Lennox ELP090S4S, ELP120S4S Installation Instructions Manual

Page 1
THIS MANUAL MUST BE LEFT WITH THE
BUILDING OWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTALLATION INSTRUCTIONS
Elite Class™ ELP Series
7.5 and 10 Ton
HEAT PUMPS
7.5 AND 10 TONS 507744-01 11/2017
Table of Contents
Shipping and Packing List .............................................1
Outdoor Unit ..................................................................1
Unit Dimensions, Corner Weights and Centers of Gravity .2
Unit Plumbing Parts Arrangement ..................................3
Model Number Identication .......................................... 4
Unit Control Box Components Arrangement ..................4
Rigging the Unit for Lifting .............................................4
Installation Clearances ..................................................5
Line Set .........................................................................5
Electrical Connections ................................................... 5
Refrigerant Charge ........................................................ 9
System Operation ........................................................ 12
Defrost System ............................................................ 12
Defrost Control Board .................................................. 12
Maintenance ................................................................ 13
Shipping and Packing List
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Check the unit for shipping damage. If damaged or parts are missing, immediately contact the last shipping carrier.
1 - Assembled outdoor unit
1 - Installation instructions
Outdoor Unit
ELP Series heat pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC-410A refrig­erant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the EL Series Engi­neering Handbook.
This outdoor unit is designed for use in thermal expansion valve (TXV) systems only.
Page 1
Page 2
Unit Dimensions, Corner Weights and Centers of Gravity
Corner Weights
Centers of Gravity
Model No.
ELP090S4S 108 49 108 49 114 52 114 52
ELP120S4S 120 54 11 4 52 139 63 149 68
AA BB CC DD
lbs. kg lbs. kg lbs. kg lbs. kg
9−1/8 (232)
LIQUID LINE
SUCTION LINE
5
(127)
1−1/8
(29)
1−1/8
(29)
2−1/2
(54)
REFRIGERANT LINE
CONNECTIONS DETAIL
OPTIONAL COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
57−7/8
(1470)
DISCHARGE
AIR
OPTIONAL HAIL GUARD (Field Installed All Coil Sides) (Not used with Coil Guard)
Model No.
ELP090S4S 21.80 554 29.0 737
ELP120S4S 20.0 508 25.30 643
OUTDOOR
FAN GUARDS
CENTER OF
GRAVITY
FF
inch mm inch mm
INLET AIR
EE
DD
ELECTRICAL INLETS (Above Refrigerant Lines)
TOP VIEW
41−3/8
(1051)
DISCHARGE
AIR
EE FF
OPTIONAL HAIL GUARD
(Field Installed All Coil Sides)
(Not used with Coil Guard)
BBAA
INLET AIR
CC
OPTIONAL
INLET AIR
COIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Hail Guard)
12
(286)
2 (51)
COMPRESSOR
FORKLIFT SLOTS (Both Sides)
60−1/8
(1527)
FRONT VIEW
BASE
CONTROL BOX ACCESS
REFRIGERANT
LINE CONNECTIONS
SEE DETAIL
ELECTRICAL INLETS (Above Refrigerant Lines)
Page 2
LIFTING HOLES (For Rigging)
43−5/8
(1108)
SIDE VIEW
48−3/4 (1238)
45−1/4 (1149)
3−1/2
(89)
BASE
OPTIONAL
COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
Page 3
Unit Plumbing Parts Arrangement
ELP090S4S
ELP120S4S
HIGH PRESSURE SWITCH (S4)
PRESSURE SWITCH (S192)
LIQUID LINE BI-FLOW DRIER
PRESSURE SWITCH (S192)
REVERSING
HIGH PRESSURE SWITCH (S4)
VALV E
DEFROST SWITCH LOCATION (S6)
CHECK EXPANSION VALVE (CTXV)
LOSS OF CHARGE SWITCH (S24)
CTXV SENSING BULB
SUCTION LINE SERVICE VALV E
LIQUID LINE SERVICE VALV E
DEFROST SWITCH LOCATION (S6)
CTXV SENSING BULB
LIQUID LINE BI-FLOW DRIER
REVERSING
Page 3
VALV E
DEFROST SWITCH LOCATION (S6)
LOSS OF CHARGE SWITCH (S24)
CHECK EXPANSION VALVE (CTXV)
CTXV SENSING BULB
SUCTION LINE SERVICE VALV E
LIQUID LINE SERVICE VALV E
Page 4
Model Number Identication
ELPY1120 S N4 S
L
Brand/Family
Elite™ Product Line
P = Split System Heat Pump
Nominal Cooling Capacity -
Tons
090 = 7.5 Tons
120 = 10 To ns
Unit Control Box Components Arrangement
ELP090S4S AND ELP120S4S
Voltage
Y = 208/230V‐3 phase60hz G = 460V‐3 phase60hz J = 575V‐3 phase60hz M = 380/420V-3 phase-50hz
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Part Load Capability
N = Single Stage Compressor
Refrigerant Circuits
S = Single Circuit
Refrigerant Type
4 = R-410A
Cooling Efficiency
S = Standard Efficiency
TRANSFORMER
(T1)
CONTACTOR
(K1)
RUN CAPACITORS
(C1, C2)
Rigging the Unit for Lifting
Rig the unit for lifting by attaching four cables to the holes
in the base rail of the unit. See gure 1.
