43" Wood Burning Fireplaces
P/N 850,027M REV. A 05/2005
MODELS
ME43
This installation manual will enable you to obtain a safe, efficient and
dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any
circumstances. Any modification or alteration of the fireplace system,
including but not limited to the fireplace, chimney components and
accessories, may void the warranty, listings and approvals of this system
and could result in an unsafe and potentially dangerous installation.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS:
INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION,
USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.
Listed to standard: ULC-S610
UL-127
A French manual is available upon request. Order Form Number
850,027CF.
Ce manuel d’installation est disponible en francais, simplement en
faire la demande. Numéro de la pièce 850,027CF.
SAFETY RULES FOR OPERATING
YOUR FIREPLACE MODEL ELITE
ME43
WARNING: AN OUTSIDE AIR KIT MUST
BE INSTALLED ON THE FIREPLACE
MODEL ELITE ME43.
WARNING: THE FIREPLACE MUST BE
OPERATED WITH THE DOORS FULLY
OPENED OR FULLY CLOSED. IF THE
DOORS ARE LEFT PARTLY OPENED, GAS
AND FLAME MAY BE DRAWN OUT OF
THE FIREPLACE OPENING, CREATING
RISKS OF BOTH FIRE AND SMOKE.
• Use only Lennox Fireplace glass doors, spe-
cifically designed for the model ELITE ME43
fireplace. (See Appendix for part number).
• Always keep the fire screen or the doors
closed and the damper opened when using
the fireplace. Keep the damper closed when
the fireplace is not in use.
• The ME43 fireplace is sold with a steel log
grate. If you have to replace it, we recommend for optimum efficiency, to replace it
with an identical or similar Lennox model
grate.
• A fireplace insert heating unit may be in-
stalled in the fireplace only if this unit has
been certified with the ME43 fireplace.
• This fireplace must be installed with Secu-
rity Chimneys FTF8 (8" inside diameter)
chimney System only. These systems are
intended for use in any application where a
traditional masonry type fireplace would
apply. The chimney system must always
vent to the outside of the building.
• This fireplace has been tested for installa-
tion in Canada to CAN/ULC S610-M87 and
ANSI/UL 127-1996 under report number
192-5166. For installations in Canada,
the chimney clearance to combustibles
must be 2 inches and the Cold Climate
Kit must be installed.
• The minimum installed height of the com-
pleted fireplace system is 15' 0". The maximum height is 60' 0".
CAUTION: NEVER USE GASOLINE, KEROSENE, CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR "FRESHEN UP" A
FIRE IN THIS FIREPLACE. KEEP ALL SUCH
LIQUIDS WELL AWAY FROM THE FIREPLACE
AT ALL TIMES.
CAUTION: KEEP COMBUSTIBLE MATERIALS
AT LEAST 48 INCHES AWAY FROM THE FRONT
OF THE FIREPLACE OPENING.
CAUTION: NEVER LEAVE CHILDREN UNATTENDED WHEN THERE IS A FIRE BURNING IN
THE FIREPLACE.
CAUTION: THIS APPLIANCE IS DESIGNED
FOR USE WITH WOOD OR CERTIFIED PROCESSED SOLID FUEL FIRE LOGS. DO NOT
POKE OR STIR THE LOGS WHILE THEY ARE
BURNING. USE ONLY FIRE LOGS THAT HAVE
BEEN EVALUATED FOR THE APPLICATION IN
FIREPLACE AND REFER TO FIRE LOG WARNINGS AND CAUTION MARKINGS ON PACKAGING PRIOR TO USE.
WARNING: THIS FIREPLACE IS NOT
APPROVED WITH AN UNVENTED GAS
LOG SET. TO REDUCE RISK OF FIRE OR
INJURY, DO NOT INSTALL AN UNVENTED
GAS LOG SET INTO THIS FIREPLACE.
FIREPLACE MAINTENANCE
CREOSOTE
When wood is burned slowly, it produces tar
and other organic vapors which combine with
expelled moisture to form a black deposit
called creosote. The creosote vapors condense in the relatively cool chimney flue of a
slow burning fire. As a result, creosote residue
accumulates on the flue lining. When ignited,
this creosote makes an extremely hot fire. If
the creosote accumulation is large, a creosote
fire in the chimney can damage the chimney
and overheat the surrounding wood framing.
Creosote formation in a chimney can be minimized by making small hot fires rather than
slow burning, smouldering fires.
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 3
CHIMNEY MAINTENANCE
Door Frame Care
Glass Replacement
Regular chimney inspection and maintenance
combined with proper operation will help prevent chimney fires. Keep your chimney clean.
Do not allow more than a 1/16" (1.6 mm) buildup of creosote in your chimney. The amount
of creosote will depend on variables such as
frequency of use and type of fire. We recommend that you follow the instructions below:
1. Initially, inspect the chimney system weekly.
By doing this, you will learn how often it will be
necessary to clean your chimney.
2. Have your chimney cleaned by a qualified
chimney sweep. Chimney maintenance should
only be conducted by a qualified technical or
chimney sweep company.
3. Do not expect chemical cleaners to keep
your chimney clean.
The raincap can be removed for inspection
and/or cleaning of the chimney. Unscrew the
braces which attach the raincap to the chimney. Using gloves, firmly grip the upper portion of the rain cap. Turn the cap and lift it off
the chimney.
CHIMNEY FIRES
If you are having a chimney fire, follow these
steps:
1. Close the glass doors and the air inlet.
2. Close the chimney outside air register.
3. Alert your family of the possible danger.
4. If you require assistance, alert your fire
department.
5. If possible, use a dry chemical fire extinguisher, baking soda or sand to control the
fire. Do not use water as it may cause dangerous steam explosions.
6. Watch for smouldering or fire on combustibles next to the fireplace and chimney. Check
outside to ensure that sparks and hot embers
coming out of the chimney are not igniting the
roof.
7. Do not use the fireplace again until your
chimney and fireplace have been inspected by
a qualified chimney sweep or a fire department
inspector.
Use a glass cleaner and a soft cloth to polish
the frame. Do not use abrasives such as steel
wool or steel pads for they may scratch the
door frame finish.
Glass Cleaning
The ELITE ME43 is designed to keep the glass
clean under normal operating conditions. To
clean the glass there are a number of specially designed cleaners. Your authorized
LHP Dealer can recommend a suitable cleaner.
Regular household glass cleaners will not
clean creosote. Do not use abrasives such as
steel pads, steel wool or oven cleaner as they
will scratch the glass.
Doors Adjustment
Glass doors may lose their adjustment during
transportation or installation of the fireplace. A
wrong adjustment may cause a loss in
combustion’s efficiency and control. The glass
doors must be parallel, at the same height and
must almost touch each other when closed.
