Duralok Plus® Aluminized Steel Heat Exchanger − Twenty
years limited warranty.
All other covered components − Five years limited warranty.
Refer to Lennox Equipment Limited Warranty certificate
included with equipment for details.
APPROVALS
Units certified by CSA International and ratings are certified by
GAMA.
Units tested and rated according to US DOE test procedures and
FTC labeling regulations.
Blower data from unit tests conducted in Lennox Laboratory air
test chamber.
Approved by the California Energy Commission and meets
California Seasonal Efficiency requirements and California
Nitrogen Oxides (NOx) Standards.
NERGY STAR
E
help save money on utility bills, and help protect the
environment.
ISO 9001 Registered Manufacturing Quality System.
APPLICATIONS
Input capacities of 44,000, 66,000, 88,000, 110,000, and
132,000 Btuh (12.9, 19.3, 25.8, 32.2, and 38.7 kW).
Energy efficiency (AFUE) up to 92.1%.
Compact cabinet with either side or bottom return air entry.
Lennox add-on indoor coils, high−efficiency air cleaners and
humidifiers can easily be added to furnace.
Shipped factory assembled with all controls installed and wired.
Each unit factory test operated to ensure proper operation.
DIRECT VENT / NON−DIRECT VENT
Furnace can be installed in either Direct Vent or Non−Direct
applications. In Direct Vent applications, combustion air is
supplied from outdoors and flue gases are discharged outdoors.
In Non−Direct Vent applications, combustion air is supplied from
indoors and flue gases are discharged outdoors.
OPTIONS
Termination Kits
Facilitates installation of combustion air intake pipe and flue
exhaust pipe.
Refer to venting table in this bulletin to determine pipe size
needed and proper termination kit required.
See Specifications table and dimension drawings.
Termination Kit − Concentric − Direct Vent Applications
Only
1−1/2, 2, or 3 inch (38, 51, or 76 mm) kit contains concentric
termination assembly, reducer bushing and 45 degree elbow.
Kit requires single hole penetration of roof or wall for installation.
Roof Termination Flashing Kit is available for use with 1−1/2 and
2 inch Kits.
CSA certified.
®
certified units are designed to use less energy,
B
D
E
N
K
F
C
G
P
O
H
L
J
I
M
Termination Kits − Wall Assembly
Close Couple − Direct Vent Applications Only
2 or 3 inch (51 or 76 mm) kit consists of close-couple,
side-by-side PVC piping with galvanized steel wall cover plate
for sealing and isolating piping penetration of the wall.
Piping spacing and length is sized for proper wall installations.
CSA certified.
Close Couple WTK − Direct Vent Applications Only
2 or 3 inch (51 or 76 mm) kit contains one insulated faceplate,
one insulated exhaust pipe, elbow and fittings.
Wall Ring − Direct or Non−Direct Vent
2 inch (51 mm) kit contains 2 stainless steel outside seal caps, 2
galvanized steel inside seal caps, 4 seal rings for the caps and
18 inch (457 mm) insulation sleeve for sealing and isolating
intake and exhaust piping penetration of wall.
Maintain a maximum of 6 inches (152 mm) between the inlet
and outlet openings in the installation of the pipes.
Roof Termination Flashing Kit − Direct or Non−Direct Vent
2 or 3 inch (51 or 76 mm) kit contains two neoprene rubber roof
flashings for vertical venting through a roof.
Vent pipe and insulation not furnished. Each kit contains
enough parts for two non−direct vent installations.
Also available for use with 1−1/2 inch (use 2 inch flashing) and 2
inch (use 3 inch flashing) Concentric Vent Termination Kits used
in vertical venting rooftop applications.
G43UF / Page 2
FEATURES
HEATING SYSTEM
B
Lennox Duralok Plus
Lennox developed heat exchanger assembly consists of primary
heat exchanger and secondary condenser coil assembly.
Main 3-pass clamshell type heat exchanger constructed of
heavy−gauge, aluminized steel.
Designed for normal expansion and contraction.
Crimped seam design and construction provides maximum
efficiency and minimum resistance to airflow.
Secondary heat exchanger condenser coil constructed of
C
aluminum fins fitted to stainless steel tubes.
Coil is factory tested for leaks.
Condensate drain header box assembly located on front of coil.
Compact size of complete heat exchanger assembly permits low
overall design of furnace cabinet.
