Lennox Elite XC16, Elite XC16-024, Elite XC16-036, Elite XC16-048, Elite XC16-060 Installation Instructions Manual

Page 1
INSTALLATION
E2009 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
INSTRUCTIONS
Elite® Series XC16 Units
AIR CONDITIONER
506101−01 07/09 Supersedes 04/08
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
XC16 Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 2. . . . .
Removing Existing Outdoor Unit 5. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 5. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 5. . . . . . . . . . . . . . . . .
New or Replacement Line Set 8. . . . . . . . . . . . . . . . . . .
Brazing Connections 9. . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 10. . . . . . . . . . .
Flushing System 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing New Indoor Unit Metering Device 12. . . . . . . .
Testing for Leaks 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 12. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Units Delivered Void of Charge 14. . . . . . . . .
Electrical Connections 15. . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up, Testing and Charging Procedures 15. . . . . . .
System Operation 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Information 21. . . . . . . . . . . . . . . . . . . . . . . .
Checklists 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List
Litho U.S.A.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
07/09 506101−01
*2P0709* *P506101-01*
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
S Assembled outdoor unit
XC16 Outdoor Unit
The XC16 Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the XC16 Engineering Handbook. XC16 Air Conditioners are designed for use in thermal expansion valve (TXV) systems.
NOTE − The XC16 outdoor unit is rated for 230V applications only. A hard-start kit is required for applications where the supply voltage is less than 230V.
Page 1
Page 2
Unit Dimensions − Inches (mm)
UNIT SUPPORT
FEET
D
E
F
XC16 BASE WITH ELONGATED LEGS
C
DISCHARGE AIR
G
K
J
H
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
RUN
CAPACITOR
CONTACTOR
DISCHARGE
LINE
FILTER DRIER/
LIQUID LINE
CONNECTIONS
XC16 PARTS ARRANGEMENT
B
A
OUTDOOR FAN
COMPRESSOR
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
VAPOR LINE
VAPOR VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS
2 (51)
08)
4−3/4 (121)
1 (25)
SIDE VIEW
4−1/4(1
SIDE VIEW
XC16 A B C D E F G H J K
−024
−048
−060
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation,
39 (991) 30−1/2 (775) 35 (889)
45 (1143) 30−1/2 (775) 35 (889)
39 (991) 30−1/2 (775) 35 (889)
39 (991) 35−1/2 (902) 39−3/8 (1001) 16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)−036
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900
When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.
Table 1. Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Dallas, TX 75379−9900
Page 2
506101−01 07/09
Page 3
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings. See figure 27 for a typical manifold gauge connection setup.
Manifold gauge sets used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 on the high side and a low side of 30" vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
OPERATING SERVICE VALVES
The liquid and suction line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each service valve is equipped with a service port which has a factory−installed valve stem.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
Figure 1. Cap Tightening Distances
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Operating Angle−Type Service Valve
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
SERVICE PORT CAP
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
VALVE STEM
FRONT-SEATED
TO INDOOR
UNIT
TO OUTDOOR UNIT
CORE
Figure 2. Angle−Type Service Valve
(Font−Seated Closed)
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
Figure 3. Angle−Type Service Valve
(Back−Seated Opened)
1. Remove stem cap with a wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Page 3
XC16 SERIES
Page 4
3. Replace the stem cap and tighten as follows:
S With Torque Wrench: Tighten finger tight and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 1.
Operating Ball−Type Service Valve
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
tighten per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized to wrench turn an additional 1/12 turn clockwise as illustrated in figure 1.
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO INDOOR UNIT
Recovering Refrigerant from Existing HCFC−22 System
Remove existing HCFC−22 refrigerant using one of the following methods:
METHOD 1:
Use this method if the existing outdoor unit is not equipped with manual shut−off valves, and plan on using existing HCFC−22 refrigerant to flush the system.
NOTE − Use recovery machine instructions for specific setup requirements.
Perform the following task:
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
RECOVERY MACHINE
CLEAN RECOVERY CYLINDER
Figure 5. Typical Refrigerant Recovery
(Method 1)
MANIFOLD GAUGES
OUTDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
Figure 4. Ball−Type Service Valve
506101−01 07/09
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and plan on using new HCFC−22 refrigerant to flush the system.
IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
The following devices could prevent full system charge recovery into the outdoor unit:
S Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor OFF.
S Compressor can stop pumping due to tripped internal
pressure relief valve.