Maximum spacing between the doors is one
sixteenth of an inch (1/16’’).
The glass doors can be adjusted by loosening
the three (3) screws of the hinges’ supports
(see fastening screws in figure 1). If a minor
angular adjustment is needed, you may loosen
only two (2) of the three (3) screws using the
other as a pivot point.
Fastening
Screws
The glass used for the ELITE ME43 doors is a
high temperature ceramic glass. If the glass
breaks, it must be replaced with a ceramic glass
such as Neoceram. Tempered or ordinary
glass will not withstand the high temperatures
of the ELITE ME43. Replacement glass should
be purchased from your local LHP dealer. Do
not operate the unit with cracked or broken
glass. To remove the glass panel, unscrew the
frame screws, remove the interior frame and
the glass panel.
Removal Of Ashes
Remove ashes only when the fire is out and the
ashes are cold. Lift the front of the log grate
until it rests against the rear refractory; then
remove the ashes. Ashes should be placed in
a metal container with a tight-fitting lid. The
closed container of ashes should be placed on
a non-combustible floor or on the ground, well
away from all combustible materials, pending
final disposal. If the ashes are disposed of by
burial in soil or otherwise locally dispersed,
they should be retained in the closed container
until all cinders have thoroughly cooled. Do
not leave the ashes in the house as they give off
carbon monoxide and other toxic gases.
Frame
Screws
Interior Frame
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
Page 4
OPERATING THE ELITE ME43
Fuel
The Elite ME43 is designed to work best when
fueled with seasoned cordwood. Hardwoods
are preferred to softwoods since the energy
content of wood is relative to its density.
Hardwoods will result in a longer burning fire
and less frequent refueling. A moisture content of 15% to 20% (seasoned) is preferred.
Excessively wet wood will be difficult to burn
and will result in lower efficiency and increased creosoting.
Do not burn scrap or garbage, treated wood or
wood such as driftwood from the ocean which
has been exposed to salt or other chemicals.
Salt or chemicals can corrode the firebox and
chimney. Do not abuse the unit by burning
large amounts of paper, cardboard, Christmas
tree branches or building construction materials such as pressed wood, plywood or lumber. Intense firing with these may overheat the
fireplace, causing damage to the unit, a fire, or
even possibly igniting a chimney fire, if the
chimney is creosoted.
HOW TO USE THE RETRACTABLE DOORS
AND FIRESCREENS
The Lennox Fireplace Model ME43 features
retractable doors and firescreens in order to
allow a wider view of the fire and save space
when the doors are opened. To retract the
doors, simply open them at 90° and push them
into the opening on the side of the firebox. The
same procedure applies for the retractable
firescreens. (
Note : Do not operate the fireplace with both
fire-screen and doors closed at the same time.
see Figure 2
).
HOW TO USE THE OUTSIDE AIR REGISTER
(FIREPLACE)
The outside air register is located on the upper
part of the top louver. The outside air register
supplies oxygen to the fire and allows control
of the fire when the doors are closed. The
fresh air must come from outside the house
(the air intake must not draw air from inside
the house). This will minimize negative pressure in the house. The more you slide the
register to the left, the more fresh air into the
firebox and the more accelerated combustion
you will get (
see Figure 3
). When starting a
fire, the register should always be fully opened.
FIREPLACE INSTALLATION
Please Read Before Installing:
1. Before beginning the installation of your
fireplace, read these safety tips and installation instructions carefully to be sure you
understand them completely. Failure to
follow them could cause a fireplace malfunction resulting in serious bodily injury
and/or property damage.
First Fires
The first 5 or 6 fires should be small fires of
short duration (about 30-60 minutes). The
first fire should be especially short. This will
help cure the refractory bricks. The first fires
may produce slight smoking due to drying of
the paint and steel and any dust accumulated
on the fireplace will be burn off at this time. For
this reason the room should be well ventilated
during the first few fires.
Building A Fire
To start a fire, place several crumpled up balls
of newspaper in the firebox. Place small dry
pieces of kindling on top of the paper, crisscrossing the kindling so that there is airspaces
in between. Place the larger pieces of kindling
on top of the pile. Keep the fuel far back
enough so that air can get underneath. Open
the air control fully and light the newspaper.
Once the kindling fire is well established,
cordwood can be added.
The unit will burn best with a minimum of two
pieces of cordwood spaced 1" to 2" apart and
allowing air to get under the fuel. Crisscrossing or arranging the fuel so that air can get
underneath, will help the fire to get started
easily.
Figure 2
Figure 3
PUSH TO
OPEN
2. The ME43 fireplace has been tested and
listed to UL and ULC standards by Warnock
Hersey International Inc. These instructions were written to give you an outline for
a fast and safe installation and trouble-free
operation.
PUSH TO OPEN
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 5
OPENING
WALL
FIREPLACE
STANDOFFS
18"
(460mm)
45
°
Failure to use LHP parts or conduct variations in techniques and construction materials described in this installation manual may
create a serious fire hazard and may void the
warranty and the WHI listing.
3.
Always check your local building codes.
The installation must comply with their
regulations. Before beginning the installation, consult the local authorities and make
sure your building permit complies with
their requirements.
4. These fireplaces must be installed with Security Chimneys FTF8 (8" inside diameter)
chimney System only. These systems are
intended for use in any application where a
traditional masonry type fireplace would
apply. The chimney system must always
vent to the outside of the building.
5. To maintain top efficiency and to prevent
build-up of soot and creosote, inspect and
clean the chimney periodically during the
heating season.
6. To prevent possible hazards due to poor
combustion and to avoid affecting other fuel
burning appliances (furnace, wood stove,
etc.), ensure that the outside air kit is properly installed.
7. This fireplace is designed to allow the installation of a gas burner. In such a case, the
installation must conform with the National
Gas Code ANSI Z223.1 and Z21.60.
WARNING: WHEN USING A GAS BURNER,
IT IS MANDATORY TO KEEP THE CHIMNEY OUTSIDE AIR REGISTER OPENED.
8. This fireplace has provision for the installation of a gas pipe and is intended
connection to a decorative gas appliance
incorporating an automatic shutoff device
and complying with ANSI Z21.60-M96/CGA
2.26-M96, Standard for Decorative Gas Appliances for Installation in Solid-Fuel Burning Fireplaces (reference Clause 4.1.3 T).
9. ELITE ME43 fireplaces are sold with factory
installed doors. The outside combustionair kit is mandatory and is included with the
fireplace. Optional blowers and decorative
trims are available.
only for
Tools And Building Supplies Normally
Required
Tools:
Phillips screwdriver
Slot style screwdriver
Hammer
Saw and/or Sabersaw
Level
Measuring tape
Plumb line
Electric drill and bits
Pliers
Square
Drywall panel or equivalent
Silicone caulking (non-combustible)
Overlay material for fireplace façade
Hearth extension (non-combustible)
PRECAUTIONS!
