Lennox ENVY, ENVY CD Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
ENVY and ENVY CD Direct-Vent Gas Fireplaces
P/N 506023-17 Rev. A 08/2013
This manual is one of a set of two supporting this product. Refer to P/N 506025-09 for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 506223-74.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
MODELS
NV35IN
NVCD35IN
Report No. G100513653 PRT-001
Please read and understand these instructions before starting installation.
NV40IN
NVCD40IN
NV45IN
NVCD45IN
f i r e - p a r t s . c o m
Page 2
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
Packaging.............................2
Introduction General Information Requirements for the Commonwealth
of Massachusetts .......................4
Cold Climate Insulation Manufactured Home Requirements Location Vent Termination Clearances Minimum Clearances to Combustibles
Typical Installation Sequence . . . . . . . . . . . . .9
Pre-Installation Steps Construct the Appliance Framing Route the Gas Supply Line to the Appliance ..11 Install the Vent System and
Exterior Termination ...................11
Select Venting System—
Horizontal or Vertical...................13
Vent Section Length Vertical or Horizontal Venting Using Secure
Flex™ Venting Kits and Components ......22
Complete the Field Wiring Connect the Gas Supply Verify Correct Appliance Operation Contemporary Fireplaces Only: Install the Contemporary Floor and Contemporary Glass Media Install the Firebox Liners Traditional Fireplaces Only: Install the Logs, Decorative Volcanic Stone, and Glowing Embers Install the Glass Door Adjust the Burner to Ensure Proper
Flame Appearance.....................28
Finishing Requirements Attach the Safety-in-Operation Warnings ...31 Installation Accessories Gas Conversion Kits
...........................2
.....................2
..................5
.........5
..............................5
..............6
......8
...................9
..........9
....................14
...............23
.................25
f i r e - p a r t s . c o m
................26
...................27
..................28
.................29
.................32
....................35
........26
..............26
PACKAGING
The assembled vented gas fireplace heater is packaged with:
Traditional models only: (1 set) Logs (Packaged in a carton inside the firebox)
Traditional models only: (1 bag) Volcanic Stone
Literature Kit (Envelope containing Care and Operation Instructions, Installation Instructions, Safety-In-Operation Warning Labels, Warranty)
(1) U-Shaped Vent Restrictor (Attached to Literature Kit envelope)
INTRODUCTION
ENVY replaces are designed to operate
on natural or propane gas. An electronic intermittent pilot ignition system provides safe, efficient operation. External electrical power is required to operate these units. In the event of a power outage, four (4) AA batteries provide backup power for appliance operation (excluding blower).
These vented gas fireplace heaters are sealed combustion, air­circulating gas fireplaces designed for residential applications.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components only:
Secure Vent® Direct-Vent System Components,
Secure Flex® Flexible Vent Components, and
Z-FLEX® Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.
Use only the correct size venting (4 1/2 in. inner and 7 1/2 in. outer).
These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent components with these appliances.
GENERAL INFORMATION
WARNING
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at-risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la surface chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
NOTE: Children and adults should be alerted
to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Please read and understand these instructions before beginning your installation.
2
Remarqué : Les enfants et les adultes
devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION, AND LISTINGS OF THIS UNIT.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 3
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Codes and Standards
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
f i r e - p a r t s . c o m
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appliance must be replaced prior to operating the appliance.
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
NOTE: Installation and repair should be
done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
WARNING
AVERTISSEMENT
These appliances comply with National Safety Standards and are tested and listed by ETL/Intertek. (Report No. G100513653 PRT-001) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/ CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.
These appliances are listed by ETL/ Intertek for installation in bedrooms and manufactured homes.
The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54—latest edition (In Canada, the current CAN/CSA-B149.1 installation code).
The appliance, when installed, must be electrically grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical Code, CSA C22.1—latest edition.
Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
It is advisable to have an alternate primary heat source when installed in a dwelling.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
ENVY replaces come standard with a
remotely-modulated gas valve. Flame appearance and heat output cannot be controlled at the gas valve. The BTU Input for these appliances is shown in Table 1.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
WARNING
Do not operate without surround trim assembly and screen installed.
NOTE: Do not use these appliances if any
part has been under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Remarqué : Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
NOTE: Only trim kit(s) supplied by the manufacturer shall be used in the installation of this appliance.
Remarqué : Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 1: Input Rate, Gas Valves
Models
NV35IN
NVCD35IN
NV40IN
NVCD40IN
NV45IN
NVCD45IN
Input Rate (BTU/HR)
Natural Gas Propane Gas
35,500 high
15,500 low
31,000 high
16,000 low
41,500 high
15,500 low
40,000 high
21,000 low
47,000 high
18,000 low
47,000 high
24,000 low
35,000 high
18,000 low
28,000 high
15,000 low
37,000 high
14,500 low
32,000 high
18,500 low
45,000 high
18,000 low
40,000 high
22,000 low
3
Page 4
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Gas Pressure
Table 2 and Table 3 show the appliance inlet and manifold gas pressure requirements.
Orifice Sizes—Sea Level to High Altitude
These appliances are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level using the
Table 2: Inlet Gas Supply Pressure
Fuel Minimum Maximum
Natural Gas
Propane
4.5 in. WC (1.12 kPa)
11.0 in. WC (2.74 kPa)
10.5 in. WC (2.61 kPa)
13.0 in. WC (3.23 kPa)
standard burner orifice sizes (marked with an “*” in Table 4).
For elevations above 4500 ft, contact your gas supplier or qualified service technician.
Deration
At higher elevations, the amount of BTU fuel
Table 3: Manifold Gas Supply Pressure
Fuel Low High
Natural Gas
Propane
1.6 in. WC (0.40 kPa)
6.3 in. WC (1.57 kPa)
3.5 in. WC (0.87 kPa)
10.0 in. WC (2.49 kPa)
Test gauge connections are provided on the front of the electronic gas control valve (identified IN for the inlet and OUT for the manifold side). The control valves have a 3/8 in. (10 mm) NPT thread inlet and outlet side of the valve (Figure 1).
Figure 1: SIT Electronic Gas Valve
Green Wire
(from DFC wire
Inlet (IN) Test Port
f i r e - p a r t s . c o m
Manifold (OUT)
Test Port
Orange Wire
(from DFC
wire
harness)
Main
Gas Inlet
3/8 in. NPT
harness)
Yellow Ground Wire (from DFC wire harness)
Hi/Lo Flame Control Knob
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from
value delivered must be reduced by either:
Using gas that has been derated by the gas company.
Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition or, in Canada, the CAN/CSA-B149.1 codes— latest edition.
NOTE: Flame breadth, height and width will diminish 4% for every 1,000 feet of altitude.
Table 4: Burner Orifice Sizes, Elevation 0–4500 ft ( 0–1372 m)
Model
NV35IN
NVCD35IN
NV40IN
NVCD40IN
NV45IN
NVCD45IN
* Standard size installed at factory
• Catalog number
Natural Gas
drill size
Front
#49 (0.073 in.)*
Back
#43 (0.089 in.)*
Front
#42 (0.0935 in.)*
Back
#55 (0.052 in.)*
Front
#41 (0.096 in.)*
Back
#43 (0.089 in.)*
Front
#35 (0.11 in.)*
Back
#52 (0.0635 in.)*
Front
#40 (0.098 in.)*
Back
#40 (0.098 in.)*
Front
#32 (0.116 in.)*
Back
#49 (0.073 in.)*
Propane drill size
Front
#57 (0.043 in.)*
Back
#54 (0.055 in.)*
Front
#55 (0.052 in.)*
Back
#60 (0.040 in.)*
Front
#55 (0.052 in.)*
Back
#55 (0.052 in.)*
Front
#53 (0.0595 in.)*
Back
#65 (0.035 in.)*
Front
#54 (0.055 in.)*
Back
#54 (0.055 in.)*
Front
#51 (0.067 in.)*
Back
#62 (0.038 in.)*
the gas supply piping system by closing
In Canada—CAN/CGA-2.17-M91 (high altitude):
THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE, IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the U.S. state of Massachusetts if the following additional requirements are met:
Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R..
Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 in. (914 mm) in length.
The individual manual shut-off must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
4
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 5
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
CAUTION
Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
Figure 2: Typical Locations
T
NOITACILPPA
NEVP
O
T
TNEVPOT
APPLICATION
TOP VENT
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
CAUTION
This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with
RECESSED
INSTALLATION
APPLICATION
the National Electrical Code ANSI
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket permanently located, manufactured home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada.
f i r e - p a r t s . c o m
Cet appareil peut être installé cómme du matéri-el d’origine dans une maison préfabriquée (É.U. seulement) ou mobile et doit être installé selon les instructions du fabricant et conformément à la norme Manufactured Home Constructions and Safety, Title 24 CFR, Part 3200 aux Unis ou à la norme Can/CSA-Z240 Série MM, Maisons mobiles au Canada.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
/ NFPA 70—latest edition or the Canadian Electrical Code CSA C22.1—latest edition.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. The appliance may be installed in a bedroom.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures.
The location should also be free of electrical, plumbing, or other heating/air conditioning ducting.
These direct-vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Be aware that this is a heat producing appliance. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the appliance and the area above it.
The minimum height from the base of the appliance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 8.
HORIZONTAL VENT
(Top Vent Application)
N O
I
TNEVPOT
NOITACILPPA
TOP VENT
VERTICAL VENT
(Top Vent Application)
T A C
I L P P A
5
Page 6
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
12
X
Roof Pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
Discharge
Opening
H*
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
Horizontal Overhang
Vertical Wall
Vent
Termination
Storm Collar
Concentric
Vent Pipe
Flashing
1 in. (25.4 mm) Minimum Clearance to Combustibles
Horizontal Vent Termination Clearances
VENT TERMINATION CLEARANCES
Figure 4: Vertical Vent Termination Clearances
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA, or the current standards of CAN/ CSA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above (Figure 3).
Figure 3: Multiple Terminations
12 in.
(305 mm)
minimum
Terminate single vent caps relative to building components according to Table 5 and Figure 4.
Table 5: Termination Heights for Vents
f i r e - p a r t s . c o m
above Flat or Sloped Roofs (NFPA 54 / ANSI Z223.1)
Roof Pitch Termination Height
Flat to 6/12 6/12 to 7/12 1.25 ft (0.38 m) 7/12 to 8/12 1.5 ft (0.46 m) 8/12 to 9/12 2.0 ft (0.61 m)
9/12 to 10/12 2.5 ft (0.76 m) 10/12 to 11/12 3.25 ft (0.99 m) 11/12 to 12/12 4.0 ft (1.22 m) 12/12 to 14/12 5.0 ft (1.52 m) 14/12 to 16/12 6.0 ft (1.83 m) 16/12 to 18/12 7.0 ft (2.13 m) 18/12 to 20/12 7.5 ft (2.29 m) 20/12 to 21/12 8.0 ft (2.44 m)
1.0 ft (0.3 m)
Figure 5: Horizontal Vent Termination Clearances
Combustible Projection
2 1/2
Combustible Projection greater
than 2 1/2 in. in length
Ventilated
Soffit
Unventilated
Soffit
18 in.
(457 mm)
12 in.
(305 mm)
in. or less in length
6 in.
(152 mm)
All horizontal terminations may be located as close as 6 in. (152 mm) to any combustible exterior sidewall. This distance may be decreased to 4 in. (102 mm) for non­combustible exterior sidewalls.
Side Elevation View
Termination Kit
See Figure 24 for the exterior wall recess allowances of the square horizontal termination.
