Lennox G61MP-60C-090, G61MP-36B-070, G61MP-60C-091, G61MP-48C-110, G61MP-60C-110 Installation Instructions Manual

...
Page 1
INSTALLATION
E 2009 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
INSTRUCTIONS
G61MP SERIES UNITS
GAS UNITS
506406−01 08/2009
Supersedes 505,124M
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G61MP Parts Identification 3. . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as Construction Heater 5. . . . . . . . . . .
General 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 6. . . . . . . . . . . .
Installation − Setting Equipment 8. . . . . . . . . . . . . . . . . .
Filters 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe & Fittings Specifications 16. . . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 18. . . . . . . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 20. . . . . . . . . . . . . . . . . . . . .
Venting Practices 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board 42. . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 44. . . . . . . . . . . . . . . . . . . . . .
High Altitude Information 45. . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 46. . . . . . . . . . . . . . . . . . . . . . . . .
Service 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ignition Control Board Diagnostic Codes 56. . . . . . . . . .
Troubleshooting 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Pipe Sizing Worksheet 63. . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 63. . . . . . . . . . . . . .
Litho U.S.A.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
08/09
*2P0809*
WARNING
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately. D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
Page 1
*P506406-01*
506406−01
Page 2
G61MP Unit Dimensions − inches (mm)
*NOTE − 60C and 60D size units installed in upflow ap­plications that require air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. Required to maintain proper air velocity.
2. Single side return air with optional RAB Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
Refer to Engineering Handbook for additional information.
**Consider sizing requirements for optional IAQ equip­ment before cutting side return opening.
1
Optional External Side Return Air Filter Kit is not for use
with the optional RAB Return Air Base.
3/4 (19)
one side return air.
A
B 9/16 (14)
11−5/8 (295)
Right
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
9−3/4 (248)
Left
40
(1016)
14−3/4
(375)
16
(406)
AIR FLOW
5/8 (16)
C
*Bottom Return
Air Opening
3/4 (19)
FRONT VIEW SIDE VIEW
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
5−1/2 (140)
6−1/2 (165)
4−1/8 (103)
6−3/4 (171)
4−7/8 (124) Right
2−1/4 (57) Left
2−1/2
(64)
18-3/4 (476)
6−1/2 (165)
3−1/8
(79)
4
(102)
4−1/4 (108)
SUPPLY AIR
OPENING
23-3/4 (603)
25 (635)
TOP VIEW
28−1/2
(724)
19−7/16
(378)
COMBUSTION AIR INTAKE
(Either Side)
EXHAUST AIR OUTLET
(Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
ELECTRICAL INLET
(Either Side)
23
(584)
*OPTIONAL
RETURN CUTOUT
(Either Side)
1−15/16 (49)
23−1/2
(597)
*Bottom Return
Air Opening
9/16
(14)
14**
(356)
Model No.
G61MP−36B−045 G61MP−36B−070 G61MP−36B−071
G61MP−48C−090 G61MP−60C−090 G61MP−60C−091 G61MP−48C−110 G61MP−60C−110 G61MP−60C−111
G61MP−60D−135 24−1/2 622 23−3/8 546 23 584
in. mm in. mm in. mm
17−1/2 446 16−3/8 416 16 406
21 533 19−7/8 505 19−1/2 495
A B C
Page 2
Page 3
G61MP Parts Arrangement
G61MP PARTS IDENTIFICATION
TOP CAP
BURNER BOX
ASSEMBLY
GAS VALVE
AND MANIFOLD
FLUE
COLLAR
COMBUSTION
AIR PRESSURE
PROVE SWITCHES*
COMBUSTION AIR
INDUCER
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
CABINET
WARM HEADER
(COLLECTOR)
BOX
CONDENSER COIL
BURNER ACCESS
PANEL
BLOWER
ACCESS
DOOR
*G61MP−090 shown.
G61MP−045 and −070
are equipped with
two switches.
SIGHT
GLASS
DOOR
INTERLOCK
SWITCH
PRIMARY LIMIT
COLD HEADER
(COLLECTOR)
BOX
SECONDARY
LIMITS (2)
BLOWER
ASSEMBLY
CONTROL BOX
FIGURE 1
Page 3
Page 4
G61MP Gas Furnace
The G61MP category IV gas furnace is shipped ready for installation in the upflow, downflow, horizontal left air dis­charge or horizontal right air discharge position. The fur­nace is shipped with the bottom panel in place. The bot­tom panel must be removed if the unit is to be installed in upflow applications with bottom return air. The bottom panel must also be removed and discarded in all downflow or horizontal applications.
The furnace is equipped for installation in natural gas ap­plications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
The G61MP can be installed as either a Direct Vent or a Non−Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination.
DIRECT VENT INSTALLATION NON−DIRECT VENT
COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
EXHAUST OUTLET
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
NOTE − G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 units also include a 2" diameter PVC street elbow, which is shipped on the blower deck in the heating compartment. G61MP−60D−135 units are shipped with a 3" to 2" PVC reducing elbow.
Canadian Installations Only − Replace the provided 2" street elbow shipped with the G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 units with 2" street elbow Y0162. Replace the provided 3" X 2" reducing elbow shipped with the G61MP−60D−135 units with 3" X 2" reduc­ing elbow 40W22. Y0162 and 40W22 meet B149 vent re­quirements.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
The following items may also be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
Safety Information
G61MP
CONDENSATE
CONDENSATE
DRAIN
G61MP
FIGURE 2
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G61MP unit 1 − Bag assembly containing the following:
3 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 2 − 2" diameter vent / intake plugs 1 − 3" diameter cabinet plug (intake) 1 − 2" diameter debris screen 1 − Logo sticker (for use in downflow applications)
DRAIN
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
G61MP units are CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
In the USA, installation of gas furnaces must conform with lo­cal building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
Page 4
Page 5
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
In order to ensure proper unit operation in non−direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figures 8, 13 and 17. Accessi­bility and service clearances must take precedence over fire protection clearances.
NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code or CSA B149 standard.
NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation.
This G61MP furnace may be used as a high−static unit heater. The G61MP may also be installed in an aircraft han­gar in accordance with the Standard for Aircraft Hangars (ANSI/NFPA No. 408−1990).
Installation in parking structures must be in accordance with the Standard for Parking Structures (ANSI/NFPA No. 88A−1991). Installation in repair garages must be in accor­dance with the Standard for Repair Garages (ANSI/NFPA No. 88B−1991).
This G61MP furnace must be installed so that its electrical components are protected from water.
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually oper­ated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit­tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The G61MP furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms.
This furnace design has not been CSA certified for installa­tion in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of G61MP units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
G61MP units may be used for heating of buildings or struc­tures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
Page 5
Page 6
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
CAUTION
G61MP unit should not be installed in areas normally subject to freezing temperatures.
Combustion, Dilution & Ventilation Air
If the G61MP is installed as a Non−Direct Vent Fur­nace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a G61MP furnace:
Place the furnace as close to the center of the air dis­tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
When the furnace is installed in non−direct vent applica­tions, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
When the furnace is installed in non−direct vent applica­tions, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insu­lated space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De−icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, ap­pliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combus­tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a po­tentially dangerous situation.
In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install G61MP furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas pip­ing. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI−
Page 6
Page 7
Z223.1/NFPA 54). This reprinted material is not the com­plete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Canada, refer to the standard CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliance will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex­haust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 3.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED EX-
HAUST PIPE (ALTER-
NATE LOCATION)
NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm rating of all equipment in the enclosure, but not less than 100 square inches (64516mm.
G61MP
2
2).
(To Adjacent
Unconfined
Space)
per .29kW) per hour of the total input
FIGURE 3
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a mini­mum free area of 1 square inch per 4,000 Btu (645mm per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a mini­mum free area of 1 square inch per 2,000 Btu (645mm per .59kW) per total input rating of all equipment in the en­closure (See figure 4).
2
2
Page 7
Page 8
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
VENTILATION
LOUVERS
(For unheated
crawl space)
2
per 1.17kW) per
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
G61MP
INLET
AIR
FIGURE 4
in the enclosure. See figures 4 and 5. When communicat­ing with the outdoors through horizontal ducts, each open­ing shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 6.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm of the total input rating of all equipment in the enclosure.
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
G61MP
2
per 1.17kW) per hour
INLET AIR
(Ends 12" above
bottom)
FIGURE 5
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indi­rectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm hour of the total input rating of all other equipment in the enclosure.
G61MP
2
per .59kW) per hour of the total
INLET AIR
2
per 1.17kW) per
FIGURE 6
Installation − Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front].
Page 8
Page 9
SETTING EQUIPMENT
UPFLOW APPLICATION DOWNFLOW APPLICATION
AIR FLOW
UNIT MUST BE LEVEL SIDE−TO−SIDE IN ALL APPLICATIONS.
AIR FLOW
HORIZONTAL APPLICATION
AIR FLOW
UNIT
FRONT
FRONT VIEW
AIR FLOW
SIDE VIEW
UNIT
FRONT
1/2"
max.
UNIT SHOULD BE LEVEL FROM LEFT TO RIGHT BUT MAY BE
TILTED SLIGHTLY (MAX. 1/2") FROM BACK TO FRONT TO AID IN THE DRAINING OF THE HEAT EXCHANGER.
FRONT VIEW
The unit must be level from side to side. The unit may be tilted slightly (maximum 1/2 in.) from back to front to aid in the draining of the heat exchanger. See figure 7.
NOTE − Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic wash­er (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be re- moved before the furnace is placed into operation. Af­ter the bolt and washer have been removed, the rigid leg will not touch the blower housing.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
END VIEW
FIGURE 7
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figures 8, 13 and 17.
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
1/2"
max.
FRONT VIEW
AIR FLOW
UNIT
FRONT
SIDE VIEW
WARNING
1/2"
max.
Page 9
Page 10
Upflow Applications
The G61MP gas furnace can be installed as shipped in the upflow position. Refer to figure 8 for clearances.
Installation Clearances
Top
Left Side
Bottom (Floor)
Top/Plenum 1 in. (25 mm)
*Front 0
Back 0
Sides 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. Allow proper clearances to accommodate condensate trap and vent pipe installation. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 8
Right Side
Return Air −− Upflow Units
Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 1800 cfm (850 L/s) are required with 60C or 60D models in an upflow applica­tion, the following return air options are available:
1 − Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. (Required to maintain proper air velocity.) See figure 10.
2 − Return air from single side with optional RAB Return
Air Base. See figure 9.
3 − Return air from bottom.
4 − Return air from both sides.
5 − Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
Page 10
Page 11
(Upflow Applications Only −− For use with B, C and D cabinets only)
AIR FLOW
FURNACE
7−1/4 (184)
Optional Return Air Base
4
(102)
14
(356)
FRONT
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8 (143)
SIDE RETURN
AIR OPENINGS
(Either Side)
1
Minimum 11 (279)
2
Maximum
14 (356)
1
22−7−16
(570)
Overall
(Maximum)
17−1/2 (446) RAB−B (98M60)
21 (533) RAB−C (98M58)
24−1/2 (622) RAB−D (98M59)
OPTIONAL RAB
RETURN AIR BASE
7/8
(22)
23 (584)
27−5/8 (702)
SIDE VIEW
FRONT VIEW
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
FIGURE 9
G61MP applications which include side return air and a condensate trap installed on the same side of the cabinet require either a return air base or field−fabri­cated transition to accommodate an optional IAQ ac­cessory taller than 14.2".
Side Return Air
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 11.
Removing the Bottom Panel
Removing the Bottom Panel
(with transition and filter)
3/4
(19)
20" X 25" X 1"
(508mm X635mm X 25mm)
Return
Air
Plenum
Transition
FIGURE 10
Air Filter
Screw
Bottom Cap
Bottom Panel
FIGURE 11
Page 11
Page 12
Setting an Upflow Unit
When the side return air inlets are used in an upflow ap­plication, it may be necessary to install leveling bolts on the bottom of the furnace. Use field−supplied corrosion−resist­ant 5/16 inch machine bolts (4) and nuts (8). See figure 12.
NOTE − The maximum length of the bolt is 1−1/2 inches.
1 − Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace’s bottom. See fig­ure 12 for the correct location of the holes. Drill through the bottom panel and the bottom flange of the cabinet.
2 − Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole. A flat washer may be added between the nut and the bot­tom of the unit.
3 − Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the nut and the bottom of the unit.
4 − Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement.
NOTE − The unit may be tilted back−to−front a maximum of 1". This will ensure proper draining of the heat exchanger.
Leveling Bolt Installation
Inches (mm)
3/8
(10)
Furnace Front
3/8
(10)
1−3/4
(44)
Furnace
1−3/4
(44)
Leveling Bolt
Locations
Bottom
Leveling Bolt
Locations
3/8
(10)
1−3/4
(44)
1−3/4 (44)
3/8
(10)
FIGURE 12
Downflow Applications
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling cabi­net. Do not drag the unit across the floor in the down-
flow position. Flange damage will result.
