Lennox G60UH-X User Manual

Page 1
E 2003 Lennox Industries Inc.
Dallas, Texas, USA
504,781M 6/2003
G60UH(X)
SERIES
GAS FURNACE
Failure to follow safety warnings exactĆ ly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other apĆ pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
06/03
*2P0603*
Litho U.S.A.
WARNING
FIRE OR EXPLOSION HAZARD.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately. D Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instructions.
D If you cannot reach your gas supplier, call
the fire department.
504,781M
*P504781M*
Page 2
G60UH(X) Parts Identification
TOP CAP
FLUE
COLLAR
COMBUSTION AIR
INDUCER
UPPER ACCESS
PANEL
BURNERS
DURALOK
EXCHANGER
ASSEMBLY
TM
HEAT
CABINET
COMBUSTION AIR
PROVING
(PRESSURE)
SWITCH
GAS
VALVE
GAS
MANIFOLD
TWO-STAGE, SURELIGHT INTEGRATED
CONTROL BOARD
BLOWER ACCESS
®
PANEL
FIGURE 1
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of CalĆ ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379-9900
NOTE - This manual must be left with the equipment user.
BLOWER
MOTOR
CONTROL BOX
WARNING
Do not set thermostat below 60°F (16°C) in heating mode. Setting thermostat below 60°F (16°C) reduces the number of heating cycles. Damage to the unit may occur that is not covered by the warranty.
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or mainteĆ nance, turn the electrical power to unit OFF at the disconnect switch.
Page 2
Page 3
WARNING
Do not use this furnace if any part has been underĆ water. A flood-damaged furnace is extremely danĆ gerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified serĆ vice technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
IMPORTANT
Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the apĆ plication needs must be made by a Lennox service technician using factory specified and approved parts.
WARNING
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injuĆ ry or death.
Your furnace is a gas appliance. It is critical that the gas
supplied to the unit be completely burned to avoid the proĆ
duction of carbon monoxide gas. Complete combustion of
the gas requires, but is not limited to, correct gas pressure
and gas flow rate, adequate combustion air and proper
venting.
WARNING
Carbon monoxide gas is invisible, odorless, and toxic.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personĆ al injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Safety Instructions
1 - Keep the furnace area clear and free of combustible
material, gasoline, and other flammable vapors and liquids. If it is installed in an insulated area, the furnace must be kept free of insulating material. Insulating maĆ terial may be combustible.
2 - DO NOT obstruct air flow to unit. Unit must receive an
unobstructed flow of combustion and ventilating air. DO NOT block or obstruct air openings on the furnace or air openings to the area in which the furnace is installed. Take care to maintain established clearĆ ances surrounding the furnace.
3 - DO NOT store chlorine or fluorine products near unit
or introduce these products into the combustion air. These products can cause furnace corrosion.
4 - DO NOT draw return air from a room where this furĆ
nace, or any other gas appliance (ie., a water heatĆ er), is installed. When return air is drawn from a room,
a negative pressure is created in the room. If a gas apĆ pliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Exposure to carbon monoxide gas can cause personal injuĆ
ry and even death to all occupants, including pets. Any item
that is powered by, or gives off heat from, a combustion proĆ
cess (including lawn mowers, automobiles, and fireplaces)
has the potential to produce carbon monoxide gas. Because
of this, Lennox recommends the use of a carbon monoxĆ
ide detector in your home, even if you do not own gas
appliances. Reliable detectors are available at reasonable
retail prices. Contact your Lennox dealer for more details
about this investment in your safety.
Your furnace is designed to meet standards set by nationĆ
al agencies. It should operate safely when properly
installed and maintained. However, the unit's perforĆ
mance can be greatly impacted by the individual installaĆ
tion and the operating environment. It is your responsibilĆ
ity to ensure that this appliance is maintained. Proper
maintenance is critical for your safety and the satisfactory
operation of the product. Lennox strongly recommends
annual inspection and maintenance of this appliance.
Contact your Lennox dealer for an inspection by a qualiĆ
fied service technician.
Lighting Information & Operation
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Page 3
Page 4
BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
The gas valve on the G60UH(X) is equipped with either a gas control knob or lever. Use only your hand to turn the gas control knob or push the gas lever. Never use tools. If the knob or lever will not move by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Placing the G60UH(X) furnace into operation:
G60UH(X) units are equipped with a SureLight
®
ignition
system. Do not attempt to manually light burners on these furnaces. Each time the thermostat calls for heat, the burnĆ ers will automatically light. The ignitor does not get hot when there is no call for heat on units with the SureLight ignition system.
Operating the Gas Valve (Figures 3 and 4)
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting. See figure 2.
3 - Turn off all electrical power to the unit.
Honeywell VR8205 Gas Valve - Turn knob on gas valve counterclockwise to ON. Do not force. See figure 4.
WHITE RODGERS 36E SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
®
FIGURE 3
HONEYWELL VR8205 SERIES GAS VALVE
THERMOSTATS
FIGURE 2
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the burners by hand.
5 - Remove the upper access panel.
6 - White Rodgers 36E Gas Valve - Sw i t ch gas valve leĆ
ver to OFF. See figure 3. Honeywell VR8205 Gas Valve - Turn knob on gas
valve clockwise
to OFF. Do not force. See figure
4.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instrucĆ tions. If you do not smell gas go to next step.
8 - White Rodgers 36E Gas Valve - Switch gas valve lever to
ON. See figure 3.
GAS VALVE SHOWN IN OFF POSITION
FIGURE 4
9 - Replace the upper access panel.
