Lennox G60DF(X), G60DF(X)−36A−070, G60DF−36B−090, G60DF(X)−48C−110 Installation Instructions Manual

Page 1
Page 1
05/09
*2P0509*
506178−01
*P506178-01*
E 2008 Lennox Industries Inc.
Dallas, Texas, USA
FOR FUTURE REFERENCE
INSTALLATION INSTRUCTIONS
G60DF(X) Series
GAS FURNACE
506178−01 05/2009 Supersedes 10/2008
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G60DF(X) Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . .
G60DF(X) Gas Furnace 4. . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as a Construction Heater 5. . . . . . . . . . .
General 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 6. . . . . . . . . . . . . .
Downflow Installation 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Equipment 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 28. . . . . . . . . . . . . . . . . . . . . . . .
High Altitude Information 28. . . . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 29. . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Performance 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 31. . . . . . . . . . . . . . . . . . .
Service 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planned Service 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ignition Control Diagnostic Codes 34. . . . . . . . . . . . . . . . .
Troubleshooting 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 42. . . . . . . . . . . . . . . .
WHAT TO DO IF YOU SMELL GAS:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other ap­pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
D If you cannot reach your gas supplier, call
the fire department.
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
WARNING
D Leave the building immediately.
Litho U.S.A.
Page 2
Page 2
506178−01 05/2009
G60DF(X) Unit Dimensions − inches (mm)
GAS PIPING INLET
(Either Side)
FLUE OUTLET
(Top)
ELECTRICAL INLET
(Either Side)
RETURN AIR
OPENING
FRONT VIEW SIDE VIEW
TOP VIEW
A
B
C
D
3/4
(19)
3/4
(19)
28−1/2
(724)
19−1/2
(495)
19−1/4
(489)
9−1/4 (235)
4−7/8 (124) Right
2−1/4 (57) Left
40
(1016)
3−3/4 (95)
5/8
(16)
AIR FLOW
5/8
(16)
3/4
(19)
19−1/2
(495)
5/8
(16)
B
5/8 (16)
5/8 (16)
Supply
Air
Supply
Air
A B C D
Model No.
in. mm in. mm in. mm in. mm G60DF(X)−36A−070 14−1/2 368 13−1/4 337 13 330 4−1/2 114 G60DF−36B−090 17−1/2 446 16−1/4 413 16 406 6 152
G60DF(X)−48C−110
21 533 19−1/4 502 19−1/2 495 7−3/4 197
Page 3
Page 3
G60DF Series
G60DF(X) Parts Arrangement
FIGURE 1
Blower Assembly
Blower Motor
Capacitor
Internal Flue Pipe
Assembly
Flue Box Gasket
Flue Collector Box
Gasket
Combustion Air Inducer
Gasket
Primary
Limit
Heat Exchanger
Combustion Air
Pressure Switch
Assembly
(Two Switches)
Combustion
Air Orifice
Transformer
Two−Stage
Integrated Control
Flue
Chase
Gasket
Door
Interlock Switch
Limit Shield
Circuit Breaker
Flame Sensor
Gas Valve
Burners
Ignitor
Flame Rollout Switches*
Flame Rollout Bracket
Gas Orifices
Ignitor Bracket
Burner Bottom Shield
*Flame rollout switches are located on brackets on the inner sides.
Page 4
Page 4
506178−01 05/2009
G60DF(X) Gas Furnace
The G60DF(X) gas furnace is equipped with a two−stage integrated control. Each G60DF(X) unit is shipped ready for installation in the downflow position.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G60DF(X) unit 1 − Bag assembly containing the following:
2 − Screws 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Vent warning label 1 − Owner’s manual and warranty card
The following items may be ordered separately: 1 − Thermostat 1 − Propane/LP changeover kit 1 − Additive base 1 − High altitude kit
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
Requirements
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
The G60DF is designed for installation as a Non−Direct Vent gas central furnace.
NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
G60DF(X) units are CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA-B149 installation codes for natu­ral gas and propane gas burning appliances and equip­ment, local plumbing or waste water codes and other appli­cable local codes.
Adequate clearance must be made around the air open­ings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standards.
Vent installations must be consistent with the venting tables (in this instruction) and applicable provisions of local building codes.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figure 9. Accessibility and service clearances must take precedence over fire protec­tion clearances.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous at­mosphere, the furnace must be installed according to rec­ommended good practice requirements and current Na­tional Fuel Gas Code or CSA B149 standards.
NOTE − Furnace must be adjusted to obtain a temperature rise(high and low fire) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit op­eration and may lead to premature heat exchanger failure.
This G60DF(X) furnace must be installed so that its electri­cal components are protected from water.
Page 5
Page 5
G60DF Series
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manu­ally operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent op­eration down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The G60DF(X) furnace may be installed in alcoves, clos­ets, attics, basements, garages, and utility rooms in the downflow position.
This furnace design has not been CSA International certi­fied for installation in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as a Construction Heater
Lennox does not recommend the use of G60DF(X) units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
G60DF(X) units may be used for heating of buildings or structures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct sys-
tem, air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
NOTE − The Commonwealth of Massachusetts stipu­lates these additional requirements:
D Gas furnaces shall be installed by a licensed plumb-
er or gas fitter only.
D The gas cock must be T handle" type. D When a furnace is installed in an attic, the passage-
way to and service area surrounding the equipment shall be floored.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a G60DF(X) furnace:
D Place the furnace as close to the center of the air dis-
tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
D Do not install the furnace where drafts might blow direct-
ly into it. This could cause improper combustion and un­safe operation.
D Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
D When the furnace is installed in an attic or other insu-
lated space, keep insulation away from the furnace.
Page 6
Page 6
506178−01 05/2009
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction prac­tices make it necessary to bring in air from outside for com­bustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless out­side air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the fur­nace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situ­ation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install G60DF(X) furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI Z223.1/NFPA 54). This re­printed material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Canada, refer to the current CSA B149 standards.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the com­bustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliances will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When fire­places, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft. In­sufficient air causes incomplete combustion which can re­sult in carbon monoxide.
In addition to providing combustion air, fresh outdoor air di­lutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace compo­nents.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by
Page 7
Page 7
G60DF Series
infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cu­bic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space ei­ther from inside the building or from outside.
EQUIPMENT IN CONFINED
SPACE ALL AIR FROM INSIDE
CHIMNEY
OR GAS
VENT
FURNACE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
NOTE − Each opening shall have a free area of at least one square inch (645 mm
2
) per 1,000 Btu (.29 kW) per hour of the total input rat­ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm
2
).
FIGURE 2
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm
2
). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 2.
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate di­rectly or by ducts with the outdoors or spaces (crawl or at­tic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm
2
) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the en­closure. See figures 3 and 4. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm
2
) per
2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 5.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cov­ering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera­tion.
Page 8
Page 8
506178−01 05/2009
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
WATER
HEATER
INLET
AIR
CHIMNEY OR
GAS VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip­ment in the enclosure.
CHIMNEY
OR GAS
VENT
WATER
HEATER
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12 in.
above bottom)
FURNACE
FIGURE 4
EQUIPMENT IN
CONFINED SPACE
ALL AIR FROM
OUTSIDE
OUTLET AIR
INLET AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
NOTE − Each air duct opening shall have a free area of at least one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each open­ing shall have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.
FURNACE
FIGURE 5
Page 9
Page 9
G60DF Series
Downflow Installation
Downflow unit installs in three ways: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling cabinet. Do not drag the unit across the floor.
Installation on Non−Combustible Flooring
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
3 − Ensure that the seal is adequate.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Front to Rear Side to Side
Model N
o.
in. mm in. mm
A Cabinet (14.5") 19 − 3/4 502 13 − 1/4 337
B Cabinet (17.5") 19 − 3/4 502 16 − 1/4 413
C Cabinet (21") 19 − 3/4 502 19 − 3/4 502
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See unit dimensions on page 2.
Installation on Combustible Flooring
1 − When unit is installed on a combustible floor, an addi-
tive base must be installed between the furnace and the floor. The base must be ordered separately for the following cabinet sizes:
D A cabinet 14.5" − # 11M59 D B cabinet 17.5" − # 11M60 D C cabinet −21" # 11M61
See table 2 for opening size to cut in floor.
