Failure to follow safety warnings exactly could result in serious injury, death,
or property damage.
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
03/06
*2P0306*
WARNING
FIRE OR EXPLOSION HAZARD.
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance.
D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately.
D Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
D If you cannot reach your gas supplier, call
the fire department.
Page 1
505,181M
*P505181M*
Page 2
G40UH(X) Unit Dimensions − inches (mm)
*NOTE − 60C and 60D units that require air volumes
over 1800 cfm (850 L/s) must have one of the following:
1. Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm)
cleanable air filter. (Required to maintain proper air
velocity.)
2. Return air from single side with optional RAB Return
Air Base.
3. Return air from bottom.
4. Return air from both sides.
5. Return air from bottom and
Refer to Engineering Handbook for additional information.
**Flue outlet may be horizontal but furnace must be
vented vertically
Optional external side return air filter kit cannot be used
with the optional RAB Return Air Base.
*135 and 155 kBtuh units only −−
Flame rollout switches are located
on brackets on the inner sides (one
on the left and one on the right) of
the burner box.
Integrated Ignition
Control Board
Blower Assembly
Capacitor
Control Transformer
FIGURE 1
Page 3
Page 4
G40UH(X) Gas Furnace
The G40UH(X) gas furnace is shipped ready for installation in the upflow and horizontal position (left or right)
fueled by natural gas. A conversion kit (ordered separately) is required for use in propane/LP gas applications. The
furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in a
horizontal application. The panel may also be removed in
upflow applications.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled G40UH(X) unit
1 − Bag assembly containing the following:
The following items may also be ordered separately:
1 − Thermostat
1 − Hanging bracket (for horizontal installations)
1 − Propane/LP changeover kit
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Safety Information
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a qualified installer, service agency
or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
G40UH(X) units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must
be installed according to the current National Fuel Gas Code
(ANSI-Z223.1). The National Fuel Gas Code is available
from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current CSA
B149 Natural Gas and Propane Installation Codes, local
plumbing or waste water codes and other applicable local
codes.
Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit
operation, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA B149 standards.
Vent installations must be consistent with the venting
tables (in this instruction) and applicable provisions of local
building codes.
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in figures 6 and 11. Accessibility
and service clearances must take precedence over fire
protection clearances.
NOTE − For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE − Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Failure
to do so may cause erratic limit operation and premature heat
exchanger failure.
This G40UH(X) furnace must be installed so that its electrical components are protected from water.
When this furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
With a parallel flow arrangement, a damper (or other means
to control the flow of air) must adequately prevent chilled air
from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the
heating or the cooling unit, unless it is in the full HEAT or
COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Page 4
Page 5
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
NOTE − G40UH(X) series units should not be installed as
a unit heater.
The G40UH(X) furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the upflow or horizontal position.
This furnace design has not been CSA International certified for installation in mobile homes, recreational vehicles,
or outdoors.
Lennox does not recommend the use of G40UH(X) units as
a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
G40UH(X) units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified
according to these installation instructions.
NOTE − The Commonwealth of Massachusetts stipulates these additional requirements:
D Gas furnaces shall be installed by a licensed plumb-
er or gas fittter only.
D The gas cock must be T handle" type.
D When a furnace is installed in an attic, the passage-
way to and service area surrounding the equipment
shall be floored.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered
when installing a G40UH(X) furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be
located close to the chimney or vent termination point.
• Do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
• Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that
was needed. In today’s homes, tight construction practices
make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents,
chimneys, and fireplaces force additional air that could be
used for combustion out of the house. Unless outside air is
brought into the house for combustion, negative pressure
Page 5
Page 6
(outside pressure is greater than inside pressure) will build
to the point that a downdraft can occur in the furnace vent
pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install G40UH(X) furnaces to ensure efficient
and safe operation. You must consider combustion air
needs and requirements for exhaust vents and gas piping.
A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1).
This reprinted material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
CAUTION
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliances will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all
fuel-burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as
the furnace, much more air is necessary to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace
components.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the
combined input rating of all appliances installed in that
space. This definition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
negative pressure condition. Air for combustion and dangerous ventilation can be brought into the confined space
either from inside the building or from outside.
Page 6
Page 7
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
NOTE−Each opening shall have a free area of at least one square
inch (645 mm2) per 1,000 Btu (.29 kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square
inches (64516 mm2).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 2
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas−fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 2.
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the
top of the enclosure and one opening within 12 inches (305
mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum
free area of 1 square inch (645 mm2) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the enclosure. See figures 3 and 4. When communicating with
the outdoors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch (645 mm2) per
2,000 Btu (.56 kW) per total input rating of all equipment in
the enclosure. See figure 5.
When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens must
be considered. If the design and free area of protective covering is not known for calculating the size opening required,
it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in the
open position or interlocked with the equipment so that they
are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE
CHIMNEY OR
GAS VENT
VENTILATION LOUVERS
(Each end of attic)
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2)
per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
OUTLET
AIR
ALL AIR FROM OUTSIDE
WATER
HEATER
INLET
AIR
FIGURE 3
Page 7
Page 8
CHIMNEY
OR GAS
VENT
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
The G40UH(X) gas furnace can be installed as shipped
in either the upflow position or the horizontal position,
with right-hand or left-hand air discharge.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
and installation and service clearances [24 inches (610
mm) at unit front]. The unit must be level.
FURNACE
NOTE−The inlet and outlet air openings shall each have a
free area of at least one square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
INLET AIR
(Ends 12 in.
above bottom)
WATER
HEATER
FIGURE 4
EQUIPMENT IN
CONFINED SPACE
ALL AIR FROM
OUTSIDE
OUTLET AIR
FURNACE
CHIMNEY
OR GAS
VENT
WATER
HEATER
NOTE − 1/3 hp blower motors are equipped with four flexible mounting legs, and 1/2 hp blower motors are equipped
with three flexible legs and one rigid leg. The rigid leg is
equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a
flexible mounting leg). The bolt and washer must be re-moved before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
Upflow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 6.
