 1415 670 1540 725 1735 820 1930 910
1180
555 1345 635 1510 710 1685 795 1245 590 1350 635 1545 730 1725 815
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1330 625 1510 715 1695 800 1875 885 1085 510 1155 545 1310 620 1475 695
NORM 1195 565 1375 650 1550 730 1725 815 955 450 1050 495 1185 560 1335 630
1080 510 1210 570 1370 645 1520 715 850 400 920 435 1070 505 1195 565
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 463 cfm (220 L/s).
TABLE 26
G61MPV−60D−135 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1505 710 1705 805 1900 900 2110 995 1615 760 1730 815 1945 920 2190 1035
NORM 1365 645 1550 730 1740 820 1920 905 1455 685 1580 745 1780 840 1985 935
1225
580 1380 650 1545 730 1720 810 1305 615 1400 660 1600 755 1780 840
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1385 655 1570 740 1760 830 1930 910 1135 535 1205 570 1365 645 1540 725
NORM 1250 590 1425 670 1595 755 1775 835 1025 485 1105 520 1235 580 1390 655
1135 535 1265 595 1430 675 1585 750 915 430 985 465 1115 525 1235 585
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm (210 L/s).
Page 52
Page 52
TABLE 27
G61MPV−60D−135 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1470 695 1650 780 1845 870 2040 965 1585 750 1705 805 1905 900 2130 1005
NORM 1325 625 1495 705 1680 795 1865 880 1430 675 1545 730 1765 835 1975 930
N/A
N/A 1335 630 1505 710 1670 790 1275 600 1370 645 1565 740 1755 830
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1335 630 1510 710 1695 800 1870 885 1105 520 1180 555 1330 630 1500 710
NORM 1210 570 1370 645 1540 725 1710 810 990 465 1075 505 1210 570 1355 640
N/A N/A 1225 575 1375 650 1515 715 890 420 950 450 1085 515 1210 570
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm (220 L/s).
TABLE 28
G61MPV−60D−135 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air with optional RAB return air base
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1445 685 1635 770 1825 860 2025 955 1550 730 1660 785 1875 885 2105 995
NORM 1305 615 1475 695 1660 785 1840 870 1400 660 1510 715 1720 810 1920 905
N/A
N/A 1315 620 1480 700 1650 780 1250 590 1345 635 1530 725 1715 810
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1315 620 1490 705 1675 790 1855 875 1080 510 1155 545 1310 620 1478 695
NORM 1195 565 1365 645 1530 725 1695 800 985 465 1055 500 1190 560 1325 625
N/A N/A 1210 570 1360 640 1500 710 875 410 945 445 1060 500 1190 560
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 470 cfm (220 L/s).
Page 53
Page 53
TABLE 29
OPERATING SEQUENCE
G61MPV, SignatureStattThermostat and Single−Stage Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Step
Thermostat Demand Relative Humidity
Compressor
Blower
CFM
(COOL)
Comments
Y1 O G
W
1
Status D
NO CALL FOR DEHUMIDIFICATION
Normal Operation 1 On On On Acceptable
24
VAC
High 100%
Compressor and indoor blower follow thermostat demand
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24
VAC
High 100%
SignatureStatt thermo- stat energizes Y1 and de− energizes D on a call for de−humidification
Dehumidification
Call
2 On On On Demand
0
VAC
High 70%
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24
VAC
High 100%
Dehumidification mode begins when humidity is greater than set point
Dehumidification
call
2 On On On Demand
0
VAC
High 70%
Dehumidification
call ONLY
1 On On On Demand
0
VAC
High 70%
SignatureStatt thermo- stat will keep outdoor unit energized after cooling temperature setpoint has been reached in order to maintain room humidity setpoint.*
Jumpers at indoor unit with a single stage outdoor unit With Condensing unit − Cut W914 (R to DS) on SureLight
®
board
With Heat Pump − Cut W914 (R to DS) & W951 (R to O) on SureLight
®
board
*In Precision mode, SignatureStatt thermostat will allow room temperatures up to 2 °F (1.2°C) cooler than room setting.
