Lennox Elite ELO183DH Installation Instructions Manual

Page 1
INSTALLATION
E2012 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
IMPORTANT
This unit must be serviced annually by a licensed professional technician, or equivalent.
WARNING
Improper installation, adjustment, alteration, ser vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a licensed profes sional installer, or equivalent, or service agency.
WARNING
Do not store or use gasoline or other flammable va pors and liquids in the vicinity of this or any other appliance.
CAUTION
When venting this appliance, keep vent terminal free of snow, ice and debris.
INSTRUCTIONS
ELO183DH Series Units
OIL UNITS
506903-01 12/2012 Supersedes 04/2012
Table of Contents
Elite Series Oil Furnace 1........................
Shipping and Packing List 1......................
Unit Dimensions 2...............................
ELO183DH Unit Parts Arrangement 3.............
Oil Burner Parts Arrangement 3...................
Requirements 4.................................
Combustion & Ventilation Air 5....................
Installation 7....................................
Adjustments 8..................................
Venting 9......................................
Flue Connections 10..............................
Supply & Return Air Plenums 11...................
Optional Filter Kit 11..............................
Oil Supply Line Sizing 11.........................
Oil Supply Line & Filter Connections 13.............
Leak Check 13...................................
Electrical Wiring 13...............................
Unit Start-Up & Adjustments 15....................
Service 16......................................
Burner Control 17................................
Troubleshooting 19...............................
Start-Up & Performance Checklist 24...............
Elite® Series Oil Furnace
These instructions are intended as a general guide and do not supersede local codes in any way. Only licensed pro fessional technicians, or equivalent, can install and service the Lennox Elite® Series ELO183DH oil furnaces. In Cana da, refer to CSA B139 for recommended installation proce dures. Consult authorities who have jurisdiction before installation.
WARNING
Never push the ignition reset button more than one time. Pushing the reset more than once can lead to a build-up of oil within the heat exchanger resulting in a fire or explosion.
Shipping & Packing List
Litho U.S.A.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
12/12
*2P1212*
1- Assembled oil furnace 1- Draft control 2- Nozzels
Check the components for shipping damage. If you find any damage, immediately contact the last carrier.
Page 1
506903-01
*P506903-01*
Page 2
ELO183DH Unit Dimensions - Inches (mm)
Model No. A B C D E F G H
ELO183DH
101/114P36
ELO183DH
135/150P60
in. 20‐1/2 20‐1/2 18 18 18 18 3 10‐1/4
mm 521 521 457 457 457 457 76 260
in. 23‐1/2 23‐1/2 21 21 21 21 4‐3/4 11‐3/8
mm 597 597 533 533 533 533 121 289
53 (1346)
4 KNOCKOUTS
(For Suspending)
TOP VIEW
14‐1/2
3‐1/2
(89)
(368)
AIR
F A
FLOW
(4) SPACER LEGS
F
RETURN
E
AIR
OPENING
TOP VIEW
A
A
8
(203)
C
SUPPLY
D
AIR
OPENING
END VIEW FLUE OUTLET
3/4
(19)
HEAT EX CHANGER CLEAN OUT PORTS (3)
1
(25)
BURNER
HORIZONTAL POSITION
OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE
B
3/4
(19)
FRONT OF FURNACE
FLUE OUTLET
59 (1499)
G
32‐1/2 (826)
H
SIDE VIEW
RETURN
AIR
3/4
(19)
E B
RETURN
AIR
SUPPLY AIR DUCT (Not Furnished)
AIR
FLOW
32‐1/2
(826)
59
(1499)
HEAT
EXCHANGER
CLEAN OUT
PORTS (3)
BURNER
3/4
8
(203)
SUPPLY AIR OPENING
(19)
DC
SUPPLY AIR OPENING
SIDE VIEW FRONT VIEW
DOWNFLOW POSITION
101/114—
16‐1/4(413)
H
135/150—
20‐1/4(514)
FLUE OUTLET
101/114—
16‐1/4(413)
135/150—
20‐1/4(514)
BURNER
Additive Base Raises Furnace
3/4 in. (19 mm) Inch above Floor Level
OPTIONAL DOWNFLOW ADDITIVE BASE
COMBUSTIBLE FLOOR
Page 2
Page 3
ELO183DH Unit Parts Arrangement
BECKETTR
AFG BURNER
CLEAN-OUT PORT
CLEAN-OUT PORT
FLUE OPENING
HEAT EXCHANGER
INDOOR BLOWER
CONTROL BOX
Figure 1
ELO183DH Oil Burner Parts Arrangement
MAIN
HEAT
SHIELD
AIR TUBE WITH
ELECTRODE
ASSEMBLY AND
NOZZLE INSIDE
COPPER OIL
TUBE
HOUSING
ESCUTCHEON
PLATE
OIL DELAY
FUEL PUMP
VALVE
AIR BAND AND
AIR SHUTTER
Figure 2
IGNITER
BLOWER WHEEL
WITH AIR GUIDE (Inside housing)
BURNER CONTROL
(with Reset Button)
BLOWER
MOTOR
Page 3
Page 4
Requirements
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379-9900
air openings are required. Dimensions of combustion air openings are shown in table 1. One opening shall be below burner level and the other opening shall be no more than 6 inches from the room's ceiling.
Combustion air openings should provide a minimum free area one‐half square inch per 1,000 Btu per hour input. This combustion air should be brought into the area con taining the furnace below the level of the furnace burner.
IMPORTANT
An opening to the outside for combustion air is strongly recommended, especially in new homes. Refer to table 1 or the unit rating plate for specific combustion air opening dimensions.
Table 1
Combustion Air Opening Dimensions
Model No. (2 openings required)
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser vice must be performed by a qualified installer or service agency.
Installation of Lennox oil-fired furnaces must conform with the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31, the National Electrical Code, ANSI/NFPA No.70 (in the U.S.A.), CSA Standard CAN/CSA-B139 (in Canada), Installation Code for Oil Burning Equipment, the Canadian Electrical Code Part1, CSA 22.1 (Canada), the recom mendations of the National Environmental Systems Con tractors Association and any state or provincial laws or lo cal ordinances. Authorities having jurisdiction should be consulted before installation. Such applicable regulations or requirements take precedence over general instruc tions in this manual.
Chimneys and chimney connectors must be of the type and construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No. 31 or, in Cana da, CSA Standard B139. When installing ELO183DH units in confined spaces such as utility rooms, two combustion
ELO183DH
-101/114
ELO183DH
-135/150
This unit is approved for clearances to combustible materi al as listed unit rating plate and in tables 2 or 3. Unit service and accessibility clearances take precedence over fire protection clearances.
10” X 20”
11” X 22”
Table 2
Horizontal Installation Clearances
Clearances Inches (mm)
Top of Cabinet 3 (76) *Bottom and Rear of Cabinet 1 (25) Front of Cabinet 24 (610) Service Clearance (Front) 24 (610) End of Supply Plenum 0 (0) Supply Air Opening 0 (0) Return Air Opening 0 (0) Above Horizontal Warm Air Duct
within 3 ft. (914mm) of Furnace Flue Pipe Horizontal 7 (178) Flue Pipe Vertical 7 (178)
*NOTE-When furnace is installed on combustible floor, 1” (25 mm) spacer legs must be installed to elevate unit off of mounting surface.
