G26 series units are high−efficiency upflow gas furnaces manufactured with
DuralokPlus aluminized steel clamshell-type heat exchangers. G26 units
are available in heating capacities of 50,000 to 125,000 Btuh and cooling
applications up to 5 tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is available for conversion to LPG operation. G26−1 and −2 model units use electronic (intermittent pilot) ignition. G26−3, −4, −5 and −6 model units feature the Lennox SureLight silicon nitride ignition system. Each unit meets the California Nitrogen Oxides (NOx) Standards and California Seasonal Efficiency requirements without modification. All units use a redundant gas valve to assure
safety shut−off as required by A.G.A. or C.G.A.
Information contained in this manual is intended for use by qualified service
technicians only. All specifications are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes. In the absence of local or state
codes, the guidelines and procedures outlined in this manual (except where
noted) are recommended only.
G26
Corp. 9721−L11
Revised 08−2004
2
7
1
3
G26 FURNACE
4
FIGURE 1
5
G26 HEAT EXCHANGE ASSEMBLY
Combustion Process:
1. A call for heat starts the combustion air blower.
2. Outdoor air is drawn through pipe into the burner
compartment where it mixes with gas in a conventional style inshot burner.
3. The SureLight ignition system lights the burners.
4. Combustion products are drawn downward
through the heat exchanger. Heat is extracted
as indoor air passes across the outside surface
of the metal.
5. Latent heat is removed from the combustion
products as air passes through the coil. Condensate (water) is formed as the combustion products cool.
6. As the combustion products exit the coil, condensate is collected and drained away.
7. Combustion products are pulled from the heat
exchanger and forced into the flue.
Continuous Low Speed Blower Switch (optional)44J06 (−1 and −2 models) Not used with Twinning Kits
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Polyurethane frame type filter.
Determine from venting tables proper intake and exhaust pipe size and termination kit required.
Vent/Intake Air Roof
Vent/Intake Air Wall
(optional)
Non-continuous low speed64H88 (all models)
Continuous low speed35J93 (all models)
2 inch (51 mm)15F75
3 inch (76 mm)44J41
2 inch (51 mm)
3 inch (76 mm)44J40 (close couple) or 81J20 (WTK close couple)
Continuous Low Speed Blower Switch (optional)44J06 (−1 and −2 models) Not used with Twinning Kits
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Polyurethane frame type filter.
Determine from venting tables proper intake and exhaust pipe size and termination kit required.
NOTE − 2 inch x 3 inch (51 mm x 76 mm) adaptor is furnished with -100 and -125 furnaces for exhaust pipe connection.
.
Non-continuous low speed64H88 (all models)
Continuous low speed35J93 (all models)
in.1/2
mm12.7
in.10 x 1011-1/2 x 910 x 1011-1/2 x 9
mm254 x 254292 x 229254 x 254292 x 229
Tons2 to 43-1/2 to 52 to 43-1/2 to 5
kW7.0 to 14.112.3 to 17.67.0 to 14.112.3 to 17.6
Optional Accessories (Must Be Ordered Extra)
Single (44J21) Ten Pack (66K62)
(1) 20 x 25 x 1 (508 x 635 x 25)
33K97 2 inch (51 mm)
60L46 − 3 inch (76 mm)
2 inch (51 mm)15F75
3 inch (76 mm)44J41
2 inch (51 mm)
3 inch (76 mm)44J40 (close couple) 81J20 (WTK close couple)
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMediumLow
G26Q3-50 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMedium-LowLow
Air Volume and Motor Watts at Specific Blower Taps
Air Volume and Motor Watts at Specific Blower Taps
G26Q3-75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMedium-LowLow
Air Volume and Motor Watts at Specific Blower Taps
G26Q4/5-75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMediumMedium-LowLow
Air Volume and Motor Watts at Specific Blower Taps
Page 5
BLOWER PERFORMANCE DATA
External Static
External Static
External Static
External Static
G26Q3/4-100 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMedium-LowLow
G26Q4/5-100 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMediumMedium-LowLow
Air Volume and Motor Watts at Specific Blower Taps
Air Volume and Motor Watts at Specific Blower Taps
G26Q3/4-125 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMedium-LowLow
Air Volume and Motor Watts at Specific Blower Taps
G26Q4/5-125 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWattscfmL/sWatts
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable foam filter (not furnished) in place. Also see Filter Air Resistance table.
