Lennox Elite XP13-024, Elite XP13, Elite XP13-030, Elite XP13-018, Elite XP13-036 Installation Instructions Manual

...
Page 1
,t_2008 Lennox industries Inc,
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
, ®
WARNING
A CAUTION
INSTRUCTIONS
Elite® Series XP13 Units
HEAT PUMPS _ Technical 505,327M j_jj Publications
04108 Litho U.S.A.
Supersedes 03/08
Shipping and Packing List ...................... 1
XP13 Heat Pumps ............................. 1
Unit Dimensions ............................... 2
General Information ........................... 3
Recovering Refrigerant from Existing System ..... 5
Removing Existing Outdoor Unit ................. 5
Positioning New Outdoor Unit ................... 6
Removing and Installing Panels ................. 7
New or Replacement Line Set ................... 9
Brazing Connections ........................... 10
Removing Indoor Unit Metering Device ........... 11
Flushing the System ........................... 12
Installing New Indoor Unit Metering Device ........ 13
Testing for Leaks .............................. 13
Evacuating the System ......................... 15
Servicing Unit Delivered Void of Charge ........... 15
Electrical Connections ......................... 15
Start-Up and Charging Procedures ............... 17
System Operation ............................. 17
Defrost System ............................... 21
Maintenance .................................. 22
Homeowner Information ........................ 22
Start-Up and Performance Checklist ............. 24
A IMPORTANT
A IMPORTANT
04/08
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately
contact the last shipping carrier.
1 -- Assembled XP13 outdoor unit
The XP13 Heat Pumps, which will also be referred to in this instruction as the outdoor unit, uses HFC-410A
refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox
XP13 Engineering Handbook.
This outdoor unit is designed for use in systems that use check thermal expansion valve (CTXV) refrigerant
metering devices.
Page 1
505,327M
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Page 2
CAPACITOR
DEFROST
BOARD
CONTACTOR
RUN
ii CDISCHARGE AIR t
UNIT SUPPORT
FEET
TOP VIEW
SIDE VIEW
SUCTIONLINE
-CONNECTION
LIQUID LINE CONNECTION
LIQUID LINE
ELECTRICAL
VAPOR LINE
4N/4(1 4-3/4
08) (121)
REVERSING
VALVE
FILTER DRIER/
LIQUID LINE
CONNECTIONS
XP13 PARTS ARRANGEMENT
UNIT SUPPORT FEET
i}
2 (51)
tt
1(25) SIDE VIEW
\
C:=::::3 _
HIGH PRESSURE
VAPOR LINE
VAPOR VALVE AND GAUGE PORT/SUCTION
LINE CONNECTIONS
8N/2 (216)
8-3/4 (222)
13-1/2
(343)
XP13-018, 024, 030 AND 036 BASE SECTION
XP13 A
-018 31(787)
-024 31 (787)
-030 31 (787)
-036 35 (889)
-042 35(889)
-048 35 (889)
-060 45 (1143)
505327M 04/08
8N/4 (210)
9N/2 (241)
L
Page 2
3-1/4
(83)
B
27 (686) 27 (686) 27 (686)
27 (686)
30-1/2 (775)
30-1/2 (775) 30-1/2 (775)
T
13-7/8
(352)
(197)
XP13 BASE WITH ELONGATED LEGS
@ @ ®
C
28 (711) 28 (711) 28 (711)
28 (711) 35 (889)
35(889) 35(889)
20-5/8
(524)
_l
4-1/2
(114)
3-5/8
(92)
Page 3
WARNING
IMPORTANT
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows
torque values for fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft Ib 11 NM Sheet metal screws 16 in Ib 2 NM
Machine screws #10 28 in Ib 3 NM Compressor bolts 90 in Ib 10 NM
Gauge port seal cap 8ft Ib 11 NM
USING MANIFOLD GAUGE SETS When checking the system charge only use a manifold
gauge set that features low loss antiblow back fittings See figure 2 for a typical manifold gauge connection setup
Manifold gauge sets used with HFC410A refrigerant systems must be capable of handling the higher system
operating pressures The gauges should be rated for use
with pressures of 0 800 on the high side and a low side of
30" vacuum to 250 psi with dampened speed to 500 psi Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging. Each valve is equipped with a service port which has a
factory-installed valve stem.
I_ TURN
1/12 TURN
9
8 4
Figure 1. Cap Tightening Distances
Xk IMPORTANT
To Access Angle Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal
1 Remove service port cap with an appropriately sized
wrench
2 Connect gauge to the service port 3 When testing is completed replace service port cap and
tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table 1
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 1
To Open and Close AngleType Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak free seal
1 Remove stem cap with an appropriately sized wrench 2 Use a service wrench with a hex head extension
(3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go
3 Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then tighten per table 1
Without Torque Wrench: Finger tighten and use an appropriately sized wrenched to turn an additional
1/12 turn clockwise as illustrated in figure 1
Page 3
XP13 SERIES
Page 4
DISTRIBUTOR
CBECK 7 REV_#s,_T:Uv_E
NOTE - ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW.
_GAUGEM_,FOLD_ ,' ''--!, Ill _'_ 1
T LIQUID
IIBFc-°_oII b"<SE'@ II' _ II r--r'pJV,AmOR
IIA° °LtlJJ coo :sso c w,w
k_ _ CHECK EXPANSION VALVE --
Figure 2. Typical Manifold Gauge Connection Setup
SERVICE PORT
CAP_
SERVICE PORT _"
FRONT-SEATED
TO INDOOR
TO OUTDOOR UNITJ .J CLOSED TO BOTH INDOOR
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the
specified torque.
_L,_ SERVICE PORT
COREj_ _<_ (VALVESTEMSBOWN
I _ /_ _ _ CLOSED) INSERT HEX
UNIT
Figure 3. Angle-Type Service Valve
(Font-Seated Closed)
WRENCH HERE
AND OUTDOOR UNITS
_
INDOOR UNIT
INDOOR
COIL
NOTE- To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap.
To Access Bali-Type Service Port: A service port cap protects the service port core from
contamination and serves as the primary leak seal.
1, Remove service port cap with an appropriately sized
wrench, 2, Connect gauge to the service port, 3, When testing is completed, replace service port cap and
tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table 1,
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 1,
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS
OPEN.
INDOOR UNIT
SERVICE PORT
SERVICE PORT
OPEN TO BOTH
INDOORAND
OUTDOOR UNITS
TOINDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 4. Angle-Type Service Valve
(Back-Seated Opened) Figure 5. Bali-Type Service Valve
505327M 04/08
Page 4
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
BALL (SHOWN CLOSED)
VALVE
STEM
STEM CAP
Page 5
To Open and Close Bali-Type Service Valve:
A valve stem cap protects the valve stem from
contamination and assures a leak-free seal,
1, Remove stem cap with an appropriately sized wrench,
2, Use an appropriately sized wrenched to open, To open
valve, roate stem counterclockwise 90°, To close
rotate stem clockwise 90°.
3, Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then tighten per table 1,
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 1.
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Remove existing HCFC-22 refrigerant using one of the
following procedures:
METHOD 1:
If the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational and you plan to use
the existing HCFC-22 to flush the system,
NOTE - Use recovery machine instructions for specific setup requirements.
1, Disconnect all power to the existing outdoor unit,
2, Connect to the existing unit a gauge set, clean
recovery cylinder and a recovery machine. Use the instructions provided with the recovery machine on how to setup the connections,
3. Remove all HCFC-22 refrigerant from the existing system, Check gauges after shutdown to confirm that the entire system is completely void of refrigerant,
RECOVERY MACHINE
CLEAN RECOVERY
MANIFOLD GAUGES
NOTE - Use recovery machine instructions for specific setup requirements.
METHOD 2: Use this method if the existing outdoor unit is equipped
with manual shut-off valves, and plan on using new
HCFC-22 refrigerant to flush the system, IMPORTANT: Some system configurations may contain
higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets, The following
conditions may cause the compressor to stop functioning: The following devices could prevent full system charge
recovery into the outdoor unit:
Outdoor unit's high or low-pressure switches (if applicable) when tripped can cycled the compressor
OFF.
Compressor can stop pumping due to tripped internal pressure relief valve.
Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain
value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be
allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive
bearings and internal seals),
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut
off the suction valve, Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in
the indoor coil and line set, Perform the following task:
1, Start the existing HCFC-22 system in the cooling
mode and close the liquid line valve.
2. Pump as much of the existing HCFC-22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system, Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining
refrigerant in the system,
NOTE - It may be necessary to bypass the Iow pressure switches if equipped to ensure complete refrigerant
evacuation.
3, When the low side system pressures reach 0 psig,
close the suction line valve,
4, Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into the low side of the system,
Figure 6. Typical Refrigerant Recovery
(Method 1)
/
OUTDOOR UNIT
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves,
Disconnect electrical service at the disconnect switch,
Remove old outdoor unit,
Page 5
XP13 SERIES
Page 6
CAUTION
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 7 for mandatory
installation clearance requirements.
CONTROL PANEL ACCESS LOCATION
* SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
Figure 7. Installation Clearances
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control
box,
Clearance to one of the other three sides must be 36 in. (914 mm).
Clearance to one of the remaining two sides may be
12 in, (305 mm) and the final side may be 6 in, (152
mm)"
48 in. (1219 mm) clearance required on top of unit.
A clearance of 24 in. (610 mm) must be maintained between two units.
POSITIONING CONSIDERATIONS Consider the following when positioning the unit:
Some localities are adopting sound ordinances based on the unit's sound level registered from the adjacent
property, not from the installation property. Install the unit as far as possible from the property line,
When possible, do not install the unit directly outside a window, Glass has a very high level of sound
transmission, For proper placement of unit in relation to a window see the provided illustration in figure 8.
,NSTALLUN,TAWA
FROMW,NDOWS--'--------------,-II __
LINE SET VIBRATION.
Figure 8. Outside Unit Placement
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from
higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 9.
NOTE - If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
7.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING
STRUCTURE.
STRUCTURE
_i UILDING
GROUNDLEVEL
MOUNTING
SLAB
Figure 9. Slab Mounting at Ground Level
ELEVATING THE UNIT (SMALL-BASE UNITS)
If additional elevation is necessary, raise the unit by
extending the length of the unit support feet. This may be done by cutting four equal true-cut lengths of Schedule
(SCH) 40, 4" (101.6mm) piping to the height required as illustrated in figure 10.
i_L
--1-
505327M 04/08
Page 6
Page 7
LEG DETAIL
BASE
/
4" (101.6MM) SCH 40 PIPING
2"(50.8MM) SCH 40 FEMALE THREADED
ADAPTER
LEG DETAIL
Figure 11. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
BASE
Figure 10. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
NOTE - Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the
pre-installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this
procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1"
(25.4mm) square strips should be adequate to hold the extender in place.
ELEVATING THE UNIT (LARGER-BASE UNITS)
Unlike the small-base units which use round support feet, the larger-base units are outfitted with elongated support
feet as illustrated in figure 11 which uses a similar method for elevating the unit.
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be
achieved by using a 2" SCH 40 female threaded adapter. The specified coupling will fit snuggly into the recessed
portion ofthe feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded
adaptors tomake additional adjustments to the level of the unit.
NOTE - Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
ROOF MOUNTING Install unit at a minimum of four inches above the surface
of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended.
,ilk CAUTION
REMOVING PANELS Remove the Iouvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 12.
NOTE - Hold the panel firmly throughout this procedure
2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 12, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 12, detail A.
Page 7
XP13 SERIES
Page 8
INSTALLING PANEL Install the Iouvered panels as follows:
1. Position the panel almost parallel with the unit as illustrated in figure 13, detail D with the screw side as
close to the unit as possible.
2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 12, details
A and C, then upward into the top slot of the hinge
corner post.
3. Rotate panel to vertical to fully engage all tabs,
4. Holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw
holes.
5. When panel is correctly positioned and aligned, insert the screws and tighten.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW
LIP
\
ANGLE MAY BE TOO SIDE TO MAINTAIN
EXTREME -- _ FULLY-ENGAGED TABS
PREFERRED ANGLE
WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
HOLD DOOR FIRMLY TO THE HINGED
Figure 13. Removing/Installing Louvered Panels
(Detail D)
STABILIZING UNIT ON UNEVEN SURFACES To help stabilize an outdoor unit, some installations may
require strapping the unit to the pad using brackets and anchors commonly available in the marketplace,
With unit positioned at installation site, remove two side Iouvered panels to expose the unit base pan. Install the
brackets as illustrated in figure 14 using conventional
_ractices; replace the panels after installation is complete.
Slab Side Mounting
DETAIL
ROTATE IN THIS DIRECTION;
J
il C
J
THEN DOWN TO REMOVE
IMPORTANT! DO NOT ALLOW PANELS
TO HANG ON UNIT BY TOP TAB. TAB IS
FOR ALIGNMENT AND NOT DESIGNED
TO SUPPORT WEIGHT OF PANEL.
PANEL
Figure 12. Removing/Installing Louvered Panels
(Details A, B and C)
Mounting
STABILIZING BRACKET MINIMUM 1 {18 GAUGE METAL- 2" PER SIDE _
WIDTH; HEIGHT AS
REOD,;BENDTOFORM
Deck Top
FOR EXTRA
STABILITY
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
liI°
Figure 14. Installing Stabilizer Brackets
505327M 04/08
Page 8
Page 9
A IMPORTANT
This section provides information on installation or replacement of existing line set. If line set are not being
installed then proceed to Brazing Connections on page 10. If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings, floors), the
refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when
placing and installing a high-efficiency air conditioner.