Page 54
Page 54
TABLE 30
OPERATING SEQUENCE
G61MPV, SignatureStattThermostat and Two−Stage Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Step
Thermostat Demand Relative Humidity
Compressor
Blower
CFM
(COOL)
Comments
Y1 Y2 O G
W1W
2
Status D
NO CALL FOR DEHUMIDIFICATION
Normal Operation −
Y1
1 On On On Acceptable
24
VAC
Low 70%
Compressor and indoor blower follow thermostat demand
Normal Operation −
Y2
2 On On On On Acceptable
24
VAC
High 100%
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24
VAC
Low 70%
SignatureStatt thermostat energizes Y2 and de−ener­gizes D on a call for de−hu­midification
Dehumidification
Call
2 On On On On Demand
0
VAC
High 70%
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24
VAC
Low 70%
Dehumidification mode be­gins when humidity is greater than set point
Dehumidification
call
2 On On On On Demand
0
VAC
High 70%
Dehumidification
call ONLY
1 On On On On Demand
0
VAC
High 70%
SignatureStatt thermostat will keep outdoor unit en­ergized after cooling tem­perature setpoint has been reached in order to main­tain room humidity set­point.*
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On On Acceptable
24
VAC
High 100%
SignatureStatt thermostat energizes Y2 and de−ener­gizes D on a call for de−hu­midification
Dehumidification
Call
2 On On On On Demand
0
VAC
High 70%
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24
VAC
Low 70%
Dehumidification mode be­gins when humidity is greater than set point
Dehumidification
call
2 On On On On Demand
0
VAC
High 70%
Dehumidification
call ONLY
1 On On On On Demand
0
VAC
High 70%
SignatureStatt thermostat will keep outdoor unit en­ergized after cooling tem­perature setpoint has been reached in order to main­tain room humidity set­point.*
Jumpers at indoor unit with a two stage outdoor unit Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2) on SureLight
®
board
With Condensing unit − Cut W914 (R to DS) on SureLight
®
board
With Heat Pump − Cut W914 (R to DS) & W951 (R to O) on SureLight
®
board
*In Precision mode, SignatureStatt thermostat will allow room temperature up to 2 °F (1.2°C) cooler than room setting.
Page 55
Page 55
Unit Start−Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been underwater. A flood−damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified ser­vice technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch.
Priming Condensate Trap
The condensate trap should be primed with water prior to start−up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into op-
eration.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes. 4 − Adjust the thermostat to deactivate the heating de-
mand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al­low the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating de-
mand and again wait for the combustion air inducer to stop. At this point, the trap should be primed with suffi­cient water to ensure proper condensate drain opera­tion.
BEFORE LIGHTING the unit, smell all around the fur­nace area for gas. Be sure to smell next to the floor be­cause some gas is heavier than air and will settle on the floor.
The gas valve on the G61MPV is equipped with a gas control switch (lever). Use only your hand to turn the gas control switch. Never use tools. If the the switch will not move by hand, do not try to repair it. Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
G61MPV units are equipped with an automatic ignition system. Do not
attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with this ignition system.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figures 59 and 60)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit. 4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand. 5 − Remove the upper access panel. 6 − White Rodgers 36E Gas Valve − Move gas valve
switch to OFF. See figure 59 for the White Rodgers
36E valve.
Honeywell VR8205 Gas Valve − Turn switch on gas
valve clockwise
to OFF. Do not force. See figure
60.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.
WHITE RODGERS 36E SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
TAP ON SIDE
INLET PRESSURE
TAP ON SIDE
LOW FIRE MANIFOLD
PRESSURE ADJUSTMENT
ON SIDE (under cap)
FIGURE 59
Page 56
Page 56
HONEYWELL VR8205 SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
TAP
HIGH FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
FIGURE 60
8 − White Rodgers 36E Gas Valve − Move gas valve switch
to ON. See figure 59 for the White Rodgers 36E valve. Honeywell VR8205 Gas Valve − Turn switch on gas
valve counterclockwise
to ON. Do not force.
9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call the gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting. 2 − Turn off all electrical power to the unit if service is to be
performed. 3 − Remove the upper access panel. 4 − White Rodgers 36E Gas Valve − Move switch on gas
valve to OFF.
Honeywell VR8205 Gas Valve − Turn switch on gas
valve clockwise
to OFF. Do not force.
5 − Replace the upper access panel.
Gas Pressure Adjustment
Gas Flow (Approximate)
1 − Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for one revolu­tions of gas through the meter. A portable LP gas me­ter (17Y44) is available for LP applications.
2 − Compare the number of seconds and the gas meter
size in table 31 to determine the gas flow rate. Multiply the gas flow rate by the heating value to determine the unit input rate. If manifold pressure is correct and the unit input rate is incorrect, check gas orifices for proper size and restriction.
3 − Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.
TABLE 31
Gas Flow Rate (Ft.
3
/Hr.)
Seconds for 1
Revolution
Gas Meter Size
1/2 cu ft Dial 1 cu ft Dial
10 180 360 12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 11 3 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 38 75 50 36 72 52 35 69 54 33 67 56 32 64 58 31 62 60 30 60
Page 57
Page 57
Manifold Pressure Measurement & Adjustment
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. Replace the threaded plug after measurements have been taken.
Manifold Pressure Measurement
To correctly measure manifold pressure, the differential pressure between the positive gas manifold and the nega­tive burner box must be considered. Use pressure test
adapter kit (available as Lennox part 10L34) to assist in measurement.
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting. Connect test gauge +" connection to barbed fitting to measure manifold pressure.
