Lennox FCA 50, FCA 60, FCA 85, FCA 70, FCA 100 Installation Operating & Maintenance Manual

...
INSTALLATION OPERATING & MAINTENANCE MANUAL
ROOFTOP FLEXY
English Sept 2001
IOM / ROOF-TOP FLEXY™ Series - Page 1
CONTENTS
The present manual applies to the following ROOFTOP versions :
FCA 50 - FCA 60 - FCA 70 - FCA 85 - FCA 100 - FCA 120 - FCA 140 - FCA 160 - FCA 190 FCK 50 - FCK 60 - FCK 70 - FCK 85 - FCK 100 - FCK 120 - FCK 140 - FCK 160 - FCK 190 FHA 50 - FHA 60 - FHA 70 - FHA 85 - FHA 100 - FHA 120 - FHA 140 - FHA 160 - FHA 190 FHK 50 - FHK 60 - FHK 70 - FHK 85 - FHK 100 - FHK 120 - FHK 140 - FHK 160 - FHK 190 FDA 50 - FDA 60 - FDA 70 - FDA 85 - FDA 100 - FDA 120 - FDA 140 - FDA 160 - FDA 190 FDK 50 - FDK 60 - FDK 70 - FDK 85 - FDK 100 - FDK 120 - FDK 140 - FDK 160 - FDK 190 FGA 50 - FGA 60 - FGA 70 - FGA 85 - FGA 100 - FGA 120 - FGA 140 - FGA 160 - FGA 190 FGK 50 - FGK 60 - FGK 70 - FGK 85 - FGK 100 - FGK 120 - FGK 140 - FGK 160 - FGK 190
FXA 25 - FXA 30 - FXA 35 - FXA 40 - FXA 55 - FXA 70 - FXA 85 - FXA 100 - FXA 110 - FXA 140 - FXA 170 FXK 25 - FXK 30 - FXK 35 - FXK 40 - FXK 55 - FXK 70 - FXK 85 - FXK 100 - FXK 110 - FXK 140 - FXK 170
The technical information and specifications contained in this manual are for reference only. The manufacturer reserves the right to modify these without warning and without obligation to modify equipment already sold.
Ref. IOM-RT F-0901-E
IOM MANUAL
Page 2 - IOM / ROOF-TOP FLEXY Series
CONTENTS
INSTALLATION
TRANSPORT - HANDLING .............................................................................................. 3
INSTALLATION............................................................................................................... 10
INSTALLATION ON ROOF MOUNTING FRAME ........................................................... 11
INSTALLATION ON POSTS ........................................................................................... 13
COMMISSIONING .......................................................................................................... 14
OPERATION
AIR FLOW BALANCING ................................................................................................ 15
AIRFLOW BALANCING - FXA/FXK .............................................................................. 24
FILTERS .........................................................................................................................25
HOT WATER COILS....................................................................................................... 26
GAS BURNERS.............................................................................................................. 27
BEL T TENSIONING........................................................................................................ 34
PULLEYS........................................................................................................................ 35
CONTROL FUNCTIONS
USING THE KP 17 COMFORT DISPLA Y ...................................................................... 36
USING THE KP02 MAINTENANCE DISPLA Y ............................................................... 37
USING THE KP07 REMOTE GRAPHICAL DISPLA Y .................................................... 47
BMS CONT ACTS KIT ..................................................................................................... 56
CLIMATIC PARAMETERS .......................................................................................... 57
WIRING DIAGRAMS
ELECTRICAL WIRING DIAGRAMS ............................................................................... 63
ELECTRICAL WIRING DIAGRAMS LIST OF ITEMS .................................................... 74
TROUBLESHOOTING
SAFETY AND ERROR CODES ..................................................................................... 77
BEFORE CALLING FOR ASSIST ANCE ........................................................................ 82
PLANNED MAINTENANCE............................................................................................ 84
WARRANTY ................................................................................................................... 87
CERTIFICATES
AFAQ CERTIFICATION .................................................................................................. 88
CE CERTIFICA TION OF CONFORMITY........................................................................ 89
FILTERS FIRE CLASS ................................................................................................... 90
33 KW GAS BURNER CE CERTIFICA TION OF CONFORMITY................................... 91
60 KW GAS BURNER CE CERTIFICA TION OF CONFORMITY................................... 92
120 KW GAS BURNER CE CERTIFICA TION OF CONFORMITY................................. 93
180 kW GAS BURNER CE CERTIFICA TION OF CONFORMITY ................................. 94
INSULATION FIRE CLASS ............................................................................................ 95
IOM / ROOF-TOP FLEXY Series - Page 3
TRANSPORT - HANDLING
DELIVERY CHECKS
The equipment is shipped at the customers risk, and whose responsiblity it is to ensure that the products are in good working order on receipt by checking the following :
- The exterior has not been damaged in any way.
