Lennox G41UF?24B?045, G41UF?36B?070, G41UF?36B?045, G41UF?48C?090, G41UF?60C?090 Service Literature

...
Corp. 0303−L2
Service Literature
G41UF SERIES UNITS
G41UF series units are high−efficiency upflow gas fur naces manufactured with Lennox DuralokPlust alumi nized primary and stainless steel secondary clamshelltype heat exchangers. G41UF units are available in heating input capacities of 44,000 to 132,000 Btuh (12.9 to 38.6 kW) and cooling applications from 2 through 5 tons (7.0 through
17.6 kW). Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is available for conversion to LPG operation. All G41UF units are equipped with the Lennox SureLight® hot sur face ignition system. The gas valve is redundant to as sure safety shut−off as required by C.S.A.
The heat exchanger, burners and manifold assembly can be removed for inspection and service. The maintenance section gives a detailed description on how this is done.
Information contained in this manual is intended for use by qualified service technicians only. All specifications are sub ject to change. Procedures outlined in this manual are pre sented as a recommendation only and do not supersede or replace local or state codes.
G41UF
Table of Contents
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Performance Data 3. . . . . . . . . . . . . . . . . . . . . .
I−Unit Components 8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
II −Placement and Installation 16. . . . . . . . . . . . . . . . . . .
III−Start−Up 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV−Heating System Service Checks 22. . . . . . . . . . . . . .
V−Typical Operating Conditions 26. . . . . . . . . . . . . . . . .
VI−Maintenance 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII−Wiring and Sequence of Operation 30. . . . . . . . . . .
VIII−Troubleshooting 35. . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person al injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon nect switch(es). Unit may have multiple power supplies.
Page 1
2003 Lennox Industries Inc.
Litho U.S.A.
SPECIFICATIONS
Performance
Drain H
T
Ki
Gas Heating Performance
Output− Btuh (kW) 40,000 (11.7) 40,000 (11.7) 60,000 (17.6) 80,000 (23.4) 80,000 (23.4)
Highstatic(CSA)− in.w.g. (Pa) 0.5 0.5 0.5 0.5 0.5
Temperature rise range − _F (_C) 35 − 65 (19 − 36) 25 − 55 (14 − 31) 35 − 65 (19 − 36) 50 − 80 (28 − 44) 45 − 75 (25 − 42)
Connections in. (mm)
Condensate Drain (PVCPipe) − i.d. 1/2 (13)
Exhaust Pipe (PVC) 2 (51) 2 (51) 2 (51) 2 (51) 2 (51)
Condensate Drain (PVC Coupling) − o.d. 3/4 (19) 3/4 (19) 3/4 (19) 3/4 (19) 3/4 (19)
Indoor
Wheel nominal diameter x width −in. (mm)
Blower
Motoroutput − hp (W) 1/5 (149) 1/3 (249) 1/3 (249) 1/3 (249) 1/2 (373)
Tons(kW) ofaddoncooling 1 − 2 (3.5 − 7.0) 1 − 3 (3.5 − 10.5) 1 − 3 (3.5 − 10.5) 1 − 3 (3.5 − 10.5) 2 − 4 (7.0 − 14.0)
Shippingweight − 1 package 128 lbs. (58 kg) 131 lbs. (59 kg) 141 lbs (64 kg) 160 lbs. (73 kg) 164 lbs. (74 kg)
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES – MUST BE ORDERED EXTRA
4
Side Return Air Filter & Rack Kit − Number & size of
filters
EZ Filter Base
Number and size of field provided filter − in. (mm) 16 x 25 x 1 (406 x 635 x 25) 20 x 25 x 1 (508 x 635 x 25)
Condensate
eat
Cable
Heat Cable
ape
6
High Altitude Orifice Kit − Natural Gas 47M82 47M82 47M82 47M82 47M82
3
High Altitude
Pressure Switch Kit
LPG/Propane Kit
5
Termination
ts
Twinning Kit 15L38 15L38 15L38 15L38 15L38
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for nonweatherized
furnaces.
3
Required for proper operation at altitudes over 4500 ft. (1370 m).
4
Cleanable polyurethane frame type filter.
5
Kits contain enough parts for two installations. Determine from venting tables proper exhaust pipe size and termination kit required.
6
Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).
NOTE − Filters and provisions for mounting are not furnished and must be field provided.
