Lennox FWCK, FWHK Installation, Operating And Maintenance Manual

Providing indoor climate comfort
FWCK/FWHK
Application guide Installation, operating and maintenance manual
MIL101E-0105 12-2009 Original manual translation
1
Congratulations you have made a wise choice. This product has been designed, assembled and supplied
in one of our world class manufacturing facilities and we feel sure that it will meet your expectations.
WARNING: Read this manual before installation, reparation o maintenance works.
• PRODUCT RANGE
GENERAL DESCRIPTION
PHYSICAL DATA
• ELECTRICAL SPECIFICATIONS
ELECTRICAL CONNECTIONS
• OPERATING LIMITS
FAN SPECIFICATIONS
CAPACITY TABLES
CORRECTION FACTORS
DIMENSIONS
INSTALLATION
SERVICE AND MAINTENANCE
OPTIONS
POINTS TO KEEP IN MIND
• NOTES
1 2 3 3 4 4 5
6-8
9
10 11-12 13-14 15-16
17
18
INDEX
PRODUCT RANGE
COOLING ONLY UNITS
HEAT PUMP UNITS
400 V - 3Ph
MODEL V / Ph / 50 Hz
NOMINAL CAPACITY kW
10,2
13
2,73
3,47
400 V - 3Ph 230 V - 3Ph
400 V - 3Ph
NOMINAL POWER INPUT kW
230 V - 1Ph
230 V - 1Ph
7,3
1,93
230 V - 3Ph
230 V - 1Ph 8,4
2,38
230 V - 1Ph 5,7
1,5
14,9
4,28
230 V - 3Ph 400 V - 3Ph 230 V - 3Ph
20,1
5,91
4
1,12
COOLING
COOLING
FWCK 04 FWCK 06
FWCK 07 FWCK 08
FWCK 10
FWCK 12
FWCK 16 FWCK 22
230 V - 1Ph
400 V - 3Ph
MODEL V / Ph / 50 Hz
NOMINAL CAPACITY kW
400 V - 3Ph 230 V - 3Ph
400 V - 3Ph
NOMINAL POWER INPUT kW
230 V - 1Ph
230 V - 1Ph 230 V - 3Ph
230 V - 1Ph
230 V - 1Ph
230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph
3,15
3,92
2,22 2,75
1,72
4,83
6,65
12,3
15
8,6
10,4
7
18,5
24,5
5,7
1,42
COOLING
HEATING
COOLING
HEATING
FWHK 04 FWHK 06
FWHK 07 FWHK 08
FWHK 10
FWHK 12
FWHK 16 FWHK 22
230 V - 1Ph
10,2
13
7,3 8,4
5,7
14,9
20,1
4
2,73
3,47
1,93 2,38
1,5
4,28
5,91
1,12
CONTENTS PAGE
Lennox have been providing environmental solutions since 1895, our range of FWCK/FWHK continues to meet the standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and uncompromising attention to detail. Engineered to last, simple to maintain and Quality that comes as standard. Information on local contacts at www.lennoxeurope.com.
All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in the operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
ON / OFF
SET TEMP
HOLD
SWING
DAY
ON TIMER
CLOCK
SLEEP
FAN
OFF TIMER
HOUR MINUTE
MODE
SET CLOCK
MON TUE WED THU FRI SAT SUN
KEYLOCK
TIMER ACTIVE SET TIMER
AUTO
HEAT
HEAT TEMP. ROOM TEMP.
AUTO COOL TEMP.
DRY
COOL
SLEEP
SWING
FAN
Electrical heater mounted on fan discharge.
• Hot water coil (for cooling only units).
• Pressostatic valve regulating water flow for cooling only models.
• Flow switch.
• Water filter.
• Main switch (not available for 04-06-07 models).
• Compressor acoustic jacket.
Three phase protection (three phase units).
GENERAL DESCRIPTION
COMPRESSOR
WATER EXCHANGER
WATER CIRCUIT
COOLING/HEATING CIRCUIT
ELECTRIC CIRCUIT
AIR EXCHANGER
CABINET
FAN
OPTIONS
Made of welded dehumidifying copper tube with access connections.