0 (0)
Page 4
Page 5
Table 3
Downflow Installation Clearances
Clearances Inches (mm)
Bottom of Plenum and Ductwork 1 (25) Plenum Sides 1 (25) Side of Cabinet 1 (25) Rear of Cabinet 1 (25) Front of Cabinet 16 (406) Service Clearance (Front) 24 (610) Flue Pipe Horizontal 1 (25) Flue Pipe Vertical 7 (178) Return Air Opening 0 (0) *Floor *Combustible
*NOTE-Clearance for installation on combustible floor if optional additive base is installed between the furnace and combustible floor. Not required in add-on coiling ap plications.
NOTE - Downflow Application Only - For installation on combustible floors, appliance shall not be installed directly on carpeting, tile or other combustible material other than wood flooring. When installed on wood flooring, the addi tive base must be used. See Unit Dimension illustration.
Combustion & Ventilation Air
Homes built with energy conservation in mind use tight construction practices. These houses are sealed so well that it becomes necessary to provide a means of bringing in air from outside for combustion. Also, exhaust fans, ap pliance vents, chimneys and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the home for combustion, nega tive pressure (pressure outside is greater than inside pres sure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. Combustion gases enter the living space creating a potentially dangerous situation. Ne gative pressure may also interfere with proper combus tion, causing sooting within the heat exchanger.
The importance of the previous paragraph cannot be over stated. Users may inadvertently block fresh air intakes af ter installation.
In the absence of local codes concerning air for combus tion and ventilation, the following section outlines guide lines and recommends procedures for operating oil fur naces in a manner that ensures efficient and safe operation. Special consideration must be given to com bustion air needs as well as requirements for exhaust vents and oil piping.
Combustion Air Requirements
NOTE - Unit must be adjusted to obtain a temperature rise within the range listed in table 8.
When used in conjunction with a evaporator coil, the fur nace shall be installed in parallel with, or on the upstream side of the evaporator coil. In a parallel flow arrangement, the dampers, or other measures used to control flow of air flow, shall be adequate to prevent chilled air from entering the furnace. If the furnace is manually operated, it must be equipped with means to prevent operation of either unit un less dampers are in the full‐heat or full‐cool position.
When installed, furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/ NFPA No. 70, if an external electrical source is utilized.
Field wiring connection with unit must meet or exceed specifications of type T wire and withstand a 63_F (17_C) temperature rise.
Notice to Home Owner
This furnace is equipped with safety devices that protect you and your property. If one or more of these devices is activated, furnace operation will stop. If your home is left unattended for an extended period of time, equipment op eration must be checked periodically. If this is not possible, the water supply to the house should be shut off and the pipes should be drained. This will prevent problems associated with a NO HEAT condition (frozen pipes, etc.)
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust ing and premature heat exchanger failure. It can also cause property damage.
All oil‐fired appliances require air to be used for the com bustion process. If sufficient amounts of combustion air are not available, the furnace or other appliance will oper ate in an inefficient and unsafe manner. Enough air must be provided to meet the needs of all fuel‐burning ap pliances, as well as appliances such as exhaust fans which force air out of the home. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down‐draft situation. Insufficient amounts of air also cause incomplete combustion which can result in sooting. Requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by
Page 5
Page 6
infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures outlined for using air from the outside for combustion and ventilation.
Confined Space
A confined space is an area with volume less than 50 cubic feet (1.4 cubic meters) per 1,000 Btu (293 W) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which termi nate outside the space containing the furnace. This is es pecially important when the furnace is mounted on a plat form in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condi tion. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
Air from an Adjacent Space
If the confined space housing the furnace adjoins space categorized as unconfined, air can be brought in by provid ing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all fuel‐fired equipment in the confined space. Each opening must be at least 100 square inches (614.5 square centimeters). One opening shall be within 12” (305 mm) of the top of the enclosure and one opening within 12” (305 mm) of the bottom (See figure 1).
Equipment In Confined Space
All Air From Inside
Chimney or
t
Oil Ven
Air from Outside
If air from outside is brought in for combustion and ventila tion, the confined space shall be provided with two perma nent openings. One opening shall be within 12” (305 mm) of the top of the enclosure and one within 12” (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of total input rating of all equipment in the enclosure. (See figure 2.) When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (6.4 square centimeters) per 2,000 Btu (586 W) per total input rating of all equipment in the enclosure (See figure 3).
Equipment In Confined Space
(Inlet Air from Crawl Space and Outlet Air to
Chimney or
Oil Vent
Oil
Furnace
Ventilation
Louvers
(For unheated
crawl space)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all equipment in the enclosure.
All Air From Outside
Ventilated Attic)
Ventilation Louvers (Each End Of Attic)
Outlet
r
Ai
Water
Heater
Inlet
Air
Figure 2
Oil
Furnace
NOTE-Each opening shall have a free area of at least 1 square inch (6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (614.5 square centimeters).
Water
Heater
Figure 1
Openings
(To Adjacent Room)
When ducts are used, they shall be of the same cross-sec tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3” (76 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cover ing is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment opera tion.
Page 6
Page 7
Equipment In Confined Space
All Air From Outside
Chimney
Or Oil
Vent
Oil
Furnace
NOTE-Each air duct opening shall have a free area of at least one square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of the total input rating of all equipment in the enclosure. If the equip ment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W) per hour of the total input rating of all other equip ment in the enclosure.
Water
Heate
r
Outlet Air
Inlet Air
Figure 3
CAUTION
Combustion air openings in the front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may re sult in a fire hazard or injury.
CAUTION
The barometric draft control shall be in the same at mospheric pressure zone as the combustion air in let to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard or injury.
Horizontal Application
The ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application. Air flow may be reversed to right side discharge or unit may be used as downflow.
1. Reversing Airflow for Right Hand Discharge
D Rotate the furnace 180_ so that, when facing the
front, the warm discharge is to the right.
D Remove the nuts in the bracket that hold the burn
er to the furnace front. Rotate the burner and burn er mounting plate 180_ and reinstall the nuts.
D Remove the screws that hold the limit control in
place. Use the provided knockout hole to relocate the limit control to the top side of the front panel.
2. Installation on Non-Combustible Material
D Set the furnace on non‐combustible material
(such as concrete blocks, bricks or angle iron). Install spacer legs, provided with unit, by using the cabinet screws from each corner of the unit.
D Use a level to check the level of furnace in at least
two directions. Use shims or non‐combustible ma terial. A minimum clearance of 1” must be main tained between bottom of furnace and combus tible material.
3. Suspended Installation
D To suspend the furnace, remove knockouts in top
of panel at warm air discharge and at blower panel (Refer to unit dimensions). Use 3/8” rods cut to de sired length.
D Use one flat washer and two nuts for each rod (a
nut and washer on the inside of unit and the other “locking” nut on the outside of unit; see figure 4). Level the unit by adjusting the nuts on the inside of unit.
Hanger Rod Installation
ROD
LOCKING NUT
TOP OF FURNACE
Installation
When installed, ELO183DH furnaces must be level. If the furnace is not level, place fireproof wedges or shims be tween the low side of the furnace and floor. Make sure the weight of the furnace is evenly distributed on all four cor ners. Strain on sides of the cabinet causing cracking and popping noises may occur if weight of furnace is not evenly distributed.
Set the unit in desired location keeping in mind the clear ances list in tables 2 and 3. Also keep in mind oil supply connections, electrical supply, flue connections and suffi cient clearance for installing and servicing unit.
ELO183DH series units may be installed in a crawl space under a house, utility room or in a wide variety of sus pended applications.
WASHER
NUT
BLOWER COMPARTMENT
DIVISION PANEL
Figure 4
Downflow Application
When installing the ELO183DH in a downflow position and on combustible flooring, a combustible floor base must be used. See Unit Dimension illustration.
