Lennox G61MP-60C-090, G61MP-36B-070, G61MP-60C-091, G61MP-48C-110, G61MP-60C-110 Installation Instructions Manual

...
INSTALLATION
E 2009 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
INSTRUCTIONS
G61MP SERIES UNITS
GAS UNITS
506406−01 08/2009
Supersedes 505,124M
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G61MP Parts Identification 3. . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as Construction Heater 5. . . . . . . . . . .
General 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 6. . . . . . . . . . . .
Installation − Setting Equipment 8. . . . . . . . . . . . . . . . . .
Filters 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe & Fittings Specifications 16. . . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 18. . . . . . . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 20. . . . . . . . . . . . . . . . . . . . .
Venting Practices 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board 42. . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 44. . . . . . . . . . . . . . . . . . . . . .
High Altitude Information 45. . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 46. . . . . . . . . . . . . . . . . . . . . . . . .
Service 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ignition Control Board Diagnostic Codes 56. . . . . . . . . .
Troubleshooting 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Pipe Sizing Worksheet 63. . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 63. . . . . . . . . . . . . .
Litho U.S.A.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
08/09
*2P0809*
WARNING
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately. D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
Page 1
*P506406-01*
506406−01
G61MP Unit Dimensions − inches (mm)
*NOTE − 60C and 60D size units installed in upflow ap­plications that require air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. Required to maintain proper air velocity.
2. Single side return air with optional RAB Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
Refer to Engineering Handbook for additional information.
**Consider sizing requirements for optional IAQ equip­ment before cutting side return opening.
1
Optional External Side Return Air Filter Kit is not for use
with the optional RAB Return Air Base.
3/4 (19)
one side return air.
A
B 9/16 (14)
11−5/8 (295)
Right
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
9−3/4 (248)
Left
40
(1016)
14−3/4
(375)
16
(406)
AIR FLOW
5/8 (16)
C
*Bottom Return
Air Opening
3/4 (19)
FRONT VIEW SIDE VIEW
1
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
5−1/2 (140)
6−1/2 (165)
4−1/8 (103)
6−3/4 (171)
4−7/8 (124) Right
2−1/4 (57) Left
2−1/2
(64)
18-3/4 (476)
6−1/2 (165)
3−1/8
(79)
4
(102)
4−1/4 (108)
SUPPLY AIR
OPENING
23-3/4 (603)
25 (635)
TOP VIEW
28−1/2
(724)
19−7/16
(378)
COMBUSTION AIR INTAKE
(Either Side)
EXHAUST AIR OUTLET
(Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
ELECTRICAL INLET
(Either Side)
23
(584)
*OPTIONAL
RETURN CUTOUT
(Either Side)
1−15/16 (49)
23−1/2
(597)
*Bottom Return
Air Opening
9/16
(14)
14**
(356)
Model No.
G61MP−36B−045 G61MP−36B−070 G61MP−36B−071
G61MP−48C−090 G61MP−60C−090 G61MP−60C−091 G61MP−48C−110 G61MP−60C−110 G61MP−60C−111
G61MP−60D−135 24−1/2 622 23−3/8 546 23 584
in. mm in. mm in. mm
17−1/2 446 16−3/8 416 16 406
21 533 19−7/8 505 19−1/2 495
A B C
Page 2
G61MP Parts Arrangement
G61MP PARTS IDENTIFICATION
TOP CAP
BURNER BOX
ASSEMBLY
GAS VALVE
AND MANIFOLD
FLUE
COLLAR
COMBUSTION
AIR PRESSURE
PROVE SWITCHES*
COMBUSTION AIR
INDUCER
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
CABINET
WARM HEADER
(COLLECTOR)
BOX
CONDENSER COIL
BURNER ACCESS
PANEL
BLOWER
ACCESS
DOOR
*G61MP−090 shown.
G61MP−045 and −070
are equipped with
two switches.