Page 4
Page 5
S Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals).
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump as much of the existing HCFC−22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.
NOTE − It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
S Disconnect line set at the service valves. S Disconnect electrical service at the disconnect switch. S Remove old outdoor unit.
NOTES:
S Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control box.
S Clearance to one of the other three sides must be 36
in. (914 mm)
.
S Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
.
mm)
S 48 in. (1219 mm) clearance required on top of unit. S A clearance of 24 in. (610 mm) must be maintained
between two units.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
S Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
S When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 7.
INSTALL UNIT
AWAY FROM WIN-
DOWS
Positioning New Outdoor Unit
See Unit Dimensions on page for sizing mounting slab, platforms or supports. Refer to figure 6 for mandatory installation clearance requirements.
*
*
*
* SEE NOTES AFTER THIS FIGURE FOR FURTHER DETAILS.
*
Figure 6. Installation Clearances
TWO 90° ELBOWS
INSTALLED IN LINE SET
WILL REDUCE LINE SET
VIBRATION.
Figure 7. Outside Unit Placement
PLACING OUTDOOR UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 8.
NOTE − If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page
7.
Page 5
XC16 SERIES
Page 6
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BUILDING
STRUCTURE
MOUNTING SLAB
BASE
GROUND LEVEL
Figure 8. Slab Mounting at Ground Level
ELEVATING THE UNIT (SMALL−BASE UNITS)
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be done by cutting four equal true−cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as illustrated in figure 9.
BASE
LEG DETAIL
4" (101.6MM) SCH 40 PIPING
Figure 9. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the pre−installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1" (25.4mm) square strips should be adequate to hold the extender in place.
ELEVATING THE UNIT (LARGER−BASE UNITS)
Unlike the small−base units which use round support feet, the larger−base units are outfitted with elongated support feet as illustrated in figure 10 which uses a similar method for elevating the unit.
LEG DETAIL
2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER
Figure 10. Elevated Slab Mounting using
Feet Extenders (Larger Base Units)
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be achieved by using a 2" SCH 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
Slab Side Mounting
#10 1/2" LONG SELF−
DRILLING SHEET
METAL SCREWS
STABILIZING
BRACKET (18 GAUGE
METAL − 2" WIDTH;
HEIGHT AS REQ’D)
#10 1−1/4" LONG
HEX HD SCREW
AND FLATWASHER
CONCRETE SLAB − USE PLASTIC PLASTIC ANCHOR (HOLE DRILL 1/4")PLASTIC SLAB − NO PLASTIC ANCHOR (HOLE DRILL 1/8")
COIL
BASE PAN
CORNER POST
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL − 2" WIDTH; HEIGHT AS REQ’D); BEND TO FORM RIGHT ANGLE
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
MINIMUM 1 PER SIDE
FOR EXTRA
STABILITY
Figure 11. Installing Stabilizer Brackets
506101−01 07/09
Page 6
Page 7
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the brackets as illustrated in figure 11 using conventional
practices; replace the panels after installation is complete.
ROOF MOUNTING
Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended.
Removing and Installing Panels
REMOVING PANELS
Remove the louvered panels as follows:
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 12.
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
NOTE − Hold the panel firmly throughout this procedure
2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 12, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 12, detail A.
INSTALLING PANEL
Install the louvered panels as follows:
SCREW
LIP
DETAIL A
DETAIL B
HOLES
ROTATE IN THIS DIRECTION;
THEN DOWN TO REMOVE
PANEL
Detail C
Figure 12. Removing/Installing Louvered
Panels (Details A, B and C)
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Figure 13. Removing/Installing Louvered
Panels (Detail D)
1. Position the panel almost parallel with the unit as illustrated in figure 13, detail D with the screw side as close to the unit as possible.
Page 7
XC16 SERIES
Page 8
2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 12, details A and C, then upward into the top slot of the hinge corner post.
3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
5. When panel is correctly positioned and aligned, insert the screws and tighten.
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set are not being installed then proceed to Brazing Connections on page 9.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when placing and installing a high−efficiency air conditioner.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non−flare) series line set, or use field−fabricated refrigerant lines as listed in table 2.
Table 2. Refrigerant Line Set
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the XC16 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the XC16 unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
INSTALLING LINE SET Line Set IsolationThis reference illustrates
procedures, which ensure proper refrigerant line set isolation:
S Installation of line set on vertical runs is illustrated in
figure 14.
S Installation of a transition from horizontal to
vertical is illustrated in figure 15.