- The lifting and handling equipment are suitable for the equipment and comply with the specifications of the handling instructions enclosed herein.
- Accessories ordered for on site installation have been delivered and are in good working order.
- The equipment supplied corresponds with the order and matches the delivery note.
If the product is damaged, exact details must be confirmed in writing by registered post to the shipping company within 48 hours of delivery (working days). A copy of the letter must be addressed to Lennox and the supplier or distributor for information purposes. Failure to comply will invalidate any claim against the shipping company.
RA TING PLA TE
The rating plate provides a complete reference for the model and ensures that the unit corresponds to the model ordered. It states the electrical power consumption of the unit on start­up, its rated power and its supply voltage. The supply voltage must not deviate beyond +10/-15 %. The start-up power is the maximum value likely to be achieved for the specified operational voltage. The customer must have a suitable electrical supply. It is therefore important to check whether the supply voltage stated on the unit's rating plate is compatible with that of the mains electrical supply. The rating plate also states the year of manufacture as well as the type of refrigerant used with the required volume capacity of each compressor circuit.
STORAGE
When units are delivered on site they are not always required immediately and are sometimes put into storage. In the event of medium to long-term storage, we recommend the following procedures :
- Ensure that there is no water in the hydraulic systems.
- Keep the heat exchanger covers in position (AKILUX cover).
- Keep protective plastic film in position.
- Ensure the electrical panels are closed.
- Keep all items and options supplied in a dry and clean place for future assembly before using the equipment.
MAINTENANCE KEY
On delivery we recommend that you keep the key which is attached to an eyebolt in a safe and accesible place. This allows you to open the panels for maintenance and installation work. The locks are ¼ turn + then tighter (figure 2).
Figure 2
Figure 1
N˚ SERIE SERIAL NUMBER
TYPE UNIT TYPE
Usine Dijon Z.I. LONGVIC 21600 LONGVIC FRANCE
ANNEE YEAR
ALIMENTATION ELEC. SUPPLY
A. MAXI MAX. AMP.
REFRIGERANT FLUIDE
Kg/CIRC
C1 C3C2 C4
I. DEMARR. START UP AMP.
C. COMMANDE. CONTROL CIR.
V
V
A
Hz
FCK 190
2000
215 900-01/01
400 3 50
140 269
24
111111 11
R407C
Page 4 - IOM / ROOF-TOP FLEXY Series
Model Length Rain Width Height Weight
Cover
mm mm mm mm kg
FC*/FH* 050 downflow 2150 - 1780 1090 750 FC*/FH* 050 upflow 2150 - 1780 1120 750 FC*/FH* 050 horizontal flow 2150 - 1780 1120 750 FGA/FDA/FGK/FDK 050 2200 - 1900 1090 850 FC*/FH* 060 downflow 2821 629 2254 1410 1000 FC*/FH* 060 upflow 2821 629 2254 1410 1000 FC*/FH* 060 side discharge 2821 629 2254 1410 1000 FC*/FH* 060 centrif. condensing fan 2821 629 2254 2000 1100 FGA/FDA/FGK/FDK 060 2821 629 2254 1410 1100 FC*/FH* 070 downflow 2821 629 2254 1410 1000 FC*/FH* 070 upflow 2821 629 2254 1410 1000 FC*/FH* 070 side discharge 2821 629 2254 1410 1000 FC*/FH* 070 centrif. condensing fan 2821 629 2254 2000 1100 FGA/FDA/FGK/FDK 070 2821 629 2254 1410 1150 FC*/FH* 085 downflow 3781 629 2254 1495 1200 FC*/FH* 085 upflow 3781 629 2254 1495 1200 FC*/FH* 085 side discharge 3781 629 2254 1495 1200 FC*/FH* 085 centrif. condensing fan 3782 629 2254 2010 1430 FGA/FDA/FGK/FDK 085 2821 629 2254 1495 1300 FC*/FH* 100 downflow 3781 629 2254 1495 1200 FC*/FH* 100 upflow 3781 629 2254 1495 1200 FC*/FH* 100 side discharge 3781 629 2254 1495 1200 FC*/FH* 100 centrif. condensing fan 3782 629 2254 2010 1430 FGA/FDA/FGK/FDK 100 2821 629 2254 1495 1480 FC*/FH* 120 downflow 3582 629 2254 1410 1500 FC*/FH* 120 upflow 3582 629 2254 1410 