All components mounted in a heavy−gauge steel frame.
Heat exchanger assembly has been laboratory life cycle tested.
Lennox Designed Header Box
Header box on end of condenser coil collects flue condensate for
disposal through condensate collars.
Hose connects the header box drains to the condensate collars.
The condensate collars are located on each side of the cabinet
for easy field installation of condensate drain trap. Only one
collar is used, the other is plugged.
Condensate drain trap is included with the unit for field installation.
Lennox Designed Flue Condensate Trap Assembly
Condensate trap assembly is mounted outside the conditioned
air stream.
Assembly can be mounted on either side of cabinet. See
Installation Instructions.
Connection can be made with field provided 1/2 in. PVC pipe, 3/4 in.
PVC coupling, or 1−1/4 in. OD x 1 in. ID vinyl tubing with hose clamp.
Easy to clean and winterize.
Inshot Burners
D
Aluminized steel inshot burners provide efficient, trouble−free
operation.
Burner venturi mixes air and gas in correct proportion for proper
combustion.
Burner assembly is removable from the unit as a single
component for ease of service.
Hot Surface Mini−Nitride Ignitor
Unique, non−porous, high strength proprietary ceramic material
provides long life and trouble−free maintenance.
Low mass element provides fast heat−up and consistent igniter
temperature with low power usage.
Cemented to alumina block for positive mounting and protection
against current leakage.
High temperature Teflon
dependable operation.
Gas Control Valve
E
24 volt redundant combination gas control valve combines
manual shut off valve (On−Off), automatic electric valve (dual)
and gas pressure regulation into a compact combination control.
Combustion Air Inducer
F
Shaded pole heavy−duty blower prepurges heat exchanger and
safely vents flue products.
Pressure switch proves blower operation before allowing gas
G
valve to open.
Operates only during heating cycle.
Limit Control
Automatic reset, primary limit is accurately located.
Factory installed on vestibule panel on all units.
Flame Rollout Switch
Manual reset switches are factory installed on burner box.
Switch provides protection from abnormal operating conditions.
®
Heat Exchanger Assembly
®
insulated ignition lead wires for
OPTIONS
High Altitude Orifice Kit − Natural Gas Only
Required for all natural gas models for proper unit operation at
altitudes of 7501 to 10,000 feet (2286 to 3048 m).
Proper orifice for LPG/Propane models is included with
LPG/Propane Conversion Kit.
High Altitude Pressure Switch Kit
Required on certain units for proper unit operation on
installations above 4,500 ft. (1372 m).
LPG/Propane Conversion Kit
Required for field changeover from natural gas to LPG/Propane.
CONTROLS
Integrated Furnace Control Board
H
Solid−state board contains all necessary controls and relays to
operate furnace.
Combustion air inducer is controlled by board. Prior to ignition, a
pre−purge cycle for 15 seconds is initiated. After the main
burners are turned off, a post−purge cycle for 5 seconds is run.
Ignition control board continuously monitors line voltage and
maintains the igniter power at a constant level to provide
consistent lighting and maximum igniter life.
Electronic flame sensor control assures safe and reliable operation.
Should loss of flame occur, flame sensor controls will initiate 4
attempts at re−ignition before locking out unit operation for 60
minutes.
Watchguard type circuit automatically resets ignition controls
after one hour of continuous thermostat demand after unit
lockout, eliminating nuisance calls for service.
Fan control consists of adjustable blower timed−off delay (60, 90,
120, 180 seconds − factory setting 90 seconds) and fixed blower
timed−on delay (45 seconds).
For air−conditioning applications, blower is automatically
energized on thermostat demand for cooling.
Two accessory terminals furnished for additional power supply
I
requirements for 120 volt (less than 1 amp) power humidifiers and
powered air cleaners.
Ignition control has two LED’s to indicate status and as an aid in
troubleshooting.
24 Volt Transformer
J
Furnished and factory installed in control box.
40VA transformer has fuse wired in series.
Field Wiring Make-up Box
K
Furnished for line voltage wiring.
Factory installed internally on left side of furnace.
Box may be installed internally or externally on either side of
furnace.
OPTIONS
Thermostat
See Thermostat bulletins in Controls section and Lennox Price
Book for a complete list of thermostats.
Twinning Kit
Required to operate two furnaces simultaneously.
Kit consists of twinning control and two fan sensors.
