Lennox G50UHX, G50UH Unit Information

Page 1
Page 1
© 2000 Lennox Industries Inc.
Corp. 0005−L3
G50UH(X)
Service Literature
Revised 09−2006
G50UH(X) series units are mid−efficiency gas furnaces
tured with Lennox Duralok Plus heat exchangers formed of
aluminized steel. G50UH(X) units are available in heating
capacities of 44,000 to 154,000 Btuh and cooling applica-
tions up to 5 tons. Refer to Engineering Handbook for prop-
er sizing.
Units are factory equipped for use with natural gas. Kits are
available for conversion to LPG operation. G50UH(X) mod-
el units are equipped with the Lennox SureLight silicon ni-
tride ignition system. The G50UH(X) unit meets the Califor-
nia Nitrogen Oxides (NO
x
) Standards and California Sea-
sonal Efficiency requirements. All units use a redundant gas
valve to assure safety shut−off as required by C.S.A.
All specifications in this manual are subject to change. Pro-
cedures outlined in this manual are presented as a recom-
mendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommended only and do not constitute
code.
TABLE OF CONTENTS
Specifications Page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Data Page 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude Page 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Identification Page 16. . . . . . . . . . . . . . . . . . . . . . . .
I Unit Components Page 18. . . . . . . . . . . . . . . . . . . . . . .
II Installation Page 27. . . . . . . . . . . . . . . . . . . . . . . . . . . .
III Start Up Page 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating System Service Checks Page 27. . . . . . . . .
V Typical Operating Characteristics Page 29. . . . . . . . .
VI Maintenance Page 30. . . . . . . . . . . . . . . . . . . . . . . . . .
VII Wiring and Sequence of Operation Page 32. . . . . .
VIII SureLight Troubleshooting Guide Page 38. . . . . . .
IMPORTANT
Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon­nect switch(es). Unit may have multiple power supplies.
WARNING
Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury.
Page 2
Page 2
SPECIFICATIONS
Gas
ModelNo. G50UH−24A−045 G50UH−24A−070 G50UH−36A−070 G50UH−48B−070 Heating Performance
Low NOx Model No. G50UH−24A−045X − − − − G50UH−36A−070X − − − −
Input− Btuh (kW) 44,000 (12.9) 66,000 (19.3) 66,000 (19.3) 66,000 (19.3)
Output− Btuh (kW) 36,000 (10.5) 54,100 (15.8) 54,100 (15.8) 54,000 (15.8)
AFUE 80.0% 80.0% 80.0% 80.0%
California Seasonal Efficiency 74.2% 74.8% 74.8% 72.9%
Highstatic(AGA/CGA)− in.w.g. (Pa) .50 (124) .50 (124) .50 (124) .50 (124)
Flue connection − in. (mm) round 4 (102) 4 (102) 4 (102) 4 (102)
GaspipesizeIPS− in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7)
Temperature rise range − F (C) 35 − 65 (19 − 36) 40 − 70 (22 − 39) 40 − 70 (22 − 39) 25 − 55 (15 − 33)
Indoor
Wheelnominaldiameter xwidth −in. (mm) 10 x 7 (254 x 178) 10 x 7 (254 x 178) 10 x 8 (254 x 203) 10 x 10 (254 x 254)
Blower
Motoroutput − hp (W) 1/5 (149) 1/5 (149) 1/3 (249) 1/2 (373)
Tons(kW) ofadd-oncooling 2 (7.0) 2 (7.0) 2 − 3 (7.0 − 10.6) 2 − 4 (7.0 − 14.1)
Shippingweight − 1 package 121 lbs. (55 kg) 127 lbs. (58 kg) 132 lbs. (60 kg) 139 lbs. (63 kg)
Matching Coils
Up−flow cased
C33−18A−2F, C33−24A−2F, C33−30A−2F, C33−36A−2F,
C33−38A−2F
C33−24B−2F, C33−30B−2F, C33−36B−2F, C33−38B−2F, C33−42B−2F, C33−48B−2F
Horizontal CH33−18A−2F, CH33−24/30A−2F, CH33−36A−2F
CH33−36B−2F, CH33−42B−2F,
CH33−44/48B−2F
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
Air Filter and Rack Kit Number and size of filters
Horizontal (end) 87L95 − (1) 14 x 25 x 1 in. (356 x 635 x 25 mm)
87L96 − (1) 18 x 25 x 1
in.
(457 x 635 x 25 mm)
Side Return Single (44J22) or Ten Pack (66K63) − (1) 16 x 25 x 1 in. (406 x 635 x 25 mm)
EZ Filter
Catalog Number − Shipping Weight 73P55 − 6 lbs. (3 kg) 73P56 − 7 lbs. (3 kg)
Base
Dimensions − H x W x D 4 x 14−1/4 x 28−5/8 in. (102 x 362 x 727 mm)
4 x 17−5/8 x 28−5/8 in. (102 x 448 x 727 mm)
Number and size of filter (field provided) 14 x 25 x 1 in. (356 x 635 x 25 mm)
16 x 25 x 1 in.
(406 x 635 x 25 mm)
Horizontal Support Frame Kit − Ship. Weight − lbs. (kg) 56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8)
LPG/Propane Kit See High Altitude Table Page 15
Twinning Kit 15L38 15L38 15L38 15L38
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. NOTE − Filters and provisions for mounting are not furnished and must be field provided. The same C33 uncased models match the furnaces shown but require an optional adaptor base or field fabricated transition. See C33 coil bulletin for additional informa­tion.
Cleanable polyurethane frame type filter.Canada Only.
Page 3
Page 3
SPECIFICATIONS
Gas
ModelNo. G50UH−36B−090 G50UH−48B−090 G50UH−36C−110 G50UH−48C−110 Heating Performance
Low NOx Model No. − − − − G50UH−48B−090X
− − − − − − − −
Input− Btuh (kW) 88,000 (25.8) 88,000 (25.8) 110,000 (32.2) 110,000 (32.2)
Output− Btuh (kW) 72,100 (21.1) 72,100 (21.1) 90,200 (26.4) 88,500 (25.9)
AFUE 80.0% 80.0% 80.0% 80.0%
California Seasonal Efficiency 75.7% 75.3% 75.7% 75.0%
Highstatic(AGA/CGA)− in.w.g. (Pa) .50 (124) .50 (124) .50 (124) .50 (124)
Flue connection − in. (mm) round 4 (102) 4 (102) 4 (102) 4 (102)
GaspipesizeIPS− in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7)
Temperature rise range − F (C) 40 − 70 (22 − 39) 40 − 70 (22 − 39) 50 − 80 (28 − 44) 40 − 70 (22 − 39)
Indoor
Wheelnominaldiameter xwidth −in.
(mm)
10 x 8 (254 x 203) 10 x 10 (254 x 254) 10 x 8 (254 x 203) 10 x 10 (254 x 254)
Blower
Motoroutput − hp (W) 1/3 (249) 1/2 (373) 1/3 (249) 1/2 (373)
Tons(kW) ofadd-oncooling 2 − 3 (7.0 − 10.6) 2 − 4 (7.0 − 14.1) 2 − 3 (7.0 − 10.6) 2 − 4 (7.0 − 14.1)
Shippingweight − 1 package 146 lbs. (66 kg) 153 lbs (69 kg) 166 lbs. (75 kg) 169 lbs. (77 kg)
Matching Coils
Up−flow cased
C33−24B−2F, C33−30B−2F, C33−36B−2F, C33−38B−2F, C33−42B−2F, C33−48B−2F
C33−36C−2F, C33−48C−2F, C33−50/60C−2F,
Horizontal
CH33−36B−2F, CH33−42B−2F,
CH33−44/48B−2F
CH33−36C−2F, CH33−48C−2F,
CH33−50/60C−2F
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
Air Filter & Rack Kit
Horizontal (end) 87L96 − (1) 18 x 25 x 1 in. (457 x 635 x 25 mm) 87L97 − (1) 20 x 25 x 1 in. (508 x 635 x 25 mm)
Kit
Number & size of fil­ters
Side Return Single 44J22 or Ten Pack (66K63) − (1) 16 x 25 x 1 in. (406 x 635 x 25 mm)
EZ Filter
Catalog Number − Shipping Weight 73P56 − 7 lbs. (3 kg) 73P57 − 8 lbs. (4 kg)
Base
Dimensions − H x W x D 4 x 17−5/8 x 28−5/8 in. (102 x 448 x 727 mm) 4 x 21−5/8 x 28−5/8 in. (102 x 549 x 727 mm)
Number and size of field provided
filter
16 x 25 x 1 in. (406 x 635 x 25 mm) 20 x 25 x 1 in. (508 x 635 x25 mm)
Horizontal Support Frame Kit − Ship. Weightlbs. (kg)
56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8)
LPG/Propane Kit See High Altitude Table Page 15
Twinning Kit 15L38 15L38 15L38 15L38
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. NOTE − Filters and provisions for mounting are not furnished and must be field provided.
The same C33 uncased models match the furnaces shown but require an optional adaptor base or field fabricated transition. See C33 coil bulletin for additional information.Cleanable polyurethane frame type filter.Canada Only.
Page 4
Page 4
SPECIFICATIONS
ModelNo. G50UH−60C−110 G50UH−48C−135 G50UH−60D−135 G50UH−60D−155
Gas
Input− Btuh (kW) 110,000 (32.2) 132,000 (38.7) 132,000 (38.7) 154,000 (45.1)
Heating Performance
Output− Btuh (kW) 90,200 (26.4) 106,900 (31.3) 106,900 (31.3) 124,700 (36.5)
AFUE 80.0% 80.0% 80.0% 80.0%
California Seasonal Efficiency 75.7% 76.0% 75.0% 75.6%
Highstatic(AGA/CGA)− in.w.g. (Pa) .50 (124) .50 (124) .50 (124) .50 (124)
Flue connection − in. (mm) round 4 (102) 4 (102) 4 (102) 4 (102)
GaspipesizeIPS− in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7)
Temperature rise range − F (C) 35 − 65 (19 − 36) 50 − 80 (28 − 44) 45 − 75 (25 − 42) 50 − 80 (28 − 44)
Indoor Blower
Wheelnominaldiameter xwidth −in.
(mm)
11−1/2 x 10 (292 x 254) 10 x 10 (254 x 254) 11−1/2 x 10 (292 x 254) 11−1/2 x 10 (292 x 254)
Motoroutput − hp (W) 3/4 (560) 1/2 (373) 3/4 (560) 3/4 (560)
Tons(kW) ofadd-oncooling 5 − 5+ (17.6 − 17.6+) 2 − 4 (7.0 − 14.1) 5 − 5+ (17.6 − 17.6+) 5 − 5+ (17.6 − 17.6+)
Shippingweight − 1 package 172 lbs. (78 kg) 178 lbs. (81 kg) 192 lbs. (87 kg) 201 lbs. (91 kg)
Matching Coils
Up−flow cased C33−36C−2F, C33−48C−2F, C33−50/60C−2F, C33−60D−2F, C33−62D−2F
Horizontal
CH33−36C−2F, CH33−48C−2F,
CH33−50/60C−2F
CH33−60D−2F, CH33−62D−2F
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
Air Filter and Rack Kit
Horizontal (end)
87L97 (1) 20 x 25 x 1 in. (508 x 635 x 25 mm) 87L98 (1) 25 x 25 x 1 in. (635 x 635 x 25 mm)
Kit
Number & size of fil­ters
Side Return Single 44J22 or Ten Pack (66K63) − (1) 16 x 25 x 1 (406 x 635 x 25)
EZ Filter
Catalog Number − Shipping Weight 73P57 − 8 lbs. (4 kg) 73P58 − 10 lbs. (5 kg)
Base
Dimensions − H x W x D 4 x 21−5/8 x 28−5/8 in. (102 x 549 x 727 mm) 4 x 24−5/8 x 28−5/8 in. (102 x 625 x 727 mm)
Number and size of field provided fil-
ter
20 x 25 x 1 in. (508 x 635 x25 mm) 24 x 24 x 1 in. (610 x 610 x 25 mm)
High Altitude Orifice Kit − Natural Gas Only 47M82 47M82 47M82 47M82
High Altitude
4501−7500 ft. (1372−2286 m) 49L90 49L90 49L90 49L90
Pressure Switch Kit
7501−10,000 ft. (2286−3048m) 15M22 15M22 15M22 15M22
Horizontal Support Frame Kit − Ship. Weight − lbs. (kg) 56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8)
RAB Return Air Base RAB60C (12M71) − − − − RAB60D (12M72) RAB60D (12M72)
LPG/Propane Kit See High Altitude Table Page 15
Twinning Kit 15L38 15L38 15L38 15L38
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. NOTE − Filters and provisions for mounting are not furnished and must be field provided.
The same C33 uncased models match the furnaces shown but require an optional adaptor base or field fabricated transition. See C33 coil bulletin for additional information.Required for proper operation at altitudes over 4500 ft. (1370 m).Cleanable polyurethane frame type filter.Flue connection on the unit is 4 in. (102 mm) diameter. Most applications will require 5 in. (127 mm) venting and field supplied 4 x 5 in. (102 x 127 mm) adaptor. See Venting
Tables in the Installation Instructions for detailed information.