Termination Kit
Horizontal Vent Termination Clearances
6
The horizontal vent termination must have a minimum of 6 in. (152 mm) clearance to any overhead combustible projection of 2 1/2 in. (64 mm) or less (see Figure 5). For projections exceeding 2 1/2 in. (64 mm), see Figure 5. For additional vent location restrictions refer to Table 6 on Page 7.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Table 6: Exterior Horizontal Vent Termination Clearances
NOTE: Local Codes Or Regulations
See Item D in the Text Below.
*
V
L
Horizontal Termination
B
Exterior Wall
*18 in.
V
Inside Corner
6 in.
Ventilated Soffit
Detail D
V
F
V
A
X
= Air Supply Inlet
Fixed
Closed
C
C
C
V
= Vent Termination
V
Window
C
A
B
V
B
Inside
Corner Detail
G
V
Operable
Window
B
B
= Area where Termination is not Permitted
U.S. Installation ** Canadian Installation * A Clearance above grade, veranda, porch, desk, or balcony B Clearance to window or door that may be opened
12 in. (300 mm) ** 12 in. (300 mm) *
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
9 in. (230 mm)
for appliances > 10,000 Btuh (3 kW), and < 50,000 Btuh (15 kW),
12 in. (300 mm)
for appliances > 50,000 Btuh (15 kW) ** C Clearance to permanently closed window
f i r e - p a r t s . c o m
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18 in. (458 mm)
E Clearance to unventilated soffit
F Clearance to outside corner
G Clearance to inside corner
9 in. (229 mm)
recommended to prevent window condensation
18 in. (458 mm) 18 in. (458 mm)
12 in. (305 mm)
30 in. (760 mm) to vinyl soffit
5 in. (127 mm)
minimum
2 in. (50.8 mm)
minimum—SV4.5HT-2 •
6 in. (152 mm)
minimum—SV4.5HTSS H Clearance to each inside of center line extended above
meter / regulator assembly
I Clearance to service regulator vent outlet
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other appliance
36 in. (910 mm)
within a height of 15 ft above the meter / regulator assembly **
36 in. (910 mm)** 36 in. (910 mm)*
6 in. (150 mm)
for appliances < 10,000 Btuh (3 kW),
9 in. (230 mm)
for appliances > 10,000 Btuh (3 kW) and < 50,000 Btuh (15 kW),
12 in. (300 mm)
for appliances > 50,000 Btuh (15 kW)**
K Clearance to a mechanical air supply inlet
L Clearance above paved sidewalk or paved diveway located
36 in. (910 mm) above if within 10 ft (3 m) horizontally ** 72 in. (1830 mm) *
84 in. (2130 mm) ‡ 84 in. (2130 mm) ‡
on public property
M Clearance under veranda, porch, deck or balcony
N Depth of alcove (maximum) O Clearance to termination (alcove) P Width of alcove (minimum) Q Clearance to combustible above (alcove)
*
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
**
In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
2 in. clearance to non-combustibles for SV4.5HT-2 only
12 in. (300 mm) *‡ 12 in. (300 mm) *‡
72 in. (1830 mm) ** 72 in. (1830 mm) *
6 in. (15.2 mm) ** 6 in. (15.2 mm)*
36 in. (910 mm) ** 36 in. (910 mm) *
18 in. (457 mm) ** 18 in. (457 mm) *
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
May Require Different Clearances.
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
= 9 in. (in U.S.)
A
= 12 in. (in Canada)
3 ft.
X
A
A
3 ft.
J
P
N
H
M
I
N
O
V
Q
D
V
6 in. (150 mm) for appliances < 10,000 Btuh (3 kW),
12 in. (300 mm) for appliances > 10,000 Btuh (3 kW)
12 in. (305 mm) recommended to prevent window condensation
12 in. (305 mm) 30 in. (760 mm) to vinyl soffit
5 in. (127 mm) minimum
2 in. (50.8 mm)
minimum—SV4.5HT-2 •
6 in. (152 mm) minimum—SV4.5HTSS
36 in. (910 mm) within a height of 15 ft above the meter / regulator assembly *
6 in. (150 mm) for appliances < 10,000 Btuh (3 kW),
12 in. (300 mm) for appliances > 10,000 Btuh (3 kW)
E
V
7
Page 8
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
5 (127)
12 (305)
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials on all sides (Table 7), with the following exception: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding the unit must not extend beyond the front edge of the unit (Figure 7).
Table 7: Minimum Clearances *
Back
Sides
Top Spacers
Floor
From Bottom of
Unit to Ceiling
Front Service
Clearance
* 3 in. (76 mm) above any horizontal/inclined vent component.
** See Page 9 for clearance requirements to the nailing flange located at each side of the unit and
f i r e - p a r t s . c o m
any screw heads adjacent to it.
1/2 in. (13 mm) to wrapper
0 in. (0 mm) to Spacers
1/2 in. (13 mm) to wrapper 0 in. (0 mm) to Spacers **
0 in. (0 mm) 0 in. (0 mm)
78 in. (1981 mm)
36 in. (914 mm) Top *
12 in. (305 mm) Sides and Bottom
Hearth Extension
A hearth extension must be built from non-combustible, heat-resistant materials
Wall Finishes / Surrounds / Mantels
Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance face (Figure 7).
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance face with these exceptions: they must not cover any portion of the removable glass panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (Table 8). Mantels constructed of non-combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the fireplace hood.
Figure 6: Shelf Height
28 (711)
26 (660)
24 (607)
22 (559)
20 (508)
18 (457)
12
(305)
10
(254)
8
(203)
6
(152)
Table 8: Combustible Shelf Height
Top Vent with one 90° Elbow
Model
NV35 NV40 NV45
78 in.
Minimum
Shelf Height
(see table)
* Includes 3 in. (76 mm) clearance to combustibles (required above vent components)
4
2
(102)
(51)
Secure Vent
73 1/2 in.
(1867 mm) *
(e.g., Micore® 160, Glasscrete®, Durock®, or a similar material). It must extend the width of the fireplace opening and at least 20 in.
in. (mm)
in front of the fireplace.
A hearth extension is required if the fireplace is installed less than 6 in. above the finished floor surface.
A hearth extension is not required if the fireplace is installed at least 6 in. above the finished floor surface.
Shelf Height
To provide for the lowest possible shelf surface, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the appliance. Do not insulate the space between the appliance and the area above it (Figure 6).
Figure 7: Combustible Side Clearances
At 14 1/2 in. minimum side wall clearance, a combustible wall can project to any length.
At 13 3/4 in. side wall clearance, a combustible wall can project 12 in.
45
At 5 1/2 in. side wall clearance, a combustible wall can project 5 in.
o
Top View of
Fireplace
Combustible Materials Allowed In Shaded Area “Safe Zone”
Combustible Walls shown in dark gray
Combustible materials may project beyond one side of the fireplace opening as long as they are kept within the shaded areas illustrated here.
Secure Flex®
®
(flex elbow)
73 1/2 in.
(1867 mm) *
Minimum 12 in. (305 mm) vent section required before elbow.
No combustibles or insulation in the shaded area between the appliance and the shelf above it.
in. (mm)
Protected wall shown in white
8
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
D
TYPICAL INSTALLATION SEQUENCE
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
PRE-INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
1. Remove the shipping carton and the shipping pad.
2. Remove the top louver, then remove the surround trim assembly by
f i r e - p a r t s . c o m
detaching it at the top of the fireplace and lifting it 1 in. to disengage the side tabs, then pulling it away from the fireplace exposing the front glass door (Figure 8).
Figure 8: Removing the surround
trim assembly
The typical sequence of installation is outlined below. However, each installation is unique and may result in variations to the steps described.
See the pages referenced in the following steps for detailed instructions.
1. Construct the Appliance Framing (Page 9).
2. Route the Gas Supply Line to the Appliance (Page 11)
3. Install the Vent System and Exterior Termination (Page 11)
4. Complete the Field Wiring (Page 23)
5. Connect the Gas Supply (Page 25)
6. Verify Correct Appliance Operation (Page 26)
7. Contemporary Fireplaces Only: Install the Contemporary Floor and Contemporary Glass Media (Page 26)
8. Install the Firebox Liners (Page 26)
9. Traditional Fireplaces Only: Install the Logs, Decorative Volcanic Stone, and Glowing Embers (Page 27)
10. Install the Glass Door (Page 28)
11. Adjust the Burner to Ensure Proper Flame Appearance (Page 28)
12. Attach the Safety-in­Operation Warnings (Page 31)
Bend each of the two (2) L-shaped standoff components, at the designated places, into a U-shape (Figure 9). Align the closed end of each U-shaped standoff component with the left/right side of the top, front of the fireplace and the attachement holes in the top of the fireplace. Attach each U-shaped standoff component with two (2) 5/16 in. hex head screws. Align the center support with the holes in the U-shaped standoff components and the top of the fireplace. Attach the center support with two (2) 5/16 in. hex head screws in the top and two (2) screws in the bottom.
NOTE: Position the center support with the larger holes at the bottom and the smaller holes at the top.
Figure 9: Framing Standoff
The fireplace should be secured to the side framing members using the unit’s nailing flanges—one top and bottom on each side of the fireplace front (Figure 10). Use 8d nails or their equivalent.
Figure 10: Nailing Flanges *
Side
Framing
5/8 in.
Unit Nailing
1/2 in.
Flanges
Flush
Nailing Flanges Are Provided At All Four Corners
Side Tabs
3. Locate the four (4) spring-loaded
latches; two above and two below the enclosure (Figure 39).
4. Release the lower latches, by pulling
each handle out and down to unhook it from the glass door.
5. Lightly press against the door, to hold
it in position, while releasing the two upper latches.
6. Carefully grip the door at the top
and bottom, and remove it from the fireplace. Place the door in a secure location where it will not be damaged.
Construct the Appliance Framing
Frame the fireplace as illustrated in Table 9, or Table 11 for corner installations.All framing details must allow for a minimum clearance to combustible framing members as shown in Table 6 on Page 7.
If the fireplace is to be elevated above floor level, a solid continuous platform must be constructed below the fireplace.
Headers may be in direct contact with the fireplace top spacers maintaining the 15 1/2 in. (394 mm) clearance to the fireplace top, but must not be supported by them or notched to fit around them. All construction above the fireplace must be self-supporting. DO NOT use the fireplace for structural support.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
* Left side top corner of fireplace is shown. Requirements for other three corners are the same.
Bend out appropriate nailing flanges to provide for proper drywall thickness to front of firebox.
Position the fireplace within the framing and secure it with the nailing brackets. Bend out the appropriate nailing flanges for the drywall/finish material to be used. Nailing flanges are provided for flush framing, 1/2 in. (13 mm) and 5/8 in. (16 mm) framing depths (Figure 10).
NOTE: Combustible framing may be in direct contact with the nailing flanges and may be located closer than 1/2 in. (13 mm) from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified.
9
Page 10
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
FLUE OUTLET 4 1/2 (114)
COMBUSTION AIR 7 1/2 (190)
E
F
14.75 (267)
C
A
G
15 1/2
(394)
B
23
(584)
D
Table 9: Fireplace Framing Specifications
Model A B C D
NV35IN /
NVCD35IN
NV40IN /
NVCD40IN
NV45IN /
NVCD45IN
39.75 in.
1010 mm
44.75 in.
1137 mm
49.75 in.
1264 mm
44.75 in.
1137 mm
48.5 in.
1232 mm
52.25 in.
1327 mm
24.0 in.
610 mm
24.0 in.
610 mm
24.0 in.
610 mm
46.75 in.
1187 mm
50.5 in.