Upflow Application Installation Clearances
Top
Left Side
Right Side
INLET AIR
NOTE − Each air duct opening shall have a free area of at least
one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of
the total input rating of all equipment in the enclosure. If the
equipment room is located against an outside wall and the air
openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (645 mm2)
per 4,000 Btu (1.17 kW) per hour of the total input rating of all
other equipment in the enclosure.
FIGURE 5
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do
not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of
the safety control devices, which could result in personal injury or death.
Page 8
Bottom
Type of Vent
Connector
Top1 in. (25 mm)1 in. (25 mm)
*Front3 in. (76 mm)3 in. (76 mm)
Back00
Sides0†0
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
†Left side requires 3 inches if a single wall vent is used on 14−1/2
inch cabinets, or 2 inches if a single wall vent is used on 17−1/2
inch cabinets.
Type CType B1
FIGURE 6
Page 9
Return Air −− Upflow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
NOTE − When air volumes over 1800 cfm (850 L/s) are
required with 60C or 60D models in an upflow application, the following return air options are available:
1 − Return air from single side with transition which will
accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Required to maintain proper air velocity.)
See figure 7.
2 − Return air from single side with optional RAB Return
Air Base. See figure 8.
3 − Return air from bottom.
4 − Return air from both sides.
5 − Return air from bottom and
one side.
Refer to Engineering Handbook for additional information.
Side Return Air
(with transition and filter)
20" X 25" X 1"
(508mm X635mm X 25mm)
Cleanable Filter
Return Air
Plenum
Transition
FIGURE 7
Optional Return Air Base
(Upflow Applications Only −− For use with B, C and D cabinets only)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8
(143)
SIDE RETURN
AIR OPENINGS
(Either Side)
23 (584)
27−5/8 (702)
SIDE VIEW
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7−16
(570)
Overall
(Maximum)
AIR FLOW
17−1/2 (446) RAB−B (98M60)
21 (533) RAB−C (98M58)
24−1/2 (622) RAB−D (98M59)
FURNACE
FRONT
7−1/4 (184)
OPTIONAL RAB
RETURN AIR BASE
4
(102)
14
(356)
7/8
(22)
FRONT VIEW
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in.
(584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return
air opening. The size of the opening must not extend beyond the markings on the furnace cabinet..
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
NOTE− Optional Side Return Air Filter Kits are not for use with RAB Return Air Base.
3/4
(19)
FIGURE 8
Page 9
Page 10
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See figure 9.
Removing the Bottom Panel
Leveling Bolt Installation
Furnace Front
3/8
(10)
3/8
(10)
Inches (mm)
1−3/4
(44)
Screw
Bottom Cap
Bottom Panel
FIGURE 9
Leveling an Upflow Unit
When the side return air inlets are used in an upflow application, it may be necessary to install leveling bolts on the
bottom of the furnace. Use field−supplied corrosion−resistant 5/16 inch machine bolts (4) and nuts (8). See figure 10.
NOTE − The maximum length of the bolt is 1−1/2 inches.
1 − Lie the furnace on its back and drill a 5/16 inch diame-
ter hole in each corner of the furnace’s bottom. See figure 10 for the correct location of the holes. Drill through
the bottom panel and the bottom flange of the cabinet.
2 − Install one bolt and two nuts into each hole. Screw the
first nut onto a bolt and then insert the bolt into a hole. A
flat washer may be added between the nut and the bottom of the unit.
3 − Screw another nut onto the bolt on the inside of the fur-
nace base. A flat washer may be added between the
nut and the bottom of the unit.
4 − Adjust the outside nut to the appropriate height and
tighten the inside nut to secure the arrangement.
NOTE − The unit may be tilted back−to−front a maximum of
1". This will ensure proper draining of the heat exchanger.
1−3/4
(44)
Leveling Bolts
Furnace
Bottom
Leveling Bolts
3/8
(10)
1−3/4
(44)
1−3/4 (44)
3/8
(10)
FIGURE 10
Horizontal Applications
The G40UH(X) furnace can be installed in horizontal applications.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 11.
Horizontal Application
Installation Clearances
Top
Left End
Bottom
Vent Connector
Type
Top00
*Front3 in. (76 mm)3 in. (76 mm)
Back00
Ends2 in. (51 mm)2 in. (51 mm)
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Type CType B1
Right End
FIGURE 11
Page 10
Page 11
This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or
floor joists, as shown in figure 12, or install the furnace on
a platform, as shown in figure 13. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
NOTE − In horizontal applications, the unit must be level side to side. The unit may be tilted back to front a maxi-
mum of 1". This will ensure proper draining of the heat exchanger.
Typical Horizontal Application
Unit Suspended in Attic or Crawlspace
Leave sufficient clearance between rod and unit to
remove access panel.
Horizontal Application
Unit Installed on Platform
NOTE − Line contact is permissible. See the unit nameplate for
clearances.
GAS
ENTRY
VENT
PIPE
WORKING
PLATFORM
FIGURE 13
1/4 in. ROD
ANGLE
IRON
U−CHANNELS
FIGURE 12
NOTE − Heavy gauge perforated sheet metal straps
(plumbers’ straps) may be used to suspend the unit from
roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both
the ends and the middle of the furnace to prevent sagging.
The straps must not interfere with the plenum or exhaust
piping installation. Securing screws should be 1/2 inch
from the top edge and 1−1/2 inch from the side edge in all
cases. Cooling coils and supply and return air plenums
must be supported separately.