After unit has been properly set in place, position provided logo over existing logo and affix sticker on front panel.
Refer to figure 13 for clearances in downflow applica­tions.
Downflow Application Installation Clearances
Top
Left Side
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional additive base is installed between the furnace and the com­bustible floor.
Right Side
FIGURE 13
Installation on Non−Combustible Flooring
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Model No.
B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422
C Cabinet (21") 19 − 3/4 502 20−1/8 511
D Cabinet (24.5") 19 − 3/4 502 23 − 5/8 600
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Front to Rear Side to Side
in. mm in. mm
Page 12
Page 13
Installation on Combustible Flooring
(Using an Additive Base)
1 − When unit is installed on a combustible floor, an addi-
tive base must be installed between the furnace and the floor. The base must be ordered separately. See table 2 for opening size to cut in floor.
CAUTION
The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma­terial other than wood flooring.
TABLE 2
ADDITIVE BASE FLOOR OPENING SIZE
Cabinet
Width
B Cabinet
(17.5")
C Cabinet
(21")
D Cabinet
(24.5")
Catalog
Number
11M60
11M61
11M62
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 − Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
22 559 22 − 3/4 578
22 559 25 − 3/4 654
Installation on Cooling Coil Cabinet
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position.The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 15 or 16).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP (Field Provided)
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
Side View
G61MP UNIT
PROPERLY
SIZED FLOOR
OPENING
FIGURE 14
SUPPLY AIR PLENUM
ADDITIVE BASE
Page 13
PLENUM
(Field Provided)
SECURE FROM
INSIDE CABINET
FIGURE 15
SEALING STRIP (Field Provided)
CABINET
SIDE PANEL
Side View
FIGURE 16
Page 14
Horizontal Applications
The G61MP furnace can be installed in horizontal applica­tions with either right− or left−hand air discharge.
The G61MP may also be installed as a unit heater. Either suspend the furnace as shown in figure 18, or install the furnace on a field−fabricated raised platform. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
Refer to figure 17 for clearances in horizontal applications.
Horizontal Application
Installation Clearances
Right−Hand Discharge
Top
Left End Right End
Bottom (Floor)**
Left−Hand Discharge
Top
3 − If unit is installed above finished space, fabricate a
drain pan fitted with a 1/2 inch or 3/4 inch N.P.T. fitting.
4 − Using 3/8 inch rods and support frame kit or field−fabri-
cated supports, fabricate suspension hangers, keep­ing in mind front service access clearances.
5 − Mount unit on support frame as shown in figure 18.
6 − Continue with exhaust, condensate and intake line
piping instructions.
7 − If unit is suspended above finished space, hang the
field−provided drain pan below the support frame as shown in figure 18. Leave 5−1/2 inches for service clearance below unit for condensate trap.
8 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner. If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
TYPICAL HORIZONTAL CEILING APPLICATION
Left End Right End
Bottom (Floor)**
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. **A 5−1/2 service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 17
Suspended Installation of Horizontal Unit
NOTE − If unit is suspended in attic or crawl space, horizon­tal support kit (Cat No. 56J18 ordered separately) must be used to ensure proper unit support and coil drainage.
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
2 − Provide service platform in front of unit.
BLOWER ACCESS PANEL 3/8 in. RODS
INTAKE/EXHAUST
CONNECTION
SUPPORT FRAME
DRAIN PAN
(to protect finished space)
FIGURE 18
Platform Installation of Horizontal Unit
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
2 − Construct a raised wooden frame and cover frame
with a plywood sheet. Provide a service platform in front of unit. If unit is installed above finished space, fabricate a drain pan to be installed under unit. When installing the unit in a crawl space, a proper sup­port platform may be created using cement blocks and the horizontal support frame kit (ordered separately,
Page 14
Page 15
Lennox part number 56J18). Position the support frame on top of the blocks and install the unit on the frame. Leave 5−1/2 inches for service clearance for condensate trap.
3 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner. If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
4 − Set unit in drain pan as shown in figure 19. Leave 5−1/2
inches for service clearance below unit for condensate trap.
5 − Continue with exhaust, condensate and intake piping
installation according to instructions.
EXHAUST PIPE
INTAKE PIPE
*GAS
CONNECTOR
Unit Heater Discharge Duct Guidelines
A field−fabricated and installed discharge air duct and grille cabinet is suitable for use with the G61MP heater. Keep the following items in mind when constructing the cabinet.
1 − Outer dimensions of cabinet should match those of the
unit heater, so the duct/grille cabinet installs flush with the unit heater cabinet. See figure 20.
2 − Flange both ends of duct/grille cabinet so that screws
can be used to secure cabinet to discharge end of unit heater.
3 − To ensure proper operation, the duct/grille cabinet
must be at least 18 inches long.
4 − Use #10−16 x 1/2 inch sheet metal screws to secure
duct/grille cabinet to unit, taking care not to damage in­ternal components of unit heater when drilling holes or installing screws. See figure 20.
5 − Use adjustable, double−deflection grille(s) to distribute
discharge air. Adjust static pressure to be in the 0.06 inch to 0.10 inch w.c. range.
*Gas connector may be used for Canadian installation if accept­able by local authority having jurisdiction.
RAISED
PLATFORM
CONDENSATE LINE
SERVICE PLATFORM
FIGURE 19
G61MP Installed in Unit Heater Applications
The G61MP may also be installed as a unit heater. Either suspend the furnace from roof rafters or floor joists, as shown in figure 18, or install the furnace on a field−fabri­cated raised platform, as shown in figure 19. The unit must be supported at both ends and beneath the blower deck to prevent sagging. The condensate trap must be installed where it can be serviced at a later date.
18 in.
MIN.
DRAIN PAN
(to protect
finished
space)
NOTE − When installing duct/grille cabinet, take care not to damage internal unit
heater components when drilling holes or installing screws.
FIGURE 20
Return Air −− Horizontal Applications
Return air may be brought in only through the end of a fur­nace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 11.
Page 15
Page 16
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended filter sizes. A filter must be in place whenever the unit is operating.
TABLE 3
Furnace
Cabinet Width
17−1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24−1/2" 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Operation of this furnace in heating mode (indoor blower operating at selected heating speed) with an exter­nal static pressure which exceeds 0.5 inches w.c. may re­sult in erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (by reflected light) of the heat exchanger for leaks after the furnace is installed. If present, this access panel must al­ways be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled ap­pliance (i.e., water heater), or carbon monoxide− producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pres­sure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan­dards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that ad­versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica­tion, or separation that cannot be removed by stirring. Re­fer to the table 4 for approved piping and fitting materials.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
PIPING AND FITTINGS SPECIFICATIONS
PIPE & FITTING MATERIAL
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fit­tings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
TABLE 4
ASTM
SPECIFICATION
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235,
F493
D3138
MARKING
ULCS636
Page 16
Page 17
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alter­nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi­als. Use transition solvent cement when bonding ABS to ei­ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers. Uni­formly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fit­ting and male end of pipe to depth of fitting socket.
TABLE 5
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
Vent Pipe Length Equivalency (feet)
Outdoor Ex­haust Accel-
erator
(Dia. X
Length)
UNIT
MODEL
VENT
PIPE
DIA.
(in.)
1−1/2" X 12"
2 4
2−1/2 5
36B−045
36B−070 36B−071
48C−090 60C−090 60C−091
48C−110 60C−110 60C−111
60D−135
3 7
4 14
2 4
2−1/2 5
3 8
4 14
2
2−1/2
3
4
2−1/2
3
4
3
4
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
*Requires field−provided and installed 1−1/2" exhaust accelerator. **Requires field−provided and installed 2" exhaust accelerator.
Outdoor Ex-
haust Accel-
erator
(Dia. X
Length)
2" X 12"
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
1
2
2
4
2
2
4
6
10
1−1/2"
Concentric
Kit
71M80
or 44W92
12
15
21
42
12
15
24
42
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap­pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex­haust) system. When bonding the vent system to the fur­nace, use ULC S636 approved One−Step Transition Ce­ment to bond the pipe to the flue collar, or to bond the 90° elbow or reducing 90° elbow to the flue collar. In addi­tion, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 5 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when siz­ing vent pipe. All Lennox vent terminations are PVC.
2" Con-
centric Kit
69M29
or 44W92
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
3 3
6 6
6 6
12 12
6 6
6 6
12 12
Not
Allowed
Not
Allowed
 Termination kits 44W92 (includes 1−1/2" reducer), 44W93, 30G28 and 81J20 approved for use in Canadian installations.
3" Con-
centric Kit
60L46
or 44W93
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
15
25
2" Wall Plate
Kit
22G44
or 30G28
4 4* 4
5 5* 5
7 7* 7
14 14* 14
4 4* 4
5 5* 5
8 8* 8
14 14* 14
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
3" Wall Plate
Kit
44J40
or 81J20
1 1**
2 2**
2 2**
4 4**
2 2
2 2
4 4
6
10
2" Wall
Ring Kit
15F74
Not
Allowed
Not
Allowed
Page 17
Page 18
Vent Piping Guidelines
The G61MP can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −− Size pipe according to tables 6 and 7. Table 6 lists the mini­mum equivalent vent pipe lengths permitted. Table 7 lists the maximum equivalent pipe lengths permitted.
Maximum vent length is defined as:
Total length (linear feet) of pipe,
Plus Equivalent length (feet) of fittings, Plus Equivalent length (feet) of termination. NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8.
*NOTE − The exhaust pipe should be offset a minimum of 12 inches to avoid the possibility of water droplets being re-
leased from the exhaust termination. The minimum ex­haust vent length is 15 ft. Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 12−inch vertical offset. See fig­ure 21.
Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 5 feet (1.52m) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to 2.5 feet (.76m) of vent pipe of the same diameter.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact the Application Department for assistance in sizing vent pipe in these applications.
NOTE − The flue collar on all models is sized to accommo­date 2" Schedule 40 flue pipe. When vent pipe which is larger than 2" must be used in an upflow application, a 2" elbow must be applied at the flue collar in order to proper­ly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine ac­ceptable vent lengths. Assign an equivalent feet value to this elbow according to the larger size pipe being used. Contact Lennox’ Application Department for more infor­mation concerning sizing of vent systems which include multiple pipe sizes.
*12" Min.
Upflow and Downflow Application
Rooftop Termination
*12" Min.
Horizontal Application
Rooftop Termination
*A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage
Exhaust Pipe Offset
12" Min.
Upflow and Downflow Application
Side Wall Termination
*12" Min.
Horizontal Application
Side Wall Termination
FIGURE 21
Page 18
Page 19
Use the following steps to correctly size vent pipe diameter.
Refer to Vent Pipe Size Determination Worksheet on page 53.
1 − Determine the vent termination and its corresponding
equivalent feet value according to table 5.
2 − Determine the number of 90° elbows required for both
indoor and outdoor (e.g. snow riser) use. Calculate the corresponding equivalent feet of vent pipe.
3 − Determine the number of 45° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent feet of vent pipe.
4 − Determine the length of straight pipe required.
5 − Add the total equivalent feet calculated in steps 1
through 4 and compare that length to the maximum values given in table 6 for the proposed vent pipe di­ameter. If the total equivalent length required exceeds the maximum equivalent length listed in the appropri­ate table, evaluate the next larger size pipe.
TABLE 6
MINIMUM VENT PIPE LENGTHS
G61MP
MODEL
045, 070, 071, 090,
091
110, 111**
135***
*Any approved termination may be added to the minimum equivalent length listed.
**G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 must have 90° street ell (supplied or field replacment Canadian kit) installed directly into unit flue collar.
***G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replac­ment Canadian ki) installed directly into unit flue collar.
MIN. EQUIV.
VENT LENGTH
15 ft.*
EXAMPLE
5 ft. plus 2 elbows of 2", 2−1/2", 3"
or 4" diameter pipe
5 ft. plus 2 elbows of 2−1/2" 3" or 4"
diameter pipe
5 ft. plus 2 elbows of 3" or 4"
diameter pipe
MAXIMUM VENT PIPE LENGTHS
TABLE 7
MAXIMUM EQUIVALENT VENT
ALTITUDE
0 − 4500
(0 − 1371 m)
4501−7500
(1372−2286 m)
7501 − 10000
(2287 − 3048 m)
n/a −− Not allowed. *G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111must have 90°
street ell (supplied or field replacment Canadian ki) installed directly into unit flue collar.
**G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replacment Canadian ki) installed directly into unit flue collar.
***90° elbows used in configuration of G61MP−60D−135 vent, must be lim­ited to 3" sweep elbows.
†On G61MP−071, −091 and −111 units, sweep elbows must be used for all 90° elbows in the venting system when 2", 2−1/2" or 3" vent pipe is used. Sweep elbows are recommended for use in vent systems of other G61MP units.