10 - Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12 - If the appliance will not operate, follow the instructions
Turning Off Gas to the Unit" and call your service techĆ nician or gas supplier.
Turning Off Gas to the Unit
1 - Set the thermostat to the lowest setting. 2 - Turn off all electrical power to the unit if service is to be
performed. 3 - Remove the upper access panel. 4 - White Rodgers 36E Gas Valve - Sw i t ch gas valve leĆ
ver to OFF.
Honeywell VR8205 Gas Valve - Turn knob on gas
valve clockwise
to OFF. Do not force.
5 - Replace the upper access panel.
Page 4
Page 5
Filters
This unit is not equipped with a filter or rack. A field-proĆ vided, high-velocity filter is required to ensure proper unit operation. A filter must be in place any time the unit is operating.
Maintenance
A qualified service technician should inspect the complete system each season (heating and cooling). The following maintenance procedures should only be conducted by a qualified service technician. Do not attempt to service
the unit in any way.
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operaĆ tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to disĆ connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
Venting System
Inspect the furnace return air duct connection. The duct must be sealed to the furnace and it must terminate outside the space containing the furnace.
Inspect the physical support of the furnace to guarantee that it is sound. The support must not sag and must not have cracks or gaps around the base of the furnace. There must be a seal between the furnace base and the support.
During a seasonal check, the service technician will inĆ spect the indoor blower and the burner flames along with the venting system.
Blower
Check blower wheel for any debris and clean it, if necesĆ sary. The blower motor is pre-lubricated for extended bearĆ ing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injuĆ ry or death.
Burner Flame
CAUTION
To ensure proper operation, a qualified technician should annually check the burner flame.
WARNING
Asphyxiation Hazard
The exhaust vent for this furnace must be securely connected to the furnace flue collar at all times.
For your safety and to fulfill the terms of the limited warranty, a qualified service technician must annualĆ ly inspect this furnace and its vent system.
Annually (before heating season) inspect furnace venting system, vent cap, heat exchanger and burners for corroĆ sion, deterioration, or deposits of debris. Remove any obĆ structions.
Inspect thefurnace venting system to make sure it is in place, physically sound and without holes, corrosion, or blockage. The vent connector must be correctly posiĆ tioned and sloped upward. The vent connector must be physically sound, without holes or excessive corrosion.
Service Reminder
Call your Lennox service technician if the unit will not operĆ ate. Before calling, always check the following to be sure service is required.
1 - Check that electrical disconnect switches are ON. 2 - Check room thermostat for proper setting. 3 - Replace any blown fuses or reset circuit breakers. 4 - Gas valve should be ON. 5 - Air filter should not be plugged, which wil limit air flow. 6 - Is gas turned on at meter? 7 - Is manual main shut-off valve open? Record the model and serial number of the furnace. These numbers are on the unit nameplate, which is located below the burners.
Serial Number ________________________________
Model Number ________________________________
Page 5
Page 6
Safety Precautions
If you discover any of the following, shut down your unit and contact a Lennox dealer for an inspection by a qualified technician.
D If you repeatedly hear any new or unfamiliar sounds
while your unit is operating, there may be a problem. For example, poorly performing burners can produce unfaĆ miliar noises.
D If you smell any unusual odors, your unit may be operatĆ
ing improperly. For example, units can give off unfamilĆ iar odors if components are required to operate in abĆ normal conditions.
D Look for visible signs of a malfunctioning unit. Examples
include unusual amounts of condensate on windows inĆ side your house, visibly burnt components or unusual dirt or rust accumulations on the vent pipe or in the unit.
D If you experience headache, nausea, fatigue, or dizziĆ
ness, the cause could be exposure to carbon monoxide gas. This is often misdiagnosed as the flu because symptoms are similar. If you suffer from flu-like sympĆ toms that are exaggerated at home, but seem to subĆ side while you are away from the house, exposure to carbon monoxide could be the cause.
Your vigilance may pay off in early detection of a problem before either personal injury or property damage occurs. Do not hesitate to contact a qualified service technician as an investment in your well being.
Planned Service
You should expect a service technician to check the followĆ ing items during an annual inspection. Power to the unit must be shut off for the service technician's safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) - Must be open and unobĆ structed to provide combustion air.
Burners - Must be inspected for rust, dirt, or signs of water.
Vent pipe - Must be inspected for signs of water, damaged
or sagging pipe, or disconnected joints.
Unit appearance - Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door - Must be properly in place and proĆ vide a seal between the return air and the room where the furnace is installed.
Return air duct - Must be properly attached and provide an air seal to the unit.
Operating performance - Unit must be observed during operation to monitor proper performance of the unit and the vent system.
Combustion gases - Flue products must be analyzed and compared to the unit specifications.
Problems detected during the inspection may make it necĆ essary to temporarily shut down the furnace until the items can be repaired or replaced.
Pay attention to your furnace. Situations can arise beĆ tween annual furnace inspections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carĆ bon monoxide gas.
Page 6
Page 7
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA International nameplate -- Example: G60UH(X)-36A-070-4.
Cabinet Parts
Upper access panel Blower panel Top cap
Control Panel Parts
Transformer Two-stage SureLight Door interlock switch Circuit breaker
Blower Parts
Blower wheel Blower housing Motor Capacitor Motor mounting frame Blower housing cutoff plate
®
board
Heating Parts
Flame Sensor Heat exchanger assembly Gas manifold Two-speed combustion air inducer Two-stage gas valve Main burner cluster Main burner orifices Pressure switch Ignitor Primary limit control Flame rollout switch Secondary limit
Page 7
Loading...