REFRIGERANT LINE SET Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or sweat connections). Use Lennox L15 (sweat, non-flare) series line set, or use field-fabricated refrigerant
lines as listed in table 2.
Table 2. Refrigerant Line Set
Field Connections Recommended Line Set
Model
-018 L15-41
-024 3/8". 3/4" 3/8" 3/4"
-030 (10 mm) (19 mm) (10 mm) (19 mm) 15 ft, - 50 ft.
-036
-042 3/8". 7/8" 3/8" 7/8"
-048 (10 ram) (22 ram) (10 ram) (22 ram) 15 ft, - 50 ft.
-060 (10 mm) (29 ram) (10 ram) (29 ram) Fabricated
Liquid Suction Liquid Suction Line Line Line Line L15 Line Set
(4.6 m - 15 m) L15-65
(4.6 m - 15 m)
318". 1-118". 318" 1-1/8" Field
Line set diameters for the unit being installed as listed in table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
The RFCl-metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant
was metered into the evaporator by utilizing
temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit. If the XP13 is being used with either a new or existing
indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the XP13 unit. Typically
a liquid line used to meter flow is 1/4" in diameter and copper.
INSTALLING LINE SET Line Set Isolation--This reference illustrates
procedures, which ensure proper refrigerant line set isolation:
Installation of line set on horizontal runs is illustrated in figure 15.
Installation of line set on vertical runs is illustrated in figure 16.
Installation of a transition from horizontal to vertical is illustrated in figure 17.
TO HANG LINE SET FROM JOIST OR
RAFTER, USE EITHER METAL STRAPPING
MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
METAL INTERVALS THEN STRAP THE
SLEEVE LIQUID LINE TO THE SUCTION
8 FEET
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET
WIRE TIE (AROUND
ONLY)
TAPE OR
WIRE TIE
NOTE - When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the
correct information from Lennox, be sure to communicate the following points:
Model (XP13) and size of unit (e.g. -060).
w%O, L,NE
FLOOR JO/STTEO_ .b > __ > >
- I I_1 I1
Figure 15. Refrigerant Line Set: Installing
Horizontal Runs
Page 9
XP13 SERIES
Page 10
IMPORTANT-REFRIGERANTLINESMUSTNOTCONTACTWALL.
OUTSIDEWALL SUCTIONLINE
NOTE-SIMILARINSTALLATION
PRACTICESSHOULDBEUSED
IFLINESETISTOBEINSTALLED
ONEXTERIOROFOUTSIDE
WALL.
LIQUIDLINE
WOODBLOCK
STRAP
;LEI
SUCTIONLINE
WRAPPEDWITH
ARMAFLEX
UIDLINE
PIPE
Figure 16. Refrigerant Line Set: Installing Vertical
FIBERGLASS
INSULATION
Runs (New Construction Shown)
IMPORTANT!REFRIGERANT
LINESMUSTNOTCONTACT
STRUCTURE.
_WARNING
,WARNING
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint.
Also, shield the light maroon R-410A sticker.
WARNING
ANCHORED HEAVY NYLON MUFFLER-TYPE HANGER WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL
STUD
METAL SLEEVE \ SUCTION LINE - WRAPPED IN
Figure 17. Refrigerant Line Set: Transition from
Use the following procedure to braze the line set to the new air conditioner unit. Figure 18 is provided as a general
guide for preparing to braze the line set to the air conditioner unit.
505327M 04/08
Vertical to Horizontal
AUTOMOTIVE
X STRAP LIQUID LINE
TO SUCTION LINE
LIQUID LINE
ARMAFLEX
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port
connection on the liquid line service valve and out of the valve stem port connection on the suction service
valve.
NOTE - The RFCIV or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing.
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow. Repeat procedure starting at
paragraph 4 for brazing the suction line to the suction service valve.
Page 10
Page 11
i,_,,IP
CUTANDDEBUR
INDOOR UNIT
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT
POINT FOR NITROGEN SERVICE
I _ LIQUID LINE SERVICEJ
VALVE
VALVE
UNIT
outdoor
q
,4i
WRAP / (
INSTALLCOREONLYFOR
BOTHSERVICEPORTSafterthey
havecoolED.
SER
VALVE _Z£
Figure 18. Brazing Connections
7. After all connections have been brazed, disconnect 2. Remove any shipping clamps holding the liquid line manifold gauge set the from service ports and remove
wrapping. Reinstall the service port core for both of the outdoor unit's service valves.
and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage
distributor tubes during this process.
4. Remove and discard fixed orifice, valve stem
Remove the existing HCFC-22 refrigerant flow control orifice or thermal expansion valve from the indoor coil. The
existing indoor unit HCFC-22 metering device is not approved for use with HFC-410A refrigerant and may
prevent proper flushing.
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes:
assembly if present and Teflon washer as illustrated in figure 20.
5. Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing.
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING REMOVE AND DISCARD
FIXED VALVE STEM ASSEMBLY
10 -- Brass nuts for liquid line assemblies
20 -- Teflon rings
/OR,F,?./(,FPRESENT,
BRASS NUT
10 -- Liquid line orifice housings
10 -- Liquid line assemblies
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20) (_
iRASSNUTS(10,
PISTON
__ / RETAINER
D,S& ,B2TOR.."'
VALVE STEM
VALVE STEM CAP
d
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
(Uncased Coil Shown)
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10) LIQUID LINE
Figure 19. 69J46 Kit Components
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
ASSEMBLY
Figure 20. Typical Fixed Orifice Removal
TYPICAL TXV REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
Page 11
XP13 SERIES
Page 12
4, Remove the suction line sensing bulb as illustrated in
figure 21.
5, Disconnect the liquid line from the TXV at the liquid line
assembly,
TWOPIECE (Uncased Coil Shown)
PATCH PLATE
(UNCASED COIL STUB END
ONLY LIQUID LINE
ORIFICE HOUSING
DISTRIBUTOR
TUBES
SENSING
LINE
A IMPORTANT
If the original system used:
HCFC-22 refrigerant, then flush the system using the procedure provided in this section.
HFC-410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
MALE EQUALIZER LINE /
FITTING J SUCTION
/
SENSING BULB LINE
LIQUID
LINE
Figure 21. Typical TXV Removal
6, Disconnect the TXV from the liquid line orifice housing.
