Lennox G32V3-75, G32V5-100, G32V5-125 Installation Instructions Manual

Page 1
INSTALLATION
2002 Lennox Industries Inc.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INSTRUCTIONS
G32V SERIES UNITS
GAS UNITS
504,564M 5/2002
Supersedes 504,468M
Table of Contents
G32V Unit Dimensions- inches (mm) 2. . . . . . . . . . . .
G32V Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . .
Safety Instructions 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation - Setting Equipment 5. . . . . . . . . . . . . . . .
Return Air Opening Guidelines 5. . . . . . . . . . . . . . . . .
Filter & Filter Assembly 6. . . . . . . . . . . . . . . . . . . . . . .
Duct System 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe & Fittings Specifications 7. . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 8. . . . . . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 9. . . . . . . . . . . . . . . . . . . .
Venting Practices 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board Settings 23. . . . . . . . . . . . .
Unit Start-Up 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 27. . . . . . . . . . . . . . .
Gas Pressure Adjustment 31. . . . . . . . . . . . . . . . . . . .
High Altitude Information 32. . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 32. . . . . . . . . . . . . . . . . . . . . .
Service 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 35. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Board Diagnostic Codes 35. . . . .
Troubleshooting 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start-Up & Performance Check List 42. . . . . . . . . . . .
Litho U.S.A.
Do not store or use gasoline or other flamĆ mable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
05/02
*2P0502*
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.Extinguish any open flames.Do not touch any electrical switch; do not use any
phone in your building.
Leave the building immediately.Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the
fire department.
Page 1
504,564M
*P504564M*
Page 2
G32V Unit Dimensions - inches (mm)
1 1/16
(41)
5/8
(16)
1 1/16
(41)
18 7/8
(479)
B
SUPPLY
AIR
OPENING
23 3/4 (603)
25 (635)
TOP VIEW
28 1/2
(724)
CONDENSATE
DRAIN
(Both Sides)
ELECTRICAL
INLETS
(Both Sides)
3 5/8
(92)
7 3/8 (187)
2
(51)
2 1/2 (64)
21 3/4
(552)
4 1/2 (114)
GAS PIPING
(Both Sides)
F
COMBUSTION
EXHAUST
AIR OUTLET
23
(584)
INLET
AIR INTAKE
46
(1168)
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
A
(Optional)
23 (584)
C
RETURN AIR
KNOCKOUT (Either Side)
1-15/16 (49)
23 (584)
Return Air
Knockout (Bottom)
4 (102)
4 (102)
G
5/8 (16)
H
E
AIR FLOW
D
Return Air
Knockout (Bottom)
FRONT VIEWSIDE VIEW
Model No.
G32V3-75 16-1/4 413 14-1/8 359 12 305 12 305 2-1/8 54 7-5/8 194 14 356 12-3/4 324 G32V5–100 21-1/4 540 19-1/8 486 18 457 18 457 1-5/8 41 10-1/8 257 20 508 18-3/4 476 G32V5–125 26-1/4 667 24-1/8 613 18 457 18 457 4-1/8 105 12-5/8 321 20 508 18-3/4 476
A B C D E F G H
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
Page 2
Page 3
G32V Parts Arrangement
FRESH AIR
INTAKE FITTING
BURNER BOX
ASSEMBLY
PATCH
PLATE
FLAME SIGHT
BURNER BOX
COVER
GLASS
TWOĆSTAGE
GAS VALVE AND
MANIFOLD
GLASS FIBER GASKET
LOW HEAT
DIFFERENTIAL
PRESSURE
SWITCH
HIGH HEAT
DIFFERENTIAL
PRESSURE
SWITCH
(-75 only)
WARM
HEADER
(COLLECTOR)
BOX
PATCH PLATE WITH
BARBED FITTING
AND FLAME
ROLL-OUT SWITCH
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
FLUE COLLAR
TRANSITION
TOP CAP
CABINET
FLUE
SUPPLY
AIR
BLOWER
BURNER ACCESS
PANEL
BLOWER
ACCESS
DOOR
TWO-SPEED
COMBUSTION AIR
INDUCER
COMBUSTION
AIR
ORIFICE
COLD HEADER
(COLLECTOR)
BOX
SECONDARY COIL
PRIMARY LIMIT
(ALTERNATE STYLES)
TRANSFORMER
CONTROL VOLTAGE
CIRCUIT BREAKER
SURELIGHT TWO-STAGE,
VARIABLE-SPEED
INTEGRATED CONTROL BOARD
DOOR INTERLOCK SWITCH
FIGURE 1
Page 3
Page 4
Safety Instructions
To combustible
Lennox G32V units are Category IV CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
In the USA, installation of Lennox gas central furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the curĆ rent National Fuel Gas Code (ANSI-Z223.1/NFPA 54) in the United States. The National Fuel Gas Code is availĆ able from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current NationĆ al Standard of Canada CAN/CGAĆB149.1 Installation Code for Natural Gas Burning Appliances and EquipĆ ment" and CAN/CGA-B149.2 Installation Code for ProĆ pane Gas Burning Appliances and Equipment," local plumbing or waste water codes and other applicable local codes.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit rating plate and in table 1.
TABLE 1
Clearances Location Inches (mm)
Front 24 (610)
Service access
To combustible
materials
Condensate side
To p 1 (25)
Exhaust 0
Side, rear, and front 0
3 (76)
(from side of unit)
When the furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cool­ing units to avoid condensation in the heating compartĆ ment. With a parallel flow arrangement, a damper (or othĆ er means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the dampĆ er is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT" or COOL" setting.
When installed, the furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National ElecĆ tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following adĆ dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
Field wiring connections must meet or exceed specificaĆ tions of type T wire and withstand a maximum temperaĆ ture rise of 180°F (82°C).
G32V unit must be installed so that electrical components are protected from water. When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside of the space containing the furnace, return air shall be handled by a duct(s) sealed to the furnace casing and terminating outĆ side space containing furnace.
Floor 0
NOTE - For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
Accessibility and service clearances must take preceĆ dence over fire protection clearances.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed acĆ cording to recommended good practice requirements and current National Fuel Gas Code or CAN/CGA B149.1 and B149.2 standards.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379-9900
Page 4
Page 5
NOTE - G32V series units must not be used as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and misĆ placement of the filters will damage the unit and lower its efficiency.
The G32V furnace may be installed in alcoves, closĆ ets, attics, basements, garages and utility rooms in the upflow position.
General
The G32V is an upflow gas furnace which is factory­equipped for use with natural gas. A changeover kit is
necessary if the furnace is to be used with L.P. gas. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Shipping and Packing List
1 - Assembled G32V furnace
1 - 3 inch x 2 inch vent transition piece (-100, -125
units only)
1 - Bag assembly containing:
1 - Filter 1 - External filter rack for side return air application
1 - Bag assembly containing:
1 - Electrical make-up box with cover and grounding screw 4 - Thread-forming make-up box screws 1 - Green ground wire 1 - Wiring harness 1 - Snap bushing 2 - Filter clips 1 - Condensate drain pipe adapter 1 - Condensate plug 4 - Wire nuts 2 - Lockwashers and screws 8 - Self-tapping screws 2 - Filter door pins 1 - Grounding label 1 - Wire tie
Shipping Damage
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, serĆ vice or maintenance can cause property damage, personal injury or loss of life. Installation and serĆ vice must be performed by a qualified installer, serĆ vice agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injuĆ ry can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Installation - Setting Equipment
Select a location that allows for required clearances listed on the unit rating plate. Also consider gas supply connecĆ tions, electrical supply, vent connection and installation and service clearances [24 inches (610 mm) at unit front]. The furnace must be level.
CAUTION
G32V unit should not be installed in areas normally subject to freezing temperatures.
Return Air Opening Guidelines
WARNING
Improper installation of unit can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air sysĆ tem or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the furnace should be sealed airtight to the return air plenu m . A doo r mu s t never be us e d as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct systems ever be connected to or from other heat­in g devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inĆ jury or death.
Return air can be brought in either side or at the bottom of the unit. Scribe lines show the outline of each side and the bottom return air opening.
Page 5
Page 6
Bottom Return Air Applications
If return air is to terminate through the floor under the furĆ nace, a direct, airtight and sealed connection must be made to the bottom of the furnace.
1 - Cut opening in floor or platform. Using knockouts
provided, cut bottom of base panel. See figure 2.
KNOCKOUT PATTERN FOR BOTTOM
RETURN AIR APPLICATION
FIGURE 2
BOTTOM RETURN AIR APPLICATION
FILTER SIZE REQUIREMENTS
TABLE 2
UNIT MODEL
NUMBER
G32V-75 31J81
G32V-100 G32V-125
FILTER PART
NUMBER
P-8-7831
FILTER SIZE
14 inches x 25 inches
(356 x 635 mm)
20 inches x 25 inches
(508 x 635 mm)
Bottom Return Air Applications
1 - Remove blower access panel.
2 - Install filter clips, provided with unit, by slipping
folded section of clip on edge of bottom opening. See figure 4.
BOTTOM RETURN FILTER INSTALLATION
REAR FILTER CLIP
FURNACE
SIDE FILTER CLIPS (2)
RETURN AIR OPENING
BACK
G32V UNIT
RETURN AIR
PLENUM
PROPERLY
SIZED FLOOR
OPENING
FIGURE 3
2 - Bend a flange on return air plenum and lower into
floor or platform opening. See figure 3.
3 - Position unit over return air opening. Seal unit air
tight with return air plenum.
NOTE - Be careful not to damage insulation. Check for tight seal.
Side Return Air Applications
For installations where the return air is taken from a return air drop, unit may be installed using either the left or right side of furnace.
For side return air applications, cut the furnace cabinet at the dimensions given in the unit dimensions graphic. EmĆ bossed corners are pro-vided on both cabinet sides for reĆ turn air opening location.
FURNACE
FRONT
FURNACE
BASE BOTTOM
FIGURE 4
3 - Place filter in bottom of blower compartment beneath
rear filter clip. Press down on filter sides. Filter clips flex allowing filter to snap into place.
4 - To remove filter, press clip and pull filter up and out.
Side Return Air Applications
1 - Align filter rack opening with the inside edge of the
side return opening. Bottom of rack should be approximately 1 inch (25 mm) from the bottom and 3 inches (76 mm) from the front of the unit.
2 - Screw filter rack into place with the eight self drill, self
tap screws provided. See figure 5.
3 - Push filter door pins through the two holes in filter
door from the inside of the uĆchannel. See figure 6.
SIDE RETURN FILTER INSTALLATION
in. (mm)
BLOWER DECK
RETURN AIR
RETURN
AIR
OPENING
12 in. (305) for
14 in. (356) Filter
18 in. (457) for
20 in. (508) Filter
PLENUM SIZE
12-3/4 in X 23-1/2 in (324 X
597) for 14 in (356) Filter 18-3/4 in. x 23-1/2 in.
(476 x 597)
for 20 in. (508) Filter
Filter & Filter Assembly
A filter and an external filter rack for use in side return air applications are shipped with the unit. A filter must be in place anytime the unit is in operation.
Page 6
1-15/16 in.
(49)
CABINET BASE BOTTOM
FIGURE 5
15/16 in
(24)
Page 7
4 - Position filter door on end of filter so that the thumb
tab side of the filter door is away from the furnace. Squeeze thumb tabs to secure filter to door.
5 - Guide filter and filter door into the filter rack installed
on side of furnace. Push door into filter rack until se­cure.
6 - To remove filter, pull filter door pins until door is re-
leased from filter rack.
FILTER DOOR ASSEMBLY
FILTER DOOR
PIN
FILTER DOOR
TAB
FILTER
NO TE - For bot to m re tu r n air, ret ur n ai r du ct should be seĆ cured to the unit using rivets or S-locks. For side return air, secure return air duct to filter rack using screws. When using screws, take care to avoid interference with the filĆ ter which may cause improper filtration.
The ret urn ai r mu s t no t be draw n fro m a room where another gas appliance (ie., a water heater) is installed. Even though this furnace draws its combusĆ
tion air from outside of the structure, other gas apĆ pliances that share a utility room may not. When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed through the house by the furnace duct system.
FILTER DOOR
PIN
TAB
FIGURE 6
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution. If the G32V unit is being installed as a replacement for an existing furnace, the existing supply and return air duct system should be evaluated to make sure that it is approĆ priately sized.