CAUTION
The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma­terial other than wood flooring.
TABLE 2
ADDITIVE BASE FLOOR OPENING SIZE
Front to Rear Side to Side
Model N
o.
in. mm in. mm
A Cabinet (14.5")
22 559 15 − 3/4 400
B Cabinet (17.5")
22 559 18 − 3/4 476
C Cabinet (21")
22 559 22 − 3/4 578
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than unit opening. See unit dimensions on page 2.
2 − After opening is cut, set additive base into opening.
3 − Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 − Lower supply air plenum into additive base until ple-
num flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
G60DF(X)UNIT
SUPPLY AIR PLENUM
ADDITIVE BASE
PROPERLY
SIZED FLOOR
OPENING
FIGURE 6
Installation on Cooling Cabinet
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Return Air Opening −− Downflow Units
The following steps should be taken when installing ple­num:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 7).
SECURE FROM
OUTSIDE CABINET
HEMMED EDGE
PLENUM
FIBERGLASS SEALING STRIP (Field Provided)
CABINET SIDE PANEL
Side View
FIGURE 7
2 − Fiberglass sealing strips should be used.
3 − In all cases, plenum should be secured to top flanges
of furnace with sheet metal screws.
Page 10
Page 10
506178−01 05/2009
4 − In closet installations, it may be impossible to install
sheet metal screws from the outside. In this case, make plenum with a removable front and install screws from the inside (See figure 8).
5 − Make certain that an adequate seal is made.
SECURE FROM IN-
SIDE CABINET
HEMMED EDGE
FIBERGLASS
SEALING STRIP
(Field Provided)
CABINET SIDE
PANEL
PLENUM
Side View
FIGURE 8
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­sonal injury or death.
Install the G60DF(X) gas furnace as shipped. Do not install the furnace horizontally.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level.
NOTE − Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic wash­er (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be re- moved before the furnace is placed into operation. Af­ter the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Downflow Application Allow for clearances to combustible materials as indi­cated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 9.
Downflow Application Installation Clearances
Top
Bottom
Left Side
Right Side
Type of Vent
Connector
Type C Type B1
Top 1 in. (25 mm) 1 in. (25 mm)
*Front 3 in. (76 mm) 3 in. (76 mm)
Back 0 0
Sides 0 0
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor NC†† NC††
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Left side requires 3 in. if a single wall vent is used on 14 −1/2 in. cabinets, or 2 in. if a single wall vent is used on 17 − 1/2 in. cabinets. ††The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor.
FIGURE 9
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace. In platform installations with bottom return air, the furnace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or proper­ty damage could result.
Page 11
Page 11
G60DF Series
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
This unit is not equipped with a filter or rack. A field−pro­vided high−velocity filter is required for the unit to operate properly. Table 3 lists recommended filter sizes. A filter must be in place any time the unit is operating.
TABLE 3
Furnace
Cabinet Width
Return Air Filter Size (inches)
14−1/2" 14 X 25 X 1 (1)
17−1/2" 16 X 25 X 1 (1)
21" 20 X 25 X 1 (1)
Duct System
Use industry-approved standards (such as those pub­lished by Air Conditioning Contractors of America or Ameri­can Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Do not operate the furnace with an external static pressure that exceeds 0.5 inches w.c. Higher external stat­ic pressures may cause erratic limit operation.
Ensure that you have made a seal between the supply air plenum and the furnace and between the furnace and the return air plenum.
Return Air Plenum
NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide−producing de­vice (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This re­verse flow of the flue gas may result in incomplete combus­tion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Venting
A 4−inch diameter flue transition is factory-installed on all models. Modifying or removing the flue transition will
cause the unit to operate unsafely and will void the unit certification. The vent connector does not require insula-
tion.
The G60DF(X) series units are classified as fan−assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA and the current standards of the CSA B149 Natural Gas and Propane Installation Codes in Canada. A fan−assisted Category I furnace is an ap­pliance equipped with an integral mechanical means to ei­ther draw or force combustion products through the com­bustion chamber and/or heat exchanger.
NOTE − Use these instructions as a guide. They do not su­persede local codes. This furnace must be vented accord­ing to all local codes these installation instructions, and the provided venting tables in these instructions
The venting tables in this manual were extracted from the National Fuel Gas Code (ANSI Z223.1/NFPA 54) and are provided as a guide for proper vent installation. Proper ap­plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab­sence of local codes, the NFGC serves as the defining doc­ument.
Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.
IMPORTANT
Once the venting system is installed, attach the Dis­connected Vent" warning sticker to a visible area of the plenum near the vent pipe. The warning sticker is provided in the bag assembly.
WARNING
Asphyxiation hazard. The exhaust vent for this fur­nace must be securely connected to the furnace flue transition at all times.
Use self−drilling sheet metal screws or a mechanical fas­tener to firmly secure the vent pipe to the round collar of the flue transition. If self−drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self−drilling screw through the front and one through each side of the vent pipe and collar. See figure 10.
FLUE TRANSITION
COLLAR
VENT CONNECTION
VENT
PIPE
FURNACE
FIGURE 10
Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet.
Page 12
Page 12
506178−01 05/2009
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central fur­naces must be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 11 and 12 for com­mon venting.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile−lined must be lined with B1 vent or a listed insulated flexible metal vent. An exterior tile−lined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent.
If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting meth­od must be found.
Insulation for the flexible vent pipe must be an encapsu­lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 11.
IMPORTANT
SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized ac­cording to the provided venting tables and the vent pipe manufacturer’s instructions.
DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran­ular insulating material
A fan−assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:
S The chimney is currently serving at least one drafthood
equipped appliance
S The vent connectors and chimney are sized according
to the provided venting tables for the USA, and the ap­propriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes in Cana­da.
Common Venting Using Metal−Lined Masonry Chimney
4 in. (102 mm)
minimum
MIN. LENGTH −− AS
SHORT AS PRACTICAL
MAX. LENGTH
−− SEE NOTE 1 BELOW.
SEALED
PERMANENTLY
SEALED FIREPLACE
OPENING
EXTERIOR
CHIMNEY WITH
METAL
LINER
VENT CONNECTOR
SEE NOTE 2
NOTE 1 − Refer to the provided venting tables for installations in the USA and the venting tables in CSA−B149 for installations Canada. NOTE 2 − Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements shown in the provided venting tables for installations in USA and the venting tables in current CSA− B149 for installations in Canada.
OTHER
APPLIANCE
FURNACE
FIGURE 11
5 ft. (1.5 m)
minimum
Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector
MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT
INTERIOR TILE−LINED MASONRY CHIMNEY
NOTE − the chimney must be properly sized per provided venting tables or lined with listed metal lining system.
PERMANENTLY SEALED FIREPLACE OPENING
VENT
CONNECTOR
SEE NOTE 1 BELOW
NOTE − Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements as shown in the pro­vided venting tables for installations in USA and the venting tables in current CSA−B149 for installations in Canada.
NOTE− Refer to provided venting tables for installations in the USA and the venting tables in current CSA−B149 for installations in Canada.
FURNACE
OTHER
APPLIANCE
FIGURE 12
Page 13
Page 13
G60DF Series
If type B1 double-wall vent is used inside a chimney, no oth­er appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products.
A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof as­sembly according to the terms of their respective listings and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting G60DF(X) series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney. Never connect a Category I appliance to a chimney that is servicing a solid−fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed. A type B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors.
General Venting Requirements
Vent all G60DF(X) furnaces according to these instruc­tions:
1 − Vent diameter recommendations and maximum allow-
able piping runs are found in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Pro­pane Installation Codes for Canada.
2 − In no case should the vent or vent connector diameter
be less than the diameter specified in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada.
3 − The minimum vent capacity determined by the sizing
tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input rating.
4 − Single appliance vents − If the vertical vent or tile-lined
chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to de­termine the minimum vent capacity and the vent
connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, however,
shall not exceed 7 times the flow area of the listed ap­pliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.
5 − Multiple appliance vents − The flow area of the largest
section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering meth­ods.
6 − The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning, and replacement.
