Lennox Elite ELO183DH Series Installation Instructions Manual

INSTALLATION
E2012 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
IMPORTANT
This unit must be serviced annually by a licensed professional technician, or equivalent.
WARNING
Improper installation, adjustment, alteration, ser vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a licensed profes sional installer, or equivalent, or service agency.
WARNING
Do not store or use gasoline or other flammable va pors and liquids in the vicinity of this or any other appliance.
CAUTION
When venting this appliance, keep vent terminal free of snow, ice and debris.
INSTRUCTIONS
ELO183DH Series Units
OIL UNITS
506903-01 12/2012 Supersedes 04/2012
Table of Contents
Elite Series Oil Furnace 1........................
Shipping and Packing List 1......................
Unit Dimensions 2...............................
ELO183DH Unit Parts Arrangement 3.............
Oil Burner Parts Arrangement 3...................
Requirements 4.................................
Combustion & Ventilation Air 5....................
Installation 7....................................
Adjustments 8..................................
Venting 9......................................
Flue Connections 10..............................
Supply & Return Air Plenums 11...................
Optional Filter Kit 11..............................
Oil Supply Line Sizing 11.........................
Oil Supply Line & Filter Connections 13.............
Leak Check 13...................................
Electrical Wiring 13...............................
Unit Start-Up & Adjustments 15....................
Service 16......................................
Burner Control 17................................
Troubleshooting 19...............................
Start-Up & Performance Checklist 24...............
Elite® Series Oil Furnace
These instructions are intended as a general guide and do not supersede local codes in any way. Only licensed pro fessional technicians, or equivalent, can install and service the Lennox Elite® Series ELO183DH oil furnaces. In Cana da, refer to CSA B139 for recommended installation proce dures. Consult authorities who have jurisdiction before installation.
WARNING
Never push the ignition reset button more than one time. Pushing the reset more than once can lead to a build-up of oil within the heat exchanger resulting in a fire or explosion.
Shipping & Packing List
Litho U.S.A.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
12/12
*2P1212*
1- Assembled oil furnace 1- Draft control 2- Nozzels
Check the components for shipping damage. If you find any damage, immediately contact the last carrier.
Page 1
506903-01
*P506903-01*
ELO183DH Unit Dimensions - Inches (mm)
Model No. A B C D E F G H
ELO183DH
101/114P36
ELO183DH
135/150P60
in. 20‐1/2 20‐1/2 18 18 18 18 3 10‐1/4
mm 521 521 457 457 457 457 76 260
in. 23‐1/2 23‐1/2 21 21 21 21 4‐3/4 11‐3/8
mm 597 597 533 533 533 533 121 289
53 (1346)
4 KNOCKOUTS
(For Suspending)
TOP VIEW
14‐1/2
3‐1/2
(89)
(368)
AIR
F A
FLOW
(4) SPACER LEGS
F
RETURN
E
AIR
OPENING
TOP VIEW
A
A
8
(203)
C
SUPPLY
D
AIR
OPENING
END VIEW FLUE OUTLET
3/4
(19)
HEAT EX CHANGER CLEAN OUT PORTS (3)
1
(25)
BURNER
HORIZONTAL POSITION
OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE
B
3/4
(19)
FRONT OF FURNACE
FLUE OUTLET
59 (1499)
G
32‐1/2 (826)
H
SIDE VIEW
RETURN
AIR
3/4
(19)
E B
RETURN
AIR
SUPPLY AIR DUCT (Not Furnished)
AIR
FLOW
32‐1/2
(826)
59
(1499)
HEAT
EXCHANGER
CLEAN OUT
PORTS (3)
BURNER
3/4
8
(203)
SUPPLY AIR OPENING
(19)
DC
SUPPLY AIR OPENING
SIDE VIEW FRONT VIEW
DOWNFLOW POSITION
101/114—
16‐1/4(413)
H
135/150—
20‐1/4(514)
FLUE OUTLET
101/114—
16‐1/4(413)
135/150—
20‐1/4(514)
BURNER
Additive Base Raises Furnace
3/4 in. (19 mm) Inch above Floor Level
OPTIONAL DOWNFLOW ADDITIVE BASE
COMBUSTIBLE FLOOR
Page 2
ELO183DH Unit Parts Arrangement
BECKETTR
AFG BURNER
CLEAN-OUT PORT
CLEAN-OUT PORT
FLUE OPENING
HEAT EXCHANGER
INDOOR BLOWER
CONTROL BOX
Figure 1
ELO183DH Oil Burner Parts Arrangement
MAIN
HEAT
SHIELD
AIR TUBE WITH
ELECTRODE
ASSEMBLY AND
NOZZLE INSIDE
COPPER OIL
TUBE
HOUSING
ESCUTCHEON
PLATE
OIL DELAY
FUEL PUMP
VALVE
AIR BAND AND
AIR SHUTTER
Figure 2
IGNITER
BLOWER WHEEL
WITH AIR GUIDE (Inside housing)
BURNER CONTROL
(with Reset Button)
BLOWER
MOTOR
Page 3
Requirements
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379-9900
air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6 inches from the room's ceiling.