S Installation of line set on horizontal runs is
illustrated in figure 16.
IMPORTANT - REFRIGERANT LINES MUST NOT CONTACT WALL.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
SUCTION LINE
LIQUID
LINE
WIRE TIE
INSIDE WALL
Field Connections Recommended Line Set
Model
−024
−036
−048
−060
Liquid
Line
3/8". (10 mm)
3/8". (10 mm)
3/8". (10 mm)
Suction
Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8". (29 mm)
Liquid
Line
3/8" (10 mm)
3/8" (10 mm)
3/8" (10 mm)
Suction
Line
3/4" (19 mm)
7/8" (22 mm)
1−1/8" (29 mm)
L15 Line Set
L15−41 15 ft. − 50 ft. (4.6 m − 15 m)
L15−65 15 ft. − 50 ft. (4.6 m − 15 m)
Field Fabricated
NOTE − When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
S Model (XC16) and size of unit (e.g. −060).
S Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S Number of elbows and if there is a rise or drop of the
piping.
NOTE − SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
SLEEVE
SUCTION LINE WRAPPED WITH
OUTSIDE
WALL
PVC PIPE FIBERGLASS INSULATION
ARMAFLEX
LIQUID LINE
IMPORTANT! REFRIGERANT
LINES MUST NOT CONTACT
CAULK
STRUCTURE.
Figure 14. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown)
STRAP
SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
506101−01 07/09
Page 8
Page 9
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE MUFFLER-TYPE HANGER
WALL STUD
METAL SLEEVE
MUFFLER-TYPE HANGER
AUTOMOTIVE
STRAP LIQUID LINE TO SUCTION LINE
LIQUID LINE
SUCTION LINE − WRAPPED IN ARMAFLEX
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
STRAPPING MATERIAL
(AROUND SUCTION
LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR WIRE TIE
8 FEET
FLOOR JOIST OR
ROOF RAFTER
METAL
SLEEVE
WIRE TIE (AROUND SUCTION LINE ONLY)
TAPE OR
8 FEET
STRAP THE SUCTION LINE TO THE JOIST OR RAFTER AT 8 FEET INTERVALS THEN STRAP THE LIQUID LINE TO THE SUCTION LINE.
WIRE TIE
Figure 15. Refrigerant Line Set: Transition
from Vertical to Horizontal
1
CUT AND DEBUR
2
REMOVE CAP AND CORE FROM
BOTH LIQUID AND SUCTION
INDOOR UNIT
7
INSTALL CORE ONLY FOR
BOTH SERVICE PORTS AFTER
THEY HAVE COOLED.
6
BRAZE LINE SET
Figure 17. Brazing Connections
SERVICE PORTS
SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
SUCTION LINE
LIQUID LINE
5
Figure 16. Refrigerant Line Set: Installing
Horizontal Runs
3
ATTACH
GAUGES
SERVICE
VALVE
SERVICE
VALVE
OUTDOOR
UNIT
FLOW NITROGEN
NITROGEN
4
WRAP
SERVICE
VALV E
Brazing Connections
Use the following procedure to braze the line set to the new air conditioner unit. Figure 17 on page 9 is provided as a general guide for preparing to braze the line set to the air conditioner unit.
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Page 9
XC16 SERIES
Page 10
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
IMPORTANT
Repeat procedure starting at paragraph 4 for brazing the suction line to service port valve.
7. After all connections have been brazed, disconnect manifold gauge set the from service ports and remove wrapping. Reinstall the service port core for both of the outdoor unit’s service valves.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
2. Remove service cap and core from both the suction and liquid line service ports.
3. Connect gauge low pressure side to liquid line service valve.
4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint. Also, shield the light maroon R−410A sticker.
5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve.
NOTE − The fixed orifice or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.)
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel brazing.
6. Braze the liquid line to the liquid line service valve. Turn off nitrogen flow.
Removing Indoor Unit Metering Device
Remove the existing HCFC−22 fixed orifice or TXV from the indoor coil. The existing indoor unit HCFC−22 metering device is not approved for use with HFC−410A refrigerant and may prevent proper flushing.