G61MP
MODEL
045 59 65 77 234 070 59 65 78 214
071† 59 65 78 214
090 26 42 72 204 091† 26 42 72 204 110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 61 160
045 59 65 77 234
070 59 65 78 214 071† 59 65 78 214
090 26 42 72 204 091† 26 42 72 204 110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 46 160
045 59 65 77 234
070 59 65 78 214 071† 59 65 78 214
090 26 42 72 204 091† 26 42 72 204 110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 46 160
2"
PIPE
LENGTH FEET
2−1/2"
PIPE
PIPE4"PIPE
3"
Page 19
Page 20
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
WARNING
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
NOTE − Furnace flue collar and air inlet fitting are both made of ABS material. Use transition solvent cement when bonding ABS to either PVC or CPVC, refer to the procedure specified in ASTM D3138..
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur­ing assembly (but not after pipe is fully inserted) to dis­tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Page 20
Page 21
Venting Practices
The thickness of construction through which vent pipes may be installed is 24" (610mm) maximum and 3" (76mm) minimum. If a G61MP furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue prod­ucts, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
1 − Use recommended piping materials for exhaust pip-
ing.
2 − Secure all joints so that they are gas-tight using ap-
proved cement.
Suspend piping using hangers at a minimum of every 5 feet (1.52m) for schedule 40 PVC and every 3 feet (.91m) for ABS−DWV, PVC− DWV, SPR−21 PVC, and SDR−26 PVC piping. A suit­able hanger can be fabri­cated by using metal or plastic strapping or a large wire tie.
3 − In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
STRAPPING
(metal, plastic
or large wire
ties)
FIGURE 22
4 − Isolate piping at the point where it exits the outside wall
or roof in order to prevent transmission of vibration to the structure.
5 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
Exhaust Piping
NOTE − A 2" diameter PVC street ell is located on the blower deck of 48C−110, 60C−110 and 60C−111 units. In upflow or downflow applications the street ell must be glued using transition solvent cement directly into the unit flue collar. See figure 23. A 3" to 2" PVC reducing ell is located on the blower deck of the 60D−135 units. In up-
flow or downflow applications, the reducing ell must be glued using transition solvent cement directly into the
unit flue collar.
1 − Choose the appropriate side for venting in upflow or
downflow positions. Exhaust piping exits from the top of the unit in horizontal air discharge applications. Glue the field−provided exhaust vent pipe (or provided street ell or reducing ell in upflow or downflow applica­tions) to the flue collar. All PVC cement joints should be made according to the specifications outlined in ASTM D 2855. Refer to pipe and fittings specifications and gluing procedures.
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
IN UPFLOW OR DOWNFLOW DIRECT OR NONDIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
PLUG
VENT PLUG
(Must be
glued in
place)
PLUG
*2" diameter street elbow provided.
**Street elbow may be used on −045, −070, 071, −090 and −091.
PLUG
2"
CONDENSATE
TRAP
(Must be installed
on same side as
exhaust piping)
2"
2"
2−1/2", 3", OR
or
**2"
2"
2−1/2", 3", OR
4"
TRANSITION
*2"
G61MP−110, −111 with
2−1/2", 3", OR 4" vent
pipe
FIGURE 23
4"
2"
2" max
length
TRANSITION
G61MP−045,
−070, −071 or
−090, −091 with 2−1/2", 3", or 4"
vent pipe
TRANSITION (use only if 4"
pipe is
required)
G61MP−135, −110, −111
with
3" OR 4" vent pipe
45°
MAX
SIDE VIEW
4"
2" max
length
3" to 2" REDUCING ELBOW
45°
MAX
(provided)
Page 21
Page 22
TYPICAL EXHAUST PIPE CONNECTIONS
HORIZONTAL DIRECT OR NON−DIRECT VENT
APPLICATIONS
(Horizontal RightHand Air
Discharge Application Shown)
* 2" maximum length
for −110, −111 −135 only
DO NOT transition from smaller to larger pipe size in horizontal runs of exhaust pipe.
2−1/2", 3", OR
4"
TRANSITION
*2"
2"
36B−045 36B−070 36B−071 48C−090 60C−090 60C−091
48C−110 60C−110* 60C−111* 60D−135*
2"
2"
36B−045 36B−070 36B−071 36C−090 60C−090 60C−091
FIGURE 24
IMPORTANT
Exhaust piping and condensate trap must be installed on the same side of the unit in upflow and dowflow applications or use alternate drain kit 76M20.
2 − All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage. Horizontal runs of exhaust piping must be supported ev­ery 5 feet (1.52m) using hangers.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
3 − On the opposite side of the cabinet, glue the provided
2" ABS vent plug into the unused ABS flue collar with ABS or all purpose solvent cement.
4 − Route piping to outside of structure. Continue with
installation following instructions given in piping ter­mination section.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
Intake Piping
The G61MP furnace may be installed in either direct vent or non−direct vent applications. In non−direct vent applica- tions, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be consid­ered and guidelines listed in Combustion, Dilution and Ven­tilation Air section must be followed.
The G61MP unit is designed for either left−side or right−side air intake connections in either upflow or downflow applica­tions. In horizontal applications, air intake must be brought in through the top. Intake air piping is independent of ex­haust piping.
Follow the next four steps when installing the unit in direct vent applications, where combustion air is taken from out­doors and flue gases are discharged outdoors. The pro-
vided air intake screen must not be used in direct vent ap­plications.
1 − Use transition solvent cement to connect PVC pipe to
the ABS slip connector located on the side of the burn­er box.
2 − Use a #7 sheet metal screw to secure the intake pipe to
the connector, if desired. A pilot indentation is provided in the slip connector to assist in locating and starting the fas­tener.
3 − Glue the provided 2" ABS plug into the unused ABS air
intake connector on the opposite side of the cabinet with ABS all pupose cement.
4 − Route piping to outside of structure. Continue with instal-
lation following instructions given in general guide lines for piping terminations and in intake and exhaust piping ter­minations for direct vent sections. Refer to figure 25 for pipe sizes.
Page 22
Page 23
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR DOWNFLOW DIRECT VENT APPLICATIONS
(RightHand Exit in Upflow Application Shown)
2
PLUG
(Must be
glued in
place)
2
−36B−045−
−36B−070
−36B−071
−48C−090
−60C−090
−60C−091
2
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
2−1/2",
3" OR
4
TRANSITION
2
2
2
−36B−045
−36B−070
−36B−071
−48C−090
−60C−090
−60C−091
−48C−110
−60C−110
−60C−111
*Limit pipe length to 4" in G61MP−110,
−111, −135 applications.
FIGURE 25
Follow the next three steps when installing the unit in Non­Direct Vent applications where combustion air is taken
from indoors and flue gases are discharged outdoors.
TRANSITION
*2"
2−1/2",
3" OR
4
−36B−045
−36B−070
−36B−071
−48C−090
−60C−090
−60C−091
−48C−110
−60C−110*
−60C−111*
−60D−135*
*Limit pipe length to 4" in −110, −111,
−135 applications.
−36B−045
−36B−070
−36B−071
−48C−090
−60C−090
−60C−091
−48C−110
−60C−110
−60C−111
−36B−045
−36B−070
−36B−071
−48C−090
−60C−090
−60C−091
−48C−110
−60C−110*
−60C−111
−60D−135*
2”
−36B−045
−36B−070
−36B−071
−48C−090
−60C−090
−60C−091
2”
2”
2”
21/2”,
3” OR 4”
TRANSITION
*2”
2”
TRANSITION
21/2”,
3” OR 4”
2”
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW OR HORIZONTAL NON−DIRECT
(RightHand Exit in Upflow Application Shown)
PLUG
(Must be
glued in
place)
NOTE − Debris screen and elbow may be rotated, so that screen may be positioned to face forward, backward or downward.
VENT APPLICATIONS
6 in. Max.
INTAKE
DEBRIS
SCREEN
(Provided)
FIGURE 26
FIGURE 27
Page 23
Page 24
TYPICAL AIR INTAKE PIPE CONNECTIONS
DOWNFLOW NONDIRECT VENT APPLICATIONS
(RightHand Exit in Downflow Applications Shown)
2" SWEEP
ELL
INTAKE
DEBRIS
SCREEN
(Provided)
PLUG
(Must be
glued in
place)
6 in. Max.
INTAKE DEBRIS
SCREEN
(Provided)
Downflow
Evaporator
Coil
FIGURE 28
1Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in figures 27 and 28. Maintain a minimum clearance of 3" (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed either downward or straight out. Use 2" pipe and fittings only and make sure that the air intake does not extend more than 6" beyond the G61MP cabinet.
The air intake connector must not be located near the floor. To avoid this complication in downflow applications which do not include a downflow
PLUG
(Must be
glued in
place)
Downflow Additive Flloor Base
2"
2" SWEEP ELL
18 in.
NOTE − Debris screen and sweep ell may be rotated, so that screen may be positioned to face forward, backward or to the side.
evaporator coil, the intake air routing should be modi­fied as shown in figure 28.
2 − Use a #7 sheet metal screw to secure the intake pipe to
the connector, if desired. A pilot indentation is provided in the slip connector to assist in locating and starting the fas­tener.
3 − Glue the provided 2" ABS plug into the unused ABS air
intake connector on the opposite side of the cabinet with ABS or all purpose solvent cement.
Page 24
Page 25
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the out­doors. The G61MP is then classified as a non-direct vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the out­doors. The G61MP is then classified as a direct vent, Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current CSA−B149 Natural Gas and Propane Installation Codes in Canada for details.
Position termination according to location given in figure 29 or 30. In addition, position termination so it is free from any obstructions and 12" above the average snow accumula­tion.
At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of a condensing unit because the condensate can damage the painted coating.
NOTE − If winter design temperature is below 32°F (0°C), exhaust piping should be insulated with 1/2" (13mm), Ar­maflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to out­side air; exterior exhaust pipe should be insulated with 1/2"
(13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or equivalent may be neces­sary. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect insulation from deterioration. Exhaust pipe insulation may not be necessary in some specific applications.
NOTE − During extremely cold temperatures, below approximately 20°F (6.7°C), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze−ups. Heating cable installation kit is avail­able from Lennox. See Condensate Piping section for part numbers.
IMPORTANT
Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze−ups and may block the terminations.
IMPORTANT
For Canadian Installations Only: In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).
Page 25
Page 26
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
C =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
Clearance to permanently
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
closed window
D =
Vertical clearance to ventilated soffit
located above the terminal within a
* Equal to or greater than soffit depth.
horizontal distance of 2 feet (mm)
from the center line of the terminal
E =
F =
G =
H =
I =
J =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
* Equal to or greater than soffit depth.
* No minimum to outside corner * No minimum to outside corner
* 3 feet (.9m) * 3 feet (.9m)
3 feet (.9m) within a height 15 feet (4.5m)
*
above the meter / regulator assembly
* 3 feet (.9m)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
pliance
K =
L =
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)
paved driveway located on public property
M =
1
2
 A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.  Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
Clearance under veranda, porch,
deck or balcony
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
*12 inches (305mm)
FIGURE 29
H
Operable
A
Fixed
Closed
J
B
I
M
AREA WHERE TERMINAL IS NOT PERMITTED
1
Canadian Installations
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12"
* 12"
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clear­ance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."
K
2
Page 26
Page 27
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
C =
Clearance to permanently
closed window
D =
Vertical clearance to ventilated soffit
located above the terminal within a
* Equal to or greater than soffit depth
horizontal distance of 2 feet (mm)
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
* Equal to or greater than soffit depth * Equal to or greater than soffit depth
* No minimum to outside corner
* 3 feet (.9m)
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
K =
L =
M =
1
2
 A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
 Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)
FIGURE 30
H
Operable
A
Fixed
Closed
J
B
I
M
AREA WHERE TERMINAL IS NOT PERMITTED
1
Canadian Installations
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12"
* 12"
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
* 3 feet (.9m)
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clear­ance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."
K
2
Page 27
Page 28
Details of Intake and Exhaust Piping Terminations for Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.
Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In at­tic or closet installations, vertical termination through the roof is preferred. Figures 31 through 39 show typical ter­minations.
1 − Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.
2 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il­lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina­tions.
3 − If necessary, install a field−provided reducer to adapt
larger vent pipe size to termination pipe size.
4 − On roof terminations, the intake piping should termi-
nate straight down using two 90° elbows (See figure
31).
5 − Exhaust piping must terminate straight out or up as
shown. In rooftop applications, a reducer may be re­quired on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.
NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.
6 − On field supplied terminations for side wall exits, ex-
haust piping should extend a minimum of 12 inches (305mm) beyond the outside wall. Intake piping should be as short as possible. See figure 32.
7 − On field supplied terminations, a minimum separation
distance between the end of the exhaust pipe and the end of the intake pipe is 8 inches (203mm).
8 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other obstruc­tions, piping must be supported every 3 ft. (.9m) as shown in figure 22. Refer to figure 35 for proper piping method. In addition, WTK wall termination kit must be extended for use in this application. See figure 38. When exhaust and intake piping must be run up an outside wall, the exhaust piping is reduced to 1−1/2" (38mm) after the final elbow. The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.