2 − Tee into the gas valve regulator vent hose and connect
test gauge −" connection.
3 − Start unit on low heat (68% rate) and allow 5 minutes
for unit to reach steady state.
4 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue.
5 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
32.
6 − Repeat steps 3, 4 and 5 on high heat.
NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.
CAUTION
Do not attempt to make adjustments to the gas valve.
TABLE 32
Manifold Pressure (Outlet)
Model Number
Fuel
Altitude (feet)
0−2000 2001−4500 4501−5500 5501−6500 6501−7500 7501−10000
Low Fire
High Fire
Low Fire
High Fiire
Low Fire
High Fiire
Low Fire
High Fiire
Low Fire
High Fiire
Low Fire
High Fiire
045, 070, 071, 090, 110, 135
Natural 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5
Propane 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0
091, 111
Natural 1.7 3.5 1.7 3.4 1.7 3.3 1.7 3.2 1.7 3.1 1.7 3.5
Propane 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0
High Altitude Information
NOTE − In Canada, certification for installations at eleva­tions over 4500 feet (1372 m) is the jurisdiction of local au­thorities.
The manifold pressure may require adjustment to ensure proper operation at higher altitudes. Refer to table 32 for manifold pressure and table 33 for required pressure
switch changes and conversion kits at varying altitudes.
The combustion air pressure switches are factory−set and require no adjustment.
NOTE − A natural to L.P. propane gas changeover kit is nec­essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
TABLE 33
Conversion Kit Requirements
Input
High Altitude
Orifice Kit
Natural Gas
Only
High Altitude Pressure Switch Kit
ORDER TWO EACH
LPG/Propane Kit LPG/Propane to
Natural Gas Kit
7501−10,000 ft. 2000−4500 ft. 4501−7500 ft. 7501−10,000 ft. 0−7500 ft. 7501−10,000 ft. 0−7500 ft.
1
7501−10,000 ft.
−045 44W51 − − − − − − − − − 44W48 44W50 44W49 44W49 + 44W51
−070 44W51 − − − − − − 56M23 44W48 44W50 44W49 44W49 + 44W51
−071 44W51 75M22 75M22 56M21 44W48 44W50 44W49 44W49 + 44W51
−090 44W51 − − − 75M22 56M21 44W48 44W50 44W49 44W49 + 44W51
−091 47M82 26W85 26W85 26W86 44W48 44W50 44W49 44W49 + 47M82
−110 44W51 − − − 56M23 75M22 44W48 44W50 44W49 44W49 + 44W51
−111 47M82 56M22 56M22 56M23 44W48 44W50 44W49 44W49 + 47M82
−135 44W51 − − − 56M93 56M93 44W48 44W50 44W49 44W49 + 44W51
1
High Altitude Orifice Kit is required and must be ordered separately for applications from 7501 to 10,000 ft.
Page 58
Page 58
Testing for Proper Venting and Sufficient Combustion Air for Non−Direct Vent Applications
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monox­ide poisoning or death. The following steps shall be followed for each ap­pliance connected to the venting system being placed into operation, while all other appliances con­nected to the venting system are not in operation.
After the G61MPV gas furnace has been started, the fol­lowing test should be conducted to ensure proper venting and sufficient combustion air has been provided to the G61MPV, as well as to other gas-fired appliances which are separately vented.
If a G61MPV furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue prod­ucts, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section.
1 − Seal any unused openings in the venting system.
2 − Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re­striction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − To the extent that it is practical, close all building doors
and windows and all doors between the space in which the appliances connected to the venting system are lo-
cated and other spaces of the building. 4 − Close fireplace dampers. 5 − Turn on clothes dryers and any appliances not con-
nected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. 6 − Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously. 7 − Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 min-
utes of main burner operation. 8 − If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make-up air must be provided.
The venting system should be re-sized to approach
the minimum size as determined by using the ap-
propriate tables in appendix G in the current standards
of the National Fuel Gas Code ANSI−Z223.1/NPFA 54
in the U.S.A., and the appropriate Natural Gas and
Propane appliances venting sizing tables in the cur-
rent standard of the CSA−B149 Natural Gas and Pro-
pane Installation Codes in Canada. 9 − After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their previous
condition of use.
Page 59
Page 59
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits are located in the blower compartment, attached to the back side of the blow­er. These limits are factory set and require no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the burner box. If tripped, check for adequate combustion air before resetting.
Pressure Switches (Two or Four)
The pressure switches are located in the heating compart­ment on the combustion air inducer. These switches check for proper combustion air inducer operation before allow­ing ignition trial. The switches are factory−set and require no adjustment.
Back−Up Secondary Limit (090, 091, 110, 111 & 135)
The back−up secondary limit is located on the combustion air inducer. This switch protects the plastic components from overheating due to indoor blower motor failure. If tripped, check for proper blower operation before resetting.