1500 FC*/FH* 120 side discharge 3582 629 2254 1410 1500 FC*/FH* 120 centrif. condensing fan. 3582 629 2254 1910 1550 FGA/FDA/FGK/FDK 120 4030 629 2254 1410 1750 FC*/FH* 140 downflow 3582 629 2254 1410 1600 FC*/FH* 140 upflow 3582 629 2254 1410 1600 FC*/FH* 140 side discharge 3582 629 2254 1410 1600 FC*/FH* 140 centrif. condensing fan 3582 629 2254 1910 1650 FGA/FDA/FGK/FDK 140 4030 629 2254 1410 1950 FC*/FH* 160 downflow 3590 900 2254 2050 2000 FC*/FH* 160 upflow 3590 900 2254 2050 2000 FC*/FH* 160 side discharge 3590 900 2254 2050 2000 FC*/FH* 160 centrif. condensing fan 3590 900 2254 2050 2150 FGA/FDA/FGK/FDK 160 4040 900 2254 2050 2500 FC*/FH* 190 downflow 3590 900 2254 2050 2250 FC*/FH* 190 upflow 3590 900 2254 2050 2250 FC*/FH* 190 side discharge 3590 900 2254 2050 2250 FC*/FH* 190 centrif. condensing fan 3590 900 2254 2050 2350 FGA/FDA/FGK/FDK 190 4040 900 2254 2050 2750
TRANSPORT - HANDLING
DIMENSIONS AND WEIGHTS
IOM / ROOF-TOP FLEXY Series - Page 5
TRANSPORT - HANDLING
Model
Length Side Ventil. Width Height Weight
louver louver
mm mm mm mm mm kg
FX* 25 4070 490 600 1633 1055 950 FX* 30 4070 490 600 1633 1055 980 FX* 35 4750 490 600 2254 1290 1400 FX* 40 4750 490 600 2254 1290 1450 FX* 55 4750 490 600 2254 1290 1600 FX* 70 5050 890 600 2254 1725 1800 FX* 85 5050 890 600 2254 1725 1900 FX* 100 5050 890 600 2254 1725 2000 FX* 110 5650 860 2254 2000 2300 FX* 140 5650 860 2254 2000 2400 FX* 170 5650 860 2254 2000 2600
HANDLING
The equipment can be moved using the lifting holes on the top of the unit. The "sling" length is the value that we recommend for safe handling of the equipment.
Some units can only be supported by four slings at right­angles. Others require different lengths (see figure 3). It is essential that all lifting holes are used and that the slings are all of the same size to avoid damaging the equipment.
Sling length = 1580 mm for angle = 45°C
FC.../FH.../FD.../FG... 050
Sling length = 2210 mm for angle = 45°C
FC.../FH.../FD.../FG... 060 & 070
Page 6 - IOM / ROOF-TOP FLEXY Series
TRANSPORT - HANDLING
Sling length = 1855 mm for angle = 45°C
FC.../FH.../FD.../FG... 060 & 070 with centrifugal fans
Sling length = 2590 mm for angle = 45°C
Sling length = 2330 mm for angle = 64,5°C
FC.../FH.../FD.../FG... 085 & 100
Sling length = 2430 mm for angle = 45°C
FC.../FH.../FD.../FG... 085 & 100 with centrifugal fans
Sling length = 3230 mm
for angle = 45°C
Sling length = 2830 mm
for angle = 45°C
Sling length = 1870
mm
for angle = 45°C
IOM / ROOF-TOP FLEXY Series - Page 7
TRANSPORT - HANDLING
Sling length = 2080 mm for angle = 45°C
FC.../FH.../FD... 120 & 140
Sling length = 2700 mm for angle = 45°C
Sling length = 2410 mm for angle = 45°C
FC.../FH.../FD... 120 & 140 with centrifugal fans
Sling length = 2080 mm for angle = 45°C
FG... 120 & 140 with gas burner
Sling length = 2700 mm
for angle = 45°C
Sling length = 3000 mm
for angle = 45°C
Sling length = 1880 mm for angle = 45°C
Page 8 - IOM / ROOF-TOP FLEXY Series
TRANSPORT - HANDLING
Sling length = 2700 mm for angle = 45°C
FG... 120 & 140 with gas burner and centrifugal fans
Sling length = 3300 mm
for angle = 45°C
Sling length = 2080 mm for angle = 45°C
Sling length = 2090 mm for angle = 45°C
FC.../FH.../FD... 160 & 190
FC.../FH.../FD... 160 & 190 with centrifugal fans
Sling length = 2700 mm
for angle = 45°C
Sling length = 2320 mm for angle = 45°C
FG... 160 & 190
FG... 160 & 190 with centrifugal fans
Sling length = 3000 mm
for angle = 45°C
IOM / ROOF-TOP FLEXY Series - Page 9
TRANSPORT - HANDLING
FX 25 & 30
Sling length = 3000 mm
FX 35 - 40 - 55
Sling length = 3700 mm
Sling length = 3900 mm
FX 70 - 85 - 100
Sling length = 4300 mm
FX 110 - 140 - 170
Page 10 - IOM / ROOF-TOP FLEXY Series
PRELIMINARY CHECK
Before installing the equipment, the following items MUST be checked :
- Is there sufficient space for the equipment?
