INSTALLATION
INSTRUCTIONS
X_ WARNING
_, CAUTION
IMPORTANT
_, IMPORTANT
Elite ® Series CB30U Units
AIR HANDLER F[_ Technical
505,340M J_LL Publications
07/07 Litho U.S.A.
Supersedes 504,720M
CB30U Up-flow Unit Dimensions ................ 2
CB30U Up-flow Side Return Air Filter Adapter ..... 2
General Information ............................ 3
Shipping and Packing List ...................... 3
Requirements ................................. 3
Installing the Unit .............................. 3
Brazing Connections ........................... 4
Installing the Condensate Drain .................. 5
Inspecting and Replacing Filters ................. 5
Sealing the Unit ............................... 6
Adjusting the Blower Speed .................... 6
Making Electrical Connections ................... 8
Repairing or Replacing Cabinet Insulation ......... 12
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
BLOWER MOTOR
SHIPPING BOLT
TOP CAP SHIPPING BRACKET (REPLACE
SCREWS IN TOP CAP AFTER REMOVAL)
C
CHECK FOR AND REMOVE THE FOLLOWING ITEMS BEFORE OPERATING UNIT.
BLOWER HOUSING SUPPORT PAD
B
BLOWER MOTOR SHIPPING
BRACKET
D
REFRIGERANT LINE CAPS [SEE BRAZING
CONNECTION ON PAGE 4]
E
@..
07/07
I IIHIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Page1
505,340M
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
3/4
t(19)
3/4 3/4
(19)_ _1_)
DETAIL OF PIPING PLATE
t 5/8
OPTIONAL
ELECTRIC
HEAT
(Field
InstaBed)
FILTER
ACCESS
A
LIQUID
LINE
SUCTION
LINE
K
SIDE VIEW
LINE VOLTAGE LOW VOLTAGE
INLETS INLETS
(Top and Left Side) (Top and
TOP VIEW
Right Side)
I
I
JL_ _J JL_
5/8 F (215) BottEom
Bottom 5/8
Return Air (16)
(16) Return Air
FRONT VIEW
Model CB30U-21/26 CB30U-31 CB30U-51 / CB30U-65
No. inch mm inch mm mm inch mm
A 45-1/4 1149 49-1/4 1251 1334 58-1/2 1486
B 16-1/4 413 21-1/4 540 540 21-1/4 540
C 20-5/8 524 20-5/8 524 575 24-5/8 625
D 14-3/4 375 19-3/4 502 502 19-3/4 502
E 19 483 19 483 533 23 584
F 15 351 20 508 508 20 508
CB30U-41/46
inch
52-1/2
21-1/4
22-5/8
19-3/4
21
2O
G ............... 27-7/8 708
H ............... 30-5/8 778
J 14-1/4 362 18-1/4 464 464 18-1/4 464
K 1-1/8 29 1-1/8 29 54 3-1/8 79
L 7-1/8 181 9-5/8 244 244 9-5/8 244
M 6-1/4 159 6-1/2 165 165 6-1/2 165
N 6-5/8 168 9-1/8 232 232 9-1/8 323
P 4-1/8 105 4-9/16 116 116 4-9/16 116
18-1/4
2-1/8
9-5/8
6-1/2
9-1/8
4-9/16
(19)
3/4
1-3/16
(30)
ii _:_NiN;i!N_;i!iiiili;iiii!ilililililill |!:!:!:;!i!i!_!:!i!ili!iiii_i!!
i
i _iiiiiiiiiiiii'i;!ii_!;i; i
20
(508)
3,, i ii ii ii ii ii ii ii ii iiiiii!;!ii!;'ii]i
(,9, iiiiiiiiiiii i ;! :!: i i i;!i !: ! i i ii i : i ii iiiii i i i iiii iiii iiiiiiiiiiiiiiiiiiiiii!!!!!! iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ii!ii!iiiiiii i"':ii!i!i!!i!iiiiiiiiiiiiiiiii!i!iiiiiiiiiiii!!ii!i!ii'iiil
(25) '_
1 ii_I:I:I:I:_!_!_!_!_!_!_!:_i_!i_i_i_i!i_i_:iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii:!_:_iii:iI_;!!_!I;_i_ i ii_iiiii!iiiiiiiiiii!!i_ii
AIR FILTERS
(FURNISHED)
505340M 07/07
*NOTE - Air flow may be either direction.
FRONT VIEW SIDE VIEW
I_ (25)
Page 2
Model CB30U-51 and CB30U-65
CB30U-21/26 CB3OU-31 , CB30U-41/46
Number
Inch mm Inch mm
A 16 406 20 508
B 14 356 18 457
WARNING
The CB30U series air handler units are designed for
installation with optional field-installed electric heat and a
matched remote outdoor unit. These units are for indoor
installation only. The CB30U units are designed for up-flow
operations with either bottom or side return air
applications.
These instructions are intended as a general guide and do
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation. Check
equipment for shipping damage; if found, immediately
report damage to the last carrier.
