AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
WARNING /AVERTISSEMENT/AVISO
• HOT GLASS WILL CAUSE
BURNS.
• DO NOT TOUCH GLASS
UNTIL COOLED.
• NEVER ALLOW CHILDREN
TO TOUCH GLASS.
• UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
• LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
• NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
• EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
• USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
• LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
ENVY and ENVY CD
Direct-Vent Gas Fireplaces
P/N 506023-17 Rev. A 08/2013
This manual is one of a set of two supporting this product.
Refer to P/N 506025-09 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 506223-74.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
MODELS
NV35IN
NVCD35IN
Report No. G100513653 PRT-001
Please read and understand these instructions
before starting installation.
NV40IN
NVCD40IN
NV45IN
NVCD45IN
fire-parts.com
Page 2
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging.............................2
Introduction
General Information
Requirements for the Commonwealth
of Massachusetts .......................4
Cold Climate Insulation
Manufactured Home Requirements
Location
Vent Termination Clearances
Minimum Clearances to Combustibles
Pre-Installation Steps
Construct the Appliance Framing
Route the Gas Supply Line to the Appliance ..11
Install the Vent System and
Exterior Termination ...................11
Select Venting System—
Horizontal or Vertical...................13
Vent Section Length
Vertical or Horizontal Venting Using Secure
Flex™ Venting Kits and Components ......22
Complete the Field Wiring
Connect the Gas Supply
Verify Correct Appliance Operation
Contemporary Fireplaces Only:
Install the Contemporary Floor and
Contemporary Glass Media
Install the Firebox Liners
Traditional Fireplaces Only:
Install the Logs, Decorative Volcanic Stone,
and Glowing Embers
Install the Glass Door
Adjust the Burner to Ensure Proper
Flame Appearance.....................28
Finishing Requirements
Attach the Safety-in-Operation Warnings ...31
Installation Accessories
Gas Conversion Kits
...........................2
.....................2
..................5
.........5
..............................5
..............6
......8
...................9
..........9
....................14
...............23
.................25
fire-parts.com
................26
...................27
..................28
.................29
.................32
....................35
........26
..............26
PACKAGING
The assembled vented gas fireplace heater
is packaged with:
• Traditional models only: (1 set) Logs
(Packaged in a carton inside the firebox)
• Traditional models only:
(1 bag) Volcanic Stone
• Literature Kit
(Envelope containing Care and
Operation Instructions, Installation
Instructions, Safety-In-Operation
Warning Labels, Warranty)
• (1) U-Shaped Vent Restrictor
(Attached to Literature Kit envelope)
INTRODUCTION
ENVY replaces are designed to operate
on natural or propane gas. An electronic
intermittent pilot ignition system provides
safe, efficient operation. External electrical
power is required to operate these units.
In the event of a power outage, four (4)
AA batteries provide backup power for
appliance operation (excluding blower).
These vented gas fireplace heaters
are sealed combustion, aircirculating gas fireplaces designed for
residential applications.
Approved Vent Components
These fireplaces are designed, tested and
listed for operation and installation with the
following vent components only:
• Secure Vent® Direct-Vent System
Components,
• Secure Flex® Flexible Vent Components,
and
• Z-FLEX® Model GA Venting Systems
listed to UL1777 and ULCS635
manufactured by Flexmaster
Canada Limited.
Use only the correct size venting (4 1/2 in.
inner and 7 1/2 in. outer).
These approved vent system components
are labeled for identification. DO NOT use
any other manufacturer’s vent components
with these appliances.
GENERAL INFORMATION
WARNING
Young children should be
carefully supervised when
they are in the same room
as the appliance. Toddlers,
young children and others may
be susceptible to accidental
contact burns. A physical
barrier is recommended if
there are at-risk individuals in
the house. To restrict access
to a fireplace or stove, install
an adjustable safety gate to
keep toddlers, young children
and other at risk individuals
out of the room and away from
hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient
être surveillés étroitement
lorsqu’ils se trouvent dans la
même pièce que l’appareil.
Les tout petits, les jeunes
enfants ou les adultes
peuvent subir des brûlures
s’ils viennent en contact
avec la surface chaude. Il
est recommandé d’installer
une barrière physique si des
personnes à risques habitent
la maison. Pour empêcher
l’accès à un foyer ou à un
poêle, installez une barrière
de sécurité; cette mesure
empêchera les tout petits,
les jeunes enfants et toute
autre personne à risque
d’avoir accès à la pièce et aux
surfaces chaudes.
NOTE: Children and adults should be alerted
to the hazards of high surface temperature
and should stay away to avoid burns or
clothing ignition.
Please read and understand these
instructions before beginning
your installation.
2
Remarqué : Les enfants et les adultes
devraient être infor-més des dangers
que posent les températures de surface
élevées et se tenir à distance afin d’éviter
des brûlures ou que leurs vêtements ne
s’enflamment.
DO NOT ATTEMPT TO ALTER OR
MODIFY THE CONSTRUCTION OF THE
APPLIANCE OR ITS COMPONENTS.
ANY MODIFICATION OR ALTERATION
MAY VOID THE WARRANTY,
CERTIFICATION, AND LISTINGS OF
THIS UNIT.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 3
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Codes and Standards
WARNING
Improper installation,
adjustment, alteration, service
or maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these
installation instructions will
result in an improperly installed
and operating appliance, voiding
its warranty. Any change to this
appliance and/or its operating
controls is dangerous.
WARNING
Clothing or other flammable
material should not be placed on
or near the appliance.
fire-parts.com
AVERTISSEMENT
On ne devrait pas placer de vêtements
ni d’autres matières inflammables sur
l’appareil ni à proximité.
WARNING
Any safety screen or guard
removed for servicing the
appliance must be replaced prior
to operating the appliance.
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil
sont utilisées.
NOTE: Installation and repair should be
done by a qualified service person. The
appliance should be inspected before use
and at least annually by a professional
service person. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, etcetera. It
is imperative that control compartments,
burners and circulating air passageways of
the appliance be kept clean.
Remarqué : L’installation et la
réparation devrait être confiées à un
technicien qualifié. L’appareil devrait
faire l’objet d’une inspection par un
technicien professionnel avant d’être
utilisé et au moins une fois l’an par la
suite. Des nettoyages plus fréquents
peuvent être nécessaires si les tapis,
la literie, et cetera produisent une
quantité importante de pous-sière. Il
est essentiel que les compartiments
abritant les commandes, les brûleurs
et les conduits de circulation d’air de
l’appareil soient tenus propres.
WARNING
AVERTISSEMENT
These appliances comply with National
Safety Standards and are tested and
listed by ETL/Intertek. (Report No.
G100513653 PRT-001) to ANSI Z21.88
(in Canada, CSA-2.33), and CAN/
CGA-2.17-M91 in both USA and Canada, as
vented gas fireplace heaters.
These appliances are listed by ETL/
Intertek for installation in bedrooms and
manufactured homes.
The installation must conform to local
codes or, in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54—latest edition (In Canada, the
current CAN/CSA-B149.1 installation code).
The appliance, when installed, must
be electrically grounded and wired in
accordance with local codes or, in the
absence of local codes, with the National
Electrical Code, ANSI/NFPA 70—latest
edition, or the Canadian Electrical Code,
CSA C22.1—latest edition.
Provide adequate clearances around
air openings and adequate accessibility
clearance for service and proper operation.
Never obstruct the front or back openings
of the appliance.
These appliances are designed to operate
on natural or propane gas only. The use
of other fuels or combination of fuels will
degrade the performance of this system and
may be dangerous.
It is advisable to have an alternate primary
heat source when installed in a dwelling.
These appliances must not be connected to
a chimney or flue serving a separate solid
fuel burning appliance.
ENVY replaces come standard with a
remotely-modulated gas valve. Flame
appearance and heat output cannot be
controlled at the gas valve. The BTU Input
for these appliances is shown in Table 1.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
Improper installation or use of this
appliance can cause serious injury
or death from fire, burns, explosion
or carbon monoxide poisoning.
WARNING
Do not operate without surround trim
assembly and screen installed.
NOTE: Do not use these appliances if any
part has been under water. Immediately call
a qualified, professional service technician
to inspect the appliance and to replace any
parts of the control system and any gas
control which have been under water.
Remarqué : Ne pas utiliser cet appareil
s’il a été plongé, même partiellement,
dans l’eau. Appeler un technicien
qualifié pour inspecter l’appareil et
remplacer toute partie du système de
commande et toute commande qui a été
plongée dans l’eau.
NOTE: Only trim kit(s) supplied by
the manufacturer shall be used in the
installation of this appliance.
Remarqué : Seules les trousses de
garniture fournies par le fabricant
doivent être utilisées pour l’installation
de cet appareil.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 1: Input Rate, Gas Valves
Models
NV35IN
NVCD35IN
NV40IN
NVCD40IN
NV45IN
NVCD45IN
Input Rate (BTU/HR)
Natural GasPropane Gas
35,500 high
15,500 low
31,000 high
16,000 low
41,500 high
15,500 low
40,000 high
21,000 low
47,000 high
18,000 low
47,000 high
24,000 low
35,000 high
18,000 low
28,000 high
15,000 low
37,000 high
14,500 low
32,000 high
18,500 low
45,000 high
18,000 low
40,000 high
22,000 low
3
Page 4
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Gas Pressure
Table 2 and Table 3 show the appliance
inlet and manifold gas pressure
requirements.
Orifice Sizes—Sea Level to
High Altitude
These appliances are tested and approved
for installation at elevations of 0–4500 ft
(0–1372 m) above sea level using the
Table 2: Inlet Gas Supply Pressure
FuelMinimumMaximum
Natural Gas
Propane
4.5 in. WC
(1.12 kPa)
11.0 in. WC
(2.74 kPa)
10.5 in. WC
(2.61 kPa)
13.0 in. WC
(3.23 kPa)
standard burner orifice sizes (marked with
an “*” in Table 4).
For elevations above 4500 ft, contact your
gas supplier or qualified service technician.
Deration
At higher elevations, the amount of BTU fuel
Table 3: Manifold Gas Supply Pressure
FuelLowHigh
Natural Gas
Propane
1.6 in. WC
(0.40 kPa)
6.3 in. WC
(1.57 kPa)
3.5 in. WC
(0.87 kPa)
10.0 in. WC
(2.49 kPa)
Test gauge connections are provided on
the front of the electronic gas control valve
(identified IN for the inlet and OUT for the
manifold side). The control valves have a
3/8 in. (10 mm) NPT thread inlet and outlet
side of the valve (Figure 1).
Figure 1: SIT Electronic Gas Valve
Green Wire
(from DFC wire
Inlet (IN) Test Port
fire-parts.com
Manifold (OUT)
Test Port
Orange Wire
(from DFC
wire
harness)
Main
Gas Inlet
3/8 in. NPT
harness)
Yellow Ground Wire
(from DFC
wire harness)
Hi/Lo
Flame
Control
Knob
Propane tanks are at pressures that will
cause damage to valve components. Verify
that the tanks have step down regulators to
reduce the pressure to safe levels.
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from
value delivered must be reduced by either:
• Using gas that has been derated by the
gas company.
• Changing the burner orifice to a
smaller size as regulated by the local
authorities having jurisdiction and by
the (USA) National Fuel Gas Code NFPA
54/ANSI Z223.1—latest edition or, in
Canada, the CAN/CSA-B149.1 codes—
latest edition.
NOTE: Flame breadth, height and width will
diminish 4% for every 1,000 feet of altitude.
Table 4: Burner Orifice Sizes,
Elevation 0–4500 ft ( 0–1372 m)
Model
NV35IN
NVCD35IN
NV40IN
NVCD40IN
NV45IN
NVCD45IN
* Standard size installed at factory
• Catalog number
Natural Gas
drill size
Front
#49 (0.073 in.)*
Back
#43 (0.089 in.)*
Front
#42 (0.0935 in.)*
Back
#55 (0.052 in.)*
Front
#41 (0.096 in.)*
Back
#43 (0.089 in.)*
Front
#35 (0.11 in.)*
Back
#52 (0.0635 in.)*
Front
#40 (0.098 in.)*
Back
#40 (0.098 in.)*
Front
#32 (0.116 in.)*
Back
#49 (0.073 in.)*
Propane
drill size
Front
#57 (0.043 in.)*
Back
#54 (0.055 in.)*
Front
#55 (0.052 in.)*
Back
#60 (0.040 in.)*
Front
#55 (0.052 in.)*
Back
#55 (0.052 in.)*
Front
#53 (0.0595 in.)*
Back
#65 (0.035 in.)*
Front
#54 (0.055 in.)*
Back
#54 (0.055 in.)*
Front
#51 (0.067 in.)*
Back
#62 (0.038 in.)*
the gas supply piping system by closing
In Canada—CAN/CGA-2.17-M91
(high altitude):
THE CONVERSION SHALL BE CARRIED
OUT BY A MANUFACTURER’S
AUTHORIZED REPRESENTATIVE, IN
ACCORDANCE WITH THE REQUIREMENTS
OF THE MANUFACTURER, PROVINCIAL
OR TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE
WITH THE REQUIREMENTS OF THE
CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
REQUIREMENTS FOR
THE COMMONWEALTH
OF MASSACHUSETTS
These fireplaces are approved for
installation in the U.S. state of
Massachusetts if the following additional
requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations
248 C.M.R..
• Installation and repair must be done by
a plumber or gas fitter licensed in the
Commonwealth of Massachusetts.
