Lennox EL296UH045XV36B, EL296UH110XV48C, EL296UH110XV60C, EL296UH135XV60D, EL296UH090XV48C Installation Instructions Manual

...
Page 1
© 2017 Lennox Industries Inc.
INSTALLATION INSTRUCTIONS EL296UHV
ELITE® SERIIES GAS FURNACE UP/FLOW HORIZONTAL AIR DISCHARGE
507264-03 06/2017 Superseds 03/2017
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in man­uals, be alert to the potential for personal injury or death.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
AIR FLOW
AIR FLOW
HORIZONTAL LEFT
UPFLOW
AIR FLOW
HORIZONTAL RIGHT
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Table of Contents
Unit Dimensions - inches (mm) .....................................2
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 5
Shipping Bolt Removal ...................................................8
Installation - Setting Equipment ...................................... 8
Filters ............................................................................ 13
Duct System .................................................................13
Pipe & Fittings Specications .......................................13
Joint Cementing Procedure .......................................... 15
Venting Practices ..........................................................16
Gas Piping .................................................................... 36
Electrical ....................................................................... 39
NOTICE
A thermostat is not included and must be ordered separately.
The Lennox icomforti® thermostat must be used in communicating applications.
In non-communicating applications, the Lennox ComfortSense® 7500 thermostat may be used, as well as other non-communicating thermostats.
In all cases, setup is critical to ensure proper system operation.
Field wiring for both communicating and non­communicating applications is illustrated in diagrams,
which begin on Page 41.
Integrated Control ......................................................... 48
Conventional Thermostat (non-communicating) ...........49
Blower Data .................................................................. 51
On-Board Links.............................................................55
Unit Start Up ................................................................. 57
Gas Pressure Adjustment ............................................. 58
Proper Cumbustion.......................................................59
High Altitude .................................................................59
Combustion Air for Non-Direct Vent Applications .........60
Repair Parts..................................................................60
Other Unit Adjustments................................................. 61
Heating Sequence of Operation ...................................61
Service..........................................................................63
Program Unit Capacity/Size Mode ...............................65
Requirements for Commonwealth of Massachusetts ... 66
Page 1
Page 2
Unit Dimensions - inches (mm)
1
NOTE - 60C and 60D size units that require second stage
air volumes over 1800 cfm must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. cleanable air filter. Required to maintain proper air velocity.
2. Single side return air with Optional Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
See Blower Performance Ta bles for additional information.
2
Optional Side Return Air Filter Kit is not for use with the Optional Return Air Base.
one side return air.
1-7/8 (48)
D
3-1/4
(83)
EXHAUST AIR
OUTLET
SUPPLY AIR
OPENING
Flue Condensate Trap Assembly
Furnished for external field installation on either side of unit. (See installation instructions for additional information.)
A
B
9/16 (14)
2
OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
14-3/4
(375)
16
(406)
7
(178)
(838)
33
COMBUSTION
AIR INTAKE
2
SIDE RETURN
AIR FILTER KIT
(Either Side)
1-1/2 (38)
Front Panel
6-9/16 (167)
12-5/8 (321)
(Either Side)
ELECTRICAL
INLET
(Either Side)
OPTIONAL
Left
9 (229)
Right
23-3/4
(603)
TOP VIEW
27-3/4
(705)
2 (51) (Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE TRAP CONNECTION (Either Side)
6-1/2 (165) (Either Side)
23
(584)
1
Side Return Air Opening (Either Side)
25
(635)
19-7/16
(494)
14
(356)
9/16 (14)
1-1/2
(38)
AIR FLOW
3/4
(19)
C
1
Bottom Return
Air Opening
FRONT VIEW SIDE VIEW
Model A B C D
EL296UH045XV36B
EL296UH070XV36B
EL296UH090XV36C EL296UH090XV48C EL296UH090XV60C EL296UH110XV48C EL296UH110XV60C
EL296UH135XV60D 24−1/2 in 622 mm 23−3/8 in 594 mm 23 in 584 mm 11−1/8 in 283 mm
17−1/2 in 446 mm 16−3/8 in 416 mm 16 in 406 mm 7−5/8 in 194 mm
21 in 533 mm 19−7/8 in 505 mm 19−1/2 in 495 mm 9−3/8 in 238 mm
3/4
(19)
5/8
(16)
Page 2
3-1/4
(83)
23-1/2
(597)
1
Bottom Return
Air Opening
1-15/16 (49)
Page 3
EL296UHV Gas Furnace
NON-DIRECT VENT
INSTALLATION
NON-DIRECT VENT
INSTALLATION
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
EXHAUST OUTLET
EXHAUST OUTLET
The EL296UHV Category IV gas furnace is shipped ready for installation in the upow or horizontal position. The fur­nace is shipped with the bottom panel in place. The bot­tom panel must be removed if the unit is to be installed
in horizontal or upow applications with bottom return air.
The EL296UHV can be installed as either a Direct Vent or a Non-Direct Vent gas central furnace.
The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is re­quired for use in propane/LP gas applications.
NOTE - In Direct Vent installations, combustion air is tak-
en from outdoors and ue gases are discharged outdoors.
In Non-Direct Vent installations, combustion air is taken
from indoors or ventilated attic or crawlspace and ue gases are discharged outdoors. See for applications in­volving roof termination.
DIRECT VENT INSTALLATION NON-DIRECT VENT
EXHAUST OUTLET
COMBUSTION
AIR INTAKE OUTSIDE
OF HOUSE
INSTALLATION
EXHAUST
OUTLET
Shipping and Packing List
Package 1 of 1 contains
1 - Assembled EL296UHV unit 1 - Bag assembly containing the following:
1 - Snap bushing 1 - Snap plug 1 - Wire tie 1 - Condensate trap 1 - Condensate trap cap 1 - Condensate trap clamp 1 - 2” diameter debris screen 1 - 3/4” Threaded street elbow
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier. The following items may also be ordered separately: 1 - Thermostat 1 - LP/Propane changeover kit 1 - Return air base kit 1 - Horizontal suspension kit 1 - High altitude pressure switch
Safety Information
Figure 1
Figure 2
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
DANGER
Danger of explosion. There are circumstances in which odorant used with LP/
propane gas can lose its scent. In case of a leak, LP/
propane gas will settle close to the oor and may be difcult to smell. An LP/propane leak detector should be
installed in all LP applications.
Use only the type of gas approved for use with this fur­nace. Refer to unit nameplate.
EL296UHV units are CSA International certied to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
Page 3
Page 4
In order to ensure proper unit operation in non-direct vent
Gas Unit
Heating Unit Installed Upstream of Cooling Unit
Gas Unit
Dampers
(open during heating operation only)
Dampers
(open during cooling operation only)
Heating Unit Installed Parallell to Air Handler Unit
Air Handler Unit
Evaporator
applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
Installation Locations
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit nameplate and in the table in Figure 12. Accessibility and service clearances must take precedence over re protec­tion clearances.
NOTE - For installation on combustible oors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood ooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed ac­cording to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specied on the unit nameplate. Fail­ure to do so may cause erratic limit operation and prema­ture heat exchanger failure.
This EL296UHV furnace must be installed so that its elec­trical components are protected from water. Installed in Combination with a Cooling Coil When this furnace is used with cooling coils (Figure 3), it shall be installed in parallel with, or on the upstream side of, cooling coils to avoid condensation in the heating compartment. With a
parallel ow arrangement, a damper (or other means to control the ow of air) must adequately prevent chilled ai
from entering the furnace. If the damper is manually op­erated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec­tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
Figure 3
NOTE - This furnace is designed for a minimum contin­uous return air temperature of 60°F (16°C) or an inter­mittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The EL296UHV furnace may be installed in alcoves, clos­ets, attics, basements, garages, crawl spaces and utility
rooms in the upow or horizontal position. This furnace design has not been CSA certied for installation in mobile
homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
NOTE - Gas furnaces manufactured on or after May 1st 2017 are not permitted to be used in Canada for heating of buildings or structures under construction.
The following statement only applies to the US. Lennox does not recommend the use of EL296UHV units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors, construction dust and operation of the unit with clogged or misplaced
lters may damage the unit.
However, EL296UHV units may be used for heating of
buildings or structures under construction in the US, if the
following conditions are met to ensure proper operation:
The vent system must be permanently installed per
these installation instructions.
A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to
the furnace.
Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
Air lters must be installed in the system and must
be maintained during construction.
Page 4
Page 5
Air lters must be replaced upon construction com-
pletion.
The input rate and temperature rise must be set per
the furnace rating plate.
One hundred percent (100%) outdoor air must be
provided for combustion air requirements during construction. Temporary ducting may supply out­door air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilu­tion and Ventilation Air in a conned space with air from outside.
The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be thoroughly cleaned following nal construction clean-up.
All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. In addition to the requirements outlined previously, the fol-
lowing general recommendations must be considered when installing a EL296UHV furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.
• When the furnace is installed in non-direct vent ap­plications, do not install the furnace where drafts might blow directly into it. This could cause improp­er combustion and unsafe operation.
• When the furnace is installed in non-direct vent ap­plications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is need­ed for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the fur­nace.
• When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
• Please consult the manufacturer of your evaporator coil for their recommendations on distance required between the heat exchanger and their drain pan. Adequate space must be provided between the drain pan and the furnace heat exchanger.
CAUTION
EL296UHV unit should not be installed in areas normally subject to freezing temperatures.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
WARNING
Insufcient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
Combustion, Dilution & Ventilation Air
If the EL296UHV is installed as a Non-Direct Vent Fur­nace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air is taken from indoors or ventilated attic or crawlspace and
ue gases are discharged out-doors.
In the past, there was no problem in bringing in sufcient outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Unless outside air is brought into the house for combus-
tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a poten­tially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install EL296UHV furnaces to ensure ef-
Page 5
Page 6
cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI. Z223.1/NFPA 54). This reprinted material is not the com-
plete and ofcial position of the ANSI on the referenced
subject, which is represented only by the standard in its entirety.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-red appliances require air for the combustion process. If sufcient combustion air is not available, the furnace or other appliance will operate inefciently and
unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When replac­es, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insuf­cient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace com­ponents.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be
unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the procedures in the Air from Outside section
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace.This is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room. Even a small leak around the base of the unit at the plat-
form or at the return air duct connection can cause a po­tentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the con-
ned space either from inside the building or from outside.
Air from Inside
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in by
providing two permanent openings between the two spac­es. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See Figure 4.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE - Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm all equipment in the enclosure, but not less than 100 square inches (64516mm.
2).
EL296UH
V
2
per .29kW) per hour of the total input rating of
(To Adjacent
Unconfined
Space)
Figure 4
Page 6
Page 7
Air from Outside
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
If air from outside is brought in for combustion and ventila­tion, the conned space shall be provided with two perma­nent openings. One opening shall be within 12” (305mm) of the top of the enclosure and one within 12” (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the en­closure. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rating of all equipment in the enclosure (See Figure 5). It is also permissible to bring in air for combus-
tion from a ventilated attic (gure 6) or ventilated crawl
space (Figure 7).
(Inlet Air from Crawl Space and Outlet Air to Outside)
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Inlet Air
(Minimum
Ventilation
Louvers
(Crawl space)
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
Furnace
12 in.(305mm)
Above crawl
space floor)
*Intake Debris Screen Provided)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
2
per 1.17kW) per
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
FURNACE
INLET
AIR
Figure 5
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Roof Terminated
Exhaust Pipe
*Intake Debris
Screen
(Provided)
Furnace
(Minimum
12 in.(305mm) Above
attic floor)
VENTILATION
LOUVERS
(For unheated
crawl space)
Inlet Air
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
2
per 1.17kW) per
Figure 7
If air from outside is brought in for combustion and ventila­tion, the conned space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or in­directly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See Figure 5 and Figure 8. When com­municating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rat­ing of all equipment in the enclosure. See Figure 9.
When ducts are used, they shall be of the same cross-sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they are opened automatically during equipment operation.
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
Figure 6
2
per 1.17kW) per
Page 7
Page 8
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
of the total input rating of all equipment in the enclosure.
ROOF TERMINATED
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
of the total input rating of all equipment in the enclosure.
r
EXHAUST PIPE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
The bolt and washer must be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg will not touch the blower hous­ing.
UNITS WITH 1/2 HP
BLOWER MOTOR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
FURNACE
INLET AIR
(Ends 12” above
bottom)
2
per 1.17kW) per hour
Figure 8
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
FURNACE
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12” above
bottom)
2
per 1.17kW) per hour
Figure 9
Shipping Bolt Removal
Units with 1/2 hp blower motor are equipped with three
exible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a at white plastic washer (rather than the rubber mounting grommet used with a exible
mounting leg). See Figure 10.
remove shipping bolt and washe
RIGID LEG
Figure 10
Installation - Setting Equipment
WARNING
Do not connect the return air duct to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Upow Applications
The EL296UHV gas furnace can be installed as shipped in the upow position. Refer to Figure 12 for clearances. Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. The unit may be
positioned from level to ½” toward the front. See Figure
11.
Allow for clearances to combustible materials as indicated on the unit nameplate.
Page 8
Page 9
SETTING EQUIPMENT
END VIEW
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
UPFLOW APPLICATION
UNIT
FRONT
1/2” max.
SIDE VIEW
AIR FLOW
FRONT VIEW
UNIT
FRONT
SIDE VIEW
HORIZONTAL APPLICATION
AIR FLOW
FRONT VIEW
Figure 11
UNIT
FRONT
1/2”
max.
