Lennox FLATAIR FMC-H, FLATAIR, FLATAIR FIC-H, FLATAIR FSC-H Application Manual

lennoxemeia.com
FMC - H
FIC - H
FSC - H
FLATAIR
APPLICATION GUIDE
10 28 kW
FLATAIR AGU-MSL60-1505-E
• 1 •
2
4
5
7
8
9
10
17
18
25
28
FLATAIR
TM
Application Guide • FLATAIR-AGU-MSL60-1505-E
Ref : FLATAIR AGU-MSL60-1505-E
INDEX
All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
CONTENTS PAGE
1 - General description
2 - Denomination
3 - Range of products /technical features
4 - Operation limits
5 - Fan performances
6 - Sound level
7 - Capacities
9 - Electrical data
10 - Dimensions
11 - Installation
12 - Options
APPLICATION GUIDE
• 2 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
1 - GENERAL DESCRIPTION
FURNITURE
Painted in galvanized metal furniture, high resistant to corrosion. The units are provided with metal profi les, capable of withstanding the unit and able as well of installing the unit hung from the ceiling or mounted on the fl oor . Panels are easily inter exchangeable, giving several air suction and return alternatives. An insulation with a protection of mesh is used in indoor section with a classifi cation of M1 and F1, certifying that the material is auto-extinguishable and avoiding the fumes inside the room to be aconditionned. Auto extinguishable insulation M1 is used in outdoor units.
COMPRESSORS
All units are provided with scroll compressor, cooling by a suc­tion gas with thermic protection inside the engine, so no other additional protection is required.
It is mounted on anti-vibration devices both external and internal. All compresors are R410A
In heat pump units the compressors are provided with a crank­case heater to heat the oil in the compressor so that a suitable lubrication can take place.
AIR FILTER
Washable air fi lter; auto extinguishable material with M1 clas- sifi cation, high effi ciency fi ltrate with G2 classifi cation. It can be removed through the upper part and from both sides.
FAN
Outdoor and indoor fans are centrifugal with an assembled engine, statically balancing, with a low sound level.
Those fans are assembled to the inserted panel of the units and split from upper side of the fan with insulated materials to void vibrations.
EXCHANGER
Made-up with copper pipes and aluminium fi ngs, designed to get a high heat transfer.
Their dimensions and design of the refrigenrant circuit have been specially worked to obtain the maximum performance of the exchanger increasing the power of the unit and reducing the consumption.
COOLING CIRCUIT
Carried out with welded deshydratable copper pipes with pres­sure intakes with schraeder valves in the suction and liquid lines both indoors and outdoor units.
In unit 20-25-30 the pressure intakes in the outdoor section are approachable from the outer part of the unit.
The unit is equipped with both high-low pressure switches with an automatic reset. It also has a dehydrating fi lter , expansion system with restrictors in units 10-12-15; expansion valves in units 20-25-30. The heat pump units are equipped as well with a suction accumulator to avoid the liquid return to the compressor, 4 way valve and no-return valve.
ELECTRICAL CIRCUIT
Designed according to EN 60204-1 normative hermetically sealed to avoid condensation. With circuits breakers to protecto the unit from overloading.
1.1- GENERAL DESCRIPTION
The horizontal air conditioning units, range Flatair, cooling only or heat pump are air condensed units designed for small shopping center and housing. They can be supplied either compact or on split system. Due to their small dimensions they are designed for false ceiling and can be placed in air conducts both indoor and outdoor sec­tions. A wide range of optionals, completed-factory assembled are also available.
Flatair units are designed for false ceiling mounting, to be installed exclusively indoor. For outdoor moun­ting, a shelter or roof structure has to be installed, to avoid direct water entry in the sensible parts of the unit (electrical board, joints between the indoor unit and the outdoor unit).
• 3 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
1 - GENERAL DESCRIPTION
1.2- CONTROL
CLIMATIC 40 VERSION CLIMATIC 60 VERSION
We have two versions of Control in Flatair units:
- The basic C40 platform, wich includes one terminal in the unit and another DC40 remote
- The advanced platform C60 which includes one terminal in the unit, and 3 remote terminals as in option (DC, DS, DM)
CLIMATIC™ 60 controller intelligently improves effi ciency and helps set up and service operations to guarantee long lasting performance.