SIGHT
GLASS
DOOR
INTERLOCK
SWITCH
PRIMARY LIMIT
COLD HEADER
(COLLECTOR)
BOX
SECONDARY
LIMITS (2)
BLOWER
ASSEMBLY
CONTROL BOX
FIGURE 1
Page 3
G61MP Gas Furnace
The G61MP category IV gas furnace is shipped ready for installation in the upflow, downflow, horizontal left air dis­charge or horizontal right air discharge position. The fur­nace is shipped with the bottom panel in place. The bot­tom panel must be removed if the unit is to be installed in upflow applications with bottom return air. The bottom panel must also be removed and discarded in all downflow or horizontal applications.
The furnace is equipped for installation in natural gas ap­plications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
The G61MP can be installed as either a Direct Vent or a Non−Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination.
DIRECT VENT INSTALLATION NON−DIRECT VENT
COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
EXHAUST OUTLET
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
NOTE − G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 units also include a 2" diameter PVC street elbow, which is shipped on the blower deck in the heating compartment. G61MP−60D−135 units are shipped with a 3" to 2" PVC reducing elbow.
Canadian Installations Only − Replace the provided 2" street elbow shipped with the G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 units with 2" street elbow Y0162. Replace the provided 3" X 2" reducing elbow shipped with the G61MP−60D−135 units with 3" X 2" reduc­ing elbow 40W22. Y0162 and 40W22 meet B149 vent re­quirements.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
The following items may also be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
Safety Information
G61MP
CONDENSATE
CONDENSATE
DRAIN
G61MP
FIGURE 2
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G61MP unit 1 − Bag assembly containing the following:
3 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 2 − 2" diameter vent / intake plugs 1 − 3" diameter cabinet plug (intake) 1 − 2" diameter debris screen 1 − Logo sticker (for use in downflow applications)
DRAIN
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
G61MP units are CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
In the USA, installation of gas furnaces must conform with lo­cal building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
Page 4
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
In order to ensure proper unit operation in non−direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figures 8, 13 and 17. Accessi­bility and service clearances must take precedence over fire protection clearances.
NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code or CSA B149 standard.
NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation.
This G61MP furnace may be used as a high−static unit heater. The G61MP may also be installed in an aircraft han­gar in accordance with the Standard for Aircraft Hangars (ANSI/NFPA No. 408−1990).
Installation in parking structures must be in accordance with the Standard for Parking Structures (ANSI/NFPA No. 88A−1991). Installation in repair garages must be in accor­dance with the Standard for Repair Garages (ANSI/NFPA No. 88B−1991).
This G61MP furnace must be installed so that its electrical components are protected from water.
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually oper­ated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit­tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The G61MP furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms.
This furnace design has not been CSA certified for installa­tion in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of G61MP units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
G61MP units may be used for heating of buildings or struc­tures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
Page 5
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
CAUTION
G61MP unit should not be installed in areas normally subject to freezing temperatures.
Combustion, Dilution & Ventilation Air
If the G61MP is installed as a Non−Direct Vent Fur­nace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a G61MP furnace:
Place the furnace as close to the center of the air dis­tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
When the furnace is installed in non−direct vent applica­tions, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
When the furnace is installed in non−direct vent applica­tions, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insu­lated space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De−icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, ap­pliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combus­tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a po­tentially dangerous situation.
In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install G61MP furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas pip­ing. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI−
Page 6
Z223.1/NFPA 54). This reprinted material is not the com­plete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Canada, refer to the standard CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliance will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex­haust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 3.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED EX-
HAUST PIPE (ALTER-
NATE LOCATION)
NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm rating of all equipment in the enclosure, but not less than 100 square inches (64516mm.
G61MP
2
2).
(To Adjacent
Unconfined
Space)
per .29kW) per hour of the total input
FIGURE 3
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space shall be provided with two perma­nent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a mini­mum free area of 1 square inch per 4,000 Btu (645mm per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a mini­mum free area of 1 square inch per 2,000 Btu (645mm per .59kW) per total input rating of all equipment in the en­closure (See figure 4).