Not for use with RAB Return Air Base or with 60C and 60D size units with air flow requirements of 1800 cfm (850 L/s) or greater. See Blower Performance Tables
for additional information.
Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).
Page 5
Page 5
SPECIFICATIONS
Gas
ModelNo. G50UH−60C−110−4 G50UH−60D−135−4 G50UH−60D−155−4 Heating Performance
Input− Btuh (kW) 110,000 (32.2) 132,000 (38.7) 154,000 (45.1)
Output− Btuh (kW) 89,400 (26.2) 106,900 (31.3) 124,700 (36.5)
AFUE 80.0% 80.0% 80.0%
California Seasonal Efficiency 73.9% 75.0% 75.6%
Highstatic(AGA/CGA)− in.w.g. (Pa) .50 (124) .50 (124) .50 (124)
Flue connection − in. (mm) round 4 (102) 4 (102) 4 (102)
GaspipesizeIPS− in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7)
Temperature rise range − F (C) 30 − 60 (18 − 36) 45 − 75 (25 − 42) 50 − 80 (28 − 44)
Indoor
Wheelnominaldiameter xwidth −in. (mm) 11−1/2 x 10 (292 x 254) 11−1/2 x 10 (292 x 254) 11−1/2 x 10 (292 x 254)
Blower
Motoroutput − hp (W) 1 (746) 1 (746) 1 (746)
Tons(kW) ofadd-oncooling 5 (17.6) 5 (17.6) 5 (17.6)
Shippingweight − 1 package 175 lbs. (79 kg) 195 lbs. (88 kg) 204 lbs. (93 kg)
Matching Coils
Up−flow cased
C33−36C−2F, C33−48C−2F,
C33−50/60C−2F,
C33−60D−2F, C33−62D−2F
Horizontal
CH33−36C−2F, CH33−48C−2F,
CH33−50/60C−2F
CH33−60D−2F, CH33−62D−2F
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
Air Filter and Rack Kit Number & size of filters
Horizontal (end)
87L97 (1) 20 x 25 x 1
in. (508 x 635 x 25 mm)
87L98 (1) 25 x 25 x 1 in. (635 x 635 x 25 mm)
Side Return
Single 44J22 or Ten Pack (66K63) − (1) 16 x 25 x 1 (406 x 635 x
25)
EZ Filter
Catalog Number − Shipping Weight 73P57 − 8 lbs. (4 kg) 73P58 − 10 lbs. (5 kg)
Base
Dimensions − H x W x D
4 x 21−5/8 x 28−5/8 in.
(102 x 549 x 727 mm)
4 x 24−5/8 x 28−5/8 in. (102 x 625 x 727 mm)
Number and size of field provided filter
20 x 25 x 1 in. (508 x
635 x25 mm)
24 x 24 x 1 in. (610 x 610 x 25 mm)
Horizontal Support Frame Kit − Ship. Weight − lbs. (kg) 56J18 − 18 (8) 56J18 − 18 (8) 56J18 − 18 (8)
RAB Return Air Base RAB60C (12M71) RAB60D (12M72) RAB60D (12M72)
LPG/Propane Kit See High Altitude Table Page 15
Twinning Kit 15L38 15L38 15L38
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. NOTE − Filters and provisions for mounting are not furnished and must be field provided.
The same C33 uncased models match the furnaces shown but require an optional adaptor base or field fabricated transition. See C33 coil bulletin for additional information.Cleanable polyurethane frame type filter.Flue connection on the unit is 4 in. (102 mm) diameter. Most applications will require 5 in. (127 mm) venting and field supplied 4 x 5 in. (102 x 127 mm) adaptor. See Venting
Tables in the Installation Instructions for detailed information.
Not for use with RAB Return Air Base or with 60C and 60D size units with air flow requirements of 1800 cfm (850 L/s) or greater. See Blower Performance Tables
for additional information.
Page 6
Page 6
BLOWER DATA
G50UH−24A−045 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1090 515 460 905 425 390 725 340 300
0.05 12 1080 510 450 900 425 390 720 340 300
0.10 25 1065 505 445 895 420 385 710 335 295
0.15 37 1050 495 435 895 420 380 700 330 290
0.20 50 1030 485 425 890 420 375 690 325 290
0.25 62 1015 480 415 875 415 370 680 320 285
0.30 75 995 470 410 860 405 365 665 315 280
0.40 100 960 455 395 840 395 350 650 305 270
0.50 125 910 430 380 795 375 335 610 290 260
0.60 150 840 395 355 750 355 315 540 255 245
0.70 175 770 365 340 665 315 295 490 230 235
0.80 200 660 310 315 555 260 275 420 200 225
0.90 225 560 265 295 480 225 260 355 170 210
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−24A−070 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1075 505 445 905 425 375 730 345 290
0.05 12 1070 505 445 900 425 375 725 340 290
0.10 25 1065 505 440 895 420 370 720 340 285
0.15 37 1060 500 435 890 420 365 715 335 285
0.20 50 1055 500 430 885 420 360 710 335 280
0.25 62 1045 495 425 880 415 360 700 330 280
0.30 75 1030 485 415 875 415 355 690 325 270
0.40 100 1010 475 400 860 405 350 675 320 270
0.50 125 975 460 390 840 395 340 660 310 265
0.60 150 940 445 375 805 380 325 640 300 255
0.70 175 890 420 360 755 355 305 605 285 240
0.80 200 830 390 340 700 330 285 565 265 225
0.90 225 765 360 305 640 300 265 515 245 205
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 7
Page 7
BLOWER DATA
G50UH−36A−070 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1500 710 705 1290 610 565 985 465 455 830 390 375
0.05 12 1475 695 695 1275 600 555 980 465 445 820 385 365
0.10 25 1450 685 680 1255 590 545 970 460 440 810 380 360
0.15 37 1425 675 670 1240 585 535 965 455 430 805 380 355
0.20 50 1400 660 655 1225 580 525 955 450 425 795 375 350
0.25 62 1370 645 645 1205 570 510 945 445 415 790 375 345
0.30 75 1340 630 630 1180 555 500 930 440 405 780 370 335
0.40 100 1285 605 610 1140 540 475 900 425 390 745 350 325
0.50 125 1215 575 580 1080 510 450 865 410 375 705 335 310
0.60 150 1150 545 560 1015 480 430 810 380 355 655 310 290
0.70 175 1060 500 535 940 445 405 730 345 330 585 275 270
0.80 200 955 450 515 800 375 370 655 310 305 480 225 260
0.90 225 785 370 475 605 285 325 585 275 270 410 195 255
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−36B−090 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1500 710 720 1255 590 595 1040 490 460 900 425 370
0.05 12 1485 700 705 1250 590 580 1040 490 450 895 420 365
0.10 25 1465 690 685 1240 585 570 1035 490 445 890 420 360
0.15 37 1450 685 675 1235 585 555 1035 490 440 885 420 355
0.20 50 1435 675 660 1225 580 545 1030 485 435 880 415 350
0.25 62 1420 670 645 1215 575 530 1025 485 425 875 415 345
0.30 75 1400 660 630 1200 565 520 1020 480 415 870 410 340
0.40 100 1345 635 595 1170 550 495 1000 470 400 855 405 330
0.50 125 1300 615 575 1135 535 475 965 455 380 830 390 300
0.60 150 1235 585 545 1080 510 445 930 440 360 780 370 290
0.70 175 1165 550 510 1020 480 415 870 410 340 740 350 280
0.80 200 1080 510 480 940 445 385 800 380 315 670 315 260
0.90 225 985 465 445 840 395 355 710 335 290 600 285 245
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 8
Page 8
BLOWER DATA
G50UH−36C−110 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1555 735 715 1335 630 575 1085 510 460 925 435 365
0.05 12 1540 725 705 1330 630 555 1080 510 450 920 435 360
0.10 25 1525 720 690 1320 625 545 1075 505 440 915 430 355
0.15 37 1510 715 680 1310 620 535 1070 505 430 910 430 350
0.20 50 1490 705 670 1295 610 525 1065 505 420 900 425 340
0.25 62 1465 690 655 1280 605 510 1060 500 415 890 420 335
0.30 75 1440 680 645 1260 595 495 1050 495 405 880 415 330
0.40 100 1385 655 615 1230 580 485 1030 485 390 865 410 320
0.50 125 1320 625 590 1190 560 460 995 470 375 835 395 300
0.60 150 1260 595 570 1135 535 430 960 455 355 815 385 295
0.70 175 1190 560 545 1075 505 410 915 430 345 775 365 285
0.80 200 1090 515 515 970 460 385 860 405 325 760 360 280
0.90 225 975 460 485 880 415 360 790 375 305 705 335 275
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−48B−070 PERFORMANCE
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2080 980 846 1810 855 764 1535 725 634 1295 610 519
.10 25 2030 955 810 1790 845 714 1520 715 600 1285 605 492
.20 50 1955 920 767 1760 830 675 1515 715 566 1275 600 477
.30 75 1885 890 732 1710 805 640 1505 710 555 1265 595 459
.40 100 1820 860 699 1670 790 611 1470 695 525 1255 590 443
.50 125 1740 820 664 1600 755 575 1420 670 496 1215 575 414
.60 150 1635 770 624 1530 720 544 1350 635 464 1175 555 400
.70 175 1545 730 597 1420 670 501 1270 600 432 1080 510 368
.80 200 1400 660 554 1295 610 462 1135 535 392 990 465 343
.90 225 1250 590 512 1125 530 419 1050 495 372 875 410 310
NOTES − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G50UH−48B−090 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1970 930 790 1810 855 735 1585 750 670 1340 630 565
0.05 12 1940 915 780 1785 840 715 1580 745 650 1335 630 555
0.10 25 1915 905 765 1760 830 695 1570 740 630 1325 625 540
0.15 37 1880 885 745 1730 815 660 1560 735 615 1325 625 530
0.20 50 1840 870 730 1700 800 620 1545 730 600 1320 625 520
0.25 62 1805 850 715 1670 790 625 1520 715 585 1310 620 510
0.30 75 1765 835 695 1640 775 625 1490 705 565 1295 610 500
0.40 100 1695 800 670 1570 740 595 1440 680 540 1260 595 480
0.50 125 1600 755 635 1490 705 560 1360 640 505 1195 565 450
0.60 150 1505 710 600 1400 660 530 1285 605 480 1140 540 425
0.70 175 1395 660 565 1265 595 485 1170 550 440 990 465 380
0.80 200 1250 590 520 1100 520 445 975 460 390 905 425 355
0.90 225 1005 475 460 870 410 385 900 425 365 810 380 325
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 9
Page 9
BLOWER DATA
G50UH−48C−110 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2015 950 895 1620 765 780 1340 630 640 1150 545 525
0.05 12 1990 940 870 1615 760 760 1340 630 640 1150 545 525
0.10 25 1965 925 850 1610 760 745 1340 630 640 1150 545 525
0.15 37 1930 910 825 1605 755 725 1335 630 630 1150 545 525
0.20 50 1895 895 805 1600 755 710 1335 630 615 1150 545 525
0.25 62 1860 880 785 1590 750 695 1330 630 605 1150 545 520
0.30 75 1820 860 765 1580 745 675 1330 630 590 1145 540 515
0.40 100 1740 820 725 1530 720 635 1320 625 560 1140 540 490
0.50 125 1665 785 695 1475 695 600 1285 605 525 1120 530 470
0.60 150 1575 745 650 1405 665 555 1230 580 490 1075 505 445
0.70 175 1475 695 610 1310 620 515 1165 550 470 1015 480 415
0.80 200 1350 635 560 1210 570 485 1080 510 430 930 440 380
0.90 225 1210 570 520 1070 505 430 870 410 365 740 350 325
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−48C−135 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2075 980 820 1800 850 710 1425 675 570 1115 525 435
0.05 12 2035 960 805 1785 840 695 1425 670 560 1120 530 435
0.10 25 1990 940 790 1765 835 675 1420 670 545 1125 530 430
0.15 37 1950 920 765 1740 820 660 1410 665 535 1125 530 425
0.20 50 1905 900 745 1715 810 645 1405 665 525 1120 530 420
0.25 62 1865 880 730 1680 795 625 1390 655 515 1115 525 410
0.30 75 1825 860 715 1650 780 610 1375 650 505 1105 520 405
0.40 100 1740 820 680 1585 745 580 1355 640 485 1090 515 390
0.50 125 1640 775 645 1495 705 545 1300 615 455 1050 495 370
0.60 150 1540 730 615 1420 670 515 1225 580 430 1000 470 355
0.70 175 1420 670 575 1310 615 475 1140 535 400 935 440 330
0.80 200 1260 595 520 1155 545 425 1025 485 365 865 410 315
0.90 225 1125 530 495 1010 475 385 880 415 330 750 355 285
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 10
Page 10
BLOWER DATA
G50UH−60C−110−1, −2, −3 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2450 1155 1220 2300 1085 1060 2056 970 905 1725 815 735
0.05 12 2410 1135 1205 2265 1070 1045 2040 965 895 1715 810 725
0.10 25 2370 1120 1195 2230 1050 1030 2020 955 890 1710 810 720
0.15 37 2325 1095 1175 2200 1040 1015 1995 940 875 1700 800 715