9 − Based on the recommendation of the manufacturer, a
multiple furnace installation may use a group of up to four termination kits WTK assembled together hori­zontally, as shown in figure 37.
EXHAUST PIPE TERMINATION SIZE REDUCTION
TABLE 8
G61MP
MODEL
045, 070, −071 2", 2−1/2", 3" or 4" 1−1/2"
090, −091 2", 2−1/2", 3" or 4" 2"
110, −111 2−1/2", 3" or 4" *2"
135 3" or 4" *2"
*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.
Inches(mm)
8" (203) MIN
12" (305) ABOVE
AVERAGE SNOW
ACCUMULATION
3" (76) OR
2" (51) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
Exhaust Pipe Size Termination Pipe Size
3(76) MAX.
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
SIZE TERMINATION PIPE PER TABLE 8.
UNCONDITIONED
ATTIC SPACE
1/2" (13) FOAM INSULATION IN
UNCONDITIONED
SPACE
FIGURE 31
12" (305) MAX.
1/2" (13) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
TOP VIEW WALL RING KIT WITH STRAIGHT INTAKE
1/2 (13) ARMAFLEX
INSULATION IN
UNCONDITIONED
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
Inches (mm)
TOP VIEW WALL RING KIT WITH 90° ELBOW ON INTAKE
OUTSIDE
SPACE
OUTSIDE
WALL
WALL
2" (51)
PVC
COUPLING
(unless supported)
6" (152)
8" (203)
MINIMUM
(15F74)
12 (305) MAX.
6 (152)
MAXIMUM
4 (102)
MINIMUM
(15F74)
1/2" (13)
ARMAFLEX
INSULATION
TERMINA-
MAXI-
MUM
TION PIPE
PER TABLE
Inches (mm)
1/2" (13)
ARMAFLEX
INSULATION
TERMINATION PIPE
PER TABLE 8.
SIZE
8.
SIZE
FIGURE 32
Page 28
Page 29
EXHAUST
TERMINATION
INTAKE
TERMINATION
12" (305) ABOVE
AVERAGE SNOW
ACCUMULATION
Inches (mm)
INTAKE
VENT
EXHAUST VENT
Front View
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST
INTAKE
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
(71M80, 69M29 or 60L46)
FIGURE 33
Inches (mm)
EXHAUST
INTAKE
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
DIRECT VENT CONCENTRIC WALL TERMINATION
(71M80, 69M29 or 60L46)
INTAKE
TERMINATION
12" (305) Min.
above grade or average
snow accumulation.
EXHAUST
TERMINATION
FIGURE 34
12" (305) MAX. for 2" (51)
(15F74)
(unless supported)
8 (203)
MIN.
12" (305) ABOVE
AVERAGE SNOW
ACCUMULATION
1/2" (13) FOAM
INSULATION
SIZE
TERMINATION
PIPE PER
TABLE 8.
Inches(mm)
UNCONDITIONED
SPACE
OUTSIDE WALL
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES EVERY
36" (914)
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
1/2" (13) FOAM INSULATION IN
UNCONDITIONED
SPACE
SIDE VIEW
DIRECT VENT WALL RING TERMINATION
See venting table 6 for maximum venting lengths with this arrangement.
1/2" (13) Foam Insulation
in Unconditioned Space
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
Side View
EXHAUST VENT
INTAKE VENT
Inches (mm)
OUTSIDE WALL
DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
FIGURE 36
EXHAUST
VENT
INTAKE
VENT
Inches (mm)
5"
(127)
18" MAX.
(457)
12"
(305)
5−1/2"
(140)
Front View
EXHAUST VENT
INTAKE
VENT
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT WTK
FIGURE 37
FIGURE 35
Page 29
Page 30
INTAKE
AIR
GRADE
12" (305) MAX. for 2" (51) 20" (508) MAX. for 3" (76)
(unless supported)
8" (203)
Minimum
Side View
Inches (mm)
EXHAUST
AIR
Minimum 12"
(305)
above grade or
average snow accumulation.
INTAKE
AIR
5"
(127)
12"
(305)
5-1/2"
(140)
COVER EXHAUST
VENT WITH
1/2" (13)
FOAM
INSULATION
EXHAUST
AIR
Minimum 12"
(305)
above grade or
average snow accumulation.
GRADE
DIRECT VENT TERMINATION
WALL TERMINATION KIT (22G44, 44J40, 30G28 or 81J20) EXTENDED VENT FOR GRADE CLEARANCE
FIGURE 38
Front View
G61MP DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
3" − 8"
8" − 12"
(203mm − 305mm)
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
Minimum 12" (305)
MINIMUM 12"
above roof or average
(305mm) ABOVE
snow accumulation.
ROOF
INSULATE TO FORM
SEAL
*SIZE TERMINATION
PIPE PER TABLE 8.
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­trated. In any exterior portion of chimney, the exhaust vent must be insulated.
(76mm− 203mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3" − 8" (76mm− 203mm)
ALTERNATE
INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
FIGURE 39 Details of Exhaust Piping Terminations for Non-Direct Vent Applications
Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre­ferred. Figures 40 through 43 show typical terminations.
1 − Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in table 8.The specified pipe size ensures proper veloc­ity required to move the exhaust gases away from the building.
2 − On field supplied terminations for side wall exits, ex-
haust piping should extend a maximum of 12 inches (305mm) beyond the outside wall, unless support is provided in the horizontal section. See figure 41.
Inches(mm)
12" (305mm) ABOVE AVE.
SNOW
ACCUMULATION
3" (76) OR
2" (51) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 40
12" (305) Max. for 2" (51)
1/2" (13) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER VENT PIPE SIZE
TO TERMINATION
Unless Supported
Inches (mm)
TOP VIEW
NON−DIRECT VENT WALL RING KIT
(15F74)
FIGURE 41
SIZE TERMINATION
PIPE PER TABLE 8.
UNCONDITIONED
ATTIC SPACE
1/2" (13)
ARMAFLEX
INSULATION
PVC REDUCER
SIZE TERMINATION PIPE PER TABLE 8.
Page 30
Page 31
3 − If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, pip­ing must be supported every 3 feet (.9m) as shown in figure 22. Refer to figure 42 for proper piping method. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.
Inches(mm)
UNCONDITIONED
SPACE
OUTSIDE WALL
PROVIDE SUPPORT
FOR EXHAUST LINES
EVERY 36" (914)
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
1/2" (13) FOAM
INSULATION IN
UNCONDITIONED
SPACE
SIDE VIEW
NON−DIRECT VENT WALL RING TERMINATION
(15F74)
12" (305) Max. for 2" (51) Unless Supported
SIZE TER­MINATION
PIPE PER
TABLE 8.
12" (305) ABOVE
AVERAGE SNOW
ACCUMULATION
1/2" (13) FOAM
INSULATION
FIGURE 42
G61MP NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION PIPE PER TABLE 8.
MINIMUM 12"
MINIMUM
12" (304mm)
(305mm) ABOVE
ABOVE AVERAGE
AVERAGE SNOW
SNOW ACCUMULATION
ACCUMULATION
INSULATE TO FORM
SEAL
SHEET
METAL TOP
PLATE
3" − 8" (76mm− 203mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3" − 8" (76mm− 203mm)
EXTERIOR
PORTION OF
CHIMNEY
sate trap should extend below the unit. A 5−1/2" service clearance is required for the condensate trap. Refer to fig­ure 44 for condensate trap locations.
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position)
Horizontal
left and optional
downflow
Optional
upflow
Horizontal
right and
optional
downflow
Optional
upflow
FIGURE 44
1 − Determine which side condensate piping will exit the
unit. Remove plugs from the condensate collar at the appropriate location on the side of the unit.
NOTE − The condensate trap is factory−shipped with two rubber O−rings and two rubber clean−out caps installed. Check to make sure that these items are in place before installing the trap assembly.
2 − Install condensate trap onto the condensate collar.
Use provided HI/LO screws to secure two upper flanges of the trap to the collar. Use provided sheet metal screw to secure bottom trap flange to side of unit. DO NOT apply glue to secure condensate trap to cabinet. All other joints must be glued. See figure
45.
NOTE − In upflow and downflow applications, con­densate trap must be installed on the same side as exhaust piping.
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver­tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 43
Condensate Piping
This unit is designed for either right- or left-side exit of con­densate piping in either upflow or downflow applications; however, it must be installed on the same side of the unit as the exhaust piping. In horizontal applications, the conden-
CAUTION
DO NOT use a power driver to tighten screws which secure condensate trap to cabinet. Screws should be hand−tightened using a screw driver to avoid the possibility of damage to the trap assembly.
3 − The condensate trap provided with the unit is
manufactured using ABS material. Use ABS to PVC transition solvent cement to glue a field−provided PVC coupling or PVC pipe to the trap. Install a tee and vent pipe near the trap.
Page 31
Page 32
NOTE − The condensate trap drain stubs (both sides) have an outer diameter which will accept a standard 3/4" PVC coupling. The inner diameter of each stub will accept standard 1/2" diameter PVC pipe.
NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain stubs on the trap using a hose clamp.
4 − Glue the field−provided drain line to the tee. Route the
drain line to an open drain. As an alternate, clear vinyl tubing may be used to drain condensate away from the trap. Secure the vinyl tubing to the drain stubs on the trap using a hose clamp. Do not overtighten the hose clamp. Condensate line must be sloped downward away from condensate trap to drain. If drain level is above con­densate trap, condensate pump must be used. Con­densate drain line should be routed within the condi­tioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft. (15.2m) − kit no. 26K70.
5 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit Start−Up section.
6 − Glue the provided cap onto the unused condensate
drain line stub.
CONDENSATE ASSEMBLY
CAP
O−RINGS
SCREW
HI/LO SCREWS (DO NOT use power driver. Hand−tighten using screw driver.)
NIPPLE
COUPLING
CLEAN−OUT ACCESS
CONDENSATE TRAP
VENT
NIPPLE
TEE
(both sides)
CAUTION
Do not use copper tubing or existing copper condensate lines for drain line.
NOTE − Use screws to secure condensate trap to cabinet. DO NOT apply glue to this joint. All other joints must be glued.
FIGURE 45
Page 32
Page 33
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­leum gases.
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
FURNACE
WARNING
Do not exceed 600 in−lbs (50 ft−lbs) torque when at­taching the gas piping to the gas valve.
1 − Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into the gas valve from the side of the valve as shown in figure 48.
2 − When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be con­sidered to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical applications.
NOTE − Use two wrenches when connecting gas pip­ing to avoid transferring torque to the manifold.
3 − Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or eleva­tor shafts. Center gas line through piping hole. Gas line should not touch side of unit. See figure 48.
4 − Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, ev­ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.
5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection. See figures 55 and 56.
6 − In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by in­staller) external to the unit. Union must be of the ground joint type.
ISOLATE
GAS VALVE
CAP
FIGURE 46
Leak Check
After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 46. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa).
WARNING
Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.
FIRE OR EXPLOSION HAZARD
Upflow Application
Left Side Piping
(Standard)
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT UNION
DRIP LEG
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
FIELD
PROVIDED
AND INSTALLED
FIGURE 47
Page 33
Upflow Application
Right Side Piping
(Alternate)
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Page 34
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Horizontal Application
Right−Side Air Discharge
Horizontal Applications
Possible Gas Piping Configerations
MANUAL
MAIN SHUT−OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Horizontal Application
Left−Side Air Discharge
MANUAL
MAIN SHUT−OFF
VALV E
(With 1/8 in. NPT
Plugged Tap
Shown)
GROUND
JOINT
UNION
DRIP LEG
FIGURE 48
TABLE 9
GAS PIPE CAPACITY − FT3/HR (kL/HR)
Nominal
Iron Pipe Size
−Inches(mm)
1/4
(6.35)
3/8
(9.53)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1−1/4
(31.75)
1−1/2
(38.1)
2
(50.8)
2−1/2
(63.5)
3
(76.2)
4
(101.6)
Internal
Diameter
−Inches(mm)
.364
(9.246)
.493
(12.522)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
43
(1.13)
95
(2.69)
175
(4.96)
360
(10.19)
680
(19.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
29
(.82)
65
(1.84)
120
(3.40)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
24
(.68)
52
(1.47)
97
(2.75)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Length of Pipe−Feet(m)
20
(.57)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
18
(.51)
40
(1.13)
73
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
16
(.45)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
8800
(249.18)
15
(.42)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
14
(.40)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
13
(.37)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
7200
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Page 34
Page 35
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic com­ponents. Take precautions during furnace installa­tion and service to protect the furnace’s electronic controls. Precautions will help to avoid control ex­posure to electrostatic discharge by putting the fur­nace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an un­painted unit surface, such as the gas valve or blower deck, before performing any service procedure.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Right Side
FIGURE 49
INTERIOR MAKE−UP BOX INSTALLATION
Left side
MAKE−UP
BOX
FIGURE 50
The unit is equipped with a field make−up box. The make− up box may be moved to the right side of the furnace to fa­cilitate installation. If the make−up box is moved to the right side, the excess wire must be pulled into the blower compartment. Secure the excess wire to the existing har­ness to protect it from damage.