Combustion air openings should provide a minimum free area one‐half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area con taining the furnace below the level of the furnace burner.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 1 or the unit rating plate for specific combustion air opening dimensions.
Table 1
Combustion Air Opening Dimensions
Model No. (2 openings required)
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser vice must be performed by a qualified installer or service agency.
Installation of Lennox oil-fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA-B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recom mendations of the National Environmental Systems Con tractors Association and any state or provincial laws or lo cal ordinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instruc tions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No. 31 or, in Cana da, CSA Standard B139. When installing ELO183DH units in confined spaces such as utility rooms, two combustion
ELO183DH
-101/114
ELO183DH
-135/150
This unit is approved for clearances to combustible materi al as listed unit rating plate and in tables 2 or 3. Unit service and accessibility clearances take precedence over fire protection clearances.
10” X 20”
11” X 22”
Table 2
Horizontal Installation Clearances
Clearances Inches (mm)
Top of Cabinet 3 (76) *Bottom and Rear of Cabinet 1 (25) Front of Cabinet 24 (610) Service Clearance (Front) 24 (610) End of Supply Plenum 0 (0) Supply Air Opening 0 (0) Return Air Opening 0 (0) Above Horizontal Warm Air Duct
within 3 ft. (914mm) of Furnace Flue Pipe Horizontal 7 (178) Flue Pipe Vertical 7 (178)
*NOTE-When furnace is installed on combustible floor, 1” (25 mm) spacer legs must be installed to elevate unit off of mounting surface.
0 (0)
Page 4
Table 3
Downflow Installation Clearances
Clearances Inches (mm)
Bottom of Plenum and Ductwork 1 (25) Plenum Sides 1 (25) Side of Cabinet 1 (25) Rear of Cabinet 1 (25) Front of Cabinet 16 (406) Service Clearance (Front) 24 (610) Flue Pipe Horizontal 1 (25) Flue Pipe Vertical 7 (178) Return Air Opening 0 (0) *Floor *Combustible
*NOTE-Clearance for installation on combustible floor if optional additive base is installed between the furnace and combustible floor. Not required in add-on coiling ap plications.
NOTE - Downflow Application Only - For installation on combustible floors, appliance shall not be installed directly on carpeting, tile or other combustible material other than wood flooring. When installed on wood flooring, the addi tive base must be used. See Unit Dimension illustration.
Combustion & Ventilation Air
Homes built with energy conservation in mind use tight construction practices. These houses are sealed so well that it becomes necessary to provide a means of bringing in air from outside for combustion. Also, exhaust fans, ap pliance vents, chimneys and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the home for combustion, nega tive pressure (pressure outside is greater than inside pres sure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases enter the living space creating a potentially dangerous situation. Ne gative pressure may also interfere with proper combus tion, causing sooting within the heat exchanger.
The importance of the previous paragraph cannot be over stated. Users may inadvertently block fresh air intakes af ter installation.
In the absence of local codes concerning air for combus tion and ventilation, the following section outlines guide lines and recommends procedures for operating oil fur naces in a manner that ensures efficient and safe operation. Special consideration must be given to com bustion air needs as well as requirements for exhaust vents and oil piping.
Combustion Air Requirements
NOTE - Unit must be adjusted to obtain a temperature rise within the range listed in table 8.