0.20 50 2280 1075 1165 2170 1025 1005 1975 935 870 1695 800 710
0.25 62 2245 1060 1150 2130 1005 990 1950 920 855 1680 795 705
0.30 75 2205 1040 1135 2095 990 975 1925 910 845 1665 785 700
0.40 100 2115 995 1105 2010 950 940 1860 875 820 1625 770 685
0.50 125 2025 955 1060 1945 920 920 1810 855 805 1605 755 675
0.60 150 1910 900 1015 1850 875 885 1715 810 780 1540 730 670
0.70 175 1835 865 1005 1775 840 865 1655 780 765 1495 705 655
0.80 200 1745 825 975 1655 780 835 1540 725 730 1400 660 635
0.90 225 1610 760 945 1540 725 805 1475 695 715 1310 620 615
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60C−110−1, −2, −3 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2395 1130 1230 2260 1065 1085 2015 950 920 1730 815 750
0.05 12 2365 1115 1220 2230 1050 1070 1985 935 905 1720 810 745
0.10 25 2330 1100 1205 2200 1040 1060 1960 925 890 1705 805 750
0.15 37 2285 1080 1190 2170 1025 1045 1030 485 880 1695 800 740
0.20 50 2245 1060 1170 2135 1010 1030 1905 900 870 1675 790 735
0.25 62 2200 1040 1160 2100 990 1020 1890 890 860 1665 785 730
0.30 75 2170 1025 1145 2070 980 1005 1870 880 850 1655 780 720
0.40 100 2085 985 1110 1990 940 975 1825 860 835 1610 760 705
0.50 125 1980 935 1075 1910 900 945 1755 830 810 1555 735 690
0.60 150 1890 890 1045 1835 865 915 1670 790 780 1515 715 680
0.70 175 1800 850 1020 1725 815 885 1615 760 770 1445 685 655
0.80 200 1700 805 995 1645 775 855 1525 720 745 1380 650 645
0.90 225 1590 750 980 1520 720 820 1410 665 710 1300 615 625
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 11
Page 11
BLOWER DATA
G50UH−60C−110 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2655 1250 1407 2370 1120 1063 2085 985 894 1665 785 679
.10 25 2580 1215 1376 2350 1110 1043 2065 975 875 1650 780 667
.20 50 2500 1180 1346 2305 1085 1012 2045 965 849 1645 775 662
.30 75 2410 1135 1305 2230 1050 978 2010 950 820 1640 775 649
.40 100 2320 1095 1270 2165 1020 947 1940 915 786 1625 765 634
.50 125 2225 1050 1235 2090 985 914 1895 895 763 1610 760 622
.60 150 2130 1005 1205 2000 945 880 1840 870 740 1570 740 603
.70 175 2030 955 1155 1915 905 851 1760 830 709 1535 725 590
.80 200 1925 910 1123 1820 860 823 1670 790 681 1475 695 566
.90 225 1795 845 1078 1690 795 788 1560 735 655 1395 660 537
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60C−110 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accom­modate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2430 1145 1309 2245 1060 1006 1910 900 843 1635 770 686
.10 25 2355 1110 1277 2190 1035 978 1905 900 817 1620 765 677
.20 50 2280 1075 1242 2140 1010 950 1885 890 797 1610 760 667
.30 75 2205 1040 1218 2075 980 924 1860 875 782 1605 755 655
.40 100 2130 1005 1189 2005 945 905 1815 855 752 1595 750 636
.50 125 2045 965 1159 1920 905 864 1750 825 726 1565 740 619
.60 150 1955 920 1132 1850 875 840 1700 800 705 1525 720 605
.70 175 1860 875 1105 1760 830 817 1610 760 674 1475 700 582
.80 200 1755 830 1067 1670 790 789 1540 725 654 1395 660 560
.90 225 1645 775 1033 1575 745 763 1445 680 627 1325 625 540
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60D−135−1, −2, −3 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2465 1165 1205 2325 1100 1060 2155 1015 930 1895 895 780
0.05 12 2430 1145 1195 2295 1085 1050 2125 1000 920 1875 885 770
0.10 25 2395 1130 1180 2265 1070 1040 2095 990 910 1855 875 765
0.15 37 2350 1110 1165 2230 1050 1025 2070 975 900 1830 865 755
0.20 50 2310 1090 1150 2195 1035 1010 2045 965 890 1805 850 745
0.25 62 2265 1070 1135 2155 1015 995 2010 950 875 1785 840 735
0.30 75 2220 1050 1120 2115 1000 980 1975 930 865 1765 830 730
0.40 100 2120 1000 1080 2035 960 950 1915 905 845 1715 810 720
0.50 125 2050 970 1055 1955 925 925 1830 865 815 1645 775 700
0.60 150 1930 910 1015 1860 880 895 1745 825 795 1585 745 680
0.70 175 1835 865 985 1775 840 870 1655 780 770 1530 720 670
0.80 200 1720 810 955 1645 775 830 1560 735 745 1445 685 650
0.90 225 1595 755 925 1535 725 800 1455 685 720 1310 620 620
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 12
Page 12
BLOWER DATA
G50UH−60D−135−1, −2, −3 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2350 1110 1180 2225 1050 1035 2055 970 905 1855 875 775
0.05 12 2310 1090 1170 2195 1035 1025 2035 960 895 1835 865 765
0.10 25 2275 1075 1155 2165 1020 1010 2010 950 885 1815 855 760
0.15 37 2235 1055 1140 2130 1005 1000 1980 935 875 1795 845 755
0.20 50 2195 1035 1130 2100 990 985 1945 920 865 1775 835 750
0.25 62 2155 1020 1115 2055 970 970 1915 905 855 1750 825 740
0.30 75 2115 1000 1100 2010 950 950 1885 890 845 1725 815 735
0.40 100 2010 950 1055 1940 915 930 1830 865 830 1665 785 720
0.50 125 1930 910 1035 1860 880 905 1745 825 805 1600 755 705
0.60 150 1830 865 1005 1770 835 880 1655 780 775 1530 720 685
0.70 175 1735 820 985 1655 780 845 1595 755 765 1480 700 675
0.80 200 1645 775 955 1545 730 815 1480 700 735 1375 650 650
0.90 225 1515 715 925 1435 675 785 1385 655 710 1290 610 630
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60D−135 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2715 1280 1407 2255 1065 1070 1910 900 850 1660 785 674
.10 25 2640 1245 1403 2250 1060 1030 1900 895 834 1645 775 668
.20 50 2540 1200 1355 2245 1060 1006 1890 890 821 1630 770 665
.30 75 2480 1170 1319 2200 1040 975 1890 890 781 1625 765 656
.40 100 2390 1125 1282 2155 1015 940 1885 890 775 1615 760 642
.50 125 2320 1095 1251 2085 985 904 1860 875 758 1605 755 631
.60 150 2205 1040 1210 2020 955 876 1815 855 731 1595 750 611
.70 175 2080 980 1161 1935 915 839 1760 830 707 1545 730 588
.80 200 2010 950 1122 1855 875 810 1690 795 679 1495 705 568
.90 225 1880 885 1071 1755 830 781 1585 745 646 1430 675 545
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60D−135 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accom­modate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2455 1160 1336 2170 1025 1019 1850 875 829 1555 735 673
.10 25 2380 1125 1299 2140 1010 974 1840 870 812 1550 730 664
.20 50 2305 1085 1266 2105 995 947 1830 865 791 1545 730 656
.30 75 2235 1055 1234 2045 965 914 1820 860 774 1540 725 642
.40 100 2160 1020 1240 1985 935 886 1800 850 755 1540 725 628
.50 125 2065 975 1170 1925 910 863 1745 825 726 1535 725 614
.60 150 1990 940 1146 1870 880 844 1700 800 706 1505 710 599
.70 175 1895 895 1111 1775 835 808 1655 780 689 1465 690 573
.80 200 1805 850 1074 1680 790 779 1565 740 656 1425 670 562
.90 225 1695 800 1042 1590 750 752 1480 700 630 1335 630 533
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 13
Page 13
BLOWER DATA
G50UH−60D−155−1, −2, −3 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2380 1120 1135 2235 1055 1000 2060 970 875 1875 885 750
0.05 12 2340 1105 1130 2205 1040 990 2035 960 865 1840 870 745
0.10 25 2305 1090 1125 2180 1030 975 2015 950 855 1810 855 735
0.15 37 2265 1070 1105 2145 1010 960 1990 940 845 1790 845 725
0.20 50 2220 1045 1090 2105 995 945 1960 925 835 1765 835 720
0.25 62 2180 1030 1075 2080 980 935 1935 910 825 1740 820 710
0.30 75 2145 1010 1065 2050 965 925 1905 900 815 1715 810 700
0.40 100 2060 970 1040 1975 930 900 1845 870 795 1655 780 685
0.50 125 1955 925 1005 1890 890 870 1765 835 770 1610 760 670
0.60 150 1885 890 975 1795 850 840 1695 800 750 1560 735 655
0.70 175 1800 850 955 1730 815 815 1605 760 720 1480 700 635
0.80 200 1700 805 930 1630 770 785 1520 715 695 1405 660 615
0.90 225 1575 745 895 1525 720 760 1395 660 660 1285 605 585
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G50UH−60D−155−1, −2, −3 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2230 1050 1080 2130 1005 945 1995 940 840 1830 865 745
0.05 12 2200 1035 1070 2105 990 935 1970 930 830 1810 855 735
0.10 25 2165 1025 1060 2075 980 930 1950 920 820 1795 845 725
0.15 37 2135 1005 1050 2040 965 915 1920 905 815 1765 835 720
0.20 50 2100 990 1035 2005 945 905 1890 895 805 1735 820 710
0.25 62 2050 965 1015 1975 930 895 1855 875 795 1705 805 700
0.30 75 2000 945 995 1940 915 880 1820 860 780 1675 790 690
0.40 100 1905 900 965 1860 875 850 1755 825 770 1630 770 680
0.50 125 1825 860 945 1780 840 830 1700 800 750 1555 735 660
0.60 150 1745 825 920 1690 795 805 1595 750 715 1495 705 645
0.70 175 1650 780 905 1610 760 785 1515 715 705 1430 675 625
0.80 200 1565 740 880 1520 715 755 1445 680 680 1330 630 605
0.90 225 1445 685 845 1385 655 720 1300 610 640 1225 580 575
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Page 14
Page 14
BLOWER DATA
G50UH−60D−155 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2670 1260 1386 2325 1095 1048 1970 930 857 1700 800 706
.10 25 2580 1215 1342 2320 1095 1045 1965 925 842 1690 795 696
.20 50 2510 1185 1311 2255 1065 985 1960 925 817 1640 775 662
.30 75 2425 1145 1277 2210 1040 953 1955 920 803 1635 770 649
.40 100 2345 1105 1246 2150 1015 922 1925 910 778 1630 770 633
.50 125 2255 1065 1217 2095 990 897 1890 890 752 1615 760 618
.60 150 2170 1025 1182 2010 950 863 1840 870 733 1590 750 605
.70 175 2090 985 1139 1925 910 833 1785 840 708 1550 730 588
.80 200 1895 895 1106 1840 870 806 1710 805 683 1500 705 571
.90 225 1855 875 1064 1740 820 776 1620 765 655 1430 675 551
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
BLOWER DATA
G50UH−60D−155 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to accom­modate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 2410 1135 1282 2175 1025 987 1870 880 833 1620 765 675
.10 25 2335 1100 1257 2140 1010 956 1860 875 810 1610 760 667
.20 50 2255 1065 1225 2085 985 918 1855 875 788 1605 755 658
.30 75 2205 1040 1200 2025 955 896 1830 865 764 1600 755 647
.40 100 2120 1000 1164 1975 930 874 1795 845 742 1595 750 628
.50 125 2040 960 1131 1905 900 847 1745 825 731 1575 745 618
.60 150 1955 920 1103 1835 865 820 1695 800 698 1540 725 601
.70 175 1870 880 1069 1760 830 792 1635 770 673 1465 690 568
.80 200 1770 835 1041 1670 790 763 1560 735 646 1415 665 548
.90 225 1660 785 1006 1585 745 740 1480 700 629 1345 635 527
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
FILTER AIR RESISTANCE ALL UNITS
cfm (L/s) in. w.g. (Pa)
0 (0) 0.00 (0)
200 (95) 0.01 (0)
400 (190) 0.03 (5)
600 (285) 0.04 (10)
800 (380) 0.06 (15)
1000 (470) 0.09 (20)
1200 (565) 0.12 (30)
1400 (660) 0.15 (35)
1600 (755) 0.19 (45)
1800 (850) 0.23 (55)
2000 (945) 0.27 (65)
2200 (1040) 0.33 (80)
2400 (1130) 0.38 (95)
2600 (1225) 0.44 (110)
Page 15
Page 15
HIGH ALTITUDE
All −1 to −14
models − Pressure regulator adjustment may be required depending on altitude. See below for proper pressure regulator setting.
Manifold Pressure (Outlet) in. w.g. (kPa)
ALTITUDE ft. (m)
FUEL
0−4500
(0−1372)
4501−5500
(1373−1676)
5501−6500
(1677−1981)
6501−7500
(1982−2286)
Natural Gas 3.5 (.87) 3.3 (.82) 3.2 (.80) 3.1 (.77)
LPG/Propane 10.0 (2.49)
All −15 and later models − Pressure regulator adjustment
is not rquired. See below for proper pressure regulator setting.