- Is the surface on which the equipment will be placed sufficiently solid to withstand its weight? A detailed study of the frame must be made beforehand.
- Do the supply and return ductwork openings excessively weaken the structure?
- Are there any obstructing items which could hinder the operation of the equipment?
- Does the electrical power available correspond to the equipment's electrical specifications?
- Does the noise level of the equipment meet the specification ?
- Is drainage provided for the condensate?
- Is there sufficient access for maintenance?
- Installation of the equipment could require different lifting methods which may vary with each installation (helicopter or crane). Have these been evaluated ?
- Ensure that the unit is installed in accordance with the installation instructions and applicable codes.
- Check to ensure that the refrigerant lines do not rub against the cabinet or against other refrigerant lines.
In general, make sure no obstacles (walls, trees or roof ledges) are obstructing the duct connections or hindering assembly and maintenance access.
INSINS
INSINS
INS
TT
TT
T
ALLAALLA
ALLAALLA
ALLA
TIONTION
TIONTION
TION
Figure 4
INST ALLA TION DEVICE
The surface on which the equipment is to be installed must be clean and free of any obstacles which could hinder the flow of air to the condensers:
- Avoid uneven surfaces
- Avoid installing two units side by side or close to each other as this may restrict the airflow to the condensers.
Before installing a packaged rooftop unit it is important to understand :
- The direction and position of air flows.
- The external dimensions of the unit and the dimensions of the supply and return air connections.
- The arrangement of the doors and the space required to open them to access the various components.
Figure 4 shows the required clearances and dimensions.
CONNECTIONS DEVICE
- Ensure that all the pipework crossing walls or roofs are secured and insulated.
- To avoid condensation problems, be sure all pipes are insulated according to temperatures of fluids and type of rooms.
NOTE : The AQUILUX covers which protect the finned surfaces must be removed prior to unit commissioning.
MODELS A B C D FC/FH/FG/FD
50 1000 1000 1000 2000 60 è 140 1400 1000 1400 2300 160 & 190 2000 1000 2000 2300
FX 25 & 30 * 1100 * 1700 35 è 55 * 1300 * 2300 70 è 100 * 1700 * 2300 110 è 170 * 2000 * 2300
* : according to connection
IOM / ROOF-TOP FLEXY Series - Page 11
2
INSTALLATION ON A ROOFMOUNTING FRAME
As levels are adjustable, observe the following recommendations for correct installation of the equipment.
Above all, ensure that all the flaps are facing outward (1 - figure 5). They are sometimes stored inside for transport.
Place the roof mounting frame on the trimmer beam by first lining up the inlet and then the outlet. (2 - figure 6).
After levelling the frame, fix the surface flaps onto the trimmer.
1
Figure 5
Figure 6
Figure 7
Page 12 - IOM / ROOF-TOP FLEXY Series
INSTALLATION ON A ROOFMOUNTING FRAME
When the frame is correctly positioned, it is essential to secure the assembly with a disconnected welding seam (20 to 30 mm for every 200 mm) along the outside, or by using an alternative method (1 - figure 8).
Assembly joint (1 - figure 9) Insulate the frame before installation. We recommend the
minimum application of 20 mm thick insulation. Check that the covering is continuous and apply a seal (2 ­figure 9).
CAUTION : To be effective, the upstream must end below the drop edge (3 - figure 9)
Before installing the equipment, make sure that the assembly seal or the puttying is not damaged and check that the unit is fixed to the mounting frame so that it is resting flat on the frame. Once in position, the bottom of the equipment must be horizontal.
The installer must comply to local authority standards and specifications.
1
2
3
Figure 9
1
Figure 8
IOM / ROOF-TOP FLEXY Series - Page 13
INSTALLATION ON POSTS
The unit can be fitted on corner posts using the frame provided. The minimum height of the posts should be 400mm.
Figure 10
Page 14 - IOM / ROOF-TOP FLEXY Series
This work must only be carried out by trained refrigeration engineers
Before connecting to the power :
- Ensure that the power supply between the building and the unit meets local authority standards and that the cable specification satisfies the start-up and operating conditions.
- Ensure that the electrical connections in the control panel and on the motors are secure.
- Ensure that all drive motors are secure.
- Ensure that the adjustable pulley blocks are secure and that the belt is tensioned with the transmission correctly aligned.
- Using the electrical wiring diagram, check the conformity of the electrical safety devices (circuit breaker settings, presence and rating of fuses).
At this point attach the manometers to the refrigerant circuit
Powering up the system with the unit isolating switch
- Check the direction of rotation of the fans by pressing their contactors. Refer to the rotation arrows situated next to the coils or fans (NOTE: unlike a coil, a fan rotating in the wrong direction may fail).