Temperature Rise
After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the air ducts or structure.
Electronic Ignition
The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re­set device for ignition control lockout caused by ignition fail­ure. This type of lockout is usually due to low gas line pres­sure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat de­mand to the furnace and automatically reset the control to begin the ignition sequence.
Exhaust and Air Intake Pipe
1 − Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 − Are pressure switches closed? Obstructed exhaust
pipe will cause unit to shut off at pressure switches. Check termination for blockages.
3 − Reset manual flame rollout switches on burner box
cover.
Failure To Operate
If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse? 5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lock out? If the unit locks out
again,inspect the unit for blockages.
Heating Sequence of Operation
NOTE − The thermostat selection DIP switchon the control board is factory−set in the TWO−STAGE" position.
Applications Using a Two−Stage Thermostat
A − Heating Sequence −− Control Board Thermostat Selection DIP switch in Two−Stage" Position (Factory Setting)
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low−fire
pressure switch has closed, the combustion air induc­er begins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc­curs. At the same time, the control module sends a sig­nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener­gized on the low fire heating speed and the 24V hu­midifier terminal is energized. The furnace will contin­ue this operation as long as the thermostat has a first−stage heating demand.
5 − If second−stage heat is required, the thermostat sec-
ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.
6 − At the end of the recognition delay, the integrated con-
trol energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once
Page 60
Page 60
the the control receives a signal that the high−fire pres­sure switch is close, the high−fire (second stage) gas valve is energized and the indoor blower motor is en­ergized for operation at the high−fire heating speed.
7 − When the demand for high−fire (second stage) heat is
satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.
8 − When the thermostat demand for low−fire (first stage)
heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.
9 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Applications Using A Single−Stage Thermostat
B − Heating Sequence −− Control Board Thermostat Selection DIP switch in Single−Stage" Position
NOTE − In these applications, two−stage heat will be initi­ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the 120 VAC humidifier termi­nal is energized.
2 − Once the control receives a signal that the low−fire
pressure switch has closed, the combustion air induc­er begins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc­curs. At the same time, the control module sends a sig­nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener­gized on the low−fire heating speed and the 24V hu­midifier terminal is energized. The integrated control also initiates a second−stage on delay (factory−set at 10 minutes; adjustable to 15 minutes).
5 − If the heating demand continues beyond the second−
stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the control receives a sig­nal the high−fire pressure switch is closed, the high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.
6 − When the thermostat heating demand is satisfied, the-
combustion air inducer begins a 5−second post−purge. The field−selected indoor blower off delay begins.
7 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis­connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
All G61MPV filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation. Table 3 lists recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage.
NOTE − After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes.
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 − Turn off power to the unit.
Page 61
Page 61
2 − Have a shallow pan ready to empty condensate water.
3 − Remove the drain plug from the condensate trap and
empty water. Inspect the trap then reinstall the drain plug.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassem­bling unit. Use papers or protective covering in front of fur­nace while removing heat exchanger assembly.
1 − Turn off electrical and gas supplies to the furnace.
2 − Remove the upper and lower furnace access panels.
3 − Mark all gas valve wires and disconnect them from
valve.
4 − Remove gas supply line connected to gas valve. Re-
move gas valve/manifold assembly.
5 − Remove sensor wire from sensor. Disconnect 2-pin
plug from the ignitor.
6 − Disconnect wires from flame roll−out switches.
7 − Remove burner box cover and remove four burner box
screws at the vestibule panel and remove burner box. Set burner box assembly aside.
NOTE − G61MPV−135 units are secured to the vesti­bule panel by two additional screws. These screws must be removed for servicing; however it is not nec­essary to replace the screws. NOTE − If necessary, clean burners at this time. Follow procedures outlined in Burner Cleaning section.
8 − Loosen three clamps and remove flexible exhaust tee.
9 − Remove 3/8 inch rubber cap from condensate drain
plug and drain. Replace cap after draining.
10 − Disconnect condensate drain line from the conden-
sate trap. Remove condensate trap (it may be neces­sary to cut drain pipe). Remove screws that secure condensate collars to either side of the furnace and re­move collars. Remove drain tubes from cold end header collector box.
11 − Disconnect condensate drain tubing from flue collar.
Remove screws that secure both flue collars into place. Remove flue collars. It may be necessary to cut the exiting exhaust pipe for removal of the fittings.
12 − Mark and disconnect all combustion air pressure tub-
ing from cold end header collector box.
13 − Mark and remove wires from pressure switches. Re-
move pressure switches. Keep tubing attached to pressure switches.
14 − Disconnect the 3-pin plug from the combustion air in-
ducer. Disconnect the two wires to the backup secon­dary limit, if applicable. Remove four screws which se­cure combustion air inducer to collector box. Remove combustion air inducer assembly. Remove ground wire from vest panel.
15 − Remove electrical junction box from the side of the fur-
nace.
