ELITE® SERIIES GAS FURNACE
UP/FLOW HORIZONTAL AIR DISCHARGE
507264-03
06/2017
Superseds 03/2017
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be
ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
AIR FLOW
AIR FLOW
HORIZONTAL LEFT
UPFLOW
AIR FLOW
HORIZONTAL RIGHT
CAUTION
As with any mechanical equipment, personal injury can
result from contact with sharp sheet metal edges. Be
careful when you handle this equipment.
Table of Contents
Unit Dimensions - inches (mm) .....................................2
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 5
EL296UH135XV60D24−1/2 in 622 mm23−3/8 in 594 mm23 in 584 mm11−1/8 in 283 mm
17−1/2 in 446 mm16−3/8 in 416 mm16 in 406 mm7−5/8 in 194 mm
21 in 533 mm19−7/8 in 505 mm19−1/2 in 495 mm9−3/8 in 238 mm
3/4
(19)
5/8
(16)
Page 2
3-1/4
(83)
23-1/2
(597)
1
Bottom Return
Air Opening
1-15/16 (49)
EL296UHV Gas Furnace
NON-DIRECT VENT
INSTALLATION
NON-DIRECT VENT
INSTALLATION
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
EXHAUST
OUTLET
EXHAUST
OUTLET
The EL296UHV Category IV gas furnace is shipped ready
for installation in the upow or horizontal position. The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed
in horizontal or upow applications with bottom return air.
The EL296UHV can be installed as either a Direct Vent
or a Non-Direct Vent gas central furnace.
The furnace is equipped for installation in natural gas
applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.
NOTE - In Direct Vent installations, combustion air is tak-
en from outdoors and ue gases are discharged outdoors.
In Non-Direct Vent installations, combustion air is taken
from indoors or ventilated attic or crawlspace and ue
gases are discharged outdoors. See for applications involving roof termination.
DIRECT VENT INSTALLATIONNON-DIRECT VENT
EXHAUST OUTLET
COMBUSTION
AIR INTAKE OUTSIDE
OF HOUSE
INSTALLATION
EXHAUST
OUTLET
Shipping and Packing List
Package 1 of 1 contains
1 - Assembled EL296UHV unit
1 - Bag assembly containing the following:
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
The following items may also be ordered separately:
1 - Thermostat
1 - LP/Propane changeover kit
1 - Return air base kit
1 - Horizontal suspension kit
1 - High altitude pressure switch
Safety Information
Figure 1
Figure 2
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/
propane gas can lose its scent. In case of a leak, LP/
propane gas will settle close to the oor and may be
difcult to smell. An LP/propane leak detector should be
installed in all LP applications.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
EL296UHV units are CSA International certied to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel
Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel
Gas Code is available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA-B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
Page 3
In order to ensure proper unit operation in non-direct vent
Gas Unit
Heating Unit Installed Upstream of Cooling Unit
Gas Unit
Dampers
(open during heating operation only)
Dampers
(open during cooling operation only)
Heating Unit Installed Parallell to Air Handler Unit
Air Handler Unit
Evaporator
applications, combustion and ventilation air supply must
be provided according to the current National Fuel Gas
Code or CSA-B149 standard.
Installation Locations
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the table in Figure 12. Accessibility and
service clearances must take precedence over re protection clearances.
NOTE - For installation on combustible oors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood ooring.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a
hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and
current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specied on the unit nameplate. Failure to do so may cause erratic limit operation and premature heat exchanger failure.
This EL296UHV furnace must be installed so that its electrical components are protected from water. Installed in
Combination with a Cooling Coil When this furnace is
used with cooling coils (Figure 3), it shall be installed in
parallel with, or on the upstream side of, cooling coils to
avoid condensation in the heating compartment. With a
parallel ow arrangement, a damper (or other means to
control the ow of air) must adequately prevent chilled ai
from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either
the heating or the cooling unit, unless it is in the full HEAT
or COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of
the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Figure 3
NOTE - This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The EL296UHV furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and utility
rooms in the upow or horizontal position. This furnace
design has not been CSA certied for installation in mobile
homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
NOTE - Gas furnaces manufactured on or after May 1st
2017 are not permitted to be used in Canada for heating
of buildings or structures under construction.
The following statement only applies to the US. Lennox
does not recommend the use of EL296UHV units as a
construction heater during any phase of construction. Very
low return air temperatures, harmful vapors, construction
dust and operation of the unit with clogged or misplaced
lters may damage the unit.
