Lennox Elite CBX32M-024, Elite CBX32M-030, Elite CBX32M-018, Elite CBX32M-036, Elite CBX32M-042 Installation Instructions Manual

...
Page 1
INSTALLATION
,B,2008 Lennox industries Inc,
Dallas, Texas, USA
X_ WARNING
_ CAUTION
IMPORTANT
INSTRUCTIONS
Elite® Series CBX32M Units
MULTI-POSITION AIR HANDLER 505,342M
05108 Supersedes 04/08
CBX32M Up-flow/Down-flow Unit Dimensions .... 2
CBX32M Horizontal LH/RH Unit Dimensions ...... 3
General Information ........................... 4
Shipping and Packing List ...................... 4
Requirements ................................. 4
Installing the Unit .............................. 4
Brazing Connections ........................... 4
Installing the Condensate Drain ................. 8
_puTeCh ical
n
blications
Litho U.S.A.
_, IMPORTANT
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
BLOWER MOTOR
SHIPPING BOLT
TOP CAP SHIPPING BRACKET (REPLACE
SCREWS IN TOP CAP AFTER REMOVAL)
C
Making Electrical Connections .................. 9
Sealing the Unit ............................... 12
Inspecting and Replacing Filters ................. 9
Adjusting the Blower Speed .................... 12
Repairing or Replacing Cabinet Insulation ......... 14
CHECK FOR AND REMOVE THE FOLLOWING ITEMS BEFORE OPERATING UNIT.
BLOWER HOUSING SUPPORT PAD
B
BLOWER MOTOR SHIPPING
BRACKET
D
HORIZONTAL DRAIN PAN (SEE UP-FLOW
APPLICATIONS ON PAGE 4 AND
DOWN-FLOWAPPLICATIONS ON PAGE 6)
iiiiiiiiiiiii_i':i-_
REFRIGERANT LINE PLUGS [SEE
BRAZING CONNECTIONS ON PAGE 7]
F
05/08
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Page 1
E
505,342M
IIIIIIIIIIIIIIIIIIIIIIHIIIIIIIIIIIIIIIIIIIIIIII
Page 2
CBX32M Model Dimensions (for Up-flow, Down-flow, LH and RH Horizontal Applications)
-018/-024 -030 -036 -042 -048/-060
Dimension inches mm inches mm inches mm inches mm inches mm
A 45-1/4 1149 49-1/4 1251 51 1295 52-1/2 1333 58-1/2 1486
B 16-1/4 413 21-1/4 540 21-1/4 540 21-1/4 540 21-1/4 540
C 20-5/8 524 20-5/8 524 22-5/8 575 22-5/8 575 24-5/8 625
D 14-3/4 375 19-3/4 502 19-3/4 502 19-3/4 502 19-3/4 502 E 19 483 19 483 21 533 21 533 23 584
F 15 381 20 508 20 508 20 508 20 508
G 24-5/8 625 24-5/8 625 26-3/8 670 27-7/8 708 27-7/8 708
H 20-5/8 524 24-5/8 625 24-5/8 625 24-5/8 625 30-5/8 778
3/4
(19)
SUPPLY
AIR OPENING _
(FOR UP-FLOW AND DOWN-FLOW POSITIONS)
ilU i iiiii!i¸! ! i!i ii i i i i i iii i ii iiiiiiii ii!iiii i !i!i ! ! !!i! i i iiiiiiiii iiiiiiiiiiiii 4_8/8(111,
iiiiiiiii_i_iiiiiiiii_ii_i!_iiiii_!i_!ii_!_!!i!i!!!_!!_i!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_!_i_I_i!_ii!i_i_i_!_i!i_i!_!iiii_!_!i_i_!_i_i!_i_i_ii_ii_!_!_i_i_ii_i_i_i_i_!_!i_!i_!i_i_i!!i!i_i_i!_i_ii_i_!_ii_ii_i!i_!iii_i__SUCT'°NL'NE
- 3/4 (19)
LINE VOLTAGE INLETS (TOP AND LEFT SIDE)
Top View 5/8
RETURN AIR RETURN AIR |
L oc ss
5/8 5/8 1 5/8
(15) Front View (15) (25) Side View (15)
F E "'"-_
LOW VOLTAG E INLETS (TOP AND RIGHT
SIDE)
(15)
OPTIONAL
ELECTRIC
(FIELD-
INSTALLED)
HEAT
Up-flow Position
i ililil .CONDENSATEiii !i DRA,NS(2,
PIPING PLATE DETAIL
1-3/4 (44)
SUCTION
LINE
LINE
OPTIONAL
ELECTRIC
INSTALLED)
LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)
/
5/8(15)
(HORIZONTAL)
DRAINS (2) (UPFLOW AND
DOWNFLOW_
1 (25)
\
11-1/16
Side View (15) (15) Front View
_KIT NUMBER 83M57 (LB-909844A) REQUIRED TO CONVERT
5/8 5/8
Down-flow Position
UNIT TO DOWN-FLOW APPLICATIONS.)
t
FILTER
Top View ACCESS
A i,
H
A
V
505342M 05/08
Page 2
Page 3
CONDENSATE
DRAINS (2)
(UPFLOW AND "_
DOWNFLOW)
CONDENSATE
DRAINS (2)
(HORIZONTAL)
PIPING PLATE
DETAIL
5-3/8 2 FILTER
5-3/4 -3/ 1-1/2
44 (38)
5/8
(16)I
(16) (25)
(5/8)j End View
Horizontal Position (Right-Hand Air Discharge)
C
LIQU{D _SUCTION OPTIONAL ELECTRIC
LINE LINE HEAT (FIELDqNSTALLED)
FOR DIMENSIONS "A" THROUGH
"H", SEE CHART ON PAGE 2.