Page 9
Page 10
WARNING
Installation Clearances
Side Return Air
Improper installation of the furnace can result in
personal injury or death. Combustion and ue products
must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct systems ever be connected to or from other heating devices
such as a replace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property damage could result.
Return Air Guidelines
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cab­inet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
Refer to Engineering Handbook for additional information.
EL296UHV applications which include side return air and a condensate trap installed on the same side of the cabinet (trap can be installed remotely within 5
ft.) require either a return air base or eld-fabricated
transition to accommodate an optional IAQ accessory taller than 14.5”. See Figure 13.
Top
Left Side Right Side
Bottom (Floor)
Top/Plenum 1 in. (25 mm)
*Front 0
Back 0
Sides 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.
Allow proper clearances to accommodate condensate trap.For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other than wood flooring.
(with transition and filter)
20” X 25” X 1”
(508mmX635mmX 25mm)
Air Filter
Return
Air
Plenum
Transition
Figure 13
Figure 12
Page 10
Page 11
CONDENSATE
Removing the Bottom Panel
Bottom Panel
See figure 4.
TRAP
AIR FLOW
17−1/2 (446) B Width (50W98) 21 (533) C Width (50W99) 24−1/2 (622) D Width (51W00)
FURNACE
INDOOR AIR
QUALITY
CABINET
(PCO, Filter
Cabinet, etc.)
FRONT VIEW
NOTE- Optional side return air filter kits are not for use with return air base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
Optional Return Air Base
(Upflow Applications Only)
FRONT
IF BASE
IS USED
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
OPTIONAL RETURN AIR BASE
3−1/4
(83)
7−1/4
(184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
SIDE RETURN
5−5/8
AIR OPENINGS
(143)
(Either Side)
26−7/8
(683)
SIDE VIEW
23
(584)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
3/4
(19)
Figure 14
Screw
Figure 15
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See Figure 15.
Horizontal Applications
WARNING
Do not install the furnace on its front or back. See Figure 16.
Bottom Cap
Front Back
Figure 16
Page 11
Page 12
The EL296UHV furnace can be installed in horizontal ap-
Horizontal Application
HORIZONTAL SUSPENSION KIT
plications with either right- or left-hand air discharge. Re­fer to Figure 17 for clearances in horizontal applications.
Installation Clearances
Metal Strap
(typical)
Internal Brace
(provided with kit)
Right-Hand Discharge
Air
Flow
dnE thgiRdnE tfeL
dnE thgiRdnE tfeL
AIR FLOW
Air
Flow
Bottom (Floor)**
Left-Hand Discharge
Top
AIR FLOW
Bottom (Floor)**
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. **An 8” service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
Figure 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl­space. Either suspend the furnace from roof rafters or oor joists, as shown in Figure 18, or install the furnace on a platform, as shown in Figure 19. A horizontal sus­pension kit (51W10) may be ordered from Lennox or use equivalent.
NOTE - Heavy-gauge sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust piping installation.
Cooling coils and supply and return air plenums must be supported separately.
Bracket
(typical)
Air
Flow
Figure 18
NOTE - When the furnace is installed on a platform or with the horizontal suspension kit in a crawlspace, it must be elevated enough to avoid water damage, accommodate drain trap and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1 - Select location for unit keeping in mind service and
other necessary clearances. See Figure 17.
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above
nished space, install an an auxiliary drain pan
under unit. Set unit in drain pan as shown in Figure
19. Leave 8 inches for service clearance below unit for condensate trap.
3 - Provide a service platform in front of unit. When
installing the unit in a crawl space, a proper support platform may be created using cement blocks.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5 - If necessary, run the condensate line into a
condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line from the pump to the outside to avoid freezing.
6 - Continue with exhaust, condensate and intake
piping installation according to instructions.
Page 12
Page 13
INTAKE PIPE
EXHAUST PIPE
*Gas connector may be used for Canadian
able by local authority having jurisdiction.
SERVICE PLATFORM
*GAS CONNECTION
RAISED
PLATFORM
Figure 19
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a furnace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate in­stallation. See Figure 15.
Filters
This unit is not equipped with a lter or rack. A eld-pro­vided high velocity rated lter is required for the unit to operate properly. Table 1 lists recommended lter sizes. A lter must be in place whenever the unit is operating.
IMPORTANT
If a highefciency lter is being installed as part of this system to ensure better indoor air quality, the lter must be properly sized. Highefciency lters have a higher static pressure drop than standardefciency glass/foam lters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop may also cause the limit to trip more
frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls.
Before using any lter with this system, check the specications provided by the lter manufacturer against
the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002 (August 2000).
TABLE 1
Furnace
Cabinet Width
Side Return Bottom Return
17-1/2” 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21” 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24-1/2” 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Filter Size
Duct System
Use industry-approved standards to size and install the supply and return air duct system. Refer to ACCA Manual D. This will result in a quiet and low-static system that has uniform air distribution.
NOTE - This furnace is not certied for operation in heat­ing mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.8 inches w.c. Operation at these conditions may result in improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a remov­able access panel should be installed in the supply air duct. The access panel should be large enough to per­mit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operat­ing and it must not allow leaks.
Return Air Plenum
NOTE - Return air must not be drawn from a room where this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing de-
vice (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This reverse ow of the ue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed through­out the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace (return air brought into either side of
furnace allowed only in upow applications). If a furnace
with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use berglass sealing strips, caulking, or equiva­lent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the return air duct to t the lter frame.
Pipe & Fittings Specications
All pipe, ttings, primer and solvent cement must conform
with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan-
dards. The solvent shall be free owing and contain no
lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, strati-
cation, or separation that cannot be removed by stirring. Refer to the table 2 below for approved piping and tting
materials.
Page 13
Page 14
CAUTION
Solvent cements for plastic pipe are ammable liquids
and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to
reduce re hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785
Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR-21 PVC or SDR-26 PVC (Pipe) D2241
SDR-21 CPVC or SDR-26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe)
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS-DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC-DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656
PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm
F628
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235,
F493
D3188
MARKING
ULCS636
IMPORTANT
EL296UHV exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the
PVC ttings in the unit.
Use PVC primer and solvent cement or ABS solvent ce-
ment meeting ASTM specications, refer to Table 2. As an
alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using ttings and pipe made of the same
materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean
inside socket surface of tting and male end of pipe to depth of tting socket.
Canadian Applications Only - Pipe, ttings, primer and solvent cement used to vent (exhaust) this appliance must be certied to ULC S636 and supplied by a single manu­facturer as part of an approved vent (exhaust) system. In addition, the rst three feet of vent pipe from the furnace ue collar must be accessible for inspection.
Page 14
Page 15
TABLE 3
OUTDOOR TERMINATION USAGE*
STANDARD CONCENTRIC
Wall Kit
2 inch 3 inch 2 inch
22G44
(US)
4
30G28
(CA)
44J40
(US)
4
81J20
(CA)
1
YES
1
YES
1
YES
1
YES
1
YES
1
YES
Input Size
045
070
090
Vent Pipe
Dia. in.
2
2-1/2
3
2
2-1/2
3
2
2-1/2
3
Flush
Mount Kit
51W11
(US)
51W12
(CA)
3
YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES YES
3
YES YES YES
3
YES YES YES
2 YES YES YES
110
2-1/2 YES YES
3 YES YES
135 3 YES YES
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length
calculations. See vent length tables. * Kits must be properly installed according to kit instructions.
1Requires eld-provided outdoor 1-1/2” exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models. 3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4 Termination kits 30G28, 44W92, 44W93 and 81J20 are certied to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
Wall Ring
Kit
15F74
1
YES
1
YES
1
YES
1
YES
1
YES
1
YES
1-1.2 inch 2 inch 3 inch
Field
Fabricated
5
YES
5
YES
5
YES
5
YES
5
YES
5
YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES
71M80
(US)
4
44W92
(CA)
2
YES
2
YES
2
YES
2
YES
2
YES
2
YES
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
Joint Cementing Procedure
All cementing of joints should be done according to the
specications outlined in ASTM D 2855.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation..
1 - Measure and cut vent pipe to desired length. 2 - Debur and chamfer end of pipe, removing any
ridges or rough edges. If end is not chamfered,
edge of pipe may remove cement from tting socket
and result in a leaking joint.
NOTE - Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 - Test t joint and mark depth of tting on outside of
pipe.
5 - Uniformly apply a liberal coat of PVC primer for
PVC or use a clean dry cloth for ABS to clean inside
socket surface of tting and male end of pipe to depth of tting socket.
NOTE - Time is critical at this stage. Do not allow primer to dry before applying cement.
6 - Promptly apply solvent cement to end of pipe and
inside socket surface of tting. Cement should be
applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.
7 - Immediately after applying last coat of cement to
pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular core pipe.
Page 15
Page 16
NOTE - Assembly should be completed within 20
Piping Suspension Guidelines
NOTE
r
roof in order to prevent transmission of vibration to the structure.
seconds after last application of cement. Hammer blows should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at
end of tting socket. A properly made joint will show
a bead around its entire perimeter. Any gaps may
indicate an improper assembly due to insufcient
solvent.
9 - Handle joints carefully until completely set.
Venting Practices
SCHEDULE 40
PVC - 5'
all other pipe* - 3'
Conduct the following test while each appliance is oper­ating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting re­quirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
* See Piping and Fittings Specifications table
- Isolate piping at the point where it exits the outside wall o
Wall Thickness Guidelines
24” maximum 3/4” minimum
Wall
Figure 20
1 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
2 - When furnace is installed in a residence where unit
is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas applianc­es, the venting system is likely to be too large to properly vent the remaining attached appliances.
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances remaining connected to the common venting system
edistuoedisni
are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5 - After the main burner has operated for 5 minutes,
test for leaks of ue gases at the draft hood relief opening. Use the ame of a match or candle.
6 - After determining that each appliance connected
to the common venting system is venting properly, (step 3 return all doors, widows, exhaust fans,
replace dampers, and any other gas-burning
appliances to their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modied to correct the problem.
Resize the common venting system to the minimum vent pipe size determined by using the appropriate ta­bles in Appendix G. (These are in the current standards
Page 16
Page 17
appliance.
REPLACING FURNACE THAT WAS PART OF A
COMMON VENT SYSTEM
Exhaust Pipe
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
WATER
FURNACE
(Replaced)
If replacing a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining
HEATER
OPENINGS
(To Adjacent
Room)
Figure 21
Exhaust Piping (Figure 22, Figure 24 and Figure 25)
Route piping to outside of structure. Continue with instal­lation following instructions given in piping termination section.
The EL296UHV can be installed as either a Non-Direct Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air is taken from indoors or ventilated attic or crawlspace and
ue gases are discharged outdoors. In Direct Vent instal­lations, combustion air is taken from outdoors and ue gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 4 and 5. Count all elbows inside and outside the home. Table 4 lists the minimum vent pipe lengths per­mitted. Table 5 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8. In some appli­cations which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications.
NOTE - The exhaust collar on all models is sized to ac­commodate 2” Schedule 40 vent pipe. In horizontal ap­plications, any transition to exhaust pipe larger than 2” must be made in vertical runs of the pipe. Therefore a 2” elbow must be added before the pipe is transitioned to any size larger than 2”. This elbow must be added to the elbow count used to determine acceptable vent lengths. Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.
Vent Piping Guidlines
NOTE - Lennox has approved the use of DuraVent® and Centrotherm manufactured vent pipe and terminations as an option to PVC. When using the PolyPro® by Du­raVent or InnoFlue® by Centrotherm venting system the vent pipe requirements stated in the unit installation in­struction – minimum & maximum vent lengths, termination clearances, etc. – apply and must be followed. Follow the instructions provided with PoyPro by DuraVent and Inno­Flue by Centrotherm venting system for assembly or if re­quirements are more restrictive. The PolyPro by Duravent and InnoFlue by Centrotherm venting system must also follow the uninsulated
CAUTION
Exhaust Pipe
Horizontal
Gas Furnace
NOTE -
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm) of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
12” ma x
of straight pip
e
12”Min .
Figure 22
TABLE 4
MINIMUM VENT PIPE LENGTHS
EL296UHV MODEL MIN. VENT LENGTH*
045, 070, 090, 110, 135
*Any approved termination may be added to the minimum length list­ed.
15 ft. or 5 ft plus 2 elbows or
10 ft plus 1 elbow
Page 17
Page 18
Piping Size Process
What is the
furnace capacity?
1
045, 070, 090,
110 or 135?
Which style termination
2
3
4
5
being used?
Standard or concentric?
See table 3.
Which needs
most elbows?
Intake or
exhaust?
How many elbows? Count all elbows inside and outside house.
Desired pipe size?
2”, 2-1/2”, 3”
IMPORTANT
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations.
What is the altitude of
6
the furnace installation?
Use table 5 or 6 to find max intake or exhaust pipe
7
length. Includes all vent pipe and elbows inside and outside the house.
Figure 23
Page 18
Page 19
TABLE 5
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 81 66 44 22
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
115 115 93 58
138 137 118 118 114
2 76 61 39 19 110 110 88 53 133 132 113 113 109
3 71 56 34 14 105 105 83 48 128 127 108 108 104
4 66 51 29
100 100 78 43 123 122 103 103 99
5 61 46 24 95 95 73 38 118 117 98 98 94
n/a
n/a
6 56 41 19 90 90 68 33 113 112 93 93 89
7 51 36 14 85 85 63 28 108 107 88 88 84
8 46 31
9 41 26 75 75 53 18 98 97 78 78 74
n/a
n/a
80 80 58 23 103 102 83 83 79
10 36 21 70 70 48 13 93 92 73 73 69
Standard Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
045 070 090 11 0 135 045 070 090 11 0 135 045 070 090 11 0 135
1 81 66 44
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
115 115 93 58
138 137 118 118 11 4
2 76 61 39 110 110 88 53 133 132 11 3 113 109
3 71 56 34 105 105 83 48 128 127 108 108 104
4 66 51 29 100 100 78 43 123 122 103 103 99
5 61 46 24 95 96 73 38 118 117 98 98 94
n/a n/a
n/a
6 56 41 19 90 90 68 33 113 112 93 93 89
7 51 36 14 85 85 63 28 108 107 88 88 84
8 46 31
9 41 26 75 75 53 18 98 97 78 78 74
n/a
10 36 21 70 70 48 13 93 92 73 73 69
See concentric terminations next page.
