Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
01/10
*2P0110*
WARNING
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in serious injury, death,
or property damage.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance.
D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately.
D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
D If you cannot reach your gas supplier, call
the fire department.
Page 1
*P506176-01*
506176−01
Page 2
G60UH(X) Unit Dimensions − inches (mm)
*NOTE − 60C and 60D units that require air volumes over
1800 cfm (850 L/s) must have one of the following:
1. Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm)
cleanable air filter. (Required to maintain proper air
velocity.)
2. Return air from single side with optional RAB Return
Air Base.
3. Return air from bottom.
4. Return air from both sides.
5. Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
**Flue outlet may be horizontal but furnace must be
vented vertically
Optional external side return air filter kit cannot be used
with the optional RAB Return Air Base.
A
B9/16 (14)
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
40
(1016)
3−3/4 (95)
D
FLUE OUTLET
(Top)
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
3−1/4 (83) Right
8−1/8 (206) Left
14 (356) Right
13−1/4 (337) Left
4−7/8 (124) Right
2−1/4 (57) Left
TOP VIEW
3−3/4
(95)
SUPPLY AIR
OPENING
23-3/4 (603)
25 (635)
TOP VIEW
28−1/2
(724)
19−7/16
(494)
**FLUE OUTLET
(Either Side)
ELECTRICAL INLET
(Either Side)
GAS PIPING INLET
(Either Side)
ELECTRICAL INLET
(Either Side)
9/16
(14)
14−3/4
AIR FLOW
3/4 (19)
C
3/4 (19)
*Bottom Return
Air Opening
FRONT VIEWSIDE VIEW
Model No.
G60UH−24A−070,
G60UH−36A−070
G60UH−36B−090,
G60UH−48B−090
G60UH−36C−110,
G60UH−48C−110,
G60UH−60C−110
G60UH−60D−13524−1/262223−3/8546235849−1/2241
14−1/236813−3/8340133304−1/211 4
17−1/244616−3/8416164066152
ABCD
in.mmin.mmin.mmin.mm
2153319−7/845419−1/24957−3/4197
506176−01 01/2010
(375)
16
(406)
5/8 (16)
Page 2
4
(102)
4−1/4
(108)
23
(584)
*Side Return
Air Opening
(Either Side)
23−1/2
(597)
*Bottom Return
Air Opening
14
(356)
1−15/16 (49)
Page 3
G60UH(X) Parts Arrangement
Gasket
Flue
Transition
Flame Sensor
Flame Rollout Switches*
Flame Rollout Bracket
Gas Valve
Flue Box Gasket
Combustion Air
Orifice
Combustion Air
Pressure Switch Assembly
(two switches)
Combustion Air Inducer
Primary
Limit
(NOx Units Only)
Flue
Collector
Box
Limit Shield
NOx Insert
Air Deflector
G60UH−60C−110
Units Only
Heat Exchanger
Burners
Gas Orifices
Ignitor Bracket
Burner Bottom Shield
Control Transformer
Circuit Breaker
Two−Stage Integrated
Control
*Flame rollout switches are located
on brackets on the inner sides.
Ignitor
Secondary Limit(s)
Blower Motor
Capacitor
Door Interlock Switch
FIGURE 1
Page 3
G60UH Series
Page 4
G60UH(X) Gas Furnace
The G60UH(X) gas furnace is equipped with a two−stage
integrated control. Each G60UH(X) unit is shipped ready
for installation in the upflow or horizontal position (left or
right). The furnace is shipped with the bottom panel in
place. The bottom panel must be removed if the unit is to
be installed in a horizontal application. The panel may also
be removed in upflow applications.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G60UH(X) unit
1 − Bag assembly containing the following:
The following items may be ordered separately:
1 − Thermostat
1 − Hanging bracket (for horizontal installations)
1 − Propane/LP changeover kit
1 − Return air base
1 − High altitude kit
1 − Side filter kit
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
DANGER
Danger of explosion.
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
Safety Information
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
The G60UH is designed for installation as a Non−Direct
Vent gas central furnace.
NOTE − In Non−Direct Vent installations, combustion air
is taken from indoors and flue gases are discharged out−
doors.
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
G60UH(X) units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel
Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas
Code is available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA-B149 Natural Gas and Propane
Installation Code, local plumbing or waste water codes and
other applicable local codes.
Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit
operation, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA-B149 standards.
Vent installations must be consistent with the venting
tables (in this instruction) and applicable provisions of local
building codes.
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in figures 6 and 11. Accessibility
and service clearances must take precedence over fire
protection clearances.
NOTE − For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
506176−01 01/2010
Page 4
Page 5
NOTE − Furnace must be adjusted to obtain a temperature
rise(high and low fire) within the range(s) specified on the unit
nameplate. Failure to do so may cause erratic limit operation.
This G60UH(X) furnace must be installed so that its electrical components are protected from water.
When this furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
With a parallel flow arrangement, a damper (or other
means to control the flow of air) must adequately prevent
chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of
either the heating or the cooling unit, unless it is in the full
HEAT or COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The G60UH(X) furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the upflow or horizontal position.
This furnace design has not been CSA International certified for installation in mobile homes, recreational vehicles,
or outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
Use of Furnace as a Construction Heater
Lennox does not recommend the use of G60UH(X) units as
a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
G60UH(X) units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified
according to these installation instructions.
NOTE − The Commonwealth of Massachusetts stipulates these additional requirements:
D Gas furnaces shall be installed by a licensed plumb-
er or gas fitter only.
D The gas cock must be T handle" type.
D When a furnace is installed in an attic, the passage-
way to and service area surrounding the equipment
shall be floored.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered
when installing a G60UH(X) furnace:
D Place the furnace as close to the center of the air dis-
tribution system as possible. The furnace should also be
located close to the chimney or vent termination point.
D Do not install the furnace where drafts might blow direct-
ly into it. This could cause improper combustion and unsafe operation.
D Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
D When the furnace is installed in an attic or other insu-
lated space, keep insulation away from the furnace.
Page 5
G60UH Series
Page 6
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that
was needed. In today’s homes, tight construction practices
make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents,
chimneys, and fireplaces force additional air that could be
used for combustion out of the house. Unless outside air is
brought into the house for combustion, negative pressure
(outside pressure is greater than inside pressure) will build
to the point that a downdraft can occur in the furnace vent
pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install G60UH(X) furnaces to ensure efficient
and safe operation. You must consider combustion air
needs and requirements for exhaust vents and gas piping.
A portion of this information has been reprinted with permission from the National Fuel Gas Code
(ANSI-Z223.1/NFPA 54). This reprinted material is not the
complete and official position of the ANSI on the referenced
subject, which is represented only by the standard in its entirety.
In Canada, refer to the standard CSA B149 installation
code.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
CAUTION
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliances will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all
fuel-burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as
the furnace, much more air is necessary to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace
components.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
506176−01 01/2010
Page 6
Page 7
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the
combined input rating of all appliances installed in that
space. This definition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space either
from inside the building or from outside.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
NOTE − Each opening shall have a free area of at least one square
inch (645 mm2) per 1,000 Btu (.29 kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square
inches (64516 mm2).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas−fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 2.
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the
top of the enclosure and one opening within 12 inches (305
mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum
free area of 1 square inch (645 mm2) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the enclosure. See figures 3 and 4. When communicating with
the outdoors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch (645 mm2) per
2,000 Btu (.56 kW) per total input rating of all equipment in
the enclosure. See figure 5.
When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens must
be considered. If the design and free area of protective covering is not known for calculating the size opening required,
it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in the
open position or interlocked with the equipment so that they
are opened automatically during equipment operation.