1. Rotate the furnace so that return is on top and supply is on bottom. Refer to table 3 for clearances to com bustible flooring.
2. Remove the nuts in the bracket that hold the burner to the furnace front. Rotate the burner and burner mount ing plate 90_ and reinstall the nuts.
Page 7
Page 8
3. It is also recommended that the upper rear screw hold ing the blower housing to the blower deck be removed before installation in a closet. Removing this screw al lows for easy service and removal of the blower as sembly in a closet installation.
Adjustments
Neither the nozzle setting nor the air adjustments are fac tory set. The furnace is fire-tested and the limit control is checked to make sure it functions properly; no factory set tings are made. During installation, the furnace must be adjusted to ensure proper operation. The installing dealer/ contractor must have and use proper test equipment in or der to correctly adjust the oil furnace. The use of test equip ment is more critical than ever due to tighter tolerances needed to keep the furnace operating efficiently. Among the test equipment for an oil furnace, the proper combustion test kit should contain the following:
D Draft gauge D CO
or O2 analyzer
2
D Smoke tester D Pressure gauge D High temperature thermometer D Oil vacuum gauge D Beckett T-501 or Z-2000 nozzle gauge D Knowledge of proper test equipment operation
CAUTION
Improper nozzle and/or air adjustment of this unit may result in sooting problems. Refer to the follow ing section for correct adjustment procedures.
Nozzle Adjustment
Proper adjustment of the nozzle assembly is critical. Be fore the flue pipe and oil lines are installed, the nozzle as sembly must be checked for proper depth and alignment. You must remove the entire burner assembly (not just the nozzle) from the furnace to check the nozzle depth and alignment. The smaller sized firing nozzle has been facto ry-installed. This should be verified by the installer. A larger nozzle has been provided in the bag assembly for use with ELO183DH114 and 150 units. Inspect the spark trans former leads also to ensure they are still attached to the electrodes.
The burner assembly is attached to the vestibule panel by three nuts. Slots are provided in the mounting flange for re moving the burner assembly from the vestibule. Loosen the nuts and turn the whole burner assembly clockwise (figure 5) to remove the entire burner assembly from the furnace. There is adequate wire to remove the burner with out disconnecting wires. Once removed, turn the burner around in the vest panel area.
ELO183DH Series Burner Removal
First, loosen three nuts which
attach burner to vest panel.
Next, rotate burner clockwise on slots then pull toward you.
Figure 5
To correctly check and adjust the nozzle depth and align ment, use the Beckett T-501 or Z-2000 gauge.
To check the oil nozzle depth, insert the small end of the gauge into the end of the cone and measure from the flat of the end cone to the face of the nozzle. When nozzle depth is correct, the tip of the nozzle should just touch the end of the gauge. Refer to the illustration sheet provided with the gauge. Note that the scale side of the gauge is not used for this purpose. If necessary, loosen the escutcheon plate securing screw and slide the entire nozzle assembly for ward or backward within the air tube (figure 6). Re-secure escutcheon plate screw when adjustment is completed.
To check nozzle alignment, again insert the small end of gauge into the end cone and measure the nozzle and elec trode alignment against the center lines marked on the gauge (again refer to enclosed illustration sheet). If the nozzle is not centered, but found to be too far left or right, a new nozzle assembly will need to be ordered. Do not at tempt to adjust by bending the 90 degree elbow in the oil line.
Take care to properly re-install burner assembly when nozzle adjustment has been completed.
Beckett Oil Burner Nozzle Adjustment
Burner must be removed from
furnace for this procedure.
T-501 Gauge
To Adjust Nozzle
1-Loosen escutcheon plate screw.
2-Slide entire nozzle/electrode assembly back and forth inside air tube until nozzle just touches gauge.
2
1
Escutcheon Plate
Figure 6
Page 8
Page 9
Indoor Coil Placement
In cooling / heat pump applications, Lennox recommends that the indoor coil be installed at least 4 inches above the top of the furnace cabinet to allow proper airflow. If coil cabinet does not provide proper clearance, use field-fabri cated transition.
Venting
feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).
7. The vent must not pass through a floor or ceiling. Clearances to single wall vent pipe should be no less than 6” (152 mm); more if local codes require it.
8. The vent may pass through a wall where provisions have been made for a thimble as specified in the Stan dards of the National Board of Fire Underwriters. See figure 7.
WARNING
Combustion air openings in front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may re sult in a fire hazard.
WARNING
The barometric draft control shall be in the same at mospheric pressure zone as the combustion air in let to the furnace. Deviation from this practice will cause improper burner operation and may result in a fire hazard.
CAUTION
Do not store combustible materials near the furnace or supply air ducts. The material (such as paint, mo tor oil, gasoline, paint thinner, etc.) may ignite creat ing a fire hazard.
WARNING
This furnace is certified for use with type “L” vent. “B” vent must not be used with oil furnaces.
Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protec tion Association. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04” w.c. (9.9 Pa) is re quired during burner operation.
1. Local building codes may have more stringent installa tion requirements and should be consulted before installation of unit.
2. The vent connector should be as short as possible.
3. The vent connector should not be smaller than the out let diameter of the vent outlet of the furnace.
4. Pipe should be at least 24 gauge galvanized.
5. Single wall vent pipe should not run outside or through any unconditioned space.
6. Chimney should extend 3 feet (0.9 m) above highest point where the vent passes through the roof, and 2
Wall Thimble
THIMBLE
COMBUSTIBLE
WALL
VENT PIPE
Figure 7
Masonry Chimney
BAROMETRIC
CONTROL* (IN EITHER
LOCATION)
horizontal
application
shown
clean out
*Barometric draft control may be installed in either vertical or horizontal section of flue pipe no less than 12” and no more than 18” from furnace flue outlet.
LINER
clean out
MASONRY CHIMNEY
Figure 8
9. The vent pipe should slope upward toward the chim ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers.
10. Extend the vent pipe into the chimney so that it is flush with the inside of the vent liner. Seal the joint between the pipe and the liner.
11. The furnace shall be connected to a factory-built chim ney or vent complying with a recognized standard, or masonry or concrete chimney lined with a lining mate rial acceptable to the authority having jurisdiction.
12. When two or more appliances vent into a common vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the areas of the additional vent or vent connection. Chimney must be able to sufficiently vent all appliances operating at the same time.
Page 9
Page 10
13. The vent pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system.
14. All unused chimney openings should be closed.
15. All vent pipe run through unconditioned areas or out side shall be constructed of factory-built chimney sec tions. See figure 9.
16. Where condensation of vent gas is apparent, the vent should be repaired or replaced. Accumulation of con densation in the vent is unacceptable.
17. Vent connectors serving this appliance shall not be connected into any portion of mechanical draft sys tems operating under positive pressure.
18. Keep the area around the vent terminal free of snow, ice and debris.
Factory‐Built Chimney
BAROMETRIC
CONTROL* (IN EITHER LOCATION)
horizontal ap
plication shown
FACTORY BUILT CHIMNEY
3 - Insofar as is practical, close all building doors and win
dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not con nected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom ex hausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 - Following the lighting instruction on the unit, place the
appliance being inspected in operation. Adjust ther mostat so appliance will operate continuously.
5 - Test for spillage using a draft gauge.
6 - After it has been determined that each appliance re
maining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other fuel burning appliance to its previous condi tion of use.
7 - If improper venting is observed during any of the
above tests, the common venting system must be corrected.
DRAIN FOR CONDENSATE
*Barometric draft control may be installed in either vertical or horizontal section of flue pipe no less than 12” and no more than 18” from furnace flue outlet.
