Lennox G60UHV?36A?070, G60UHV-36B-090, G60UHV-60C-090, G60UHV-60C-110, G60UHV-60D-135 Installation Instructions Manual

Page 1
Page 1
10/08
*2P1008*
506177−01
*P506177-01*
E 2008 Lennox Industries Inc.
Dallas, Texas, USA
FOR FUTURE REFERENCE
INSTALLATION INSTRUCTIONS
G60UHV(X) Series
GAS FURNACE
506177−01 10/2008 Supersedes 505,121M
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G60UHV(X) Parts Arrangement 3. . . . . . . . . . . . . . . . . . .
G60UHV(X) Gas Furnace 4. . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 6. . . . . . . . . . . . . .
Setting Equipment 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Settings 28. . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 38. . . . . . . . . . . . . . . . . . . . . . . .
High Altitude Information 38. . . . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 38. . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 39. . . . . . . . . . . . . . . . . . .
Service 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planned Service 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Diagnostic Codes 43. . . . . . . . . . . . . . .
Troubleshooting 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 50. . . . . . . . . . . . . . . .
WHAT TO DO IF YOU SMELL GAS:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
WARNING
D Leave the building immediately.
Litho U.S.A.
Page 2
Page 2
G60UHV(X) Unit Dimensions − inches (mm)
*Bottom Return
Air Opening
GAS PIPING INLET
(Either Side)
*Side Return
Air Opening
(Either Side)
*Bottom Return
Air Opening
FLUE OUTLET
(Top)
ELECTRICAL INLET
(Either Side)
ELECTRICAL INLET
(Either Side)
SUPPLY AIR
OPENING
AIR FLOW
FRONT VIEW SIDE VIEW
TOP VIEW
A
B
9/16 (14)
C
D
3/4 (19)
3/4 (19)
28−1/2
(724)
19−7/16
(494)
23−1/2
(597) 4−1/4 (108)
14 (356) Right
13−1/4 (337) Left
4−7/8 (124) Right
2−1/4 (57) Left
40
(1016)
3−3/4 (95)
4
(102)
1−15/16 (49)
23
(584)
14
(356)
9/16
(14)
3−3/4 (95)
3−1/4 (83) Right
8−1/8 (206) Left
**FLUE OUTLET
(Either Side)
TOP VIEW
16
(406)
14−3/4
(375)
5/8 (16)
23-3/4 (603)
25 (635)
*NOTE − 60C and 60D units that require air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Return air from single side with transition which will accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Required to maintain proper air velocity.)
2. Return air from single side with optional RAB Return Air Base.
3. Return air from bottom.
4. Return air from both sides.
5. Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
**Flue outlet may be horizontal but furnace must be vented vertically Optional external side return air filter kit cannot be used with the optional RAB Return Air Base.
A B C D
Model No.
in. mm in. mm in. mm in. mm G60UHV−36A−070 14−1/2 368 13−3/8 340 13 330 4−1/2 114 G60UHV−36B−090 17−1/2 446 16−3/8 416 16 406 6 152 G60UHV−60C−090,
G60UHV−60C−110
21 533 19−7/8 454 19−1/2 495 7−3/4 197
G60UHV−60D−135 24−1/2 622 23−3/8 546 23 584 9−1/2 241
Page 3
Page 3
G60UHV(X) Parts Arrangement
FIGURE 1
Flue
Transition
Combustion Air Inducer
Combustion Air
Orifice
Combustion Air
Pressure Switch Assembly
(two switches)
Flue
Collector
Box
Heat Exchanger
Flame Sensor
Gas Valve
Burners
Ignitor
NO
x
Insert
Primary
Limit
Door Interlock Switch
Two−Stage, Variable Speed
Integrated Control
Control Transformer
Circuit Breaker
Gasket
Flue Box Gasket
Gas
Orifices
Ignitor
Bracket
Burner Box Bottom
Limit Shield
Secondary Limit(s)
(NOx Units Only)
Air Deflector
G60UH−60C−110
Units Only
Variable
Speed
Blower Motor
Flame Rollout Switches
Air Intake
Cover
Air Baffle
Gasket
Burner
Box Cover
Power Choke
(1 hp Only)
Sight
Glass
Burner
Box Top
Page 4
Page 4
G60UHV(X) Gas Furnace
The G60UHV(X) gas furnace is equipped with a two−stage, variable speed integrated control. This control ensures compatibility with Lennox’ Harmony III zone control sys­tem, as well as a thermostat which provides humidity con­trol. Each G60UHV(X) unit is shipped ready for installation in the upflow or horizontal position (left or right). The fur­nace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in a hori­zontal application. The panel may also be removed in up­flow applications.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G60UHV(X) unit 1 − Bag assembly containing the following:
2 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Vent warning label 1 − Owner’s manual and warranty card
The following items may be ordered separately: 1 − Thermostat 1 − Hanging bracket (for horizontal installations) 1 − Propane/LP changeover kit 1 − Return air base 1 − High altitude kit 1 − Side filter kit
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Safety Information
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
G60UHV(X) units are CSA International certified to ANSI Z21.47 and CSA 2.3 standard.
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA-B149 installation codes for natu­ral gas and propane gas burning appliances and equip­ment, local plumbing or waste water codes and other appli­cable local codes.
Adequate clearance must be made around the air open­ings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standards.
Vent installations must be consistent with the venting tables (in this instruction) and applicable provisions of local building codes.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figures 6 and 11. Accessibil­ity and service clearances must take precedence over fire protection clearances.
NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous at­mosphere, the furnace must be installed according to rec­ommended good practice requirements and current Na­tional Fuel Gas Code or CSA B149 standards.
NOTE − Furnace must be adjusted to obtain a temperature rise(high and low fire) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit op­eration.
This G60UHV(X) furnace must be installed so that its elec­trical components are protected from water.
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent
Page 5
Page 5
chilled air from entering the furnace. If the damper is manu­ally operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent op­eration down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The G60UHV(X) furnace may be installed in alcoves, clos­ets, attics, basements, garages, and utility rooms in the up­flow or horizontal position.
This furnace design has not been CSA International certi­fied for installation in mobile homes, recreational vehicles, or outdoors.
Lennox does not recommend the use of G60UHV(X) units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
G60UHV(X) units may be used for heating of buildings or structures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct sys-
tem, air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
NOTE − The Commonwealth of Massachusetts stipu­lates these additional requirements:
D Gas furnaces shall be installed by a licensed plumb-
er or gas fittter only.
D The gas cock must be T handle" type. D When a furnace is installed in an attic, the passage-
way to and service area surrounding the equipment shall be floored.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a G60UHV(X) furnace:
D Place the furnace as close to the center of the air dis-
tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
D Do not install the furnace where drafts might blow direct-
ly into it. This could cause improper combustion and un­safe operation.
D Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
D When the furnace is installed in an attic or other insu-
lated space, keep insulation away from the furnace.
Page 6
Page 6
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction prac­tices make it necessary to bring in air from outside for com­bustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless out­side air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the fur­nace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situ­ation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install G60UHV(X) furnaces to ensure effi­cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas pip­ing. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprinted material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Canada, refer to the standard CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliances will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When fire­places, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft. In­sufficient air causes incomplete combustion which can re­sult in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by
Page 7
Page 7
infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cu­bic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
EQUIPMENT IN CONFINED
SPACE ALL AIR FROM INSIDE
CHIMNEY
OR GAS
VENT
FURNACE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
NOTE − Each opening shall have a free area of at least one square inch (645 mm
2
) per 1,000 Btu (.29 kW) per hour of the total input rat­ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm
2
).
FIGURE 2
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm
2
). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 2.
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate di­rectly or by ducts with the outdoors or spaces (crawl or at­tic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm
2
) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the en­closure. See figures 3 and 4. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm
2
) per
2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 5.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cov­ering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera­tion.
Page 8
Page 8
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
WATER
HEATER
INLET
AIR
CHIMNEY OR
GAS VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip­ment in the enclosure.
CHIMNEY
OR GAS
VENT
WATER
HEATER
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12 in.
above bottom)
FURNACE
FIGURE 4
EQUIPMENT IN
CONFINED SPACE
ALL AIR FROM
OUTSIDE
OUTLET AIR
INLET AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
NOTE − Each air duct opening shall have a free area of at least one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each open­ing shall have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.
FURNACE
FIGURE 5
Page 9
Page 9
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
The G60UHV(X) gas furnace can be installed as shipped in either the upflow position or the horizontal position, with right-hand or left-hand air discharge.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level.
NOTE − Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic wash­er (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be re- moved before the furnace is placed into operation. Af­ter the bolt and washer have been removed, the rigid leg will not touch the blower housing.
NOTE − G60UHV−60D−135 units are equipped with a ship­ping pad under the blower housing. Remove the shipping pad prior to operation.
Upflow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figure 6.
Upflow Application Installation Clearances
Top
Bottom
Left Side
Right Side
Type of Vent
Connector
Type C Type B1
Top 1 in. (25 mm) 1 in. (25 mm)
*Front 3 in. (76 mm) 3 in. (76 mm)
Back 0 0
Sides 0 0
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor 0 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. For installation on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring. Left side requires 3 inches if a single wall vent is used on 14−1/2 inch cabinets, or 2 inches if a single wall vent is used on 17−1/2 inch cabinets.
FIGURE 6
Page 10
Page 10
Return Air −− Upflow Applications
Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 1800 cfm (850 L/s) are required with 60C or 60D models in an upflow applica­tion, the following return air options are available:
1 − Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) clean­able air filter. (Required to maintain proper air velocity.) See figure 7.
2 − Return air from single side with optional RAB Return
Air Base. See figure 8.
3 − Return air from bottom.
4 − Return air from both sides.