The total external static pressure (ESP) should not exĆ ceed 0.8" w.c. The ESP calculation should include presĆ sure losses caused by electronic air cleaners, filters, cooling coils, the duct system, registers and grilles. A properly sized duct system will help to optimize efficiency and reliability and to minimize sound levels. Operation of a G32V unit outside of its specified static pressure range will result in poor performance and will reduce the useful life-expectancy of the product and its components.
Supply Air Plenum
Furnaces installed without a cooling coil require the installaĆ tion of a removable access panel in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reflected light) of the heat exchanger for leaks after installation. The furnace access panel must alĆ ways be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
See dimension illustration for proper return air duct size.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the AmeriĆ can Society for Testing and Materials (ANSI/ASTM) stanĆ dards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifiĆ cation, or separation that cannot be removed by stirring. Refer to table 3 for approved piping and fitting materials.
Primers and solvents must meet ASTM specifications. PVC primer is specified in ASTM F 656. Use PVC solvent cement as specified in ASTM D 2564 and ABS solvent cement as specified in ASTM D 2235. Low temperature solvent cement is recommended. Metal or plastic strapĆ ping may be used for vent pipe hangers.
Table 4 lists the available exhaust termination kits. All Lennox vent terminations are PVC.
TABLE 3
PIPING AND FITTINGS SPECIFICATIONS
PIPE & FITTING MATERIAL
Schedule 40 PVC (Pipe) D1785
Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR-21 PVC (Pipe) or SDR-26 PVC (Pipe) D2241
SDR-21 CPVC (Pipe) or SDR-26 CPVC (Pipe) F442
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS-DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC-DWV (Drain Waste & Vent ­Pipe & Fittings)
ASTM
SPECIFICATION
D2661
D2665
Page 7
Page 8
TABLE 4
TERMINATION KITS
Lennox Part
No.
60G77 LB-49107CE
33K97 LB-87942
15F75 LB-49107CC
22G44 LB-49107CD
15F74 LB-49107CB 2" (50.8) Wall Ring Kit
44J41 LB-65678A
44J40 LB-65701A
30G28 WTK
30G79 WTKX
Kit LB# Description-Inches (mm)
1-1/2" (50.8) Concentric
Termination Kit
3" (50.8) Low Pressure Drop ConĆ
centric Term. Kit
2" (50.8) Roof
Termination Kit
2" (50.8) Wall
Assembly Termination Kit
3" (76.2) Roof Termination Kit
3" (76.2) Wall
Assembly Termination Kit
2" (50.8) Wall
Termination Extended Vent
2" (50.8) Wall
Termination Extension Riser
CAUTION
Solvent cements for plastic pipe are flammable liqĆ uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid conĆ tact of cement with skin and eyes.
When making ABS joints, pieces can be prepared with a cleaner. When joining ABS to PVC materials, use PVC solvent cement. Refer to this procedure as specified in ASTM D3138.
Vent Piping Guidelines
Pipe used for exhaust and intake lines should be sized acĆ cording to table 5. Note that maximum length of vent pipe is for one run; either intake or exhaust. Maximum vent length given is not the total length of intake plus exhaust vents.
Each 90° elbow is equivalent to 5 feet (1.52 m) of vent
pipe. Two 45° elbows are equivalent to one 90° elbow. One 45° elbow is equal to 2.5 feet (.76 m) of vent pipe. If intake and exhaust piping runs are not equal in length and number of elbows, the larger diameter pipe must be used for both runs.
TABLE 5
VENT PIPE SIZING TABLE FOR G32V FURNACES
MINIMUM DIAMETER OF INTAKE/EXHAUST PIPE
Vent Pipe
Equivalent Length
Max. Feet (Meters)
15 (4.57) 2" 2" 2" 20 (6.10) 2" 2" 3"
25 (7.62) 2" 2" 3"
30 (9.14) 2" 3" 3"
40 (12.19) 2" 3" 3"
50 (15.24) 2" 3" 3"
55 (16.76) 2" 3" 3"
60 (18.29) 3" 3" 3"
70 (21.34) 3" 3" 3"
80 (24.38) 3" 3" 3"
90 (27.43) 3" 3" 3"
100 (30.48) 3" 3" 3"
110 (33.53) 3" 3" 3"
120 (36.58) 3" 3" 3"
130 (39.62) 3" 3" --
NOTE - Minimum vent pipe for G32V-75, G32V-100, and G32V-125 is 5 feet with 2 elbows of 2-inch diameter pipe.
G32V-75
75,000
BTU
G32V-100
100,000
BTU
G32V-125
125,000
BTU
NOTE - When you install a WTKX termination kit as part of the intake and exhaust piping, the two 2-inch diameter 90° elbows and the 27 inch pipe (in the kit) should be inĆ cluded in the maximum vent pipe length for each run.
For 75 kBtuh units, connections are provided for 2-inch
diameter vent pipe which should satisfy most venting reĆ quirements. No transition pieces are provided or needed for use with 2-inch vent pipe.
For -100 and -125 kBtuh units, the intake connection is sized for 3-inch diameter pipe. The exhaust connection ha s a 2- inc h ni pp le . A pipe transition piece is shipped with the unit for use with 3-inch pipe. See figure 7 for 2-inch and 3-inch vent pipe applications. Most venting applications will require 3-inch vent pipe for proper unit operation. The intake and exhaust pipe
must never be constructed of different diameter pipes. Regardless of the diameter of pipe used, the stanĆ
dard roof and wall terminations described in section InĆ take and Exhaust Piping Terminations should be used.
Exhaust piping must terminate with 1-1/2 inch pipe for 1-1/2 inch or 2 inch vents and 2-inch vent pipe for 3-inch vents.
Page 8
Page 9
G32V-100 OR -125 WITH 2 IN. VENTING
2 IN. VENT PIPE
2 IN. OUT
3 IN. X 2 IN.
REDUCER
3 IN.
IN
G32V-100 OR -125 WITH 3 IN. VENTING
3 IN. X 2 IN. REDUCER
2 IN. FIELD PROVIDED
NIPPLE
2 IN. OUT
3 IN.
IN
3 IN. FIELD PROVIDED
NIPPLE
3 IN. VENT PIPE
into socket until it bottoms out. Turn pipe 1/4 turn durĆ ing assembly (but not after pipe is fully inserted) to distribute cement evenly.
NOTE - Assembly should be completed within 20 seĆ conds after last application of cement. Hammer blows should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at
end of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indiĆ cate a defective assembly due to insufficient sol­vent.
9 - Handle joints carefully until completely set.
Venting Practices
FIGURE 7
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
WARNING
DANGER OF EXPLOSION! Fumes from PVC glue may ignite during system check. Disconnect wire from pressure switch terminal before 115 volt powĆ er is applied to unit. Reconnect wire after two minĆ utes of combustion air blower operation.
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 - Clean and dry surfaces to be joined.
4 - Test fit joint and mark depth of fitting on outside of
pipe.
5 - Uniformly apply liberal coat of PVC primer for PVC or
ABS cleaner for ABS to inside socket surface of fitĆ ting and male end of pipe to depth of fitting socket.
6 - Promptly apply solvent cement to end of pipe and inĆ
side socket surface of fitting. Cement should be apĆ plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.
NOTE - Time is critical at this stage. Do not allow primer to dry before applying cement.
7 - Immediately after applying last coat of cement to
pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following subĆ stances in the combustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
The thickness of construction through which vent/air inĆ take pipes may be installed is a minimum of 3 inches (76 mm) and a maximum of 24 inches (610 mm). If a G32V furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
Intake Piping
1 - Cement intake piping in slip connector located at top
of unit.
2 - Route piping to outside of structure. Continue with
installation following instructions given in exhaust and intake piping termination section.
Page 9
Page 10
Exhaust Piping
1 - Cement exhaust piping into flue collar socket located
on the left side of the top cap.
2 - All horizontal runs of exhaust pipe must slope back
toward the unit. A minimum of 1/4 inch (6 mm) drop for each 12 inches (305 mm) of horizontal run is manĆ datory for drainage. Horizontal runs of exhaust pipĆ ing must be supported every 5 feet (1.52 m) using hangers.
NOTE - Exhaust piping should be checked carefully to make sure there are no sags or low spots.
NOTE - Exhaust piping must be insulated with 1/2 inch (13 mm) Armaflex or equivalent when run through unheated space. Do not leave any area of exhaust pipe open to outside air; exterior exhaust must be insulated with 1/2 inch (13 mm) Armaflex or equivalent.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verĆ tical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pressure and must be completely sealed to pre­vent leakage of combustion products into the livĆ ing space.
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting system commonly run with separate gas apĆ pliances, the venting system may be too large to properly vent the remaining attached appliances. The following test should be conducted while all appliances (both in opĆ eration and those not in operation) are connected to the common venting system. If the venting system has been installed improperly, corrections must be made as outĆ lined in the previous section.
1 - Seal any unused openings in the common venting
system.
2 - Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockĆ age or restriction, leakage, corrosion or other defiĆ ciencies which could cause an unsafe condition.
3 - Close all building doors and windows, and all doors
between the space in which the appliances remainĆ
ing connected to the common venting system are loĆ cated and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operĆ ate a summer exhaust fan. Close fireplace dampers.
4 - Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so appliance will operate continuously.
5 - Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of match or candle, or smoke from a cigarette or cigar, or a draft gauge.
6 - After determining that each appliance remaining
connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gasĆburning appliance to their preĆ vious condition of use.
7 - If improper venting is observed during any of the
above tests, the common venting system must be corrected. The common venting system should be resized to approach the minimum size as deterĆ mined by using the appropriate tables in appendix G in the current standards of the National Fuel Gas Code ANSI Z223-1 in the USA, and the appropriate Category 1 Natural Gas appliances venting sizing tables in the current standard of the CAN/ CGA-B149.1 in the Natural Gas Installation Code in Canada.
Intake and Exhaust Piping Terminations
Intake and exhaust pipes may be routed either horizontalĆ ly through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 8 through 20 show typical terminations.
1 - Use recommended piping materials for both intake
and exhaust piping.
2 - Secure all joints, including drain leg, gas-tight using
approved cement.
3 - Piping diameters should be determined according
to length of pipe run. See table 5. Locate intake pipĆ ing upwind (prevailing wind) from exhaust piping. To avoid recirculation of exhaust gas on roof terĆ minations, end of exhaust pipe must be higher than intake pipe.
Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.
Page 10
Page 11
4 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to ilĆ lustrations). Maximum separation is 3 inches (76 mm) on roof terminations and 6 inches (152 mm) on side wall terminations.
5 - Exhaust piping must terminate straight out or up as
shown. In rooftop applications, a 2 inch X 1-1/2 inch reducer for 2 inch venting, 3 inch x 2 inch reducer for 3 inch venting must be used on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping.
On roof terminations, the intake piping should termiĆ
nate straight down using two 90° elbows. See figure 8.
Inches (mm)
8 (203) MIN
12 (305) ABOVE AVERAGE SNOW ACCUMULATION
3 (76) MAX.
3 x 2 (76 x 51) OR
2 x 1-1/2 (51 x 38)
PVC REDUCER
1/2 (13) FOAM
INSULATION IN
UNCONDITIONED
SPACE
NOTE - During extremely cold temperatures, below approximately 20°F (6.67°C), units with long runs of vent pipe through unconditioned space, even when inĆ sulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviat e mos t icing probĆ lems. Also, a heatin g cable may be installed on exhaust piping and termination to prevent freezeĆups. Heating cable installation kit is available from Lennox. See ConĆ densate Piping section for part numbers.
NOTE - Avoid recirculation of exhaust back into the inĆ take pipe.
6 - On field-supplied terminations for side wall exits, exĆ
haust piping should extend a maximum of 12 inches (305 mm) beyond the outside wall. Intake piping should be as short as possible. See figure 9.
1/2 (13) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
2 (51) PVC 1-1/2 (38) PVC
12 (305) MIN.
2 X 1-1/2
(51 x 38)
PVC REDUCER
3 (76) OR
2 (51) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
ROOF TERMINATION KIT
(15F75) LB-49107CC for 2 (51) Venting
(44J41) LB-65678A for 3 (76) Venting
UNCONDITIONED
ATTIC SPACE
FIGURE 8
IMPORTANT
Do not use screens or perforated metal in intake and exhaust terminations. Doing so will cause freeze-ups and may block the terminations.
NOTE - If winter design temperature is below 32°F (0°C), exhaust piping must be insulated with 1/2 inch (13 mm), Armaflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to outside air; exterior exhaust pipe must be insuĆ lated with 1/2 inch (13 mm) Armaflex or equivalent. In exĆ treme cold climate areas, 3/4 inch (19 mm) Armaflex or equivalent is recommended. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect inĆ sulation from deterioration.