7 − Single appliance venting configurations with zero lat-
eral lengths (tables 5 and 6) are assumed to have no elbows in the vent system. For all other vent configura­tions, the vent system is assumed to have two 90° el­bows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed ca­pacity).
8 − The common venting tables (7, 8, 9, and 10) were gen-
erated using a maximum horizontal vent connector length of 1−1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows:
TABLE 4
Connector Diameter
inches (mm)
Maximum Horizontal
Connector Length feet (m)
3 (76) 4−1/2 (1.37)
4 (102) 6 (1.83)
5 (127) 7−1/2 (2.29)
6 (152) 9 (2.74)
7 (178) 10−1/2 (3.20)
9 − If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90° elbows (0.80 x maximum common vent capacity). The horizontal length of the offset shall not exceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.
10 − The vent pipe should be as short as possible with the
least number of elbows and angles required to com­plete the job. Route the vent connector to the vent us­ing the shortest possible route.
11 − A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance.
Page 14
Page 14
506178−01 05/2009
12 − Vent connectors shall be firmly attached to the furnace
flue collar by self−drilling screws or other approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means.
13 − When the vent connector used for Category I ap-
pliances must be located in or pass through a crawl­space or other areas which may be cold, that portion of the vent connector shall be constructed of listed double-wall type B vent material or material having equivalent insulation qualities.
14 − All venting pipe passing through floors, walls, and ceil-
ings must be installed with the listed clearance to com­bustible materials and be fire stopped according to lo­cal codes. In absence of local codes, refer to NFGC (ANSI Z223.1/NFPA 54).
15 − No portion of the venting system can extend into, or
pass through any circulation air duct or plenum.
16 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90° elbow (0.90 x maxi­mum common vent capacity).
18 − The common vent diameter must always be at least as
large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of the draft hood outlet or flue collar outlet.
20 − Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the chimney.
21 − When connecting this appliance to an existing dedi-
cated or common venting system, you must inspect the venting system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149 Natural Gas and Propane Installation Codes for Canada. If the existing venting system does not meet these requirements, it must be resized.
Page 15
Page 15
G60DF Series
TABLE 5
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
Lateral
3 Inch 4 Inch 5 Inch 6 Inch
H
(
feet
)L(
feet
)
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
(feet)
MIN MAX MIN MAX MIN MAX MIN MAX
0 0 78 0 152 0 251 0 375
2 13 51 18 97 27 157 32 232
6
4 21 49 30 94 39 153 50 227
6 25 46 36 91 47 149 59 223
0 0 84 0 165 0 276 0 415
2 12 57 16 109 25 178 28 263
8
5 23 53 32 103 42 171 53 255
8 28 49 39 98 51 164 64 247
0 0 88 0 175 0 295 0 447
2 12 61 17 118 23 194 26 289
10
5 23 57 32 113 41 187 52 280
10 30 51 41 104 54 176 67 267
0 0 94 0 191 0 327 0 502
2 11 69 15 136 20 226 22 339
15
5 22 65 30 130 39 219 49 330
10 29 59 40 121 51 206 64 315
15 35 53 48 112 61 195 76 301
0 0 97 0 202 0 349 0 540
2 10 75 14 149 18 250 20 377
5 21 71 29 143 38 242 47 367
20
10 28 64 38 133 50 229 62 351
15 34 58 46 124 59 217 73 337
20 48 52 55 116 69 206 84 322
0 0 100 0 213 0 374 0 587
2 9 81 13 166 14 283 18 432
5 21 77 28 160 36 275 45 421
30
10 27 70 37 150 48 262 59 405
15 33 64 44 141 57 249 70 389
20 56 58 53 132 66 237 80 374
30 NR NR 73 113 88 214 104 346
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi­mum listed capacity).
Page 16
Page 16
506178−01 05/2009
TABLE 6
Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
Lateral
3 Inch 4 Inch 5 Inch 6 Inch
H
(
feet
)L(
feet
)
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
(feet)
MIN MAX MIN MAX MIN MAX MIN MAX
0 38 77 59 151 85 249 126 373
2 39 51 60 96 85 156 123 231
6
4 NR NR 74 92 102 152 146 225
6 NR NR 83 89 114 147 163 220
0 37 83 58 164 83 273 123 412
2 39 56 59 108 83 176 121 261
8
5 NR NR 77 102 107 168 151 252
8 NR NR 90 95 122 161 175 243
0 37 87 57 174 82 293 120 444
2 39 61 59 117 82 193 119 287
10
5 52 56 76 111 105 185 148 277
10 NR NR 97 100 132 171 188 261
0 36 93 56 190 80 325 116 499
2 38 69 57 136 80 225 115 337
15
5 51 63 75 128 102 216 144 326
10 NR NR 95 116 128 201 182 308
15 NR NR NR NR 158 186 220 290
0 35 96 54 200 78 346 114 537
2 37 74 56 148 78 248 113 375
5 50 68 73 140 100 239 141 363
20
10 NR NR 93 129 125 223 177 344
15 NR NR NR NR 155 208 216 325
20 NR NR NR NR 186 192 254 306
0 34 99 53 211 76 372 110 584
2 37 80 55 164 76 281 109 429
5 49 74 72 157 98 271 136 417
30
10 NR NR 91 144 122 255 171 397
15 NR NR 115 131 151 239 208 377
20 NR NR NR NR 181 223 246 357
30 NR NR NR NR NR NR NR NR
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi­mum listed capacity).
Page 17
Page 17
G60DF Series
TABLE 7
Vent Connector Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Vent and Connector Diameter − D (inches)
Vent
Height
C
onnector
Rise
3 Inch 4 Inch 5 Inch 6 Inch
Height
H
Rise
R
Appliance Input Rating in Thousands of Btu Per Hour
(feet) (feet)
MIN MAX MIN MAX MIN MAX MIN MAX
1 22 37 35 66 46 106 58 164
6
2 23 41 37 75 48 121 60 183
6
3 24 44 38 81 49 132 62 199
1 22 40 35 72 49 114 64 176
8
2 23 44 36 80 51 128 66 195
3 24 47 37 87 53 139 67 210
1 22 43 34 78 49 123 65 189
10
2 23 47 36 86 51 136 67 206
3 24 50 37 92 52 146 69 220
1 21 50 33 89 47 142 64 220
15
2 22 53 35 96 49 153 66 235
3 24 55 36 102 51 163 68 248
1 21 54 33 99 46 157 62 246
20
2 22 57 34 105 48 167 64 259
3 23 60 35 110 50 176 66 271
1 20 62 31 113 45 181 60 288
30
2 21 64 33 118 47 190 62 299
3 22 66 34 123 48 198 64 309
TABLE 8
Common Vent Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Common Vent Diameter − D (inches)
Vent
Height
4 Inch 5 Inch 6 Inch 7 Inch
Height
H
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
6 92 81 140 116 204 161 309 248
8 101 90 155 129 224 178 339 275
10 110 97 169 141 243 194 367 299
15 125 112 195 164 283 228 427 352
20 136 123 215 183 314 255 475 394
30 152 138 244 210 361 297 547 459
Page 18
Page 18
506178−01 05/2009
TABLE 9
Vent Connector Capacity
Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving Two or More Category I Appliances
Vent and Connector Diameter − D (inches)
Vent
Height
C
onnector
Rise
3 Inch 4 Inch 5 Inch 6 Inch
Height
H
Rise
R
Appliance Input Rating in Thousands of Btu Per Hour
(feet) (feet)
MIN MAX MIN MAX MIN MAX MIN MAX
1 NR NR NR NR NR NR NR NR
6
2 NR NR NR NR NR NR 168 182
6
3 NR NR NR NR 121 131 174 198
1 NR NR 79 87 116 138 177 214
15
2 NR NR 83 94 121 150 185 230
3 NR NR 87 100 127 160 193 243
1 47 60 77 110 113 175 169 278
30
2 50 62 81 115 117 185 177 290
3 54 64 85 119 122 193 185 300
TABLE 10
Common Vent Capacity
Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving Two or More Category I Appliances
Common Vent Diameter − D (inches)
Vent
Height
4 Inch 5 Inch 6 Inch 7 Inch
Height
H
Appliance Input Rating in Thousands of Btu Per Hour
(feet)
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
6 89 78 136 113 200 158 304 244
8 98 87 151 126 218 173 331 269
10 106 94 163 137 237 189 357 292
15 121 108 189 159 275 221 416 343
20 131 118 208 177 305 247 463 383
30 145 132 236 202 350 286 533 446
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas ap­pliances, the venting system is likely to be too large to prop­erly vent the remaining attached appliances.