Cooling only units (FWCK): They include dehydrator filter, liquid recipient, and expansion system, high pressure switch for all models and low pressure switch for modes 08-10-12-16-22. Heat pump units (FWHK): They include thermostatic valve as expansion system, high and low pressure switches for all models. In addition they includes a security thermostat for low warter temperatures, 4 ways valve and liquid recipient. To work properly in heating mode, the unit includes check valve, restrictor and filter drier.
The unit leaves the factory with R407C refrigerant.
The electrical box includes all the components and terminal blocks needed for the installation. It includes a printed board, starting timer and reversible working mode in heat pump units. In addition alarm, ON/OFF remote and dry contact for water pump are available too. The wired remote control manages the unit.
REMOTE CONTROL
2
The air conditioner, horizontal compact, water condensed type FWCK/FWHK, are specially designed for small and average installation, office, house, etc. On standard version the unit cleans, filters, cools and dehumidifies the air (FWCK), and in addition heats if it is heat pump unit (FWHK). You are able to incorporate option elements such as electrical heater or hot water coil.
The unit includes an exchanger plate, compact and resistant made on stainless steel, specially selected for this type of unit.
The cabinet is made of galvanised steel with compact dimensions and features allow the unit to be positioned in almost any location. Internally the unit incorporates thermal acoustic insulation to reduce sound level.
Made of copper tubing with aluminum swirl fins, they are designed and specially dimensioned to obtain the maximum output.
The units include a centrifugal three speed motor fan, with a motor directly fitted (except FWCK/FWHK 22 with belts­pulley), with high performance on air flow.
It includes water threaded connections H-G. Heat pump units include a differential water switch in order to stop the unit without water flow.
Rotary compressor for 04 model and Scroll for the rest of the models, all of them with internal thermic protection. It is mounted on vibration-absorbent blocks both on the inside and outside, statically and dynamically balanced.
AIR FILTER
A polypropylene washable air filter is incorporated in the unit it is accessible for maintenance operations.
The unit includes a wired remote control with LCD display.
OLT-1X Controller
Basic characteristics for the controller:
- 3 fan speeds (High/Medium/Low).
- Different modes of working: Cool, Heat, Auto, Fan and Dry.
- Sleep mode.
- 7 days programmable timers.
- Real time clock
- Keyblock function
- Alarms display
- Temperature indication ºC ó ºF.
3
MAXIMUM ABSORBED POWER
ELECTRICAL SPECIFICATIONS
kW.
Compressor Indoor fan
MAXIMUM RUNNING CURRENT
TOTAL
kW.
kW.
2,3
0,33 2,63
2,9
0,33 3,23
3,4
0,46 3,86
4,05 0,46
4,51
4,70
0,83
5,53
5,78 0,83
6,61
A
VOLTAGE
7,60 1,10
8,70
Maximum running current
13,0 16,4 19,5
18,9/9,4
23,3/12,7
23,9/15,5
26,8/16,5
20,8
A
48,6
62,6 78,2
93,2/48,2 102,0/54,0 137,0/70,0 180,5/103,5
97,2
Starting current
PHYSICAL DATA
MODEL
Total cooling capacity
Nominal absorbed power Cooling
kW (**)
kW (*)
Air flow (max./min.)