Catalog Number − Shipping Weight 73P56 − 7 lbs. (3 kg) 73P57 − 8 lbs. (4 kg)
Dimensions − H x W x D − in. (mm) 4 x 17−5/8 x 28−5/8 (102 x 448 x 727)
50 ft. (15.2 m) long 26K70 26K70 26K70 26K70 26K70
Fiberglass − 1/2 in. (38 mm) x 66 ft. (20 m)
Aluminum foil − 2 in. (25 mm) x 60 ft. (18 m)
4501−7500 ft. (1372−2286 m)
7501−10,000 ft. (2286−3048 m)
0−7500 ft. (0−2286 m) 47M83 47M83 47M83 47M83 47M83
7501−10,000 ft. (2286−3048 m) 47M81 47M81 47M81 47M81 47M81
Roof − 2 inch (51 mm)
Roof − 3 inch (76 mm)
Wall Ring − 2 inch (51 mm) 15F74 15F74 15F74 15F74 15F74
ModelNo. G41UF−24B−045 G41UF−36B−045 G41UF−36B−070 G41UF−36C−090 G41UF−48C−090
Input− Btuh (kW) 44,000 (12.9)
1
AFUE 90.0% 90.0% 90.0% 90.0% 90.0%
44,000 (12.9) 66,000 (19.3) 88,000 (25.8) 88,000 (25.8)
1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13)
GaspipesizeIPS 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13)
10 x 7
(254 x 178)
10 x 8
(254 x 203)
10 x 8
(254 x 203)
10 x 8
(254 x 203)
10 x 10
(254 x 254)
Single 44J22 or Ten Pack 66K63 − (1) 16 x 25 x 1 in. (406 x 635 x 25 mm)
4 x 21−5/8 x 28−5/8 (102 x 549 x 727)
6 ft. (1.8 m) long 26K68 26K68 26K68 26K68 26K68
24 ft. (7.3 m) long 26K69
26K69 26K69 26K69 26K69
39G04 39G04 39G04 39G04 39G04
39G03
39G03 39G03 39G03 39G03
− − − − − − − − − 46M94 46M94
46M94
46M94 46M94 46M94 46M94
15F75 15F75 15F75 15F75 15F75
44J41
44J41 44J41 44J41 44J41
Page 2
SPECIFICATIONS
Performance
Drain H
T
Ki
Gas Heating Performance
Highstatic(CSA)− in.w.g. (Pa) 0.5 0.5 0.5 0.5
Temperature rise range − _F (_C) 25 − 55 (14 − 31) 50 − 80 (28 − 44) 40 − 70 (22 − 39) 45 − 75 (25 − 42)
Connections in. (mm)
Condensate Drain (PVC Pipe) − i.d. 1/2 (13)
Exhaust Pipe (PVC) 2 (51) 2 (51) 2 (51) 2 (51)
Condensate Drain (PVC Coupling) − o.d. 3/4 (19) 3/4 (19) 3/4 (19) 3/4 (19)
Indoor Blower
Wheelnominaldiameter xwidth −in. (mm) 11−1/2 x 10 (292 x 229)
Motoroutput − hp (W) 3/4 (560) 1/2 (373) 3/4 (560) 3/4 (560)
Tons(kW) ofaddoncooling 4 − 5 (14.0 − 17.5) 2 − 4 (7.0 − 14.0) 4 − 5 (14.0 − 17.5) 4 − 5 (14.0 − 17.5)
Shippingweight − 1 package 168 lbs. (76 kg) 173 lbs. (78 kg) 177 lbs. (80 kg) 194 lbs. (88 kg)
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES – MUST BE ORDERED EXTRA
4,6
Air Filter and Rack Kit − Number & size of filters Single 44J22 or Ten Pack 66K63 − (1) 16 x 25 x 1 (406 x 635 x 25)
EZ Filter Base
Condensate
eat
Cable
Heat Cable
ape
7
High Altitude Orifice Kit − Natural Gas Only 47M82 47M82 47M82 47M82
3
High Altitude
Pressure Switch Kit
RAB Return Air Base RAB60C (12M71) − − − − RAB60D (12M72) RAB60D (12M72)
LPG/Propane Kit
5
Termination
ts
Twinning Kit 15L38 15L38 15L38 15L38
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for nonweatherized
furnaces.
3
Required for proper operation at altitudes over 4500 ft. (1370 m).