Manifold Pressure (Outlet) in. w.g. (kPa)
ALTITUDE ft. (m)
FUEL
0 − 10,000 (0 − 3048)
Natural Gas 3.5 (.87)
LPG/Propane 10.0 (2.49)
HIGH ALTITUDE
G50UH−1
1
High Altitude
Orifice Kit
High Altitude Prove
Switch Kit
LPG/Propane Kit
G50UH−1
to −14
Natural Gas Only
4501−7500 ft.
(1373 − 2286m)
7501−10,000 ft. (2287 − 3048m)
0−7500 ft.
(0 − 2286m)
7501−10,000 ft. (2287 − 3048m)
−045−
−070
47M82 56L32 56L32 45L60 47M81
−090 47M82 49L90 15M22 45L60 47M81
−110 47M82 49L90 15M22 45L60 47M81
−135 47M82 49L90 15M22 45L60 47M81
−155 47M82 49L90 15M22 45L60 47M81
G50UH−15
1
High Altitude
Orifice Kit
High Altitude Pressure
Switch Kit
LPG/Propane Kit
G50UH−15
and later
Natural Gas Only
4501−7500 ft.
(1373 − 2286m)
7501−10,000 ft. (2287 − 3048m)
0−7500 ft.
(0 − 2286m)
7501−10,000 ft. (2287 − 3048m)
all models 59M17 NO CHANGE 56L32 25W20 25W21
1
Required for proper operation at altitudes from 7501 to 10,000 ft.
Page 16
Page 16
Flue Transition
Combustion Air Inducer
Combustion Air Orifice
Combustion Air
Prove Switch
Flue Collector Box
Heat Exchanger
Flame Sensor
Gas Valve
Burners
Ignitor
NOx Insert
Primary Limit
Blower Assembly
Capacitor
Gasket
Flue Box Gasket
Flame Rollout Switches*
Flame Rollout Bracket
Gas Orifices
Ignitor Bracket
Burner Bottom Shield
Limit Shield
Secondary Limit
(as required)
(NOx Units Only)
G50UH(X) PARTS ARRANGEMENT
(UP FLOW POSITION)
FIGURE 1
Gas Manifold
*135 and 155 kBtuh units only −− Flame rollout switches are located on brackets on the inner sides (one on the left and one on the right) of the burner box.
Air Deflector ALL G50UH−48C−135, ALL G50UH−36C−110.
ALL G50UH−60D−155 &
G50UH−60C−110−1, −2, −3
Units Only
SURELIGHT
CONTROL BOARD
TRANSFORMER
CIRCUIT BREAKER
DOOR INTERLOCK
SWITCH
Pressure Port
Pressure Port Location
for −1 to −14 units
Page 17
Page 17
FIGURE 2
G50UH(X) PARTS IDENTIFICATION
(HORIZONTAL POSITION)
BLOWER
ACCESS PANEL
HEAT EXCHANGER ASSEMBLY
BURNER
ASSEMBLY
COMBUSTION AIR
INDUCER
CONTROL
BOARD
PROVE
SWITCH
GAS VALVE
BURNER
ACCESS PANEL
BLOWER ASSEMBLY
PRIMARY LIMIT
FIGURE 3
G50UH (X) HEATING COMPONENTS
COMBUSTION AIR INDUCER
PROVE SWITCH
PRIMARY LIMIT
PRIMARY LIMIT SHIELD
GAS VALVE
ROLLOUT SWITCHES*
MANIFOLD/BURNER
ASSEMBLY
NOx Insert
(NOx Units Only)
HEAT EXCHANGER
FLUE COLLECTOR BOX
*135 and 155 kBtuh units only −− Flame rollout switches are located on brackets on the inner sides (one on the left and one on the right) of the burner box.
Air Deflector ALL G50UH−48C−135, ALL G50UH−36C−110.
ALL G50UH−60D−155 &
G50UH−60C−110−1, −2, −3
Units Only
Page 18
Page 18
I−UNIT COMPONENTS
G50UH(X) unit components are shown in figures 1, 2 and
3. The gas valve, combustion air inducer and burners can be accessed by removing the burner access panel. Electri­cal components are in the control box (figure 4) found in the blower section. G50UH(X) units are factory equipped with a bottom return air
panel in place. The panel is designed to be field removed as required for bottom air return. Markings are provided for side return air and may be cut out in the field.
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic dis­charge by putting the furnace, the control and the technician at the same electrostatic poten­tial. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before per­forming any service procedure.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V sec­ondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in se­ries with line voltage. When the blower door is removed the unit will shut down.
FIGURE 4
CONTROL BOX
G50UH(X)
SURELIGHT
CONTROL
BOARD
TRANSFORMER
CIRCUIT BREAKER
DOOR INTERLOCK
SWITCH
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the trans­former (T1). The breaker is rated 3A at 32V. If the cur­rent exceeds this limit the breaker will trip and all unit op­eration will shutdown. The breaker can be manually re­set by pressing the button on the face. See figure 5.
FIGURE 5
CIRCUIT BREAKER CB8
PRESS TO RESET
WARNING
Shock hazard. Disconnect power before servicing. Control is
not field repairable. If control is inoperable, sim­ply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
4. SureLight Integrated Ignition Control (A92) 56L83 & 97L48
The Lennox SureLight ignition system consists of ignition
control board (figure 6 with control terminal designations
in table 1), sensor (figure 10) and ignitor (figure 12). The
ignition control and ignitor work in combination to ensure
furnace ignition and ignitor durability. The ignition control ,
controls all major furnace operations. The ignition control
also features two LED lights for troubleshooting (DIAG 1
green and DIAG 2 green) and two accessory terminals
rated at (1) one amp. Tables 2 and 3 show jack plug termi-
nal designations. See table 8 for troubleshooting diagnos-
tic codes. Units equipped with the SureLight system can
be used with either electronic or electro−mechanical ther-
mostats without modification. The SureLight ignitor is
made of durable silicon−nitride. Ignitor longevity is also
enhanced by voltage ramping by the control board. The
ignition control finds the lowest ignitor temperature which
will successfully light the burner, thus increasing the life of
the ignitor. Each time power is applied to the furnace, the
ignition control performs a selfcheck including energizing
the combustion air inducer for a period of 1 second.
Page 19
Page 19
SURELIGHT INTEGRATED CONTROL BOARD
FIGURE 6
J58
J156
TABLE 1
SURELIGHT CONTROL TERMINAL DESIGNATIONS
ACB COOL ACB HEAT PARK ACB LOW ACC TX HOT HTG ACC NEUTRALS 24VAC HOT 24VAC RTN FLAME SENSE
Blower − Cooling Speed (Line Volt) Blower − Heating Speed (Line Volt) Alternate Blower Speeds (Dead) Continuous Low Speed Blower Accessory Terminal (Line Volt) 120VAC Hot to Transformer 120VAC Hot Input Heat Only Accessory (Line Volt) 120VAC Neutrals 24VAC Hot from Transformer 24VAC Return from Transformer Flame Sense Terminal
a−Electronic Ignition (See Figure 9)
On a call for heat the SureLight control monitors the com­bustion air inducer prove switch. The control will not begin the heating cycle if the prove switch is closed (by−passed). Once the proving switch is determined to be open, the combustion air inducer is energized. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the prove switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re− set period.
After the 15−second pre−purge period, the SureLight igni­tor warms up for 20 seconds during which the gas valve opens at 19 seconds for a 4−second trial for ignition. Units with control 56L83: ignitor stays energized for the first sec­ond of the 4−second trial. Units with control 97L48: ignitor stays energized during the 4−second ignition trial until flame is sensed. If ignition is not proved during the 4−sec­ond period, the control will try four more times with an inter purge and warm−up time between trials of 35 seconds. Af­ter a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure mode. Af­ter a 60−minute reset period, the control will begin the igni­tion sequence again. The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the low­est power is determined and the cycle begins again.
b−Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. For customized comfort, monitor the supply air temperature once the heat demand is satis­fied. Note the supply air temperature at the instant the blower is de−energized. Adjust the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de−energized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher air temperature). See figure 7.
FIGURE 7
FAN-OFF TIME ADJUSTMENT
To adjust fan−off timing, flip dip switch to desired setting.
60sec. 90sec. 120sec. 180sec.
Page 20
Page 20
TABLE 2
SURELIGHT BOARD 56L83 & 97L48 J156 (J2)
TERMINAL DESIGNATIONS
PIN # FUNCTION
1 Ignitor
2
Not Used
3
Ignitor Neutral
4
Combustion Air Inducer Line Voltage
5
Not Used
6
Combustion Air Inducer Neutral
TABLE 3
SURELIGHT BOARD 56L83 & 97L48 J58 (J1)
TERMINAL DESIGNATIONS
PIN # FUNCTION
1 Primary Limit In
2
Gas Valve Common
3
Roll Out Switch Out
4
Gas Valve 24V
5
Pressure Switch In
6
Pressure Switch and Primary Limit Out
7
Not Used
8
Roll Out Switch In
9
Ground
5. SureLight Integrated Ignition Control (A92) 69M15
The Lennox SureLight ignition system consists of ignition control (figure 8), sensor (figure 10) and ignitor (figure
12). The ignition control and ignitor work in combination
to ensure furnace ignition and ignitor durability. The igni­tion control, controls all major furnace operations. The ignition control also features two LED lights (DS1 red and DS2 green) for troubleshooting and two 120 volt accesso­ry terminals each rated at (1) one amp. A 24 volt accesso­ry terminal rated at 0.5 amps is also provided. Table 4 shows 24 volt and 120 volt control terminal designations. Tables 5 and 6 show jack plug terminal designations. See table 8 for troubleshooting diagnostic codes. Units equipped with the SureLight system can be used with ei­ther electronic or electro−mechanical thermostats without modification. The SureLight ignitor is made of durable sili­con−nitride. Ignitor longevity is also enhanced by voltage ramping by the ignition control. The ignition control finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor. Each time power is applied to the furnace, the SureLight board performs a selfcheck.
TABLE 4
SURELIGHT BOARD 69M15 TERMINAL
DESIGNATIONS
COOL Blower − Cooling Speed (120V)
HEAT Blower − Heating (120V)
PARK
Unused blower lead not energized
FAN
Continuous Low Blower Speed
EAC
Accessory Terminal (120V)
XFMR
Transformer (120V)
LINE
Input (120V)
HUM
Heat Only Accessory (120V)
5 Terminals
120 Volt Neutral
FS
Flame Sensor
24V HUM
Heat Only Accessory (24V)
TABLE 5
SURELIGHT BOARD 69M15 TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Combustion Air Inducer Line Voltage
2
Ignitor Voltage
3
Combustion Air Inducer Neutral
4
Ignitor Neutral
SURELIGHT INTEGRATED CONTROL BOARD
FIGURE 8
Page 21
Page 21
TABLE 6
SURELIGHT BOARD 69M15 TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Prove Switch and Limit Out
2
Not Used
3
24V Hot
4
Not Used
5
Roll Out Switch Out
6
24V Common
7
Limit In
8
Ground
9
Gas Valve Common
10
Prove Switch In
11
Roll Out Switch In
12
Gas Valve 24V Hot
c−Electronic Ignition (See Figure 9)
On a call for heat the SureLight control monitors the com­bustion air inducer prove switch. The control will not begin the heating cycle if the prove switch is closed (by−passed). Once the proving switch is determined to be open, the combustion air inducer is energized. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the prove switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re− set period. After the 15−second pre−purge period, the SureLight igni­tor warms up for 20 seconds during which the gas valve opens at 19 seconds for a 4−second trial for ignition. The ignitor stays energized during the trial until flame is sensed. If ignition is not proved during the 4−second peri­od, the control will try four more times with an inter purge and warm−up time between trials of 35 seconds. After a to­tal of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the low­est power is determined and the cycle begins again.
d−Fan Time Control Heating
The heating fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by setting the S1 dip switches l0ocated on the SureLight integrated con­trol. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. For customized comfort, monitor the supply air temperature once the heat demand is satisfied. Note the supply air temperature at the instant the blower is de−energized. Adjust the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de−energized. (Longer delay times al­low for lower air temperature, shorter delay times allow for higher air temperature). See table 7 for switch settings and fan delay times..
e−Fan Time Control Cooling
The cooling fan on time is fixed at 2 seconds and cannot be adjusted. Fan off time (time that the blower operates after the cool demand has been satisfied) can be adjusted by setting the S1 dip switches (switch 3) located on the Sur­eLight integrated control. See table 7 for switch settings and fan delay times.
TABLE 7
S1 DIP SWITCH SETTINGS
Heat Off Delay
Switch 1 Switch 2 SECONDS
OFF OFF 60
OFF ON 90
ON OFF 120
ON ON 180
Cool Off Delay
Switch 3 SECONDS
OFF 2
ON 45
Page 22
Page 22
The SureLight board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed below in table 8.
TABLE 8
DIAGNOSTIC CODES
Make sure to Identify LED’S Correctl..