Top View
(_68) 3/4
S,DE,
'N SlTOT 1,19
B D
LOWVOLTAGE:
INLETSBOTTOM_._1
AND RIGHT I_
FILTERACCESS Front View End View
PIPING PLATE t
DETAIL 1-1/8
SIDE) --(19)
4-3/8 t
(111)
(29) _-
3/4 AND LEFT SIDE)
(19) 11H 16
o,
lll°°°
(19)-
LINE VOLTAGE INLETS
(BOTTOM AND LEFT SIDE)
End View
LOW VOLTAGE
INLETS (TOP
OPTIONAL ELECTRIC FILTER SUCTION LIQUID HEAT (FIELD INSTALLED) LINE LINE
B
CONDENSATE DRAINS (2)
(HORIZONTAL) (44)-
Top View
Front View
.FILTER
ACCESS
lq/2
(38)
Horizontal Position (Left-Hand Air Discharge)
SUCTION i
LIQUID
LINE
1
(25)
End View
5/8
5/8
(16)
5/8
(18)
Page 3
CBX32M SERIES
Page 4
,&,WARNING
The Lennox Elite* Series CBX32M air handler units are designed for installation with a matched remote outdoor
unit that is charged with HFC-410A refrigerant and optional
field-installed electric heat, The air handler units are for
indoor installation only. These instructions are intended as a general guide and do
not supersede local or national codes in any way. Consult authorities having jurisdiction before installation. Check
equipment for shipping damage; if found, immediately report damage to the last carrier.
Package 1 of 1 contains the following:
1--Assembled air handler unit
In addition to conforming to manufacturer's installation instructions and local municipal building codes, installation of Lennox air handler units (with or without optional electric
heat), shall conform with the following National Fire Protection Association (NFPA) standards:
NFPA No. 90A - Standard for Installation of Air Conditioning and Ventilation Systems
NFPA No. 90B - Standard for Installation d Residence Type Warm Air Heating and Air Conditioning Systems
This unit is approved for installation clearance to combustible material as stated on the unit rating plate,
Accessibility and service clearances must take
precedence over combustible material clearances.
CBX32M units are factory-configured for up-flow or horizontal right-hand discharge installation. For down-flow
or horizontal left-hand discharge, some field modification is required.
WARNING
IMPORTANT
DISASSEMBLE AND REASSEMBLE AIR HANDLER UNIT
The CBX32M air handler unit consists of two sections which are shipped assembled from the factory, If
necessary, the unit may be disassembled to facilitate setting the unit, Follow the steps below: To disassemble:
Step 1_ Remove access panels. Step 2.. Remove both blower and coil assemblies. This
will lighten the cabinet for lifting,
Step 3.. Remove one screw from the left and right posts
inside the unit. Remove one screw from each side on the back of the unit, Unit sections will
now separate,
To reassemble: Step 1.. Align cabinet sections together,
Step 2,, Reinstall screws, Step 3.. Replace blower and coil assemblies. Step 4,, Replace access panel.
UP-FLOW APPLICATION
Use the following procedures to configure the unit for
up-flow operations: Step 1.. Remove access panels. Remove corrugated
padding from the space between the blower and coil assemblies.
Step 2.. The horizontal drain pan must be removed when
the coil blower is installed in the up-flow position,
Removing horizontal drain pain will allow proper
airflow and increase efficiency.
Step 3.. Place unit in desired location. Make sure that
unit is level, Connect return and supply air plenums as required using sheet metal screws as illustrated in figure 1,
Step 4.. Install units which have no return air plenum on
a mounting stand that is at least 14" from the
505342M 05/08
Page 4
Page 5
floorfor properair return.Lennoxoffersan Step2_
optionalup-flowunitstandaslistedintable1.
HORIZONTAL DRAIN PAN
r q I(MUST BE REMOVED)
I; II
UP-FLOW/ II
DRAIN PAN
DOWN-FLOW _J
Table 1. Optional Unit Side Stand (Up-Flow Only)
Model Kit Number
-21,-26, and -31 45K31
-41 through -65. 45K32
i i
Figure 1. Upflow Configuration
Step 3..
No further adjustment is necessary. Set unit so that it is sloped 1/4 inch toward the drain pan end of the unit as illustrate in figure 2 on page 5.
