Lennox EVB125, EVB130 Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
B-VENT GAS FIREPLACE HEATER INSERT
Elite™ Series, Model: EBVI25 & EBVI30
Suitable for installation into masonry or factory built fi replaces.
Report No. 116-F-15-5
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline or other fl ammable vapors or liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• If your gas supplier cannot be reached, call the fi re department.
Installation and service must be performed by a qualifi ed installer, service agency or the gas sup­plier.
RETAIN THIS MANUAL FOR FUTURE REFERENCE
P/N 775,154M B, 7/2004
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D’INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d’essence ni d’autre vapeurs ou liquides infl ammables dans le voisinage de cet appareil ou de tout autre appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournis­seur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies. L’installation et service doit être exécuté par un qualifi é installeur, agence de service ou le fournisseur de gaz.
Page 2
CONGRATULATIONS ON THE PURCHASE OF YOUR NEW GAS APPLIANCE MANU­FACTURED BY LENNOX HEARTH PRODUCTS.
When you purchased your new gas fi red heater, you joined the ranks of thousands of concerned individuals whose answer to their home heating needs refl ects their concern for aesthetics, effi ciency and our environment. We extend our continued support to help you achieve the maximum benefi t and enjoyment available from your new gas fi red heater. It is our goal at Lennox Hearth Products to provide you, our valued customer, with an appli­ance that will ensure you years of trouble free warmth and pleasure. Thank you for selecting a Lennox Hearth Products gas fi red heater as the answer to your home heating needs.
Sincerely, All of us at Lennox Hearth Products
TABLE OF CONTENTS
Packaging List page 2 Introduction page 2 General Information page 3 Questions/Building Offi cials page 4 High Altitude page 4 Fireplace Requirements page 4 Specifi cations page 5 Clearance to Combustibles page 7 Step 1 Preparation page 8 Step 2 Clean Fireplace page 8 Step 3 Unpack the insert. page 9 Step 4 Lift Insert into Position page 9 Step 5 Remove Glass Door page 9 Step 6 Remove Firebox Contents page 9 Step 7 Install LP Conv. (if necessary) page 9 Step 8 Install Venting page 9 Step 9 Connect Gas Line page 12 Step 10 Purge Air page 12 Step 11 Install Log Set page 13 Step 12 Reinstall Front Glass Door page 14 Step 13 Perform Leak Test page 14 Step 14 Install Surround Assembly page 14 Step 15 Install Wall Thermostat page 14 Step 16 Check Appliance Operation page 14 Step 17 Perform Spillage Test page 16 Step 18 Check Blower Operation page 16 Step 19 Adjust Burner page 17 Step 20 Install Louver Kit page 17 Rating Plates page 18
This installation manual will help you obtain a safe, effi cient, dependable installation for your appliance and vent system.
PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE BEGINNING YOUR INSTALLATION.
This appliance may be used with a thermo­stat (see Optional Wall Thermostat). This appliance is certifi ed for use in bedrooms. If installed in a bedroom in Canada, a ther­mostat IS required.
PACKAGING LIST
The assembled vented gas fi replace heater is packaged with:
• One accessory package containing a literature package (installation and operation instruction manuals) is located on top of the appliance.
• One log set, one bag of embers, one bag of vermiculite, one propane conversion kits.
• One Warranty Certifi cate.
• One Fireplace Warning Label.
• One Draft Hood Sliding Tool.
SURROUND ASSEMBLY SOLD SEPA­RATELY
MODEL: EBVI25
SKS-25, Surround Kit, Small (41 1/16" W x 26 1/16" H) SKM-25, Surround Kit, Medium (44 1/8" W x 27 5/8" H)
MODEL: EBVI30
SKS-30, Surround Kit, Small (40 1/4" W x 27 1/2" H) SKM-30, Surround Kit, Medium (45 3/4" W x 30 1/4" H) SKL-30, Surround Kit, Large (49 1/4" W x 30" H)
INTRODUCTION
This appliance complies with National Safety Standards and is tested and listed by OMNI-Test Laboratories Inc.; Beaverton, Oregon (Report No. 116-F-15-5) to ANSI Z21.88-2002 (in Canada, CSA-2.33-2002), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fi red room heater.
Installation must conform to local codes. In the absence of local codes, installation must comply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code.) Electrical wiring must comply with the National Elec­trical Code ANSI/ NFPA 70 - latest edition. In Canada, the current CSA C22-1 Canadian Electrical Code - latest edition.
This appliance requires an adequate supply of combustion and ventilation air. As an aid in determining whether or not these requirements have been satisfi ed, follow the procedure indicated in the section entitled Spill Test Procedure (see page 16).
This gas fi replace heater is a natural con­vection, heat circulating gas fi replace insert designed for residential applications.This heater is designed to be installed into an exist­ing masonry or factory built solid fuel burning fi replace only - Masonry fi replace must be built to UBC 37 or ULC S628 standards and factory built (zero clearance) fi replace must be listed to UL 127 or ULC S610. Units must use a 4” listed B-Vent or listed liner (conforming to UL 1777) from the appliance outlet to the chimney termination. The venting system must be routed through the existing fi replace fl ue system to the vent termination.
This millivolt appliance is designed to oper­ate on natural gas or propane gas only.
A millivolt gas control valve with piezo igni­tion system provides safe, effi cient operation. External electrical power is required to operate the blower.
This unit is factory set for use with Natural Gas and will require a fi eld conversion for use with Propane (other fuels are NOT allowed). The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERA­TION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
The millivolt appliance is manually con­trolled and features a spark igniter (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage.
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 3
This appliance uses a millivolt type control system consisting of a gas control valve with regulator (control to adjust for fl ame appear­ance and heat output), a standing pilot burner assembly, a thermopile, thermocouple, a piezo igniter, and ON/OFF switch. All exhaust gases must be vented outside the structure. Combustion air is drawn from the room where appliance is installed. THE GAS BURNER SYSTEM ON THIS APPLIANCE DOES NOT REQUIRE 120 VOLT POWER TO OPERATE. However, the heat circulation blower requires 120 Volt power (the appliance can be safely used with the blower turned off). The blower operation is controlled by a variable speed rheostat located on the left side surround panel (if optional surround is installed) and temperature switch located beneath of fi rebox bottom on the front left side.
GENERAL INFORMATION
The appliance installation, repair and annual inspection should be performed by a quali­fi ed service person. It is imperative that the control compartment, burners and circulat­ing air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instructions d'installation et d'utilisation qui accompagnent l'appareil.
Provide adequate clearances and adequate accessibility clearance for service and proper operation.