BLOWER
Multi-speed, direct drive blower.
L
Statically and dynamically balanced.
Resiliently mounted.
Blower assembly slides out of unit for servicing.
M
Blower speeds are easily changed on the integrated furnace
control board. See blower performance tables.
G43UF / Page 3
FEATURES
FILTER (NOT FURNISHED)
Filter and provisions for external mounting must be field
provided.
OPTIONS
Air Filter and Rack Kit for Side Return Air Applications
(Not for use with RAB Return Air Base)
Washable or vacuum cleanable polyurethane frame type filter
and external side return air rack available for field installation.
Available in single and ten pack kits.
Rack has filter door for easy filter servicing.
Flanges on rack allow easy duct connection.
Field installs on either side of unit cabinet.
See dimension drawing.
EZ Filter Base for Bottom Return Air Applications
Hinged door with thumbscrew for easy filter access.
Uses standard size filters (field provided).
CABINET
Low−profile, narrow width cabinet allows easy installation.
Heavy−gauge, cold rolled steel construction.
Pre−painted cabinet finish.
Flanges provided on supply air opening for ease of plenum
connection or alignment with indoor coil.
Cabinet is insulated with foil faced insulation on sides and back
N
of heating compartment.
Complete service access.
O
Safety interlock switch automatically shuts off power to unit
when blower compartment access door is removed.
Gas piping and electrical inlets are provided in both sides of cabinet.
P
Return Air Entry:
For bottom return−air entry, remove furnished bottom seal panel
from cabinet.
For side return−air entry, corners are marked on either side of
cabinet for return air cut−outs. On furnaces with side return air
and condensate trap on the same side of the cabinet, a field
fabricated transition or RAB is required to use an IAQ product
higher than 14−3/16 in. (360 mm) when installed next to the unit
and serviced from the front. IAQ products higher than 20 in. (508
mm) require a field fabricated transition. See dimension
drawings.
NOTE − 60C and 60D size units that require air volumes over
1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x
25 x 1 in. (508 x 635 x 25 mm) cleanable air filter, required to
maintain proper air velocity.
2. Single side return air with optional RAB Return Air Base.
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
See Blower Performance Tables for additional information.
Coil Match−up
All furnaces exactly match C33 and CX34 cased up−flow indoor
coils with same letter designation in model number. No adaptor
required. Engaging holes furnished on cabinet for alignment.
C33 uncased coils match furnaces without any overhang but
require an optional adaptor base or field fabricated transition to
match furnace opening. See C33 coil bulletin for additional
information.
one side return air.
OPTIONS
Condensate Drain Heat Cable Kits
Self-limiting wattage heat cable prevents condensate drain from
freezing in unconditioned areas.
Available in 6, 24 or 50 ft. (1.8, 7.3, or 15.2 m) lengths.
Heat Cable Tape:
66 ft. (20 m) length, 1/2 in. (13 mm) wide fiberglass.
60 ft. (18 m) length, 2 in. (51 mm) wide aluminum foil.
Condensate Trap Alternate Location Kit
Allows condensate drain to be installed on the opposite side of
the furnace from the exhaust venting (up−flow applications only).
RAB Return Air Base
On furnaces with side return air and condensate trap on the
same side of the cabinet, a field fabricated transition or RAB is
required when installing an IAQ product higher than 14−3/16 in.
(360 mm) when installed next to the unit and serviced from the
front. IAQ products higher than 20 in. (508 mm) require a field
fabricated transition.
Must be used for 60C and 60D models with air volumes over
1800 cfm (850 L/s) in up−flow applications when only one side
return is required.
Cabinet is pre−painted steel to match the furnace.
See Dimension Drawing.
NOTE − Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non−weatherized furnaces
Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).
G43UF / Page 6
High Altitude Pressure
Switch Kit
4501−7500 ft.
(1372−2286 m)
7501−10,000 ft.
(2286−3048 m)
LPG/Propane Kit
0−7500 ft.
(0−2286 m)
7501−10,000 ft.
(2286−3048 m)
EXHAUST PIPE VENTING TABLE
()
,
Heat
Altitude
0 − 2000 ft.
(0 − 609 m)
2001 − 4500 ft.
(610 − 1371 m)
4501 − 7500 ft.
(1372 − 2286 m)
7501 − 10,000 ft.
(2287 − 3048 m)
NOTE − Minimum Equivalent Vent Pipe length is 15 feet (4.6 m).