1283 mm
54.25 in.
1378 mm
Vertical Venting Through the Ceiling:
To frame the ceiling opening, use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/ or frame an opening, 10 1/2 x 10 1/2 in. (267 x 267 mm) inside dimensions, about this center mark (Table 15).
Vent Framing - Top Vent With One 90° Elbow
B
1/2
A
A
Inches (millimeters)
Framing should be constructed of 2x4
267
)
or larger lumber
7
(178)
12 1/8
(308)
10 1/2
(
5 1/8 (130)
D
C
C is the required framing depth dimension when the finish material (drywall) thickness is 1/2 in. (13mm)
Table 10: Fireplace Specifications
Model A B C D E F G
f i r e - p a r t s . c o m
NV35IN /
NVCD35IN
NV40IN /
NVCD40IN
NV45IN /
NVCD45IN
44.5 in.
1130 mm
48.25 in.
1226 mm
52.0 in.
1321 mm
24.75 in. 629 mm
28.0 in.
711 mm
32.25 in. 819 mm
28.75 in. 730 mm
33.75 in. 857 mm
38.75 in. 984 mm
39.25 in. 997 mm
44.25 in.
1124 mm
49.25 in.
1251 mm
21.85 in. 555 mm
27.0 in.
686 mm
32.0 in.
813 mm
10.93 in. 278 mm
13.5 in.
343 mm
16.0 in.
406 mm
28.5 in.
724 mm
32.25 in. 819 mm
36.0 in.
914 mm
15 1/2
(394)
A
Standoff Assembly
D
C
Table 11: Corner Framing with Horizontal Termination
Model A B C D E
NV35IN /
NVCD35IN
NV40IN /
NVCD40IN
NV45IN /
NVCD45IN
NOTE: The horizontal vent length of “A” to “B” must not exceed 28 in. (711 mm).
39.25 in.
1000 mm
44.25 in.
1124 mm
49.25 in.
1251 mm
68.00 in.
1727 mm
73.00 in.
1854 mm
78.00 in.
1981 mm
48.10 in.
1222 mm
51.60 in.
1311 mm
55.10 in.
1400 mm
13.75 in. 349 mm
15.50 in. 394 mm
17.25 in. 438 mm
34.00 in. 864 mm
36.50 in. 927 mm
39.00 in. 991 mm
D
a
C
B
G
b
7 in.
(178 mm)
E
10
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Back wall of chase/enclosure
(including any finishing materials)
A B
Page 11
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Route the Gas Supply Line to the Appliance
A 1/2 in. (13 mm) gas line must be routed to the left side of the appliance (Figure 11). Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. All appliances are factory­equipped with a flexible gas line connector and a 1/2 in. shutoff valve (Page 25).
Figure 11: Routing the gas line
Left Side Front
Corner of
Fireplace Framing
4 1/2 in.
(114 mm)
1 1/2 in. (38 mm)
4 in.
(102 mm)
f i r e - p a r t s . c o m
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54—latest edition (USA) or CAN/CSA-B149.1—latest edition (Canada).
Never use galvanized or plastic pipe. Refer to the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
Hire a qualified plumber or gas fitter to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, controls, pressure, sediment, and more. No one unfamiliar and unqualified should attempt sizing or installing gas piping.
All appliances are factory-equipped with
See Massachusetts Requirements
The gas supply line should not be
A pipe joint compound rated for gas
A sediment trap in the supply line as
Check with the local building official
Table 12 for proper sizing of
Table 12: Schedule 40 Black Iron Pipe, Inside Diameter
Pipe Length Natural Gas Propane Gas
0–10 ft 1/2 in. 3/8 in.
10–40 ft 1/2 in. 1/2 in.
40–100 ft 1/2 in. 1/2 in. 100–150 ft 3/4 in. 1/2 in. 150–200 ft 3/4 in. 1/2 in.
a flexible gas line connector and 1/2 in. shutoff valve (Figure 31).
(Page 4) for additional requirements for installations in the state of Massachusetts in the USA.
connected to the appliance until Page 25.
should be used on the threaded joints. Ensure propane-resistant compounds are used in propane applications. Be very careful that the pipe compound does not get inside the pipe.
close as possible to the appliance is recommended. Appliances using propane should have a sediment trap at the base of the tank.
for local code requirements (e.g., Are below grade penetrations of the gas line allowed?, etc).
CAUTION
If propane is used, be aware that with a tank that is too small (i.e., under 100 lbs, if this is the only gas appliance in the dwelling—see NPFA 58), there may be a loss of pressure. This can result in insufficient fuel delivery that can cause sooting, severely delayed ignition, or other malfunctions. Any damage resulting from an improper installation is not covered by the limited warranty.
Install the Vent System and Exterior Termination
NOTE: These instructions should be used
as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installation locaux et aux exigences du foumisseunde gaz.
Use only approved venting components (Page 2). These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). Inspection openings in the enclosing wall, at the vent pipe joints, are not required.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Page 12
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Installation of Vent Restrictor
A vent restrictor may be needed with this appliance. The restrictor is installed in the appliance top flue outlet (Figure 13), either before adding vent from above, or after installation of vent from below—within the firebox. The restrictor is self securing with a positive friction fit.
Determine the vent restrictor configuration for the appliance (
Use the base vent restrictor for:
Horizontal termination with total vertical run of more than 6 ft.
Vertical termination with total vertical run of 6–10 ft.
Use intermediate setting for:
Vertical termination with total vertical run of >10–40 ft.
Use the maximum setting for:
Vertical termination with total vertical run of >40–60 ft.
Figure 12):
Figure 12: Vent Restrictor Configuration
Base Vent Restrictor
Intermediate Vent Restrictor
f i r e - p a r t s . c o m
Maximum Vent Restrictor
Figure 13: Vent Restrictor Installation
Vent
Collar
Vent
Restrictor
Assembly
(held in place
by friction only)
12
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
10 1/2 in. Min.
SV4.5CGV-1
Select Venting System— Horizontal or Vertical
With the appliance secured in the framing, determine the vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent installations. A list of approved venting components are shown on Page 32.
Vertical (Roof) Termination Systems
See the tables starting on Page 17 for the various vertical venting configurations that are possible for use with these appliances. Secure Vent™ pipe applications are shown in these figures. Secure Flex™ pipe may also be used. A vertical vent table summarizes each system’s minimum and maximum vertical and horizontal lengths.
Both vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is specified in ANSI Z223.1—latest edition (In Canada, the current CAN/CSA-B149.1 installation code) by major building codes. Always consult your local codes for specific requirements. A general guide to follow is the Gas Vent Rule (
Page 6).
Vertical (Straight) Installation
Determine the number of straight vent
f i r e - p a r t s . c o m
sections required. 4 1/2 in. (114 mm), 10 1/2 in. (267 mm), 22 1/2 in. (572 mm), 34 1/2 in. (876 mm) and 46 1/2 in. (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists.
Figure 14: Vertical (Straight) Installation
Termination
SV4.5FA OR SV4.5FB Flashing AND SV4.5SC STORM COLLAR
Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to the vertical vent figures and tables starting on Page 17 to select the type of vertical installation desired. Vent sections are available in net lengths of 4 1/2 in. (114 mm), 10 1/2 in. (267 mm), 22 1/2 in. (572 mm), 34 1/2 in. (876 mm) and 46 1/2 in. (1181 mm). Refer to Table 13 for an aid in selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to Figure 18 on Page 15 for the SV4.5E45 and SV4.5E90 elbow dimensional specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option in installing in tight and confined spaces, or where the vent run made up of fixed length pieces results in a joint in a undesirable location or will not build up to the required length. The SV4.5LA telescopic vent section has an effective length of from 1 1/2 in. (38 mm) to 7 1/2 in. (191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with 3 pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three screws.
Maintain a minimum 1 in. (25 mm) clearance to combustible materials for all vertical elements. Clearances for all horizontal elements are 3 in. (76 mm) on top, 1 in. (25 mm) on sides and 1 in. (25 mm) on the bottom.
1. Frame ceiling opening—Use a plumb
line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening, 10 1/2 x 10 1/2 in. (267 x 267 mm) inside dimensions, about this center mark (Figure 15).
Figure 15: Ceiling Opening
1 in. (25.4 mm) Minimum Clearance to Combustibles
SV4.5VF
Firestop/Spacer
Roof Framing
10 1/2 in. Min. (267 mm)
(267 mm)
2. Attach vent components to appliance—
Secure Vent SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist lock connections (Figure 16). To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (Figure 16). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the ends of the channels.
Slide the rope gasket over the vent component and position it snugly against the apppliance.
The unitized design of Secure Vent™ components will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired, a #6 x 1/2 in. screw may be used at the joint, but is not required as the pipe will securely lock when twisted. An elbow may not be directly attached to the appliance collar.
NOTE: All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
Figure 16: Appliance Collar
Align the dimple (4 places) of the upper vent section with the opening of the locking incline channel on the lower vent section or appliance collar. Twist vent component clockwise to engage and seal until arrow and
Arrow
Appliance Collar or Vent Section
dimple align.
Dimple
Locking Incline Channel
Connected Vent Sections
Arrow
60 ft Maximum
(18.3 m)
6 ft Minimum
(1.8 m)
SV4.5L6/12/24/36/48 Vent Sections
When using Secure Flex
use Firestop/Spacer
SF4.5VF
Vertical (Offset) Installation
Ceiling Framing
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Plumb Bob
13
Page 14
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
3. Attach vent components to each other—Additional vent sections may be added to the previously installed section in accordance with the requirements of the vertical vent figures and tables.
4. Install firestop/spacer at ceiling—When using Secure Vent™, use SV4.5VF firestop/spacer at ceiling joists. When using Secure Flex™, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1 in. (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (H3907) may be used to obtain the required clearances. The gap between the vent pipe and a vertical firestop can be sealed with non-combustible caulking.
f i r e - p a r t s . c o m
14
Table 13: Vent Section Length
Nominal
Section Length
(in.)
Net Section Length (in.)
Height of Vent
in. ft
4.5 0.375 1 0 0 0 0 1
9 0.75 2 0 0 0 0 2
10.5 0.875 0 1 0 0 0 1
15 1.25 1 1 0 0 0 2
22.5 1.875 0 0 1 0 0 1
31.5 2.625 0 3 0 0 0 3
34.5 2.875 0 0 0 1 0 1
37.5 3.125 1 1 1 0 0 3
43.5 3.625 0 2 1 0 0 3
45 3.75 0 0 2 0 0 2
46.5 3.875 0 0 0 0 1 1
51 4.25 1 0 0 0 1 2
55.5 4.625 0 1 2 0 0 3
57 4.75 0 0 1 1 0 2
67.5
69 5.75 0 0 0 2 0 2
73.5 6.125 1 0 0 2 0 3
79.5 6.625 0 1 0 2 0 3
81 6.75 0 0 0 1 1 2
91.5 7.625 0 0 2 0 1 3
93 7.75 0 0 0 0 2 2
97.5 8.125 1 0 0 0 2 3
103.5 8.625 0 0 0 3 0 3
108 9 1 0 0 3 0 4
117 9.75 1 0 5 0 0 6
118.5 9.875 1 1 0 3 0 5
126 10.5 0 0 1 3 0 4
130.5 10.875 1 0 1 3 0 5
135 11.25 0 0 6 0 0 6
139.5 11.625 0 0 0 0 3 3
142.5 11.875 1 0 0 4 0
144 12 1 0 0 0 3 4
154.5 12.875 1 1 0 0 3 5
160.5 13.375 0 2 0 0 3 5
172.5 14.375 0 0 0 5 0 5
177 14.75 1 0 0 5 0 6
186 15.5 0 0 0 0 4 4
196.5 16.375 0 1 0 0 4 5
207 17.25 0 0 0 6 0 6
211.5 17.625 1 0 0 6 0 7
217.5 18.125 0 1 0 6 0 7
229.5 19.125 0 0 1 6 0 7
232.5 19.375 0 0 0 0 5 5
241.5 20.125 0 0 0 7 0 7
246 20.5 1 0 0 7 0 8
252 21 0 1 0 7 0 8
276 23 0 0 0 8 0 8
279 23.25 0 0 0
280.5 23.375 1 0 0 8 0 9
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
6 12 24 36 48
4.5 10.5 22.5 34.5 46.5
Number of Vent Sections
5.625 0 0 3 0 0 3
0 6 6
Table 13: Vent Section Length
Nominal
Section Length
(in.)