REPLACEMENT PARTS
If replacement parts are necessary for the indoor unit, order kit 69J46 (LB−95325A). The kit includes:
LIQUID LINE ORIFICE HOUSINGS (10)
TEFLON RINGS (20)
LIQUID LINE ASSEMBLIES
(INCLUDES STRAINER) (10)
BRASS NUTS (10)
LIQUID LINE
ASSEMBLY
Figure 18. 69J46 Kit Components
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
Use the following procedures to remove a fixed orifice metering device from an existing indoor unit:
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR
ASSEMBLY
VALVE STEM
TEFLON RING
VALVE STEM CAP
FIXED ORIFICE
REMOVE AND DISCARD VALVE STEM ASSEMBLY (IF PRESENT)
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
(Uncased Coil Shown)
Figure 19. Typical Fixed Orifice Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
PISTON RETAINER
STRAINER
COPPER TUBE
BRASS NUT
506101−01 07/09
Page 10
Page 11
4. Remove and discard fixed orifice, valve stem assembly if present and Teflon ring as illustrated in figure 19.
5. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
TYPICAL TXV REMOVAL PROCEDURE
Use following procedure for a typical TXV removal:
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
TEFLON
RING
SENSING
LINE
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.
Failure to properly flush the system per the instructions below will void the warranty.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
MALE EQUALIZER
LINE FITTING
SENSING
BULB
SUCTION
LINE
LIQUID
LINE
Figure 20. Typical TXV Removal
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
4. Remove the suction line sensing bulb as illustrated in figure 20.
5. Disconnect the liquid line from the TXV at the liquid line assembly.
6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
7. Remove and discard TXV and the two Teflon rings as illustrated in figure 20.
8. Use a field−provided fitting to temporary reconnect the liquid line to the indoor unit’s liquid line orifice housing.
Flushing the System
If the original system used:
S HCFC−22 refrigerant, then flush the system using the
procedure provided in this section.
S HFC−410A refrigerant, then proceed to Installing New
Refrigerant Metering Device.
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
SUCTION LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE VALVE
RECOVERY
CYLINDER
SUCTION
LIQUID
NOTE − The inverted HCFC−22 cylinder must contain at least the same amount of refrigerant as was recovered from the existing system.
NEW
OUTDOOR
UNIT
OPENED
RECOVERY MACHINE
Figure 21. Typical Flushing Connection
MANIFOLD
LOW
PRESSURE
TANK RETURN
INLET
DISCHARGE
GAUGE
PRESSURE
HIGH
CLOSED
IMPORTANT
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
CAUTION
This procedure should not be performed on systems which contain contaminants (Example: compressor burn out).
Page 11
XC16 SERIES
Page 12
REQUIRED EQUIPMENT
Equipment required to flush the existing line set and indoor unit coil:
S Two clean HCFC−22 recovery bottles, S Oilless recovery machine with pump-down feature, S Two gauge sets (one for HCFC−22; one for
HFC−410A).
PROCEDURE
1. Connect the following:
S HCFC−22 cylinder with clean refrigerant to the
suction service valve,
S HCFC−22 gauge set to the liquid line valve, S Recovery machine with an empty recovery tank to
the gauge set.
2. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
3. Invert the cylinder of clean HCFC−22 and open its valve to allow liquid refrigerant to flow into the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
4. After all of the liquid refrigerant has been recovered, switch the recovery machine to suction recovery so that all of the HCFC−22 suction is recovered. Allow the recovery machine to pull a vacuum on the system.
5. Close the valve on the inverted HCFC−22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
6. Use dry nitrogen to break the vacuum on the refrigerant lines and indoor unit coil before removing the recovery machine, gauges and refrigerant drum.
Installing New Indoor Unit Metering Device
XC16 units can be configured for use in with HFC−410A fixed orifice or TXV metering devices. This section provides instructions on installing either a fixed orifice or TXV refrigerant metering device.
TXV (1)
HEX HEAD BOLTS
AND NUTS (2)
TEFLON RINGS (2)
COPPER
MOUNTING
STRAP (1)
Figure 23. TXV Kit Components
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the TXV in a manner that will provide access for field servicing of the TXV. Refer to Figure 24 for reference during installation of TXV unit.
To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
TWO PIECE
PATCH PLATE
(UNCASED COIL
ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TXV
TEFLON RING
LIQUID LINE ASSEMBLY
WITH BRASS NUT
TEFLON
RING
SENSING
LINE
1/8 TURN
10
8
11
12
7
6
9
10
8
11
12
1
2
3
9
4
7
5
6
Figure 22. Tightening Distance
XC16 ENGINEERING HANDBOOK
See the XC16 Engineering Handbook for approved indoor/outdoor match−ups, applicable TXV kit and application information. The following is the typical contents of a TXV kit:
506101−01 07/09
1/2 TURN
1
2
3
4
5
MALE EQUALIZER LINE
FITTING (SEE FIGURE 26 FOR FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SEE FIGURE 25 FOR BULB POSITIONING.