1
Maximum Equivalent Vent Length" permitted is defined as Total Length (linear feet) of vent pipe, plus equivalent length (ft.) of fittings, plus equivalent length (ft.) of termination".
2
110 models must have the supplied 90° street ell installed directly into the unit flue collar. The street ell must be included in the elbow count.
3
135 models must have 3 in. to 2 in. reducing elbow (supplied) installed directly into the flue collar. Reducing ell must be included in elbow count.
4
90 elbows must be limited to 3 in. sweep type elbows.
VENTING NOTES One 90elbow is equivalent to 5 feet (1.5 m) of straight vent pipe.
Wall and roof termination (non−concentric) exhaust pipe must terminate with reducer to improve exhaust velocity away from intake piping.
TERMINATION KITS − EQUIVALENT VENT LENGTHS
Heat
Size
−045
−070
−090
−110
−135
1
Requires field provided 1−1/2 in. (38 mm) outdoor exhaust accelerator.
2
Requires field provided 2 in. (51 mm) outdoor exhaust accelerator.
3
For use only in non−direct vent applications, when snow riser is not required. Requires field provided 2 in. (51 mm) outdoor exhaust accelerator.
1
Maximum Equivalent Vent Length − One or Two Pipe Applications
Two 45 elbows are equal to one 90 elbow.
One 45 elbow is equivalent to 2.5 feet (.75 m) of straight vent pipe.
045 and 070 − 2, 2−1/2, 3 or 4 in. − terminate with 1−1/2 in. pipe
090 − 2, 2−1/2, 3 or 4 in. − terminate with 2 in. pipe
110 − 2, 2−1/2, 3 or 4 in. − terminate with 2 in. pipe
135 − 3 or 4 in. − terminate with 2 in. pipe
376not allowed not allowed15 (4.6)not allowed6 (1.8)
4102not allowed not allowed25 (7.6)not allowed10 (3.0)
2
G43UF−48C−110
2
G43UF−60C−110
Wall Ring
Kit
2 in.
(51 mm)
1−1/2 x 12 in.
(38 x 305 mm)
3
G43UF−60D−135
4
125
4
90
4
90
4
90
Outdoor Exhaust
Accelerator
(Diameter X Length)
2 x 12 in.
(51 x 305 mm)
15F74− − −− − −
2
1 (0.3)not allowed1 (0.3)
2
2 (0.6)not allowed2 (0.6)
2
2 (0.6)not allowed2 (0.6)
2
4 (1.2)not allowed4 (1.2)
2
1 (0.3)not allowed1 (0.3)
3
2 (0.6)not allowed2 (0.6)
3
2 (0.6)not allowed2 (0.6)
3
4 (1.2)not allowed4 (1.2)
3
6 (1.8)not allowed6 (1.8)
3
10 (3.0)not allowed10 (3.0)
G43UF / Page 7
4
4
4
4
38
27
27
27
FILTER AIR RESISTANCE
For 1 Inch (25 mm) Cleanable Filter (Field Provided)
cfmL/sin. w.g.
0
200950.010
4001900.03
600
8003800.0615
10004700.09
1200
14006600.1535
16007550.19
1800
20009450.2765
220010400.33
2400
260012250.44110
00.000
2850.0410
5650.1230
8500.2355
11300.3895
Pa
5
20
45
80
HIGH ALTITUDE INFORMATION
Pressure regulator adjustment may be required depending on
altitude. See below for proper pressure regulator setting.
Manifold Pressure
(Outlet)
FuelAltitude − ft. (m)
Natural
0−4500 (0−1372)3.5 (0.87)
4501−7500 (1373−2286)
7501−10000 (2287−3048)
3
LPG
Propane
0−4500 (0−1372)10.0 (2.49)
4501−7500 (1373−2286)
7501−10,000 (0−3048)
1
High Altitude Orifice Kit required, see Gas Heat Accessories table for order number.
2
High Altitude Pressure Switch Kits as required, see Gas Heat Accessories table for
order number.