The most important areas of concern dealing
with the fireplace installation are clearances to
combustible materials, secure assembly of
components parts, the height of the chimney
system, the proper use of accessory equipment and the techniques used in using finishing materials applied to fireplace surrounds,
hearth extensions and wall coverings. Each of
these topics will be covered in greater detail
throughout this manual. Please give special
attention to these instructions as you progress
with your installation.
Fireplace Installation Procedure
1. Move the fireplace into the desired position
(follow the recommendations below for enclosure).
2. Install the outside air assembly (or assemblies) - refer to page 7.
3. Install the enclosure surrounding the fireplace (refer to the sections “Enclosure” below and “ Facing and Mantel” on page 6).
4. Install the hearth extension (see page 7).
Make sure the gap between the fireplace and
the hearth extension is sealed.
LOCATING THE SECURITY FIREPLACE
Do not place the fireplace on carpeting, vinyl or
other soft surface floor coverings. It may,
however, be directly placed on flat wood, plywood, particle board or other hard surface
materials.
ADJACENT WALL
A wall perpendicular to and in front of the
fireplace front facing must be at least 18" (460
mm) from the fireplace opening. A wall at 45º
to the front facing and starting at the fireplace’s
outer edge is permitted. Projections within
this area are permitted.
See Figure 4
.
Figure 4
ENCLOSURE
WARNING: DO NOT PLACE LOOSE INSULATION OR ANY OTHER MATERIAL IN
THE SPACE AROUND THE FIREPLACE OR
THE CHIMNEY. INSULATION PLACED ON
OR AROUND THE FIREPLACE OR CHIMNEY MAY CAUSE ADJACENT WOOD TO
OVERHEAT AND CATCH ON FIRE.
1. The fireplace must be installed against a
finished wall (like drywall finish). It must not
be installed against a vapor barrier or exposed insulation (
2. Combustible materials like wood, plywood,
particle board or drywall can be in direct
contact with the fireplace standoffs. Two
inch (50 mm) clearance to combustibles
must be kept around the chimney.
see Figure 5
).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
Page 6
WARNING: THE TOP OF THE FIREPLACE
IS NOT ZERO CLEARANCE. DO NOT PLACE
ANY INSULATING MATERIAL IN THE
SPACE ABOVE THE FIREPLACE FOR A
HEIGHT OF 7 FEET FROM THE BASE OF
THE FIREPLACE.
3. Do not block the fireplace’s hot air vents or
air inlets as this will cause the fireplace to
overheat.
Fireplace Facing
The fireplace should be framed using 2" x 3"
(50 mm x 75 mm) or heavier lumber.
Figure 10
Combustible materials must be installed
flush with the fireplace facing. They may
not project out in front of the fireplace.
Non-combustible materials such as brick,
stone or ceramic tile, may project in front of
and/or on the fireplace facing.
shows the general framing layout.
GYPROC
2" x 3" MIN.
SPACER
FIREPLACE
Figure 6
ROOF SUPPORT
ATTIC
FIRESTOP
7 ft. Min.
FLASHING
NON COMBUSTIBLE
CHASE TOP
WARNING: THE HEADER SHOULD REST
ON TOP OF THE METAL SPACERS. DO
NOT ALTER THE SPACERS OR NOTCH
THE HEADER TO FIT AROUND THEM. DO
NOT BLOCK THE AIR INLET OR OUTLET
CEILING/FLOOR
SEPARATION
AS THIS WILL CAUSE THE FIREPLACE TO
OVERHEAT.
Mantel
A wood mantel, if installed, must be at least
48" (1.2 m) above the base of the fireplace (
MUST HAVE THE SAME FIRE RATING
2"
AS ADJACENT CEILING.
MUST HAVE THE SAME INSULATION
AS ADJACENT CEILING.
LOCAL CODE REGULATION FOR CEILING
MUST BE APPLIED TO THE CEILING/FLOOR
SEPARATION, I.E. FIRESTOP, ETC.
FINISHED
WALL
Figure 7
the length or the width of the mantel.
). There is no restriction regarding
see
FIREPLACE
NOTE: Chase wall and floor must be insulated in
the same manner than the rest of the building
below the attic.
Figure 5
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
48"
18"
Figure 7
8"
1"
52"
Page 7
Hearth Extension Requirements
A non-combustible hearth extension must be
built in front of the fireplace and extend out on
both sides. Hearth extensions must be constructed according to the following guidelines:
1. A layer of sheet metal 0.018" (0.45 mm)
thick or 3/8" (9 mm) thick milboard or any
other material (tiles, marble, granite) with
equivalent heat resistance may be used.
Check with the local building authorities
before installing to determine what other
materials are acceptable in your area.
2. The hearth extension should be secured to
the floor. The gap between the fireplace and
the hearth extension must be sealed with
non-combustible caulking or cement.
3. On a raised base or raised hearth, a “Z”
shape piece of metal must be fabricated to
join the bottom of the fireplace to the floor.
Outside Air Assembly
The outside air assembly is mandatory
for the fireplace
.
Outside Air Installation
The outside air assembly must be installed
according to the following guidelines:
1.The maximum length of 4" I.D.(100 mm)
insulated flexible duct is 20 ft (6.1 m ). If a
longer duct is required, use a 6" I.D (150
mm) insulated flexible duct. The maximum
length is 40 ft (12 m ). Refer to figures 8b
and 8c for connections.
2.The duct and register may be installed above
or below floor level.
3.The outside air register must not be in-
stalled more than 7 feet (2.1 m) above the
base of the fireplace.
4.The outside air assembly must draw air
from outside the house. It must not draw air
from the attic, the basement or a garage.
5.Locate the outside register where it will be
well away from automobile exhaust fumes
or other vents.
6.The outside air register should be installed
where it is not likely to be blocked by snow
or exposed to extreme wind
7.It is recommended to install the outside air
register at floor level. However, if you must
raise the air register above the fireplace
level, you will have to make a loop to the
floor with the flexible pipe to prevent from
causing a draught in the outside air register
(
see Figure 8 Detail A
).
During operation, the fireplace requires air
for combustion and draws air out of the
house. It may starve other fuel burning
appliances such as gas or oil furnaces. As
well, exhaust fans and fan driven appliances
may compete for air, causing a negative pressure in the home, resulting in smoke entering
the home from the fireplace. This situation is
aggravated in modern airtight houses.
To overcome this potential problem, the in-
stallation of an outside air assembly is
required to provide outside combustion air
to the fireplace.