16 − Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief bushing and pull wiring and bushing through the hole in
the blower deck. 17 − Remove the primary limit from the vestibule panel. 18 − Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger. 19 − Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as-
sembly to cabinet. Remove two screws from blower
rail which secure bottom heat exchanger flange. Re-
move heat exchanger from furnace cabinet. 20 − Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
21 − Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire
assembly. 22 − Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly are
resting on the support located at the rear of the cabi-
net. Remove the indoor blower to view this area
through the blower opening. 23 − Re-secure the supporting screws along the vestibule
sides and bottom to the cabinet. 24 − Reinstall cabinet screws on front flange at blower
deck. 25 − Reinstall the primary limit on the vestibule panel. 26 − Route heating component wiring through hole in blow-
er deck and reinsert strain relief bushing. 27 − Reinstall electrical junction box. 28 − Reinstall the combustion air inducer. Reconnect the
3−pin plug to the wire harness. Reconnect the two
wires to the backup secondary limit, if applicable. 29 − Reinstall pressure switches and reconnect pressure
switch wiring. 30 − Carefully connect combustion air pressure switch
hosing from pressure switches to proper stubs on
cold end header collector box. 31 − Reinstall condensate collars on each side of the fur-
nace. Reconnect drain tubing to collector box. 32 − Reinstall condensate trap on same side as exhaust
pipe. Reconnect condensate drain line to the conden-
sate trap. 33 − Use securing screws to reinstall flue collars to either
side of the furnace. Reconnect exhaust piping and ex-
haust drain tubing. 34 − Replace flexible exhaust tee on combustion air induc-
er and flue collars. Secure using three existing hose
clamps. 35 − Reinstall burner box assembly in vestibule area. 36 − Reconnect flame roll−out switch wires. 37 − Reconnect sensor wire and reconnect 2−pin plug from
ignitor.
Page 62
Page 62
38 − Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
39 − Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve. 40 − Reinstall burner box cover. 41 − Reconnect wires to gas valve. 42 − Replace the blower compartment access panel. 43 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies. 44 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly. 45 − Replace heating compartment access panel.
Cleaning the Burner Assembly
1 − Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels. 2 − Mark all gas valve wires and disconnect them from the
valve. 3 − Disconnect the gas supply line from the gas valve. Re-
move gas valve/manifold assembly. 4 − Mark and disconnect sensor wire from the sensor. Dis-
connect 2-pin plug from the ignitor at the burner box. 5 − Remove burner box cover and remove four screws
which secure burner box assembly to vest panel. Re-
move burner box from the unit.
NOTE − G61MPV−135 units are secured to the vesti-
bule panel by two additional screws. These screws
must be removed for servicing; however it is not nec-
essary to replace the screws.
6 − Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block-
age caused by foreign matter. Remove any blockage. 7 − Reconnect the sensor wire and reconnect the 2−pin
plug to the ignitor wiring harness. 8 − Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports. 9 − Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn-
er box cover. 10 − Reconnect the gas valve wires to the gas valve. 11 − Replace the blower compartment access panel. 12 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies.
13 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is clean and dry and that furnace is operating properly.
14 − Replace heating compartment access panel.
Planned Service
A service technician should check the following items dur­ing an annual inspection. Power to the unit must be shut off for safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob­structed to provide combustion air.
Burners − Must be inspected for rust, dirt, or signs of water.
Vent pipe − Must be inspected for signs of water, damaged,
cracked or sagging pipe, or disconnected joints.
Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door − Must be properly in place and pro­vide a seal between the return air and the room where the furnace is installed.
Return air duct − Must be properly attached and provide an air seal to the unit.
Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.
Combustion gases − Flue products must be analyzed and compared to the unit specifications.
Problems detected during the inspection may make it nec­essary to temporarily shut down the furnace until the items can be repaired or replaced.
Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace in-
spections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon monoxide gas.
Page 63
Page 63
Ignition Control Board Diagnostic Codes (Red LED)
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
Pulse A 1/4 second flash followed by four seconds of off time.
Heartbeat Constant 1/2 second bright and 1/2 second dim cycles.
X + Y
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four seconds, then repeats.
Pulse Power on − Standby.
Heartbeat Normal operation − signaled when heating demand initiated at thermostat.
FLAME CODES
1 + 2 Low flame current −− run mode.
1 + 3 Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3 Low pressure switch failed open.
2 + 4 Low pressure switch failed closed.
2 + 5 High pressure switch failed open.
2 + 6 High pressure switch failed closed.
2 + 7 Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1 Limit switch open.
WATCHGUARD CODES
4 + 1 Watchguard −− Exceeded maximum number of retries.
4 + 2 Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3 Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5 Watchguard −− Limit remained open longer than three minutes.
4 + 6
Watchguard −− Flame sensed out of sequence; flame signal gone.
