FLEXYII-IOM-0409-E Page 97
Check HP / LP safety switches
Install manifold gauges on the circuit to be checked. Shut
down the axial fans and wait for the HP switch to shut
down the compressor: 29bar (+1 / -0) auto-reset 22bar (+
- 0.7) Reconnect fans. Switch off the centrifugal supply fan
and wait for the LP switch to cut out: 0.5bar (+ - 0.5) reset
1.5bar (+-0.5).
[] 15
Check outdoor fans and fan guards
Check the fan blades conditions and all fan guards and
protections
o 5
Check position of all sensors
Check the good positioning and operation of all sensors of
all sensors. Check the values given in the control system.
Replace sensor if necessary
o 5
Check and clean if necessary all fresh
air grilles
Check the fresh air grilles (if fitted). If dirty or damaged,
remove them from unit and clean with high pressure water
cleaner. Refit on unit once clean and dry.
o 5
Clean condensate drain, indoor and
outdoor coils (following local
regulations)
Visually check the coils for dirt. If not too dirty, cleaning
with a light brush may be enough (WARNING: Fins and
copper tubes are very fragile! Any damage WILL reduce
the performances of the unit). If very dirty, deep industrial
cleaning is required using de-greasing agents.(External
contractors must be called).
o / []
1h if
cleaning
Check electric heater element for
excessive corrosion
Isolate the unit; Pull the electric heater out of the heater
module box and check the resistances of traces of
corrosion; Replace resistance as required;
o
1h if
replacement
Check anti-vibration mountings, for
wear and tear.
Visually check anti-vibration mountings on compressors
and centrifugal fan. Replace if damaged.
o
1h if
replacement
Check refrigeration circuit for traces of
acid in the oil
Take a sample of oil from the refrigeration circuit. []
Check Glycol concentration in the HWC
circuit
Check the glycol concentration in the pressurised water
circuit. ( a concentration of 30% gives a protection down to
aprox. -15°C) check the circuit pressure
[] 30
Check defrost cycle with 4-way valve
inversion.
Switch the unit to heat pump mode. Change the set point
to obtain the standard defrost mode and reduce the cycle
time to the min value. Check the operation of the defrost
cycle.
[] 30
Gas burner module check for corrosion
Pull out the burner to access the tubes (refer to Gas burner
section in the IOM)
[] 30
Sweeping and cleaning the gas burner
Clean the in-shot burners and the blower wheel lightly with
a brush. Sweep the flue and flue box. Wipe-off the dust
from the housing of the motor. Clean combustion air inlet
louvers Pull-out baffles from the tubes, sweep the tubes
CHECK FLUE BOX GASKET
[] 30
Gas supply pressures / connections
checks
refer to Gas burner section in the IOM for details [] 15
Gas regulation valve settings refer to Gas burner section in the IOM for details [] 30
Check gas burner safety switches refer to Gas burner section in the IOM for details [] 30
MAINTENANCE PLAN