OPTIMIZED OPERATION AND SETUP SAVES ENERGY
CLIMATIC™ 60 is designed to provide the best energy
effi ciency throughout unit’s life cycle while ensuring reliable and consistent operation with user friendly interfaces. This new controller constantly monitors more machine parameters than ever to improve rooftop operation and maximize effi ciency and reliability
1.3- OPTIONS
Flatair units can be equipped with the following options:
- Main switch
- Heating electrical heater, made of blinded elements and assembled inside the unit
- Kit low ambient -15 degrees
- Kit low ambient 0 degrees (only for cooling units)
- 3 Phase controller (only for 3 phase units)
- Customer terminal DC60 (only for CLIMATIC 60 version)
- Service terminal DS60 (only for CLIMATIC 60 version)
- Remote duct sensor in return
- Ambient remote sensor (only en CLIMATIC 40 version)
- Thermostatic freecooling
- Enthalpic freecooling (only in CLIMATIC 60 version)
- Second return damper for kit freecooling
- Different airfl ow confi gurations in return and supply
- BMS communication interface (CLIMATIC 40 as standard and CLIMATIC 60 as an option)
- Echelon communication interface (CLIMATIC 60)
- Bacnet communication interface (CLIMATIC 60)
• 4 •
F
FLATAIR
F M C 015 S N M 1 M
M S
I
S
C H X
M
M
- - -
i
Application Guide • FLATAIR-AGU-MSL60-1505-E
2 - DENOMINATION
EXAMPLE :
Approximate Cooling capacity in kW
Revision number
Compact unit Outdoor unit Indoor unit
1 Circuit
Cooling only Heat pump Cooling only / heat pump
R410A
400V/3/50
FMC: Cooling only unit R-410A FMH: Heat pump unit R-410A
• 5 •
A BOX B BOX C BOX D BOX
FCM/FCH
10 12 15 20 25 30
kW 9.7 12 15 19.5 23.5 27
kW 10 12.5 15.5 20.5 25 27.9
mm 495 495 595 595 645 645 mm 1250 1250 1300 1450 1500 1500 mm 1250 1250 1330 1520 1800 1800
Kg 170 174 250 268 322 338
10 12 15 20 25 30
m3/h 3500 3400 4500 5650 6000 5850 m
3
/h 2350 2400 3740 4095 4760 5000
Pa 100 90 120 150 160 100
kg 112 116 165 159 202 208
mm 495 495 595 595 645 465 mm 1250 1250 1300 1450 1500 1500 mm 820 820 830 900 1025 1025
3/8" 3/8" 1/2" 5/8" 5/8" 5/8" 3/4" 3/4" 7/8" 7/8" 1-1/8" 1-1/8"
FIX 10 FIX 12 FIX 15
FIC/H
2O 20
FIC/H 25FIC/H
30
m3/h 2350 2300 3575 4850 5750 5500 m
3
/h 1500 1650 2410 2090 3455 3695
Pa 120 110 160 200 240 180
kg 58 58 85 109 121 131
kg 777788 kg 12 12 12 14 15 15 kg 24 24 24 28 30 30
mm 495 495 595 595 645 645 mm 1250 1250 1300 1450 1500 1500 mm 430 430 500 620 775 775
3/8" 3/8" 1/2" 5/8" 5/8" 5/8" 3/4" 3/4" 7/8" 7/8" 1-1/8" 1-1/8"
Application Guide • FLATAIR-AGU-MSL60-1505-E
3 - MAIN TECHNICAL FEATURES
Cooling capacity * (cooling only)
Heating capacity* (heat pump)
DIMENSIONS
Height Lenght Depth
NET WEIGHT
OUTDOOR UNIT FSC/FSH
Number & Type of compressor
FAN
Maximum airfl ow rate Minimum airfl ow rate Maximum available presure
(1)
NET WEIGHT DIMENSIONS
Height Lenght Depth
PIPES CONNEXIONS
Liquid m
3
/h
Gas m
3
/h
INDOOR UNIT FIX
Number & Type of compressor
FAN
Maximum airfl ow rate Minimum airfl ow rate Maximum available presure
(1)
NET WEIGHT OPTIONS WIEGHT
Electrical heater Free-cooling 1 damper Free-cooling 2 damper
DIMENSIONS
Height Lenght Depth
PIPES CONNEXIONS
Liquid m
3
/h
Gas m
3
/h
(*) Air intake temperature in the indoor exchanger :
27ºC DB/19ºC WB
(*) Air intake temperature in the outdoor exchanger: :
35ºC DB
(1) With admissible minimum air fl ow
DB Dry bulb temperature WB Wet bulb temperature
1 / Scroll
1 / Scroll
• 6 •
A 10-12 1250 1250 495 B15 1300 1330 595 C20 1450 1520 595 D 25-30 1500 1800 645
A 10-12 1250 430 495 B15 1300 500 595 C20 1450 620 595 D 25-30 1500 775 645
A 10-12 1250 820 495 B15 1300 830 595 C20 1450 900 595 D 25-30 1500 1025 645
FIH 10
2350 2140 1500
FIH 12
2300 2040 1650
FIH 15
3575 3170 2410
FIH 20
4850 4500 3090