FIGURE 2
Page 7
G60UH Series
Page 8
CHIMNEY OR
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
INLET
AIR
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645
mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
above bottom)
INLET AIR
(Ends 12 in.
WATER
HEATER
FURNACE
CHIMNEY
OR GAS
VENT
CONFINED SPACE
WATER
HEATER
OUTLET AIR
INLET AIR
EQUIPMENT IN
ALL AIR FROM
OUTSIDE
NOTE−The inlet and outlet air openings shall each have a
free area of at least one square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
FIGURE 4
506176−01 01/2010
NOTE − Each air duct opening shall have a free area of at least
one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of
the total input rating of all equipment in the enclosure. If the
equipment room is located against an outside wall and the air
openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (645 mm2)
per 4,000 Btu (1.17 kW) per hour of the total input rating of all
other equipment in the enclosure.
FIGURE 5
Page 8
Page 9
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do
not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of
the safety control devices, which could result in personal injury or death.
The G60UH(X) gas furnace can be installed as shipped
in either the upflow position or the horizontal position,
with right-hand or left-hand air discharge.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
and installation and service clearances [24 inches (610
mm) at unit front]. The unit must be level.
NOTE − 1/3 hp blower motors are equipped with four flexible mounting legs. 1/2 hp blower motors are equipped with
three flexible legs and one rigid leg. The rigid leg is
equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a
flexible mounting leg). The bolt and washer must be re-moved before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
Upflow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 6.
Upflow Application Installation Clearances
Top
Left Side
Bottom
Type of Vent
Connector
Top1 in. (25 mm)1 in. (25 mm)
*Front3 in. (76 mm)3 in. (76 mm)
Back00
Sides0†0
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
‡For installation on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
†Left side requires 3 inches if a single wall vent is used on 14−1/2
inch cabinets, or 2 inches if a single wall vent is used on 17−1/2
inch cabinets.
Type CType B1
Right Side
FIGURE 6
Page 9
G60UH Series
Page 10
Return Air −− Upflow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 1800 cfm (850 L/s) are
required with 60C or 60D models in an upflow application, the following return air options are available:
1 − Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Required to maintain proper air velocity.)
See figure 7.
2 − Return air from single side with optional RAB Return
Air Base. See figure 8.
3 − Return air from bottom.
4 − Return air from both sides.
5 − Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
Side Return Air
(with transition and filter)
20" X 25" X 1"
(508mm X635mm X 25mm)
Filter
Return Air
Plenum
Transition
FIGURE 7
Optional Return Air Base
(Upflow Applications Only −− For use with B, C and D cabinets only)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
SIDE RETURN AIR
5−5/8
(143)
OPENINGS
(Either Side)
23 (584)
27−5/8 (702)
SIDE VIEW
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7−16
(570)
Overall
(Maximum)
AIR FLOW
17−1/2 (446) RAB−B (98M60)
21 (533) RAB−C (98M58)
24−1/2 (622) RAB−D (98M59)
FURNACE
FRONT
7−1/4 (184)
OPTIONAL RAB
RETURN AIR BASE
4
(102)
14
(356)
7/8
(22)
FRONT VIEW
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in.
(584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return
air opening. The size of the opening must not extend beyond the markings on the furnace cabinet..
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
3/4
(19)
506176−01 01/2010
FIGURE 8
Page 10
Page 11
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See figure 9.
Removing the Bottom Panel
Leveling Bolt Installation
Furnace Front
3/8
(10)
3/8
(10)
Inches (mm)
1−3/4
(44)
Screw
Bottom Panel
Leveling an Upflow Unit
FIGURE 9
Bottom Cap
1−3/4
(44)
Furnace
Leveling Bolt
Locations
Bottom
Leveling Bolt
Locations
3/8
(10)
1−3/4
(44)
1−3/4 (44)
3/8
(10)
FIGURE 10
Horizontal Applications
The G60UH(X) furnace can be installed in horizontal applications.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 11.
Horizontal Application
Installation Clearances
Top
When the side return air inlets are used in an upflow application, it may be necessary to install leveling bolts on the
bottom of the furnace. Use field−supplied corrosion−resistant 5/16 inch machine bolts (4) and nuts (8). See figure 10.
NOTE − The maximum length of the bolt is 1−1/2 inches.
1 − Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace’s bottom. See figure 10 for the correct location of the holes. Drill through
the bottom panel and the bottom flange of the cabinet.
2 − Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole. A
flat washer may be added between the nut and the bottom of the unit.
3 − Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the
nut and the bottom of the unit.
4 − Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement.
Left End
Bottom
Vent Connector
Type
Top00
*Front3 in. (76 mm)3 in. (76 mm)
Back00
Ends2 in. (51 mm)2 in. (51 mm)
Vent6 in. (152 mm)1 in. (25 mm)
Bottom0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Type CType B1
Right End
FIGURE 11
Page 11
G60UH Series
Page 12
This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or
floor joists, as shown in figure 12, or install the furnace on a
platform, as shown in figure 13. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
Typical Horizontal Application
Unit Suspended in Attic or Crawlspace
Leave sufficient clearance between rod and unit to
remove access panel.
1/4 in. ROD
ANGLE
IRON
U−CHANNELS
FIGURE 12
NOTE − Heavy−gauge perforated sheet metal straps
(plumbers’ straps) may be used to suspend the unit from
roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be providedfor both
the ends and the middle of the furnace to prevent sagging.
The straps must not interfere with the plenum or exhaust
piping installation. Securing screws should be 1/2 inch
from the top edge and 1−1/2 inch from the side edge in all
cases. Cooling coils and supply and return air ple-
nums must be supported separately.
NOTE − When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the evaporator coil to drain.
Return Air −− Horizontal Applications
Return air can be brought in through the end of a furnace
installed in a horizontal application. The furnace is
equipped with a removable bottom panel to facilitate
installation. See figure 9.
Horizontal Application
Unit Installed on Platform
NOTE − Line contact is permissible. See the unit nameplate for
clearances.
GAS
ENTRY
VENT
PIPE
WORKING
PLATFORM
FIGURE 13
WARNING
Improper installation of the furnace can result in personal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or the living space. Use screws and joint tape to seal
the return air system to the furnace.
In platform installations with bottom return air, the
furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
The return and supply air duct systems must never
be connected to or from other heating devices such
as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property damage could result.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
506176−01 01/2010
Page 12
Page 13
Filters
This unit is not equipped with a filter or rack. A field−provided high−velocity filter is required for the unit to operate
properly. Table 1 lists recommended filter sizes.
A filter must be in place any time the unit is operating.
TABLE 1
Furnace
Cabinet Size
14−1/2"16 X 25 X 1 (1)14 X 25 X 1 (1)
17−1/2"16 X 25 X 1 (1)16 X 25 X 1 (1)
21"16 X 25 X 1 (1)20 X 25 X 1 (1)
24−1/2"16 X 25 X 1 (2)24 X 25 X 1 (1)
Side ReturnBottom Return
Filter Size
Duct System
Use industry-approved standards (such as those published by Air Conditioning Contractors of America or American Society of Heating, Refrigerating and Air Conditioning
Engineers) to size and install the supply and return air duct
system. This will result in a quiet and low-static system that
has uniform air distribution.
NOTE − Do not operate the furnace with an external static
pressure that exceeds 0.8 inches w.c. Higher external static pressures may cause erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel must be installed in the supply air duct. The
access panel should be large enough to permit inspection
(either by smoke or reflected light) of the heat exchanger
for leaks after the furnace is installed. The furnace access
panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room
where this furnace, or any other gas−fueled appliance
(i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This
toxic gas might then be distributed throughout the house
by the furnace duct system.
