Lennox ELITE ME43 Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
43" Wood Burning Fireplaces P/N 850,027M REV. A 05/2005
MODELS
ME43
This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and under­stand these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any circumstances. Any modification or alteration of the fireplace system, including but not limited to the fireplace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS: INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION, USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.
Listed to standard: ULC-S610 UL-127
A French manual is available upon request. Order Form Number 850,027CF.
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce 850,027CF.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
PIME43
1
Page 2
TABLE OF CONTENTS
Safety Rules .................................... page 2
Fireplace maintenance
Creosote .......................................... page 2
Chimney maintenance ..................... page 3
Chimney fires .................................. page 3
Glass cleaning ................................. page 3
Doors adjustment ........................... page 3
Glass replacement........................... page 3
Removal of ashes............................ page 3
Fireplace operation
Fuel.................................................. page 4
First fires ......................................... page 4
Building a fire .................................. page 4
Using the retractable
doors and firescreens ................... page 4
How to use the outside air kit ......... page 4
Fireplace installation
Recommendations .......................... page 4
Tools and building supplies ............ page 5
Installation procedure ..................... page 5
Locating the fireplace...................... page 5
Adjacent walls ................................. page 5
Enclosure ........................................ page 5
Facing and mantel ........................... page 6
Hearth extension ............................. page 7
Outside air installation .................... page 7
UZY3 fan kit installation .................. page 8
Central forced air kit........................ page 8
CHIMNEY SYSTEM ................... page 9
Framing Specifications .................... page 10
Installing the Chimney System ........ page 11
30° Offset through Floor/Ceiling ...... page 12
Ten Foot Rule Summary .................. page 14
Multiple Terminations ...................... page 14
Chimney Component Calculations ... page 14
Special Offset Instructions............... page 14
Offset Calculations........................... page 15
Vertical Elevation Chart ................... page 15
Offset Elevation Chart ..................... page 16
Installing Offsets.............................. page 17
Parts and Components ................... page 18
Appendix
(Specifications, Clearances) ......... page 18
Replacement parts, Options............ page 19
Fireplace Dimensions ...................... page 20
Installation Components ................. page 21
SAFETY RULES FOR OPERATING YOUR FIREPLACE MODEL ELITE ME43
WARNING: AN OUTSIDE AIR KIT MUST BE INSTALLED ON THE FIREPLACE MODEL ELITE ME43.
WARNING: THE FIREPLACE MUST BE OPERATED WITH THE DOORS FULLY OPENED OR FULLY CLOSED. IF THE DOORS ARE LEFT PARTLY OPENED, GAS AND FLAME MAY BE DRAWN OUT OF THE FIREPLACE OPENING, CREATING RISKS OF BOTH FIRE AND SMOKE.
Use only Lennox Fireplace glass doors, spe-
cifically designed for the model ELITE ME43 fireplace. (See Appendix for part number).
Always keep the fire screen or the doors
closed and the damper opened when using the fireplace. Keep the damper closed when the fireplace is not in use.
The ME43 fireplace is sold with a steel log
grate. If you have to replace it, we recom­mend for optimum efficiency, to replace it with an identical or similar Lennox model grate.
A fireplace insert heating unit may be in-
stalled in the fireplace only if this unit has been certified with the ME43 fireplace.
This fireplace must be installed with Secu-
rity Chimneys FTF8 (8" inside diameter) chimney System only. These systems are intended for use in any application where a traditional masonry type fireplace would apply. The chimney system must always vent to the outside of the building.
This fireplace has been tested for installa-
tion in Canada to CAN/ULC S610-M87 and ANSI/UL 127-1996 under report number 192-5166. For installations in Canada,
the chimney clearance to combustibles must be 2 inches and the Cold Climate Kit must be installed.
The minimum installed height of the com-
pleted fireplace system is 15' 0". The maxi­mum height is 60' 0".
CAUTION: NEVER USE GASOLINE, KERO­SENE, CHARCOAL LIGHTER FLUID OR SIMI­LAR LIQUIDS TO START OR "FRESHEN UP" A FIRE IN THIS FIREPLACE. KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE FIREPLACE AT ALL TIMES.
CAUTION: KEEP COMBUSTIBLE MATERIALS AT LEAST 48 INCHES AWAY FROM THE FRONT OF THE FIREPLACE OPENING.
CAUTION: NEVER LEAVE CHILDREN UNAT­TENDED WHEN THERE IS A FIRE BURNING IN THE FIREPLACE.
CAUTION: THIS APPLIANCE IS DESIGNED FOR USE WITH WOOD OR CERTIFIED PRO­CESSED SOLID FUEL FIRE LOGS. DO NOT POKE OR STIR THE LOGS WHILE THEY ARE BURNING. USE ONLY FIRE LOGS THAT HAVE BEEN EVALUATED FOR THE APPLICATION IN FIREPLACE AND REFER TO FIRE LOG WARN­INGS AND CAUTION MARKINGS ON PACKAG­ING PRIOR TO USE.
WARNING: THIS FIREPLACE IS NOT APPROVED WITH AN UNVENTED GAS LOG SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN UNVENTED GAS LOG SET INTO THIS FIREPLACE.
FIREPLACE MAINTENANCE
CREOSOTE
When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form a black deposit called creosote. The creosote vapors con­dense in the relatively cool chimney flue of a slow burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire. If the creosote accumulation is large, a creosote fire in the chimney can damage the chimney and overheat the surrounding wood framing. Creosote formation in a chimney can be mini­mized by making small hot fires rather than slow burning, smouldering fires.
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 3
CHIMNEY MAINTENANCE
Door Frame Care
Glass Replacement
Regular chimney inspection and maintenance combined with proper operation will help pre­vent chimney fires. Keep your chimney clean. Do not allow more than a 1/16" (1.6 mm) build­up of creosote in your chimney. The amount of creosote will depend on variables such as frequency of use and type of fire. We recom­mend that you follow the instructions below:
1. Initially, inspect the chimney system weekly. By doing this, you will learn how often it will be necessary to clean your chimney.
2. Have your chimney cleaned by a qualified chimney sweep. Chimney maintenance should only be conducted by a qualified technical or chimney sweep company.
3. Do not expect chemical cleaners to keep your chimney clean.
The raincap can be removed for inspection and/or cleaning of the chimney. Unscrew the braces which attach the raincap to the chim­ney. Using gloves, firmly grip the upper por­tion of the rain cap. Turn the cap and lift it off the chimney.
CHIMNEY FIRES
If you are having a chimney fire, follow these steps:
1. Close the glass doors and the air inlet.
2. Close the chimney outside air register.
3. Alert your family of the possible danger.
4. If you require assistance, alert your fire department.
5. If possible, use a dry chemical fire extin­guisher, baking soda or sand to control the fire. Do not use water as it may cause danger­ous steam explosions.
6. Watch for smouldering or fire on combus­tibles next to the fireplace and chimney. Check outside to ensure that sparks and hot embers coming out of the chimney are not igniting the roof.
7. Do not use the fireplace again until your chimney and fireplace have been inspected by a qualified chimney sweep or a fire department inspector.
Use a glass cleaner and a soft cloth to polish the frame. Do not use abrasives such as steel wool or steel pads for they may scratch the door frame finish.
Glass Cleaning
The ELITE ME43 is designed to keep the glass clean under normal operating conditions. To clean the glass there are a number of spe­cially designed cleaners. Your authorized LHP Dealer can recommend a suitable cleaner. Regular household glass cleaners will not clean creosote. Do not use abrasives such as steel pads, steel wool or oven cleaner as they will scratch the glass.
Doors Adjustment
Glass doors may lose their adjustment during transportation or installation of the fireplace. A wrong adjustment may cause a loss in combustion’s efficiency and control. The glass doors must be parallel, at the same height and must almost touch each other when closed. Maximum spacing between the doors is one sixteenth of an inch (1/16’’).
The glass doors can be adjusted by loosening the three (3) screws of the hinges’ supports (see fastening screws in figure 1). If a minor angular adjustment is needed, you may loosen only two (2) of the three (3) screws using the other as a pivot point.