However, EL296UHV units may be used for heating of
buildings or structures under construction in the US, if the
following conditions are met to ensure proper operation:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous
heating is not allowed.
• The return air duct must be provided and sealed to
the furnace.
• Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
• Air lters must be installed in the system and must
be maintained during construction.
Page 4
• Air lters must be replaced upon construction com-
pletion.
• The input rate and temperature rise must be set per
the furnace rating plate.
• One hundred percent (100%) outdoor air must be
provided for combustion air requirements during
construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly
to the furnace. Size the temporary duct following
these instructions in section for Combustion, Dilution and Ventilation Air in a conned space with air
from outside.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be
thoroughly cleaned following nal construction
clean-up.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the fol-
lowing general recommendations must be considered
when installing a EL296UHV furnace:
• Place the furnace as close to the center of the air
distribution system as possible. The furnace should
also be located close to the vent termination point.
• When the furnace is installed in non-direct vent applications, do not install the furnace where drafts
might blow directly into it. This could cause improper combustion and unsafe operation.
• When the furnace is installed in non-direct vent applications, do not block the furnace combustion air
opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other
insulated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent
freezing of condensate drain system.
• Please consult the manufacturer of your evaporator
coil for their recommendations on distance required
between the heat exchanger and their drain pan.
Adequate space must be provided between the
drain pan and the furnace heat exchanger.
CAUTION
EL296UHV unit should not be installed in areas normally
subject to freezing temperatures.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
WARNING
Insufcient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Combustion, Dilution & Ventilation Air
If the EL296UHV is installed as a Non-Direct Vent Furnace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air is
taken from indoors or ventilated attic or crawlspace and
ue gases are discharged out-doors.
In the past, there was no problem in bringing in sufcient
outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house.
Unless outside air is brought into the house for combus-
tion, negative pressure (outside pressure is greater than
inside pressure) will build to the point that a downdraft
can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install EL296UHV furnaces to ensure ef-
Page 5
cient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
piping. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI.
Z223.1/NFPA 54). This reprinted material is not the com-
plete and ofcial position of the ANSI on the referenced
subject, which is represented only by the standard in its
entirety.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contaminated
atmosphere. Meet all combustion and ventilation air
requirements, as well as all local codes.
All gas-red appliances require air for the combustion
process. If sufcient combustion air is not available, the
furnace or other appliance will operate inefciently and
unsafely. Enough air must be provided to meet the needs
of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When replaces, exhaust fans, or clothes dryers are used at the same
time as the furnace, much more air is required to ensure
proper combustion and to prevent a downdraft. Insufcient air causes incomplete combustion which can result
in carbon monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be
unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the Air
from Outside section
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of
the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air must be handled by
ducts which are sealed to the furnace casing and which
terminate outside the space containing the furnace.This
is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room.
Even a small leak around the base of the unit at the plat-
form or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for
combustion and ventilation can be brought into the con-
ned space either from inside the building or from outside.
Air from Inside
If the conned space that houses the furnace adjoins a
space categorized as unconned, air can be brought in by
providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See Figure 4.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE - Each opening shall have a free area of at least one square inch
per 1,000 Btu (645mm
all equipment in the enclosure, but not less than 100 square inches
(64516mm.
2).
EL296UH
V
2
per .29kW) per hour of the total input rating of
(To Adjacent
Unconfined
Space)
Figure 4
Page 6
Air from Outside
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
If air from outside is brought in for combustion and ventilation, the conned space shall be provided with two permanent openings. One opening shall be within 12” (305mm)
of the top of the enclosure and one within 12” (305mm) of
the bottom. These openings must communicate directly or
by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free
area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW)
per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free
area of 1 square inch per 2,000 Btu (645mm2 per .59kW)
per total input rating of all equipment in the enclosure (See
Figure 5). It is also permissible to bring in air for combus-
tion from a ventilated attic (gure 6) or ventilated crawl
space (Figure 7).