Refer to figure 51 and table 10 for field wiring and figure 54 for schematic wiring diagram and troubleshooting.
1 − Select circuit protection and wire size according to the
unit nameplate. The power supply wiring must meet Class I restrictions.
2 − Holes are on both sides of the furnace cabinet to facili-
tate wiring.
3 − Install a separate disconnect switch (protected by ei-
ther fuse or circuit breaker) near the furnace so that power can be turned off for servicing.
4 − Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.
5 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wir­ing diagram shown in figure 51 and table 10. Use 18−gauge wire or larger that is suitable for Class II rat­ing for thermostat connections.
NOTE − Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the G61MP integrated control.
6 − Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.
NOTE − The G61MP furnace contains electronic com­ponents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
7 − One line voltage HUM" 1/4" spade terminal is provided
on the furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 52 for control board configuration. This terminal is energized in the heating mode when the combustion air inducer is oper­ating.
8 − One line voltage EAC" 1/4" spade terminal is provided
on the furnace control board. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 52 for control board configuration. This terminal is energized when the indoor blower is operating.
Page 35
Page 36
9 − One 24V H" terminal is provided on the furnace control
board terminal block. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the C" terminal. See figure 52 for control board config­uration.
10 −Install the room thermostat according to the instruc-
tions provided with the thermostat. See table 10 for field wiring connections in varying applications. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.
TYPICAL G61MP FIELD WIRING DIAGRAM
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously on the low heat speed when there is no cooling or heating demand.
2 − When the G61MP is operating in the high−fire or low−
fire heating mode, the indoor blower will run on the cor­responding heating speed.
3 − When there is a cooling demand, the indoor blower will
run on the corresponding cooling speed.
FIGURE 51
Page 36
Page 37
Thermostat
1 Heat / 1 Cool
NOTE − Use DIP switch 2 to set sec­ond−stage heat ON delay. OFF10 minutes. ON−15 minutes.
TABLE 10
Field Wiring Applications
DIP Switch Settings and On−Board Links
(Figure 52)
W915
DIP Switch 1
(Y1 to Y2)
Two−Stage
Cooling
ON Intact Intact
W951
(O to R)
Heat Pumps
S1
T’STAT
Wiring Connections
CONTROL
TERM. STRIP
W915 JUMPER
OUTDOOR
UNIT
EXISTING
1 Heat / 2 Cool
NOTE − Use DIP switch 2 to set sec­ond−stage heat ON delay. OFF−10 minutes. ON−15 minutes.
ON Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 37
Page 38
TABLE 10
Field Wiring Applications (Continued)
DIP Switch Settings and On−Board Links
(Figure 52)
Thermostat
DIP Switch 1
W915
(Y1 to Y2)
Two−Stage
Cooling
W951
(O to R)
Heat Pumps
2 Heat / 2 Cool OFF Cut Intact
S1
T’STAT
Wiring Connections
CONTROL
TERM. STRIP
OUTDOOR
UNIT
2 Heat / 1 Cool OFF Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
EXISTING
W915 JUMPER
NOTEDo NOT make a wire connection between the room thermostat L terminal and the L terminal of the G61MP integrated control.
Page 38
Page 39
DIAGNOSTIC
LEDs
DIP
SWITCHES
TWO−STAGE INTEGRATED CONTROL BOARD
1/4" QUICK CONNECT TERMINALS
SENSE = 120 VAC OUTPUT TO FLAME SENSER
NEUTRALS= 120 VAC NEUTRAL
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD
W915
W951
HEAT LOW = 120 VAC OUTPUT TO CIRC BLWR −− LOW HT SPEED
HEAT HIGH/ COOL LOW = 120 VAC OUTPUT TO CIRC BLWR −−
COOL HIGH = 120 VAC OUTPUT TO CIRC BLWR −− HIGH COOL SPEED
ON−BOARD
JUMPERS
1= ERROR CODE RECALL H= 24V HUMIDIFIER OUTPUT L= DO NOT USE
DIP SWITCH(ES) FUNCTION
1 −− 2 Stage T’stat Selects t/stat type (single or two−stage)
2 −− 2nd Stage Delay Second stage ON delay (single−stage t’stat)
3 & 4 −− Heat Off Delay Heating fan OFF delay
5 −− Cool Off Delay Cooling fan OFF delay
AND CONTINUOUS FAN
HIGH HEAT AND LOW COOL SPEED
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH FUNCTIONS
FIGURE 52
Page 39
Page 40
INTEGRATED CONTROL BOARD DIP SWITCH SETTINGS AND JUMPERS
FIGURE 53
Page 40
Page 41
TYPICAL G61MP WIRING DIAGRAM
FIGURE 54
Page 41
Page 42
Integrated Control Board
G61MP units are equipped with a two−stage integrated control. This control manages ignition timing and fan off delays based on selections made using the control DIP switches and jumpers. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out. After one hour of con­tinuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and automatically reset the control to relight the furnace.
DIP Switch Settings −− Figure 53 Switch 1 −− Thermostat Selection −− This unit may be used
with either a single−stage or two−stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular application. The DIP switch is factory−positioned for use with a two− stage thermostat. If a single−stage thermostat is to be used, the DIP switch must be repositioned.
a − Select OFF" for two−stage heating operation con-
trolled by a two−stage heating thermostat (factory set­ting);
b − Select ON" for two−stage heating operation con-
trolled by a single−stage heating thermostat. This set­ting provides a timed delay before second−stage heat is initiated.
Switch 2 −− Second Stage Delay (Used with Single− Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage ther­mostat is being used. The switch is factory−set in the OFF position, which provides a 10−minute delay before second− stage heat is initiated. If the switch is toggled to the ON position, it will provide a 15−minute delay before second− stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE− stage thermostat use.
Switches 3 and 4 −− Heating Blower−Off Delay −− The heating blower−on delay of 45 seconds is not adjustable. The heating blower−off delay (time that the blower operates after the heating demand has been satisfied) can be ad­justed by moving switches 3 and 4 on the integrated control board. The unit is shipped from the factory with a heating blower−off delay of 90 seconds. The heating blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a sup­ply air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter set­tings provide higher supply air temperatures.Table 11 pro­vides the blower off timings that will result from different switch settings.
Heating Blower−Off Delay Switch Settings
Blower Off Delay
(Seconds)
60 Off On
90 Off Off 120 On Off 180 On On
Switch 5 −− Cooling Blower−Off Delay −− The cooling blower−off delay (time that the blower operates after the cooling demand has been satisfied) can be adjusted by moving switch 5 on the integrated control board. The switch is factory−set in the OFF position, which provides a cooling blower−off delay of 45 seconds. If the switch is toggled to the ON position, it will provide a 2−second cool­ing blower−off delay
On−Board Jumper W951 −− Figure 53
On−board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the fur­nace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the jumper is left intact, terminal O" will remain energized elim­inating the HEAT MODE in the heat pump.
On−Board Jumper W915 −− Figure 53
On−board jumper W915, which connects terminals Y1 and Y2 on the integrated control board, must be cut if two−stage cooling will be used. If the jumper is not cut the outdoor unit will operate in first−stage cooling only.
TABLE 11
Switch 3 Switch 4
Unit Start−Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been under­water. A flood−damaged furnace is extremely dan­gerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified ser­vice technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
Page 42
Page 43
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch.
Priming Condensate Trap
The condensate trap should be primed with water prior to start−up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into op-
eration.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes.
4 − Adjust the thermostat to deactivate the heating de-
mand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al­low the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating de-
mand and again wait for the combustion air inducer to stop. At this point, the trap should be primed with suffi­cient water to ensure proper condensate drain opera­tion.
BEFORE LIGHTING the unit, smell all around the fur­nace area for gas. Be sure to smell next to the floor be­cause some gas is heavier than air and will settle on the floor.
The gas valve on the G61MP will be be equipped with a gas control switch (lever). Use only your hand to move the switch. Never use tools. If the the switch will not move by hand, do not try to repair it. Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
G61MP units are equipped with an automatic ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with this ignition system.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand. 5 − Remove the upper access panel. 6 − White Rodgers 36E Gas Valve − Move gas valve
switch to OFF. See figure 55 for the White Rodgers
36E valve.
Honeywell VR8205 Gas Valve − Move switch on gas
valve clockwise to OFF. Do not force. See figure
56.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.
WHITE RODGERS 36E SERIES GAS VALVE
HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
TAP ON SIDE
INLET PRESSURE
TAP ON SIDE
GAS VALVE SHOWN IN OFF POSITION
LOW FIRE MANIFOLD
PRESSURE ADJUSTMENT
ON SIDE (under cap)
FIGURE 55
HONEYWELL VR8205 SERIES GAS VALVE
HIGH FIRE
ADJUSTING SCREW
(under cap)
MANIFOLD
PRESSURE
TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE TAP
GAS VALVE SHOWN IN OFF POSITION
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figures 55 and 56)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
FIGURE 56
8 − White Rodgers 36E Gas Valve − Move gas valve switch
to ON. See figure 55 for the White Rodgers 36E
valve.
Honeywell VR8205 Gas Valve − Move switch on gas
valve counterclockwise to ON. Do not force. 9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
Page 43
Page 44
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service techni­cian or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the upper access panel.
4 − White Rodgers 36E Gas Valve − Move gas valve
switch to OFF. Honeywell VR8205 Gas Valve − Move switch on gas
valve clockwise to OFF. Do not force.
5 − Replace the upper access panel.
Gas Pressure Adjustment
Gas Flow (Approximate)
1 − Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for one revolu­tions of gas through the meter. A portable LP gas me­ter (17Y44) is available for LP applications.
2 − Compare the number of seconds and the gas meter
size in table 12 to determine the gas flow rate. Multiply the gas flow rate by the heating value to determine the unit input rate. If manifold pressure is correct and the unit input rate is incorrect, check gas orifices for proper size and restriction.
3 − Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. Replace the threaded plug after measurements have been taken.
Manifold Pressure Measurement
To correctly measure manifold pressure, the differential pressure between the positive gas manifold and the nega­tive burner box must be considered. Use pressure test
adapter kit (available as Lennox part 10L34) to assist in measurement.
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting. Connect test gauge +" connection to barbed fitting to measure manifold pressure.
2 − Tee into the gas valve regulator vent hose and connect
test gauge −" connection.
TABLE 12
Gas Flow Rate (Ft.3/Hr.)
Seconds for 1
Revolution
10 180 360 12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 113 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 38 75 50 36 72 52 35 69 54 33 67 56 32 64 58 31 62 60 30 60
3 − Start unit on low heat (68% rate) and allow 5 minutes
for unit to reach steady state.
4 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue.
5 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
13.
6 − Repeat steps 3, 4 and 5 on high heat.
NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.
1/2 cu ft Dial 1 cu ft Dial
Gas Meter Size
CAUTION
Do not attempt to make adjustments to the gas valve.
Page 44
Page 45
TABLE 13
Manifold Pressure (Outlet) inches w.c.
Model Number Fuel
045, 070, 090, 110, 135
Natural 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5
Propane 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0
0−2000 2001−4500 4501−5500 5501−6500 6501−7500 7501−10000
Low Fire
High Fire
Low Fire
Natural 1.7 3.5 1.7 3.4 1.7 3.3 1.7 3.2 1.7 3.1 1.7 3.5
071, 091, 111
Propane 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0 4.9 10.0
High Altitude Information
NOTE − In Canada, certification for installations at eleva­tions over 4500 feet (1372 m) is the jurisdiction of local au­thorities.
The manifold pressure may require adjustment to ensure proper operation at higher altitudes. Refer to table 13 for proper manifold pressure settings at varying altitudes. Refer to table 14 for required pressure switch changes and conversion kits at varying altitudes.
Altitude (feet)
High Fiire
Low Fire
High Fiire
Low Fire
High Fiire
Low Fire
High Fiire
The combustion air pressure switches are factory−set and require no adjustment.
NOTE − A natural to L.P. propane gas changeover kit is nec­essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
Low Fire
High Fiire
TABLE 14
Conversion Kit Requirements
High Altitude
Orifice Kit
Input
−045 44W51 − − − − − − − − − 44W48 44W50 44W49 44W49 + 44W51
−070 44W51 − − − − − − 56M06 44W48 44W50 44W49 44W49 + 44W51
−071 47M82 24W49 24W49 26W83 44W48 44W50 44W49 44W49 + 47M82
−090 44W51 − − − 75M22 56M21 44W48 44W50 44W49 44W49 + 44W51
−091 47M82 26W85 26W85 26W86 44W48 44W50 44W49 44W49 + 47M82
−110 44W51 − − − − − − 75M22 44W48 44W50 44W49 44W49 + 44W51
−111 47M82 56M22 56M22 56M23 44W48 44W50 44W49 44W49 + 47M82
−135 44W51 − − − 56M93 56M93 44W48 44W50 44W49 44W49 + 44W51
1
High Altitude Orifice Kit is required and must be ordered separately for applications from 7501 to 10,000 ft.