Take care not to twist or damage distributor tubes during this process,
7, Remove and discard TXV and the two Teflon rings as
illustrated in figure 21,
8, Use a field-provided fitting to temporary reconnect the
liquid line to the indoor unit's liquid line orifice housing,
IMPORTANT
Xk CAUTION
A IMPORTANT
505327M 04/08
Page 12
CONTAINS CLEAN HCFC-22 TO BE USED FOR FLUSHING GAUGE
_( _ INVERTED HCFC-22 CYLINDER
#
h I PRESSURE PRESSURE
SUCTION LINE
SERVICE VALVE _
EXISTING
OOR
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
NOTE - THE INVERTED HCFC-22 CYLINDER MUST CONTAIN AT LEAST THE SAME AMOUNT OF REFRIGERANT AS WAS RECOVERED FROM THE EXISTING SYSTEM,
MANIFOLD
LOW HIGH
CLOSED
RECOVERY MACHINE
Figure 22. Typical Flushing Connection
REQUIRED EQUIPMENT Equipment required to flush the existing line set and indoor
unit coil:
Two clean HCFC-22 recovery bottles,
Oilless recovery machine with pump-down feature,
Two gauge sets (one for HCFC-22; one for
HFC-410A),
FLUSHING PROCEDURE
1, Connect the following:
HCFC-22 cylinder with clean refrigerant to the
suction service valve,
HCFC-22 gauge set to the liquid line valve,
Recovery machine with an empty recovery tank to
the gauge set,
2, Set the recovery machine for liquid recovery and start
the recovery machine, Open the gauge set valves to
Page 13
allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
3, Invert the cylinder of clean HCFC-22 and open its
valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4, After all of the liquid refrigerant has been recovered,
switch the recovery machine to suction recovery so that all of the HCFC-22 suction is recovered. Allow the
recovery machine to pull a vacuum on the system,
5, Close the valve on the inverted HCFC-22 drum and
the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off,
XP13 units use CTXV for metering refrigerant only. This section provides instructions on installing CTXV
refrigerant metering device,
1/2 TURN
an additional 1/2 turn clockwise as illustrated in figure 23, or 20 ft-lb,
6, Attach the suction line sensing bulb in the proper
orientation as illustrated in figure 25 using the clamp and screws provided,
TWOPIECE (Uncased Coil Shown)
PATCH PLATE
UNCASED COIL
ONLY) LIQUID LINE
DISTRIBUTOR CTXV
TUBES. -
MALE EQUALIZER LINE
FITTING (SEE FIGURE 26 FOR FURTHER
SENSING BULB INSULATION IS
REQUIRED IF MOUNTED EXTERNAL
TO THE COIL CASING SEE FIGURE 25
FOR BULB POSITIONING.
HOUSING
._ORI FIC E STUB END
SUCTION LINE
LIQUID
LINE
Figure 23. Tightening Distance
TYPICAL CTXV INSTALLATION PROCEDURE
The CTXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field-provided plenum, install the CTXV in a manner that will provide access for field servicing of the
CTXV. Refer to Figure 24 for reference during installation of CTXV unit,
1, Remove the field-provided fitting that temporary
reconnected the liquid line to the indoor unit's
distributor assembly,
2, Install one of the provided Teflon rings around the
stubbed end of the CTXV and lightly lubricate the
connector threads and expose surface of the Teflon ring with refrigerant oil.
3, Attach the stubbed end of the CTXV to the liquid line
orifice housing, Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise
as illustrated in figure 23, or 20 ft-lb,
4, Place the remaining Teflon washer around the other
end of the CTXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant
oil,
5, Attach the liquid line assembly to the CTXV. Finger
tighten and use an appropriately sized wrench to turn
Figure 24. Typical TXV Installation
NOTE - Insulating the sensing bulb once installed may be required when the bulb location is external to the coil
casing.
SUCTION LINE 7/8", MOUNT SENSING BULB
I' '_,,,,- O'CLOCK POSITION.
/
BULB
\
SUCTION LINE
_--,_--"_:",..,_ MOUNT SENSING BULB AT
'_ >.,, POSITION. NEVER MOUNT
,,'_,%_ " ON BOTTOM OF LINE.
,. __ EITHER THE 4 OR 8 O'CLOCK
ON LINES SMALLER THAN
AT EITHER THE 3 OR 9
ON 7/8" AND LARGER LINES,
_'.1,_"Y "_.\\_ i Y _X/
(BULB }'_L I j_ BULB)
NOTE - NEVER MOUNT ON BOTTOM OF LINE.
Figure 25. TXV Sensing Bulb Installation
Page 13
XP13 SERIES
Page 14
7, Remove and discard either the flare seal cap or flare
nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 26,
IMPORTANT
FLARE SEAL --
CAP
I
I
_ LARE NUT
OR
J
MALE BRASS EQUALIZER
COPPER
BONNET
After the line set has been connected tothe indoor unit and air conditioner, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
IMPORTANT
WARNING
WARNING
_ LINE FITTING
SUCTION LINE
Figure 26. Copper Flare Seal Bonnet Removal
8, Connect the equalizer line from the TXV to the
equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated in figure 23.
NOTE - To prevent any possibility of water damage,
properly insulate all parts of the TXV assembly that may
sweat due to temperature differences between the valve and its surrounding ambient temperatures.
See the XP13 Engineering Handbookforapproved CTXV kit match-ups and application information,
The reference CTXV kits include: 1--CTXV
2 -- Teflon rings 1 -- 1 1/4" wide copper mounting strap for sensing bulb 2 -- #10 hex head bolts and nuts for securing sensing bulb
AND NUTS (2)
@ TEPLON
COPPER
MOUNTING
RINGS (2) /%
STRAP (1)
Figure 27. CTXV Kit Components
WARNING
1. Connect an HFC-410A manifold gauge set high pressure hose to the suction valve service port.
(Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high
pressure damage.)
2. With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A
cylinder (suction only).
3. Open the high pressure side of the manifold to allow
HFC-410A into the line set and indoor unit. Weigh in
a trace amount of HFC-410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC-410A cylinder and the valve on the high pressure
side of the manifold gauge set. Disconnect the
HFC-410A cylinder.
505327M 04/08
Page 14
Page 15
4, Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold
gauge set,
5, Adjust dry nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit,
6, After a few minutes, open one of the service valve
ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector,
7, After leak testing disconnect gauges from service
ports,
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are
defined as any gas that will not condense under temperatures and pressures present during operation of
an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances
that corrode copper piping and compressor parts,
Xk WARNING
6, When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves,
7, Shut off the dry nitrogen cylinder and remove the
manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from
the line set and indoor unit,
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9, When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder d HFC-410A refrigerant, Open the manifold gauge valve
1 to 2 psig in order to release the vacuum in the line set
and indoor unit.