1/2 (13) ARMAFLEX
Inches (mm)
INSULATION
OUTSIDE
WALL
TOP VIEW
(15J74) LB-49107CB for 2 (50.8) Venting
WALL RING KIT
6 (152)
MAXIMUM
8 (203)
MINIMUM
2 (51) PVC
COUPLING
FIGURE 9
7 - On field-supplied terminations, a minimum separaĆ
tion distance between the end of the exhaust pipe and the end of the intake pipe is 8 inches (203 mm).
8 - If intake and exhaust piping must be run up a side
wall to position above snow accumulation or other obstructions, the piping must be supported every 3 fee t (.91 m) as shown in figure 14. Refer to figures 13 and 15 for proper piping method. WTK wall terminaĆ tion kit must be extended for use in this application. See figure 18 or use kit WTKX shown in figure 19. When exhaust and intake piping must be run up an outside wall, the exhaust piping is reduced to 1 1/2 inches (38 mm) after the final elbow. The intake pipĆ ing may be equ i p ped wit h a 90° elbow turndown. UsĆ in g tu rn- do wn wi ll ad d 5 fe et (1 . 5 m) to th e eq ui va len t length of the pipe.
Page 11
Page 12
1/2 (12.7) FOAM INSULATION
IN UNCONDITIONED SPACE
Inches (mm)
OUTSIDE WALL
Inches(mm)
UNCONDITIONED
SPACE
OUTSIDE WALL
12 (305) MIN. for 2 (51)
20 (508) MAX. for 3 (76)
8 (203)
MIN.
EXHAUST
INTAKE
PIPE
PIPE
Optional Turndown
TOP VIEW
WALL TERMINATION
(22G44) LB-49107CD for 2 (50.8) Venting
(44J40) LB-65701A for 3 (76.2) Venting
(Intake Only)
FIGURE 10
EXHAUST
TERMINATION
INTAKE
TERMINATION
EXHAUST
CONCENTRIC ROOFTOP TERMINATION
(60G77) LB-49107CE for G32V-75 Units Only
(33K97) LB-87942 for G32V-100 & -125 Units Only
12 (305) ABOVE AVERAGE SNOW ACCUMULATION
INTAKE
Inches (mm)
FIGURE 11
OUTSIDE WALL
EXHAUST
INTAKE
Inches (mm)
CONCENTRIC WALL TERMINATION
(60G77) LB-49107CE for G32V-75 Units Only
(33K97) LB-87942 for G32V-100 & -125 Units Only
EXHAUST
TERMINATION
INTAKE
TERMINATION
12 (305) Min.
above grade.
Shown
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES EVERY
36 (914)
1/2 (13) FOAM
INSULATION IN
UNCONDITIONED
SPACE
WALL RING TERMINATION
(15F74) LB-49107CB for 2 in. (51) Venting
See venting table 5 for maximum venting lengths with
SIDE VIEW
this arrangement.
12 (305) ABOVE AVERAGE SNOW ACCUMULATION
1/2 (13) FOAM
INSULATION
FIGURE 13
9 - Position termination ends so they are free from any
obstructions and above the level of snow accumulaĆ tion (where applicable). Termination ends must be a minimum of 12 inches (305 mm) above grade level. Do not point into window wells, stairwells, alcoves, courtyard areas or other recessed areas. Do not position termination ends directly below roof eaves or above a walkway. Since the G32V is a certified diĆ rect vent, Category IV gas furnace, the location of the termination is limited by local building codes. In the absence of local codes, refer to the current NaĆ tional Fuel Gas Code ANSI Z223-1 in USA, and curĆ rent standard CAN/CGA-B149.1 of the Natural Gas Installation Instructions in Canada for details. The termination should be at least 12 inches (305 mm) from any opening through which flue products could enter the building.
When horizontally vented, minimum clearance for termination from electric meters, gas meters, regulaĆ tors and relief equipment is 4 feet (1.2 m) for US installations. Refer to the current CAN/CGA-B149.1 for installations in Canada or with authorities having local jurisdiction.
FIGURE 12
Page 12
Page 13
At vent termination, care must be taken to maintain protective coatings over building materials (proĆ longed exposure to exhaust condensate can destroy protective coatings). It is recommended that the exĆ haust outlet not be located within 6 feet (1.8 m) of a condensing unit because the condensate can damĆ age the painted coating.
METAL OR PLASTIC
STRAPPING
OR LARGE WIRE TIES
FIGURE 14
IMPORTANT
Combustion air intake inlet and exhaust outlet should not be located within 6 feet (1.8 m) of dryer vent or combustion air inlet or outlet of another apĆ pliance. Piping should not exit less than 3 feet (.91 m) from opening into another building.
IMPORTANT
For Canadian Installations Only: In accordance to CAN/CGA-B149.1 and .2, the miniĆ mum allowed distance between the combustion air intake inlet and the exhaust outlet of other apĆ pliances shall not be less than 12 inches (305 mm).
10 - Suspend piping using hangers at a minimum of every
5 feet (1.52 m) for schedule 40 PVC and every 3 feet (.91 m) for ABS-DWV, PVC-DWV, SDR-21 PVC, and SDRĆ26 PVC piping. A suitable hanger can be fabricated by using metal or plastic strapping or a large wire tie.
11 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe as it passes through the center of the hole.
12 - Isolate piping at the point where it exits the outside
wall or roof.
13 - When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conĆ densate collection trap and lines.
14 - Based on the recommendation of the manufacturer,
a multiple furnace installation may use a group of up to four termination kits WTK assembled together horizontally, as shown in figure 17.
Inches(mm)
3 (76) OR
2 (51) 90_ ELBOW
Optional Turndown
(Not Shown)
May Be Used on
Intake Only
(22G44) LB-49107CD for 2(51) Venting
(44J40) LB-65701A for 3(76) Venting
Front View
INTAKE
VENT
1/2 (13) Foam
Insulation in
Unconditioned Space
Inches (mm)
WALL TERMINATION KIT (30G28) WTK
1/2 (13)
FOAM
INSULATION
FRONT VIEW
WALL TERMINATION
FIGURE 15
12
(305)
VENT TERMINATIONS
FIGURE 16
3 x 2 (76 x 51) OR 2 x 1-1/2 (51 x 38)
REDUCER BUSHING LOCAĆ
FOR OFFSET TERMINATION
TION
3 (76) OR
2 (51) 90_ ELBOW
EXHAUST VENT
5
(127)
Side View
EXHAUST VENT
INTAKE VENT
OUTSIDE WALL
Page 13
Page 14
Front View
INTAKE VENT
EXHAUST
VENT
18 MAX.
(457)
5
(127)
5-1/2 (140)
12
(305)
Inches (mm)
Front View
34
(864)
9
(229)
INTAKE
VENT
EXHAUST
VENT
NOTE - Enclosed exhaust pipe is insulated with 1/2 inch (13 mm) foam insulation. If intake and exĆ haust pipes are reversed, slit and remove foam insulation and reapply to other vent. Exhaust vent must be insulated.
Side View
EXHAUST VENT
Inches (mm)
OPTIONAL VENT TERMINATION FOR
MULTIPLE UNIT INSTALLATION
WALL TERMINATION KIT WTK
FIGURE 17
AIR
12
(305)
5Ć1/2 (140)
Minimum
8 (203)
Front View
INTAKE
AIR
5
(127)
EXHAUST
INTAKE
AIR
MODEL WTK WALL TERMINATION KIT (30G28)
EXTENDED VENT FOR GRADE CLEARANCE
VENT TERMINATIONS
FIGURE 18
INTAKE
VENT
COVER EXHAUST
VENT WITH
1/2 (13)
FOAM
INSULATION
EXHAUST
AIR
12 MIN.
(305)
Above Grade
GRADE
Side View
Inches (mm)
12 (305)
Minimum
ABOVE GRADE
GRADE
Side View
4
(102)
12
(305)
GRADE
EXHAUST VENT
8 MIN.
(203)
INTAKE
VENT
OUTSIDE WALL
GRADE
VENT TERMINATIONS
MODEL WTKX (30G79)
EXTENSION RISER FOR GRADE CLEARANCE
FIGURE 19
G32 VENTING IN EXISTING CHIMNEY
3 in. - 8 in.
8 in. - 12 in.
(203 mm - 305 mm)
INTAKE VENT
INSULATION
(OPTIONAL)
TOP PLATE
(18 GA. MIN.)
MIN. 12" (304 mm)
ABOVE ROOF
INSULATE
TO FORM
SEAL
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
(76 mm­203 mm)
STRAIGHT CUT OR
ANGLE CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13 mm)
WEATHERPROOF
INSULATION
SHOULDERS OF FITTINGS
PROVIDE SUPPORT FOR
PIPE ON TOP PLATE
ALTERNATE
3 in. - 8 in.
(76 mm­203 mm)
INTAKE VENT
EXTERIOR
PORTION
OF CHIMNEY
FIGURE 20
Page 14
Page 15
Condensate Piping
This unit is designed for either right- or left-side exit of condensate piping. Route the condensate drainline only within the conditioned space: this prevents possible freezing of the condensate, which would block the drain­line. Use an electric heat cable if you route the conden­sate line through unconditioned areas.
CAUTION
Do not use copper tubing or existing copper conĆ densate lines for drain line.
1 - Determine which side of the unit that the condensate
will exit.
2 - Connect 1/2" (13 mm) plastic pipe plug (provided) in
the unused end of the condensate trap. Install plug so that it is sealed water tight yet able to be removed. Do not permanently seal the connection. Teflon tape is recommended to seal joint. See figure 21.
CONDENSATE ASSEMBLY
(For left or right installation)
COLD
COMBUSTION AIR
BLOWER BRACKET
HEADER
BOX
Right-Hand Side Condensate Exit:
Install the nipple/adapter assembly from the outĆ side of the cabinet and insert the adapter into the threaded opening in the condensate trap.
Left-Hand Side Condensate Exit:
Insert nipple/adapter assembly from the left-hand side of the cabinet and through the combustion air blower mounting structure into the threaded opening in the condensate trap.
5 - Connect field-supplied plumbing to nipple and route
to open drain. Plumbing should be vented to a point higher than the condensing coil. See figure 22.
CONDENSATE PLUMBING
(Plumbing must be vented higher than coil.)
NIPPLE
ADAPTER
ELBOW
CONDENSATE TRAP
NIPPLE
ADAPTER
PLUG
BOOT OR CAP
FIGURE 21
3 - Use the provided adapter (1/2" mpt X 3/4" PVC) and
a field-provided nipple to carry drainage outside the cabinet. A 1/2" CPVC x 1/2" MPT adapter and 1/2" CPVC is acceptable for use.
4 - Glue nipple to the adapter using the procedures out-
lined in the Joint Cementing Procedures" section. The nipple/adapter assembly should be connected in a non-permanent manner and must be water tight. Teflon tape is recommended to seal the joint.
FIGURE 22
6 - Connect condensate drain line [1/2" (13 mm) SDR 11
plastic pipe or tubing] to condensate connection on condensate trap assembly and route to open drain. Condensate line must be sloped downward away from condensate trap to the drain. If drain level is above condensate outlet, use a condensate pump to pump condensate to the higher level. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and condenĆ sate line. Heating cable kit is available from Lennox in various lengths; 6 feet (1.8 m) - kit no. 26K68; 24 feet (7.3 m) - kit no. 26K99; and 50 feet (15.2 m) - kit no. 26K70. Also available from Lennox: 1/2" (12.7 mm) glass fiber tape - 39G04; 2" (50.8 mm) plum foil tape - 39G03.
Page 15
Page 16
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outĆ side the furnace cabinet.
1 - Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into the gas valve from the bottom of the valve as shown in figure 23.
2 - When connecting the gas supply, factors such as
length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 6 lists recommended pipe sizes for typiĆ cal applications.
NOTE - Use two wrenches when connecting gas pipĆ ing to avoid transferring torque to the manifold.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waitĆ ers, or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. When left-hand gas plumbing is required, gas line should be installed in the lower half of knockout so that pip­ing will clear combustion air blower. See figure 23.
LEFT SIDE PIPING
4 – The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the furĆ nace. The piping must be supported at proper interĆ vals [every 8 to 10 feet (2.44 to 3.01 m)] using suitĆ able hangers or straps. A drip leg should be installed in vertical pipe runs to the unit.
5 - In some localities, codes may require installation of a
manual main shutĆoff valve and union (furnished by the installer) external to the unit. Union must be of the ground joint type.