1 - Remove protective packaging before rigging the
unit for lifting.
2 - Connect the rigging to the holes in each corner of
the unit’s base.
DEFROST CONTRO BOARD
TERMINAL STRIP
(TB14)
GROUND LUG
3 - All panels must be in place for rigging.
4 - Place a eld-provided H-style frame just above the
top edge of the unit. The frame must be of adequate strength and length. (An H-style frame will prevent the top of the unit from being damaged.)
Page 4
Page 5
Lifting point should be directly above the center of gravity.
Caution - do not
walk on unit
.
Important - all panels
must be in place for
rigging.
Piping can be routed directly from the service valves or
eld supplied elbows can be added to divert the piping as
required.
Refer to table 1 for eld-fabricated refrigerant line sizes for
runs up to 50 linear feet (15 m).
TABLE 1. Refrigerant Line Sizes for Runs
Up to 50 Linear Feet
Unit Liquid Line Suction Line
ELP090 5/8” (16mm) 1-1/8” (29mm)
ELP120 5/8" (16mm) 1-1/8” (29mm)
Refrigerant Line Limitations
You may install the unit in applications that have line set lengths of up to 50 linear feet (15 m) with refrigerant line sizes as outlined in table 1 (excluding equivalent length of
ttings). Size refrigerant lines greater than 50 linear feet
(15m or greater) according to the Lennox Refrigerant Pip­ing Design and Fabrication Guidelines (Corp. 9351-L9) or latest version.
FIGURE 1. ELP090S4S and ELP120S4S
Installation Clearances
See Unit Dimensions on page 2 for sizing mounting slab,
platforms or supports. Refer to gures 4 through 6 for
mandatory installation clearance requirements.
NOTES:
• Clearance to one of the remaining two sides may be 12
in. (305 mm) and the nal side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained be- tween two units.
• 48 in. (1219 mm) clearance required on top of unit.
SEE
NOTES
SEE
NOTES
30”
Electrical Connections
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
In the United States, wiring must conform with current lo­cal codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
TRANSFORMER – 24VAC, 70VA – PROVIDED
NOTE – The addition of accessories to the system could exceed the 70VA power requirement of the factory-pro­vided transformer. Measure the system’s current and voltage after installation is complete to determine trans­former loading. If loading exceeds the factory-provided
transformer capacity, a larger eld-provided transformer
will need to be installed in the system.
36”
FIGURE 2. ELP090S4S and ELP120S4S
Installation Clearances
Line Set
Field refrigerant piping consists of liquid and suction lines connecting the condensing unit and the indoor unit. Liquid and suction service valves are located in a compartment at the corner of the unit below the control box.
CONTROL BOX ACCESS
Page 5
Page 6
GROUND.
CIRCUIT SIZING AND DISCONNECT SWITCH
1
W
2
can be affected by sunlight, drafts or vibrations.
3
4
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
Refer to the unit nameplate for minimum circuit ampacity amperage minimum, and maximum fuse or circuit breaker fusible (HACR per NEC). Install power wiring and properly sized disconnect switch.