10, Close manifold gauge valves and shut off the
HFC-410A cylinder and remove the manifold gauge set,
A IMPORTANT
1, Connect manifold gauge set to the service valve ports
as follows:
low pressure gauge to suction line service valve
high pressure gauge to liquid line service valve
2, Connect micron gauge,
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set,
4, Open both manifold valves and start the vacuum
pump.
5. Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29,01 inches of mercury),
NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak, If this occurs, repeat the leak testing
procedure.
NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum
pressure,
Page 1
If the system is void of refrigerant, clean the system using the procedure described below,
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2, Evacuate the system to remove as much of the
moisture as possible.
3, Use nitrogen to break the vacuum and install a new
filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC-410A refrigerant as listed on unit nameplate into the system.
5, Monitor the system to determine the amount of
moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the
required dryness level. If system dryness is not verified, the compressor will fail in the future.
In the U,S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC), Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum overcurrent protection size,
1, Install line voltage power supply to unit from a properly
sized unit disconnect switch,
2, Ground the unit at the unit disconnect switch or to
earth ground,
5
XP13 SERIES
Page 16
NOTE - To facilitate conduit, a hole is provided in the bottom of the control box. Connect conduit to the control
box using a proper conduit fitting.
WARNING
3, Install room thermostat (ordered separately) on an
inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It
should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations,
I
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figures 30 and 31, ( 24V, Class II circuit connections are made in the
low voltage junction box.)
THERMOSTAT
| ||
J!
Wire run length AWG # Insulation type
less than 100' (30m) 18 color-coded, temperature more than 100' (30m) 16 rating 35°C minimum
NOTE - Units are approved for use only with copper conductors. Refer to figure 28 for high voltage field wiring diagram. (A complete unit wiring diagram is located inside the unit control box cover.)
NOTE - For proper voltages, select thermostat wire gauge oer the following chart:
OUTDOOR
FAN
!I?JPURPLE
T BLACK
ORANGE
RED
L_Ow
COMPRESSOR
CRANKCASE HEATER
BLACK
CAPACITOR
DUAL
BLACK
BLACK
r- --
F---
_
i_tr-
GROUND
; F
LUG
I II Ill
----J ii I
DEFROST_ !F'_---'_REVERSING THERMOSTAT _VALVE
ZOB-ZSO/60/I
LZ_- : - IL_
EOUIPMENT
__J
OMCI
FAN
OUT II
LO-PS
COMMON
Y_OUT YI
RI-PS
z_NOTE - For use with copper conductors only. Refer to unit
DEFROST CONTROL
FAN
r
L0-PS
YI_OUT
HI-PS
i [ I i i
Ill I
III II I
20B-ZSO/_I I
LINE VOLTAGE FIELD INSTALLED
_ _ _OLASS VOLTAGE
FIELD INSTALLED
WARNING! - ELECTRIC SHOCK HAZARD. Can cause INJU- RY or DEATH, Unit must be grounded in accordance with
national and local codes.
rating plate for minimum circuit ampacity and maximum over- current protection size.
Figure 28. Typical Field Wiring
DESCRIPTION
(EY COMPONENT _I COMPRESSOR
THERMOSTAT
208-250160/I
_ LI
I_'GROUND
IPRESSURE /
-J PRESSURE
L2 _
HI-PS
Be MOTOR-0UTD00R FAN CI2 CAPACITOR- DUAL
:MCI CONTROL-DEFROST _R_.]_IHEATER-COMPRESSOR
(I.-ICONTACTOR-COMPRESSOR .I VALVE-REVERSING
;4 SWlTCH-HIGHPRESSURE
$6 S_ITCH-DEFROST _€0 THERNGGTAT-CRANKCASE
_87 SWITCH-LOW PRESSURE
A
NOTE- FOR USE WITH COPPER CONOUCTORS
ONLY.REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVER-
CURRENT PROTECTION SIZE.
h,
CONNECTION MUST BE JUMPERED WHEN OPTIONAL SWITCH IS NOT USED
WARNING- ELECTRIC SHOCK HAZARD,
CAN CAUSE INJURY OR DEATN_ UNIT MUST BE GROUNDED IN ACCORDANCE
WITH NATIONAL AND LOCAL CODES.
DENOTES OPTIONAL COMPONENTS
_LINE VOLTAGE
I I CLASS II VOLTAGE
FIELD INSTALLED
FIELD INSTALLED
A
505327M 04/08
Figure 29. Typical Wiring Diagram
Page 16
Page 17
THERMOSTAT
24VPOWER
COMMON
1ST-STAGE
AUXILIARY
HEAT
INDOORUNIT
_L
_ COMMON
r__ 24VPOWER
_ 1ST_STAGE _L
'L. @1 AUXILIARYHEAT
OUTDOOR UNIT
®1 ©1
@1
@1
-- @1
INDOOR BLOWER
REVERSING VALVE
@1
COMPRESSOR @1
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT,)
Figure 30. Outdoor and Blower Unit Thermostat
Designations
THERMOSTAT
®+
©4 COMMON @4
EMERGENCY
HEAT
@4 ,STSTAGE
AUXILIARY
HEAT
INDOOR UNIT
OUTDOOR UNIT
®
\ "-, 24V POWER _
"'. \ COMMON EMERGENCY
l-
J
k@"
"-//_[-- -- HEAT RELAY
/
1 ST-STAG E
AUXILIARY
HEAT
OUTDOOR
_ THERMOSTAT
@
®4
INDOOR BLOWER
@4
REVERSING VALVE
@4
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER_O SPECIFIC THERMOSTAT AND INDOOR UNIT.)
Figure 31. Outdoor and Blower Unit Thermostat
Designations (with emergency heat)
®
® @
IMPORTANT
5, Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected,
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate,
8, Check system for sufficient refrigerate by using the
procedures listed under Testing and Charging
System,
TESTING AND CHARGING SYSTEM
This system uses HFC-410A refrigerant which operates at much higher pressures than HCFC-22. The pre-installed
liquid line filter drier is approved for use with HFC-410A only. Do not replace it with components designed for use
with HCFC-22. This unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device,
SETTING UP TO CHECK CHARGE
1, Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC-410A,
2. Connect the manifold gauge set to the unit's service ports as illustrated in figure 2.
low pressure gauge to vapor service port
high pressure gauge to liquid service port
COOLING MODE INDOOR AIRFLOW CHECK Check airflow using the Delta-T (DT) process using the
illustration in figure 32, HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
Temperature rise between the return air and supply air temperatures at the indoor coil blower unit,
Measuring voltage supplied to the unit,
Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
1, Rotate fan to check for binding.
2, Inspect all factory- and field-installed wiring for loose
connections.
3, After evacuation is complete, open both the liquid and
vapor line service valves to release the refrigerant
charge contained in outdoor unit into the system.