• The flexible gas line connector used
shall not exceed 36 in. (914 mm)
in length.
• The individual manual shut-off must be
a T-handle type valve.
Massachusetts Horizontal Vent
Requirements
In the Commonwealth of Massachusetts,
horizontal terminations installed less than
seven (7) feet above the finished grade
must comply with the following additional
requirements:
• A hard wired carbon monoxide detector
with an alarm and battery back-up must
be installed on the floor level where the
gas fireplace is installed. The carbon
monoxide detector must comply with
NFPA 720, be ANSI/UL 2034 listed and
be ISA certified.
• A metal or plastic identification plate
must be permanently mounted to the
exterior of the building at a minimum
height of eight (8) feet above grade and
be directly in line with the horizontal
termination. The sign must read, in
print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS.
its equipment shutoff valve during any
pressure testing of the gas supply piping
system at test pressures equal to or less
than 1/2 psi (3.5 kPa).
4
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 5
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to
insulate outside chase cavity between studs
and under floor on which appliance rests, if
floor is above ground level. Gas line holes
and other openings should be caulked or
stuffed with unfaced fiberglass insulation.
CAUTION
Ensure that the cross members
are not cut or weakened during
installation. The structural
integrity of the manufactured
home floor, wall, and ceiling /
roof must be maintained.
Figure 2: Typical Locations
T
NOITACILPPA
NEVP
O
T
TNEVPOT
APPLICATION
TOP VENT
If the fireplace is being installed on a
cement slab in cold climates, a sheet of
plywood or other raised platform can be
placed underneath to prevent conduction
of cold transferring to the fireplace and
into the room. It also helps to sheetrock
inside surfaces and tape for maximum air
tightness and caulk firestops.
CAUTION
This appliance must be
grounded to the chassis of
the manufactured home in
accordance with local codes or in
the absence of local codes, with
RECESSED
INSTALLATION
APPLICATION
the National Electrical Code ANSI
MANUFACTURED HOME
REQUIREMENTS
This appliance may be installed in
an aftermarket permanently located,
manufactured home and must be installed
in accordance with the manufacturer’s
instructions and the Manufactured Home
Construction and Safety Standard, Title 24
CFR, Part 3280, in the United States, or the
Standard for Installation in Mobile Homes,
CAN/CSA Z240 MH Series, in Canada.
fire-parts.com
Cet appareil peut être installé
cómme du matéri-el d’origine dans
une maison préfabriquée (É.U.
seulement) ou mobile et doit être
installé selon les instructions du
fabricant et conformément à la norme
Manufactured Home Constructions and
Safety, Title 24 CFR, Part 3200 aux Unis
ou à la norme Can/CSA-Z240 Série MM,
Maisons mobiles au Canada.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement
avec le type de gaz indiqué sur la plaque
signalétique. Cet appareil ne peut être
converti à d’autres gaz, sauf si une
trousse de conversion est utilisée.
/ NFPA 70—latest edition or the
Canadian Electrical Code CSA
C22.1—latest edition.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply
are also important. The appliance may be
installed in a bedroom.
Due to high temperatures, the appliance
should be located out of traffic and away
from furniture and draperies.
En raison des températures élevées,
l’appareil devrait être installé dans un
endroit où il y a peu de circulation et
loin du mobilier et des tentures.
The location should also be free of
electrical, plumbing, or other heating/air
conditioning ducting.
These direct-vent appliances are uniquely
suited for installations requiring a utility
shelf positioned directly above the fireplace.
Utility shelves like these are commonly
used for locating television sets and
decorative plants.
Be aware that this is a heat producing
appliance. Objects placed above the unit are
exposed to elevated temperatures.
Do not insulate the space between the
appliance and the area above it.
The minimum height from the base of the
appliance to the underside of combustible
materials used to construct a utility shelf in
this fashion is shown in
The appliance should be mounted on a
fully supported base extending the full
width and depth of the unit. The appliance
may be located on or near conventional
construction materials. However, if
installed on combustible materials, such as
carpeting, vinyl tile, etc., a metal or wood
barrier covering the entire bottom surface
must be used.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 8.
HORIZONTAL VENT
(Top Vent Application)
N
O
I
TNEVPOT
NOITACILPPA
TOP VENT
VERTICAL VENT
(Top Vent Application)
T
A
C
I
L
P
P
A
5
Page 6
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
12
X
Roof Pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
Discharge
Opening
H*
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
Horizontal Overhang
Vertical
Wall
Vent
Termination
Storm Collar
Concentric
Vent Pipe
Flashing
1 in. (25.4 mm) Minimum
Clearance to Combustibles
Horizontal Vent Termination Clearances
VENT TERMINATION CLEARANCES
Figure 4: Vertical Vent Termination Clearances
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to
local codes, these instructions, the current
National Fuel Gas Code (ANSI-Z223.1) in
the USA, or the current standards of CAN/
CSA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations
according to the installation codes listed
above (Figure 3).
Figure 3: Multiple Terminations
12 in.
(305 mm)
minimum
Terminate single vent caps relative to
building components according to Table 5
and Figure 4.
Table 5: Termination Heights for Vents
fire-parts.com
above Flat or Sloped Roofs
(NFPA 54 / ANSI Z223.1)
Roof PitchTermination Height
Flat to 6/12
6/12 to 7/121.25 ft (0.38 m)
7/12 to 8/121.5 ft (0.46 m)
8/12 to 9/122.0 ft (0.61 m)
9/12 to 10/122.5 ft (0.76 m)
10/12 to 11/123.25 ft (0.99 m)
11/12 to 12/124.0 ft (1.22 m)
12/12 to 14/125.0 ft (1.52 m)
14/12 to 16/126.0 ft (1.83 m)
16/12 to 18/127.0 ft (2.13 m)
18/12 to 20/127.5 ft (2.29 m)
20/12 to 21/128.0 ft (2.44 m)
1.0 ft (0.3 m)
Figure 5: Horizontal Vent Termination Clearances
Combustible Projection
2 1/2
Combustible Projection greater
than 2 1/2 in. in length
Ventilated
Soffit
Unventilated
Soffit
18 in.
(457 mm)
12 in.
(305 mm)
in. or less in length
6 in.
(152 mm)
All horizontal terminations
may be located as close as
6 in. (152 mm) to any
combustible exterior
sidewall. This distance
may be decreased to 4 in.
(102 mm) for noncombustible exterior
sidewalls.
Side Elevation View
Termination Kit
See Figure 24 for the exterior wall
recess allowances of the square
horizontal termination.
Termination Kit
Horizontal Vent Termination
Clearances
6
The horizontal vent termination must have
a minimum of 6 in. (152 mm) clearance
to any overhead combustible projection of
2 1/2 in. (64 mm) or less (see Figure 5). For
projections exceeding 2 1/2 in. (64 mm),
see Figure 5. For additional vent location
restrictions refer to Table 6 on Page 7.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
U.S. Installation **Canadian Installation *
A Clearance above grade, veranda, porch, desk, or balcony
B Clearance to window or door that may be opened
12 in. (300 mm) **12 in. (300 mm) *
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
9 in. (230 mm)
for appliances > 10,000 Btuh (3 kW), and < 50,000 Btuh (15 kW),
12 in. (300 mm)
for appliances > 50,000 Btuh (15 kW) **
C Clearance to permanently closed window
fire-parts.com
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18 in. (458 mm)
E Clearance to unventilated soffit
F Clearance to outside corner
G Clearance to inside corner
9 in. (229 mm)
recommended to prevent window condensation
18 in. (458 mm)18 in. (458 mm)
12 in. (305 mm)
30 in. (760 mm) to vinyl soffit
5 in. (127 mm)
minimum
2 in. (50.8 mm)
minimum—SV4.5HT-2 •
6 in. (152 mm)
minimum—SV4.5HTSS
H Clearance to each inside of center line extended above
meter / regulator assembly
I Clearance to service regulator vent outlet
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other appliance
36 in. (910 mm)
within a height of 15 ft above the meter / regulator assembly **
36 in. (910 mm)**36 in. (910 mm)*
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
9 in. (230 mm)
for appliances > 10,000 Btuh (3 kW) and < 50,000 Btuh (15 kW),
12 in. (300 mm)
for appliances > 50,000 Btuh (15 kW)**
K Clearance to a mechanical air supply inlet
L Clearance above paved sidewalk or paved diveway located
36 in. (910 mm) above if within 10 ft (3 m) horizontally **72 in. (1830 mm) *
84 in. (2130 mm) ‡84 in. (2130 mm) ‡
on public property
M Clearance under veranda, porch, deck or balcony
N Depth of alcove (maximum)
O Clearance to termination (alcove)
P Width of alcove (minimum)
Q Clearance to combustible above (alcove)
*
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
**
In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes
‡
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
•
2 in. clearance to non-combustibles for SV4.5HT-2 only
12 in. (300 mm) *‡12 in. (300 mm) *‡
72 in. (1830 mm) **72 in. (1830 mm) *
6 in. (15.2 mm) **6 in. (15.2 mm)*
36 in. (910 mm) **36 in. (910 mm) *
18 in. (457 mm) **18 in. (457 mm) *
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
May Require Different Clearances.
NOTE: Location Of The Vent Termination
Must Not Interfere With Access To The
Electrical Service.
= 9 in. (in U.S.)
A
= 12 in. (in Canada)
3 ft.
X
A
A
3 ft.
J
P
N
H
M
I
N
O
V
Q
D
V
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
12 in. (300 mm)
for appliances > 10,000 Btuh (3 kW)
12 in. (305 mm)
recommended to prevent
window condensation
12 in. (305 mm)
30 in. (760 mm) to vinyl soffit
5 in. (127 mm)
minimum
2 in. (50.8 mm)
minimum—SV4.5HT-2 •
6 in. (152 mm)
minimum—SV4.5HTSS
36 in. (910 mm)
within a height of 15 ft above the meter /
regulator assembly *
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
12 in. (300 mm)
for appliances > 10,000 Btuh (3 kW)
E
V
7
Page 8
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
5 (127)
12 (305)
MINIMUM CLEARANCES TO
COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero
clearance to combustible materials on
all sides (Table 7), with the following
exception: When the unit is installed with
one side flush with a wall, the wall on the
other side of the unit must not extend
beyond the front edge of the unit. In
addition, when the unit is recessed, the side
walls surrounding the unit must not extend
beyond the front edge of the unit (Figure 7).
Table 7: Minimum Clearances *
Back
Sides
Top Spacers
Floor
From Bottom of
Unit to Ceiling
Front Service
Clearance
* 3 in. (76 mm) above any horizontal/inclined vent
component.
** See Page 9 for clearance requirements to the
nailing flange located at each side of the unit and
fire-parts.com
any screw heads adjacent to it.
1/2 in. (13 mm) to wrapper
0 in. (0 mm) to Spacers
1/2 in. (13 mm) to wrapper
0 in. (0 mm) to Spacers **
0 in. (0 mm)
0 in. (0 mm)
78 in. (1981 mm)
36 in. (914 mm) Top *
12 in. (305 mm) Sides and Bottom
Hearth Extension
A hearth extension must be built from
non-combustible, heat-resistant materials
Wall Finishes / Surrounds / Mantels
Combustible wall finish materials and/or
surround materials must not be allowed to
encroach the area defined by the appliance
front face (black sheet metal). Never allow
combustible materials to be positioned in
front of or overlapping the appliance face
(Figure 7).
Non-combustible materials, such as
surrounds and other appliance trim, may be
installed on the appliance face with these
exceptions: they must not cover any portion
of the removable glass panel.
Vertical installation clearances to
combustible mantels vary according to
the depth of the mantel (Table 8). Mantels
constructed of non-combustible materials
may be installed at any height above the
appliance opening; however, do not allow
anything to hang below the fireplace hood.
Figure 6: Shelf Height
28 (711)
26 (660)
24 (607)
22 (559)
20 (508)
18 (457)
12
(305)
10
(254)
8
(203)
6
(152)
Table 8: Combustible Shelf Height
Top Vent with one 90° Elbow
Model
NV35
NV40
NV45
78 in.
Minimum
Shelf Height
(see table)
* Includes 3 in. (76 mm) clearance to combustibles
(required above vent components)
4
2
(102)
(51)
Secure Vent
73 1/2 in.
(1867 mm) *
(e.g., Micore® 160, Glasscrete®, Durock®, or
a similar material). It must extend the width
of the fireplace opening and at least 20 in.
in. (mm)
in front of the fireplace.
• A hearth extension is required if the
fireplace is installed less than 6 in.
above the finished floor surface.
• A hearth extension is not required if the
fireplace is installed at least 6 in. above
the finished floor surface.
Shelf Height
To provide for the lowest possible shelf
surface, the venting attached to the
top vent should be routed in a way to
minimize obstructions to the space above
the appliance. Do not insulate the space
between the appliance and the area above it
(Figure 6).
Figure 7: Combustible Side Clearances
At 14 1/2 in.
minimum
side wall
clearance, a
combustible
wall can
project to
any length.
At 13 3/4 in.
side wall
clearance, a
combustible
wall can
project 12 in.