Package 1 of 1 contains the following:
1--Assembled air handler unit
In addition to conforming to manufacturer's installation
instructions and local municipal building codes, installation
of Lennox air handler units (with or without optional electric
heat), MUST conform with the following National Fire
Protection Association (NFPA) standards:
• NFPA No. 90A - Standard for Installation of Air
Conditioning and Ventilation Systems
• NFPA No. 90B - Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning Systems
This unit is approved for installation clearances to
combustible materials as listed on the unit rating plate which
is located on the unit. Accessibility and service clearances
must take precedence over combustible material
clearances.
I
CB30U units come from the factory ready for up-flow,
bottom return installation. This unit is not designed for
down-flow or horizontal discharge. Return air for the
CB30U may be either from the bottom or sides of the unit.
Side return air applications require some field
modifications.
WARNING
IMPORTANT
DISASSEMBLE/REASSEMBLE AIR HANDLER UNITS
The air handler units consists of two factory-assembled
sections. It may be necessary to disassemble the sections
when positioning the unit for installation,
To disassemble:
Step 1. Remove access panels,
Step 2, Remove both blower and coil assemblies, This
will lighten the cabinet for lifting,
Step 3, Remove one screw from the left and right posts
To reassemble:
Step 1. Align cabinet sections together.
Step 2, Reinstall screws,
Step 3, Replace blower and coil assemblies,
Step 4, Replace access panel,
UP-FLOW APPLICATION
Use the following procedures to configure the unit for
up-flow operations:
Step 1, Remove access panels and corrugated padding
Step 2. Place unit in desired location. Set unit so that it
Step 3, Mount units that have no return air plenum on a
Table 1. Optional Unit Side Stand (Up-Flow Only)
Model Kit Number
-21, -26, and -31 45K31
41 through-65 45K32
inside the unit, Remove one screw from each
side on the back of the unit, Unit sections will now
separate,
between the blower and coil assembly before
operation,
is level. Connect return and supply air plenums
as required using sheet metal screws.
stand at least 14" from the floor for proper air
return, Lennox offers an optional up-flow unit
stand as listed in table 1.
Page 3
CB30U/CBX27UH SERIES
SIDE RETURN AIR APPLICATIONS
The CB30U unit is shipped from the factory ready for
bottom return air application. You can order an optional
side return air filter kit as listed in table 2.
Table 2. Optional Side Return Air Filter Kit
Model Kit Number
-21 and-26 65K23
All other models 65K24
Use the following procedures to configure the unit for side
return air operations:
All CB30U coils are equipped with a factory-installed,
internally mounted expansion valve. Use Lennox L15
(sweat) series line sets as shown in table 2 or use
field-fabricated refrigerant lines, L10 (flare) line sets may
be used by cutting off flare nut. Refer to the piping section
of the Lennox Unit Information Service Manual for proper
size, type, and application of field-fabricated lines.
_WARNING
Step 1,
Step 2,
Step 3.
Step 4.
Step 5.
Remove the coil access panel,
Remove the coil assembly from the cabinet,
Cut the side or sides of the cabinet used for
return air according to the dimensions given in
figure 1 and table 1. For -41, 46, -51 and -65
units, it is recommended that return air come into
the unit from both sides. Therefore, both sides of
the cabinet should be cut for these units,
Set the unit so that it is level. Seal the bottom
opening of the cabinet,
Connect the return and supply air plenums as
required.
B
I AIR HANDLER UNIT
SUCTION LINE
LIQUID LINE
Figure 2. Brazing Connections
Ak IMPORTANT
CUT BOTH SIDES OF CABINET FOR -41/46, -51 AND -65 UNITS.
Figure 1. CB3OU Side Return Air Dimensions
Table 3. Side Return Air Dimensions
CB3OU CB30U CB30U CB30U-51
Model # -21/26 -31 -41/46 CB30U-65
inch (mm) inch (mm) inch (mm) inch (mm)
18-1/4
A 14-1/4 (362) 18-1/4 (464) (464) 18-1/4 (464)
B 1-1/8 (29) 1-1/8 (29) 2-1/8 (54) 3-1/8 (79)
505340M 07/07
Page 4
Table 4. Refrigerant Line Sets
CB30MV LIQUID SUCTION L10 L15
UNIT LINE LINE SETS LINE SETS
-21/26 (10 mm) (16 mm) 20 ft, - 50 ft, 20 ft. - 50 ft.
-31 -41/16 (10 mm) (19 mm) 20 ft, - 50 ft. 20 ft. - 50 ft.
-51 30 if, - 50 ft, 30 ft. - 50 ft.
-65 (10 ram) (29 ram) FABRICATED FABRICATED
3/8 in 5/8 in.
3/8 in 3/4 in,
3/8 in 7/8 in.
(10 mm) (22 mm) (9 m - 15 m) (9 m- 15 m)
3/8 in 1-1/8 in, FIELD FIELD
VAPOR/
LINE
L10-26 L15-26
(6m- 15m) (6m-15m)
L10-41 L15-41
(6 m - 15 m) (6 m- 15 m)
L10-65 L15-65