Fastening
Screws
The glass used for the ELITE ME43 doors is a high temperature ceramic glass. If the glass breaks, it must be replaced with a ceramic glass such as Neoceram. Tempered or ordinary glass will not withstand the high temperatures of the ELITE ME43. Replacement glass should be purchased from your local LHP dealer. Do not operate the unit with cracked or broken glass. To remove the glass panel, unscrew the frame screws, remove the interior frame and the glass panel.
Removal Of Ashes
Remove ashes only when the fire is out and the ashes are cold. Lift the front of the log grate until it rests against the rear refractory; then remove the ashes. Ashes should be placed in a metal container with a tight-fitting lid. The closed container of ashes should be placed on a non-combustible floor or on the ground, well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have thoroughly cooled. Do not leave the ashes in the house as they give off carbon monoxide and other toxic gases.
Frame Screws
Interior Frame
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
Page 4
OPERATING THE ELITE ME43
Fuel
The Elite ME43 is designed to work best when fueled with seasoned cordwood. Hardwoods are preferred to softwoods since the energy content of wood is relative to its density. Hardwoods will result in a longer burning fire and less frequent refueling. A moisture con­tent of 15% to 20% (seasoned) is preferred. Excessively wet wood will be difficult to burn and will result in lower efficiency and in­creased creosoting.
Do not burn scrap or garbage, treated wood or wood such as driftwood from the ocean which has been exposed to salt or other chemicals. Salt or chemicals can corrode the firebox and chimney. Do not abuse the unit by burning large amounts of paper, cardboard, Christmas tree branches or building construction mate­rials such as pressed wood, plywood or lum­ber. Intense firing with these may overheat the fireplace, causing damage to the unit, a fire, or even possibly igniting a chimney fire, if the chimney is creosoted.
HOW TO USE THE RETRACTABLE DOORS AND FIRESCREENS
The Lennox Fireplace Model ME43 features retractable doors and firescreens in order to allow a wider view of the fire and save space when the doors are opened. To retract the doors, simply open them at 90° and push them into the opening on the side of the firebox. The same procedure applies for the retractable firescreens. (
Note : Do not operate the fireplace with both fire-screen and doors closed at the same time.
see Figure 2
).
HOW TO USE THE OUTSIDE AIR REGISTER (FIREPLACE)
The outside air register is located on the upper part of the top louver. The outside air register supplies oxygen to the fire and allows control of the fire when the doors are closed. The fresh air must come from outside the house (the air intake must not draw air from inside the house). This will minimize negative pres­sure in the house. The more you slide the register to the left, the more fresh air into the firebox and the more accelerated combustion you will get (
see Figure 3
). When starting a
fire, the register should always be fully opened.
FIREPLACE INSTALLATION
Please Read Before Installing:
1. Before beginning the installation of your fireplace, read these safety tips and installa­tion instructions carefully to be sure you understand them completely. Failure to follow them could cause a fireplace mal­function resulting in serious bodily injury and/or property damage.
First Fires
The first 5 or 6 fires should be small fires of short duration (about 30-60 minutes). The first fire should be especially short. This will help cure the refractory bricks. The first fires may produce slight smoking due to drying of the paint and steel and any dust accumulated on the fireplace will be burn off at this time. For this reason the room should be well ventilated during the first few fires.
Building A Fire
To start a fire, place several crumpled up balls of newspaper in the firebox. Place small dry pieces of kindling on top of the paper, criss­crossing the kindling so that there is airspaces in between. Place the larger pieces of kindling on top of the pile. Keep the fuel far back enough so that air can get underneath. Open the air control fully and light the newspaper. Once the kindling fire is well established, cordwood can be added.
The unit will burn best with a minimum of two pieces of cordwood spaced 1" to 2" apart and allowing air to get under the fuel. Crisscross­ing or arranging the fuel so that air can get underneath, will help the fire to get started easily.
Figure 2
Figure 3
PUSH TO OPEN
2. The ME43 fireplace has been tested and listed to UL and ULC standards by Warnock Hersey International Inc. These instruc­tions were written to give you an outline for a fast and safe installation and trouble-free operation.
PUSH TO OPEN
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 5
OPENING
WALL
FIREPLACE
STANDOFFS
18"
(460mm)
45
°
Failure to use LHP parts or conduct varia­tions in techniques and construction materi­als described in this installation manual may create a serious fire hazard and may void the warranty and the WHI listing.
3.
Always check your local building codes. The installation must comply with their regulations. Before beginning the installa­tion, consult the local authorities and make sure your building permit complies with their requirements.
4. These fireplaces must be installed with Se­curity Chimneys FTF8 (8" inside diameter) chimney System only. These systems are intended for use in any application where a traditional masonry type fireplace would apply. The chimney system must always vent to the outside of the building.
5. To maintain top efficiency and to prevent build-up of soot and creosote, inspect and clean the chimney periodically during the heating season.
6. To prevent possible hazards due to poor combustion and to avoid affecting other fuel burning appliances (furnace, wood stove, etc.), ensure that the outside air kit is prop­erly installed.
7. This fireplace is designed to allow the instal­lation of a gas burner. In such a case, the installation must conform with the National Gas Code ANSI Z223.1 and Z21.60.
WARNING: WHEN USING A GAS BURNER, IT IS MANDATORY TO KEEP THE CHIM­NEY OUTSIDE AIR REGISTER OPENED.
8. This fireplace has provision for the installa­tion of a gas pipe and is intended connection to a decorative gas appliance incorporating an automatic shutoff device and complying with ANSI Z21.60-M96/CGA
2.26-M96, Standard for Decorative Gas Ap­pliances for Installation in Solid-Fuel Burn­ing Fireplaces (reference Clause 4.1.3 T).
9. ELITE ME43 fireplaces are sold with factory installed doors. The outside combustion air kit is mandatory and is included with the fireplace. Optional blowers and decorative trims are available.
only for
Tools And Building Supplies Normally Required
Tools: Phillips screwdriver
Slot style screwdriver Hammer Saw and/or Sabersaw Level Measuring tape Plumb line Electric drill and bits Pliers Square
If gas pipe is used: Pipe wrench
Pipe cutter Pipe threader Pipe joint compound Pipe key valve
Building supplies: 2" x 3" or heavier lumber
Drywall panel or equivalent Silicone caulking (non-combustible) Overlay material for fireplace façade Hearth extension (non-combustible)
PRECAUTIONS!
The most important areas of concern dealing with the fireplace installation are clearances to combustible materials, secure assembly of components parts, the height of the chimney system, the proper use of accessory equip­ment and the techniques used in using finish­ing materials applied to fireplace surrounds, hearth extensions and wall coverings. Each of these topics will be covered in greater detail throughout this manual. Please give special
attention to these instructions as you progress with your installation.
Fireplace Installation Procedure
1. Move the fireplace into the desired position (follow the recommendations below for en­closure).
2. Install the outside air assembly (or assem­blies) - refer to page 7.
3. Install the enclosure surrounding the fire­place (refer to the sections “Enclosure” be­low and “ Facing and Mantel” on page 6).
4. Install the hearth extension (see page 7). Make sure the gap between the fireplace and the hearth extension is sealed.
LOCATING THE SECURITY FIREPLACE
Do not place the fireplace on carpeting, vinyl or other soft surface floor coverings. It may, however, be directly placed on flat wood, ply­wood, particle board or other hard surface materials.
ADJACENT WALL
A wall perpendicular to and in front of the fireplace front facing must be at least 18" (460 mm) from the fireplace opening. A wall at 45º to the front facing and starting at the fireplace’s outer edge is permitted. Projections within this area are permitted.
See Figure 4
.
Figure 4
ENCLOSURE
WARNING: DO NOT PLACE LOOSE INSU­LATION OR ANY OTHER MATERIAL IN THE SPACE AROUND THE FIREPLACE OR THE CHIMNEY. INSULATION PLACED ON OR AROUND THE FIREPLACE OR CHIM­NEY MAY CAUSE ADJACENT WOOD TO OVERHEAT AND CATCH ON FIRE.
1. The fireplace must be installed against a finished wall (like drywall finish). It must not be installed against a vapor barrier or ex­posed insulation (
2. Combustible materials like wood, plywood, particle board or drywall can be in direct contact with the fireplace standoffs. Two
inch (50 mm) clearance to combustibles must be kept around the chimney.
see Figure 5
).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
Page 6
WARNING: THE TOP OF THE FIREPLACE IS NOT ZERO CLEARANCE. DO NOT PLACE ANY INSULATING MATERIAL IN THE SPACE ABOVE THE FIREPLACE FOR A HEIGHT OF 7 FEET FROM THE BASE OF THE FIREPLACE.