5 − Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
Side Return Air
(with transition and filter)
FIGURE 7
Return Air
Plenum
Transition
20" X 25" X 1"
(508mm X635mm X 25mm)
Cleanable Filter
Optional Return Air Base
(Upflow Applications Only −− For use with B, C and D cabinets only)
FIGURE 8
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Unit side return
air
Opening
FRONT VIEW
SIDE VIEW
27−5/8 (702)
4
(102)
1
23 (584) Overall
(Maximum)
OPTIONAL RAB
RETURN AIR BASE
23 (584)
7−1/4 (184)
7/8
(22)
3/4
(19)
1
22−7−16
(570)
Overall
(Maximum)
SIDE RETURN
AIR OPENINGS
(Either Side)
FURNACE
FRONT
14
(356)
AIR FLOW
5−5/8 (143)
1
Minimum 11 (279)
2
Maximum
14 (356)
21 (533) RAB−C (98M58)
24−1/2 (622) RAB−D (98M59)
17−1/2 (446) RAB−B (98M60)
Page 11
Page 11
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 9.
Removing the Bottom Panel
FIGURE 9
Screw
Bottom Panel
Bottom Cap
Leveling an Upflow Unit
When the side return air inlets are used in an upflow ap­plication, it may be necessary to install leveling bolts on the bottom of the furnace. Use field−supplied corrosion−resist­ant 5/16 inch machine bolts (4) and nuts (8). See figure 10.
NOTE − The maximum length of the bolt is 1−1/2 inches.
1 − Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace’s bottom. See fig­ure 10 for the correct location of the holes. Drill through the bottom panel and the bottom flange of the cabinet.
2 − Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole. A flat washer may be added between the nut and the bot­tom of the unit.
3 − Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the nut and the bottom of the unit.
4 − Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement.
FIGURE 10
1−3/4
(44)
1−3/4
(44)
3/8
(10)
1−3/4 (44)
3/8
(10)
3/8
(10)
3/8
(10)
1−3/4
(44)
Leveling Bolt Installation
Leveling Bolt
Locations
Leveling Bolt
Locations
Inches (mm)
Furnace Front
Furnace
Bottom
Horizontal Applications
The G60UHV(X) furnace can be installed in horizontal ap­plications.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figure 11.
Horizontal Application
Installation Clearances
Top
Bottom
Left End
Right End
Vent Connector
Type
Type C Type B1
Top 0 0
*Front 3 in. (76 mm) 3 in. (76 mm)
Back 0 0
Ends 2 in. (51 mm) 2 in. (51 mm)
Vent 6 in. (152 mm) 1 in. (25 mm)
Bottom 0 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. For installations on a combustible floor, do not install the fur­nace directly on carpeting, tile or other combustible materials oth­er than wood flooring.
FIGURE 11
Page 12
Page 12
This furnace may be installed in either an attic or a crawl­space. Either suspend the furnace from roof rafters or floor joists, as shown in figure 12, or install the furnace on a plat­form, as shown in figure 13. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
Typical Horizontal Application
Unit Suspended in Attic or Crawlspace
Leave sufficient clearance between rod and unit to remove access panel.
FIGURE 12
1/4 in. ROD
ANGLE
IRON
U−CHANNELS
NOTE − Heavy−gauge perforated sheet metal straps (plumbers’ straps) may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to sus­pend the unit in this way, support must be providedfor both the ends and the middle of the furnace to prevent sagging. The straps must not interfere with the plenum or exhaust piping installation. Securing screws should be 1/2 inch from the top edge and 1−1/2 inch from the side edge in all cases. Cooling coils and supply and return air plenums
must be supported separately.
NOTE − When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain.
Return Air −− Horizontal Applications
Return air can be brought in through the end of a furnace installed in a horizontal application. The furnace is equipped with a removable bottom panel to facilitate instal­lation. See figure 9.
Horizontal Application
Unit Installed on Platform
WORKING
PLATFORM
GAS
ENTRY
VENT
PIPE
NOTE − Line contact is permis­sible. See the unit nameplate for clearances.
FIGURE 13
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace. In platform installations with bottom return air, the furnace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or proper­ty damage could result.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Page 13
Page 13
Filters
This unit is not equipped with a filter or rack. A field−pro­vided high−velocity filter is required for the unit to operate properly. Table 1 lists recommended filter sizes. A filter must be in place any time the unit is operating.
TABLE 1
Furnace
Filter Size
Furnace
Cabinet Width
Side Return Bottom Return
14−1/2" 16 X 25 X 1 (1) 14 X 25 X 1 (1)
17−1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24−1/2" 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Duct System
Use industry-approved standards (such as those pub­lished by Air Conditioning Contractors of America or Ameri­can Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Do not operate the furnace with an external static pressure that exceeds 0.8 inches w.c. Higher external stat­ic pressures may cause erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after the furnace is installed. The furnace access panel must always be in place when the furnace is operat­ing and it must not allow leaks into the supply air duct sys­tem.
Return Air Plenum
Return air must not be drawn from a room where this furnace, or any other gas appliance (ie., a water heat­er), is installed. When return air is drawn from a room, a
negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue prod­ucts can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incom­plete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
In upflow applications, the return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an air­tight seal between the bottom of the furnace and the plat­form to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent seal­ing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Venting
A 4−inch diameter flue transition is factory-installed on the combustion air inducer outlet of all models. Modifying or
removing the flue transition will cause the unit to oper­ate unsafely and will void the unit certification. The
vent connector does not require insulation. The combustion air inducer may be rotated clockwise or
counterclockwise by 90° to allow for top or side vent dis­charge in all applications. When the unit is installed, the flue transition must be in the 9 o’clock, 12 o’clock or 3 o’clock position. The unit will not vent properly with the flue transition pointed down in the 6 o’clock position. Re­move the four mounting screws, rotate the assembly (in­cluding the gasket), then reinstall the mounting screws. See figure 14. Use the provided wire tie to bundle the pres­sure switch wires with the inducer motor power leads.
Route the wires away from moving parts and the heat of the inducer motor to prevent damage to the wires.
FIGURE 14
Combustion Air Inducer
(Upflow Position)
Mounting Screws
MOUNTING SCREWS90°
90°
(Remove)
(Remove)
Flue Transition
(Do not remove
)
Flue Outlet
Hole
(
Reattach
Cutout Here)
Supply Air
Opening
Top View of Furnace
Top Cap
Cut out
Optional
Flue Outlet
Optional Flue Outlet
(Horizontal Installation)
FIGURE 15
Page 14
Page 14
Use sheet metal shears to remove the cut out from the side of the cabinet. Use the two provided sheet metal screws to install the cut out on the top cap to cover the original flue outlet opening. See figure 15.
The G60UHV(X) series units are classified as fan−assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the USA and the current standards of CSA B149 Natural Gas and Propane Installation Codes in Can­ada. A fan−assisted Category I furnace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger.
NOTE − Use these instructions as a guide. They do not su­persede local codes. This furnace must be vented accord­ing to all local codes these installation instructions, and the provided venting tables in these instructions
The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper ap­plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab­sence of local codes, the NFGC serves as the defining doc­ument.
Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.
IMPORTANT
Once the venting system is installed, attach the Dis­connected Vent" warning sticker to a visible area of the plenum near the vent pipe. The warning sticker is provided in the bag assembly.
WARNING
Asphyxiation hazard. The exhaust vent for this fur­nace must be securely connected to the furnace flue transition at all times.
FLUE TRANSITION
COLLAR
VENT CONNECTION
VENT
PIPE
FURNACE
FIGURE 16
Use self−drilling sheet metal screws or a mechanical fas­tener to firmly secure the vent pipe to the round collar of the flue transition. If self−drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self−drilling screw through the front and one through each side of the vent pipe and collar. See figure 16.
Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central fur­naces must be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 17 and 18 for com­mon venting.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile−lined must be lined with B1 vent or a listed insulated flexible metal vent. An exterior tile−lined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent.
If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting meth­od must be found.
G60UHV units installed in upflow applications may be vented into a tile−lined masonry chimney without using a listed metal liner, provided that the optional masonry chim­ney vent adapter kit (18M79) is used. Instructions provided with the kit must be followed exactly.
Insulation for the flexible vent pipe must be an encapsu­lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 17.
Common Venting Using Metal−Lined Masonry Chimney
4 in. (102 mm)
minimum
MIN. LENGTH −− AS
SHORT AS PRACTICAL
MAX. LENGTH
−− SEE NOTE 1 BELOW.
SEALED
PERMANENTLY
SEALED FIREPLACE
OPENING
EXTERIOR
CHIMNEY WITH
METAL
LINER
VENT CONNECTOR
SEE NOTE 2
NOTE 1 − Refer to the provided venting tables for installations in the USA and the venting tables in CSA−B149 for installations Canada. NOTE 2 − Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements shown in the provided venting tables for installations in USA and the venting tables in current CSA−B149 for installations in Canada.
OTHER
APPLIANCE
FURNACE
FIGURE 17
5 ft. (1.5 m)
minimum
Page 15
Page 15
Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector
MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT
INTERIOR TILE−LINED MASONRY CHIMNEY
NOTE − the chimney must be properly sized per provided venting tables or lined with listed metal lining system.
PERMANENTLY SEALED FIREPLACE OPENING
VENT
CONNECTOR
SEE NOTE 1 BELOW
NOTE − Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements as shown in the pro­vided venting tables for installations in USA and the venting tables in current CSA−B149 for installations in Canada.
NOTE− Refer to provided venting tables for installations in the USA and the venting tables in current CSA−B149 for installations in Canada.
FURNACE
OTHER
APPLIANCE
FIGURE 18 DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran­ular insulating material
IMPORTANT
SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized ac­cording to the provided venting tables and the vent pipe manufacturer’s instructions.
A fan−assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:
S The chimney is currently serving at least one drafthood
equipped appliance
S The vent connectors and chimney are sized according
to the provided venting tables for the USA, and the ap­propriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes in Cana­da.
If type B1 double-wall vent is used inside a chimney, no oth­er appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products.
A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof as­sembly according to the terms of their respective listings and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting G60UHV(X) series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is servicing a solid−fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed.
A type B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors.
General Venting Requirements
Vent all G60UHV(X) furnaces according to these instruc­tions:
1 − Vent diameter recommendations and maximum allow-
able piping runs are found in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Pro­pane Installation Codes for Canada.
2 − In no case should the vent or vent connector diameter
be less than the diameter specified in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada.
3 − The minimum vent capacity determined by the sizing
tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input rating.