4, Replace the stem caps and tighten to the value listed
in table 1,
CALCULATING CHARGE If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the unit, To calculate the total refrigerant charge:
Additional charge
Amount Adjust amount, for specified per
specified variation in line set indoor unit
on length listed on table match-up listed in Total
nameplate infigure 33. tables 3 through 9. charge
+ + =
Page 17
XP13 SERIES
Page 18
Temp. IDT
ofair 180 24 24 24 23 23 22 22 22 20 19 18 17 16 15 entering,._J78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
indoor _ I _ _ coilOF _jru _ 22 22 21 21 20 19 19 18 17 16 15 14 13
m _174 21 21 21 20 19 19 18 17 16 16 15 14 15 12 _72 20 20 19 18 17 17 16Z_15 14 13 12 11 10
_70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
Wet-bulb °F 57 58 59 60 61 62 63 64 65 66 67 68 69 70 J
n A
DRY
BULB
,0o INDOOR
All temperatures are expressed in °F COIL BULB
Figure 32. Checking Indoor Coil Airflow Guide
WET
1. Determine the desired DT--Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across ceil--Measure the coil's dry bulb entering and leaving air temperatures (A and C). Temperature Drop
Formula: (TDrop) = A minus C.
3. Determine if fan needs adjustment--If the difference between the measured TDrop and the desired DT (TDropi])T) is within ±3 °, no
adjustment is needed. See examples: Assume DT = 15 and A temp. = 72°, these C temperatures would necessitate stated actions:
C° TDrop- DT = °F ACTION 53° 19 15 = 4 Increase the airflow
58° 14 15 = -1 (within +3 °range) no change 62° 10 15 = -5 Decrease the airflow
4. Adjust the fan speed--See indoor unit instructions to increase/ decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3 °.
WEIGH
Refrigerant Charge per Line Set Length
Liquid Line Ounces per 5 feet (g per 1.5 m)
Set Diameter adjust from 15 feet (4.6 m) line set*
3/8" (9.5 mm) 3 ounce per 5' (85 g per 1.5 m)
NOTE - *If line length is greater than 15 ft. (4.6 m), add this
amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Figure 33. Using Weigh In Method
1
Check the airflow as illustrated in figure 32 to be sure the indoor airflow is as required. (Make any air
SUBCOOUNG2
USE COOLING 5
MODE
60°F (15 °) --
USE HEATING
MODE
SATo LIQ o -
SCo =
flow adjustments before continuing with the following procedure,)
Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check charge,
3
Connect gauge set,
4
Check Liquid and Vapor line pressures. Compare pressures with Normal Operating Pressures table 10, (The reference table is a general guide. Expect minor pressure variations. Significant differences may
mean improper charge or other system problem.)
Set thermostat for heat/cool demand, depending on mode being used: Using cooling mode--When the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values in table below are based on 70 to 80°F (21-27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint
to 68°F (20°C). When pressures have stabilized, continue with step 6. Using heating mode--When the outdoor ambient temperature is below 60°F (15°C). Target subcooling
values in table below are based on 65-75°F (18-24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77°F (25°C). When
pressures have stabilized, continue with step 6.
6 Read the liquid line temperature; record in the LIQ ° space. 7 Read the liquid line pressure; then find its corresponding temperature in the temperature/pressure chart
listed in table 11 and record it inthe SAT ° space. 8 Subtract LIQ ° temp. from SAT ° temp. to determine subcooling; record it in SC° space. 9 Compare SC ° results with table below, being sure to note any additional charge for line set and/or match-up.
10 If subcooling value is greater than shown in tables 3 through 10 for the applicable unit, remove refrigerant;
if less than shown, add refrigerant.
11 If refrigerant is added or removed, repeat steps 6 through 10 to verify charge.
Figure 34. Using Subcooling Method
LENNOX
't,__,_7_!_ _'_
M@ululJ
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 10,
Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences
over feet,
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor
unit for charge information.
505327M 04/08
Page 18
Page 19
Table 3. XP13-018
Target *Add charge
INDOOR MATCHUPS Heat Cool
CBX26UH-018 25 5 1 1 CBX26UH-024 25 5 0 1 CBX27UH-018/024 15 8 0 2
CBX32MV-018/024 30 3 0 0 CBX32MV-024/030 15 8 1 2
Subcooling
(+5OF) (+1OF) Ib oz
Table 4. XP13-024
Target *Add charge
INDOOR MATCHUPS Heat Cool
CBX26UH-024 26 5 0 1 CBX26UH-030 26 3 1 3
CBX27UH-018/024 12 3 0 11 CBX27UH-030 12 3 1 4 CBX32M-030 12 3 0 11
CBX32M-036 12 3 1 4 CBX32MV 018/024 12 6 0 5
CBX32MV 024/030 12 3 0 11 CH33-25A 16 6 0 7
CH33 31A 12 3 0 7 CH33 31B 12 3 0 15 CH33-36A 16 6 0 7
CH33 36B 16 7 0 15 CH33 36C 12 5 0 0 CR33-30, -36 12 4 0 3
CX34 25 12 6 0 5 CX34 31 12 3 0 11
CX34-36 16 7 0 11
Subcooling
{±5OF) (±1OF) Ib oz
Table 5. XP13-030
Target *Add charge
INDOOR MATCHUPS Heat Cool
CBX26UH-030, -036 25 4 0 11 CBX27UH-030 15 4 0 11
CBX27UH-036 15 4 0 11 CBX32M 030, 036 15 4 0 11
CBX32M-042 15 4 0 11 CBX32MV-024/030, -036 15 4 0 11
CH33 25A 20 3 0 8 CH33-31A 15 4 0 11 CH33-31B 20 4 0 11
CH33 36A 20 3 0 8 CH33-36C 15 3 0 11
CH33-42B 20 4 0 11 CR33 30, 36 15 4 0 11
CX34-25 15 3 0 12 CX34-31 15 4 0 11 CX34 36 27 2 0 0
CX34-38 SN# 6007K and after 4 4 0 11 CX34-38 before SN# 6007K 20 4 0 11
CX34_42 27 2 0 0
Subcooling
{±5OF) {±1OF) Ib oz
Table 6. XP13-036
Target *Add charge
INDOOR MATCHUPS Heat Cool
CBX26UH-036 25 5 2 2 CBX27UH-036 10 5 2 2
CBX27UH-042 10 10 2 8 CBX32M 036, 042 10 5 2 2
CBX32MV-036 10 5 2 2
*Amount of charge required in additional to charge shown on unit
nameplate. (Remember to consider line set length difference.)