3. Do not block the fireplace’s hot air vents or air inlets as this will cause the fireplace to overheat.
Fireplace Facing
The fireplace should be framed using 2" x 3" (50 mm x 75 mm) or heavier lumber.
Figure 10
Combustible materials must be installed flush with the fireplace facing. They may not project out in front of the fireplace. Non-combustible materials such as brick, stone or ceramic tile, may project in front of and/or on the fireplace facing.
shows the general framing layout.
GYPROC
2" x 3" MIN.
SPACER
FIREPLACE
Figure 6
ROOF SUPPORT
ATTIC
FIRESTOP
7 ft. Min.
FLASHING
NON COMBUSTIBLE CHASE TOP
WARNING: THE HEADER SHOULD REST ON TOP OF THE METAL SPACERS. DO NOT ALTER THE SPACERS OR NOTCH THE HEADER TO FIT AROUND THEM. DO NOT BLOCK THE AIR INLET OR OUTLET
CEILING/FLOOR SEPARATION
AS THIS WILL CAUSE THE FIREPLACE TO OVERHEAT.
Mantel
A wood mantel, if installed, must be at least 48" (1.2 m) above the base of the fireplace (
MUST HAVE THE SAME FIRE RATING
2"
AS ADJACENT CEILING. MUST HAVE THE SAME INSULATION
AS ADJACENT CEILING. LOCAL CODE REGULATION FOR CEILING
MUST BE APPLIED TO THE CEILING/FLOOR SEPARATION, I.E. FIRESTOP, ETC.
FINISHED WALL
Figure 7
the length or the width of the mantel.
). There is no restriction regarding
see
FIREPLACE
NOTE: Chase wall and floor must be insulated in the same manner than the rest of the building below the attic.
Figure 5
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
48"
18"
Figure 7
8"
1"
52"
Page 7
Hearth Extension Requirements
A non-combustible hearth extension must be built in front of the fireplace and extend out on both sides. Hearth extensions must be con­structed according to the following guidelines:
1. A layer of sheet metal 0.018" (0.45 mm) thick or 3/8" (9 mm) thick milboard or any other material (tiles, marble, granite) with equivalent heat resistance may be used. Check with the local building authorities before installing to determine what other materials are acceptable in your area.
2. The hearth extension should be secured to the floor. The gap between the fireplace and the hearth extension must be sealed with non-combustible caulking or cement.
3. On a raised base or raised hearth, a “Z” shape piece of metal must be fabricated to join the bottom of the fireplace to the floor.
Outside Air Assembly
The outside air assembly is mandatory for the fireplace
.
Outside Air Installation
The outside air assembly must be installed according to the following guidelines:
1.The maximum length of 4" I.D.(100 mm)
insulated flexible duct is 20 ft (6.1 m ). If a longer duct is required, use a 6" I.D (150 mm) insulated flexible duct. The maximum length is 40 ft (12 m ). Refer to figures 8b and 8c for connections.
2.The duct and register may be installed above
or below floor level.
3.The outside air register must not be in-
stalled more than 7 feet (2.1 m) above the base of the fireplace.
4.The outside air assembly must draw air
from outside the house. It must not draw air from the attic, the basement or a garage.
5.Locate the outside register where it will be
well away from automobile exhaust fumes or other vents.
6.The outside air register should be installed
where it is not likely to be blocked by snow or exposed to extreme wind
7.It is recommended to install the outside air
register at floor level. However, if you must raise the air register above the fireplace level, you will have to make a loop to the floor with the flexible pipe to prevent from causing a draught in the outside air register (
see Figure 8 Detail A
).
During operation, the fireplace requires air for combustion and draws air out of the house. It may starve other fuel burning appliances such as gas or oil furnaces. As well, exhaust fans and fan driven appliances may compete for air, causing a negative pres­sure in the home, resulting in smoke entering the home from the fireplace. This situation is aggravated in modern airtight houses.
To overcome this potential problem, the in-
stallation of an outside air assembly is required to provide outside combustion air
to the fireplace.
7' MAX.
FIREPLACE
CONNECTION
ALUMINIUM
FLEXIBLE
PIPE
TAPE
PLASTIC COVER
LOOP IS MANDATORY
OUTSIDE AIR CONNECTION TO THE FIREPLACE
FIREPLACE
(Detail B)
(Detail A)
FACING DOWN
OUTSIDE AIR CONNECTION
OUTSIDE
INTAKE
SCREW
OPENING
WALL
ALUMINIUM TAPE
FLEXIBLE PIPE
(Detail C)
PLASTIC COVER
INSULATION
Figure 8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
Page 8
INSTALLATION OF THE FAN KIT MODEL UZY3
Note: This fan kit can easily be installed when
the fireplace has a pre-installed junction box. You just have to plug them in.
Rating: 120 Volts, 60Hz, .63A.
The fans have magnetic blower mounts. The junction box (factory installed on approved fireplaces for the use of this fan kit) must be connected to 110 VAC service before perma­nently enclosing the fireplace. The access hole for connecting the 110 VAC is located on the lower right exterior side of the fireplace.
Installation instructions:
1. Open the bottom louver of the fireplace.
2. Place each fan kit into the fireplace side
opening 1" from the back of the fireplace.
3. Install the automatic fan activator on the
side of the firebox (the fan activator has a magnetic mount).
4. Plug the fan kit into the junction box.
5. Ground both fans to the back panel using
the green screws.
INSULATED
FLEX PIPE
Figure 9
NOTE: The fireplace must be electrically con-
nected and grounded in accordance with local codes or in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code. For U.S.A. installations, follow local codes and the National Electrical Code ANSI/NFPA No 70.
CAUTION: SHOULD THIS FAN REQUIRE SER­VICING, THE POWER SUPPLY MUST BE DIS­CONNECTED.
These fans require periodic maintenance. Check the area in front of the fans and wipe or vacuum at least once a month during the burn season.
7' MIN.
Figure 10
43 1/4"
2" X 3" MIN.
27 1/2"
42 1/2"
ROUGH FRAMING FACE (UNFINISHED SHOWN)
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 9
Insulate Joists Same As Ceiling
Draft Stops
Firestop
CTDT Termination
Note: Non­Combustible Chase Flashing Must Be Used To Cover Chase Opening
Insulation (Thermal Barrier)
Figure 11
8'
Level
Optional Insulation In Outside Walls Of Chase
Solid Continuous Surface
Outside Base
CHIMNEY SYSTEM
These fireplaces are designed and code listed for use with Security Chimneys FTF8 chimney System only. Always use Security Chimneys FTF8 chimney components with these fire­places. Do not modify or alter these compo­nents as this may cause a potential serious hazard and void the Warranty.
*Construction Materials:
• framing materials • paneling
• particle board • flooring
• millboard • dry wall
• plywood • etc.
Note: 2" clearance to combustibles around chimney components required.
WARNING: IF INSULATION IS USED, THE FIREPLACE MUST NOT BE PLACED DI­RECTLY AGAINST IT. INSULATION OR VAPOR BARRIERS, IF USED, MUST FIRST BE COVERED WITH GYPSUM BOARD, PLYWOOD, PARTICLE BOARD OR OTHER MATERIAL TO ASSURE INSULATION AND VAPOR BARRIERS REMAIN IN PLACE.
WARNING: DO NOT PACK OR FILL RE­QUIRED AIR SPACES WITH INSULATION OR OTHER MATERIAL. NO MATERIAL IS ALLOWED IN THESE AREAS.
Note: Do not insulate the chase cavity with
blown or fill type insulation materials.
Note: Local codes may not require firestopping at the ceiling levels for outside chase installa­tions. However, it is recommended for safety and the reduction of heat loss.
Chimney Height
The total height of your completed fireplace system from the surface the fireplace rests on to the chimney top must not exceed 60' and must also meet minimum height requirements. Refer to the minimum system height chart.