2
2
Page 7
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
VENTILATION
LOUVERS
(For unheated
crawl space)
2
per 1.17kW) per
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
G61MP
INLET
AIR
FIGURE 4
in the enclosure. See figures 4 and 5. When communicat­ing with the outdoors through horizontal ducts, each open­ing shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 6.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm of the total input rating of all equipment in the enclosure.
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
G61MP
2
per 1.17kW) per hour
INLET AIR
(Ends 12" above
bottom)
FIGURE 5
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indi­rectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm hour of the total input rating of all other equipment in the enclosure.
G61MP
2
per .59kW) per hour of the total
INLET AIR
2
per 1.17kW) per
FIGURE 6
Installation − Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front].
Page 8
SETTING EQUIPMENT
UPFLOW APPLICATION DOWNFLOW APPLICATION
AIR FLOW
UNIT MUST BE LEVEL SIDE−TO−SIDE IN ALL APPLICATIONS.
AIR FLOW
HORIZONTAL APPLICATION
AIR FLOW
UNIT
FRONT
FRONT VIEW
AIR FLOW
SIDE VIEW
UNIT
FRONT
1/2"
max.
UNIT SHOULD BE LEVEL FROM LEFT TO RIGHT BUT MAY BE
TILTED SLIGHTLY (MAX. 1/2") FROM BACK TO FRONT TO AID IN THE DRAINING OF THE HEAT EXCHANGER.
FRONT VIEW
The unit must be level from side to side. The unit may be tilted slightly (maximum 1/2 in.) from back to front to aid in the draining of the heat exchanger. See figure 7.
NOTE − Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic wash­er (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be re- moved before the furnace is placed into operation. Af­ter the bolt and washer have been removed, the rigid leg will not touch the blower housing.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
END VIEW
FIGURE 7
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figures 8, 13 and 17.
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
1/2"
max.
FRONT VIEW
AIR FLOW
UNIT
FRONT
SIDE VIEW
WARNING
1/2"
max.
Page 9
Upflow Applications
The G61MP gas furnace can be installed as shipped in the upflow position. Refer to figure 8 for clearances.
Installation Clearances
Top
Left Side
Bottom (Floor)
Top/Plenum 1 in. (25 mm)
*Front 0
Back 0
Sides 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. Allow proper clearances to accommodate condensate trap and vent pipe installation. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 8
Right Side
Return Air −− Upflow Units
Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 1800 cfm (850 L/s) are required with 60C or 60D models in an upflow applica­tion, the following return air options are available:
1 − Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. (Required to maintain proper air velocity.) See figure 10.
2 − Return air from single side with optional RAB Return
Air Base. See figure 9.
3 − Return air from bottom.
4 − Return air from both sides.
5 − Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
Page 10
(Upflow Applications Only −− For use with B, C and D cabinets only)
AIR FLOW
FURNACE
7−1/4 (184)
Optional Return Air Base
4
(102)
14
(356)
FRONT
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8 (143)
SIDE RETURN
AIR OPENINGS
(Either Side)
1
Minimum 11 (279)
2
Maximum
14 (356)
1
22−7−16
(570)
Overall
(Maximum)
17−1/2 (446) RAB−B (98M60)
21 (533) RAB−C (98M58)
24−1/2 (622) RAB−D (98M59)
OPTIONAL RAB
RETURN AIR BASE
7/8
(22)
23 (584)
27−5/8 (702)
SIDE VIEW
FRONT VIEW
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
FIGURE 9
G61MP applications which include side return air and a condensate trap installed on the same side of the cabinet require either a return air base or field−fabri­cated transition to accommodate an optional IAQ ac­cessory taller than 14.2".
Side Return Air
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 11.