7' MAX.
FIREPLACE
CONNECTION
ALUMINIUM
FLEXIBLE
PIPE
TAPE
PLASTIC COVER
LOOP IS MANDATORY
OUTSIDE AIR CONNECTION
TO THE FIREPLACE
FIREPLACE
(Detail B)
(Detail A)
FACING DOWN
OUTSIDE AIR CONNECTION
OUTSIDE
INTAKE
SCREW
OPENING
WALL
ALUMINIUM TAPE
FLEXIBLE PIPE
(Detail C)
PLASTIC
COVER
INSULATION
Figure 8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
Page 8
INSTALLATION OF THE FAN KIT MODEL
UZY3
Note: This fan kit can easily be installed when
the fireplace has a pre-installed junction box.
You just have to plug them in.
Rating: 120 Volts, 60Hz, .63A.
The fans have magnetic blower mounts. The
junction box (factory installed on approved
fireplaces for the use of this fan kit) must be
connected to 110 VAC service before permanently enclosing the fireplace. The access
hole for connecting the 110 VAC is located on
the lower right exterior side of the fireplace.
Installation instructions:
1.Open the bottom louver of the fireplace.
2.Place each fan kit into the fireplace side
opening 1" from the back of the fireplace.
3.Install the automatic fan activator on the
side of the firebox (the fan activator has
a magnetic mount).
4.Plug the fan kit into the junction box.
5.Ground both fans to the back panel using
the green screws.
INSULATED
FLEX PIPE
Figure 9
NOTE: The fireplace must be electrically con-
nected and grounded in accordance with local
codes or in the absence of local codes, with the
current CSA C22.1 Canadian Electrical Code.
For U.S.A. installations, follow local codes and
the National Electrical Code ANSI/NFPA No 70.
CAUTION: SHOULD THIS FAN REQUIRE SERVICING, THE POWER SUPPLY MUST BE DISCONNECTED.
These fans require periodic maintenance.
Check the area in front of the fans and wipe
or vacuum at least once a month during the
burn season.
7' MIN.
Figure 10
43 1/4"
2" X 3" MIN.
27 1/2"
42 1/2"
ROUGH FRAMING FACE (UNFINISHED SHOWN)
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 9
Insulate Joists
Same As Ceiling
Draft Stops
Firestop
CTDT
Termination
Note: NonCombustible
Chase
Flashing
Must Be
Used To
Cover
Chase
Opening
Insulation
(Thermal Barrier)
Figure 11
8'
Level
Optional
Insulation
In Outside
Walls Of
Chase
Solid
Continuous
Surface
Outside
Base
CHIMNEY SYSTEM
These fireplaces are designed and code listed
for use with Security Chimneys FTF8 chimney
System only. Always use Security Chimneys
FTF8 chimney components with these fireplaces. Do not modify or alter these components as this may cause a potential serious
hazard and void the Warranty.
*Construction Materials:
• framing materials• paneling
• particle board• flooring
• millboard• dry wall
• plywood• etc.
Note: 2" clearance to combustibles around
chimney components required.
WARNING: IF INSULATION IS USED, THE
FIREPLACE MUST NOT BE PLACED DIRECTLY AGAINST IT. INSULATION OR
VAPOR BARRIERS, IF USED, MUST FIRST
BE COVERED WITH GYPSUM BOARD,
PLYWOOD, PARTICLE BOARD OR OTHER
MATERIAL TO ASSURE INSULATION AND
VAPOR BARRIERS REMAIN IN PLACE.
WARNING: DO NOT PACK OR FILL REQUIRED AIR SPACES WITH INSULATION
OR OTHER MATERIAL. NO MATERIAL IS
ALLOWED IN THESE AREAS.
Note: Do not insulate the chase cavity with
blown or fill type insulation materials.
Note: Local codes may not require firestopping
at the ceiling levels for outside chase installations. However, it is recommended for safety
and the reduction of heat loss.
Chimney Height
The total height of your completed fireplace
system from the surface the fireplace rests on
to the chimney top must not exceed 60' and
must also meet minimum height requirements.
Refer to the minimum system height chart.
Minimum System Height
Security's FTF8 Pipe
Vertical Installation15' 0"
One Offsets15' 0"
Two Offsets25' 0"
Chase Enclosure
A chase is a vertical box-like structure constructed to surround the fireplace and chimney.
Refer to
Figure 11
ration. As with all chimney installations, avoid
overhead obstructions such as trees, power
lines, etc. A chase should be constructed and
insulated just like any outside wall. In a cold
climate, we recommend the base of the chase
should also be insulated between the solid
continuous floor beneath the fireplace and the
chase bottom. Chase insulation in a cold climate installation is not required for safety.
for a typical chase configu-
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Page 10
FRAMING SPECIFICATIONS
For Canadian Installations Proceed
with Steps 1 through 4
Figure 12
Framing Dimensions for Ceiling
Step 1. Attach the cold climate kit, Model
FTF8-CCK1-LD, around the chimney collar with
Flue TypeAB
FTF8 Vertical16 ¹⁄₂"16 ¹⁄₂"
at 2"(419 mm) (419 mm)
the screws provided (
Note: CCK1-LD model requires a 6" diameter
Class 0 metallic air duct, acquired locally by
see Figure 14
).
installer.
FTF8 Offset 30°16 ¹⁄₂"27"
at 2"(419 mm) (686 mm)
Figure 14
Step 2. Connect the 6" (152 mm) Class 0
B
A
Ceiling Framing
D
Figure 13
C
Roof Framing
metallic air duct to the collar on the chimney
collar enclosure with the screws provided in
the hardware kit.
Step 3. Route the Class 0 metallic air duct out
the back wall or side wall, up through the ceiling
or floor joists to an outside wall. The air duct’s
inlet should be located above any anticipated
Framing Dimensions for Roof
snow level.
FTF8 at 2"
PitchCD*
0/1216 ¹⁄₂"16 ¹⁄₂"
(419 mm)(419 mm)
6/1216 ¹⁄₂"19"
(419 mm)(483 mm)
12/1216 ¹⁄₂"23 ¹⁄₂"
(419 mm)(579 mm)
* Perpendicular to roof ridge
Note: If the fireplace is installed against an inside
wall, the Class 0 metallic air duct may be extended into a ventilated attic space at least 18"
(457 mm) above the attic floor. Secure the duct
hood to a vertical post with the inlet positioned
downward. Ensure that nothing blocks the hood
opening. This air duct must never terminate
higher than the fireplace chimney.