SUCTION LINE
LIQUID
LINE
Figure 24. Typical TXV Installation
1. Remove the field−provided fitting that temporary reconnected the liquid line to the indoor unit’s distributor assembly.
2. Install one of the provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
Page 12
Page 13
3. Attach the stubbed end of the TXV to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 22, or 20 ft−lb.
4. Place the remaining Teflon ring around the other end of the TXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
5. Attach the liquid line assembly to the TXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 22, or 20 ft−lb.
6. Attach the suction line sensing bulb in the proper orientation as illustrated in figure 25 using the clamp and screws provided.
NOTE − Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
SUCTION LINE
BULB
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
8. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated in figure 22.
Testing for Leaks
After the line set has been connected to both the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
SUCTION LINE
12
BULB
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
NOTE − NEVER MOUNT ON BOTTOM OF LINE.
Figure 25. TXV Sensing Bulb Installation
7. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in figure 26.
IMPORTANT
When removing the flare nut, ensure that the copper flare seal bonnet is removed.
FLARE SEAL
CAP
OR
MALE BRASS EQUALIZER
Figure 26. Copper Flare Seal Bonnet Removal
FLARE NUT
COPPER
FLARE SEAL
BONNET
LINE FITTING
SUCTION LINE
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/ or an explosion, that could result in personal injury or death.
1. Connect an HFC−410A manifold gauge set high pressure hose to the suction valve service port.
NOTE − Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.
2. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (suction only).
3. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
4. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
Page 13
XC16 SERIES
Page 14
5. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
6. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
NOTE − Amounts of refrigerant will vary with line lengths.
7. Check all joints for leaks.
8. Purge dry nitrogen and HFC−410A mixture.
9. Correct any leaks and recheck.
10. After leak testing disconnect gauges from service ports.
Evacuating the System
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
1. Connect manifold gauge set to the service valve ports as follows:
S low pressure gauge to suction line service valve S high pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE − During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in sure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
10. Close manifold gauge valves and shut off the HFC−410A cylinder and remove the manifold gauge set.
Servicing Unit Delivered Void of Charge
If the system is void of refrigerant, clean the system using the procedure described below.
1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again. Then, weigh the appropriate amount of HFC−410A refrigerant as listed on unit nameplate into the system.
506101−01 07/09
Page 14
Page 15
Figure 1. Typical Wiring Diagram
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Electrical Connections
Electric Shock Hazard. Can cause injury or death.
Line voltage is present at all components on units with single-pole contactors, even when unit is not in operation!
Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel.
Unit must be grounded in accordance with national and local codes.
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
TRANSFORMER − 24VAC
Use the transformer provided with the furnace or coil blower for low-voltage control power (24 − 40VAC minimum)
NOTE − The addition of accessories to the system could exceed the 40VAC power requirement of the factory-provided transformer. Measure the system’s current and voltage after installation is complete to determine transformer loading. If loading exceeds the factory-provided transformer capacity, a larger field-provided transformer will need to be installed in the system.
Page 15
XC16 SERIES
Page 16
WIRING CONNECTIONS
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring as illustrated in figure 2.
HIGH VOLTAGE FIELD WIRING
WIRE TIES
GROMMET
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
Table 1. Wire Run Lengths
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
color−coded, temperature rating 35ºC minimum
6. Install low−voltage wiring from outdoor to indoor unit and from thermostat to indoor unit.
7. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provided low voltage strain relief and to maintain separation of field installed low and high voltage circuits as illustrated in figure 2 on page
16.
Start−Up, Testing and Charging Procedures
Figure 2. Separating High/Low Voltage
(Typical Field Wiring)
NOTE − To facilitate conduit, a hole is located in the bottom of the control box.
GROUND
230 / 60 / 1
WARNING! − ELECTRIC SHOCK HAZARD. CAN CAUSE INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
NOTE − FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVER-CURRENT PROTECTION SIZE.
NOTE − HARD START KIT (INCLUDES OPTIONAL COMPONENTS SHOWN) IS REQUIRED IN APPLICATIONS WHERE SUPPLY VOLTAGE IS LESS THAN 230 VOLTS.