In upflow applications, the return air can be brought in
through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the unit operates properly and
safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a filter is installed, size the
return air duct to fit the filter frame.
Venting
A 4−inch diameter flue transition is factory-installed on the
combustion air inducer outlet of all models. Modifying or
removing the flue transition will cause the unit to operate unsafely and will void the unit certification. The
vent connector does not require insulation.
The combustion air inducer may be rotated clockwise or
counterclockwise by 90° to allow for top or side vent discharge in all applications. When the unit is installed, the flue
transition must be in the 9 o’clock, 12 o’clock or 3 o’clock
position. The unit will not vent properly with the fluetransition pointed down in the 6 o’clock position. Remove the four mounting screws, rotate the assembly (including the gasket), then reinstall the mounting screws.
Page 13
G60UH Series
Page 14
See figure 14. Use the provided wire tie to bundle the pressure switch wires with the inducer motor power leads.
Route the wires away from moving parts and the heat
of the inducer motor to prevent damage to the wires.
Combustion Air Inducer
(Upflow Position)
90°
Flue Transition
(Do not remove)
MOUNTING SCREWS
(Remove)
90°
Codes in Canada. A fan−assisted Category I furnace is an
appliance equipped with an integral mechanical means to
either draw or force combustion products through the combustion chamber and/or heat exchanger.
NOTE − Use these instructions as a guide. They do not supersede local codes. This furnace must be vented according to all local codes these installation instructions, and the
provided venting tables in these instructions
The venting tables in this manual were extracted from the
National Fuel Gas Code (ANSI-Z223.1/NFPA 54) and are
provided as a guide for proper vent installation. Proper application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the absence of local codes, the NFGC serves as the defining document.
Refer to the tables and the venting information contained in
these instructions to properly size and install the venting
system.
Mounting Screws
(Remove)
FIGURE 14
Optional Flue Outlet
(Horizontal Installation)
Top View of Furnace
Top Cap
Flue Outlet
Hole
(Reattach
Supply Air
Opening
Cutout Here)
Cut out
Optional
Flue Outlet
FIGURE 15
Use sheet metal shears to remove the cut out from the side
of the cabinet. Use the two provided sheet metal screws to
install the cut out on the top cap to cover the original flue
outlet opening. See figure 15.
The G60UH(X) series units are classified as fan−assisted
Category I furnaces when vertically vented according to
the latest edition of National Fuel Gas Code
(ANSI-Z223.1/NFPA 54) in the USA and the current standards of CSA B149 Natural Gas and Propane Installation
IMPORTANT
Once the venting system is installed, attach the Disconnected Vent" warning sticker to a visible area of
the plenum near the vent pipe. The warning sticker
is provided in the bag assembly.
WARNING
Asphyxiation hazard. The exhaust vent for this furnace must be securely connected to the furnace flue
transition at all times.
VENT CONNECTION
VENT
PIPE
FLUE
TRANSITION
COLLAR
FIGURE 16
Use self−drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the
flue transition. If self−drilling screws are used to attach the
vent pipe, it is recommended that three be used. Drive one
self−drilling screw through the front and one through each
side of the vent pipe and collar. See figure 16.
Install the first vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet.
FURNACE
506176−01 01/2010
Page 14
Page 15
Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector
MINIMUM LENGTH = AS SHORT AS PRACTICAL.
FOR MAXIMUM LENGTH SEE NOTE TO LEFT
NOTE− Refer to provided venting tables
for installations in the USA and the
venting tables in current CSA−B149 for
installations in Canada.
FURNACE
OTHER
APPLIANCE
NOTE − Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements as shown in the provided venting tables for installations in USA and the venting tables in current CSA−B149 for installations in Canada.
VENT
CONNECTOR
SEE NOTE 1 BELOW
INTERIOR TILE−LINED
MASONRY CHIMNEY
NOTE − the chimney must be properly
sized per provided venting tables or
lined with listed metal lining system.
PERMANENTLY
SEALED FIREPLACE
OPENING
FIGURE 17
Venting Using a Masonry Chimney
Common Venting Using Metal−Lined Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central furnaces must be either tile-lined or lined with a listed metal
lining system or dedicated gas vent. Unlined masonry
5 ft. (1.5 m)
minimum
MAX. LENGTH
−− SEE NOTE 1
BELOW.
MIN. LENGTH −− AS
SHORT AS PRACTICAL
chimneys are prohibited. See figures 18 and 17 for common venting.
A chimney with one or more sides exposed to the outside of
the structure is considered to be an exterior chimney.
4 in. (102 mm)
minimum
VENT CONNECTOR
SEE NOTE 2
An exterior masonry chimney that is not tile−lined must be
lined with B1 vent or a listed insulated flexible metal vent.
An exterior tile−lined chimney that is sealed and capped
may be lined with a listed uninsulated flexible metal vent.
If the existing chimney will not accommodate a listed metal
liner, either the chimney must be rebuilt to accommodate
one of these liners or an alternate approved venting method must be found.
G60UH units installed in upflow applications may be
vented into a tile−lined masonry chimney without using a
listed metal liner, provided that the optional masonry chim-
OTHER
APPLIANCE
NOTE 1 − Refer to the provided venting tables for installations in the USA
and the venting tables in CSA−B149 for installations Canada.
NOTE 2 − Either single-walled or double-walled vent connector may be
used. Refer to the capacity requirements shown in the provided venting
tables for installations in USA and the venting tables in current CSA−
B149 for installations in Canada.
FURNACE
FIGURE 18
PERMANENTLY
SEALED FIREPLACE
ney vent adapter kit (18M79) is used. Instructions provided
with the kit must be followed exactly.
Insulation for the flexible vent pipe must be an encapsulated fiberglass sleeve recommended by the flexible vent
pipe manufacturer. See figure 18.
SINGLE appliance venting of a fan-assisted furnace
into a tile-lined masonry chimney (interior or outside
wall) is PROHIBITED. The chimney must first be lined
IMPORTANT
with either type B1 vent or an insulated single wall
DO NOT insulate the space between the liner and the
chimney wall with puffed mica or any other loose granular insulating material
flexible vent lining system which has been sized according to the provided venting tables and the vent
pipe manufacturer’s instructions.
SEALED
EXTERIOR
CHIMNEY WITH
OPENING
METAL
LINER
Page 15
G60UH Series
Page 16
A fan−assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
S The chimney is currently serving at least one drafthood
equipped appliance
S The vent connectors and chimney are sized according
to the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149
Natural Gas and Propane Installation Codes in Canada.
If type B1 double-wall vent is used inside a chimney, no other appliance can be vented into the chimney. The outer wall
of type B1 vent pipe must not be exposed to flue products.
A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings
and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting G60UH(X) series units. The chimney
passageway must be checked periodically to ensure that it
is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator,
or flue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is
servicing a solid−fuel appliance. If a fireplace chimney flue
is used to vent this appliance, the fireplace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney flue is not considered
to be exposed to the outdoors.
General Venting Requirements
Vent all G60UH(X) furnaces according to these instructions:
1 − Vent diameter recommendations and maximum allow-
able piping runs are found in the provided venting tables
for the USA, and the appropriate venting tables in the
standards of CSA B149 Natural Gas and Propane
Installation Codes for Canada.
2 − In no case should the vent or vent connector diameter
be less than the diameter specified in the provided
venting tables for the USA, and the appropriate venting
tables in the standards of CSA B149 Natural Gas and
Propane Installation Codes for Canada.
3 − The minimum vent capacity determined by the sizing
tables must be less than the low fire input rating and the
maximum vent capacity must be greater than the high
fire input rating.