80 80 58 23 103 102 83 83 79
Page 19
Page 20
TABLE 5 Continued
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 73 58 42 22
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
105 105 89 54
121 121 114 114 105
2 68 53 37 17 100 100 84 49 116 116 109 109 100
3 63 48 32 12 95 95 79 44 111 111 104 104 95
4 58 43 27
90 90 74 39 106 106 99 99 90
5 53 38 22 85 85 69 34 101 101 94 94 85
n/a
n/a
6 48 33 17 80 80 64 29 96 96 89 89 80
7 43 28 12 75 75 59 24 91 91 84 84 75
8 38 23
9 33 18 65 65 49 14 81 81 74 74 65
n/a
n/a
70 70 54 19 86 86 79 79 70
10 28 13 60 60 44 n/a 76 76 69 69 60
Concentric Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
045 070 090 11 0 135 045 070 090 11 0 135 045 070 090 11 0 135
1 73 58 42
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
105 105 89 54
121 121 114 114 105
2 68 53 37 100 100 84 49 116 116 109 109 100
3 63 48 32 95 95 79 44 111 111 104 104 95
4 58 43 27 90 90 74 39 106 106 99 99 90
5 53 38 22 85 85 69 34 101 101 94 94 85
n/a n/a
n/a
6 48 33 17 80 80 64 29 96 96 89 89 80
7 43 28 12 75 75 59 24 91 91 84 84 75
8 38 23
9 33 18 65 65 49 14 81 81 74 74 65
n/a
10 28 13 60 60 44 n/a 76 76 69 69 60
70 70 54 19 86 86 79 79 70
Page 20
Page 21
TABLE 6
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation
Standard Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 71 56 34 14
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
100 100 78 43
118 117 98 98 94
2 66 51 29 9 95 95 73 38 113 112 93 93 89
3 61 46 24 4 90 90 68 33 108 107 88 88 84
4 56 41 19
85 85 63 28 103 102 83 83 79
5 51 36 14 80 80 58 23 98 97 78 78 74
n/a
n/a
6 46 31 9 75 75 53 18 93 92 73 73 69
7 41 26 4 70 70 48 13 88 87 68 68 64
8 36 21
9 31 16 60 60 38 3 78 77 58 58 54
n/a
n/a
65 65 43 8 83 82 63 63 59
10 26 11 55 55 33 n/a 73 72 53 53 49
Standard Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
045 070 090 11 0 135 045 070 090 11 0 135 045 070 090 11 0 135
1 71 56 34
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
100 100 78 43
118 117 98 98 94
2 66 51 29 95 95 73 38 113 112 93 93 89
3 61 46 24 90 90 68 33 108 107 88 88 84
4 56 41 19 85 85 63 28 103 102 83 83 79
5 51 36 14 80 80 58 23 98 97 78 78 74
n/a n/a
n/a
6 46 31 9 75 75 53 18 93 92 73 73 69
7 41 26 4 70 70 48 13 88 87 68 68 64
8 36 21
9 31 16 60 60 38 3 78 77 58 58 54
n/a
10 26 11 55 55 33 n/a 73 72 53 53 49
65 65 43 8 83 82 63 63 59
Page 21
Page 22
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON-DIRECT VENT APPLICATIONS
EXHAUST
2”
INTAKE
2”
EXHAUSTINTAKE
2”
2”
or
3”
TRANSITION
*2”
3”
TRANSITION
*2”
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
Figure 24
2”
2”
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON-DIRECT VENT
APPLICATIONS
12” max.
EXHAUST
2”
INTAKE
EXHAUST
*2”
INTAKE
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
(RIGHT HAND DISCHARGE SHOWN)
2”
or
2”
2”
3”
*2”
2”
2”
TRANSITION
*2”
2”
or
2”
3”
*2”
45°
MAX
2”
*2”
2”
SIDE VIEW
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
45°
MAX
Figure 25
Page 22
Page 23
Intake Piping
TYPICAL AIR INTAKE PIPE CONNECTIONS
(preferred) or with an elbow rotated to face down.
The EL296UHV furnace may be installed in either direct vent or non-direct vent applications. In non-direct vent
applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
Follow the next two steps when installing the unit in Direct Vent applications, where combustion air is taken from
outdoors and ue gases are discharged outdoors. The provided air intake screen must not be used in direct vent applications (outdoors).
1 - Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
2 - Route piping to outside of structure. Continue with
installation following instructions given in general guidelines for piping terminations and intake and exhaust piping terminations for direct vent sections. Refer to table 5 for pipe sizes.
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
VENT APPLICATIONS
INTAKE DEBRIS
SCREEN
(Provided)
NOTE - Debris screen and elbow may be rotated, so that screen may be positioned to face forward or to either side.
Figure 26
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
PVC pipe
coupling
OR
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE - Debris screen may be positioned straight out
Figure 27
Follow the next two steps when installing the unit in Non­Direct Vent applications where combustion air is taken
from indoors or ventilated attic or crawlspace and ue
gases are discharged outdoors.
1 - Use eld-provided materials and the factory-
provided air intake screen to route the intake piping as shown in Figure 26 or Figure 27. Maintain a minimum clearance of 3” (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed
forward or to either side in the upow position, and
either straight out or downward in the horizontal position.
The air intake piping must not terminate too close
to the ooring or a platform. Ensure that the intake air inlet will not be obstructed by loose insulation
or other items that may clog the debris screen.
2 - If intake air is drawn from a ventilated attic (Figure
28) or ventilated crawlspace (Figure 29) the exhaust vent length must not exceed those listed in table 6. If 3” diameter pipe is used, reduce to 2” diameter pipe at the termination point to accommodate the debris screen.
3 - Use a sheet metal screw to secure the intake pipe
to the connector, if desired.
Page 23
Page 24
CAUTION
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
Furnace
*Intake Debris
Screen
(Provided)
EQUIPMENT IN CONFINED SPACE
If this unit is being installed in an application with combustion air coming in from a space serviced by an exhaust fan, power exhaust fan, or other device which may create a negative pressure in the space, take care when sizing the inlet air opening. The inlet air opening must be sized to accommodate the maximum volume of exhausted air as well as the maximum volume of combustion air required forall gas appliances serviced by this space.
Figure 28
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Inlet Air
(Minimum
Ventilation
Louvers
(Crawl space)
(Field Provided)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
Furnace
Coupling or 3 in. to 2 in.
Transition
12 in.(305mm)
Above crawl
space floor)
*Intake Debris Screen Provided)
2
per 1.17kW) per
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken
from indoors or ventilated attic or crawlspace and the ue
gases are discharged to the outdoors. The EL296UHV is then classied as a non-direct vent, Category IV gas fur­nace.
In Direct Vent applications, combustion air is taken from
outdoors and the ue gases are discharged to the out­doors. The EL296UHV is then classied as a direct vent,
Category IV gas furnace. In both Non-Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current CSA-B149 Natural Gas and Propane Installation Codes in Canada for details.
Position termination according to location given in Figure 31 or Figure 32. In addition, position termination so it is free from any obstructions and 12” above the average snow accumulation.
At vent termination, care must be taken to maintain protec­tive coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of an outdoor AC unit because the condensate can damage the painted coating.
NOTE - See table 7 for maximum allowed exhaust pipe length without insulation in unconditioned space during winter design temperatures below 32°F (0°C). If required exhaust pipe should be insulated with 1/2” (13mm) Ar­maex or equivalent. In extreme cold climate areas, 3/4” (19mm) Armaex or equivalent may be necessary. Insu­lation must be protected from deterioration. Armaex with UV protection is permissable. Basements or other en­closed areas that are not exposed to the outdoor ambient temperature and are above 32 degrees F (0°C) are to be considered conditioned spaces.
IMPORTANT
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations.
IMPORTANT
For Canadian Installations Only: In accordance to CSA International B149 installation
codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).
Figure 29
Page 24
Page 25
TABLE 7
Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
Winter Design Temperatures Two - Stage High Efciency Furnace
Winter Design
Temperatures1 °F
(°C)
32 to 21
(0 to -6)
Vent Pipe
Diameter
2 in 21 18 33 30 46 42 30 30 n/a n/a
2-1/2 in 16 n/a 26 n/a 37 n/a 36 n/a n/a n/a
045 070 090 110 135
PVC
2
PP
PVC
3 in 12 12 21 21 30 30 29 29 42 42
20 to 1
(-7 to -17)
0 to -20
(-18 to -29)
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2 Poly-Propylene vent pipe (PP) by Duravent and Centrotherm.
NOTE - Concentric terminations are the equivalent of 5’ and should be considered when measuring pipe length.
NOTE - Maximum unisulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See Figure 30.
2 in 11 9 19 17 28 25 27 24 n/a n/a
2-1/2 in 7 n/a 14 n/a 21 n/a 20 n/a n/a n/a
3 in n/a n/a 9 9 16 16 14 14 23 23
2 in 6 4 12 10 19 16 18 15 n/a n/a
2-1/2 in n/a n/a 7 n/a 13 n/a 12 n/a n/a n/a
3 in n/a n/a n/a n/a 8 8 7 7 13 13
Unit Input Size
2
PP
PVC
2
PP
PVC
2
PP
PVC
2
PP
Conditioned
Space
Conditioned
Space
Figure 30
Pipe Insulation
Unconditioned
Space
Exhaust
Pipe
Intake
Pipe
Page 25
Page 26
VENT TERMINATION CLEARANCES
FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non-mechanical air
pliance
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* 12”
* Equal to or greater than soffit depth.
*
* 3 feet (.9m)
* 12”
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
7 feet (2.1m)†
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner * No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*12 inches (305mm)‡
**
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the lation instructions.”
Figure 31
Page 26
Page 27
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
pliances > 10,000 Btuh (3kw) and <50,000
pliances > 50,000 Btuh (15kw)
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
3 feet (.9m) within a height 15 feet (4.5m)
Clearance to non-mechanical air
pliance
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
above the meter / regulator assembly
6 inches (152mm) for appliances <10,000
pliances > 10,000 Btuh (3kw) and <50,000
pliances > 50,000 Btuh (15kw)
3 feet (.9m) above if within 10 feet
* 12”
*
*
3 feet (.9m)
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)‡
H
B
Fixed
Closed
A
J
AREA WHERE TERMINAL IS NOT PERMITTED
1
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
I
M
Canadian Installations
K
2
* 12”
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions.”
Figure 32
Page 27
Page 28
Details of Intake and Exhaust Piping Terminations for
Exiting Exhaust and Intake Vent
Direct Vent Installations
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and ue gases are discharged to outdoors. NOTE - Flue gas may be slightly acidic and may adverse-
ly affect some building materials. If any vent termination is used and the ue gasses may impinge on the building material, a corrosion-resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommend­ed. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See Figure 41.
Intake and exhaust pipes may be routed either horizontal­ly through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figure 33 through Figure 40 show typical terminations.
1 - Intake and exhaust terminations are not required
to be in the same pressure zone. You may exit the intake on one side of the structure and the exhaust on another side (Figure 34). You may exit the exhaust out the roof and the intake out the side of the structure (Figure 35).
2 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to illustrations). Maximum separation is 3” (76MM) on roof terminations and 6” (152MM) on side wall terminations.
NOTE - When venting in different pressure zones, the maximum separation requirement of intake and exhaust pipe DOES NOT apply.
3 - On roof terminations, the intake piping should
terminate straight down using two 90° elbows (See Figure 33).
4 - Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.
NOTE - Care must be taken to avoid recirculation of exhaust back into intake pipe.
5 - On eld-supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches (305MM) for 2” PVC and 20 inches (508MM) for 3” (76MM) PVC beyond the outside wall. Intake piping should be as short as possible. See Figure 41.
6 - On eld-supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8” and a minimum distance of 6” with a termination elbow. See Figure 41.
7 - If intake and exhaust piping must be run up a
side wall to position above snow accumulation or other obstructions, piping must be supported. At least one bracket must be used within 6” from the top of the elbow and then every 24” (610mm) as shown in Figure 41, to prevent any movement in
any direction. When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated with pipe sized per table 8.The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.
Inches(mm)
8” (203mm) MIN
12” (305mm) ABOVE
AVERAGE SNOW ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
3”(76mm) MAX.
(15F75 or 44J41)
UNCONDITIONED
ATTIC SPACE
Figure 33
Exiting Exhaust and Intake Vent
(different pressure zone)
Exhaust
Pipe
Furnace
Inlet Air (Minimum 12 in. 305 MM) above
grade or snow
accumulation
Figure 34
(different pressure zone)
Roof T
erminated
Exhaust Pipe
Inlet Air
Furnace
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
Figure 35
Page 28
Page 29
TABLE 8
41W92 or 41W93 (Canada)
(30G28 or 81J20)
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL296UHV
MODEL
*045 and 070 1-1/2” (38MM)
*090 2” (51MM)
110 2” (51MM)
135 2” (51MM)
*EL296UHV-045, -070 and -090 units with the ush mount termination
must use the 1-1/2”accelerator supplied with the kit.