(Inlet Air from Crawl Space and Outlet Air to Outside)
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Inlet Air
(Minimum
Ventilation
Louvers
(Crawl space)
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
Furnace
12 in.(305mm)
Above crawl
space floor)
*Intake Debris Screen Provided)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
2
per 1.17kW) per
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
FURNACE
INLET
AIR
Figure 5
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Roof Terminated
Exhaust Pipe
*Intake Debris
Screen
(Provided)
Furnace
(Minimum
12 in.(305mm) Above
attic floor)
VENTILATION
LOUVERS
(For unheated
crawl space)
Inlet Air
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
2
per 1.17kW) per
Figure 7
If air from outside is brought in for combustion and ventilation, the conned space must have two permanent openings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See Figure 5 and Figure 8. When communicating with the outdoors through horizontal ducts,
each opening shall have a minimum free area of 1 square
inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See Figure 9.
When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protective covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
Figure 6
2
per 1.17kW) per
Page 7
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
of the total input rating of all equipment in the enclosure.
ROOF TERMINATED
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
of the total input rating of all equipment in the enclosure.
r
EXHAUST PIPE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
The bolt and washer must be removed before the furnace
is placed into operation. After the bolt and washer have
been removed, the rigid leg will not touch the blower housing.
UNITS WITH 1/2 HP
BLOWER MOTOR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm
FURNACE
INLET AIR
(Ends 12” above
bottom)
2
per 1.17kW) per hour
Figure 8
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm
FURNACE
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12” above
bottom)
2
per 1.17kW) per hour
Figure 9
Shipping Bolt Removal
Units with 1/2 hp blower motor are equipped with three
exible legs and one rigid leg. The rigid leg is equipped
with a shipping bolt and a at white plastic washer (rather
than the rubber mounting grommet used with a exible
mounting leg). See Figure 10.
remove shipping bolt and washe
RIGID LEG
Figure 10
Installation - Setting Equipment
WARNING
Do not connect the return air duct to the back of the
furnace. Doing so will adversely affect the operation of
the safety control devices, which could result in personal
injury or death.
WARNING
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Upow Applications
The EL296UHV gas furnace can be installed as shipped
in the upow position. Refer to Figure 12 for clearances.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
condensate trap and drain connections, and installation
and service clearances [24 inches (610 mm) at unit front].
The unit must be level from side to side. The unit may be
positioned from level to ½” toward the front. See Figure
11.
Allow for clearances to combustible materials as indicated
on the unit nameplate.
Page 8
SETTING EQUIPMENT
END VIEW
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
UPFLOW APPLICATION
UNIT
FRONT
1/2” max.
SIDE VIEW
AIR FLOW
FRONT VIEW
UNIT
FRONT
SIDE VIEW
HORIZONTAL APPLICATION
AIR FLOW
FRONT VIEW
Figure 11
UNIT
FRONT
1/2”
max.
Page 9
WARNING
Installation Clearances
Side Return Air
Improper installation of the furnace can result in
personal injury or death. Combustion and ue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace. In platform
installations with furnace return, the furnace should be
sealed airtight to the return air plenum. A door must
never be used as a portion of the return air duct system.
The base must provide a stable support and an airtight
seal to the furnace. Allow absolutely no sagging, cracks,
gaps, etc.
For no reason should return and supply air duct systems
ever be connected to or from other heating devices
such as a replace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property
damage could result.
Return Air Guidelines
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the
furnace cabinet at the maximum dimensions shown on
page 2.
Refer to Engineering Handbook for additional information.
EL296UHV applications which include side return air
and a condensate trap installed on the same side of
the cabinet (trap can be installed remotely within 5
ft.) require either a return air base or eld-fabricated
transition to accommodate an optional IAQ accessory
taller than 14.5”. See Figure 13.
Top
Left SideRight Side
Bottom (Floor)
Top/Plenum1 in. (25 mm)
*Front0
Back0
Sides0†
Vent0
Floor0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
(with transition and filter)
20” X 25” X 1”
(508mmX635mmX 25mm)
Air Filter
Return
Air
Plenum
Transition
Figure 13
Figure 12
Page 10
CONDENSATE
Removing the Bottom Panel
Bottom Panel
See figure 4.
TRAP
AIR FLOW
17−1/2 (446) B Width (50W98)
21 (533) C Width (50W99)
24−1/2 (622) D Width (51W00)
FURNACE
INDOOR AIR
QUALITY
CABINET
(PCO, Filter
Cabinet, etc.)
FRONT VIEW
NOTE- Optional side return air filter kits are not for use with return air base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
Optional Return Air Base
(Upflow Applications Only)
FRONT
IF BASE
IS USED
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
OPTIONAL
RETURN
AIR BASE
3−1/4
(83)
7−1/4
(184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
SIDE RETURN
5−5/8
AIR OPENINGS
(143)
(Either Side)
26−7/8
(683)
SIDE VIEW
23
(584)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
3/4
(19)
Figure 14
Screw
Figure 15
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See Figure 15.