NOTE CONDUCTORS. GROUND UNIT AT DISCONNE CT SWITCH OR TO AN EARTH
UNITS ARE APPROVED FOR USE ONLY WITH COPPER
TYPICAL HIGH VOLTAGE POWER SUPPLY CONNECTIONS
CONTROL BOX
USE THE LEFT CUTOUT TO ROUTE HIGH VOLTAGE WIRING TO THE K1 CONTACTOR ON THE ELP090S AND 120S MODELS.
K1 CONTACTOR
INSTALL THERMOSTAT
THERMOSTAT
Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it
5 FEET
(1.5M)
TYPICAL CONTROL WIRING
ELP HEAT
PUMP
R
C1
W1
W2
ELA AIR
HANDER
RO
C1
W1
W2
THERMOSTAT
A2
R
S1
S2
Y1
W
W2
RT2 REMOTE
SENSOR
GROUND LUG
NOTE - ANY EXCESS HIGH VOLTA GE FIELD WIRING SHOULD BE TRIMMED AND SECURED AWAY FROM ANY LO VOLTAGE FIELD WIRING.
LEFT CUTOUT
HIGH VOLTAGE WIRING
ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG.
C
C
C
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
Page 6
Page 7
TYPICAL UNIT CONTROL WIRE CONNECTIONS
5
K1 CONT
CONTROL BOX
ACTOR
ROUTE THROUGH
B
WIRE TIES
TIGHTEN
D
WIRE TIES
RIGHT CUTOUT
A
LOW VOLTAGE
C
CONTROL WIRING
HIGH VOLTAGE WIRING
ROUTE EARTH GROUND THROUGH LEFT CUTOUT AND CONNECT TO GROUND LUG.
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30M) 18 TEMPERATURE RATING
MORE THAN 100’ (30M) 16 35°C MINIMUM
A
RUN CONTROL WIRES THROUGH RIGHT CUTOUT.
B RUN CONTROL WIRES THROUGH WIRE TIES.
MAKE CONTROL WIRE CONNECTIONS USING FIELD
C
PROVIDED WIRE NUTS. SEE FIGURE 3 FOR CONNECTION REQUIREMENTS.
D
TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRING) GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.
Page 7
Page 8
7
K67-1
2
8
K8-2
1
HEAT 1
H1
HEAT 2
4
H2
COOL 1
C1
COOL 2
C2
S192
3
9
6
K48
J36
CMC1
K1 FAN
O OUT
S24
LO-PS
S9
5
2
1
DF
COM
B
Y1 OUT
A
HI PS
P45
TST
K2
24
K2
W1
K3
Y1
DF
PS
Y1ORC
2
C
L
1
R
O
7
K8-1
4
6
CB8
T1
208V
L34
400V
240 / 460 / 575V
3
1
4
1
3
B5
2
S9 IS USED ON ELP120 ONLY
2
FOR USE WITH COPPER CONDUCTORS ONLY
3
IF ANY WIRE IN THIS APPLIANCE IS REPLACED, IT MUST BE REPLACED WITH WIRE OF LIKE SIZE, RATING,INSULATION THICKNESS AND TERMINATION
WARNING-ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATH, UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES
DISCONNECT ALL POWER BEFORE SERVICING
B5
MOTOR-OUTDOOR FAN 2
CAPACITOR-OUTDOOR FAN 2
C2
CIRCUIT BREAKER-TRANS T1
CB8
K10,-1
1
3
K48
2
K67,-1
C2
L34
P45
PLUG-INPUT
SWITCH-DEFROST,COMPRESSOR 1 SWITCH-DEFROST,COMPRESSOR 2
S9
SWITCH-LOSS OF CHARGE COMP 1
S24
SWITCH, LIMIT HI PRESS CHANGEOVER COMP 1
TRANSFORMER-CONTROL
T1
DENOTES OPTIONAL COMPONENTS LINE VOLTAGE, FIELD INSTALLED
II
WIRING DIAGRAM
09/17
DUAL SPEED COMPRESSOR
ELP-090,120-G,J,M,Y WITH 2 SPD COMP PROTECTION
2011
SECTION A5
537912-02
REV. 0
FIGURE 3. Typical Wiring Diagram – ELP090S4S and ELP120S4S (G, J, Y, M Voltages)
Page 8
Page 9
Refrigerant Charge
OUTDOOR WIT TESTIN
ELP units have a factory holding charge of 2 pounds of HFC-410A. Additional refrigerant will need to be added during installation (table 2).