4
Cleanable polyurethane frame type filter.
5
Kits contain enough parts for two installations. Determine from venting tables proper exhaust pipe size and termination kit required.
6
Not for use with RAB Return Air Base or with 60C and 60D size units with air flow requirements of 1800 cfm (850 L/s) or greater. See Blower Performance
tables for additional information.
7
Required for proper operation at altitudes from 7501 to 10,000 ft. (2286 to 3048 m).
NOTE − Filters and provisions for mounting are not furnished and must be field provided.
Catalog Number − Shipping Weight 73P57 − 8 lbs. (4 kg) 73P58 − 10 lbs. (5 kg)
Dimensions − H x W x D 4 x 21−5/8 x 28−5/8 in. (102 x 549 x 727 mm)
Number and size of field provided filter 20 x 25 x 1 in. (508 x 635 x 25 mm) 24 x 24 x 1 in. (610 x 610 x 25 mm)
Fiberglass − 1/2 in. (38 mm) x 66 ft. (20 m)
Aluminum foil − 2 in. (25 mm) x 60 ft. (18 m)
4501−7500 ft. (1372−2286 m) 46M94 46M94 46M94 − − −
7501−10,000 ft. (2286−3048m) 46M94
0−7500 ft. (0−2286 m) 47M83 47M83 47M83 47M83
7501−10,000ft. (2286−3048m) 47M81 47M81 47M81 47M81
Roof − 2 inch (51 mm)
Roof − 3 inch (76 mm)
Wall Ring − 2 inch (51 mm) 15F74 15F74 15F74 15F74
ModelNo. G41UF−60C−090 G41UF−48C−110 G41UF−60C−110 G41UF−60D−135
Input− Btuh (kW) 88,000 (25.8)
110,000 (32.2) 110,000 (32.2) 132,000 (38.7)
Output− Btuh (kW) 80,000 (23.4) 100,000 (29.3) 100,000 (29.3) 120,000 (35.1)
1
AFUE 90.0% 90.0% 90.0% 90.0%
1/2 (13) 1/2 (13) 1/2 (13)
GaspipesizeIPS 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13)
10 x 10 (254 x
254)
11−1/2 x 10 (292 x
229)
11−1/2 x 10 (292 x
229)
4 x 24−5/8 x 28−5/8 in. (102 x 625 x 727 mm)
6 ft. (1.8 m) long 26K68 26K68 26K68 26K68
24 ft. (7.3 m) long 26K69
26K69 26K69 26K69
50 ft. (15.2 m) long 26K70 26K70 26K70 26K70
39G04 39G04 39G04 39G04
39G03
39G03 39G03 39G03
46M94 46M94 46M95
15F75 15F75 15F75 15F75
44J41
44J41 44J41 44J41
Page 3
BLOWER PERFORMANCE
External Static
External Static
External Static
External Static
G41UF−24B−045 PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 1190 560 455 990 470 355 815 385 275
0.20 50 1160
0.30
0.40 100 1070 505 395 910 430 305 755 355 245
0.50 125 1015
0.60
0.70 175 885 415 335 750 355 260 640 300 210
0.80 200 825
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 1225 580 485 1000 470 365 820 385 290
75 1120 530 415 945 445 325 780 365 260
150 955 450 355 835 395 285 695 325 225
225 715 335 3000 600 285 220 435 205 170
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
High
545 435 970 460 340 805 380 265
480 375 865 405 295 740 350 240
390 320 695 330 245 545 255 185
G41UF−36B−045 PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 1515 715 605 1385 655 555 1190 560 485 1020 480 415
0.20 50 1470
0.30
0.40 100 1350 640 535 1250 590 465 1120 530 410 980 465 360
0.50 125 1290
0.60
0.70 175 1145 540 460 1080 510 400 975 460 345 860 405 300
0.80 200 1050
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
25 1555 735 630 1410 665 585 1190 560 520 1030 485 435
75 1410 665 555 1310 620 495 1155 545 440 1000 470 385
150 1220 575 485 1145 540 420 1020 480 365 905 430 320
225 945 445 410 900 425 345 825 390 305 730 345 270
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
High
695 580 1345 635 520 1170 550 455 1010 475 400
610 505 1205 570 450 1080 510 390 950 450 345
495 425 985 465 365 870 410 320 785 370 285
G41UF−36B−070 PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 1600 755 635 1395 660 550 1160 545 460 1000 470 385
0.20 50 1540
0.30
0.40 100 1420 670 545 1275 605 480 1125 530 395 965 455 345
0.50 125 1360
0.60
0.70 175 1170 555 465 1085 515 385 965 430 335 860 405 295
0.80 200 1080
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 1640 775 660 1415 665 575 1160 545 485 1005 475 410
75 1495 705 580 1345 635 505 1145 540 425 990 465 365
150 1275 600 490 1165 550 410 1025 485 350 900 425 305
225 945 445 400 840 395 320 765 360 275 710 335 245
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
High
725 605 1370 650 525 1160 545 445 995 470 375
640 525 1245 590 450 1080 510 375 945 445 325
510 440 1010 475 360 865 410 310 775 365 270