Net Section Length (in.)
Total Qty
Height of Vent
in. ft
289.5 24.125 0 1 0 0 6 7
301.5 25.125 0 0 1 0 6 7
310.5 25.875 0 0 0 9 0 9
325.5 27.125 0 0 0 0 7 7
330 27.5 1 0 0 0 7 8
345 28.75 0 0 0 10 0 10
349.5 29.125 1 0 0 10 0 11
372 31 0 0 0 0 8 8
379.5 31.625 0 0 0 11 0 11
465 38.75 0 0 0 0 10 10
475.5 39.625 0 1 0 0 10 11
480 40 1 1 0 0 10 11
492 41 1 0 1 0 10 12
499.5 41.625 0 0 0 1 10 11
504
511.5 42.625 0 0 0 0 11 11
520.5 43.375 0 2 0 1 11 14
531 44.25 0 2 2 0 11 15
538.5 44.875 1 0 0 2 11 14
549 45.75 1 0 2 1 11 15
558 46.5 0 0 0 0 12 12
562.5 46.875 1 0 0 0 12 13
568.5 47.375 0 1 0 0 12 13
573 47.75 1 1 0 0 12 14
580.5 48.375 0 0 1 0 12 13
589.5 49.125 0 1 2 2 10 15
595.5 49.625 1 1 1 0 12 15
604.5 50.375 0 0 0 0 13 13
615 51.25 0 1 0 0 13 14
625.5 52.125 0 2 0 0 13 15
5
631.5 52.625 1 0 1 0 13
637.5 53.125 0 1 1 0 13 15
651 54.25 0 0 0 0 14 14
655.5 54.625 1 0 0 0 14 15
672 56 0 2 0 0 14 16
678 56.5 1 0 1 0 14 16
688.5 57.375 1 1 1 0 14 17
697.5 58.125 0 0 0 0 15 15
702 58.5 1 0 0 0 15 16
712.5 59.375 1 1 0 0 15 17
720 60 0 0 1 0 15 16
6 12 24 36 48
4.5 10.5 22.5 34.5 46.5
Number of Vent Sections
42 1 0 0 1 10 12
Total Qty
15
Page 15
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Table 14: Effective Vent Length
Model Effective Length
SV4.5L6 SV4.5L12 10 1/2 in. SV4.5L24 22 1/2 in.
SV4.5L36 34 1/2 in. SV4.5L48 46 1/2 in.
4 1/2 in.
5. Support the vertical vent run sections—
Support the vertical portion of the venting system every 8 ft (2.4 m) above the fireplace vent outlet. One method of support is by utilizing field provided support straps (conventional plumber’s tape). Secure the plumber’s tape to the framing members with nails or screws. Loop the tape around the vent and secure the ends of the tape to the framing. If desired, sheet metal screws (#6 x 1/2 in.) may be used to secure the support straps to the vent pipe (Figure 17).
Figure 17: Venting Support
Blocking
Support Straps (Plumber's tape)
6. Change vent direction to horizontal/
inclined run—At transition to/from a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a clockwise direction only, to avoid the possibility of unlocking any of the previously connected vent sections (Figure 16).
Figure 18: Elbow Mounting
4 13/16 in.
(122 mm)
Swivel Joint
(360° swivel)
SV4.5E45
(45° Elbow)
Swivel Joint
(360° swivel)
(90° Elbow)
7. Continue installation of horizontal/
inclined sections—Continue with the
8 ft (2.4 m) maximum
installation of the straight vent sections in horizontal/inclined run. Install support straps every 5 ft (1.52 m)
f i r e - p a r t s . c o m
1/2 in. (12.7 mm) minimum clearance to combustibles
along horizontal/inclined vent runs using conventional plumber’s tape (Figure 22). Maintain the horizontal/ inclined run in a straight (no dips) and slightly elevated (recommended) plane, in a direction away from the fireplace of 1/4 in. rise per foot (20 mm per meter). Smaller rise per foot run ratios are
NOTE: Proper venting support is very important. The weight of the vent must not be supported by the fireplace.
acceptable all the way down to at/near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
SV4.5E90
8 1/8 in.
(206 mm)
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: Maintain the required clearances to combustibles: 1 in. (25 mm) at all sides for all vertical runs; and 3 in. (76 mm) at the top, 1 in. (25 mm) at sides, and 1 in. (25 mm) at the bottom for all horizontal/inclined runs.
15
Page 16
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
C
D
8. Frame the roof opening—Identify the
location for vent at the roof. Cut and/or frame the opening per Table 15.
Table 15: Roof Framing Dimensions
Pitch C D
0/12 10 1/2 in.
6/12 10 1/2 in.
12/12 10 1/2 in.
9. Install the roof flashing—Extend
the vent sections through the roof structure. Using a carpenter’s level, install the roof flashing over the vent section and position it such that the vent column rises vertically (Figure 19). Nail along perimeter to secure flashing or adjust roofing to overlap the flashing
f i r e - p a r t s . c o m
edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking.
(267 mm)
(267 mm)
(267 mm)
10 1/2 in.
(267 mm)
12 in.
(305 mm)
17 3/4 in.
(451 mm)
10. Install the storm collar—Install the
storm collar, supplied with the flashing, over the vent/flashing joint (Figure 19). Loosen the storm collar screw. Slide the collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a watertight seal.
Figure 19: Storm Collar
Storm
Flashing
Collar
11. Install the vertical termination
(SV4.5CGV-1)—Extend the vent sections to the correct height (Figure 4). The SV4.5CGV-1 vertical termination (Figure 20) can be installed in the exact same fashion as any other Secure Vent™ section. Align the termination over the end of the previously installed section, adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they are seated at the end of the channels. If the vent system extends more than 5 ft (1.5 m) above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional support on multiple joint configurations.
Figure 20: Vertical Termination
16
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Vertical Vent Tables and Figures
Table 16: Top Vent—Two 90° Elbows
Table 17: Top Vent—Three Elbows
NOTE: Secure Vent® rigid vent pipe is shown in the figures. Secure Flex® flexible vent pipe may also be used.
H
V
1
Ceiling Firestop/Spacer SV4.5VF*
NOTE: It is very important that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4 in. per foot (20 mm per meter) horizontal, in a direction away from the fireplace. The rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
NOTE: SV4.5VF (Secure Vent), SF4.5VF
V1
Ceiling Firestop/Spacer SV4.5VF*
Wall Firestop/Spacer SV4.5HF**
H
1
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
H
(Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
NOTE: Two 45° elbows may be used in place of one 90° elbow. The same rise to run ratios, as shown in the venting figures for 90°, must be followed if 45° elbows are used.
NOTE: An elbow is acceptable as 1 ft of vertical rise, but may not be connected
f i r e - p a r t s . c o m
directly to the appliance collar.
WARNING
Under no circumstances, may separate sections of concentric flexible vent pipe be joined together.
Figure 21: Top Vent—Straight
*When using Secure Flex, use Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use Wall Firestop/Spacer SF4.5HF.
H Maximum V Minimum
feet meters feet meters
5 1.524 2 0.610
10 3.048 3 0.914
15 4.572 4 1.219
20 6.096 5 1.524
V + V
+ H = 60 ft (18.3 m) maximum
1
H = 20 ft (6.096 m) maximum Install the U-shaped vent restrictor in any vent run
with more than 6 ft of vertical rise. See Page 12 for more information.
If 20 ft of (H) horizontal vent run is needed, then 4 ft (straight section) minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H) horizontal run, up to a maximum
V
H + H1 Maximum V Minimum feet meters feet meters
5 1.524 1 0.305
5 1.524 1 0.305
10 3.048 2 0.610
15 4.572 3 0.914
20 6.096 4 1.219
H + H
= 20 ft (6.1 m) maximum
1
V + V1 + H + H1 = 60 ft (18.3 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 12 for more information.
If 20 ft of (H) horizontal vent run is needed, then 4 ft (straight section) minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft.
An elbow is acceptable as 1 ft of vertical rise, but may not be connected directly to the appliance collar.
NOTE: The vent system may have a
maximum of three (3) 90° elbows. horizontal run of 20 ft. An elbow is acceptable as 1 ft of vertical
rise, but may not be connected directly to the appliance collar.
u Ceiling Firestop /
Spacer (SV4.5VF)
60 ft (18.3 m)
Maximum
Wall Firestop/Spacer SV4.5HF**
V
When using
u
Secure Flex, use
Firestop / Spacer
SF4.5VF
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 12 for more information.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Page 18
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Horizontal (Outside Wall) Termination System
See the horizontal vent tables on Page 20 that illustrate the various horizontal venting configurations that are possible for use with these appliances. Secure Vent™ pipe applications are shown in these figures; Secure Flex™ pipe may also be used. The tables summarize each system’s minimum and maximum vertical and horizontal lengths for installing the vent components in a variety of applications.
These horizontal vent systems terminate through an outside wall. Building codes limit or prohibit terminating in specific areas (
Table 6).
Secure Vent SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist lock connections (Figure 16). All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
1. Plan the vent run—Analyze the vent
routing and determine the types and quantities of sections required: 4 1/2 in. (114 mm), 10 1/2 in. (267 mm), 22 1/2 in. (572 mm), 34 1/2 in. (876 mm) and 46 1/2 in. (1181 mm)
f i r e - p a r t s . c o m
net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Make allowances for elbows. Maintain a minimum 1 in. (25 mm) clearance to combustibles on the vertical sections. Clearances for the horizontal runs are 3 in. (76 mm) on top, 1 in. (25 mm) on sides, and 1 in. (25 mm) at the bottom.
2. Frame exterior wall opening—Locate
the center of the vent outlet on the exterior wall according to the dimensions shown in (Figure 23). Cut and/or frame an opening, 10 1/2 x 12 1/8 in. (267 x 308 mm) inside dimensions, about this center.
3. Frame ceiling opening—If the vertical
route will penetrate a ceiling, use a plumb line to locate the center above the appliance. Cut and/or frame an opening, 10 1/2 x 10 1/2 in. (267 x 267 mm) inside dimensions, about this center (Table 15).
4. Attach vent components to appliance—
To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (Figure 16). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along
18
the incline channels until they seat at the end of the channels.
Slide the rope gasket over the vent component and position it snugly against the apppliance.
The unitized design of Secure Vent™ components will engage and seal both the inner and outer pipe elements with the same procedure. Sealant and securing screws are not required.
NOTE: An elbow may not be attached directly to the appliance collar. At a
minimum, a 12 in. (305 mm) straight vent section is required before attaching the first elbow (Figure 22).