Step 4. Cut or frame a hole through the outside
wall for the installation of the duct inlet hood. A
6 ¹⁄₂" (165 mm) diameter hole is required. Feed
the loose end of the flexible duct through the
hole cut for the inlet hood and attach to the
collar on inlet hood using two (2) screws. Insert
the hood into the opening. Secure in place with
nails driven through the holes in hood flange.
Seal with noncombustible waterproof silicon
type caulking. If additional air duct is needed,
use Class 0 metallic duct.
10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 11
INSTALLING THE CHIMNEY SYSTEM
Step 1. Before continuing, check the operation
of the damper.
Step 2. Using standard construction framing
techniques, construct opening for chimney route
up through the ceiling(s) and roof or through an
outside chase.
Framing must maintain adequate minimum air
space clearance at all times.
CAUTION: ALLOW MINIMUM 2" CHIMNEY
AIR SPACE TO COMBUSTIBLE FRAMING MEMBERS THROUGHOUT VERTICAL OR OFFSET
CHIMNEY INSTALLATION.
A minimum 2" air space must be reserved for
all combustible materials extending for any
continuous length surrounding the chimney.
Reference
ing Dimensions for Ceiling and Roof, which
specify minimum ceiling and roof dimensions.
Figures 12 and 13
and charts Fram-
Step 3. Position appropriate firestop spacer at
ceiling and nail temporarily with two (2) 8d
nails. Use flat firestop spacer, Model F8FS-2,
if chimney penetrates ceiling vertically. If chimney penetrates ceiling at 30° angle (offset
chimney), use 30° firestop spacer, Model
F8FS30. Use one nail on opposite sides to hold
firestop spacer in position. Nail permanently,
using at least two (2) more 8d nails, after
chimney sections have been assembled
through the firestop spacer and after any necessary adjustments have been made. Firestop
spacer must be secured by at least four (4) 8d
nails when completely installed.
Note: If there is a room above ceiling level,
firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 16 and 17 ).
Room Above
F8FS30-2
Firestop Spacer
2" Min.
Air Space
Figure 18
F8FS30-2
Firestop Spacer
2" Min.
Air Space
Attic Space
10'
Max.
Room Above
10'
Max.
2" Min.
Air Space
FTF8-S4 Stabilizer
30° Firestop
And Attic Above
2" Min.
Air Space
FTF8-S4 Stabilizer
30° Firestop
And Room Above
In new construction, to determine chimney center line, use plumb line from roof or ceiling above
fireplace to center of flue collar on fireplace.
For remodeling, plumb to center of flue collar
from ceiling above, drive nail through ceiling
from below to mark position, then mark and
cut to passage from above ceiling (around
nail) (
see Figure 15
). Then plumb from ceiling
or roof level directly above hole which has just
been completed.
Figure 15
Firestop Spacer
Figure 16
Attic Above
Firestop Spacer
Figure 17
CHIMNEY 30° OFFSET THROUGH FLOOR
OR CEILING
It may be necessary to assemble the chimney at 30° when passing through the floor or
ceiling area. Use the F8FS30-2 firestop
spacer as shown in
Support the chimney at floor or ceiling penetration with a FTF8 stabilizer if distance of
chimney below ceiling is 10' or more. Maintain 2" minimum air space to combustibles
from chimney sections.
Figures 18 and 19
Figure 19
Required For Canada
When installing the chimney system through
an open attic space, the attic shield assemblyfirestop spacer must be used (
installation is required only for use in Canada.
Open Attic Space
Figure 20
Note: For Canadian installations, all chimney
installed outside the building must be constructed with galvalume (outer sections only).
The appropriate model designations are lo-
.
cated in the back of this manual.
Note: Attic insulation shield is required in
any installation to insure the 2" air space is
maintained anywhere "blown in" insulation
is used.
Figure 20
FTF8-FSAS
). This
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Page 12
Note:
Step 4.
Chimney sections are constructed
with a unique locking tab design, which ensures an immediate, tight assembly between
sections. Plan your chimney requirements
carefully before assembly as chimney is difficult to disassemble after installation. If disassembled, the tabs might become damaged. Be
certain tabs are properly formed to ensure
locking tabs engage properly.
The Security Chimney's FTF8 chimney system
is a two piece chimney, which snap together
from the fireplace up. Start with the inner flue
section with the lanced end up, snap lock it in to
the matching collar on top of the fireplace. At all
subsequent joints, the upper flue section fits
into the preceding flue section. Each piece
snaps together by means of locking tabs (9
locking tabs per joint). Check each piece by
pulling up slightly from the top to ensure proper
engagement before installing the next section.
If the flue has been installed correctly, it will not
separate when you test it. Also, the inner flue
joint where each section is joined should be
tight and flat without gaps (
Figure 21
).
Figure 21
Outer pipe section installs in just the opposite
way; the lanced end goes down and each new
section goes OVER the outside of the previous
section installed (
Figure 22
).
Locking
Tabs
(Lances)
Note: Assemble one component of chimney at
a time (inner section first, then outer section
last) before proceeding with the next complete
section.
Continue to assemble the chimney up through
framed opening. Assemble just enough to penetrate the roof flashing openings (
Figure 23
).
Always maintain 2" minimum air space to combustible materials and always check each chimney joint (inner and outer) to ensure proper
engagement. Check vertical alignment of chimney so that it projects from the roof in true
vertical position.
2" Min. Air Space
To Combustibles
Figure 23
Security's chimney sections do not need to be
screwed together. Additional reinforcement is
not necessary except in certain offset conditions (refer to page 17,
Figure 34
).
Step 5. The height of vertical chimney pipe
supported only by the fireplace must not exceed 30'. Chimney heights above 30' must be
supported by a Model FTF8-S4 stabilizer installed at 30' intervals.
Note: The Model FTF8-S4 adds 3" net effective
height to the total chimney system.
Install the Model FTF8-S4 stabilizer by fitting
inner section down into respective section of
proceeding flue pipe and locking outer stabilizer section into place over the outer chimney
pipe. Position for proper clearance through
framed opening and nail straps securely (under
tension in “shear”) into place on framing. Use
8d nails. Attach successive lengths of chimney
pipe directly to stabilizer using same techniques as described in Step 4 (
see Figure 24
).
FTF8-S4 Stabilizer
Figure 24
Note: Do not apply excessive pressure to any
subsequent chimney sections following the
stabilizer when installing. Ensure each subsequent chimney section is securely attached by
testing as noted in Step 4.
Step 6. Select the proper Security Chimneys
roof flashing based on pitch of roof. Use chart
below for selection:
Roof PitchModel
Flat to 6/12F8F6
6/12 to 12/12F8F12
Next, slide roof flashing over extended chimney
section that previously has been installed above
the roof opening in Step 4. Slide flashing all the
way down until the flashing base rests flat on
the roof (
Figure 25
). Again, check the vertical
position of the chimney and the 2" minimum air
space to combustibles.