HighMedium-HighMediumMedium-LowLow
Air Volume and Motor Watts at Specific Blower Taps
MINIMUM PIPE LENGTHS FOR FURNACES G26-50 5 feet (1.5 m) with two 90 elbows of 1-1/2 inch (38 mm) diameter pipe. (15 equivalent feet (4.6 m) total).
VENTING NOTES One 90elbow is equivalent to 5 feet (1.5 m) of straight vent pipe.
Two 45 elbows are equal to one 90 elbow.
One 45 elbow is equivalent to 2.5 feet (.75 m) of straight vent pipe.
One foot (305 mm) length of 2 in. (51 mm) diameter pipe is equivalent to 8 feet (2.4 m) of 3 in. (76 mm) diameter pipe.
Intake and Exhaust pipes must be the same diameter.
2 inch x 3 inch (51 mm x 76 mm) adaptor is furnished with -100 and -125 furnaces for exhaust pipe connection.
Exhaust pipe must terminate with 1-1/2 inch (38 mm) diameter pipe for furnaces using1-1/2 (38 mm) or 2 inch (51 mm) diameter pipe runs.
Exhaust pipe must terminate with 2 inch (51 mm) diameter pipe for furnaces using 3 inch (76 mm) diameter pipe runs.
See pages 10 thru 12 for Termination Kits available.
G26-75 5 feet (1.5 m) with two 90 elbows of 2 inch (51 mm) diameter pipe. (15 equivalent feet (4.6 m) total).
G26-100 5 feet (1.5 m) with two 90 elbows of 2 inch (51 mm) diameter pipe. (15 equivalent feet (4.6 m) total).
G26-125 5 feet (1.5 m) with two 90 elbows of 2 inch (51 mm) diameter pipe. (15 equivalent feet (4.6 m) total).
NOTE−Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Length of Pipe−Feet(m)
20
(.57)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
18
(.51)
40
(1.13)
73
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
16
(.45)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
8800
(249.18)
15
(.42)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
14
(.40)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
13
(.37)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
7200
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Page 7
GLASS FIBER GASKET
FRESH AIR
INTAKE FITTING
BURNER BOX
ASSEMBLY
PATCH
PLATE
G26−3 THROUGH −6 COMPONENTS
FLUE COLLAR
WARM
HEADER
(COLLECTOR)
BOX
PATCH PLATE WITH
BARBED FITTING
AND FLAME
ROLL−OUT SWITCH
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
TOP CAP
CABINET
FLUE
TRANSITION
FLAME SIGHT
BURNER
BOX
COVER
GLASS
GAS VALVE AND
MANIFOLD
BURNER
ACCESS
PANEL
BLOWER
ACCESS
DOOR
COMBUSTION AIR
BLOWER
COMBUSTION AIR
PROVE (PRESSURE)
SWITCH
COMBUSTION AIR
ORIFICE
SUPPLY
AIR
BLOWER
PRIMARY LIMIT
(ALTERNATE STYLES)
CONDENSER COIL
CONTROL TRANSFORMER
CONTROL VOLTAGE
CIRCUIT BREAKER
DOOR INTERLOCK
SWITCH
CONTROL BOX COVER
COLD HEADER
(COLLECTOR)
BOX
FIGURE 1
Page 8
BURNER
ACCESS
COVER
BURNER BOX
MANIFOLD
GAS VALVE
FRESH AIR INTAKE
FITTING
G26 HEAT EXCHANGER
CORBEL ORIFICE
CUPS
SURELIGHT IGNITORLENNOX DURALOKPLUS
HEAT EXCHANGER AS-
SEMBLY
COMBUSTION AIR
BLOWER MOTOR
COMBUSTION
AIR BLOWER
FLAME SIGHT GLASS
FLUE TRANSITION
DIFFERENTIAL
(COMBUSTION AIR)
PRESSURE SWITCH
BURNER
BOX
COLD HEADER
(COLLECTOR )
BOX
FIGURE 2
G26 GENERAL PARTS ORIENTATION
WARM HEAD
(COLLECTOR)
BOX
CONDENSER COIL
SUPPLY AIR DUCT
FLANGE
UPPER VEST PANEL
GAS MANIFOLD
PRIMARY LIMIT
GAS VALVE
COMBUSTION AIR BLOWER
DOOR INTERLOCK
SWITCH
BLOWER HOUSING
BLOWER
COMPARTMENT
COLD HEADER BOX
HEADER BOX
CONDENSATE
TRAP
LOWER VEST PANEL
CONTROL BOX
CIRCUIT BREAKER
BLOWER MOTOR
BLOWER MOTOR CAPACITOR
FIGURE 3
Page 9
OUTSIDE INSTALLATION
MAKE-UP BOX
MAKE-UP BOX INSTALLATION
Box may be installed inside or outside cabinet and may
be installed on left side or right side of cabinet
STAR WASHERS
MUST BREAK
PAINT ON UNIT
CABINET FOR
PROPER
GROUND.