G41UF−36C−090 PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 1680 795 700 1390 650 585 1185 560 480 1005 475 395
0.20 50 1645
0.30
0.40 100 1560 735 615 1345 635 515 1155 545 425 990 465 360
0.50 125 1495
0.60
0.70 175 1330 630 505 1205 570 435 1035 490 360 890 420 300
0.80 200 1255
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 1705 805 730 1395 660 605 1195 555 495 1010 475 410
75 1600 755 635 1365 645 535 1165 550 445 995 470 375
150 1415 665 540 1270 600 475 1080 510 375 940 445 320
225 1135 535 450 1020 480 365 830 390 300 760 360 260
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
High
775 675 1380 650 560 1175 555 465 1000 470 390
705 580 1305 615 500 1125 530 400 970 460 345
590 485 1120 530 400 955 450 330 840 395 280
Air Volume / Watts at Different Blower Speeds
Medium Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Page 4
BLOWER PERFORMANCE
External Static
External Static
External Static
External Static
G41UF−48C−090 PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2135 1005 885 1825 860 750 1510 710 610 1275 600 495
0.20 50 2085
0.30
0.40 100 1940 915 760 1735 820 650 1480 700 535 1250 590 440
0.50 125 1865
0.60
0.70 175 1645 775 640 1475 695 520 1290 610 450 1105 520 375
0.80 200 1540
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2180 1030 930 1835 865 790 1520 715 630 1280 605 510
75 2030 955 800 1775 835 685 1500 705 565 1265 595 460
150 1740 820 670 1590 750 575 1380 650 475 1175 555 410
225 1335 630 540 1170 555 440 1070 505 375 950 450 330
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
High
985 840 1810 855 720 1505 710 580 1270 600 475
880 725 1660 785 600 1430 675 505 1215 575 425
725 600 1340 630 465 1175 555 405 1020 480 355
G41UF−60C−090 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to ac commodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2460 1160 1145 2310 1090 970 2095 990 825 1780 840 660
0.20 50 2395
0.30
0.40 100 2225 1050 1050 2110 995 880 1950 920 745 1720 810 620
0.50 125 2135
0.60
0.70 175 1950 920 950 1865 880 790 1750 825 675 1535 725 555
0.80 200 1845
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2510 1185 1160 2350 1110 990 2145 1010 850 1785 845 670
75 2325 1095 1090 2175 1025 910 2015 950 775 1735 820 630
150 2025 955 975 1950 920 820 1820 860 700 1600 755 575
225 1730 815 885 1640 775 720 1555 735 625 1340 630 510
High Medium−High Medium−Low Low
1130 1125 2240 1060 940 2060 970 805 1760 830 650
1010 1015 2050 965 855 1900 895 725 1665 785 600
870 915 1760 830 755 1640 775 650 1450 685 530
G41UF−60C−090 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2525 1195 1210 2320 1095 1010 2040 960 855 1775 835 710
0.20 50 2450
0.30
0.40 100 2300 1085 1125 2155 1020 930 1970 930 800 1720 815 665
0.50 125 2210
0.60
0.70 175 2080 980 1035 1975 935 865 1805 855 730 1610 760 615
0.80 200 2000
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2575 1215 1235 2360 111 5 1030 2050 965 875 1790 845 720
75 2375 1120 1140 2215 1045 955 1995 940 815 1740 820 680
150 2140 1010 1030 2055 970 895 1875 885 755 1665 785 635
225 1905 900 970 1785 845 800 1640 775 675 1495 705 570
High
1155 1170 2270 1070 985 2025 955 840 1755 830 695
1045 1075 2090 985 900 1915 905 775 1700 800 650
945 1010 1890 890 830 1730 815 705 1565 740 595
G41UF−48C−110 PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2160 1020 880 1880 890 755 1490 705 602 1235 580 485
0.10 25 2100 990 850 1855 875 730 1480 700 585 1230 580 475
0.20 50 2035 960 805 1815 860 690 1475 695 560 1225 580 460
0.30
0.40 100 1885 890 725 1715 810 625 1465 690 510 1215 575 430
0.50 125 1780
0.60
0.70 175 1575 745 620 1410 665 505 1210 570 405 1035 490 350
0.80 200 1375
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
75 1965 925 750 1755 830 650 1475 695 545 1220 575 445
150 1690 800 660 1550 735 550 1360 640 460 111 0 525 380
225 1225 580 520 1120 530 415 1050 495 365 885 420 310
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
High
840 680 1630 770 580 1420 670 490 1150 540 400
650 550 1230 580 450 1125 530 380 970 460 325
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Page 5
BLOWER PERFORMANCE