When used in conjunction with a evaporator coil, the fur nace shall be installed in parallel with, or on the upstream side of the evaporator coil. In a parallel flow arrangement, the dampers, or other measures used to control flow of air flow, shall be adequate to prevent chilled air from entering the furnace. If the furnace is manually operated, it must be equipped with means to prevent operation of either unit un less dampers are in the full‐heat or full‐cool position.
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/ NFPA No. 70, if an external electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63_F (17_C) temperature rise.
Notice to Home Owner
This furnace is equipped with safety devices that protect you and your property. If one or more of these devices is activated, furnace operation will stop. If your home is left unattended for an extended period of time, equipment op eration must be checked periodically. If this is not possible, the water supply to the house should be shut off and the pipes should be drained. This will prevent problems associated with a NO HEAT condition (frozen pipes, etc.)
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust ing and premature heat exchanger failure. It can also cause property damage.
All oil‐fired appliances require air to be used for the com bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will oper ate in an inefficient and unsafe manner. Enough air must be provided to meet the needs of all fuel‐burning ap pliances, as well as appliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down‐draft situation. Insufficient amounts of air also cause incomplete combustion which can result in sooting. Requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by
Page 5
infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures outlined for using air from the outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which termi nate outside the space containing the furnace. This is es pecially important when the furnace is mounted on a plat form in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condi tion. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by provid ing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all fuel‐fired equipment in the confined space. Each opening must be at least 100 square inches (614.5 square centimeters). One opening shall be within 12” (305 mm) of the top of the enclosure and one opening within 12” (305 mm) of the bottom (See figure 1).
Equipment In Confined Space
All Air From Inside
Chimney or
t
Oil Ven
Air from Outside
If air from outside is brought in for combustion and ventila tion, the confined space shall be provided with two perma nent openings. One opening shall be within 12” (305 mm) of the top of the enclosure and one within 12” (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure. (See figure 2.) When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 3).
Equipment In Confined Space
(Inlet Air from Crawl Space and Outlet Air to
Chimney or
Oil Vent
Oil
Furnace
Ventilation
Louvers
(For unheated
crawl space)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
All Air From Outside
Ventilated Attic)
Ventilation Louvers (Each End Of Attic)
Outlet
r
Ai
Water
Heater
Inlet
Air
Figure 2
Oil
Furnace
NOTE-Each opening shall have a free area of at least 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (614.5 square centimeters).
Water
Heater
Figure 1
Openings
(To Adjacent Room)
When ducts are used, they shall be of the same cross-sec tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3” (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cover ing is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera tion.
Page 6
Equipment In Confined Space
All Air From Outside
Chimney
Or Oil
Vent
Oil
Furnace
NOTE-Each air duct opening shall have a free area of at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equip ment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all other equip ment in the enclosure.
Water
Heate
r
Outlet Air
Inlet Air
Figure 3
CAUTION
Combustion air openings in the front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may re sult in a fire hazard or injury.
CAUTION
The barometric draft control shall be in the same at mospheric pressure zone as the combustion air in let to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard or injury.
Horizontal Application
The ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application. Air flow may be reversed to right side discharge or unit may be used as downflow.
1. Reversing Airflow for Right Hand Discharge
D Rotate the furnace 180_ so that, when facing the
front, the warm discharge is to the right.
D Remove the nuts in the bracket that hold the burn
er to the furnace front. Rotate the burner and burn er mounting plate 180_ and reinstall the nuts.
D Remove the screws that hold the limit control in
place. Use the provided knockout hole to relocate the limit control to the top side of the front panel.
2. Installation on Non-Combustible Material
D Set the furnace on non‐combustible material
(such as concrete blocks, bricks or angle iron). Install spacer legs, provided with unit, by using the cabinet screws from each corner of the unit.
D Use a level to check the level of furnace in at least
two directions. Use shims or non‐combustible ma terial. A minimum clearance of 1” must be main tained between bottom of furnace and combus tible material.
3. Suspended Installation
D To suspend the furnace, remove knockouts in top
of panel at warm air discharge and at blower panel (Refer to unit dimensions). Use 3/8” rods cut to de sired length.
D Use one flat washer and two nuts for each rod (a
nut and washer on the inside of unit and the other “locking” nut on the outside of unit; see figure 4). Level the unit by adjusting the nuts on the inside of unit.