UNIT
CABINET
INSIDE INSTALLATION
MAKE-UP BOX
Line Voltage Enters Through
Knockout In Make-Up Box. J69
Passes Through Side Knockout
Into Side Of Unit.
JACK J69
BLOWER MULLION
PLUG P69
FIGURE 4
I−UNIT COMPONENTS
G26 unit components are shown in figure 1. General parts orientation is shown in figure 3. The gas valve, ignition control
and burners can be accessed by removing the burner access
panel. The blower and blower controls can be accessed by
removing the blower access door.
G26 units are designed for bottom and side return air. The
panels are designed to be knocked-out (bottom return) or
cut-out (side return) as required for return air duct connection.
A−Make-Up Box (Figure 5)
The line voltage make-up box is shown in figure 5. The box
may be installed inside or outside the unit and may be
installed on the unit left or right side (figure 4).
MAKE-UP BOX
BOX
POWER ENTRY KNOCKOUT
120V LINE VOLTAGE
PIGTAIL CONNECTIONS
COVER
Line Voltage Enters Make-Up
Box Through Side Of Unit and
J69 Passes Through Bottom
Knockout in Make-Up Box.
BLOWER MULLION
An accessory (brown) output wire is provided with the makeup box. The wire provides a 120V connection for optional accessories such as electronic air cleaner or humidifier. If used,
the wire is field installed in J69 jack plug by inserting the pin
of the brown wire into the open
socket of the jack. See figure
6. 120V accessories rated up
to 4 amps total may be connected to this wire. The neutral
leg of the accessory is con-
INSTALLING BROWN
ACCESSORY WIRE TO J69
BROWN
WHITE
NEUTRAL
nected to the neutral white
wire in the make-up box. The
accessory terminal is energized whenever the blower is
in operation.
BLACK
J69
FIGURE 6
B−Control Box Components
G26 CONTROL BOX
TRANSFORMER
UNIT
GROUND
JACK J69
to blower deck
Box may be installed inside or outside unit. See Figure 4
TO BLOWER MULLION
FIGURE 5
Page 10
DOOR
INTERLOCK
SWITCH
SURELIGHT CONTROL
(−3 through −6 models )
FIGURE 7
CIRCUIT
BREAKER
Electrical blower control components (A15), unit transformer (T1) and 24V circuit breaker (CB8) are located in the control box. In addition, a door interlock switch (S51) is located
in the control box. Jackplugs and a snap-off" terminal strip
allow the control box to be easily removed for blower service.
1− Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage 24volt section of the unit. Transformers on
all models are rated 40VA with a 120V primary and a 24V
secondary.
2− Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated 3A at 32V. If the current exceeds
this limit the breaker will trip and all unit operation will shutdown. The breaker can be manually reset by pressing the
button on the face.
3−Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is located on
the control box. The switch is wired in series with line voltage. When the blower door is removed the unit will shut
down.
4−Flame Sensor (−3 through −6 models)
A flame sensor is located on the left side of the burner support. See figure 8. The sensor is mounted on a bracket in
the burner support and the tip protrudes into the flame envelope of the left−most burner. The sensor is fastened to
burner supports and can be removed for service without
removing any part of the burners. During operation, flame
is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve
to remain open as long as flame signal is sensed.