Table 1 shows the BTU input:
Millivolt Models with
Manually-Modulated Gas Valves
Nat. Gas Propane
Model No. Input Rate
(BTU / HR)
EBVI25 17,000 to
25,000
EBVI30 21,500 to
30,000
Table 1
Input Rate (BTU / HR)
19,500 to
25,000
22,000 to
28,000
Tables 2 and 3 show the gas pressure requirements for this appliance:
Manifold Gas Supply Pressure (all models)
Fuel # Low High
Natural
Gas
Propane (Lo) 6.3" WC
Table 3
(Lo) 1.6" WC
(.40 kPa)
(1.57 kPa)
(Hi) 3.5" WC
(.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Test gauge connections are provided on the front of the millivolt gas control valve (identi­fi ed IN for the inlet and OUT for the manifold side). See Figures 32 & 33.
Table 4 shows the gas orifi ce size for the elevations indicated.
Model
No.
EBVI25 #41
EBVI30 #37
Table 4
Orifi ce Size Elevation
Nat.
Gas
(.096")
(.104")
Prop.
Gas
#53
(.0595")
1/16"
(.0625")
(meters)
0-4500
(0-1372)
0-4500
(0-1372)
Feet
This appliance must be isolated from the gas supply piping system (by closing it's individual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
This appliance and it's individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures greater
than 1/2 psig (3.5 kPa).
THIS APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY OR FLUE SERVING A SEPA­RATE SOLID FUEL BURNING APPLIANCE.
WARNING: THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM. OPERATION OF THIS GAS APPLIANCE WHEN NOT CONNECTED TO A PROPERLY INSTALLED AND MAINTAINED VENTING SYSTEM CAN RESULT IN CARBON MONOXIDE (CO) POISONING AND POSSIBLE DEATH.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED, PROFESSIONAL SERVICE TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY PARTS OF THE CONTROL SYSTEM AND ANY GAS CONTROLS WHICH HAVE BEEN UNDER WATER.
NE PAS SE SERVIR DE CET APPAREIL S'IL A ÉTÉ PLONGÉ DANS L'EAU, COMPLÈTEMENT OU EN PARTIE. APPELER UN TECHNICIEN QUALIFIÉ POUR INSPECTER L'APPAREIL ET REMPLACER TOUTE PARTIE DU SYSTÈME DE CONTRÔLE ET TOUTE COMMANDE QUI ONT ÉTÉ PLONGÉS DANS L'EAU.
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING INSTRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OPERATING APPLI­ANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGEROUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERIOUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OR CARBON MONOXIDE POISONING.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES À COTE DE L'APPAREIL.
Inlet Gas Supply Pressure (all models)
Fuel # Minimum Maximum
Natural Gas 4.5" WC
(1.12 kPa)
Propane 11.0" WC
(2.73 kPa)
Table 2
10.5" WC
(2.61 kPa)
13.0" WC
(3.23 kPa)
CARBON MONOXIDE POISONING: EARLY SIGNS OF CARBON MONOXIDE POISONING ARE SIMILAR TO THE FLU WITH HEAD­ACHES, DIZZINESS AND/OR NAUSEA. IF YOU HAVE THESE SIGNS, OBTAIN FRESH AIR IMMEDIATELY. TURN OFF THE GAS SUPPLY TO THE APPLIANCE AND HAVE IT SERVICED BY A QUALIFIED PROFES­SIONAL, AS IT MAY NOT BE OPERATING PROPERLY.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
Page 4
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
This appliance must be installed per manufacturers’ instructions. Installations must conform to appropriate local codes and applicable state and federal requirements. Familiarity with these requirements before installation is essential. Some important considerations to discuss with local building offi cials include:
1. Applicable codes (i.e. Uniform Mechanical Code, State or Regional Gas Codes, National Fuel Gas Code).
2. Local amendments.
3. Recognized listing/testing agency: OMNI­Test Laboratories Inc.; Beaverton, Oregon
4. Is a permit required - cost?
5. In some states or municipalities, a licensed gas fi tter or plumber may be required to install this appliance. Check with your local building offi cial for requirements in your area (i.e. Is a license required for installation of gas supply line)?
6. Maximum amount of gas pipe without a pressure test - type of test required?
7. Are below grade penetrations of the gas line allowed?
8. Is concealed gas piping allowed?
9. Specific requirements of concealed fi ttings?
10. Is rigid pipe to appliance required?
11. Allowed piping materials?
12. Shut-off valve required within 4 feet of the fi rebox?
13. May the shut-off valve be concealed?
14. Rooms where the installation is not allowed?
15. This appliance is NOT approved for installation into a manufactured (mobile) home.
In the absence of local codes, installation should conform to National Fuel Gas Code, ANSI Z223.1 / NFPA 54-Latest Edition in the USA or National Fuel Gas Code, CAN/CGA­B149-Latest Edition in Canada.
HIGH ALTITUDE
Installations at Altitudes of 0 to 4500 feet:
This appliance has been tested and approved for elevations of 0 to 4500 feet (0 to 1370 meters).
Installations at Altitudes above 4500 feet:
For elevations above 4500 feet (1370 meters), install this appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the latest edition of the National Fuel Gas Code (ANSI Z223.1) or, in Canada, the latest edition of the CAN­B149.1 and CAN-B149.2 codes.
FIREPLACE REQUIREMENTS
IMPORTANT: When installing this appliance
into a factory built fi replace or heatform, the air fl ow within and around the fi replace shall not be altered by the installation of the insert (i.e. DO NOT BLOCK louvers or cooling air inlet or outlet ports, circulating air chambers in a steel fi replace liner or metal heat circulator).
CAUTION: The factory built fi rebox must accept the insert without modifi cation other
than removing bolted or screwed together pieces such as smoke shelf / defl ectors, ash lips, screen or door tracks and damper assemblies. Any fi replace component, which is removed, must be retained so they can be reinstalled to restore the fireplace to its original operating condition. The removal of any part must not alter the integrity of the outer shell of the pre-engineered fi replace cabinet in any way.
If any components are removed from (or altered) from the existing fi replace, a Warning Label (see below) must be affi xed inside the fi replace fi rebox, so that it shall be visible upon removal of the fi replace insert. Note: RTV high temperature silicone is an approved adhesive.
Fireplace Warning Label
(Provided in Accessory Package)
WARNING
THIS FIREPLACE HAS BEEN ALTERED TO
ACCOMMODATE A FIREPLACE INSERT AND
SHOULD BE INSPECTED BY A QUALIFIED
PERSON PRIOR TO RE-USE AS A
CONVENTIONAL FIREPLACE.