Horizontal Applications
WARNING
Do not install the furnace on its front or back.
See Figure 16.
Bottom Cap
FrontBack
Figure 16
Page 11
The EL296UHV furnace can be installed in horizontal ap-
Horizontal Application
HORIZONTAL SUSPENSION KIT
plications with either right- or left-hand air discharge. Refer to Figure 17 for clearances in horizontal applications.
Installation Clearances
Metal Strap
(typical)
Internal Brace
(provided with kit)
Right-Hand Discharge
Air
Flow
dnE thgiRdnE tfeL
dnE thgiRdnE tfeL
AIR FLOW
Air
Flow
Bottom (Floor)**
Left-Hand Discharge
Top
AIR FLOW
Bottom (Floor)**
Top0
Front*0
Back0
Ends0
Vent0
Floor0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
**An 8” service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Figure 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or
oor joists, as shown in Figure 18, or install the furnace
on a platform, as shown in Figure 19. A horizontal suspension kit (51W10) may be ordered from Lennox or use
equivalent.
NOTE - Heavy-gauge sheet metal straps may be used to
suspend the unit from roof rafters or ceiling joists. When
straps are used to suspend the unit in this way, support
must be provided for both the ends. The straps must not
interfere with the plenum or exhaust piping installation.
Cooling coils and supply and return air plenums must
be supported separately.
Bracket
(typical)
Air
Flow
Figure 18
NOTE - When the furnace is installed on a platform or with
the horizontal suspension kit in a crawlspace, it must be
elevated enough to avoid water damage, accommodate
drain trap and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1 - Select location for unit keeping in mind service and
other necessary clearances. See Figure 17.
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above
nished space, install an an auxiliary drain pan
under unit. Set unit in drain pan as shown in Figure
19. Leave 8 inches for service clearance below unit
for condensate trap.
3 - Provide a service platform in front of unit. When
installing the unit in a crawl space, a proper support
platform may be created using cement blocks.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5 - If necessary, run the condensate line into a
condensate pump to meet drain line slope
requirements. The pump must be rated for use
with condensing furnaces. Protect the condensate
discharge line from the pump to the outside to avoid
freezing.
6 - Continue with exhaust, condensate and intake
piping installation according to instructions.
Page 12
INTAKE PIPE
EXHAUST PIPE
*Gas connector may be
used for Canadian
able by local authority
having jurisdiction.
SERVICE PLATFORM
*GAS CONNECTION
RAISED
PLATFORM
Figure 19
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a
furnace installed in the horizontal position. The furnace is
equipped with a removable bottom panel to facilitate installation. See Figure 15.
Filters
This unit is not equipped with a lter or rack. A eld-provided high velocity rated lter is required for the unit to
operate properly. Table 1 lists recommended lter sizes. A
lter must be in place whenever the unit is operating.
IMPORTANT
If a highefciency lter is being installed as part of this
system to ensure better indoor air quality, the lter must
be properly sized. Highefciency lters have a higher
static pressure drop than standardefciency glass/foam
lters. If the pressure drop is too great, system capacity
and performance may be reduced.
The pressure drop may also cause the limit to trip more
frequently during the winter and the indoor coil to freeze
in the summer, resulting in an increase in the number of
service calls.
Before using any lter with this system, check the
specications provided by the lter manufacturer against
the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002
(August 2000).
TABLE 1
Furnace
Cabinet Width
Side ReturnBottom Return
17-1/2”16 X 25 X 1 (1)16 X 25 X 1 (1)
21”16 X 25 X 1 (1)20 X 25 X 1 (1)
24-1/2”16 X 25 X 1 (2)24 X 25 X 1 (1)
Filter Size
Duct System
Use industry-approved standards to size and install the
supply and return air duct system. Refer to ACCA Manual
D. This will result in a quiet and low-static system that has
uniform air distribution.
NOTE - This furnace is not certied for operation in heating mode (indoor blower operating at selected heating
speed) with an external static pressure which exceeds 0.8
inches w.c. Operation at these conditions may result in
improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air
duct. The access panel should be large enough to permit inspection of the heat exchanger. The furnace access
panel must always be in place when the furnace is operating and it must not allow leaks.