3
LPG/Propane conversion kit required, see Gas Heat Accessories table for order
number.
in. w.g. (kPa)
2
3.5 (0.87)
1,2
3.5 (0.87)
2
10.0 (2.49)
2
10.0 (2.49)
INSTALLATION CLEARANCES
Sides
Rear0 inches (0 mm)
Top/Plenum1 inch (25 mm)
Front0 inches (0 mm)
Front (service/alcove)24 inches (610 mm)
Floor
NOTE − Air for combustion and supply air ventilation must conform to the methods
outlined in American National Standard (ANSI-Z223.1) National Fuel Gas Code or
National Standard of Canada CAN/CGA-149.1, & CAN/CGA-149.2 Installation Code
for Gas Burning Appliances".
NOTE−In the U.S. flue sizing must conform to the methods outlined in current
GAMA/A.G.A. venting tables, American National Standard (ANSI-Z223.1) National
Fuel Gas Code or applicable provisions of local building codes. In Canada flue sizing
must conform to the methods outlined in National Standard of Canada
CAN/CGA-149.1 and .2.
1
Allow proper clearances to accommodate condensate trap and vent pipe installation.
2
Do not install the furnace directly on carpeting, tile, or other combustible materials other
than wood flooring.
1
0 inches (0 mm)
2
Combustible
INSTALLATION CONFIGURATIONS
VENT
PIPING
CONDENSATE
DRAIN
AIR FLOW
HEAT
EXCHANGER
BLOWER
NOTE − The vent
piping and condensate drain can be
moved to the other
side of the unit. Vent
piping and drain
must be installed on
the same side of the
unit with each other
unless optional Condensate Trap Alternate Location Kit is
used.
G43UF / Page 8
DIMENSIONS − INCHES (MM)
Model N
1
NOTE − 60C and 60D size units that require air volumes over
1800 cfm (850 L/s) must have one of the following:
a. Single side return air with transition, to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) air filter. Required to
maintain proper air velocity.
b. Single side return air with optional RAB Return Air Base
c. Bottom return air.
d. Return air from both sides.
e. Bottom and
See Blower Performance Tables for additional information.
2
Optional External Side Return Air Filter Kit is not for use with the
RAB RETURN AIR BASE (Up−Flow Applications Only)
For use with B, C, and D size furnaces only
4
(102)
AIR FLOW
17−1/2 (446) RAB−B−6 (76M88)
21 (533) RAB−C−6 (74M74)
24−1/2 (622) RAB−D−6 (74M75)
CONDENSATE
TRAP
14
(356)
FURNACE
FRONT
6 (152)
OPTIONAL RAB
RETURN AIR BASE
14
(356)
7/8
(22)
4
(102)
1
23 (584)
Overall
(Maximum)
1
Unit side return
air Opening
SIDE RETURN
5
(102)
AIR OPENINGS
(Either Side)
20−1/2 (521)
27−5/8 (702)
SIDE VIEW
1
Minimum
11 (279)
2
Maximum
14 (356)
1
18−1/2
(470)
Overall
(Maximum)
3/4
(19)
FRONT VIEW
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
14 inches (356 mm) is the maximum size the height of the unit opening can be cut. This may interfere with the condensate drain
(if located on the same side of the unit as the opening).
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
WALL ASSEMBLY TERMINATION KIT − RING KIT
15F74 − 2 inch (51 mm)
See Installation Instructions for specific usage.
DIRECT VENT APPLICATION
8 in. (203 mm)
minimum
NOTE − 12 in. (305 mm) minimum height above
average snow accumulation.
12 in. (305 mm) maximum
without support
6 in. (152 mm)
maximum
4−1/2 (114)
INTAKE AIR
ELBOW
(Field Supplied)
TERMINATION
ASSEMBLY
(Furnished)
NON−DIRECT VENT APPLICATION
NOTE EXHAUST PIPE SHOWN
Kit Contains Enough Parts For Two Installations
NOTE 12 in. (305 mm) minimum height above
average snow accumulation.
12 in. (305 mm) maximum
without support
EXHAUST
AIR
G43UF / Page 11
OPTIONAL ACCESSORY DIMENSIONS − INCHES (MM)
DIRECT VENT APPLICATIONS
WALL TERMINATION KITS (CLOSE-COUPLE) − 22G44 − 2 inch (51 mm) or 44J40 − 3 inch (76 mm)
See Installation Instructions for specific usage.
12
(305)
If Intake and Exhaust Pipe is less than
12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed.