4 − Single appliance vents − If the vertical vent or tile-lined
chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to de­termine the minimum vent capacity and the vent
connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, however,
shall not exceed 7 times the flow area of the listed ap­pliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.
Page 16
Page 16
5 − Multiple appliance vents − The flow area of the largest
section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering meth­ods.
6 − The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning, and replacement.
7 − Single appliance venting configurations with zero lat-
eral lengths (tables 3 and 4) are assumed to have no elbows in the vent system. For all other vent configura­tions, the vent system is assumed to have two 90° el­bows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed ca­pacity).
8 − The common venting tables (5, 6, 7, and 8) were gen-
erated using a maximum horizontal vent connector length of 1−1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows:
TABLE 2
Connector Diameter
inches (mm)
Maximum Horizontal
Connector Length feet (m)
3 (76) 4−1/2 (1.37)
4 (102) 6 (1.83)
5 (127) 7−1/2 (2.29)
6 (152) 9 (2.74)
7 (178) 10−1/2 (3.20)
9 − If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90° elbows (0.80 x maximum common vent capacity). The horizontal length of the offset shall not exceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.
10 − The vent pipe should be as short as possible with the
least number of elbows and angles required to com­plete the job. Route the vent connector to the vent us­ing the shortest possible route.
11 − A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance.
12 − Vent connectors shall be firmly attached to the furnace
flue collar by self−drilling screws or other approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means.
13 − When the vent connector used for Category I ap-
pliances must be located in or pass through a crawl­space or other areas which may be cold, that portion of the vent connector shall be constructed of listed double-wall type B vent material or material having equivalent insulation qualities.
14 − All venting pipe passing through floors, walls, and ceil-
ings must be installed with the listed clearance to com­bustible materials and be fire stopped according to lo­cal codes. In absence of local codes, refer to NFGC (Z223.1).
15 − No portion of the venting system can extend into, or
pass through any circulation air duct or plenum.
16 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90° elbow (0.90 x maxi­mum common vent capacity).
18 − The common vent diameter must always be at least as
large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of the draft hood outlet or flue collar outlet.
20 − Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the chimney.
21 − When connecting this appliance to an existing dedi-
cated or common venting system, you must inspect the venting system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada. If the existing venting system does not meet these requirements, it must be resized.
Page 17
Page 17
TABLE 3
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
Lateral
3 Inch 4 Inch 5 Inch 6 Inch
H
(
feet
)L(
feet
)
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
(feet)
MIN MAX MIN MAX MIN MAX MIN MAX
0 0 78 0 152 0 251 0 375
2 13 51 18 97 27 157 32 232
6
4 21 49 30 94 39 153 50 227
6 25 46 36 91 47 149 59 223
0 0 84 0 165 0 276 0 415
2 12 57 16 109 25 178 28 263
8
5 23 53 32 103 42 171 53 255
8 28 49 39 98 51 164 64 247
0 0 88 0 175 0 295 0 447
2 12 61 17 118 23 194 26 289
10
5 23 57 32 113 41 187 52 280
10 30 51 41 104 54 176 67 267
0 0 94 0 191 0 327 0 502
2 11 69 15 136 20 226 22 339
15
5 22 65 30 130 39 219 49 330
10 29 59 40 121 51 206 64 315
15 35 53 48 112 61 195 76 301
0 0 97 0 202 0 349 0 540
2 10 75 14 149 18 250 20 377
5 21 71 29 143 38 242 47 367
20
10 28 64 38 133 50 229 62 351
15 34 58 46 124 59 217 73 337
20 48 52 55 116 69 206 84 322
0 0 100 0 213 0 374 0 587
2 9 81 13 166 14 283 18 432
5 21 77 28 160 36 275 45 421
30
10 27 70 37 150 48 262 59 405
15 33 64 44 141 57 249 70 389
20 56 58 53 132 66 237 80 374
30 NR NR 73 113 88 214 104 346
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi­mum listed capacity).
Page 18
Page 18
TABLE 4
Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
Lateral
3 Inch 4 Inch 5 Inch 6 Inch
H
(
feet
)L(
feet
)
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
(feet)
MIN MAX MIN MAX MIN MAX MIN MAX
0 38 77 59 151 85 249 126 373
2 39 51 60 96 85 156 123 231
6
4 NR NR 74 92 102 152 146 225
6 NR NR 83 89 114 147 163 220
0 37 83 58 164 83 273 123 412
2 39 56 59 108 83 176 121 261
8
5 NR NR 77 102 107 168 151 252
8 NR NR 90 95 122 161 175 243
0 37 87 57 174 82 293 120 444
2 39 61 59 117 82 193 119 287
10
5 52 56 76 111 105 185 148 277
10 NR NR 97 100 132 171 188 261
0 36 93 56 190 80 325 116 499
2 38 69 57 136 80 225 115 337
15
5 51 63 75 128 102 216 144 326
10 NR NR 95 116 128 201 182 308
15 NR NR NR NR 158 186 220 290
0 35 96 54 200 78 346 114 537
2 37 74 56 148 78 248 113 375
5 50 68 73 140 100 239 141 363
20
10 NR NR 93 129 125 223 177 344
15 NR NR NR NR 155 208 216 325
20 NR NR NR NR 186 192 254 306
0 34 99 53 211 76 372 110 584
2 37 80 55 164 76 281 109 429
5 49 74 72 157 98 271 136 417
30
10 NR NR 91 144 122 255 171 397
15 NR NR 115 131 151 239 208 377
20 NR NR NR NR 181 223 246 357
30 NR NR NR NR NR NR NR NR
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi­mum listed capacity).
Page 19
Page 19
TABLE 5
Vent Connector Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Vent and Connector Diameter − D (inches)
Vent
Height
C
onnector
Rise
3 Inch 4 Inch 5 Inch 6 Inch
Height
H
Rise
R
Appliance Input Rating in Thousands of Btu Per Hour
(feet) (feet)
MIN MAX MIN MAX MIN MAX MIN MAX
1 22 37 35 66 46 106 58 164
6
2 23 41 37 75 48 121 60 183
6
3 24 44 38 81 49 132 62 199
1 22 40 35 72 49 114 64 176
8
2 23 44 36 80 51 128 66 195
3 24 47 37 87 53 139 67 210
1 22 43 34 78 49 123 65 189
10
2 23 47 36 86 51 136 67 206
3 24 50 37 92 52 146 69 220
1 21 50 33 89 47 142 64 220
15
2 22 53 35 96 49 153 66 235
3 24 55 36 102 51 163 68 248
1 21 54 33 99 46 157 62 246
20
2 22 57 34 105 48 167 64 259
3 23 60 35 110 50 176 66 271
1 20 62 31 113 45 181 60 288
30
2 21 64 33 118 47 190 62 299
3 22 66 34 123 48 198 64 309
TABLE 6
Common Vent Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Common Vent Diameter − D (inches)
Vent
Height
4 Inch 5 Inch 6 Inch 7 Inch
Height
H
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
6 92 81 140 116 204 161 309 248
8 101 90 155 129 224 178 339 275
10 110 97 169 141 243 194 367 299
15 125 112 195 164 283 228 427 352
20 136 123 215 183 314 255 475 394
30 152 138 244 210 361 297 547 459
Page 20
Page 20
TABLE 7
Vent Connector Capacity
Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving Two or More Category I Appliances
Vent and Connector Diameter − D (inches)
Vent
Height
C
onnector
Rise
3 Inch 4 Inch 5 Inch 6 Inch
Height
H
Rise
R
Appliance Input Rating in Thousands of Btu Per Hour
(feet) (feet)
MIN MAX MIN MAX MIN MAX MIN MAX
1 NR NR NR NR NR NR NR NR
6
2 NR NR NR NR NR NR 168 182
6
3 NR NR NR NR 121 131 174 198
1 NR NR 79 87 116 138 177 214
15
2 NR NR 83 94 121 150 185 230
3 NR NR 87 100 127 160 193 243
1 47 60 77 110 113 175 169 278
30
2 50 62 81 115 117 185 177 290
3 54 64 85 119 122 193 185 300
TABLE 8
Common Vent Capacity
Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving Two or More Category I Appliances
Common Vent Diameter − D (inches)
Vent
Height
4 Inch 5 Inch 6 Inch 7 Inch
Height
H
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
6 89 78 136 113 200 158 304 244
8 98 87 151 126 218 173 331 269
10 106 94 163 137 237 189 357 292
15 121 108 189 159 275 221 416 343
20 131 118 208 177 305 247 463 383
30 145 132 236 202 350 286 533 446
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas ap­pliances, the venting system is likely to be too large to prop­erly vent the remaining attached appliances.
Conduct the following test while each appliance is operat­ing and the other appliances (which are not operating) re­main connected to the common venting system. If the vent­ing system has been installed improperly, you must correct the system as indicated in the general venting re­quirements section.
1 − Seal any unused openings in the common venting sys-
tem.
2 − Inspect the venting system for proper size and horizon-
tal pitch. Determine that there is no blockage, restric­tion, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − Close all building doors and windows and all doors be-
tween the space in which the appliances remaining connected to the common venting system are located
and other spaces of the building. Turn on clothes dry­ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper­ate at maximum speed. Do not operate a summer ex­haust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace damp­ers, and any other gas−burning appliances to their pre­vious mode of operation.
7 − If a venting problem is found during any of the preced-
ing tests, the common venting system must be modi­fied to correct the problem.
Page 21
Page 21
Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan­dards of the National Fuel Gas Code ANSI Z223.1 in the USA, and the appropriate Category 1 Natural Gas and Propane appliances venting sizing tables in the current standards of the CSA B149 Natural Gas and Propane Installation Codes in Canada.)
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet.
Gas Supply
1 − This unit is shipped standard for left or right side instal-
lation of gas piping (or top entry in horizontal applica­tions). Connect the gas supply to the piping assembly.
2 − When connecting the gas supply piping, consider fac-
tors such as length of run, number of fittings, and fur­nace rating to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical applications.
3 − The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the fur­nace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang­ers or straps. Install a drip leg inside vertical pipe runs to the unit.
5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection. See figures 26 and 27.