Minimum System Height
Security's FTF8 Pipe
Vertical Installation 15' 0"
One Offsets 15' 0"
Two Offsets 25' 0"
Chase Enclosure
A chase is a vertical box-like structure con­structed to surround the fireplace and chimney. Refer to
Figure 11
ration. As with all chimney installations, avoid overhead obstructions such as trees, power lines, etc. A chase should be constructed and insulated just like any outside wall. In a cold climate, we recommend the base of the chase should also be insulated between the solid continuous floor beneath the fireplace and the chase bottom. Chase insulation in a cold cli­mate installation is not required for safety.
for a typical chase configu-
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Page 10
FRAMING SPECIFICATIONS
For Canadian Installations Proceed with Steps 1 through 4
Figure 12
Framing Dimensions for Ceiling
Step 1. Attach the cold climate kit, Model
FTF8-CCK1-LD, around the chimney collar with
Flue Type A B
FTF8 Vertical 16 ¹⁄₂" 16 ¹⁄₂" at 2" (419 mm) (419 mm)
the screws provided (
Note: CCK1-LD model requires a 6" diameter Class 0 metallic air duct, acquired locally by
see Figure 14
).
installer.
FTF8 Offset 30° 16 ¹⁄₂" 27" at 2" (419 mm) (686 mm)
Figure 14
Step 2. Connect the 6" (152 mm) Class 0
B
A
Ceiling Framing
D
Figure 13
C
Roof Framing
metallic air duct to the collar on the chimney collar enclosure with the screws provided in the hardware kit.
Step 3. Route the Class 0 metallic air duct out the back wall or side wall, up through the ceiling or floor joists to an outside wall. The air duct’s inlet should be located above any anticipated
Framing Dimensions for Roof
snow level.
FTF8 at 2"
Pitch C D*
0/12 16 ¹⁄₂" 16 ¹⁄₂"
(419 mm) (419 mm)
6/12 16 ¹⁄₂" 19"
(419 mm) (483 mm)
12/12 16 ¹⁄₂" 23 ¹⁄₂"
(419 mm) (579 mm)
* Perpendicular to roof ridge
Note: If the fireplace is installed against an inside wall, the Class 0 metallic air duct may be ex­tended into a ventilated attic space at least 18" (457 mm) above the attic floor. Secure the duct hood to a vertical post with the inlet positioned downward. Ensure that nothing blocks the hood opening. This air duct must never terminate higher than the fireplace chimney.
Step 4. Cut or frame a hole through the outside wall for the installation of the duct inlet hood. A 6 ¹⁄₂" (165 mm) diameter hole is required. Feed the loose end of the flexible duct through the hole cut for the inlet hood and attach to the collar on inlet hood using two (2) screws. Insert the hood into the opening. Secure in place with nails driven through the holes in hood flange. Seal with noncombustible waterproof silicon type caulking. If additional air duct is needed, use Class 0 metallic duct.
10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 11
INSTALLING THE CHIMNEY SYSTEM
Step 1. Before continuing, check the operation
of the damper.
Step 2. Using standard construction framing techniques, construct opening for chimney route up through the ceiling(s) and roof or through an outside chase.
Framing must maintain adequate minimum air space clearance at all times.
CAUTION: ALLOW MINIMUM 2" CHIMNEY AIR SPACE TO COMBUSTIBLE FRAMING MEM­BERS THROUGHOUT VERTICAL OR OFFSET CHIMNEY INSTALLATION.
A minimum 2" air space must be reserved for all combustible materials extending for any continuous length surrounding the chimney.
Reference ing Dimensions for Ceiling and Roof, which specify minimum ceiling and roof dimensions.
Figures 12 and 13
and charts Fram-
Step 3. Position appropriate firestop spacer at ceiling and nail temporarily with two (2) 8d nails. Use flat firestop spacer, Model F8FS-2, if chimney penetrates ceiling vertically. If chim­ney penetrates ceiling at 30° angle (offset chimney), use 30° firestop spacer, Model F8FS30. Use one nail on opposite sides to hold firestop spacer in position. Nail permanently, using at least two (2) more 8d nails, after chimney sections have been assembled through the firestop spacer and after any nec­essary adjustments have been made. Firestop spacer must be secured by at least four (4) 8d nails when completely installed.
Note: If there is a room above ceiling level, firestop spacer must be installed on the bottom side of the ceiling. If an attic is above ceiling level, firestop spacer must be installed on top side of ceiling joist (Figures 16 and 17 ).
Room Above
F8FS30-2 Firestop Spacer
2" Min.
Air Space
Figure 18
F8FS30-2 Firestop Spacer
2" Min.
Air Space
Attic Space
10'
Max.
Room Above
10'
Max.
2" Min.
Air Space
FTF8-S4 Stabilizer
30° Firestop And Attic Above
2" Min.
Air Space
FTF8-S4 Stabilizer
30° Firestop And Room Above
In new construction, to determine chimney cen­ter line, use plumb line from roof or ceiling above fireplace to center of flue collar on fireplace.
For remodeling, plumb to center of flue collar from ceiling above, drive nail through ceiling from below to mark position, then mark and cut to passage from above ceiling (around nail) (
see Figure 15
). Then plumb from ceiling or roof level directly above hole which has just been completed.
Figure 15
Firestop Spacer
Figure 16
Attic Above
Firestop Spacer
Figure 17
CHIMNEY 30° OFFSET THROUGH FLOOR OR CEILING
It may be necessary to assemble the chim­ney at 30° when passing through the floor or ceiling area. Use the F8FS30-2 firestop spacer as shown in Support the chimney at floor or ceiling pen­etration with a FTF8 stabilizer if distance of chimney below ceiling is 10' or more. Main­tain 2" minimum air space to combustibles from chimney sections.
Figures 18 and 19
Figure 19
Required For Canada
When installing the chimney system through an open attic space, the attic shield assembly­firestop spacer must be used ( installation is required only for use in Canada.
Open Attic Space
Figure 20
Note: For Canadian installations, all chimney
installed outside the building must be con­structed with galvalume (outer sections only). The appropriate model designations are lo-
.
cated in the back of this manual.
Note: Attic insulation shield is required in any installation to insure the 2" air space is maintained anywhere "blown in" insulation is used.
Figure 20
FTF8-FSAS
). This
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Page 12
Note:
Step 4.
Chimney sections are constructed with a unique locking tab design, which en­sures an immediate, tight assembly between sections. Plan your chimney requirements carefully before assembly as chimney is diffi­cult to disassemble after installation. If disas­sembled, the tabs might become damaged. Be certain tabs are properly formed to ensure locking tabs engage properly.
The Security Chimney's FTF8 chimney system is a two piece chimney, which snap together from the fireplace up. Start with the inner flue section with the lanced end up, snap lock it in to the matching collar on top of the fireplace. At all subsequent joints, the upper flue section fits into the preceding flue section. Each piece snaps together by means of locking tabs (9 locking tabs per joint). Check each piece by pulling up slightly from the top to ensure proper engagement before installing the next section. If the flue has been installed correctly, it will not separate when you test it. Also, the inner flue joint where each section is joined should be tight and flat without gaps (
Figure 21
).
Figure 21
Outer pipe section installs in just the opposite way; the lanced end goes down and each new section goes OVER the outside of the previous section installed (
Figure 22
).
Locking Tabs (Lances)
Note: Assemble one component of chimney at
a time (inner section first, then outer section last) before proceeding with the next complete section.
Continue to assemble the chimney up through framed opening. Assemble just enough to pen­etrate the roof flashing openings (
Figure 23
). Always maintain 2" minimum air space to com­bustible materials and always check each chim­ney joint (inner and outer) to ensure proper engagement. Check vertical alignment of chim­ney so that it projects from the roof in true vertical position.
2" Min. Air Space To Combustibles
Figure 23
Security's chimney sections do not need to be screwed together. Additional reinforcement is not necessary except in certain offset condi­tions (refer to page 17,
Figure 34
).
Step 5. The height of vertical chimney pipe supported only by the fireplace must not ex­ceed 30'. Chimney heights above 30' must be supported by a Model FTF8-S4 stabilizer in­stalled at 30' intervals.
Note: The Model FTF8-S4 adds 3" net effective height to the total chimney system.