NORMAL FLAME SIGNAL u 0.7 MICROAMPS
LOW FLAME SIGNAL v 0.7 MICROAMPS
MINIMUM FLAME SIGNAL v 0.15 MICROAMPS
SENSOR
3/8"
FIGURE 8
NOTE − The G26 furnace contains electronic components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
IGNITOR
5/16"
5−Burners
All units use inshot burners (see figure 9). Burners are factory
set and do not require adjustment. A s ight g l a s s i s f u rnished in the burner box assembly for flame viewing. Always operate the unit with the burner box cover in place.
Burners can be removed as an assembly for service. Burner
maintenance and service is detailed in the MAINTENANCE
section of this manual. Each burner uses an orifice which is
precisely matched to the burner input (see nameplate for
orifice size). The orifice is threaded into the burner manifold. The burner is supported by the orifice and will easily
slide off for service. Each orifice and burner are sized specifically to the unit. Refer to Lennox Repair Parts Listing for
correct sizing information. A flame retention ring in the end of
each burner maintains correct flame length and shape and
keeps the flame from lifting off the burner head. In addition, the
burner entrance to each clamshell (Figure 2) is fitted with a
corbel cup (orifice)
TYPICAL BURNER ASSEMBLY
used to direct the
flow of combustion
products.
FIGURE 9
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
6− SureLight Ignition System A3
(−3 through −6 models)
All G26−3 through −6 model units are equipped with the
Lennox Sure − Light ignition system. The system consists
of ignition control board (figure 10 with control terminal
designations in table 1) and ignitor (figures 8 and 11). The
board and ignitor work in combination to ensure furnace
ignition and ignitor durability. The SureLight integrated
board controls all major furnace operations. The board
also features two LED lights for troubleshooting and two
accessory terminals rated at (4) four amps. See table 2
for troubleshooting diagnostic codes. Table 3 and 4 show
jack plug terminal designations. Units equipped with the
SureLight board can be used with either electronic or
electro−mechanical thermostats without modification.
The SureLight ignitor is made of durable silicon−nitride.
Ignitor longevity is also enhanced by voltage ramping by
the control board. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor.
NOTE − Do not remove blower access panel to read
SureLight LED lights. A sight glass is provided on the
access panel for viewing.
Page 11
SURELIGHT CONTROL BOARD
TABLE 1
SURELIGHT CONTROL TERMINAL DESIGNATIONS
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
Blower − Cooling Speed (Line Volt)
Blower − Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
SURELIGHT IGNITOR
MEASUREMENT IS TO I.D.
5/8"
OF RETENTION RING
13/32’
FIGURE 10
FIGURE 11
TABLE 2
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1LED #2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
Also signaled during cooling and continues fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Units with board 63K8901 or 24L85: Limit must
SLOW FLASHON
close within 5 trials for ignition or board goes into one hour limit Watchguard.
Units with board 56L83 or 97L48: Limit must close within 3 minutes or board
Pressure switch open or has opened 5 times during a single call for heat; OR:
OFFSLOW FLASH
Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
ALTERNATING SLOW
FLASH
SLOW FLASHOFF
ONSLOW FLASH
ON
ON
OFF
FAST FLASHSLOW FLASH
SLOW FLASHFAST FLASH
ALTERNATING FAST
FLASH
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.15 microAmps
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .7 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
goes into one hour limit Watchguard.
Watchguard − burners fail to ignite.
Open ignitor circuit.
Page 12
TABLE 3
SureLight BOARD J156 (J2) TERMINAL
PIN #FUNCTION
1Ignitor
2
3
4
5
6
DESIGNATIONS
Not Used
Ignitor Neutral
Combustion Air Blower Line Voltage
Not Used
Combustion Air Blower Neutral
TABLE 4
SureLight BOARD J58 (J1) TERMINAL
PIN #FUNCTION
1Primary Limit In
2
3
4
5
6
7
8
9
DESIGNATIONS
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Pressure Switch and Primary Limit Out
Not Used
Roll Out Switch In
Ground
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s
electronic controls. Precautions will help to
avoid control exposure to electrostatic discharge by putting the furnace, the control and
the technician at the same electrostatic potential. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface,
such as the gas valve or blower deck, before performing any service procedure.