Removing the Bottom Panel
Removing the Bottom Panel
(with transition and filter)
3/4
(19)
20" X 25" X 1"
(508mm X635mm X 25mm)
Return
Air
Plenum
Transition
FIGURE 10
Air Filter
Screw
Bottom Cap
Bottom Panel
FIGURE 11
Page 11
Setting an Upflow Unit
When the side return air inlets are used in an upflow ap­plication, it may be necessary to install leveling bolts on the bottom of the furnace. Use field−supplied corrosion−resist­ant 5/16 inch machine bolts (4) and nuts (8). See figure 12.
NOTE − The maximum length of the bolt is 1−1/2 inches.
1 − Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace’s bottom. See fig­ure 12 for the correct location of the holes. Drill through the bottom panel and the bottom flange of the cabinet.
2 − Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole. A flat washer may be added between the nut and the bot­tom of the unit.
3 − Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the nut and the bottom of the unit.
4 − Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement.
NOTE − The unit may be tilted back−to−front a maximum of 1". This will ensure proper draining of the heat exchanger.
Leveling Bolt Installation
Inches (mm)
3/8
(10)
Furnace Front
3/8
(10)
1−3/4
(44)
Furnace
1−3/4
(44)
Leveling Bolt
Locations
Bottom
Leveling Bolt
Locations
3/8
(10)
1−3/4
(44)
1−3/4 (44)
3/8
(10)
FIGURE 12
Downflow Applications
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling cabi­net. Do not drag the unit across the floor in the down-
flow position. Flange damage will result.
After unit has been properly set in place, position provided logo over existing logo and affix sticker on front panel.
Refer to figure 13 for clearances in downflow applica­tions.
Downflow Application Installation Clearances
Top
Left Side
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional additive base is installed between the furnace and the com­bustible floor.
Right Side
FIGURE 13
Installation on Non−Combustible Flooring
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Model No.
B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422
C Cabinet (21") 19 − 3/4 502 20−1/8 511
D Cabinet (24.5") 19 − 3/4 502 23 − 5/8 600
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Front to Rear Side to Side
in. mm in. mm
Page 12
Installation on Combustible Flooring
(Using an Additive Base)
1 − When unit is installed on a combustible floor, an addi-
tive base must be installed between the furnace and the floor. The base must be ordered separately. See table 2 for opening size to cut in floor.
CAUTION
The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma­terial other than wood flooring.
TABLE 2
ADDITIVE BASE FLOOR OPENING SIZE
Cabinet
Width
B Cabinet
(17.5")
C Cabinet
(21")
D Cabinet
(24.5")
Catalog
Number
11M60
11M61
11M62
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 − Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
22 559 22 − 3/4 578
22 559 25 − 3/4 654
Installation on Cooling Coil Cabinet
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position.The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 15 or 16).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP (Field Provided)
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
Side View
G61MP UNIT
PROPERLY
SIZED FLOOR
OPENING
FIGURE 14
SUPPLY AIR PLENUM
ADDITIVE BASE
Page 13
PLENUM
(Field Provided)
SECURE FROM
INSIDE CABINET
FIGURE 15
SEALING STRIP (Field Provided)
CABINET
SIDE PANEL
Side View
FIGURE 16
Horizontal Applications
The G61MP furnace can be installed in horizontal applica­tions with either right− or left−hand air discharge.
The G61MP may also be installed as a unit heater. Either suspend the furnace as shown in figure 18, or install the furnace on a field−fabricated raised platform. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
Refer to figure 17 for clearances in horizontal applications.
Horizontal Application
Installation Clearances
Right−Hand Discharge
Top
Left End Right End
Bottom (Floor)**
Left−Hand Discharge
Top
3 − If unit is installed above finished space, fabricate a
drain pan fitted with a 1/2 inch or 3/4 inch N.P.T. fitting.
4 − Using 3/8 inch rods and support frame kit or field−fabri-
cated supports, fabricate suspension hangers, keep­ing in mind front service access clearances.
5 − Mount unit on support frame as shown in figure 18.
6 − Continue with exhaust, condensate and intake line
piping instructions.
7 − If unit is suspended above finished space, hang the
field−provided drain pan below the support frame as shown in figure 18. Leave 5−1/2 inches for service clearance below unit for condensate trap.