TABLE 2. Adding Refrigerant
Models
ELP090 /
ELA090
ELP120 /
ELA120
1
Total amount of charge necessary to accommodate 25
25 Feet1 (pounds
23.25 5/8 1-1/8 1.7
31.0 5/8 1-1/8 1.7
Liquid
Line Dia.
(inches)
feet of line set.
2
If line set length is greater than 25 feet, add this amount to each circuit. If line set is less than 25 feet, subtract this amount from each circuit. Refer to Lennox Refrigerant Piping Design and Fabrication Guidelines for more infor­mation.
NOTE - Refrigerant line sets longer than 200 feet (60 me- ters) are not recommended. For assistance contact Len­nox Application Department.
To charge the system, use either of the following proce­dures:
CHARGE PROCEDURE – NORMAL OPERATING PRESSURES
1 - Connect a manifold gauge set to the service valves:
A - Low pressure gauge to vapor service port.
B - High pressure gauge to liquid valve service port
2 - Operate system in cooling mode until pressures
and temperatures stabilize (5 minutes minimum).
3 - Use a thermometer to measure the outdoor
ambient temperature. The outdoor temperature will determine which charging procedure to use.
Outdoor Temp > 65ºF (18ºC)
1 - Apply the outdoor ambient temperature to table
4 or 5 to determine normal operating pressures. Compare the normal operating pressures to the pressures obtained from the connected gauges. If discharge pressure is high, remove refrigerant from the system. If discharge pressure is low, add refrigerant to the system.
A - Add or remove charge in increments.
B - Allow the system to stabilize at least 5 minutes each
time refrigerant is added or removed
2 - Minor variations in these pressures may be
expected due to differences in installations.
Signicant differences could mean that the system
is not properly charged or that a problem exists with some component in the system.
Vapor
Line
Dia.
(inches)
Ounces
Adjustment
per foot of
line set
2
3 - Switch to heating mode to conrm normal operating
pressures. Let the system stabilize at least 10 minutes, then compare the pressure obtained from the connected gauges to the normal operating pressures (heating mode) in table 5.
4 - Verify the charge, as described in the approach
method section.
Outdoor Temp < 65ºF (18ºC)
1 - When the outdoor ambient temperature is below
65F (18C) it may be necessary to restrict the air ow
through the outdoor coil to achieve liquid pressures in the 325-375 psig (2240-2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of the outdoor coil on all coil sides until the liquid pressure is in the 325-
375 psig range (gure 4).
2 - Charge the unit using the approach method in the
approach method section.
3 - Switch to heating mode and let the system stabilize
at least 10 minutes. Then conrm that the pressures
obtained from the connected gauges match the normal operating pressures (heating mode) in table 5.
4 - Minor variations in these pressures may be
expected due to differences in installations.
Signicant differences could mean that the system
is not properly charged or that a problem exists with some component in the system.
CARDBOARD OR PLASTIC SHEET
COIL SHOULD BE BLOCKED ONE SIDE AT A TIME
H CARDBOARD OR PLASTIC SHEET UNTIL PROPER
G PRESSURES ARE REACHED.
FIGURE 4. Blocking Outdoor Coil
CHARGE PROCEDURE – APPROACH METHOD
Use the following approach method along with the normal
operating pressures to conrm readings.
1 - Using the same thermometer, compare liquid
temperature at service valve to outdoor ambient temperature.
Approach Temperature = Liquid temperature minus
ambient temperature
Page 9
Page 10
2 - Approach temperature should be as indicated in
table 3 for each stage. An approach temperature greater than this value indicates an undercharge. An approach temperature less than this value indicates an overcharge.
A - Add or remove charge in increments.
B - Allow system to stabilize at least 5 minutes each
time refrigerant is added or removed.