Figure 3. Typical Field Wiring Diagram
2. Ground unit at unit disconnect switch or to an earth ground.
3. Connect conduit to the unit using provided conduit bushing.
NOTE − Units are approved for use only with copper conductors. 24VAC, Class II circuit connections are made in the low voltage junction box. See figure 3 for field wiring and figure 1 on page 15 for typical wiring. A complete unit wiring diagram is located inside the unit control box cover.
4. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.
5. For proper voltages, select thermostat wire gauge per the following chart:
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and suction line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor blower and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the procedures listed under this section.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service ports as illustrated in figure 27.
D low pressure gauge to suction line service port. D high pressure gauge to liquid line service port.
INDOOR COIL AIRFLOW CHECK
Check indoor coil airflow using the Delta−T (DT) process as illustration in figure 28.
DETERMINING CHARGE METHOD
To determine the correct charging method, use the illustration in figure 29.
506101−01 07/09
Page 16
Page 17
OUTDOOR UNIT
(Uncased Coil Shown)
LOW
PRESSURE
GAUGE MANIFOLD
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
C
53º
DRY
BULB
HIGH
PRESSURE
TO
HFC−410A
DRUM
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
Drop
19º
All temperatures are
expressed in ºF
OUTDOOR
COIL
SUCTION LINE SERVICE VALVE
FILTER
DRIER
LIQUID LINE
SERVICE VALVE
COMPRESSOR
Figure 27. Typical Manifold Gauge Connection Setup
Delta−T
air flowair flow
INDOOR COIL
B
A
72º
B
WET
BULB
DRY
BULB
64º
1. Determine the desired DTMeasure entering air temperature
using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
) = A minus C.
Drop
3. Determine if fan needs adjustmentIf the difference between the
measured T adjustment is needed. See examples: Assume DT = 15 and A temp. =
and the desired DT (T
Drop
72º, these C temperatures would necessitate stated actions: Cº T
DT = ºF ACTION
Drop
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to
increase/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
TXV
DT) is within +3º, no
Drop
Figure 28. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart
START: Determine how refrigerant is metered
WHEN TO CHARGE?
S Warm weather best S Can charge in colder weather
CHARGE METHOD? Determine by:
S Metering device type S Outdoor ambient temperature
REQUIREMENTS:
S Sufficient heat load in structure S Indoor temperature between 70-80ºF (21−26ºC) S Manifold gauge set connected to unit S Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure suction line temperature
Figure 29. Determining Charging Method
Page 17
OUTDOOR AMBIENT
TEMPERATURE
65ºF (18.3ºC)
and ABOVE
APPROACH OR
SUBCOOLING
(SECOND STAGE − HIGH
CAPACITY)
TXV
64ºF (17.7ºC)
and BELOW
WEIGH-IN
XC16 SERIES
Page 18
START: Measure outdoor ambient temperature
USE EITHER APPROACH
OR SUBCOOLING
METHOD
65ºF
and
ABOVE
WEIGH IN TXV
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 30. Weigh In Method
ABOVE or
BELOW
64ºF and
BELOW
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 2, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
64ºF and
ABOVE or
BELOW
BELOW
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.
If refrigerant is added or removed, verify charge using the Approach Method.
If value is LESS than shown, add refrigerant.
If value is MORE than shown, remove refrigerant.
MORE or
LESS
65ºF
and
ABOVE
1. Confirm proper airflow across coil using figure
28.
2. Compare unit pressures with Table 2, Normal
Operating Pressures − Second Stage (High Capacity).
3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
4. Connect gauge set
5. Measure outdoor ambient temperature
6. When heat demand is satisfied, set thermostat to call for second stage (high capacity) cooling.
7. Allow temperatures and pressures to stabilize.
NOTE − If necessary, block outdoor coil to maintain 325 − 375 psig.
8. Record liquid line temperature:
LIQº = ______
9. Measure liquid line pressure and use the value to determine saturation temperature (see table 3):
SATº = ______
10. Subtract to determine subcooling (SCº):
SATº_____ − LIQº _____ = SCº _____
11. Compare results with table below.
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])
Second Stage (High Capacity)
Models ºF (ºC)* −024 −036 −048 −060 Any 5 (2.7) 6 (3.3) 6 (3.3) 9 (5.0) *Temperature of air entering outdoor coil
Figure 31. Subcooling TXV Charge  Second Stage (High Capacity)
506101−01 07/09
Page 18
Page 19
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
64ºF and
BELOW
If refrigerant is added or removed, retest to confirm that unit is properly charged.