6 − In some localities, codes may require the installation of
a manual main shut-off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­leum gases.
NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect main power to the furnace. The installer should properly label these devices.
TABLE 9
Gas Pipe Capacity − ft
3
/hr (m3/hr)
Nominal
Iron Pipe
Internal
Length of Pipe − feet (m)
Iron Pipe
Size
inches
(mm)
Diameter
inches
(mm)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
100
(30.480)
3/8
(9.53)
.493
(12.522)95(2.69)65(1.84)
52
(1.47)
45
(1.27)
40
(1.13)
36
(1.02)
33
(.73)
31
(.88)
29
(.82)
27
(.76)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
1
(25.4)
1.049
(26.645)
680
(919.25)
465
(13.17)
375
(10.62)
320
(9.06)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
1−1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1−1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
2−1/2
(63.5)
2.469
(67.713)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3
(76.2)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
Page 22
Page 22
GROUND
JOINT
UNION
AUTOMATIC
GAS VALVE (with manual
shut−off valve)
FIELD
PROVIDED
AND INSTALLED
GROUND
JOINT UNION
Left Side Piping
(Standard)
Right Side Piping
(Alternate)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
DRIP LEG
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap Shown)
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap
Shown)
FIGURE 19
Leak Check
After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.
NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these de­vices.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af­ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 20. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN
SHUT−OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
ISOLATE
GAS VALVE
FURNACE
FIGURE 20
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic compo­nents. Take precautions during furnace installation and service to protect the furnace’s electronic con­trols. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touch­ing hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before per­forming any service procedure.
The unit is equipped with a field make−up box. The make− up box may be moved to the right side of the furnace to fa­cilitate installation. If the make−up box is moved to the right side, the excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harn­ess to protect it from damage.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Right Side
FIGURE 21
Page 23
Page 23
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Left side
FIGURE 22
Refer to figure 23 for schematic wiring diagram and trou­bleshooting and table 10 and figure 24 for field wiring.
1 − Select circuit protection and wire size according to the
unit nameplate. The power supply wiring must meet Class I restrictions.
2 − Holes are on both sides of the furnace cabinet to facili-
tate wiring.
3 − Install a separate disconnect switch (protected by ei-
ther fuse or circuit breaker) near the furnace so that power can be turned off for servicing.
4 − Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.
5 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wir­ing diagrams shown in table 10 and figure 24. Use 18−gauge wire or larger that is suitable for Class II ra­ting for thermostat connections.
6 − Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.
NOTE − The G60UHV(X) furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
7 − One line voltage EAC" 1/4" spade terminal is provided
on the furnace integrated control. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con­nected to the one of the provided neutral terminals. See figure 25 for control configuration. This terminal is energized when the indoor blower is operating.
8 − One line voltage HUM" 1/4" spade terminal is pro-
vided on the furnace integrated control. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 25 for control configuration. This terminal is energized in the heating mode whenever the combustion air inducer is operating.
9 − One 24V H" terminal is provided on the furnace inte-
grated control terminal block. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the C" terminal. See figure 25 for control configuration.
10 −Install the room thermostat according to the instruc-
tions provided with the thermostat. See table 10 for field wiring connections in varying applications. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously at approximately 38% of the second−stage cooling speed when there is no cool­ing or heating demand.
2 − When the G60UHV(X) is running in the heating mode,
the indoor blower will run on the heating speed desig­nated by the positions of DIP switches 11 and 12.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed designated by the positions of DIP switches 5 and 6.
Page 24
Page 24
TABLE 10
Field Wiring Applications
DIP Switch Settings and On−Board Links (See figure 25)
Thermostat
DIP Switch 1
W915
Two−Stage
Cooling
W914 Dehu-
midification or Harmony
III
W951
Heat Pumps
Wiring Connections
1 Heat / 1 Cool
NOTE − Use DIP switch 2 to set second−stage heat ON delay. OFF−10 min­utes. ON−15 minutes.
ON Intact Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool
NOTE − Use DIP switch 2 to set second−stage heat ON delay. OFF−10 min­utes. ON−15 minutes.
ON Cut Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool with t’stat with humidity control
NOTE − Use DIP switch 2 to set second−stage heat ON delay. OFF−10 min­utes. ON−15 minutes.
ON Cut Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 25
Page 25
TABLE 10
Field Wiring Applications (Continued)
DIP Switch Settings and On−Board Links (See figure 25)
Thermostat
DIP Switch 1
W915
Two−Stage
Cooling
W914 Dehu-
midification or Harmony
III
W951
Heat Pumps
Wiring Connections
2 Heat / 2 Cool OFF Cut Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
2 Heat / 2 Cool with t’stat with humidity control
OFF Cut Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
2 Heat / 1 Cool OFF Intact Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 26
Page 26
G60UHV(X) Schematic Wiring Diagram
FIGURE 23
Page 27
Page 27
FIELD INSTALLED CLASS II 24V FIELD INSTALLED LINE VOLTAGE
TYPICAL G60UHV(X) FIELD WIRING DIAGRAM
USE COPPER CONDUCTORS ONLY.
FIGURE 24
TWO−STAGE, VARIABLE SPEED INTEGRATED CONTROL
DIP SWITCH FUNCTIONS
HTG DIP SWITCH(ES) FUNCTION
5 and 6 Cooling Mode Blower Speed 7 and 8 Blower Speed Adjustment
9 and 10 Cooling Mode Blower Ramping Profile
11 and 12 Heating Mode Blower Speed
INDOOR
BLOWER DIP
SWITCHES
HEATING
DIP
SWITCHES
DIAGNOSTIC
LEDs
ON−BOARD
LINKS
1 T’stat Heat Stages (single or two−stage) 2 Second Stage ON Delay (single−stage t’stat)
3 and 4 Heating Fan OFF Delay
INDOOR BLOWER
DIP SWITCH(ES)
FUNCTION
W914
W951
W915
THERMOSTAT CONNECTIONS (TB1)
1/4" QUICK CONNECT TERMINALS
H= 24V HUMIDIFIER OUTPUT L= LENNOX SYSTEM OPERATION MONITOR 1= FUTURE USE
NEUTRALS= 120 VAC NEUTRAL
FIGURE 25
Page 28
Page 28
Integrated Control Settings
G60UHV units are equipped with a two−stage, variable speed integrated control. This control manages ignition timing, heating mode fan off delays and indoor blower speeds based on selections made using the control dip switches and jumpers. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out. After one hour of con­tinuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and automatically reset the control to relight the furnace.
Heating Operation DIP Switch Settings Switch 1 −− Thermostat Selection −− This unit may be
used with either a single−stage or two−stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular application. TheDIP switch is factory−positioned for use with a two− stage thermostat. If a single−stage thermostat is to be used, the DIP switch must be repositioned.
a − Select OFF" for two−stage heating operation con-
trolled by a two−stage heating thermostat (factory set­ting);
b − Select ON" for two−stage heating operation con-
trolled by a single−stage heating thermostat. This set­ting provides a timed delay before second−stage heat is initiated.
Switch 2 −− Second Stage Delay (Used with Single− Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage ther­mostat is being used. The switch is factory−set in the OFF position, which provides a 10−minute delay before second− stage heat is initiated. If the switch is toggled to the ON position, it will provide a 15−minute delay before second− stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE− stage thermostat use.
Switches 3 and 4 −− Blower−Off Delay −− The blower−on delay of 45 seconds is not adjustable. The blower−off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated control. The unit is shipped from the factory with a blower−off delay of 90 seconds. The blower off delay affects comfort and is adjustable to satisfy individ­ual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter set­tings provide higher supply air temperatures.Table 11 pro­vides the blower off timings that will result from different switch settings.
TABLE 11
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3 Switch 4
60 Off On
90 Off Off 120 On Off 180 On On
Indoor Blower Operation DIP Switch Settings Switches 5 and 6 −− Cooling Mode Blower Speed −−
Switches 5 and 6 are used to select cooling blower motor speed. The unit is shipped from the factory with the dip switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below pro­vides the cooling mode blower speeds that will result from different switch settings. Refer to tables 16 through 25 for corresponding cfm values.
TABLE 12
Cooling Mode Blower Speeds
Speed
Switch 5 Switch 6
1 − Low On On
2 − Medium Low Off On
3 − Medium High On Off
4 − High (Factory) Off Off
Switches 7 and 8 −− Blower Speed Adjustment −−
Switches 7 and 8 are used to select blower speed adjust­ment settings. The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or −10% to better suit the application. The table below provides blower speed adjustments that will result from different switch settings. Refer to tables 16 through 25 for corresponding cfm values.
TABLE 13
Blower Speed Adjustment
Adjustment
Switch 7 Switch 8
+10% (approx.) On Off
NORMAL (Factory) Off Off
−10% (approx.) Off On
Switches 9 and 10 −− Cooling Mode Blower Speed Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramp­ing may be used to enhance dehumidification perfor­mance. The switches are factory set at option A which has the greatest effect on blower motor performance. Table 14 provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed on the next page.
NOTE − The off portion of the selected ramp profile also ap­plies during heat pump operation in dual fuel applications.
Page 29
Page 29
TABLE 14
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 9 Switch 10
A (Factory) Off Off
B On Off C Off On D On On
Ramping Option A (Factory Selection)
D Motor runs at 50% for 30 seconds. D Motor then runs at 82% for approximately 7−1/2 minu-
tes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 30 sec-
onds then ramps down to stop.
OFF
OFF
1/2 MIN 50% CFM
COOLING DEMAND
7 1/2 MIN 82% CFM
100% CFM
1/2 MIN 50% CFM
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFF
OFF
82%CFM
100% CFM
COOLING DEMAND
7 1/2 MIN
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 45 sec-
onds then ramps down to stop.
OFF
OFF
100% CFM
100% CFM
DEMAND
45 SEC.
Ramping Option D
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING DEMAND
Switches 11 and 12 −− Heating Mode Blower Speed −−
Switches 11 and 12 are used to select heating mode blower motor speed. The unit is shipped from the factory with the dip switches positioned for medium low (2) speed indoor blower motor operation during the heating mode. The table below provides the heating mode blower speeds that will result from different switch settings. Refer to tables 16 through 25 for corresponding cfm values.