45
At 5 1/2 in.
side wall
clearance, a
combustible
wall can
project 5 in.
o
Top View of
Fireplace
Combustible Materials
Allowed In Shaded
Area “Safe Zone”
Combustible Walls
shown in dark gray
Combustible materials
may project beyond
one sideof the fireplace
opening as long as
they are kept within
the shaded areas
illustrated here.
Secure Flex®
®
(flex elbow)
73 1/2 in.
(1867 mm) *
Minimum 12 in.
(305 mm) vent
section required
before elbow.
No combustibles
or insulation
in the shaded
area between
the appliance
and the shelf
above it.
in. (mm)
Protected wall shown in white
8
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
D
TYPICAL INSTALLATION SEQUENCE
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil
sont utilisées.
PRE-INSTALLATION STEPS
The appliance is shipped with all gas
controls and components installed and
pre-wired.
1. Remove the shipping carton and the
shipping pad.
2. Remove the top louver, then remove
the surround trim assembly by
fire-parts.com
detaching it at the top of the fireplace
and lifting it 1 in. to disengage the side
tabs, then pulling it away from the
fireplace exposing the front glass door
(Figure 8).
Figure 8: Removing the surround
trim assembly
The typical sequence of installation is
outlined below. However, each installation
is unique and may result in variations to the
steps described.
See the pages referenced in the following
steps for detailed instructions.
1. Construct the Appliance Framing
(Page 9).
2. Route the Gas Supply Line to
the Appliance (Page 11)
3. Install the Vent System and
Exterior Termination (Page 11)
4. Complete the Field Wiring
(Page 23)
5. Connect the Gas Supply (Page 25)
6. Verify Correct Appliance Operation
(Page 26)
7. Contemporary Fireplaces Only:
Install the Contemporary Floor
and Contemporary Glass Media
(Page 26)
8. Install the Firebox Liners (Page 26)
9. Traditional Fireplaces Only:
Install the Logs, Decorative Volcanic
Stone, and Glowing Embers
(Page 27)
10. Install the Glass Door (Page 28)
11. Adjust the Burner to Ensure Proper
Flame Appearance (Page 28)
12. Attach the Safety-inOperation Warnings (Page 31)
Bend each of the two (2) L-shaped standoff
components, at the designated places, into
a U-shape (Figure 9). Align the closed end
of each U-shaped standoff component with
the left/right side of the top, front of the
fireplace and the attachement holes in the
top of the fireplace. Attach each U-shaped
standoff component with two (2) 5/16 in.
hex head screws. Align the center support
with the holes in the U-shaped standoff
components and the top of the fireplace.
Attach the center support with two (2)
5/16 in. hex head screws in the top and
two (2) screws in the bottom.
NOTE: Position the center support with the
larger holes at the bottom and the smaller
holes at the top.
Figure 9: Framing Standoff
The fireplace should be secured to the side
framing members using the unit’s nailing
flanges—one top and bottom on each side
of the fireplace front (Figure 10). Use 8d
nails or their equivalent.
Figure 10: Nailing Flanges *
Side
Framing
5/8 in.
Unit
Nailing
1/2 in.
Flanges
Flush
Nailing Flanges
Are Provided At
All Four Corners
Side Tabs
3. Locate the four (4) spring-loaded
latches; two above and two below the
enclosure (Figure 39).
4. Release the lower latches, by pulling
each handle out and down to unhook it
from the glass door.
5. Lightly press against the door, to hold
it in position, while releasing the two
upper latches.
6. Carefully grip the door at the top
and bottom, and remove it from the
fireplace. Place the door in a secure
location where it will not be damaged.
Construct the Appliance Framing
Frame the fireplace as illustrated in Table 9,
or Table 11 for corner installations.All
framing details must allow for a minimum
clearance to combustible framing members
as shown in Table 6 on Page 7.
If the fireplace is to be elevated above floor
level, a solid continuous platform must be
constructed below the fireplace.
Headers may be in direct contact with
the fireplace top spacers maintaining
the 15 1/2 in. (394 mm) clearance to the
fireplace top, but must not be supported
by them or notched to fit around them. All
construction above the fireplace must be
self-supporting. DO NOT use the fireplace
for structural support.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
* Left side top corner of fireplace is shown.
Requirements for other three corners are the same.
Bend out appropriate nailing flanges to
provide for proper drywall thickness to front
of firebox.
Position the fireplace within the framing
and secure it with the nailing brackets. Bend
out the appropriate nailing flanges for the
drywall/finish material to be used. Nailing
flanges are provided for flush framing,
1/2 in. (13 mm) and 5/8 in. (16 mm)
framing depths (Figure 10).
NOTE: Combustible framing may be in
direct contact with the nailing flanges
and may be located closer than 1/2 in.
(13 mm) from screw heads and the firebox
wrapper in areas adjacent to the nailing
flanges. Frame the opening to the exact
dimensions specified.
9
Page 10
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
FLUE OUTLET
4 1/2 (114)
COMBUSTION AIR
7 1/2 (190)
E
F
14.75
(267)
C
A
G
15 1/2
(394)
B
23
(584)
D
Table 9: Fireplace Framing Specifications
ModelABCD
NV35IN /
NVCD35IN
NV40IN /
NVCD40IN
NV45IN /
NVCD45IN
39.75 in.
1010 mm
44.75 in.
1137 mm
49.75 in.
1264 mm
44.75 in.
1137 mm
48.5 in.
1232 mm
52.25 in.
1327 mm
24.0 in.
610 mm
24.0 in.
610 mm
24.0 in.
610 mm
46.75 in.
1187 mm
50.5 in.
1283 mm
54.25 in.
1378 mm
Vertical Venting Through the Ceiling:
To frame the ceiling opening, use a plumb line from the ceiling
above the appliance to locate center of the vertical run. Cut and/
or frame an opening, 10 1/2 x 10 1/2 in. (267 x 267 mm) inside
dimensions, about this center mark (Table 15).
Vent Framing - Top Vent
With One 90° Elbow
B
1/2
A
A
Inches (millimeters)
Framing should be
constructed of 2x4
267
)
or larger lumber
7
(178)
12 1/8
(308)
10 1/2
(
5 1/8
(130)
D
C
C is the required framing depth dimension when the
finish material (drywall) thickness is 1/2 in. (13mm)
Table 10: Fireplace Specifications
ModelABCDEFG
fire-parts.com
NV35IN /
NVCD35IN
NV40IN /
NVCD40IN
NV45IN /
NVCD45IN
44.5 in.
1130 mm
48.25 in.
1226 mm
52.0 in.
1321 mm
24.75 in.
629 mm
28.0 in.
711 mm
32.25 in.
819 mm
28.75 in.
730 mm
33.75 in.
857 mm
38.75 in.
984 mm
39.25 in.
997 mm
44.25 in.
1124 mm
49.25 in.
1251 mm
21.85 in.
555 mm
27.0 in.
686 mm
32.0 in.
813 mm
10.93 in.
278 mm
13.5 in.
343 mm
16.0 in.
406 mm
28.5 in.
724 mm
32.25 in.
819 mm
36.0 in.
914 mm
15 1/2
(394)
A
Standoff Assembly
D
C
Table 11: Corner Framing with Horizontal Termination
ModelABCDE
NV35IN /
NVCD35IN
NV40IN /
NVCD40IN
NV45IN /
NVCD45IN
NOTE: The horizontal vent length of “A” to “B” must not exceed 28 in. (711 mm).
39.25 in.
1000 mm
44.25 in.
1124 mm
49.25 in.
1251 mm
68.00 in.
1727 mm
73.00 in.
1854 mm
78.00 in.
1981 mm
48.10 in.
1222 mm
51.60 in.
1311 mm
55.10 in.
1400 mm
13.75 in.
349 mm
15.50 in.
394 mm
17.25 in.
438 mm
34.00 in.
864 mm
36.50 in.
927 mm
39.00 in.
991 mm
D
a
C
B
G
b
7 in.
(178 mm)
E
10
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Back wall of chase/enclosure
(including any finishing materials)
A
B
Page 11
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Route the Gas Supply Line to
the Appliance
A 1/2 in. (13 mm) gas line must be
routed to the left side of the appliance
(Figure 11). Gas lines must be routed,
constructed and made of materials that
are in strict accordance with local codes
and regulations. All appliances are factoryequipped with a flexible gas line connector
and a 1/2 in. shutoff valve (Page 25).
Figure 11: Routing the gas line
Left Side Front
Corner of
Fireplace Framing
4 1/2 in.
(114 mm)
1 1/2 in.
(38 mm)
4 in.
(102 mm)
fire-parts.com
Proper Sizing of Gas Line
Properly size and route the gas supply
line from the supply regulator to the area
where the appliance is to be installed per
requirements outlined in the National Fuel
Gas Code, NFPA 54—latest edition (USA) or
CAN/CSA-B149.1—latest edition (Canada).
Never use galvanized or plastic pipe.
Refer to
the gas supply line, if black iron pipe is
being used. Gas lines must be routed,
constructed and made of materials that are
in strict accordance with local codes and
regulations.
Hire a qualified plumber or gas fitter to
correctly size and route the gas supply line
to the appliance. Installing a gas supply
line from the fuel supply to the appliance
involves numerous considerations of
materials, protection, sizing, locations,
controls, pressure, sediment, and more.
No one unfamiliar and unqualified should
attempt sizing or installing gas piping.
• All appliances are factory-equipped with
• See Massachusetts Requirements
• The gas supply line should not be
• A pipe joint compound rated for gas
• A sediment trap in the supply line as
• Check with the local building official
Table 12 for proper sizing of
Table 12: Schedule 40 Black Iron Pipe,
Inside Diameter
Pipe LengthNatural GasPropane Gas
0–10 ft1/2 in.3/8 in.
10–40 ft1/2 in.1/2 in.
40–100 ft1/2 in.1/2 in.
100–150 ft3/4 in.1/2 in.
150–200 ft3/4 in.1/2 in.
a flexible gas line connector and 1/2 in.
shutoff valve (Figure 31).
(Page 4) for additional
requirements for installations in the
state of Massachusetts in the USA.
connected to the appliance until
Page 25.
should be used on the threaded joints.
Ensure propane-resistant compounds
are used in propane applications. Be
very careful that the pipe compound
does not get inside the pipe.
close as possible to the appliance
is recommended. Appliances using
propane should have a sediment trap at
the base of the tank.
for local code requirements (e.g., Are
below grade penetrations of the gas line
allowed?, etc).
CAUTION
If propane is used, be aware
that with a tank that is too small
(i.e., under 100 lbs, if this is
the only gas appliance in the
dwelling—see NPFA 58), there
may be a loss of pressure. This
can result in insufficient fuel
delivery that can cause sooting,
severely delayed ignition, or
other malfunctions. Any damage
resulting from an improper
installation is not covered by the
limited warranty.
Install the Vent System and
Exterior Termination
NOTE: These instructions should be used
as a guideline and do not supersede
local codes in any way. Install venting
according to local codes, these instructions,
the current National Fuel Gas Code
(ANSI-Z223.1) in the USA or the current
standards of CAN/CSA-B149.1 in Canada.
Ensure clearances are in accordance
with local installation codes and the
requirements of the gas supplier.
Dégagement conforme aux codes
d’installation locaux et aux exigences du
foumisseunde gaz.
Use only approved venting components
(Page 2). These fireplaces must be
vented directly to the outside.
The vent system may not service multiple
appliances, and must never be connected to
a flue serving a solid fuel burning appliance.
The vent pipe is tested to be run inside an
enclosed wall (such as a chase). Inspection
openings in the enclosing wall, at the vent
pipe joints, are not required.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Page 12
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Installation of Vent Restrictor
A vent restrictor may be needed with this
appliance. The restrictor is installed in the
appliance top flue outlet (Figure 13), either
before adding vent from above, or after
installation of vent from below—within the
firebox. The restrictor is self securing with a
positive friction fit.
Determine the vent restrictor configuration
for the appliance (
Use the base vent restrictor for:
• Horizontal termination with total vertical
run of more than 6 ft.
• Vertical termination with total vertical
run of 6–10 ft.
Use intermediate setting for:
• Vertical termination with total vertical
run of >10–40 ft.
Use the maximum setting for:
• Vertical termination with total vertical
run of >40–60 ft.
Figure 12):
Figure 12: Vent Restrictor Configuration
Base Vent Restrictor
Intermediate Vent Restrictor
fire-parts.com
Maximum Vent Restrictor
Figure 13: Vent Restrictor Installation
Vent
Collar
Vent
Restrictor
Assembly
(held in place
by friction only)
12
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
10 1/2 in. Min.
SV4.5CGV-1
Select Venting System—
Horizontal or Vertical
With the appliance secured in the framing,
determine the vent routing and identify the
exterior termination location. The following
sections describe vertical (roof) and
horizontal (exterior wall) vent installations.
A list of approved venting components are
shown on Page 32.
Vertical (Roof) Termination Systems
See the tables starting on Page 17 for
the various vertical venting configurations
that are possible for use with these
appliances. Secure Vent™ pipe applications
are shown in these figures. Secure Flex™
pipe may also be used. A vertical vent table
summarizes each system’s minimum and
maximum vertical and horizontal lengths.
Both vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is
specified in ANSI Z223.1—latest edition
(In Canada, the current CAN/CSA-B149.1
installation code) by major building codes.