a−Electronic Ignition
On a call for heat the SureLight control monitors the combustion air blower pressure switch. The control will not begin the heating cycle if the pressure switch is closed (by−
passed). Once the pressure switch is determined to be
open, the combustion air blower is energized. When the
differential in the pressure switch is great enough, the
pressure switch closes and a 15−second pre−purge begins. If the pressure switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch
mode for a 5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve
opens for a 4−second trial for ignition. G26 units with board
63K89, 24L85 or 56L83: the ignitor stays energized for the
first second of the 4−second trial. Units with board 97L48:
ignitor stays energized for the full 4−second ignition trial. If
ignition is not proved during the 4−second period, the control will try four more times with an inter purge and warm−up
time between trials of 35 seconds. After a total of five trials
for ignition (including the initial trial), the control goes into
Watchguard−Flame Failure mode. After a 60−minute reset
period, the control will begin the ignition sequence again.
The SureLight control board has an added feature that
prolongs the life of the ignitor. After a successful ignition,
the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to
ramp down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition.
This amount of power is used for 255 cycles. On the 256th
call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
b−Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 12.
FAN-OFF TIME ADJUSTMENT
60sec.90sec.120sec.180sec.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 12
7−Blower Motors and Capacitors
All G26 units use direct drive blower motors. All motors
used are 120V permanent split capacitor motors to ensure
maximum efficiency. See table 5 for ratings.
Page 13
TABLE 5
BLOWER MOTORHP
G26Q2
G26Q3
G26Q3/4
G26Q4/5
G26 BLOWER RATINGS 120V 1PH
1/5
1/3
1/2
3/440MFD 370V
5MFD 370V
CAP
5MFD 370V
7.5MFD 370V
8−Combustion Air Blower (B6)
All G26 units use a combustion air blower to move air
through the burners and heat exchanger during heating operation. The blower uses a PSC or shaded Pole 120VAC
motor. PSC motors use run capacitors. The motor operates
during all heating operation and is controlled by blower control A15. The blower operates continuously while there is a
call for heat. The ignition control is prevented from proceeding through the ignition sequence until combustion air blower
operation is sensed by the prove switch.
The pressure switch connected to the combustion air blower
housing is used to prove combustion air blower operation.
The switch monitors air pressure in the blower housing. During normal operation, the pressure in the housing is negative. If the pressure drops (becomes more positive), the pressure switch opens. When the pressure switch opens, the
ignition control (A3) immediately closes the gas valve to prevent burner operation.
9−Primary Limit Control (S10)
The primary limit (S10) on G26 units is located in the
middle of the heating vestibule panel. When excess heat
is sensed in the heat exchanger, the limit will open. If the
limit is tripped, the furnace control energizes the supply air
blower and de−energizes the gas valve. The limit automatically resets when unit temperature returns to normal. The
switch is factory set and cannot be adjusted. The switch
may have a different setpoint for each unit model number. However, the setpoint will be printed on the side of
the limit.
SPADE CONNECTORS
G26 SERIES UNITS AND ALTERNATE STYLE
LIMIT CONTROL (S10) FOR
Units may be equipped with either style limit.
LIMIT
INSULATING COVER (s)
FIGURE 13
10−Rollout Switch (S47) −3 Through −6
Flame rollout switch S47 is a SPST N.C. high temperature
limit located on the right side of the burner box assembly (see
figure 14). S47 is wired to the burner ignition control A3.
When S47 senses flame rollout (indicating a blockage
in the combustion passages), the flame rollout switch
trips, and the ignition control immediately closes the
gas valve.
Switch S47 in all G26 units is factory preset to open at
200F + 12F (93C + 6.7C) on a temperature rise. All
flame rollout switches are manually reset. A kit (#65K60) is
available for G26 −1 and −2 models.
FLAME ROLLOUT SWITCH (S47)
FLAME ROLLOUT
SWITCH (S47)
FIGURE 14
11− BCC2−3 Blower Control A15
(−1 and −2 models)
All G26−2 and −1 model units utilize the BCC2-3 blower control manufactured by Heatcraft. The BCC2-3 is a printed circuit board which controls the supply air blower and monitors
primary limit and gas valve operation. The control has a
non-adjustable, factory preset fan-on" timing. Fan off" timing is adjustable. The board is divided into two sections,
120 and 24VAC. Line voltage comes into the board on the
120VAC side. See figure 16.