NOTE - Install a 1/8 inch NPT plugged tap in the field pipĆ ing upstream of the gas supply connection to the unit. The tap must be accessible for test gauge connection. See figure 24.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8 in. (3.2 mm) NPT
PLUGGED TAP
CAP
FURNACE
ISOLATE
GAS VALVE
FIGURE 24
Leak Check
After gas piping is completed, carefully check all piping connections (factory- and field-installed) for gas leaks. Use a leak detecting solution or other preferred means.
MANUAL MAIN
SHUT-OFF
VALV E
1/8 in. NPT PLUGGED
TAP
GAS VALVE
GAS VALVE
RIGHT SIDE PIPING
(STANDARD)
FIGURE 23
MANUAL MAIN
SHUT-OFF
VALV E
1/8 in. NPT PLUGGED
TAP
IMPORTANT
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, flame, or other sources of igniĆ tion to check for gas leaks.
IMPORTANT
The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.45 kPa). See figure 24.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping sysĆ tem during any pressure testing of the system at test pressures greater than 1/2 psig (3.45 kPa).
Page 16
Page 17
Nominal Internal
Nominal
Internal
Iron Pipe Size
-Inches(mm)
1/4
(6.35)
3/8
(9.53)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
4
(101.6)
Diameter
-Inches(mm)
.364
(9.246)
.493
(12.522)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
NOTE - Capacity given in cubic feet (m
GAS PIPE CAPACITY - ft.3/hr (m3/hr)
TABLE 6
Length of Pipe-Feet (m)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
43
(1.13)
95
(2.69)
175
(4.96)
360
(10.19)
680
(19.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
3
) of gas per hour and based on 0.60 specific gravity gas.
29
(.82)
65
(1.84)
120
(3.40)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
24
(.68)
52
(1.47)
97
(2.75)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
20
(.57)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
18
(.51)
40
(1.13)36(1.02)
73
(2.07)66(1.87)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
(3.91)
(7.36)
(15.01)
(22.94)
(43.04)
(67.96)
(121.76)
(249.18)
16
(.45)
138
260
530
810
1520
2400
4300
8800
15
(.42)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
14
(.40)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
13
(.37)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
7200
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Electrical
A field make-up box is provided for line voltage wiring. Line voltage wiring to unit is done through the J69 jack from the field make-up box to plug P69 from the control box. See figures 25 and 26 for make-up box installation.
Refer to figure 27 for schematic wiring diagram and trouĆ bleshooting, figure 28 for point-to-point field wiring and figure 29 for a detailed illustration of the Surelight inteĆ grated control.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic comĆ ponents. Take precautions during furnace installaĆ tion and service to protect the furnace's electronic controls. Precautions will help to avoid control exĆ posure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unĆ painted unit surface, such as the gas valve or blowĆ er deck, before performing any service procedure.
1 - Select circuit protection and wire size according to
the unit nameplate. The power supply wiring must meet Class 1 restrictions.
2 - A snaphole bushing is provided to seal around the
wiring as it enters the cabinet. A snaphole plug is proĆ vided to seal the unused wire entry hole.
3 - Install a separate disconnect switch (protected by eiĆ
ther a fuse or circuit breaker) near the unit so that power can be turned off for servicing.
4 - Install field makeĆup box on either side, inside or out
of the cabinet. Knockouts are provided in box and cabinet to facilitate wiring. See figures 25 and 26.
To ensure proper grounding of the furnace, two lockĆ washers are included in the electrical make-up box bag assembly. Place each lockwasher on a securing screw before installing the make-up box. Make sure the lockwasher breaks the paint on the cabinet so that the washer is touching metal. Unit is not properly grounded if paint has not been removed by the lockĆ washer.
5 - Remove cap from knockout in blower deck on the
same side as the installed make-up box.
6 - Insert the three-pin (P69) plug from the control box
into the knockout provided in the blower deck.
7 - Connect jack (J69) from make-up box to jack plug in
blower deck.
8 - Before connecting the thermostat or the power wirĆ
ing, check to make sure the wires will be long enough for servicing at a later date. Remove the blower acĆ cess panel to check the length of the wire.
9 - Electrically ground unit in accordance with local
codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No.
70) and in Canada with the current Canadian Electric Code part 1 (CSA standard C22.1). The ground wire is provided in the field make-up box.
Page 17
Page 18
IMPORTANT
Ignition control will not operate unless unit is propĆ erly grounded. 120V supply must be installed with correct polarity.
CAUTION
Bundle all wires connected to control board in such a way that drip loops are formed. Drip loops direct damaging moisture away from control board.
INTERIOR MAKE-UP BOX INSTALLATION
MAKE-UP
BOX
J69
BUSHING
FIGURE 25
EXTERIOR MAKEĆUP BOX INSTALLATION
MAKE-UP
BOX
J69
P69 from
Control Box
BUSHING
10 -One line voltage EAC" terminal is provided on the
furnace control board. Any electronic air cleaner rated up to one amp can be connected to this termiĆ nal with the neutral leg of the circuit being connected to the neutral EAC" terminal. See figure 29 for conĆ trol board configuration. This terminal is energized when the indoor blower is operating.
11 -One line voltage HUM" terminal is provided on the
furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neuĆ tral leg of the circuit being connected to the neutral HUM" terminal. See figure 29 for control board conĆ figuration. This terminal is energized in the heating mode whenever the combustion air inducer is operĆ ating.
12 - Install room thermostat according to instructions
provided with thermostat. The furnace may be conĆ trolled by either a single- or two-stage thermostat. If furnace is being used with heat pump refer to FM21 installation instruction.
13 - Complete wiring connections to equipment using
wiring diagrams provided with unit and figures 27 and 28. Use 18-gauge wire or larger that is suitable for Class II rating for thermostat connections. See table 7 for diagrams for specific applications.
Indoor Blower Speeds
1 - When the thermostat is set to FAN ON," the indoor
blower will run continuously at approximately 38% of the second-stage cooling speed when there is no cooling or heating demand.
2 - When the G32V unit is running in the heating mode,
the indoor blower will run on the heating speed desigĆ nated by the positions of dip switches 11 and 12.
3 - When there is a cooling demand, the indoor blower
will run on the cooling speed designated by the posiĆ tions of dip switches 5 and 6.
P69 from
Control Box
FIGURE 26
Page 18
Page 19
TYPICAL G32V SCHEMATIC WIRING DIAGRAM
FIGURE 27
Page 19
Page 20
TYPICAL G32V FIELD WIRING DIAGRAM
FIGURE 28
Thermostat
1 Heat / 1 Cool
NOTE - Use dip switch 3 to set second-stage heat ON delay. ON-10 minutes. OFF-15 minĆ utes.
1 Heat / 1 Cool with CCB1
NOTE - Use dip switch 3 to set second-stage heat ON delay. ON-10 minutes. OFF-15 minĆ utes.
TABLE 7
Field Wiring Applications
Jumper Settings (See figure 29)
E20
Term. Strip
Y1 to Y2
W914 W951
SINGLE Yes Intact Intact
SINGLE Yes Cut Intact
Wiring Connections
S1
T'STAT
S1
T'STAT
CONTROL
TERM. STRIP
CCB1
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
Page 20
Page 21
Thermostat
1 Heat / 2 Cool
NOTE - Use dip switch 3 to set second-stage heat ON delay. ON-10 minutes. OFF-15 minĆ utes.
TABLE 7
Field Wiring Applications (Continued)
Jumper Settings (See figure 29)
E20
Term. Strip
Y1 to Y2
W914 W951
SINGLE No Intact Intact
Wiring Connections
S1
T'STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool
SINGLE No Cut Intact
with CCB1
NOTE - Use dip switch 3 to set second-stage heat ON delay. ON-10 minutes. OFF-15 minĆ utes.
2 Heat / 2 Cool TWO No Intact Intact
S1
T'STAT
S1
T'STAT
CCB1
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
2 Heat / 2 Cool
TWO No Cut Intact
with CCB1
Page 21
S1
T'STAT
CCB1
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 22
TABLE 7
Field Wiring Applications (Continued)
Jumper Settings (See figure 29)
Thermostat
E20
Term. Strip
Y1 to Y2
W914 W951
2 Heat / 1 Cool TWO Yes Intact Intact
Wiring Connections
S1
T'STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
FM21 Heat Pump / 1 Cool
Harmony Application* 2 Heat / 1 Cool
SINGLE Yes Intact Cut
TWO Yes Cut Intact
*Disconnect existing furnace transformer and replace with 75VA, 24V transformer if deĆ frost option to be used.
75VA, 24V
TRANSFORMER*
NOTE - Wiring connecĆ tions to outdoor unit and thermostat made at FM21 control board per FM21 instructions.
TEMP.
MOD.
SWITCH
FAN LO
FAN LINE
HARMONY
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
FM21
NOTE ­Remove Y1/Y2 jumper for two-stage cooling.
OUTĆ
DOOR
UNIT
Harmony
TWO No Cut Intact Application* 2 Heat / 2 Cool
*Cut wires at pin positions 2 and 13 of J/P46. Insulate ends to prevent a short. Blower operates on PWM signal generated by Harmony. Harmony overrides blower speed taps. Blower speed varies according to zone demand. Low and high-fire controlled by temperature modulating switch.
Page 22
TEMP.
MOD.
SWITCH
FAN LO
FAN LINE
HARMONY
CONTROL
TERM. STRIP
OUTĆ
DOOR
UNIT
Page 23
Integrated Control Board Settings
TWO-STAGE, VARIABLE SPEED INTEGRATED CONTROL BOARD
DIAGNOSTIC
LEDs
DIP
SWITCHES
1 - 3
E20
THERMOSTAT
SELECTION
JUMPER
1/4" QUICK CONNECT TERMINALS
THERMOSTAT CONNECTIONS (TB1)
LEDs
ON-BOARD
JUMPER W914
(cut when CCB1 or
Harmony II are used)
FACTORY-
INSTALLED
JUMPER
ON-BOARD
JUMPER W951
(cut when heat pump is
used with FM21)
DIP
SWITCHES
5 - 12
LED
FIGURE 29
G32V units are equipped with a two-stage, variable speed SureLight integrated control. This control manĆ ages ignition timing, heating mode fan off delays and inĆ door blower speeds based on selections made using the control dip switches and jumpers. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out because the burner has failed to light. After one hour of continuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and autoĆ matically reset the control to relight the furnace.
Thermostat Selection Jumper (E20)
This unit may be used with either a single-stage or two­stage thermostat. The thermostat selection jumper, loĆ cated just below dip switches 1 through 3, must be propĆ erly positioned for the particular application. The jumper is factory positioned for use with a two-stage thermostat. If a single-stage thermostat is to be used, the jumper must be repositioned.
DIP SWITCH FUNCTIONS
DIP SWITCH(ES) FUNCTION
1 and 2 Blower Off Delay
3 Second Stage ON Delay (Single-stage t'stat)
4 Not used 5 and 6 Cooling Mode Blower Speed 7 and 8 Blower Speed Adjustment
9 and 10 Cooling Mode Blower Ramping Profile
11 and 12 Heating Mode Blower Speed
a - Select TWO" for two-stage heating operation conĆ
trolled by a two-stage heating thermostat (factory setting);
b - Select SINGLE" for two-stage heating operation
controlled by a single-stage heating thermostat. This setting provides a timed delay before second­stage heat is initiated.
Dip Switch Settings Switches 1 and 2 -- Blower Off Delay -- The blower-on
delay of 45 seconds is not adjustable. The blower-off deĆ lay (time that the blower operates after the heating deĆ mand has been satisfied) can be adjusted by moving switches 1 and 2 on the integrated control board. The unit is shipped from the factory with a blower-off delay of 90 seconds. The blower off delay affects comfort and is adĆ justable to satisfy individual applications. Adjust the blowĆ er off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de-
Page 23
Page 24
energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures.The table below provides the blower off timings that will result from different switch settings.
TABLE 8
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 1 Switch 2
60 Off Off
90 Off On 120 On Off 180 On On
Switch 3 -- Second Stage Delay (Used with Single­Stage Thermostat Only) -- This switch is used to deterĆ
mine the second stage on delay when a single-stage therĆ mostat is being used. The switch is factory-set in the ON position, which provides a 10-minute delay before secĆ ond-stage heat is initiated. If the switch is toggled to the OFF position, it will provide a 15-minute delay before secĆ ond-stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE-stage thermostat use.
Switch 4 -- Not used in G32V application.