LED #1
56L83, 97L48 −DIAG1 Green
69M15 − DS1 Red
LED #2
56L83, 97L48 − DIAG2 Green
69M15 − DS2 Green
DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
SLOW FLASH
Power on − Normal operation. Also signaled during cooling and continuous fan.
SIMULTANEOUS
FAST FLASH
SIMULTANEOUS
FAST FLASH
Normal operation − signaled when heating demand initiated at thermostat.
SLOW FLASH ON
Primary or secondary limit switch open. Limit must close within 3 minutes or unit goes into 1 hour Watchgurad.
OFF SLOW FLASH
Prove switch open. OR: Blocked inlet/exhaust vent; OR: Prove switch closed prior to activation of combustion air inducer.
ALTERNATING
SLOW FLASH
ALTERNATING
SLOW FLASH
Watchguard −− burners failed to ignite.
SLOW FLASH OFF Flame sensed without gas valve energized.
ON SLOW FLASH Rollout switch open. OR: 9-pin connector improperly attached.
ON ON
ON OFF
Circuit board failure or control wired incorrectly.
OFF ON
y
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH
Low flame signal. Measures below: See table 16 Replace flame sense rod.
ALTERNATING
FAST FLASH
ALTERNATING
FAST FLASH
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts. (If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
FIGURE 9
SureLight Control Ignition Sequence Board 56L83, 97L48 & 69M15
DEMAND
CAI
GAS VALVE
ON
OFF
IGNITOR
15 Sec.
Pre −Purge
20 sec.
Ignitor Warmup
4 Sec.Trial**
for Ignition
Post
Purge
5 SEC
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
INDOOR BLOWER
Blower On"
Delay
End of
Heat Demand
Blower
Off
Time
**SureLight board 56L83 energizes ignitor the first second only of the four second trial for ignition
Page 23
Page 23
6. Flame Sensor
A flame sensor is located on the left side of the burner sup­port. See figure 10. The sensor is mounted on the flame rollout plate and the tip protrudes into the flame envelope of the left−most burner. The sensor can be removed for ser­vice without removing any part of the burners. During op­eration, flame is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve to remain open as long as flame signal is sensed. See table 16 for flame signal.
7. Ignitor
The SureLight ignitor is made of durable silicon nitride. Ig­nitor longevity is enhanced by controlling voltage to the ig­nitor. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor. Due to this feature of the board, voltage cannot be measured so ignitor must be ohmed. Ohm value should be 10.9 to 19.7. See figure 12 for ignitor location.
NOTE − The G50UH(X) furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
FIGURE 10
5/16"
8. Blower Motors and Capacitors
All G50UH(X) units use direct drive blower motors. All mo­tors are 120V permanent split capacitor motors to ensure maximum efficiency. Ratings for capacitors will be on motor nameplate.
NOTE − The shaft on 1 HP motors have 2 flat sides and are matched with blower wheels with 2 set screws.
FIGURE 11
SUPPLY AIR BLOWER
AND SECONDARY LIMIT (S)
SECONDARY
LIMIT (S)
CAPACITOR
MOTOR/BLOWER
ASSEMBLY
To Remove Blower From Unit: Disconnect Power, Remove Control
Box, Remove Bolts and Unplug Motor Wires From Control Board.
Then Slide Out Front of Unit.
FIGURE 12
5/16"
13/32’
5/8"
SureLight Ignitor Location
BURNERS TOP VIEW
BURNERS FRONT VIEW
MEASUREMENT IS TO I.D. OF RETENTION RING
IGNITOR
BRACKET
Page 24
Page 24
9. Combustion Air Inducer (B6)
All G50UH(X) units use a combustion air inducer to move air through the burners and heat exchanger during heating operation. The blower uses a 120VAC motor. The motor operates during all heating operation and is controlled by furnace control A92. The inducer also operates for 15 sec­onds before burner ignition (pre-purge) and for 5 seconds after the gas valve closes (post-purge).
A proving switch connected to the combustion air inducer ori­fice plate is used to prove inducer operation. The combus­tion air inducer orifice will be different for each model. See table 9 for orifice sizes. The switch monitors air pressure in the inducer housing. During normal operation, the pressure in the housing is negative. If pressure becomes less negative (signifying an obstruction) the proving switch opens. When the proving switch opens, the furnace control (A92) immedi­ately closes the gas valve to prevent burner operation.
TABLE 9
G50UH(X) Unit
C.A.I. Orifice Size
24A−045 1 1/4"
24A/36A−070 1 7/16"
48B−070 1 1/2"
36B, 48B−090 1 11/16"
48C, 60C−110 (−1, −2, −3 units) 1 7/8"
48C, 60C−110 (−4, −5 units) 2 5/32"
36C−110 2 5/32"
48C, 60D−135 (−6 and later)
(−1 to −5 units)
2 3/8"
(2 5/32")
60D−155 2.60"
Horizontal Applications
The G50UH(X) furnace can be installed in horizontal ap­plications.
The combustion air inducer may be rotated clockwise or counterclockwise by 90° to allow for vertical vent dis­charge in a horizontal application. Remove the four mount­ing screws, rotate the assembly (assembly consists of ori­fice plate, proving switch, gasket and combustion air in­ducer), then reinstall the mounting screws. See figure 13. Use the provided wire tie to bundle the pressure switch wires with the inducer motor power leads. Route the wires
away from moving parts and the heat of the inducer
motor to prevent damage to the wires. Use sheet metal
shears to remove the cut out from the side of the cabinet. See figure 14. Use the two provided sheet metal screws to install the cut out on the top cap to cover the original flue outlet opening.
FIGURE 13
Combustion Air Inducer
(Upflow Position)
Mounting Screws
MOUNTING SCREWS
90°
90°
(Remove)
(Remove)
Power Leads
Flue Transition
(Do not remove
)
G50UH−15 and later assembly Shown
Flue Outlet Hole
(
Reattach
Cutout Here)
Supply Air
Opening
Top View of Furnace
Top Cap
Cut out
Optional
Flue Outlet
Optional Flue Outlet
(Horizontal Installation)
FIGURE 14
Page 25
Page 25
10. Flame Rollout Switches (S47)
Flame rollout switch is a high temperature limit located on top of the burner box (135 and 155 kBtuh units− rollout switches are located on the inner sides of burner box). Each furnace is equipped with two identical switches. One switch is located over the leftmost burner and the other switch is located over the rightmost burner. The limit is a N.C. SPST manual-reset limit connected in series with the ignition control A92. When S47 senses rollout, the ignition control immediately stops ignition and closes the gas valve. If unit is running and flame rollout is detected, the gas valve will close and ignition control will be disabled. Rollout can be caused by a blocked heat exchanger, flue or lack of combustion air. The switch is factory set and cannot be adjusted. See table 10. The switch can be manually reset. To manually reset a tripped switch, push the reset button lo­cated on the control.
TABLE 10
BTUH INPUT
Rollout Switch Setpoint
−045
−070 °
−090
250° F
−110
−135 °
−155
200° F
11. Primary Limit Control (S10)
The primary limit (S10) on G50UH(X) units is located in the heating vestibule panel. When excess heat is sensed in the heat exchanger, the limit will open. If the limit is open, the fur­nace control energizes the supply air blower and closes the gas valve. The limit automatically resets when unit tempera­ture returns to normal. The switch must reset within three min­utes or SureLight board will go into Watch guard for one hour. The switch is factory set and cannot be adjusted. The switch may have a different setpoint for each unit model number. If limit switch must be replaced, see Lennox Repair Parts handbook.
12. Secondary Limit Controls (S21)
The secondary limit (S21) on G50UH(X) (−24A−045 will not have a secondary limit) units is located in the blower compart­ment in the back side of the blower housing. See figure 11. Table 11 and the blower speed chart on the wiring diagram show secondary limit quantities per unit. When excess heat is sensed in the blower compartment, the limit will open. If the limit is open, the furnace control energizes the supply air blow­er and closes the gas valve. The limit automatically resets when unit temperature returns to normal. G50UH−1 through −6 units use a surface type limit factory set to openat 125°F. G50UH−7 and later units use an air stream limit factory set to open at 135°. The secondary limit cannot be adjusted.
TABLE 11
G50UH
UNIT
Quantity LeftSide Right Side
24A−045 0 No No
24A−070 2 Ye s Yes
36A−070 2 Ye s Yes
36B−090 1 No Yes
36C−110 1 No Ye s
48B−070 2 Ye s Yes
48B−090 2 Ye s Yes
48C−110 1 No Ye s
48C−135 2 Ye s Yes
60C−110 1 No Ye s
60D−135 2 Ye s Yes
60D−155 2 Ye s Yes
Page 26
Page 26
13. Gas Valve Figures 15, 16 & 17
The G50UH(X) uses a gas valve manufactured by Honey­well or White Rodgers. The valve is internally redundant to assure safety shut−off. If the gas valve must be replaced, the same type valve must be used.
24VAC terminals and gas control knob or switch are located on the valve. All terminals on the gas valve are connected to wires from the electronic ignition control. 24V applied to the terminals energizes the valve.
Inlet and outlet pressure taps are located on the valve. A regu­lator adjustment screw is located on the valve.
LPG changeover kits are available from Lennox. Kit s include burner orifices and a gas valve regulator conversion kit.
WHITE RODGERS 36E SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
FIGURE 15
FIGURE 16
WHITE RODGERS 36F Series Gas Valve
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
ON
OFF
HONEYWELL VR8205 SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
FIGURE 17
14. Combustion Air Inducer Proving Switch (S18)
G50UH(X) series units are equipped with a combustion air proving switch located on the combustion air inducer orifice bracket. The switch is connected to the combustion air in­ducer housing by means of a flexible silicone hose. It moni­tors negative air pressure in the combustion air inducer housing.
The switch is a single-pole single-throw proving switch elec­trically connected to the furnace control. The purpose of the switch is to prevent burner operation if the combustion air inducer is not operating or if the flue becomes obstructed.
On start-up, the switch senses that the combustion air in­ducer is operating. It closes a circuit to the furnace control when pressure inside the combustion air inducer de­creases to a certain set point. Set points vary depending on unit size. See table 12. The pressure sensed by the switch is negative relative to atmospheric pressure. If the flue be­comes obstructed during operation, the switch senses a loss of negative pressure (pressure becomes more equal with atmospheric pressure) and opens the circuit to the fur­nace control and gas valve. A bleed port on the switch al­lows relatively dry air in the vestibule to purge switch tub­ing, to prevent condensate build up. The switch is factory set and is not field adjustable. It is a
safety shut-down control in the furnace and must not be by− passed for any reason. If switch is closed or by−passed, the control will not initiate ignition at start up.
TABLE 12
PROVE SWITCH SET POINTS
−1 to −14 Units
0 − 4500ft
(0 − 1372m)
4501’ − 7500’
1373m − 7500m
7501’ − 10,000’
(2287 − 3048m)
−045
0.47"
(116Pa)
0.36" (89Pa) 0.36" (89Pa)
−070
0.47"
(116Pa)
0.36" (89Pa) 0.36" (89Pa)
−090
0.51"
(126Pa)
0.47" (116Pa) 0.43" (106Pa)
−110 0.58" (.14Pa) 0.47" (116Pa) 0.43" (106Pa)
−135
0.51"
(126Pa)
0.47" (116Pa) 0.43" (106Pa)
−155
0.51"
(126Pa)
0.47 (116a) 0.43" (106Pa)
All −15 and
later models
0.40" (99pa) no change 0.36" (89Pa)
NOTE−− −1 to −14 units require a high altitude prove switch kit if installed above 4500 ft (1370 m).
NOTE−− −15 and later units require a high altitude prove switch kit if installed above 7500 ft (2286 m).
Page 27
Page 27
II−PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation instructions and applicable codes.
III−START-UP A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be
within range listed on the nameplate. If not, consult the power company and have voltage condition corrected before starting unit.
B−Heating Start-Up
WARNING
Shock and burn hazard.
G50UH(X) units are equipped with a hot surface igni­tion system. Do not attempt to light manually.
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set thermostat to lowest setting.
3 − Turn off all electrical power to appliance.
which automatically lights the burners. Do not try to light the burners by hand.
5 − Remove top access panel. 6 − White Rodgers Gas Valve −− Switch lever to OFF.
See figure 15. Honeywell Gas Valve −− Turn knob on gas valve
clockwise
to OFF. Do not force. See figure 17.
7 − Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instruc­tions. If you do not smell gas go to next step.
8 − White Rodgers Gas Valve −− Switch gas valve lever to
ON. Honeywell Gas Valve −− Turn knob on gas valve coun-
terclockwise
to ON. Do not force.
9 − Replace access panel.
10− Turn on all electrical power to unit.
11− Set thermostat to desired setting.
12− If the appliance will not operate, follow the instructions
To Turn Off Gas To Unit" and call your service techni­cian or gas supplier.
Turning Off Gas To Unit
1 − Set thermostat to lowest setting. 2 − Turn off all electrical power to unit if service is to be
performed.
3 − Remove access panel.
4 − Switch lever on White Rodgers gas valve to OFF; turn
knob on Honeywell valve clockwise
to OFF. Do not
force.
5 − Replace access panel.
C−Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
D−Extended Period Shutdown
IV−HEATING SYSTEM SERVICE CHECKS A−C.S.A. Certification
All units are C.S.A. (formally A.G.A. and C.G.A. combined) design certified without modifications. Refer to the G50UH(X) Installation Instruction.