Return Air Plenum
NOTE - Return air must not be drawn from a room
where this furnace, or any other gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing de-
vice (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure
is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This
reverse ow of the ue gas may result in incomplete combustion and the formation of carbon monoxide gas. This
raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system.
Return air can be brought in through the bottom or either
side of the furnace (return air brought into either side of
furnace allowed only in upow applications). If a furnace
with bottom return air is installed on a platform, make an
airtight seal between the bottom of the furnace and the
platform to ensure that the unit operates properly and
safely. Use berglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the
return air duct to t the lter frame.
Pipe & Fittings Specications
All pipe, ttings, primer and solvent cement must conform
with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) stan-
dards. The solvent shall be free owing and contain no
lumps, undissolved particles or any foreign matter that
adversely affects the joint strength or chemical resistance
of the cement. The cement shall show no gelation, strati-
cation, or separation that cannot be removed by stirring.
Refer to the table 2 below for approved piping and tting
materials.
Page 13
CAUTION
Solvent cements for plastic pipe are ammable liquids
and should be kept away from all sources of ignition.
Do not use excessive amounts of solvent cement when
making joints. Good ventilation should be maintained to
reduce re hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)D1785
Schedule 40 PVC (Cellular Core Pipe)F891
Schedule 40 PVC (Fittings)D2466
Schedule 40 CPVC (Pipe)F441
Schedule 40 CPVC (Fittings)F438
SDR-21 PVC or SDR-26 PVC (Pipe)D2241
SDR-21 CPVC or SDR-26 CPVC (Pipe)F442
Schedule 40 ABS Cellular Core DWV
(Pipe)
Schedule 40 ABS (Pipe)D1527
Schedule 40 ABS (Fittings)D2468
ABS-DWV (Drain Waste & Vent) (Pipe &
Fittings)
PVC-DWV (Drain Waste & Vent) Pipe &
Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC PrimerF656
PVC Solvent CementD2564
CPVC Solvent CementF493
ABS Solvent CementD2235
PVC/CPVC/ABS All Purpose Cement
For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition
Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm
F628
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235,
F493
D3188
MARKING
ULCS636
IMPORTANT
EL296UHV exhaust and intake connections are made
of PVC. Use PVC primer and solvent cement when
using PVC vent pipe. When using ABS vent pipe, use
transitional solvent cement to make connections to the
PVC ttings in the unit.
Use PVC primer and solvent cement or ABS solvent ce-
ment meeting ASTM specications, refer to Table 2. As an
alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using ttings and pipe made of the same
materials. Use transition solvent cement when bonding
ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean
inside socket surface of tting and male end of pipe to
depth of tting socket.
Canadian Applications Only - Pipe, ttings, primer and
solvent cement used to vent (exhaust) this appliance must
be certied to ULC S636 and supplied by a single manufacturer as part of an approved vent (exhaust) system. In
addition, the rst three feet of vent pipe from the furnace
ue collar must be accessible for inspection.
Page 14
TABLE 3
OUTDOOR TERMINATION USAGE*
STANDARDCONCENTRIC
Wall Kit
2 inch3 inch2 inch
22G44
(US)
4
30G28
(CA)
44J40
(US)
4
81J20
(CA)
1
YES
1
YES
1
YES
1
YES
1
YES
1
YES
Input Size
045
070
090
Vent Pipe
Dia. in.
2
2-1/2
3
2
2-1/2
3
2
2-1/2
3
Flush
Mount Kit
51W11
(US)
51W12
(CA)
3
YESYES
3
YESYES
3
YESYES
3
YESYES
3
YESYES
3
YESYES
3
YESYESYES
3
YESYESYES
3
YESYESYES
2YESYESYES
110
2-1/2YESYES
3YESYES
1353YESYES
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total
vent length
calculations. See vent length tables.
* Kits must be properly installed according to kit instructions.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4 Termination kits 30G28, 44W92, 44W93 and 81J20 are certied to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
Wall Ring
Kit
15F74
1
YES
1
YES
1
YES
1
YES
1
YES
1
YES
1-1.2 inch2 inch3 inch
Field
Fabricated
5
YES
5
YES
5
YES
5
YES
5
YES
5
YES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYES
71M80
(US)
4
44W92
(CA)
2
YES
2
YES
2
YES
2
YES
2
YES
2
YES
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
Joint Cementing Procedure
All cementing of joints should be done according to the
specications outlined in ASTM D 2855.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check.