EXHAUST
AIR
INTAKE
AIR
5 (127)
5-1/2
(140)
EXHAUST
AIR
GRADE
INSULATION
(Not Furnished)
12
(305)
2
(51)
INTAKE
AIR
12
(305)
ABOVE GRADE
GRADE
12 (305)
Minimum
WTK WALL ASSEMBLY TERMINATION KIT WITH FIELD FABRICATED ABOVE GRADE EXTENDED CLEARANCE
30G28 − 2 inch (51 mm) or 81J20 − 3 inch (76 mm)
See Installation Instructions for specific usage.
12
(305)
INTAKE
AIR
5
(127)
5-1/2
(140)
EXHAUST
AIR
GRADE
INSULATION
(Not Furnished)
If Intake and Exhaust Pipe is less than
12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed.
EXHAUST
AIR
INTAKE
AIR
8 (203)
Minimum
12 (305)
Maximum
ABOVE GRADE
GRADE
12 (305)
Minimum
G43UF / Page 12
BLOWER/WATTS DATA
External Static
External Static
External Static
External Static
G43UF−24B−045 PERFORMANCE (Less Filter)
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
0.00
01125530425900425360745350295690325265
0.10251115525410905425350760360285695330260
0.20501090
0.30
751060500380880415325740350270675320250
515395895420335755355280685325255
0.401001020480365860405315720340260665315240
0.50125970
0.60
150920435335795375290665315240600285220
460345835395300700330255640300230
0.70175860405315730345270620295230565265215
0.80200760
0.90
225675320275585275230495235200465190175
360295665315250560265215510240200
G43UF−24B−070 PERFORMANCE (Less Filter)
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
0.00
01115525435875415360720340290665315255
0.10251115525425865410350725340285670315255
0.20501100
0.30
751080510400870410330725340270655310240
520415870410335730345280665315250
0.401001050495385855405320715335265645305240
0.501251010
0.60
150980460355810380295675320250600285225
475365835395310695330255625295230
0.70175930440340770365285640300235565265215
0.80200855
0.90
225770365295650305250525245205465220190
405320720340270585275220520245200
G43UF−36B−070 PERFORMANCE (Less Filter)
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
0.00
01640775660141566557511605454851005475410
0.10251600755635139566055011605454601000470385
0.20501540
0.30
75149570558013456355051145540425990465365
72560513706505251160545445995470375
0.40100142067054512756054801125530395965455345
0.501251360
0.60
150127560049011655504101025485350900425305
64052512455904501080510375945445325
0.7017511705554651085515385965430335860405295
0.802001080
0.90
225945445400840395320765360275710 335245
5104401010475360865410310775365270
G43UF−36C−090(H) PERFORMANCE (Less Filter)
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
0.00
0163077074513606406351125530540975460440
0.10251620765715136564561011605455151000470430
0.20501590
0.30
75155073065513556405651170550475985465395
75068013656455801160545495990465405
0.40100152071563013306305451160545460980460380
0.501251465
0.60
150141567057012505904901095515420940445350
69060513006155151140540440960455360
0.70175135063554512155754701065500400905425335
0.802001260
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
22511655504751035485395900425335730345285
59551011405404401005475375850400310
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
G43UF / Page 13
BLOWER/WATTS DATA
External Static
External Static
G43UF−48C−090 PERFORMANCE (Less Filter)
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
0.00
021601020880188089075514907056021235580485
0.10252100990850185587573014807005851230580475
0.20502035
0.30
751965925750175583065014756955451220575445
960805181586069014756955601225580460
0.401001885890725171581062514656905101215575430
0.501251780
0.60
1501690800660155073555013606404601110525380
840680163077058014206704901150540400
0.701751575745620141066550512105704051035490350
0.802001375
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
225122558052011205304151050495365885420310
65055012305804501125530380970460325
G43UF−60C−110 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
G43UF−60C−110 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
G43UF / Page 14
22519109001050182086079517058056751540725590
9551090190590082518108557101625765610
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
BLOWER/WATTS DATA
G43UF−60D−135 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
22519309101110180085083516557806851440680570
9551160189089087517208107101515715590
G43UF−60D−135 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base,
Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Pressure
High
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
22519709301120183586583016807956901540725545
9951195194591588017658307101540725580
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
Air Volume / Watts at Different Blower Speeds
Medium−HighMedium−LowLow
G43UF / Page 15
Visit us at www.lennox.com
For the latest technical information, www.lennoxdavenet.com
Contact us at 1−800−4−LENNOX
NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.