Conduct the following test while each appliance is operat­ing and the other appliances (which are not operating) re­main connected to the common venting system. If the vent­ing system has been installed improperly, you must correct the system as indicated in the general venting re­quirements section.
1 − Seal any unused openings in the common venting sys-
tem.
2 − Inspect the venting system for proper size and horizon-
tal pitch. Determine that there is no blockage, restric­tion, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − Close all building doors and windows and all doors be-
tween the space in which the appliances remaining connected to the common venting system are located
and other spaces of the building. Turn on clothes dry­ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper­ate at maximum speed. Do not operate a summer ex­haust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace damp­ers, and any other gas−burning appliances to their pre­vious mode of operation.
7 − If a venting problem is found during any of the preced-
ing tests, the common venting system must be modi­fied to correct the problem.
Page 19
Page 19
G60DF Series
Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan­dards of the National Fuel Gas Code ANSI Z223.1/NFPA 54 in the USA, and the appropriate Category 1 Natural Gas and Propane appliances vent­ing sizing tables in the current standards of the CSA B149 Natural Gas and Propane Installation Codes in Canada.)
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet.
Gas Supply
1 − This unit is shipped standard for left or right side instal-
lation of gas piping. Connect the gas supply to the pip­ing assembly.
2 − When connecting the gas supply piping, consider fac-
tors such as length of run, number of fittings, and fur­nace rating to avoid excessive pressure drop. Table 11 lists recommended pipe sizes for typical applications.
3 − The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the fur­nace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang­ers or straps. Install a drip leg inside vertical pipe runs to the unit.
5 − In some localities, codes may require the installation of
a manual main shut-off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­leum gases.
NOTE − Install a 1/8 inch NPT plugged tap in the field piping upstream of the gas supply connection to the unit. The tap must be accessible for test gauge connection. See figure
13.
NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect main power to the furnace. The installer should properly label these devices.
TABLE 11
Gas Pipe Capacity − ft
3
/hr (m3/hr)
Nominal
Iron Pipe
Internal
Length of Pipe − feet (m)
Iron Pipe
Size
inches
(mm)
Diameter
inches
(mm)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
100
(30.480)
3/8
(9.53)
.493
(12.522)95(2.69)65(1.84)
52
(1.47)
45
(1.27)
40
(1.13)
36
(1.02)
33
(.73)
31
(.88)
29
(.82)
27
(.76)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
1
(25.4)
1.049
(26.645)
680
(919.25)
465
(13.17)
375
(10.62)
320
(9.06)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
1−1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1−1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
2−1/2
(63.5)
2.469
(67.713)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3
(76.2)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
Page 20
Page 20
506178−01 05/2009
GROUND
JOINT
UNION
AUTOMATIC
GAS VALVE (with manual
shut−off valve)
FIELD
PROVIDED
AND INSTALLED
GROUND
JOINT
UNION
Left Side Piping
(Standard)
Right Side Piping
(Alternate)
AUTOMATIC
GAS VALVE (with manual
shut−off valve)
DRIP LEG
DRIP LEG
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap Shown)
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap
Shown)
FIGURE 13
Leak Check
After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.
NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these de­vices.
WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.Some soaps used for leak detection are corrosive to cer­tain metals. Carefully rinse piping thoroughly after leak test has been completed.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 14. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN
SHUT−OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
ISOLATE
GAS VALVE
FURNACE
FIGURE 14
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic compo­nents. Take precautions during furnace installation and service to protect the furnace’s electronic con­trols. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touch­ing hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before per­forming any service procedure.
The unit is equipped with a field make−up box. The make− up box may be moved to the right side of the furnace to fa­cilitate installation. Secure the excess wire to the existing harness to protect it from damage.
INTERIOR MAKE−UP BOX INSTALLATION
(Left Side)
FIGURE 15
MAKE−UP
BOX
Page 21
Page 21
G60DF Series
INTERIOR MAKE−UP BOX INSTALLATION
(Right Side)
FIGURE 16
MAKE−UP
BOX
Refer to figure 17 for schematic wiring diagram and trou­bleshooting and table 12 and figure 18 for field wiring.
1 − Select circuit protection and wire size according to the
unit nameplate. The power supply wiring must meet Class I restrictions.
2 − Holes are on both sides of the furnace cabinet to facili-
tate wiring.
3 − Install a separate disconnect switch (protected by ei-
ther fuse or circuit breaker) near the furnace so that power can be turned off for servicing.
4 − Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.
5 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wir­ing diagrams shown in table 12 and figure 18. Use 18−gauge wire or larger that is suitable for Class II rat­ing for thermostat connections.
6 − Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.
NOTE − The G60DF(X) furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
7 − One line voltage HUM" 1/4" spade terminal is pro-
vided on the furnace integrated control. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 19 for control configuration. This terminal is energized in the heating mode when the combustion air inducer is oper­ating.
8 − One line voltage EAC" 1/4" spade terminal is provided
on the furnace integrated control. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con­nected to one of the provided neutral terminals. See figure 19 for control configuration. This terminal is en­ergized when the indoor blower is operating.
9 − One 24V H" terminal is provided on the furnace control
terminal block. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit being connected to either ground or the C" ter­minal. See figure 19 for control configuration.
10 −Install the room thermostat according to the instruc-
tions provided with the thermostat. See table 12 for field wiring connections in varying applications. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously on the low speed when there is no cooling or heating demand.
2 − When the G60DF(X) is operating in the high−fire or low−
fire heating mode, the indoor blower will run on the cor­responding heating speed.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed.
Page 22
Page 22
506178−01 05/2009
TABLE 12
Field Wiring Applications
DIP Switch Settings and On−Board Links (See figure 19)
Thermostat
DIP Switch 1
W915
(Y1 to Y2)
Two−Stage
Cooling
W951
(O to R)
Heat Pumps
Wiring Connections
1 Heat / 1 Cool
NOTE − Use DIP switch 2 to set sec­ond−stage heat ON delay. OFF10 minutes. ON−15 minutes.
ON Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool
NOTE − Use DIP switch 2 to set sec­ond−stage heat ON delay. OFF−10 minutes. ON−15 minutes.
ON Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 23
Page 23
G60DF Series
TABLE 12
Field Wiring Applications (Continued)
DIP Switch Settings and On−Board Links (See figure 19)
Thermostat
DIP Switch 1
W915
(Y1 to Y2)
Two−Stage
Cooling
W951
(O to R)
Heat Pumps
Wiring Connections
2 Heat / 2 Cool OFF Cut Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
2 Heat / 1 Cool OFF Intact Intact
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 24
Page 24
506178−01 05/2009
G60DF(X) Schematic Wiring Diagram
FIGURE 17
Page 25
Page 25
G60DF Series
TYPICAL FIELD WIRING DIAGRAM
FIGURE 18
TWO−STAGE INTEGRATED CONTROL
THERMOSTAT CONNECTIONS (TB1)
1/4" QUICK CONNECT TERMINALS
DIP SWITCH FUNCTIONS
DIP
SWITCHES
DIAGNOSTIC
LEDs
ON−BOARD
LINKS
1= ERROR CODE RECALL H= 24V HUMIDIFIER OUTPUT L= LENNOX SYSTEM OPERATION MONITOR
SENSE = 120 VAC OUTPUT TO FLAME SENSER
NEUTRALS= 120 VAC NEUTRAL
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD HEAT LOW = 120 VAC OUTPUT TO CIRC BLWR −− LOW HT SPEED HEAT HIGH/ COOL LOW = 120 VAC OUTPUT TO CIRC BLWR −−
HIGH HEAT AND LOW COOL SPEED
COOL HIGH = 120 VAC OUTPUT TO CIRC BLWR −− HIGH COOL SPEED
DIP SWITCH(ES) FUNCTION
1 −− 2 Stage T’stat Selects t/stat type (single or two−stage)
2 −− 2nd Stage Delay Second stage ON delay (single−stage t’stat)
3 & 4 −− Heat Off Delay Heating fan OFF delay
5 −− Cool Off Delay Cooling fan OFF delay
W915
W951
FIGURE 19
Page 26
Page 26
506178−01 05/2009
Integrated Control
G60DF units are equipped with a two−stage integrated con­trol. This control manages ignition timing and fan off delays based on selections made using the control DIP switches. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out. After one hour of continuous thermostat de­mand for heat, the watchguard will break and remake ther­mostat demand to the furnace and automatically reset the control to relight the furnace.