Figure 9
Removal of Unit from Common Venting System
In the event that an existing furnace is removed from a venting system commonly run with separate appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted while each appliance is in operation and the other appliances not in operation remain con nected to the common venting system. If venting system has been installed improperly, the system must be cor rected as outlined in the previous section.
1 - Seal any unused openings in the common venting
system.
2 - Visually inspect venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
Flue Connections
IMPORTANT
When flue pipe is installed at less than minimum clearance listed in tables 2 and 3, radiation shields must be installed. See figure 10.
Use 24 gauge or heavier galvanized smoke pipe and fit tings to connect furnace to vent. Maintain rise of at least one inch per foot. Connect flue pipe to chimney using the least number of elbows and angles possible. Flue pipe or vent connector must be inserted into but not beyond the outside wall of the chimney flue. No reduction in diameter of flue pipe is acceptable. It is best to have flue pipe as short and direct as possible.
Where two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue or vent connector, plus 50% of the area of any additional flues or vent connectors. Install barometric draft control (provided) and flue pipe according to instructions packed with control.
Inspect flue pipe annually. Clean soot or ash from flue pipe, if necessary. If pipe is rusted, replace.
Page 10
Page 11
Radiation Shield Installation
COMBUSTIBLE
MATERIAL
ELO183DH UNIT
(TOP)
RADIATION
UNIT
CABINET
NON-COMBUSTIBLE
SPACERS
NOTE 1-Radiation shields must be constructed of 24 gauge sheet metal minimum.
NOTE 2-Radiation shields required when A is less than 9” (229mm). NOTE 3-Radiation shields should extend from the top of the unit to
the top of the flue pipe.
(SEE NOTE 2)
SHIELDS
RADIATION SHIELDS
(SEE NOTE 1)
FLUE
PIPE
ELO183DH UNIT
(FRONT)
AA
(25 mm)
(305 mm)
7”
(178 mm)
B
(SEE
NOTE 3)
1”
min.
12”
Optional Filter Kit
An Optional filter kit is available for ELO183DH units. Kit 35K05 is used with ELO183DH-101/114 units, and kit 35K06 is used with ELO183DH-135/150 units. All kits in clude the following:
S 2 filters S 3 rods S 7 screws S 1 rack assembly S 1 panel
ELO183DH Filter Rack Installation
1. Slide filter rack over return duct flanges.
2. Using a scriber through the filter rack mounting holes, mark seven mounting hole locations in the return end of the cabinet. See figure 11.
3. Remove filter rack and drill 1/8” diameter holes at the marked positions.
4. Place filter rack in position again and secure it to the cabinet using the sheet metal screws provided. Clear ance for the screw driver is provided in outside holes of rack and in filter support angles.
5. Bend the ends of filter rods and hook ends through holes provided in top and bottom filter support angles.
6. Slide filter between the support angles and the plenum side for the filter rack. The filter rods hold the filter in place.
Figure 10
Barometric Draft Control Installation
Install the provided barometric draft control in the flue pipe at least 12 inches beyond the furnace flue outlet to pro vide space for flue gas sampling. The barometric draft con trol may be installed in either vertical or horizontal sections of the flue pipe; however, it should be positioned no more than 18” beyond the furnace flue outlet. Follow the instruc tions packed with the barometric draft control.
Supply & Return Air Plenums
NOTE - Following these suggestions when installing sup ply and return air plenums.
1. Use sealing strips of fiberglass.
2. In all cases, the plenum should be secured to furnace or evaporator cabinet with sheet metal screws.
3. Both supply and return air plenums shall be square and least 18” long. They should be the same dimen sion as the furnace opening.
4. If unit is installed in a confined space such as a utility room where there is no complete return air duct sys tem, a return air connection should be run (the same size as the return air opening) to a location outside the room containing the furnace.
5. Install supply and return air ducts as desired.
ELO183DH Optional Filter Kit
FILTER RACK
22 (559)
14 (356)
RETURN AIR DUCT (Not Furnished by Lennox)
FILTER
OPENING
IN UNIT
(Either Side)
Figure 11
Oil Supply Line Sizing
Ensure that the restrictions of the piping system, plus any lift involved, do not exceed the capability of the oil pump. Use the following guidelines when determining whether to use a single-or two-stage oil pump.
Page 11
Page 12
One-Pipe System
When using a one-pipe system even with the oil tank that is above the burner and a vacuum of 6” (152 mm) Hg or less, a single-stage fuel pump with a supply line should be ade quate without a separate return line. See figure 12.
Manual bleeding of the fuel pump is required on initial start up. Failure to bleed air from the oil pump could result in an air lock/oil starvation condition.
NOTE - As an extra precaution, cycle heating on and off ten times after bleeding air from the oil pump. This will elim inate air in the gun assembly.
Oil Piping
Two‐Pipe System
Air Vent
Fill
Pipe
Return
pipe
Oil
Tank
3”-4”
(76 mm -102 mm)
Return
pipe
Outside tank fuel pump above bottom of tank.
R
Figure 13
Fuel
Pump
Miain
Filter
Inlet
H
Oil Piping
air vent
fill
pipe
To determine the correct tubing size for piping, refer to table 4.
Line Length Pipe Diameter (OD Tubing)
0-50' (15 m) 3/8” (10 mm)
51-100' (15 m) 1/2” (12 mm)
When using a two-pipe system with the oil tank below the level of the burner, use a single-stage fuel pump in lift con ditions of up to 10 feet (3 m) and/or a vacuum of 10” (254 mm) Hg or less. See figure 13. Use a two-stage fuel pump when lift exceeds 10 feet (3 m) and/or a vacuum of 12” Hg to 17” Hg. Both conditions require that you use of a two­pipe system, which consists of a return line that purges the fuel pump of air by returning it to the tank. To determine the run and lift for piping, refer to table 5.
One‐Pipe System
fuel
pump
Oil
Tank
Shut-off
Valve
Figure 12
Table 4
One-Pipe Oil Line Sizing
Two-Pipe System
Mian Filter
8 ft (2.4 m)
Maximum
One Pipe Lift
Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe. Install oil supply pipe under floor or near walls to protect it from damage. Avoid running pipes along joists or reverberating surfaces. Always use flare fittings. All fittings must be accessible. Do not use compression fittings.
IMPORTANT
Both oil supply and return pipes must be sub merged in oil in the supply tank.
Table 5
Two-Pipe Maximum Pipe Length (H + R)
3450 RPM - 3 GPH (11.4 LPH)
Lift “H”
0'
(0.0 m)
2'
(0.6 m)
4'
(1.2 m)
6 '
(1.8m)
8'
(2.4 m)
10'
(3.0 m)
12'
(3.7 m)
14'
(4.3 m)
16'
(4.9 m)
18'
(5.5 m)
3/8” (10 mm) OD
Tubing
Single
Stage
84'
(25.6 m)
73'
(22.3 m)
63'
(19.2 m)
52'
(15.8 m)
42'
(12.8 m)
31'
(9.4 m)
21'
(6.4 m)
---
---
Two
Stage
93'
(28.3 m)
85'
(25.9 m)
77'
(23.5 m)
69'
(21.0 m)
60'
(18.3 m)
52'
(15.9 m)
44'
(13.4 m)
36'
(11.0 m)
27'
(8.2 m)
--- --- ---
1/2” (12 mm) OD
Tubing
Single
Stage
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
83'
(25.3 m)
41'
(12.5 m)
---
Two
Stage
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
100'
(30.5 m)
76'
(23.2 m)
Page 12
Page 13
Table 6
Fuel Pump Usage
Pump Piping Application Maximum Lift (vacuum)
Single-Stage Pump
Two-Stage Pump Two-Pipe System
One-Pipe System 8 ft. (6” Hg vacuum)
Two-Pipe System 10 ft. (12” Hg vacuum)
10 ft. or greater
(12” to 17” Hg vacuum)
Oil Supply Line & Filter Connections
One-Pipe Systems
CAUTION
Do not install the bypass plug into the pump on one­pipe systems.