B−Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet.
WARNING
Do not exceed 600 in−lbs (50 ft−lbs) torque when attaching the gas piping to the gas valve.
Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off the main shut-off valve and disconnect the main power to unit. These controls should be properly labeled by the installer.
When pressure testing gas lines, the gas valve must be disconnected and isolated. Gas valves can be damaged if subjected to more than 0.5psig (14" W.C.). See figure 18. If the pressure is equal to or less than 0.5psig (14"W.C.), use the manual shut−off valve before pressure testing to isolate furnace from gas supply.
FIGURE 18
MANUAL MAIN SHUT−OFF VALVE
GAS VALVE
CAP
GAS PIPING TEST PROCEDURE
FIELD PROVIDED
LINE PRESSURE TAP
Page 28
Page 28
When checking piping connections for gas leaks, use pre­ferred means. Kitchen detergents can cause harmful corro­sion on various metals used in gas piping. Use of a specialty Gas Leak Detector is strongly recommended. It is available through Lennox under part number 31B2001. See Corp. 8411−L10, for further details.
Do not use matches, candles, flame or any other source of ignition to check for gas leaks.
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to inlet pressure tap (field provided). See figure 18. Check gas line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High pressure can result in permanent damage to gas valve or overfire. See table 13 for operating pressure at unit gas connection (line).
On multiple unit installations, each unit should be checked separately, with and without units operating. Supply pres­sure must fall within range listed in previous paragraph.
E−Check Manifold Pressure
After line pressure has been checked and adjusted, check manifold pressure. Move pressure gauge to outlet pres­sure tap located on unit gas valve (GV1). Checks of man­ifold pressure are made as verification of proper regulator ad­justment. Manifold pressure for the G50UH(X) can be mea­sured at any time the gas valve is open and is supplying gas to the unit. See table 13 for normal operating manifold pres­sure.
TABLE 13
All G50UH Units
Natural LP
Line Pressure WC" 4.5 − 10.5 11.0 − 13.0
Manifold Pressure WC" 3.5 10.0
IMPORTANT
For safety, connect a shut-off valve between the manometer and the gas tap to permit shut off of gas pressure to the manometer.
The gas valve is factory set and should not require adjust­ment. All gas valves are factory regulated. See specifica­tions section of this manual for High Altitude manifold pres­sure settings.
Manifold Adjustment Procedure:
1 − Connect a test gauge to outlet pressure tap on gas
valve. See figures 15, 16 and 17. Start unit and allow 5 minutes for unit to reach steady state.
2 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue. L.P. gas should burn mostly blue with some orange streaks.
3 − After allowing unit to stabilize for 5 minutes, record
manifold pressure.
NOTE−Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
F− Proper Gas Flow (Approximate)
& Combustion
Furnace should operate at least 5 minutes before check­ing gas flow. Determine time in seconds for two revolu­tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 14 below. If manifold pressure matches table 13 and rate is incorrect, check gas orifices for proper size and restriction. After furnace has been in operation for 15 minutes, take a combustion sample beyond the flue out­let. Compare to table 15 .
NOTE− To obtain accurate reading, shut off all other gas appliances connected to meter.
TABLE 14
GAS METER CLOCKING CHART
Seconds for One Revolution
G50UH
Natural LP
G50UH
Unit
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
−45 82 164 205 410
−70 55 110 136 272
−90 41 82 102 204
−110 33 66 82 164
−135 27 54 68 136
−155 23 46 58 116
Natural−1000 btu/cu ft LP−2500 btu/cu ft
IMPORTANT
For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
TABLE 15
G50UH Unit CO2 Range Nat CO2 Range LP
24A−045(X) 5.50 − 6.50 6.80 − 7.80
24A−070 7.00 − 8.00 8.00 − 9.00
36A−070(X) 6.80 − 7.80 7.80 − 8.80
36B−090 7.20 − 8.20 7.70 − 8.70
48B−090(X) 7.20 − 8.20 7.70 − 8.70
36C−110 6.50 − 7.50 7.50 − 8.50
48C−110 6.90 − 7.90 8.50 − 9.50
60C−110(X) 6.50 − 7.50 7.50 − 8.50
48C−135 6.70 − 7.70 7.60 − 8.60
60D−135 6.70 − 7.70 7.60 − 8.60
60D−155 6.80 − 7.80 7.80 − 8.80
Page 29
FIGURE 19
TRANSDUCER
(PART #78H5401)
Page 29
G−Flame Signal
A microamp DC meter is needed to check the flame signal on the ignition control. Flame (microamp) signal is an electrical current which passes from the furnace control through the sensor during unit opera­tion. Current passes from the sensor through the flame to ground to complete a safety circuit.
To Measure Flame Signal − Ignition Control:
A transducer (Part #78H5401 available from Lennox Repair Parts) is required to measure flame signal if meter used will not read a low micro amp signal. Seefig­ure19. The transducer converts microamps to volts on a 1:1 conversion. Flame sig­nal for the SureLight control is shown in table16. A digital readout meter must b e used. The t r an s du c e r plugs into most meters. See figure 20 for proper use of transducer.
1 − Set the volt meter to the DC voltage scale. Insert
transducer into the VDC and common inputs. Ob­serve correct polarities. Failure to do so results in negative (−) values.
2 − Turn off supply voltage to control.
3 − Disconnect ignition control flame sensor wire from the
flame sensor.
4 − Connect (−) lead of the transducer to flame sensor.
5 − Connect (+) lead of transducer to the ignition control sen-
sor wire.
6 − Turn supply voltage on and close thermostat contacts to
cycle system.
7 − When main burners are in operation for two minutes, take
reading. Remember 1 DC volt = 1 DC microamp.
SET DIAL TO MEASURE VDC
(+)
(−) TO
FLAME
SENSOR
NOTE−MUST USE DIGITAL METE
R
RED COLLAR
INDICATES
POSITIVE
LEAD
(+) TO
IGNITION
CONTROL
SENSOR
WIRE
FIGURE 20
(−)
TABLE 16
FLAME SIGNAL in MICROAMPS
SureLight Normal Low Drop Out
56L83 & 97L48
0.61
0.21 − 0.60
0.20
69M15
0.31
0.25 − 0.30
0.24
V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment
1 − Blower operation is dependent on thermostat control
system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.
3 − Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in
OFF position.
B−Temperature Rise
Temperature rise for G50UH(X) units depends on unit in-
put, blower speed, blower horsepower and static pressure
as marked on the unit rating plate. The blower speed must
be set for unit operation within the range of TEMP. RISE
°F" listed on the unit rating plate.
To Measure Temperature Rise:
1 − Place plenum thermometers in the supply and return air
plenums. Locate supply air thermometer in the first hor-
izontal run of the plenum where it will not pick up radiant
heat from the heat exchanger.
2 − Set thermostat to highest setting.
3 − After plenum thermometers have reached their high-
est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check the
firing rate. Provided the firing rate is acceptable, in-
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.
Page 30
FIGURE 21
STATIC PRESSURE TEST
Page 30
C−External Static Pressure
1 − Tap locations shown in figure 21.
2 − Punch a 1/4" diameter hole
in supply and return air ple­nums. Insert manometer hose flush with inside edge of hole or insulation. Seal around the hose with per­magum. Connect the zero end of the manometer to the discharge (supply) side of the system. On ducted sys­tems, connect the other end of manometer to the re­turn duct as above. For systems with non−ducted re­turns, leave the other end of the manometer open to the atmosphere.
3 − With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow­er motor speed to deliver the air desired according to the job requirements.
4 − External static pressure drop must not be more than
0.5" W.C.
5 − Seal around the hole when the check is complete.
D−Blower Taps SureLight 56L83 & 97L48
Blower speed tap changes are made on the SureLight con­trol board. See figure 6. Unused taps must be secured on dummy terminals "PARK M1" and or "PARK M2" on the SureLight board. The heating tap is connected to the "ACB HEAT " terminal and the cooling tap is connected to the "ACB COOL" terminal. The continuous blower tap is con­nected to the "ACB LOW" terminal. To change existing heat tap, turn off power then switch out speed tap on "ACB HEAT" with tap connected to "PARK M1" or "PARK M2". See wiring diagram for for blower motor tap colors for each speed.
E−Blower Taps SureLight 69M15
Blower speed tap changes are made on the SureLight con­trol board. See figure 8. Unused taps must be secured on dummy terminals "PARK" on the SureLight board. The heating tap is connected to the "HEAT " terminal and the cooling tap is connected to the "COOL" terminal. The con­tinuous blower tap is connected to the "FAN" terminal. To change existing heat tap, turn off power then switch out speed tap on "HEAT" with tap connected to one of two "PARK" terminals. See wiring diagram for for blower motor tap colors for each speed.
VI−MAINTENANCE
At the beginning of each heating season, the system should be checked as follows:
A−Filters
All G50UH(X) filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure that the furnace operates prop­erly. Replacement filters must be rated for high velocity air­flow.
B− Heat Exchanger and Burners
Cleaning the Heat Exchanger and Burners
NOTE−Use papers or protective covering in front of fur­nace while cleaning furnace.
Cleaning the heat exchanger requires a steel spring snake," a reversible drill and a vacuum cleaner. The steel spring snake may be constructed by purchasing a 4 ft. long by 1/4" diameter steel wire cable and a 1/4" diameter wire brush. These items are available at a hardware store. In­sert wire end of brush into the open end of the spring cable. Crimp the cable around the brush so that the brush is se­cured and will not come off during cleaning. Attach the oth­er end of the cable to the reversible drill to complete the tool for cleaning the heat exchanger. See figure 1 for parts ar­rangement when disassembling furnace. 1 − Turn off both electrical and gas power supplies to fur-
nace.
2 − Remove flue pipe and top cap from unit. Mark and dis-
connect wiring from prove switch and combustion air inducer.
FIGURE 22
G50UH(X) BURNER & HEAT
EXCHANGER REMOVAL
HEAT EXCHANGER
BURNER BOX ASSEMBLY
3 − Remove four screws securing the combustion air in-
ducer. Carefully remove the combustion air inducer and prove switch together as a unit to avoid damaging blow­er gasket. If gasket is damaged, it must be replaced to prevent leakage.
Page 31
Page 31
FIGURE 23
NOx INSERTS
NOX UNITS ONLY
4 − Remove collector box located behind combustion air
inducer. Care must be taken to avoid damaging the collector box gasket. If the gasket is damaged it must be replaced to prevent leakage.
5 − Mark then disconnect wires from gas valve and rollout
switch.
6 − Disconnect gas supply piping. Remove six screws se-
curing the burner manifold assembly to the lower vesti­bule panel and remove the assembly from the unit. NO
x
units only: remove screws holding NO
x
inserts. Carefully remove inserts from each heat exchanger clam. See figure 23.
7 − Insert brush end of cable snake into top of one of the
heat exchanger openings. DO NOT FORCE CABLE INTO HEAT EXCHANGER. Once the cable has been inserted, operate drill on slow speed. Move the cable in and out of the heat exchanger section three or four times or until sufficient cleaning is accomplished. Re­verse drill and slowly work cable out of opening.
8− Repeat procedure for each heat exchanger section. 9− When the top heat exchanger sections are complete,
place brush end of cable snake into the bottom openings of each of the heat exchanger sections. Clean the bottom opening as described in step 7.
10− Remove cable from heat exchanger. Use a vacuum to
remove debris knocked loose during cleaning from each heat exchanger section.
11− Attach the exhaust end (positive pressure) of the
vacuum to the top of the heat exchanger sections. Any loose debris will be forced to the bottom of the heat exchanger section. Vacuum debris from bottom openings.
12− Replace collector box and combustion air inducer/
prove switch combination. Check gaskets for damage. Damaged seals must be replaced to avoid heat ex­changer leaks. Replace all screws to the collector box and combustion air inducer. Leaving off screws may cause leaks.
13− Clean burner by running a vacuum with a soft brush at-
tachment over face of burners. Visually inspect inside of burners and crossovers for any blockage caused by for­eign matter. Remove any blockage.
14− For NOX units, replace inserts in each heat exchanger
section. DO NOT BEND.
15− Replace burner / manifold assembly onto vestibule
panel.
16− Reconnect wires to pressure switch, roll−out switch, gas
valve and combustion air inducer. Refer to unit wiring diagram.
17− Reconnect vent pipe to combustion blower outlet.
18− Reconnect gas supply piping.
19− Turn on power and gas supply to unit.
20− Set thermostat and check for proper operation.
21− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred means. Don not use matches, candles, flame or
other sources of ignition to check for gas leak.
22− If a leak is detected, shut gas and electricity off and
repair leak.
23− Repeat steps 21 and 22 until no leaks are detected.
24− Replace front access panel.
CAUTION
Potential for gas leaks, fire or explosion. Some soaps used for leak detection are corrosive to certain metals. Carefully clean piping thor­oughly after leak detection has been completed. Can cause damage to piping resulting in gas leaks, fire or explosion.
C−Supply Air Blower
1 − Check and clean blower wheel. 2 − Motors used on the Lennox G50UH(X) series units
are permanently lubricated and need no further lu­brication.
