Lennox Elite XP13 Units, Elite XP13-018, Elite XP13-024, Elite XP13-030, Elite XP13-036 Installation Instructions Manual

...
Page 1
INSTALLATION
2009 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
INSTRUCTIONS
Elite® Series XP13 Units
HEAT PUMPS
506270−01 05/09 Supersedes 01/09
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
XP13 Heat Pumps 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . .
Removing Existing Outdoor Unit 6. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 6. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 7. . . . . . . . . . . . . . . . .
New or Replacement Line Set 9. . . . . . . . . . . . . . . . . . .
Brazing Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 11. . . . . . . . . . .
Flushing the System 12. . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing New Indoor Unit Metering Device 13. . . . . . . .
Testing for Leaks 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 15. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 16. . . . . . . . . . .
Electrical Connections 17. . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Charging Procedures 18. . . . . . . . . . . . . . .
System Operation 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Information 23. . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 26. . . . . . . . . . . . .
Shipping and Packing List
Litho U.S.A.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HFCs, and HCFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox’ Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
05/09 506270−01
*2P0509* *P506270-01*
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1  Assembled XP13 outdoor unit
XP13 Heat Pumps
The XP13 Heat Pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox XP13 Engineering Handbook.
This outdoor unit is designed for use in systems that use check thermal expansion valve (CTXV) refrigerant metering devices.
Page 1
Page 2
Unit Dimensions − Inches (mm) and Parts Arrangement
RUN
CAPACITOR
DEFROST
BOARD
CONTACTOR
REVERSING
VALV E
FILTER DRIER/
LIQUID LINE
CONNECTIONS
XP13 PARTS ARRANGEMENT
TOP VIEW
DISCHARGE AIR
SUCTION LINE CONNECTION
LIQUID LINE CONNECTION
C
LIQUID LINE CONNECTION
ELECTRICAL INLETS
VAPOR LINE CONNECTION
OUTDOOR FAN
COMPRESSOR
HIGH PRESSURE SWITCH
VAPOR LINE
VAPOR VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS
B
A
2 (51)
08)
4−3/4 (121)
9−1/2 (241)
8−1/4 (210)
UNIT SUPPORT FEET
13−7/8
(352)
7−3/4 (197)
3−1/4
(83)
1 (25)
SIDE VIEW
27−1/8
(689)
XP13 BASE WITH ELONGATED LEGS
4−1/4(1
SIDE VIEW
UNIT SUPPORT
FEET
8−1/2 (216)
8−3/4 (222)
5−1/2 (140)
13−1/2
(343)
XP13−018, 024, 030 AND 036 BASE SECTION
XP13 A B C
−018
−024
−030
−036
−042
−048
−060
31 (787) 27 (686) 28 (711)
31 (787) 27 (686) 28 (711)
31 (787) 27 (686) 28 (711)
35 (889) 27 (686) 28 (711)
35 (889) 30−1/2 (775) 35 (889)
35 (889) 30−1/2 (775) 35 (889)
45 (1143) 30−1/2 (775) 35 (889)
20−5/8
K
(524)
4−1/2
J
(114)
3−5/8
(92)
506270−01 05/09
Page 2
Page 3
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
General Information
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings. See figure 2 for a typical manifold gauge connection setup.
Manifold gauge sets used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem.
Figure 1. Cap Tightening Distances
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrenched to turn an additional 1/12 turn clockwise as illustrated in figure 1.
Page 3
XP13 SERIES
Page 4
CHECK
EXPANSION VALVE
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO HFC−410 A DRUM
HIGH
LIQUID LINE VALV E
BI−FLOW FILTER / DRIER
MUFFLER
LIQUID
SERVICE
PORT
DISTRIBUTOR
OUTDOOR
COIL
COMPRESSOR
HEAT PUMP
REVERSING VALVE
VAPOR
SERVICE
PORT
VAPOR LINE VALV E
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW.
INDOOR UNIT
Figure 2. Typical Manifold Gauge Connection Setup
SERVICE PORT
CORE
VALVE STEM
FRONT-SEATED
TO INDOOR
UNIT
TO OUTDOOR UNIT
SERVICE PORT
CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
STEM CAP
CLOSED TO BOTH INDOOR
AND OUTDOOR UNITS
Figure 3. Angle−Type Service Valve
(Font−Seated Closed)
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
CHECK EXPANSION VALVE
INDOOR
COIL
NOTE− To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap.