Install the Model FTF8-S4 stabilizer by fitting inner section down into respective section of proceeding flue pipe and locking outer stabi­lizer section into place over the outer chimney pipe. Position for proper clearance through framed opening and nail straps securely (under tension in “shear”) into place on framing. Use 8d nails. Attach successive lengths of chimney pipe directly to stabilizer using same tech­niques as described in Step 4 (
see Figure 24
).
FTF8-S4 Stabilizer
Figure 24
Note: Do not apply excessive pressure to any
subsequent chimney sections following the stabilizer when installing. Ensure each subse­quent chimney section is securely attached by testing as noted in Step 4.
Step 6. Select the proper Security Chimneys roof flashing based on pitch of roof. Use chart below for selection:
Roof Pitch Model
Flat to 6/12 F8F6
6/12 to 12/12 F8F12
Next, slide roof flashing over extended chimney section that previously has been installed above the roof opening in Step 4. Slide flashing all the way down until the flashing base rests flat on the roof (
Figure 25
). Again, check the vertical position of the chimney and the 2" minimum air space to combustibles.
FTF8 Chimney
FTF8 Flashing
Do Not Seal
Figure 25
Note: Do not caulk or seal the ventilating
openings.
Figure 22
12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 13
Step 7. Secure flashing by nailing along the perimeter into roof using 8d nails. If shingled roof, slide upper end and sides of roof flash­ing under shingles (trim if necessary), seal the top and both sides of the flashing to the roof with roof caulking. Cover nail heads with roof caulking (
see Figure 26
).
Step 9. Security Chimneys locking bands, Model FLB, may be required if the chimney extends too high above the roof flashing. As a general rule, if the chimney extends more than 6' above the roof flashing, the use of locking bands is advisable to strengthen the chimney assembly. Align the locking band at the chim­ney joint. Locking bands wrap around pipe joints equally covering the joints of both pipe sections. Use the nut provided and TIGHTEN snugly. Do not overtighten as this might dam­age the chimney section (
refer to Figure 27
CTD
Termination
Chimney
).
Figure 26
Step 8. The standard Security FTF8 roof flash-
ing assemblies include a storm collar. Slide the storm collar over outer chimney, rest on flashing spacers and align with top surface of flashing. Insert tab in slot, pull tight and bend tab back over slot. Seal storm collar to outer chimney with roof caulking or mastic around entire circumference of pipe. Also add extra roof caulking to the tab/slot area to seal com­pletely against water penetration (
Figure 27
Check all joints very carefully to ensure no water intrusion can take place.
Locking Band
Mastic
Note: If chimney extends more than 8' above
roof surface, guy wires are also recommended. Use three (3) guy wires, attach to locking band assembly, extend and secure to roof in a trian­gular pattern (see Figure 28 ). Guy wires are not supplied by the manufacturer.
Roof Ridge
).
120°
Figure 28
Step 10. Using a FTF8-CTD Round Termination:
1. Hold the FTF8-CTD over top of last chimney
section (
Figure 29
).
2. Center inner slip section in inner flue pipe­slip down.
Figure 29
3. Center outer locking section over outer flue
pipe. Push down until locking tabs are firmly engaged.
4. Pull up slightly on CTD to ensure locking joint has firmly engaged.
Using a FTF8-CTDT Chase Termination:
Refer to specific installation instructions in­cluded with the FTF8-CTDT chase termination for clearance and installation details.
Using a FTF8-CT1 Chase Termination:
Refer to specific installation instructions in­cluded with FTF8-CT1 chase terminations for clearance and installation details.
Using a FTF8-CT2 Chase Termination:
Refer to specific installation instructions in­cluded with FTF8-CT2 chase terminations for clearance and installation details.
Figure 27
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
Page 14
Less Than 10'
3'
Min
2' Min.
10'
3'
Min
To determine the number of chimney sections and chimney components required, follow these steps:
1. Determine total vertical height of the fireplace installation. This dimension is the distance from the surface the fireplace sets on to the point where smoke exits from the termination.
2. Determine the number of chimney compo­nents required, except chimney sections. This would include firestop spacers, stabilizers, roof flashing, etc.
3. The effective heights of the components are:
Figure 30
Note: It is recommended that all exterior ex-
posed metal fireplace components; such as ter­minations, flashings, storm collars and/or flue be painted with a premium quality, high tem­perature, rust preventative paint designed for metal. This is especially important when instal­lations are made in abnormally adverse or corro­sive environments; such as near lakes, oceans or in areas with consistently high humidity condi­tions. Consult the paint manufacturers instruc­tions for proper preparation and application.
TEN FOOT RULE SUMMARY
The minimum chimney height above the roof and/or to adjacent walls and buildings is speci­fied by all major building codes.
If the horizontal distance from the peak of the roof is less then 10', the top of the chimney must be at least 2' above the peak of the roof.
If the horizontal distance from the chimney edge to the peak of the roof is more than 10' a chimney height reference point is established on the roof surface 10' horizontally from the chimney edge. The top of the chimney must be at least 2' above this reference point. In all cases, the chimney cannot be less then 3' above the roof at the edge of the chimney.
The 2' in 10' rule is necessary in the interest of safety but does not ensure smoke-free opera­tion. Trees, buildings, adjoining roof lines, ad­verse wind conditions, etc., may require a taller chimney should the fireplace not draft properly (
refer to Figure 30
).
MULTIPLE TERMINATIONS
If more than one termination is located in the same chase or within the same general proxim­ity, we suggest they should be separated in distance at least 24" horizontally from flue cen­ter to flue center and stacked or staggered vertically at least 18" apart, from the termina­tion of one smoke exit to the termination of another smoke exit (
18"
CTDT
24"
Figure 31
24"
).
CTD
18"
CTDT
Figure 31
This suggestion is provided in the interest of better operation. If the terminations are located too close to each other, smoke may migrate from one flue into the other.
FTF8 CHIMNEY COMPONENT CALCULATIONS
The minimum installed height of the com­pleted fireplace system is 15' 0". The maxi­mum height is 60' 0".
The Fireplace = 36 ¹⁄₄" FTF8-12 = 10 ¹⁄₄" FTF8-18 = 16 ¹⁄₄" FTF8-36 = 34 ¹⁄₄" FTF8-48 = 46 ¹⁄₄" FTF8-CTD Termination = 4" FTF8-CT1 Termination = 12" to 18" FTF8-CT2 Termination = 15" to 23" FTF8-CTDT Termination = 12" to 18" FTF8-S4 Stabilizer * = 3"*
* Required for every 30' of vertical chimney and/or 10' of offset chimney.
4. Determine amount of chimney height re­quired by subtracting total combined height of all pre-selected components (fireplace and chimney components from total desired height.)
Reference Vertical Elevation Chart and deter­mine the number of chimney sections (quantity and length) required.
SPECIAL OFFSET INSTRUCTIONS
To clear any overhead obstructions, you may offset your chimney system using Security Chimneys 30° offset and return elbows. Use two elbows - an offset elbow to initiate the offset and a return elbow to terminate it. A 30° offset elbow, angling in any direction, may be the first component used off the top of the fireplace flue collar.
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 15
The offset and return elbows may be attached together, or a section or sections of chimney may be used between, but do not exceed 20' in total length between elbows. If sections of pipe exceed 10' between elbows, a chimney stabi­lizer must be used at the midpoint (
Figure 32
The stabilizer support straps must be attached under tension (in shear) to structural framing members above. When two sets of elbows are used, the maximum combined length of chim­ney used between elbows cannot exceed 20' (
Figure 33
). Example: If C1 = 10' then C2 cannot
exceed 10'.
If an offset exceeds 6' in length, each chimney joint beyond the first 6' of offset to the return elbow, must be secured by a No. 8 x ¹⁄₂" sheet metal screw located at the underside of the joint (
Figure 34
).
A ¹⁄₈" diameter hole must be drilled in the chimney joint using a ¹⁄₈" diameter drill. Hole should be drilled in center of joint overlap (
Figure 35
). Be sure to drill only through the
outer chimney casting. Do not puncture the inner flue.
Maximum offset of chimney system is 30°. Two offsets must not be assembled to form a 60° offset. However, two sets of offset and return elbows may be used on a single flue system, provided the total height of the system exceeds 25'.