The burner is shipped with fuel pump set for one-pipe op eration. For one-pipe systems, the oil supply pipe is con nected to the inlet tap on the pump. A one-pipe system should only be used where there is gravity oil flow to the pump and the pipe is not run at any point above the oil level in the tank.
1 - Connect the inlet pipe to the pump inlet. Start the
burner.
2 - Set the primary burner control for continuous opera
tion during purging.
3 - Turn the bleed valve one turn counterclockwise to
open.
4 - Bleed the unit until all air bubbles disappear.
NOTE - Hurried bleeding will prevent the unit from op erating properly.
5 - Tighten the bleed valve securely.
Two-Pipe Systems
If the installation requires a two-pipe operation, install the bypass plug included in the bag which is attached to the pump. To convert the pump, install the bypass plug ac cording to the provided pump instructions. Notice in the two‐pipe system the return pipe must terminate in the tank 3” (76 mm) to 4” (102 mm) above the supply inlet. Ensure the return pipe terminates at the correct measurement or air may escape into the system. This could result in loss of prime.
NOTE- If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended.
1 - Remove 1/4” plug from return port.
2 - Insert bypass plug and tighten it. See figure 13. 3 - Attach the return and inlet pipes. Start the burner. Air
bleeding is automatic.
NOTE - If a faster bleed is necessary, open the bleed valve.
4 - The return pipe must terminate 3” to 4” above the sup
ply pipe inlet. See figure 13.
NOTE - If the return pipe does not terminate where it should, air may enter the system, and prime may be lost.
An oil filter is required for all models. Install a field sup plied oil filter inside the building between the tank shut‐off valve and the burner. Locate filter close to burner for easy maintenance. Table 7 lists the filters for the ELO183DH furnace.
Table 7
Oil Filters
10 micron filter (no mounting bracket) 81P89 10 micron filter (mounting bracket) 53P92 10 micron replacement cartridge for filter, 45 gph 53P93 Filter restriction indicator gauge 53P90
Consult burner manufacturer's instructions packaged with unit for further details concerning oil supply pipe connec tions.
Cat.
Number
Leak Check
After oil piping is completed, carefully check all piping con nections (factory and field) for oil leaks.
Oil Line Heater (Optional)
A heater for the oil line is available for applications that are located in cold climates. The heater warms the oil pipe to assist the initial start-up. An oil line heater is available from Beckett using part number 51621 (Beckett Start Helper).
Electrical Wiring
All wiring must conform to the National Electric Code (NEC), or Canadian Electric Code (CEC) and any local codes.
1 - Refer to the appliance rating plate for proper fuse size.
2 - Install the room thermostat and make wire connec
tions to the control. Avoid installing thermostat on an outside wall or where it can be affected by radiant heat. Set the adjustable heat anticipator on thermostat ac cording to the wiring diagram sticker provided on unit.
3 - Install a separate fused disconnect switch near unit so
power can be shut off for servicing.
Page 13
Page 14
4 - Complete line voltage wiring from disconnect switch
near unit to make‐up box.
NOTE - An equipment ground screw is provided. Refer to unit wiring diagram. Ground unit using a suitable ground wire.
CAUTION
Use copper conductors only.
IMPORTANT
WARNING
Run 24V Class II wiring only through specified low voltage opening. Run line voltage wiring only through specified high voltage opening. Do not combine voltage in one opening.
Typical ELO183DH Wiring Diagram
If using a programmable thermostat, be sure to use a type of thermostat that retains its memory in event of a power loss.
Figure 14
Page 14
Page 15
Unit Start-Up & Adjustments
CAUTION
Before starting unit, make sure the oil tank is adequately filled with clean No. 1 or No. 2 furnace oil.
NOTE - Water, rust or other contaminants in oil supply sys tem will cause malfunction and failure of the internal parts of the fuel pump.
CAUTION
Never burn garbage or paper in the heating system. Never leave papers near or around the unit.
CAUTION
Blower access door must be in place before start­up.
Burner Start-Up
1 - Set thermostat for heating demand and turn on elec
trical supply to unit.
2 - Open all shut-off valves in the oil supply line to the
burner.
3 - While the ignition is on, press and release the reset
button on the burner control (hold 1/2 second or less).
4 - Bleed the pump until all froth and bubbles are purged.
The bleed port is located on the bottom of the fuel pump. To bleed, attach a clear plastic hose over the vent plug. Loosen the plug and catch the oil in an empty container. Tighten the plug when all the air has been purged.
NOTE - A two-line fuel system will normally bleed itself by forcing air back to the tank through the return line. This type of bleeding procedure is not necessary.
5 - If burner fails to start within the set time, the burner
control will lock out operation. Press the reset button to reset the control as in step 3. See figure 2 for burner parts arrangement.
Table 9
Burner Specifications
Unit
ELO183DH101/114 100591-05 ARM2008 AF46XNHS 105,000 0.65gph X 80° B 140 F3 5 2.75
ELO183DH101/114 100591-05 ARM2008 AF46XNHS 120,000 *0.75gph X 80° B 140 F3 5 2.75
ELO183DH135/150 100591-06 ARM2009 AF46WPHS 140,000 0.85gph X 80° B 140 F4 5 3.38
ELO183DH135/150 100591-06 ARM2009 AF46WPHS 150,000 *1.00gph X 80° B 140 F4 5 3.38
*Nozzle must be field-installed for conversion to higher heating input. NOTE - All nozzles are Delavan brand
Burner
Number
Beckett
Spec. No.
Beckett
Air Tube Part
No.
Do not push the reset button on the primary control more than one time.
6 - If 2 pipe system fails to prime after pressing the reset
button one time, use the manual bleed port to prime the pump.
Fuel Pump Pressure Adjustment
Measure fuel pump pressure with unit off. Attach pressure gauge to pump outlet. Turn unit on and check pressure and compare to table 9. Adjust if necessary.
Temperature Rise Adjustment
To measure temperature rise, place plenum thermome ters in warm air and return air plenums. Locate thermome ter in warm air plenum where thermometer will not “see” the heat exchanger to prevent it from picking up radiant heat. Set thermostat to its highest setting to start unit. After plenum thermometers have reached their highest and steadiest readings, subtract the readings. The difference in temperatures in the supply and return air plenums should approximate the temperatures listed in table 8 and on the appliance rating plate.
If the temperature rise is not within the range listed, check the following items:
D Make sure that properly sized nozzle has been
used (table 9).
D Make sure that fuel pump pressure is correct. D If furnace is in cutback mode, check for:
Dirty filters, Dirty indoor coil, Restricted ducts, closed registers, etc.
Table 8
Temperature Rise
Unit Temperature Rise °F
ELO183DH101 65 - 75 ELO183DH114 70 - 80 ELO183DH135 65 - 75 ELO183DH150 70 - 80
Input
Rating
BTU/HR
Nozzle Size,
Spray, Angle, &
Pattern
Pump
Pressure
Head
Insertion
Length
Static
Plate
Diameter
Page 15
Page 16
Fan Delay
Fan on time is 1 to 30 seconds and non adjustable. Fan off time is 60 to 120 seconds and non adjustabe.