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO INDOOR UNIT
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 4. Angle−Type Service Valve
(Back−Seated Opened)
506270−01 05/09
Page 4
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
Figure 5. Ball−Type Service Valve
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
Page 5
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, roate stem counterclockwise 90°. To close rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 1.
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
NOTE − Use recovery machine instructions for specific setup requirements.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and plan on using new HCFC−22 refrigerant to flush the system.
IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor
OFF.
Recovering Refrigerant from Existing System
Remove existing HCFC−22 refrigerant using one of the following procedures:
METHOD 1:
If the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
NOTE − Use recovery machine instructions for specific setup requirements.
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recovery machine on how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
RECOVERY MACHINE
MANIFOLD GAUGES
Compressor can stop pumping due to tripped internal
pressure relief valve.
Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals).
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump as much of the existing HCFC−22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.
CLEAN RECOVERY CYLINDER
Figure 6. Typical Refrigerant Recovery
(Method 1)
OUTDOOR UNIT
NOTE − It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Page 5
XP13 SERIES
Page 6
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves. Disconnect electrical service at the disconnect switch. Remove old outdoor unit.
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 7 for mandatory installation clearance requirements.
property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 8.
INSTALL UNIT AWAY
FROM WINDOWS
*
*
* SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
*
CONTROL PANEL ACCESS LOCATION
*
Figure 7. Installation Clearances
NOTES:
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36
in. (914 mm)
.
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
48 in. (1219 mm) clearance required on top of unit. A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
TWO 90° ELBOWS INSTALLED
IN LINE SET WILL REDUCE
LINE SET VIBRATION.
Figure 8. Outside Unit Placement
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 9.
NOTE − If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
7.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
Figure 9. Slab Mounting at Ground Level
506270−01 05/09
Page 6
Page 7
ELEVATING THE UNIT (SMALL−BASE UNITS)
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be done by cutting four equal true−cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as illustrated in figure 10.
BASE
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
BASE
2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER
LEG DETAIL
LEG DETAIL
4" (101.6MM) SCH 40 PIPING
Figure 10. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the pre−installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1" (25.4mm) square strips should be adequate to hold the extender in place.
ELEVATING THE UNIT (LARGER−BASE UNITS)
Unlike the small−base units which use round support feet, the larger−base units are outfitted with elongated support feet as illustrated in figure 11 which uses a similar method for elevating the unit.
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be achieved by using a 2" SCH 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
Figure 11. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
ROOF MOUNTING
Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood, steel supports, or roofed in equipment platform is recommended.
Removing and Installing Panels
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
REMOVING PANELS
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 12.
NOTE − Hold the panel firmly throughout this procedure
2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 12, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 12, detail A.
Page 7
XP13 SERIES
Page 8
INSTALLING PANEL
Install the louvered panels as follows:
1. Position the panel almost parallel with the unit as illustrated in figure 13, detail D with the screw side as close to the unit as possible.
2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 12, details A and C, then upward into the top slot of the hinge corner post.
3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
5. When panel is correctly positioned and aligned, insert the screws and tighten.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW
LIP
HOLES
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Figure 13. Removing/Installing Louvered Panels
(Detail D)
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the brackets as illustrated in figure 14 using conventional
practices; replace the panels after installation is complete.
DETAIL A
DETAIL B
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL
Detail C
Figure 12. Removing/Installing Louvered Panels
(Details A, B and C)
Slab Side Mounting
#10 1/2" LONG SELF−
DRILLING SHEET
METAL SCREWS
STABILIZING
BRACKET (18 GAUGE
METAL − 2" WIDTH;
HEIGHT AS REQ’D)
#10 1−1/4" LONG
HEX HD SCREW
AND FLATWASHER
CONCRETE SLAB − USE PLASTIC PLASTIC ANCHOR (HOLE DRILL 1/4")PLASTIC SLAB − NO PLASTIC ANCHOR (HOLE DRILL 1/8")
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL − 2" WIDTH; HEIGHT AS REQ’D); BEND TO FORM RIGHT ANGLE
FOR EXTRA
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
STABILITY
MINIMUM 1 PER SIDE
Figure 14. Installing Stabilizer Brackets
COIL
BASE PAN
CORNER POST
506270−01 05/09
Page 8
Page 9
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set are not being installed then proceed to Brazing Connections on page 10.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when placing and installing a high−efficiency air conditioner.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non−flare) series line set, or use field−fabricated refrigerant lines as listed in table 2.