Return elbow support straps must be securely attached under tension (in shear) to structural framing members above. Do not substitute a FTF8-30 offset elbow in place of a FTF8-E30 return elbow.
OFFSET CALCULATIONS
Step 1. Use Offset Chart to determine amount
of horizontal offset (A) and height (B) for vari­ous chimney section assemblies.
Step 2. Use “Height of Chimney Only” column in The Vertical Elevation Chart to determine combinations of chimney used above return elbow to achieve desired heights. Reference Components Effective Height Chart in vertical elevation chart section.
Step 3. Use Elevation Chart as job estimator only. Add necessary firestop spacers and stabi­lizers as required. Firestop spacers must be used as shown in stabilizers as shown in
Figures 18 and 19
Figure 24
.
and
FTF8 VERTICAL ELEVATION CHART
Height Of Number Of FTF8
Chimney Only Chimney Lengths
).
Inches Feet/Inches 12" 18" 36" 48"
11 0 11 1 0 0 0 17 1 5 0 1 0 0 21 ¹⁄₄ 19¹⁄₄ 2000 27 ¹⁄₄ 23¹⁄₄ 1100 35 2 11 0 0 1 0 47 3 11 0 0 0 1 51 ¹⁄₄ 43¹⁄₄ 0110 57 ¹⁄₄ 49¹⁄₄ 1001 63 ¹⁄₄ 53¹⁄₄ 0101 67 ¹⁄₄ 57¹⁄₄ 2001 73 ¹⁄₄ 61¹⁄₄ 1101 81 ¹⁄₄ 69¹⁄₄ 0011 93 ¹⁄₄ 79¹⁄₄ 0002
97 ¹⁄₄ 81¹⁄₄ 0111 102 ¹⁄₂ 86¹⁄₂ 1002 109 ¹⁄₄ 91¹⁄₄ 0102 113 ¹⁄₂ 95¹⁄₂ 2002 119 ¹⁄₂ 911¹⁄₂ 1102 127 ¹⁄₄ 10 7 ¹⁄₄ 0012 137 ¹⁄₂ 11 5 ¹⁄₂ 1012 139 ¹⁄₄ 11 7 ¹⁄₄ 0003 143 ¹⁄₂ 11 11 ¹⁄₂ 0112 149 ¹⁄₂ 12 5 ¹⁄₂ 1003 155 ¹⁄₂ 12 11 ¹⁄₂ 0103 159 ³⁄₄ 13 3 ³⁄₄ 2003 165 ³⁄₄ 13 9 ³⁄₄ 1103 173 ¹⁄₂ 14 5 ¹⁄₂ 0013 183 ³⁄₄ 15 3 ³⁄₄ 1013 185 ¹⁄₂ 15 5 ¹⁄₂ 0004 189 ³⁄₄ 15 9 ³⁄₄ 0113 195 ³⁄₄ 16 3 ³⁄₄ 1004 201 ³⁄₄ 16 9 ³⁄₄ 0104 206 17 2 2 0 0 4 212 17 8 1 1 0 4 219 ³⁄₄ 18 3 ³⁄₄ 0014 230 19 2 1 0 1 4 231 ³⁄₄ 19 3 ³⁄₄ 0005 236 19 8 0 1 1 4 242 20 2 1 0 0 5 248 20 8 0 1 0 5 252 21 0 2 0 0 5 258 21 6 1 1 0 5 266 22 2 0 0 1 5 276 23 0 1 0 1 5 278 23 2 0 0 0 6 282 23 6 0 1 1 5 288 24 0 1 0 0 6 294 ³⁄₄ 24 6 ³⁄₄ 0106 298 ¹⁄₄ 24 10 ¹⁄₄ 2006 304 ¹⁄₄ 25 4 ¹⁄₄ 1106 312 26 0 0 0 1 6 322 ¹⁄₄ 26 10 ¹⁄₄ 1016 324 27 0 0 0 0 7 328 ¹⁄₄ 27 4 ¹⁄₄ 0116 334 ¹⁄₄ 27 10 ¹⁄₄ 1007 340 ¹⁄₄ 28 4 ¹⁄₄ 0107 344 ¹⁄₂ 28 8 ¹⁄₂ 2007 350 ¹⁄₂ 29 2 ¹⁄₂ 1107 358 ¹⁄₄ 29 10 ¹⁄₄ 0017 368 ¹⁄₂ 30 8 ¹⁄₂ 1017 370 ¹⁄₄ 30 10 ¹⁄₄ 0008 374 ¹⁄₂ 31 2 ¹⁄₂ 0117 380 ¹⁄₂ 31 8 ¹⁄₂ 1008
Height Of Number Of FTF8
Chimney Only Chimney Lengths
Inches Feet/Inches 12" 18" 36" 48"
386 ¹⁄₂ 32 2 ¹⁄₂ 0108 390 ³⁄₄ 32 6 ³⁄₄ 2008 396 ³⁄₄ 33 0 ³⁄₄ 1108 404 ¹⁄₂ 33 8 ¹⁄₂ 0018 414 ³⁄₄ 34 6 ³⁄₄ 1018 416 ¹⁄₂ 34 8 ¹⁄₂ 0009 420 ³⁄₄ 35 0 ³⁄₄ 0118 426 ³⁄₄ 35 6 ³⁄₄ 1009 432 ³⁄₄ 36 0 ³⁄₄ 0109 437 36 5 2 0 0 9 443 36 11 1 1 0 9 450 ³⁄₄ 37 6 ³⁄₄ 0019 461 38 5 1 0 1 9 462 ³⁄₄ 38 6 ³⁄₄ 00010 466 ³⁄₄ 38 10 ³⁄₄ 0119 472 ³⁄₄ 39 4³⁄₄ 10010 478 ³⁄₄ 39 10 ³⁄₄ 01010 483 40 3 2 0 0 10 489 40 9 1 1 0 10 496 ³⁄₄ 41 4 ³⁄₄ 00110 507 42 3 1 0 1 10 508 ³⁄₄ 42 4 ³⁄₄ 00011 513 42 9 0 1 1 10 519 43 3 1 0 0 11 525 43 9 0 1 0 11 529 ¹⁄₄ 44 1 ¹⁄₄ 20011 535 ¹⁄₄ 44 7 ¹⁄₄ 11011 543 45 3 0 0 1 11 553 ¹⁄₄ 46 1 ¹⁄₄ 10111 555 46 3 0 0 0 12 559 ¹⁄₄ 46 7 ¹⁄₄ 01111 565 ¹⁄₄ 47 1 ¹⁄₄ 10012 571 ¹⁄₄ 47 5 ¹⁄₄ 01012 575 ¹⁄₂ 47 11 ¹⁄₂ 20012 581 ¹⁄₂ 48 5 ¹⁄₂ 11012 589 ¹⁄₄ 49 1 ¹⁄₄ 00112 599 ¹⁄₂ 49 11 ¹⁄₂ 10112 601 ¹⁄₄ 50 1 ¹⁄₄ 00013 605 ¹⁄₂ 50 5 ¹⁄₂ 01112 611 ¹⁄₂ 51 11 ¹⁄₂ 10013 617 ¹⁄₂ 51 5 ¹⁄₂ 01013 621 ¹⁄₂ 51 9 ¹⁄₂ 20013 627 ¹⁄₂ 52 3 ¹⁄₂ 11013 635 ¹⁄₂ 52 11 ¹⁄₂ 00113 645 ¹⁄₂ 53 9 ¹⁄₂ 10113 647 ¹⁄₂ 53 11 ¹⁄₂ 00014 651 ¹⁄₂ 54 3 ¹⁄₂ 01113 657 ¹⁄₂ 54 9 ¹⁄₂ 10014 663 ¹⁄₂ 55 3 ¹⁄₂ 01014 667 ³⁄₄ 55 7 ³⁄₄ 20014 673 ³⁄₄ 56 1 ³⁄₄ 11014 681 ¹⁄₂ 56 9 ¹⁄₂ 00114 691 ³⁄₄ 57 7 ³⁄₄ 10114 693 ¹⁄₂ 57 9 ¹⁄₂ 00015 697 ³⁄₄ 58 1 ³⁄₄ 01114 703 ³⁄₄ 58 7 ³⁄₄ 10015 709 ³⁄₄ 59 1 ³⁄₄ 01015 714 59 6 2 0 0 15 720 60 0 1 1 0 15 727 ³⁄₄ 60 7 ³⁄₄ 00115 738 61 6 1 0 1 15 739 ³⁄₄ 61 7 ³⁄₄ 00016 744 62 0 0 1 1 15
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
Page 16
A
1
OFFSET ELEVATION CHART
B
1
Figure 32
A
A B FTF8-ES30 Number of FTF8 Chimney Sections
Offset Height Offset/Return FTF8-S4
(Inches) (Inches) Elbow Stabilizer 12" 18" 38" 48"
415³⁄₄ 100000
20'
Max.