NOTE − When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the evaporator coil to drain.
Return Air −− Horizontal Applications
Return air can be brought in through the end of a furnace
installed in a horizontal application. The furnace is
equipped with a removable bottom panel to facilitate
installation. See figure 9.
WARNING
Improper installation of the furnace can result in personal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or the living space. Use screws and joint tape to seal
the return air system to the furnace.
In platform installations with bottom return air, the
furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
The return and supply air duct systems must never
be connected to or from other heating devices such
as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property damage could result.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Page 11
Page 12
Filters
Furnace
This unit is not equipped with a filter or rack. A field−provided high−velocity filter is required for the unit to operate
properly. Table 1 lists recommended filter sizes.
A filter must be in place whenever the unit is operating.
TABLE 1
Furnace
Cabinet Size
14−1/2"16 X 25 X 1 (1)14 X 25 X 1 (1)
17−1/2"16 X 25 X 1 (1)16 X 25 X 1 (1)
21"16 X 25 X 1 (1)20 X 25 X 1 (1)
24−1/2"16 X 25 X 1 (2)24 X 25 X 1 (1)
Side ReturnBottom Return
Filter Size
Venting
A 4−inch diameter flue transition is factory-installed on the
combustion air inducer outlet of all models. Modifying or
removing the flue transition will cause the unit to operate unsafely and will void the unit certification. The
vent connector does not require insulation.
The combustion air inducer may be rotated clockwise or
counterclockwise by 90° to allow for vertical vent discharge. Remove the four mounting screws, rotate the assembly (including the gasket), then reinstall the mounting
screws. See figure 14. Use the provided wire tie to bundle
the pressure switch wires with the inducer motor power
leads. Route the power leads away from any moving
parts to prevent damage to the wires.
Duct System
Use industry-approved standards to size and install the
supply and return air duct system. This will result in a quiet
and low-static system that has uniform air distribution.
NOTE − Do not operate the furnace with an external static
pressure that exceeds 0.5 inches w.c. Higher external static pressures may cause erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel must be installed in the supply air duct. The
access panel should be large enough to permit inspection
(either by smoke or reflected light) of the heat exchanger
for leaks after the furnace is installed. The furnace access
panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
Return air must not be drawn from a room where this
furnace, or any other gas appliance (ie., a water heater), is installed. When return air is drawn from a room, a
negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the
flue products can be pulled back down the vent pipe and
into the room. This reverse flow of the flue gas may result
in incomplete combustion and the formation of carbon
monoxide gas. This toxic gas might then be distributed
throughout the house by the furnace duct system.
In upflow applications, the return air can be brought in
through the bottom or either side of the furnace. If a furnace
with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely.
Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to
ensure a tight seal. If a filter is installed, size the return air
duct to fit the filter frame.
90°
Flue Transition
(Do not remove)
Mounting Screws
(Remove)
Top Cap
Flue Outlet Hole
(Reattach
Cutout Here)
Combustion Air Inducer
MOUNTING SCREWS
(Remove)
Power Leads
FIGURE 14
Optional Flue Outlet
Supply Air
Opening
(Top View)
Cut out
Optional Flue Outlet
(Side View)
FIGURE 15
90°
Page 12
Page 13
Use sheet metal shears to remove the cut out from the side
of the cabinet. Use the two provided sheet metal screws to
install the cut out on the top cap to cover the original flue
outlet opening. See figure 15.
The G40UH(X) series units are classified as fan−assisted
Category I furnaces when vertically vented according to
the latest edition of the National Fuel Gas Code (NFPA 54/
ANSI Z223.1) in the USA and the current CSA B149 Natural Gas and Propane Installation Codes in Canada. A fan−
assisted Category I furnace is an appliance equipped with
an integral mechanical means to either draw or force combustion products through the combustion chamber and/or
heat exchanger.
NOTE − Use these instructions as a guide. They do not supersede local codes. This furnace must be vented according to all local codes these installation instructions, and the
provided venting tables in these instructions
The venting tables in this manual were extracted from the
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are
provided as a guide for proper vent installation. Proper application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the absence of local codes, the NFGC serves as the defining document.
Refer to the tables and the venting information contained in
these instructions to properly size and install the venting
system.
IMPORTANT
Once the venting system is installed, attach the Disconnected Vent" warning sticker to a visible area of
the plenum near the vent pipe. The warning sticker
is provided in the bag assembly.
Use self−drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the
flue transition. If self−drilling screws are used to attach the
vent pipe, it is recommended that three be used. Drive one
self−drilling screw through the front and one through each
side of the vent pipe and collar. See figure 16.
Install the first vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central furnaces must be either tile-lined or lined with a listed metal
lining system or dedicated gas vent. Unlined masonry
chimneys are prohibited. See figures 17 and 18 for common venting.
A chimney with one or more sides exposed to the outside of
the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile−lined must be
lined with B1 vent or a listed insulated flexible metal vent.
An exterior tile−lined chimney that is sealed and capped
may be lined with a listed uninsulated flexible metal vent.
If the existing chimney will not accommodate a listed metal
liner, either the chimney must be rebuilt to accommodate
one of these liners or an alternate approved venting method must be found.
Insulation for the flexible vent pipe must be an encapsulated fiberglass sleeve recommended by the flexible vent
pipe manufacturer. See figure 17.
DO NOT insulate the space between the liner and the
chimney wall with puffed mica or any other loose granular insulating material
Common Venting Using Metal−Lined Masonry Chimney
SEALED
WARNING
Asphyxiation hazard. The exhaust vent for this furnace must be securely connected to the furnace flue
transition at all times.