4 − Single appliance vents − If the vertical vent or tile-lined
chimney has a larger diameter or flow area than the
vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent
connector diameter to determine the maximum vent
capacity. The flow area of the vertical vent, however,
shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood outlet area or
flue collar area unless designed according to approved
engineering methods.
5 − Multiple appliance vents − The flow area of the largest
section of vertical vent or chimney shall not exceed 7
times the smallest listed appliance categorized vent
area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.
6 − The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
7 − Single appliance venting configurations with zero lat-
eral lengths (tables 3 and 4) are assumed to have no
elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond
two, the maximum capacity listed in the venting table
should be reduced by 10% (0.90 x maximum listed capacity).
8 − The common venting tables (5, 6, 7, and 8) were gen-
erated using a maximum horizontal vent connector
length of 1−1/2 feet (.46 m) for each inch (25 mm) of
connector diameter as follows:
TABLE 2
Connector Diameter
inches (mm)
3 (76)4−1/2 (1.37)
4 (102)6 (1.83)
5 (127)7−1/2 (2.29)
6 (152)9 (2.74)
7 (178)10−1/2 (3.20)
Maximum Horizontal
Connector Length feet (m)
9 − If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent of two
90° elbows (0.80 x maximum common vent capacity).
The horizontal length of the offset shall not exceed
1-1/2 feet (.46 m) for each inch (25 mm) of common
vent diameter.
10 − The vent pipe should be as short as possible with the
least number of elbows and angles required to complete the job. Route the vent connector to the vent using the shortest possible route.
506176−01 01/2010
Page 16
Page 17
11 − A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4 mm)
per linear foot (305 mm) of connector, back toward the
appliance.
12 − Vent connectors shall be firmly attached to the furnace
flue collar by self−drilling screws or other approved
means, except vent connectors of listed type B vent
material which shall be assembled according to the
manufacturer’s instructions. Joints between sections
of single wall connector piping shall be fastened by
screws or other approved means.
13 − When the vent connector used for Category I ap-
pliances must be located in or pass through a crawlspace or other areas which may be cold, that portion of
the vent connector shall be constructed of listed
double-wall type B vent material or material having
equivalent insulation qualities.
14 − All venting pipe passing through floors, walls, and ceil-
ings must be installed with the listed clearance to combustible materials and be fire stopped according to local codes. In absence of local codes, refer to NFGC
(Z223.1).
15 − No portion of the venting system can extend into, or pass
through any circulation air duct or plenum.
16 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10%, the equivalent of one 90° elbow (0.90 x maximum
common vent capacity).
18 − The common vent diameter must always be at least as
large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of
the draft hood outlet or flue collar outlet.
20 − Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the
chimney.
21 − When connecting this appliance to an existing dedi-
cated or common venting system, you must inspect the
venting system’s general condition and look for signs
of corrosion. The existing vent pipe size must conform
to these instructions and the provided venting tables
for the USA, and the appropriate venting tables in the
standards of CSA B149 Natural Gas and Propane
Installation Codes for Canada. If the existing venting
system does not meet these requirements, it must be
resized.
Page 17
G60UH Series
Page 18
TABLE 3
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
0078015202510375
2135118972715732232
4214930943915350227
6254636914714959223
0084016502760415
21257161092517828263
52353321034217153255
8284939985116464247
0088017502950447
212611711 82319426289
523573211 34118752280
103051411045417667267
0094019103270502
21169151362022622339
52265301303921949330
102959401215120664315
1535534811 26119576301
0097020203490540
21075141491825020377
52171291433824247367
102864381335022962351
153458461245921773337
2048525511 66920684322
00100021303740587
2981131661428318432
52177281603627545421
102770371504826259405
153364441415724970389
205658531326623780374
30NRNR7311388214104346
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
506176−01 01/2010
Page 18
Page 19
TABLE 4
Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
038775915185249126373
23951609685156123231
4NRNR7492102152146225
6NRNR8389114147163220
037835816483273123412
239565910883176121261
5NRNR77102107168151252
8NRNR9095122161175243
037875717482293120444
239615911782193119287
5525676111105185148277
10NRNR97100132171188261
03693561908032511 6499
23869571368022511 5337
5516375128102216144326
10NRNR95116128201182308
15NRNRNRNR158186220290
03596542007834611 4537
23774561487824811 3375
5506873140100239141363
10NRNR93129125223177344
15NRNRNRNR155208216325
20NRNRNRNR186192254306
034995321176372110584
237805516476281109429
549747215798271136417
10NRNR91144122255171397
15NRNR11 5131151239208377
20NRNRNRNR181223246357
30NRNRNRNRNRNRNRNR
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 19
G60UH Series
Page 20
Vent
Height
H
(feet)
6
8
10
15
20
30
TABLE 5
Vent Connector Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Connector
Rise
R
(feet)
1223735664610658164
2234137754812160183
3244438814913262199
1224035724911 464176
2234436805112866195
3244737875313967210
1224334784912365189
2234736865113667206
3245037925214669220
1215033894714264220
2225335964915366235
32455361025116368248
1215433994615762246
22257341054816764259
32360351105017666271
12062311134518160288
22164331184719062299
32266341234819864309
3 Inch4 Inch5 Inch6 Inch
MINMAXMINMAXMINMAXMINMAX
Vent and Connector Diameter − D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 6
Common Vent Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter − D (inches)
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
1 − Seal any unused openings in the common venting sys-
tem.
2 − Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 − Close all building doors and windows and all doors be-
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle, or smoke from a
cigarette, cigar, or pipe.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.
7 − If a venting problem is found during any of the preced-
ing tests, the common venting system must be modified to correct the problem.
Page 21
G60UH Series
Page 22
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current standards of the National Fuel Gas Code
ANSI-Z223.1/NFPA 54 in the USA, and the appropriate Category 1 Natural Gas and Propane appliances
venting sizing tables in the current standards of the
CSA B149 Natural Gas and Propane Installation
Codes in Canada.)
3 − The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters,
or elevator shafts.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the furnace. The piping must be supported at proper intervals
[every 8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or straps. Install a drip leg inside vertical pipe runs
to the unit.
5 − In some localities, codes may require the installation of
Gas Piping
a manual main shut-off valve and union (furnished by
the installer) external to the unit. The union must be of
CAUTION
the ground joint type.
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet.
Gas Supply
1 − This unit is shipped standard for left or right side instal-
lation of gas piping (or top entry in horizontal applications). Connect the gas supply to the piping assembly.
2 − When connecting the gas supply piping, consider fac-
tors such as length of run, number of fittings, and furnace rating to avoid excessive pressure drop. Table 9
lists recommended pipe sizes for typical applications.
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petroleum gases.
NOTE − Install a 1/8 inch NPT plugged tap in the field piping
upstream of the gas supply connection to the unit. The tap
must be accessible for test gauge connection. See figure 19.
NOTE − If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect main power to the furnace. The installer should properly label these devices.
NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
Length of Pipe − feet (m)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
990
1900
3000
5300
40
(1.13)
73
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
100
(30.480)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
506176−01 01/2010
Page 22
Page 23
MANUAL
MAIN SHUT−OFF
VALV E
(With 1/8 in. NPT
Plugged Tap Shown)
GROUND
JOINT
UNION
Left Side Piping
(Standard)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
MANUAL
MAIN SHUT−OFF
VALV E
(With 1/8 in. NPT
Plugged Tap
Shown)
GROUND
JOINT
UNION
DRIP LEG
PROVIDED
DRIP LEG
AND INSTALLED
FIGURE 19
Leak Check
After gas piping is completed, carefully check all piping
connections (factory− and field−installed) for gas leaks. Use
a leak detecting solution or other preferred means.