DIP Switch Settings Switch 1 −− Thermostat Selection −− This unit may be
used with either a single−stage or two−stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular application. TheDIP switch is factory−positioned for use with a two− stage thermostat. If a single−stage thermostat is to be used, the DIP switch must be repositioned.
a − Select OFF" for two−stage heating operation con-
trolled by a two−stage heating thermostat (factory set­ting);
b − Select ON" for two−stage heating operation con-
trolled by a single−stage heating thermostat. This set­ting provides a timed delay before second−stage heat is initiated.
Switch 2 −− Second Stage Delay (Used with Single− Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage ther­mostat is being used. The switch is factory−set in the OFF position, which provides a 10−minute delay before second− stage heat is initiated. If the switch is toggled to the ON position, it will provide a 15−minute delay before second− stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE− stage thermostat use.
Switches 3 and 4 −− Heating Blower−Off Delay −− The heating blower−on delay of 45 seconds is not adjustable. The heating blower−off delay (time that the blower operates after the heating demand has been satisfied) can be ad­justed by moving switches 3 and 4 on the integrated con­trol. The unit is shipped from the factory with a heating blower−off delay of 90 seconds. The heating blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a sup­ply air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter set­tings provide higher supply air temperatures.Table 13 pro­vides the blower off timings that will result from different switch settings.
TABLE 13
Heating Blower−Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3 Switch 4
60 Off On
90 Off Off 120 On Off 180 On On
Switch 5 −− Cooling Blower−Off Delay −− The cooling blower−off delay (time that the blower operates after the cooling demand has been satisfied) can be adjusted by moving switch 5 on the integrated control. The switch is fac­tory−set in the OFF position, which provides a cooling blow­er−off delay of 45 seconds. If the switch is toggled to the ON position, it will provide a 2−second cooling blower−off delay
On−Board Link W951
On−board link W951 is a clippable connection between ter­minals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the link is left intact, terminal O" will remain ener­gized eliminating the HEAT MODE in the heat pump.
On−Board Link W915
On−board link W915 is a clippable connection between ter­minals Y1 and Y2 on the integrated control. W915 must be cut if two−stage cooling will be used. If the link is not cut the outdoor unit will operate in second−stage cooling only.
Unit Start−Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been underwa­ter. A flood−damaged furnace is extremely danger­ous. Attempts to use the furnace can result in fire or explosion. Immediately call a licensed professional service technician (or equivalent) to inspect the fur­nace and to replace all gas controls, control system parts, and electrical parts that have been wet or to re­place the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
Page 27
Page 27
G60DF Series
CAUTION
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
The gas valve on the G60DF(X) unit may be equipped with either a gas control knob or gas control switch. Use only your hand to move the control switch or to turn the gas con­trol knob. Never use tools. If the knob will not turn or if the control switch will not move by hand, do not try to repair it. Call a licensed professional service technician. Force or at­tempted repair may result in a fire or explosion.
Placing the furnace into operation:
G60DF(X) units are equipped with a n automatic ignition system. Do not attempt to manually light burners on these furnaces. Each time the thermostat calls for heat, the burn­ers will automatically light. The ignitor does not get hot when there is no call for heat on units with this ignition sys­tem.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figures 20 and 21)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the burners by hand.
5 − Remove the upper access panel.
6 − White Rodgers 36E Gas Valve − Move gas valve con-
trol switch to OFF. See figure 20. Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise
to OFF. Do not force. See figure
21.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instruc­tions. If you do not smell gas go to next step.
8 − White Rodgers 36E Gas Valve − Move gas valve con-
trol switch to ON. See figure 20. Honeywell VR8205 Gas Valve − Turn knob on gas
valve counterclockwise
to ON. Do not force. See
figure 21.
9 − Replace the upper access panel.
WHITE RODGERS 36E SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
HIGH FIRE MANIFOLD PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
TAP ON SIDE
INLET PRESSURE
TAP ON SIDE
LOW FIRE MANIFOLD
PRESSURE ADJUSTMENT
ON SIDE (under cap)
FIGURE 20
HONEYWELL VR8205 SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
TAP
HIGH FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
FIGURE 21
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call the gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting. 2 − Turn off all electrical power to the unit if service is to be
performed. 3 − Remove the upper access panel. 4 − White Rodgers 36E Gas Valve − Move gas valve con-
trol switch to OFF.
Honeywell VR8205 Gas Valve − Turn knob on gas
valve clockwise
to OFF. Do not force.
5 − Replace the upper access panel.
Page 28
Page 28
506178−01 05/2009
Gas Pressure Adjustment
Gas Flow (Approximate)
1 − Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for one revolu­tions of gas through the meter. A portable LP gas me­ter (17Y44) is available for LP applications.
TABLE 14
Gas Flow Rate (Ft.3/Hr.)
Seconds for 1
Gas Meter Size
Seconds for 1
Revolution
1/2 cu ft Dial 1 cu ft Dial
10 180 360 12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 113 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 38 75 50 36 72 52 35 69 54 33 67 56 32 64 58 31 62 60 30 60
2 − Compare the number of seconds and the gas meter
size in table 14 to determine the gas flow rate. Multiply the gas flow rate by the heating value to determine the unit input rate. If manifold pressure is correct and the unit input rate is incorrect, check gas orifices for proper size and restriction.
3 − Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.
Gas Pressure
1 − Check the gas line pressure with the unit firing at maxi-
mum rate. A minimum of 4.5 in. w.c. for natural gas or
11.0 in. w.c. for LP/propane gas should be maintained.
2 − After the line pressure has been checked and ad-
justed, check the low fire and high fire manifold pres­sures. See figures 20 and 21 for the location of the manifold pressure adjustment screws. Low and high fire manifold pressures are given in table 15. A natural gas to LP/propane gas changeover kit is required to convert the unit.
High Altitude Information
Refer to table 15 for high altitude requirements and man­ifold pressure settings at all altitudes.
NOTE − In Canada, certification for installations at eleva­tions over 4500 feet (1372 m) is the jurisdiction of local au­thorities.
NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
TABLE 15
High Altitude Requirements / Manifold Pressure Settings
Altitude
Model
Input
Gas
0 − 7500 ft.
(0 − 2285 m)
7501−10,000 ft.
(2286 − 3048 m)
Manifold Pressure
at all altitudes
Input
Size
Gas
Required Pressure Required Pressure
Low Fire High Fire
Required
Conversion Kit
Pressure
Switch
Required
Conversion Kit
Pressure
Switch
in. w.g. kPa in. w.g. kPa
−070, −090,
Nat. N/A No Change 44W51 44W31 1.7 0.42 3.5 0.87
−070, −090
,
−110
LPG 44W48 No Change 44W50 44W31 4.9 1.22 10.0 2.5
Pressure switch is factory set. No adjustment necessary. All models use the factory installed pressure switch from 0−7500 feet (0−2285 m).
Page 29
Page 29
G60DF Series
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo­cated in the blower compartment, attached to the back side of the blower. These limits are factory set and require no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on (or inside of) the burner box. If tripped, check for adequate combustion air before resetting.
Pressure Switches
The pressure switch assembly (includes two switches) is located in the heating compartment adjacent to the com­bustion air inducer. These switches check for proper com­bustion air inducer operation before allowing ignition trial. The switches are factory−set and require no adjustment.
Temperature Rise
Unit must be adjusted for the temperature rise range and within the allowable external static pressure as listed on unit nameplate. Place the unit into operation with a second−stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature rise. Decrease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation and may result in premature heat exchanger failure.