Return
Elbow
924¹⁄₂ 101000
Stabilizer
12 29 ³⁄₄ 100100 14 ¹⁄₄ 33 ¹⁄₂ 102000 17 ¹⁄₄ 38 ¹⁄₂ 101100
10' Max.
20 ¹⁄₄ 43 ³⁄₄ 100200 21 45 ¹⁄₄ 1 0 0010
Offset Elbow
22 ¹⁄₄ 47 ¹⁄₂ 1 0 2 1 0 0 25 ¹⁄₄ 52 ¹⁄₂ 1 0 1 2 0 0 26 ¹⁄₄ 54 ¹⁄₄ 101010 27 55 ³⁄₄ 100001 28 ¹⁄₄ 57 ³⁄₄ 1 0 0 3 0 0 29 ¹⁄₄ 59 ¹⁄₄ 100110 31 ¹⁄₄ 63 1 0 2010 32 ¹⁄₄ 64 ¹⁄₂ 101001 34 ¹⁄₄ 68 ¹⁄₄ 1 0 1110 35 ¹⁄₄ 69 ³⁄₄ 100101 37 ¹⁄₄ 73 ¹⁄₄ 100210
A
2
38 ¹⁄₄ 75 1 0 0 0 2 0
39 ¹⁄₄ 77 1 0 2110
41 ¹⁄₂ 80 ¹⁄₂ 101400
C
2
A
1
B
2
43 ¹⁄₄ 83 ³⁄₄ 1 0 1 0 2 0 44 ¹⁄₄ 85 ¹⁄₄ 100011 45 ¹⁄₄ 87 ¹⁄₂ 1 0 0 3 1 0
46 ¹⁄₄ 89 1 0 0 1 2 0 48 ¹⁄₄ 91 ¹⁄₂ 1 0 2 0 2 0
49 ¹⁄₄ 94 ¹⁄₄ 101011
B
C
1
1
50 ¹⁄₄ 95 ³⁄₄ 100002 51 ¹⁄₄ 97 ³⁄₄ 1 0 1 1 2 0 54 ¹⁄₄ 103 1 0 0 2 2 0 55 ¹⁄₄ 104 ¹⁄₂ 101002 56 ¹⁄₂ 106 ¹⁄₂ 1 0 2 1 2 0 58 ¹⁄₄ 109 ³⁄₄ 100102 61 ³⁄₄ 116 1 1 1 0 3 0 64 ³⁄₄ 121 ¹⁄₄ 110130 67 124 ³⁄₄ 112030 68 ³⁄₄ 128 1 1 0 0 1 2
2
70 130 1 1 1 1 3 0 73 135 ¹⁄₄ 1 1 0230
C
2
B
2
74 ³⁄₄ 138 ¹⁄₄ 110003 79 145 ¹⁄₂ 1 1 1 0 4 0
80 147 ¹⁄₄ 1 1 1 0 0 3
A
1
82 150 ³⁄₄ 1 1 0 1 4 0 82 ¹⁄₄ 152 1 1 0 1 0 3
B
C
1
1
Figure 33
16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 17
INSTALLING OFFSETS
Return Elbow Assembly
Chimney Section
Figure 34
Underside Of Chimney
Figure 35
Chimney Section (S)
Joints
4'
Screws Required At
Every Joint Past 6'
6'
No Screws Required In
Joints For First 6' of Offset
FTF8-E30 Return Elbow*
No. 8 x 1/2" SMS
First, review the Offset Elevation Chart and
Figure 36
for reference.
Step 1. Determine the offset distance where chimney is to pass through the first ceiling­dimension “A.” To find this point on your ceil­ing, first determine the center point for a verti­cal chimney following the instructions for ver­tical installation.
Measure height to the ceiling from the top of fireplace-dimension “B.” Use the appropriate Offset Elevation Chart to find dimension “A.” Mark point where you will drive your nail to show the center point for your offset ceiling cut.
Step 2. Proceed by using the Straight Up Instal­lation Instructions for cutting and framing ceil­ing and roof openings.
Note: See Framing and Dimension Chart for the sizes of the ceiling and roof openings. The size of the roof opening varies with the degree of pitch of the roof.
Offset Elbow Assembly
Offset elbows install the same as chimney sections. First, snap the inner section INTO the preceding inner section of flue. Check connec­tion by pulling up slightly to ensure a tight fit. Next, the outer sections snap lock OVER the preceding outer section of chimney. Again, check outer section by pulling up slightly to ensure proper connection is made.
Return elbows install the same way as round terminations and stabilizers:
Step 1. Hold return elbow over top of last chimney section.
Step 2. Center inner slip section into inner flue pipe-slip down.
Step 3. Center outer-locking section over outer chimney pipe. Push down until locking joint has firmly engaged.
Step 4. Pull up slightly on return elbow to ensure locking joint has firmly engaged.
Step 5. Secure support straps to framing members by nailing under tension in sheer
Figure 37
(
).
Return Elbow
Figure 37
Note: The return elbow assembly performs the
same function as a stabilizer. Consider this when determining the need for a stabilizer.
FTF8-30 Offset Elbow*
A
*Part of Offset/Return Package Model FTF8-ES30
Figure 36
B
Note: Do not apply excessive pressure to any
subsequent chimney section following return elbow assembly when installing. Ensure that each subsequent chimney section is securely attached by testing as noted above.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
Page 18
PARTS AND COMPONENTS LIST
APPENDIX
SPECIFICATIONS
Weight 343 lbs Height 42 1/2” Width 43" Depth 26 5/8"
CLEARANCE TO COMBUSTIBLES
The following clearances meet the minimum requirements for a safe installation : Side wall: 18". (457 mm)
Ceiling: 7 ft. (2135 mm) measured from the base of the fireplace Fireplace enclosure Bottom: 0"
Side: 0" Back: 0" (to standoffs) Top: Do not fill the space above the fireplace with any material (7 ft. measured from the base of the fireplace)
Chimney: 2" (50 mm) Mantel: 48" (1219 mm) from the base of the fireplace
18
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 19
REPLACEMENT PARTS PART NO. CATALOG NO.
Refractory Baffle PR-SR2028 H3398 Back refractory PR-SR2027 H3399 Right side refractory PR-SR2025D H3400 Left side refractory PR-SR2025G H3401 Bottom refractory PR-SR1722 H3402 Front refractory ash lip PR-SR2026 H3403 Log support PR-HELS43 H3404 Top/Bottom louver PR-SR15P H3405 Louver hinges PR-PIVOT H3406 Rigid firescreen (left) PR-PARETING-1 H3407 Rigid firescreen (right) PR-PARETIND-1 H3408 Black door (left) PR-SR2610GP H3409 Black door (right) PR-SR2608DP H3410 Black door capping (right) CAPME43BLKR H3413 Black door capping (left) CAPME43BLKL H3414 Wooden handle PR-SAC #83 H3415 Ceramic glass panel PR-VC10 H3416 Door gasket assembly (including a tube of PR-GASKPORTEHE-1 H3417 hi-temperature silicone glue) Damper PR-DAMPER43 H3418
OPTIONAL PARTS
Outside Air Kit (Fireplace) UZI H0251 Heat Activated On/Off Fan Kit UZY3 H0250 Variable Speed Control For UZY3 VRUW H3396 Door Capping, Brushed Nickel CAPME43BN H3394 Door Capping, Gold CAPME43G H3393 Horizontal Trim Kit, Gold 43GTK H3426 Horizontal Trim Kit, Brushed Nickel 43NTK H3395
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
19
Page 20
33"
43"
FIREPLACE DIMENSIONS
10 5/8"
27 5/8"
42 1/2"
36"
21 1/4"
43 1/4"
42"
20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 21
INSTALLATION COMPONENTS
The following items are available for use in the installation of this appliance.