External Static
External Static
External Static
External Static
G41UF−60C−110 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to ac commodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2500 1180 1270 2280 1075 1050 2025 950 855 1730 815 720
0.20 50 2410
0.30
0.40 100 2280 1075 1170 2115 995 940 1910 900 790 1675 790 680
0.50 125 2195
0.60
0.70 175 1980 935 1030 1860 880 845 1705 805 700 1540 725 605
0.80 200 1895
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2550 1205 1300 2345 1105 1080 2055 970 895 1740 820 715
75 2350 111 0 1190 2175 1025 965 1945 920 805 1690 795 670
150 2075 980 1065 1955 925 875 1785 845 735 1585 750 630
225 1770 835 975 1640 775 770 1535 725 645 1415 670 565
High
1140 1225 2220 1050 1000 2000 945 840 1715 810 695
1035 1115 2035 960 910 1840 870 760 1630 770 650
895 1005 1770 835 810 1615 765 675 1475 695 580
G41UF−60C−110 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2515 1190 1295 2295 1085 1075 2040 960 880 1740 820 745
0.20 50 2450
0.30
0.40 100 2310 1090 1190 2145 1010 975 1925 910 815 1690 800 695
0.50 125 2200
0.60
0.70 175 2045 965 1065 1930 910 890 1750 825 730 1575 745 625
0.80 200 1930
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2580 1215 1340 2330 1100 1100 2045 965 950 1760 830 745
75 2375 1120 1225 2200 1040 1015 1965 925 835 1715 810 710
150 2130 1005 1105 2025 955 930 1825 860 770 1600 755 650
225 1820 860 980 1730 815 815 1555 735 660 1430 675 580
High
1155 1255 2255 1065 1040 2005 945 855 1735 820 730
1040 1135 2085 985 955 1870 880 780 1660 785 670
910 1025 1825 860 850 1650 780 695 1500 710 600
G41UF−60D−135 PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition to ac commodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2490 1175 1305 2275 1075 1100 2025 955 900 1720 810 755
0.20 50 2430
0.30
0.40 100 2285 1080 1210 2140 1010 1010 1910 900 830 1680 790 700
0.50 125 2200
0.60
0.70 175 2010 950 1075 1915 905 910 1740 820 740 1545 730 630
0.80 200 1910
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2550 1205 1340 2330 1100 1145 2035 960 955 1725 815 775
75 2355 111 0 1235 2180 1030 1035 1955 920 855 1700 800 715
150 2100 990 1110 1985 935 935 1815 855 780 1600 755 660
225 1815 855 1005 1735 820 835 1605 755 690 1420 670 580
High
1145 1285 2230 1050 1065 1990 940 890 1715 810 740
1040 1160 2070 975 980 1865 880 805 1645 775 675
900 1050 1845 870 875 1670 790 720 1490 705 605
G41UF−60D−135 PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00
0.10 25 2530 1195 1335 2330 1100 1120 2075 980 945 1730 820 750
0.20 50 2475
0.30
0.40 100 2355 1110 1230 2185 1030 1040 1975 930 865 1680 795 695
0.50 125 2275
0.60
0.70 175 2100 990 1125 1955 925 930 1785 840 780 1550 730 635
0.80 200 1995
0.90
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
0 2585 1220 1370 2355 111 0 1160 2075 980 985 1730 820 765
75 2410 1135 1260 2230 1050 1060 2010 950 890 1715 810 725
150 2190 1035 1155 2045 965 960 1850 875 805 1615 765 660
225 1860 880 1020 1750 825 835 1635 770 720 1425 670 580
High
1170 1300 2295 1085 1090 2050 970 920 1730 815 745
1075 1190 2120 1000 995 1915 905 830 1650 780 685
945 1080 1855 875 890 1715 810 745 1500 710 615
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Air Volume / Watts at Different Blower Speeds
Medium−High Medium−Low Low
Page 6
G41UF PARTS IDENTIFICATION
BURNER BOX
ASSEMBLY
GAS VALVE AND
MANIFOLD
COMBUSTION AIR
PROVE
(PRESSURE)
SWITCH
FLUE
COLLAR
COMBUSTION AIR
INDUCER
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
TOP CAP
CABINET
WARM HEADER
(COLLECTOR)
BOX
BURNER ACCESS
PANEL
BLOWER
ACCESS
DOOR
SIGHT
GLASS
DOOR
INTERLOCK
SWITCH
CONTROL BOX
CONDENSER COIL
PRIMARY LIMIT
COLD HEADER
(COLLECTOR)
BOX
FIGURE 1
Page 7
I−UNIT COMPONENTS
G41UF unit components are shown in figure 1. The com bustion air inducer, gas valve and burners can be accessed by removing the burner access panel. The blower and con trol box can be accessed by removing the blower access door. G41UF units are designed for bottom and side re turn air.
A−MakeUp Box (Figure 2)