Blower Speeds
NOTE − CFM ratings are taken external to unit with a dry evaporator coil and without accessories. See blower per­formance data on page 30.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.
Electrical
1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace
operating). 3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the air ducts or structure.
Electronic Ignition
The two−stage integrated control used in G60DF units has an added feature of an internal Watchguard control. The feature serves as an automatic reset device for ignition control lockout caused by ignition failure. This type of lock­out is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the control to begin the ignition se­quence.
Flue And Chimney
1 − Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage. 2 − Check unit for proper draft. 3 − Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and outlet
for blockages. 4 − Reset manual flame rollout switches on burner box.
Failure To Operate
If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse or tripped circuit breaker? 5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lock out? If the unit locks
out again, inspect the unit for blockages.
Page 30
Page 30
506178−01 05/2009
Blower Performance Data
G60DF−36A−070X PERFORMANCE
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
High
Medium−
High
Medium−
Low
Low
in. w.g.
cfm
Watt cfm Watt cfm Watt cfm Watt
0.00 1475 616 1345 554 1150 495 990 415
0.05 1450 606 1320 543 1140 481 985 407
0.10 1425
595 1300 532 1125 466 975 398
0.15
1395 585 1275 521 1115 452 970 390
0.20 1375 574 1255 510 1105 437 965 381
0.25 1345
563 1230 494 1090 428 955 371
0.30
1320 552 1205 478 1075 418 945 360
0.40 1250 528 1150 455 1040 395 920 346
0.50 1200
508 1095 432 1000 374 880 331
0.60
1110 475 1035 409 950 354 830 313
0.70 1030 455 970 390 855 338 720 280
0.80 960
434 875 359 735 299 665 266
0.90
770 389 715 321 665 278 590 244
G60DF−36B−090 PERFORMANCE
External
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
High
Medium−
High
Medium−
Low
Low
in. w.g. cfm Watt cfm Watt cfm Watt cfm Watt
0.00 1600 608 1410 526 1165 436 965 355
0.05 1580 599 1400 518 1165 428 965 351
0.10 1560
589 1390 509 1160 420 970 346
0.15
1530 573 1370 497 1155 413 965 341
0.20 1495 556 1350 485 1150 406 965 335
0.25 1465
544 1325 473 1135 398 955 329
0.30
1430 532 1300 460 1125 389 945 323
0.40 1370 509 1250 438 1095 373 935 313
0.50 1295
482 1200 420 1055 355 900 302
0.60
1215 456 1140 397 1010 343 860 285
0.70 1140 437 1055 371 915 313 800 272
0.80 1000
401 950 342 850 295 730 251
0.90
900 374 820 313 740 272 − − − − − −
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place.
G60DF−48C−110 PERFORMANCE
External
Air Volume / Watts at Different Blower Speeds
Static
Pressure
High Medium−High Medium−Low Low
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts
0.00
2035 846 1790 712 1510 595 1225 477
0.05 2000 825 1760 694 1495 581 1225 470
0.10 1970
803 1730 675 1475 567 1220 463
0.15
1925 781 1710 657 1475 555 1220 455
0.20 1880 758 1685 638 1465 542 1215 447
0.25 1835
736 1655 618 1440 528 1200 437
0.30
1795 714 1625 597 1420 514 1185 427
0.40 1680 669 1550 564 1360 483 1135 400
0.50 1620
630 1445 524 1280 447 1065 371
0.60
1445 592 1310 479 1165 404 1000 343
0.70 1290 545 1180 434 1055 369 905 319
0.80 1155
502 1065 406 955 348 815 296
0.90
1010 472 930 372 840 320 690 265
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not fur­nished − field provided) in place.
Page 31
Page 31
G60DF Series
Heating Sequence of Operation
NOTE − The thermostat jumper on the integratred control is factory−set in the TWO−STAGE" position.
Applications Using a Two−Stage Thermostat
A − Heating Sequence −− Control Thermostat Selection DIP switch in Two−Stage" Position (Factory Setting)
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be­gins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the
gas valve is energized on low fire (first stage) and igni­tion occurs. At the same time, the control module sends a signal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is energized on the low fire heating speed. The furnace will continue this operation as long as the ther­mostat has a first−stage heating demand.
5 − If second−stage heat is required, the thermostat sec-
ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.
6 − At the end of the recognition delay, the integrated con-
trol energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed.The high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.
7 − When the demand for high−fire (second stage) heat is
satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.
8 − When the thermostat demand for low−fire (first stage)
heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.
9 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Applications Using A Single−Stage Thermostat
B − Heating Sequence −− Integrated Control Thermostat Selection DIP switch in Single−Stage" Position
NOTE − In these applications, two−stage heat will be initi­ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).
1 − On a call for heat, thermostat first−stage contacts close
sending a signal to the integrated control. The inte­grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts.The combustion air inducer is ener­gized at low speed and the humidifier terminal is ener­gized.
2 − Once the control receives a signal that the low pres-
sure switch has closed, the combustion air inducer be­gins a 15−second pre−purge in low speed.
3 − After the pre−purge is complete, a 20−second initial ig-
nitor warm−up period begins. The combustion air in­ducer continues to operate at low speed.
4 − After the 20−second warm−up period has ended, the
gas valve is energized on low fire (first stage) and igni­tion occurs. At the same time, the control module sends a signal to begin an indoor blower 45−second ON−delay. When the delay ends, the indoor blower motor is energized on the low−fire heating speed. The integrated control also initiates a second−stage on delay (factory−set at 10 minutes; adjustable to 15 min­utes).
5 − If the heating demand continues beyond the second−
stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high−fire (second stage) pressure switch to make sure it is closed.The high−fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high−fire heating speed.
6 − When the thermostat heating demand is satisfied, the-
combustion air inducer begins a 5−second post−purge. The field−selected indoor blower off delay begins.
7 − When the combustion air post−purge period is com-
plete, the inducer and humidifier terminal are de−ener­gized. The indoor blower is de−energized at the end of the off delay.
Page 32
Page 32
506178−01 05/2009
Service
WARNING
Disconnect power before servicing unit.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after ser­vicing.
At the beginning of each heating season, a licensed profes­sional technician (or equivalent) should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
All G60DF(X) filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure that the furnace operates prop­erly. Replacement filters must be rated for high velocity air­flow. Table 3 lists recommended filter sizes.
Flue And Chimney
Check the flue pipe, chimney and all connections for tight­ness and to make sure there is no blockage.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Cleaning the Heat Exchanger and Burners
NOTE − Use papers or protective covering in front of the fur­nace during cleaning.
Cleaning the heat exchanger requires a steel spring snake," a reversible drill and a vacuum cleaner. The steel spring snake may be constructed by purchasing a 4 ft. long by 1/4 inch diameter steel wire cable and a 1/4 inch diame­ter wire brush. These items are available at a hardware store. Insert wire end of brush into the open end of the
spring cable. Crimp the cable around the brush so that the brush is secured and will not come off during cleaning. At­tach the other end of the cable to the reversible drill to com­plete the tool for cleaning the heat exchanger. 1 − Turn off both electrical and gas power supplies to fur-
nace.
2 − Remove flue pipe and top cap from the unit. Label the
pressure switch wires, then disconnect them.
3 − Remove the four screws that secure the combustion
air inducer. Carefully remove the combustion air induc­er to avoid damaging blower gasket. If gasket is dam­aged, it must be replaced to prevent leakage. See fig­ure 1.
4 − Remove the collector box located behind the combus-
tion air inducer. Be careful with the collector box gas­ket. If the gasket is damaged, it must be replaced to prevent leakage.
5 − Label the wires from gas valve and rollout switches,
then disconnect them.
6 − Disconnect gas supply piping. Remove six screws se-
curing the burner box / manifold assembly to the vesti­bule panel and remove the assembly from the unit. Take care not to damage the gasket.
7 − NOx units only Remove the three screws that attach
the NOx insert to the corbel at the entrance to each heat exchanger section. Carefully remove the NOx in­sert from each section. See figure 23.