Termination
Pipe Size
8 - A multiple furnace installation may use a group
of up to four terminations assembled together horizontally, as shown in Figure 39.
FIELD-PROVIDED
QUIRED TO ADAPT
LARGER VENT PIPE
SIZE TO TERMINATION.
EXHAUST
AIR
INTAKE
AIR
OUTSIDE
WALL
CLAMP
(Not Furnished)
INTAKE
AIR
INTAKE
AIR
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
EXHAUST
AIR
12” (305mm) Min.
above grade or
cumulation.
GRADE
2” EXTENSION FOR 2” PVC PIPE1” EXTENSION FOR 3” PVC PIPE
4''
FURNACE
INTAKE
PIPE
FLAT SIDE
1-1/2” ACCELERATOR
FLUSH-MOUNT SIDE WALL TERMINATION KIT
51W11 (US) or 51W12 (Canada)
Figure 36
12” (305mm)
Minimum
Above Average
Snow
Accumulation
INTAKE
FURNACE
EXHAUST
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLASHING
(Not Furnished)
Figure 38
EXHAUST
VENT
5”
(127mm)
INTAKE
AIR
18” MAX.
(457mm)
EXHAUST VENT
Inches (mm)
INTAKE
AIR
optional intake elbow
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
12”
(305mm)
5-1/2”
(140mm)
Front View
12” (305mm) Min.
above grade or
cumulation.
Figure 39
DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field−installed to support
CLAMP
the weight of the termination kit.)
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
Figure 37
Page 29
3” - 8”
8” - 12”
(203mm - 305mm)
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
*SIZE TERMINATION
PIPE PER TABLE 7.
NOTE - Do tical discharge through an existing unused chimney or stack is required, insert piping inside trated. In any exterior portion of chimney, the exhaust vent must be insulated.
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE TO FORM
SEAL
(76mm-
203mm)
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8”
(76mm-
203mm)
ALTERNATE
INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
Figure 40
Page 30
NOTE − FIELD−PROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
* WALL
SUPPORT
C1
B
2
B
2
FIELD FABRICATED WALL TERMINATION
REDUCER MAY BE
TO TERMINATION
C1
A
E
D
B
STRAIGHT
APPPLICATION
A
Intake Elbow
D
B
EXTENDED
APPLICATION
C2
C2
D
B
A
E
D
B
A
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal
separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
distance from top of each
pipe (intake/exhaust)
See maximum allowable venting tables for venting lengths with this arrangement.
* Use wall support every 24” (610 mm). Use two wall supports if extension is greater than
24” (610 mm) but less than 48” (1219 mm). NOTE − One wall support must be within 6” (152 mm) from top of each pipe (intake and exhaust) to prevent movement in any direction.
ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)
D
B
Exhaust
D
1
C
A
D
E
12”
C
A
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration. In horizontal tee applications there must be be a minimum of 3 ft away from covered patios or any living ares and
cannot be within 3 ft of a window. Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
Intake Elbow
1
C
A
E
B
2
A
3
D
1
12”
C
A− Clearance above
grade or average snow
accumulation
B− Horizontal
separation between
intake and exhaust
C− Minimum from
end of exhaust to
inlet of intake
D− Exhaust pipe length
E− Wall support distance
from top of each pipe
(intake/exhaust)
Front View of
Intake and Exhaust
Intake
Exhaust
Figure 41
2” (51mm)
Vent Pipe
12” (305 mm)
12” (305 mm)
6” (152 mm)
2” (51MM)
Vent Pipe
12” (305 mm) Min.12” (305 mm) Min.
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 16” (405 mm) Max.
6” (152 mm) Max.
3” (76mm)
Vent Pipe
12” (305 mm)
6” (152 mm)6” (152 mm)
8” (203 mm)8” (203 mm)
6” (152 mm)6” (152 mm)
20” (508 mm)
6” (152 mm)
3” (76MM)
Vent Pipe
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 20” (508 mm) Max.
6” (152 mm) Max.
Page 30
Page 31
Details of Exhaust Piping Terminations for Non-Direct Vent Applications
Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figure 42 and Figure 43 show typical termi­nations.
1 - Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed
in table 8.The specied pipe size ensures proper
velocity required to move the exhaust gases away from the building.
2 - On eld supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches (305MM) for 2” PVC and 20 inches (508MM) for 3” (76MM) PVC beyond the outside wall.
DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
3” - 8”
(203mm - 305mm)
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
*SIZE TERMINATION
PIPE PER TABLE 7.
8” - 12”
INSULATION (optional)
INSULATE TO FORM
SEAL
INTAKE PIPE
SHEET
METAL TOP
PLATE
(76mm­203mm)
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8” (76mm­203mm)
ALTERNATE
INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
12” (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
UNCONDITIONED
ATTIC SPACE
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
Figure 42
3 - If exhaust piping must be run up a side wall
to position above snow accumulation or other obstructions, piping must be supported every 24 inches (610MM). When exhaust piping must be run up an outside wall, any reduction in exhaust pipe
size must be done after the nal elbow.
4 - Distance between exhaust pipe terminations on
multiple furnaces must meet local codes.
Crawl Space and Extended Horizontal Venting
NOTE - Do tical discharge through an existing unused chimney or stack is required, insert piping inside trated. In any exterior portion of chimney, the exhaust vent must be insulated.
Figure 43
Venting In A Crawl Space
Basement Floor
Lennox provides kit 51W18 (USA) and kit 15Z70 (Cana-
da) to install 2” or 3” PVC exhaust piping through the oor
joists and into the the crawl space. See Figure 44. This kit can also be used as a supplemental drain for in-
stallations with condensate run back in the vent pipe (ie. long horizontal runs, unconditioned spaces, etc.).
KIT 51W18
(USA)
KIT 15Z70
(CANADA)
Figure 44
Page 31
Page 32
Condensate Piping
This unit is designed for either right- or left-side exit of
condensate piping in upow applications. In horizontal
applications, the condensate trap must extend below the unit. An 8” service clearance is required for the conden­sate trap. Refer to Figure 45 and Figure 47 for condensate trap locations. Figure 53 shows trap assembly using 1/2” PVC or 3/4” PVC.
NOTE - If necessary the condensate trap may be installed up to 5’ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.
1 - Determine which side condensate piping will exit
the unit, location of trap, eld-provided ttings and
length of PVC pipe required to reach available drain.
2 - Use a large at head screw driver or a 1/2” drive
socket extension and remove plug (Figure 45) from the cold end header box at the appropriate location on the side of the unit. Install provided 3/4 NPT
street elbow tting into cold end header box. Use Teon tape or appropriate pipe dope.
NOTE - Cold end header box drain plugs are facto­ry installed. Check the unused plug for tightness to prevent leakage.
3 - Install the cap over the clean out opening at the
base of the trap. Secure with clamp. See Figure 53.
4 - Install drain trap using appropriate PVC ttings,
glue all joints. Glue the provided drain trap as shown in Figure 53. Route the condensate line to an open drain. Condensate line must maintain a 1/4” downward slope from the furnace to the drain.
5 - Figure 48 and Figure 49 show the furnace and
evaporator coil using a separate drain. If necessary the condensate line from the furnace and evaporator coil can drain together. See Figure 50, Figure 51 and Figure 52. Upow furnace (Figure 51) - In upow
furnace applications the eld provided vent must
be a minimum 1” to a maximum 2” length above the condensate drain outlet connection. Any length
above 2” may result in a ooded heat exchanger
if the combined primary drain line were to become restricted. Horizontal furnace (Figure 52) - In
horizontal furnace applications the eld provided
vent must be a minimum 4” to a maximum 5” length above the condensate drain outlet connection.
Any length above 5” may result in a ooded heat
exchanger if the combined primary drain line were to become restricted.
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Trap
(same on
right side)
1-1/2 in.
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond condensate trap or trap must be re-located to avoid interference.
Figure 45
NOTE - In horizontal applications it is recommended to install a secondary drain pan underneath the unit and trap assembly.
NOTE - Appropriately sized tubing and barbed tting may be used for condensate drain. Attach to the drain on the trap using a hose clamp. See Figure 46.
Field Provided Drain Components
Elbow
Tubing
Hose Clamp
Figure 46
Rubber
Grommet
Plug
(same on left side)
Barbed Fitting
CAUTION
Do not use copper tubing or existing copper condensate lines for drain line.
Page 32
Page 33
6 - If unit will be started immediately upon completion
CONDENSATE TRAP LOCATIONS
minimum 1/4” per ft. toward trap
of installation, prime trap per procedure outlined in Unit Start-Up section.
(Unit shownin upflow position withremote trap)
FieldProvidedVent
Min.1” AboveCondensate
Drain
1”
2” Max.
Connection
Min.
Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, conden­sate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possi­ble, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in var­ious lengths; 6 ft. (1.8m) - kit no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft. (15.2m) - kit no. 26K70.
Furnace With Evaporator Coil Using A Separate Drain
*5’ max.
PVCPipe Only
Trap CanBeInstalleda
Maximum 5’ From Furnac
e
To Drain
*Piping from furnace must slope down a
Figure 47
Furnace with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
(Trap at coil is optional)
Field Provided Vent (1” min. 2” max. above condensate connection)
Condensate
Drain
Connection
Evaporator drain
line required
Figure 48
Evaporator
Coil
Drain
Pan
(Trap at coil is optional)
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
Field Provided Vent (4” min. to 5” max. above condensate connection)
4”min
5”max
5’ max.
PVC Pipe Only
Condensate
DrainConnection
.
Figure 49
Page 33
Page 34
IMPORTANT
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in order for the furnace pressure switch to operate properly.
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
HorizontalFurnace4 ” Min.to5” Max.above
condensatedrain connection)
FurnaceCondensate
Connection
Drain
Optional
Furnace with Evaporator Coil Using a Common Drain
(Trap at coil is optional)
(1” min.to2” Max.above
condensatedrain connection)
Condensate
Connection
Drain
Figure 51
Evaporator drain
line required
Drain
Pan
Figure 50
Furnace with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Evaporator
Coil
(Trap at coil is optional)
Piping from furnace and evaporator coil must slope
down a minimum 1/4” per ft. toward trap
Condensate Drain
Connection
5’ max.
PVC Pipe Only
Figure 52
4”min
5”max
(4” min.to5” Max.above
condensatedrain
connection)
Page 34
Page 35
Optional Condensate Drain Connection
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow 3/4 inch PVC (not furnished)
Condensate Drain
Connection In Unit
90° Street Elbow 3/4 inch PVC ( furnished)
To
Trap
Optional DrainPipingFrom Trap
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain Assembly for 3/4 inch Drain Pipe
Drain
1(25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
Elbow 3/4 inch PVC
90°
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
V
ent
5 Feet
Maximum
3/4 inch PVC Pipe
(Not Furnished)
Coupling 3/4 inch slip X slip
Drain Trap
Assembly
(Furnished)
Condensate Drain
Connection In Unit
(Not Furnished)
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
DrainTrapAssembly
(Furnished)
7
(178)
Drain Trap Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
T
o
Coupling 3/4 inch slip X slip
Drain
DrainTrap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
(Not Furnished)
Vent
1/2 inch
Condensate Drain
Connection In Unit
To
Drain
Figure 53
DrainTr ap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
Vent
3/4 inch
Condensate Drain
Connection In Unit
To
Drain
Page 35
Page 36
Gas Piping
Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
6 - In some localities, codes may require installation of
a manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type.
CAUTION
If a exible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace
cabinet. The exible connector can then be added
between the black iron pipe and the gas supply line.
WARNING
Do not over torque (800 in-lbs) or under torque (350 in­lbs) when attaching the gas piping to the gas valve.
1 - Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into the gas valve from the side of the valve as shown
in gure 55. Connect the gas supply piping into the
gas valve. The maximum torque is 800 in lbs and minimum torque is 350 in lbs when when attaching the gas piping to the gas valve.
2 - When connecting gas supply, factors such as length
of run, number of ttings and furnace rating must
be considered to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical applications.
NOTE - Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.
3 - Gas piping must not run in or through air ducts,
clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See Figure 55 and Figure 56.
4 - Piping should be sloped 1/4 inch per 15 feet (6mm
per 5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection. See Figure 62.
IMPORTANT
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and eld-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
Never use an open ame to test for gas leaks. Check all
connections using a commercially available soap solution
made specically for leak detection.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8” N.P. T. PLUGGED TAP
Figure 54
CAP
FURNACE
ISOLATE
GAS VALV E
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. See Figure 54. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use
an open ame to test for gas leaks. Check all connections
using a commercially available soap solution made
specically for leak detection. Some soaps used for leak
detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.