TABLE 3. HFC-410A Approach Temperatures*
Models
ELP090S4S /
ELA090
ELP120S4S /
ELA120
*Approach temperature method valid at full load.
Approach
Temperature (ºF)
(+/-1)
7.0 3.9
6.0 3.3
3 - Do not use the approach method if system pressures
do not match pressures in table 4 except when the
outdoor ambient temperature is below 65ºF (18ºC).
The approach method is not valid for grossly over or undercharged systems.
TABLE 4. HFC-410A Normal Operating Pressures – Cooling Mode (Liquid ±10 and Suction ±5 psig)**
Temp*
65º F (18º C) 226 119 247 132
75º F (24º C) 261 125 291 136
85º F (29º C) 303 129 333 138
95º F (35º C) 349 133 370 140
105º F (41º C) 404 135 437 142
115º F (46º C) 462 137 495 144
125º F (52º C) 525 136 562 146
STD. CFM 2760 4000
*Temperature of air entering outdoor coil. Liquid and suction pressures measured via condenser service valve ports.
** Indoor conditions – 80° F Dry Bulb and 67° F Wet Bulb.
ELP090 / ELA090 ELP120 / ELA120
Liquid Suction Liquid Suction
Approach
Temperature (ºC)
(+/-.05)
TABLE 5. HFC-410A Normal Operating Pressures – Heating Mode (Liquid ±10 and Suction ±5 psig)**
Temp*
60º F (15º C) 364 121 335 115
50º F (10º C) 343 100 322 101
40º F (4º C) 324 83 308 86
30º F (-1º C) 311 72 294 72
20º F (-6º C) 297 57 280 58
10º F (-12º C) 280 44 266 44
STD. CFM 2760 4000
*Temperature of air entering outdoor coil. Liquid and suction pressures measured via condenser service valve ports. ** Indoor conditions – 70° F.
ELP090 / ELA090 ELP120 / ELA120
Liquid Suction Liquid Suction
Page 10
Page 11
TABLE 6. HFC-410A Temperature (ºF) – Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Page 11
Page 12
System Operation
SWITCH
Defrost Control Board
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates contin­uously.
HIGH PRESSURE SWITCHES (S4 AND S7)
These units are equipped with an auto-reset high pressure switch (single-pole, single-throw) which is located on the discharge line. The switch shuts off the compressor when discharge pressure rises above the factory setting. High
Pressure (auto reset) – trip at 640 psig; reset at 512 psig.
LOSS OF CHARGE SWITCH (S24)
These units are equipped with a loss-of-charge switch that is located in the liquid line. The switch is a SPST, auto-re­set switch that is normally closed. The switch opens at 40 psi and closes at 90 psi.
Defrost System
The defrost system includes a defrost thermostat and a defrost control.
DEFROST THERMOSTAT
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor on each coil. When the defrost thermostat senses 42°F (5.5°C) or cooler, its contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
DEFROST CONTROL
The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay, time
delay, diagnostic LEDs, and a terminal strip for eld wiring
connections. The control provides automatic switching from normal
heating operation to defrost mode and back. During com­pressor cycle (defrost thermostat is closed, calling for de­frost), the control accumulates compressor run times at 30, 60, or 90 minute eld adjustable intervals. If the de­frost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.
Each timing pin selection provides a different accumulat­ed compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated.
The defrost interval can be adjusted to 30 (T1), 60 (T2), or
90 (T3) minutes. The maximum defrost period is 14 min­utes and cannot be adjusted.
NOTE — Defrost control part number is listed near the P1 timing pins.
• Units with defrost control 100269-02: The factory de-
fault defrost interval is 60 minutes.
• Units with defrost control 100269-04 or higher: The fac-
tory default defrost interval is 90 minutes.
If the timing selector jumper is missing, the defrost control defaults to a 90-minute defrost interval.
DEFROST CONTROL TIMING PINS
FIELD SELECT
TIMING PINS
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S24
LOSS-OF-CHARGE
SWITCH
DEFROST
THERMOSTAT
S4
HIGH PRESSURE
LEDS
24V TERMINAL STRIP CONNECTIONS
SERVICE LIGHT CONNECTIONS
FIGURE 5. Outdoor Unit Defrost Control Board
A TEST option is provided for troubleshooting. The TEST mode may be started any time the unit is operating in the heating mode and the defrost thermostat is closed or jum­pered. If the jumper is in the TEST position at power-up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the con­trol will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 sec­onds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-sec­ond period has elapsed, the defrost will terminate and the test option will not function again until the jumper is re­moved and re-applied.