- The fans' direction of rotation is checked during an end of production test. They should therefore all turn in either the right or wrong direction.
- If they turn in the opposite direction, disconnect the power supply to the machine at the building's mains switch, reverse two phases of the incoming supply to the machine and try again.
- If only one of the fans rotates in the wrong direction, disconnect the power supply at the machine's isolating switch and reverse two of the component initial phases on the terminal within the electrical panel.
Using CLIMA TIC
- Check the voltages recorded against the rated values, in particular on the system supply fans.
- If the readings on the fans are outside the limits, this indicates excessive air flow which will affect the thermodynamic performance. Refer to the "Air Flow Balancing" section.
Thermodynamic readings using manometers and prevailing environmental conditions
- No rated values are given here. These depend on the climatic conditions both outside and inside the building during operation. However, an experienced refrigeration engineer will be able to detect any abnormal machine operation.
COMMISSIONING
Safety Test
- "Clogged filter" detection test : vary the setpoint value (KP02 setpoint 93) in respect to the air pressure value (KP02, variable 16). Observe the response of the CLIMATIC™.
- Same procedure for detecting "Missing Filter" (setpoint
94) or "Air Flow Detection" (setpoint 92).
- Check the smoke detection function.
- Check the Firestat by pressing the test button.
- Disconnect the circuit breakers of the capacitor fans and check the high pressure cut-out points on different refrigerant circuits.
Reverse Cycle Test
On reversible units this test is used to check the switching of the 4-way valves. Start the reverse cycle with reference to the cold or hot temperature threshold data according to the climatic conditions at the time of testing (setpoint 15 + setpoint 16).
Your machine is now operational. You can now proceed to the setting stage. See the "Control" section.
IOM / ROOF-TOP FLEXY Series - Page 15
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
The actual resistance of ductwork systems is not always the same as the calculated theoretical values. To rectify this, it may be necessary to modify the pulley and belt setting. To this effect, the motors are fitted with variable pulleys.
TEST
You should already have measured the + ve pressure experienced on fan discharge, as well as the pressure experienced in the return duct to the fan. Measure the motor absorbed power.
If the absorbed power is greater and the pressure lower than the rated values, your system has a lower pressure drop than anticipated. Reduce the flow. If the system resistence is significantly lower than design, there is a risk that the motor will overheat resulting in an emergency cut out.
If the absorbed power is lower and the pressure greater than the rated values, your system has a higher pressure drop than anticipated. Increase the flow. At the same time you will increase the absorbed power which may result in having to fit a larger motor.
To carry out the adjustment and to avoid a time-consuming re-start, stop the machine and if necessary lock the main switch.
First unscrew the 4 Allen screw(s) on the pulley (see figure
11).
Figure 12
Slacken the belts, then remove then (see § "BELT TENSION"). The flow can now be increased by turning the flange(s) to
move them closer (or alternatively, move them apart to reduce the flow). For two-groove pulleys, turn the flanges the same number of turns.
If necessary, check the pulley diameter by measuring the outer diameter of a belt positioned in the groove (figure 12).
Finally, replace and tension the belts before carrying out a test. Re-check the absorbed power levels. Repeat the operation until a satisfactory result has been achieved.
To minimise the number of operations, refer to the flow / pressure charts on the following pages for the type of fans used. With reference to the following example, you can estimate your flow and thus calculate the necessary adjustment.
ALLEN wrench 4
Figure 11
Page 16 - IOM / ROOF-TOP FLEXY Series
UNIT/F AN KIT REFERENCE TABLE
CHART (see following pages)
Size Fan type A B C D E F
50 FCx or FHx 1
FGx or FDx 1
60 FCx or FHx 1
Centrifugal condensor 1 (*) FGx or FDx 2
70 FCx or FHx 1
Centrifugal condensor 1 (*) FGx or FDx 2
85 FCx or standard FHx 1 (*)
FCx or side FHx 2 Centrifugal condensor 2 FGx or FDx 2
100 FCx or standard FHx 1 (*)
FCx or side FHx 2 Centrifugal condensor 2 FGx or FDx 2
120 FCx or standard FHx 2
FCx or side FHx 2 Centrifugal condensor 2 (*) FGx or FDx 2
140 FCx or standard FHx 2
FCx or side FHx 2 Centrifugal condensor 2 (*) FGx or FDx 2
160 FCx or standard FHx 2
Centrifugal condensor 4 FGx or FDx 2
190 FCx or standard FHx 2
Centrifugal condensor 4 FGx or FDx 2
ROOF-TOP type FX*
Size Fan type ABCDEF
25 Supply 1
Extract 1
30 Supply 1
Extract 1
35 Supply 1
Extract 1
40 Supply 1
Extract 1
55 Supply 1
Extract 1
70 Supply 1
Extract 1
85 Supply 1
Extract 1
100 Supply 1
Extract 1 (*)
110 Supply 2
Extract 2
140 Supply 2
Extract 2
170 Supply 2
Extract 2
The number indicated in the table refers to the number of fans. 1(*) : In this case the two fans are coupled to the same shaft. 2(*) : Indicates that there are 2 groups of 2 coupled fans.
