Page 6
BLOWER DATA Cont.
G60DF−48C−090 PERFORMANCE
External Static
Pressure
Air Volume / Watts at Different Blower Speeds
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2039 960 749 1852 875 657 1595 755 562 1325 625 466
0.05 12 1998 945 727 1826 860 638 1576 745 547 1338 632 460
0.10 25 1956 925 704 1800 850 619 1556 735 532 1351 640 453
0.15 37 1921 905 692 1770 835 602 1541 725 518 1340 630 441
0.20 50 1885 890 679 1739 820 585 1526 720 503 1329 625 428
0.25 62 1844 870 662 1701 805 568 1502 710 488 1301 615 414
0.30 75 1802 850 645 1663 785 551 1477 695 473 1272 600 399
0.40 100 1693 800 606 1583 745 517 1415 670 448 1226 580 378
0.50 125 1600 755 570 1491 705 485 1334 630 414 1170 550 360
0.60 150 1494 705 540 1406 665 457 1248 590 389 111 0 525 337
0.70 175 1378 650 509 1300 615 426 1166 550 367 1026 485 316
0.80 200 1248 590 478 1161 550 390 1027 485 331 − − − − − − − − −
0.90 225 1097 520 439 1028 485 360 925 435 307 − − − − − − − − −
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G60DF−48C−110 PERFORMANCE
External Static
Pressure
Air Volume / Watts at Different Blower Speeds
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2034 960 846 1790 845 712 1508 710 595 1226 580 477
0.05 12 2001 945 825 1761 830 694 1493 705 581 1224 580 470
0.10 25 1968 930 803 1731 815 675 1477 695 567 1222 575 463
0.15 37 1924 910 781 1708 805 657 1470 695 555 1219 575 455
0.20 50 1879 885 758 1685 795 638 1463 690 542 1216 575 447
0.25 62 1837 865 736 1654 780 618 1442 680 528 1201 565 437
0.30 75 1794 845 714 1623 765 597 1420 670 514 1186 560 427
0.40 100 1681 795 669 1548 730 564 1361 640 483 1134 535 400
0.50 125 1622 765 630 1445 680 524 1280 605 447 1065 505 371
0.60 150 1447 685 592 1312 620 479 1165 550 404 1000 470 343
0.70 175 1289 610 545 1178 555 434 1056 500 369 907 430 319
0.80 200 1157 545 502 1067 505 406 956 450 348 816 385 296
0.90 225 1012 480 472 931 440 372 840 395 320 690 325 265
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G60DF−60C−110 with 3/4 hp PERFORMANCE
External Static
Pressure
Air Volume / Watts at Different Blower Speeds
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2450 1155 1170 2355 111 0 1005 2145 1015 840 1845 870 705
.05 10 2430 1150 1165 2340 1105 995 2130 1005 835 1840 870 695
.10 25 2380 1120 1145 2315 1090 985 2105 995 825 1830 865 690
.15 35 2350 1110 1135 2260 1065 965 2085 985 815 1815 855 680
.20 50 2300 1085 1115 2235 1055 955 2060 975 805 1805 850 675
.25 60 2270 1070 1105 2205 1040 945 2015 950 785 1780 840 665
.30 75 2245 1060 1100 2150 1015 925 1995 940 775 1770 835 655
.40 100 2135 1010 1060 2070 975 895 1925 910 750 1730 815 640
.50 125 2055 970 1035 1990 940 870 1855 875 725 1695 800 625
.60 150 1975 930 1010 1910 900 845 1785 845 705 1650 775 605
.70 175 1870 880 980 1830 865 820 1695 800 680 1575 745 585
.80 200 1760 830 950 1720 815 795 1605 755 655 1505 710 570
.90 225 1625 765 915 1560 735 755 1515 715 640 1435 675 555
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.