Page 36
Page 37
Upflow Application
Left Side Piping
(Standard)
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
1/2” NPT
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 55
Horizontal Applications
Possible Gas Piping Configurations
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Upflow Application
Right Side Piping
(Alternate)
Horizontal Application
Left-Side Air Discharge
1/2” NPT
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
DRIP LEG
Horizontal Application
Right-Side Air Discharge
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 56
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Page 37
Page 38
TABLE 9
Gas Pipe Capacity - ft3/hr (m3/hr)
Nominal
Iron Pipe
Size Inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
Internal
Diameter
inches
(mm)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
10
(3.048)
172
(4.87)
360
(10.19)
678
(19.19)
1350
(38.22)
2090
(59.18)
4020
(113.83)
6400
(181.22)
11300
(319.98)
20
(6.096)
118
(3.34)
247
(7.000)
466
(13.19)
957
(27.09)
1430
(40.49)
2760
(78.15)
4400
(124.59)
7780
(220.30)
30
(9,144)
95
(2.69)
199
(5.63)
374
(10.59)
768
(22.25)
1150
(32.56)
2220
(62.86)
3530
(99.95)
6250
(176.98)
40
(12,192)
81
(2.29)
170
(4.81)
320
(9.06)
657
(18.60)
985
(27.89)
1900
(53.80)
3020
(85.51)
5350
(151.49)
Length of Pipe - feet (m)
50
(15.240)
72
(2.03)
151
(4.23)
284
(8.04)
583
(16.50)
873
(24.72)
1680
(47.57)
2680
(75.88)
4740
(134.22)
60
(18.288)
65
(1.84)
137
(3.87)
257
(7.27)
528
(14.95)
791
(22.39)
1520
(43.04)
2480
(70.22)
4290
(121.47)
70
(21.336)
60
(1.69)
126
(3.56)
237
(6.71)
486
(13.76)
728
(20.61)
1400
(39.64)
2230
(63.14)
3950
(111.85)
80
(24.384)
56
(1.58)
117
(3.31)
220
(6.23)
452
(12.79)
677
(19.17)
1300
(36.81)
2080
(58.89)
3670
(103.92)
NOTE - Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specic gravity gas.
90
(27.432)
52
(1.47)
110
(3.11)
207
(5.86)
424
(12.00)
635
(17.98)
1220
(34.55)
1950
(55.22)
3450
(97.69)
100
(30,480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
3260
(92.31)
Page 38
Page 39
Electrical
INTERIOR MAKE-UP BOX INSTALLATION
WARNING
Electrostatic discharge can affect electronic components. Take care during unit installation and service to
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product may
result in a re, causing property damage, severe injury
or death. Use copper wire only with this product.
The unit is equipped with a eld make-up box on the left
hand side of the cabinet. The make-up box may be moved to the right side of the furnace to facilitate installation. If the make-up box is moved to the right side, clip the wire ties that bundle the wires together. The excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harness to protect it from damage.
MAKE-UP
BOX
Right Side
The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.
CAUTION
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit
breaker(s) per Product Specications bulletin (EHB) and
unit rating plate.
NOTE - Unit nameplate states maximum current draw. Maximum over-current protection allowed is shown in ta­ble 10.
TABLE 10
EL296UHV Maximum Over-Current
045V36B, 070V36B, 090V36C, 090V48C,
110V48C
090V60C, 110V60C,
135V60D
Holes are on both sides of the furnace cabinet to facilitate wiring.
Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing. Before connecting the thermostat or the power wiring, check to make sure the wires will be long enough for ser­vicing at a later date. Remove the blower access panel to check the length of the wire.
Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the eld wiring di­agrams shown in table 11 and Figure 60. Use 18-gauge wire or larger that is suitable for Class II rating for thermo­stat connections.
Electrically ground the unit according to local codes or, in the absence of local codes, according to the current Na­tional Electric Code (ANSI/NFPA No. 70). A green ground
wire is provided in the eld make-up box. NOTE - The
EL296UHV furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
One line voltage “ACC” 1/4” spade terminal is provided on the furnace integrated control. Any electronic air cleaner or other accessory rated up to one amp can be connect­ed to this terminal with the neutral leg of the circuit being connected to the one of the provided neutral terminals. See Figure 61 for control conguration. This terminal is energized when the indoor blower is operating.
15
20
Figure 57
Refer to Figure 60 for unit schematic and eld wiring. See Figure 58 and Figure 59 for icomfort Wi-Fi® thermostat wiring in communicating applications. Table 11 shows DIP switch and on-board link settings for non-communicating thermostat applications. Typical wiring schematic is shown in Figure 60.
Page 39
Page 40
An unpowered, normally open (dry) set of contacts with
a 1/4” spade terminal “HUM” are provided for humidier
connections and may be connected to 24V or 120V. Any
humidier rated up to one amp can be connected to these terminals. In 120V humidier applications the neutral leg of
the circuit can be connected to one of the provided neutral terminals. This terminal is energized in the heating mode.
Install the room thermostat according to the instructions
provided with the thermostat. See table 11 for eld wiring
connections in varying applications. If the furnace is being matched with a heat pump, refer to the instruction pack­aged with the dual fuel thermostat.
Thermostat Selection
CAUTION
Field wiring for both communicating and non­communicating applications is illustrated in diagrams, which begin on the next page.
Non-Communicating
In non-communicating applications the EL296UHV is designed to operate in a SINGLE-STAGE mode or TWOSTAGE mode using a conventional thermostat.
For optimal performance in non-communicating applica­tions, Lennox recommends use of a ComfortSense® 7000 high quality electronic digital thermostat or any other with adjustable settings for 1st stage / 2nd stage on / off differ­entials and adjustable stage timers.
Communicating
In communicating applications the icomfort Wi-Fi® ther­mostat must be used. Refer to the instructions provided with the thermostat for installation, set-up and operation. In communicating system all unused thermostat wire in the wire bundle needs to be terminated inside and out. The extra wires can terminate on the ‘C” terminal of the icomfort communication terminal strip. (RSBus). Using an additional wire come off ”C” terminal and wire nut all the extra wires together. Termination on the outdoor control must match the indoor control.
Indoor Blower Speeds
Non-Communicating
When the thermostat is set to “FAN ON,” the indoor blower
will run continuously at a eld selectable percentage of
the second-stage cooling speed when there is no cooling or heating demand. The factory default setting is 38% of cool speed. When the EL296UHV is running in the heat­ing mode,the indoor blower will run on the heating speed designated by the positions of DIP switches 11, 12 and 13. When there is a cooling demand, the indoor blower will run on the cooling speed designated by the positions of DIP switches 5 and 6. First stage cooling will run at 70% cool speed.
Communicating
NOTE - When the EL296UHV is used with icomfort Wi­F® thermostat, proper indoor blower speed selections are made by the communicating thermostat.
When the thermostat is set to “FAN ON,” the indoor blower
will run at setting determined during system conguration.
When there is a heating demand the fan will run on heat-
ing speeds for ring rate. When there is a cooling demand, the fan will run on the rst stage and second stage cooling
speed set using the icomfort WiFi® thermostat in the in­staller setup mode. The factory default is based upon 400 CFM a ton.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when specifying a generator for use with this equipment:
• The furnace requires 120 volts (Range: 102 volts to 132 volts)
• The furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz)
• The furnace integrated control requires both correct polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or tempo­rary power
• Generator should have a wave form distortion of less than 5% THD (total harmonic distortion)
Page 40
Page 41
icomfort Wi-Fi
®
Thermostat with Furnace and
Non-Communicating Outdoor Unit
icomfort®­ENABLED FURNACE
icomfort Wi-Fi®
THERMOSTAT
NON-COMMUNICATING
OUTDOOR AIR
CONDITIONING UNIT -
1 OR 2 STAGE
icomfort Wi-Fi® Thermostat icomfort
®
-Enabled Indoor Furnace
Non-Communicating Outdoor Air Conditioner
OPTIONAL OUTDOOR
AIR SENSOR
OPTIONAL
DISCHARGE
AIR SENSOR
icomfort Wi-Fi® Thermostat with Furnace and
icomfort
®
-ENABLED Outdoor Unit
icomfort Wi-Fi® Thermostat icomfort
®
-Enabled Indoor Furnace
icomfort
®
-Enabled Outdoor Air Conditioner or Heat Pump
icomfort®­ENABLED FURNACE
icomfort
®
- ENABLED
OUTDOOR AIR CONDITIONING
OR HEAT PUMP UNIT
OPTIONAL OUTDOOR
AIR SENSOR
OPTIONAL
DISCHARGE
AIR SENSOR
CLIP ON-BOARD LINK W915 (Y1 TO Y2) FOR
TWO-STAGE OPERATION
icomfort Wi-Fi® THERMOSTAT
Indoor Unit Controller
Outdoor Unit
Icomfort Wi-Fi
®
thermostat
Single wire to terminal C
Single wire to terminal C
Unused wires
Unused wires
Communicating systems using the Icomfort Wi-Fi
®
mostat wires between the thermostat and the furnace/air handler control and four wires between mostat cable with more than four wires is used, the extra wires must be properly connected to avoid electrical noise. The wires must not be left disconnected.
Use wire nuts to bundle the four unused wires at each end of the cable. A single wire should then be connected to the indoor unit end of the wire bundle and attached to the “C” terminals as shown in the diagram above.
Figure 58
Page 41
Page 42
Optional Accessories for use with any icomfort Touch
NOTE: Icomfort Wi-Fi® THERMOSTAT SENSES HUMIDITY & CONTROLS HUM CONTACTS TO CYCLE HUMIDIFIER BASED
QUIRED.
TIONS. BUILT INTO ALL icomfort by Lennox OUTDOOR UNITS).
®
System
120V CONNECTIONS
“HUM” CONTACT IS CLOSED ANYTIME HUMIDITY DEMAND IS PRESENT
icomfort® ENABLED
FURNACE
sor (Required for
even heat)
Icomfort Wi-Fi THERMOSTAT
®
RSBus
Maximum total
tions on the RSBus is limited to 1500ft.
Wire gauge of RSBus wire is 18.
®
icomfort ENABLED OUTDOOR AIR CONDITIONING OR HEAT
PUMP UNIT
ENABLED
®
FURNACE
icomfort
(POWER COMPANY INTERRUPTION SYSTEMS ARE WIRED SAME AS OVERFLOW SWITCH)
HEPA BYPASS FILTER X2680 HEPA INTERLOCK KIT
NOTE: 24V UV LIGHT APPLICATIONS
In an icomfort by Lennox neither furnace nor air handler transformer will have adequate VA to power 24V UV light applications. An additional transformer for UV light applications is required.
system,
24V HUMIDIFIER CONNECTIONS
CONVENTIONAL NON­COMMUNICATING SYSTEM
COMMUNICATING SYSTEM
*24V IN jumper not used in non­communicating configuration
icomfort ENABLED
FURNACE
Icomfort Wi-Fi THERMOSTAT
HVAC EQUIPMENT
®
DEHUMIDIFIER CONTROL
Rf WGhGsCf
DH
HVAC EQUIP
CS 7000 THERMOSTAT
*24V IN JUMPER
ENABLED
®
FURNACE
icomfort
LVCS VENTILATION CONTROL SYSTEM
ENABLED
®
FURNACE
icomfort
TOR COMMON WIRE THROUGH CURRENT LOOP.
SEE HEPA INTERLOCK KIT FOR INSTALLATION DETAILS
SEE LVCS VENTILATION INSTRUCTIONS FOR DAMPER & SENSOR WIRING
Figure 59
Page 42
STANDARD 1 OR 2 STAGE
AC OR HP UNIT
2 STAGE FURNACE
CUT R-DS W914
NON-COMMUNICATING SYSTEM WIRING
DS
R
COMMUNICATING SYSTEM WIRING
Page 43
Thermostat
* Not required on all units.
1 Heat / 1 Cool
NOTE - Use DIP switch 2 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
DIP Switch Settings and On-Board Links
DIP Switch 1
Thermostat
Heating
Stages
ON
On Board Links Must Be Cut To Select
System Options
DO NOT CUT ANY ON-BOARD LINKS
Wiring Connections
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
*
UNIT
1 Heat / 2 Cool
NOTE - Use DIP switch 2 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
1 Heat / 2 Cool with t'stat with humidity control
NOTE - Use DIP switch 2 to set second-stage heat ON delay. OFF-7 minutes. ON-12 minutes.
ON
ON
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
S1
T'STAT
S1
T'STAT
FURNACE
TERM. STRIP
FURNACE
TERM. STRIP
*
o
OUTDOOR
UNIT
OUTDOOR
UNIT
*
Page 43
Page 44
DIP Switch 1
Thermostat
Thermostat
Heating
Stages
2 Heat / 2 Cool OFF
DIP Switch Settings and On-Board Links
On Board Links Must Be Cut To Select
System Options
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
Wiring Connections
S1
T'STAT
FURNACE
TERM. STRIP
OUTDOOR
*
UNIT
2 Heat / 2 Cool
OFF with t'stat with humidity control
2 Heat / 1 Cool
OFF with t'stat with humidity control
2 Heat / 1 Cool OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
S1
T'STAT
S1
T'STAT
S1
T'STAT
FURNACE
TERM. STRIP
FURNACE
TERM. STRIP
FURNACE
TERM. STRIP
o
o
OUTDOOR
UNIT
*
OUTDOOR
UNIT
*
OUTDOOR
UNIT
* Not required on all units.
DO NOT CUT ANY ON-BOARD LINKS
*
Page 44
Page 45
Thermostat
Dual Fuel Single Stage Heat Pump
ComfortSense thermostat w/
DIP Switch Settings and On-Board Links
DIP Switch 1
Thermostat
Heating
Stages
OFF
On Board Links Must Be Cut To Select
System Options
CUT ON-BOARD LINK
W951 HEAT
PUMP
T'STAT
H
Wiring Connections
FURNACE
TERM. STRIP
HEAT PUMP
67M41*
bilities Capable of 2 stage gas heat control
Dual Fuel Two Stage Heat Pump
ComfortSense thermostat w/
bilities Capable of 2 stage gas heat control
OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W951 HEAT PUMP
L
Y2
D
B
T
T
T'STAT
H
L
Y2
D
B
Y2
FURNACE
TERM. STRIP
67M41*
L
Y
outdoor
sensor
HEAT PUMP
L
Y2
out blue
T
T
outdoor sensor
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the furnace integrated control.