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
IOM / ROOF-TOP FLEXY Series - Page 17
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
EXAMPLE :
You may want to adjust a FHK 120 set to 22 000 m3/h with a system resistance of 150Pa: The machine has 2 fans (chart D). For this operating point, the unit supplied is fitted with E kits comprising 112 mm - 131 mm variable pulleys on the motors and 250 mm pulleys on the fans. In this case the pulley motor adjustment is 126 mm for a fan speed of 730 rpm.
On the chart, for 11 000 m3/h (2 fans), indicates 730 rpm (point A).
Total pressure 500 Pa (150 Pa system pressure + 230 Pa equipment loss + 120 Pa static pressure)
Absorbed power 2.1 kW, which gives 5.7 A, calculated as follows: In = (P.kw x Ct / Rm ) / ( 3 x U x cos
ϕϕ
ϕϕ
ϕ) = ( 2100 * 1.2 / 0.8 ) / ( 3 x 400 x 0.8 ) = 5.7A
Rm = Motor output Ct = Transmission coefficient
On site you measure :
System static pressure 70 Pa or total pressure 230 Pa (the pressure must be measured after 1 m minimun on the return ductwork)
Absorbed power 6.8A
The theoretical absorbed power will be : P = (
3 x 400 x 6.8 x 0.8 ) / 0.8(Rm) x 1.2(Ct) = 2,500 W
With reference to the chart data, the operating point B has been highlighted as we note that: the system is exceeding design airflow rates. 12 700 m
3
/h and 25 400 m3/h can be read for the two fans instead of the 22,000 m3/h specified.
To return to the design flow, consider point C, which now gives a rotation speed of 650 rpm, i.e. a variable pulley adjustment of : Adjustment = fan speed / motor speed * pulley diameter = 650 / 1450 * 250 = 112 mm.
Alternatively, where there is reduced airflow, i.e.caused by a greater system resistance than anticipated (items B and C), follow the same procedure, but in this case ensure that the absorbed power at C' is compatible with the motor fitted.
Pression dynamique
Pression statique demandée
Pression totale mesurée
Pression statique mesurée
730 RPM
650 RPM
Page 18 - IOM / ROOF-TOP FLEXY Series
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
CHART A
IOM / ROOF-TOP FLEXY Series - Page 19
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
CHART B
Page 20 - IOM / ROOF-TOP FLEXY Series
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
CHART C
IOM / ROOF-TOP FLEXY Series - Page 21
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
CHART D
Page 22 - IOM / ROOF-TOP FLEXY Series
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
CHART E
IOM / ROOF-TOP FLEXY Series - Page 23
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCINGAIR FLOW BALANCING
AIR FLOW BALANCING
CHART F
Page 24 - IOM / ROOF-TOP FLEXY Series
A. Set the unit to the "recycle air" position (figure 15) B. Measure the static pressure in the areas indicated 1/2/
3/4/5/6
C. Before proceeding further, check that the pressure
difference between zones 1 and 4 satisfies the static pressure required.
If this is not the case, refer to the
"AIR FLOW
BALANCING"
section.
D. If the flow and the pressure are correct :
On grills "b" and "b", bring the pressure at 5 to the same level as 3 (the grills must be moved simultaneously by the same amount).
E. Check that the power absorbed by the extract fan
motor is less than its rated power. If the values are not the same, refer to the
"AIR FLOW
BALANCING"
section.
F. Switch the unit to "fresh air" (figure 16), and measure
the static pressure at 2/3/4/5/6.
G. Adjust grill "a" so that the value measured at 3 is the
same as the value at point B.
H. Finally check that the pressure at 5 is the same as the
pressure measured at point B. If not, slightly adjust the grill "b" setting of the fresh air by-pass.
1
2 3 4 5
6
a
b, b'
Figure 15
FX in "recycle air" position
Figure 16
FX in "fresh air" position
AIRFLOW BALANCING - FXA/FXKAIRFLOW BALANCING - FXA/FXK
AIRFLOW BALANCING - FXA/FXKAIRFLOW BALANCING - FXA/FXK
AIRFLOW BALANCING - FXA/FXK
The FX* models are designed to operate with more complex supply and extract ductwork systems. Without balancing there are numerous risks :
- Fan motor overvoltage
- Significant flow variations depending on the position of the dampers, which affects the building concerned, especially when applied to pressure balanced systems.