D−Flue and Chimney
Flue must conform to local codes. In the absence of local codes, flue must meet the National Fuel Gas Code ANSI−Z223.1 venting requirements. Flue pipe deteriorates from the inside out and must be disconnected in order to check thoroughly. Check flue pipe, chimney and all con­nections for tightness and to make sure there is no block­age or leaks.
E−Electrical
1 − Check all wiring for loose connections. 2 − Check for correct voltage. 3 − Check amp−draw on blower motor.
Page 32
Page 32
VII− Wiring and Sequence of Operation
G50UH−1 through −7 Units
1 − When there is a call for heat, W1 of the thermostat energizes
W of the furnace control with 24VAC.
2 − S10 primary limit switch, S47 rollout switch and S21 secon-
dary limit are closed. Call for heat can continue.
3 − SureLight control (A92) energizes combustion air inducer
B6. Combustion air inducer runs until S18 combustion air prove switch closes (switch must close within 2−1/2 minutes or control goes into 5 minute Watchguard Pressure Switch delay). Once S18 closes, a 15−second pre−purge follows.
4 − SureLight control (A92) energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve opens for a 4−second trial for ignition.
6 − Flame is sensed, gas valve remains open for the heat call.
7 − After 45−second delay, SureLight control (A92) energizes in-
door blower B3.
8 − When heat demand is satisfied, W1 of the indoor thermostat
de−energizes W of the SureLight control which de−ener­gizes the gas valve. Combustion air inducer B6 continues a 5−second post−purge period, and indoor blower B3 com­pletes a selected OFF time delay.
Page 33
Page 33
G50UH−8 Units
1 − When there is a call for heat, W1 of the thermostat energizes
W of the furnace control with 24VAC.
2 − S10 primary limit switch, S47 rollout switch and S21 secon-
dary limit are closed. Call for heat can continue.
3 − SureLight control (A92) energizes combustion air inducer
B6. Combustion air inducer runs until S18 combustion air prove switch closes (switch must close within 2−1/2 minutes or control goes into 5 minute Watchguard Pressure Switch delay). Once S18 closes, a 15−second pre−purge follows.
4 − SureLight control (A92) energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve opens for a 4−second trial for ignition.
6 − Flame is sensed, gas valve remains open for the heat call.
7 − After 45−second delay, SureLight control (A92) energizes in-
door blower B3.
8 − When heat demand is satisfied, W1 of the indoor thermostat
de−energizes W of the SureLight control which de−ener­gizes the gas valve. Combustion air inducer B6 continues a 5−second post−purge period, and indoor blower B3 com­pletes a selected OFF time delay.
Page 34
Page 34
SURELIGHT CONTROL
HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
BURNER OFF?
(CONTINUOUS FLAME CHECK)
NORMAL OPERATION:
LED #1 −− SLOW FLASH LED #2 −− SLOW FLASH
YES
YES
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED #1 ON LED #2 ON
(RESET CONTROL BY TURNING MAIN POWER OFF.)
POLARITY REVERSED.
LED #1 −− FAST FLASH
LED #2 −− SLOW FLASH
POWER ON
COMBUSTION AIR INDUCER ON FOR 1 SECOND.
(Control 56L83, 97L48)
TURN INDUCER ON FOR 1 SECOND.
IS POLARITY REVERSED? ((Control 56L83, 97L48)
ROLLOUT SWITCH CLOSED?
THERMOSTAT CALLS FOR HEAT:
LED #1 −− FAST FLASH LED #2 −− FAST FLASH
IS COMBUSTION AIR
PROVE SWITCH OPEN?
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 −− ON. LED #2 −− SLOW FLASH.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
LED #1 −− SLOW FLASH
LED #2 −− OFF
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 OFF
LED #2 SLOW FLASH
(Sequence holds until PROVE switch
closes or thermostat resets control.)
NO
NO
YES
NO
IS THERE
PROPER GROUND?
IS VOLTAGE
ABOVE 75 VOLTS?
LED#1 AND LED#2 ALTERNATING FAST
FLASH. SIGNAL HOLDS UNTIL VOLTAGE
RISES ABOVE 75 VOLTS.
NO
YES
NO
NO
NO
IS COMBUSTION AIR INDUCER ENERGIZED?
(ACCESSORY TERMINAL IS ENERGIZED WITH C.A.I.)
HAS COMBUSTION AIR PROVE SWITCH
CLOSED IN 2.5 MINUTES?
YES
YES
PROVE SWITCH IS IN WATCHGUARD MODE.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 −− OFF. LED #2 −− SLOW FLASH.
IS 5-MINUTE RESET PERIOD COMPLETE?
NO
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PROVE SWITCH.
YES
YES
CONTINUED NEXT PAGE
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
LED #1 ALTERNATING FAST FLASH
LED#2 ALTERNATING FAST FLASH
CHECK FOR BROKEN IGNITOR OR
OPEN IGNITOR CIRCUIT
LED#1 AND LED#2 ALTERNATING FAST FLASH. SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUND.
56L83 & 97L48
SuerLight Control
69M15
Normal
Low Drop Out
0.31
0.25 − 0.30 0.24
0.61
0.21 − 0.60 0.20
TABLE 17
FLAME SIGNAL
Page 35
Page 35
NORMAL HEATING MODE ABNORMAL HEATING MODE
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
See table 17
FLAME PRESENT?
INDOOR BLOWER ON DELAY BEGINS
(45 seconds.)
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
COMBUSTION AIR PROVE
SWITCH CLOSED?
LOW FLAME SIGNAL
(Does not affect operation of control)
LED #1 −− SLOW FLASH
LED #2 −− FAST FLASH
GAS VALVE DE−ENERGIZED. COMBUSTION AIR INDUCER
DE−ENERGIZED.INDOOR BLOWER
ON UNTIL SWITCH CLOSES.LED #1
−− SLOW FLASH. LED #2 −− ON. IS LIMIT SWITCH CLOSED?
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− OFF. LED #2 −− SLOW FLASH.
HAS CAB SWITCH CLOSED IN 2.5 MINUTES?
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP −− 20 SECONDS.
YES
YES
FLAME STABILIZATION PERIOD.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF. HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE
HEAT DEMAND?
IGNITION WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
LED 1 ALT. SLOW FLASH LED 2 ALT SLOW FLASH
IS 60-MINUTE RESET PERIOD COMPLETE?
YES
4 SECONDS
YES
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
FLAME SIGNAL NORMAL?
See table 17
YES
YES
HAS PRIMARY/SECONDARY LIMIT
RESET (CLOSED) WITHIN 3
MINUTES?
YES
ROLLOUT SWITCH CLOSED?
GAS VALVE POWER OFF.
COMBUSTION AIR INDUCER POWER OFF.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− ON. LED #2 −− SLOW FLASH.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET
YES
THERMOSTAT DEMAND SATISFIED.
LED #1 & #2 SIMULTANEOUS SLOW FLASHES.
COMB. AIR INDUCER CONTINUES 5-SECOND POST PURGE
AFTER T’STAT DEMAND IS SATISFIED. INDOOR AIR BLOWER
COMPLETES SELECTED OFF" DELAY BEFORE SHUTTING OFF.
HEAT SPEED, ACCESSORY AND EAC. TERMINAL OFF.
YES
NO
5-MINUTE PRESSURE SWITCH
WATCHGUARD MODE.
YES
IS THERE A PROPER GROUND?
IS VOLTAGE ABOVE 75 VOLTS?
IS IGNITOR INTACT AND CONNECTED?
LEDS SIGNAL ALTERNATING
FAST FLASH
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
NO
NO
YES
YES
LIMIT SWITCH WATCH GUARD MODE. GAS VALVE OFF. COMB. AIR INDUCER OFF. IN­DOOR BLOWER OFF WITH DELAY. LED#1−SLOW FLASH LED#2− ON. IS 60MINUTE RE­SET PERIOD COMPLETE.?
YES
YES
4-SECOND TRIAL FOR IGNITION. GAS VALVE OPENS.
IGNITOR ENERGIZED DURING TRIAL UNTIL FLAME
SENSED.
Page 36
Page 36
SURELIGHT CONTROL
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE ABNORMAL COOLING MODE
IGNITION CONTROL MAIN POWER ON.
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
TURN INDUCER ON FOR 1 SECOND (Control 56L83, 97L48)
IS POLARITY REVERSED?
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM
FAN ENERGIZED AFTER DELAY.
(Control 69M15 2 second delay)
(Control 56L83, 97L48 0 second delay) COOL SPEED AND ELECTRONIC AIR CLEANER TERMINAL IS ENERGIZED.
COMPRESSOR OFF.
THERMOSTAT OPENS.
COOLING SPEED AND ELECTRONIC AIR CLEANER
TERMINAL OFF WITH FIELD ADJUSTABLE DELAY.
(Control 69M15 2 or 45 seconds)
(Control 56L83, 97L48 0 second del;ay)
NO
YES
NO
THERMOSTAT OFF
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
NO
IS THERE
PROPER GROUND?
IS VOLTAGE
ABOVE 75 VOLTS?
NO
YES
NO
LED#1 AND LED#2 ALTERNATING FAST FLASH. SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUND.
LED#1 AND LED#2 ALTERNATING FAST
FLASH. SIGNAL HOLDS UNTIL VOLTAGE
RISES ABOVE 75 VOLTS.
LED#1 FAST FLASH LED#2 SLOW FLASH
YES
Page 37
Page 37
SURELIGHT CONTROL
CONTINUOUS FAN SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES INDOOR BLOWER ON
CONTINUOUS BLOWER SPEED. ELECTRONIC AIR
CLEANER TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
THERMOSTAT OPENS. COMBUSTION AIR INDUCER AND
HEATING ACCESSORY TERMINAL ARE DE−ENERGIZED.
INDOOR BLOWER SWITCHES TO COOL SPEED.
THERMOSTAT OPENS.
INDOOR BLOWER SWITCHES TO
CONTINUOUS BLOWER. ELECTRONIC AIR
CLEANER TERMINAL IS ENERGIZED.
NO
YES
YES
NO
HEATING ACCESSORY TERMINAL
ENERGIZES WITH COMB. AIR INDUCER.
INDOOR BLOWER SWITCHES TO HEAT SPEED AFTER
NORMAL DELAY.
(blower remains energized during continuous fan mode)
INDOOR BLOWER SELECTED TIME OFF DELAY BEGINS.
AFTER DELAY HEAT SPEED DE−ENERGIZED.
(blower remains energized during continuous fan mode).
Page 38
Page 38
SURELIGHT − TROUBLE SHOOTING GUIDE
UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Condition Possible Cause Corrective Action / Comments
1.1
Both diagnostic lights fail to light up.
1.1.1
Main voltage 120V not supplied to unit.
ACTION 1 − Check 120V main voltage. Determine cause of main power failure.
LED#1−Off LED#2−Off
1.1.2
Miswiring of furnace or improper con­nections.
ACTION 1 − Check for correct wiring of 120V to power make up box and transformer.
ACTION 2 − Check 24V wiring to control board.
1.1.3
Circuit breaker tripped or fails to close.
ACTION 1 − Replace circuit breaker if it is reset but does not have continuity. ACTION 2 − If circuit breaker still trips, check for short.
1.1.4
Door interlock switch failure.
ACTION 1 − Check that door switch is activated when door is closed. ACTION 2 − Check wire connections to switch, re­place loose connectors. ACTION 3 − Check continuity of switch in closed position. Replace if defective.
1.1.5
Transformer Failure.
ACTION 1 − Check that transformer output is 24V. Replace if defective.
1.1.6
Failed control board.
ACTION 1 − If all the above items have been checked, replace board.
1.2
Diagnostic lights flash the roll−out
code.
1.2.1
Roll−out switch open.
ACTION 1 − Manually reset the roll−out switch by pushing the top button. ACTION 2 − Determine the cause of the roll−out switch activation before leaving furnace.
code
.
1.2.2
Roll−out switch failure.
ACTION 1 − Check continuity across roll−out switch. Replace roll−out switch if switch is reset but does not have continuity.
LED#1−On, LED#2−Slow Flash
1.2.3
LED#2 Slow Flash
Miswiring or improper connections at roll−out switch.
ACTION 1
− Check wiring connections to switch.
1.2.4
Low voltage pin connector failure
ACTION 1 − Check pin connector for proper connection to control board. ACTION 2 − Check continuity of the multi plug pin.
1.3
− On initial power−up the comb. air in-
ducer does not energize
.
ducer does not energize
.
− Diagnostic lights flash the reverse polarity code.
1.3.1
120V main power polarity reversed.
ACTION 1 − Check the 120V has line and neutral correctly input into control. ACTION 2 − Reverse the line and neutral at the 120V field connection.
LED#1−Fast Flash, LED#2−Slow Flash.
120V field connection.
1.4
− On initial power up the combustion air inducer does not energize.
− Diagnostic lights flash normal power on o
p
eration.
1.4.1
Open combustion air inducer motor circuit.
ACTION 1 − Check for 120V to combustion air inducer. If no power, check wire and connec­tions.
on operation
.
LED#1−Slow Flash LED#2−Slow Flash
1.4.2
Failed combustion air inducer motor.
ACTION 1 − If power is present at blower, replace blower.