Limit Control
Limit Control — Do not adjust from factory setting.
Burner Adjustment
The following instructions are essential to the proper op eration of ELO183DH series oil furnaces. To prevent soot ing and prevent premature failure of the heat exchanger,, these instructions must be followed in sequence:
1. Draft—This test should be taken at the breach be
tween the outlet of the vent connector and the baro metric draft control. Generally a 1/4” hole will need to be drilled for the draft gauge to be inserted into the vent connector.
A minimum of 0.03 draft must be established without the burner in operation. With the burner in operation, the draft should be 0.04 to 0.05. This is VERY critical to the flame retention head burners.
Oil furnace installations also require careful inspection to make sure the chimney is in good shape and can ac commodate the products of combustion. The temper ature in the unconditioned space will also affect the draft if long vent connectors are allowed to get too cold.
2. Overfire Draft—This test should be taken with the
burner in operation. Remove the plug from the center of the inspection port. Insert your draft gauge into the hole.
A reading of the overfire draft should be 0.02 less than the reading found in the vent connector. If a positive reading is seen at this point, the combustion fan is pumping too much air into the heat exchanger. Make the necessary adjustments with the air shutter or air band.
3. Smoke Test—The smoke test should be taken at the
hole drilled in step 1.
Air Shutter / Band Adjustment
Loosen this screw to adjust air band.
Using a smoke test gun, adjust the air so that you will have just a trace (between 0 and #1) of smoke. If the burner is producing more than #1 smoke, adjust the air shutter (primary) and air band (secondary) to reduce the smoke. See figure 15. To adjust the air shutter, loosen the top screw on the air shutter (and lower screw, if necessary). Then, rotate the shutter until the desired smoke level is achieved. If smoke cannot be reduced to the desired level by moving the air shutter, adjust the air band to increase the air. To adjust the air band, loosen the air band screw and rotate the band.This is the starting point. Do not stop here.
4. CO2 Test—Again, take this sample at the vent pipe.
With the unit firing at a trace of smoke, take a sample of the CO2. From the results of this test, a “window of operation” will be determined. This window of opera tion establishes some tolerance. The tolerance the in staller builds in provides room within the set‐up for those things which might affect combustion. Those things which might affect combustion can then do so without causing the unit to start sooting/smoking. Things which might affect combustion include a nozzle going bad, draft that changes during different climatic conditions, dirty oil, dirt obstructing the air inlet, etc.
To build in a “window of operation,” set up the burner to be 2% less in CO2. For example, if you find a reading of 12% CO2, adjust the air shutter (and air band, if neces sary) to increase the air and drop the CO2 to 10%.
5. Retest the Smoke—With a drop in the CO2 and in
crease in the air you should see that the smoke has re turned to 0.
6. Retest the Overfire Draft—This test serves to con
firm that you have not increased the air too much. Again you do not want a positive pressure at the test port. It should still be 0.02 less than the draft pressure reading taken at the breach. You may need to increase the stack draft by adjusting the barometric draft con trol.
7. Stack Temperature—Take a stack temperature
reading in the vent pipe. Subtract the room air temper ature from the stack temperature. This will give you the net stack temperature. Use the efficiency charts pro vided in most CO2 analyzers to determine furnace effi ciency.
8. When the proper combustion and smoke readings have been achieved, re-tighten the air shutter screw(s) and air band screw.
Air Shutter
Air Band
(Secondary)
Air Band
Figure 15
Service
Servicing Filter
NOTE - Under no circumstances should the access panels to the blower compartment be left off or left partially open.
1. Throw‐Away Type Filters — Filters should be checked monthly and replaced when necessary to assure prop er furnace operation. Replace filters with like kind and size filters.
Page 16
Page 17
2. Reusable Type Filters — Filters should be checked monthly and cleaned when necessary to assure prop er furnace operation. Use warm water and a mild de tergent. Replace filter when dry. Permanent filters supplied with ELO183DH furnaces do not require oil ing after cleaning. Examine filter label for any for spe cial instructions that may apply.
Servicing Blower
Blower motor is pre-lubricated and sealed for extended op eration. No further lubrication is required. Disconnect pow er to unit before cleaning blower wheel for debris.
Servicing Nozzle
Replace nozzle every year to to ensure proper operation. Clogged nozzles will result in improper firing or non‐firing of unit.
Flue Pipe Inspection
The flue pipe should be inspected annually by a qualified service technician. Remove and clean any soot or ash found in the flue pipe. Inspect pipe for holes or rusted areas. If replacement is necessary, replace with the same size and type as required by code. Inspect the flue draft control device and replace if found defective.
Cleaning Heat Exchanger
1. Remove the vent pipe from the furnace.
2. Remove the locking screws and the caps from the clean-out tubes. Remove flue access elbow.
3. Using a long spiral wire brush, sweep down the outer drum of the heat exchanger. Then using the hose at tachment, vacuum out loose debris.
4. Remove the locking screw and cap from the observa tion tube and with the spiral wire brush, reach upward toward the rear of the heat exchanger to clean out the crossover tube.
CAUTION
Do not attempt to clean the combustion chamber. It can be easily damaged.
5. Replace the clean-out caps and flue access elbow. Make sure locking screws are secure.
6. Brush out and vacuum the vent outlet area of the outer drum and replace vent pipe.
7. Clean around burner, blower deck and vestibule area.
NOTE - A heat exchanger clean‐out kit ABRSH380 (35K09) is available from Lennox. The kit includes a radiator brush, a tapered brush and a non-metallic 36” spiral wire handle.
GeniSyst Primary Burner Control
ELO183DH units are equipped with the Beckett GeniSyst 7505B primary burner control. The control is positioned on the upper right-hand side of the Beckett AFG burner assembly. The control includes a reset button and three status lights. See figure 16 for location of reset buttons and status lights. Table 10 details reset button operation. Table 11 details status light function.
Additional information on the GeniSyst 7505B primary burner control is provided with this furnace.
Beckett GeniSyst 7505B Primary Burner Control
Reset Button
with Red Status Light
FRONT VIEW
Yellow Pump
Prime Status Light
Green Flame
Status Light
Cad Cell
Connections
Wiring
Connections
REAR VIEW
Figure 16
Page 17
Page 18
Table 10
Reset Button Operation
If the burner is in the
below state:
Button Click
(press < 1 second)
Valve-on Delay, Trial for Ignition, Ignition Carryover
Run (igniter is shut off) No action
Pump Prime No action Exit Pump Prime mode and return to Standby
Go to pump prime (see “Priming the Pump” above)
No action
Status Light Function
R
Green
Flame Sensed during normal operation (Could be stray light during standby)
Yellow
Control is in pump prime mode or Reset button currently held for 15+ seconds.
Heating Sequence - Actions & Responses
1. Action: Thermostat calls for heat (W terminal is en
ergized) Response:
D Primary control is energized. D After 15-second prepurge, power is sent to the oil
delay valve, ignition occurs and flame is established.
D Igition sequence continues for 10 seconds after
flame is sensed. Oil will continue to flow as long as cad cell senses flame.
D Heat fan on timing (1 to 30 seconds) begins. When
timing is complete, the indoor blower is at heat speed and warm air is delivered to the controlled space.
2. Action: Thermostat ends call for heat (W terminal
is de-energized) Response:
D After the thermostat is satisfied, the thermostat
circuit opens. The oil delay valve and burner are de-energized.
D Burner is de-energized. D Heat fan off timing (60 to 120 seconds) begins.
When timing is complete, indoor blower is de-en ergized.