5. Attach vent components to each
other—Other vent sections may be added to the previously installed section in accordance with the requirements of the vent tables. To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating position is indicated by the alignment of the arrow and dimple (
6. Install firestop/spacer at ceiling—
When using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists. When using Secure Flex, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
NOTE: Maintain 1 in. (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
7. Support the vertical run sections—
See Page 15.
8. Change vent direction—At transition to/
from a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a clockwise
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 16).
direction only, to avoid the possibility of unlocking any of the previously connected vent sections (Figure 16).
9. Continue installation of horizontal/
inclined sections—Continue with the installation of the straight vent sections in horizontal/inclined run. Install support straps every 5 ft (1.52 m) along horizontal/inclined vent runs using conventional plumber’s tape (Figure 22). Maintain the horizontal/ inclined run in a straight (no dips) and slightly elevated plane, in a direction away from the fireplace of 1/4 in. rise per foot (20 mm per meter). Smaller rise per foot run ratios are acceptable, all the way down to at/near level.
NOTE: Maintain the required clearances to combustibles: 1 in. (25 mm) at all sides for all vertical runs; and 3 in. (76 mm) at the top, 1 in. (25 mm) at sides, and 1 in. (25 mm) at the bottom for all horizontal/inclined runs. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
10. Assemble the vent run to the exterior
wall—If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Figure 23. Assemble the vent system to point where the terminus of the last section is located relative to the exterior surface to which the termination is to be attached (Figure 24). If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than those shown in Figure 24, refer to Table 18.
11. Attach the termination adaptor—Attach
the adaptor (SV4.5RCH, provided with the termination) to the vent section or telescoping vent section elbow or appliance collar (Figure 23) in the same manner as any SV4.5 vent component.
12. Install the firestop/spacer at the exterior
wall—When using the termination, install the SV4.5HF (Secure Vent™), or SF4.5HF (Secure Flex™) firestop/spacer over the opening at the exterior side of the framing, long side up, with the 3 in. spacer clearance at the top (Figure 23), and nail into place. The firestop/spacer may also be installed over the opening at the interior side of framing.
NOTE: The firestop/spacer also may be installed over the opening on the interior side of framing. The gap between the vent pipe and a firestop can be sealed with noncombustible caulking.
Page 19
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
of
13. Install the Termination (SV4.5HT-2)—
For the last step, from outside the exterior wall, slide the collars of the termination onto the adaptor (the outer inside the outer and the inner outside the inner) until the termination seats against the exterior wall surface to
Figure 22: Typical Horizontal Vent Installation
Building Support Framing
90° elbow
Horizontal Support Brackets
which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal termination must not be recessed into the exterior wall or siding by more than the 1 1/4 in. (32 mm) (Figure 24).
Vertical Rise
Ceiling
Vertical Firestop/ Spacer
u
Support vertical venting every 8 ft (2.4 m) above fireplace vent outlet
Place horizontal support brackets every 5 ft (1.524 m)
12 in. straight section required before a 90° elbow
NOTE: The vent termination is hot while in operation and for a period of time following the use of the fireplace. To
Fireplace
prevent contact with hot surfaces, use a termination guard (
Page 32). This
can be purchased at your local dealer.
Horizontal terminations have been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination where water from eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap. If the cap
f i r e - p a r t s . c o m
must be placed where the possibility
Figure 23: Installing Horizontal Termination
Firestop/Spacer (SV4.5HF) shown on the exterior side of the wall. It
may also be installed on the
10 1/2 in.
(267 mm)
12 1/8 in.
(308 mm)
5 1/8 in.
(130 mm)
7 in.
(178)
interior side.
of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Adapter
SV4.5RCH
Carefully follow the installation instructions for the termination, including the use of silicone caulking where required.
6 to 48 in. Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Frame Opening.
Base of Appliance
Exterior Wall
Horizontal Termination
Termination
1 in.
(25.4 mm)
Typical
Shown
3 in.
(76 mm)
Figure 24: Horizontal Termination
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
*Caulk
*Caulk
Stucco
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Siding
Square Termination
Interior Surface of
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section. Use Telescopic Vent Section (SV4.5LA), If Necessary
SV4.5HT-2
Shown
Finished Wall
Adapter
SV4.5RCH
Maximum wall thickness
9 1/4 in. (235 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9 1/4 in.
(152 to 235 mm)**
SV4.5HT-2
Square Termination
Shown
1-1/4 in. Maximum Recess the Square Termination into Exterior Finishing Material
19
Page 20
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Horizontal Vent Tables and Figures
Table 19: Top Vent—One 90° Elbow, Elbow Connection NOT at Appliance
NOTE: Secure Vent® components (rigid vent pipe and terminal) are shown in the figures; Secure Flex® components (flexible vent pipe and terminal) may also be used.
NOTE: Two 45° elbows may be used in place of one 90° elbow. The same rise to run ratios, as shown in the venting figures for 90° elbows, must be followed if 45° elbows are used.
NOTE: It is very important that the horizontal/inclined run be maintained in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4 in. per foot (20 mm per meter) horizontal, in a direction away from
When using Secure Flex,
use Firestop/Spacer
SF4.5VF.
When using Secure Flex,
use Firestop/Spacer
SF4.5HF.
Wall Firestop/Spacer
(SV4.5HF)
H
Min. One Foot Vent
Section
Required
Ceiling
Firestop/Spacer
(SV4.5VF)
the fireplace. Rise per foot run ratios are acceptable to at or near level.
NOTE:
SV4.5VF (Secure Vent), SF4.5VF
(Secure Flex) firestop/spacer must be
feet meters feet meters
used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
NOTE: The tables show a 1(V) to 1.6 (H) ratio up to a maximum horizontal run of 16 ft.
NOTE: An elbow is acceptable as 1 ft of
f i r e - p a r t s . c o m
vertical rise, but may not be connected directly to the appliance collar.
WARNING
Under no circumstances, may separate sections of
V + H = 60 ft (18.3 m) maximum H = 16 ft (4.87 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 12 for more information.
Square termination (SV4.5HT-2) shown. If 16 ft of (H) horizontal vent run is needed, then 10 ft minimum of (V) vertical vent will be required. This table shows a 1 (V) to 1.6 (H) ratio. For every 1 ft of (V) vertical, you are allowed 1.6 ft of (H) horizontal run, up to
a maximum horizontal run of 16 ft (4.87 m).
H Maximum V Minimum
3 0.91 1.6 0.490
5.2 1.58 3 0.914
6.8 2.07 4 1.22
8.4 2.56 5 1.524
10 3.05 6 1.729
16 4.87 10 3.050
concentric flexible vent pipe be joined together.
V
Table 18: Venting Components Required for Various Exterior Wall Thicknesses, when using Typical Termination Kits
Vent Components
Required
Termination Kit Only
Termination Kit and 6 in.
Vent Section (SV4.5L6)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
Termination Kit and
Telescopic Section
(SV4.5L12)
20
Exterior Wall Thickness
6–9 1/4 in.
(152–235 mm)
10 3/4–14 in.
(2733–356 mm)
16 3/4–20 in.
(426–508 mm)
11 3/4–20 in.
(299–508 mm)
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Table 20: Top Vent—Two 90° Elbows
H + H1 Maximum V Minimum
feet meters feet meters
3 0.91 1.6 0.490
5.2 1.58 3 0.914
6.8 2.07 4 1.22
8.4 2.56 5 1.524
10 3.05 6 1.729
16 4.87 10 3.050
V + H + H H + H1 = 16 ft (4.87 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 12 for more information.
Square termination (SV4.5HT-2) shown. See Table 18 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
If 16 ft of (H) horizontal vent run is needed, then 10 ft minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 1.6 (H) ratio. For every 1 ft of (V) vertical, you are allowed
1.6 ft of (H) horizontal run, up to a maximum horizontal run of 16 ft (4.87 m). An elbow is acceptable as 1 ft of vertical rise, but may not be connected directly to
the appliance collar.
= 60 ft (18.3 m) maximum
1
H
1
Note - When using
Secure Flex
Firestop/Spacer SF4.5VF.
When using SecureFlex,
use Firestop/Spacer
SF4.5HF.
TM
, use
Wall Firestop/Spacer
(SV4.5HF)
Wall
Firestop/Spacer
(SV4.5HF)
Ceiling
Firestop/Spacer
(SV4.5VF)
H
Min. One Foot Vent
Section Required
V
f i r e - p a r t s . c o m
Table 21: Top Vent—Three 90° Elbows
H Maximum V Minimum
feet meters feet meters
3 0.91 1.6 0.490
5.2 1.58 3 0.914
6.8 2.07 4 1.22
8.4 2.56 5 1.524
10 3.05 6 1.729
16 4.87 10 3.050
H + H
= 16 ft (4.87 m) maximum
1
V + V1 +H + H1 = 60 ft (18.3 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 12 for more information.
Square termination (SV4.5HT-2) shown. See Table 18 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
If 16 ft of (H) horizontal vent run is needed, then 10 ft minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 1.6 (H) ratio. For every 1 ft of (V) vertical, you are allowed
1.6 ft of (H) horizontal run, up to a maximum horizontal run of 16 ft (4.87 m). An elbow is acceptable as 1 ft of vertical rise, but may not be connected directly to
the appliance collar.
Wall Firestop/Spacer
(SV4.5HF)
H
1
V
1
When using Secure Flex
use Firestop/Spacer
When using Secure
Flex, use Firestop/Spacer
Wall Firestop/Spacer
(SV4.5HF)
Min. One Foot Vent
Section Required
SF4.5VF.
SF4.5HF.
Ceiling
Firestop/Spacer
(SV4.5VF)
H
TM,
V
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Vertical or Horizontal Venting Using Secure Flex™ Venting Kits and Components
Secure Flex™ venting kits and components may be used in any venting application in place of rigid Secure Vent™ (SV4.5) direct-vent components. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting. Secure Flex kits may not be modified. Do not join separate sections of flex pipe together.
Using an adaptor (SV4.5RF), Secure Flex kits may be added to the end of a vent run made up of rigid Secure Vent (SV4.5) vent sections provided that doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio requirements or clearance considerations detailed in this manual.
Secure Flex kits come with an adaptor that can be fitted to the inclined channel end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent section. Align the dimpled end of the adaptor over the previously installed section or appliance collar, adjusting the radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four inclined channels of the last vent section or collar.
f i r e - p a r t s . c o m
Push on the adaptor until it fully engages, then twist the adaptor clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Attach the flexible vent to the adaptor as follows (
1. Install the Inner flex pipe—Install the
Figure 25):
small gear clamp loosely around the inner flexible vent pipe and push it back out of the way. Apply a bead of Mill­Pac Black (700 °F) high temperature sealant (P/N 10K81) to the inner adaptor collar, approximately 1/2 in. from the end. Pull and extend the inner flexible vent pipe. Slide the inner flex pipe over the adaptor collar. Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1 3/4 in. from the end, and that it is free from damage or tears. Slide the gear clamp into place tighten it fully to secure the flexible vent to the adaptor inner collar approximately 3/4 in. from the end of the flex. Install the three (3) screws, 120° apart, through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide additional security to the connection.
2. Install the outer flex pipe—Install the
large gear clamp loosely around the outer flexible vent pipe and push it back out of the way. Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the outer adaptor collar, to the grooves of the collar that extend approximately 1 in. from the end and to the flat surface, approximately 1 3/8 in. from the end. Pull and extend the outer flexible vent pipe. Slide the outer flex pipe over the adaptor collar. Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1 3/8 in. from the end, and that it is free from damage or tears. Slide the gear into place and tighten it fully to secure the flexible vent to the adaptor outer collar approximately 3/4 in. from the end of the flex. Install three screws, 120° apart, through the flexible vent pipe and into the adaptor collar just below the gear clamp to provide additional security to the connection.