Switches 5 and 6 -- Cooling Mode Blower Speed --
Switches 5 and 6 are used to select cooling blower motor speed. The unit is shipped from the factory with the dip switches positioned for high speed (4) indoor blower moĆ tor operation during the cooling mode. The table below provides the cooling mode blower speeds that will result from different switch settings. Refer to tables 13 through 13 for corresponding cfm values.
TABLE 9
Cooling Mode Blower Speeds
Speed Switch 5 Switch 6
1 - Low On On
2 - Medium Low Off On
3 - Medium High On Off
4 - High (Factory) Off Off
Switches 7 and 8 -- Blower Speed Adjustment --
Switches 7 and 8 are used to select blower speed adjustĆ ment settings. The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustĆ ment. The dip switches may be positioned to adjust the blower speed by -15% to better suit the application. The table below provides blower speed adjustments that will result from different switch settings. Refer to tables 13 and14 for corresponding cfm values.
TABLE 10
Blower Speed Adjustment
Adjustment Switch 7 Switch 8
NORMAL (Factory) Off Off
-15% (approx.) Off On
Switches 9 and 10 -- Cooling Mode Blower Speed Ramping -- Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramping may be used to enhance dehumidification perĆ formance. The switches are factory set at option A which has the greatest effect on blower motor performance. The table below provides the cooling mode blower speed ramping options that will result from different switch setĆ tings. The cooling mode blower speed ramping options are detailed below.
TABLE 11
Cooling Mode Blower Speed Ramping
Ramping Option Switch 9 Switch 10
A (Factory) Off Off
B On Off C Off On D On On
Ramping Option A (Factory Selection)
 Motor runs at 50% for 1/2 minute. Motor then runs at 82% for approximately 7-1/2 miĆ
nutes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
 Once demand is met, motor runs at 50% for 1/2 minĆ
ute.
 Motor ramps down to off.
OFF
1/2 MIN
50% CFM
7-1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
 Motor runs at 50% for 1/2 minute. Motor then runs at 82% for approximately 7-1/2 miĆ
nutes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
 Once demand is met, motor ramps down to off.
OFF
1/2 MIN 50% CFM
7-1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
Motor runs at 82% for approximately 7-1/2 minutes. If demand has not been satisfied after 7-1/2 minutes,
the motor runs at 100% until demand is satisfied.
 Once demand is met, motor ramps down to off.
OFF
7-1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option D
 Motor runs at 100% until demand is satisfied.  Once demand is met, motor ramps down to off.
Page 24
Page 25
100% CFM
COOLING DEMAND
OFFOFF
Switches 11 and 12 -- Heating Mode Blower Speed --
Switches 11 and 12 are used to select heating mode blowĆ er motor speed. The unit is shipped from the factory with the dip switches positioned for medium low (2) speed inĆ door blower motor operation during the heating mode. The table below provides the heating mode blower speeds that will result from different switch settings. Refer to tables 13 and 14 for corresponding cfm values.
TABLE 12
Heating Mode Blower Speeds
Speed Switch 11 Switch 12
1 - Low On On
2 - Medium Low
(Factory)
Off On
3 - Medium High On Off
4 - High Off Off
On-Board Jumper W914
On-board jumper W914, which connects terminals DS and R on the integrated control board, must be cut when the furnace is installed with either the Harmony II zone control board or the CCB1 EfficiencyPlus humidity conĆ trol. Refer to table 15 for operation sequence in applicaĆ
tions including a G32V, CCB1 and single-speed outdoor unit. Table 16 gives the operation sequence in applicaĆ tions with a two-speed outdoor unit.
On-Board Jumper W951
On-board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the furnace is installed in applications which include a heat pump unit and the FM21 FuelMaster control board.
Factory-Installed Jumper Y1 to Y2
A factory-installed jumper from Y1 to Y2 terminals on the integrated control board terminal strip must be removed if two-stage cooling will be used.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two-stage, variĆ able speed integrated control just to the left of the first bank of dip switches. The LED flashes correspond with diagnostic codes detailed on page 35.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate operating status. The green ON/OFF LED is lit any time the blower is operating. The green CFM LED indicates the blower motor speed. Count the number of blinks beĆ tween the two-second pauses to determine the CFM. Each blink represents approximately 100 CFM. The yelĆ low HI/LO LED is lit when the W914 (DS to R) jumper has not been clipped for CCB1 or Harmony operation. The yellow HEAT LED is lit when the indoor blower is operatĆ ing at the HEATING speed.
Page 25
Page 26
TABLE 13
G32V3-75 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Blower Speed Adjustment Settings (Switches 5 and 6)
Cool
Adjust"
Setting
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 880 415 930 440 980 465 1040 490 1060 500 1105 520 1260 595 1330 630
ć
775 365 810 380 850 400 910 430 930 440 970 460 1070 505 1130 535
Low Speed High Speed
Blower Speed Adjustment Settings (Switches 7 and 8)
Heat
Adjust"
Setting
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 945 446 1025 484 1125 531 1270 599 1080 510 1172 533 1286 607 1452 685
ć
803 379 871 411 956 451 1080 510 918 433 996 470 1093 516 1234 582
15% lower motor speed than NORM switch setting.
NOTE - The effect of static pressure and filter resistance is included in air volumes shown. NOTE - Continuous Fan only speed is approximately 800 cfm (380 L/s) - non adjustable. NOTE - Lennox Harmony IIt zone control applications - MAX CFM is determined by COOL switch setting with a minimum of approximately 850 cfm (400 L/s) for all positions.
Low Speed High Speed
TABLE 14
G32V5-100/125 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Blower Speed Adjustment Settings (Switches 5 and 6)
Cool
Adjust"
Setting
1
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Low Speed High Speed
2
3 4 1
2
3 4
Norm 1140 540 1250 590 1440 680 1550 730 1620 765 1820 860 2000 945 2100 990
ć
970 455 1060 500 1280 605 1320 595 1380 650 1550 730 1700 800 1780 840
Blower Speed Adjustment Settings (Switches 7 and 8)
Heat
Adjust"
Setting
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 1140 540 1250 590 1440 680 1550 730 1560 735 1720 810 2030 960 2150 1015
ć
15% lower motor speed than NORM switch setting.G32V5-125 Models Only - Do not set switches for position #1 (at NORM or ć" setting) or position #2 (at -" setting) for HEAT speed.
NOTE - The effect of static pressure and filter resistance is included in air volumes shown. NOTE - Continuous Fan only speed is approximately 1150 cfm (545 L/s) - non adjustable. NOTE - Lennox Harmony IIt zone control applications - MAX CFM is determined by COOL switch setting with a minimum of approximately 1140 cfm (540 L/s) for all positions.
970 455 1060 500 1280 605 1320 595 1330 660 1460 690 1730 815 1830 865
Low Speed High Speed
Page 26
Page 27
Unit Start-Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been underĆ water. Immediately call a qualified service techniĆ cian to inspect the furnace and to replace any part of the control system and any gas control which has been under water.
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or mainĆ tenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
This unit is equipped with a gas control knob. Use only your hand to turn the gas control knob. Never use tools. If knob will not switch by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
G32V units are equipped with a SureLight ignition sysĆ tem. Do not attempt to manually light burners on this furĆ nace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with SureLight ignition system.
Gas Valve Operation
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or death.
1 - STOP! Read the safety information at the beginning
of this section.
2 - Set thermostat to lowest setting.
3 - Turn off all electrical power to furnace.
4 - This furnace is equipped with an ignition device
which automatically lights the burner. Do not try to light the burner by hand.
5 - Remove unit access panel. 6 - Turn gas valve knob to OFF position. See figure 30. 7 - Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you do not smell gas go to next step.
HONEYWELL VR8205 SERIES GAS VALVE
HIGH FIRE
ADJUSTING SCREW
(under cap)
MANIFOLD
PRESSURE
TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE
TAP
GAS VALVE SHOWN IN OFF POSITION
FIGURE 30
8 - Turn gas valve knob to ON position. 9 - Replace access panel. 10 - Turn on all electrical power to unit. 11 - Set thermostat to desired setting. 12 - If the appliance will not operate, follow the instrucĆ
tions given in the "Turning Off Gas To Unit" section and call your service technician or gas supplier.
Turning Off Gas To Unit
1 - Set thermostat to lowest setting. 2 - Turn off all electrical power to unit if service is to be
performed.
3 - Remove access panel. 4 - Turn gas valve knob to OFF position. Do not force. 5 - Replace access panel.
Heating Sequence of Operation
NOTE - The thermostat jumper on the control board is facĆ tory-set in the TWO-STAGE" position.
Applications Using a Two-Stage Thermostat A - Heating Sequence -- Control Board Thermostat Selection Jumper (E20) in Two-Stage" Position (Factory Setting)
1 - On a call for heat, thermostat first-stage contacts
close sending a signal to the integrated control. The integrated control runs a selfĆdiagnostic program and checks high temperature limit switch for normalĆ ly closed contacts and pressure switch(es) for norĆ mally open contacts.The combustion air inducer is energized at low speed and the humidifier terminal is energized.
2 - Once the control receives a signal that the low presĆ
sure switch has closed, the combustion air inducer begins a 15-second pre-purge in low speed.
Page 27
Page 28
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air inducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended, the
gas valve is energized on low fire (first stage) and igniĆ tion occurs. At the same time, the control module sends a signal to begin an indoor blower 45-second ON-delay. When the delay ends, the indoor blower motor is energized on the low-fire heating speed. The furnace will continue this operation as long as the thermostat has a first-stage heating demand.
5 - If second-stage heat is required, the thermostat secĆ
ond-stage heat contacts close and send a signal to the integrated control. The integrated control initiĆ ates a 30-second second-stage recognition delay.
6 - At the end of the recognition delay, the integrated
control energizes the combustion air inducer at high speed. The control also checks the high-fire (second stage) pressure switch to make sure it is closed.The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed.
7 - When the demand for high fire (second stage) heat
is satisfied, thecombustion air inducer is switched to the low-fire heating speed and the high-fire (second stage) gas valve is de-energized. The low-fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low-fire heating speed.
8 - When the thermostat demand for low-fire (first
stage) heat is satisfied, the gas valve is de-energized and the field-selected indoor blower off delay begins. The combustion air inducer begins a 5-second post­purge period.
9 - When the combustion air post-purge period is comĆ
plete, the inducer and humidifier terminal are de-enĆ ergized. The indoor blower is de-energized at the end of the off delay.
Applications Using A Single-Stage Thermostat
B - Heating Sequence -- Control Board Thermostat Selection Jumper (E20) in Single-Stage" Position
NOTE - In these applications, two-stage heat will be initiĆ
ated by the integrated control if heating demand has not been satisfied after the field adjustable period (10 or 15 minutes).
1 - On a call for heat, thermostat first-stage contacts
close sending a signal to the integrated control. The integrated control runs a selfĆdiagnostic program and checks high temperature limit switch for normalĆ ly closed contacts and pressure switch(es) for norĆ mally open contacts.The combustion air inducer is energized at low speed and the humidifier terminal is energized.
2 - Once the control receives a signal that the low presĆ
sure switch has closed, the combustion air inducer begins a 15-second pre-purge in low speed.
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air inducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended, the
gas valve is energized on low fire (first stage) and igniĆ tion occurs. At the same time, the control module sends a signal to begin an indoor blower 45-second ON-delay. When the delay ends, the indoor blower motor is energized on the low-fire heating speed. The integrated control also initiates a second-stage on delay (factory-set at 10 minutes; adjustable to 15 minutes).
5 - If the heating demand continues beyond the second-
stage on delay, the integrated control energizes the combustion air inducer at high speed. The control also checks the high-fire (second stage) pressure switch to make sure it is closed.The high-fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heatĆ ing speed.
6 - When the thermostat heating demand is satisfied,
thecombustion air inducer begins a 5-second low speed post-purge. The field-selected indoor blower off delay begins. The indoor blower operates at the low-fire heating speed.
7 - When the combustion air post-purge period is comĆ
plete, the inducer and humidifier terminal are de-enĆ ergized. The indoor blower is de-energized at the end of the off delay.
Page 28
Page 29
TABLE 15
Dehumidification mode begins when rela
satisfied between
d
lid
d
OPERATING SEQUENCE
G32V, CCB1 and Single-Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System Condition
Thermostat
Demand
Normal operation Y1
*Call for humidity
removal during
cooling demand
Dehumidification
demand satisfied during cooling deĆ
mand.
Call for cooling after
call for humidity
removal.