Page 45
Page 46
Thermostat
Dual Fuel Single Stage Heat Pump
ComfortSense thermostat w/
DIP Switch Settings and On-Board Links
DIP Switch 1
Thermostat
Heating
Stages
OFF
On Board Links Must Be Cut To Select
System Options
CUT ON-BOARD LINK
W951 HEAT
PUMP
Wiring Connections
T'STAT
H
FURNACE
TERM. STRIP
HEAT PUMP
67M41*
bilities Capable of 2 stage gas heat
midification control
Dual Fuel Two Stage Heat Pump
ComfortSense thermostat w/
bilities Capable of 2 stage gas heat
midification
OFF
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W951 HEAT
PUMP
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
L
Y2
D
B
T
T
T'STAT
H
L
Y2
D
B
Y2
FURNACE
TERM. STRIP
Y2
67M41*
L
Y
outdoor
sensor
HEAT PUMP
L
Y2
out blue
T
T
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the furnace integrated control.
Page 46
outdoor
sensor
Page 47
EL296UHV Schematic Wiring Diagram
Figure 60
Page 47
Page 48
Integrated Control
ACC
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
COMMUNICATING
OUTDOOR
EQUIPMENT
TB84
COMMUNICATING
INDOOR
THERMOSTAT
HUM
LINE 1
I +I -CRI +I -
R
C
W1 W2 GY2Y1
NON-COMMUNICATINGNG
24V TERMINALS
CC
RDHLODS
HS/ CAI
INDOOR
BLOWER
CONNECTOR
12 PIN LOW
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O HEAT PUMP
W914 R TO DS
DEHUM OR
HARMONY
NEUTRAL
VOLTAGE
RS-BUS LINK (TB82, future use)
I+ = DATA HIGH CONNECTION I - = DATA LOW CONNECTION
RS-BUS OUTDOOR (TB83)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
RS-BUS INDOOR (TB84)
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
REVERSING VALV E
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
THERMOSTAT ONLY
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
Figure 61
Page 48
Page 49
Integrated Control DIP Switch Settings -
Conventional Thermostat (non-communicating)
EL296UHV units are equipped with a two-stage, variable speed integrated control. This control manages ignition timing, heating mode fan off delays and indoor blower speeds based on selections made using the control dip switches and jumpers. The control includes an internal watchguard feature which automatically resets the ignition control when it has been locked out. After one hour of con­tinuous thermostat demand for heat, the watchguard will break and remake thermostat demand to the furnace and automatically reset the control to relight the furnace.
Note: All icomfort settings are set at the icomfort Wi-Fi® thermostat. See icomfort installation instruction. In icom­fort communication system all DIP switch and clippable link settings are ignored. For conventional thermostats proceed with DIP switch and clippable link settings as out­lined in the following.
Heating Operation DIP Switch Settings Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular appli­cation. The DIP switch is factory-positioned for use with a twostage thermostat. If a single-stage thermostat is to be used, the DIP switch must be repositioned.
a. Select “OFF” for two-stage heating operation controlled by a
two-stage heating thermostat (factory setting);
b. Select “ON” for two-stage heating operation controlled by
a single-stage heating thermostat. This setting provides a timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with Single-
Stage Thermostat Only) -- This switch is used to deter­mine the second stage on delay when a single-stage ther­mostat is being used. The switch is factory-set in the OFF
position, which provides a 7-minute delay before second­stage heat is initiated. If the switch is toggled to the ON position, it will provide a 12-minute delay before second­stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE­stage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on delay of 30 seconds is not adjustable. The blower-off de­lay (time that the blower operates after the heating de-
mand has been satised) can be adjusted by moving
switches 3 and 4 on the integrated control. The unit is shipped from the factory with a blower-off delay of 90 sec­onds. The blower off delay affects comfort and is adjust­able to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de-en­ergized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatures.Table 12 provides the blower off timings that will result from different switch settings.
TABLE 11
Blower Off Delay Switch Settings
Blower Off Delay
Seconds
60 On Off
90 (factory) Off Off
120 Off On
180 On On
Switch 3 Switch 4
Indoor Blower Operation DIP Switch Settings Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches po­sitioned for high speed (4) indoor blower motor operation during the cooling mode. Table 13 provides the cooling mode blower speeds that will result from different switch settings. Switches 5 and 6 set the blower cfm for second­stage cool. The integrated control automatically ramps
down to 70% of the second-stage cfm for rst-stage cfm.
Refer to tables for corresponding cfm values. See Product
Specications for more detailed blower cfm tables.
TABLE 12
Cooling Mode Blower Speeds
Speed Switch 5 Switch 6
Low On On
Medium Low Off On
Medium High On Off
High (factory) Off Off
Switches 7 and 8 -- Cooling Blower Speed Adjustment
-- The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or
-10% to better suit the application. Table 14 below pro­vides blower speed adjustments that will result from dif­ferent switch settings. Refer to tables for corresponding
cfm values. See Product Specications for more detailed
blower cfm tables.
TABLE 13
Cooling Blower Speed Adjustment
Adjustment Switch 7 Switch 8
+10% (approx) On Off
Factory Default Off Off
-10% (approx) Off On
Switches 9 and 10 -- Cooling Mode Blower Speed
Ramping -- Blower speed ramping may be used to en-
hance dehumidication performance. The switches are
factory set at option A which has the greatest effect on dehumidication performance. Table 15 provides the cool­ing mode blower speed ramping options that will result from different switch settings. The cooling mode blower mode blower speed ramping options are detailed on the
next page.
Page 49
Page 50
NOTE - The off portion of the selected ramp prole also
OFF
applies during heat pump operation in dual fuel applica­tions.
TABLE 14
Cooling Mode Blower Speed Ramping
Ramping Switch 9 Switch 10
A (Factory) Off Off
B Off On
C On Off
D On On
Ramping Option A (Factory Selection)
• Motor runs at 50% for 30 seconds.
• Motor then runs at 82% for approximately 7-1/2 minutes.
If demand has not been satised after 7-1/2 min-
utes, motor runs at 100% until demand is satised.
• Once demand is met, motor runs at 50% for 30 seconds then ramps down to stop.
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COMPRESSOR DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
• Motor runs at 82% for approximately 7-1/2 minutes.
If demand has not been satised after 7-1/2 min­utes, motor runs at 100% until demand is satised.
• Once demand is met, motor ramps down to stop.
Ramping Option D
Motor runs at 100% until demand is satised.
• Once demand is met, motor ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
OFFOFF
Switches 11, 12 and 13 -- Heating Mode Blower Speed The switches are factory set to the OFF position which provides factory default heat speed. Refer to table 16 for switches 11, 12 and 13 that provided the corresponding increases or decrease to both high and low heat demand.
TABLE 15
Heating Mode Blower Speeds
Heat Speed Switch 11 Switch 12 Switch 13
Increase 24% On On On
Increase 18% On On Off
Increase 12% On Off On
Increae 6% On Off Off
Factory
Off Off Off
Default
Decrease 6% Off Off On
Decrease
Off On Off
12%
Decrease
Off On On
18%
Switches 14 and 15 -- Continuous Blower Speed --
Table 17 provides continuous blower speed adjustments that will result from different switch settings.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
Ramping Option C
Motor runs at 100% until demand is satised.
• Once demand is met, motor runs at 100% for 45
seconds then ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
100% CFM
45 SEC.
OFF
OFF
Page 50
TABLE 16
Continuous Blower Speed
Coninuous Blower Speed Switch 14 Switch 15
28% of High Cool Speed Off On
38% of High Cool Speed
(Factory)
70% of High Cool Speed On Off
100% of High Cool Speed On On
Off Off
Page 51
Blower Data
EL296UH045XV36B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 915 1125
+18% 865 1085
+12% 805 1040
+6% 780 985
Factory Default 740 925
–6% 665 875
–12% 630 800
–18% 585 735
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 595 760 865 980 905 1075 1210 1370
Factory Default 540 660 785 890 815 980 1120 1255
485 600 695 790 720 885 1020 1135
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
EL296UH070XV36B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 1095 1220
+18% 1035 1170
+12% 985 1120
+6% 915 1055
Factory Default 850 995
–6% 835 915
–12% 755 845
–18% 695 810
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
+ 600 740 840 970 860 1060 1215 1365
Factory Default 555 665 770 855 810 960 1130 1265
500 600 680 790 705 840 1005 1140
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm.
Page 51
Page 52
Blower Data
EL296UH090XV36C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1215 1300
+18% 1140 1240
+12% 1100 1170
+6% 1020 111 5
Factory Default 965 1070
–6% 915 970
–12% 850 925
–18% 805 855
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 625 710 830 950 875 1040 1210 1360
Factory Default 565 670 760 860 800 945 1100 1245
520 610 685 785 720 840 970 111 5
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
EL296UH110XV48C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 1470 1605
+18% 1450 1495
+12% 1385 1445
+6% 1295 1385
Factory Default 1225 1305
–6% 1160 1225
–12% 1090 1150
–18% 1035 1070
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
+ 810 980 1085 1235 1100 1325 1530 1760
Factory Default 760 875 1010 1135 1025 1205 1405 1565
695 805 905 1040 920 1080 1260 1440
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm for EL296UH090XV60C and 380 cfm for EL296UH110XV48C.
Page 52
Page 53
Blower Data
EL296UH090XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1490 1985
+18% 1435 1915
+12% 1335 1805
+6% 1280 1645
Factory Default 1185 1625
–6% 1095 1530
–12% 990 1450
–18% 900 1345
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 1050 1270 1445 1620 1590 1815 2010 2195
Factory Default 975 1120 1295 1460 1460 1645 1845 2010
865 1010 1120 1290 1320 1500 1645 1860
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
EL296UH110XV48C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
Settings
+24% 1470 1605
+18% 1450 1495
+12% 1385 1445
+6% 1295 1385
Factory Default 1225 1305
–6% 1160 1225
–12% 1090 1150
–18% 1035 1070
COOLING
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
+ 810 980 1085 1235 1100 1325 1530 1760
Factory Default 760 875 1010 1135 1025 1205 1405 1565
695 805 905 1040 920 1080 1260 1440
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. for EL296UH090XV60C and 380 cfm for EL296UH110XV48C
Page 53
Page 54
Blower Data
EL296UH110XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1385 1965
+18% 1475 1880
+12% 1355 1790
+6% 1370 1725
Factory Default 1200 1630
–6% 1140 1550
–12% 1070 1460
–18% 980 1345
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 1060 1245 1345 1545 1560 1740 1930 2125
Factory Default 970 1145 1265 1395 1405 1565 1775 1945
885 1025 1110 1250 1270 1425 1610 1770
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm.
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
High
Page 54
Page 55
On-Board Links
Note: In icomfort systems with a conventional outdoor unit (non-communicating), the on-board clippable links must be set to properly congure the system.
WARNING
Carefully review all conguration information provided.
Failure to properly set DIP switches, jumpers and on­board links can result in improper operation!
Refer to table 18 for operation sequence in applications including EL296UHV, a thermostat which features humid­ity control and a single-speed outdoor unit. Table 19 gives the operation sequence in applications with a two-speed outdoor unit.
On-Board Link W951 Heat Pump (R to O)
On-board link W951 is a clippable connection between terminals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features
On-Board Link W914 Dehum or Harmony (R to DS)
On-Board Link W914 Dehum or Harmony (R to DS) On­board link W914, is a clippable connection between termi­nals R and DS on the integrated control. W914 must be cut when the furnace is installed with either the Harmony III zone control or a thermostat which features humidity control. If the link is left intact the PMW signal from the Harmony III control will be blocked and also lead to control damage
dual fuel use. If the link is left intact, terminal “O” will re­main energized eliminating the HEAT MODE in the heat pump.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board link W915 is a clippable connection between terminals Y1 and Y2 on the integrated control. W915 must be cut if two-stage cooling will be used. If the Y1 to Y2 link is not cut the outdoor unit will operate in second-stage cooling only.
TABLE 17
OPERATING SEQUENCE
EL296UHV, Non-Communicating Thermostat with Humidity Control Feature and Single-Speed Outdoor Unit
OPERATING SEQUENCE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
NO CALL FOR DEHUMIDIFICATION
Normal Operation 1 On On On Acceptable
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidication
call
PRECISION MODE (operates independent of a Y1 demand)
Normal Operation 1 On On On Acceptable
Dehumidication
Call
Dehumidication
Call Only
Dave Lennox ComfortSense® 7000 thermostat to use for this application - Y2081 4 heat / 2 cool
*Dehumidication blower speed is 70% of COOL speed for all units .
**In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
Step
2 On On On Demand 0 VAC High 70%
2 On On On Demand 0 VAC High 70%
1 On On On Demand 0 VAC High 70%
Jumpers at indoor unit with a single stage outdoor unit. With Condensing unit - Cut W914 (R to DS) on SureLight® control With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight® control
Thermostat Demand Relative Humidity
Y1 O G W1 Status D
24
VAC
24
VAC
24
VAC
Compre
ssor
High 100%
High 100%
High 100%
Blower
CFM
(cool)
Comments
Compressor and indoor blower follow thermostat demand
ComfortSense® 7500
thermostat energizes
Y1 and de-energizes
D on a call for de-
humidication
Dehumidication
mode begins when
humidity is greater
than set point
ComfortSense® 7500 thermostat will try to maintain room humidity setpoint by
allowing the room space to maintain
a cooler room
thermostat setpoint**
Page 55
Page 56
TABLE 18
OPERATING SEQUENCE
SL280UHV, Non-Communicating Thermostat with Humidity Control Feature and Two-Speed Outdoor Unit
OPERATING
SEQUENCE
System
Condition
Step
NO CALL FOR DEHUMIDIFICATION
Normal Operation
Y1
Normal Operation
Y2
1 On On On Acceptable
2 On On On On Acceptable
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidication
call
2 On On On On Demand
PRECISION MODE (operates independent of a Y1 demand)
Normal Operation 1 On On On Acceptable
Dehumidication
Call
Dehumidication
Call Only
2 On On On On Demand
1 On On On On Demand
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On On Acceptable
Dehumidication
Call
2 On On On On Demand
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidication
Call
Dehumidication
Call ONLY
2 On On On On Demand
1 On On On On Demand
Jumpers at indoor unit with a two stage outdoor unit
Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2)
With Condensing unit - Cut W914 (R to DS) on SureLight® control
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight® control
Dave Lennox ComfortSense® 7000 thermostat to use for this application - Y2081 4 heat / 2 cool
*Normal operation rst stage cooling blower speed is 70% COOL speed.