8 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner. If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
TYPICAL HORIZONTAL CEILING APPLICATION
Left End Right End
Bottom (Floor)**
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. **A 5−1/2 service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
FIGURE 17
Suspended Installation of Horizontal Unit
NOTE − If unit is suspended in attic or crawl space, horizon­tal support kit (Cat No. 56J18 ordered separately) must be used to ensure proper unit support and coil drainage.
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
2 − Provide service platform in front of unit.
BLOWER ACCESS PANEL 3/8 in. RODS
INTAKE/EXHAUST
CONNECTION
SUPPORT FRAME
DRAIN PAN
(to protect finished space)
FIGURE 18
Platform Installation of Horizontal Unit
1 − Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
2 − Construct a raised wooden frame and cover frame
with a plywood sheet. Provide a service platform in front of unit. If unit is installed above finished space, fabricate a drain pan to be installed under unit. When installing the unit in a crawl space, a proper sup­port platform may be created using cement blocks and the horizontal support frame kit (ordered separately,
Page 14
Lennox part number 56J18). Position the support frame on top of the blocks and install the unit on the frame. Leave 5−1/2 inches for service clearance for condensate trap.
3 − Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner. If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
4 − Set unit in drain pan as shown in figure 19. Leave 5−1/2
inches for service clearance below unit for condensate trap.
5 − Continue with exhaust, condensate and intake piping
installation according to instructions.
EXHAUST PIPE
INTAKE PIPE
*GAS
CONNECTOR
Unit Heater Discharge Duct Guidelines
A field−fabricated and installed discharge air duct and grille cabinet is suitable for use with the G61MP heater. Keep the following items in mind when constructing the cabinet.
1 − Outer dimensions of cabinet should match those of the
unit heater, so the duct/grille cabinet installs flush with the unit heater cabinet. See figure 20.
2 − Flange both ends of duct/grille cabinet so that screws
can be used to secure cabinet to discharge end of unit heater.
3 − To ensure proper operation, the duct/grille cabinet
must be at least 18 inches long.
4 − Use #10−16 x 1/2 inch sheet metal screws to secure
duct/grille cabinet to unit, taking care not to damage in­ternal components of unit heater when drilling holes or installing screws. See figure 20.
5 − Use adjustable, double−deflection grille(s) to distribute
discharge air. Adjust static pressure to be in the 0.06 inch to 0.10 inch w.c. range.
*Gas connector may be used for Canadian installation if accept­able by local authority having jurisdiction.
RAISED
PLATFORM
CONDENSATE LINE
SERVICE PLATFORM
FIGURE 19
G61MP Installed in Unit Heater Applications
The G61MP may also be installed as a unit heater. Either suspend the furnace from roof rafters or floor joists, as shown in figure 18, or install the furnace on a field−fabri­cated raised platform, as shown in figure 19. The unit must be supported at both ends and beneath the blower deck to prevent sagging. The condensate trap must be installed where it can be serviced at a later date.
18 in.
MIN.
DRAIN PAN
(to protect
finished
space)
NOTE − When installing duct/grille cabinet, take care not to damage internal unit
heater components when drilling holes or installing screws.
FIGURE 20
Return Air −− Horizontal Applications
Return air may be brought in only through the end of a fur­nace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 11.
Page 15
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended filter sizes. A filter must be in place whenever the unit is operating.
TABLE 3
Furnace
Cabinet Width
17−1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24−1/2" 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Operation of this furnace in heating mode (indoor blower operating at selected heating speed) with an exter­nal static pressure which exceeds 0.5 inches w.c. may re­sult in erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (by reflected light) of the heat exchanger for leaks after the furnace is installed. If present, this access panel must al­ways be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled ap­pliance (i.e., water heater), or carbon monoxide− producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pres­sure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan­dards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that ad­versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica­tion, or separation that cannot be removed by stirring. Re­fer to the table 4 for approved piping and fitting materials.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
PIPING AND FITTINGS SPECIFICATIONS
PIPE & FITTING MATERIAL
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fit­tings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
TABLE 4
ASTM
SPECIFICATION
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235,
F493
D3138
MARKING
ULCS636
Page 16
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alter­nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi­als. Use transition solvent cement when bonding ABS to ei­ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers. Uni­formly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fit­ting and male end of pipe to depth of fitting socket.