Always consult your local codes for specific
requirements. A general guide to follow is
the Gas Vent Rule (
Page 6).
Vertical (Straight) Installation
Determine the number of straight vent
fire-parts.com
sections required. 4 1/2 in. (114 mm),
10 1/2 in. (267 mm), 22 1/2 in. (572 mm),
34 1/2 in. (876 mm) and 46 1/2 in.
(1181 mm) net section lengths are
available. Plan the vent lengths so that a
joint does not occur at the intersection of
ceiling or roof joists.
Figure 14: Vertical (Straight) Installation
Termination
SV4.5FA OR
SV4.5FB Flashing
AND SV4.5SC
STORM COLLAR
Analyze the vent routing and determine the
quantities of vent sections and number of
elbows required. Refer to the vertical vent
figures and tables starting on Page 17
to select the type of vertical installation
desired. Vent sections are available in net
lengths of 4 1/2 in. (114 mm), 10 1/2 in.
(267 mm), 22 1/2 in. (572 mm), 34 1/2 in.
(876 mm) and 46 1/2 in. (1181 mm). Refer
to Table 13 for an aid in selecting length
combinations. Elbows are available in 90°
and 45° configurations. Refer to Figure 18
on Page 15 for the SV4.5E45 and
SV4.5E90 elbow dimensional specifications.
Where required, a telescopic vent section
(SV4.5LA) may be used to provide the
installer with an option in installing in
tight and confined spaces, or where the
vent run made up of fixed length pieces
results in a joint in a undesirable location
or will not build up to the required length.
The SV4.5LA telescopic vent section
has an effective length of from 1 1/2 in.
(38 mm) to 7 1/2 in. (191 mm). The
SV4.5LA is fitted with a locking inclined
channel end (identical to a normal vent
section component) and a plain end with
3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5
vent component the required distance and
secure with three screws.
Maintain a minimum 1 in. (25 mm)
clearance to combustible materials for
all vertical elements. Clearances for all
horizontal elements are 3 in. (76 mm)
on top, 1 in. (25 mm) on sides and 1 in.
(25 mm) on the bottom.
1. Frame ceiling opening—Use a plumb
line from the ceiling above the appliance
to locate center of the vertical run.
Cut and/or frame an opening, 10 1/2
x 10 1/2 in. (267 x 267 mm) inside
dimensions, about this center mark
(Figure 15).
Figure 15: Ceiling Opening
1 in. (25.4 mm)
Minimum
Clearance to
Combustibles
SV4.5VF
Firestop/Spacer
Roof
Framing
10 1/2 in. Min.
(267 mm)
(267 mm)
2. Attach vent components to appliance—
Secure Vent SV4.5 direct-vent system
components are unitized concentric
pipe components featuring positive
twist lock connections (Figure 16).
To attach a vent component to the
appliance collar, align the dimpled
end over the collar, adjusting the
radial alignment until the four locking
dimples are aligned with the inlet of
the four inclined channels on the collar
(Figure 16). Push the vent component
against the collar until it fully engages,
then twist the component clockwise,
running the dimples down and along
the incline channels until they seat at
the ends of the channels.
Slide the rope gasket over the vent
component and position it snugly
against the apppliance.
The unitized design of Secure Vent™
components will engage and seal both
the inner and outer pipe without the
need for sealant or screws. If desired,
a #6 x 1/2 in. screw may be used at the
joint, but is not required as the pipe will
securely lock when twisted. An elbow
may not be directly attached to the
appliance collar.
NOTE: All of the appliances covered in
this document are fitted with collars
having locking inclined channels. The
dimpled end of the vent components fit
over the appliance collar to create the
positive twist lock connection.
Figure 16: Appliance Collar
Align the dimple (4 places) of the
upper vent section with the opening
of the locking incline channel on the
lower vent section or appliance collar.
Twist vent component clockwise to
engage and seal until arrow and
Arrow
Appliance Collar or
Vent Section
dimple align.
Dimple
Locking
Incline
Channel
Connected Vent
Sections
Arrow
60 ft Maximum
(18.3 m)
6 ft Minimum
(1.8 m)
SV4.5L6/12/24/36/48
Vent Sections
When using Secure Flex
use Firestop/Spacer
SF4.5VF
Vertical (Offset) Installation
Ceiling
Framing
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Plumb
Bob
13
Page 14
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
3. Attach vent components to each
other—Additional vent sections may be
added to the previously installed section
in accordance with the requirements of
the vertical vent figures and tables.
4. Install firestop/spacer at ceiling—When
using Secure Vent™, use SV4.5VF
firestop/spacer at ceiling joists. When
using Secure Flex™, use SF4.5VF
firestop/spacer. If there is living space
above the ceiling level, the firestop/
spacer must be installed on the bottom
side of the ceiling. If attic space is
above the ceiling, the firestop/spacer
must be installed on the top side of the
joist. Route the vent sections through
the framed opening and secure the
firestop/spacer with 8d nails or other
appropriate fasteners at each corner.
Remember to maintain 1 in. (25 mm)
clearance to combustibles, framing
members, and attic or ceiling insulation
when running vertical chimney sections.
Attic insulation shield (H3907) may be
used to obtain the required clearances.
The gap between the vent pipe and
a vertical firestop can be sealed with
non-combustible caulking.
fire-parts.com
14
Table 13: Vent Section Length
Nominal
Section Length
(in.)
Net Section
Length (in.)
Height of Vent
in.ft
4.50.375100001
90.75200002
10.50.875010001
151.25110002
22.51.875001001
31.52.625030003
34.52.875000101
37.53.125111003
43.53.625021003
453.75002002
46.53.875000011
514.25100012
55.54.625012003
574.75001102
67.5
695.75000202
73.56.125100203
79.56.625010203
816.75000112
91.57.625002013
937.75000022
97.58.125100023
103.58.625000303
1089100304
1179.75105006
118.59.875110305
12610.5001304
130.5 10.875101305
13511.25006006
139.5 11.625000033
142.5 11.87510040
14412100034
154.5 12.875110035
160.5 13.375020035
172.5 14.375000505
17714.75100506
18615.5000044
196.5 16.375010045
20717.25000606
211.5 17.625100607
217.5 18.125010607
229.5 19.125001607
232.5 19.375000055
241.5 20.125000707
24620.5100708
25221010708
27623000808
27923.25000
280.5 23.375100809
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
612243648
4.510.522.534.546.5
Number of Vent Sections
5.625003003
066
Table 13: Vent Section Length
Nominal
Section Length
(in.)
Net Section
Length (in.)
Total Qty
Height of Vent
in.ft
289.5 24.125010067
301.5 25.125001067
310.5 25.875000909
325.5 27.125000077
33027.5100078
34528.7500010010
349.5 29.12510010011
37231000088
379.5 31.62500011011
46538.7500001010
475.5 39.62501001011
4804011001011
4924110101012
499.5 41.62500011011
504
511.5 42.62500001111
520.5 43.37502011114
53144.2502201115
538.5 44.87510021114
54945.7510211115
55846.500001212
562.5 46.87510001213
568.5 47.37501001213
57347.7511001214
580.5 48.37500101213
589.5 49.12501221015
595.5 49.62511101215
604.5 50.37500001313
61551.2501001314
625.5 52.12502001315
5
631.5 52.625101013
637.5 53.12501101315
65154.2500001414
655.5 54.62510001415
6725602001416
67856.510101416
688.5 57.37511101417
697.5 58.12500001515
70258.510001516
712.5 59.37511001517
7206000101516
612243648
4.510.522.534.546.5
Number of Vent Sections
4210011012
Total Qty
15
Page 15
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Table 14: Effective Vent Length
ModelEffective Length
SV4.5L6
SV4.5L1210 1/2 in.
SV4.5L2422 1/2 in.
SV4.5L3634 1/2 in.
SV4.5L4846 1/2 in.
4 1/2 in.
5. Support the vertical vent run sections—
Support the vertical portion of the
venting system every 8 ft (2.4 m) above
the fireplace vent outlet. One method
of support is by utilizing field provided
support straps (conventional plumber’s
tape). Secure the plumber’s tape to
the framing members with nails or
screws. Loop the tape around the vent
and secure the ends of the tape to the
framing. If desired, sheet metal screws
(#6 x 1/2 in.) may be used to secure
the support straps to the vent pipe
(Figure 17).
Figure 17: Venting Support
Blocking
Support Straps
(Plumber's tape)
6. Change vent direction to horizontal/
inclined run—At transition to/from
a horizontal/inclined run, install the
SV4.5E45 and SV4.5E90 elbows in
the same manner as the straight vent
sections. The elbows feature a twist
section to allow them to be routed
about the center axis of their initial
collar section to align with the required
direction of the next vent run element.
Twist elbow sections in a clockwise
direction only, to avoid the possibility
of unlocking any of the previously
connected vent sections (Figure 16).
Figure 18: Elbow Mounting
4 13/16 in.
(122 mm)
Swivel Joint
(360° swivel)
SV4.5E45
(45° Elbow)
Swivel Joint
(360° swivel)
(90° Elbow)
7. Continue installation of horizontal/
inclined sections—Continue with the
8 ft (2.4 m)
maximum
installation of the straight vent sections
in horizontal/inclined run. Install
support straps every 5 ft (1.52 m)
fire-parts.com
1/2 in. (12.7 mm)
minimum
clearance to
combustibles
along horizontal/inclined vent runs
using conventional plumber’s tape
(Figure 22). Maintain the horizontal/
inclined run in a straight (no dips) and
slightly elevated (recommended) plane,
in a direction away from the fireplace of
1/4 in. rise per foot (20 mm per meter).
Smaller rise per foot run ratios are
NOTE: Proper venting support is very
important. The weight of the vent must
not be supported by the fireplace.
acceptable all the way down to at/near
level. Use a carpenter’s level to measure
from a constant surface and adjust the
support straps as necessary.
SV4.5E90
8 1/8 in.
(206 mm)
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: Maintain the required clearances
to combustibles: 1 in. (25 mm) at all
sides for all vertical runs; and 3 in.
(76 mm) at the top, 1 in. (25 mm) at
sides, and 1 in. (25 mm) at the bottom
for all horizontal/inclined runs.
15
Page 16
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
C
D
8. Frame the roof opening—Identify the
location for vent at the roof. Cut and/or
frame the opening per Table 15.
Table 15: Roof Framing Dimensions
PitchCD
0/1210 1/2 in.
6/1210 1/2 in.
12/1210 1/2 in.
9. Install the roof flashing—Extend
the vent sections through the roof
structure. Using a carpenter’s level,
install the roof flashing over the vent
section and position it such that the
vent column rises vertically (Figure 19).
Nail along perimeter to secure flashing
or adjust roofing to overlap the flashing
fire-parts.com
edges at top and sides only and trim
where necessary. Seal the top and both
sides of the flashing with waterproof
caulking.
(267 mm)
(267 mm)
(267 mm)
10 1/2 in.
(267 mm)
12 in.
(305 mm)
17 3/4 in.
(451 mm)
10. Install the storm collar—Install the
storm collar, supplied with the flashing,
over the vent/flashing joint (Figure 19).
Loosen the storm collar screw. Slide the
collar down until it meets the top of the
flashing. Tighten the adjusting screw.
Apply non-combustible caulking or
mastic around the circumference of the
joint to provide a watertight seal.
Figure 19: Storm Collar
Storm
Flashing
Collar
11. Install the vertical termination
(SV4.5CGV-1)—Extend the vent
sections to the correct height
(Figure 4). The SV4.5CGV-1 vertical
termination (Figure 20) can be installed
in the exact same fashion as any
other Secure Vent™ section. Align
the termination over the end of the
previously installed section, adjusting
the radial alignment until the four
locking dimples of the termination
are aligned with the inlets of the four
incline channels of the last vent section.
Push the termination down until it fully
engages, then twist the termination
clockwise running the dimples down
and along the incline channels until they
are seated at the end of the channels.
If the vent system extends more than
5 ft (1.5 m) above the roof flashing,
stabilizers may be necessary. Additional
screws may be used at section joints
for added stability. Guide wires may
be attached to the joint for additional
support on multiple joint configurations.
Figure 20: Vertical Termination
16
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Vertical Vent Tables and Figures
Table 16: Top Vent—Two 90° Elbows
Table 17: Top Vent—Three Elbows
NOTE: Secure Vent® rigid vent pipe
is shown in the figures. Secure Flex®
flexible vent pipe may also be used.
H
V
1
Ceiling
Firestop/Spacer
SV4.5VF*
NOTE: It is very important that the
horizontal/inclined run be maintained
in a straight (no dips), slightly elevated
plane. The recommended incline is
approximately 1/4 in. per foot (20 mm
per meter) horizontal, in a direction
away from the fireplace. The rise per
foot run ratios that are smaller are
acceptable all the way down to at or
near level.
NOTE: SV4.5VF (Secure Vent), SF4.5VF
V1
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
H
1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
H
(Secure Flex) firestop/spacer must be
used anytime vent pipe passes through
a combustible floor or ceiling. SV4.5HF
(Secure Vent), SF4.5HF (Secure Flex)
firestop/spacer must be used anytime
vent pipe passes through a combustible
wall.
NOTE: Two 45° elbows may be used in
place of one 90° elbow. The same rise
to run ratios, as shown in the venting
figures for 90°, must be followed if 45°
elbows are used.