FIH 25
5750 5470 3455
FIH 30
5500 5060 3695
FSH 10
3500 2970 2350
FSH 12
3400 2890 2400
FSH 15
4500 4250 3740
FSH 20
5650 5150 4095
FSH 25
6000 5600 4760
FSH 30
5850 5400 5000
FIC/H
FSC/H
Application Guide • FLATAIR-AGU-MSL60-1505-E
3 - MAIN TECHNICAL FEATURES
Box Unit Lenght Deep Height
Packaged
Indoor unit
Outdoor unit
3.2 MINIMUM, MAXIMUM AND NOMINAL AIRFLOW RATES
INDOOR UNIT
AIRFLOW RATE
Maximum Nominal Minimum
OUTDOOR UNIT
3.1 DIMENSIONS
AIRFLOW RATE
Maximum Nominal Minimum
• 7 •
10 12 15 20 25 30
FIX/FIC 58 58 85 109 121 131 FSC 112 116 165 159 202 208
FMC 170 174 250 268 322 338 FIX/FIH 58 58 85 109 121 131
FSH 117 121 170 164 207 213 FMH 175 179 255 273 327 343
777788 12 12 12 14 15 15 24 24 24 28 30 30
Application Guide • FLATAIR-AGU-MSL60-1505-E
OPERATION LIMITS FOR COOLING ONLY UNITS
3 - MAIN TECHNICAL FEATURES
Maximum temperatures Minimum temperatures
Cooling mode
Indoor temperature 32ºC DB / 23ºC WB 21ºC DB / 15ºC WB
Outdoor temperature Table 1
Standard unit : + 15ºC
0ºC(*) / -15ºC(**)
(*) With option kit low temperature 0ºC (**) With option kit low temperature -15ºC
DB.- Dry bulb temperature WB.- Wet bulb temperature
OPERATION LIMITS FOR HEAT PUMP UNITS
Maximum temperatures Minimum temperatures
Cooling mode
Indoor temperature
32ºC DB / 23ºC WB 21ºC DB / 15ºC WB
Outdoor temperature
Table 1
+ 15ºC STANDARD UNIT
0ºC(*) / -15ºC(**)
Heat pump mode
Indoor temperature
27ºC DB 15ºC DB
Outdoor temperature
Sizes 12-15-20-30 : 25ºC
(1)
Sizes 12-25 : 23ºC
-12ºC
(*) Active CL40 parameter to operate at 0ºC (**) With option kit low temperature -15ºC
(1) : Indoor temperature : 20°C DB.- Dry bulb temperature WB.- Wet bulb temperature
3.3 WEIGHTS
4 - OPERATION LIMITS
FLATAIR (STANDARD)
OPTIONS
MODEL
Cooling only units
Indoor unit Outdoor unit
Package (indoor+outdoor)
Heat pump units
Indoor unit Outdoor unit
Package (indoor+outdoor)
to add indoor unit
electrical heater free-cooling 1 damper free-cooling 2 damper
• 8 •
10 12 15 20 25 30
0
2350 2300 3575 4850 5750 5500
10
2275 2250 3495 4785 5730 5455
20
2240 2200 3410 4715 5705 5405
30
2190 2150 3330 4645 5670 5350
40
2140 2100 3250 4575 5630 5285
50
2080 2040 3170 4500 5580 5220
60
2025 1975 3095 4425 5530 5140
70
1975 1925 3020 4345 5470 5060
80
1925 1860 2945 4260 5405 4965
90
1840 1800 2875 4175 5330 4870
100
1775 1730 2800 4090 5250 4765
110
1625 1650 2735 4000 5165 4655
120
1500 ---- 2665 3910 5075 4640
130
--- --- 2600 3815 4975 4415
140
--- --- 2535 3720 4870 4285
150
--- --- 2470 3620 4755 4150
160
--- --- 2410 3520 4640 4005
170
--- --- --- 3415 4515 3855
180
--- --- --- 3310 4380 3695
190
--- --- --- 3200 4245 ---
200
--- --- --- 3090 4100 ---
210
--- --- --- --- 3945 ---
220
--- --- --- --- 3790 ---
230
--- --- --- --- 3625 ---
240
--- --- --- --- 3455 ---
10 12 15 20 25 30
0
3500 3400 4500 5650 6000 5850
10
3410 3325 4460 5550 5920 5755
20
3300 3160 4410 5450 5840 5665
30
3190 3075 4360 5350 5760 5575
40
3080 2980 4310 5250 5680 5485
50
2970 2890 4250 5150 5600 5400
60
2840 2790 4190 5050 5520 5315
70
2700 2690 4125 4945 5445 5235
80
2560 2580 4055 4840 4365 5155
90
2410 2400 3980 47365 5290 5075
100
2350 --- 3905 4630 5210 5000
110
--- --- 3825 4525 5135 ----
120
--- --- 3740 4420 5060 ----
130
--- --- --- 4315 4985 ----
140
--- --- --- 4205 4910 ----
150
--- --- --- 4095 4835 ----
160
--- --- --- --- 4760 ----
Application Guide • FLATAIR-AGU-MSL60-1505-E
5 - FAN PERFORMANCES
INDOOR UNITS
Nominal airfl ow rate
OUTDOOR UNITS
With option G4 additional pressure drop 50Pa Keep in mind reduction on air fl ow and static pressure services if you use muffl ers or
external air fi lter.
Available static pressure (Pa)Available static pressure (Pa)
Airfl ow rate (m3/h)
Airfl ow rate (m
3
/h)