Subcooling
{±5OF) (±1OF) Ib oz
Target *Add charge
INDOOR MATCHUPS Heat Cool
CH33 31A 10 5 0 2 CH33-31B 10 5 1 0
CH33-36C 10 4 0 0 CH33_42 10 11 2 3
CH33-44, -48 10 11 2 5 CR33-36 10 4 0 1
CR33_48 30 5 2 3 CR33-50/60 30 11 2 5
CX34-38 SN# 6007K and after 5 5 2 2 CX34 38 before SN# 6007K 10 5 2 2
CX34-44/48 10 5 2 2
Subcooling
{±5OF) {±1OF) Ib oz
Table 7. XP13-042
Target *Add charge
INDOOR MATCHUPS Heat Cool
CH23 65 32 6 0 12 CBX26UH-042 32 6 1 2
CBX26UHq348 10 12 4 5 CBX27UH-042 15 5 0 0
CBX27UH-048 15 5 0 0 CBX32Mq336, 042 15 5 0 0 CBX32MV 036 15 5 0 0
CH33-43B 10 12 4 8 CH33_43C 10 6 1 1
CH33_44 10 6 0 16 CH33-48 10 6 1 1
CH33_49C 10 12 3 12 CR33_48 32 5 0 5 CR33-50/60 32 9 2 6
CX34 43 10 6 1 1 CX34 49 10 12 3 7
CX34-50/60 10 6 1 1 CX34 60 10 9 2 6
Subcooling
(±5OF) {±1OF) Ib oz
Table 8. XP13-048
Target *Add charge
INDOOR MATCHUPS Heat Cool
CBX26UH-048 10 11 0 8 CBX26UHq360 5 12 3 8
CBX27UH-048 10 9 0 7 CBX27UH-060 10 9 0 7
CBX32M-048 10 9 0 7 CBX32MV-048 10 9 0 7
C33-43 0 4 0 3 CH33_43C 13 4 0 3
CH33-49C 10 9 0 7 CH33-60 10 7 0 5 CR33_48 36 4 0 0 CR33-50/60, -60 35 7 0 5
CX34-60 10 7 0 5
Subcooling
{±5OF) {±1OF) Ib oz
Table 9. XP13-060
Target *Add charge
INDOOR MATCHUPS Heat Cool
CBX26UH-060 10 9 3 3 CBX27UH-060 10 8 1 12
CBX32MV 060 10 8 1 12 CBX32MV-068 10 9 2 5
CH33 62 10 9 2 7 CR33 60 35 4 0 0 CX34-60 15 4 0 0
CX34 62 10 9 2 1
Subcooling
(±5OF) (±1OF) Ib oz
Page 19
XP13 SERIES
Page 20
Table 10. Normal Operating Pressures - Liquid +10 and Vapor +5 PSIG*
IMPORTANT
Mode,t-018 b024 L-030 L.038 1.042 1.048 j.080
°F (°C)** Liquid Line Pressure / Vapor Line Pressure
Cooling Operation
65 (18) 228 / 140 232 / 139 245 / 135 251 / 134 239 / 135 244 / 139 248 / 129 75 (24) 265 / 142 268 / 142 284 / 137 292 / 138 277 / 136 283 / 141 289 / 131 85 (29} 311 / 144 317 / 144 328 / 140 339 / 140 321 / 139 318 / 143 336 / 132 95 (35) 350 / 147 366 / 146 377 / 144 392 / 143 379 / 142 369 / 145 385 / 133
105 (41) 402 / 149 412 / 148 429 / 145 443 / 145 423 / 144 420 / 148 440 / 136 115 (45} 458 / 152 464 / 152 486 / 147 508 / 149 484 / 147 484 / 150 500 / 140
Heating Operation
60 (16} 350 / 135 331 / 130 341 / 126 361 / 112 376/118 350/124 370/127
50 (10} 328/116 315/109 324/107 331 / 106 355/107 323/106 348/105
40 (4.5} 310 / 96 299 / 89 307 / 88 304 / 96 336 / 89 294 / 92 328 / 85
30 (-1) 294 / 81 283 / 72 294 / 72 295 / 77 325 / 74 291 / 73 317 / 72 20 (-7) 278 / 67 267 / 55 278 / 55 285 / 57 309 / 60 277 / 59 305 / 59
*These are most-popular-match-up pressures. Indoor match up, indoor air quafity, and indoor load cause pressures to var_ **Temperature of the air entering the outdoor coil.
Table 11. HFC-410A Temperature (°F) - Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0 125 445.9 141 545.6 33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1 35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8 37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 116 396.0 131 481.6 147 586.8 39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 117 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 118 406.7 133 494.0 149 601.0 41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4 43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1 45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0 47 134.6 78 228.0 109 360.0 140 539.0
505327M 04/08
Page 20
Page 21
INSTALLING SERVICE VALVE CAPS Disconnect gauge set and re-install both the liquid and
suction service valve caps,
INSTALL CAPS
OUTDOOR UNIT /
SERVICE VALVES _
Figure 35. Installing Service Valve Caps
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch
is in the ON position, the indoor blower operates continuously.
SERVICE LIGHT OPERATION The thermostat is not included with the unit and must be
purchased separately, Some outdoor thermostats incorporate isolating contacts and an emergency heat
function (which includes an amber indicating light), The
service light thermostat will enable the emergency heat light function on the room thermostat.
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat
is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the
outdoor unit control circuit is isolated from power and
field-provided relays bypass the outdoor thermostats. An
amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat
mode, Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power outage if power has been off for over an hour and the
outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to
allow the crankcase heater sufficient time to prevent compressor slugging.
FILTER DRIER The unit is equipped with a large-capacity bifiow filter drier
which keeps the system clean and dry, If replacement is
necessary, order another of the same design and capacity. The replacement filter drier must be suitable for use with
HFC-410A refrigerant,
The XP13 defrost system includes two components: a defrost thermostat and a defrost control board (figure 36).
DEFROST THERMOSTAT
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor, When
defrost thermostat senses 42°F (5,5°C) or cooler, the thermostat contacts close and send a signal to the defrost
control board to start the defrost timing, It also terminates defrost when the liquid line warms up to 70°F (21°C),
DEFROST CONTROL The defrost control board includes the combined functions of a time/temperature defrost control, defrost relay,
diagnostic LEDs and terminal strip for field wiring connections,
The control provides automatic switching from normal heating operation to defrost mode and back, During
compressor cycle (call for defrost), the control accumulates compressor run times at 30-, 60-, or
90-minute field-adjustable intervals. If the defrost thermostat is closed when the selected compressor run
time interval ends, the defrost relay is energized and defrost begins.