VENT CONNECTION
VENT
PIPE
FURNACE
FLUE TRANSITION
COLLAR
FIGURE 16
Page 13
MAX. LENGTH
−− SEE NOTE 1
5 ft. (1.5 m)
minimum
VENT CONNECTOR
SEE NOTE 2
4 in. (102 mm)
minimum
OTHER
APPLIANCE
NOTE 1 − Refer to the provided venting tables for installations in the USA
and the venting tables in CSA−B149 for installations Canada.
NOTE 2 − Either single-walled or double-walled vent connector may be
used. Refer to the capacity requirements shown in the provided venting
tables for installations in USA and the venting tables in current CSA−
B149 for installations in Canada.
BELOW.
MIN. LENGTH −− AS
SHORT AS PRACTICAL
FURNACE
EXTERIOR
CHIMNEY WITH
METAL
LINER
PERMANENTLY
SEALED FIREPLACE
OPENING
FIGURE 17
Page 14
Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector
MINIMUM LENGTH = AS SHORT AS PRACTICAL.
FOR MAXIMUM LENGTH SEE NOTE TO LEFT
NOTE− Refer to provided venting tables
for installations in the USA and the
venting tables in current CSA−B149 for
installations in Canada.
FURNACE
OTHER
APPLIANCE
Note − Either single-walled or double-walled vent connector may be used. Refer to the capacity requirements as shown in the provided venting tables for installations in USA and the venting tables in current CSA−B149 for installations in Canada.
VENT
CONNECTOR
SEE NOTE 1 BELOW
INTERIOR TILE−LINED
MASONRY CHIMNEY
NOTE − the chimney must be properly
sized per provided venting tables or
lined with listed metal lining system.
PERMANENTLY
SEALED FIREPLACE
OPENING
FIGURE 18
Never connect a Category I appliance to a chimney that is
IMPORTANT
SINGLE appliance venting of a fan-assisted furnace
into a tile-lined masonry chimney (interior or outside
wall) is PROHIBITED. The chimney must first be lined
with either type B1 vent or an insulated single wall
flexible vent lining system which has been sized according to the provided venting tables and the vent
pipe manufacturer’s instructions.
servicing a solid−fuel appliance. If a fireplace chimney flue
is used to vent this appliance, the fireplace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney flue is not considered
to be exposed to the outdoors.
General Venting Requirements
Vent all G40UH(X) furnaces according to these instructions:
A fan−assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
• The chimney is currently serving at least one drafthood
equipped appliance.
S The vent connectors and chimney are sized according
to the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149
Natural Gas and Propane Installation Codes in Canada
If type B1 double-wall vent is used inside a chimney, no other appliance can be vented into the chimney. The outer wall
of type B1 vent pipe must not be exposed to flue products.
A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings
and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting G40UH(X) series units. The chimney
passageway must be checked periodically to ensure that it
is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator,
or flue restrictor between the furnace and the chimney.
1 − Vent diameter recommendations and maximum allow-
able piping runs are found in the provided venting tables
for the USA, and the appropriate venting tables in the
standards of CSA B149 Natural Gas and Propane
Installation Codes for Canada.
2 − In no case should the vent or vent connector diameter
be less than the diameter specified in the provided
venting tables for the USA, and the appropriate venting
tables in the standards of CSA B149 Natural Gas and
Propane Installation Code for Canada.
3 − Single appliance vents − If the vertical vent or tile-lined
chimney has a larger diameter or flow area than the
vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent
connector diameter to determine the maximum vent
capacity. The flow area of the vertical vent, however,
shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood outlet area or
flue collar area unless designed according to approved
engineering methods.
4 − Multiple appliance vents − The flow area of the largest
section of vertical vent or chimney shall not exceed 7
times the smallest listed appliance categorized vent
area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.
Page 14
Page 15
5 − The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
6 − Single appliance venting configurations with zero lat-
eral lengths (tables 3 and 4), are assumed to have no
elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond
two, the maximum capacity listed in the venting table
should be reduced by 10% (0.90 x maximum listed capacity).
7 − The common venting tables (5, 6, 7, and 8) were gen-
erated using a maximum horizontal vent connector
length of 1−1/2 feet (.46 m) for each inch (25 mm) of
connector diameter as follows:
TABLE 2
Connector Diameter
inches (mm)
3 (76)4−1/2 (1.37)
4 (102)6 (1.83)
5 (127)7−1/2 (2.29)
6 (152)9 (2.74)
7 (178)10−1/2 (3.20)
Maximum Horizontal
Connector Length feet (m)
8 − If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent of two
90° elbows (0.80 x maximum common vent capacity).
The horizontal length of the offset shall not exceed
1-1/2 feet (.46 m) for each inch (25 mm) of common
vent diameter.
9 − The vent pipe should be as short as possible with the
least number of elbows and angles required to complete the job. Route the vent connector to the vent using the shortest possible route.
10 − A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4 mm)
per linear foot (305 mm) of connector, back toward the
appliance.
11 − Vent connectors shall be firmly attached to the furnace
flue collars by self−drilling screws (three recom-
mended) or other approved means, except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions.
Joints between sections of single wall connector piping
shall be fastened by screws or other approved means.
12 − When the vent connector used for Category I ap-
pliances must be located in or pass through a crawlspace or other areas which may be cold, that portion of
the vent connector shall be constructed of listed
double-wall type B vent material or material having
equivalent insulation qualities.
13 − All venting pipe passing through floors, walls, and ceil-
ings must be installed with the listed clearance to combustible materials and be fire stopped according to local codes. In absence of local codes, refer to NFGC
(Z223.1).
14 − No portion of the venting system can extend into, or pass
through any circulation air duct or plenum.
15 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
16 −If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10%, the equivalent of one 90° elbow (0.90 x maximum
common vent capacity).
17 −The common vent diameter must always be at least as
large as the largest vent connector diameter.