If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temperature too close to ambient temperature, low approach), remove refrigerant.
Figure 32. Approach TXV Charge  Second Stage (High Capacity)
ABOVE or
BELOW
1. Confirm proper airflow across coil using figure
65ºF
and
ABOVE
28.
2. Compare unit pressures with Table 2, Normal
Operating Pressures − Second Stage (High Capacity).
3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC).
4. Connect gauge set.
5. When heat demand is satisfied, set thermostat to call for second stage (high capacity) cooling.
6. Allow temperatures and pressures to stabilize.
7. Record outdoor ambient temperature:
AMBº =_________
8. Record liquid line temperature:
LIQº = __________
9. Subtract to determine approach (APPº):
LIQº_____ − AMBº _____ = APPº_____
10. Compare results with table below.
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])
Second Stage (High Capacity)
Models ºF (ºC)* −024 −036 −048 −060 Any 6 (3.3) 6 (3.3) 8 (4.4) 4 (2.2) *Temperature of air entering outdoor coil
Table 2. Normal Operating Pressures In PSIG (Liquid +/− 10 and Suction+/− 5 PSIG)*
Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to
IMPORTANT
differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Temp. of air entering outdoor coil 5F (5C)
Liquid Suction Liquid Suction Liquid Suction Liquid Suction
−024 −036 −048 −060
First Stage (Low Capacity)
65 (18.3) 215 144 226 142 224 142 215 136
75 (23.9) 247 146 261 144 258 144 250 139
85 (29.4) 288 148 304 145 299 146 291 142
95 (35.0) 332 151 352 147 345 148 337 144
105 (40.6) 381 153 405 150 395 150 388 146
115 (46.1) 435 155 460 150 450 153 444 148
Second Stage (High Capacity)
65 (18.3) 225 140 228 144 235 135 220 130
75 (23.9) 258 142 262 146 269 137 256 133
85 (29.4) 301 144 306 148 313 139 299 136
95 (35.0) 346 146 353 150 361 141 347 138
105 (40.6) 397 149 405 151 412 143 402 141
115 (46.1) 452 151 462 154 471 146 462 143
*These are typical pressures only. Indoor indoor match up, indoor air quality, and indoor load will cause the pressures to vary.
Page 19
XC16 SERIES
Page 20
Table 3. HFC−410A Temperature (°F) − Pressure (Psig)
Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
°F
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 11 0 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 11 2 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 11 3 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 11 4 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 11 5 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 119 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
TWO−STAGE COMPRESSOR
The two−stage scroll compressor operates much like the standard scroll compressor. The two−stage compressor steps between low capacity and high capacity as required to meet cooling demand. The steps occur when gas is bypassed through a vent port in the first suction pocket. This bypassing of gas allows the compressor to operate at low capacity if thermostat demand allows, creating a more cost effective and efficient compressor.
Full capacity is achieved by blocking the vent port with a slider ring. The slider ring (vent port cover) is controlled by a 24VDC internal solenoid in the open position allowing low capacity. When energized the internal solenoid closes the slider ring, blocking the vent port and bringing the compressor to full capacity. Stepping can occur during a single thermostat demand as the motor runs continuously while the compressor steps from low to full capacity.
FILTER DRIER
A filter drier is factory−installed in each XC16 unit to ensure a clean, moisture−free system. Replacement driers are available (refer to Lennox Repair Part Program).
HIGH PRESSURE SWITCH
XC16 units are equipped with a high pressure switch that is located in the liquid line of the compressor. The switch (SPST, manual reset, normally closed) removes power from the compressor when liquid pressure rises above factory setting at 590 + 10 psi.
LOW PRESSURE SWITCH
XC16 units are also equipped with a low pressure switch that is located in the vapor line of the compressor. The switch (SPST, auto−reset, normally closed) removes power from the compressor when vapor line pressure drops below factory setting at 40 + 5 psi.
Maintenance
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency. At the beginning of each cooling season, the system should be checked as follows:
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
OUTDOOR UNIT
1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
Unit Nameplate: _________ Actual: __________
7. Inspect drain holes in coil compartment base and clean if necessary.
506101−01 07/09
Page 20
Page 21
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
INDOOR COIL
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
INDOOR UNIT
1. Clean or change filters.
2. Blower motors are prelubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor. Unit Nameplate: _________ Actual: __________
TWO−STAGE COMPRESSOR CHECKS
Use the checklist procedure on page 23, to verify part-load and full-load capacity operation of two-stage modulation compressors.