TABLE 5
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
Vent Pipe Length Equivalency (feet)
Outdoor Ex­haust Accel-
erator
(Dia. X
Length)
UNIT
MODEL
VENT
PIPE
DIA.
(in.)
1−1/2" X 12"
2 4
2−1/2 5
36B−045
36B−070 36B−071
48C−090 60C−090 60C−091
48C−110 60C−110 60C−111
60D−135
3 7
4 14
2 4
2−1/2 5
3 8
4 14
2
2−1/2
3
4
2−1/2
3
4
3
4
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
*Requires field−provided and installed 1−1/2" exhaust accelerator. **Requires field−provided and installed 2" exhaust accelerator.
Outdoor Ex-
haust Accel-
erator
(Dia. X
Length)
2" X 12"
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
1
2
2
4
2
2
4
6
10
1−1/2"
Concentric
Kit
71M80
or 44W92
12
15
21
42
12
15
24
42
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap­pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex­haust) system. When bonding the vent system to the fur­nace, use ULC S636 approved One−Step Transition Ce­ment to bond the pipe to the flue collar, or to bond the 90° elbow or reducing 90° elbow to the flue collar. In addi­tion, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 5 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when siz­ing vent pipe. All Lennox vent terminations are PVC.
2" Con-
centric Kit
69M29
or 44W92
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
3 3
6 6
6 6
12 12
6 6
6 6
12 12
Not
Allowed
Not
Allowed
 Termination kits 44W92 (includes 1−1/2" reducer), 44W93, 30G28 and 81J20 approved for use in Canadian installations.
3" Con-
centric Kit
60L46
or 44W93
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
15
25
2" Wall Plate
Kit
22G44
or 30G28
4 4* 4
5 5* 5
7 7* 7
14 14* 14
4 4* 4
5 5* 5
8 8* 8
14 14* 14
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
3" Wall Plate
Kit
44J40
or 81J20
1 1**
2 2**
2 2**
4 4**
2 2
2 2
4 4
6
10
2" Wall
Ring Kit
15F74
Not
Allowed
Not
Allowed
Page 17
Vent Piping Guidelines
The G61MP can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing in Direct Vent applications and exhaust pipe sizing in Non-Direct Vent applications −− Size pipe according to tables 6 and 7. Table 6 lists the mini­mum equivalent vent pipe lengths permitted. Table 7 lists the maximum equivalent pipe lengths permitted.
Maximum vent length is defined as:
Total length (linear feet) of pipe,
Plus Equivalent length (feet) of fittings, Plus Equivalent length (feet) of termination. NOTE − Include ALL pipe and ALL fittings, both in doors and outdoors.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8.
*NOTE − The exhaust pipe should be offset a minimum of 12 inches to avoid the possibility of water droplets being re-
leased from the exhaust termination. The minimum ex­haust vent length is 15 ft. Shorter exhaust vent lengths may result in the discharge of water droplets from the exhaust termination, in spite of the 12−inch vertical offset. See fig­ure 21.
Each 90° elbow (including those provided with the furnace) of any diameter is equivalent to 5 feet (1.52m) of vent pipe of the same diameter. Two 45° elbows are equivalent to one 90° elbow of the same diameter. One 45° elbow is equal to 2.5 feet (.76m) of vent pipe of the same diameter.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact the Application Department for assistance in sizing vent pipe in these applications.