NOTE: An elbow is acceptable as 1 ft of
vertical rise, but may not be connected
fire-parts.com
directly to the appliance collar.
WARNING
Under no circumstances, may
separate sections of concentric
flexible vent pipe be joined
together.
Figure 21: Top Vent—Straight
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
H MaximumV Minimum
feetmetersfeetmeters
51.52420.610
103.04830.914
154.57241.219
206.09651.524
V + V
+ H = 60 ft (18.3 m) maximum
1
H = 20 ft (6.096 m) maximum
Install the U-shaped vent restrictor in any vent run
with more than 6 ft of vertical rise. See Page 12
for more information.
If 20 ft of (H) horizontal vent run is needed,
then 4 ft (straight section) minimum of
(V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 ft of (V) vertical, you are allowed
5 ft of (H) horizontal run, up to a maximum
V
H + H1 MaximumV Minimum
feetmetersfeetmeters
51.52410.305
51.52410.305
103.04820.610
154.57230.914
206.09641.219
H + H
= 20 ft (6.1 m) maximum
1
V + V1 + H + H1 = 60 ft (18.3 m) maximum
Install the U-shaped vent restrictor in any vent run
with more than 6 ft of vertical rise. See Page 12
for more information.
If 20 ft of (H) horizontal vent run is needed,
then 4 ft (straight section) minimum of
(V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 ft of (V) vertical, you are allowed
5 ft of (H) horizontal run, up to a maximum
horizontal run of 20 ft.
An elbow is acceptable as 1 ft of vertical
rise, but may not be connected directly to
the appliance collar.
NOTE: The vent system may have a
maximum of three (3) 90° elbows.
horizontal run of 20 ft.
An elbow is acceptable as 1 ft of vertical
rise, but may not be connected directly to
the appliance collar.
u Ceiling Firestop /
Spacer (SV4.5VF)
60 ft (18.3 m)
Maximum
Wall
Firestop/Spacer
SV4.5HF**
V
When using
u
Secure Flex, use
Firestop / Spacer
SF4.5VF
Install the U-shaped vent restrictor in any vent run
with more than 6 ft of vertical rise. See Page 12
for more information.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Page 18
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Horizontal (Outside Wall)
Termination System
See the horizontal vent tables on Page 20
that illustrate the various horizontal venting
configurations that are possible for use
with these appliances. Secure Vent™ pipe
applications are shown in these figures;
Secure Flex™ pipe may also be used. The
tables summarize each system’s minimum
and maximum vertical and horizontal
lengths for installing the vent components
in a variety of applications.
These horizontal vent systems terminate
through an outside wall. Building codes
limit or prohibit terminating in specific areas
(
Table 6).
Secure Vent SV4.5 direct-vent system
components are unitized concentric pipe
components featuring positive twist
lock connections (Figure 16). All of the
appliances covered in this document are
fitted with collars having locking inclined
channels. The dimpled end of the vent
components fit over the appliance collar to
create the positive twist lock connection.
1. Plan the vent run—Analyze the vent
routing and determine the types and
quantities of sections required: 4 1/2 in.
(114 mm), 10 1/2 in. (267 mm),
22 1/2 in. (572 mm), 34 1/2 in.
(876 mm) and 46 1/2 in. (1181 mm)
fire-parts.com
net section lengths are available. Plan
the vent lengths so that a joint does
not occur at the intersection of ceiling
or roof joists. Make allowances for
elbows. Maintain a minimum 1 in.
(25 mm) clearance to combustibles on
the vertical sections. Clearances for the
horizontal runs are 3 in. (76 mm) on
top, 1 in. (25 mm) on sides, and 1 in.
(25 mm) at the bottom.
2. Frame exterior wall opening—Locate
the center of the vent outlet on
the exterior wall according to the
dimensions shown in (Figure 23).
Cut and/or frame an opening, 10 1/2
x 12 1/8 in. (267 x 308 mm) inside
dimensions, about this center.
3. Frame ceiling opening—If the vertical
route will penetrate a ceiling, use
a plumb line to locate the center
above the appliance. Cut and/or
frame an opening, 10 1/2 x 10 1/2 in.
(267 x 267 mm) inside dimensions,
about this center (Table 15).
4. Attach vent components to appliance—
To attach a vent component to the
appliance collar, align the dimpled
end over the collar, adjusting the
radial alignment until the four locking
dimples are aligned with the inlets of
the four incline channels on the collar
(Figure 16). Push the vent component
against the collar until it fully engages,
then twist the component clockwise,
running the dimples down and along
18
the incline channels until they seat at
the end of the channels.
Slide the rope gasket over the vent
component and position it snugly
against the apppliance.
The unitized design of Secure Vent™
components will engage and seal both
the inner and outer pipe elements
with the same procedure. Sealant and
securing screws are not required.
NOTE: An elbow may not be attached
directly to the appliance collar. At a
minimum, a 12 in. (305 mm) straight
vent section is required before
attaching the first elbow (Figure 22).
5. Attach vent components to each
other—Other vent sections may be
added to the previously installed section
in accordance with the requirements
of the vent tables. To add another vent
component to a length of vent run,
align the dimpled end of the component
over the inclined channel end of the
previously installed section, adjusting
the radial alignment until the four
locking dimples are aligned with the
inlets of the four incline channels of
the previous section. Push the vent
component against the previous section
until it fully engages, then twist the
component clockwise running the
dimples down and along the incline
channels until they seat at the end of
the channels. This seating position is
indicated by the alignment of the arrow
and dimple (
6. Install firestop/spacer at ceiling—
When using Secure Vent, use SV4.5VF
firestop/spacer at ceiling joists. When
using Secure Flex, use SF4.5VF
firestop/spacer. If there is living space
above the ceiling level, the firestop/
spacer must be installed on the bottom
side of the ceiling. If attic space is
above the ceiling, the firestop/spacer
must be installed on the top side of the
joist. Route the vent sections through
the framed opening and secure the
firestop/spacer with 8d nails or other
appropriate fasteners at each corner.
NOTE: Maintain 1 in. (25 mm) clearance
to combustibles, framing members, and
attic or ceiling insulation when running
vertical chimney sections.
7. Support the vertical run sections—
See Page 15.
8. Change vent direction—At transition to/
from a horizontal/inclined run, install
the SV4.5E45 and SV4.5E90 elbows in
the same manner as the straight vent
sections. The elbows feature a twist
section to allow them to be routed
about the center axis of their initial
collar section to align with the required
direction of the next vent run element.
Twist elbow sections in a clockwise
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 16).
direction only, to avoid the possibility
of unlocking any of the previously
connected vent sections (Figure 16).
9. Continue installation of horizontal/
inclined sections—Continue with the
installation of the straight vent sections
in horizontal/inclined run. Install
support straps every 5 ft (1.52 m)
along horizontal/inclined vent runs
using conventional plumber’s tape
(Figure 22). Maintain the horizontal/
inclined run in a straight (no dips) and
slightly elevated plane, in a direction
away from the fireplace of 1/4 in. rise
per foot (20 mm per meter). Smaller
rise per foot run ratios are acceptable,
all the way down to at/near level.
NOTE: Maintain the required clearances
to combustibles: 1 in. (25 mm) at all
sides for all vertical runs; and 3 in.
(76 mm) at the top, 1 in. (25 mm) at
sides, and 1 in. (25 mm) at the bottom
for all horizontal/inclined runs. Use a
carpenter’s level to measure from a
constant surface and adjust the support
straps as necessary.
10. Assemble the vent run to the exterior
wall—If not previously measured,
locate the center of the vent at the
exterior wall. Prepare an opening as
described in Figure 23. Assemble
the vent system to point where the
terminus of the last section is located
relative to the exterior surface to
which the termination is to be attached
(Figure 24). If the terminus of the last
section is not within this distance, use
the telescopic vent section SV4.5LA,
as the last vent section. For wall
thicknesses greater than those shown
in Figure 24, refer to Table 18.
11. Attach the termination adaptor—Attach
the adaptor (SV4.5RCH, provided with
the termination) to the vent section
or telescoping vent section elbow or
appliance collar (Figure 23) in the same
manner as any SV4.5 vent component.
12. Install the firestop/spacer at the exterior
wall—When using the termination,
install the SV4.5HF (Secure Vent™), or
SF4.5HF (Secure Flex™) firestop/spacer
over the opening at the exterior side of
the framing, long side up, with the 3 in.
spacer clearance at the top (Figure 23),
and nail into place. The firestop/spacer
may also be installed over the opening
at the interior side of framing.
NOTE: The firestop/spacer also may
be installed over the opening on the
interior side of framing. The gap
between the vent pipe and a firestop
can be sealed with noncombustible
caulking.
Page 19
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
of
13. Install the Termination (SV4.5HT-2)—
For the last step, from outside the
exterior wall, slide the collars of the
termination onto the adaptor (the outer
inside the outer and the inner outside
the inner) until the termination seats
against the exterior wall surface to
Figure 22: Typical Horizontal Vent Installation
Building
Support
Framing
90° elbow
Horizontal
Support
Brackets
which it will be attached. Orient the
housing of the termination with the
arrow pointed upwards. Secure the
termination to the exterior wall. The
horizontal termination must not be
recessed into the exterior wall or siding
by more than the 1 1/4 in. (32 mm)
(Figure 24).
Vertical
Rise
Ceiling
Vertical
Firestop/
Spacer
u
Support vertical
venting every
8 ft (2.4 m)
above fireplace
vent outlet
Place horizontal support brackets
every 5 ft (1.524 m)
12 in. straight section
required before a 90°
elbow
NOTE: The vent termination is hot while
in operation and for a period of time
following the use of the fireplace. To
Fireplace
prevent contact with hot surfaces, use
a termination guard (
Page 32). This
can be purchased at your local dealer.
Horizontal terminations have been
designed to perform in a wide range of
weather conditions. Our terminations
meet or exceed industry standards.
When selecting the locations of your
horizontal terminations, do not place
the termination where water from
eaves and adjoining rooflines may
create a heavy flow of cascading water
onto the termination cap. If the cap
fire-parts.com
must be placed where the possibility
Figure 23: Installing Horizontal Termination
Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
may also be installed on the
10 1/2 in.
(267 mm)
12 1/8 in.
(308 mm)
5 1/8 in.
(130 mm)
7 in.
(178)
interior side.
of cascading water exists, it is the
responsibility of the builder to direct the
water away from the termination cap by
using gutters or other means.
Adapter
SV4.5RCH
Carefully follow the installation
instructions for the termination,
including the use of silicone caulking
where required.
6 to 48 in. Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Frame Opening.
Base of Appliance
Exterior
Wall
Horizontal
Termination
Termination
1 in.
(25.4 mm)
Typical
Shown
3 in.
(76 mm)
Figure 24: Horizontal Termination
*Use silicone caulking to
seal the top and sides of
the termination, up to the
underlayment, stucco, or
masonry wall surface.
*Caulk
*Caulk
Stucco
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Siding
Square Termination
Interior Surface of
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Telescopic Vent
Section (SV4.5LA), If
Necessary
SV4.5HT-2
Shown
Finished Wall
Adapter
SV4.5RCH
Maximum wall thickness
9 1/4 in. (235 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9 1/4 in.
(152 to 235 mm)**
SV4.5HT-2
Square Termination
Shown
1-1/4 in. Maximum Recess
the Square Termination into
Exterior Finishing Material
19
Page 20
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Horizontal Vent Tables and Figures
Table 19: Top Vent—One 90° Elbow, Elbow Connection NOT at Appliance
NOTE: Secure Vent® components (rigid vent
pipe and terminal) are shown in the figures;
Secure Flex® components (flexible vent pipe
and terminal) may also be used.
NOTE: Two 45° elbows may be used in place
of one 90° elbow. The same rise to run ratios,
as shown in the venting figures for 90° elbows,
must be followed if 45° elbows are used.
NOTE: It is very important that the
horizontal/inclined run be maintained
in a straight (no dips), slightly elevated
plane. The recommended incline is
approximately 1/4 in. per foot (20 mm per
meter) horizontal, in a direction away from
When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
When using Secure Flex,
use Firestop/Spacer
SF4.5HF.
Wall Firestop/Spacer
(SV4.5HF)
H
Min. One
Foot Vent
Section
Required
Ceiling
Firestop/Spacer
(SV4.5VF)
the fireplace. Rise per foot run ratios are
acceptable to at or near level.
NOTE:
SV4.5VF (Secure Vent), SF4.5VF
(Secure Flex) firestop/spacer must be
feetmetersfeetmeters
used anytime vent pipe passes through
a combustible floor or ceiling. SV4.5HF
(Secure Vent), SF4.5HF (Secure Flex)
firestop/spacer must be used anytime vent
pipe passes through a combustible wall.
NOTE: The tables show a 1(V) to 1.6 (H)
ratio up to a maximum horizontal run of
16 ft.
NOTE: An elbow is acceptable as 1 ft of
fire-parts.com
vertical rise, but may not be connected
directly to the appliance collar.
WARNING
Under no circumstances,
may separate sections of
V + H = 60 ft (18.3 m) maximum
H = 16 ft (4.87 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 12 for more
information.
Square termination (SV4.5HT-2) shown.
If 16 ft of (H) horizontal vent run is needed, then 10 ft minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 1.6 (H) ratio. For every 1 ft of (V) vertical, you are allowed 1.6 ft of (H) horizontal run, up to
a maximum horizontal run of 16 ft (4.87 m).