FTF8 Chimney
FTF8 Flashing
Do Not Seal
Figure 25
Note: Do not caulk or seal the ventilating
openings.
Figure 22
12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 13
Step 7. Secure flashing by nailing along the
perimeter into roof using 8d nails. If shingled
roof, slide upper end and sides of roof flashing under shingles (trim if necessary), seal
the top and both sides of the flashing to the
roof with roof caulking. Cover nail heads with
roof caulking (
see Figure 26
).
Step 9. Security Chimneys locking bands,
Model FLB, may be required if the chimney
extends too high above the roof flashing. As a
general rule, if the chimney extends more than
6' above the roof flashing, the use of locking
bands is advisable to strengthen the chimney
assembly. Align the locking band at the chimney joint. Locking bands wrap around pipe
joints equally covering the joints of both pipe
sections. Use the nut provided and TIGHTEN
snugly. Do not overtighten as this might damage the chimney section (
refer to Figure 27
CTD
Termination
Chimney
).
Figure 26
Step 8. The standard Security FTF8 roof flash-
ing assemblies include a storm collar. Slide
the storm collar over outer chimney, rest on
flashing spacers and align with top surface of
flashing. Insert tab in slot, pull tight and bend
tab back over slot. Seal storm collar to outer
chimney with roof caulking or mastic around
entire circumference of pipe. Also add extra
roof caulking to the tab/slot area to seal completely against water penetration (
Figure 27
Check all joints very carefully to ensure no
water intrusion can take place.
Locking Band
Mastic
Note: If chimney extends more than 8' above
roof surface, guy wires are also recommended.
Use three (3) guy wires, attach to locking band
assembly, extend and secure to roof in a triangular pattern (see Figure 28 ). Guy wires are not
supplied by the manufacturer.
Roof Ridge
).
120°
Figure 28
Step 10. Using a FTF8-CTD Round Termination:
1. Hold the FTF8-CTD over top of last chimney
section (
Figure 29
).
2. Center inner slip section in inner flue pipeslip down.
Figure 29
3. Center outer locking section over outer flue
pipe. Push down until locking tabs are firmly
engaged.
4. Pull up slightly on CTD to ensure locking joint
has firmly engaged.
Using a FTF8-CTDT Chase Termination:
Refer to specific installation instructions included with the FTF8-CTDT chase termination
for clearance and installation details.
Using a FTF8-CT1 Chase Termination:
Refer to specific installation instructions included with FTF8-CT1 chase terminations for
clearance and installation details.
Using a FTF8-CT2 Chase Termination:
Refer to specific installation instructions included with FTF8-CT2 chase terminations for
clearance and installation details.
Figure 27
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
Page 14
Less Than 10'
3'
Min
2' Min.
10'
3'
Min
To determine the number of chimney sections
and chimney components required, follow
these steps:
1. Determine total vertical height of the fireplace
installation. This dimension is the distance from
the surface the fireplace sets on to the point
where smoke exits from the termination.
2. Determine the number of chimney components required, except chimney sections. This
would include firestop spacers, stabilizers, roof
flashing, etc.
3. The effective heights of the components are:
Figure 30
Note: It is recommended that all exterior ex-
posed metal fireplace components; such as terminations, flashings, storm collars and/or flue
be painted with a premium quality, high temperature, rust preventative paint designed for
metal. This is especially important when installations are made in abnormally adverse or corrosive environments; such as near lakes, oceans or
in areas with consistently high humidity conditions. Consult the paint manufacturers instructions for proper preparation and application.
TEN FOOT RULE SUMMARY
The minimum chimney height above the roof
and/or to adjacent walls and buildings is specified by all major building codes.
If the horizontal distance from the peak of the
roof is less then 10', the top of the chimney
must be at least 2' above the peak of the roof.
If the horizontal distance from the chimney
edge to the peak of the roof is more than 10' a
chimney height reference point is established
on the roof surface 10' horizontally from the
chimney edge. The top of the chimney must be
at least 2' above this reference point. In all
cases, the chimney cannot be less then 3'
above the roof at the edge of the chimney.
The 2' in 10' rule is necessary in the interest of
safety but does not ensure smoke-free operation. Trees, buildings, adjoining roof lines, adverse wind conditions, etc., may require a taller
chimney should the fireplace not draft properly
(
refer to Figure 30
).
MULTIPLE TERMINATIONS
If more than one termination is located in the
same chase or within the same general proximity, we suggest they should be separated in
distance at least 24" horizontally from flue center to flue center and stacked or staggered
vertically at least 18" apart, from the termination of one smoke exit to the termination of
another smoke exit (
18"
CTDT
24"
Figure 31
24"
).
CTD
18"
CTDT
Figure 31
This suggestion is provided in the interest of
better operation. If the terminations are located
too close to each other, smoke may migrate
from one flue into the other.
FTF8 CHIMNEY COMPONENT
CALCULATIONS
The minimum installed height of the completed fireplace system is 15' 0". The maximum height is 60' 0".
The Fireplace= 36 ¹⁄₄"
FTF8-12= 10 ¹⁄₄"
FTF8-18= 16 ¹⁄₄"
FTF8-36= 34 ¹⁄₄"
FTF8-48= 46 ¹⁄₄"
FTF8-CTD Termination= 4"
FTF8-CT1 Termination= 12" to 18"
FTF8-CT2 Termination= 15" to 23"
FTF8-CTDT Termination= 12" to 18"
FTF8-S4 Stabilizer *= 3"*
* Required for every 30' of vertical chimney
and/or 10' of offset chimney.
4. Determine amount of chimney height required by subtracting total combined height of
all pre-selected components (fireplace and
chimney components from total desired height.)
Reference Vertical Elevation Chart and determine the number of chimney sections (quantity
and length) required.
SPECIAL OFFSET INSTRUCTIONS
To clear any overhead obstructions, you may
offset your chimney system using Security
Chimneys 30° offset and return elbows. Use
two elbows - an offset elbow to initiate the
offset and a return elbow to terminate it. A 30°
offset elbow, angling in any direction, may be
the first component used off the top of the
fireplace flue collar.
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 15
The offset and return elbows may be attached
together, or a section or sections of chimney
may be used between, but do not exceed 20' in
total length between elbows. If sections of pipe
exceed 10' between elbows, a chimney stabilizer must be used at the midpoint (
Figure 32
The stabilizer support straps must be attached
under tension (in shear) to structural framing
members above. When two sets of elbows are
used, the maximum combined length of chimney used between elbows cannot exceed 20'
(
Figure 33
). Example: If C1 = 10' then C2 cannot
exceed 10'.