TABLE 15
Heating Mode Blower Speeds
Speed
Switch 11 Switch 12
1 − Low On On
2 − Medium Low
(Factory)
Off On
3 − Medium High On Off
4 − High Off Off
On−Board Link W914
On−board link W914, is a clippable connection between ter­minals DS and R on the integrated control. W914 must be cut when the furnace is installed with either the Harmony IIIt zone control or a thermostat which features humidity control. If the link is left intact the PMW signal from the Har­mony III control will be blocked and also lead to control damage. Refer to table 27 for operation sequence in ap­plications including G60UHV, a thermostat which features humidity control and a single−speed outdoor unit. Table 28 gives the operation sequence in applications with a two− speed outdoor unit.
On−Board Link W951
On−board link W951 is a clippable connection between ter­minals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the link is left intact, terminal O" will remain ener­gized eliminating the HEAT MODE in the heat pump.
On−Board Link W915
On−board link W915 is a clippable connection between ter­minals Y1 and Y2 on the integrated control. W915 must be cut if two−stage cooling will be used. If the link is not cut the outdoor unit will operate in second−stage cooling only.
Status LEDs (SPEED, CFM, STATUS, E−COM)
The green SPEED LED indicates circulating blower speed in response to the DS signal. The LED is lit during normal blower operation and is off during a dehumidification de­mand. In Harmony III applications, the brightness of the LED indicates the requested blower speed.
The green CFM LED indicates the blower air flow. Count the number of blinks between the two−second pauses to determine the CFM. Each blink represents approximately 100 CFM.
The STATUS LED flashes diagnostic codes, which are de­tailed on page 43.
The green E−COM LED indicates that the control is receiv­ing and processing of commands and inputs. The LED may flash rapidly or may display a single flash, depending upon the activity.
Page 30
Page 30
TABLE 16
G60UHV−36A−070 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
895 420 1015 480 1275 600 1320 625 1000 470 1165 550 1260 595 1380 650
NORM 815 385 925 435 1120 530 1170 555 915 430 1035 490 1115 525 1230 580
740
350 845 400 1000 475 1040 490 830 390 945 445 990 470 1085 510
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
820 390 930 440 1140 540 1195 565 730 3455 810 385 865 410 910 430
NORM 755 355 855 405 1020 480 1060 500 670 315 745 350 785 370 850 400
695 325 775 365 920 435 965 455 630 295 690 325 725 340 770 365
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 426 cfm (200 L/s).
TABLE 17
G60UHV−36B−090 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
N/A N/A 1025 485 1265 600 1320 625 1005 475 1165 550 1260 595 1385 655
NORM N/A N/A N/A N/A 1125 530 1170 555 905 425 1035 490 1110 525 1225 580
N/A
N/A N/A N/A 1010 475 1045 495 825 390 940 445 1000 470 1090 515
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
N/A N/A 940 445 1140 540 1185 560 725 340 810 385 860 405 920 435
NORM N/A N/A N/A N/A 1030 485 1065 505 670 315 740 350 785 370 840 395
N/A N/A N/A N/A 925 435 950 450 625 295 695 330 725 345 770 365
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 453 cfm (215 L/s).
Page 31
Page 31
TABLE 18
G60UHV−60C−090 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1 2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1570 740 1770 835 1965 925 2185 1030 1680 795 1795 845 2015 950 2255 1065
NORM 1425 675 1625 765 1810 855 1990 940 1520 715 1635 770 1855 875 2065 975
1270
600 1435 680 1635 770 1790 845 1355 640 1460 690 1670 785 1845 870
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1430 675 1625 770 1815 855 1990 940 1170 550 1250 590 1425 670 1600 755
NORM 1290 610 1470 695 1660 780 1830 865 1060 500 1140 540 1280 605 1445 680
1165 550 1300 615 1470 695 1635 770 930 440 1015 480 1155 545 1285 605
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 478 cfm (225 L/s).
TABLE 19
G60UHV−60C−090 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1520 715 1705 805 1910 900 2120 1000 1605 760 1745 825 1955 925 2195 1035
NORM 1380 650 1540 730 1750 825 1925 910 1475 695 1565 740 1785 840 1985 935
1230
580 1395 660 1570 740 1745 825 1305 615 1410 665 1590 750 1795 845
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1385 655 1560 735 1765 835 1945 920 1125 530 1210 570 1370 650 1525 720
NORM 1255 590 1425 670 1580 745 1785 840 1020 480 1100 520 1235 580 1385 655
1135 535 1265 600 1430 675 1570 740 890 420 980 465 1115 525 1235 580
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 478 cfm (225 L/s).
Page 32
Page 32
TABLE 20
G60UHV−60C−090 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Side return air with optional RAB return air base.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1 2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1505 710 1690 800 1900 895 2090 985 1625 765 1715 810 1940 915 2175 1030
NORM 1370 645 1535 725 1745 825 1915 905 1450 685 1560 735 1765 835 1945 915
1215
575 1375 650 1535 725 1705 805 1310 620 1405 660 1595 755 1795 850
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1370 650 1540 725 1745 825 1925 910 1130 530 1205 570 1360 645 1530 720
NORM 1240 585 1405 665 1565 740 1765 830 1025 485 1100 520 1240 585 1385 655
1135 535 1265 600 1420 670 1560 735 900 425 985 465 1115 525 1240 585
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 478 cfm (225 L/s).
TABLE 21
G60UHV−60C−110 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1510 715 1700 805 1895 895 2105 995 1610 760 1730 815 1955 920 2185 1030
NORM 1365 645 1545 730 1725 815 1915 905 1460 690 1575 745 1780 840 1995 940
N/A
N/A 1375 650 1545 730 1715 810 1295 610 1395 660 1600 755 1780 840
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1370 650 1560 735 1750 825 1925 910 1125 530 1190 565 1350 640 1530 720
NORM 1245 585 1410 665 1590 750 1760 830 1015 480 1090 515 1230 580 1360 640
N/A N/A 1255 595 1420 670 1575 745 900 425 975 460 1110 525 1235 580
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 483 cfm (230 L/s).
Page 33
Page 33
TABLE 22
G60UHV−60C−110 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1 2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1540 725 1750 825 1945 915 2170 1025 1635 770 1760 830 1995 940 2225 1050
NORM 1385 655 1635 770 1785 845 1960 925 1485 700 1610 760 1820 860 2035 960
1230
580 1390 655 1585 750 1760 830 1310 620 1415 665 1620 765 1815 855
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1390 655 1595 750 1785 845 1955 925 1140 540 1215 575 1370 645 1555 735
NORM 1255 590 1425 675 1615 765 1800 850 1030 485 1105 520 1245 585 1400 660
1135 535 1265 600 1435 675 1610 760 925 435 990 470 1125 530 1255 595
NOTES − The effect of static pressure included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 483 cfm (230 L/s).
TABLE 23
G60UHV−60C−110 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Side return air with optional RAB return air base.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1490 705 1680 790 1875 885 2085 985 1620 765 1735 820 1950 920 2185 1030
NORM 1340 635 1525 720 1715 810 1885 890 1470 695 1595 750 1780 840 1975 935
N/A
N/A 1350 635 1525 720 1700 805 1305 615 1400 660 1605 760 1785 845
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1375 650 1570 740 1765 830 1935 915 1017 480 1075 510 1375 650 1540 725
NORM 1255 590 1425 670 1570 740 1750 825 1025 485 1100 520 1235 585 1385 655
N/A N/A 1255 590 1415 665 1880 885 920 435 990 470 1000 470 1110 525
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 483 cfm (230 L/s).
Page 34
Page 34
TABLE 24
G60UHV−60D−135 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1470 695 1665 785 1855 875 2050 970 1575 745 1695 800 1900 900 2140 1010
NORM 1335 630 1520 715 1695 800 1870 885 1430 675 1540 725 1745 825 1945 920
N/A
N/A 1340 630 1510 710 1675 790 1275 600 1370 645 1565 740 1735 820
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1345 635 1520 715 1710 805 1880 890 1100 520 1180 560 1330 625 1495 705
NORM 1220 575 1375 650 1545 730 1725 815 1000 475 1075 510 1205 570 1350 635
N/A N/A 1230 580 1380 650 1535 725 900 425 670 455 1095 515 1210 570
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 495 cfm (235 L/s).
TABLE 25
G60UHV−60D−135 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1
2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1405 665 1600 755 1775 840 1965 925 1500 705 1620 765 1815 860 2040 965
NORM N/A N/A 1440 680 1635 770 1800 850 1360 645 1470 695 1660 785 1860 875
N/A
N/A N/A N/A 1445 685 1620 765 1225 580 1310 620 1490 705 1670 785
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1285 605 1450 685 1635 770 1800 850 1075 505 1150 545 1275 605 1425 675
NORM N/A N/A 1325 625 1485 700 1660 785 955 450 1040 490 1165 550 1300 615
N/A N/A N/A N/A 1325 625 1460 690 870 410 930 440 1065 500 1175 555
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 495 cfm (235 L/s).
Page 35
Page 35
TABLE 26
G60UHV−60D−135 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Side return air with optional RAB return air base.
Speed Switch Positions
ADJUST"
Second Stage HEAT" Speed Second Stage COOL" Speed
Switch
Positions
1 2 3 4 1 2 3 4
Positions
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1425 675 1615 760 1795 845 1975 930 1505 710 1620 765 1815 855 2035 960
NORM N/A N/A 1455 690 1640 775 1805 850 1370 650 1470 695 1670 790 1850 875
N/A
N/A N/A N/A 1455 685 1630 770 1225 580 1320 625 1500 705 1670 790
"
First Stage HEAT" Speed First Stage COOL" Speed
ADJUST"
Switch
1 2 3 4 1 2 3 4
Stc
Positions
cfm
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
1305 615 1470 695 1655 780 1825 860 1075 510 1155 545 1295 610 1445 680
NORM N/A N/A 1345 635 1505 710 1670 790 980 465 1050 495 1175 555 1305 615
N/A N/A N/A N/A 1340 635 1475 695 875 415 935 440 1070 505 1180 555
N/A − First and second stage HEAT positions shown cannot be used on this model. NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s). Lennox Harmony IIIt Zone Control Applications − Minimum blower speed is 495 cfm (235 L/s).