H MaximumV Minimum
30.911.60.490
5.21.5830.914
6.82.0741.22
8.42.5651.524
103.0561.729
164.87103.050
concentric flexible vent pipe be
joined together.
V
Table 18: Venting Components Required
for Various Exterior Wall Thicknesses,
when using Typical Termination Kits
Vent Components
Required
Termination Kit Only
Termination Kit and 6 in.
Vent Section (SV4.5L6)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
Termination Kit and
Telescopic Section
(SV4.5L12)
20
Exterior Wall Thickness
6–9 1/4 in.
(152–235 mm)
10 3/4–14 in.
(2733–356 mm)
16 3/4–20 in.
(426–508 mm)
11 3/4–20 in.
(299–508 mm)
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Table 20: Top Vent—Two 90° Elbows
H + H1 MaximumV Minimum
feetmetersfeetmeters
30.911.60.490
5.21.5830.914
6.82.0741.22
8.42.5651.524
103.0561.729
164.87103.050
V + H + H
H + H1 = 16 ft (4.87 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of
vertical rise. See Page 12 for more information.
Square termination (SV4.5HT-2) shown.
See Table 18 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
If 16 ft of (H) horizontal vent run is needed, then 10 ft minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 1.6 (H) ratio. For every 1 ft of (V) vertical, you are allowed
1.6 ft of (H) horizontal run, up to a maximum horizontal run of 16 ft (4.87 m).
An elbow is acceptable as 1 ft of vertical rise, but may not be connected directly to
the appliance collar.
= 60 ft (18.3 m) maximum
1
H
1
Note - When using
Secure Flex
Firestop/Spacer SF4.5VF.
When using SecureFlex,
use Firestop/Spacer
SF4.5HF.
TM
, use
Wall Firestop/Spacer
(SV4.5HF)
Wall
Firestop/Spacer
(SV4.5HF)
Ceiling
Firestop/Spacer
(SV4.5VF)
H
Min. One Foot Vent
Section Required
V
fire-parts.com
Table 21: Top Vent—Three 90° Elbows
H MaximumV Minimum
feetmetersfeetmeters
30.911.60.490
5.21.5830.914
6.82.0741.22
8.42.5651.524
103.0561.729
164.87103.050
H + H
= 16 ft (4.87 m) maximum
1
V + V1 +H + H1 = 60 ft (18.3 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of
vertical rise. See Page 12 for more information.
Square termination (SV4.5HT-2) shown.
See Table 18 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
If 16 ft of (H) horizontal vent run is needed, then 10 ft minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 1.6 (H) ratio. For every 1 ft of (V) vertical, you are allowed
1.6 ft of (H) horizontal run, up to a maximum horizontal run of 16 ft (4.87 m).
An elbow is acceptable as 1 ft of vertical rise, but may not be connected directly to
the appliance collar.
Wall Firestop/Spacer
(SV4.5HF)
H
1
V
1
When using Secure Flex
use Firestop/Spacer
When using Secure
Flex, use Firestop/Spacer
Wall Firestop/Spacer
(SV4.5HF)
Min. One Foot Vent
Section Required
SF4.5VF.
SF4.5HF.
Ceiling
Firestop/Spacer
(SV4.5VF)
H
TM,
V
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Vertical or Horizontal Venting
Using Secure Flex™ Venting Kits
and Components
Secure Flex™ venting kits and components
may be used in any venting application
in place of rigid Secure Vent™ (SV4.5)
direct-vent components. All restrictions,
clearances and allowances that pertain to
the rigid piping apply to the flexible venting.
Secure Flex kits may not be modified.
Do not join separate sections of flex
pipe together.
Using an adaptor (SV4.5RF), Secure Flex
kits may be added to the end of a vent
run made up of rigid Secure Vent (SV4.5)
vent sections provided that doing so does
not violate any of the venting length,
height, routing, horizontal to vertical ratio
requirements or clearance considerations
detailed in this manual.
Secure Flex kits come with an adaptor that
can be fitted to the inclined channel end of
the last Secure Vent (SV4.5) vent section
in a rigid system in the exact same fashion
as any other Secure Vent section. Align
the dimpled end of the adaptor over the
previously installed section or appliance
collar, adjusting the radial alignment until
the four locking dimples of the adaptor are
aligned with the inlets of the four inclined
channels of the last vent section or collar.
fire-parts.com
Push on the adaptor until it fully engages,
then twist the adaptor clockwise running
the dimples down and along the incline
channels until they seat at the end of the
channels.
Attach the flexible vent to the adaptor as
follows (
1. Install the Inner flex pipe—Install the
Figure 25):
small gear clamp loosely around the
inner flexible vent pipe and push it back
out of the way. Apply a bead of MillPac Black (700 °F) high temperature
sealant (P/N 10K81) to the inner
adaptor collar, approximately 1/2 in.
from the end. Pull and extend the inner
flexible vent pipe. Slide the inner flex
pipe over the adaptor collar. Ensure the
flexible vent pipe completely engages
the adaptor collar to a distance of
1 3/4 in. from the end, and that it is
free from damage or tears. Slide the
gear clamp into place tighten it fully to
secure the flexible vent to the adaptor
inner collar approximately 3/4 in. from
the end of the flex. Install the three (3)
screws, 120° apart, through the flexible
vent pipe and into the adaptor collar
just below the gear clamp to provide
additional security to the connection.
2. Install the outer flex pipe—Install the
large gear clamp loosely around the
outer flexible vent pipe and push it back
out of the way. Apply a bead of Mill-Pac
Black (700 °F) high temperature sealant
(P/N 10K81) to the outer adaptor
collar, to the grooves of the collar that
extend approximately 1 in. from the end
and to the flat surface, approximately
1 3/8 in. from the end. Pull and extend
the outer flexible vent pipe. Slide the
outer flex pipe over the adaptor collar.
Ensure the flexible vent pipe completely
engages the adaptor collar to a distance
of 1 3/8 in. from the end, and that it is
free from damage or tears. Slide the
gear into place and tighten it fully to
secure the flexible vent to the adaptor
outer collar approximately 3/4 in.
from the end of the flex. Install three
screws, 120° apart, through the flexible
vent pipe and into the adaptor collar
just below the gear clamp to provide
additional security to the connection.
Figure 25: Flexible Vent Adapter
Flex Vent
Mil-Pac
black high
temperature
sealant
1 3/4 in.
(44 mm)
overlap
Adaptor
(SV4.5RF)
3. Route the flex vent—Ensure that the
flex vent is properly routed to provide
the required clearance. Do not allow the
flexible vent to bend in a radius tighter
than 5 in. (127 mm) (Figure 26). Evenly
space the internal flex vent spacers
(roughly every 6 in.) and avoid kinking
the inner pipe. Support the horizontal
sections of flex with metal straps at 2 ft
(0.61 m) intervals.
Figure 26: Flexible Vent
Flexible vent
section
Securing screws
(3 Places)
Gear clamps
1 3/4 in.
(44 mm)
overlap
Securing screws
(3 Places)
4. Install the firestop/spacers at the
ceilings and walls—When Secure Flex
penetrates a wall or ceiling, a firestop/
spacer is required. Use the SF4.5 VF
firestop/spacer for ceilings and the
SF4.5 HF firestop/spacer for walls. See
the appropriate sections and figures
shown throughout the venting section
for their installation requirements.
5. Attach the flex vent to the termination—
Secure Flex components can be
purchased separately and attached to
bulk lengths of Secure Flex flexible
tubing cut to size at the job site.
Secure the flexible vent to the Secure
Flex terminations in the same manner
(Figure 25) as it was attached to the
adaptor.
NOTE: Secure Flex vent must be attached
to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or
the Secure Vent adaptor for Secure Flex
components. The collars of Secure Flex
terminations and adaptors have a different
diameter than those used with the Secure
Vent pipe. Additionally, Secure Flex
components have an extended length center
tube for use in attaching the flexible vent.
22
5 in. (127 mm)
radius minimum
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Complete the Field Wiring
CAUTION
The ground supply lead must be
connected to the wire attached
to the green ground screw
located on the outlet box (see
wiring diagrams). Failure to
do so will result in a potential
safety hazard. The appliance
must be electrically grounded in
accordance with local codes or,
in the absence of local codes,
the National Electrical Code,
ANSI/NFPA 70—latest edition (in
Canada, the current CSA C22-1
Canadian Electrical Code).
CAUTION
Label all wires prior to
disconnection when servicing
controls. Wiring errors
can cause improper and
dangerous operation.
Figure 27: Wiring Diagram—Electronic Gas Valves
Schematic Representation Only
COLOR CODE:
B = BLACK
BB = BROWN W/BLACK STRIPE
BG = BROWN W/GREEN STRIPE
BL = BLUE
BR = BROWN
G = GREEN
GY = GRAY
O = ORANGE
R = RED
W = WHITE
Y = YELLOW
Models w/o pressure switch have
these connectors plugged together
BR
Air Pressure Switch
Power Vent Only
Optional Circulation
Blower
B
Main Wire
Harness
Y
G
Y
Optional Variable Light
W
G
Battery Holder w/Switch
Battery Holder w/Switch
ON/Remote/Off
ON/ Remote/OFF
B
Battery Holder
Wire Harness
GR
GR
BB
BG
O
R
BL
O
885 Valve
BL
G
W
R
B
R
B
WH
BR
BB
Split Flow
Reset Switch
“see instructions”
Pilot Tube
Control Module
IPI Pilot
B
Fuse
BG
Flame Sensor
Spark Electrode
B
Ground Y
B
G
W
Main Power Cord
fire-parts.com
Au moment de l’entretien des
commandes, étiquetez tous les
fils avant de les débrancher.
Des erreurs de cáblage peuvent
entraîner un fonctionnement
inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne
adéquatement une fois l’entretien
terminé.
The gas valve is set in place and pre-wired
at the factory. This appliance must be
connected to a 120 Vac power source.
ATTENTION
Electronic Wiring
One of the following optional controls may
be used:
• ON/OFF Wall Switch,
• Thermostat / Remote Control.
See the fireplace Care and Operation
Instructions for details.
1. Route a 3-wire, 120 Vac, 60 Hz,
1 ph power supply to the left side of
the appliance.
2. Remove the electrical inlet cover plate
from the side of the unit by removing
the plate’s securing screws.
3. Remove the cover plate knockout.
Install a strain relief. Then, feed
the power supply wire through the
knockout opening.
4. Use wire nuts to connect the leads from
the appliance to the power supply leads.
5. Replace the cover plate.
6. Install the wall-mounted ON/OFF
control in a convenient location near
the fireplace.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Page 24
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Hot Fireplace Will Cause
Severe Burns
Never Allow Children to
Touch Glass or other Fire-
place Parts
WARNING
Installing and initializing the Remote
Control System
Required Items (not provided):
• Standard Junction Box
• Paper Clip or similar object (for remote
control system initialization)
The receiver for the Total Comfort Control™
Remote Control System connects directly
to the gas valve, stepper motor, and fan
control module with an umbilical cord
wiring harness.
1. Install a junction box (not provided)
on the wall adjacent to the appliance,
within reach of the remote system
umbilical cord wiring harness. Position
the terminal within the junction box
in preparation for attachment to the
remote wall switch.
2. When wall finish is complete, install the
wall switch in the previously installed
junction box, and connect the terminal
to the connector on the back of the wall
switch.
3. Install the wall switch cover plate,
taking care to ensure the wall switch
is properly indexed with the switch
cover when aligning the components
for attachments.
fire-parts.com
After completing fireplace installation,
initialize the remote control system before
operating the fireplace.
1. Insert the three (3) provided AAA
batteries into the battery bay in the
transmitter. Take care to correctly align
polarity (+/–).
2. Insert the four (4) provided AA batteries
into the wall switch battery bay (behind
the wall switch plate). Take care to
correctly align polarity (+/–).
3. On the wall switch, place the three-
position slider switch in the REMOTE
position (Figure 28).
4. On the wall switch front cover, insert
the end of a paper clip (or other similar
object) into the hole marked PRG.
The Receiver will beep three (3)
NOTE:
times to indicate it is ready to
synchronize with the transmitter.
5. On the transmitter, press the ON button.
The receiver will beep four (4) times to
indicate acceptance of the transmitter’s
command (and set the receiver to the
transmitter’s specific code). The system
is now initialized.
The remote control system provides
remote operation of the following fireplace
functions:
• Primary burner ON/OFF
• Auxiliary burner ON/OFF
• Dimmable light function
• 6-Speed blower operation
• Flame height and heat output
adjustment (six levels)
The receiver accepts commands via radio
frequency from the transmitter and does
not require line-of-sight operation.
The slider on the wall switch can be set to
one of three positions:
• ON (manual override)
• OFF (manual override)
• REMOTE (remote control)
See the fireplace Care and Operation
Instructions for detailed instructions on
using the remote control system to operate
the fireplace.
Figure 28: Wall Switch
Three-position slider switch
in REMOTE position
Figure 29: Transmitter (Remote Control)
UP/DOWN
ARROW
Key
MODE Key
WARNING
Fire hazard. Can cause severe
injury or death. The receiver
causes ignition of the appliance.
The appliance can turn on
suddenly. Keep away from
the appliance burner when
operating the remote system or
activating manual bypass of the
remote system.