Firestop Spacer (30°) 63L32 F8FS30-2
Offset/ Return Package (30°) 63L22 FTF8-ES30
Stabilizer 63L25 FTF8-S4
Chimney Section 63L10 FTF8-12
63L13 FTF8-18 63L14 FTF8-36 63L15 FTF8-48
Canadian 62L92 FTF8-18C Chimney Section 62L93 FTF8-36C
63L38 F8F6
Flashing 63L39 F8F12
Round Termination 63L42 FTF8-CTD
Outside Combustion Air Kits (with duct) UZI (without duct) UZIDF
Firestop Spacer (Flat) 63L31 F8FS-2
Combination Offset/Return Elbow 63L28 FTF8-OR15
Storm Collar 63L59 FSC
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Cold Climate Kits 63L61 FTF8-CCK1-LD
21
Page 22
INSTALLATION COMPONENTS
Chase Termination (Square) 63L51 FTF8-CT2
Chase Termination (Round) 63L45 FTF8-CTDT
Locking Band 63L60 FLB
Chase Termination (Square) 63L48 FTF8-CT1
Attic Shield Assembly 63L67 FTF8-FSAS
22
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 23
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
23
Page 24
Lennox Hearth Products Wood Burning
Fireplaces, Stoves and Inserts 20 Year Limited Warranty
THE WARRANTY
Lennox Hearth Products ("LHP") warrants the components of this wood burning factory-built fireplace system, stove or insert manufactured by LHP (LHP System) to be free from defects in materials and workmanship at the time of manufacture.
REMEDY AND EXCLUSIONS
The coverage of this Warranty is limited to all components of the fireplace system, stove or insert manufactured by LHP, with the exception of optional LHP tempered glass doors. A separate limited warranty is available from LHP for optional glass doors manufactured by LHP. Ceramic glass doors manufactured by LHP are warranted against thermal breakage only. LHP warrants the components of this factory-built system manufactured by LHP (LHP System) to be free from defects in materials and workmanship at the time of manufacture.
(1) During the first five years of this Warranty, LHP will, at its option and except for the components listed in subparagraphs (a) through (f), below, provide replacement or repair
components of the LHP System manufactured by LHP, at no charge, and will also pay for reasonable labor costs incurred in replacing or repairing such components. If repair or replacement is not commercially practicable, LHP will, at its option, refund the purchase price of the LHP Fireplace, Stove or Insert and LHP Chimney Components and Accessories. With respect to the components listed below, the remedies of this paragraph (1) are available only for the period of time indicated. Thereafter, however, until the expiration of 20 years from date of installation, LHP will, subject to the conditions of paragraph (3) below, provide replacements or repairs for those components at 50% off the then prevailing factory list prices for those components.
a. Cast iron, iron, or steel fuel grates are considered consumable accessories and therefore are not warranted, with the exception of defects in material or workmanship. b. Fireplace screens, interior refractories, and side shields (metal or refractory) - two years from date of installation. c. Electrical components, such as fan motors and blowers - one year from date of installation (light bulbs are excluded). d. Certain model fireplaces are supplied with standard glass doors which are warranted 90 days from the date of installation for defects in material and workmanship.
Replacement glass for fireplaces utilizing tempered glass will be supplied at no-charge during the terms of the 90 day limited warranty with the following exceptions:
Accidental glass breakage or damage to the glass door frame finishes incurred in transit, handling or operation either before, during or after installation.
e. Certain fireplaces, stoves and inserts are supplied with ceramic glass, which is warranted against thermal breakage only for 2 years from date of installation.
LHP will assume no responsibility for glass replacement labor costs.
f. Certain fireplaces, stoves and inserts are supplied with catalysts, which are warranted for a period of six years. Warranty coverage for years three - six will be pro-
rated from time of installation. g. Air tubes, baffles and brick retainers - one year from date of installation. h. By-pass damper assembly (catalytic models only) - five years from date of installation.
(2) During the sixth through tenth year of the Warranty, LHP will, at its option, provide replacement or repair components at no-charge, except as is provided for the components
listed in subparagraph (a) through (e) above. This coverage provides for parts only and does not include any labor.
(3) During the eleventh through the twentieth year of the Warranty, LHP will, at its option, provide replacement or repair components at 50% off the then prevailing factory list prices
for those components. This coverage only provides for the purchase of replacement or repair components at discount and does not include any labor.
This Warranty covers only parts, and in some instances labor (as provided in subparagraph (1) above). In no case shall LHP be responsible for materials, parts or construction which were not manufactured or supplied by LHP or for the labor necessary to install, repair, or remove such materials, parts or construction. All replacement or repair components will be shipped F.O.B. the nearest LHP factory.
QUALIFICATIONS TO THE WARRANTY
The complete fireplace Warranty outlined above is further subject to the following qualifications: (1) The factory-built fireplace system, stove or insert manufactured by LHP (LHP System) must be installed in accordance with LHP installation instructions and local building codes.
The Warranty on this LHP system manufactured by LHP covers only the component parts manufactured by LHP. The use of components manufactured by others with this LHP System could create serious safety hazards, may result in the denial of certification by recognized national safety listing agencies, and could be in violation of local building codes. This Warranty does not cover any damages occurring from the use of any components not manufactured or supplied by LHP. Any modifications to the system or the retro-fitting of any appliance to the system which alters the function or performance of the appliance will void this Warranty.
(2) The factory-built fireplace system, stove or insert manufactured by LHP (LHP System) is subjected to normal use with fuels stated in the Home Owners Manual. Factory-built
fireplace system includes burning such natural fireplace fuels as wood and natural or propane gas. Fuel products with abnormal burning characteristics, including but not limited to fuel such as driftwood, coal or plywood and wood products using a binder, may burn at excessive temperatures and may cause damage to the factory-built fireplace or may cause it to function improperly; stoves and inserts are approved for burning dry seasoned wood only.
(3) Coverage of this Warranty is conditional upon use of an adequate fireplace grate on factory-built fireplaces only, when applicable. Coverage of this warranty for stoves and inserts
is that these appliances are operated without the use of grates, irons or any other method to elevate the fire.
(4) LHP is not responsible for inadequate fireplace, stove or insert system draft caused by air conditioning, heating, mechanical systems, or general construction conditions which
may generate negative air pressure in the room in which the appliance is installed. Additionally LHP assumes no responsibility for smoking conditions caused by inadequate chimney heights from adjoining trees or building, adverse wind conditions or unusual environmental factors and conditions.
LIMITATION ON LIABILITY It is expressly agreed and understood that LHP’s sole obligation and purchaser’s exclusive remedy under this Warranty, under any other warranty, expressed or implied,
otherwise, shall be limited to replacement, repair, or refund, as specified above. In no event shall LHP be responsible for any incidental or consequential damages caused by defects in its products, whether such damage occurs or is discovered before or
after replacement or repair, and whether or not such damage is caused by LHP’s negligence. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. The duration of any implied warranty with respect to this LHP fireplace is limited to the duration of the foregoing warranty. Some states do not allow limitations on how long an implied warranty lasts, so the above may not apply to you.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
LHP reserves the right to investigate any and all claims against this Warranty and to decide upon method of settlement.
LHP IS NOT RESPONSIBLE FOR WORK DONE WITHOUT WRITTEN CONSENT
LHP shall in no event be responsible for any warranty work done without first obtaining LHP’s written consent.
DEALERS HAVE NO AUTHORITY TO ALTER THIS WARRANTY
LHP’s employees and dealers have no authority to make any warranties nor to authorize any remedies in addition to or inconsistent with those stated above.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this Warranty to be valid, LHP must be notified of the claimed defect in writing to Lennox Hearth Products, attention Customer Service Department, 1110 West Taft Avenue, Orange, CA. 92865, as soon as reasonably possible after the defect is discovered. Claims against this Warranty in writing should include the date of installation, and a description of the defect.
OTHER RIGHTS
This Warranty gives you specific legal rights, and you may have other rights which vary from state to state.
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2005 by LHP
24
P/N 850,027M REV. A 05/2005
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
LHP
1110 West Taft Avenue Orange, CA 92865
Loading...