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 5
SPECIFICATIONS - Model EBVI25
DIMENSIONS
inches (millimeter) inches (millimeter)
A 26 5/8” (675 mm) H 11 1/8” (282 mm) B 20 1/2” (520 mm) I 1 1/4” (31 mm) C 13 3/8” (340 mm) J 17 5/16” (439 mm) D SM - 41 1/16” (1043 mm)
MED. = 44 1/8” (1121 mm)
E SM.- 26 1/16” (662 mm)
MED. - 27 5/8” (702 mm) F 19 3/8” (493 mm) M **24 7/8” (632 mm) G 1 15/16” (49 mm)
**
The total glass viewing area equals approx. 270 1/2 Sq. In
K 15 1/4” (388 mm)
L **10 7/8” (276 mm)
Top View
A
B
SPECIFICATIONS
Natural Gas BTU Input 17,000 to 25,000
Propane Gas BTU Input 19,500 to 25,000
B-Vent Size 4” Dia. Liner
Room Blower CFM 110 cfm
EFFICIENCIES
64 % Nat. Gas; 68 % Prop. Gas
Steady State Effi ciency * 79 % Nat. Gas; 81 % Prop. Gas
NOTES
* The Steady State Effi ciency numbers based on maximum vent confi guration. Note: Due to Lennox' ongoing commitment to quality, all specifi cations, ratings
and dimensions are subject to change without notice.
C
D
G
H
I
E
L
F
J
M
K
Figure 1
Front View
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Side View
5
Page 6
SPECIFICATIONS - Model EBVI30
DIMENSIONS
inches (millimeter) inches (millimeter)
A 26 1/16” (662 mm) H 11 1/2” (292 mm) B 22 3/8” (568 mm) I 15/16” (24 mm) C 13 5/8” (346 mm) J 20 1/8” (511 mm)
SM.= 40 1/4”(1022 mm),
D
MED. = 45 3/4”(1162 mm),
LG. = 49 1/4”(1251 mm)
SM.= 27 1/2”(699 mm),
E
MED.= 30 1/4”(768 mm),
LG. = .30”(762 mm)
F 20 7/8” (530 mm) M **23 7/16” (595 mm)
G 1 13/16” (46 mm)
K 15 5/8” (397 mm)
L **12 3/8” (314 mm)
Top View
A B
SPECIFICATIONS
Natural Gas BTU Input 21,500 to 30,000
Propane Gas BTU Input 22,000 to 28,000
B-Vent Size 4” Dia. Liner
Room Blower CFM 130 cfm
EFFICIENCIES
62 % Nat. Gas; 60 % Prop. Gas
Steady State Effi ciency * 83 % Nat. Gas; 82 % Prop. Gas
NOTES
* The Steady State Effi ciency numbers based on maximum vent confi guration. ** The total glass viewing area equals approx. 290 Sq. In. *** Due to Lennox' ongoing commitment to quality, all specifi cations, ratings
and dimensions are subject to change without notice.
C
D
E
L
F
M
Front View
G
H
K
Side View
I
J
6
Figure 2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 7
MINIMUM CLEARANCES TO COMBUSTIBLES MODELS: EBVI25 & EBVI30
These appliances can be installed in most residential fi replace confi gurations. If installed close to an adjacent wall, ensure that the minimum clearances to combustible surfaces are maintained. A local building inspector should review your plans prior to installation.
Refer to Figures 3, 4a, 4b and 6 for Clearances to Combustibles.
Minimum clearances include spacers/standoffs or surfaces to combustible construction.
Notes for Table 5:
* This includes any projections such as shelves, window
sills, mantels, spacers/standoffs or surfaces to combustible construction etc. above the appliance. Paint or lacquer used to fi nish the mantel must be heat resistant in order to avoid discoloration.
** If hearth is elevated, subtract 1 inch of hearth extension
required for every 2 inches of height (see Figure 6).
Clearances to Combustibles
Side Wall 8” (203 mm) 8” (203 mm) Min.
A
Ceiling or Alcove Height 64” (1626 mm) 64” (1626 mm) Min.
B
Mantel Height See Fig. 4b See Fig. 4a Min.
C*
Mantel Projection from
D*
See Fig. 4b See Fig. 4a Min.
Inches (millimeters)
EBVI25 EBVI30
Wall
Clearance to Floor 0” (0 mm) 0” (0 mm) MAX.
E
Hearth Protection
F**
**16” (406 mm) **16” (406 mm) Min.
(from Fireplace Face)
Hearth Protection
G
44” (1118 mm) 40” (1016 mm) Min.
Width
Alcove Width 45” (1143 mm) 48” (1219 mm) Min.
H
Alcove Depth 36” (914 mm) 36” (914 mm) MAX.
I
Table 5
Min./Max.
Clearances
Mantel
Side Wall
A
Hearth Protection
Figure 3
Mantel Clearance, Model: EBVI30: The mantel should be located in the shaded area (light gray) shown below.
D
18"
17" 16"
15"
C
14"
0
10
12
11
Side View
0
2345678
9
1
Top of Insert
(see "C" on Fig. 3)
\
Figure 4a
Ceiling (or) Alcove Height
C
Top of Insert
G
E
Mantel Clearance, Model: EBVI25: The
mantel should be located in the shaded area (light gray) shown below.
15 1/2"
13" 11"
C
8 1/2"
0
8”
Side View
Figure 4b
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
B
D
5”
Top of Insert louver
(see "C" on Fig. 3)
0
1”12”
Alcove Minimum Width: The specifi ed minimum width of the
alcove cannot be reduced with the use of wall protection.
Fireplace
Top View Alcove
Insert
Hearth
I
H
Figure 5
Hearth Protection: For every 2" of hearth height, subtract 1" of hearth extension required.
Side View of Insert
F
Existing Fireplace Hearth
16"
15"
14"
2"
4"
6"
7"
13 1/2"
\
At 7" hearth height, no hearth extension is required
Figure 6
7
Page 8
MINIMUM FIREPLACE DIMENSIONS
Refer to Figures 7 & 8 for Minimum Fire­place Clearance Dimensions. See pages 5 & 6 for actual insert body dimensions.
Consult your local authority having jurisdic­tion for requirements in your area.
Before the fi replace insert is assembled and installed, you must consider whether the appliance must be converted for use with pro­pane gas (see step 7 on page 9). You must also consider the vent length requirements.
Minimum Fire­place Clearance Dimensions
J Height 19"
K Depth 14 1/2"
L Width @
Front
M Width @
Rear
Inches (millimeters)
EBVI25 EBVI30
(483 mm)
(368 mm)
27"
(686 mm)
23 1/4"
(591 mm)
(533mm)
(356 mm)
26 1/2"
(673 mm)
22 1/2"
(572 mm)
21"
14"
Table 6
M
Top View
K
L
Figure 7
9"
Min.