Y1
Y1
None
Y1
*Relative Humidity
(EfficiencyPlus Lights)
No demand. Humidity
level is acceptable
Humidity level rises
above setpoint. Demand
initiated.
Humidity level falls below
setpoint. No demand
Humidity level above setĆ
point. Demand initiated.
Humidity level above setĆ
point. Demand initiated.
Blower
CFM
(COOL)
COOL
77%/74%
of COOL
COOL
Off
77%/74%
of COOL
Comments
Compressor demand and indoor blower speed controlled by thermostat demand.
Call for dehumidification initiated by CCB1 control. Indoor blower speed reduced by CCB1 control.
When humidity demand is satisfied, blowĆ er speed immediately increases to the COOL CFM to hasten the end of the cycle.
Dehumidification mode begins when relaĆ tive humidity is greater than setpoint.
Humidity demand
satisfied between
thermostat demands
(unit off cycle).
NOTE - When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first thermostat heating demand. * Reduced blower speed is 77% of COOL for V3 units and 74% of COOL for the V5 units.
None Over setpoint (1 or more) Off
Y1 Change to acceptable COOL
While unit is not operating (no thermostat
emand), s
e switch is moved down an
back up. Blower operates at COOL CFM.
Page 29
Page 30
TABLE 16
Normal operation
blower speed controlled by
removal during
until after initial thermostat demand is
humidity duri
point, or if slide switch is moved signifi
g
When humidity demand is satisfied,
isfied during
speed compressor operation at begin
d
d
compressor) begins with next thermo
isfied between thermo
OPERATING SEQUENCE
G32V, CCB1 and Two-Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Normal operation
Call for humidity
1st-stage cooling
demand
Significant increase in
ng
thermostat cooling
demand.
Humidity demand satĆ
isfied durin
thermostat demand.
Call for humidity
removal during 2nd
stage thermostat
eman
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase in
humidity
Humidity demand satĆ
isfied between thermoĆ
stat demands (unit off
cycle). Y1 or Y2
Note - During mode of operation change from cooling to heating, indicating lights will not change until the first thermostat heatĆ ing demand.
Thermostat
Demand
Y1 No demand. Acceptable Low
Y2 No demand. Acceptable High HIGH COOL
Y1 No demand. Acceptable Low
Y1
Demand satisfied
Y1
Y1
Y1
Y1
Y1
None
Y1
Y2
Y2
Y2
None
Y1
None
Y2
None
Y1 or Y2
None
*Relative Humidity
(EfficiencyPlus Lights)
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
Humidity level remains slightĆ
ly (1) above setpoint. DeĆ
mand continues.
Humidity level remains slightĆ
ly (1) above setpoint. DeĆ
mand continues.
No demand. Acceptable
Humidity level rises signifiĆ
cantly (2 or more) above setĆ
point. Demand initiated.
Humidity level
above setpoint.
Humidity level falls below
setpoint. No demand.
No demand. Acceptable
No demand. Acceptable
No demand. Acceptable
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
No demand. Acceptable
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is significantly
above setpoint (2 or more).
Humidity level is significantly
above setpoint (2 or more).
Humidity level is slightly (1)
above setpoint.
Humidity level falls below
setpoint. No demand.
****Compressor
Speed
Low
Off
High
Low
High
High
High
Off
Low
High
High
High
Off
Low
Off
High
Off
High
Off
High
Blower CFM
HIGH COOL
HIGH COOL
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
HIGH COOL
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
(COOL)
55% of
55% of
55% of
Off
55% of
Off
55% of
Off
55% of
Off
Off
Off
Comments
Compressor demand and indoor
blower speed controlled by
thermostat demand
Dehumidification mode does not begin
satisfied and new cooling demand is iniĆ
tiated.
If humidity rises significantly above setĆ point, or if slide switch is moved signifiĆ
cantly, unit will immediately go into deĆ
humidification mode (in presence of
thermostat demand).
When humidity demand is satisfied,
blower immediately shifts to the COOL
CFM in order to hasten the end of the
cycle. Unit can only shift out of high
speed compressor operation at beginĆ
ning of next cycle.
Blower immediately changes speed in
response to thermostat demand.
Dehumidification mode (high speed
compressor) begins with next thermoĆ
stat demand after initial demand is satĆ
isfied.
Reduced blower speed (dehumidificaĆ
tion speed) begins immediately with
thermostat demand
If humidity increases significantly over
setpoint, or if slide switch is moved, unit
immediately goes into dehumidification
mode (in presence of thermostat deĆ
mand).
While unit is not operating (no thermoĆ
stat demand), slide switch is moved
down and back up. Blower and comĆ
pressor operate at high speed until next
thermostat demand.
*IMPORTANT Ć If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed indefinitely. To reset, move the humidity slide switch all the way down then back up to desired setpoint while the unit is running. ** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5. ***If the two-speed control on a two-speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compresĆ sor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 30
Page 31
Gas Pressure Adjustment
TABLE 17
Manifold Pressure (Outlet) in. w.c. (kPa)
No gas pressure adjustment is needed when operating at altitudes from 0 to 4500 ft. (0 to 8 m). See below for correct manifold pressures
for altitudes greater than 4500 ft. (1372 m) for natural and L.P. gas.
Manifold Pressure (outlet) in. w.g. (kPa)
Model No.
G32V-75 natural 3.5 3.5 3.5 3.5
G32V-100 natural
G32V-125 natural
G32V-75L.P. 7.5 7.5 7.5 7.5
G32V-100 L.P. 7.5 (1.90) 7.3 (1.81) 7.1 (1.80) 7.0 (1.74)
G32V-125 L.P. 7.5 (1.90) 7.3 (1.81) 7.1 (1.80) 7.0 (1.74)
0 to 4500 ft. (0 to 1372 m)
above sea level
3.5 (0.87) 3.4 (0.85) 3.3 (0.82) 3.2 (0.80)
4501 to 5500 ft.
(1373 to 1676 m)
above sea level
5501 to 6500 ft.
(1677 to 1981 m)
above sea level
6501 to 7500 ft.
(1982 to 2286 m)
above sea level
Gas Flow
To check for proper gas flow to the combustion chamber, determine the Btu (kW) input from the unit rating plate. DiĆ vide this input rating by the Btu (kW) per cubic foot (cubic meter) of available gas. The result is the required number of cubic feet (cubic meter) per hour. Determine the flow of gas through the gas meter for two minutes and multiply by 30 to get the hourly flow of gas.
Gas Pressure
1 - Check gas line pressure with unit firing at maximum
rate. Maintain a minimum of 4.5 in. w.c. (1.12 kPa) for natural gas or 8.5 inches w.c. (2.11kPa) for LP/proĆ pane gas.
2 - After line pressure has been checked and adjusted,
check high heat regulator pressure. See figure30 for gas pressure adjustment screw location. High heat manifold pressure for natural and LP/propane gas is given in table 17.
Manifold Pressure Measurement & Adjustment
NOTE - Pressure test adaptor kit (10L34) is available from Lennox to facilitate manifold pressure measureĆ ment.
1 - Connect test gauge to outlet tap on gas valve. 2 - Disconnect pressure sensing hose from gas valve
and plug hose by covering opening with tape or equivalent. Leave barbed fitting on valve open to atĆ mosphere. See figure 31 for differential pressure switch circuitry on 75 kBtuh models. Only 75 kBtuh models are equipped with a second pressure switch. Other models have single pressure switch.
3 - Start unit on high heat and allow 5 minutes for unit to
reach steady state.
4 - While waiting for the unit to stabilize, notice the
flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.
5 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table 17.
NOTE - Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to re­place pressure tap plug.
75 kBtuh DIFFERENTIAL PRESSURE SWITCH CIRCUITRY
LOW HEAT
DIFFERENTIAL
PRESSURE
SWITCH
TEE
HIGH HEAT
DIFFERENTIAL
PRESSURE
SWITCH
COMBUSTION
AIR PRESSURE
SENSING HOSE
COMBUSTION
AIR BLOWER
LEFT SIDE OF PRESSURE SWITCH = MORE NEGATIVE
RIGHT SIDE OF PRESSURE SWITCH = LESS NEGATIVE (Closer to Zero)
Honeywell PPS
Pressure Switch
Shown
BURNER
BOX
HOSE
BARB
BURNER
BOX
SENSING
HOSE
GAS
VALV E
SENSING
HOSE
GAS
VALV E
PRESSURE
SWITCH
SENSING
HOSE
FIGURE 31
NO T E - Dur ing this tes t procedure, the unit will be overĆ firing:
Operate unit only long enough to obtain accurate
reading to prevent overheating heat exchanger.
Attempts to clock gas valve during this procedure will
be inaccurate. Measure gas flow rate only during normal unit operation.
6 - When test is complete remove obstruction from hose
and return hose to gas valve barbed fitting.
Page 31
Page 32
High Altitude Information
Refer to table 17 for manifold pressure settings for instalĆ lations at altitudes from 0 to 7500 feet (0 to 2286 m).
NOTE - In Canada, certification for installations at elevaĆ tions over 4500 feet (1372 m) is the jurisdiction of local auĆ thorities.
The pressure switch(es) are factory-set and should not be adjusted. The -75 is equipped with both a high- and low-heat pressure switch. The -100 and -125 units have a single pressure switch.
Other Unit Adjustments
NOTE - Disconnect power to unit before making any adjustments.
Heat Anticipation Settings
Thermostat anticipator setting (if adjustable) should be set according to amps listed on wiring diagram on unit.
Flame Rollout Switch
Factory set: No adjustment necessary.
Limit Control
Factory set: No adjustment necessary.
Pressure Switches
Factory set: No adjustment is necessary.
Temperature Rise
Check temperature rise and, if necessary, adjust blower speed to maintain temperature rise within range shown on unit rating plate.
Electrical
1 - Check all wiring for loose connections.
2 - Check circuit breaker located on unit control box.
3 - Check for the correct voltage at the furnace (furnace
operating).
4 - Check amp-draw on the blower motor.
Motor Nameplate __________Actual__________.
NOTE - Do not secure electrical conduit directly to ductĆ ing or structure.
Electronic Ignition
The SureLight integrated control has an internal watchĆ guard feature. The feature serves as an automatic reset device for ignition controls locked out because the burner has failed to light. After one hour of continuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and automatically reĆ set the control to relight the furnace.
Burner Flame
Start burner and allow to operate for a few minutes to esĆ tablish normal burning conditions. Check burner flame by observation. Flame should be predominantly blue and strong in appearance.
Check burner flame periodically to ensure proper opera­tion.
Service
WARNING
Disconnect power before servicing unit.
CAUTION
Label all wires prior to disconnection when servicĆ ing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Annual Service
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Electrical
1 - Check all wiring for loose connections. 2 - Check circuit breaker located on unit control box. 3 - Check for the correct voltage at the furnace (furnace
operating).
4 - Check amp-draw on the blower motor.
Motor Nameplate_________Actual_________
5 - Check to see that heat (if applicable) is operating.
Blower
Check the blower wheels for debris and clean if necesĆ sary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
Filters
1 - Filters must be cleaned or replaced when dirty to as-
sure proper furnace operation.
2 - Reusable foam filters used with the unit can be
washed with water and mild detergent.
3 - If replacement is necessary, order Lennox part no.
31J81 for 14 inches x 25 inches (356 x 635 mm) filĆ ter for G32V-75 units and P-8-7831 for 20 inches x 25 inches (508 x 635 mm) filter for G32V-100 and
-125 units.
Intake and Exhaust Lines
Check intake and exhaust lines and all connections for tightness and make sure there is no blockage. Also check condensate line for free flow during operation.
Insulation
Outdoor piping insulation should be inspected yearly for deterioration. If necessary, replace with same materials.
Winterizing and Condensate Trap Care
1 - Turn off power to unit. 2 - Have a shallow pan ready to empty condensate waĆ
ter. Avoid spilling water into the control box.
3 - Remove clamp from flue assembly and remove boot
or cap. Empty water from cap. Visually inspect botĆ tom of flue assembly. Replace boot and clamp.
4 - Remove boot from condensate trap and empty waĆ
ter. Inspect trap then replace boot.
Page 32
Page 33
Cleaning DuralokPlusTM Heat Exchanger
If cleaning the heat exchanger is necessary, follow the procedures below, and refer to figure 1 while you disasĆ semble the furnace. Place papers or protective covering in front of the furnace while you remove the heat exchangĆ er assembly.
1 - Turn off electrical and gas power supplies to furnace. 2 - Remove upper and lower furnace access panels. 3 - Remove four screws around air intake fitting and lift
intake pipe up and away.