FIELD SELECT
TIMING PINS
TEST
PINS
COMPRESSOR
DELAY PINS REVERSING
VALVE
LOW PRESSURE
SWITCH
DEFROST j
THERMOSTAT
PIo (_ FAN
9
- 0-O{_T P2
¥I-0UT
OBSl
ODS_
DIAGNOSTIC LEDS
24V TERMINAL STRIP
CONNECTIONS
o
HIGH PRESSURE
SWITCH
Figure 36. Outdoor Unit Defrost Control Board
DEFROST CONTROL TIMING PINS Each timing pin selection provides a different
accumulated compressor run time period for one defrost cycle, This time period must occur before a defrost cycle
is initiated, The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 36), The
defrost timing jumper is factory-installed to provide a 60-minute defrost interval. If the timing selector jumper
is not in place, the control defaults to a 90-minute defrost interval, The maximum defrost period is 14 minutes and
cannot be adjusted,
A TEST option is provided for troubleshooting, The TEST
mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or
jumpered. If the jumper is in the TEST position at
power-up, the control will ignore the test pins. When the
jumper is placed across the TEST pins for two seconds,
the control will enter the defrost mode, If the jumper is
(_ I,;,W;,t;q q J;,IP__)
Page 21
XP13 SERIES
Page 22
removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost
mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the
additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the
jumper is removed and re-applied.
COMPRESSOR DELAY
The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling
in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost
mode when the compressor delay jumper is removed.
NOTE - The 30-second compressor feature is ignored when jumpering the TEST pins.
TIME DELAY
The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the
power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
PRESSURE SWITCH CIRCUIT
The defrost control incorporates two pressure switch circuits. The high pressure switch (S4) is
factory-connected to the board's HI PS terminals (see figure 36). The board also includes a low pressure, or
loss-of-charge-pressure, switch (S87). Switches are shown in wiring diagrams in figures 29 and 36.
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted
by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out
pressure switch after the fifth occurrence of an open pressure switch as listed in table 12. The unit will remain
locked out until power to the board is interrupted, then re-established or until the jumper is applied to the TEST
pins for 0.5 seconds.
Table 12. Defrost Control Board Diagnostic LED
Mode Green LED (DS2) Red LED (DS1)
No power to con-
trol
Normal operation / Simultaneous Slow FLASH power to control
Anti-short cycle
lockout Alternating Slow FLASH Low pressure OFF Slow FLASH
switch fault
Low pressure OFF ON
switch lockout
High pressure Slow FLASH OFF
switch fault
High pressure ON OFF
switch lockout
OFF OFF
NOTE - The defrost control board ignores input from the low-pressure switch terminals as follows:
during the TESTmode,
during the defrost cycle,
during the 90-second start-up period,
and for the first 90 seconds each time the reversing valve switches heat/cool modes.
DIAGNOSTIC LEDS
The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the condition.
WARNING
Before the start of each heating and cooling season, the
following service checks should be performed by a qualified service technician. First, turn off electrical power
to the unit prior to performing unit maintenance.
Inspect and clean the outdoor and indoor coils. The outdoor coil may be flushed with a water hose.
NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil
(e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks.
Check wiring for loose connections.
Check voltage at the indoor and outdoor units (with
units operating).
Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters.
Check the refrigerant charge and gauge the system
pressures.
Check the condensate drain line for free and unobstructed flow; clean, if necessary.
Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure.
Check drive belt for wear and proper tension. NOTE - If owner reports insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this
instruction.
505327M 04/08
Page 22
Page 23
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1, Air Filter--Ask your Lennox dealer to show you where
your indoor unit's filter is located. It will be either at the
indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2, Disposable Filter--Disposable filters should be
replaced with a filter of the same type and size.
NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
,& IMPORTANT
3. Reusable Filter--Many indoor units are equipped with reusable foam filters. Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE - The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air Cleaner--Some systems are equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor Unit--The indoor unit's evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the
inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
A IMPORTANT
6. Outdoor Unit--Make sure no obstructions restrict airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder
and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which
collects around the unit.
When removing debris from around the unit, be aware of metal edges on parts and screws. Although special
care has been taken to keep exposed edges to a minimum, physical contact with metal edges and
corners while applying excessive force or rapid motion can result in personal injury.
Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system.
HEAT PUMP OPERATION
Your new Lennox heat pump has several characteristics that you should be aware of:
Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This
is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are below 45°F (7°C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the conclusion of the defrost cycle.
EXTENDED POWER OUTAGE The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant slugging during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the
Emergency Heat setting to obtain temporary heat without the risk of serious damage to the heat pump.
In emergency heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a
six-hour compressor crankcase warm-up period, the thermostat can be switched to the heat setting and normal
heat pump operation may resume. THERMOSTAT OPERATION Though your thermostat may vary somewhat from the
description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the
levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature
adjustment; turning the unit off and back on before pressures equalize puts stress on the unit compressor.
Page 23
XP13 SERIES
Page 24
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling, This
mode is generally preferred when humidity control is a priority, The ON or CONT mode provides continuous
indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to
automatically switch from heating mode to cooling mode to maintain predetermined comfort settings, Many heat
pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and
provides temporary heat supplied by the auxiliary heat,
Indicating Light
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the
emergency heat mode.
Temperature Indicator
The temperature indicator displays the actual room temperature,
Programmable Thermostats
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the
added feature of programmable time-of-day setpoints for both heating and cooling, Refer to the user's information
manual provided with your particular thermostat for operation details.
Preservice Check
If your system fails to operate, check the following before
calling for service:
Check to see that all electrical disconnect switches are ON,
Make sure the room thermostat temperature selector is properly set.
Make sure the room thermostat system switch is properly set.
Replace any blown fuses, or reset circuit breakers.
Make sure unit access panels are in place.
Make sure air filter is clean.
Identify the unit model number before calling,
OPTIONAL ACCESSORIES
Refer to the Engineering Handbook for optional accessories that may apply to this unit, The following may or may not apply:
Compressor crankcase heater
Mounting bases
Timed off control
Stand-off kit
Sound cover
Low ambient kit
Monitor kit
SignatureStat'" room thermostat
Loss of charge kit
High pressure switch kit
Mild weather kit
Compressor monitor
!i!i!ii'_!_i;i_i;_ii_!!ii_i!ii!ii_ii!ili_ii!i__i!a!i!i¸!i!i_!i_i_ii!_!!ii_'i!__!!i!!i!ii!i!!!_ii!_i!_i!_!!!_ii!ii!_iii_i__!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!il
Job Name Job no. Date Job Location City State
Installer City State Unit Model No, Serial No. Service Technician
Nameplate Voltage Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker Electrical Connections Tight? Indoor Filter clean? _ Supply Voltage (Unit Off)
Indoor Blower RPM
S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Vapor Pressure; Refrigerant Lines: - Leak Checked? _] Properly Insulated? _] Outdoor Fan Checked? Service Valves: --- Fully Opened? _] Caps Tight? _] Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? _ Cooling Correct?
Calibrated? _ Properly Set? _ Level?
THERMOSTAT
Page 24
505327M 04/08
Loading...