A field makeup box is provided for line voltage wiring. Line voltage wiring to unit is routed from the make up box. The hot" wire is connected to the door switch and then from the switch to the SureLight board. The make−up box may be installed inside or outside the unit and on the unit left or right side (right side shown figure 2).
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Right Side
CLAMP LOCATION
FIGURE 2
B−Control Box Components (Figure 3)
Unit transformer (T1) and SureLight control (A92) are lo cated in the control box. In addition, a door interlock switch (S51) is located in the control box.
DOOR INTERLOCK
SWITCH (S51)
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage 24 volt section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 120VAC is located on the control box. The switch is wired in series with line volt age. When the blower door is removed the unit will shut down.
WARNING
Shock hazard. Disconnect power before servicing. Control is
not field repairable. If control is inoperable, sim ply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
3. Furnace Control (A92)
All G41UF model units are equipped with the Lennox Sur eLight ignition system. The system consists of ignition control board (figure 5 with control terminal designations in table 3), ignitor (figure 6) and sensor (figure 7). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The SureLight integrated board controls all major furnace operations. The board also features two LED lights for troubleshooting and two accessory terminals rated at (1) one amp. Tables 1 and 2 show jack plug terminal designations. See table 4 for trou bleshooting diagnostic codes. The SureLight ignitor is made of durable silicon−nitride. Ignitor longevity is also enhanced by voltage ramping by the control board. The board finds the lowest ignitor temperature which will suc cessfully light the burner, thus increasing the life of the ig nitor.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
SURELIGHT
CONTROL
BOARD
(A92)
FIGURE 3
TRANSFORMER
(T1)
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the techni cian at the same electrostatic potential. Neutral ize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
Page 8
TABLE 1
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Combustion Air Inducer Line
2
3
Combustion Air Inducer Neutral
4
Ignitor Line
Ignitor Neutral
TABLE 2
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 High Limit Output
2
3
4
5
6
7
8
9
10
11
12
Not Used
24V Line
Not Used
Rollout Switch In
24V Neutral
High Limit Input
Ground
Gas Valve In
Pressure Switch Out
Rollout Switch Out
Gas Valve Out
a−Electronic Ignition (See Figure 8)
On a call for heat the SureLight control monitors the com bustion air inducer prove switch. The control will not begin the heating cycle if the prove switch is closed (by−passed). Once the prove switch is determined to be open, the com bustion air inducer is energized. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the prove switch is not proven within 2−1/2 minutes, the control goes into Watch guard−Pressure Switch mode for a 5−minute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds during which the gas valve opens at 19 seconds for a 4−second trial for ignition. The ignitor stays energized during the 4 second trial until flame is sensed. If ignition is not proved during the 4−second period,
the control will try four more times with an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure mode. After a 60−min ute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that pro longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again. Each time 120V is removed and then re−applied, the control re−starts the learning process.
b−Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by setting the dip switches located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. For customized comfort, monitor the supply air tempera ture once the heat demand is satisfied. Note the supply air temperature at the instant the blower is de−energized. Ad just the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de−ener gized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher air temperature). See figure 4.