COMPRESSOR DELAY
The defrost board has a eld-selectable function to reduce
occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When the compressor de­lay jumper is removed, the compressor will be cycled off for 30 seconds going in and out of the defrost mode.
NOTE – The 30-second compressor feature is ignored when the TEST pins have been jumpered.
TIME DELAY
The timed-off delay is ve minutes long. The delay helps
protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
NOTE – The board must have a thermostat demand for the bypass function.
PRESSURE SWITCH CIRCUITS
The defrost control includes two pressure switch circuits. The factory-installed high pressure switch (S4) wires are
connected to the board’s HI PS terminals (gure 5). The
board also includes LO PS terminals to accommodate the factory installed loss-of-charge switch.
Page 12
Page 13
During a single thermostat cycle, the defrost control will lock out the unit after the fth time that the circuit is in­terrupted by any pressure switch that is wired to the con­trol board. In addition, the diagnostic LEDs will indicate
a pressure switch lockout after the fth occurrence of an
open pressure switch (table 7). The unit will remain locked out until power is broken then remade to the control or un­til the jumper is applied to the TEST pins for 0.5 seconds.
NOTE – The defrost control board ignores input from the loss-of-charge switch terminals during the TEST mode, during the defrost cycle, during the 90-second start-up period, and for the rst 90 seconds each time the revers­ing valve switches heat/cool modes. If the TEST pins are
jumpered and the 5-minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90-second start-up period.
SERVICE LIGHT CONNECTION
The defrost control board includes terminal connections for a service light which provides a signal that activates the room thermostat service light during periods of inef­cient operation.
IMPORTANT
After testing has been completed, properly reposition test jumper across desired timing pins.
DIAGNOSTIC LEDS
The defrost board uses two LEDs for diagnostics. The LEDs ash a specic sequence according to the diagno­sis (table 7).
TABLE 7. Defrost Control Board Diagnostic LEDs
DS2 Green DS1 Red Condition
OFF OFF Power problem
Simultaneous Slow Flash Normal operation
Alternating Slow Flash 5-min. anti-short cycle delay
Fault and Lockout Codes
OFF Slow Flash Loss-of-Charge Fault
OFF ON Loss-of-Charge Lockout
Slow Flash OFF High Pressure Fault
ON OFF High Pressure Lockout
Maintenance
At the beginning of each cooling season, the system should be checked as follows:
OUTDOOR UNIT
1 - Clean and inspect the condenser coil. You can ush
the coil with a water hose.
2 - The outdoor fan motor is prelubricated and sealed.
No further lubrication is necessary.
3 - Visually inspect connecting lines and coils for
evidence of oil leaks.
4 - Check wiring for loose connections.
5 - Check for correct voltage at the unit while the unit is
operating and while it is off.
6 - Check amp-draw of the outdoor fan motor.
Unit nameplate _________ Actual ____________
7 - Check amp-draw of the compressor.
Unit nameplate _________ Actual ____________
NOTE — If the owner complains of insufcient cooling,
gauge the unit and check the refrigerant charge. Refer to section on refrigerant charging in this instruction.
INDOOR COIL
1 - If necessary, clean the coil.
2 - Check connecting lines and coils for evidence of oil
leaks.
3 - If necessary, check the condensate line and clean it.
INDOOR UNIT
1 - Clean or change lters.
2 - Adjust the blower speed for cooling. Measure the
pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3 - On belt drive blowers, check the belt for wear and
proper tension.
4 - Check all wiring for loose connections.
5 - Check for correct voltage at the unit (blower
operating).
6 - Check amp-draw on blower motor.
Unit nameplate _________ Actual ____________
Page 13
Page 14
Start-Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Te mp.
Vapor Pressure;
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? Cooling Correct?
Calibrated?
THERMOSTAT
Properly Set?
Level?
Page 14
Loading...