18 −In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of
the draft hood outlet or flue collar outlet.
19 − Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the
chimney.
20 − When connecting this appliance to an existing dedicated
or common venting system, you must inspect the venting
system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these
instructions and the provided venting tables for the USA,
and the appropriate venting tables in the standards of
CSA B149 Natural Gas and Propane Installation Codes
for Canada. If the existing venting system does not meet
these requirements, it must be resized.
Page 15
Page 16
TABLE 3
(
)L(
)
(feet)
(feet)
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
H
feet
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
feet
0078015202510375
2135118972715732232
4214930943915350227
6254636914714959223
0084016502760415
21257161092517828263
52353321034217153255
8284939985116464247
0088017502950447
21261171182319426289
52357321134118752280
103051411045417667267
0094019103270502
21169151362022622339
52265301303921949330
102959401215120664315
153553481126119576301
0097020203490540
21075141491825020377
52171291433824247367
102864381335022962351
153458461245921773337
204852551166920684322
00100021303740587
2981131661428318432
52177281603627545421
102770371504826259405
153364441415724970389
205658531326623780374
30NRNR7311 388214104346
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 16
Page 17
TABLE 4
(
)L(
)
(feet)
(feet)
Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving a Single Category I Appliance
Vent and Connector Diameter − D (inches)
Height
H
feet
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
feet
038775915185249126373
23951609685156123231
4NRNR7492102152146225
6NRNR8389114147163220
037835816483273123412
239565910883176121261
5NRNR77102107168151252
8NRNR9095122161175243
037875717482293120444
23961591178219311 9287
5525676111105185148277
10NRNR97100132171188261
03693561908032511 6499
23869571368022511 5337
5516375128102216144326
10NRNR9511 6128201182308
15NRNRNRNR158186220290
03596542007834611 4537
23774561487824811 3375
5506873140100239141363
10NRNR93129125223177344
15NRNRNRNR155208216325
20NRNRNRNR186192254306
03499532117637211 0584
237805516476281109429
549747215798271136417
10NRNR91144122255171397
15NRNR115131151239208377
20NRNRNRNR181223246357
30NRNRNRNRNRNRNRNR
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 17
Page 18
V
ent
C
Height
Rise
6
V
Height
Height
H
(feet)(feet)
6
8
10
15
20
30
onnector
Rise
TABLE 5
Vent Connector Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving Two or More Category I Appliances
Vent and Connector Diameter − D (inches)
3 Inch4 Inch5 Inch6 Inch
R
MINMAXMINMAXMINMAXMINMAX
1223735664610658164
2234137754812160183
3244438814913262199
1224035724911464176
2234436805112866195
3244737875313967210
1224334784912365189
2234736865113667206
3245037925214669220
1215033894714264220
2225335964915366235
32455361025116368248
1215433994615762246
22257341054816764259
32360351105017666271
12062311134518160288
22164331184719062299
32266341234819864309
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 6
Common Vent Capacity
Type B Double−Wall Vents with Type B Double−Wall Connectors
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter − D (inches)
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
1 − Seal any unused openings in the common venting sys-
tem.
2 − Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 − Close all building doors and windows and all doors be-
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 − After the main burner has operated for five minutes,
test for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle, or smoke from
a cigarette, cigar, or pipe.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.
7 − If a venting problem is found during any of the preced-
ing tests, the common venting system must be modified to correct the problem.
Page 19
Page 20
Resize the common venting system to the minimum
p
Iron Pipe
size determined by using the appropriate tables in appendix G. (These are in the current standards of the
National Fuel Gas Code ANSI Z223.1 in the USA, and
the appropriate Category 1 Natural Gas and Propane
appliances venting sizing tables in the current standards of the CSA B149 Natural Gas and Propane
Installation Codes in Canada.)
2 − When connecting the gas supply piping, consider fac-
tors such as length of run, number of fittings, and furnace rating to avoid excessive pressure drop. Table 9
lists recommended pipe sizes for typical applications.
3 − The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters,
or elevator shafts.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the fur-
Gas Piping
nace. The piping must be supported at proper intervals
[every 8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or straps. Install a drip leg inside vertical pipe runs
to the unit.
5 − In some localities, codes may require the installation of
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
a manual main shut-off valve and union (furnished by
the installer) external to the unit. The union must be of
the ground joint type.
shall be installed at the gas valve and extend outside
the furnace cabinet.
IMPORTANT
Compounds used on threaded joints of gas piping
WARNING
Do not exceed 600 in−lbs (50 ft−lbs) torque when attaching the gas piping to the gas valve.
Gas Supply
1 − This unit is shipped standard for left or right side instal-
lation of gas piping (or top entry in horizontal applications). Connect the gas supply to the piping assembly.
TABLE 9
Gas Pipe Capacity − ft3/hr (m3/hr)
Nominal
Iron Pi
Size
inches
(mm)
3/8
(9.53)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1−1/4
(31.75)
1−1/2
(38.1)
2
(50.8)
2−1/2
(63.5)
3
(76.2)
NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
must be resistant to the actions of liquified petroleum gases.
NOTE − Install a 1/8 inch NPT plugged tap in the field piping
upstream of the gas supply connection to the unit. The tap
must be accessible for test gauge connection. See figure 19.
NOTE − If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect main power to the furnace. The installer should properly label these devices.
Length of Pipe − feet (m)
40
(1.13)
73
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
100
(30.480)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
Page 20
Page 21
MANUAL
MAIN SHUT−OFF
VALV E
(With 1/8 in. NPT
Plugged Tap Shown)
GROUND
JOINT
UNION
Left Side Piping
(Standard)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
MANUAL
MAIN SHUT−OFF
VALV E
(With 1/8 in. NPT
Plugged Tap
Shown)
GROUND
JOINT
UNION
DRIP LEG
PROVIDED
DRIP LEG
AND INSTALLED
FIGURE 19
Leak Check
After gas piping is completed, carefully check all piping
connections (factory− and field−installed) for gas leaks. Use
a leak detecting solution or other preferred means.