Reference
J
Side View
K
Figure 8
DETAILED INSTALLATION STEPS
Step 1: PREPARATION - Plan and install gas
line.
This appliance is provided with an opening on the left hand side of the control compartment. A 3/8" NPT gas supply pipe must be brought near this inlet hole.
Gas Supply Line - Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protec­tion, sizing, locations, controls, pressure, sedi­ment, and more. Certainly no one unfamiliar and unqualifi ed should attempt sizing or installing gas piping.
The gas supply line should be plumbed from the fuel source to the area where the appliance is to be installed per requirements outlined in NFPA 54 - latest edition (USA) or B149
- latest edition (Canada).
The proper gas line diameter must be used to run from the supply regulator (at the gas company meter) to the appliance. Never use galvanized or plastic pipe. Refer to table 7 for suggested sizing of the gas supply line if black iron pipe is being used.
The gas supply line should be connected to the appliance at step 9 (page 12).
Suggested Sizing of Black Iron Pipe
Schedule 40 - Pipe Supply Line
Schedule 40 Pipe Schedule 40 Pipe Length (Feet)
Inside Diameter (Inches)
Natural
Gas
Propane
Gas
0-10 1/2 3/8
10-40 1/2 1/2
40-100 1/2 1/2
100-150 3/4 1/2
150-200 3/4 1/2
Table 7
IMPORTANT NOTE: If propane is used, be aware that if the tank size is too small (i.e. under 100-lbs, if this is the only gas appliance in the dwelling. Ref. NPFA 58), there may be loss of pressure, resulting in insuffi cient fuel delivery (which can result in sooting or other malfunctions). Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.
Step 2: CLEAN FIREPLACE (If necessary)
Thoroughly clean the masonry or factory
built fi replace.
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 9
CAUTION: THE FIREPLACE IN WHICH THIS GAS INSERT IS TO BE INSTALLED MUST BE THOROUGHLY CLEANED IF IT HAS BEEN USED TO BURN WOOD OR SYNTHETIC LOGS. HAVE THE CHIMNEY AND ALL INSIDE SURFACES OF THE FIREPLACE BRUSHED AND VACUUMED SO THAT NO SOOT, EMBERS, OR LOOSE COMBUSTION DEPOSITS CAN BE DRAWN INTO THE HEAT CIRCULATION BLOWER AND BLOWN INTO THE LIVING AREA. IF ANY PORTION OF THE CHIMNEY SYSTEM SHOWS SIGNS OF STRUCTURAL OR MECHANICAL WEAKNESSES, SUCH AS: CRACKS, LEAKY JOINTS, CORRODED OR WARPED SURFACES, THE FAULTY POR­TION MUST BE REPAIRED OR REPLACED PRIOR TO INSTALLING THIS APPLIANCE.
Step 3: UNPACK THE INSERT - Remove
the top and side cartons. Remove all the inner packages and packing materials and discard.
Step 4: LIFT INSERT INTO POSITION (see Fireplace Requirements on page 4 fi rst)
insert into position in front of the fi replace where unit is to be installed. Discard bottom carton
Lift
Step 5: REMOVE STANDARD GLASS DOOR ASSEMBLY.
WARNING: NEVER OPERATE UNIT WITH­OUT THE FRONT GLASS DOOR PANEL IN PLACE AND SECURE.
1) Open the 2 latches below the glass door
as shown in Figures 9 & 10.
Glass Door
Release latch on each side (below door)
Figure 9
2) Swing the bottom of the door outward (see Figure 10) and lift it off of fi rebox top. Set door aside in a safe place.
Top Flange Door Frame
Glass Door
Latches
Firebox Floor
Bottom Vee-fl ange Door Frame
STEP 6: REMOVE PACKAGED MATERIALS FROM INSIDE FIREBOX AND SET ASIDE (
log set, bag of embers, bag of vermiculite, propane conversion kit. and draft hood sliding tool).
Step 7: INSTALL LP CONVERSION KIT (IF NECESSARY) - Install the LP conversion kit
per instructions provided with kit.
Step 8: VENTING SYSTEM INSTALLATION (Refer to Installation Instructions provided with venting components).
VENTING REQUIREMENTS: This appliance
requires the use of 4” B-Vent or, a 4” UL 1777 listed gas vent liner from fl ue outlet to the chimney termination to ensure proper operation. Follow all vent manufacturer’s requirements and local building codes. The vent termination must be in accordance with the vent manufacturer’s instructions.
Flex Liner Installation (see Figure 17 for Masonry Fireplace Installations and Figure 18 for Factory Built Fireplaces):
• Flexible vent pipe is packaged and shipped in its contracted state. When installing fl exible vent pipe, its length may be expanded to twice it contracted size. This appliance is approved for 40 feet maximum vertical venting (from the outlet to termination). A minimum fl ue height of 12 feet is required.
• The fl exible vent pipe must NOT be allowed to sag behind the insert or in the fi replace fl ue.
WARNING: HANDLE GLASS DOOR WITH EXTREME CARE! THE GLASS DOOR ASSEMBLY IS SUSCEPTIBLE TO DAMAGE. DO NOT SCRATCH WHILE HANDLING OR WHILE REINSTALLING.
Remove the front door assembly from insert as follows:
Figure 10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Page 10
Vertical Termination Height Minimum
(Factory Built and Masonry Fireplaces)
The vent termination clearances above the high side of an angled roof is as follows:
Feet (meters) 8 (2.4) 7 (2.1) 6 (1.8) 5 (1.5) 4 (1.2) 3 (0.9) 2 (0.6) 1 (0.3) 0 (0.0)
Table 8
6/12
Roof Pitch
8/12
10/12
12/12
14/12
16/12
4/12
2/12
2 ft. (610 mm)
minimum
No height above wall or parapet is required when dis­tance is greater than 10 ft.
WARNING: Do not substitute the heat-rated (UL 1777) liner with any other type liner or a fi re may result causing property damage, personal injury or loss of life.
NOTES:
• Adjust Leveling Bolts if Necessary: Two leg leveling bolts are installed into existing holes in the bottom rear of appliance. Turn the leveling bolts to adjust for correct height.
• Refer to Vent Manufacturer Installation Instructions.
Installation Steps:
1) Cut the fl ex liners as required
.
2) Connect the liner to the collar on the termination cap.
3) Install fl ashing.
4) Insert liner into chimney, passing through the damper opening.
5) Install termination cap.
6) Remove the screw from the front of the detachable draft hood (see
18/12
Figure 12). Slide the draft hood off the back (see Figure 13).