4 - Loosen hose clamp securing top of flue transition to
bottom of flue collar. Remove screw securing flue collar to top cap and lift exhaust pipe and flue collar up and away.
5 - If electrical field makeĆup box is located inside the
unit, it must be removed. 6 - Remove gas supply line connected to gas valve. 7 - Mark all gas valve wires and disconnect them from
valve. Mark and remove wires from flame rollĆout
switch. 8 - Remove top cap of unit. 9 - Remove sensor wire from SureLight control. DisconĆ
nect 2Ćpin plug from the ignitor. 10 - Mark and disconnect pressure switch tubing from
both sides of the pressure switch(es). 11 - Loosen two screws holding gas manifold support at
vestibule panel. 12 - Remove four burner box screws at the vestibule panĆ
el and remove burner box and gas valve/manifold asĆ
sembly with bracket. 13 - Drain condensate trap. Disconnect condensate line
from the outside of unit. Remove condensate line
from condensate trap by turning the adapter fitting
counterclockwise. The fitting has standard right
hand threads. 14 - Disconnect the drain hose from the flue transition to
the elbow on the cold header (collector) box trap. 15 - Disconnect the 3Ćpin plug from the combustion air inĆ
ducer at the blower deck. Remove four screws from
combustion air inducer and remove flue transition
and inducer assembly from cabinet. Take care not to
lose the combustion air orifice. 16 - Mark and disconnect remaining wiring to heating
compartment components. 17 - Disengage strain relief bushing from blower deck.
Pull bushing and wiring into blower compartment. 18 - Remove the limit switch and the pressure switch(es)
from the vestibule panel. 19 - Remove two screws from the front cabinet flange at
the blower deck. Remove front screws from cabinet
at blower deck on left and right sides. Cabinet sides
must be slightly spread to clear heat exchanger pasĆ
sage. 20 - Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger
assembly to cabinet. Remove heat exchanger.
21 - Back wash heat exchanger with soapy water soluĆ
tion or steam. If steam is used it must be below
275°F (135°C).
22 - Thoroughly rinse and drain the heat exchanger.
Soap solution can be corrosive so take care that enĆ tire assembly is completely rinsed.
23 - Reinstall heat exchanger in the cabinet making sure
that the clamshells of the heat exchanger assembly are resting in the notches of the support located at the rear of the cabinet. This can be viewed by removĆ ing the indoor blower and examining through the blower opening.
24 - Resecure the supporting screws along the vestibule
sides and bottom to the cabinet.
25 - Reinstall cabinet screws on sides and front flange at
blower deck.
26- Reinstall the limit switch and pressure switches on
the vestibule panel.
27 - Route heating component wires through hole in
blower deck. Reinsert strain relief bushing. ReconĆ nect wires.
28 - Reinstall the combustion air inducer. Check to enĆ
sure that the plastic orifice in the inducer inlet has not fallen out. See figure 1. Reconnect the 3Ćpin plug to the wire harness. Reinstall the flue transition in the cabinet and reattach the drain tube. Route the drain tube below the combustion air inducer housing and to the elbow on the cold header (collector) box trap. See figure 31.
29 - Reconnect condensate line with adapter to condenĆ
sate trap. Use fresh Teflon tape to ensure a leak-free joint. Reconnect to condensate line outside of the unit.
30 - Reinstall the burner box. Tighten the screws holding
the support bracket. It is important that the glass fiber gasket not be damaged so it will provide a continuĆ ous seal between the burner box and the vestibule panel.
31 - Reconnect pressure switch tubing by connecting the
tubing from the burner box to the barbed fitting on the bottom and the tubing from the combustion air inducĆ
er to the barbed fitting on the top. See figure 31. 32 - Reconnect the sensor and ignitor wires. 33 - Reinstall top cap on unit. 34 - Reconnect wiring to gas valve. Brown wire to HI, yelĆ
low wire to C and orange wire to M. Reconnect wires
to flame rollĆout switch.
NOTE - Unit is polarityĆsensitive. 120V supply wiring
must be installed correctly.
35 - Reconnect main gas line to gas valve. Use second
wrench on gas valve to avoid transferring torque to
the gas manifold. 36 - Reinstall field makeĆup box if removed. 37 - Reinstall exhaust pipe/flue collar and secure flue colĆ
lar on the unit top cap using existing screw. Insert the
bottom of the flue collar into the top of the flue transiĆ
tion and tighten hose clamp.
Page 33
Page 34
38 - Reinstall intake pipe fitting on burner box with
screws. 39 - Replace both upper and lower access panels. 40 - Refer to instruction on verifying gas and electrical
connections when reĆestablishing supply. 41 - Following lighting instructions from installation
manual, light and operate unit for 5 minutes to ensure
heat exchanger is clean, dry and operating safely.
Cleaning the Burner Assembly
1 - Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels. 2 - Disconnect the gas supply line from gas valve. DeĆ
pending on gas plumbing installation, the gas manĆ
ifold may move aside enough that breaking the union
may not be necessary. 3 - Remove five screws from edges of burner box cover. 4 - Loosen two screws on bottom of burner box front.
The cover has a key hole on each side, so screws do
not need to be removed. Remove the cover and set it
aside. 6 - Mark all gas valve wires and disconnect them from
valve. 7 - Mark and disconnect sensor wires from the burner
box at the ignition control. Disconnect 2-pin plug
from the ignitor at the burner box. 8 - Loosen two screws at the gas manifold support
bracket. 9 - Pull on the left side of the gas manifold and follow
with tension to the right side. The manifold support
bracket will be free of the mounting screws on the
vestibule panel. Set the gas manifold/gas valve asĆ
sembly aside. Take care not to damage foam gasĆ
kets on each end of the gas manifold. 10 - Using a 1/4 inch nut driver, remove the burner
mounting screws from underneath the burners. 11 - While supporting ignitor and sensor lines at the
grommet, grasp burners and simultaneously pull
burners and grommet out of the burner box. 12 - Remove ignitor and sensor bracket assemblies from
burners using a 1/4 inch nut driver to remove two
screws from each bracket. 13 - Clean burner by running a vacuum with a soft brush
attachment over face of burners. Use burner brush
to clean inside of burners. Visually inspect inside of
burners and crossovers for any blockage caused by
foreign matter. Remove any blockage.
14 - Reinstall ignitor and sensor bracket assemblies on
burners.
NOTE - Install the ignitor on the opposite side of the burner from the metal button protrusions. Screws that attached the ignitor bracket must be installed from the same side as the ignitor and through the bracket to engage in the smaller holes located in the burner. The correct burner orientation is with metal button protrusions always pointing up.
15 - Reinstall the burner ignitor assembly in the burner
box so that grommet groove fits back into sheet metĆ al notch and makes a good seal. The burners sit on top of the burner box flanges. Make certain that the screws underneath the box pass through the larger holes in the flange and engage in the smaller holes in the burner. Reinstall the two screws.
16 - Reinstall the gas manifold/gas valve assembly by
first inserting the right hand side of the gas manifold into the burner box. Swing left side of manifold into box while engaging support bracket to vestibule panĆ el screws. Make sure the foam gaskets are providing a seal around each end of the gas manifold. All gas orifices should be engaged. If at this point the burnĆ ers were mounted in the wrong holes, this needs to be corrected. The saddle brackets on the gas manĆ ifold should be flush with the front surfaces on the burner box sides.
17 - Inspect the dual layered metal pieces at the front lip
of the cover. These pieces must form a sandwich around the lip. Reinstall burner box cover.
18 - Reinstall the screws to secure the burner box cover.
Make sure screws are tight to ensure a leak tight burner box. Tighten the two screws underneath the box. Again, inspect the grommet to ensure a tight seal.
19 - Tighten the two screws holding the manifold bracket
to the vestibule panel.
20 - Reconnect gas valve wiring. Brown wire to HI yellow
wire to C and orange wire to M.
21 - Reinstall the 2Ćpin ignitor plug at the burner box. ReĆ
install sensor line to ignition control spade connector. 22 - Reconnect gas line to gas valve. 23 - Replace lower access panel. 24 - Following lighting instructions and gas line connecĆ
tion test procedures from installation manual. 25 - Replace upper access panel.
Page 34
Page 35
Repair Parts List
ONONON
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the unit rating plate. Example: G32VQ3-75-5.
Cabinet Parts
Cabinet cap Blower panel Upper access panel
Control Panel Parts
TwoĆstage, variable-speed SureLight control board Transformer
Circuit breaker Door interlock switch
Blower Parts
Blower wheel Motor Belly-band assembly Power choke Blower housing cutĆoff plate Blower housing
Heating Parts
Heat exchanger/coil assembly Gas manifold Main burner orifices Main burners TwoĆstage gas valve Ignitor Primary limit control Flame rollout switch Filter and filter rack assembly Flue transition Pressure switch - high fire (-75 only) Pressure switch - low fire Flame sensor Sight glass and grommet Rubber boot trap Foam manifold gaskets TwoĆspeed combustion air blower Condensate pipe plug and adapter Cold end header (collector) box
Integrated Control Board Diagnostic Codes
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 29 for location of diagnostic LEDs.
DS1 DS2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH ON
OFF SLOW FLASH
OFF FAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH OFF Flame sensed without gas valve energized.
ON ON
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below .7 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
NOTE - Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Minimum flame sense current = 0.15-0.17 microAmps.
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on - Normal operation. Also signaled during cooling and continuous fan.
Normal operation - signaled when heating demand initiated at thermostat.
Primary limit or rollout limit switch open. Limits must close within 3 minutes or unit goes into 1 hour Watchguard. Low-fire pressure switch open; OR: Blocked inlet/exhaust vent; OR: Low-fire pressure switch closed prior to activation of combustion air inducer.
High-fire pressure switch open (G32V-75 only); OR: Blocked inlet/exhaust vent; OR: High-fire pressure switch closed prior to activation of combustion air inducer.
Watchguard -- burners failed to ignite; OR limit open more than 3 minutes; OR lost flame sense 5 times in one heating cycle; OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm-up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts. (If voltage lower than 75 volts prior to ignitor warmĆup, control will signal waiting on call from thermostat, and will not respond.
Page 35
Page 36
SureLight Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
POWER ON
CONTROL SELF-CHECK OKAY?
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CHECK FOR BROKEN IGNITOR OR OPEN IGNITER CIRCUIT. DS 1 AND DS 2 ALTERNATING FAST FLASH.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.) DS1 ON, DS2 ON
NO
POLARITY OKAY?
YES
IS THERE A
PROPER GROUND?
YES
IS VOLTAGE
ABOVE 75 VOLTS?
YES
BURNER OFF?
(CONTINUOUS FLAME CHECK)
YES
A
NORMAL OPERATION:
DS 1 -- SIMULTANEOUS SLOW FLASH DS 2 -- SIMULTANEOUS SLOW FLASH
B
THERMOSTAT CALLS FOR HEAT:
DS 1 -- SIMULTANEOUS FAST FLASH DS 2 -- SIMULTANEOUS FAST FLASH
YES
PRIMARY LIMIT
SWITCH CLOSED?
YES
ROLLOUT SWITCH CLOSED?
YES
FIRST (LOW) STAGE PRESSURE SWITCH
CONTACTS OPEN?
YES
SECOND (HIGH) STAGE PRESSURE SWITCH
CONTACTS OPEN?
NO
NO
NO
NO
NO
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
DS1 AND DS2 ALTERNATING FAST FLASH.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
DS1 AND DS2 ALTERNATING FAST FLASH.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
INDOOR BLOWER ON. HAS PRIMARY LIMIT
NO
NO
NO
60-MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
DS1 AND DS2 ALTERNATING SLOW FLASH,
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
HAS MANUAL ROLLOUT SWITCH(ES) BEEN
RESET (CLOSED) WITHIN 3 MINUTES?
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
ON/OFF LED OFF, HEAT LED OFF.
POLARITY REVERSED.
DS 1 -- FAST FLASH
DS 2 -- SLOW FLASH
DS1 SLOW FLASH, DS2 OFF,
ON/OFF LED OFF
COMBUSTION AIR INDUCER OFF.
RESET WITHIN 3 MINUTES?
DS1 SLOW FLASH, DS2 ON,
ON/OFF LED ON, HEAT LED ON.
NO
ON/OFF LED OFF, HEAT LED ON.
DS1 SLOW FLASH, DS2 ON,
ON/OFF LED ON, HEAT LED ON.