Figure 25: Flexible Vent Adapter
Flex Vent
Mil-Pac
black high
temperature
sealant
1 3/4 in. (44 mm)
overlap
Adaptor (SV4.5RF)
3. Route the flex vent—Ensure that the
flex vent is properly routed to provide the required clearance. Do not allow the flexible vent to bend in a radius tighter than 5 in. (127 mm) (Figure 26). Evenly space the internal flex vent spacers (roughly every 6 in.) and avoid kinking the inner pipe. Support the horizontal sections of flex with metal straps at 2 ft (0.61 m) intervals.
Figure 26: Flexible Vent
Flexible vent section
Securing screws (3 Places)
Gear clamps
1 3/4 in. (44 mm) overlap
Securing screws (3 Places)
4. Install the firestop/spacers at the
ceilings and walls—When Secure Flex penetrates a wall or ceiling, a firestop/ spacer is required. Use the SF4.5 VF firestop/spacer for ceilings and the SF4.5 HF firestop/spacer for walls. See the appropriate sections and figures shown throughout the venting section for their installation requirements.
5. Attach the flex vent to the termination—
Secure Flex components can be purchased separately and attached to bulk lengths of Secure Flex flexible tubing cut to size at the job site. Secure the flexible vent to the Secure Flex terminations in the same manner (Figure 25) as it was attached to the adaptor.
NOTE: Secure Flex vent must be attached
to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or
the Secure Vent adaptor for Secure Flex
components. The collars of Secure Flex
terminations and adaptors have a different
diameter than those used with the Secure
Vent pipe. Additionally, Secure Flex
components have an extended length center
tube for use in attaching the flexible vent.
22
5 in. (127 mm)
radius minimum
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Complete the Field Wiring
CAUTION
The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box (see wiring diagrams). Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70—latest edition (in Canada, the current CSA C22-1 Canadian Electrical Code).
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Figure 27: Wiring Diagram—Electronic Gas Valves
Schematic Representation Only
COLOR CODE:
B = BLACK
BB = BROWN W/BLACK STRIPE BG = BROWN W/GREEN STRIPE
BL = BLUE BR = BROWN G = GREEN GY = GRAY O = ORANGE R = RED W = WHITE Y = YELLOW
Models w/o pressure switch have these connectors plugged together
BR
Air Pressure Switch
Power Vent Only
Optional Circulation
Blower
B
Main Wire
Harness
Y
G
Y
Optional Variable Light
W
G
Battery Holder w/Switch
Battery Holder w/Switch
ON/Remote/Off
ON/ Remote /OFF
B
Battery Holder Wire Harness
GR
GR
BB
BG
O
R
BL
O
885 Valve
BL
G
W
R
B
R
B
WH
BR
BB
Split Flow
Reset Switch
“see instructions”
Pilot Tube
Control Module
IPI Pilot
B
Fuse
BG
Flame Sensor
Spark Electrode
B
Ground Y
B
G
W
Main Power Cord
f i r e - p a r t s . c o m
Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adéquatement une fois l’entretien terminé.
The gas valve is set in place and pre-wired at the factory. This appliance must be connected to a 120 Vac power source.
ATTENTION
Electronic Wiring
One of the following optional controls may be used:
ON/OFF Wall Switch,
Thermostat / Remote Control.
See the fireplace Care and Operation Instructions for details.
1. Route a 3-wire, 120 Vac, 60 Hz,
1 ph power supply to the left side of the appliance.
2. Remove the electrical inlet cover plate
from the side of the unit by removing the plate’s securing screws.
3. Remove the cover plate knockout.
Install a strain relief. Then, feed the power supply wire through the knockout opening.
4. Use wire nuts to connect the leads from
the appliance to the power supply leads.
5. Replace the cover plate.
6. Install the wall-mounted ON/OFF
control in a convenient location near the fireplace.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Page 24
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Hot Fireplace Will Cause Severe Burns
Never Allow Children to Touch Glass or other Fire-
place Parts
WARNING
Installing and initializing the Remote Control System
Required Items (not provided):
Standard Junction Box
Paper Clip or similar object (for remote
control system initialization)
The receiver for the Total Comfort Control™ Remote Control System connects directly to the gas valve, stepper motor, and fan control module with an umbilical cord wiring harness.
1. Install a junction box (not provided)
on the wall adjacent to the appliance, within reach of the remote system umbilical cord wiring harness. Position the terminal within the junction box in preparation for attachment to the remote wall switch.
2. When wall finish is complete, install the
wall switch in the previously installed junction box, and connect the terminal to the connector on the back of the wall switch.
3. Install the wall switch cover plate,
taking care to ensure the wall switch is properly indexed with the switch cover when aligning the components for attachments.
f i r e - p a r t s . c o m
After completing fireplace installation, initialize the remote control system before operating the fireplace.
1. Insert the three (3) provided AAA
batteries into the battery bay in the transmitter. Take care to correctly align polarity (+/–).
2. Insert the four (4) provided AA batteries
into the wall switch battery bay (behind the wall switch plate). Take care to correctly align polarity (+/–).
3. On the wall switch, place the three-
position slider switch in the REMOTE position (Figure 28).
4. On the wall switch front cover, insert
the end of a paper clip (or other similar object) into the hole marked PRG.
The Receiver will beep three (3)
NOTE:
times to indicate it is ready to synchronize with the transmitter.
5. On the transmitter, press the ON button.
The receiver will beep four (4) times to indicate acceptance of the transmitter’s command (and set the receiver to the transmitter’s specific code). The system is now initialized.
The remote control system provides remote operation of the following fireplace functions:
Primary burner ON/OFF
Auxiliary burner ON/OFF
Dimmable light function
6-Speed blower operation
Flame height and heat output
adjustment (six levels)
The receiver accepts commands via radio frequency from the transmitter and does not require line-of-sight operation.
The slider on the wall switch can be set to one of three positions:
ON (manual override)
OFF (manual override)
REMOTE (remote control)
See the fireplace Care and Operation Instructions for detailed instructions on using the remote control system to operate the fireplace.
Figure 28: Wall Switch
Three-position slider switch in REMOTE position
Figure 29: Transmitter (Remote Control)
UP/DOWN
ARROW
Key
MODE Key
WARNING
Fire hazard. Can cause severe injury or death. The receiver causes ignition of the appliance. The appliance can turn on suddenly. Keep away from the appliance burner when operating the remote system or activating manual bypass of the remote system.
CAUTION
Property damage hazard. Excessive heat can cause property damage. The appliance can stay lit for many hours. Turn off the appliance if it is not going to be attended for any length of time. Always place the Transmitter where children can not reach it.
On
Remote
Off
PRG
LCD Display
ON/OFF Key
THERMOSTAT Key
Refer to the Appliance Care & Operations
manual (P/N 506025-01) for detailed
remote system operation instructions.
24
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Flex Line Connector
Connect the Gas Supply
All codes require a shutoff valve mounted in the supply line. The shut-off valve should be oriented to face the fireplace front. Figure 31 illustrates two methods for connecting the gas supply. Use a sediment trap in the gas piping within the home to prevent moisture and debris in the line from damaging the valve.
The flex-line method is acceptable in the U.S.A. where local codes permit it. In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter. Canadian requirements vary depending on locality. Installation must be in compliance with local codes. These appliances are equipped with a gas flex line for use in connecting the unit to the gas line (Figure 31). The flex line is rated for both natural and propane gas. A manual shutoff valve is also provided with the flex line.
The gas control valve is located on the left of the firebox, in the side control compartment. The valve is accessible with the glass door removed (Figure 30).
Secure all joints tightly using appropriate tools and sealing compounds. Ensure propane resistant compounds are used in propane applications. Seal around the gas line to prevent cold air leakage.
f i r e - p a r t s . c o m
Route a hard pipe from the lefthand side to a spot directly below the access plate opening.
Locate the shut-off valve and gas flex line and pull the assembly forward, out of the compartment. Separate the shutoff valve from the gas flex line. Determine the length of pipe needed to route the gas line from the last fitting to a point directly below the access plate opening.
Using pipe-dressing materials appropriate for the gas type, securely affix the shutoff valve to this pipe at a convenient location outside of the appliance lower control compartment.
Refer to Figure 31 and insert the last length of gas pipe with the attached shutoff valve into the lower control compartment, and pass it through the gas line access hole on the left side of the appliance outer wrapper.
Using materials appropriate for the gas type, thread the last length of pipe into the end of the gas vent run and tighten it in place using a pipe wrench.
Figure 30: Gas Control Access
Access Plate
Gas Valve
Figure 31: Gas Line Connection Methods
1/2 in. x 3/8 in. Flare
Shut-Off Valve
Gas Stub
Test all connections (factory and field)
for gas leaks
Turn on gas supply and test for leaks using
a gas leak test solution.
NOTE: A soapy water solution is
effective for leak testing. However, it is
not recommended, because the soap
residue left on the pipes/fittings can result
in corrosion.
1. Light the appliance NOTE: Refer to the lighting instructions
label in the control compartment or in the Care and Operation Instructions.
2. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (OFF/PILOT/ON) to the OFF position. Either tighten or refasten the leaking connection, then retest as described above.
3. When the gas lines are tested and leak free, rinse off the leak testing solution.
3/8 in. NPT x 3/8 in.
Flare Fitting
3/8 in. Flex Tubing
Gas Valve
NOTE: Turn the last piece of gas pipe in the last fitting until the shut-off valve is positioned in a way that allows the shutoff valve handle to be accessed in the lower control compartment and easily operated through its full range of motion.
Bring the flex line to the shutoff valve by hand and align the flare fittings. Tighten the fittings by hand, and then use a wrench to tighten completely, 1/4 turn at a time.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Page 26
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Verify Correct Appliance Operation
With the gas line installed, perform an initial system inspection before closing the front of the unit. Follow the pilot lighting instructions provided in the Care and Operation Instructions manual.
NOTE: Lighting Instructions are also found on the literature tag tied to the gas piping next to the gas valve in the left side compartment. To access the tag, remove the surround trim assembly.
When lighting the appliance for the first time, the gas line will purge itself of air. This may take a few minutes. Once complete, the pilot and burner will light. Subsequent lightings of the appliance will not require air purging. Inspect the pilot flame (carefully remove the logs, if necessary).
To light the burner, turn the wall switch or (optional) remote control ON. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod (Figure 32).
Figure 32: Pilot Flame Appearance
Ignitor
Pilot Hood
f i r e - p a r t s . c o m
Sensor
Contemporary Fireplaces Only: Install the Contemporary Floor and Contemporary Glass Media
NOTE: Turn off all electricity to the appliance
before installing the contemporary floor and contemporary media.
1. Position the rear contemporary floor
to the back of the firebox, aligning the holes in the mounting tabs with the screw holes in the firebox floor (Figure 33). Secure with the two (2) included 5/16 in. screws.
NOTE: It may be easier to install the rear porcelain firebox liner (Step 3 in Porcelain Firebox Liners), before installing the rear contemporary floor.
Figure 33: Installing the Contemporary Floor
Screws
2. Position the front contemporary floor
to the front of the firebox, aligning the holes in the mounting tabs with the screw holes in the firebox floor (Figure 33). Secure with the two (2) included 5/16 in. screws.
Install the Firebox Liners
Ceramic Firebox Liners
1. Remove the four (4) firebox liner panels
from the packing materials.
2. Carefully position the rear panel, upper
edge first, in the firebox against the rear wall.
3. While holding the rear panel, carefully
position the left side panel in the firebox.