Remove Screw using a 1/4" nut driver or equivalent
wall or parapet
Never install termiation below the wall or parapet when distance is less than 10 ft. as shown below
wall or parapet
Figure 11
B-Vent System Components
The following fl ex liner kits are available for relining the existing fi replace (see Figures 17 & 18).
Lennox Hearth Products - 4" B-Vent Kits
Cat. No. Model Description
H0906 VKBVI25 Vent Kit, BVI, 4" X 25 ft.
H0907 VKBVI35 Vent Kit, BVI, 4" X 35 ft.
Table 9
10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 12
Detachable Draft Hood
Figure 13
7) Strech the liner just enough to prevent the possibility of sagging or coiling in the fl ue. Cut off excess liner.
8) Attach the fl ue pipe or chimney fl ex liner to the draft hood collar using a stainless steel hose clamp (see Figure 14). Note: Mill-pac, high temperature silicone and/or screws may also be used to secure the liner to the collar (hose clamp must also be used). Ensure that the draft hood assembly is level with the insert top for attachment.
Page 11
Before installing liner, ensure that the damper plate is open and secure to prevent the damper plate from fall­ing down and crushing the liner.
Secure fl ex liner to collar using a Hose Clamp
Vent
Flex Liner
Masonry Fireplace Installation Diagram
Vent Kits, HO906 (25') & H0907 (35') includes: 1 ea. fl ex liner 1 ea. fl ashing 1 ea. collar 2 ea. hose clamps
(see table 9)
Liner
Vertical Term. Cap
Collar
2 Hose Clamps
Draft Hood
Figure 14
9) After liner is secured to draft hood collar, use the tool provided to slide it forward (aligning with guide brackets) until the screw hole in the spill tube aligns with the screw hole in the top of the fi rebox (see Figure 12). Secure two parts in place with removed screw. While pulling draft hood forward, push the insert.
While pushing the unit back into place, use the tool provided to pull the draft hood forward until screw hole in spill tube aligns with screw hole in top of the fi rebox.
Draft hood sliding tool (provided)
Spill Tube
Draft Hood
The fl exible vent pipe must NOT be allowed to sag behind insert or in fi replace fl ue.
Masonry chimneys may take various contours which the fl exible liners will accomodate. However, keep the fl exible liner as STRAIGHT as possible and avoid unnecessary bending.
4" diameter Vent, type B-Vent or listed gas fuel type vent liner listed to UL 1777
Remove or lock damper open
Flashing
Termination Cap
Figure 15
Guide Bracket
Draft hood sliding tool (provided)
Figure 16
Draft Hood
Read Fireplace Requirements on page 4
Liner Requirements: Exhaust Vent = 4" Dia. B-Vent or Liner listed to
Guide Bracket
UL 1777 Vertical Height Min. = 12 ft. (3.66 M) Vertical Height Max. = 40 ft. (10.7 M)
Figure 17
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
IMPORTANT
Under no circumstances, may separate sections of concentric fl exible vent pipe be joined together.
11
Page 12
Factory Built Fireplace Installation Diagram
Vent Kits, HO906 (25') & H0907 (35') includes: 1 ea. fl ex liner 1 ea. fl ashing 1 ea. collar 2 ea. hose clamps
(see table 9)
Flashing
Liner Requirements: Exhaust Vent = 4" Dia. B-Vent or Liner listed to UL 1777 Vertical Height Min. = 12 ft. (3.66 M) Vertical Height Max. = 40 ft. (10.7 M)
Storm Collar
Liner
Vertical Term. Cap
Collar
Termination Cap
2 Hose Clamps
Step 9. CONNECTING GAS LINE
Note: Final gas connection should be made after unit is in place to avoid damage to line when pushing the unit into position.
Make gas line connections. All codes require a shut-off valve mounted in the supply line. Figure 19 illustrates two methods for connecting the gas supply. The fl ex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.
This appliance is equipped with a gas fl ex line for use (where permit­ted) in connecting the unit to the gas line. A gas fl ex line is provided to aid in attaching the B-Vent appliance to the gas supply. The gas fl ex line can only be used where local codes permit. See Figure 19 for fl ex line description. The fl ex line is rated for both natural and propane gas. A manual shut off valve is also provided with the fl ex line. The gas con­trol valve is located in the lower control compartment. To access the valve, open the lower access door. The millivolt control valve has a 3/8" (10 mm) NPT thread inlet port fi tting.
GAS CONNECTION
Gas Valve
Gas Flex Line Connector
3/8" NPT x
Flare Fitting
1/2" x 3/8" Flare
Shut-Off Valve
The fl exible vent pipe must NOT be allowed to sag behind insert or in fi replace fl ue.
4" diameter vent, type B-Vent or listed gas fuel type vent liner (listed to UL
1777)
Remove or Secure Damper Open
SEE FIREPLACE
REQUIREMENTS
ON PAGE 4
Roof Flashing
3/8" Flex Tubing
Gas
Stub
3/8" Nipple
3/8" Union
Figure 19
1/2" x 3/8"
Reducer
3/8" Close Nipple
3/8" Shut-Off Valve
Step 10. PURGING AIR
AIR PURGING PROCEDURES MUST BE PERFORMED BY A QUALIFIED TECHNICIAN ONLY.
Purging Air from Supply Line
a. Turn gas supply line valve off. b. Loosen setscrew at inlet pressure tap on control valve (see Figures 32 & 33). c. Turn gas supply line valve on. d. When gas fl ows, turn supply valve off. e. Close the inlet pressure tap.
Purging Air from Appliance
Purge air from appliance by holding gas control valve down in the pilot position until pilot will light (see Figure 20). DO NOT LIGHT A MATCH IF YOU SMELL GAS. Light a match then allow gas fl ow to pilot. If the Match “blows”, there is air in the line (purge line). If the fl ame is straight and tall, there is no gas pressure.
12
IMPORTANT
Under no circumstances, may separate sections of concentric fl exible vent pipe be joined together.
Figure 18
When lighting the appliance for the fi rst time, it will take a few minutes to purge air from the gas line. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent light­ings of the appliance will not require such purging. Inspect the pilot fl ame (remove logs, if necessary, handling carefully).
Figure 20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 13
Step 11. INSTALLING LOGS, VERMICULITE AND EMBERS
The packaged log set, vermiculite and embers are located within the fi rebox of the insert
Top Left Log
Front Center Log
Center Log
Figure 21
Front Left Log
Rear Log
Top Right Log
Front Right Log
Log Installation Instructions:
WARNING: IF LOGS ARE NOT INSTALLED ACCORDING TO THE DIRECTIONS SHOWN HERE, FLAME IMPINGEMENT AND IMPROPER COMBUSTION COULD OCCUR AND RESULT IN SOOT AND/OR EXCES­SIVE PRODUCTION OF CARBON MONOXIDE (CO), A COLORLESS, ODORLESS, TOXIC GAS.