Fan Timings
Fan off" timing (time that the blower operates after the heat
demand has been satisfied) is determined by the arrangement of a jumper across pins on the BCC2-3 blower control
board. See figure 15. To adjust fan off " timing, gently disconnect jumper and reposition across pins corresponding
with new timing. Fan on" time is factory set at 45 seconds
and is not adjustable.
NOTEIf fan off" time is set too low, residual heat in
heat exchanger may cause primary limit S10 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Figure 15 shows the various fan off" timings and how jumper
should be positioned. Unit is shipped with a factory fan off"
setting of 90 seconds. Fan off" time will affect comfort and
efficiency and is adjustable to satisfy individual applications.
The fan off" timing is initiated after a heating demand but not
after a blower or cooling demand (that is, when indoor thermostat switch is changed from ON to AUTO and heating/
cooling demand is not present, the blower stops immediately).
FAN-OFF TIME ADJUSTMENT
To adjust fan-off timing:
TIMING
JUMPER
270
150
Remove jumper from BCC2-3 and select one of the other pin combinations
to achieve the desired time.
210
90
TIMING
PINS
(seconds)
Leave jumper off for
330 second fan-off timing.
FIGURE 15
Page 14
G26 BLOWER CONTROL - BCC2-3 (A15)
DETACHABLE
STRIP ON EARLY
BOARDS ONLY
Table 8 shows
terminal designations.
FIGURE 16
12−Ignition Control (−1 and −2 models)
G26 −1 and −2 model units use an intermittent pilot ignition
manufactured by Johnson Controls. The ignition control is
located on the upper vest panel.
Unit Operation
When there is a call for heat, the control is prevented from
beginning an ignition sequence until the pressure switch
proves combustion air blower operation. When the pressure
switch closes, the control generates a spark and opens the
pilot valve to ignite the pilot. When flame is sensed, the control opens the main gas valve and the pilot ignites the main
burners. The indoor blower starts after a 45 second delay.
Gas valve remains open and combustion air blower continues to run until demand stops, flame sensor senses loss of
flame, a limit opens or the prove switch opens. If any of these
events occur during a thermostat demand, the gas valve
closes.
The control will attempt ignition for 85 seconds. If ignition is
not successful, the control will lockout (indicated by flashing LED). Within one hour the control will momentarily remove then reapply the thermostat signal and the ignition
sequence will begin again (Watchguard circuit). If pilot
ignition is successful, but flame is lost when the main valve
opens, the ignition sequence will retry up to 15 more times.
If ignition is not successful after the 16th try, the control will
shut-down and must be reset manually. Manual reset is
accomplished by removing thermostat demand for at least
2 seconds then reapplying demand.
Table 8 shows
terminal designations.
IGNITION CONTROL A3
SPARK
OUTPUT
SEE TABLE 6
FOR TERMINAL
DESIGNATIONS
FIGURE 17
DANGER
Shock hazard. Spark related components contain
high voltage. Disconnect power before servicing.
Control is not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
TABLE 6
IGNITION CONTROL A3 TERMINAL DESIGNATIONS
TerminalTypeFunction
GROUND1/4" SpadeCabinet Ground
THS 21/4" Spade
P. V. 11/4" Spade
M.V.31/4" Spade
SENSE 41/4" SpadeMicroamp Flame Sensing Input
Unmarked
Pin Type
Bare Wire
Safety Limit 24VAC Input
From Differential Switch
24VAC Output to Pilot Operator
24VAC Output to Main Operator
of Gas Valve
of Gas Valve
High Voltage Spark Output
Page 15
Diagnostic LED
The furnace control is equipped with a diagnostic LED
used for troubleshooting the unit and the control. LED
functions are shown in table 7.