NOTE − If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect the main power to the
furnace. The installer should properly label these devices.
WARNING
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available soap
solution made specifically for leak detection.Some
soaps used for leak detection are corrosive to certain
metals. Carefully rinse piping thoroughly after leak
test has been completed.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures lessthan or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
FIRE OR EXPLOSION HAZARD
FIELD
Right Side Piping
(Alternate)
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic
controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same
electrostatic potential. Neutralize electrostatic
charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower
deck, before performing any service procedure.
The unit is equipped with a field make−up box. The make−
up box may be moved to the right side of the furnace to facilitate installation. If the make−up box is moved to the right
side, the excess wire must be pulled into the blower
compartment. Secure the excess wire to the existing harness to protect it from damage.
IMPORTANT
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 20. Gas
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN
SHUT−OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
FIGURE 20
ISOLATE
GAS VALVE
FURNACE
Page 23
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Right Side
FIGURE 21
G60UH Series
Page 24
INTERIOR MAKE−UP BOX INSTALLATION
Left side
MAKE−UP
BOX
FIGURE 22
Refer to figure 23 for schematic wiring diagram and troubleshooting and table 10 and figure 24 for field wiring.
1 − The power supply wiring must meet Class I restric-
tions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit
nameplate.
NOTE − Unit nameplate states maximum current draw.
Maximum Over−Current Protection allowed is 20AMP.
2 − Holes are on both sides of the furnace cabinet to facili-
tate wiring.
3 − Install a separate (properly sized) disconnect switch
near the furnace so that power can be turned off for
servicing.
4 − Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for
servicing at a later date. Remove the blower access
panel to check the length of the wire.
5 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wiring diagrams shown in table 10 and figure 24. Use
18−gauge wire or larger that is suitable for Class II rating for thermostat connections.
6 − Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70) for the
USA and current Canadian Electric Code part 1 (CSA
standard C22.1) for Canada. A green ground wire is
provided in the field make−up box.
NOTE − The G60UH(X) furnace contains electronic
components that are polarity sensitive. Make sure
that the furnace is wired correctly and is properly
grounded.
7 − One line voltage HUM" 1/4" spade terminal is provided
on the furnace integrated control. Any humidifier rated
up to one amp can be connected to this terminal with
the neutral leg of the circuit being connected to one of
the provided neutral terminals. See figure 25 for control
configuration. This terminal is energized in the heating
mode when the combustion air inducer is operating.
8 − One line voltage EAC" 1/4" spade terminal is provided
on the furnace integrated control. Any electronic air
cleaner rated up to one amp can be connected to this
terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See
figure 25 for control configuration. This terminal is energized when the indoor blower is operating.
9 − One 24V H" terminal is provided on the furnace inte-
grated control terminal block. Any humidifier rated up
to 0.5 amp can be connected to this terminal with the
ground leg of the circuit being connected to either
ground or the C" terminal. See figure 25 for control
configuration.
10 −Install the room thermostat according to the instruc-
tions provided with the thermostat. See table 10 for
field wiring connections in varying applications. If the
furnace is being matched with a heat pump, refer to the
instruction packaged with the dual fuel thermostat.
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously on the low speed when
there is no cooling or heating demand.
2 − When the G60UH(X) is operating in the high−fire or
low−fire heating mode, the indoor blower will run on the
corresponding heating speed.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed.
506176−01 01/2010
Page 24
Page 25
Thermostat
TABLE 10
Field Wiring Applications
DIP Switch Settings and On−Board Links (See figure 25)
W915
DIP Switch 1
Two−Stage
Cooling
W951
Heat Pumps
Wiring Connections
1 Heat / 1 Cool
NOTE − Use DIP
switch 2 to set second−stage heat ON
delay.
OFF10 minutes.
ON−15 minutes.
1 Heat / 2 Cool
NOTE − Use DIP
switch 2 to set second−stage heat ON
delay.
OFF−10 minutes.
ON−15 minutes.
ONIntactIntact
ONCutIntact
S1
T’STAT
S1
T’STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
Page 25
G60UH Series
Page 26
Thermostat
TABLE 10
Field Wiring Applications (Continued)
DIP Switch Settings and On−Board Links (See figure 25)
W915
DIP Switch 1
Two−Stage
Cooling
W951
Heat Pumps
Wiring Connections
2 Heat / 2 CoolOFFCutIntact
2 Heat / 1 CoolOFFIntactIntact
S1
T’STAT
S1
T’STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
506176−01 01/2010
Page 26
Page 27
G60UH(X) Schematic Wiring Diagram
FIGURE 23
Page 27
G60UH Series
Page 28
USE COPPER CONDUCTORS ONLY.
FIELD INSTALLED CLASS II 24V
FIELD INSTALLED LINE VOLTAGE
TYPICAL G60UH(X) FIELD WIRING DIAGRAM
FIGURE 24
DIAGNOSTIC
LEDs
DIP
SWITCHES
TWO−STAGE INTEGRATED CONTROL
1/4" QUICK CONNECT TERMINALS
SENSE = 120 VAC OUTPUT TO FLAME SENSER
NEUTRALS= 120 VAC NEUTRAL
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD
HEAT LOW = 120 VAC OUTPUT TO CIRC BLWR −− LOW HT SPEED
1 −− 2 Stage T’statSelects t/stat type (single or two−stage)
2 −− 2nd Stage DelaySecond stage ON delay (single−stage t’stat)
3 & 4 −− Heat Off DelayHeating fan OFF delay
5 −− Cool Off DelayCooling fan OFF delay
HIGH HEAT AND LOW COOL SPEED
DIP SWITCH FUNCTIONS
506176−01 01/2010
FIGURE 25
Page 28
Page 29
Integrated Control
G60UH units are equipped with a two−stage integrated
control. This control manages ignition timing and fan off
delays based on selections made using the control DIP
switches and jumpers. The control includes an internal
watchguard feature which automatically resets the ignition
control when it has been locked out. After one hour of continuous thermostat demand for heat, the watchguard will
break and remake thermostat demand to the furnace and
automatically reset the control to relight the furnace.
DIP Switch Settings
Switch 1 −− Thermostat Selection −− This unit may be used
with either a single−stage or two−stage thermostat. The
thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory−positioned for use with a two−
stage thermostat. If a single−stage thermostat is to be used,
the DIP switch must be repositioned.
a − Select OFF" for two−stage heating operation con-
trolled by a two−stage heating thermostat (factory setting);
b − Select ON" for two−stage heating operation con-
trolled by a single−stage heating thermostat. This setting provides a timed delay before second−stage heat
is initiated.
Switch 2 −− Second Stage Delay (Used with Single−
Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the OFF
position, which provides a 10−minute delay before second−
stage heat is initiated. If the switch is toggled to the ON
position, it will provide a 15−minute delay before second−
stage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLE−
stage thermostat use.
Switches 3 and 4 −− Heating Blower−Off Delay −− The
heating blower−on delay of 45 seconds is not adjustable.
The heating blower−off delay (time that the blower operates
after the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated control. The unit is shipped from the factory with a heating
blower−off delay of 90 seconds. The heating blower off
delay affects comfort and is adjustable to satisfy individual
applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact
moment that the blower is de−energized. Longer off delay
settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures.Table 11 provides the blower off timings that will result from different
switch settings.