NOTE − If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect the main power to the
furnace. The installer should properly label these devices.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures less
than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
FIELD
Right Side Piping
(Alternate)
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic
controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same
electrostatic potential. Neutralize electrostatic
charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
The unit is equipped with a field make−up box. The make−
up box may be moved to the right side of the furnace to facilitate installation. If the make−up box is moved to the right
side, the excess wire must be pulled into the blower
compartment. Secure the excess wire to the existing harness to protect it from damage.
IMPORTANT
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 20. Gas
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN
SHUT−OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
FIGURE 20
ISOLATE
GAS VALVE
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
Right Side
FURNACE
FIGURE 21
Page 21
Page 22
INTERIOR MAKE−UP BOX INSTALLATION
Left side
MAKE−UP
BOX
FIGURE 22
Refer to figure 24 for field wiring and figure 26 for schematic
wiring diagram and troubleshooting.
1 − Select circuit protection and wire size according to the
unit nameplate. The power supply wiring must meet
Class I restrictions.
2 − Holes are on both sides of the furnace cabinet to facili-
tate wiring.
3 − Install a separate disconnect switch (protected by ei-
ther fuse or circuit breaker) near the furnace so that
power can be turned off for servicing.
4 − Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for
servicing at a later date. Remove the blower access
panel to check the length of the wire.
5 − Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wiring diagram shown in figure 24. Use 18−gauge wire or
larger that is suitable for Class II rating for thermostat
connections.
6 − Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70) for the
USA and current Canadian Electric Code part 1 (CSA
standard C22.1) for Canada. A green ground wire is
provided in the field make−up box.
NOTE − The G40UH(X) furnace contains electronic
components that are polarity sensitive. Make sure
that the furnace is wired correctly and is properly
grounded.
7 − One line voltage EAC" accessory terminal is provided
on the furnace control board. Any electronic air cleaner
rated up to one amp can be connected to this terminal
with the neutral leg of the circuit being connected to the
any of the NEUTRAL" terminals. See figure 25 for control board configuration. This terminal is energized
whenever the blower is operating.
8 − One line voltage HUM" accessory terminal is provided
on the furnace control board. Any humidifier rated up
to one amp can be connected to this terminal with the
neutral leg of the circuit being connected to any of the
NEUTRAL" terminals. See figure 25 for control board
configuration. This terminal is energized in the heating
mode whenever the combustion air inducer is operating.
9 − Install the room thermostat according to the instruc-
tions provided with the thermostat. See figure 23 for
thermostat designations. If the furnace is being
matched with a heat pump, refer to the FM21 installation instruction.
G40UH(X) and CONDENSING UNIT
(Refer to specific thermostat and outdoor unit.)
Thermostat
R
W1
Y
G
C
THERMOSTAT DESIGNATIONS
G40UH(X)
Furnace
POWER
HEAT
COOLING
INDOOR BLOWER
COMMON
R
W
Y
G
C
Condensing
Unit
CONDENSING
UNIT
CONDENSING
UNIT COMMON
FIGURE 23
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously on the heating speed
when there is no cooling or heating demand.
2 − When the G40UH(X) is running in the heating mode,
the indoor blower will run on the heating speed.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed.
Page 22
Page 23
TYPICAL G40UH(X) FIELD WIRING DIAGRAM
BLOWER OFF
DELAY JUMPER
FIGURE 24
INTEGRATED CONTROL BOARD
(Automatic Hot Surface Ignition System)
TERMINAL DESIGNATIONS
HUM
LINE
XFMR
EAC
COOL
HEAT
PARK
FLAME
NEUTRALS
3 AMP, 32 VAC FUSE
Humidifier (120VAC)
Input (120VAC)
Transformer (120VAC)
Electronic Air Cleaner (120VAC)
Blower − Cooling Speed (120VAC)
Blower − Heating Speed (120VAC)
Dead terminals to park alternate spd taps
Flame senser
Neutral terminals (120VAC)
FIGURE 25
Page 23
Page 24
G40UH(X) Schematic Wiring Diagram
FIGURE 26
Page 24
Page 25
Unit Start−Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been underwater. Immediately call a qualified service technician to
inspect the furnace and to replace any part of the
control system and any gas control which has been
under water.
WARNING
If overheating occurs or if gas supply fails to shut off,
shut off the manual gas valve to the appliance before
shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 − Remove the upper access panel.
6 − Honeywell VR8205 Gas Valve with ON/OFF Switch
− Move gas valve switch to OFF. See figure 27.
Honeywell VR8205 Gas Valve with Control Knob −
Turn knob on gas valve clockwise to OFF. Do not
force. See figure 28.
White Rodgers 36G Gas Valve − Move gas valve
switch to OFF. See figure 29.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.
Honeywell VR8205 Series Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
(under cap)
(With On/Off Switch)
MANIFOLD
PRESSURE
OUTLET
BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
The gas valve on the G40UH(X) unit may be equipped with
either a gas control knob or gas control lever. Use only your
hand to push the lever or to turn the gas control knob. Never
use tools. If the knob will not turn or if the lever will not move
by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
G40UH(X) units are equipped with an automatic hot surface ignition system. Do not attempt to manually light
burners on these furnaces. Each time the thermostat calls
for heat, the burners will automatically light. The igniter
does not get hot when there is no call for heat on units with
this ignition system.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figures 27, 28 and 29)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
GAS VALVE ON/OFF SWITCH SHOWN IN OFF POSITION
FIGURE 27
Honeywell VR8205 Series Gas Valve
with Gas Control Knob
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
ON
OFF
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
OUTLET
FIGURE 28
White Rodgers 36G Series Gas Valve
OUTLET
PRESSURE
POST
INLET
PRESSURE
POST
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
(Under cover
screw)
FIGURE 29
Page 25
Page 26
8 − Honeywell VR8205 Gas Valve with ON/OFF Switch
Seconds for 1
− Move gas valve switch to ON. See figure 27.