3. Action: Burner fails to light
Response:
D Oil primary control enters soft lockout after ignition
failure (15 seconds without flame being sensed). Push reset button on primary control for one sec ond to reset soft lockout.
Pushing the reset button will:
Button Hold
(press > 1 second)
tuokcoLtfoSmorfteseRtuokcoL
Disable the Burner: Any time the burner is running, press and hold the reset button to disable the burner. The burner will remain off as long as the button is held.
Table 11
D After soft lockout reset, oil primary control allows
second ignition attempt. Primary control enters hard lockout after second ignition failure (15 sec onds without flame being sensed). Push reset but ton on primary control for 15 seconds until light on control turns yellow to reset hard lockout.
D Burner motor is de-energized.
4. Action: Established flame fails
Response:
D Burner motor is de-energized and oil primary con
trol goes into recycle mode.
D If the fan off delay is longer than the recycle timing,
the indoor blower continues to run on heating speed through the next trial for ignition.
5. Action: Limit Switch Opens
Response:
D Oil primary control de-energizes burner. D Indoor blower is energized immediately at cool
speed.
D Oil primary control is de-energized. D Indoor blower runs as long as limit stays open.
6. Action: Limit Switch Closes
Response: If there is a heating demand, oil primary control and ignition sequence begins.
Button Hold
(press 15+ seconds)
Reset from Restricted (Hard) Lockout
Enables pump priming After the reset button has been held for 15 seconds. The button can then be clicked during the next ignition sequence to enter pump prime mode.
gnihsalFylsuounitnoCnOroloCthgiL
tuokcoLtfoStuokcoL)draH(detcirtseRde
Recycle
N/A
Page 18
Page 19
Troubleshooting
Burner failure or improper operation can result from a num ber of different causes. Often the cause can be pinpointed by observing the different types of failure or by the process of elimination.
The following troubleshooting charts list some failures, causes and a sequence of steps to isolate the point of fail ure. Check the simplest and most obvious items before progressing to other items.
Troubleshooting: Fan operating sequence
Action System Response
Thermostat calls for heat. (W terminal is energized.)
Thermostat ends call for heat. (W terminal is de-energized.)
Burner fails to light. Oil primary control locks out within lockout timing (timing depends on oil primary control).
Established flame fails. Burner motor is de-energized and oil primary control goes into recycle mode.
Thermostat begins call for cool. (G and Y terminals are energized.)
Oil primary control is energized.
Ignition system and oil primary control start the furnace. Oil flows as long as cad cell senses flame.
Burner motor is energized and heat fan on delay timing begins. When timing is complete, the circulating fan is energized at heat speed and warm air is delivered to the controlled space.
Oil primary control is de-energized, terminating the burner cycle.
Heat fan off delay (60 to 120 seconds) timing begins. When timing is complete, the circulat ing fan is de-energized.
Oil primary control and circulating fan are off.
Burner motor is de-energized.
If heat fan has started, it continues through the delay off period.
If heat fan off delay is longer than the recycle delay timing, the heat fan continues to run through the next trial for ignition.
Circulating fan is energized at the cool speed.
Cooling compressor turns on immediately.
Thermostat ends call for cool. (G and Y terminals are de-energized.)
Thermostat begins call for fan. (G terminal is energized.)
Thermostat ends call for fan. (G terminal is de-energized.)
Limit switch string opens. Oil primary control shut off the burner.
Limit switch string closes. Heat fan off delay (60 to 120 seconds) begins.
Continuous circulating fan is connected. (Optional connectors are available for separate circulat ing fan speed tap.)
Humidity control is connected. (Optional connectors are available for 120 Vac humidifi er.)
Circulating fan and cooling compressor turn off immediately.
Circulating fan is energized immediately at cool speed.
Circulating fan is de-energized.
Circulating fan is energized immediately at heat speed.
Oil primary control is de-energized.
Circulating fan runs as long as limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heat speed to cool speed.
Circulating fan turns off after the selected heat fan off delay timing.
Oil primary control is energized, initiating burner light off.
Circulating fan is energized at low speed when there is no call for heat, cool or fan.
Humidifier connections are energized when the burner motor is energized.
Page 19
Page 20
Troubleshooting: Burner fails to start.
Source Procedure Causes Correction
Thermostat in OFF or COOL Switch to HEAT.
Thermostat Check thermostat settings.
Check burner motor, primary
Safety Overloads
Power
Thermostat
Cad Cell
Primary Control
Burner
safety control, & auxiliary limit switch.
Check furnace disconnect switch & main disconnect.
Touch jumper wire across TR­TW terminals on primary control. If burner starts, then fault is in the thermostat circuit.
Disconnect the flame detector wires at the primary control. If the burner starts, fault is in the detector circuit.
Place trouble light between the orange and white leads. No light indicates that no power is going to the control.
Place trouble light between the orange and white leads. No light indicates faulty control.
Place the trouble light between the orange and white leads to the burner motor. No light indi cates that no power is getting to the motor.
Place trouble light between the black and white leads to the blower motor. Light indicates power to the motor and burner fault.
Thermostat is set too low
Burner motor overload tripped Push reset button pump motor.
Primary control tripped on safe ty
Auxiliary limit switch tripped on safety
Open switch Close switch.
Blown fuse or tripped circuit breaker
Broken or loose thermostat wires
Loose thermostat screw con nection
Dirty thermostat contacts Clean contacts.
Thermostat not level Level thermostat.
Faulty thermostat Replace thermostat.
Open circuit in wiring between fan relay and oil primary control.
Flame detector leads are shorted
Flame detector exposed to light Seal off false source of light.
short circuit in the flame detec tor
Primary or auxiliary control switch is open
Open circuit between discon nect switch and limit control
Low line voltage or power fail ure
Failed internal control circuit Replace the control.
Blown fuse Replace the fuse.
Binding burner blower wheel
Seized fuel pump
Failed burner motor Replace the motor.
Turn thermostat to higher tem perature.
Reset primary control.
Reset auxiliary limit.
Replace fuse or reset circuit breaker.
Repair or replace wires.
Tighten connection.
Check wiring between fan relay and oil primary control.
Separate leads.
Replace detector.
Check adjustment. Set the maximum setting.
Jumper terminals; if burner starts, switch is faulty, replace control.
Trace wiring and repair or re place it.
Call the power company.
Turn off power and rotate the blower wheel by hand. If seized, free the wheel or re place the fuel pump.
Page 20
Page 21
Troubleshooting: Burner starts, but no flame is established.
Source Procedure Causes Correction
Oil Supply
Oil Filters & Oil Line
Oil Pump
Nozzle
Ignition Electrodes
Ignition
Transformer
Burner Motor
Check tank gauge or use dip stick.
Coat dip stick with litmus paste and insert into bottom of tank.
Listen for pump whine. Tank shut-off valve closed Open valve.
Listen for pump whine.
Open bleed valve or gauge port. Start the burner. No oil or milky oil indicates loss or prime.
Install pressure gauge on pump and read pressure. Should not be less than 140 psi.
Observe the oil spray (gun as sembly must be removed from unit). Inspect the nozzle for plugged orifice or carbon build­up around orifice.
Remove gun assembly and in spect electrodes.
Start burner and observe spark. Check line voltage to transform er primary.
Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for bind ing or excessive drag.
No oil in tank Fill tank.
Water in oil tank
Oil line filter is plugged Replace filter cartridges.
Kinks or restriction in oil line Repair or replace oil line.
Plugged fuel pump strainer Clean strainer or replace pump.