Heating Blower−Off Delay Switch Settings
Blower Off Delay
(Seconds)
60OffOn
90OffOff
120OnOff
180OnOn
Switch 5 −− Cooling Blower−Off Delay −− The cooling
blower−off delay (time that the blower operates after the
cooling demand has been satisfied) can be adjusted by
moving switch 5 on the integrated control. The switch is factory−set in the OFF position, which provides a cooling blower−off delay of 45 seconds. If the switch is toggled to the ON
position, it will provide a 2−second cooling blower−off delay
On−Board Link W951
On−board link W951 is a clippable connection between terminals R and O on the integrated control. W951 must be cut
when the furnace is installed in applications which include a
heat pump unit and a thermostat which features dual fuel
use. If the link is left intact, terminal O" will remain energized eliminating the HEAT MODE in the heat pump.
On−Board Link W915
On−board link W915 is a clippable connection between terminals Y1 and Y2 on the integrated control. W915 must be
cut if two−stage cooling will be used. If the link is not cut the
outdoor unit will operate in second−stage cooling only.
TABLE 11
Switch 3Switch 4
Unit Start−Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been underwater. A flood−damaged furnace is extremely dangerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a licensed professional service technician (or equivalent) to inspect the furnace and to replace all gas controls,
control system parts, and electrical parts that have
been wet or to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
Page 29
G60UH Series
Page 30
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
8 − White Rodgers 36E Gas Valve − Move the gas valve
control switch to ON. See figure 26.Honeywell VR8205 Gas Valve − Turn knob on gas
valve counterclockwise to ON. Do not force. See
figure 27.
9 − Replace the upper access panel.
BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
The gas valve on the G60UH(X) unit may be equipped with
either a gas control knob or gas control switch. Use only
your hand to move the control switch or to turn the gas control knob. Never use tools. If the knob will not turn or if the
control switch will not move by hand, do not try to repair it.
Call a licensed professional service technician (or equivalent). Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
G60UH(X) units are equipped with an automatic ignition
system. Do not attempt to manually light burners on these
furnaces. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get
hot when there is no call for heat on units with this ignition
system.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figures 26 and 27)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 − Remove the upper access panel.
6 − White Rodgers 36E Gas Valve − Move gas valve
control switch to OFF. See figure 26.Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise to OFF. Do not force. See figure
27.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
WHITE RODGERS 36E SERIES GAS VALVE
HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
TAP ON SIDE
INLET PRESSURE
TAP ON SIDE
GAS VALVE SHOWN IN OFF POSITION
LOW FIRE MANIFOLD
PRESSURE ADJUSTMENT
ON SIDE (under cap)
FIGURE 26
HONEYWELL VR8205 SERIES GAS VALVE
HIGH FIRE
ADJUSTING SCREW
(under cap)
MANIFOLD
PRESSURE
TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE TAP
GAS VALVE SHOWN IN OFF POSITION
FIGURE 27
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call the gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the upper access panel.
4 − White Rodgers 36E Gas Valve − Move gas valve
control switch to OFF.
Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise to OFF. Do not force.
5 − Replace the upper access panel.
506176−01 01/2010
Page 30
Page 31
Gas Pressure Adjustment
Gas Flow (Approximate)
1 − Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for one revolutions of gas through the meter. A portable LP gas meter (17Y44) is available for LP applications.
2 − Compare the number of seconds and the gas meter
size in table 12 to determine the gas flow rate. Multiply
the gas flow rate by the heating value to determine the
unit input rate. If manifold pressure is correct and the
unit input rate is incorrect, check gas orifices for proper
size and restriction.
3 − Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas
appliances connected to meter.
Gas Pressure
1 − Check the gas line pressure with the unit firing at maxi-
mum rate. A minimum of 4.5 in. w.c. for natural gas or
11.0 in. w.c. for LP/propane gas should be maintained.
2 − After the line pressure has been checked and ad-
justed, check the low fire and high fire manifold pressures. See figures 26 and 27 for the location of the
manifold pressure adjustment screws. Low and high
fire manifold pressures are given in table 13. A natural
gas to LP/propane gas changeover kit is required to
convert the unit.
High Altitude Information
Refer to table 13 for high altitude requirements and manifold pressure settings at all altitudes.
NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.
NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
High Altitude Requirements / Manifold Pressure Settings
Model
Input
Size
−070, −090,
−110, −135
Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0−7500 feet (0−2285 m).
Gas
Required
Conversion Kit
Nat.N/AN/A44W5118M641.70.423.50.87
LPG44W48N/A44W5018M644.91.2210.02.5
0 − 7500 ft.
(0 − 2285 m)
Pressure
Switch
Altitude
Conversion Kit
TABLE 13
7501−10,000 ft.
(2286 − 3048 m)
Required
Page 31
Pressure
Switch
Manifold Pressure
at all altitudes
Low FireHigh Fire
in. w.g.kPain. w.g.kPa
G60UH Series
Page 32
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment
vestibule panel. The secondary limits (if equipped) are located in the blower compartment, attached to the back side
of the blower. These limits are factory set and require no
adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on (or inside of)
the burner box. If tripped, check for adequate combustion
air before resetting.
Pressure Switches
The pressure switch assembly (includes two switches) is
located in the heating compartment adjacent to the combustion air inducer. These switches check for proper combustion air inducer operation before allowing ignition trial.
The switches are factory−set and require no adjustment.
Temperature Rise
Unit must be adjusted for the temperature rise range and
within the allowable external static pressure as listed on
unit nameplate.
Place the unit into operation with a second−stage heating
demand. After supply and return air temperatures have
stabilized, check the temperature rise. If necessary, adjust
the heating blower speed to maintain the temperature rise
within the range shown on the unit nameplate. Increase the
blower speed to decrease the temperature rise. Decrease
the blower speed to increase the temperature rise. Failure
to properly adjust the temperature rise may cause erratic
limit operation.
Blower Speeds
NOTE − CFM ratings are taken external to unit with a dry
evaporator coil and without accessories. See blower performance data which begins on page 33.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the
air ducts or structure.
Electronic Ignition
The two−stage SureLight® integrated control used in
G60UH units has an added feature of an internal Watchguard control. The feature serves as an automatic reset device for ignition control lockout caused by ignition failure.
This type of lockout is usually due to low gas line pressure.
After one hour of continuous thermostat demand for heat,
the Watchguard will break and remake thermostat demand
to the furnace and automatically reset the control to begin
the ignition sequence.
Flue And Chimney
1 − Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage.
2 − Check unit for proper draft.
3 − Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and outlet
for blockages.
4 − Reset manual flame rollout switches on burner box.
Failure To Operate
If the unit fails to operate, check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse or tripped circuit breaker?
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 − Is the unit ignition system in lock out? If the unit locks out
again, inspect the unit for blockages.
506176−01 01/2010
Page 32
Page 33
Blower Performance Data
NOTES − All air data is measured external to unit with 1 in. cleanable filter (not furnished − field provided) in place.
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G60UH−24A−070 PERFORMANCE
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
HighMediumLow
cfmWattscfmWattscfmWatts
0.001075445905375730290
0.051070445900375725290
0.101065
0.15
1060435890365715285
440895370720285
0.201055430885360710280
0.251045
0.30
1030415875355690270
425880360700280
0.401010400860350675270
0.50975
0.60
940375805325640255
390840340660265
0.70890360755305605240
0.80830
0.90
765305640265515205
340700285565225
G60UH−36B−090 PERFORMANCE
External
Static
Pressure
in. w.g.
0.00150072012555951040460900370
0.05148570512505801040450895365
0.101465
0.15
0.20143566012255451030435880350
0.251420
0.30
0.40134559511704951000400855330
0.501300
0.60
0.7011655101020415870340740280
0.801080
0.90
Air Volume / Watts at Various Blower Speeds
High
Medium−
High
Medium−
Low
cfm Watt cfm Watt cfm Watt cfm Watt
68512405701035445890360
145067512355551035440885355
64512155301025425875345
140063012005201020415870340
5751135475965380830300
12355451080445930360780290
480940385800315670260
985445840355710290600245
Low
G60UH−36A−070 PERFORMANCE
External
Static
Pressure
in. w.g.