If an offset exceeds 6' in length, each chimney
joint beyond the first 6' of offset to the return
elbow, must be secured by a No. 8 x ¹⁄₂" sheet
metal screw located at the underside of the joint
(
Figure 34
).
A ¹⁄₈" diameter hole must be drilled in the
chimney joint using a ¹⁄₈" diameter drill. Hole
should be drilled in center of joint overlap
(
Figure 35
). Be sure to drill only through the
outer chimney casting. Do not puncture the
inner flue.
Maximum offset of chimney system is 30°.
Two offsets must not be assembled to form a
60° offset. However, two sets of offset and
return elbows may be used on a single flue
system, provided the total height of the system
exceeds 25'.
Return elbow support straps must be securely
attached under tension (in shear) to structural
framing members above. Do not substitute a
FTF8-30 offset elbow in place of a FTF8-E30
return elbow.
OFFSET CALCULATIONS
Step 1. Use Offset Chart to determine amount
of horizontal offset (A) and height (B) for various chimney section assemblies.
Step 2. Use “Height of Chimney Only” column
in The Vertical Elevation Chart to determine
combinations of chimney used above return
elbow to achieve desired heights. Reference
Components Effective Height Chart in vertical
elevation chart section.
Step 3. Use Elevation Chart as job estimator
only. Add necessary firestop spacers and stabilizers as required. Firestop spacers must be
used as shown in
stabilizers as shown in
Step 1. Determine the offset distance where
chimney is to pass through the first ceilingdimension “A.” To find this point on your ceiling, first determine the center point for a vertical chimney following the instructions for vertical installation.
Measure height to the ceiling from the top of
fireplace-dimension “B.” Use the appropriate
Offset Elevation Chart to find dimension “A.”
Mark point where you will drive your nail to
show the center point for your offset ceiling cut.
Step 2. Proceed by using the Straight Up Installation Instructions for cutting and framing ceiling and roof openings.
Note: See Framing and Dimension Chart for the
sizes of the ceiling and roof openings. The size
of the roof opening varies with the degree of
pitch of the roof.
Offset Elbow Assembly
Offset elbows install the same as chimney
sections. First, snap the inner section INTO the
preceding inner section of flue. Check connection by pulling up slightly to ensure a tight fit.
Next, the outer sections snap lock OVER the
preceding outer section of chimney. Again,
check outer section by pulling up slightly to
ensure proper connection is made.
Return elbows install the same way as round
terminations and stabilizers:
Step 1. Hold return elbow over top of last
chimney section.
Step 2. Center inner slip section into inner flue
pipe-slip down.
Step 3. Center outer-locking section over outer
chimney pipe. Push down until locking joint has
firmly engaged.
Step 4. Pull up slightly on return elbow to
ensure locking joint has firmly engaged.
Step 5. Secure support straps to framing
members by nailing under tension in sheer
Figure 37
(
).
Return
Elbow
Figure 37
Note: The return elbow assembly performs the
same function as a stabilizer. Consider this
when determining the need for a stabilizer.
FTF8-30 Offset Elbow*
A
*Part of Offset/Return Package Model FTF8-ES30
Figure 36
B
Note: Do not apply excessive pressure to any
subsequent chimney section following return
elbow assembly when installing. Ensure that
each subsequent chimney section is securely
attached by testing as noted above.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
Page 18
PARTS AND COMPONENTS LIST
APPENDIX
SPECIFICATIONS
Weight343 lbs
Height42 1/2”
Width43"
Depth26 5/8"
CLEARANCE TO COMBUSTIBLES
The following clearances meet the minimum requirements for a safe installation :
Side wall:18". (457 mm)
Ceiling:7 ft. (2135 mm) measured from the base of the fireplace
Fireplace enclosureBottom: 0"
Side: 0"
Back: 0" (to standoffs)
Top: Do not fill the space above the fireplace with any material
(7 ft. measured from the base of the fireplace)
Chimney:2" (50 mm)
Mantel:48" (1219 mm) from the base of the fireplace
18
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 19
REPLACEMENT PARTSPART NO.CATALOG NO.
Refractory BafflePR-SR2028H3398
Back refractoryPR-SR2027H3399
Right side refractoryPR-SR2025DH3400
Left side refractoryPR-SR2025GH3401
Bottom refractoryPR-SR1722H3402
Front refractory ash lipPR-SR2026H3403
Log supportPR-HELS43H3404
Top/Bottom louverPR-SR15PH3405
Louver hingesPR-PIVOTH3406
Rigid firescreen (left)PR-PARETING-1H3407
Rigid firescreen (right)PR-PARETIND-1H3408
Black door (left)PR-SR2610GPH3409
Black door (right)PR-SR2608DPH3410
Black door capping (right)CAPME43BLKRH3413
Black door capping (left)CAPME43BLKLH3414
Wooden handlePR-SAC #83H3415
Ceramic glass panelPR-VC10H3416
Door gasket assembly (including a tube ofPR-GASKPORTEHE-1H3417
hi-temperature silicone glue)
DamperPR-DAMPER43H3418
OPTIONAL PARTS
Outside Air Kit (Fireplace)UZIH0251
Heat Activated On/Off Fan KitUZY3H0250
Variable Speed Control For UZY3VRUWH3396
Door Capping, Brushed NickelCAPME43BNH3394
Door Capping, GoldCAPME43GH3393
Horizontal Trim Kit, Gold43GTKH3426
Horizontal Trim Kit, Brushed Nickel43NTKH3395
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
19
Page 20
33"
43"
FIREPLACE DIMENSIONS
10 5/8"
27 5/8"
42 1/2"
36"
21 1/4"
43 1/4"
42"
20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 21
INSTALLATION COMPONENTS
The following items are available for use in the
installation of this appliance.
Outside Combustion Air Kits
(with duct)UZI
(without duct)UZIDF
Firestop Spacer (Flat)63L31F8FS-2
Combination
Offset/Return Elbow63L28FTF8-OR15
Storm Collar63L59FSC
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Cold Climate Kits63L61FTF8-CCK1-LD
21
Page 22
INSTALLATION COMPONENTS
Chase Termination
(Square)63L51FTF8-CT2
Chase Termination
(Round)63L45FTF8-CTDT
Locking Band63L60FLB
Chase Termination
(Square)63L48FTF8-CT1
Attic Shield Assembly63L67FTF8-FSAS
22
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 23
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
23
Page 24
Lennox Hearth Products Wood Burning
Fireplaces, Stoves and Inserts 20 Year Limited Warranty
THE WARRANTY
Lennox Hearth Products ("LHP") warrants the components of this wood burning factory-built fireplace system, stove or insert manufactured by LHP (LHP System) to be free from
defects in materials and workmanship at the time of manufacture.