CAUTION
Property damage hazard.
Excessive heat can cause
property damage. The appliance
can stay lit for many hours.
Turn off the appliance if it is
not going to be attended for any
length of time. Always place the
Transmitter where children can
not reach it.
On
Remote
Off
PRG
LCD Display
ON/OFF Key
THERMOSTAT
Key
Refer to the Appliance Care & Operations
manual (P/N 506025-01) for detailed
remote system operation instructions.
24
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Flex Line Connector
Connect the Gas Supply
All codes require a shutoff valve mounted
in the supply line. The shut-off valve should
be oriented to face the fireplace front.
Figure 31 illustrates two methods for
connecting the gas supply. Use a sediment
trap in the gas piping within the home to
prevent moisture and debris in the line from
damaging the valve.
The flex-line method is acceptable in the
U.S.A. where local codes permit it. In
the Commonwealth of Massachusetts,
installation must be performed by a
licensed plumber or gas fitter. Canadian
requirements vary depending on locality.
Installation must be in compliance with
local codes. These appliances are equipped
with a gas flex line for use in connecting the
unit to the gas line (Figure 31). The flex line
is rated for both natural and propane gas. A
manual shutoff valve is also provided with
the flex line.
The gas control valve is located on the
left of the firebox, in the side control
compartment. The valve is accessible with
the glass door removed (Figure 30).
Secure all joints tightly using appropriate
tools and sealing compounds. Ensure
propane resistant compounds are used in
propane applications. Seal around the gas
line to prevent cold air leakage.
fire-parts.com
Route a hard pipe from the lefthand side
to a spot directly below the access plate
opening.
Locate the shut-off valve and gas flex line
and pull the assembly forward, out of the
compartment. Separate the shutoff valve
from the gas flex line. Determine the length
of pipe needed to route the gas line from
the last fitting to a point directly below the
access plate opening.
Using pipe-dressing materials appropriate
for the gas type, securely affix the shutoff
valve to this pipe at a convenient location
outside of the appliance lower control
compartment.
Refer to Figure 31 and insert the last length
of gas pipe with the attached shutoff valve
into the lower control compartment, and
pass it through the gas line access hole on
the left side of the appliance outer wrapper.
Using materials appropriate for the gas
type, thread the last length of pipe into the
end of the gas vent run and tighten it in
place using a pipe wrench.
Figure 30: Gas Control Access
Access Plate
Gas Valve
Figure 31: Gas Line Connection Methods
1/2 in. x 3/8 in. Flare
Shut-Off Valve
Gas
Stub
Test all connections (factory and field)
for gas leaks
Turn on gas supply and test for leaks using
a gas leak test solution.
NOTE: A soapy water solution is
effective for leak testing. However, it is
not recommended, because the soap
residue left on the pipes/fittings can result
in corrosion.
1. Light the appliance
NOTE: Refer to the lighting instructions
label in the control compartment or in
the Care and Operation Instructions.
2. Brush all joints and connections with
the gas leak test solution to check for
leaks. If bubbles are formed, or gas
odor is detected, turn the gas control
knob (OFF/PILOT/ON) to the OFF
position. Either tighten or refasten
the leaking connection, then retest as
described above.
3. When the gas lines are tested and leak
free, rinse off the leak testing solution.
3/8 in. NPT x 3/8 in.
Flare Fitting
3/8 in. Flex Tubing
Gas
Valve
NOTE: Turn the last piece of gas pipe in
the last fitting until the shut-off valve is
positioned in a way that allows the shutoff
valve handle to be accessed in the lower
control compartment and easily operated
through its full range of motion.
Bring the flex line to the shutoff valve by
hand and align the flare fittings. Tighten the
fittings by hand, and then use a wrench to
tighten completely, 1/4 turn at a time.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Page 26
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Verify Correct Appliance Operation
With the gas line installed, perform an
initial system inspection before closing the
front of the unit. Follow the pilot lighting
instructions provided in the Care and
Operation Instructions manual.
NOTE: Lighting Instructions are also
found on the literature tag tied to the gas
piping next to the gas valve in the left side
compartment. To access the tag, remove
the surround trim assembly.
When lighting the appliance for the first
time, the gas line will purge itself of air. This
may take a few minutes. Once complete,
the pilot and burner will light. Subsequent
lightings of the appliance will not require air
purging. Inspect the pilot flame (carefully
remove the logs, if necessary).
To light the burner, turn the wall switch
or (optional) remote control ON. Ensure
the ignitor lights the pilot. The pilot flame
should engulf the flame rod (Figure 32).
Figure 32: Pilot Flame Appearance
Ignitor
Pilot
Hood
fire-parts.com
Sensor
Contemporary Fireplaces Only:
Install the Contemporary Floor and
Contemporary Glass Media
NOTE: Turn off all electricity to the appliance
before installing the contemporary floor and
contemporary media.
1. Position the rear contemporary floor
to the back of the firebox, aligning
the holes in the mounting tabs with
the screw holes in the firebox floor
(Figure 33). Secure with the two (2)
included 5/16 in. screws.
NOTE: It may be easier to install the rear
porcelain firebox liner (Step 3 in Porcelain Firebox Liners), before installing the rear
contemporary floor.
Figure 33: Installing the Contemporary Floor
Screws
2. Position the front contemporary floor
to the front of the firebox, aligning
the holes in the mounting tabs with
the screw holes in the firebox floor
(Figure 33). Secure with the two (2)
included 5/16 in. screws.
Install the Firebox Liners
Ceramic Firebox Liners
1. Remove the four (4) firebox liner panels
from the packing materials.
2. Carefully position the rear panel, upper
edge first, in the firebox against the
rear wall.
3. While holding the rear panel, carefully
position the left side panel in the
firebox.
4. While holding the left panel, carefully
position the top panel, left edge up to
a resting position on the upper edge of
the left panel.
5. Raise the right end of the top panel, and
hold it in position while installing the
right panel in the following step.
6. Carefully position the right side panel in
the firebox.
7. Lower the top panel onto the upper
edge of the right side panel.
NOTE: Do not force the top panel into
place. Excessive force may cause
breakage. If the top panel is correctly
positioned, it will fit snugly in place.
8. Ensure the top panel is positioned over
both the left side and right side panels
and that all panels are aligned with the
sides and rear of the firebox.
Porcelain Firebox Liners
1. Remove the four (4) firebox liner panels
from the packing materials.
2. Locate the rear, left, and right panels.
3. Position the rear panel, upper edge
first, in the firebox against the rear
wall. Insert the lower mounting tabs
into the mounting slots in the firebox
base. Secure the panel to the rear wall
with a 5/16 in. screw through the upper
mounting tab.
4. Position the left panel in the firebox
against the left wall and the rear panel.
5. Position the top panel, left edge up, so
that it rests on the upper edge of the
left panel.
6. Raise the right edge of the top panel,
and hold it against the firebox ceiling
when installing the right panel in the
following step.
7. Position the right panel in the firebox
against the right wall and the rear panel.
8. Lower the top panel onto the upper
edge of the right panel, and slide it
under the two tabs on the left and
right panels.
9. Ensure the top panel is positioned over
both the left side and right side panels
and that all panels are aligned with the
sides and rear of the firebox.
10. Use an ammonia-free glass cleaner and
a soft, non-abrasive cloth to remove
fingerprints and smudges from the
porcelain firebox liner panels.
11. Install the contemporary glass media in
a thin, even layer.
NOTE: Do not mound or overapply the
glass media.
26
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Traditional Fireplaces Only:
Install the Logs, Decorative Volcanic
Stone, and Glowing Embers
NOTE: Turn off all electricity to the appliance
before installing volcanic stone, embers and
logs.
NOTE: The log set and fire are artistically
arranged to provide an asymmetrical fire.
The fire does not burn in the left rear
quarter of the log set.
Figure 34: Log Set
1
2
6
NOTE: Figure 34 is representative of all
fireplace models. Logs 5 and 6 may vary in
appearance from those shown above.
3
5
4
1. Align the two holes in the bottom of
Log 1 over the two tabs at the rear of
the burner (Figure 35).
Figure 35: Placing Logs 1 and 2
1
2
2. Hold Log 1 in position while placing
Log 2 on the burner and resting it
against the alignment notch in Log 1
(Figure 35).
3. Place Log 3 in position with the
base aligned in the burner surface
(Figure 36).
Figure 36: Placing Log 3
6. Place Log 5 in position in the notches
on the upper right portions of Logs 1
and 3 (Figure 38).
Figure 38: Placing Logs 5 and 6
5
6
7. Place Log 6 in position in the notches
near the left ends of Logs 2 and 3
(Figure 38).
8. Install the volcanic stone in front of and
on the sides of the log set. Cover all of
the exposed metal floor.
Table 22: Log Set
fire-parts.com
Log NumberDescription
1Rear Log
2Bottom Left Log
3Bottom Right Log
4Front Log
5Top Right Log
6Top Left Log
Catalog number for the entire set:
35 in. H8707
40 in. H8708
45 in. H8824
4. Insert the left end of Log 4 under Log 3
and position the right end of Log 4 in
the notch on the top, right end of Log 3
3
(Figure 37).
Figure 37: Placing Log 4
4
5. Ensure all logs are properly positioned
on the surface of the burner and
interlocked with each other (Figure 37).
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Install the Glass Door
WARNING
•Do not attempt to substitute
the materials used on these
doors, or replace cracked or
broken glass.
•Handle this glass with
extreme care! Glass is
susceptible to damage—Do
not scratch or handle roughly
1. Retrieve the glass door. Visually inspect
the gasket on the backside.
2. Locate the four (4) spring-loaded
latches; two above and two below the
fireplace opening (Figure 39).
Figure 39: Glass Door
Latch
Latch
Adjust the Burner to Ensure Proper
Flame Appearance
WARNING
•Air shutter adjustment
should only be performed
by a qualified professional
service technician.
•Ensure front glass panel
is in place and sealed
during adjustment.
while reinstalling the glass
door frame.
•The glass door of this appliance
must only be replaced as a
complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
cracked or chipped glass
separately.
•Do not attempt to touch the
front enclosure glass with your
hands while the fireplace is
in use.
fire-parts.com
WARNING
Do not operate appliance with
the glass front removed, cracked,
or broken.
AVERTISSEMENT
Ne pas utiliser l’appareil si
3. Carefully grip the door at the top and
bottom, and align it with the fireplace
opening. Lightly press against the door,
to hold it in position.
4. Secure the two upper latches by pulling
each handle down and pressing in to
hook it to the glass door.
5. Secure the two lower latches,
6. Install the surround trim assembly
by lowering it onto the appliance and
pressing in to secure it (Figure 8).
To Remove the Glass Door
For more information on removing the glass
door, see Page 9.
Latch
le panneau frontal en verre
n’est pas en place, est craqué,
ou brisé.
Only doors certified with the appliance shall
be used.
Seules des portes certifiées pour cet
appareil doivent être utilisées.
CAUTION
DO NOT abuse glass door by
• Soot will be produced if the air shutter
is closed too much. Any damage due
to sooting, resulting from improperly
setting the air shutter, is not covered
under the warranty.
•The air shutter rod and nearby
appliance surfaces are hot.
Exercise caution to avoid injury
while adjusting flame appearance.
Flame Appearance and Sooting
The flame should be blue at the base, and
yellow-orange in the body of the flame.
When the appliance is first lit, the entire
flame may be blue and will gradually turn
yellow-orange during the first 15 minutes
of operation. If the flame remains blue, or if
the flame is orange with evidence of sooting
(black tip), the air shutter opening may need
to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated
by black puffs developing at the tips of very
long orange flames. Sooting results in black
deposits forming on the logs, appliance
inside surfaces, and on exterior surfaces
adjacent to the vent termination.
Sooting is caused by incomplete
combustion in the flames and lack of
combustion air entering the air shutter
opening. To achieve a warm yellow-orange
flame with an orange body that does not
soot, the shutter opening must be adjusted
between these two extremes.
CAUTION
striking or slamming shut.
NOTE: Visually inspect the gasket on the
backside of the glass door. The gasket
surface must be clean, free of irregularities,
and seated firmly. Ensure it is properly
located. Make sure the bead is not rolled
into the channel at the top of the door, but
remains flat against the top of the glass.
NOTE: When installing the glass door,
ensure the spacing on both sides is even.
28
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Air Shutter Adjustment Guidelines
• If there is smoke or soot present, first
check the log set positioning to ensure
that the flames are not impinging on
any of the logs. If the log set is properly
positioned and a sooting condition still
exists, then the air shutter opening
should be increased.
• The more offsets in the vent system, the
larger the air shutter opening will need
to be.
• An appliance operated with the air
shutter opened too far, may have flames
that appear blue and transparent. These
weak, blue and transparent flames are
termed anemic.
• Propane models may exhibit flames
which candle or appear stringy. If this
is present and persists, adjust the air
shutter to a more closed position,
then operate the appliance for a few
more minutes to ensure that the flame
normalizes and the flames do not
appear sooty.
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
5. When satisfied that the burner flame
appearance is normal, reinstall the
lower control compartment door then
proceed to finish the installation.
Figure 40: Air Shutter Adjustment Rod
Air Shutter
Adjustment Rod
Figure 41: Traditional Fireplaces
Flame Appearance
Finishing Requirements
1. Remove the surround trim assembly
(Figure 8)
2. Remove the finish trim gap fillers from
the side of the fireplace, and identify the
left and right side pieces (Figure 43).