Table 2. Refrigerant Line Set
Field Connections Recommended Line Set
Model
−018
−024
−030
−036
−042
−048
−060
NOTE − When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (XP13) and size of unit (e.g. −060).
Liquid Line
3/8". (10 mm)
3/8". (10 mm)
3/8". (10 mm)
Suction Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8". (29 mm)
Liquid Line
3/8" (10 mm)
3/8" (10 mm)
3/8" (10 mm)
Suction Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8" (29 mm)
L15 Line Set
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the XP13 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the XP13 unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
INSTALLING LINE SET Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set isolation:
Installation of line set on horizontal runs is
illustrated in figure 15.
Installation of line set on vertical runs is illustrated in
figure 16.
Installation of a transition from horizontal to
vertical is illustrated in figure 17.
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR WIRE TIE
8 FEET
FLOOR JOIST OR
ROOF RAFTER
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET
METAL
SLEEVE
INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.
8 FEET
Figure 15. Refrigerant Line Set: Installing
Horizontal Runs
WIRE TIE (AROUND SUCTION LINE ONLY)
TAPE OR
WIRE TIE
Page 9
XP13 SERIES
Page 10
IMPORTANT - REFRIGERANT LINES MUST NOT CONTACT WALL.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
NOTE − SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
SUCTION LINE
WIRE TIE
INSIDE WALL
STRAP
SLEEVE
WIRE TIE
WIRE TIE
LIQUID LINE
WOOD BLOCK
STRAP
Brazing Connections
Use the following procedure to braze the line set to the new air conditioner unit. Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
SLEEVE
SUCTION LINE
WRAPPED WITH
ARMAFLEX
LIQUID LINE
OUTSIDE
PVC
PIPE
WALL
FIBERGLASS
INSULATION
CAULK
IMPORTANT! REFRIGERANT LINES MUST NOT CONTACT STRUCTURE.
Figure 16. Refrigerant Line Set: Installing Vertical
Runs (New Construction Shown)
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER−TYPE HANGER
WALL STUD
METAL SLEEVE SUCTION LINE − WRAPPED IN
MUFFLER-TYPE HANGER
AUTOMOTIVE
STRAP LIQUID LINE TO SUCTION LINE
LIQUID LINE
ARMAFLEX
Figure 17. Refrigerant Line Set: Transition from
Vertical to Horizontal
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint. Also, shield the light maroon R−410A sticker.
WARNING
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve.
506270−01 05/09
Page 10
Page 11
1
2
3
CUT AND DEBUR
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS after they
have coolED.
INDOOR UNIT
6
BRAZE LINE SET
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
Figure 18. Brazing Connections
NOTE − The RFCIV or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing.
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow. Repeat procedure starting at paragraph 4 for brazing the suction line to the suction service valve.
7. After all connections have been brazed, disconnect manifold gauge set the from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedure. Reinstall service caps if desired to close off refrigerant ports.
Removing Indoor Unit Metering Device
Remove the existing HCFC−22 refrigerant flow control orifice or thermal expansion valve from the indoor coil. The existing indoor unit HCFC−22 metering device is not approved for use with HFC−410A refrigerant and may prevent proper flushing.
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes:
10  Brass nuts for liquid line assemblies
ATTACH
GAUGES
SERVICE
5
VALVE
SERVICE
VALVE
outdoor
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
20  Teflon rings 10  Liquid line orifice housings 10  Liquid line assemblies
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20)
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
Figure 19. 69J46 Kit Components
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
4. Remove and discard fixed orifice, valve stem assembly if present and Teflon washer as illustrated in figure 20.
5. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
BRASS NUTS (10)
LIQUID LINE
ASSEMBLY
PISTON RETAINER
STRAINER
COPPER TUBE
Page 11
XP13 SERIES
Page 12
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING
FIXED ORIFICE
REMOVE AND DISCARD VALVE STEM ASSEMBLY (IF PRESENT)
BRASS NUT
5. Disconnect the liquid line from the TXV at the liquid line assembly.
6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
7. Remove and discard TXV and the two Teflon rings as illustrated in figure 21.
8. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
Flushing the System
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
VALVE STEM
VALVE STEM CAP
(Uncased Coil Shown)
Figure 20. Typical Fixed Orifice Removal
TYPICAL TXV REMOVAL PROCEDURE
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING
(Uncased Coil Shown)
LIQUID LINE
ORIFICE HOUSING
EQUALIZER LINE
SENSING BULB
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION
LINE
TEFLON
RING
SENSING
LINE
LIQUID
LINE
Figure 21. Typical TXV Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in figure 21.