Note: If an optional Brick Liner Kit was purchased, intall it now, per instructions provided in kit
Carefully install the seven-piece log set into the fi rebox as shown in these instructions. All logs should fi t onto corresponding pins and/or log stoppers. This will ensure a proper fl ame and safe combustion.
1. Place the rear log onto the 2 corresponding locating pins at the back of the fi rebox as shown in Figure 22.
2. Place the Front Right Log onto the 2 corresponding locating pins as shown in Figure 23.
Figure 23
Front Right Log
3. Place the Center Log onto the 2 corresponding locating pins as shown in Figure 24.
Figure 22
Rear Log
Figure 24
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Center Log
13
Page 14
4. Place the Front Left Log onto the 2 corresponding locating pins as
shown in Figure 25.
Figure 25
Front Left Log
5. Install the Top Left Log onto the corresponding locating pin and indentation on Center Log as shown in Figure 26.
Figure 26
Top Left Log
6. Install the Front Center Log over the Front Right Log . The front of log will rest on the burner and the back of log will rest on rear log as shown in Figure 27.
Figure 28
Top Right Log
8. Place the glowing embers on the burner as shown in Figure 29. One package of ember material has been included with this log set You will not need to use the entire bag.
IMPORTANT: The quantity and placement of the ember material can affect insert performance therefore it is very important that it be placed as shown in Figure a. Unpackage and divide the fi ne ember material (mineral wool) into dime-sized fl uffy pieces. b. Distribute the pieces over the top of the front burner ports, fi lling the area in front of the forward logs.
29.
Figure 27
Front Center Log
7. Install the Top Right Log into the corresponding indentations on Front Center Log and front right twig as shown in Figure 28.
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 29
Embers
9. Place some vermiculite around the logs as shown in Figure 30 (the entire bag of vermiculite will NOT be used).
Figure 30
Vermiculite
Page 15
VERIFY THAT THE GAS LINE HAS BEEN PURGED OF AIR (See Step 10).
Step 12. REINSTALL FRONT GLASS DOOR ASSEMBLY.
SIT & Honeywell
Millivolt Wiring Diagram
If original wire as supplied must be replaced, it must be replaced with Type AWM 105°C, 18 gage wire.
Burner On/Off Switch and Rheostat Location
If optional surround is installed
Burner On/Off Switch
To reinstall glass door assembly panel, reverse instructions on Step 5, page 9.
Step 13. TEST ALL CONNECTIONS FOR LEAKS (FACTORY AND FIELD).
A. Mix a 50% dish soap, 50% water solution (or use a gas leak detection solution).
B. Light the appliance (refer to the lighting instructions provided in the insert control compartment and the Homeowner's Care and Operation Instructions).
C. Brush all joints and connections with the soapy water or leak detection solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the “OFF” position and close the gas shut-off valve. Either tighten or refasten the leaking connection and retest as described above.
D. When the gas lines are tested and leak free, observe the individual tongues of fl ame on the burner. Make sure all ports are open and producing fl ame evenly across the burner. If any ports are blocked, or partially blocked, turn off unit, allow it to cool, then clean out the ports.
Step 14. INSTALL SURROUND KIT OR CON­TROL KIT (see pages 11 & 12 in Homeowners Manual).
Step 15. INSTALL WALL THERMOSTAT AND REMOTE CONTROL (if purchased)
If an optional Wall Thermostat or Remote Control Kit was purchased, intall it now, per instructions provided in kit. See Figure 31. I
f a wall-mounted thermostat is selected, mount it in a convenient location on a wall near the insert. Wire the thermostat within the millivolt control circuit using a maximum of 25 feet of 18 gage, 2 conductor wire. Caution: Do not connect the optional wall thermostat, gas control valve or control wiring system of the unit to a 120 volt power supply (residential line voltage).
Spill Switch
TP
TH
TP
TH
Thermopile
* Switch
Figure 31
* On/Off Switch, Optional Thermo­stat or Remote Control Receiver
Step 16. CHECKING APPLIANCE OPERATION
With gas line installed run initial system checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Homeowner's Care and Opera­tion Instructions (or pull out the instruction label located in control compartment below glass door assembly).
MODEL EBVI30
Honeywell Millivolt Gas Valve Controls
PILOT ADJUSTMENT SCREW
TP/TH
TP
TH
WIRING TERM­INALS
GAS CONTROL KNOB
O
N
I
P
I
L
O
O
F
T
F
INLET PRESSURE TAP
PIEZO IGNITER
CONVERTIBLE HI/LO REGUL ATOR (adjusts fl ame height and heat output)
L
O
H
OUTLET PRESSURE TAP
Figure 32
MODEL EBVI25
SIT Millivolt Gas Valve Controls
GAS CONTROL KNOB
T
O
L
I
O
W
L
H
I
CONVERTIBLE HI/LO REGUL ATOR (adjusts fl ame height and heat output)
P
F
INLET PRESSURE TAP
IN
PIEZO IGNITER
N
O
T
O
L
I
P
F
OUT
it
O
OUTLET PRESSURE TAP
Figure 33
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Rheostat
Left Front Surround Panel
Figure 34
Control Compartment Access
Pull down hinged door to access control compartment
Side View of Insert
Pull down lower louver (hinged)
Figure 35
Millivolt Appliance Checkout
The pilot fl ame should be steady, not lifting or fl oating. Flame should be blue in color with traces of orange at the outer edge. The top 3/8" (10 mm) at the pilot generator (thermopile) and the top 1/8" minimum (tip) of the quick drop out thermocouple should be engulfed in the pilot fl ame. The fl ame should project 1" (25 mm) beyond the hood at all three ports (Figure 36).
Replace logs if removed for pilot inspection.
To light the burner, rotate the gas valve control knob counterclockwise to the “ON” position then turn “ON” the on/off switch mounted on the surround assembly (see Figure 34) or operate the burner with the optional remote control, wall thermostat or control switch.
Proper Pilot Flame Appearance
Thermocouple
1/8" Min.
(3 mm)
TPTH TP TH
Igniter Rod
Hood
Pilot
Nozzels
Thermopile
Figure 36
3/8" Min.
(9 mm)
15
Page 16
Step 17. SPILLAGE TEST PROCEDURE
(Proper Vent Operation Test):
A fl ue spillage test should be performed as part of the installation process to test for proper vent operation.
Perform the Spill Test as Follows:
1) Light the appliance. Adjust fi re to highest fl ame setting. Allow unit to operate for approximately 15 minutes. Blower should be off.