20,1 24,5
210
13 15
14,9 18,5
10,2 12,3
8,4
10,4
2350/1000
7,3 8,6
1400/800
5,7
7
FWCK 06 FWHK 06
1550/600
3618
72
168/171
---/56,5
2250/1200 3100/1500 3100/1800 4500/2250
1" G
FWCK 08 FWHK 08
FWCK 10 FWHK 10
FWCK 12 FWHK 12
FWCK 16 FWHK 16
FWCK 22 FWHK 22
FWCK 07 FWHK 07
4
5,7
FWCK 04 FWHK 04
1050/450
Nominal water flow
Water pressure drop
Hydraulic connections
Sound pressure
level (LP) (2)
dB(A)
Dimensions
l/h
kPa
Cooling
(low / high) speed
(mm)
Height Width
Depth
(mm) (mm)
Pa
Max. available static pressure(1)
Net weight
Kg
120 120100120100140
2340 26641829150513071019
75 3545836135
147/150
155/158
104/106
101/103
78/80
75/77
47/50 46/4949/5051/5244/4542/49
3/4" G 3/4" G 3/4" G 3/4" G 1" G 1" G
80
713
16
54/56 44/47
440 492
792
3/4" G
Total heating capacity
Nominal absorbed power Heating
5,91 6,65
3,47 3,92
4,28 4,83
2,73 3,15
2,38 2,75
1,93 2,22
1,5
1,72
1,12 1,42
kW (**)
kW (*)
440 492
792
465 623
1083
505 703
1503
465 623
1083
505 703
1503
505 703
1503
1,4
0,19 1,59
9,7
29,9
FWCK 06 FWHK 06
FWCK 08 FWHK 08
FWCK 10 FWHK 10
FWCK 12 FWHK 12
FWCK 16 FWHK 16
FWCK 22 FWHK 22
FWCK 07 FWHK 07
FWCK 04 FWHK 04
440 492
792
44/47
47/49
51/52
47/50
50/50
46/49
---/56,544/45
Heating
(low / high) speed
Cooling / heating
230V /1Ph
230V / 400V 3Ph
m /h
3
(*) Exchanger air inlet temperature: 27ºC DB / 19ºC WB. Exchanger water inlet temperature: 30ºC. (**) Exchanger air inlet temperature: 20ºC DB. Exchanger water inlet temperature: 20ºC. (1) With admissible minimum air flow. (2) Sound pressure level has been tested at a distance of 2 m from the unit, with duct in aspiration and air discharge, normal absorption in
accordance with room size and unit capacity.
DB.- Dry bulb temperature WB.- Wet bulb temperature
4
Power supply Thermostat connection Electrical heater power supply Connection Electrical heater - control.
2
2 2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2 2 2
Electrical heater
ON / OFF
SET TEMP
HOLD
SWING
DAY
ON TIMER
CLOCK
SLEEP
FAN
OFF TIMER
HOUR MINUTE
MODE
SET CLOCK
MON TUE WED THU FRI SAT SUN
KEYLOCK
TIMER ACTIVESET TIMER
AUTO
HEAT
HEAT TEMP. ROOM TEMP.
AUTO COOL TEMP.
DRY
COOL
SLEEP SWING
FAN
(supplied with
the unit)
Length 15m.
4x1mm
2
23
3x1mm
2
ELECTRICAL CONNECTIONS: Power supply, remote ON/OFF, alarm and dry contact for water pump.
NOTE: Remote ON/OFF and dry contact for water pump. Can support 3A for AC3.
ELECTRICAL CONNECTIONS
FOR ELECTRICAL CONNECTION REFER TO WIRING DIAGRAM IN THE
UNIT.
PLEASE, CHECK ELECTRICAL DATA IN ORDER TO SELECT THE
FUSES.
Nº OF WIRES X SECTION
3 X6mm
4 X 6mm 4 X 4mm
4 X 4mm
4 X 6mm
3 X 6mm 4 X 4mm
4 X 2,5mm
1
3 X 4mm
4 X 4mm
5 X 2,5mm
5 X 4mm
4 X 6mm
3 X 4mm 4 X 4mm
5 X 2,5mm
MODEL
FWCK/FWHK 08
FWCK/FWHK
10
FWCK/FWHK
12-16
FWCK/FWHK
22
VOLTAGE
50Hz
230 V / 1Ph 230 V / 1Ph
230 V / 3Ph 400 V / 3Ph 230 V / 3Ph 400 V / 3Ph 230 V / 3Ph
400 V / 3Ph
FWCK/FWHK 04 FWCK/FWHK 06
FWCK/FWHK 07
230 V / 1Ph
230 V / 1Ph
230 V / 1Ph 3 X 2,5mm
3 X 2,5mm 3 X 2,5mm
3 X 2,5mm
3 X 4mm 3 X 4mm
OPERATING LIMITS
WB.- Wet bulb temperature DB.- Dry bulb temperature
Water inlet temperature
Air inlet temperature into indoor section D.B/W.B
Air inlet temperature into indoor section D.B/W.B
Water inlet temperature
HEATING MODE
(*)
(*)
Up to 35
ºC mimimum or more than minimum water flo
w can be used.
Between 35
ºC and 43ºC nominal or more than nominal water flow can be used.
It is not possible to use minimum water flow for that range of temperatures.