Honeywell VR8205 Gas Valve with Control Knob −
Turn knob on gas valve counterclockwise to ON.
Do not force. See figure 28.
White Rodgers 36G Gas Valve − Move gas valve
switch to ON. See figure 29.
9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service technician or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the upper access panel.
4 − Honeywell VR8205 Gas Valve with ON/OFF Switch
− Move gas valve switch to OFF. See figure 27.
Honeywell VR8205 Gas Valve with Control Knob −
Turn knob on gas valve clockwise to OFF. Do not
force. See figure 28.
White Rodgers 36G Gas Valve − Move gas valve
switch to OFF. See figure 29.
5 − Replace the upper access panel.
Heating Sequence Of Operation
1 − When thermostat calls for heat, combustion air inducer
starts.
2 − Combustion air pressure switch proves blower opera-
tion. Switch is factory set and requires no adjustment.
3 − After a 15−second prepurge, the hot surface igniter en-
ergizes.
4 − After a 20−second igniter warm−up period, the gas
valve solenoid opens.
5 − Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6 − If flame is not detected after first ignition trial, the igni-
tion control will repeat steps 3 and 4 four more times
before locking out the gas valve (WATCHGUARD"
flame failure mode). The ignition control will then automatically repeat steps 1 through 6 after 60 minutes.
7 − To interrupt the 60−minute WATCHGUARD" period,
move thermostat from Heat" to OFF" then back to
Heat". Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
1 − Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for one revolutions of gas through the meter. A portable LP gas meter (17Y44) is available for LP applications.
2 − Compare the number of seconds and the gas meter
size in table 10 to determine the gas flow rate. Multiply
the gas flow rate by the heating value to determine the
unit input rate. If manifold pressure is correct and the
unit input rate is incorrect, check gas orifices for proper
size and restriction.
3 − Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas
appliances connected to meter.
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
Page 26
Page 27
Gas Pressure
1 − Check the gas line pressure with the unit firing at maxi-
mum rate. A minimum of 4.5 in. w.c. for natural gas or
11.0 in. w.c. for LP/propane gas should be maintained.
2 − After the line pressure has been checked and ad-
justed, check the manifold pressure. A natural gas to
LP/propane gas changeover kit is required to convert
the unit. Manifold pressure for all units is given in table
11. See figures 27, 28 and 29 for the location of the
manifold pressure adjustment screws.
High Altitude Information
NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.
The manifold pressure may require adjustment to ensure
proper operation at higher altitudes. See table 11 for proper
manifold pressure settings at varying altitudes.
TABLE 11
Manifold Pressure (Outlet) inches w.c.
Fuel
Nat.
Gas
L.P.
Gas
0−45004501−5500 5501−6500 6501−7500
3.53.33.23.1
10.010.010.010.0
NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. L.P. conversion kit 45L60 is used
with all units installed at altitudes up to 7,500 feet. L.P. conversion kit 47M81 is used with all units installed at altitudes
from 7,501 to 10,000 feet above sea level. Refer to the
changeover kit installation instruction for the conversion
procedure.
NOTE − Units fueled by natural gas and installed at altitudes of 7501−10,000 feet above sea level require installation of a high altitude orifice kit (47M82).
The combustion air pressure switches are factory−set and
require no adjustment. Table 12 lists the replacement pressure switch required for G40UH(X) units installed at altitudes above 4,500 feet above sea level.
The primary limit is located on the heating compartment
vestibule panel. The secondary limits (if equipped) are located in the blower compartment, attached to the back side
of the blower. These limits are factory set and require no
adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on (or inside of)
the burner box. If tripped, check for adequate combustion
air before resetting.
Pressure Switch
The pressure switch is located in the heating compartment
adjacent to the combustion air inducer. This switch checks
for proper combustion air inducer operation before allowing ignition trial. The switch is factory−set and requires no
adjustment.
Temperature Rise
Place the unit into operation with a heating demand. After
supply and return air temperatures have stabilized, check
the temperature rise. If necessary, adjust the blower speed
to maintain the temperature rise within the range shown on
the unit nameplate. Increase the blower speed to decrease
the temperature rise. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.
Fan Control
There is no cooling mode fan on delay; however, there is a
cooling fan off delay of 45 seconds. This delay is not adjustable.
The heating mode fan on delay of 45 seconds is not adjustable. The heating mode fan off delay (amount of time that
the blower operates after the heat demand has been satisfied) may be adjusted by changing the jumper position
across the five pins on the integrated control. The unit is
shipped with a factory fan off setting of 90 seconds. The fan
off delay affects comfort and is adjustable to satisfy individual applications. Adjust the fan off delay to achieve a supply
air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures. See figure 30.
FAN-OFF TIME ADJUSTMENT
To adjust fan−off timing, reposition jumper across pins to
achieve desired setting.
FIGURE 30
Page 27
Page 28
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the
air ducts or structure.
Blower Speeds
NOTE − CFM readings are taken external to unit with a dry
evaporator coil and without accessories.
1 − Turn off electrical power to furnace.
2 − Remove blower access panel.
3 − Disconnect existing speed tap at control board speed
terminal.
NOTE − Termination of any unused motor leads must be insulated.
4 − Refer to blower speed selection chart on unit wiring dia-
gram for desired heating or cooling speed.