To rectify this we have fitted an equilizing grill on the fresh air dampers. The grill can be moved after unscrewing the knurled nuts (1 - figure 14) and operates as an adjustable damper.
Before starting to adjust fully open the equilising grills.
To equilise, proceed as follows :
Example :
Zone 1 2 3 4 5 6
Technical specification Pa 200 -180 Recycled air without setting Pa 190 -230 -210 -190 -70 -120 Recycled air after setting b/b Pa 190 -230 -210 -190 -210 -240 Fresh air before setting Pa 270 -80 -50 -200 -220 -250 Fresh air after setting grill a Pa 190 -230 -210 -200 -220 -250 Fresh air after setting grill b Pa 190 -230 -210 -190 -210 -240
Extracted air
Fresh air
Discharge
Grill b'
fresh air by pass
Figure 14
1
Supply air
IOM / ROOF-TOP FLEXY Series - Page 25
filfil
filfil
fil
tersters
tersters
ters
The CLIMATIC controls the filters. Two types of problems may occur :
1 - 004 error code (lit LED “filter”) or the following icon (for a
graphics screen - KP07) :
Item 8 on KP 17 indicates that the filters must be changed. The unit has not stopped but the airflow is likely to be reduced due to increased pressure drop acros the filters.
2 - 005 error code or the following icon (for a graphics screen - KP07) :
Item 9 on KP17 indicates that the filters are out of position : either they have been damaged or not been replaced during maintenance. In the latter case, the unit has not stopped but the increased flowrate may result in the motor overheating. It is important to check the filter immediately.
FIL TER REPLACEMENT :
After opening the filter access panel, unscrew the butterfly nuts maintaining the filter support and remove it (figure 18).
Remove the cells that are slide-mounted (figure 19). Use the rod in the lower filter section to remove the cells at the botton of the sliders.
Install new filters inside the sliders.
Figure 17
Figure 18
Figure 19
KP 17 DISPLAY
Page 26 - IOM / ROOF-TOP FLEXY Series
HOHO
HOHO
HO
T WT W
T WT W
T W
AA
AA
A
TER COILSTER COILS
TER COILSTER COILS
TER COILS
HYDRAULIC CONNECTIONS
The heating coil is connected to the isolating valves. Two keys must be used to tighten the connections, one of the keys maintains the valve body. Failure to use two keys may damage the pipes and invalidates the warranty.
Proceed as follows :
- Open the stop valves and set the 3-way valve to the intermediate position (manual position and turn the thumbwheel to a mid position).
- Fill the hydraulic system and bleed the battery using the air vent (figure 20).
- Check the connections for possible leaks.
- Reset the 3-way valve to automatic.
PROTECTION AGAINST FREEZING
1) Use glycol water
GLYCOL IS THE ONLY
EFFECTIVE PROTECTION AGAINST FREEZING
The antifreeze must protect the unit and avoid icing under winter conditions. Warning : monoethylene glycol-based antifreeze may produce corrosive agents when mixed with air.
2) Drain the installation You must ensure that the manual or automatic air vents have
been installed on all high points in the system. In order to drain the system check that all the drain cocks have been installed on all low points of the system. To drain, open all the valves and remember to place the unit in air.
A HEATING COIL FROZEN DUE TO LOW AMBIENT CONDITIONS IS NOT COVERED BY THE WARRANTY.
Figure 21
Figure 20
Figure 22
ELECTROLYTIC CORROSION
Attention is drawn to the corrosion problems resulting from electrolytic reaction created from unbalanced earth connections.
ANY COIL DAMAGED BY ELECTRONIC
REACTION IS NOT COVERED BY THE
WARRANTY.
CONDENSA TE DRAINS
The traps are not assembled when delivered and are stored in the electrical panel with their clamping collars. To assemble them, insert them on the condensate tray outlets and use a screwdriver to tighten the collars (Figure 22).
IOM / ROOF-TOP FLEXY Series - Page 27
GAS BURNERGAS BURNER
GAS BURNERGAS BURNER
GAS BURNER
PRELIMINARY CHECKS ON COMMISSIONING
NOTE : Any work on the gas system must only be carried out by qualified personnel.
CAUTION : Smoking is forbidden during any intervention on the gas components.
Make sure that the gas supply line installation conforms to the latest technology and the local safety regulations. Check that the gas supply line can provide the burners with the pressure and the gas flow rate necessary to provide the heating output duty.
Bleed the air in the gas delivery pipes by loosening the nuts of the copper tubes on the gas solenoid valve inlet by two turns. Tighten properly after bleeding.
Measure the pressure on the gas solenoid valve inlet (5 - figure
24), with the appliance at its rated value. The rated value must be 20 mbar ± 2 for natural gas and 37 mbar ± 3 for propane. If this is not the case, consult the gaz supplier or see the following "Pressure reducing valve" section in the event of the appliance being pwered by natural gas at 300 mbar.