Air leak in oil supply line
Pump is partially or completely frozen. No pressure and the motor locks out on overload.
Coupling disengaged or broken
- no pressure
Fuel pressure too low Adjust to 140 psi.
Nozzle orifice plugged
Nozzle strainer plugged
Poor or off center spray
Fouled or shorted electrodes
Dirty electrodes
Eroded electrode tips
Improper electrode gap spacing
Improper position of electrode tips
Bad buss bar connection Retension and realign.
Cracked or chipped insulators Replace electrode.
Low line voltage
Burned out transformer wind ings.
No spark or weak spark
Low line voltage
Pump or blower overloading motor
Faulty motor Replace motor.
If water depth exceeds 1 inch, pump or drain water.
Locate and correct leak.
Tighten all connections.
Replace pump.
Re-engage or replace coupling.
Replace nozzle with the same size, spray angle, and spray pattern.
Clean or replace electrodes.
Clean electrode tips and use T-501 gauge to reset the gap to 5/32 inches and correctly posi tion tips.
Check voltage at power source. Correct cause of voltage drop or call the power company.
Replace the transformer.
Properly ground the transformer case.
Check voltage at power source. Correct cause of voltage drop or the call power company.
Correct cause of overloading.
Page 21
Page 22
Troubleshooting: Burner starts and fires, but lock out on safety.
Source Procedure Causes Correction
Unbalanced fire Replace nozzle
Reduce combustion air - check combustion.
Increase combustion air - check combustion.
Adjust barometric draft control for correct draft.
Correct draft or remove restric tion.
Secure connections or replace cad cell holder and wire leads.
Check cad cell for proper align ment. Check cad cell face and clean, if necessary.
Poor Fire
Flame Detector
Primary Control
After burner fires, immedi ately jumper across flame detector termi nals at the pri mary control.
If burner con tinues to run, this may be due to poor fire. Inspect fire.
If fire is good, fault is in the flame detector. Check detec tor circuit.
If burner locks out on safety, fault is in the primary con trol.
Too much air - -lean short fire
Too little air - - long dirty fire
Excessive draft
Too little draft or restriction
Faulty cad cell (open circuit) Replace cad cell.
Loose connections or broken cad cell wires
Cad cell cannot sense flame
Primary control circuit failed Replace primary control.
Troubleshooting: Burner Starts and Fires, but Loses Flame and Lock Out on Safety
Source Procedure Causes Correction
Unbalanced fire Replace nozzle
Poor Fire
Flame Detector
Oil Supply
After burner fires, immedi ately jumper across flame detector termi nals at the pri mary control.
Listen for pump whine
If burner con tinues to run (does not lock out of safety), fault may be due to poor fire. Inspect fire.
If fire is good, fault is in the flame detector. Check detec tor circuit.
If burner loses flame (does not lock out on safety), fault is in the fuel sys tem.
Too much air - - lean short fire
Too little air - - long dirty fire
Excessive draft
Too little draft or restriction
Faulty cad cell (open circuit) Replace cad cell.
Loose connections or broken cad cell wires
Cad cell cannot sense flame
Pump loses prime - air slug Prime pump at bleed port
Pump loses prime - air leak in supply line
Water slug in line Check oil tank for water (over 1
Partially plugged nozzle or nozzle strainer
Restriction in oil line Clear restriction.
Plugged fuel pump strainer Clean strainer or replace pump.
Cold oil - outdoor tank Change to number 1 oil.
Reduce combustion air - check combustion.
Increase combustion air - check combustion.
Adjust barometric draft control for correct draft.
Correct draft or remove restric tion.
Secure connections or replace cad cell holder and wire leads.
Check cad cell for proper align ment. Check cad cell face and clean, if necessary.
Check supply line for loose con nections and tighten fittings.
inch) pump or drain out water. Replace nozzle.
Page 22
Page 23
Troubleshooting: Burner starts and fires, but short cycles (too little heat)
Source Procedure Causes Correction
Heat anticipator set too low Correct heat anticipator setting.
Thermostat Check thermostat.
Connect voltmeter between line voltage connections to primary
Limit Control
control (black & white leads). If burner cycles due to power inter ruption, it is cycling on limit.
Vibration at thermostat Correct source of vibration.
Thermostat in the path of a warm air draft
Dirty furnace air filters Clean or replace filter.
Temperature rise too high
Blower motor seized or burned out
Blower wheel dirty Clean blower wheel.
Wrong motor rotation Replace motor.
Restrictions in return or supply air system
Shield thermostat from draft or relocate.
Check fo proper nozzle size. Replace nozzle, if necessary. Check for restrictions and re move, if necessary. Check speed tap jumper and make sure it is still in factory position.
Replace motor.
Correct cause of restriction.
Power
If voltage fluctuates, fault is in the power source. Recheck voltage at the power source.
Loose wiring connection Locate and secure connection.
Low or fluctuating line voltage Call power company.
Troubleshooting: Burner runs continuously (too much heat).
Source Procedure Causes Correction
Thermostat
Primary control
Disconnect thermostat wires at the pri mary control.
If burner turns off, fault is in the thermostat circuit.
If burner does not turn off, fault is in the primary control.
Shorted or welded thermostat contacts
Stuck thermostat bimetal
Thermostat not level Level thermostat.
Shorted thermostat wires Repair short or replace wires.
Thermostat out of calibration Replace thermostat.
Thermostat in cold draft
Failed primary control Replace the primary control.
Repair or replace the thermo stat.
Clear obstruction or replace thermostat.
Correct draft or relocate the thermostat.
Page 23
Page 24
Troubleshooting: Burner runs continuously (too little heat).
Source Procedure Causes Correction
Too much combustion air Reduce combustion air.
Combustion
Oil Pressure
Check burner combustion for CO2, stack tem perature, and smoke
Inspect fire and check
oil pressure.
Low CO
2
less
than 10%.
High smoke reading more than a trace.
High stack tem perature is more than 550
_F Net.
Air leaks into heat exchanger around inspection door, etc.
Excessive overfire draft
Incorrect nozzle assembly depth
Dirty or plugged heat exchanger
Insufficient overfire draft Increase draft.
Incorrect nozzle assembly depth
Too little combustion air Increase combustion air.
Low volume indoor blower air
Dirty heat exchanger Clean heat exchanger.
Dirty burner blower wheel Clean burner blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or dampers
Partially plugged or bad nozzle Replace nozzle.
Oil pressure is too low (less than 140 psi.)
Correct cause of air leak.
Adjust barometric draft con trol for correct draft.
Set to 1.13.
Clean heat exchanger.
Readjust burner.
Set to 1.13.
Check pump coupling for wear / slippage.
Readjust registers or damp ers.
Increase oil pressure to 140 psi.
ELO183DH Start-Up & Performance Check List
Job Name
Job Location Installer Unit Model No.
HEATING SECTION
Electrical Connections Tight?
Supply Voltage
Blower Motor H.P.
Piping Connections Tight?
Flue Connections Tight?
Burner Model No.
Oil Pump Pressure [recommended minimum 140 psi]
Blower Motor Amps
All Valves Open?
Vent Clear?
Serial Number
Filter Clean & Secure?
Job No.
Serial No.
Date
City
City
PROPER DRAFT
Draft Reading (recommended .03-.04 inches w.c.)
% CO
2
Smoke Test
Stack Draft Overfire Draft
Net Stack Temp
Calibrated? Heat Anticipator Properly Set? Level?
% O
2
THERMOSTAT
State State
Serviceman
ppm CO
Ambient Temp
Temperature RiseExternal Static Pressure
Page 24
Loading...