5 − Connect selected speed tap at control board speed
terminal.
6 − Resecure blower access panel.
7 − Turn on electrical power to furnace.
Electronic Ignition
The integrated ignition control has an added feature of an
internal Watchguard control. The feature serves as an automatic reset device for ignition control lockout because the
burner has failed to ignite. This type of lockout is usually due
to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically
reset the control to begin the ignition sequence.
Flue And Chimney
1 − Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage.
2 − Check unit for proper draft.
3 − Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and outlet
for blockages.
4 − Reset manual flame rollout switches on burner box
cover.
Failure To Operate
If the unit fails to operate, check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse?
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 − Is the unit ignition system in lock out? If the unit locks out
again, call the service technician to inspect the unit for
blockages.
Service
WARNING
Disconnect power before servicing unit.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
At the beginning of each heating season, a qualified technician should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Filters
All G40UH(X) filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation.
Replacement filters must be rated for high velocity airflow.
Table 1 lists recommended filter sizes.
Flue And Chimney
Check the flue pipe, chimney and all connections for tightness and to make sure there is no blockage.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Cleaning the Heat Exchanger and Burners
NOTE − Use papers or protective covering in front of the furnace while you clean furnace.
Page 28
Page 29
Cleaning the heat exchanger requires a steel spring
snake," a reversible drill and a vacuum cleaner. The steel
spring snake may be constructed by purchasing a 4 ft. long
by 1/4 inch diameter steel wire cable and a 1/4 inch diameter wire brush. These items are available at a hardware
store. Insert wire end of brush into the open end of the
spring cable. Crimp the cable around the brush so that the
brush is secured and will not come off during cleaning. Attach the other end of the cable to the reversible drill to complete the tool for cleaning the heat exchanger.
1 − Turn off both electrical and gas power supplies to fur-
nace.
2 − Remove flue pipe and top cap from the unit. Label the
pressure switch wires, then disconnect them.
3 − Remove the four screws that secure the combustion air
inducer. Carefully remove the combustion air inducer to
avoid damaging blower gasket. If gasket is damaged, it
must be replaced to prevent leakage. See figure 31.
NOx INSERTS
(X models only)
NOx INSERTS
G40UH(X) BURNER & HEAT
EXCHANGER REMOVAL
HEAT EXCHANGER
BURNER BOX ASSEMBLY
FIGURE 31
4 − Remove the collector box located behind the combus-
tion air inducer. Be careful with the collector box gasket. If the gasket is damaged you must replace it to prevent leakage.
5 − Label the wires from gas valve and rollout switches,
then disconnect them.
6 − Disconnect gas supply piping. Remove four screws se-
curing the burner manifold assembly to the vestibule
panel and remove the assembly from the unit.
FIGURE 32
7 − NOx units only − remove the three screws that attach
the NOx insert to the corbel at the entrance to each
heat exchanger section. Carefully remove the NOx insert from each section. See figure 32.
8 − Insert the brush end of cable snake into the top of one
of the heat exchanger openings. Do not force thecable into the heat exchanger. Insert the cable and
operate the drill on slow speed. Move the cable in and
out of the heat exchanger section three or four times or
until sufficient cleaning is accomplished. Reverse drill
and slowly work the cable out of opening.
9− Repeat procedure for each heat exchanger section.
10− After each of the top heat exchanger sections has been
cleaned, insert the brush end of the cable snake into
the bottom openings of each of the heat exchanger
sections. Clean the bottom opening as described in
step 8.
11− Remove cable from heat exchanger. Use a vacuum
cleaner to remove debris knocked loose during clean-
ing from each heat exchanger section.
12− Attach the exhaust end (positive pressure) of the vacu-
um cleaner to the top of the heat exchanger section.
Any loose debris will be forced to the bottom of the heat
exchanger section. Vacuum debris from bottom open-
ings.
13− Replace collector box and combustion air inducer.
Check gaskets for damage. Damaged gaskets must be
replaced to avoid heat exchanger leaks. Replace all
screws to the collector box and combustion air inducer.
Failure to replace all screws may cause leaks.
Page 29
Page 30
14− To clean the burner, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually inspect inside the burners and crossovers for any blockage
caused by foreign matter. Remove any blockage.
15− NOx Units − Reattach the NOx inserts to the corbels
at the entrance to each heat exchanger opening. See
figure 32.
16− Replace burner/manifold assembly onto the vestibule
panel.
17− Reconnect wires to pressure switch, roll−out switches,
gas valve and combustion air inducer. Refer to unit wiring diagram.
18− Reconnect vent pipe to combustion air inducer outlet.
19− Reconnect gas supply piping.
20− Turn on power and gas supply to unit.
21− Set thermostat and check for proper operation.
22− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
23− If a leak is detected, shut gas and electricity off and
repair leak.
24− Repeat steps 23 and 24 until no leaks are detected.
25− Replace front access panel.
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model
number listed on the CSA nameplate −− Example: G40UH(X)−24A−045−1.
Cabinet Parts
Upper access panel
Blower panel
Top cap
Control Panel Parts
Transformer
Integrated ignition control board
Door interlock switch
Circuit breaker
Blower Parts
Blower wheel
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Heating Parts
Flame sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orifices
Pressure switch
Igniter
Primary limit control
Flame rollout switch
Secondary limit (not used on 24A−45−1)
Page 30
Page 31
Ignition Control Board Diagnostic Codes
y
DIAGNOSTIC CODES
Make sure to Identify LED’S Correctly.
Refer to figure NO TAG for control board layout.
LED #1 (Red)LED #2 (Green)DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASHON
OFFSLOW FLASH
ALTERNATING
SLOW FLASH
SLOW FLASHOFFFlame sensed without gas valve energized.