4 + 7 Ignitor circuit fault −− Failed ignitor or triggering circuitry.
4 + 8 Low line voltage.
HARD LOCKOUT CODES
5 + 1 Hard lockout −− Rollout circuit open or previously opened.
5 + 2 Control failed self check, internal error (control will restart if error recovers).
5 + 3 No Earth ground (control will restart if error recovers).
5 + 4 Reversed line voltage polarity (control will restart if the error recovers).
5 + 6 Low secondary (24VAC) voltage.
Page 64
Page 64
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.)
NO
POLARITY REVERSED.
STATUS ERROR CODE 5 + 4.
POWER ON
POLARITY OKAY?
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
STATUS ERROR CODE 5 + 3.
IS THERE A
PROPER GROUND?
NO
YES
A
NORMAL OPERATION:
STATUS LED −− PULSE
B
THERMOSTAT CALLS FOR HEAT:
STATUS LED −− HEARTBEAT
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
NO
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON. HAS PRIMARY OR
SECONDARY LIMIT RESET WITHIN 3 MINUTES?
STATUS ERROR CODE 3 + 1.
ROLLOUT SWITCH CLOSED?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.
NO
YES
FIRST (LOW) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
STATUS ERROR CODE 2 + 4
YES
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
CONTROL WILL NOT ATTEMPT SECOND−STAGE
OPERATION DURING THIS HEAT DEMAND.
FIRST−STAGE OPERATION WILL BE ATTEMPTED.
STATUS ERROR CODE 2 + 6.
NO
TWO−STAGE OR SINGLE−STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
STATUS LED −− HEARTBEAT
CONTINUED ON NEXT PAGE
NO
NO
60−MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5.
YES
NO
YES
SECOND (HIGH) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
YES
Page 65
Page 65
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
FIRST−STAGE (LOW FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
STATUS ERROR CODE 2 + 3.
YES
NO
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED FIRST−STAGE
PRESSURE SWITCH (or 15 SECOND
INTER−PURGE PERIOD.)
STATUS LED −− HEARTBEAT.
IGNITOR WARM−UP (20 SECONDS)
STATUS LED −− HEARTBEAT.
IS VOLTAGE ABOVE 90 VOLTS?
NO
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95
VOLTS. STATUS ERROR CODE 4 + 8.
YES
NO
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED OR
RECONNECTED.
STATUS ERROR CODE 4 + 7.
YES
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
YES
4−SECOND FLAME STABILIZATION PERIOD.
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.20 microamps)
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
STATUS LED −− HEARTBEAT.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
THERMOSTAT CALLS FOR HEAT
STATUS LED − HEARTBEAT
(Refer to box A on previous page)
YES
FLAME PRESENT?
NO
HAS CONTROL RESET IGNITION SEQUENCE
FOUR (4) TIMES?
WATCHGUARD MODE.
STATUS ERROR CODE 4 + 3.
YES
CONTINUED ON NEXT PAGE
YES
NO
NO
CONTINUED
IS IGNITOR INTACT AND CONNECTED?
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
STATUS ERROR CODE 4 + 1.
IS 60−MINUTE RESET PERIOD COMPLETE?
NO
YES
Page 66
Page 66
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
LOW FLAME SIGNAL
(Does not affect control operation)
STATUS ERROR CODE 1 + 2.
FLAME SIGNAL ABOVE
(u1.40 microamps)
NO
YES
CONTINUED ON NEXT PAGE
YES
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
TWO STAGE THERMOSTAT MODE
(DIP SWITCH SET AT TWO")
YES
YES
START SECOND−STAGE RECOGNITION
ON DELAY (10 OR 15 MINUTES).
STATUS LED −− HEARTBEAT
45−SECOND INDOOR BLOWER ON DELAY BEGINS.
STATUS LED −− HEARTBEAT.
YES
YES
PRIMARY & SECONDARY LIMIT SWITCHES
CLOSED?
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
INDOOR BLOWER ON.
STATUS ERROR CODE 3 + 1.
HAS PRIMARY OR SECONDARY LIMIT
SWITCH CLOSED WITHIN 3 MINUTES?
(Indoor blower on low speed during 3−minute period)
FIRST−STAGE (LOW FIRE)
PRESSURE SWITCH CLOSED?
LIMIT SWITCH WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5
IS 60−MINUTE RESET PERIOD COMPLETE?
THERMOSTAT CALLS FOR HEAT.
STATUS LED −− HEARTBEAT.
SEE BOX A.
NO
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF AFTER DELAY.
STATUS ERROR CODE 2 + 3. CONTROL RESTARTS
IGNITION SEQUENCE IF PRESSURE SWITCH
CLOSES WITHIN 2−1/2 MINUTES.
NO
YES
FIRST−STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
STATUS LED −− PULSE
YES
SECOND−STAGE HEAT DEMAND.