If the unit is to be suspended, it must be supported along the entire length of the cabinet as illustrated in figure 3. Ifa strap is used, attach
a piece of angle iron or sheet metal to the unit (either above or below) so that the full length of the cabinet is supported. Use securing screws which are no longer than 1/2 inch to avoid damaging the coil or filter, Connect the return and supply air plenums as required using sheet
metal screws.
CAUTION
HORIZONTAL DRIP SHIELD
V
HORIZONTAL I I I I
DRAIN PAN "_I__
DRA,NPAN
NO ADJUSTMENT IS NECESSARY
Figure 2. Right-Hand Discharge Configuration
ANGLE IRON OR
SHEET METAL
SCREWS
MAX.
1/2 IN. q
FRONT VIEW END VIEW
Figure 3. Suspending Horizontal Unit
HORIZONTAL RIGHT-HAND DISCHARGE
APPLICATION
Use the following procedures to configure the unit for horizontal right-hand discharge operations:
NOTE - For horizontal applications, an secondary drain
pan is recommended, Refer to local codes,
Step 1.. Remove access panels. Remove corrugated
padding from the space between the blower and coil assembly.
ELECTRICAL INLET
CLEARANCE 4 IN. (102 MM)
HORIZONTAL LEFT-HAND DISCHARGE
APPLICATION
Use the following procedures to configure the unit for horizontal left-hand discharge operations:
NOTE - For horizontal applications, an secondary drain
pan is recommended. Refer to local codes.
Remove access panels. Remove corrugated padding from the space between the blower and coil assembly before
operation. Step 1.. Remove coil assembly from unit and remove the
horizontal drain pan as illustrated in figure 4, detail A on page 6.
Step 2.. Remove drain plugs from back drain holes on
horizontal drain pan and reinstall them on front holes.
A IMPORTANT
Step 3..
Step 4..
Step 5..
Rotate the drain pan 180° front to back and install it on the opposite side of coil,
Remove screws from top cap. Remove horizontal drip shield screw located in the center of the back coil end seal as illustrated in figure 4, details B and C on page 6.
Rotate horizontal drip shield 180° front to back.
Page 5
CBX32M SERIES
Page 6
PLUGGED
END
OPENENDFOR
CONDENSATION
DRAIN
COIL
COIL SHOWN IN UP-FLOW
POSITION FOR EASY
CONVERSION
DETAIL A
(DRAIN PAN)
ORIGINAL PLUG
LOCATION
TOP CAP ROTATED TO CORRECT POSITION
SUPPORT
TOP CAP SCREWS
DETAIL B
(TOP CAP)
\
TOP _ _ _ ALIGN HOLES WITH
CAP HOLES IN COIL END
_'_o _ PLATE.
BEND BACK COIL END SEAL
90 _ / _
DRAIN PAN [
LOCATION
G
Figure 4. Left-Hand
Step 6_ Remove plastic plug from left hole on coil front
end seal and reinstall plug in back hole. Reinstall
horizontal drip shield screw in front coil end seal, Drip shield should drain downward into horizontal drain pan inside coil,
Step 7,. Rotate top cap 180° front to back and align with
unused screw holes. Holes must align with front
and back coil end plates. Note that top cap has a 45° bend on one side and 90 ° bend on the
other. The 90° bend must be on the same side as the horizontal drain pan as illustrated in figure
4 on page 6,
NOTE -Be very careful when you reinstall the screws into coil end plate engaging holes. Misaligned screws may damage the coil,
Step 8,, From the up-flow position, flip cabinet 90° to the
left and set into place, Replace blower assembly. Secure coil in place by bending down tab on
cabinet support rail as illustrated in figure 5 on page 6.
NOTE - For horizontal applications in high humidity areas, seal around the exiting drain pipe, liquid line and
suction line to prevent infiltration of humid air,
Step 9,. Knock out drain seal plate from access door,
Secure plate to cabinet front flange with screw
provided, Step 10,, Flip access door and replace it on the unit. Step 11,. Set unit so that it is sloped 1/4 inch toward the
drain pan end of the unit, Connect return and supply air plenums as required using sheet
metal screws, Step 12,. If the unit is to be suspended, it must be
supported along the entire length of the cabinet
505342M 05/08
t
DETAIL C
Discharge Modifications
as illustrated in figure 3 on page 5. If using a chain or strap, attach a piece of angle iron or sheet metal to the unit (either above or below the unit), so that the full length of the cabinet is supported. Use securing screws which are no
longer than 1/2 inch to avoid damaging the coil or filter, Use sheet metal screws to connect the
return and supply air plenums,
SECURING TAB ON
CABINET SUPPORT RAIL
\
Figure 5. Left-Hand Discharge Configuration
DOWN-FLOW APPLICATION
Use the following procedures to configure the unit for
down-flow operations:
WARNING
NOTE - If down-flow application is required, separately order kit number 83M57 and install per kit's instructions, Also, use metal or class I supply and return air plenums,
Page 6
HORIZONTAL DRIP SHIELD
_ HORIZONTALDRAIN PAN
Page 7
COMBUSTIBLE FLOOR ADDITIVE BASE
PROPERLY-SIZEDi
FLOOR OPENING,,_
Figure 6. Combustible Flooring Additive Base
On combustible flooring, use an additive base as illustrated in figure 6. and use the following procedures:
WARNING
IMPORTANT
Jh 11-3/8
1-5/8(41)
T:
oox32 !i
CB30M-21/26
20 (508)
CBX32M-41 to -65
CB3OM-3_ t_65
5/8 (16) 1OPENING3-3/8(340) _ 1_
_1- (289) --I_
_ i{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{{;i;.............