REMEDY AND EXCLUSIONS
The coverage of this Warranty is limited to all components of the fireplace system, stove or insert manufactured by LHP, with the exception of optional LHP tempered glass doors.
A separate limited warranty is available from LHP for optional glass doors manufactured by LHP. Ceramic glass doors manufactured by LHP are warranted against thermal breakage
only. LHP warrants the components of this factory-built system manufactured by LHP (LHP System) to be free from defects in materials and workmanship at the time of manufacture.
(1) During the first five years of this Warranty, LHP will, at its option and except for the components listed in subparagraphs (a) through (f), below, provide replacement or repair
components of the LHP System manufactured by LHP, at no charge, and will also pay for reasonable labor costs incurred in replacing or repairing such components. If repair
or replacement is not commercially practicable, LHP will, at its option, refund the purchase price of the LHP Fireplace, Stove or Insert and LHP Chimney Components and
Accessories. With respect to the components listed below, the remedies of this paragraph (1) are available only for the period of time indicated. Thereafter, however, until the
expiration of 20 years from date of installation, LHP will, subject to the conditions of paragraph (3) below, provide replacements or repairs for those components at 50% off the
then prevailing factory list prices for those components.
a. Cast iron, iron, or steel fuel grates are considered consumable accessories and therefore are not warranted, with the exception of defects in material or workmanship.
b. Fireplace screens, interior refractories, and side shields (metal or refractory) - two years from date of installation.
c. Electrical components, such as fan motors and blowers - one year from date of installation (light bulbs are excluded).
d. Certain model fireplaces are supplied with standard glass doors which are warranted 90 days from the date of installation for defects in material and workmanship.
Replacement glass for fireplaces utilizing tempered glass will be supplied at no-charge during the terms of the 90 day limited warranty with the following exceptions:
Accidental glass breakage or damage to the glass door frame finishes incurred in transit, handling or operation either before, during or after installation.
e. Certain fireplaces, stoves and inserts are supplied with ceramic glass, which is warranted against thermal breakage only for 2 years from date of installation.
LHP will assume no responsibility for glass replacement labor costs.
f. Certain fireplaces, stoves and inserts are supplied with catalysts, which are warranted for a period of six years. Warranty coverage for years three - six will be pro-
rated from time of installation.
g. Air tubes, baffles and brick retainers - one year from date of installation.
h. By-pass damper assembly (catalytic models only) - five years from date of installation.
(2) During the sixth through tenth year of the Warranty, LHP will, at its option, provide replacement or repair components at no-charge, except as is provided for the components
listed in subparagraph (a) through (e) above. This coverage provides for parts only and does not include any labor.
(3) During the eleventh through the twentieth year of the Warranty, LHP will, at its option, provide replacement or repair components at 50% off the then prevailing factory list prices
for those components. This coverage only provides for the purchase of replacement or repair components at discount and does not include any labor.
This Warranty covers only parts, and in some instances labor (as provided in subparagraph (1) above). In no case shall LHP be responsible for materials, parts or construction which
were not manufactured or supplied by LHP or for the labor necessary to install, repair, or remove such materials, parts or construction. All replacement or repair components will
be shipped F.O.B. the nearest LHP factory.
QUALIFICATIONS TO THE WARRANTY
The complete fireplace Warranty outlined above is further subject to the following qualifications:
(1) The factory-built fireplace system, stove or insert manufactured by LHP (LHP System) must be installed in accordance with LHP installation instructions and local building codes.
The Warranty on this LHP system manufactured by LHP covers only the component parts manufactured by LHP. The use of components manufactured by others with this LHP
System could create serious safety hazards, may result in the denial of certification by recognized national safety listing agencies, and could be in violation of local building codes.
This Warranty does not cover any damages occurring from the use of any components not manufactured or supplied by LHP. Any modifications to the system or the retro-fitting
of any appliance to the system which alters the function or performance of the appliance will void this Warranty.
(2) The factory-built fireplace system, stove or insert manufactured by LHP (LHP System) is subjected to normal use with fuels stated in the Home Owners Manual. Factory-built
fireplace system includes burning such natural fireplace fuels as wood and natural or propane gas. Fuel products with abnormal burning characteristics, including but not limited
to fuel such as driftwood, coal or plywood and wood products using a binder, may burn at excessive temperatures and may cause damage to the factory-built fireplace or may
cause it to function improperly; stoves and inserts are approved for burning dry seasoned wood only.
(3) Coverage of this Warranty is conditional upon use of an adequate fireplace grate on factory-built fireplaces only, when applicable. Coverage of this warranty for stoves and inserts
is that these appliances are operated without the use of grates, irons or any other method to elevate the fire.
(4) LHP is not responsible for inadequate fireplace, stove or insert system draft caused by air conditioning, heating, mechanical systems, or general construction conditions which
may generate negative air pressure in the room in which the appliance is installed. Additionally LHP assumes no responsibility for smoking conditions caused by inadequate
chimney heights from adjoining trees or building, adverse wind conditions or unusual environmental factors and conditions.
LIMITATION ON LIABILITY
It is expressly agreed and understood that LHP’s sole obligation and purchaser’s exclusive remedy under this Warranty, under any other warranty, expressed or implied,
otherwise, shall be limited to replacement, repair, or refund, as specified above.
In no event shall LHP be responsible for any incidental or consequential damages caused by defects in its products, whether such damage occurs or is discovered before or
after replacement or repair, and whether or not such damage is caused by LHP’s negligence. Some states do not allow the exclusion or limitation of incidental or consequential
damages, so the above limitation or exclusion may not apply to you. The duration of any implied warranty with respect to this LHP fireplace is limited to the duration of the
foregoing warranty. Some states do not allow limitations on how long an implied warranty lasts, so the above may not apply to you.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
LHP reserves the right to investigate any and all claims against this Warranty and to decide upon method of settlement.
LHP IS NOT RESPONSIBLE FOR WORK DONE WITHOUT WRITTEN CONSENT
LHP shall in no event be responsible for any warranty work done without first obtaining LHP’s written consent.
DEALERS HAVE NO AUTHORITY TO ALTER THIS WARRANTY
LHP’s employees and dealers have no authority to make any warranties nor to authorize any remedies in addition to or inconsistent with those stated above.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this Warranty to be valid, LHP must be notified of the claimed defect in writing to Lennox Hearth Products, attention Customer Service Department, 1110
West Taft Avenue, Orange, CA. 92865, as soon as reasonably possible after the defect is discovered. Claims against this Warranty in writing should include the date of installation,
and a description of the defect.
OTHER RIGHTS
This Warranty gives you specific legal rights, and you may have other rights which vary from state to state.
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.