Allow fumes to dissipate for at least 5 minutes before
placing unit into operation..
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any
ridges or rough edges. If end is not chamfered,
edge of pipe may remove cement from tting socket
and result in a leaking joint.
NOTE - Check the inside of vent pipe thoroughly for
any obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 - Test t joint and mark depth of tting on outside of
pipe.
5 - Uniformly apply a liberal coat of PVC primer for
PVC or use a clean dry cloth for ABS to clean inside
socket surface of tting and male end of pipe to
depth of tting socket.
NOTE - Time is critical at this stage. Do not allow
primer to dry before applying cement.
6 - Promptly apply solvent cement to end of pipe and
inside socket surface of tting. Cement should be
applied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply
second coat to end of pipe.
7 - Immediately after applying last coat of cement to
pipe, and while both inside socket surface and end
of pipe are wet with cement, forcefully insert end of
pipe into socket until it bottoms out. Turn PVC pipe
1/4 turn during assembly (but not after pipe is fully
inserted) to distribute cement evenly. DO NOT turn
ABS or cellular core pipe.
Page 15
NOTE - Assembly should be completed within 20
Piping Suspension Guidelines
NOTE
r
roof in order to prevent transmission of vibration to the structure.
seconds after last application of cement. Hammer
blows should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at
end of tting socket. A properly made joint will show
a bead around its entire perimeter. Any gaps may
indicate an improper assembly due to insufcient
solvent.
9 - Handle joints carefully until completely set.
Venting Practices
SCHEDULE 40
PVC - 5'
all other pipe* - 3'
Conduct the following test while each appliance is operating and the other appliances (which are not operating)
remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
* See Piping and Fittings Specifications table
- Isolate piping at the point where it exits the outside wall o
Wall Thickness Guidelines
24” maximum
3/4” minimum
Wall
Figure 20
1 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance
on all sides of pipe through center of hole using a
hanger.
2 - When furnace is installed in a residence where unit
is shut down for an extended period of time, such
as a vacation home, make provisions for draining
condensate collection trap and lines.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly
vent the remaining attached appliances.
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances
remaining connected to the common venting system
edistuoedisni
are located and other spaces of the building. Turn on
clothes dryers and any appliances not connected to
the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so
that the appliance operates continuously.
5 - After the main burner has operated for 5 minutes,
test for leaks of ue gases at the draft hood relief
opening. Use the ame of a match or candle.
6 - After determining that each appliance connected
to the common venting system is venting properly,
(step 3 return all doors, widows, exhaust fans,
replace dampers, and any other gas-burning
appliances to their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modied to correct the problem.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current standards
Page 16
appliance.
REPLACING FURNACE THAT WAS PART OF A
COMMON VENT SYSTEM
Exhaust Pipe
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
WATER
FURNACE
(Replaced)
If replacing a furnace which was
commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent
should be checked for proper draw with the remaining
HEATER
OPENINGS
(To Adjacent
Room)
Figure 21
Exhaust Piping (Figure 22, Figure 24 and Figure 25)
Route piping to outside of structure. Continue with installation following instructions given in piping termination
section.
The EL296UHV can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air is
taken from indoors or ventilated attic or crawlspace and
ue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from outdoors and ue
gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 4 and 5. Count all elbows inside and outside the
home. Table 4 lists the minimum vent pipe lengths permitted. Table 5 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas
as it exits the termination. Refer to table 8. In some applications which permit the use of several different sizes of
vent pipe, a combination vent pipe may be used. Contact
Lennox’ Application Department for assistance in sizing
vent pipe in these applications.
NOTE - The exhaust collar on all models is sized to accommodate 2” Schedule 40 vent pipe. In horizontal applications, any transition to exhaust pipe larger than 2”
must be made in vertical runs of the pipe. Therefore a 2”
elbow must be added before the pipe is transitioned to
any size larger than 2”. This elbow must be added to the
elbow count used to determine acceptable vent lengths.
Contact the Application Department for more information
concerning sizing of vent systems which include multiple
pipe sizes.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even
with the top or outlet end of the metal stack.
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of
combustion products into the living space.