_1-1-5/8 (41)
SUPPLY
AIR
OPENING
221/8 562 -,.i
(mm)
l inches
18-1/4(464) CBX32M-21/26 and 31
CB30M-21/26
23-1/4 (591) CBX32M-41 to -65
B30M-31 to 65
iI JI 2(51)
SIDE VIEW _i,
Figure 7. Downflow Combustible Base Dimensions
Step 1.. Cut an appropriately sized opening for
combustible base as illustrated figure 7. Step 2.. Set the additive base into opening. Step 3.. Connect supply air plenum to the additive base.
All coils are equipped with a factory-installed, internally
mounted check/expansion valve, which is suitable for use in applications as follows:
valve suitable for HCFC-22 use (CBX32M unit)
valve suitable for HFC-410A use (CB30M unit) The CBX32M/CB30M air handler's coil line sizes are listed
in table 2. Use Lennox L15 (sweat) series line sets (refer to the outdoor unit Engineering Handbook for proper size,
type and application). For field-fabricated refrigerant lines, see the piping section of the Lennox Unit Information
Service Manual.
AIR HANDLER UNIT
Step 4.. Set the unit on the additive base so flanges of the
unit drop into the base opening and seal against
the insulation strips. The unit is now locked in
place. Step 5_ Install retum air plenum and secure with sheet
metal screws. If the homeowner reports water dripping from supply air
diffusers, check the shields and tape. Make sure the tape is completely attached to the edges of the drip shield, and
that the drip shield is wedged firmly in place.
SUCTION LINE
LIQUID LINE
Figure 8. Brazing Connections
NOTE - CBX32M series evaporators use nitrogen or dry air as a holding charge. If there is no pressure when the
rubber plugs are removed, check the coil or line set for leaks before installing. After installation, pull a vacuum
on the line set and coil before releasing the unit charge into the system.
Page 7
CBX32M SERIES
Page 8
NOTE - See outdoor unit instructions on how to flow nitrogen through line sets.
Step 1_ Remove access panel, Step 2,, Remove the refrigerant line caps from the
refrigerant lines,
Step 3,, Use a wet rag to protect TXV sensing bulb (or
remove it) when brazing suction line connections,
Step 4..
Place a wet rag against piping plate and around
the suction line connection, The wet rag must be
in place to guard against damage to the paint,
Step 5..
With the wet rag in place, position a field
provided elbow fitting to the air handler's suction line and line set, Start nitrogen flow before
brazing,
Step 6_
After the procedure is completed then remove the wet rag,
Step 7_
Place wet rag against piping plate and around the liquid line connection. Position liquid line elbow to air handler's suction line and to line set.
Start nitrogen flow and begin brazing both
connections and after procedure is completed then remove both wet rags,
Step 8..
Refer to instructions provided with outdoor unit for leak testing, evacuating and charging
procedures,
Connect main condensate drain and route downward to an open drain or sump. Do not connect drain to a closed waste
system. Refer to figure 9 on page 8 for typical condensate trap configuration.
It is recommended that the auxiliary drain be connected to a drain line for all units. Ifauxiliary drain is not connected, it must be plugged with provided cap. For down-flow units,
the auxiliary drain shall be connected and routed to a drain. See figure 10 for auxiliary and main drain locations,
The following practices are recommended to ensure condensate removal as illustrated in figures 9 and 10:
Drain piping should not be smaller than the drain connections at drain pan.
A trap must be installed in the main drain line,
The trap must be deep enough to offset the difference in static pressure between drain pan and atmosphere. Generally, two inches is satisfactory for medium static
applications.
Horizontal runs must be sloped 1 inch per 10 feet of drain line to offset friction,
An open vent indrain line will sometimes be required due to line length, friction and static pressure,
Drain construction and routing should facilitate future cleaning and must not interfere with filter access,
Auxiliary drain should run to an area where homeowner will notice any drainage. The auxiliary drain line does not required venting or a trap. Refer to
local codes.
Step 9_ Install access panel,
Table 2. Refrigerant Line Sets
CBX32M Liquid Vapor/ L10 L15
Units Line No. Suction Line Line Sets Line Sets
-018/024 3/8 in 5/8 in L10-26 L15-26 (Smm) (16 mm) 20 ft. - 50 ft. 20 ft. - 50 fb
(6 m- 15 m) (6 m- 15 m)
-030,-036 3/8 in 3/4 in. L10-41 L15-41 (10 mm) (19mm 20 ft. - 50 ft. 20 ft. -50 ft.