IMPORTANT
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
CAUTION
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
If the original system used:
HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
HFC−410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
506270−01 05/09
Page 12
Page 13
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR unit
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NOTE − THE INVERTED HCFC−22 CYLINDER MUST CONTAIN AT LEAST THE SAME AMOUNT OF REFRIGERANT AS WAS RECOVERED FROM THE EXISTING SYSTEM.
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
GAUGE
MANIFOLD
LOW
PRESSURE
TANK RETURN
INLET
DISCHARGE
HIGH
PRESSURE
CLOSED
Figure 22. Typical Flushing Connection
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
Two clean HCFC−22 recovery bottles, Oilless recovery machine with pump-down feature, Two gauge sets (one for HCFC−22; one for
HFC−410A).
FLUSHING PROCEDURE
1. Connect the following:
HCFC−22 cylinder with clean refrigerant to the
suction service valve,
HCFC−22 gauge set to the liquid line valve, Recovery machine with an empty recovery tank to
the gauge set.
2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
3. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC−22 suction is recovered. Allow the recovery machine to pull a vacuum on the system.
5. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
Installing New Indoor Metering Device
XP13 units use CTXV for metering refrigerant only. This section provides instructions on installing CTXV refrigerant metering device.
Page 13
9
10
8
11
1/8 TURN
10
8
11
12
7
6
12
1
2
3
9
4
7
5
6
1/2 TURN
1
2
3
4
5
Figure 23. Tightening Distance
TYPICAL CTXV INSTALLATION PROCEDURE
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE FIGURE 26
FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE FIGURE 25 FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
CTXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
SUCTION LINE
TEFLON
RING
SENSING
LINE
LIQUID
LINE
Figure 24. Typical TXV Installation
The CTXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the CTXV in a manner that will provide access for field servicing of the CTXV. Refer to Figure 24 for reference during installation of CTXV unit.
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s distributor assembly.
2. Install one of the provided Teflon rings around the stubbed end of the CTXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
3. Attach the stubbed end of the CTXV to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft−lb.
4. Place the remaining Teflon washer around the other end of the CTXV. Lightly lubricate connector threads
XP13 SERIES
Page 14
and expose surface of the Teflon ring with refrigerant oil.
5. Attach the liquid line assembly to the CTXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft−lb.
6. Attach the suction line sensing bulb in the proper orientation as illustrated in figure 25 using the clamp and screws provided.
NOTE − Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
SUCTION LINE
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated in figure 23.
NOTE − To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
See the XP13 Engineering Handbook for approved CTXV kit match−ups and application information.
The reference CTXV kits include: 1  CTXV 2  Teflon rings 1  1 1/4" wide copper mounting strap for sensing bulb 2  #10 hex head bolts and nuts for securing sensing bulb
BULB
SUCTION LINE
BULB
NOTE − NEVER MOUNT ON BOTTOM OF LINE.
12
12
BULB
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
Figure 25. TXV Sensing Bulb Installation
7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 26.
IMPORTANT
When removing the flare nut, ensure that the copper flare seal bonnet is removed.
FLARE SEAL
CAP
OR
FLARE NUT
COPPER
FLARE SEAL
BONNET
CTXV (1)
HEX HEAD BOLTS
AND NUTS (2)
TEFLON RINGS (2)
COPPER
MOUNTING
STRAP (1)
Figure 27. CTXV Kit Components
Testing for Leaks
After the line set has been connected to the indoor unit and air conditioner, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
MALE BRASS EQUALIZER
Figure 26. Copper Flare Seal Bonnet Removal
506270−01 05/09
LINE FITTING
SUCTION LINE
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Page 14
Page 15
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
1. Connect an HFC−410A manifold gauge set high pressure hose to the suction valve service port.
(Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.)
2. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (suction only).
3. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
6. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
7. After leak testing disconnect gauges from service ports.
Evacuating the System
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
NOTE − Remove cores from service valves if not already done.
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to suction line service valve high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE − During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
Page 15
XP13 SERIES
Page 16
Figure 28. Typical Wiring Diagram
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
10. Perform the following:
A Close manifold gauge valves.
B Shut off HFC−410A cylinder.
C Reinstall service valve cores by removing
manifold hose from service valves. Quickly install cores with core tool while maintaining a positive system pressure.