TABLE 27
OPERATING SEQUENCE
G60UHV, Thermostat with Humidity Control Feature and Single−Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System Condition
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
Blower
CFM
(COOL)
Comments
Normal operation Y1
No demand. Humidity
level is acceptable
COOL
Compressor demand and indoor blower speed controlled by thermostat demand.
*Call for humidity
removal during
cooling demand
Y1
Humidity level rises
above setpoint. Demand
initiated.
60%/65%
of COOL
Call for dehumidification initiated by ther­mostat. Indoor blower speed reduced by thermostat.
Dehumidification
demand satisfied
during cooling de-
mand.
Y1
Humidity level falls below
setpoint. No demand
COOL
When humidity demand is satisfied, blow­er speed immediately increases to the COOL CFM to hasten the end of the cycle.
Call for cooling after
None
Humidity level above set-
point. Demand initiated.
Off
Dehumidification mode begins when rela-
call for humidity
removal.
Y1
Humidity level above set-
point. Demand initiated.
60%/65%
of COOL
Dehumidification mode begins when rela
tive humidity is greater than setpoint.
Humidity demand satisfied between
None Over setpoint (1 or more) Off
While unit is not operating (no thermostat
satisfied between
thermostat demands
(unit off cycle).
Y1 Change to acceptable COOL
d
emand), s
lid
e switch is moved down an
d
back up. Blower operates at COOL CFM.
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther­mostat heating demand. * Reduced blower speed is 65% of COOL for the −36A and −36B units; 60% of COOL for −60C and −60D series units.
Page 36
Page 36
TABLE 28
OPERATING SEQUENCE
G60UHV, Thermostat with Humidity Control Feature and Two−Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
****Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Y1 No demand. Acceptable Low
**42%/46% of
HIGH COOL
Compressor demand and indoor
blower s
p
eed controlled by
Normal operation
Y2 No demand. Acceptable High HIGH COOL
blower speed controlled by
thermostat demand
Y1 No demand. Acceptable Low
**42%/46% of
HIGH COOL
Call for humidity
Y1
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
Low
**42%/46% of
HIGH COOL
Dehumidification mode does not begin
removal during
1st−stage cooling
demand
Demand
satisfied
Humidity level remains
slightly (1) above setpoint.
Demand continues.
Off
Off
until after initial thermostat demand is
satisfied and new cooling demand is
initiated.
Y1
Humidity level remains
slightly (1) above setpoint.
Demand continues.
High
***65%/60% of
HIGH COOL
Significant increase in
Y1
No demand. Acceptable
Low
**42%/46% of
HIGH COOL
If humidity rises significantly above set­point, or if slide switch is moved signifi-
humidity duri
ng
thermostat cooling
demand.
Y1
Humidity level rises signifi-
cantly (2 or more) above
setpoint. Demand initiated.
High
***65%/60% of
HIGH COOL
point, or if slide switch is moved signifi
cantly, unit will immediately go into de-
humidification mode (in presence of
thermostat demand).
Y1
Humidity level
above setpoint.
High
***65%/60% of
HIGH COOL
When humidity demand is satisfied,
Humidity demand
satisfied durin
g
Y1
Humidity level falls below
setpoint. No demand.
High
HIGH COOL
When humidity demand is satisfied,
blower immediately shifts to the COOL
CFM in order to hasten the end of the
satisfied during
thermostat demand.
None
No demand. Acceptable
Off
Off
cycle. Unit can only shift out of high
speed compressor operation at begin-
Y1
No demand. Acceptable
Low
**42%/46% of
HIGH COOL
speed compressor operation at begin
ning of next cycle.
Y2
No demand. Acceptable
High
HIGH COOL
Call for humidity
removal during 2nd
stage thermostat
Y2
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
High
***65%/60% of
HIGH COOL
Blower immediately changes speed in
response to thermostat demand.
d
eman
d
Y2
No demand. Acceptable
High
HIGH COOL
*Call for 1st stage
None
Humidity level is slightly (1)
above setpoint.
Off
Off
Dehumidification mode (high speed
compressor) begins with next thermo-
cooling after call for
humidity removal.
Y1
Humidity level is slightly (1)
above setpoint.
Low
**42%/46% of
HIGH COOL
compressor) begins with next thermo
stat demand after initial demand is sat-
isfied.
Call for 2nd stage
None
Humidity level is slightly (1)
above setpoint.
Off
Off
Reduced blower speed (dehumidifica-
cooling after call for
humidity removal
Y2
Humidity level is slightly (1)
above setpoint.
High
***65%/60% of
HIGH COOL
tion speed) begins immediately with
thermostat demand
Call for cooling after
None
Humidity level is significantly
above setpoint (2 or more).
Off
Off
If humidity increases significantly over
setpoint, or if slide switch is moved,
significant increase in
humidity
Y1 or Y2
Humidity level is significantly
above setpoint (2 or more).
High
***65%/60% of
HIGH COOL
unit immediately goes into dehumidifi-
cation mode (in presence of thermostat
demand).
Humidity demand satisfied between
None
Humidity level is slightly (1)
above setpoint.
Off
Off
While unit is not operating (no thermo-
stat demand), slide switch is moved
satisfied between
thermostat demands
(unit off cycle).
Y1 or Y2
Humidity level falls below
setpoint. No demand.
High
HIGH COOL
down and back up. Blower and com-
pressor operate at high speed until
next thermostat demand.
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther­mostat heating demand.
*IMPORTANT - If power to unit is turned on with thermostat calling for humidity removal, outdoor unit may be locked into high speed indefinitely. To reset, move humidity slide switch all the way down then back up to desired setpoint (with unit running) ** Reduced blower speed is 42% of HIGH COOL for −36A and −36B units; 46% of HIGH COOL for −60C and −60D series units. *** Reduced blower speed is 65% of HIGH COOL for −36A and −36B units; 60% of HIGH COOL for −60C and −60D series units. ****If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compres­sor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 37
Page 37
Unit Start−Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been underwa­ter. Immediately call a licensed professional service technician (or equivalent) to inspect the furnace and to replace any part of the control system and any gas control which has been under water.
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch.
WARNING
During blower operation, the ECM motor emits ener­gy that may interfere with pacemaker operation. In­terference is reduced by both the sheet metal cabinet and distance.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
The gas valve on the G60UHV(X) unit may be equipped with either a gas control knob or gas control switch. Use only your hand to move the control switch or to turn the gas control knob. Never use tools. If the knob will not turn or if the control switch will not move by hand, do not try to repair it. Call a licensed professional service technician (or equiv­alent). Force or attempted repair may result in a fire or ex­plosion.
Placing the furnace into operation:
G60UHV(X) units are equipped with an automatic ignition system. Do not attempt to manually light burners on these furnaces. Each time the thermostat calls for heat, the burn­ers will automatically light. The ignitor does not get hot when there is no call for heat on units with an automatic ignition system.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figures 26 and 27)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit. 4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand. 5 − Remove the upper access panel. 6 − White Rodgers 36E Gas Valve − Move gas valve con-
trol switch to OFF. See figure 26.
Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise
to OFF. Do not force. See figure
27.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.
WHITE RODGERS 36E SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
HIGH FIRE MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
TAP ON SIDE
INLET PRESSURE
TAP ON SIDE
LOW FIRE MANIFOLD
PRESSURE ADJUSTMENT
ON SIDE (under cap)
FIGURE 26
HONEYWELL VR8205 SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
TAP
HIGH FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE
TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
FIGURE 27
8 − White Rodgers 36E Gas Valve − Move gas valve con-
trol switch to ON. See figure 26.
Honeywell VR8205 Gas Valve − Turn knob on gas
valve counterclockwise
to ON. Do not force. See
figure 27. 9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.
Page 38
Page 38
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service techni­cian or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting. 2 − Turn off all electrical power to the unit if service is to be
performed. 3 − Remove the upper access panel. 4 − White Rodgers 36E Gas Valve − Move gas valve con-
trol switch to OFF.
Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise
to OFF. Do not force.
5 − Replace the upper access panel.
Gas Pressure Adjustment
Gas Flow
To check for proper gas flow to the combustion chamber, determine the Btu (kW) input from the unit nameplate. Di­vide this input rating by the Btu (kW) per cubic foot (cubic meter) of available gas. The result is the required number of cubic feet (cubic meter) per hour. Determine the flow of gas through the gas meter for two minutes and multiply by 30 to get the hourly flow of gas.
Gas Pressure
1 − Check the gas line pressure with the unit firing at maxi-
mum rate. A minimum of 4.5 in. w.c. for natural gas or
11.0 in. w.c. for LP/propane gas should be maintained.
2 − After the line pressure has been checked and ad-
justed, check the low fire and high fire manifold pres-
sures. See figures 26 and 27 for the location of the
manifold pressure adjustment screws. Low and high
fire manifold pressures are given in table 29. A natural
gas to LP/propane gas changeover kit is required to
convert the unit.
High Altitude Information
Refer to table 29 for high altitude requirements and man­ifold pressure settings at all altitudes.
NOTE − In Canada, certification for installations at eleva­tions over 4500 feet (1372 m) is the jurisdiction of local au­thorities.
NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo­cated in the blower compartment, attached to the back side of the blower. These limits are factory set and require no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on (or inside of) the burner box. If tripped, check for adequate combustion air before resetting.
Pressure Switches
The pressure switch assembly (includes two switches) is located in the heating compartment adjacent to the com­bustion air inducer. These switches check for proper com­bustion air inducer operation before allowing ignition trial. The switches are factory−set and require no adjustment.
Temperature Rise
Place the unit into operation with a second−stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature rise. Decrease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.
TABLE 29
High Altitude Requirements / Manifold Pressure Settings
Altitude
Model
Input
Gas
0 − 7500 ft.
(0 − 2285 m)
7501−10,000 ft.