2) Close all the external doors and windows.
3) Start all the exhaust fans and other appliances which remove air from the home (clothes dryer, furnace, etc.).
4) To ensure a valid test, hold a scrap piece of sheet metal (or other noncombustible material) between the spill tube and the top of the door (to prevent the natural convection of the unit from interfering with the test).
5) Use an open fl ame (preferably a wooden match) or smoke (cigarette, rope) to determine if spillage is present. Move the fl ame or smoke device across the opening of the draft test port on the front of unit (see Figure 37). If the fl ame or smoke is drawn into the opening, there is no spillage. If the fl ame or smoke is blown out or away from the opening, spillage is present and corrective action should be taken before operating the appliance.
Draft Test Port for Spill Testing
If spillage continues, it may be a result of nega­tive air pressure within the home. To test:
1) Turn off a mechanical devices that were turned on in step 17, instruction #3 and retest.
2) Open a window (6" min.) near the insert and retest.
If spillage continues, The Technician should contact Technical Services at Lennox Hearth Products.
Note: Spillage occurs when fl ue gases can not exit the vent system at an adequate rate causing it to back up into the dwelling. If spillage occurs, the heated exhaust spills out of the draft hood which should result in tripping the spill switch (see Spill Switch below) which will shut down the unit. Other symptoms of fl ue gas spillage at the draft hood may include condensation on walls and windows and/or noticeable odors.
SPILL SWITCH - This thermally activated safety switch will sense the change in temperatrure and shut down the gas valve in the event of a severe downdraft or a blocked or disconnected vent. The switch acts as a safety shut-off to prevent a build-up of carbon monoxide. If the fl ue is blocked or has no "draw," the switch will automaticlly shut off the supply of gas within 5-10 minutes. Tampering with the switch can result in Carbon Monoxide (CO) Posioning and possible death.
Carbon monoxide is a color-
less, odorless, highly toxic gas.
WARNING: SPILLAGE CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH!
Combustion and Ventilation Air
Air for combustion is drawn in through the front of the unit therfore, the front of the unit must be kept clear of any obstructions.
Step 18. CHECK BLOWER SYSTEM OPERATION
WARNING: THE POWER CORD MUST BE PLUGGED DIRECTLY INTO A PROP­ERLY GROUNDED, 120 VOLT, 60 HZ, 3-PRONG RECEPTACLE ELECTRICAL OUTLET. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG. IT MUST BE ROUTED TO AVOID CON­TACT. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE.
When the insert heats up, the blower will auto­matically be turned on by the fan disc, located under the fi rebox bottom on the front left side. It will come on at the speed determined by the rheostat, located on left surround panel (see Figure 34). To adjust the blower speed, dial the rheostat to the desired speed setting. Rotate the dial down (clockwise), just past the click (the fi rst ON position) for the highest speed setting. Turning the knob further clockwise will provide slower blower speeds. Note: If the rheostat is not turned “on,” the blower will not operate.
Blower Wiring
120 V AC
Diagram
Power Cord
Black
Hot (Live)
Green
White
Flame drawn in, indicates no spillage
Figure 37
If spillage is detected, check the following:
• Check the vent sizing according to specifi cations, and vent confi gurations.
• Examine entire venting system for faults such as disconnected joints, damaged vent sections, or sagging liner.
• Make sure vent and air openings are not obstructed.
16
WARNING: THIS APPLIANCE NEEDS FRESH AIR FOR SAFE OPERATION AND MUST BE INSTALLED WITH PROVISIONS FOR ADEQUATE COMBUSTION AND VENTILATION AIR AVAILABLE TO THE ROOM IN WHICH IT IS TO BE OPERATED.
Follow CAN /CGA B149 (in Canada) or ANSI Z223.1 (in the USA) requirements, and any local codes or regulations of the enforcing authority.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 38
Fan Disc
RedBlackBlack
Rheostat
Black
(Ground)
Blower Assembly
(Neutral)
Page 17
Step 19. BURNER ADJUSTMENT
Flame Appearance and Sooting
Proper fl ame appearance is a fl ame which is blue at the base and becomes yellow / orange in the body of the fl ame. When the insert is fi rst lit, the entire fl ame may be blue and will graduallay turn yellow/orange during the fi rst 6-8 minutes of operation. If after 6-8 minutes the fl ame stays lowered blue, or if the fl ame is orange with evidence of sooting (black tip), the air shutter may require adjustment.
Appliances operated with air shutter openings that are too large will exhibit fl ames that are blue and transparent. These weak, blue and transparent fl ames are termed anemic. If the air shutter openings are too small, sooting may develop.
Burner Flame Appearance
Figure 39
EBVI25
Sooting is indicated by black puffs developing at the tips of very long orange fl ames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination. Sooting is caused by incomplete combus­tion in the fl ames and lack of combustion air entering the air shutter opening. To achieve a warm yellow to orange fl ame that does not soot, the shutter opening must be adjusted between these two extremes.
No smoke or soot should be present. Repo­sition the logs if fl ames impinge on any of them. If the logs are properly positioned and sooting conditions exist, the air shutter opening on the main burner tube should be adjusted.
Burner Adjustment Procedure
AIR SHUTTER ADJUSTMENT SHOULD ONLY BE PERFORMED BY AN AUTHO­RIZED INSTALLER AT THE TIME OF THE INSTALLATION OR SERVICE.
CAUTION: THE ADJUSTMENT ROD AND NEARBY APPLIANCE SURFACES ARE HOT. EXERCISE CAUTION TO AVOID INJURY WHILE ADJUSTING FLAME APPEARANCE.
Initially, always position the air shutter to the factory setting as shown in Figure 39 (adjust­ment rod is located in the lower control area). This can be done by moving the adjustment rod up or down accordingly. Allow the burner to operate for at least 15 minutes. Observe the fl ame continuously. If it appears weak or sooty as previously described, adjust the air shutter to a more open position until the proper fl ame appearance is achieved.
Burner Air Shutter Adjustment
Adjusting Set Screw
Adjustment Rod Up
(1/8" Open Position)
Burner Tube
Air Shutter
Adjustment Rod Down
(full open position)
MAIN BURNER FACTORY AIR SHUTTER OPENING SETTING
Model Gas Type Air Shutter Gap
EBVI30 Natural Gas 5/16" (7.94mm)
Propane 1/2" (12.7mm)
EBVI25 Natural Gas 1/16" (1.59mm)
Propane 1/2" (12.7mm)
Figure 39
CAUTION: CARBON WILL BE PRODUCED IF THE AIR SHUTTER IS CLOSED TOO MUCH. ANY DAMAGE DUE TO CARBONING RESULT­ING FROM IMPROPERLY SETTING THE AIR SHUTTER IS NOT COVERED UNDER THE WARRANTY.