D Replace the stem caps and secure finger tight,
then tighten an additional one−sixth (1/6) of a turn as illustrated in figure 1.
Servicing Units Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC−410A refrigerant as listed on unit nameplate into the system.
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
506270−01 05/09
Page 16
Page 17
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
1. Install line voltage power supply to unit from a properly sized unit disconnect switch.
2. Ground the unit at the unit disconnect switch or to earth ground.
NOTE − To facilitate conduit, a hole is provided in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJU­RY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE − For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over­current protection size.
Figure 29. Typical Field Wiring
THERMOSTAT INDOOR UNIT OUTDOOR UNIT
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
NOTE − Units are approved for use only with copper conductors. Refer to figure 29 for high voltage field wiring diagram. (A complete unit wiring diagram is located inside the unit control box cover.)
3. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figures 30 and
31. ( 24V, Class II circuit connections are made in the
low voltage junction box.)
color−coded, temperature rating 35ºC minimum
W1
W2
W3
R
C
G
24V POWER
COMMON
1ST-STAGE
AUXILIARY
HEAT
R
C
W1
O
Y1
R
24V POWER
C
COMMON
W1
1ST-STAGE
AUXILIARY
HEAT
G
INDOOR BLOWER
O
REVERSING VALVE
Y1
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
Figure 30. Outdoor and Blower Unit Thermostat
Designations
THERMOSTAT
R
24V POWER 24V POWER
C
COMMON
E
EMERGENCY
HEAT
W1
1ST-STAGE
AUXILIARY
HEAT
G
INDOOR BLOWER
O
REVERSING VALVE
Y1
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
INDOOR UNIT OUTDOOR UNIT
W2
W3
W1
R
C
G
COMMON
1ST-STAGE
AUXILIARY
HEAT
R
C
W1
O
Y1
EMERGENCY
HEAT RELAY
OUTDOOR THERMOSTAT
NOTE − For proper voltages, select thermostat wire gauge per the following chart:
Figure 31. Outdoor and Blower Unit Thermostat
Designations (with emergency heat)
Page 17
XP13 SERIES
Page 18
Start−Up and Charging Procedures
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.
4. Replace the stem caps and tighten to the value listed in table 1.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the procedures listed under Testing and Charging System.
TESTING AND CHARGING SYSTEM
This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
C
53º
DRY
BULB
All temperatures are expressed in ºF
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
Drop
19º
air flowair flow
INDOOR COIL
B
B
64º
WET
BULB
A
72º
DRY
BULB
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service ports as illustrated in figure 2.
low pressure gauge to vapor service porthigh pressure gauge to liquid service port
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (DT) process using the illustration in figure 32.
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
Measuring voltage supplied to the unit,
Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
CALCULATING CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount
specified
on
nameplate
1. Determine the desired DTMeasure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between the measured T adjustment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº T
Drop
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to increase/
decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
Amps x Volts x 3.41
1.08 x Temperature rise (F)
Adjust amount. for variation in line set
length listed on table
in figure 33.
Additional charge
specified per
indoor unit
match−up listed in
table 3.
+ + =
) = A minus C.
Drop
and the desired DT (T
Drop
DT = ºF ACTION
DT) is within +3º, no
Drop
Total
charge
Figure 32. Checking Indoor Coil Airflow Guide
506270−01 05/09
Page 18
Page 19
WEIGH IN
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
SUBCOOLING
SATº LIQº – SCº =
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 33. Using Weigh In Method
1 Check the airflow as illustrated in figure 32 to be sure the indoor airflow is as required. (Make any air flow
adjustments before continuing with the following procedure.)
2 Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to
check charge.
3 Connect gauge set.
4 Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 4,
(The reference table is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.)
USE COOLING
MODE
60ºF (15º)
USE HEATING
MODE
5 Set thermostat for heat/cool demand, depending on mode being used:
Using cooling modeWhen the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values in table below are based on 70 to 80°F (21−27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC). When pressures have stabilized, continue with step 6.
Using heating modeWhen the outdoor ambient temperature is below 60°F (15°C). Target subcooling
values in table below are based on 65−75°F (18−24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC). When pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQº space.
7 Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart
listed in table 5 and record it in the SATº space.
8 Subtract LIQº temp. from SATº temp. to determine subcooling; record it in SCº space.
9 Compare SCº results with table below, being sure to note any additional charge for line set and/or match−up.
10 If subcooling value is greater than shown in table 3 for the applicable unit, remove refrigerant; if less than
shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge.