Natural Gas
Only
7501−10,000 ft. 2000−4500 ft. 4501−7500 ft. 7501−10,000 ft. 0−7500 ft. 7501−10,000 ft. 0−7500 ft.
High Altitude Pressure Switch Kit
ORDER TWO EACH
LPG/Propane Kit LPG/Propane to
Natural Gas Kit
1
7501−10,000 ft.
Page 45
Page 46
Testing for Proper Venting and Sufficient Combustion Air for Non−Direct Vent Applications
sufficient combustion/make-up air must be provided.
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monox­ide poisoning or death. The following steps shall be followed for each ap­pliance connected to the venting system being placed into operation, while all other appliances con­nected to the venting system are not in operation.
After the G61MP gas furnace has been started, the follow­ing test should be conducted to ensure proper venting and sufficient combustion air has been provided to the G61MP, as well as to other gas-fired appliances which are separate­ly vented.
If a G61MP furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue prod­ucts, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section.
1 − Seal any unused openings in the venting system. 2 − Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re­striction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − To the extent that it is practical, close all building doors
and windows and all doors between the space in which the appliances connected to the venting system are lo-
cated and other spaces of the building. 4 − Close fireplace dampers. 5 − Turn on clothes dryers and any appliances not con-
nected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. 6 − Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously. 7 − Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 min-
utes of main burner operation. 8 − If improper venting is observed during any of the
above tests, the venting system must be corrected or
The venting system should be re-sized to approach the minimum size as determined by using the ap­propriate tables in appendix G in the current standards of the National Fuel Gas Code ANSI−Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and Propane appliances venting sizing tables in the cur­rent standard of the CSA−B149 Natural Gas and Pro­pane Installation Codes in Canada.
9 − After determining that each appliance remaining
connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits are located in the blower compartment, attached to the back side of the blow­er. These limits are factory set and require no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the burner box. If tripped, check for adequate combustion air before resetting.
Pressure Switches (Two or Four)
The pressure switches are located in the heating compart­ment on the combustion air inducer. These switches check for proper combustion air inducer operation before allow­ing ignition trial. The switches are factory−set and require no adjustment.
Back−Up Secondary Limit (090, 110 & 135 Models)
The back−up secondary limit is located on the combustion air inducer. This switch protects the plastic components from overheating due to indoor blower motor failure. If tripped, check for proper blower operation before resetting.
Temperature Rise
After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to do adjust the temperature rise may cause erratic limit operation.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.
Electrical
1 − Check all wiring for loose connections.
Page 46
Page 47
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the air ducts or structure.
Blower Speeds
NOTE − CFM readings are taken external to unit with a dry evaporator coil and without accessories.
1 − Turn off electrical power to furnace. 2 − Remove blower access panel. 3 − Disconnect existing speed tap at control board speed
terminal.
NOTE − Termination of any unused motor leads must be insulated.
4 − Refer to blower speed selection chart on unit wiring dia-
gram for desired heating or cooling speed. See blower performance data beginning on Page 48.
5 − Connect selected speed tap at control board speed
terminal. 6 − Resecure blower access panel. 7 − Turn on electrical power to furnace.
Electronic Ignition
The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re­set device for ignition control lockout caused by ignition fail­ure. This type of lockout is usually due to low gas line pres-
sure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat de­mand to the furnace and automatically reset the control to begin the ignition sequence.
Exhaust and Air Intake Pipe
1 − Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 − Are pressure switches closed? Obstructed exhaust
pipe will cause unit to shut off at pressure switches. Check termination for blockages.
3 − Reset manual flame rollout switches on burner box
cover.
Failure To Operate
If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse? 5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lock out? If the unit locks out
again, inspect the unit for blockages.
Page 47
Page 48
Blower Performance Data
G61MP−36B−045 PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00
0.10 1515 605 1385 555 1190 485 1020 415
0.20 1470
0.30
0.40 1350 535 1250 465 1120 410 980 360
0.50 1290
0.60
0.70 1145 460 1080 400 975 345 860 300
0.80 1050
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided). Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G61MP−36B−070 PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00
0.10 1600 635 1395 550 1160 460 1000 385
0.20 1540
0.30
0.40 1420 545 1275 480 1125 395 965 345
0.50 1360
0.60
0.70 1170 465 1085 385 965 335 860 295
0.80 1080
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided). Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G61MP−36B−071 PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00
0.10 1420 590 1215 545 990 425 815 365
0.20 1365
0.30
0.40 1255 495 1155 455 945 365 795 320
0.50 1190
0.60
0.70 1035 410 975 365 790 295 695 255
0.80 900
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided). Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
Air Volume / Watts at Different Blower Speeds
High
Medium−
High
Medium−
Low
Low
cfm Watts cfm Watts cfm Watts cfm Watts
1555 630 1410 585 1190 520 1030 435
580 1345 520 1170 455 1010 400
1410 555 1310 495 1155 440 1000 385
505 1205 450 1080 390 950 345
1220 485 1145 420 1020 365 905 320
425 985 365 870 320 785 285
945 410 900 345 825 305 730 270
Air Volume / Watts at Different Blower Speeds
High
Medium−
High
Medium−
Low
Low
cfm Watts cfm Watts cfm Watts cfm Watts
1640 660 1415 575 1160 485 1005 410
605 1370 525 1160 445 995 375
1495 580 1345 505 1145 425 990 365
525 1245 450 1080 375 945 325
1275 490 1165 410 1025 350 900 305
440 1010 360 865 310 775 270
945 400 840 320 765 275 710 245
Air Volume / Watts at Different Blower Speeds
High
Medium−
High
Medium−
Low
Low
cfm Watts cfm Watts cfm Watts cfm Watts
1460 620 1215 570 965 445 785 375
550 1195 505 980 410 810 350
1325 525 1170 490 980 390 820 335
465 1080 425 915 345 785 305
1120 440 1050 395 865 320 755 285
375 865 330 715 275 615 235
795 350 745 300 600 245 510 215
G61MP−48C−090 PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00
Air Volume / Watts at Different Blower Speeds
High
Medium−
High
Medium−
Low
Low
cfm Watts cfm Watts cfm Watts cfm Watts
2180 930 1835 790 1520 630 1280 510
0.10 2135 885 1825 750 1510 610 1275 495
0.20 2085 840 1810 720 1505 580 1270 475
0.30 2030 800 1775 685 1500 565 1265 460
0.40 1940 760 1735 650 1480 535 1250 440
0.50 1865 725 1660 600 1430 505 1215 425
0.60 1740 670 1590 575 1380 475 1175 410
0.70 1645 640 1475 520 1290 450 1105 375
0.80 1540
600 1340 465 1175 405 1020 355
0.90 1335 540 1170 440 1070 375 950 330
NOTES − All air data is measured external to unit without filter (not furnished − field provided). Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G61MP−48C−110 PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00
Air Volume / Watts at Different Blower Speeds
High
Medium−
High
Medium−
Low
Low
cfm Watts cfm Watts cfm Watts cfm Watts
2160 880 1880 755 1490 602 1235 485
0.10 2100 850 1855 730 1480 585 1230 475
0.20 2035 805 1815 690 1475 560 1225 460
0.30 1965 750 1755 650 1475 545 1220 445
0.40 1885 725 1715 625 1465 510 1215 430
0.50 1780 680 1630 580 1420 490 1150 400
0.60 1690 660 1550 550 1360 460 111 0 380
0.70 1575 620 1410 505 1210 405 1035 350
0.80 1375 550 1230 450 1125 380 970 325
0.90 1225 520 1120 415 1050 365 885 310
NOTES − All air data is measured external to unit without filter (not furnished − field provided). Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
Page 48
Page 49
G61MP−60C−090 PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High
Medium−
High
Medium−
Low
Low High
Single Side Return Air − Air volumes in bold require field
fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.
Medium−
High
Medium−
Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2840 1450 2345 1105 1895 900 1515 700 2835 1495 2340 1155 1800 895 1440 695
0.10 2765 1415 2365 1080 1950 885 1580 700 2785 1475 2345 1135 1805 865 1515 690
0.20 2695
0.30
1385 2345 1050 1985 870 1620 695 2715 1435 2275 1080 1825 845 1560 685
2605 1335 2315 1030 1990 850 1645 690 2620 1380 2260 1035 1840 825 1600 680
0.40 2530 1300 2265 990 1990 825 1665 675 2550 1350 2230 1015 1845 815 1620 670
0.50 2420
0.60
1260 2210 955 1970 800 1675 665 2450 1305 2175 990 1850 790 1615 655
2330 1220 2145 925 1930 775 1665 650 2365 1270 2130 940 1830 775 1615 640
0.70 2250 1190 2050 885 1875 745 1645 630 2240 1205 2070 915 1815 760 1595 620
0.80 2135
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
2030 1090 1885 830 1720 685 1560 590 2015 1150 1820 820 1690 715 1440 580
1140 2000 865 1810 715 1620 615 2185 1190 1965 865 1775 745 1555 605
G61MP−60C−091 PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High
Medium−
High
Medium−
Low
Low High
Single Side Return Air − Air volumes in bold require field
fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.
Medium−
High
Medium−
Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2320 1230 2240 960 1970 810 1505 690 2350 1275 2195 960 1920 830 1535 680
0.10 2250 1195 2155 910 1950 805 1610 665 2270 1240 2125 930 1910 800 1580 665
0.20 2185
0.30
2060 1120 1965 835 1795 710 1590 620 2070 1135 1945 830 1830 725 1545 625
1165 2080 890 1915 775 1630 660 2200 1190 2060 905 1875 775 1570 655
0.40 1995 1095 1890 805 1720 690 1535 600 1935 1095 1875 815 1750 705 1495 605
0.50 1920
0.60
1060 1860 790 1705 665 1540 580 1910 1070 1820 780 1715 670 1510 585
1800 1025 1750 755 1605 640 1485 560 1825 1050 1720 760 1635 645 1450 555
0.70 1710 1000 1625 735 1500 605 1380 535 1705 1025 1605 725 1485 615 1360 535
0.80 1600
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
1475 940 1405 670 1305 555 1105 450 1460 950 1370 665 1285 555 1175 480
975 1545 700 1455 585 1335 515 1605 995 1515 700 1440 585 1320 510
Low
Low
Page 49
Page 50
Blower Performance Data
G61MP−60C−110 PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High
Medium−
High
Medium−
Low
Low High
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2720 1385 2410 1090 2055 935 1620 710 2625 1350 2310 1080 1885 885 1515 700
0.10 2665 1355 2385 1075 2025 885 1730 735 2570 1330 2325 1060 1910 865 1575 700
0.20 2585
1315 2350 1015 2030 865 1680 690 2410 1305 2285 1035 1930 845 1620 690
0.30 2505 1275 2290 990 2025 840 1695 675 2425 1265 2230 990 1925 825 1635 675
0.40 2435 1250 2235 940 2030 830 1695 660 2335 1220 2175 950 1910 810 1640 660
0.50 2350 1205 2170 930 1975 790 1735 665 2270 1195 2120 935 1895 785 1640 640
0.60 2255 1185 2100 895 1915 765 1720 650 2170 1155 2045 885 1860 765 1630 630
0.70 2160 1150 2005 840 1865 730 1680 635 2110 1130 1950 855 1795 730 1590 610
0.80 2020 1090 1905 825 1810 710 1625 610 2035 1090 1885 820 1745 705 1540 580
0.90 1910 1050 1820 795 1705 675 1540 590 1900 1055 1760 780 1665 680 1470 565
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
G61MP−60C−111 PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High
Medium−
High
Medium−
Low
Low High
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2475 1305 2275 1010 1800 870 1425 680 2460 1355 2210 1045 1850 860 1435 670
0.10 2395 1260 2215 980 1850 850 1495 675 2395 1320 2170 1010 1850 830 1490 660
0.20 2340 1220 2165 945 1860 830 1535 665 2280 1270 2115 965 1875 810 1525 650
0.30 2255 1205 2085 915 1855 805 1545 655 2225 1250 2075 940 1835 785 1530 640
0.40 2165 1160 2000 880 1820 780 1540 645 2150 1210 2005 905 1800 760 1535 626
0.50 2055 1140 1920 845 1780 755 1535 625 2050 1155 1935 885 1760 740 1555 620
0.60
1995 1120 1845 825 1720 725 1485 605 1975 1140 1835 845 1660 705 1480 595
0.70 1880 1075 1760 800 1680 710 1470 595 1870 1110 1745 810 1620 685 1440 575
0.80 1795 1060 1640 755 1595 680 1415 570 1760 1065 1645 770 1510 655 1370 550
0.90 1680 1020 1530 725 1505 645 1345 550 1635 1025 1545 740 1415 620 1295 530
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
Single Side Return Air − Air volumes in bold require field
fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.
Medium−
High
Medium−
Low
Single Side Return Air − Air volumes in bold require field
fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.