Figure 43: Finish Trim Gap Fillers
Right
Left
3. Loosen the nine (9) screws securing the
integrated finish trim and slide the trim
out and away from the fireplace door
(Figure 44).
Table 23: Air Shutter Adjustment Guidelines
Amount of
fire-parts.com
Primary Air
If air shutter
is closed
too far
If air shutter
is open
too far
Flame Color
Flame will
be orange
Flame will
be blue
1. Remove the top louver and the
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
Figure 42: Contemporary Fireplaces
Flame Appearance
Figure 44: Finish Trim Fasteners
Fireplace Top
Screws
surround trim assembly.
2. Locate the air shutter adjustment rod
in the lower control compartment
(Figure 40), and adjust it to the
standard setting.
NOTE: Pull the rod out to close, and
push the rod in to open the air shutter.
3. Light the appliance (follow lighting
NOTE: Integrated finish trim
shown in gray. Three (3)
screws on right side not
shown, but mirror left side.
procedure on lighting label in control
compartment or the Care and
Operations Manual).
4. Allow the burner to operate for at
least 15 minutes while observing the
flame continuously to ensure that the
proper flame appearance has been
achieved (Figure 41 and Figure 42). If
the following conditions are present,
adjust accordingly. If flame appears
weak or sooty, adjust the air shutter,
incrementally, to a more open position
until the proper flame appearance is
achieved. If flame remains blue, adjust
Table 24: Main Burner Shutter Opening—
Factory Setting
ModelsNatural GasPropane
NV35
NV403/16 in. (4.8 mm)3/8 in. (9.5 mm)
NV453/16 in. (4.8 mm)3/8 in. (9.5 mm)
3/16 in. (4.8 mm)7/16 in. (11.1 mm)
the air shutter, incrementally, to a more
closed position until the proper flame
appearance is achieved.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Page 30
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
NOTE: The integrated finish trim is
designed to be “flush face” with a
minimum thickness of 1 in. (25 mm)
in a non-combustible wall. The
fireplace is supplied with 1/2 in.
(13 mm) non-combustible wall
material (Figure 45).
NOTE: A “flush face” installation will
require a minimum of an additional
1/2 in. (13 mm) non-combustible
(installer-supplied) wall material
(Figure 46) to create the minimum 1 in.
(25 mm) thick wall.
NOTE: The integrated finish trim
is adjustable to accommodate a
wall thickness of an additional 1 in.
(25 mm)—for a 2 in. (51 mm) total
4. Slide the finish trim in until it is flush
with the finished wall surface. Tighten
the nine (9) screws (Figure 44)
securing the finish trim.
5. Install the surround trim assembly
by lowering it onto the appliance and
pressing in to secure it (Figure 8).
6. Slide the left finish trim gap filler
into the left gap between the finish
trim and the surround trim assembly
(Figure 47).
NOTE: Ensure the finish trim gap filler
slides into the spring clip, as shown.
Figure 47: Finished Installation
Spring Clip
thickness.
NOTE: For wall thicknesses greater
than 2 in. (51 mm), remove the
three integrated finish trim pieces
(Figure 44).
Figure 45: Non-combustible Wall
15 1/2
(394)
Shaded area is non-combustible wall
7. Slide the right finish trim gap filler
into the right gap between the finish
fire-parts.com
trim and the surround trim assembly
(Figure 47).
Figure 46: Wall Finishing
Combustible
finished wall
materials
The shaded area
must remain clear of
combustible materials
Combustible
materials
not allowed
below this
point on the
face of the
appliance
15 1/2 in.
394 mm
Spacer
Top of Appliance
1 in. (25 mm)
Minimum
NOTE: Ensure the finish trim gap filler
slides into the spring clip, as shown.
30
Top of Door Frame
NOTE: See Page 5 for Cold
Climate Insulation and Page 6 for
Clearances.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 31
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Attach the Safety-in-Operation Warnings
NOTE: It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing
consumers of safe operation of this appliance.
Attaching Safety-inOperation Warnings
It is required that the set of safety instruction
labels that have been furnished with the fireplace
be affixed to the operation and control points of
the fireplace. A safety instruction label must be
affixed to the receiver wall switch plate where
the fireplace is turned on and off (Figure A)
and on the remote control handheld transmitter
(Figure B). To properly complete the installation
of this fireplace, locate the multi-lingual adhesive
labels provided with the Care and Operation
Instructions and proceed as follows:
1. Locate the wall receiver that controls the
fireplace (verify the switch operates the
fireplace by turning it on and off). Clean the
wall receiver plate thoroughly to remove
any dust and oils. Affix the label to the
surface of the plate of the wall receiver that
controls the fireplace (Figure A). Choose the
language primarily spoken in the home. If
unknown, affix the English language label.
2. Locate the remote control transmitter and
clean it thoroughly to remove any dust
and oils. Affix the label to the surface of
handheld transmitter (Figure B). Choose the
language primarily spoken in the home. If
fire-parts.com
unknown, affix the English language label.
3. If you are unable to locate the labels, please
call Lennox Hearth Products or your nearest
Lennox Hearth Products dealer to receive
additional safety instruction labels free
of charge.
Cat. No. H8024 Replacement Label Kit Étiquettes de remplacement, n° cat. H8024 Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
NOTE: English is red text on clear label. French
and Spanish are white text on black label.
SAFETY LABEL DIAGRAMSDIAGRAMMES DES ÉTIQUETTES DE SÉCURITÉDIAGRAMAS DE ETIQUETAS DE SEGURIDAD
Apposition des mises en garde
relatives à la sécurité d’utilisation
Il est impératif que le jeu d’étiquettes de sécurité
qui ont été fournies avec le foyer soient collées
à côté des dispositifs de contrôle du foyer. Une
étiquette de sécurité doit être collée sur la plaque
du récepteur mural contrôlant l’allumage du foyer
(Figure A) et sur le boîtier de la télécommande
(Figure B). Pour achever l’installation correcte de
ce foyer, procédez comme suit avec les étiquettes
adhésives en langues étrangères fournies avec
les instructions d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le
foyer (vérifiez que l’interrupteur contrôle
le fonction -nement du foyer en le faisant
basculer de Marche à Arrêt, et vice-versa).
Nettoyez soigneusement la plaque du
récepteur mural pour éliminer la poussière
et les traces de graisse ou d’huile. Collez
l’étiquette sur la surface de la plaque
du récepteur mural qui contrôle le foyer
(Figure A). Choisissez la langue qui est
principalement parlée dans la résidence
du propriétaire. En cas de doute, collez
l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la
soigneuse ment pour éliminer la poussière
et les traces de graisse ou d’huile. Collez
l’étiquette sur le boîtier de la télécommande
(Figure B). Choisissez la langue qui est
principalement parlée dans la résidence
du propriétaire. En cas de doute, collez
l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre
distribu teur Lennox Hearth Products local
pour recevoir gratuitement des étiquettes
supplémentaires.
LENNOX HEARTH PRODUCTS
1-800-655-2008
Remarqué : Le texte anglais est rouge sur un
support transparent. Le texte français et espagnol
est blanc sur un support noir.
Colocación de advertencias de
seguridad en operación
Se requiere que el juego de etiquetas de
instrucciones de seguridad que se incluyeron
con la chimenea se coloque en los puntos de
operación y control de la misma. Se debe colocar
una etiqueta de instrucciones de seguridad en
la placa del interruptor de pared del receptor
desde el cual se enciende y se apaga la chimenea
(Figure A) y en el transmisor de control remoto
(Figure B). Para completar correctamente la
instalación de esta chimenea, encuentre las
etiquetas adhesivas multilingües incluidas con
las instrucciones de cuidado y operación y haga
lo siguiente:
1. Identifique el receptor de pared que
controla la chimenea (verifique que el
interruptor opera la chimenea encendiéndola
y apagándola). Limpie bien la placa del
receptor de pared para quitar el polvo y
aceite. Pegue la etiqueta en la superficie de
la placa del receptor de pared que controla
la chimenea (Figure A). Seleccione el idioma
que más se habla en la casa. Si no sabe cuál
es, use la etiqueta en inglés.
2. Identifique el transmisor de control remoto
y límpielo bien para quitar el polvo y aceite.
Pegue la etiqueta en la superficie del
transmisor (Figure B). Seleccione el idioma
que más se habla en la casa. Si no sabe cuál
es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas,
sírvase llamar a Lennox Hearth Products
o al distribuidor de Lennox Hearth
Products más cercano para recibir
etiquetas de instrucciones de seguridad
adicionales gratuitas.
LENNOX HEARTH PRODUCTS
1-800-655-2008
Nota: La etiqueta en inglés es transparente con
texto rojo. Las etiquetas en francés y español son
negras con texto blanco.
Figure A
On
Remote
Off
PRG
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure B
31
Page 32
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n
t
INSTALLATION ACCESSORIES
Table 25: Listed Secure Vent™ Components
Catalog
Number
H1968SV4.5HT-2
77L70SV4.5L66 in. (152 mm)H1985CTSO-33
77L71SV4.5L1212 in. (305 mm)H1987CTSO-44
77L72SV4.5L2424 in. (610 mm)H1986CTSO-46
77L73SV4.5L3636 in. (914 mm)
77L74SV4.5L4848 in. (1219 mm)60L10SF-1818 ft (5.49 m)* compressed flex
Flare 90° Elbow, 3/8 in. NPT (M) X 3/8 in.H89941H89941H89941
35
Flare Straight Fitting, 3/8 in. NPT (M) X 3/8 in.H89951H89951H89951
36 Split ValveH89961H89961H89961
37
Assembly Harness, Wall to Proflame II, 12 ftH88131H88131H88131
38 Assembly Harness, Valve to Proflame IIH88141H88141H88141
39 Assembly Harness, Power to Proflame IIH88111H88111H88111
40 Assembly Harness, Blower Plug-InH88171H88171H88171
41 Assembly Harness, Lights to Proflame IIH88101H88101H88101
42 Assembly Harness, Split Flow to Proflame IIH88121H88121H88121
43
Assembly Harness, Light and Fan Connector, 5 in.H88151H88151H88151
44 Volcanic Stone80L42180L42180L421
Catalog
Number
Qty
Catalog
Number
Qty
Catalog
Number
Contact a Lennox Hearth Products dealer
to obtain any of these parts. Never use
substitute materials. Use of non-approved
parts can result in poor performance and
Qty
safety hazards.
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil
sont utilisées.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Figure 48: Replacement Parts
2
1
8
10
9
4
On
Remote
Off
PRG
6
17
5
14
fire-parts.com
15
22
23
36
24
19
27
20
34
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 35
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be
installed by a qualified service
agency in accordance with the
manufacturer’s instructions
and all applicable codes and
requirements of the authority
having jurisdiction. If the
information in these instructions
is not followed exactly, a fire,
explosion, or the production of
carbon monoxide may result;
causing property damage,
personal injury, or loss of life.
The qualified service agency
is responsible for the proper
installation of this kit. The
installation is not proper and
complete until the operation
of the converted appliance is
checked as specified in the
manufacturer’s instructions
supplied with the kit.The
qualified service agency
performing this installation
assumes responsibility for
fire-parts.com
this conversion.
Cette trousse de conversion doit
être installée par un technicien
agréé, selon les instructions
du fabricant et selon toutes
les exigences et tous les
codes pertinents de l’autorité
compétente. Assurez-vous de
bien suivre les instructions dans
cette notice pour réduire au
minimum le risque d’incendie,
d’explosion ou la production de
monoxyde de carbone pouvant
causer des dommages matériels,
des blessures ou la mort. Le
tecnicien agréé est responsable
de l’installation de cette trousse.
L’installation n’est pas adéquate
ni complète tant que le bon
fonctionnement de l’appareil
converti n’a pas été vérifié selon
les instructions du fabricant
fournies avec la trousse. Le
fournisseur de service qualifié
ayant réalisé l’installation
assume les responsabilités liées
à la conversion.
AVERTISSEMENT
In Canada:
The conversion shall be carried out in
accordance with the requirements of the
provincial authorities having jurisdiction
and in accordance with the requirements
of the CAN/CSA-B149.1 Installation code.
La conversion devra être effectuée
conformément aux recommandations
des autorités provinciales ayant
juridiction et conformément aux
exigences du code d’installation CAN/
CSA-B149.1.
Gas conversion kits are available to adapt
your appliance from the use of one type of
gas to the use of another. These kits contain
all the necessary components needed to
complete the task including labeling that
must be affixed to ensure safe operation.
Refer to the instructions provided with the
conversion kit when performing any gas
conversion.
Table 28: Traditional Fireplaces—
Natural Gas to Propane Conversion Kits
ModelsCatalog Number
NV35INH8754
NV40INH8722
NV45INH8757
Table 29: Traditional Fireplaces—
Propane to Natural Gas Conversion Kits
ModelsCatalog Number
NV35INH8755
NV40INH8756
NV45INH8758
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 30: Contemporary Fireplaces—
Natural Gas to Propane Conversion Kits
ModelsCatalog Number
NVCD35INH8759
NVCD40INH8760
NVCD45INH8761
35
Page 36
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
fire-parts.com
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related
LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used
with permission.