12 Disconnect gauge set and re−install both the liquid and suction service valve caps.
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 4, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
Figure 34. Using Subcooling Method
Page 19
XP13 SERIES
Page 20
Table 3. Unit Indoor Matchups for Subcooling
g
Subcooling
g
Subcooling
018
Target
INDOOR MATCHUPS
CBX26UH–018 23 5 0 1 CBX26UH–024 23 5 0 1 CBX27UH–018/024 15 8 0 2 CBX32MV–018/024 30 3 0 0 CBX32MV–024/030 15 8 0 2 CBX40UHV−024 30 3 0 0 CBX40UHV−030 15 8 0 2
Subcoolin
Heat Cool
5ºF)(+1ºF)
(+
*Add charge
lb oz
024
CBX26UH–024 23 5 0 1 CBX26UH–030 23 3 1 3 CBX27UH–018/024 12 3 0 11 CBX27UH–030 12 3 1 4 CBX32M–030 12 3 0 11 CBX32M–036 12 3 1 4 CBX32MV–018/024 12 6 0 5 CBX32MV–024/030 12 3 0 11 CBX40UHV−024 12 6 0 5 CBX40UHV−030 12 3 0 11 CH33–25A 16 6 0 7 CH33–31A 12 3 0 7 CH33–31B 12 3 0 15 CH33–36A 16 6 0 7 CH33–36B 16 7 0 15 CH33–36C 12 5 0 0 CR33–30, –36 12 4 0 3 CX34–25 12 6 0 5 CX34–31 12 3 0 11 CX34–36 16 7 0 11
030
CBX26UH–030, –036 22 4 0 11 CBX27UH−030 15 4 0 11 CBX27UH−036 15 4 0 11 CBX32M–030, –036 15 4 0 11 CBX32M–042 15 4 0 11 CBX32MV–024/030, –036 15 4 0 11 CBX40UHV−024, −030, −036 15 4 0 11 CH33–25A 20 3 0 8 CH33–31A 15 4 0 11 CH33–31B 20 4 0 11 CH33–36A 20 3 0 8 CH33–36C 15 3 0 11 CH33–42B 20 4 0 11 CR33–30, –36 38 9 1 9 CX34–25 15 3 0 12 CX34–31 15 4 0 11 CX34–36 27 2 0 0 CX34–38 SN# 6007K and after 4 4 0 11 CX34–38 before SN# 6007K 20 4 0 11 CX34–42 27 2 0 0
036
CBX26UH–036 25 5 2 2 CBX27UH−036 10 5 2 2 CBX27UH−042 10 10 2 8 CBX32M–036, –042 10 5 2 2 CBX32MV–036 10 5 2 2 CBX40UHV−036 10 5 2 2 CH33–31A 10 5 0 2
Target
INDOOR MATCHUPS
CH33–31B 10 5 1 0 CH33–36C 10 4 0 0 CH33–42 10 11 2 3 CH33–44, –48 10 11 2 5 CR33–36 10 4 0 1 CR33–48 30 5 2 3 CR33–50/60 30 11 2 5 CX34–38 SN# 6007K and after 5 5 2 2 CX34–38 before SN# 6007K 10 5 2 2 CX34–44/48 10 5 2 2
Subcoolin
Heat Cool
5ºF)(+1ºF)
(+
*Add charge
lb oz
042
CH23–65 32 6 0 12 CBX26UH–042 26 6 1 2 CBX26UH–048 10 12 4 5 CBX27UH−042 15 5 0 0 CBX27UH−048 15 5 0 0 CBX32M–036, –042 15 5 0 0 CBX32MV–036 15 5 0 0 CBX40UHV−034, −042 15 5 0 0 CH33–43B 10 12 4 8 CH33–43C 10 6 1 1 CH33–44 10 6 0 16 CH33–48 10 6 1 1 CH33–49C 10 12 3 12 CR33–48 32 5 0 5 CR33–50/60 32 9 2 6 CX34–43 10 6 1 1 CX34–49 10 12 3 7 CX34–50/60 10 6 1 1 CX34–60 10 9 2 6
048
CBX26UH–048 12 11 0 8 CBX26UH–060 5 12 3 8 CBX27UH−048 10 9 0 7 CBX27UH−060 10 9 0 7 CBX32M–048 10 9 0 7 CBX32MV–048 10 9 0 7 CBX40UHV−048 10 9 0 7 C33–43 0 4 0 3 CH33–43C 13 4 0 3 CH33–49C 10 9 0 7 CH33–60 10 7 0 5 CR33–48 36 4 0 0 CR33–50/60, –60 35 7 0 5 CX34–60 10 7 0 5
060
CBX26UH–060 10 9 3 3 CBX27UH−060 10 8 1 12 CBX32MV–060 10 8 1 12 CBX32MV–068 10 9 2 5 CBX40UHV−060 10 8 1 12 CH33–62 10 9 2 7 CR33–60 35 4 0 0 CX34–60 15 4 0 0 CX34–62 10 9 2 1
*Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.)