Medium−
High
Medium−
Low
Low
Low
Page 50
Page 51
G61MP−60D−135 PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High
Medium−
High
Medium−
Low
Low High
Single Side Return Air − Air volumes in bold require field
fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.
Medium−
High
Medium−
Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2730 1465 2425 1125 2055 915 1560 680 2665 1440 2325 1100 1865 890 1410 690
0.10 2670 1440 2400 1100 2065 890 1590 675 2615 1405 2310 1065 1915 865 1465 685
0.20 2600 1400 2365 1070 2045 865 1620 665 2530 1370 2280 1055 1925 850 1570 675
0.30 2525 1360 2315 1045 2035 845 1615 655 2470 1330 2235 1015 1920 825 1590 670
0.40 2445 1325 2260 1015 2020 820 1615 645 2380 1290 2175 985 1910 805 1590 655
0.50 2360 1280 2195 985 1960 790 1610 635 2310 1265 2120 965 1890 790 1595 645
0.60 2290 1255 2130 965 1900 755 1600 615 2200 1230 2055 935 1835 765 1580 630
0.70 2205 1220 2035 910 1825 730 1570 600 2120 1190 1970 900 1790 740 1545 605
0.80 2110 1195 1945 880 1765 710 1540 580 2025 1160 1890 875 1720 710 1515 590
0.90 1970 1120 1835 830 1680 690 1540 545 1930 1110 1800 835 1655 685 1440 570
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
Low
Page 51
Page 52
Heating Sequence of Operation
NOTE − The thermostat selection DIP switch on the control board is factory−set in the TWO−STAGE" position.
Applications Using a Two−Stage Thermostat A − Heating Sequence −− Control Board Thermostat Selection DIP switch in Two−Stage" Position (Factory Setting)
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low−fire
pressure switch has closed, the combustion air induc­er begins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc­curs. At the same time, the control module sends a sig­nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener­gized on the low fire heating speed. The furnace will continue this operation as long as the thermostat has a first−stage heating demand.
5 − If second−stage heat is required, the thermostat sec-
ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.
6 − At the end of the recognition delay, the integrated con-
trol energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the the control receives a signal that the high−fire pres­sure switch is close, the high−fire (second stage) gas valve is energized and the indoor blower motor is en­ergized for operation at the high−fire heating speed.
7 − When the demand for high−fire (second stage) heat is
satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.
8 − When the thermostat demand for low−fire (first stage)
heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.
9 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Applications Using A Single−Stage Thermostat
B − Heating Sequence −− Control Board Thermostat Selection DIP switch in Single−Stage" Position
NOTE − In these applications, two−stage heat will be initi­ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low−fire
pressure switch has closed, the combustion air induc­er begins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc­curs. At the same time, the control module sends a sig­nal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is ener­gized on the low−fire heating speed. The integrated control also initiates a second−stage on delay (factory− set at 10 minutes; adjustable to 15 minutes).
5 − If the heating demand continues beyond the second−
stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed. Once the control receives a sig­nal the high−fire pressure switch is closed, the high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.
6 − When the thermostat heating demand is satisfied, the-
combustion air inducer begins a 5−second post−purge. The field−selected indoor blower off delay begins.
7 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Page 52
Page 53
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis­connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
All G61MP filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation. Table 3 lists recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage.
NOTE − After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes.
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 − Turn off power to the unit.
2 − Have a shallow pan ready to empty condensate water.
3 − Remove the drain plug from the condensate trap and
empty water. Inspect the trap then reinstall the drain plug.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassem­bling unit. Use papers or protective covering in front of fur­nace while removing heat exchanger assembly.
1 − Turn off electrical and gas supplies to the furnace. 2 − Remove the upper and lower furnace access panels. 3 − Mark all gas valve wires and disconnect them from
valve.
4 − Remove gas supply line connected to gas valve. Re-
move gas valve/manifold assembly.
5 − Remove sensor wire from sensor. Disconnect 2-pin
plug from the ignitor. 6 − Disconnect wires from flame roll−out switches. 7 − Remove burner box cover and remove four burner box
screws at the vestibule panel and remove burner box.
Set burner box assembly aside.
NOTE − G61MP−135 units are secured to the vestibule
panel by two additional screws. These screws must be
removed for servicing; however it is not necessary to
replace the screws.
NOTE − If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
8 − Loosen three clamps and remove flexible exhaust tee. 9 − Remove 3/8 inch rubber cap from condensate drain
plug and drain. Replace cap after draining. 10 − Disconnect condensate drain line from the conden-
sate trap. Remove condensate trap (it may be neces-
sary to cut drain pipe). Remove screws that secure
condensate collars to either side of the furnace and re-
move collars. Remove drain tubes from cold end
header collector box. 11 − Disconnect condensate drain tubing from flue collar.
Remove screws that secure both flue collars into
place. Remove flue collars. It may be necessary to cut
the exiting exhaust pipe for removal of the fittings. 12 − Mark and disconnect all combustion air pressure tub-
ing from cold end header collector box. 13 − Mark and remove wires from pressure switches. Re-
move pressure switches. Keep tubing attached to
pressure switches. 14 − Disconnect the 3-pin plug from the combustion air in-
ducer. Disconnect the two wires to the backup secon-
dary limit, if applicable. Remove four screws which se-
cure combustion air inducer to collector box. Remove
combustion air inducer assembly. Remove ground
wire from vest panel. 15 − Remove electrical junction box from the side of the fur-
nace. 16 − Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck.
Page 53
Page 54
17 − Remove the primary limit from the vestibule panel. 18 − Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow clearance for removal of heat exchanger.
19 − Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as­sembly to cabinet. Remove two screws from blower rail which secure bottom heat exchanger flange. Re­move heat exchanger from furnace cabinet.
20 − Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
21 − Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire assembly.
22 − Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly are resting on the support located at the rear of the cabi­net. Remove the indoor blower to view this area through the blower opening.
23 − Re-secure the supporting screws along the vestibule
sides and bottom to the cabinet.
24 − Reinstall cabinet screws on front flange at blower
deck. 25 − Reinstall the primary limit on the vestibule panel. 26 − Route heating component wiring through hole in blow-
er deck and reinsert strain relief bushing. 27 − Reinstall electrical junction box. 28 − Reinstall the combustion air inducer. Reconnect the
3−pin plug to the wire harness. Reconnect the two
wires to the backup secondary limit, if applicable. 29 − Reinstall pressure switches and reconnect pressure
switch wiring. 30 − Carefully connect combustion air pressure switch
hosing from pressure switches to proper stubs on
cold end header collector box. 31 − Reinstall condensate collars on each side of the fur-
nace. Reconnect drain tubing to collector box. 32 − Reinstall condensate trap on same side as exhaust
pipe. Reconnect condensate drain line to the conden-
sate trap. 33 − Use securing screws to reinstall flue collars to either
side of the furnace. Reconnect exhaust piping and ex-
haust drain tubing. 34 − Replace flexible exhaust tee on combustion air induc-
er and flue collars. Secure using three existing hose
clamps. 35 − Reinstall burner box assembly in vestibule area. 36 − Reconnect flame roll−out switch wires. 37 − Reconnect sensor wire and reconnect 2−pin plug from
ignitor.
38 − Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
39 − Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve.
40 − Reinstall burner box cover. 41 − Reconnect wires to gas valve. 42 − Replace the blower compartment access panel. 43 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies.
44 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is clean and dry and that furnace is operating properly.
45 − Replace heating compartment access panel.
Cleaning the Burner Assembly
1 − Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 − Mark all gas valve wires and disconnect them from the
valve.
3 − Disconnect the gas supply line from the gas valve. Re-
move gas valve/manifold assembly.
4 − Mark and disconnect sensor wire from the sensor. Dis-
connect 2-pin plug from the ignitor at the burner box.
5 − Remove burner box cover and remove four screws
which secure burner box assembly to vest panel. Re­move burner box from the unit.
NOTE − G61MP−135 units are secured to the vestibule panel by two additional screws. These screws must be removed for servicing; however it is not necessary to replace the screws.
6 − Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect the inside of the burners and crossovers for any block­age caused by foreign matter. Remove any blockage.
7 − Reconnect the sensor wire and reconnect the 2−pin
plug to the ignitor wiring harness.
8 − Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the center of the burner ports.
9 − Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn­er box cover.
10 − Reconnect the gas valve wires to the gas valve. 11 − Replace the blower compartment access panel. 12 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies.
13 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is clean and dry and that furnace is operating properly.
14 − Replace heating compartment access panel.
Page 54
Page 55
Planned Service
A service technician should check the following items dur­ing an annual inspection. Power to the unit must be shut off for safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob­structed to provide combustion air.
Return air duct − Must be properly attached and provide an air seal to the unit.
Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.
Combustion gases − Flue products must be analyzed and compared to the unit specifications.
Burners − Must be inspected for rust, dirt, or signs of water.
Vent pipe − Must be inspected for signs of water, damaged,
cracked or sagging pipe, or disconnected joints.
Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door − Must be properly in place and pro­vide a seal between the return air and the room where the furnace is installed.
Problems detected during the inspection may make it nec­essary to temporarily shut down the furnace until the items can be repaired or replaced.
Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace in-
spections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon monoxide gas.
Page 55
Page 56
Ignition Control Board Diagnostic Codes
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
Pulse A 1/4 second flash followed by four seconds of off time.
Heartbeat Constant 1/2 second bright and 1/2 second dim cycles.
X + Y
Pulse Power on − Standby.
Heartbeat Normal operation − signaled when heating demand initiated at thermostat.
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four seconds, then repeats.
FLAME CODES
1 + 2 Low flame current −− run mode.
1 + 3 Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3 Low pressure switch failed open.
2 + 4 Low pressure switch failed closed.
2 + 5 High pressure switch failed open.
2 + 6 High pressure switch failed closed.
2 + 7 Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1 Limit switch open.
WATCHGUARD CODES
4 + 1 Watchguard −− Exceeded maximum number of retries.
4 + 2 Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3 Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5 Watchguard −− Limit remained open longer than three minutes.
4 + 6 Watchguard −− Flame sensed out of sequence; flame signal gone.
4 + 7 Ignitor circuit fault −− Failed ignitor or triggering circuitry.
4 + 8 Low line voltage.
HARD LOCKOUT CODES
5 + 1 Hard lockout −− Rollout circuit open or previously opened.
5 + 2 Control failed self check, internal error (control will restart if error recovers).
5 + 3 No Earth ground (control will restart if error recovers).
5 + 4 Reversed line voltage polarity (control will restart if the error recovers).
5 + 6 Low secondary (24VAC) voltage.
Error Code Storage
The ignition control stores the last ten error codes in memory. The codes are retained in case of power loss.
Error Code Review
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED
will stay lit continuously to indicate that the short was sensed.
2 − Continue to hold the short between R (2) to (1). After 5
seconds, STATUS LED will go from being continuously lit to off. This indicates that error code review is pend­ing.
3 − Remove R (2) to (1) short within ten seconds of STA-
TUS LED turning off. This activates error code review.
4 − Last ten error codes will be flashed on the STATUS
LED.
5 − After final error code is indicated, STATUS LED will
flash to indicate normal operation.
Clearing Error Codes
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED
will stay lit continuously to indicate that the short was sensed.
2 − Continue to hold the short between R (2) to (1). After 5
seconds, STATUS LED will go from being continuously lit to off.
3 − Continue to hold the short between R (2) to (1) beyond
ten seconds after STATUS LED has turned off. STA­TUS LED will turn on, indicating that error codes have been cleared.
4 − Remove R (2) to (1) short. STATUS LED will flash to in-
dicate normal operation.
Page 56
Page 57
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
CONTROL SELF−CHECK OKAY?
NO
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.)
NO
POLARITY OKAY?
YES
IS THERE A
PROPER GROUND?
YES
A
NORMAL OPERATION:
STATUS LED −− PULSE
B
THERMOSTAT CALLS FOR HEAT:
STATUS LED −− HEARTBEAT
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
ROLLOUT SWITCH CLOSED?
YES
FIRST (LOW) STAGE PRESSURE SWITCH
CONTACTS OPEN?
YES
SECOND (HIGH) STAGE PRESSURE SWITCH
CONTACTS OPEN?
YES
NO
NO
NO
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
INDOOR BLOWER ON. HAS PRIMARY OR
SECONDARY LIMIT RESET WITHIN 3 MINUTES?
NO
NO
NO
60−MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS
RESET AND MAIN POWER IS INTERRUPTED OR
T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
POLARITY REVERSED.
STATUS ERROR CODE 5 + 4.
STATUS ERROR CODE 5 + 3.
COMBUSTION AIR INDUCER OFF.
STATUS ERROR CODE 3 + 1.
NO
STATUS ERROR CODE 4 + 5.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1.
STATUS ERROR CODE 2 + 4
YES
NO
YES
TWO−STAGE OR SINGLE−STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
STATUS LED −− HEARTBEAT
CONTINUED ON NEXT PAGE
COMBUSTION AIR INDUCER OFF.
GAS VALVE OFF.
INDOOR BLOWER OFF.