(2286 − 3048 m)
Manifold Pressure
at all altitudes
Input
Size
Gas
Required Pressure Required Pressure
Low Fire High Fire
Required
Conversion Kit
Pressure
Switch
Required
Conversion Kit
Pressure
Switch
in. w.g. kPa in. w.g. kPa
−070, −090,
Nat. N/A No Change 44W51 18M64 1.7 0.42 3.5 0.87
−070, −090
,
−110, −135
LPG 44W48 No Change 44W50 18M64 4.9 1.22 10.0 2.5
Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0−7500 feet (0−2285 m).
Page 39
Page 39
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the air ducts or structure.
Electronic Ignition
The two−stage, variable speed integrated control used in G60UHV units has an added feature of an internal Watch­guard control. The feature serves as an automatic reset de­vice for ignition control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the control to begin the ignition sequence.
Flue And Chimney
1 − Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage. 2 − Check unit for proper draft. 3 − Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and outlet
for blockages. 4 − Reset manual flame rollout switches on burner box.
Failure To Operate
If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse or tripped circuit breaker? 5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the unit
for blockages.
Heating Sequence of Operation
NOTE − The ignition control thermostat selection DIP switch is factory−set in the TWO−STAGE" position.
Applications Using a Two−Stage Thermostat
A − Heating Sequence −− Integrated Control Thermostat Selection DIP Switch in Two−Stage" Position (Factory Setting)
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the 120 VAC humidifier termi­nal is energized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be­gins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the
gas valve is energized on low fire (first stage) and igni­tion occurs. At the same time, the control module sends a signal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is energized on the low fire heating speed and the 24V humidifier terminal is energized. The furnace will continue this operation as long as the thermostat has a first−stage heating demand.
5 − If second−stage heat is required, the thermostat sec-
ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.
6 − At the end of the recognition delay, the integrated con-
trol energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed.The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed.
7 − When the demand for high fire (second stage) heat is
satisfied, thecombustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.
8 − When the thermostat demand for low−fire (first stage)
heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.
9 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminals are de−en­ergized. The indoor blower is de−energized at the end of the off delay.
Applications Using A Single−Stage Thermostat
B − Heating Sequence −− Integrated Control Thermostat Selection DIP Switch in Single−Stage" Position
NOTE − In these applications, two−stage heat will be initi­ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the 120 VAC humidifier termi­nal is energized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be­gins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
Page 40
Page 40
4 − After the 20−second warm−up period has ended, the
gas valve is energized on low fire (first stage) and igni­tion occurs. At the same time, the control module sends a signal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is energized on the low fire heating speed and the 24V humidifier terminal is energized. The inte­grated control also initiates a second−stage on delay (factory−set at 10 minutes; adjustable to 15 minutes).
5 − If the heating demand continues beyond the second−
stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed.The high fire (second stage) gas valve is energized and the indoor blower motor is en­ergized for operation at the high fire heating speed.
6 − When the thermostat heating demand is satisfied, the-
combustion air inducer begins a 5−second low speed post−purge. The field−selected indoor blower off delay begins. The indoor blower operates at the low−fire heating speed.
7 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminals are de−en­ergized. The indoor blower is de−energized at the end of the off delay.
Service
WARNING
Disconnect power before servicing unit.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after ser­vicing.
At the beginning of each heating season, a licensed profes­sional service technician (or equivalent) should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
All G60UHV(X) filters are installed external to the unit. Fil­ters should be inspected monthly. Clean or replace the fil­ters when necessary to ensure that the furnace operates properly. Replacement filters must be rated for high veloc­ity airflow. Table 1 lists recommended filter sizes.
Flue And Chimney
Check the flue pipe, chimney and all connections for tight­ness and to make sure there is no blockage.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Cleaning the Heat Exchanger and Burners
NOTE − Use papers or protective covering in front of the fur­nace during cleaning.
Cleaning the heat exchanger requires a steel spring snake," a reversible drill and a vacuum cleaner. The steel spring snake may be constructed by purchasing a 4 ft. long by 1/4 inch diameter steel wire cable and a 1/4 inch diame­ter wire brush. These items are available at a hardware store. Insert wire end of brush into the open end of the spring cable. Crimp the cable around the brush so that the brush is secured and will not come off during cleaning. At­tach the other end of the cable to the reversible drill to com­plete the tool for cleaning the heat exchanger.
1 − Turn off both electrical and gas power supplies to fur-
nace.
2 − Remove flue pipe and top cap from the unit. Label the
pressure switch wires, then disconnect them.
3 − Remove the four screws that secure the combustion
air inducer. Carefully remove the combustion air induc­er to avoid damaging blower gasket. If gasket is dam­aged, it must be replaced to prevent leakage. See fig­ure 1.
4 − Remove the collector box located behind the combus-
tion air inducer. Be careful with the collector box gas­ket. If the gasket is damaged, it must be replaced to prevent leakage.
5 − Label the wires from gas valve and rollout switches,
then disconnect them.
6 − Remove the four screws securing the burner box cover
and remove the cover.
7 − Disconnect gas supply piping. Remove six screws se-
curing the burner box / manifold assembly to the vesti­bule panel and remove the assembly from the unit. Take care not to damage the gasket.
8 − NOx units only Remove the three screws that attach
the NOx insert to the corbel at the entrance to each heat exchanger section. Carefully remove the NOx in­sert from each section. See figure 29.
9 − Insert the brush end of cable snake into the top of one
of the heat exchanger openings. Do not force the cable into the heat exchanger. Insert the cable and operate the drill on slow speed. Move the cable in and out of the heat exchanger section three or four times or until sufficient cleaning is accomplished. Reverse drill and slowly work the cable out of opening.
Page 41
Page 41
G60UHV(X) BURNER & HEAT EXCHANGER REMOVAL
FIGURE 28
HEAT EXCHANGER
BURNER BOX
ASSEMBLY
GAS VALVE ASSEMBLY
GASKET
NOx INSERTS
(X models only)
FIGURE 29
NOx INSERT
10− Repeat procedure for each heat exchanger section. 11− After each of the top heat exchanger sections has been
cleaned, insert the brush end of the cable snake into
the bottom openings of each of the heat exchanger
sections and clean as described in step 8.
12− Remove the cable from the heat exchanger. Use a vac-
uum cleaner to remove debris knocked loose during cleaning.
13− Attach the exhaust end (positive pressure) of the vacu-
um cleaner to the top of the heat exchanger section. Any loose debris will be forced to the bottom of the heat exchanger section. Vacuum debris from bottom open­ings.
14− Replace collector box and combustion air inducer.
Check gaskets for damage. Damaged gaskets must be replaced to avoid heat exchanger leaks. Replace all screws to the collector box and combustion air inducer. Failure to replace all screws may cause leaks.
15− To clean the burner, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually in­spect inside the burners and crossovers for any block­age caused by foreign matter. Remove any blockage.
16− NOx units only Reattach the NOx inserts to the cor-
bels at the entrance to each heat exchanger opening. See figure 29.
17− Re−install gasket and burner box / manifold assembly
onto the vestibule panel. Replace burner box cover and re−secure using screws.
NOTE − Gasket must be replaced if it was damaged during disassembly.
18− Reconnect wires to pressure switch, roll−out switches,
gas valve and combustion air inducer. Refer to unit wir­ing diagram.
19− Re−install top cap and re−secure vent pipe to combus-
tion air inducer outlet.
20− Reconnect gas supply piping.
21− Turn on power and gas supply to unit.
22− Set thermostat and check for proper operation.
23− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred means.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af­ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.
24− If a leak is detected, shut gas and electricity off and re-
pair leak.
25− Repeat steps 23 and 24 until no leaks are detected.
26− Replace front access panel.
Page 42
Page 42
Planned Service
The following items should be checked during an annual in­spection. Power to the unit must be shut off for the service technician’s safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob­structed to provide combustion air.
Burners − Must be inspected for rust, dirt, or signs of water.
Vent pipe − Must be inspected for signs of water, damaged
or sagging pipe, or disconnected joints.
Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door − Must be properly in place and pro­vide a seal between the return air and the room where the furnace is installed.
Return air duct − Must be properly attached and provide an air seal to the unit.
Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.
Combustion gases − Flue products must be analyzed and compared to the unit specifications.
Problems detected during the inspection may make it nec­essary to temporarily shut down the furnace until the items can be repaired or replaced.
Pay attention to your furnace. Situations can arise be­tween annual furnace inspections that may result in unsafe operation.
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA International nameplate −− Example: G60UHV(X)−36A−070−7.
Cabinet Parts
Upper access panel Blower panel Top cap
Control Panel Parts
Transformer Two−stage, variable speed integrated control Door interlock switch Circuit breaker
Blower Parts
Blower wheel Blower housing Motor Motor electronics Power choke (1 hp only) Motor mounting frame Motor capacitor Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly Gas manifold Two−speed combustion air inducer Two−stage gas valve Main burner cluster Main burner orifices Pressure switch Ignitor Primary limit control Flame rollout switch
Secondary limit
Page 43
Page 43
Integrated Control Diagnostic Codes (Red LED)
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
Pulse A 1/4 second flash followed by four seconds of off time.
Heartbeat Constant 1/2 second bright and 1/2 second dim cycles.
X + Y
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four seconds, then repeats.
Pulse Power on − Standby.
Heartbeat Normal operation − signaled when heating demand initiated at thermostat.
FLAME CODES
1 + 2 Low flame current −− run mode.
1 + 3 Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3 Low pressure switch failed open.
2 + 4 Low pressure switch failed closed.
2 + 5 High pressure switch failed open.
2 + 6 High pressure switch failed closed.
2 + 7 Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1 Limit switch open.
WATCHGUARD CODES
4 + 1 Watchguard −− Exceeded maximum number of retries.
4 + 2 Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3 Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5 Watchguard −− Limit remained open longer than three minutes.
4 + 6
Watchguard −− Flame sensed out of sequence; flame signal gone.
4 + 7 Ignitor circuit fault −− Failed ignitor or triggering circuitry.
4 + 8 Low line voltage.
HARD LOCKOUT CODES
5 + 1 Hard lockout −− Rollout circuit open or previously opened.
5 + 2 Control failed self check, internal error (control will restart if error recovers).
5 + 3 No Earth ground (control will restart if error recovers).