FANOFF TIME ADJUSTMENT
60sec. 90sec.
OFF
ON
1
2
OFF
ON
OFF
1
2
(Black square indicates switch position)
To adjust fan−off timing, flip dip switch to desired setting.
120sec.
OFFOFF OFF
ON
OFF
180sec.
1
OFF
2
ON
1
2
FIGURE 4
Page 9
SURELIGHT INTEGRATED CONTROL BOARD
XFMR–N
J156
4. Ignitor (Figure 6)
The SureLight ignitor is made of durable silicon nitride. Ig nitor longevity is enhanced by controlling voltage to the ig nitor. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor. Due to this feature of the board, voltage cannot be measured so ignitor must be ohmed. Ohm value should be 10.9 to 19.7
SureLight Ignitor Location
MEASUREMENT IS TO I.D.
5/8"
OF RETENTION RING
13/32’
J58
FIGURE 5
TABLE 3
TERMINAL DESIGNATIONS
COOL−H 120V HOT Blower Cooling Speed (120VAC)
HEAT−H Blower Heating Speed−(120VAC)
EAC−H Electronic Air Cleaner (120VAC)
HUM−H Humidifier (120VAC)
XFMR−H Transformer (120VAC)
LINE−H Input (120VAC)
LINE−N 120V NEUT Input (Neutral)
HUM−N Humidifier (Neutral)
EAC−N Electronic Air Cleaner (Neutral)
XFMR−N Transformer (Neutral)
CIR−N Blower (Neutral)
PARK Alternate Blower Speeds (dead)
(FLAME SENSE) Flame Sensor
BRACKET
IGNITOR
BURNERS FRONT VIEW
FIGURE 6
5. Flame Sensor (Figure 7)
A flame sensor is located on the left side of the burner sup port. The sensor is mounted on the bottom burner box plate and the tip protrudes into the flame envelope of the left− most burner. The sensor can be removed for service with out removing any part of the burners. During operation, flame is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve to remain open as long as flame signal is sensed.
NOTE − The G41UF furnace contains electronic com ponents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
NORMAL FLAME SIGNAL > 0.18 MICROAMPS LOW FLAME SIGNAL < DROP OUT SIGNAL = 0.15 MICROAMPS
5/16"
0.17 MICROAMPS
FIGURE 7
Page 10
The SureLight board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed below in table 4.
y
TABLE 4
DIAGNOSTIC CODES
Make sure to Identify LED’S Correctly.
Refer to Installation Instructions for control board layout.
LED #1 LED #2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH ON
OFF SLOW FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH OFF Flame sensed without gas valve energized.
ON SLOW FLASH Rollout switch open. OR: 12pin connector improperly attached.
ON ON
ON OFF
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below 0.18 microamps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
ALTERNATING
FAST FLASH
Power on − Normal operation. Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or secondary limit switch open. Limit must close within 3 minutes or unit goes into 1 hour Watchgurad.
Prove switch open. OR:Blocked inlet/exhaust vent; OR: Prove switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite.
Circuit board failure or control wired incorrectly.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage to control below 75 volts.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Low flame sense current = 0.16−0.17 microAmps.
ON OFF
DEMAND
CAI IGNITOR GAS VALVE INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
1
Pre −Purge Ignitor Warmup
15
34
Trial for Ignition
38
Blower On"
Delay
5 SEC80
Post
Purge
FIGURE 8
Page 11
ROLLOUT SWITCH
BURNER BOX
ASSEMBLY
G41UF HEATING COMPONENTS
LENNOX DURALOKPlust
HEAT EXCHANGER
(Assembly)
CLAMSHELL
(Each Segment)
CORBEL CUP
SURELIGHT
IGNITOR
LIMIT CONTROL
PROVE SWITCH
PROVE SWITCH
TUBING
BACKUP SECONDARY
LIMIT
GAS VALVE
WARM END HEADER BOX
CONDENSER COIL
COLD END HEADER BOX
ORIFICE SIZE WINDOW
COMBUSTION AIR INDUCER
COLD END HEADER BOX
FIGURE 9
Page 12