Page 39
Page 39
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Condition Possible Cause Corrective Action / Comments
1.5
On initial power−up the combustion
air blower remains energized.
1.5.1
Improper ground to the unit.
ACTION 1 − Check that the unit is properly ground. ACTION 2 − Install a proper main ground to the unit
g
Diagnostic lights flash the improper main ground.
1.5.2
6−Pin connector is improperly at-
tached to the circuit board.
ACTION 1 − Check 6−pin connector for proper installation. Correctly insert connector into con­trol.
LED#1−Alternating Fast Flash LED#2−Alternating Fast Flash
1.5.3
Line voltage is below 75V.
ACTION 1 − Check that the line voltage is above 75V. Determine cause of voltage drop and supply correct voltage to the control.
PROBLEM 2: UNIT FAILS TO OPERATE IN THE COOLING OR HEATING MODE, BUT COMBUSTION
AIR INDUCER OPERATES CONTINUOUS. UNITS WITH CONTROL BOARDS DATE CODED AFTER
NOV. 1 1997, WILL OPERATE IN COOLING BUT NOT IN THE HEATING MODE, WITH COMBUSTION
AIR INDUCER CYCLING 5 SECONDS ON 55 SECONDS OFF.
Condition Possible Cause Corrective Action / Comments
2.1
On initial power−up the combustion
air inducer remains energized.
Diagnostic lights flash the improper main ground.
− Units with control boards date
2.1.1
Open ignitor circuit.
ACTION 1 − Check for correct wiring and loose connections in the ignitor circuit. Check mult− plug connections for correct installation.
coded after Nov.1 1997; combustion air inducer will cycle 5 seconds on 55 seconds off.
LED#1−Alternating Fast Flash LED#2−Alternating Fast Flash
2.1.2
Broken or failed ignitor.
ACTION 1 − Unplug ignitor and read resistance across ignitor. If resistance does not read be­tween 10.9 and 19.7 ohms, replace the ignitor.
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES
NOT ENERGIZE
Condition Possible Cause Corrective Action / Comments
3.1
Unit operates with a cooling or contin-
uous fan demand.
Combustion air inducer will not start with a Heating demand.
− Diagnostic lights flash the limit failure
3.1.1
Primary or secondary (if equipped )
limit open.
ACTION 1 − Check continuity across switch(es). Switches reset automatically upon cool down. ACTION 2 − Check for restrictions on blower inlet air (including filter) and outlet air. Determine cause for limit activation before placing unit back in operation.
gg
mode.
LED#1−Slow Flash, LED#2−On
3.1.2
Miswiring of furnace or improper con-
nections at limit switch(es).
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
3.2
− Unit operates with a cooling and con­tinuous fan demand.
− Combustion air inducer will not start with a Heating demand.
Dia
g
nostic lights flash the pressure
3.2.1
Miswiring of furnace or improper con-
nections to combustion air inducer.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
Diagnostic lights flash the pressure
switch failure code.
LED#1−Off, LED#2−Slow Flash
3.2.2
Prove switch stuck closed.
ACTION 1 − Check that the pressure switch is open without the combustion air inducer operat­ing. Replace if defective.
Page 40
Page 40
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR INDUCER DOES
NOT ENERGIZE (CONT.).
Condition Possible Cause Corrective Action/Comments
3.3
− Unit operates with a cooling and con­tinuous fan demand.
Combustion air inducer will not start with a Heating demand.
Diagnostic lights flash the pressure
3.3.1
Miswiring of furnace or improper con-
nections to combustion air inducer.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
switch failure code 2.5 minutes after heating demand.
LED#1−Off, LED#2−Slow Flash
3.3.2
Combustion air inducer failure.
ACTION 1 − If there is 120V to combustion air in­ducer and it does not operate, replace combus­tion air inducer.
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
Condition Possible Cause Corrective Action/Comments
4.1
Unit operates with a cooling and
continuous fan demand.
Combustion air inducer energizes
4.1.1
Prove switch does not close due to
incorrect routing of the pressure
switch lines.
ACTION 1 − Check that the pressure switch lines are correctly routed. Correctly route pressure switch lines.
with a heating demand.
− Diagnostic lights flash the pressure switch failure code 2.5 minutes after heating demand.
4.1.2
Prove switch does not close due to
obstructions in the pressure lines.
ACTION 1 − Remove any obstructions from the the pressure lines and/or taps.
g
LED#1−Off
4.1.3
Prove switch lines damaged
ACTION 1 − Check pressure switch lines for leaks. Replace any broken lines.
LED#1 Off
LED#2−Slow Flash
4.1.4
Condensate in prove switch line.
ACTION 1 − Check pressure switch lines for con­densate. Remove condensate from lines.
4.1.5
Prove switch does not close due to a
low differential pressure across the
pressure switch.
ACTION 1 − Check the differential pressure across the pressure switch. This pressure should exceed the set point listed on the switch. ACTION 2 − Check for restricted inlet vent. Re­move all blockage. ACTION 3 − Check for proper vent sizing and run length. See installation instructions.
4.1.6
Wrong prove switch installed in the
unit, or prove switch is out of calibra-
tion.
ACTION 1 − Check that the proper pressure switch is installed in the unit. Replace pressure switch if necessary.
4.1.7
Miswiring of furnace or improper
connections at prove switch.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
4.1.8
Prove switch failure.
ACTION 1 − If all the above modes of failure have been checked, the pressure switch may have failed. Replace pressure switch and determine if unit will operate.
Page 41
Page 41
PROBLEM 5: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS ENERGIZED.
Condition Possible Cause Corrective Action/Comments
5.1
− Unit operates with a cooling and continuous fan demand.
5.1.1
Check that gas is being supplied to
the unit.
ACTION 1 − Check line pressure at the gas valve. Pressure should not exceed 13" WC for both nat­ural and propane. Line pressure should read a minimum 4.5" WC for natural and 8.0"WC for pro­pane.
− Combustion air inducer energizes with Heating demand.
Ignitor is energized but unit fails to light.
5.1.2
Miswiring of gas valve or loose con-
nections at multi−pin control amp
plugs or valve.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
5.1.3
Defective gas valve or ignition con-
trol.
ACTION 1 − Check that 24V is supplied to the gas valve approximately 35 seconds after heat de­mand is initiated. ACTION 2 − Replace the valve if 24V is supplied but valve does not open. ACTION 3 − Replace the control board if 24V is not supplied to valve.
PROBLEM 6: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY
Condition Possible Cause Corrective Action/Comments
6.1
− Burners fire with a heating demand.
− Burners light but unit shuts off prior to satisfying T−stat demand.
− Diagnostic lights flash the pressure switch code.
LED#1−Off LED#2−Slow Flash
6.1.1
Low pressure differential at the prove
switch.
ACTION 1 − Check for restricted exhaust vent. Remove all blockage. ACTION 2: Check for proper vent sizing. See installation instructions.
6.2
− Combustion air inducer energizes with a heating demand.
6.2.1
Sensor or sense wire is improperly
installed.
ACTION 1 − Check that sensor is properly lo­cated and that the sense wire is properly at­tached to both the sensor and the control.
− Burners light but fail to stay lit.
− After 5 tries the control diagnostics flash the watchguard burners failed to ignite code.
6.2.2
Sensor or sense wire is broken.
ACTION 1 − Check for a broken sensor. ACTION 2 − Test continuity across the sense
wire. If wire or sensor are damaged replace the component.
ignite code.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
6.2.3
Sensor or sensor wire is grounded to
the unit.
ACTION 1 − Check for resistance between the sensor rod and the unit ground. ACTION 2 − Check for resistance between the sensor wire and the unit ground.
ACTION 3 − Correct any shorts found in circuit.
6.2.4
Control does not sense flame.
ACTION 1 − Check the microamp signal from the burner flame. If the microamp signal is be­low 0.70 microamps, check the sense rod for proper location or contamination. ACTION 2 − Replace, clean, or relocate flame sense rod. If rod is to be cleaned, use steel wool or replace sensor. DO NOT CLEAN ROD WITH SAND PAPER. SAND PAPER WILL CONTRIBUTE TO THE CONTAMINATION PROBLEM. NOTE: Do not attempt to bend sense rod. ACTION 3 − Check that there is proper ground to burner box. Repair as necessary.
Page 42
Page 42
PROBLEM 6: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY (CONT.)
Condition Possible Cause Corrective Action/Comments
6.3
− Combustion air inducer energizes with a heating demand.
− Burners light.
− Roll−out switch trips during the heating demand.
6.3.1
Unit is firing above 100% of the
nameplate input.
ACTION 1 − Check that the manifold pressure matches value listed on nameplate. See installa­tion instructions for proper procedure. ACTION 2 − Verify that the installed orifice size match the size listed on the nameplate or installa­tion instructions. ACTION 3 − Check the input rate to verify rate matches value listed on nameplate.
− Diagnostic lights flash roll−out fail­ure.
LED#1−On
6.3.2
Gas orifices leak at the manifold con-
nection.
ACTION 1 − Tighten orifice until leak is sealed. NOTE: Be careful not to strip orifice threads. ACTION 2 − Check for gas leakage at the
threaded orifice connection. Use approved method for leak detection (see unit instructions).
LED#1 On
LED#2−Slow Flash
6.3.3
Insufficient flow through the heat ex-
changer caused by a sooted or re-
stricted heat exchanger.
ACTION 1 − Check for sooting deposits or other restrictions in the heat exchanger assembly. Clean assembly as outlined in instruction manu­al. ACTION 2 − Check for proper combustion. See IV−Heating System Service Checks section NO TAG.
6.3.4
Burners are not properly located in
the burner box.
ACTION 1 − Check that the burners are firing into the center of the heat exchanger openings. Cor­rect the location of the burners if necessary.
6.4
Combustion air inducer energizes
with a heating demand.
− Burners light roughly and the unit
6.4.1
Poor Venting
ACTION 1 −Check vent pipe and remove any ob­structions ACTION 2 − Check for correct exhaust vent installation. See instructions
Burners light roughly and the unit
fails to stay lit.
− Diagnostic lights flash watchguard flame failure.
6.4.2
Improper burner cross−overs
ACTION 1 − Remove burner and inspect the cross−overs for burrs, or any restriction or if crossover is warped. Remove restriction or re­place burners.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
6.4.3
Burrs in gas orifices
ACTION 1 − Remove gas orifices and inspect. Remove any burrs that are present or replace ori­fice.
Page 43
Page 43
PROBLEM 6: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY (CONT.)
6.5
− Combustion air inducer energizes with a heating demand.
− Burners light.
− Dia
g
nostic lights flash watch guard
6.5.1
Loose sensor wire connection causes
intermittent loss of flame signal.
ACTION 1 − Check that the sensor is properly lo­cated. ACTION 2 − Check that the sense wire is proper­ly attached to both the sensor and the control. Pay extra attention to the pin connectors.
Diagnostic lights flash watch guard
flame failure.
− NOTE" Unit might go into 60 min­ute Watchguard mode depending on
6.5.2
Poor ground to burner box
ACTION 1 − Check for proper ground and repair as necessary.
int
erm
ittent
nature of sensor signal.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
6.5.3
Prove Switch opens 5 times during a
single demand
ACTION 1 − Inspect vent pipe installation and for any restriction. Remove restriction.
ACTION 2 − Check prove switch reliability.
PROBLEM 7: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE
Condition Possible Cause Corrective Action/Comments
7.0
− Unit operates correctly but the diagnostic lights flash low flame
7.1.1
Sense rod is improperly located on
the burner.
ACTION 1 − Check the sense rod for proper loca­tion on the burner. Properly locate the sense rod or replace if rod cannot be located correctly.
sense code
.
LED#1−Slow Flash LED#2−Fast Flash
7.1.2
Sense rod is contaminated.
ACTION 1 − Check sense rod for contamination or coated surface. Clean the sense rod with steel wool or replace sensor. DO NOT USE SAND PA­PER TO CLEAN ROD. SAND PAPER WILL CONTRIBUTE TO THE CONTAMINATION PROBLEM.
PROBLEM 8: INDOOR BLOWER FAILS TO OPERATE IN COOLING, HEATING, OR CONTINUOUS
FAN MODE
Condition Possible Cause Corrective Action/Comments
8.0
− Indoor blower fails to operate in continuous fan, cooling, or heating mode.
8.1.1
Miswiring of furnace or improper con-
nections at control or indoor blower
motor.
ACTION 1− Correct wiring and/or replace any loose connections. Check for correct wiring and loose connections.
8.1.2
120V is not being supplied to the in­door air blower or blower motor fail-
ure.
ACTION 1 − Check for 120V at the various calls for indoor blower by energizing "Y", "G", and "W" individually on the low voltage terminal strip. Note that when "W’ is energized, the blower is delayed 45 seconds. If there is 120V to each mo­tor tap but the blower does not operate, replace the motor.
8.1.3
Defective control board
ACTION 1 − If there is not 120V when "Y", "G", or "W" is energized, replace the control.
8.1.4
Defective run capacitor
ACTION 1 − Replace capacitor
PROBLEM 9: RF STATIC DURING TIME FOR IGNITION
Condition Possible Cause Corrective Action/Comments
9.0
− AM radio interference.
9.1.2
Ignitor operation
ACTION 1 − Call Technical Support, Dallas.
Loading...