CONTROL WILL NOT ATTEMPT SECOND−STAGE
OPERATION DURING THIS HEAT DEMAND.
FIRST−STAGE OPERATION WILL BE ATTEMPTED.
STATUS ERROR CODE 2 + 6.
Page 57
Page 58
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
THERMOSTAT CALLS FOR HEAT
STATUS LED − HEARTBEAT.
(Refer to box A on previous page)
FIRST−STAGE (LOW FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
YES
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED FIRST−STAGE
PRESSURE SWITCH (or 15 SECOND
INTER−PURGE PERIOD.)
STATUS LED −− HEARTBEAT.
IGNITOR WARM−UP (20 SECONDS)
STATUS LED −− HEARTBEAT.
YES
IS IGNITOR INTACT AND CONNECTED?
YES
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
YES
4−SECOND FLAME STABILIZATION PERIOD.
NO
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
STATUS ERROR CODE 2 + 3.
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED OR
RECONNECTED.
STATUS ERROR CODE 4 + 7.
IS VOLTAGE ABOVE 90 VOLTS?
NO
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95
VOLTS. STATUS ERROR CODE 4 + 8.
YES
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.20 microamps)
FLAME PRESENT?
YES
CONTINUED ON NEXT PAGE
NO
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
STATUS LED −− HEARTBEAT.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
STATUS ERROR CODE 4 + 1.
IS 60−MINUTE RESET PERIOD COMPLETE?
YES
HAS CONTROL RESET IGNITION SEQUENCE
FOUR (4) TIMES?
WATCHGUARD MODE.
STATUS ERROR CODE 4 + 3.
NO
YES
NO
Page 58
Page 59
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
FLAME SIGNAL ABOVE
(u1.40 microamps)
YES
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
YES
START SECOND−STAGE RECOGNITION
ON DELAY (10 OR 15 MINUTES).
STATUS LED −− HEARTBEAT
ROLLOUT SWITCHES CLOSED?
NO
YES
TWO STAGE THERMOSTAT MODE
(DIP SWITCH SET AT TWO")
45−SECOND INDOOR BLOWER ON DELAY BEGINS.
YES
NO
THERMOSTAT CALLS FOR HEAT.
STATUS LED −− HEARTBEAT.
SEE BOX A.
LOW FLAME SIGNAL
(Does not affect control operation)
STATUS ERROR CODE 1 + 2.
YES
STATUS LED −− HEARTBEAT.
YES
PRIMARY & SECONDARY LIMIT SWITCHES
NO
CLOSED?
YES
FIRST−STAGE (LOW FIRE)
PRESSURE SWITCH CLOSED?
YES
NO
FIRST−STAGE HEAT DEMAND SATISFIED?
YES
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
STATUS LED −− PULSE
SECOND−STAGE HEAT DEMAND.
SECOND−STAGE HEAT DEMAND REQUIRED?
YES
SECOND STAGE PRESSURE SWITCH CLOSED?
NOTE − IF SECOND−STAGE PRESSURE SWITCH
SECOND−STAGE 30−SECOND DELAY ON BEGINS.
SECOND−STAGE COMBUSTION AIR INDUCER
ON. SECOND−STAGE GAS VALVE ON. HIGH
SECOND−STAGE PRESSURE SWITCH CLOSED
ABNORMAL FLASH CODE.
WAS ORIGINALLY FOUND CLOSED,
ABNORMAL CODE WILL FLASH.
NO
STATUS LED −− HEARTBEAT.
YES
HEAT INDOOR BLOWER SPEED ON.
STATUS LED −− HEARTBEAT.
YES
IN LESS THAN TEN (10) SECONDS?
STATUS LED −− HEARTBEAT
YES
YES
CONTINUED ON NEXT PAGE
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
YES
NO
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS
UNTIL ROLLOUT SWITCH IS RESET AND MAIN
POWER IS INTERRUPTED OR THERMOSTAT
IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
SWITCH CLOSED WITHIN 3 MINUTES?
(Indoor blower on low speed during 3−minute period)
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
IS 60−MINUTE RESET PERIOD COMPLETE?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF AFTER DELAY.
STATUS ERROR CODE 2 + 3. CONTROL RESTARTS
IGNITION SEQUENCE IF PRESSURE SWITCH
SECOND−STAGE PRESSURE SWITCH CLOSED
RETURNS TO FIRST−STAGE HEAT MODE WHICH
CONTINUES UNTIL SECOND−STAGE PRESSURE
SWITCH CAN BE PROVEN or HEAT DEMAND IS
SATISFIED. FIVE (5) MINUTE WAIT PERIOD
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS
CONTINUES FIRST−STAGE HEATING DEMAND.
WILL NOT REATTEMPT SECOND−STAGE
INDOOR BLOWER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 3 + 1.
HAS PRIMARY OR SECONDARY LIMIT
NO
LIMIT SWITCH WATCHGUARD MODE.
INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5
CLOSES WITHIN 2−1/2 MINUTES.
AT BEGINNING OF HEAT DEMAND?
STATUS ERROR CODE 2 + 6.
SECOND STAGE HEAT DEMAND
STATUS LED −− HEARTBEAT.
NO
MADE FOR SECOND−STAGE HEAT?
YES
HEATING DEMAND.
STATUS ERROR CODE 2 + 5.
YES
YES
YES
NO
Page 59
Page 60
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
NORMAL OPERATION.
SEE BOX A
SECOND−STAGE (HIGH FIRE) HEAT
PRESSURE SWITCH CLOSED?
YES
HEAT DEMAND SATISFIED? STATUS LED −− HEARTBEAT.
YES
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5−SECOND
LOW SPEED POST PURGE PERIOD,
INDOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
STATUS LED −− HEARTBEAT.
RETURN TO FIRST−STAGE HEAT MODE.
FIRST−STAGE CONTINUES UNTIL SECOND−
NO
YES
TWO STAGE THERMOSTAT MODE?
(DIP SWITCH SET AT TWO")
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
STATUS LED −− HEARTBEAT.
STAGE PRESSURE SWITCH CAN BE PROVEN
or HEAT DEMAND IS SATISFIED. A FIVE (5)
MINUTE WAIT PERIOD IS INITIATED BEFORE
YES
THERMOSTAT CALLS FOR HEAT.
RETRY. WERE 5 ATTEMPTS MADE FOR
FIRST−STAGE HEAT DEMAND SATISFIED?
SEE BOX B
SECOND−STAGE HEAT?
NO
SEE BOX C
SECOND STAGE HEAT
NO
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST−
STATUS LED −− HEARTBEAT.
DEMAND SASTISFIED?
STATUS LED −− HEARTBEAT.
YES
STAGE OPERATION.
YES
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY.
STATUS LED −− PULSE.
FIRST STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5−SECOND LOW SPEED POST−
PURGE PERIOD. INDOOR BLOWER OFF. DELAY INITIATED ON LOW HEAT SPEED.
STATUS LED −− PULSE.
YES
Page 60
Page 61
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
POWER ON
YES
IS POLARITY REVERSED?
NO
CONTROL WILL CONTINUE TO CALL FOR COOLING
SIGNAL POLARITY REVERSED.
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.
IS THERE
PROPER GROUND?
YES
THERMOSTAT CALLS FOR FIRST−STAGE COOL.
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
INDOOR BLOWER ENERGIZED ON FIRST STAGE
COOL SPEED AFTER 2 SECOND DELAY.
FIRST−STAGE DEMAND FOR COOL SATISFIED?
NO
THERMOSTAT CALLS FOR SECOND−STAGE COOL.
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
NO
YES
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 3.
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
INDOOR BLOWER DE−ENEGIZED.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
Page 61
Page 62
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
YES YES
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
AFTER 45−SECOND DELAY, INDOOR BLOWER
YES
SWITCHES TO LOW HEAT SPEED.
YES
FIRST−STAGE COOL DEMAND SATISFIED?
NO
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
SECOND STAGE COOL DEMAND SATISFIED?
YES
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
FIRST−STAGE HEAT DEMAND SATISFIED.
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
YES
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
YES
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate −− Example: G61MP−36B−045−1. All service must be performed by a licensed pro-
fessional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel
Blower access panel
Top Cap
Control Panel Parts
Transformer
Two−stage integrated control board
Door interlock switch
Circuit Breaker
Blower Parts
Blower wheel
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure switches Ignitor Primary limit control Secondary limit control Flame rollout switches Combustion air inducer auxiliary limit
Page 62
Page 63
Vent Pipe Sizing Worksheet
Step 1 Step 2
Proposed vent pipe size : ______ Termination kit catalog number : _____________
Equivalent Feet
Vent pipe equivalency value from table 5 : ______
Step 3
Total number of 90° elbows required (indoors and outdoors) ______ X 5 = ______ equivalent feet of pipe
Step 4
Total number of 45° elbows required (indoors and outdoors) ______ X 2.5 = ______ equivalent feet of pipe
Step 5
Step 6
Linear feet of straight pipe required : ______
Add equivalent feet of vent pipe listed in
TOTAL
steps 2 through 5.
If the total is equal to, or less than, the allowable maximum given in table 6, the proposed pipe size is acceptable. If the total exceeds the maximum allowed vent pipe length, repeat the process above using the next larger diameter pipe until an acceptable total is achieved.
NOTE − In Direct Vent systems, total the equivalent length of either the exhaust OR intake piping run, depending upon which will be LONGER. Intake and exhaust pipe diameter must be the same size and must be terminated in the same pressure zone. Intake and exhaust pipe should be roughly the same length.
G61MP Start−Up & Performance Check List
Job Name
Job No.
Date
Job Location
Installer
Unit Model No.
Serial No.
City
City
Technician
Heating Section
Electrical Connections Tight?
Line Voltage
Blower Motor Amps
Fuel Type: Natural Gas?
Furnace Btu Input (High fire) Line Pressure
Low Fire Manifold Pressure
High Fire Manifold Pressure
Flue Connections Tight?
Combustion Gas Tested (high fire and low fire)?
Blower ON delay confirmed?
(45 Seconds Fixed On)
Blower OFF Delay Setting (60, 90, 120 or 180)?
LP/Propane Gas?
w.c. − Nat.:
w.c. − Nat.:
Blower Motor H.P.
Gas Piping Connections Tight & Leak−Tested?
w.c. − LP/Propane
w.c. − LP/Propane
Proper Draft?
CO
2
External Static Pressure? (0.5 maximum)
Temperature Rise
State
State
CO
Filter Clean & Secure?
Thermostat
Heat Anticipator Setting? Thermostat Level?
Page 63
Page 64
Requirements for Commonwealth of Massachusetts
Modifications to NFPA−54, Chapter 10
Revise NFPA−54 section 10.8.3 to add the following re­quirements:
For all side wall, horizontally vented, gas−fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the finished grade in the area of the venting, in­cluding but not limited to decks and porches, the following requirements shall be satisfied:
1 − INSTALLATION OF CARBON MONOXIDE DETEC-
TORS. At the time of installation of the side wall, hori-
zontally vented, gas−fueled equipment, the installing
plumber or gasfitter shall observe that a hard−wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery−oper-
ated or hard−wired carbon monoxide detector with an
alarm is installed on each additional level of the dwell-
ing, building or structure served by the side wall, hori-
zontally vented, gas−fueled equipment. It shall be the
responsibility of the property owner to secure the ser-
vices of qualified licensed professionals for the instal-
lation of hard−wired carbon monoxide detectors.
a − In the event that the side wall, horizontally vented,
gas−fueled equipment is installed in a crawl space or an attic, the hard−wired carbon monoxide detec­tor with alarm and battery back−up may be installed on the next adjacent floor level.
b − In the event that the requirements of this subdivi-
sion cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery−operated carbon monoxide detec­tor with an alarm shall be installed.
2 − APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certi-
fied.
3 − SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade di-
rectly in line with the exhaust vent terminal for the hori-
zontally vented, gas−fueled heating appliance or
equipment. The sign shall read, in print size no less
than one−half (1/2) inch in size, GAS VENT DIRECT-
LY BELOW. KEEP CLEAR OF ALL OBSTRUC-
TIONS."
4 − INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas−fueled equipment shall not approve the installation unless, upon inspec­tion, the inspector observes carbon monoxide detec­tors and signage installed in accordance with the pro­visions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:
1 − The equipment listed in Chapter 10 entitled Equip-
ment Not Required to Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2 − Product Approved side wall, horizontally vented, gas−
fueled equipment installed in a room or structure sepa­rate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment provides a vent­ing system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1 − Detailed instructions for the installation of the venting
system design or the venting system components: and
2 − A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment does not pro­vide the parts for venting the flue gases, but identifies spe­cial venting systems," the following requirements shall be satisfied by the manufacturer:
1 − The referenced special venting system" instructions
shall be included with the appliance or equipment installation instructions; and
2 The special venting systems" shall be Product Ap-
proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall, horizontally vented, gas−fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc­tions shall remain with the appliance or equipment at the completion of the installation.
Page 64
Loading...