Vent Piping Guidlines
NOTE - Lennox has approved the use of DuraVent® and
Centrotherm manufactured vent pipe and terminations
as an option to PVC. When using the PolyPro® by DuraVent or InnoFlue® by Centrotherm venting system the
vent pipe requirements stated in the unit installation instruction – minimum & maximum vent lengths, termination
clearances, etc. – apply and must be followed. Follow the
instructions provided with PoyPro by DuraVent and InnoFlue by Centrotherm venting system for assembly or if requirements are more restrictive. The PolyPro by Duravent
and InnoFlue by Centrotherm venting system must also
follow the uninsulated
CAUTION
Exhaust Pipe
Horizontal
Gas Furnace
NOTE -
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)
of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
12” ma x
of straight pip
e
12”Min .
Figure 22
TABLE 4
MINIMUM VENT PIPE LENGTHS
EL296UHV MODELMIN. VENT LENGTH*
045, 070, 090, 110, 135
*Any approved termination may be added to the minimum length listed.
15 ft. or 5 ft plus 2 elbows or
10 ft plus 1 elbow
Page 17
Piping Size Process
What is the
furnace capacity?
1
045, 070, 090,
110 or 135?
Which style termination
2
3
4
5
being used?
Standard or concentric?
See table 3.
Which needs
most elbows?
Intake or
exhaust?
How many elbows?
Count all elbows inside
and outside house.
Desired pipe size?
2”, 2-1/2”, 3”
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
What is the altitude of
6
the furnace installation?
Use table 5 or 6 to find
max intake or exhaust pipe
7
length. Includes all vent
pipe and elbows inside
and outside the house.
Figure 23
Page 18
TABLE 5
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must
be same pipe size.
Standard Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
045070090110135045070090110135045070090110135
181664422
2” Pipe2-1/2” Pipe3” Pipe
ModelModelModel
1151159358
138137118118114
2766139191101108853133132113113109
3715634141051058348128127108108104
4665129
100100784312312210310399
561462495957338118117989894
n/a
n/a
656411990906833113112939389
751361485856328108107888884
84631
94126757553189897787874
n/a
n/a
80805823103102838379
103621707048139392737369
Standard Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
04507009011 013504507009011 013504507009011 0135
1816644
2” Pipe2-1/2” Pipe3” Pipe
ModelModelModel
1151159358
13813711811811 4
2766139110110885313313211 3113109
37156341051058348128127108108104
4665129100100784312312210310399
561462495967338118117989894
n/an/a
n/a
656411990906833113112939389
751361485856328108107888884
84631
94126757553189897787874
n/a
103621707048139392737369
See concentric terminations next page.
80805823103102838379
Page 19
TABLE 5 Continued
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total.
Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
045070090110135045070090110135045070090110135
173584222
2” Pipe2-1/2” Pipe3” Pipe
ModelModelModel
1051058954
121121114114105
2685337171001008449116116109109100
3634832129595794411111110410495
4584327
90907439106106999990
553382285856934101101949485
n/a
n/a
6483317808064299696898980
7432812757559249191848475
83823
93318656549148181747465
n/a
n/a
707054198686797970
102813606044n/a7676696960
Concentric Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
04507009011 013504507009011 013504507009011 0135
1735842
2” Pipe2-1/2” Pipe3” Pipe
ModelModelModel
1051058954
121121114114105
26853371001008449116116109109100
36348329595794411111110410495
458432790907439106106999990
553382285856934101101949485
n/an/a
n/a
6483317808064299696898980
7432812757559249191848475
83823
93318656549148181747465
n/a
102813606044n/a7676696960
707054198686797970
Page 20
TABLE 6
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total.
Both Intake and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the
total vent length calculation
Standard Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
045070090110135045070090110135045070090110135
171563414
2” Pipe2-1/2” Pipe3” Pipe
ModelModelModel
1001007843
118117989894
2665129995957338113112939389
3614624490906833108107888884
4564119
85856328103102838379
5513614808058239897787874
n/a
n/a
646319757553189392737369
741264707048138887686864
83621
9311660603837877585854
n/a
n/a
65654388382636359
102611555533n/a7372535349
Standard Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
04507009011 013504507009011 013504507009011 0135
1715634
2” Pipe2-1/2” Pipe3” Pipe
ModelModelModel
1001007843
118117989894
266512995957338113112939389
361462490906833108107888884
456411985856328103102838379
5513614808058239897787874
n/an/a
n/a
646319757553189392737369
741264707048138887686864
83621
9311660603837877585854
n/a
102611555533n/a7372535349
65654388382636359
Page 21
Loading...
+ 46 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.