4. While holding the left panel, carefully
position the top panel, left edge up to a resting position on the upper edge of the left panel.
5. Raise the right end of the top panel, and
hold it in position while installing the right panel in the following step.
6. Carefully position the right side panel in
the firebox.
7. Lower the top panel onto the upper
edge of the right side panel. NOTE: Do not force the top panel into
place. Excessive force may cause breakage. If the top panel is correctly positioned, it will fit snugly in place.
8. Ensure the top panel is positioned over
both the left side and right side panels and that all panels are aligned with the sides and rear of the firebox.
Porcelain Firebox Liners
1. Remove the four (4) firebox liner panels from the packing materials.
2. Locate the rear, left, and right panels.
3. Position the rear panel, upper edge
first, in the firebox against the rear wall. Insert the lower mounting tabs into the mounting slots in the firebox base. Secure the panel to the rear wall with a 5/16 in. screw through the upper mounting tab.
4. Position the left panel in the firebox against the left wall and the rear panel.
5. Position the top panel, left edge up, so that it rests on the upper edge of the left panel.
6. Raise the right edge of the top panel, and hold it against the firebox ceiling when installing the right panel in the following step.
7. Position the right panel in the firebox against the right wall and the rear panel.
8. Lower the top panel onto the upper edge of the right panel, and slide it under the two tabs on the left and right panels.
9. Ensure the top panel is positioned over both the left side and right side panels and that all panels are aligned with the sides and rear of the firebox.
10. Use an ammonia-free glass cleaner and a soft, non-abrasive cloth to remove fingerprints and smudges from the porcelain firebox liner panels.
11. Install the contemporary glass media in a thin, even layer.
NOTE: Do not mound or overapply the glass media.
26
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 27
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Traditional Fireplaces Only: Install the Logs, Decorative Volcanic Stone, and Glowing Embers
NOTE: Turn off all electricity to the appliance
before installing volcanic stone, embers and logs.
NOTE: The log set and fire are artistically arranged to provide an asymmetrical fire. The fire does not burn in the left rear quarter of the log set.
Figure 34: Log Set
1
2
6
NOTE: Figure 34 is representative of all fireplace models. Logs 5 and 6 may vary in appearance from those shown above.
3
5
4
1. Align the two holes in the bottom of
Log 1 over the two tabs at the rear of the burner (Figure 35).
Figure 35: Placing Logs 1 and 2
1
2
2. Hold Log 1 in position while placing
Log 2 on the burner and resting it against the alignment notch in Log 1 (Figure 35).
3. Place Log 3 in position with the
base aligned in the burner surface (Figure 36).
Figure 36: Placing Log 3
6. Place Log 5 in position in the notches on the upper right portions of Logs 1 and 3 (Figure 38).
Figure 38: Placing Logs 5 and 6
5
6
7. Place Log 6 in position in the notches near the left ends of Logs 2 and 3 (Figure 38).
8. Install the volcanic stone in front of and on the sides of the log set. Cover all of the exposed metal floor.
Table 22: Log Set
f i r e - p a r t s . c o m
Log Number Description
1 Rear Log 2 Bottom Left Log 3 Bottom Right Log 4 Front Log
5 Top Right Log
6 Top Left Log
Catalog number for the entire set: 35 in. H8707 40 in. H8708 45 in. H8824
4. Insert the left end of Log 4 under Log 3
and position the right end of Log 4 in the notch on the top, right end of Log 3
3
(Figure 37).
Figure 37: Placing Log 4
4
5. Ensure all logs are properly positioned
on the surface of the burner and interlocked with each other (Figure 37).
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27
Page 28
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Install the Glass Door
WARNING
•Do not attempt to substitute the materials used on these doors, or replace cracked or broken glass.
•Handle this glass with extreme care! Glass is susceptible to damage—Do not scratch or handle roughly
1. Retrieve the glass door. Visually inspect
the gasket on the backside.
2. Locate the four (4) spring-loaded
latches; two above and two below the fireplace opening (Figure 39).
Figure 39: Glass Door
Latch
Latch
Adjust the Burner to Ensure Proper Flame Appearance
WARNING
•Air shutter adjustment should only be performed by a qualified professional service technician.
•Ensure front glass panel is in place and sealed during adjustment.
while reinstalling the glass door frame.
•The glass door of this appliance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
•Do not attempt to touch the front enclosure glass with your hands while the fireplace is in use.
f i r e - p a r t s . c o m
WARNING
Do not operate appliance with the glass front removed, cracked, or broken.
AVERTISSEMENT
Ne pas utiliser l’appareil si
3. Carefully grip the door at the top and
bottom, and align it with the fireplace opening. Lightly press against the door, to hold it in position.
4. Secure the two upper latches by pulling
each handle down and pressing in to hook it to the glass door.
5. Secure the two lower latches,
6. Install the surround trim assembly
by lowering it onto the appliance and pressing in to secure it (Figure 8).
To Remove the Glass Door
For more information on removing the glass door, see Page 9.
Latch
le panneau frontal en verre n’est pas en place, est craqué, ou brisé.
Only doors certified with the appliance shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
CAUTION
DO NOT abuse glass door by
• Soot will be produced if the air shutter is closed too much. Any damage due to sooting, resulting from improperly setting the air shutter, is not covered under the warranty.
•The air shutter rod and nearby appliance surfaces are hot. Exercise caution to avoid injury while adjusting flame appearance.
Flame Appearance and Sooting
The flame should be blue at the base, and yellow-orange in the body of the flame.
When the appliance is first lit, the entire flame may be blue and will gradually turn yellow-orange during the first 15 minutes of operation. If the flame remains blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces, and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air entering the air shutter opening. To achieve a warm yellow-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
CAUTION
striking or slamming shut.
NOTE: Visually inspect the gasket on the
backside of the glass door. The gasket surface must be clean, free of irregularities, and seated firmly. Ensure it is properly located. Make sure the bead is not rolled into the channel at the top of the door, but remains flat against the top of the glass.
NOTE: When installing the glass door, ensure the spacing on both sides is even.
28
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 29
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Air Shutter Adjustment Guidelines
If there is smoke or soot present, first check the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
The more offsets in the vent system, the larger the air shutter opening will need to be.
An appliance operated with the air shutter opened too far, may have flames that appear blue and transparent. These weak, blue and transparent flames are termed anemic.
Propane models may exhibit flames which candle or appear stringy. If this is present and persists, adjust the air shutter to a more closed position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
5. When satisfied that the burner flame
appearance is normal, reinstall the lower control compartment door then proceed to finish the installation.
Figure 40: Air Shutter Adjustment Rod
Air Shutter Adjustment Rod
Figure 41: Traditional Fireplaces
Flame Appearance
Finishing Requirements
1. Remove the surround trim assembly
(Figure 8)
2. Remove the finish trim gap fillers from
the side of the fireplace, and identify the left and right side pieces (Figure 43).
Figure 43: Finish Trim Gap Fillers
Right
Left
3. Loosen the nine (9) screws securing the
integrated finish trim and slide the trim out and away from the fireplace door (Figure 44).
Table 23: Air Shutter Adjustment Guidelines
Amount of
f i r e - p a r t s . c o m
Primary Air
If air shutter
is closed
too far
If air shutter
is open
too far
Flame Color
Flame will be orange
Flame will
be blue
1. Remove the top louver and the
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
Figure 42: Contemporary Fireplaces
Flame Appearance
Figure 44: Finish Trim Fasteners
Fireplace Top
Screws
surround trim assembly.
2. Locate the air shutter adjustment rod in the lower control compartment (Figure 40), and adjust it to the standard setting.
NOTE: Pull the rod out to close, and push the rod in to open the air shutter.
3. Light the appliance (follow lighting
NOTE: Integrated finish trim
shown in gray. Three (3) screws on right side not shown, but mirror left side.
procedure on lighting label in control compartment or the Care and Operations Manual).
4. Allow the burner to operate for at least 15 minutes while observing the flame continuously to ensure that the proper flame appearance has been achieved (Figure 41 and Figure 42). If the following conditions are present, adjust accordingly. If flame appears weak or sooty, adjust the air shutter, incrementally, to a more open position until the proper flame appearance is achieved. If flame remains blue, adjust
Table 24: Main Burner Shutter Opening— Factory Setting
Models Natural Gas Propane
NV35 NV40 3/16 in. (4.8 mm) 3/8 in. (9.5 mm) NV45 3/16 in. (4.8 mm) 3/8 in. (9.5 mm)
3/16 in. (4.8 mm) 7/16 in. (11.1 mm)
the air shutter, incrementally, to a more closed position until the proper flame appearance is achieved.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
29
Page 30
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
NOTE: The integrated finish trim is designed to be “flush face” with a minimum thickness of 1 in. (25 mm) in a non-combustible wall. The fireplace is supplied with 1/2 in. (13 mm) non-combustible wall material (Figure 45).
NOTE: A “flush face” installation will require a minimum of an additional 1/2 in. (13 mm) non-combustible (installer-supplied) wall material (Figure 46) to create the minimum 1 in. (25 mm) thick wall.
NOTE: The integrated finish trim is adjustable to accommodate a wall thickness of an additional 1 in. (25 mm)—for a 2 in. (51 mm) total
4. Slide the finish trim in until it is flush
with the finished wall surface. Tighten the nine (9) screws (Figure 44) securing the finish trim.
5. Install the surround trim assembly
by lowering it onto the appliance and pressing in to secure it (Figure 8).
6. Slide the left finish trim gap filler
into the left gap between the finish trim and the surround trim assembly (Figure 47).
NOTE: Ensure the finish trim gap filler slides into the spring clip, as shown.
Figure 47: Finished Installation
Spring Clip
thickness. NOTE: For wall thicknesses greater
than 2 in. (51 mm), remove the three integrated finish trim pieces (Figure 44).
Figure 45: Non-combustible Wall
15 1/2
(394)
Shaded area is non-combustible wall
7. Slide the right finish trim gap filler
into the right gap between the finish
f i r e - p a r t s . c o m
trim and the surround trim assembly (Figure 47).
Figure 46: Wall Finishing
Combustible finished wall
materials
The shaded area must remain clear of combustible materials
Combustible
materials
not allowed
below this
point on the
face of the
appliance
15 1/2 in.
394 mm
Spacer
Top of Appliance
1 in. (25 mm) Minimum
NOTE: Ensure the finish trim gap filler slides into the spring clip, as shown.
30
Top of Door Frame
NOTE: See Page 5 for Cold Climate Insulation and Page 6 for Clearances.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 31
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Attach the Safety-in-Operation Warnings
NOTE: It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing
consumers of safe operation of this appliance.
Attaching Safety-in­Operation Warnings
It is required that the set of safety instruction labels that have been furnished with the fireplace be affixed to the operation and control points of the fireplace. A safety instruction label must be affixed to the receiver wall switch plate where the fireplace is turned on and off (Figure A) and on the remote control handheld transmitter (Figure B). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall receiver that controls the
fireplace (verify the switch operates the fireplace by turning it on and off). Clean the wall receiver plate thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall receiver that controls the fireplace (Figure A). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. Locate the remote control transmitter and
clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure B). Choose the language primarily spoken in the home. If
f i r e - p a r t s . c o m
unknown, affix the English language label.
3. If you are unable to locate the labels, please
call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit Étiquettes de remplacement, n° cat. H8024 Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
NOTE: English is red text on clear label. French
and Spanish are white text on black label.