NOTE − The flue collar on all models is sized to accommo­date 2" Schedule 40 flue pipe. When vent pipe which is larger than 2" must be used in an upflow application, a 2" elbow must be applied at the flue collar in order to proper­ly transition to the larger diameter flue pipe. This elbow must be added to the elbow count used to determine ac­ceptable vent lengths. Assign an equivalent feet value to this elbow according to the larger size pipe being used. Contact Lennox’ Application Department for more infor­mation concerning sizing of vent systems which include multiple pipe sizes.
*12" Min.
Upflow and Downflow Application
Rooftop Termination
*12" Min.
Horizontal Application
Rooftop Termination
*A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage
Exhaust Pipe Offset
12" Min.
Upflow and Downflow Application
Side Wall Termination
*12" Min.
Horizontal Application
Side Wall Termination
FIGURE 21
Page 18
Use the following steps to correctly size vent pipe diameter.
Refer to Vent Pipe Size Determination Worksheet on page 53.
1 − Determine the vent termination and its corresponding
equivalent feet value according to table 5.
2 − Determine the number of 90° elbows required for both
indoor and outdoor (e.g. snow riser) use. Calculate the corresponding equivalent feet of vent pipe.
3 − Determine the number of 45° elbows required for both
indoor and outdoor use. Calculate the corresponding equivalent feet of vent pipe.
4 − Determine the length of straight pipe required.
5 − Add the total equivalent feet calculated in steps 1
through 4 and compare that length to the maximum values given in table 6 for the proposed vent pipe di­ameter. If the total equivalent length required exceeds the maximum equivalent length listed in the appropri­ate table, evaluate the next larger size pipe.
TABLE 6
MINIMUM VENT PIPE LENGTHS
G61MP
MODEL
045, 070, 071, 090,
091
110, 111**
135***
*Any approved termination may be added to the minimum equivalent length listed.
**G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 must have 90° street ell (supplied or field replacment Canadian kit) installed directly into unit flue collar.
***G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replac­ment Canadian ki) installed directly into unit flue collar.
MIN. EQUIV.
VENT LENGTH
15 ft.*
EXAMPLE
5 ft. plus 2 elbows of 2", 2−1/2", 3"
or 4" diameter pipe
5 ft. plus 2 elbows of 2−1/2" 3" or 4"
diameter pipe
5 ft. plus 2 elbows of 3" or 4"
diameter pipe
MAXIMUM VENT PIPE LENGTHS
TABLE 7
MAXIMUM EQUIVALENT VENT
ALTITUDE
0 − 4500
(0 − 1371 m)
4501−7500
(1372−2286 m)
7501 − 10000
(2287 − 3048 m)
n/a −− Not allowed. *G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111must have 90°
street ell (supplied or field replacment Canadian ki) installed directly into unit flue collar.
**G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replacment Canadian ki) installed directly into unit flue collar.
***90° elbows used in configuration of G61MP−60D−135 vent, must be lim­ited to 3" sweep elbows.
†On G61MP−071, −091 and −111 units, sweep elbows must be used for all 90° elbows in the venting system when 2", 2−1/2" or 3" vent pipe is used. Sweep elbows are recommended for use in vent systems of other G61MP units.
G61MP
MODEL
045 59 65 77 234 070 59 65 78 214
071† 59 65 78 214
090 26 42 72 204 091† 26 42 72 204 110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 61 160
045 59 65 77 234
070 59 65 78 214 071† 59 65 78 214
090 26 42 72 204 091† 26 42 72 204 110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 46 160
045 59 65 77 234
070 59 65 78 214 071† 59 65 78 214
090 26 42 72 204 091† 26 42 72 204 110* n/a 32 72 179
111*† n/a 32 72 179
135**‡ n/a n/a 46 160
2"
PIPE
LENGTH FEET
2−1/2"
PIPE
PIPE4"PIPE
3"
Page 19
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
WARNING
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
NOTE − Furnace flue collar and air inlet fitting are both made of ABS material. Use transition solvent cement when bonding ABS to either PVC or CPVC, refer to the procedure specified in ASTM D3138..
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur­ing assembly (but not after pipe is fully inserted) to dis­tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Page 20
Loading...
+ 44 hidden pages