0.0015007051290565985455830375
0.0514756951275555980445820365
0.101450
0.15
0.2014006551225525955425795350
0.251370
0.30
0.4012856101140475900390745325
0.501215
0.60
0.701060535940405730330585270
0.80955
0.90
Air Volume / Watts at Various Blower Speeds
High
Medium−
High
Medium−
Low
cfm Watt cfm Watt cfm Watt cfm Watt
6801255545970440810360
14256701240535965430805355
6451205510945415790345
13406301180500930405780335
5801080450865375705310
11505601015430810355655290
515800370655305480260
785475605325585270410255
G60UH−36C−110 PERFORMANCE
External
Static
Pressure
in. w.g.
0.00155571513355751085460925365
0.05154070513305551080450920360
0.101525
0.15
0.20149067012955251065420900340
0.251465
0.30
0.40138561512304851030390865320
0.501320
0.60
0.7011905451075410915345775285
0.801090
0.90
Air Volume / Watts at Various Blower Speeds
High
Medium−
High
Medium−
Low
cfm Watt cfm Watt cfm Watt cfm Watt
69013205451075440915355
151068013105351070430910350
65512805101060415890335
144064512604951050405880330
5901190460995375835300
12605701135430960355815295
515970385860325760280
975485880360790305705275
Low
Low
Page 33
G60UH Series
Page 34
NOTES − All air data is measured external to unit with 1 in. cleanable filter (not furnished − field provided) in place.
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G60UH−48B−090 PERFORMANCE
External
Static
Pressure
in. w.g.
0.001970790181073515856701340565
0.051940780178571515806501335555
0.101915
0.15
0.201840730170062015456001320520
0.251805
0.30
0.401695670157059514405401260480
0.501600
0.60
0.70139556512654851170440990380
0.801250
0.90
Air Volume / Watts at Various Blower Speeds
High
Medium−
High
Medium−
Low
cfm Watt cfm Watt cfm Watt cfm Watt
765176069515706301325540
1880745173066015606151325530
715167062515205851310510
1765695164062514905651295500
635149056013605051195450
1505600140053012854801140425
5201100445975390905355
1005460870385900365810325
Low
G60UH−48C−110 PERFORMANCE
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
Medium−
High
Medium−
Low
cfm Watt cfm Watt cfm Watt cfm Watt
0.002015 895 1620 780 1340 6401150 525
0.051990 870 1615 760 1340 6401150 525
0.101965
0.15
850 1610 745 1340 6401150 525
1930 825 1605 725 1335 6301150 525
0.201895 805 1600 710 1335 6151150 525
0.251860
0.30
785 1590 695 1330 6051150 520
1820 765 1580 675 1330 5901145 515
0.401740 725 1530 635 1320 5601140 490
0.501665
0.60
695 1475 600 1285 5251120 470
1575 650 1405 555 1230 490 1075 445
0.701475 610 1310 5151165 470 1015 415
0.801350
0.90
560 1210 485 1080 430930380
1210 520 1070 430870365740325
G60UH−60C−100X PERFORMANCE
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
Bottom Return Air, Side Return Air with Optional RAB
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place.
506176−01 01/2010
Air Volume / Watts at Different Blower Speeds
Single Side Return Air − Air volumes in bold require field
fabricated transition to accommodate 20 x 25 x 1 in. air
filter in order to maintain proper air velocity.
Page 34
Page 35
Heating Sequence of Operation
NOTE − The thermostat selection DIP switch on the integrated
control is factory−set in the TWO−STAGE" position.
Applications Using a Two−Stage Thermostat
A − Heating Sequence −− Integrated Control Thermostat
Selection DIP switch in Two−Stage" Position (Factory
Setting)
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The integrated control runs a self-diagnostic program and
checks high temperature limit switches for normally
closed contacts and pressure switches for normally
open contacts.The combustion air inducer is energized at low speed and the humidifier terminal is energized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer begins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air inducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition occurs. At the same time, the control module sends a signal to begin an indoor blower 45−second ON−delay.
When the delay ends, the indoor blower motor is energized on the low fire heating speed. The furnace will
continue this operation as long as the thermostat has
a first−stage heating demand.
5 − If second−stage heat is required, the thermostat sec-
ond−stage heat contacts close and send a signal to the
integrated control. The integrated control initiates a
30−second second−stage recognition delay.
6 − At the end of the recognition delay, the integrated con-
trol energizes the combustion air inducer at high
speed. The control also checks the high−fire (second
stage) pressure switch to make sure it is closed.The
high−fire (second stage) gas valve is energized and
the indoor blower motor is energized for operation at
the high−fire heating speed.
7 − When the demand for high−fire (second stage) heat is
satisfied, the combustion air inducer is switched to the
low−fire heating speed and the high−fire (second
stage) gas valve is de−energized. The low−fire (first
stage) gas valve continues operation. The indoor
blower motor is switched to the low−fire heating speed.
8 − When the thermostat demand for low−fire (first stage)
heat is satisfied, the gas valve is de−energized and the
field−selected indoor blower−off delay begins. The
combustion air inducer begins a 5−second post−purge
period.
9 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−energized. The indoor blower is de−energized at the end of
the off delay.
Applications Using A Single−Stage Thermostat
B − Heating Sequence −− Integrated Control Thermostat
Selection DIP switch in Single−Stage" Position
NOTE − In these applications, two−stage heat will be initiated by the integrated control if heating demand has not
been satisfied after the field adjustable period (10 or 15
minutes).
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The integrated control runs a self-diagnostic program and
checks high temperature limit switches for normally
closed contacts and pressure switches for normally
open contacts.The combustion air inducer is energized at low speed and the humidifier terminal is energized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer begins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air inducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the gas
valve is energized on low fire (first stage) and ignition occurs. At the same time, the control module sends a signal to begin an indoor blower 45−second ON−delay.
When the delay ends, the indoor blower motor is energized on the low−fire heating speed. The integrated
control also initiates a second−stage on delay (factory−
set at 10 minutes; adjustable to 15 minutes).
5 − If the heating demand continues beyond the second−
stage on delay, the integrated control energizes the
combustion air inducer at high speed. The control also
checks the high−fire (second stage) pressure switch to
make sure it is closed.The high−fire (second stage)
gas valve is energized and the indoor blower motor is
energized for operation at the high−fire heating speed.
6 − When the thermostat heating demand is satisfied, the-
combustion air inducer begins a 5−second post−purge.
The field−selected indoor blower−off delay begins.
7 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−energized. The indoor blower is de−energized at the end of
the off delay.
Service
WARNING
Disconnect power before servicing unit.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Page 35
G60UH Series
Page 36
At the beginning of each heating season, a licensed professional technician (or equivalent) should check the system
as follows:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Filters
All G60UH(X) filters are installed external to the unit. Filters
should be inspected monthly. Clean or replace the filters
when necessary to ensure that the furnace operates properly. Replacement filters must be rated for high velocity airflow. Table 1 lists recommended filter sizes.
Flue And Chimney
Check the flue pipe, chimney and all connections for tightness and to make sure there is no blockage.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Cleaning the Heat Exchanger and Burners
NOTE − Use papers or protective covering in front of the furnace during cleaning.