DS1 OFF, DS2 SLOW FLASH,
YES
NO
YES
TWO-STAGE OR SINGLE-STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
DS1 AND DS2 SIMULTANEOUS FAST FLASH
CONTINUED ON NEXT PAGE
COMBUSTION AIR INDUCER OFF.
GAS VALVE OFF.
INDOOR BLOWER OFF.
CONTROL WILL NOT ATTEMPT SECOND-STAGE
OPERATION DURING THIS HEAT DEMAND.
FIRST-STAGE OPERATION WILL BE ATTEMPTED.
DS1 OFF, DS2 FAST FLASH,
ON/OFF LED OFF, HEAT LED ON.
Page 36
Page 37
SureLight Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
FIRST-STAGE (LOW-FIRE) PRESSURE
SWITCH CLOSED WITHIN 2.5 MINUTES?
YES
15-SECOND COMBUSTION AIR INDUCER
PRE-PURGE INITIATED BY CLOSED FIRST-STAGE
PRESSURE SWITCH (or 15 SECOND
INTER-PURGE PERIOD.)
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
IGNITOR WARM-UP (20 SECONDS)
DS1 AND DS2 SIMULTANEOUS FAST FLASH
IS VOLTAGE ABOVE 75 VOLTS?
YES
IS THERE A PROPER GROUND?
IS IGNITOR INTACT AND CONNECTED?
YES
NO
NO
NO
NO
THERMOSTAT CALLS FOR HEAT
DS1 AND DS2 SIMULTANEOUS FAST FLASH
(Refer to box A on previous page)
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. UNIT WILL RETRY AFTER
5-MINUTE WAIT PERIOD.
DS1 OFF, DS2 SLOW FLASH,
ON/OFF LED OFF, HEAT LED OFF.
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
DS1 AND DS2 ALTERNATING FAST FLASH.
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
DS1 AND DS2 ALTERNATING FAST FLASH.
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED
OR RECONNECTED.
DS1 AND DS2 ALTERNATING FAST FLASH.
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4-SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4-SECOND TRIAL UNTIL FLAME SENSED.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
YES
4-SECOND FLAME STABILIZATION PERIOD.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.15 microamps)
FLAME PRESENT?
YES
CONTINUED ON NEXT PAGE
NO
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
NO
HAS CONTROL RESET IGNITION SEQUENCE
DS1 SLOW FLASH, DS2 FAST FLASH,
ON/OFF LED OFF, HEAT LED 0N.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
DS1 AND DS2 ALTERNATING SLOW FLASH.
ON/OFF LED 0FF, HEAT LED OFF.
IS 60-MINUTE RESET PERIOD COMPLETE?
YES
FOUR (4) TIMES?
DS1 SLOW FLASH, DS2 FAST FLASH,
ON/OFF LED OFF, HEAT LED ON .
NO
YES
NO
Page 37
Page 38
SureLight Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
FLAME SIGNAL ABOVE
(u0.2 microamps)
YES
NO
YES
THERMOSTAT CALLS FOR HEAT.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
SEE BOX A.
LOW FLAME SIGNAL
(Does not affect control operation)
DS1 SLOW FLASH, DS2 FAST FLASH.
SINGLE-STAGE THERMOSTAT MODE
(E20 SET AT SINGLE")
YES
START SECOND-STAGE RECOGNITION
ON DELAY (10 OR 15 MINUTES).
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
FIRST-STAGE (LOW FIRE)
PRESSURE SWITCH CLOSED?
YES
NO
FIRST-STAGE HEAT DEMAND SATISFIED?
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
DS1 AND DS2 SIMULTANEOUS SLOW FLASH
SECOND-STAGE HEAT DEMAND.
SECOND-STAGE HEAT DEMAND REQUIRED?
DS1 AND DS2 SIMUTANEOUS SLOW FLASH.
SECOND STAGE PRESSURE SWITCH CLOSED?
ABNORMAL FLASH CODE.
NOTE - IF SECOND-STAGE PRESSURE SWITCH
WAS ORIGINALLY FOUND CLOSED,
ABNORMAL CODE WILL FLASH.
SECOND-STAGE 30-SECOND DELAY ON BEGINS.
DS1 AND DS2 SIMULTANEOUS FAST FLASH
SECOND-STAGE COMBUSTION AIR INDUCER
ON. SECOND-STAGE GAS VALVE ON. HIGH
HEAT INDOOR BLOWER SPEED ON.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
SECOND-STAGE PRESSURE SWITCH CLOSED
IN LESS THAN TEN (10) SECONDS?
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
C
YES
YES
NO
YES
ON/OFF LED ON.
YES
YES
CONTINUED ON NEXT PAGE
YES
TWO STAGE THERMOSTAT MODE
(E20 SET AT TWO")
YES
45-SECOND INDOOR BLOWER ON DELAY BEGINS.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
YES
NO
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF, INDOOR BLOWER ON. DS1 SLOW FLASH, DS2 ON,
(Indoor blower on low speed during 3-minute period)
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
DS1 AND DS2 ALTERNATING SLOW FLASH,
IS 60-MINUTE RESET PERIOD COMPLETE?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
SECOND-STAGE PRESSURE SWITCH CLOSED
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.
RETURNS TO FIRST-STAGE HEAT MODE WHICH CONTINUES UNTIL SECOND-STAGE PRESSURE
SWITCH CAN BE PROVEN or HEAT DEMAND IS
NO
SATISFIED. FIVE (5) MINUTE WAIT PERIOD
INITIATED BEFORE RETRY. WERE 5 ATTEMPTS
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.
YES
PRIMARY LIMIT AND
ROLLOUT SWITCH CLOSED?
NO
ON/OFF LED ON, HEAT LED ON.
HAS PRIMARY LIMIT OR ROLLOUT
SWITCH CLOSED WITHIN 3 MINUTES?
NO
LIMIT SWITCH WATCHGUARD MODE.
INDOOR BLOWER OFF WITH DELAY.
ON/OFF LED OFF, HEAT LED OFF.
INDOOR BLOWER OFF AFTER DELAY.
DS1 OFF, DS 2 SLOW FLASH,
ON/OFF LED OFF, HEAT LED ON.
AT BEGINNING OF HEAT DEMAND?
DS1 OFF, DS2 SLOW FLASH,
ON/OFF LED ON, HEAT LED ON.
SECOND STAGE HEAT DEMAND
NO
MADE FOR SECOND-STAGE HEAT?
YES
NORMAL OPERATION.
YES
YES
NO
Page 38
Page 39
SureLight Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE OF OPERATION
CONTINUED
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.
SEE BOX A
NORMAL OPERATION
ARE PRIMARY LIMIT AND ROLLOUT
SECOND-STAGE (HIGH FIRE) HEAT
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
SWITCH CLOSED?
YES
FIRST-STAGE (LOW FIRE) HEAT
PRESSURE SWITCH CLOSED?
PRESSURE SWITCH CLOSED?
YES
HEAT DEMAND SATISFIED?
YES
YES
NO
NO
NO
THERMOSTAT CALLS FOR HEAT
SEE BOX B
DS 1 AND DS 2 SIMULTANEOUS FAST FLASH.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON.
DS1 SLOW FLASH, DS2 ON,
ON/OFF LED ON, HEAT LED 0N.
HAS PRIMARY LIMIT OR ROLLOUT SWITCH
CLOSED WITHIN 3 MINUTES?
NO
LIMIT SWITCH WATCHGUARD MODE. GAS VALVE
OFF. COMBUSTION AIR INDUCER OFF. INDOOR
BLOWER OFF WITH DELAY. IS 60-MINUTE RESET
PERIOD COMPLETE? DS SLOW FLASH, DS2 ON,
ON/OFF LED OFF, HEAT LED OFF.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF AFTER 15 SECOND POST PURGE, INDOOR
BLOWER OFF AFTER DELAY.
DS1 OFF, DS2 FAST FLASH,
ON/OFF LED ON, HEAT LED ON.
RETURN TO HEAT DEMAND?
RETURN TO FIRST-STAGE HEAT MODE.
FIRST-STAGE CONTINUES UNTIL SECOND-
STAGE PRESSURE SWITCH CAN BE PROVEN
or HEAT DEMAND IS SATISFIED. A FIVE (5)
MINUTE WAIT PERIOD IS INITIATED BEFORE
RETRY. WERE 5 ATTEMPTS MADE FOR
SECOND-STAGE HEAT?
NO
SEE BOX C
FIRST-STAGE HEAT DEMAND SATISFIED?
YES
YES
YES
YES
SINGLE-STAGE THERMOSTAT MODE
(E20 SET AT SINGLE")
YES
HEAT DEMAND SATISFIED?
DS1 AND DS2
SIMULTANEOUS FAST FLASH.
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5-SECOND LOW
SPEED POST PURGE PERIOD, INĆ
DOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
DS1 AND DS2
SIMULTANEOUS FAST FLASH
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY.
DS1 AND DS2
SIMULTANEOUS SLOW FLASH
TWO STAGE THERMOSTAT MODE?
(E20 SET AT TWO")
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
DS1 & DS2 SIMULTANEOUS FAST FLASH.
YES
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST-
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
FIRST STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5-SECOND LOW SPEED POST-
PURGE PERIOD. INDOOR BLOWER OFF. DELAY INITIATED ON LOW HEAT SPEED.
DS1 & DS2 SIMULTANEOUS FAST FLASH.
Page 39
SECOND STAGE HEAT
NO
DEMAND SASTISFIED?
DS1 AND DS2
SIMULTANEOUS FAST FLASH.
YES
STAGE OPERATION.
YES
Page 40
SureLight Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
POWER ON
SIGNAL IMPROPER
GROUND AT DS.
SIGNAL HOLDS
UNTIL UNIT IS
PROPERLY
GROUNDED.
THERMOSTAT CALLS FOR FIRST-STAGE COOL.
INDOOR BLOWER ENERGIZED ON FIRST STAGE
FIRST-STAGE DEMAND FOR COOL SATISFIED?
THERMOSTAT CALLS FOR SECOND-STAGE COOL.
IS POLARITY REVERSED?
NO
NO
COMPRESSOR AND CONDENSER FAN
COOL SPEED AFTER 2 SECOND DELAY.
IS THERE
PROPER GROUND?
ENERGIZED.
NO
YES
YES
IS VOLTAGE
ABOVE 75 VOLTS?
YES
YES
SIGNAL POLARITY REVERSED.
DS1 FAST FLASH, DS2 SLOW FLASH.
NO
COMPRESSOR AND CONDENSER FAN DE-ENERGIZED.
LOW VOLTAGE SIGNAL AT DS HOLDS
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
INDOOR BLOWER DE-ENEGIZED.
INDOOR BLOWER RAMPS UP TO SECOND-STAGE COOL SPEED.
SECOND-STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
Page 40
Page 41
SureLight Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
YES YES
THERMOSTAT CALLS FOR FIRST-STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2-SECOND DELAY.
AFTER 45-SECOND DELAY, INDOOR BLOWER
SWITCHES TO LOW HEAT SPEED.
YES
YES
FIRST-STAGE COOL DEMAND SATISFIED?
NO
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
SECOND STAGE COOL DEMAND SATISFIED?
YES
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
FIRST-STAGE HEAT DEMAND SATISFIED.
NO
THERMOSTAT CALLS FOR SECOND-STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30-SECOND RECOGNITION PERIOD.
YES
SECOND-STAGE HEAT DEMAND SATISFIED.
YES
INDOOR BLOWER RAMPS DOWN TO LOW
HEAT SPEED.
YES
Page 41
Page 42
G32V Start-Up & Performance Check List
Job Name
Job Location
Installer
Unit Model No.
Serial No.
Heating Section
Electrical Connections Tight?
Line Voltage
Blower Motor Amps
Fuel Type: Natural Gas?
Job No.
City
City
Technician
Blower Motor H.P.
Gas Piping Connections Tight & Leak-Tested?
LP/Propane Gas?
Date
State
State
Furnace Btu Input (High fire) Line Pressure
Low Fire Manifold Pressure
High Fire Manifold Pressure
Flue Connections Tight?
Combustion Gas Tested (high fire and low fire)?
Blower ON delay confirmed? (45 Seconds Fixed On)
Blower OFF Delay Setting (60, 90, 120 or 180)?
Filter Clean & Secure?
w.c. - Nat.:
w.c. - Nat.:
External Static Pressure? (0.8 maximum)
w.c. - LP/Propane
w.c. - LP/Propane
Proper Draft?
CO
2
Temperature Rise
CO
Thermostat
Heat Anticipator Setting? Thermostat Level?
Page 42
Loading...