506270−01 05/09
Page 20
Page 21
Table 4. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Use table 4 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
Model −018 −024 −030 −036 −042 −048 −060
ºF (ºC)** Liquid Line Pressure / Vapor Line Pressure
Cooling Operation
65 (18) 228 / 140 232 / 139 245 / 135 251 / 134 239 / 135 244 / 139 248 / 129
75 (24) 265 / 142 268 / 142 284 / 137 292 / 138 277 / 136 283 / 141 289 / 131
85 (29) 311 / 144 317 / 144 328 / 140 339 / 140 321 / 139 318 / 143 336 / 132
95 (35) 350 / 147 366 / 146 377 / 144 392 / 143 379 / 142 369 / 145 385 / 133
105 (41) 402 / 149 412 / 148 429 / 145 443 / 145 423 / 144 420 / 148 440 / 136
115 (45) 458 / 152 464 / 152 486 / 147 508 / 149 484 / 147 484 / 150 500 / 140
Heating Operation
60 (16) 350 / 135 348 / 130 341 / 123 350 / 131 366 / 129 350 / 120 379 / 127
50 (10) 321 / 116 330 / 109 324 / 107 331 / 111 348 / 107 333 / 106 361 / 109
40 (4.5) 301 / 96 315 / 89 307 / 88 304 / 96 336 / 89 294 / 92 341 / 89
30 (−1) 294 / 81 301 / 77 290 / 76 295 / 77 317 / 70 291 / 73 323 / 72
20 (−7) 278 / 64 286 / 64 274 / 62 290 / 62 295 / 60 283 / 59 305 / 59
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary.
**Temperature of the air entering the outdoor coil.
Table 5. HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 11 0 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 11 2 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 11 3 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 11 4 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 11 9 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Page 21
XP13 SERIES
Page 22
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
SERVICE LIGHT OPERATION
The thermostat is not included with the unit and must be purchased separately. Some outdoor thermostats incorporate isolating contacts and an emergency heat function (which includes an amber indicating light). The service light thermostat will enable the emergency heat light function on the room thermostat.
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.
Pressure Switch Event Settings
The following are the auto reset values for low and high pressures switches:
High Pressure (auto reset) − trip at 590 psig, reset at
418 psig.
Low Pressure (auto reset) − trip at 25 psig, reset at 40
psig.
Defrost System
The XP13 defrost system includes two components: a defrost thermostat and a defrost control board (figure 35).
DEFROST THERMOSTAT
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When defrost thermostat senses 42°F (5.5°C) or cooler, the thermostat contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
DEFROST CONTROL
The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connections.
The control provides automatic switching from normal heating operation to defrost mode and back. During compressor cycle (call for defrost), the control accumulates compressor run times at 30-, 60-, or 90-minute field−adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.
FILTER DRIER
The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with HFC−410A refrigerant.
LOW PRESSURE SWITCH
The XP13 is equipped with an auto−reset low pressure switch which is located on the vapor line. The switch shuts off the compressor when the vapor pressure falls below the factory setting.
HIGH PRESSURE SWITCH
The XP13 is equipped with a auto-reset high pressure switch (single−pole, single−throw) which is located on the liquid line. The switch shuts off the compressor when discharge pressure rises above the factory setting.
NOTE − A Schrader core is under the pressure switches.
FIELD SELECT
TIMING PINS
TEST
PINS
DIAGNOSTIC
COMPRESSOR
DELAY PINS
REVERSING
VALV E
S87
LOW PRESSURE
SWITCH
DEFROST
THERMOSTAT
S4
HIGH PRESSURE
SWITCH
LEDS
24V TERMINAL STRIP CONNECTIONS
Figure 35. Outdoor Unit Defrost Control Board
506270−01 05/09
Page 22
Page 23
DEFROST CONTROL TIMING PINS
Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 35). The defrost timing jumper is factory−installed to provide a 60−minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90−minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at
power-up, the control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5−second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5−second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re−applied.