Cleaning the heat exchanger requires a steel spring
snake," a reversible drill and a vacuum cleaner. The steel
spring snake may be constructed by purchasing a 4 ft. long
by 1/4 inch diameter steel wire cable and a 1/4 inch diameter wire brush. These items are available at a hardware
store. Insert wire end of brush into the open end of the
spring cable. Crimp the cable around the brush so that the
brush is secured and will not come off during cleaning. Attach the other end of the cable to the reversible drill to complete the tool for cleaning the heat exchanger.
1 − Turn off both electrical and gas power supplies to fur-
nace.
2 − Remove flue pipe and top cap from the unit. Label the
pressure switch wires, then disconnect them.
3 − Remove the four screws that secure the combustion air
inducer. Carefully remove the combustion air inducer to
avoid damaging blower gasket. If gasket is damaged, it
must be replaced to prevent leakage. See figure 1.
4 − Remove the collector box located behind the combus-
tion air inducer. Be careful with the collector box gas-
ket. If the gasket is damaged, it must be replaced to
prevent leakage.
5 − Label the wires from gas valve and rollout switches,
then disconnect them.
6 − Disconnect gas supply piping. Remove six screws se-
curing the burner box / manifold assembly to the vesti-
bule panel and remove the assembly from the unit.
Take care not to damage the gasket.
7 − NOx units only − Remove the three screws that attach
the NOx insert to the corbel at the entrance to each
heat exchanger section. Carefully remove the NOx in-
sert from each section. See figure 29.
8 − Insert the brush end of cable snake into the top of one
of the heat exchanger openings. Do not force the
cable into the heat exchanger. Insert the cable and
operate the drill on slow speed. Move the cable in and
out of the heat exchanger section three or four times or
until sufficient cleaning is accomplished. Reverse drill
and slowly work the cable out of opening.
9 − Repeat procedure for each heat exchanger section.
10− After each of the top heat exchanger sections has been
cleaned, insert the brush end of the cable snake into
the bottom openings of each of the heat exchanger
sections and clean as described in step 8.
11− Remove the cable from the heat exchanger. Use a vac-
uum cleaner to remove debris knocked loose during
cleaning.
12− Attach the exhaust end (positive pressure) of the vacu-
um cleaner to the top of the heat exchanger section.
Any loose debris will be forced to the bottom of the heat
exchanger section. Vacuum debris from bottom open-
ings.
13− Replace collector box and combustion air inducer.
Check gaskets for damage. Damaged gaskets must be
replaced to avoid heat exchanger leaks. Replace all
screws to the collector box and combustion air inducer.
Failure to replace all screws may cause leaks.
14− To clean the burner, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually in-
spect inside the burners and crossovers for any blockage
caused by foreign matter. Remove any blockage.
15− NOx units only − Reattach the NOx inserts to the cor-
bels at the entrance to each heat exchanger opening.
See figure 29.
16− Re−install burner box / manifold assembly onto the ves-
tibule panel.
506176−01 01/2010
Page 36
Page 37
17− Reconnect wires to pressure switch, roll−out switches,
gas valve and combustion air inducer. Refer to unit wiring diagram.
22− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
G60UH(X) BURNER & HEAT EXCHANGER REMOVAL
HEAT EXCHANGER
BURNER BOX ASSEMBLY
FIGURE 28
NOx INSERTS
(X models only)
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
23− If a leak is detected, shut gas and electricity off and
repair leak.
24− Repeat steps 23 and 24 until no leaks are detected.
25− Replace front access panel.
Planned Service
The service technician should check the following during
an annual inspection. Power to the unit must be shut off for
the service technician’s safety.
Fresh air grilles and louvers (on the unit and in the room
where the furnace is installed) − Must be open and unobstructed to provide combustion air.
Burners − Must be inspected for rust, dirt, or signs of water.
Vent pipe − Must be inspected for signs of water, damaged
or sagging pipe, or disconnected joints.
NOx INSERT
FIGURE 29
18− Re−install top cap and re−secure vent pipe to combus-
tion air inducer outlet.
19− Reconnect gas supply piping.
20− Turn on power and gas supply to unit.
21− Set thermostat and check for proper operation.
Unit appearance − Must be inspected for rust, dirt, signs
of water, burnt or damaged wires, or components.
Blower access door − Must be properly in place and provide a seal between the return air and the room where the
furnace is installed.
Return air duct − Must be properly attached and provide
an air seal to the unit.
Operating performance − Unit must be observed during
operation to monitor proper performance of the unit and the
vent system.
Combustion gases − Flue products must be analyzed and
compared to the unit specifications.
Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items
can be repaired or replaced.
Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace inspec-
tions that may result in unsafe operation.
Page 37
G60UH Series
Page 38
Integrated Control Diagnostic Codes
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
PulseA 1/4 second flash followed by four seconds of off time.
HeartbeatConstant 1/2 second bright and 1/2 second dim cycles.
X + Y
PulsePower on − Standby.
HeartbeatNormal operation − signaled when heating demand initiated at thermostat.
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four
seconds, then repeats.
FLAME CODES
1 + 2Low flame current −− run mode.
1 + 3Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3Low pressure switch failed open.
2 + 4Low pressure switch failed closed.
2 + 5High pressure switch failed open.
2 + 6High pressure switch failed closed.
2 + 7Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1Limit switch open.
WATCHGUARD CODES
4 + 1Watchguard −− Exceeded maximum number of retries.
4 + 2Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5Watchguard −− Limit remained open longer than three minutes.
4 + 6Watchguard −− Flame sensed out of sequence; flame signal gone.
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
NO
YES
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 3.
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
INDOOR BLOWER DE−ENEGIZED.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
Page 43
G60UH Series
Page 44
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
YESYES
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
AFTER 45−SECOND DELAY, INDOOR BLOWER
YES
SWITCHES TO LOW HEAT SPEED.
YES
FIRST−STAGE COOL DEMAND SATISFIED?
NO
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
SECOND STAGE COOL DEMAND SATISFIED?
YES
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
FIRST−STAGE HEAT DEMAND SATISFIED.
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
YES
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
YES
506176−01 01/2010
Page 44
Page 45
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model
number listed on the CSA International nameplate −− Example: G60UH(X)−36A−070−4. All service must be performed by a
licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel
Blower panel
Top cap
Control Panel Parts
Transformer
Two−stage integrated control
Door interlock switch
Circuit breaker
Blower Parts
Blower wheel
Blower housing
Motor
Capacitor
Motor mounting frame
Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly
Gas manifold
Two−speed combustion air inducer
Two−stage gas valve
Main burner cluster
Main burner orifices
Pressure switch
Ignitor
Primary limit control
Flame rollout switch
Secondary limit
Page 45
G60UH Series
Page 46
G60UH(X) Start−Up & Performance Check List
Job Name
Job Location
Installer
Unit Model No.
Serial No.
Job No.
City
City
Technician
Heating Section
Electrical Connections Tight?
Line Voltage
Blower Motor Amps
Fuel Type: Natural Gas?
Furnace Btu Input (High fire)Line Pressure
Low Fire Manifold Pressure
High Fire Manifold Pressure
Flue Connections Tight?
Combustion Gas Tested (high fire and low fire)?
Blower ON delay confirmed?
(45 Seconds Fixed On)
Blower OFF Delay Setting (60, 90, 120 or 180)?
LP/Propane Gas?
w.c. − Nat.:
w.c. − Nat.:
Blower Motor H.P.
Gas Piping Connections
Tight & Leak−Tested?
w.c. − LP/Propane
w.c. − LP/Propane
Proper Draft?
CO
2
External Static Pressure?
(0.5 maximum)
Temperature Rise
Date
State
State
CO
Filter Clean & Secure?
Thermostat
Heat Anticipator Setting?Thermostat Level?
506176−01 01/2010
Page 46
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.