43ºC
1N~230V-50Hz+PE
PE L N 1 2 19 20
ON/OFF
Flow
switch
Dry contact for
water pump
Alarm
12 13
PE
1 2 19 20
ON/OFF
Flow
switch
Dry contact for
water pump
Alarm
12 13
3~230V-50Hz+PE
L1 L2 L3
PE
1 2 19 20
ON/OFF
Flow
switch
Dry contact for
water pump
Alarm
12 13
3N~400V-50Hz+PE
L1 L2 L3 N
INSTALLATION GUIDE FOR CONTROL CABLE (TO AVOID INTERFERENCES):
• Use the screened 15 m cable supplied with terminal (3 wires + screen).
• Wire the cable separated from electrical power wiring by a physical distance of 500 mm.
• Wire the cable separated from halogen lamps/fluorescent tube lighting... by a phyisical distance of 500 mm.
• Wire the cable separated from radio frequency sources such as radio transmitter... at least 500 mm. NEVER WIND THE REMAINING CABLE AROUND, CUT THE CABLE BY THE TERMINAL END.
Local and national legislation has to be taken into account when the unit will be installed.
1
2
3
4
4
4
1 2
3
COOLING MODE
15ºC
35ºC
21ºC/15ºC 32ºC/23ºC
12ºC
30ºC
17ºC
24°C
5
FANS SPECIFICATIONS
Unit leaves the factory with pulley opened (1-1/2 V) turn.
FWCK/FWHK 22
120
3300
150
3000
180
2750
210
2500
0
4500304200603900903600
3750 3400
4060 3750 3450 3200 2900 2650 2300 ---
2250 --- ---
3100 2800 2550
HIGH SPEED MEDIUM SPEED LOW SPEED
HIGH SPEED MEDIUM SPEED LOW SPEED
HIGH SPEED MEDIUM SPEED LOW SPEED
HIGH SPEED MEDIUM SPEED LOW SPEED
HIGH SPEED MEDIUM SPEED LOW SPEED
HIGH SPEED MEDIUM SPEED LOW SPEED
HIGH SPEED MEDIUM SPEED LOW SPEED
Unit leaves the factory with three speeds connected.
Cooling only units leave the factory with three speeds connected. Heat pump units leave the factory with HIGH and MEDIUM speeds connected.
Unit leaves the factory with HIGH and MEDIUM speeds connected (the unit can not work in LOW speed).
Cooling only units leave the factory with three speeds connected. Heat pump units leave the factory with HIGH and MEDIUM speeds connected.
Unit leaves the factory with HIGH and MEDIUM speeds connected.
Unit leaves the factory with HIGH and MEDIUM speeds connected.
Unit leaves the factory with three speeds connected.
m /h
3
AVAILABLE STATIC PRESSURE Pa.
80
1700
100
1350
120
1000
140
---
0
2350202200402050601900
1860 1840 1750 1650
2200 2075 1950 1800
FWCK/FWHK 08
1550 1250 --- --­1375 1050 --- ---
AVAILABLE STATIC PRESSURE
Pa.
80
1500
100
1220
120
---
140
---
0
2250202150402000601800
1850 1820 1700
1525
2100 2000
1875
1675
FWCK/FWHK 10
1400 ---
---
---
1260 ---
---
---
AVAILABLE STATIC PRESSURE Pa.
80
2250
100
2050
120
1800
140
---
0
3100202850402650602450
1900 1800 1700 1600
2450 2300 2150 1975
FWCK/FWHK 12
1800 1600 --- --­1500 --- --- ---
3
m /h
3
m /h
3
m /h
3
m /h
3
m /h
3
3
AVAILABLE STATIC PRESSURE Pa.
AVAILABLE STATIC PRESSURE Pa.
AIR FLOW
AVAILABLE STATIC PRESSURE Pa.
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
80
950
100 800
120
---
140
---
0
1400201300401150601075
---
1100 1050 1000 925
FWCK/FWHK 07
800 --- --- ---
--- --- ------ --- ------
80
2250
100
2050
120
1800
140
---
0
3100202850402650602450
1900 1800
2450 2300 2150 1975
FWCK/FWHK 16
1800 --- --- ---
--- --- ---
--- --- ---
FWCK/FWHK 04
80
1150
100
1000
120 800
140 600
0
1550201450401350601250
675 660 650 640
1175 1160 1140 1050
FWCK/FWHK 06
950 790 600 --­625 --- --- ---
80
500
1000
1050209504085060700
750 700 600 500
950 850 750 650 450
---
---
---
---