(6m-15m) (6m-15m)
-042, -048 3/8 in 7/8 in. L10-65 L15-65 (10 mm) (22 mm) 30 ft. - 50 ft. 30 ft. -50 ft.
(9 m- 15 m) (9 m- 15 m)
-060 3/8 in 1-1/8 in. Field Field (10 ram) (29 ram) Fabricated Fabricated
Before connecting drain line(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen
into the drain pan during installation that may plug up the drain opening,
VENT MUST EXTEND ABOVE THE HEIGHT OF THE COIL" DRAIN PAN BY 2 INCHES (51 MM). VENT
TRAP MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCE (GENERAL
2 INCHES [51MM]).
DRAIN LINE SHOULD SLOPE A MINIMUM 1 INCH PER
10 FEET (25 MM PER 3 M) TO APPROVED DRAIN
DRAIN PAN
TRAP (49P66)
Figure 9. Typical Condensate Drain Connection
LEF%HAND UP-FLOW OR RIGHT-HAND
DISCHARGE DOWN-FLOW DISCHARGE
w
AUXILIARY DRAIN ON LEFT
oo ]
MAIN DRAIN ON RIGHT
Figure 10. Drain Locations
505342M 05/08
Page 8
Page 9
A IMPORTANT
Each unit includes a factory-installed filter. Note that filter access door fits over access panel. Air leakage will occur if
access panel is placed over filter door. Filters should be inspected monthly and must be cleaned
or replaced when dirty to assure proper furnace operation. Reusable filters supplied with some units can be washed
with water and mild detergent. Some units are equipped with standard throw-away type filters which should be
replaced when dirty. To replace filter:
Step 1.. Loosen the thumbscrews holding the filter panel
in place.
Step 2.. Slide the filter out of the guides on either side of
Step 3.. Insert new filter. Step 4.. Replace panel.
See table 3 for replacement filter sizes.
UnitModel No. Filter Size Inches (mm)
CBX32M018/024 15 x20 (381 x 508)
CBX32M-030 20 x 20 (508 x 508) CBX32M-036,042 20 x 22 (508 x 559)
CBX32M-048,060 20 x 24 (508 x 610)
L2 LI
cabinet.
Table 3. Filter Dimension
K3 INDOOR BLOWER RELAY
HEAT ELEMENT _I
1L
CIRCUIT 1
CIRCUIT BREAK-
ERS OR TERMI-
NAL BLOCK
GROUND FUSE
,ll
,/_ THERMOSTAT TB, L._ (D_ __
K32 CB1
HEAT_RELAY ,I CIRCUIT _}
TERMINALI0
. I j I I
rj I L_ I " I
L-- __1
I r -J
/kvv
TRANSFORMER
BREAKER
OR
WARNING
Wiring must conform to the current National Electric Code
ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA
Standard C22.1, and local building codes. Refer to
following wiring diagrams. See unit nameplate for
minimum circuit ampacity and maximum overcurrent protection size.
Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the
National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part l, CSA
Standard C22.1.
This unit is provided with knockouts for conduit. Refer to
figure 15 for unit schematic wiring diagram. Refer to figures 14 through 13 for typical field wiring.
Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension illustration
for specific location.
NOTE - USE COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM
CIRCUIT AMPAClTY AND MAXIMUM OVERCUR- RENT PROTECTION SIZE
LINE VOLTAGE FIELD INSTALLED CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC
NOTE - ALL REMAINING WIRES ARE FACTORY
INSTALLED
z_TO EXTERNAL LOAD 24VAC AT .50 AMP MAXI-
MUM.
Z_ THERMOSTAT HEAT ANTICIPATION SETTING 0.4
AMP ELECTRIC HEAT
Z_ WHEN TWO-STAGE THERMOSTAT IS USED,
CONNECT SECOND STAGE HEAT BULB TO TER- MINAL "W2" AND REMOVE JUMPER BETWEEN
±
TERMINALS "R" AND 'W2."
/2X FACTORY INSTALLED JUMPERS
Z_ L3 CONNECTION USED ON (Y-VOLTAGE)
3-PHASE ELECTRIC HEATERS ONLY,
Figure 11. Typical Field Wiring - Cooling Application with Electric Heat
Page 9
CBX32M SERIES
Page 10
LI L2
CIRCUIT 1
K5 INDOOR BLOWER RELAY
% %
@A
CIRCUIT BREAK-
ERS OR TERMI-
NAL BLOCK
CIRCUIT
BREAKER
GROUND ORFUSE
CB1 O
TERMINAL
BLOCK _
!
TRANSFORMER
HEAT PUMP CLASS 2
VOLTAGE TERMINALS
LINE VOLTAGE FIELD INSTALLED
NOTE -ALL REMAINING WIRES ARE FACTORY INSTALLED
L_ TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM /_ FACTORY INSTALLED JUMPERS
/_ Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED (HP21).