TABLE 7
Furnace Control A3 Diagnostic LED
LED StateMeaningRemedy
Steady On Normal Operation- - - Slow Flash
(1 sec. on/
5 sec. off)
Off
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Ter mi na l
(Designation
on Wiring
Diagram)
Y
G
R
W
T
IBN (N)1/4" Spade120VAC Indoor Blower Common
N1 (N)1/4" Spade
CABN (N)1/4" Spade
XFMRN(N)1/4" Spade120VAC Transformer Common
HSIN (N)1/4" Spade
CAB1/4" Spade
L11/4" Spade120VAC Line Voltage In
A1/4" Spade
XFMR1/4" Spade24VAC In From Transformer
D1/4" Spade
CF1/4" Spade
H1/4" Spade
ACC1/4" Spade
24V
(24)
LIMIT
(L)
W1/4" Spade
VALV E
SENSE (V)
T1/4" Spade
COM (C)1/4" Spade24VAC Common To Transformer
Control Retry
Period
Control Failure or
Power Failure or
Hard Lockout
TypeFunction
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
Detachable
Screw Strip
1/4" Spade24VAC Input From Transformer
1/4" Spade
3/16" Spade24VAC Input From Gas Valve
Failed to Sense Flame. Ignition Con-
If Power and Gas Supply are OK, Try
Removing T’stat Demand For At Least
30 Seconds. If LED Remains Off
When Demand Is Returned, Replace
trol Will Retry
Before Locking Out.
Control.
TABLE 8
Cooling Demand
Blower Demand
24VAC to Thermostat
Heating Demand
24VAC Common
To Indoor Thermostat
120VAC Neutral
(L2 Line Voltage Neutral)
120VAC Combustion Air Blower Com-
120VAC Hot Surface Ignition
Combustion Air Blower
to Blower Cooling Tap
Dummy Connection for
Unused Blower Leads
Continuous Blower Tap
Switched 120VAC to Accessory (Elec-
tronic Air Cleaner, Humidifier, Etc.)
24VAC In From Primary Limit. Limit
Open: Closes Gas Valve and Turns On
Blower Limit Closed: Allows Ignition
24VAC Thermostat Demand Output
Through Differential Switch to THS"
Terminal of Ignition Control
24VAC Common From
Ignition Control and Gas Valve
mon
Common (Not Used)
Switched 120VAC to
Switched 120VAC
Switched 120VAC to
Switched 120VAC to
Blower Heating Tap
Johnson G776 Ignition Control Operation
The information in this section is protected by a copyright issued by
Johnson Controls, Inc., and is reproduced with permission.
On a call for heat from indoor thermostat, the ignition control
energizes and ignition control LED lights (steady on). The
combustion air blower is energized. After 15 second prepurge period, the control simultaneously opens pilot valve
and sends spark to pilot electrode.
If pilot ignites within 85 seconds, flame sensor detects pilot
flame and signals ignition control to energize the main
valve. The main valve cannot be energized until sensor
detects pilot flame. Spark continues until pilot flame is
sensed or 85 seconds has elapsed.
When pilot flame is sensed, main valve is energized and
spark turns off. The ignition control remains in run" mode until indoor thermostat is satisfied or flame lost.
If pilot flame is not sensed before the end of the 85 second trial
for ignition, the control enters the 100% shutoff mode. The
spark circuit and pilot valve de-energize and the ignition control automatically begins the 60 minute retry delay period.
During the 60 minute delay the diagnostic LED continually
flashes on for one second and off for five seconds. After the
delay period, another trial for ignition sequence starts, beginning with pre-purge.
If pilot flame goes out while the indoor thermostat is calling
for heat, both main and pilot valves de-energize within 0.8
seconds and remain de-energized for five seconds. After
this delay, the spark and pilot valve energize until flame is
sensed or the 85 second trial for ignition period ends. If this
flameout" cycle repeats 16 times (pilot flame is established and then lost), the control locks out and the LED
goes off. A new trial for ignition sequence begins after the
thermostat contacts are opened for 2 seconds and then
closed.
If flame is detected when the thermostat calls for heat, it
must extinguish within 30 seconds for normal operation. If
flame is still present after 30 seconds, the control goes into
lockout and the LED goes off.
13−Pilot, Spark Electrode, Flame Sensor
(−1 and −2 models)
Figure 18 shows the arrangement of pilot, flame sensor,
spark electrode and burners. The ignition control uses direct spark to ignite the pilot. The pilot ignites the burners
and the burners cross-light. The flame sensor uses flame
rectification to sense pilot ignition. The ignition control requires that pilot flame must be sensed before the main gas
valve is allowed to open. Typically, a 2 to 4 second delay
occurs between the pilot ignition and the main valve opening. Figure 19 shows the gap between the tip of the electrodes and the burner surface. It is important that the gap
be maintained for consistent ignition of pilot flame.
Page 16
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.