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning proper to correctly perform compressor modulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).
Tools Required
S Refrigeration gauge set S Digital volt/amp meter S Electronic temperature thermometer S On-off toggle switch
Procedure
NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).
1. Turn main power OFF to outdoor unit.
2. Adjust room thermostat set point 5ºF above the room temperature.
3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch OFF and install switch in series with
Y2 wire from room thermostat.
5. Cycle main power ON.
6. Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes).
7. Record all of the readings for the Y1 demand.
8. Close switch to energize Y2 demand. Verify power is going to compressor solenoid.
9. Allow pressures and temperatures to stabilize before taking any measured reading (this may take up to 10 minutes).
10. Record all of the readings with the Y1 and Y2 demand.
11. If temperatures and pressures change in the direction noted in chart, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not modulating between low and high capacity and replacement is necessary).
12. After testing is complete, return unit to original set up.
Homeowner Information
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air FilterAsk your Lennox dealer to show you where
your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable FilterDisposable filters should be
replaced with a filter of the same type and size.
NOTE − If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
Turn off electrical power to the unit at the disconnect switch before performing any maintenance. The unit may have multiple power supplies.
3. Reusable FilterMany indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE − The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air CleanerSome systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor UnitThe indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of
Page 21
XC16 SERIES
Page 22
the drain line and how to check for obstructions. This would also apply to an auxiliary drain, if installed.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish perfor­mance and longevity of the unit.
6. Outdoor UnitMake sure no obstructions restrict
airflow to the outdoor unit. Leaves, trash or shrubs crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.
When removing debris from around the unit, be aware of metal edges on parts and screws. Although special care has been taken to keep exposed edges to a minimum, physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury.
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air conditioning or heat pump system.
THERMOSTAT OPERATION
Thermostat operations vary from one thermostat to another. The following provides general operation procedures. Refer to the user’s information manual provided with your thermostat for specific operation details.
Temperature Setting Levers
Set the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit offthen back onbefore pressures can equalize will put stress on the unit’s compressor.
Fan Switch
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling or auto operation. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings.
Temperature Indicator
The temperature indicator displays the actual room temperature.
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manual provided with your thermostat for detailed programming and operation details.
Preservice Check
If your system fails to operate, check the following before calling for service:
S Make sure all electrical disconnect switches are ON. S Make sure the room thermostat Temperature Selector
and System Switch (Heat, Cool, Auto) are properly set.
S If you discover any blown fuses or tripped circuit
breakers, call your Lennox dealer for assistance.
S Make sure unit access panels are in place. S Make sure air filter is clean. S Write down the unit model number and have it handy
before calling.
OPTIONAL ACCESSORIES
Refer to the Engineering Handbook for the latest optional accessories available for XC16 series. Below is a list of some of the optional accessories that may be available:
S Hard Start Kit S Low Ambient Kit S Timed Off Control S Sound Cover S Base Pan S Suction Line Drier S Crankcase Heater
506101−01 07/09
Page 22
Page 23
Checklists
Two−Stage Modulation Compressors Field Operational Checklist
Unit Readings Y1 − First-Stage
COMPRESSOR
Voltage Same Amperage Higher
OUTDOOR UNIT FAN MO­TOR
Amperage Same or Higher
TEMPERATURE
Ambient Same Outdoor Coil Discharge Air Higher Compressor Discharge Line Higher Indoor Return Air Same Indoor Coil Discharge Air Lower
PRESSURES
Suction (Vapor) Lower Liquid Higher
Expected results during Y2
demand (Toggle switch On)
XC16 Start−Up and Performance Checklist
Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial
Notes:
Y2 − Second-Stage
START UP CHECKS
Refrigerant Type: First Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts Second Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts Outdoor Unit Fan Full Load Amps Actual Amps: Firsttage Second Stage
COOLING MODE
Suction Pressure: First Stage: Second Stage:
Liquid Pressure: First Stage: Second Stage:
Supply Air Temperature: First Stage: Second Stage:
Temperature: Ambient: Return Air:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required sub­cooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
Return Air Temperature (A)
minus Supply Air Temperature (B)
A
A
A
B
B
B
SUBCOOLING
=
APPROACH
=
COIL TEMP DROP
=
Page 23
XC16 SERIES
Loading...