SECOND−STAGE HEAT DEMAND REQUIRED?
NO
SECOND STAGE PRESSURE SWITCH CLOSED?
ABNORMAL FLASH CODE.
NOTE − IF SECOND−STAGE PRESSURE SWITCH
WAS ORIGINALLY FOUND CLOSED,
ABNORMAL CODE WILL FLASH.
SECOND−STAGE PRESSURE SWITCH CLOSED
AT BEGINNING OF HEAT DEMAND?
STATUS ERROR CODE 2 + 6.
YES
NO
SECOND−STAGE 30−SECOND DELAY ON BEGINS.
STATUS LED −− HEARTBEAT.
SECOND−STAGE COMBUSTION AIR INDUCER
ON. SECOND−STAGE GAS VALVE ON. HIGH
HEAT INDOOR BLOWER SPEED ON.
STATUS LED −− HEARTBEAT.
YES
SECOND−STAGE PRESSURE SWITCH CLOSED
IN LESS THAN TEN (10) SECONDS?
STATUS LED −− HEARTBEAT
YES
NO
RETURNS TO FIRST−STAGE HEAT MODE WHICH CONTINUES UNTIL SECOND−STAGE PRESSURE
SWITCH CAN BE PROVEN or HEAT DEMAND IS
SATISFIED. FIVE (5) MINUTE WAIT PERIOD
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS
MADE FOR SECOND−STAGE HEAT?
YES
CONTINUES FIRST−STAGE HEATING DEMAND.
WILL NOT REATTEMPT SECOND−STAGE
HEATING DEMAND.
STATUS ERROR CODE 2 + 5.
SECOND STAGE HEAT DEMAND
STATUS LED −− HEARTBEAT.
NO
YES
NO
YES
CONTINUED
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS
UNTIL ROLLOUT SWITCH IS RESET AND MAIN
POWER IS INTERRUPTED OR THERMOSTAT
IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.
ROLLOUT SWITCHES CLOSED?
NO
YES
YES
NO
YES
YES
Page 67
Page 67
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
SEE BOX B
THERMOSTAT CALLS FOR HEAT.
SEE BOX A
NORMAL OPERATION.
YES
NO
RETURN TO FIRST−STAGE HEAT MODE.
FIRST−STAGE CONTINUES UNTIL SECOND−
STAGE PRESSURE SWITCH CAN BE PROVEN
or HEAT DEMAND IS SATISFIED. A FIVE (5)
MINUTE WAIT PERIOD IS INITIATED BEFORE
RETRY. WERE 5 ATTEMPTS MADE FOR
SECOND−STAGE HEAT?
YES
NO
SEE BOX C
FIRST−STAGE HEAT DEMAND SATISFIED?
HEAT DEMAND SATISFIED?
STATUS LED −− HEARTBEAT.
YES
TWO STAGE THERMOSTAT MODE?
(DIP SWITCH SET AT TWO")
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
YES
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
STATUS LED −− HEARTBEAT.
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5−SECOND
LOW SPEED POST PURGE PERIOD,
INDOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
STATUS LED −− HEARTBEAT.
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY.
STATUS LED −− PULSE.
YES
SECOND STAGE HEAT
DEMAND SATISFIED?
STATUS LED −− HEARTBEAT.
NO
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST−
STAGE OPERATION.
STATUS LED −− HEARTBEAT.
YES
FIRST STAGE HEAT DEMAND SATISFIED?
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5−SECOND LOW SPEED POST−
PURGE PERIOD. INDOOR BLOWER OFF. DELAY INITIATED ON LOW HEAT SPEED.
STATUS LED −− PULSE.
CONTINUED
SECOND−STAGE (HIGH FIRE) HEAT
PRESSURE SWITCH CLOSED?
Page 68
Page 68
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
SIGNAL POLARITY REVERSED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.
POWER ON
YES
IS POLARITY REVERSED?
THERMOSTAT CALLS FOR FIRST−STAGE COOL.
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
NO
IS THERE
PROPER GROUND?
YES
NO
INDOOR BLOWER ENERGIZED ON FIRST STAGE
COOL SPEED AFTER 2 SECOND DELAY.
FIRST−STAGE DEMAND FOR COOL SATISFIED?
NO
THERMOSTAT CALLS FOR SECOND−STAGE COOL.
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
INDOOR BLOWER DE−ENERGIZED AFTER 45−SECOND
DELAY..
YES
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 3.
Page 69
Page 69
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
YES
AFTER 45−SECOND DELAY, INDOOR BLOWER
SWITCHES TO LOW HEAT SPEED.
FIRST−STAGE HEAT DEMAND SATISFIED.
YES
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
FIRST−STAGE COOL DEMAND SATISFIED?
YES
NO
SECOND STAGE COOL DEMAND SATISFIED?