L_ USING SERVICE LIGHT OPTION (S54)WITH SOME ELECTRONIC
THERMOSTATS MAY REQUIRE MOVING $54 COMMON WIRE TO Y1 IN HEAT PUMP UNIT.
/_ COMMON USED ONLY ON SOME THERMOSTATS.
L_ AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY
ON SOME THERMOSTATS. S I
CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC
THERMOSTAT ,/_
99J
_1 I I I
I I I II I
I
II ,
[
I
I-4=-IS I
DFaDD []
LI L2,_I I
CIR- CUIT 1
CIRCUIT
HEAT ELEMENT _I
BREAKERS
OR TERMI- AT K52
BLOC -IIEK RELAY '_I CB1
NAL
GROUND ORFUSE
v TERM INAL Z_
I LINE VOLTAGE FIELD
-- -- -- CLASS 2 VOLTAGE FIELD
L_ SETTING 0.4 AMP ELECTRIC HEAT
_ FACTORY INSTALLED JUMPERS
A
/_ EMERGENCY HEAT RELAY (USED
INSTALLED
INSTALLED NEC/CEC
NOTE -ALL REMAINING WIRES
ARE FACTORY INSTALLED
THERMOSTAT HEAT ANTICIPATION
WHEN OUTDOOR THERMOSTAT IS
USED, CONNECT LEADS TO TERMINALS "R" AND "W2" AND
REMOVE JUMPER BETWEEN TERMINALS "R' AND "W2."
ONLY IF OUTDOOR T'STAT IS USED) FIELD PROVIDED AND
INSTALLED NEW INDOOR UNIT. 24VAC 5VA MAX NEC/CEC CLASS 2
Figure 12. Typical Field Wiring - Heat Pump Only Application
K3 INDOOR BLOWER RELAY
EM
TRANSFORMER
TEl
BREAKER
CIRCUIT
OUTDOOR THERMOSTAT
I(IF USED)
I I
I
BLOCK
,r",hI ,rlL L:
,
I[ I
/_ USING SERVICE LIGHT OPTION ($54) WITH SOME ELECTRONIC
THERMOSTATS MAY REQUIRE MOVING $54 COMMON WIRE TO Y1 IN
HEAT PUMP UNIT.
/_ COMMON USED ONLY ON SOME THERMOSTATS. L_Y2 USED ONLY WHEN TWO-SPEED COMPRESSOR IS USED (HP21)
/_ AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON
SOME THERMOSTATS.
I f___l
r
4 4 q +
I __1
J
S% D
8 _
HEAT PUMP CLASS 2
VOLTAGE TERMINALS
L
I I I
o 8
@
G
0d w
O
m
,&
Figure 13. Typical Field Wiring - Heat Pump Application with Electric Heat
505342M 05/08
Page 10
Page 11
L2 LI
CIRCUIT 1
,ll
K3 INDOOR BLOWER RELAY
_LI (Black)
L2 (Orange)
FIELD-SUP-
PLIED
WIRE NUTS
GROUND
THERMOSTAT
CIRCUIT
BREAKER
CB1 0
OR
FUSE
TRANSFORMER
NOTE - USE COPPER CONDUCTORS ONLY. REFER TO UNIT RATING PLATE FOR MINIMUM
CIRCUIT AMPAClTY AND MAXIMUM OVERCUR- RENT PROTECTION SIZE
LINE VOLTAGE FIELD INSTALLED
CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC
NOTE - ALL REMAINING WIRES ARE FACTORY
INSTALLED
A'X TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM. Z_ FACTORY INSTALLED JUMPERS
j I L
r- L
Ir
wax
[ _I TERMINAL
I BLOCK I
TBI I
J
J
Figure 14. Typical Field Wiring - Cooling Only Application
2€v POWER R
T
F _ EC0N
BLL
__ j BLUER 6
CBSERIgS
I DESCRIPTION
JKEY 1 COMPONEN_
18_ IMOTOR -I_10_R
_ _IHIJIJII I_N_A_,H-INANb H
F FUSff2TIRANSFORMER
J2 ACK=ELECTRIC HEAT
_0_R
- RELAY-ECONOM I ZER HEAT
ITBI ITERI_, STRIP-CLAD5 II
EC8 S[RIEg
KEY 1 _OMP_)NgNT
I D_?qR{PTIQN
CBE IClRCOlr BREAkER-ELECT, HT _CB2 IClRCUIT BREAKER-ELECT. HT _Cg5 leIRCUIT BREA_(ER-£LEeT. HT
IT_ ITERM[NAL STRIP-UNIT
MOTOR SPEED TAP CHART
2¢V COMMON C
FIELD WIRING FOR ECB
SERIES UNITS WITHOUT CIRCUIT BREAKERS
CIRCUIT i Z_
/3
CBB USED ON 0¢8 AN_ O6,0 UNIT5 ONLY
--LINE VOLTAGE FIELD WIRING
-- --CLASS IT VOLTAGE FIELD WIRING
ZZ_ REFER TO FACTORY BLOV#ER SPEED TAP SELECTION
CHART ON UNIT FOR BLOVAER SPEED INFORMATION,
L_NEC/OEC CLASS 2 3VA
/_ USE COPPER CONDUCTORS ONLY.