SAFETY LABEL DIAGRAMS DIAGRAMMES DES ÉTIQUETTES DE SÉCURITÉ DIAGRAMAS DE ETIQUETAS DE SEGURIDAD
Apposition des mises en garde relatives à la sécurité d’utilisation
Il est impératif que le jeu d’étiquettes de sécurité qui ont été fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque du récepteur mural contrôlant l’allumage du foyer (Figure A) et sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez le récepteur mural qui contrôle le
foyer (vérifiez que l’interrupteur contrôle le fonction -nement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque du récepteur mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque du récepteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Repérez la télécommande et nettoyez-la
soigneuse ment pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distribu teur Lennox Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
LENNOX HEARTH PRODUCTS 1-800-655-2008
Remarqué : Le texte anglais est rouge sur un
support transparent. Le texte français et espagnol est blanc sur un support noir.
Colocación de advertencias de seguridad en operación
Se requiere que el juego de etiquetas de instrucciones de seguridad que se incluyeron con la chimenea se coloque en los puntos de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared del receptor desde el cual se enciende y se apaga la chimenea (Figure A) y en el transmisor de control remoto (Figure B). Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el receptor de pared que
controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del receptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del receptor de pared que controla la chimenea (Figure A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Identifique el transmisor de control remoto
y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figure B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas,
sírvase llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas.
LENNOX HEARTH PRODUCTS 1-800-655-2008
Nota: La etiqueta en inglés es transparente con
texto rojo. Las etiquetas en francés y español son negras con texto blanco.
Figure A
On
Remote
Off
PRG
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure B
31
Page 32
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
S
e
a
l
a
n
t
INSTALLATION ACCESSORIES
Table 25: Listed Secure Vent™ Components
Catalog
Number
H1968 SV4.5HT-2
77L70 SV4.5L6 6 in. (152 mm) H1985 CTSO-33
77L71 SV4.5L12 12 in. (305 mm) H1987 CTSO-44
77L72 SV4.5L24 24 in. (610 mm) H1986 CTSO-46
77L73 SV4.5L36 36 in. (914 mm) 77L74 SV4.5L48 48 in. (1219 mm) 60L10 SF-18 18 ft (5.49 m)* compressed flex
77L75 SV4.5LA
Models Description
Horizontal square termination
with firestop / spacer (H2246)
and adaptor (74L61)
Telescopic length slip section
(2–7 1/2 in., rigid)
Catalog
Number
H1988 CTSA-33
Models Description
Table 26: Listed Secure Flex™ Components
98K03 SF-12 12 ft (3.66 m)* compressed flex
Chase top shroud kit, arch top,
3 x 3 ft
Chase top shroud kit, open top,
3 x 3 ft
Chase top shroud kit, open top,
4 x 4 ft
Chase top shroud kit, open top,
4 x 6 ft
77L76 SV4.5E45 45° Elbow H2248 SF4.5HF-10
77L77 SV4.5E90 90° Elbow H2249 SF4.5VF-10
77L78 SV4.5F Flat roof flashing * 77L79 SV4.5FA 77L80 SV4.5FB 7/12–12/12 Adjustable flashing * 77L88 SFKIT18S with 18 in. (457 mm)* compressed flex
77L81 SV4.5SC6 Storm collar (6/box) * 77L89 SFKIT24S with 24 in. (610 mm)* compressed flex
1/12–7/12 Adjustable flashing * 77L87 SFKIT12S with 12 in. (305 mm)* compressed flex
H1969 SF4.5HT-2 without flex
Firestop/spacer—horizontal, flex
(3-1-1 spacing), 10 pk
Firestop/Spacer—vertical, flex
(1-1-1 spacing), 10 pk
f i r e - p a r t s . c o m
H6183 SV4.5HF5 Firestop spacer, 5 in., rigid * 77L90 SFKIT36S with 36 in. (914 mm)* compressed flex H6184 SF4.5HF5 Firestop spacer, 5 in., flex * 77L91 SFKIT48S with 48 in. (1219 mm)* compressed flex
H2246 SV4.5HF-10
H2247 SV4.5VF-10
96K92 SV4.5SP Support plate *
17M52 SV4.5HGS-1 Termination guard, square (1 pack)
17M53 SV4.5HGS-12
87L02 SV4.5HGS
H5820 SV4.5HTSK
H5816 SV4.5-TWSK10
H3907 SV4.5ARSA
96K93 SV4.5SU Support strap
Firestop/spacer—Horizontal,
rigid (3-1-1 spacing), 10 Pack *
Firestop/spacer—vertical,
rigid (1-1-1 spacing), 10 Pack *
Termination guard, horizontal
square (12 pack)
Termination guard for horizontal
square termination (deluxe) (1 pack)
Termination guard for horizontal
square termination (1 pack)
Through wall shield kit (used to shield the direct-vent pipe from
blown insulation)
Attic insulation shield w/
adjustable height, 12–22 in.
Horizontal square
termination for flex
56L74 SFVT30
56L75 SFVT45
91L66 SFGC4-6
91L67 SFGC7-6
Vertical termination for flex,
flat–6/12
with flex adaptor, section of rigid
vent, roof support collar assembly,
roof flashing and storm collar
Vertical termination for flex
6/12–12/12
with flex adaptor, section of rigid
vent, roof support collar assembly,
roof flashing and storm collar
Gear clamp
4 1/2 in. (114 mm) for flex (6 pk)
Gear clamp
7 1/2 in. (191 mm) for flex (6 pk)
10K81 SFMP
99L02 SV4.5HRK14 Horizontal Riser Kit, 14 in.
99L03 SV4.5HRK36 Horizontal Riser Kit, 36 in.
H8914 SV4.5TK90HT2 H8915 SV4.5TK90SS
* Flashing comes packaged with a storm collar.
32
Mill-Pac, black, high temperature
sealant
Horizontal Termination Kit with
SV4.5 90° elbow
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H7748 H7748
36 in. Flex connector kit, 36 in. of flex with two adapters for mating
two rigid sections of vent together
Page 33
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Table 27: Replacement Parts
NV35 NV40 NV45
Description
1 Surround Trim Assembly H8734 1 H8713 1 H8735 1 2 Glass Door H9017 1 H9018 1 H9019 1 3 Literature Kit H9020 1 H9020 1 H9020 1 4 Remote Control Receiver Wall Switch Kit H8752 1 H8752 1 H8752 1 5 Touch-Up Paint 90L73 1 90L73 1 90L73 1 6 Blower Assembly 80L84 1 80L84 1 80L84 1 7 Volcanic Stone 80L42 1 80L42 1 80L42 1 8 Electronic Pilot Assembly, Natural Gas H7268 1 H7268 1 H7268 1 9
Flex Hose Connector, 24 in. H8997 1 H8997 1 H8997 1
10
Flex Hose Connector, 12 in. H8979 1 H8979 1 H8979 1
11
Flex Hose, 10 in. H8724 1 H8724 1 H8724 1 12 Remote Control Kit H8753 1 H8753 1 H8753 1 13 ON/OFF Jumper H8809 1 H8809 1 H8809 1 14 Gas Valve, SIT Proflame, Natural Gas H7270 1 H7270 1 H7270 1 15 Shield Standoff H8980 1 H8981 1 H8982 1 16 Firebox Access Door Gasket H8983 1 H8983 1 H8983 1 17 Contemporary Burner Assembly H8984 1 H8985 1 H8986 1 18 Traditional Burner Assembly H9038 1 H9039 1 H9040 1 19 Vent Restrictor Base H8987 1 H8987 1 H8987 1
f i r e - p a r t s . c o m
20 Vent Restrictor Wing H8988 1 H8988 1 H8988 1 21 Gas Train Assembly Gasket H8989 1 H8989 1 H8989 1 22 Door Latch Assembly, Top H9063 1 H9063 1 H9063 1 23 Door Latch Assembly, Bottom H9064 1 H9064 1 H9064 1 24 Firebox Lamp H8991 1 H8991 1 H8991 1 25 Firebox Lamp Gasket H8993 1 H8993 1 H8993 1 26
Ceramic Glass, 4 1/2 x2 in. H8992 1 H8992 1 H8992 1 27 Control Module, SIT H8656 1 H8656 1 H8656 1 28 Brass Orifice, Female #35 H8828 1 H8828 1 H8828 1 29 Brass Orifice, Female #40 H8933 1 H8933 1 H8933 1 30 Brass Orifice, Female #54 H8763 1 H8763 1 H8763 1 31 Brass Orifice, Female #64 H8765 1 H8765 1 H8765 1 32 Brass Orifice, Female #65 H8767 1 H8767 1 H8767 1 33 Brass Orifice, Female #66 H8875 1 H8875 1 H8875 1 34
Flare 90° Elbow, 3/8 in. NPT (M) X 3/8 in. H8994 1 H8994 1 H8994 1 35
Flare Straight Fitting, 3/8 in. NPT (M) X 3/8 in. H8995 1 H8995 1 H8995 1 36 Split Valve H8996 1 H8996 1 H8996 1 37
Assembly Harness, Wall to Proflame II, 12 ft H8813 1 H8813 1 H8813 1 38 Assembly Harness, Valve to Proflame II H8814 1 H8814 1 H8814 1 39 Assembly Harness, Power to Proflame II H8811 1 H8811 1 H8811 1 40 Assembly Harness, Blower Plug-In H8817 1 H8817 1 H8817 1 41 Assembly Harness, Lights to Proflame II H8810 1 H8810 1 H8810 1 42 Assembly Harness, Split Flow to Proflame II H8812 1 H8812 1 H8812 1 43
Assembly Harness, Light and Fan Connector, 5 in. H8815 1 H8815 1 H8815 1 44 Volcanic Stone 80L42 1 80L42 1 80L42 1
Catalog Number
Qty
Catalog Number
Qty
Catalog Number
Contact a Lennox Hearth Products dealer to obtain any of these parts. Never use substitute materials. Use of non-approved parts can result in poor performance and
Qty
safety hazards.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
33
Page 34
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
Figure 48: Replacement Parts
2
1
8
10
9
4
On
Remote
Off
PRG
6
17
5
14
f i r e - p a r t s . c o m
15
22 23
36
24
19
27
20
34
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 35
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion, or the production of carbon monoxide may result; causing property damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.The qualified service agency performing this installation assumes responsibility for
f i r e - p a r t s . c o m
this conversion.
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l’installation assume les responsabilités liées à la conversion.
AVERTISSEMENT
In Canada: The conversion shall be carried out in
accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CAN/CSA-B149.1 Installation code.
La conversion devra être effectuée conformément aux recommandations des autorités provinciales ayant juridiction et conformément aux exigences du code d’installation CAN/ CSA-B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Refer to the instructions provided with the conversion kit when performing any gas conversion.
Table 28: Traditional Fireplaces— Natural Gas to Propane Conversion Kits
Models Catalog Number
NV35IN H8754 NV40IN H8722 NV45IN H8757
Table 29: Traditional Fireplaces— Propane to Natural Gas Conversion Kits
Models Catalog Number
NV35IN H8755 NV40IN H8756 NV45IN H8758
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 30: Contemporary Fireplaces— Natural Gas to Propane Conversion Kits
Models Catalog Number
NVCD35IN H8759 NVCD40IN H8760 NVCD45IN H8761
35
Page 36
LENNOX HEARTH PRODUCTS • SIGNATURE® SERIES DIRECT-VENT GAS FIREPLACES • ENVY/ENVY CD 35/40/45 • INSTALLATION INSTRUCTIONS
f i r e - p a r t s . c o m
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used with permission.
Printed in U.S.A. © 2013 Lennox Hearth Products LLC
P/N 506023-17 Rev. A 08/2013
DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1508ElmHillPike,Suite108•Nashville,TN37210
Loading...