The following chart (Table 10) is provided to aid you in achieving the correct air shutter adjustment for your installation.
Air Shutter Adjustment Guidelines:
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be yellow
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
Table 10
When satisfi ed that the appliance operates properly, proceed to fi nish the installation. Leave the control knob in the ON position and the on/off switch in the OFF position.
STEP 20. INSTALL LOUVER KIT
Install louver kit per the instructions provided with the kit.
IMPORTANT: ENSURE THAT THE FRONT GLASS PANEL IS IN PLACE AND SEALED DURING ADJUSTMENT.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
Page 18
SAFETY / LISTING LABEL
MODEL NO. EBVI25
MANUFACTURED AT:
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL ALTITUDE
MIN. GAS SUPPLY PRESS (“WC) PRESS MIN. D’ALIMENTATION (“ CE) MANIFOLD PRESSURE (“WC) PRESSION CE TUBULURE (“CE) MANUFACTURER’S RECOMMENDED ORIFICE SIZE DIMENSION DE L’INJECTEUR RECOMMANDE PAR MANUFACTURIER (DMS) MAX INPUT (BTU/HR) ENTREE MAX MIN INPUT (BTU/HR) ENTREE MIN
ELECTRICAL RATING/EXIGENCES ELECTRIQUES:
MINIMUM
CLEARANCES TO
COMBUSTIBLE
MATERIAL
DEGAGEMENT MUR ADJACENTS
MINIMUM DE MATERIAUX
COMBUSTIBLES
PROFONDEUR DU MANTEAU 305 mm
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC L’ APPAREIL.
Do not operate the appliance with glass removed, cracked or broken.
“CAUTION:
Replacement of panel should be done by a licensed or qualified service person.”
“This appliance is equipped at the factory for use with natural gas only. Units using
propane must be field converted using the LP conversion kit, Cat. No. H1576.
FINAL INSPECTION BY:
CEILING (FROM BOTTOM OF UNIT) 64”
MANTEL FROM TOP OF UNIT LOUVER
M ANTEL
PLAFOND (DU BAS DE L’APPAREIL) 1626 mm
MANTEAU
WITH AIR FILTERS.
GAZ A EVACUATION.
ANSI Z21.88-2002
CSA 2.33-2002
CAN/CGA 2.17-M91
Lynwood, CA
-UNIT/APPAREIL: MILIVOLT 1 ph 60 HZ 120 VOLTS LESS THAN 5 AMPS
SIDEWALL
FLOOR
(MAX)
DEPTH
PLANCHER
DU DESSUS DE L'APPAREIL
(MAX)
0-4500 FT/PI
(0-1370M)
4.5”
3.5”
# 41
25,000
17,000
15 1/2”
12”
203 mm
0 mm
394 mm
8” 0”
MODEL NO. EBVI30
MANUFACTURED AT:
FOR USE WITH NATURAL GAS. EQUIPE POUR GAZ NATUREL ALTITUDE
MIN. GAS SUPPLY PRESS (“WC) PRESS MIN. D’ALIMENTATION (“ CE) MANIFOLD PRESSURE (“WC) PRESSION CE TUBULURE (“CE) MANUFACTURER’S RECOMMENDED ORIFICE SIZE DIMENSION DE L’INJECTEUR RECOMMANDE PAR MANUFACTURIER (DMS) MAX INPUT (BTU/HR) ENTREE MAX MIN INPUT (BTU/HR) ENTREE MIN
ELECTRICAL RATING/EXI GENCES ELECTRIQUES:
MINIMUM
CLEARANCES TO
COMBUSTIBLE
MATERIAL
DEGAGEMENT
MINIMUM DE MATERIAUX
COMBUSTIBLES
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL. FOR INSTALLATION
IN SOLID FUEL FIREPLACES. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE
FOYER AU GAZ CHAUFFANT AVEC EVACUATION - NE DOIT PAS ETRE UTILISE AVEC UN
COMBUSTIBLE SOLIDE. DOIT ETRE INSTALLE DANS UNE CHEMINEE EXISTANTE QUI
BRULE LE COMBUSTIBLE SOLIDE. NE PAS UTILISER DE FILTRE A AIR AVEC CE FOYER AU
FOR USE WITH GLASS DOOR CERTIFIED WITH THE APPLIANCE ONLY.
N’UTILISER SEULEMENT QUE LA PORTE DE VERRE CERTIFIE AVEC L’ APPAREIL.
“CAUTION:
Do not operate the appliance with glass removed, cracked or broken.
Replacement of panel should be done by a licensed or qualified service person.”
“This appliance is equipped at the factory for use with natural gas only. Units using
propane must be field converted using the LP conversion kit, Cat. No. H0920.
FINAL INSPECTION BY:
CEILING (FROM BOTTOM OF UNIT) 64”
MANTEL FROM TOP OF UNIT
MANTEL DEPTH 12”
PLAFOND (DU BAS DE L’APPAREIL) 1626mm
MANTEAU
PROFONDEUR DU MANTEAU 305mm
WITH AIR FILTERS.
GAZ A EVACUATION.
ANSI Z21.88-2002
CSA 2.33-2002
CAN/CGA 2.17-M91
Union City, TN
-UNIT/APPAREIL: MILIVOLT 1 ph 60 HZ 120 VOLTS LESS THAN 5 AMPS
SIDEWALL
FLOOR
(MAX)
MUR ADJACENTS
PLANCHER
DU DESSUS DE L'APPAREIL
(MAX)
0-4500 FT/PI
(0-1370M)
4.5”
3.5”
#37
30,000
21,500
8” 0”
18”
203mm
0mm
457mm
18
VENTED GAS FIREPLACE HEATER
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION
P/N 9-1466B
SERIAL NUMBER/NOMBRE DE SERIE
XXX XXX
IIIIIIIIIIIIIIIIIIII
XXX
P/N 9-1466B
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
VENTED GAS FIREPLACE HEATER
FOYERA AU GAZ CHAUFFANT AVEC EVACUATION
P/N 9-1466A
SERIAL NUMBER/NOMBRE DE SERIE
XXX XXX
IIIIIIIIIIIIIIIIIIII
XXX
P/N 9-1466A
Page 19
Page 20
Lennox reserves the right to make changes at any time, without notice, in design, materials, specifi cations, prices and also to discontinue colors, styles and products. Consult your local distributor for code requirements for your area.
Printed in U.S.A. © LENNOX HEARTH PRODUCTS 2004
20
P/N 775,154M REV. B 7/2004
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
LHP 1110 West Taft Avenue • Orange, CA 92865
Loading...