**Dehumidication blower speed is, reduced to 70% of COOL.
***In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
SYSTEM DEMAND SYSTEM RESPONSE
Thermostat Demand Relative Humidity
Y1 Y2 O G W1 W2 Status D
24
VAC
24
VAC
24
VAC
0
VAC
24
VAC
0
VAC
0
VAC
24
VAC
0
VAC
24
VAC
0
VAC
0
VAC
Compre
ssor
Low 70%
High 100%
Low 70%
High 70%
Low 70%
High 70%
High 70%
High 100%
High 70%
Low 70%
High 70%
High 70%
Blower
CFM
(cool)
Comments
Compressor and indoor blower follow thermostat demand
ComfortSense® 7500 thermostat energizes Y1 and de-energizes D on a
call for de-humidication
Dehumidication mode
begins when humidity is greater than set point
ComfortSense® 7500 thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint**
ComfortSense® 7500 thermostat energizes Y2 and de-energizes D on a
call for de-humidication
Dehumidication mode
begins when humidity is greater than set point
ComfortSense® 7500 thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint***
Page 56
Page 57
Unit Start Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been underwater.
A ood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in re or explosion. Immediately call a qualied service technician to inspect
the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or product or property damage. If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING the unit, smell all around the furnace
area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
The gas valve on the EL296UHV is equipped with a gas control switch (lever). Use only your hand to moveswitch. Never use tools. If the the switch will not move by hand, do not try to repair it. Force or attempted repair may result
in a re or explosion.
Placing the furnace into operation:
EL296UHV units are equipped with an automatic hot surface ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on these units.
Priming Condensate Trap
The condensate trap should be primed with water prior to start-up to ensure proper condensate drainage. Either
pour 10 . oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 - Follow the lighting instructions to place the unit into
operation. 2 - Set the thermostat to initiate a heating demand. 3 - Allow the burners to re for approximately 3 minutes. 4 - Adjust the thermostat to deactivate the heating
demand.
5 - Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again
allow the burners to re for approximately 3 minutes.
6 - Adjust the thermostat to deactivate the heating
demand and wait for the combustion air inducer to stop. At this point, the trap should be primed with
sufcient water to ensure proper condensate drain
operation.
WARNING
If you do not follow these instructions exactly, a re or
explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figure 62)
1 - STOP! Read the safety information at the beginning
of this section. 2 - Set the thermostat to the lowest setting. 3 - Turn off all electrical power to the unit. 4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to
light the burners by hand. 5 - Remove the access panel. 6 - Move gas valve switch to OFF. See gure 62. 7 - Wait ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step. 8 - Move gas valve switch to ON. See Figure 62.
WHITE RODGERS GAS VALVE
INLET PRESSURE POST
GAS VALV E SHOWN IN ON POSITION
9 - Replace the access panel. 10 - Turn on all electrical power to to the unit. 11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12 - If the appliance will not operate, follow the
instructions “Turning Off Gas to Unit” and call your
service technician or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting. 2 - Turn off all electrical power to the unit if service is to
be performed. 3 - Remove the access panel.
MANIFOLD
PRESSURE TAP
Figure 62
HIGH FIRE ADJUSTMENT
SCREW
(under cap)
Page 57
Page 58
4 - Move gas valve switch to OFF. 5 - Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat? 2 - Are access panels securely in place? 3 - Is the main disconnect switch closed? 4 - Is there a blown fuse or tripped breaker? 5 - Is the lter dirty or plugged? Dirty or plugged lters
will cause the limit control to shut the unit off. 6 - Is gas turned on at the meter? 7 - Is the manual main shut-off valve open? 8 - Is the internal manual shut-off valve open? 9 - Is the unit ignition system in lockout? If the unit
locks out again, inspect the unit for blockages.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air
inducer starts.
2 - Combustion air pressure switch proves blower
operation. Switch is factory set and requires no
adjustment. 3 - After a 15-second prepurge, the hot surface ignitor
energizes. 4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second trial for ignition
period begins.” 5 - Gas is ignited, ame sensor proves the ame, and
the combustion process continues. 6 - If ame is not detected after rst ignition trial,
the ignition control will repeat steps 3 and 4 four
more times before locking out the gas valve
(“WATCHGUARD” ame failure mode). The ignition
control will then automatically repeat steps 1 through
6 after 60 minutes. To interrupt the 60-minute
“WATCHGUARD” period, move thermostat from
“Heat” to “OFF” then back to “Heat”. Heating
sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 19
GAS METER CLOCKING CHART
Seconds for One Revolution
EL296
Unit
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
Natural-1000 btu/cu ft LP-2500 btu/cu ft
Natural LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
Furnace should operate at least 5 minutes before check­ing gas ow. Determine time in seconds for two revolu­tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 20. If manifold pressure matches table 22 and rate is incorrect, check gas orices for proper size and restric­tion. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas appliances connected to meter.
Supply Pressure Measurement
An inlet post located on the gas valve provides access to the supply pressure. See Figure 62. Back out the 3/32 hex screw one turn, connect a piece of 5/16 tubing and connect to a manometer to measure supply pressure. See table 22 for supply line pressure.
On multiple unit installations, each unit should be checked separately, with and without units operating. Supply pres­sure must fall within range listed in table 22.
Manifold Pressure Measurement
NOTE - Pressure test adapter kit (10L34) is available from Lennox to facilitate manifold pressure measurement.
A manifold pressure post located on the gas valve pro­vides access to the manifold pressure. See Figure 62. Back out the 3/32 hex screw one turn, connect a piece of 5/16 tubing and connect to a manometer to measure manifold pressure.
To correctly measure manifold pressure, the differential pressure between the positive gas manifold and the neg­ative burner box must be considered.
1 - Connect the test gauge positive side “+“ to manifold
pressure tap on gas valve as noted above.
2 - Tee into the gas valve regulator vent hose and
connect to test gauge negative “-”.
3 - Ignite unit on low re and let run for 5 minutes to
allow for steady state conditions.
4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table 22.
5 - If necessary, make adjustments. Figure 62 shows
location of high re and low re adjustment screws.
6 - Repeat steps 3, 4 and 5 on high re. See values in
table 22.
7 - Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Turn the supply and manifold 3/32” hex screws one revolution back into the gas valve.
8 - Start unit and perform leak check. Seal leaks if
found.
Page 58
Page 59
Proper Cumbustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas ow rate before checking com­bustion. Take combustion sample beyond the ue outlet
and compare to the tables below.
TABLE 20
EL296
Model
CO2% For Nat CO2% For L.P
Low Fire High Fire Low Fire High Fire
045 5.4 - 6.4 7.5 - 8.5 6.4 - 7.4 8.8 - 9.8
070 5.3 - 6.3 7.4 - 8.4 6.3 - 7.3 8.7 - 9.7
090 5.8 - 6.8 7.6 - 8.6 6.8 - 7.8 8.9 - 9.9
High Altitude
NOTE - In Canada, certication for installations at eleva­tions over 4500 feet (1372 m) is the jurisdiction of local authorities.
Units may be installed at altitudes up to 10,000 ft. above sea level. See table 22 for de-rate manifold values. Units
installed at altitude of 7501 - 10,000 feet require an orice
change. Units installed at altitude of 4501 - 10,000 feet require a pressure switch change which can be ordered separately. Table 23 lists conversion kit and pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory-set and re­quiresno adjustment.
110 6.1 - 7.1 8.0 - 9.0 7.1 - 8.1 9.3 - 10.3
135 6.1 - 7.1 7.8 - 8.8 7.1 - 8.2 9.1 - 10.1
The maximum carbon monoxide reading should not exceed 100ppm.
TABLE 21
Manifold and Supply Line Pressure 0-10,000ft.
Manifold Pressure in. wg. Supply Line
Unit Gas
Natuarl 1.7 3.5 1.6 3.3 1.5 3.2 1.5 3.1 1.7 3.5 4.5 13.0
All
Sizes
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
LP/
Propane
0 - 4500 ft 4501 - 5500 ft. 5501 - 6500 ft 6501 - 7500 ft 7501 - 10,000 ft
Low Fire
4.9 10.0 4.6 9.4 4.4 9.1 4.3 8.9 4.9 10.0 11.0 13.0
High
Fire
Low
Fire
High
Fire
Low Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Pressure in. w.g
0 - 10,000 ft.
Min Max
TABLE 22
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Natural to
Unit
045
070 14A54 14A53
090 14A57 14A54
110 14A46 14A51
135 14A49 14A51
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
LP/Propane
0 - 7500 ft 7501 - 10,000 ft 7501 - 10,000 ft 4501 - 7500 ft 7501 - 10,000 ft
*11K51 73W37 *11K46
High Altitude
Natural Burner
Orice Kit
High Altitude LP/
Propane Burner
Orice Kit
High Altitude Pressure Switch
14A47 14A50
Page 59
Page 60
Testing for Proper Venting and Sufcient Combustion Air for Non-Direct Vent Applications
8 - If improper venting is observed during any of the
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.
After the EL296UHV gas furnace has been started, the following test should be conducted to ensure proper vent-
ing and sufcient combustion air has been provided to the EL296UHV as well as to other gas-red appliances which
are separately vented. If a EL296UHV furnace replaces a Category I furnace
which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace
ue products, the existing vent pipe is probably oversized
for the single water heater or other appliance. The vent should be checked for proper draw with the remaining ap­pliance.
The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been
made for sufcient amounts of combustion air, corrections
must be made as outlined in the previous section.
1 - Seal any unused openings in the venting system. 2 - Visually inspect the venting system for proper
size and horizontal pitch. Determine there is no
blockage or restriction, leakage, corrosion, or other
deciencies which could cause an unsafe condition.
3 - To the extent that it is practical, close all building
doors and windows and all doors between the
space in which the appliances connected to the
venting system are located and other spaces of the
building. 4 - Close replace dampers. 5 - Turn on clothes dryers and any appliances not
connected to the venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum speed.
Do not operate a summer exhaust fan. 6 - Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat
so appliance will operate continuously. 7 - Use the ame of match or candle to test for spillage
of ue gases at the draft hood relief opening after 5
minutes of main burner operation.
above tests, the venting system must be corrected
or sufcient combustion/make-up air must be
provided. The venting system should be re-sized to approach the minimum size as determined by using the appropriate tables in appendix G in the current standards of the National Fuel Gas Code ANSI-Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and Propane appliances venting sizing tables in the current standard of the CSA-B149 Natural Gas and Propane Installation Codes in Canada.
9 - After determining that each appliance remaining
connected to the common venting system properly vents when tested as indicated in step 3, return
doors, windows, exhaust fans, replace dampers
and any other gas-burning appliance to their previous condition of use.
Repair Parts
The following repair parts are available through Lennox dealers. When ordering parts, include the complete fur­nace model number listed on the CSA nameplate -- Ex­ample: EL296UHV045P24B-01. All service must be per­formed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Outer access panel Blower access panel Top Cap
Control Panel Parts
Transformer Integrated control board Door interlock switch
Blower Parts
Blower wheel Motor Motor mounting frame Motor capacitor Blower housing cutoff plate
Heating Parts
Flame Sensor Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster
Main burner orices
Pressure switch Ignitor Primary limit control Flame rollout switches
Page 60
Page 61
Other Unit Adjustments
NOTE - See troubleshooting ow charts if any safety
switches are found to be open.
Primary Limit.
The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of the burner box.
Pressure Switch
The pressure switch is located in the heating compartment on the cold end header box. This switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory-set and must not be adjusted.
Temperature Rise
Place the unit into operation with a second-stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature rise. De­crease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation.
Electrical
1 - Check all wiring for loose connections. 2 - Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC + 10% 3 - Check amp-draw on the blower motor with blower
access panel in place.
Unit Nameplate__________Actual__________
Exhaust and Air Intake Pipe
1 - Check exhaust and air intake connections for
tightness and to make sure there is no blockage.
2 - Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check
termination for blockages. 3 - Obstructed pipe or termination may cause rollout
switches to open. Reset manual ame rollout
switches on burner box assembly if necessary.
Heating Sequence of Operation
Electronic Ignition
The two-stage, variable speed integrated control used in EL296UHV units has an added feature of an internal
Watchguard control. The feature serves as an automatic reset device for ignition control lockout caused by ignition failure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermo­stat demand to the furnace and automatically reset the control to begin the ignition sequence.
NOTE - The ignition control thermostat selection DIP switch is factory-set in the “TWO-STAGE” position.
Applications Using a Two-Stage Thermostat
See Figure 63 for ignition control sequence
A - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 OFF in “Two-Stage” Position
(Factory Setting)
1 - On a call for heat, thermostat rst-stage contacts
close sending a signal to the integrated control. The integrated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is energized at low speed.