REFER TO UNIT RATING PLATE FORMINIMt_ CIRCUIT AMPACITY AND _AXIMUM OVERCURRENT
PROTECTION SIZE
z_ L3 CONNECT{ON USED ON (Y) ELECTRIC R[ATER_ ONLy
A
EQUIPMENT OROUND LOCATED IN INDOOR UNIT
Z_ CONNECT PO_VER WIRES FROM HEATER LABELED LI,L2,0N
"p* VOLTAGE UNITS AND LI,LZ,L3 ON "y" VOLTAGE
UNITS TO TO2 TERMINAL STRIP IN INDOOR UNIT.
z_ L_ IS NOT PRESENT ON (P) ELECTRIC HEATERS
Z_ THE NU_RO_CIRCUITS VARY ACCORDING
TO HEATER WOOEL REFER TO FAN COIL
NAMEPLATE FOR ACTUAL NU_ER EMPLOYED
FIELD WIRING FOR ECB SERIES UNITS WITH CIRCUIT BREAKERS
CIRCUIT 3 CIRCUIT 2 CIRCUIT
A
Figure 15. Typical Wiring Diagram - Single Phase
Z_ _EOUIPMEN_
GROUND
Page 11
.....t EoU'P"E°T oo,P E.,
EOU]PMENT T GROUND
GROUND
CBX32M SERIES
Page 12
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in
water blow-off problems. This is especially important when
the unit is installed in an unconditioned area,
AIR VOLUME ADJUSTMENT
Blower speed selection is accomplished by changing the
taps at the harness connector at the Blower motor as illustrated in figure 16. Refer to unit wiring diagram in figure
15 on page 11. Refer to tables 4 through 9 for air handler
)erformance data,
Make sure the liquid line and suction line entry points are sealed with either the provided flexible elastomeric thermal
HARNESS
CONNECTOR
insulation, or field provided material (e.g. Armaflex, Permagum or equivalent). Any of the previously mention
F
materials may be used to seal around the main and auxiliary drains, and around open areas of electrical inlets.
MINIMUM BLOWER SPEEDS (WITH ELECTRIC HEATERS)
For the minimum allowable speed for the CBX32M series units with electric heat, refer to the ECB29 installation instructions.
Table 4.
External Static
Pressure High
in. w.g. Pa cfm L/s Wat_
.00 0 700 485 365 .05 10 695 480 360
.10 25 690 470 355 .15 35 680 465 345 .20 50 665 455 340 .25 60 650 440 335 .30 75 635 430 325 .40 100 590 400 310 .50 125 535 370 295 .60 150 470 330 280 .70 175 395 290 265 .75 185 350 265 255
NOTE - All air dab is measu_d external _sis_nce.
External Static
Pressure High
in. w.g. Pa cfm L/s Wat_
.00 0 1045 610 385 .05 10 1075 610 380
.10 25 1085 610 375 .15 35 1085 600 370 .20 50 1065 580 360 .25 60 1030 555 350
.30 75 980 525 335 .40 100 830 445 305 .50 125 615 340 275
.60 150 335 205 240
NOTE- Allairda_ is measu_d external _sis_nce.
CBX32M-018/024 Air Handler Pe_ormance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low Medium
L/s Wat_ cfm L/s Wat_ cfm
330 245 895 425 300 1030 330 245 890 420 295 1015
325 240 875 415 290 1000 320 235 860 405 285 980 315 230 845 400 280 960 310 220 825 390 275 935 300 215 800 380 265 910 280 205 745 355 250 850 255 190 685 320 235 780 220 175 605 285 220 705
185 165 520 245 200 615 165 155 475 225 195 565
unit with air fil_r in place. Ele_ric hea_ have no app_ciable air
Table 5. CBX32M-030 Air Handler Performance (208/230V)
Air Volume and Motor Wat_ at Specific Blower Taps
Low Medium
L/s Wat_ cfm L/s Wat_ cfm
490 315 1175 555 335 1290 505 310 1190 560 330 1295
515 300 1190 560 325 1290 510 295 1175 555 320 1265 505 285 1145 540 310 1230 485 270 1105 520 295 1180
460 255 1045 495 280 1115 390 220 890 420 250 945 290 190 675 320 215 720
155 160 405 190 185 440
unit with airfil_rin place. Electric hea_ have no app_ciable air
PRESS THE TAB TO RELEASE WIRE CONNECTOR.
SELECT CONNECTOR LOCATION FOR NEW SPEED.
INSERT WIRE UNTIL IT CLICKS.
Figure 16. Blower Speed Tap Selection
505342M 05/08
Page 12
Page 13
Table 6. CBX32M-036 Air Handler Performance (208/230V)
External Static
Pressure
in. w.g. Pa
.00 0 .05 10
.10 25 .15 35 .20 50 .25 60
.30 75 .40 100 .50 125 .60 150
.70 175 .75 185
cfm 915
965 1005 1035 1055 1060
1050 1005
915
775
59O
485
NOTE - All air data is measured
Low
L/s
430 455
475 490 495 5OO
495 475 430 365
280 230
extemal to unit with air filter in place. Electric heaters have no appreciable air resistance.