8 − Insert the brush end of cable snake into the top of one
of the heat exchanger openings. Do not force the cable into the heat exchanger. Insert the cable and operate the drill on slow speed. Move the cable in and out of the heat exchanger section three or four times or until sufficient cleaning is accomplished. Reverse drill
and slowly work the cable out of opening. 9 − Repeat procedure for each heat exchanger section. 10− After each of the top heat exchanger sections has been
cleaned, insert the brush end of the cable snake into
the bottom openings of each of the heat exchanger
sections and clean as described in step 8. 11− Remove the cable from the heat exchanger. Use a vac-
uum cleaner to remove debris knocked loose during
cleaning. 12− Attach the exhaust end (positive pressure) of the vacu-
um cleaner to the top of the heat exchanger section.
Any loose debris will be forced to the bottom of the heat
exchanger section. Vacuum debris from bottom open-
ings.
13− Replace collector box and combustion air inducer.
Check gaskets for damage. Damaged gaskets must
be replaced to avoid heat exchanger leaks. Replace all
screws to the collector box and combustion air inducer.
Failure to replace all screws may cause leaks.
14− To clean the burner, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually in-
spect inside the burners and crossovers for any block-
age caused by foreign matter. Remove any blockage.
Page 33
Page 33
G60DF Series
G60DF(X) COMBUSTION AIR INDUCER,
BURNER & HEAT EXCHANGER REMOVAL
FIGURE 22
Burner Box Assembly
Heat Exchanger
Combustion Air
Inducer
NOx INSERTS
(X models only)
FIGURE 23
NOx INSERT
15− NOx units only Reattach the NOx inserts to the cor-
bels at the entrance to each heat exchanger opening. See figure 23.
16− Re−install burner box / manifold assembly onto the ves-
tibule panel.
17− Reconnect wires to pressure switch, roll−out switches,
gas valve and combustion air inducer. Refer to unit wir­ing diagram.
18− Re−install top cap and re−secure vent pipe to combus-
tion air inducer outlet.
19− Reconnect gas supply piping.
20− Turn on power and gas supply to unit.
21− Set thermostat and check for proper operation.
22− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred means.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af­ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.
23− If a leak is detected, shut gas and electricity off and re-
pair leak.
24− Repeat steps 23 and 24 until no leaks are detected.
25− Replace front access panel.
Planned Service
The service technician should check the following during an annual inspection. Power to the unit must be shut off for the service technician’s safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unob­structed to provide combustion air.
Burners − Must be inspected for rust, dirt, or signs of water.
Vent pipe − Must be inspected for signs of water, damaged
or sagging pipe, or disconnected joints.
Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door − Must be properly in place and pro­vide a seal between the return air and the room where the furnace is installed.
Return air duct − Must be properly attached and provide an air seal to the unit.
Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.
Combustion gases − Flue products must be analyzed and compared to the unit specifications.
Problems detected during the inspection may make it nec­essary to temporarily shut down the furnace until the items can be repaired or replaced.
Instruct the homeowners to pay attention to their fur­nace. Situations can arise between annual furnace inspec-
tions that may result in unsafe operation.
Page 34
Page 34
506178−01 05/2009
Integrated Control Diagnostic Codes
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
Pulse A 1/4 second flash followed by four seconds of off time.
Heartbeat Constant 1/2 second bright and 1/2 second dim cycles.
X + Y
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four seconds, then repeats.
Pulse Power on − Standby.
Heartbeat Normal operation − signaled when heating demand initiated at thermostat.
FLAME CODES
1 + 2 Low flame current −− run mode.
1 + 3 Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3 Low pressure switch failed open.
2 + 4 Low pressure switch failed closed.
2 + 5 High pressure switch failed open.
2 + 6 High pressure switch failed closed.
2 + 7 Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1 Limit switch open.
WATCHGUARD CODES
4 + 1 Watchguard −− Exceeded maximum number of retries.
4 + 2 Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3 Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5 Watchguard −− Limit remained open longer than three minutes.
4 + 6 Watchguard −− Flame sensed out of sequence; flame signal gone.
4 + 7 Ignitor circuit fault −− Failed ignitor or triggering circuitry.
4 + 8 Low line voltage.
HARD LOCKOUT CODES
5 + 1 Hard lockout −− Rollout circuit open or previously opened.
5 + 2 Control failed self check, internal error (control will restart if error recovers).
5 + 3 No Earth ground (control will restart if error recovers).
5 + 4 Reversed line voltage polarity (control will restart if the error recovers).
5 + 6 Low secondary (24VAC) voltage.
Error Code Storage
The ignition control stores the last ten error codes in memory. The codes are retained in case of power loss.
Error Code Review
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED
will stay lit continuously to indicate that the short was sensed.
2 − Continue to hold the short between R (2) to (1). After 5
seconds, STATUS LED will go from being continuous­ly lit to off. This indicates that error code review is pend­ing.
3 − Remove R (2) to (1) short within ten seconds of STA-
TUS LED turning off. This activates error code review.
4 − Last ten error codes will be flashed on the STATUS
LED.
5 − After final error code is indicated, STATUS LED will
flash to indicate normal operation.
Clearing Error Codes
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED
will stay lit continuously to indicate that the short was
sensed.
2 − Continue to hold the short between R (2) to (1). After 5
seconds, STATUS LED will go from being continuous-
ly lit to off.
3 − Continue to hold the short between R (2) to (1) beyond
ten seconds after STATUS LED has turned off. STA-
TUS LED will turn on, indicating that error codes have
been cleared.
4 − Remove R (2) to (1) short. STATUS LED will flash to
indicate normal operation.
Page 35
Page 35
G60DF Series
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.)
NO
POLARITY REVERSED.
STATUS ERROR CODE 5 + 4.
POWER ON
POLARITY OKAY?
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
STATUS ERROR CODE 5 + 3.
IS THERE A
PROPER GROUND?
NO
YES
A
NORMAL OPERATION:
STATUS LED −− PULSE
B
THERMOSTAT CALLS FOR HEAT:
STATUS LED −− HEARTBEAT
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
NO
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON. HAS PRIMARY OR
SECONDARY LIMIT RESET WITHIN 3 MINUTES?
STATUS ERROR CODE 3 + 1.
ROLLOUT SWITCH CLOSED?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.
NO
YES
FIRST (LOW) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
STATUS ERROR CODE 2 + 4
YES
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
CONTROL WILL NOT ATTEMPT SECOND−STAGE
OPERATION DURING THIS HEAT DEMAND.
FIRST−STAGE OPERATION WILL BE ATTEMPTED.
STATUS ERROR CODE 2 + 6.
NO
TWO−STAGE OR SINGLE−STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
STATUS LED −− HEARTBEAT
CONTINUED ON NEXT PAGE
NO
NO
60−MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5.
YES
NO
YES
SECOND (HIGH) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
YES
Page 36
Page 36
506178−01 05/2009
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
FIRST−STAGE (LOW FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
STATUS ERROR CODE 2 + 3.
YES
NO
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED
FIRST−STAGE PRESSURE SWITCH (or 15
SECOND INTER−PURGE PERIOD.)
STATUS LED −− HEARTBEAT.
IGNITOR WARM−UP (20 SECONDS)
STATUS LED −− HEARTBEAT.
IS VOLTAGE ABOVE 90 VOLTS?
NO
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95
VOLTS. STATUS ERROR CODE 4 + 8.
YES
NO
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED OR
RECONNECTED.
STATUS ERROR CODE 4 + 7.
YES
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
YES
4−SECOND FLAME STABILIZATION PERIOD.
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.20 microamps)
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
STATUS LED −− HEARTBEAT.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
THERMOSTAT CALLS FOR HEAT
STATUS LED − HEARTBEAT.
(Refer to box A on previous page)
YES
FLAME PRESENT?
NO
HAS CONTROL RESET IGNITION SEQUENCE
FOUR (4) TIMES?
WATCHGUARD MODE.
STATUS ERROR CODE 4 + 3.
YES
CONTINUED ON NEXT PAGE
YES
NO
NO
CONTINUED
IS IGNITOR INTACT AND CONNECTED?
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
STATUS ERROR CODE 4 + 1.
IS 60−MINUTE RESET PERIOD COMPLETE?
NO
YES
Page 37
Page 37
G60DF Series
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
LOW FLAME SIGNAL
(Does not affect control operation)
STATUS ERROR CODE 1 + 2.