5 + 4 Reversed line voltage polarity (control will restart if the error recovers).
5 + 6 Low secondary (24VAC) voltage.
Page 44
Page 44
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.)
NO
POLARITY REVERSED.
STATUS ERROR CODE 5 + 4.
POWER ON
POLARITY OKAY?
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
STATUS ERROR CODE 5 + 3.
IS THERE A
PROPER GROUND?
NO
YES
A
NORMAL OPERATION:
STATUS LED −− PULSE
B
THERMOSTAT CALLS FOR HEAT:
STATUS LED −− HEARTBEAT
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
NO
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON. HAS PRIMARY OR
SECONDARY LIMIT RESET WITHIN 3 MINUTES?
STATUS ERROR CODE 3 + 1.
ROLLOUT SWITCH CLOSED?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.
NO
YES
FIRST (LOW) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
STATUS ERROR CODE 2 + 4
YES
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
CONTROL WILL NOT ATTEMPT SECOND−STAGE
OPERATION DURING THIS HEAT DEMAND.
FIRST−STAGE OPERATION WILL BE ATTEMPTED.
STATUS ERROR CODE 2 + 6.
NO
TWO−STAGE OR SINGLE−STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
STATUS LED −− HEARTBEAT
CONTINUED ON NEXT PAGE
NO
NO
60−MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5.
YES
NO
YES
SECOND (HIGH) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
YES
Page 45
Page 45
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
FIRST−STAGE (LOW FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
STATUS ERROR CODE 2 + 3.
YES
NO
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED
FIRST−STAGE PRESSURE SWITCH (or 15
SECOND INTER−PURGE PERIOD.)
STATUS LED −− HEARTBEAT.
IGNITOR WARM−UP (20 SECONDS)
STATUS LED −− HEARTBEAT.
IS VOLTAGE ABOVE 90 VOLTS?
NO
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95
VOLTS. STATUS ERROR CODE 4 + 8.
YES
NO
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED
OR RECONNECTED.
STATUS ERROR CODE 4 + 7.
YES
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
YES
4−SECOND FLAME STABILIZATION PERIOD.
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.20 microamps)
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
STATUS LED −− HEARTBEAT.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
THERMOSTAT CALLS FOR HEAT
STATUS LED − HEARTBEAT.
(Refer to box A on previous page)
YES
FLAME PRESENT?
NO
HAS CONTROL RESET IGNITION SEQUENCE
FOUR (4) TIMES?
WATCHGUARD MODE.
STATUS ERROR CODE 4 + 3.
YES
CONTINUED ON NEXT PAGE
YES
NO
NO
CONTINUED
IS IGNITOR INTACT AND CONNECTED?
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
STATUS ERROR CODE 4 + 1.
IS 60−MINUTE RESET PERIOD COMPLETE?
NO
YES
Page 46
Page 46
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
LOW FLAME SIGNAL
(Does not affect control operation)
STATUS ERROR CODE 1 + 2.
FLAME SIGNAL ABOVE
(u1.40 microamps)
NO
YES
CONTINUED ON NEXT PAGE
YES
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
TWO STAGE THERMOSTAT MODE
(DIP SWITCH SET AT TWO")
YES
YES
START SECOND−STAGE RECOGNITION
ON DELAY (10 OR 15 MINUTES).
STATUS LED −− HEARTBEAT
45−SECOND INDOOR BLOWER ON DELAY BEGINS.
STATUS LED −− HEARTBEAT.
YES
YES
PRIMARY & SECONDARY LIMIT SWITCHES
CLOSED?
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER ON.
STATUS ERROR CODE 3 + 1.
HAS PRIMARY OR SECONDARY LIMIT SWITCH CLOSED WITHIN 3 MINUTES?
(Indoor blower on low speed during 3−minute period)
FIRST−STAGE (LOW FIRE)
PRESSURE SWITCH CLOSED?
LIMIT SWITCH WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5
IS 60−MINUTE RESET PERIOD COMPLETE?
THERMOSTAT CALLS FOR HEAT.
STATUS LED −− HEARTBEAT.
SEE BOX A.
NO
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF AFTER DELAY.
STATUS ERROR CODE 2 + 3. CONTROL RESTARTS
IGNITION SEQUENCE IF PRESSURE SWITCH
CLOSES WITHIN 2−1/2 MINUTES.
NO
YES
FIRST−STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
STATUS LED −− PULSE
YES
SECOND−STAGE HEAT DEMAND.
SECOND−STAGE HEAT DEMAND REQUIRED?
NO
SECOND STAGE PRESSURE SWITCH CLOSED?
ABNORMAL FLASH CODE.
NOTE − IF SECOND−STAGE PRESSURE SWITCH
WAS ORIGINALLY FOUND CLOSED,
ABNORMAL CODE WILL FLASH.
SECOND−STAGE PRESSURE SWITCH CLOSED
AT BEGINNING OF HEAT DEMAND?
STATUS ERROR CODE 2 + 6.
YES
NO
SECOND−STAGE 30−SECOND DELAY ON BEGINS.
STATUS LED −− HEARTBEAT.
SECOND−STAGE COMBUSTION AIR INDUCER
ON. SECOND−STAGE GAS VALVE ON. HIGH
HEAT INDOOR BLOWER SPEED ON.
STATUS LED −− HEARTBEAT.
YES
SECOND−STAGE PRESSURE SWITCH CLOSED
IN LESS THAN TEN (10) SECONDS?
STATUS LED −− HEARTBEAT
YES
NO
RETURNS TO FIRST−STAGE HEAT MODE WHICH
CONTINUES UNTIL SECOND−STAGE PRESSURE
SWITCH CAN BE PROVEN or HEAT DEMAND IS
SATISFIED. FIVE (5) MINUTE WAIT PERIOD
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS
MADE FOR SECOND−STAGE HEAT?
YES
CONTINUES FIRST−STAGE HEATING
DEMAND. WILL NOT REATTEMPT
SECOND−STAGE HEATING DEMAND.
STATUS ERROR CODE 2 + 5.
SECOND STAGE HEAT DEMAND
STATUS LED −− HEARTBEAT.
NO
YES
NO
YES
CONTINUED
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS
UNTIL ROLLOUT SWITCH IS RESET AND MAIN
POWER IS INTERRUPTED OR THERMOSTAT
IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.
ROLLOUT SWITCHES CLOSED?
NO
YES
YES
NO
YES
YES
Page 47
Page 47
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
SEE BOX B
THERMOSTAT CALLS FOR HEAT.
SEE BOX A
NORMAL OPERATION.
YES
NO
RETURN TO FIRST−STAGE HEAT MODE.
FIRST−STAGE CONTINUES UNTIL SECOND−
STAGE PRESSURE SWITCH CAN BE PROVEN
or HEAT DEMAND IS SATISFIED. A FIVE (5)
MINUTE WAIT PERIOD IS INITIATED BEFORE
RETRY. WERE 5 ATTEMPTS MADE FOR
SECOND−STAGE HEAT?
YES
NO
SEE BOX C
FIRST−STAGE HEAT DEMAND SATISFIED?
HEAT DEMAND SATISFIED?
STATUS LED −− HEARTBEAT.
YES
TWO STAGE THERMOSTAT MODE?
(DIP SWITCH SET AT TWO")
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
YES
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
STATUS LED −− HEARTBEAT.
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5−SECOND
LOW SPEED POST PURGE PERIOD,
INDOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
STATUS LED −− HEARTBEAT.
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY.
STATUS LED −− PULSE.
YES
SECOND STAGE HEAT DEMAND SASTISFIED?
STATUS LED −− HEARTBEAT.
NO
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST−
STAGE OPERATION.
STATUS LED −− HEARTBEAT.
YES
FIRST STAGE HEAT DEMAND SATISFIED?
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5−SECOND LOW SPEED POST−
PURGE PERIOD. INDOOR BLOWER OFF. DELAY INITIATED ON LOW HEAT SPEED.
STATUS LED −− PULSE.
CONTINUED
SECOND−STAGE (HIGH FIRE) HEAT
PRESSURE SWITCH CLOSED?
Page 48
Page 48
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
SIGNAL POLARITY REVERSED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.
POWER ON
YES
IS POLARITY REVERSED?
THERMOSTAT CALLS FOR FIRST−STAGE COOL.
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
NO
IS THERE
PROPER GROUND?
YES
NO
INDOOR BLOWER ENERGIZED ON FIRST STAGE
COOL SPEED AFTER 2 SECOND DELAY.
FIRST−STAGE DEMAND FOR COOL SATISFIED?
NO
THERMOSTAT CALLS FOR SECOND−STAGE COOL.
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
INDOOR BLOWER DE−ENEGIZED.
YES
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 3.
Page 49
Page 49
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
YES
AFTER 45−SECOND DELAY, INDOOR BLOWER
SWITCHES TO LOW HEAT SPEED.
FIRST−STAGE HEAT DEMAND SATISFIED.
YES
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
FIRST−STAGE COOL DEMAND SATISFIED?
YES
NO
SECOND STAGE COOL DEMAND SATISFIED?
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
YES
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
YES YES
Page 50
Page 50
G60UHV(X) Start−Up & Performance Check List
w.c. − LP/Propane
Filter Clean & Secure?
Line Voltage
Electrical Connections Tight?
Job Name
Job Location
Installer
Unit Model No.
Furnace Btu Input (High fire) Line Pressure
Job No.
City
City
Serial No.
Date
State
Technician
Flue Connections Tight?
Heating Section
Thermostat
Heat Anticipator Setting? Thermostat Level?
Fuel Type: Natural Gas?
Blower Motor Amps
Blower Motor H.P.
Gas Piping Connections Tight & Leak−Tested?
Proper Draft?
State
Blower OFF Delay Setting (60, 90, 120 or 180)?
Blower ON delay confirmed? (45 Seconds Fixed On)
High Fire Manifold Pressure
w.c. − Nat.:
LP/Propane Gas?
Combustion Gas Tested (high fire and low fire)?
CO
2
CO
w.c. − LP/Propane
Low Fire Manifold Pressure
w.c. − Nat.:
Temperature Rise
External Static Pressure? (0.8 maximum)
Loading...