Hanger Rod Installation
ROD
LOCKING NUT
TOP OF FURNACE
Installation
When installed, ELO183DH furnaces must be level. If the furnace is not level, place fireproof wedges or shims be tween the low side of the furnace and floor. Make sure the weight of the furnace is evenly distributed on all four cor ners. Strain on sides of the cabinet causing cracking and popping noises may occur if weight of furnace is not evenly distributed.
Set the unit in desired location keeping in mind the clear ances list in tables 2 and 3. Also keep in mind oil supply connections, electrical supply, flue connections and suffi cient clearance for installing and servicing unit.
ELO183DH series units may be installed in a crawl space under a house, utility room or in a wide variety of sus pended applications.
WASHER
NUT
BLOWER COMPARTMENT
DIVISION PANEL
Figure 4
Downflow Application
When installing the ELO183DH in a downflow position and on combustible flooring, a combustible floor base must be used. See Unit Dimension illustration.
1. Rotate the furnace so that return is on top and supply is on bottom. Refer to table 3 for clearances to com bustible flooring.
2. Remove the nuts in the bracket that hold the burner to the furnace front. Rotate the burner and burner mount ing plate 90_ and reinstall the nuts.
Page 7
3. It is also recommended that the upper rear screw hold ing the blower housing to the blower deck be removed before installation in a closet. Removing this screw al lows for easy service and removal of the blower as sembly in a closet installation.
Adjustments
Neither the nozzle setting nor the air adjustments are fac tory set. The furnace is fire-tested and the limit control is checked to make sure it functions properly; no factory set tings are made. During installation, the furnace must be adjusted to ensure proper operation. The installing dealer/ contractor must have and use proper test equipment in or der to correctly adjust the oil furnace. The use of test equip ment is more critical than ever due to tighter tolerances needed to keep the furnace operating efficiently. Among the test equipment for an oil furnace, the proper combustion test kit should contain the following:
D Draft gauge D CO
or O2 analyzer
2
D Smoke tester D Pressure gauge D High temperature thermometer D Oil vacuum gauge D Beckett T-501 or Z-2000 nozzle gauge D Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow ing section for correct adjustment procedures.
Nozzle Adjustment
Proper adjustment of the nozzle assembly is critical. Be fore the flue pipe and oil lines are installed, the nozzle as sembly must be checked for proper depth and alignment. You must remove the entire burner assembly (not just the nozzle) from the furnace to check the nozzle depth and alignment. The smaller sized firing nozzle has been facto ry-installed. This should be verified by the installer. A larger nozzle has been provided in the bag assembly for use with ELO183DH114 and 150 units. Inspect the spark trans former leads also to ensure they are still attached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re moving the burner assembly from the vestibule. Loosen the nuts and turn the whole burner assembly clockwise (figure 5) to remove the entire burner assembly from the furnace. There is adequate wire to remove the burner with out disconnecting wires. Once removed, turn the burner around in the vest panel area.
ELO183DH Series Burner Removal
First, loosen three nuts which
attach burner to vest panel.
Next, rotate burner clockwise on slots then pull toward you.
Figure 5
To correctly check and adjust the nozzle depth and align ment, use the Beckett T-501 or Z-2000 gauge.
To check the oil nozzle depth, insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the face of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustration sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. If necessary, loosen the escutcheon plate securing screw and slide the entire nozzle assembly for ward or backward within the air tube (figure 6). Re-secure escutcheon plate screw when adjustment is completed.
To check nozzle alignment, again insert the small end of gauge into the end cone and measure the nozzle and elec trode alignment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not centered, but found to be too far left or right, a new nozzle assembly will need to be ordered. Do not at tempt to adjust by bending the 90 degree elbow in the oil line.
Take care to properly re-install burner assembly when nozzle adjustment has been completed.
Beckett Oil Burner Nozzle Adjustment
Burner must be removed from
furnace for this procedure.
T-501 Gauge
To Adjust Nozzle
1-Loosen escutcheon plate screw.
2-Slide entire nozzle/electrode assembly back and forth inside air tube until nozzle just touches gauge.
2
1
Escutcheon Plate
Figure 6
Page 8
Loading...
+ 16 hidden pages