Check that the supply voltage of the ignition control box(es) is between 220 and 240V.
Check that the air inlet combustion vents and the smoke extract vents are not blocked.
Check that the supply air flow is correct.
IGNITION DET AILS
Make sure that the gas line valves are open. With the ROOF TOP working (Setpoint 06 to ON), adjust
settings 59 and 60 to ON to start the priority. Increase setting 1 (threshold temperature) to a temperature greater than the ambient temperature (Var. 1) This in turn produces a heating demand and starts the burner.
The control box supply switch (KM21) closes and the burner fan (VIN1) starts. When the depression in the fan is reached, the pressostat (B21) tips.
After a pre-ventilation period (approx. 30 seconds) the gas valve (YV51) opens and the firing sequence (ignition electrode B6) is initiated.
Once the ionization probe detects the flame, the burners functions normally.
If, when the ignition sequence is over, the ionization sensor (B4) does not detect a flame, the burner disconnects and CLIMATIC indicates the fault after a six-minute time delay.
If the flame goes out during normal operating, the control restarts the firing sequence with pre-ventilation until a flame has been detected or there is disconnection.
When a burner has two gas tiers, the procedure for the second tier is similar but the references are as follows :
- KM22 for the supply switch
- VIN2 for the fan
- B22 for the gas exhaust pressure switch
- YV52 for the gas valve
- B7 for the ignition electrode and
- B5 for the ionization sensor.
Page 28 - IOM / ROOF-TOP FLEXY Series
GAS BURNERGAS BURNER
GAS BURNERGAS BURNER
GAS BURNER
PRESSURE REDUCING VALVE SETTING
- Connect the tube of the manometer to the power pressure inlet of a solenoid valve (5-figure 24) after loosening the screw.
- Remove the safety plug of the expansion valve setting.
- Use a screwdriver to pre-set by placing the screw at a depth of 34 mm.
- Place the burner(s) in operation at maximum power and set the output pressure. Turn (clockwise) to increase the pressure and (anticlockwise) to reduce it.
- When the pressure has been set, replace the safety plug.
- Disconnect the pressure gauge and retighten the screw.
PRESSURE REGULATOR CONTROL OR SETTING
This is located on the burner tiers (1 – figure 24) of the gas control assembly.
- Increase the value of set point 1 (temperature set point) to a temperature higher than room temperature ) (variable 1).
- Wait until the operation of the burner(s) reaches maxi­mum power.
- Connect the tube of the manometer to the injection pressure inlet after having loosened the screw (4-figure
24).
- Wait until a stable pressure is displayed on the pressure gauge.
- Use a 8 mm key to adjust the maximum pressure (3 – figure 24) – clockwise to increase it and anticlockwise to reduce it. The maximum pressure must always be set before setting the minimum pressure.
- The minimum pressure must be measured if the regulator is not supplied. By disconnecting the tracer wire 116 on card EF45 or EF46 for the one-ramp module or the upper ramp of the two-ramp module. It can be adjusted with a 3.5 mm screwdriver on the screw located inside the maximum pressure setting.
- For the setting of the second ramp, disconnect the tracer wire 116 or 126 in order to switch to low speed.
Figure 23
1
2
3
4 5
Pressure taps : (4) : Injection (5) : Supply
Figure 24
- Manipulate the regulator several times by connecting and disconnecting wire 116 or 126 in order to check the low and high speed settings.
Note : The maximum pressure setting affects the minimum pressure setting and may have to be changed.
- When the settings are correct, connect wires 116 and 126, making sure they are properly tightened, remove the pressure gauge and replace the safety cap.
- Restart the unit and watch the burner complete several full cycles to ensure that all the components are working properly.
NOTE : The minimum and maximum pressure settings corresponding to the various gas types are listed in the table at the end of this manual.
IOM / ROOF-TOP FLEXY Series - Page 29
1
IGNITION ELECTRODE
The following two checks can be made :
- Ensure that the electrode tip (1 – figure 25) is always sharp and oxide-free. Use some sand paper to clean it, if necessary.
- The space between the tip and the air duct must be 3 mm approx. (2 – figure 26).
IONISA TION SENSOR
- The sensor must be placed in the air duct at approximately 12.5 mm from the burner (3 – figure 27).
Check that the position is correct in the flame (see figure 28). It must be placed just after the flame front. There is no ionisation inside the blue cone. It reduces and reaches the end of the flame afterwards.
2
3
GAS BURNERGAS BURNER
GAS BURNERGAS BURNER
GAS BURNER
Figure 25
Figure 26
Figure 27
Figure 28
Cône bleu
Loading...
+ 70 hidden pages