FLAME SIGNAL ABOVE
(u1.40 microamps)
NO
YES
CONTINUED ON NEXT PAGE
YES
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
TWO STAGE THERMOSTAT MODE
(DIP SWITCH SET AT TWO")
YES
YES
START SECOND−STAGE RECOGNITION
ON DELAY (10 OR 15 MINUTES).
STATUS LED −− HEARTBEAT
45−SECOND INDOOR BLOWER ON DELAY BEGINS.
STATUS LED −− HEARTBEAT.
YES
YES
PRIMARY & SECONDARY LIMIT SWITCHES
CLOSED?
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER ON.
STATUS ERROR CODE 3 + 1.
HAS PRIMARY OR SECONDARY LIMIT
SWITCH CLOSED WITHIN 3 MINUTES?
(Indoor blower on low speed during 3−minute period)
FIRST−STAGE (LOW FIRE)
PRESSURE SWITCH CLOSED?
LIMIT SWITCH WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
INDOOR BLOWER OFF WITH DELAY.
STATUS ERROR CODE 4 + 5
IS 60−MINUTE RESET PERIOD COMPLETE?
THERMOSTAT CALLS FOR HEAT.
STATUS LED −− HEARTBEAT.
SEE BOX A.
NO
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF AFTER DELAY.
STATUS ERROR CODE 2 + 3. CONTROL RESTARTS
IGNITION SEQUENCE IF PRESSURE SWITCH
CLOSES WITHIN 2−1/2 MINUTES.
NO
YES
FIRST−STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
STATUS LED −− PULSE
YES
SECOND−STAGE HEAT DEMAND.
SECOND−STAGE HEAT DEMAND REQUIRED?
NO
SECOND STAGE PRESSURE SWITCH CLOSED?
ABNORMAL FLASH CODE.
NOTE − IF SECOND−STAGE PRESSURE SWITCH
WAS ORIGINALLY FOUND CLOSED,
ABNORMAL CODE WILL FLASH.
SECOND−STAGE PRESSURE SWITCH CLOSED
AT BEGINNING OF HEAT DEMAND?
STATUS ERROR CODE 2 + 6.
YES
NO
SECOND−STAGE 30−SECOND DELAY ON BEGINS.
STATUS LED −− HEARTBEAT.
SECOND−STAGE COMBUSTION AIR INDUCER
ON. SECOND−STAGE GAS VALVE ON. HIGH
HEAT INDOOR BLOWER SPEED ON.
STATUS LED −− HEARTBEAT.
YES
SECOND−STAGE PRESSURE SWITCH CLOSED
IN LESS THAN TEN (10) SECONDS?
STATUS LED −− HEARTBEAT
YES
NO
RETURNS TO FIRST−STAGE HEAT MODE WHICH
CONTINUES UNTIL SECOND−STAGE PRESSURE
SWITCH CAN BE PROVEN or HEAT DEMAND IS
SATISFIED. FIVE (5) MINUTE WAIT PERIOD
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS
MADE FOR SECOND−STAGE HEAT?
YES
CONTINUES FIRST−STAGE HEATING
DEMAND. WILL NOT REATTEMPT
SECOND−STAGE HEATING DEMAND.
STATUS ERROR CODE 2 + 5.
SECOND STAGE HEAT DEMAND
STATUS LED −− HEARTBEAT.
NO
YES
NO
YES
CONTINUED
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS
UNTIL ROLLOUT SWITCH IS RESET AND MAIN
POWER IS INTERRUPTED OR THERMOSTAT
IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.
ROLLOUT SWITCHES CLOSED?
NO
YES
YES
NO
YES
YES
Page 38
Page 38
506178−01 05/2009
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
SEE BOX B
THERMOSTAT CALLS FOR HEAT.
SEE BOX A
NORMAL OPERATION.
YES
NO
RETURN TO FIRST−STAGE HEAT MODE.
FIRST−STAGE CONTINUES UNTIL SECOND−
STAGE PRESSURE SWITCH CAN BE PROVEN
or HEAT DEMAND IS SATISFIED. A FIVE (5)
MINUTE WAIT PERIOD IS INITIATED BEFORE
RETRY. WERE 5 ATTEMPTS MADE FOR
SECOND−STAGE HEAT?
YES
NO
SEE BOX C
FIRST−STAGE HEAT DEMAND SATISFIED?
HEAT DEMAND SATISFIED?
STATUS LED −− HEARTBEAT.
YES
TWO STAGE THERMOSTAT MODE?
(DIP SWITCH SET AT TWO")
SINGLE−STAGE THERMOSTAT MODE
(DIP SWITCH SET AT SINGLE")
YES
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
STATUS LED −− HEARTBEAT.
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5−SECOND
LOW SPEED POST PURGE PERIOD,
INDOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
STATUS LED −− HEARTBEAT.
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY.
STATUS LED −− PULSE.
YES
SECOND STAGE HEAT DEMAND SASTISFIED?
STATUS LED −− HEARTBEAT.
NO
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST−
STAGE OPERATION.
STATUS LED −− HEARTBEAT.
YES
FIRST STAGE HEAT DEMAND SATISFIED?
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5−SECOND LOW SPEED POST−
PURGE PERIOD. INDOOR BLOWER OFF. DELAY INITIATED ON LOW HEAT SPEED.
STATUS LED −− PULSE.
CONTINUED
SECOND−STAGE (HIGH FIRE) HEAT
PRESSURE SWITCH CLOSED?
Page 39
Page 39
G60DF Series
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
SIGNAL POLARITY REVERSED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 4.
POWER ON
YES
IS POLARITY REVERSED?
THERMOSTAT CALLS FOR FIRST−STAGE COOL.
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
NO
IS THERE
PROPER GROUND?
YES
NO
INDOOR BLOWER ENERGIZED ON FIRST STAGE
COOL SPEED AFTER 2 SECOND DELAY.
FIRST−STAGE DEMAND FOR COOL SATISFIED?
NO
THERMOSTAT CALLS FOR SECOND−STAGE COOL.
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
INDOOR BLOWER DE−ENEGIZED.
YES
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
STATUS ERROR CODE 5 + 3.
Page 40
Page 40
506178−01 05/2009
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
YES
AFTER 45−SECOND DELAY, INDOOR BLOWER
SWITCHES TO LOW HEAT SPEED.
FIRST−STAGE HEAT DEMAND SATISFIED.
YES
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
FIRST−STAGE COOL DEMAND SATISFIED?
YES
NO
SECOND STAGE COOL DEMAND SATISFIED?
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
YES
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
YES YES
Page 41
Page 41
G60DF Series
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA International nameplate −− Example: G60DF(X)−36A−070−4. All service must be performed by a
licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel Blower panel Top cap
Control Panel Parts
Transformer Two−stage integrated control Door interlock switch Circuit breaker
Blower Parts
Blower wheel Blower housing Motor Capacitor Motor mounting frame Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly Gas manifold Two−speed combustion air inducer Two−stage gas valve Main burner cluster Main burner orifices Pressure switch Ignitor Primary limit control Flame rollout switch Secondary limit
Page 42
Page 42
506178−01 05/2009
G60DF(X) Start−Up & Performance Check List
w.c. − LP/Propane
Filter Clean & Secure?
Line Voltage
Electrical Connections Tight?
Job Name
Job Location
Installer
Unit Model No.
Furnace Btu Input (High fire) Line Pressure
Job No.
City
City
Serial No.
Date
State
Technician
Flue Connections Tight?
Heating Section
Thermostat
Heat Anticipator Setting? Thermostat Level?
Fuel Type: Natural Gas?
Blower Motor Amps
Blower Motor H.P.
Gas Piping Connections Tight & Leak−Tested?
Proper Draft?
State
Blower OFF Delay Setting (60, 90, 120 or 180)?
Blower ON delay confirmed? (45 Seconds Fixed On)
High Fire Manifold Pressure
w.c. − Nat.:
LP/Propane Gas?
Combustion Gas Tested (high fire and low fire)?
CO
2
CO
w.c. − LP/Propane
Low Fire Manifold Pressure
w.c. − Nat.:
Temperature Rise
External Static Pressure? (0.5 maximum)
Loading...