Air Volume and Motor Watts at Specific Blower
Medium
Watts cfm L/s Watts
335 1120 530 390 330 1150 540 385
315 1170 550 380 235 1180 560 285 230 1190 560 280 220 1185 560 275
215 1175 555 375 290 1135 535 325 255 1060 500 300 230 960 455 280
205 830 390 255
195 750 355 245
Table 7. CBX32M-042 Air Handler Performance (208/230V)
External Static
Pressure
in.w.g. Pa
100 0
105 10 .10 25 .15 35
.20 50 .25 60 .30 75 .40 100
.50 125 .60 150 .70 175 .75 185
NOTE
- All air data is measu_d ex_mal _ unit with air filer in place. Ele_dc he_e_ have no app_ciable air _sistance.
cfm L/s Watts cfm L/s Watts cfm L/s Watts
1325 625 370 1600 755 455 1825 860 565 1335 630 370 1585 750 455 1790 845 555
1335 630 370 1565 740 450 1750 825 540 1330 630 365 1540 725 440 1710 805 530
1320 620 360 1505 710 435 1660 785 520 1300 615 355 1470 695 425 1610 760 505 1270 600 350 1425 675 415 1555 735 495
1195 565 330 1320 625 390 1430 675 465
1090 515 310 1195 565 365 1290 610 440
955 450 285 1050 495 335 1135 535 415
795 375 260 875 415 310 965 455 385
700 330 250 780 370 295 875 415 370
Low Medium High
Air Volume and Motor Watts at Specific Blower Taps
Table 8. CBX32M-048 Air Handler Performance (208/230V)
External Static Air Volume and Motor Watts at Specific Blower Taps
Pressure Low Medium High
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts
.00 0 1475 695 430 1785 845 520 1910 900 590 .05 10 1480 700 430 1770 835 515 1895 895 585
.10 25 1475 695 425 1750 825 510 1870 880 580 .15 35 1465 690 420 1720 810 500 1840 865 570 .20 50 1445 680 410 1685 795 490 1800 850 565 .25 60 1415 670 405 1645 775 480 1755 830 550 .30 75 1380 650 395 1600 755 465 1700 805 540 .40 100 1290 610 370 1485 700 440 1580 745 515 .50 125 1170 550 345 1350 635 410 1425 675 485 .60 150 1020 480 320 1190 560 380 1250 590 450 .70 175 840 395 295 1000 470 350 1045 495 415 .75 185 740 350 280 900 425 335 930 440 400
NOTE- Allairdata is measu_d ex_mal _ unit with airfil_rin place. Electnc heate_ have no app_ciable air _sistance.
Taps
cfm
1525 1520
1510 1495 1475 1450
1415 1335 1230
1100
95O 870
High
L/s
72O 72O
715
7O5 895 685
67O 83O
58O
52O 450
410
Watts
5O5
495 480 470 455 440
430 400
375 345
320 305
Page 13
CBX32M SERIES
Page 14
Table 9 CBX32M-060 Air Handler Performance (208/230V)
External Static Air Volume and Motor Wat_ at Specific Blower Taps
Pressure Low Medium High
in w g Pa cfm L/s Wat_ cfm L/s Wat_ cfm L/s Wat_
.00 0 1775 835 585 2025 955 670 2115 995 780 .05 10 1775 835 590 2010 950 665 2100 990 770
.10 25 1770 835 580 1995 940 655 2085 985 765 .15 35 1760 830 570 1975 930 645 2060 970 750 .20 50 1745 825 560 1950 920 635 2030 960 740
.25 60 1725 815 550 1915 905 625 2000 945 730 .30 75 1695 800 535 1880 885 610 1960 925 715 .40 100 1630 770 505 1795 845 580 1870 880 685 .50 125 1540 725 475 1690 795 545 1755 830 655
.60 150 1425 675 440 1560 735 515 1620 765 625 .70 175 1295 610 410 1415 670 480 1465 690 590 .80 200 1140 535 375 1250 590 445 1290 610 560
.85 210 1050 495 360 1160 550 425 1195 565 545
NOTE- Allairda_ is measu_d external _ unit with airfil_rin place. EleGric hea_ have no app_ciable air _sis_nce.
_IMPORTANT
Matt- or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air
conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the
insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding
ambient airwill affect the inside surface temperature of the cabinet. The temperature/humidity difference between the
inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet
metal corrosion and subsequently, component failure. REPAIRING DAMAGED INSULATION
Areas of condensation on the cabinet surface are an
indication that the insulation is in need of repair. If the insulation in need of repair is otherwise in good
condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue
and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can
retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any
cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape.
Figure 17 Repairing Insulation
ILWARNING
505342M 05/08
Page 14
Loading...