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
YES
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
YES YES
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate −− Example: G61MPV−36B−070−7. All service must be performed by a licensed
professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel Blower access panel Top Cap
Control Panel Parts
Transformer Integrated control board Door interlock switch Circuit Breaker
Blower Parts
Blower wheel Motor Motor mounting frame Power choke (1 hp only) Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure switches Ignitor Primary limit control Secondary limit control Flame rollout switches Combustion air inducer auxiliary limit
Page 70
Page 70
Vent Pipe Sizing Worksheet
Proposed vent pipe size : ______
Termination kit catalog number : _____________ Vent pipe equivalency value from table 5 : ______
Total number of 90° elbows required (indoors and outdoors) ______ X 5 = ______ equivalent feet of pipe
Total number of 45° elbows required (indoors and outdoors) ______ X 2.5 = ______ equivalent feet of pipe
Linear feet of straight pipe required : ______
Add equivalent feet of vent pipe listed in steps 2 through 5.
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
If the total is equal to, or less than, the allowable maximum given in table 7, the proposed pipe size is acceptable. If the total exceeds the maximum allowed vent pipe length, repeat the process above using the next larger diameter pipe until an acceptable total is achieved.
NOTE − In Direct Vent systems, total the equivalent length of either the exhaust OR intake piping run, depending upon which will be LONGER. Intake and exhaust pipe diameter must be the same size and must be terminated in the same pressure zone. Intake and exhaust pipe should be roughly the same length.
Equivalent Feet
TOTAL
Page 71
Page 71
G61MPV Start−Up & Performance Check List
w.c. − LP/Propane
Filter Clean & Secure?
Supply Voltage
Electrical Connections Tight?
Job Name
Job Location
Installer Unit Model No.
Furnace Btu Input
Line Pressure
Job No.
City
City
Serial No.
Date
State
Technician
Flue Connections Tight?
Heating Section
Thermostat
Calibrated? Heat Anticipator Properly Set? Level?
Fuel Type: Natural Gas?
Blower Motor Amps
Blower Motor H.P.
Gas Piping Connections Tight & Leak−Tested?
Proper Draft?
Vent Clear?
State
Temperature Rise
Fan Control Off Setting
Fan Control Setting (45 Seconds Fixed On)
Regulator Pressure
w.c. − Nat.:
LP/Propane Gas?
Combustion Gas Tested?
CO
2
CO
Condensate Connections Tight?
Page 72
Page 72
Requirements for Commonwealth of Massachusetts
Modifications to NFPA−54, Chapter 10
Revise NFPA−54 section 10.8.3 to add the following re­quirements:
For all side wall, horizontally vented, gas−fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the finished grade in the area of the venting, in­cluding but not limited to decks and porches, the following requirements shall be satisfied:
1 − INSTALLATION OF CARBON MONOXIDE DETEC-
TORS. At the time of installation of the side wall, hori­zontally vented, gas−fueled equipment, the installing plumber or gasfitter shall observe that a hard−wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery−oper­ated or hard−wired carbon monoxide detector with an alarm is installed on each additional level of the dwell­ing, building or structure served by the side wall, hori­zontally vented, gas−fueled equipment. It shall be the responsibility of the property owner to secure the ser­vices of qualified licensed professionals for the instal­lation of hard−wired carbon monoxide detectors.
a − In the event that the side wall, horizontally vented,
gas−fueled equipment is installed in a crawl space or an attic, the hard−wired carbon monoxide detec­tor with alarm and battery back−up may be installed on the next adjacent floor level.
b − In the event that the requirements of this subdivi-
sion cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery−operated carbon monoxide detec­tor with an alarm shall be installed.
2 − APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi­fied.
3 − SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade di­rectly in line with the exhaust vent terminal for the hori­zontally vented, gas−fueled heating appliance or equipment. The sign shall read, in print size no less than one−half (1/2) inch in size, GAS VENT DIRECT­LY BELOW. KEEP CLEAR OF ALL OBSTRUC­TIONS."
4 − INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas−fueled equipment shall not approve the installation unless, upon inspec­tion, the inspector observes carbon monoxide detec­tors and signage installed in accordance with the pro­visions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:
1 − The equipment listed in Chapter 10 entitled Equip-
ment Not Required to Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2 − Product Approved side wall, horizontally vented, gas−
fueled equipment installed in a room or structure sepa­rate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment provides a vent­ing system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1 − Detailed instructions for the installation of the venting
system design or the venting system components: and
2 − A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment does not pro­vide the parts for venting the flue gases, but identifies spe­cial venting systems," the following requirements shall be satisfied by the manufacturer:
1 − The referenced special venting system" instructions
shall be included with the appliance or equipment installation instructions; and
2 The special venting systems" shall be Product Ap-
proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall, horizontally vented, gas−fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc­tions shall remain with the appliance or equipment at the completion of the installation.
Loading...