COMPRESSOR DELAY
The defrost board has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.
NOTE − The 30-second compressor feature is ignored when jumpering the TEST pins.
TIME DELAY
The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
PRESSURE SWITCH CIRCUIT
The defrost control incorporates two pressure switch circuits. The high pressure switch (S4) is factory-connected to the board’s HI PS terminals (see figure 35). The board also includes a low pressure, or loss-of-charge-pressure, switch (S87). Switches are shown in wiring diagrams in figures 28 and 35.
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch as listed in table 6. The unit will remain locked out until power to the board is interrupted, then re-established or until the jumper is applied to the TEST pins for 0.5 seconds.
Table 6. Defrost Control Board Diagnostic LED
Mode Green LED (DS2) Red LED (DS1)
No power to con­trol
Normal operation / power to control
Anti-short cycle lockout
Low pressure switch fault
Low pressure switch lockout
High pressure switch fault
High pressure switch lockout
OFF OFF
Simultaneous Slow FLASH
Alternating Slow FLASH
OFF Slow FLASH
OFF ON
Slow FLASH OFF
ON OFF
NOTE − The defrost control board ignores input from the low-pressure switch terminals as follows:
S during the TEST mode, S during the defrost cycle, S during the 90-second start-up period, S and for the first 90 seconds each time the reversing
valve switches heat/cool modes.
DIAGNOSTIC LEDS
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
Maintenance
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician. First, turn off electrical power to the unit prior to performing unit maintenance.
Inspect and clean the outdoor and indoor coils. The
outdoor coil may be flushed with a water hose.
NOTE − It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks. Check wiring for loose connections. Check voltage at the indoor and outdoor units (with
units operating).
Check the amperage draw at the outdoor fan motor,
compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters. Check the refrigerant charge and gauge the system
pressures.
Page 23
XP13 SERIES
Page 24
Check the condensate drain line for free and
unobstructed flow; clean, if necessary.
Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
Check drive belt for wear and proper tension.
NOTE − If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this instruction.
Homeowner Information
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where
your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the disconnect switch before performing any maintenance. The unit may have multiple power supplies.
3. Reusable FilterMany indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE − The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air CleanerSome systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish perfor­mance and longevity of the unit.
6. Inspect and clean outdoor coil:
Make sure no obstructions restrict airflow to the
outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.
When removing debris from around the unit, be
aware of metal edges on parts and screws. Although special care has been take to keep exposed edges to a minimum, physical contact with metal edges and corners while apply excessive force or rapid motion can result in personal injury.
Clearing of the outdoor unit’s coil should be
performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your system.
NOTE − If outdoor unit is installed in a seacoast application, it is recommended to increase the frequency of washing to a minimum of every three months. Contact your installing contractor for more details on proper outdoor coil washing procedures in your geographic area.
HEAT PUMP OPERATION
Your new Lennox heat pump has several characteristics that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
EXTENDED POWER OUTAGE
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation.
506270−01 05/09
Page 24
Page 25
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the Emergency Heat setting to obtain temporary heat without the risk of serious damage to the heat pump.
In emergency heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the heat setting and normal heat pump operation may resume.
THERMOSTAT OPERATION
Though your thermostat may vary somewhat from the description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings. Many heat pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room temperature.
Programmable Thermostats
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manual provided with your particular thermostat for operation details.
Preservice Check
If your system fails to operate, check the following before calling for service:
Check to see that all electrical disconnect switches are
ON.
Make sure the room thermostat temperature selector
is properly set.
Make sure the room thermostat system switch is
properly set.
Replace any blown fuses, or reset circuit breakers. Make sure unit access panels are in place. Make sure air filter is clean. Identify the unit model number before calling.
OPTIONAL ACCESSORIES
Refer to the Engineering Handbook for optional accessories that may apply to this unit. The following may or may not apply:
Compressor crankcase heater Mounting bases Timed off control Stand−off kit Sound cover Low ambient kit Monitor kit SignatureStat room thermostat Loss of charge kit High pressure switch kit Mild weather kit Compressor monitor
Page 25
XP13 SERIES
Page 26
Start−Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Vapor Pressure;
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? Cooling Correct?
Calibrated?
THERMOSTAT
Properly Set?  Level? 
506270−01 05/09
Page 26
Loading...