2 - Once the control receives a signal that the low
pressure switch has closed, the combustion air inducer begins a 15-second pre-purge in low speed.
NOTE - If the low re pressure switch does not close the combustion air inducer will switch to high re. After a 15 second pre-purge the high re pressure switch will close and the unit will begin operation on high re. After 10 to 20 seconds of high re opera­tion the unit will switch to low re..
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air inducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended,
the gas valve is energized on low re (rst stage)
and ignition occurs. At the same time, the control module sends a signal to begin an indoor blower 30-second ON-delay. When the delay ends, the
indoor blower motor is energized on the low re
heating speed, the HUM contacts close energizing
the humidier and 120V ACC terminal is energized.
The furnace will continue this operation as long as
the thermostat has a rst-stage heating demand.
5 - If second-stage heat is required, the thermostat
second- stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30-second second-stage recognition
delay.
6 - At the end of the recognition delay, the integrated
control energizes the combustion air inducer at
high speed. The control also checks the high re
(second stage) pressure switch to make sure it is
closed. The high re (second stage) gas valve is
energized and the indoor blower motor is energized
for operation at the high re heating speed.
7 - When the demand for high re (second stage) heat
is satised, the combustion air inducer is switched to the low-re heating speed and the high-re
(second stage) gas valve is de-energized. The
low-re (rst stage) gas valve continues operation. The indoor blower motor is switched to the low-re
heating speed.
8 - When the thermostat demand for low-re (rst
stage) heat is satised, the gas valve is de­energized and the eld-selected indoor blower off
delay begins. The combustion air inducer begins a 5-second post-purge period.
9 - When the combustion air post-purge period is
complete, the inducer and the HUM contacts are de-energized. The indoor blower is de-energized at the end of the off delay as well as the 120V ACC terminals.
Page 61
Page 62
Applications Using A Single-Stage Thermostat
HEATING OPERATION WITH SINGLE STAGE THERMOSTAT
r
See Figure 64 for ignition control sequence
B - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 ON in “Single-Stage” Position
NOTE - In these applications, two-stage heat will be initi­ated by the integrated control if heating demand has not been satised after the eld adjustable period (7 or 12 minutes).
1 - On a call for heat, thermostat rst-stage contacts
close sending a signal to the integrated control. The integrated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is energized at low speed.
2 - Once the control receives a signal that the low
pressure switch has closed, the combustion air
inducer begins a 15-second pre-purge in low speed.
NOTE - If the low re pressure switch does not close the combustion air inducer will switch to high re. After a 15 second pre-purge the high re pressure switch will close and the unit will begin operation on high re. After 10 to 20 seconds of high re opera­tion the unit will switch to low re.
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air
inducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended,
the gas valve is energized on low re (rst stage)
and ignition occurs. At the same time, the control module sends a signal to begin an indoor blower 30-second ON-delay. When the delay ends, the
indoor blower motor is energized on the low re
heating speed and the HUM contacts are energized. The integrated control also initiates a second-stage on delay (factory-set at 7 minutes; adjustable to 12 minutes).
5 - If the heating demand continues beyond the
secondstage on delay, the integrated control energizes the combustion air inducer at high speed.
The control also checks the high re (second stage)
pressure switch to make sure it is closed. The high
re (second stage) gas valve is energized and the
indoor blower motor is energized for operation at
the high re heating speed.
6 - When the thermostat heating demand is satised,
the combustion air inducer begins a 5-second low
speed post-purge. The eld-selected indoor blower
off delay begins. The indoor blower operates at the
low-re heating speed.
7 - When the combustion air post-purge period is
complete, the inducer and the HUM contacts are de-energized. The indoor blower is de-energized at the end of the off delay as well as the 120V ACC terminals.
HEATING OPERATION WITH TWO-STAGE THERMOSTAT
15
Pre-Purge
Ignitor Warm-up
35
30 seconds
39
30* second
Trial For Ignition
RECOGNITION PERIOD
blower
“on” delay
ON
1 stg heat demand low speed CAI
ignitor low fire gas valve
indoor blower low heat
2 stg heat demand high speed CAI high fire gas valve indoor blower high heat
OFF
* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.
1
Figure 63
ON
OFF
heat demand low speed CAI ignitor low fire gas valve
indoor blower low heat
7 or 12 minutes after heating demand begins, furnace switches to high fire (depends on setting)
high speed CAI high fire gas valve
indoor blower high heat
* Conventional thermostat 30 seconds, icomfort Touch
1
Pre-Purge
15
Ignitor Warm-up
35
39
Trial For Ignition
30* second
blower
“on” delay
®
thermostat set for 30 adjustable 15 to 45 seconds.
80
5 SEC80
Post
Purge
blower
delay
5 SEC
Post
Purge
“off”
blowe
“off”
delay
Figure 64
Page 62
Page 63
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply with the Lennox Limited Warranty, your system should be checked as follows:
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2 - Check the condition of the belt and shaft bearings
if applicable. 3 - Inspect all gas pipe and connections for leaks. 4 - Check the cleanliness of lters and change if
necessary (monthly). 5 - Check the condition and cleanliness of burners and
heat exchanger and clean if necessary. 6 - Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor
if necessary. 7 - Inspect the condensate drain and trap for leaks and
cracks. The drain and trap must also be cleaned
and the trap must be primed with water. Inspect the
rubber hoses connected to the pressure switches for
cracks or loose connections, replace as necessary.
Remove the rubber hoses from the cold end header
box and inspect for any blockage, clean as needed.
If strainers are installed in the hoses remember to
remove and clean before reinstalling the hoses. 8 - Evaluate the heat exchanger integrity by inspecting
the heat exchanger per the AHRI heat exchanger
inspection procedure. This procedure can be
viewed at www.ahrinet.org.
9 - Ensure sufcient combustion air is available to the
furnace. Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) must be properly sized, open and unobstructed to provide combustion air.
10 - Inspect the furnace intake and exhaust pipes to
make sure they are in place, structurally sound, without holes, blockage or leakage and the exhaust pipe is sloped toward the furnace. Inspect terminations to ensure they are free of obstructions and are structurally sound. Inspect the furnace return air duct connection to ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.
11 - Inspect the furnace return air duct connection to
ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.
12 - Check the condition of the furnace cabinet insulation
and repair if necessary.
13 - Perform a complete combustion analysis during the
furnace inspection to ensure proper combustion and operation. Consult Service Literature for proper combustion values.
14 - Verify operation of CO detectors and replace
batteries as required.
Perform a general system test. Turn on the furnace to check operating functions such as the start-up and shut­off operation.
1 - Check the operation of the ignition system, inspect
and clean ame sensor. Check microamps before
and after. Check controls and safety devices (gas
valve, ame sensor, temperature limits). Consult
Service Manual for proper operating range. Thermal
Limits should be checked by restricting airow and
not disconnecting the indoor blower. For additional details, please see Service and Application Note H049.
2 - Verify that system total static pressure and airow
settings are within specic operating parameters.
3 - Clock gas meter to ensure that the unit is operating
at the specied ring rate for each stage of
operation. Check the supply pressure and the
manifold pressure on both low re and high re. If
manifold pressure adjustment is necessary, consult
the Service Literature for unit specic information
on adjusting gas pressure. Not all gas valves are adjustable. Verify correct temperature rise.
Page 63
Page 64
Winterizing and Condensate Trap Care
1 - Turn off power to the furnace. 2 - Have a shallow pan ready to empty condensate
water. 3 - Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
clean out cap.
Cleaning The Burner Assembly
If cleaning the burner assembly becomes necessary, fol­low the steps below:
1 - Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels. 2 - Disconnect the wires from the gas valve. 3 - Remove the burner box cover (if equipped). 4 - Disconnect the gas supply line from the gas valve.
Remove gas valve/manifold assembly.
5 - Mark and disconnect sensor wire from the sensor.
Disconnect wires from ame rollout switches.
6 - Disconnect combustion air intake pipe. It may be
necessary to cut the existing pipe to remove burner box assembly.
7 - Remove four screws which secure burner box
assembly to vest panel. Remove burner box from the unit.
8 - Use the soft brush attachment on a vacuum cleaner
to gently clean the face of the burners. Visually inspect the inside of the burners and crossovers for any blockage caused by foreign matter. Remove any blockage.
9 - Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the center of the burner ports.
10 - Reconnect the sensor wire and reconnect the 2-pin
plug to the ignitor wiring harness. Reconnect wires
to ame rollout switches.
11 - Reinstall the gas valve manifold assembly.
Reconnect the gas supply line to the gas valve.
Reinstall the burner box cover. 12 - Reconnect wires to gas valve. 13 - Replace the blower compartment access panel. 14 - Refer to instruction on verifying gas and electrical
connections when re-establishing supplies. 15 - Follow lighting instructions to light and operate
furnace for 5 minutes to ensure that heat exchanger
is clean and dry and that furnace is operating
properly. 16 - Replace heating compartment access panel.
Page 64
Page 65
Program Unit Capacity/Size Mode
Power-Up - Number displayed represents by integrated control unit size code (furnace model and capacity). If three horizontal bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following:
Yes
To enter Program Unit Capacity/Size: push and hold button next to 7-segment LED display until solid “P” symbol appears. Release button.
IMPORTANT: Field replacement controls may need to be manually configured to validate furnace unit size code.
Solid P starts blinking on 7-Segment LED
P
_
Furnace control in IDLE mode
No heating, cooling or indoor fan
operation)
UNIT SIZE
CODE
0
1
2
3
4
5
6
7
FURNACE MODEL
EL296UH045V36B
EL296UH070V36B
EL296UH090V36C
EL296UH09048C
EL296UH090V60C
EL296UH110V48C
EL296UH110V60C
EL296UH135V60D
No
Turn room thermostat to OFF
UNIT SIZE
CODE
FURNACE MODEL
8
EL296DF0450V36A
9
EL296DF070V48B
11
EL296DF090V60C
U
EL296DF110V60C
Push and hold button. Integrated control will display unit size code number for each furnace model for three seconds.
When the correct unit size code is displayed, release button. Selected code will flash for 10-second period. During that period, press and hold push button for 5 seconds. Integrated control will store code in memory and will automatically exit Program Unit Capacity/Size Mode and reset. (If second period expires or push button is held less than five seconds, control will automatically exit Program Capacity/Size Mode and go into IDLE mode without storing unit size code. If this happens, programming function must be repeated).
. If
Verify that the selected unit size code is correct and stored in non-volatile memory by cycling the 24 volt power to the furnace control. (At 24 volt power-up of the furnace control, the 7-segment LED will display a unit size code three horizontal bars display, board does not recognize unit size code function must be repeated)
. Programming
FINISHED
Page 65
Page 66
Requirements for Commonwealth of Massachusetts
Modications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following
requirements:
For all side wall, horizontally vented, gas-fueled equip­ment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the nished grade in the area of the venting, in­cluding but not limited to decks and porches, the following
requirements shall be satised:
1 - INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall, horizontally vented, gas-fueled equipment,
the installing plumber or gastter shall observe that
a hard-wired carbon monoxide detector with an
alarm and battery backup is installed on the oor
level where the gas equipment is to be installed.
In addition, the installing plumber or gastter shall
observe that a battery-operated or hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas-fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualied licensed professionals for the installation
of hard-wired carbon monoxide detectors.
a. I n the event that the side wall, horizontally vented, gas-fueled
equipment is installed in a crawl space or an attic, the hard­wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision cannot
be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery-operated carbon monoxide detector with an alarm shall be installed.
2 - APPROVED CARBON MONOXIDE
DETECTORSach carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
3 - SIGNAGE. A metal or plastic identication plate
shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas-fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS
4 - INSPECTION. The state or local gas inspector
of the side wall, horizontally vented, gas-fueled
equipment shall not approve the installation unless,
upon inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)
(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt­from 24 CMR 5.08(2)(a) 1 through 4:
1 - The equipment listed in Chapter 10 entitled
“Equipment Not Required to Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2 - Product Approved side wall, horizontally vented,
gasfueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIP­MENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas-fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the man­ufacturer for installation of the equipment and the venting system shall include:
1 - Detailed instructions for the installation of the venting
system design or the venting system components: and
2 - A complete parts list for the venting system design
or venting system.
MANUFACTURER REQUIREMENTS ­GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas-fueled equipment does not pro-
vide the parts for venting the ue gases, but identies
“special venting systems,” the following requirements
shall be satised by the manufacturer:
1 - The referenced “special venting system” instructions
shall be included with the appliance or equipment installation instructions; and
2 - The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc-
tions shall remain with the appliance or equipment at
the completion of the installation.
Page 66
Page 67
FOR THE PROVINCE OF ONTARIO, HORIZONTAL SIDEWALL VENT APPLICATIONS ONLY
For exterior horizontal venting applications, the 2” X 1.5” reducer for 2” venting at the point where the exhaust pipe exits the structure is not required in direct or nondirect vent applications in the Province of Ontario. In these applications, the vent should be oriented such that the exhaust plume is unobjectionable. If the installation requires more separation be-
tween the ue gases and the building structure, a reducer may be installed on the exhaust pipe to increase the ue gas
velocity.
ADDENDUM FOR THE PROVINCE OF SASKATCHEWAN
See below for venting in the province of Saskatchewan. Lennox approves the following termination for use in Saskatchewan Canada.
C
D
B
12”
A
2” (51MM)
Vent Pipe
A − Clearance above grade or
average snow accumulation
B − Horizontal separation between
intake and exhaust
C − Exhaust pipe length
D − Wall support distance from top
of each pipe (intake/exhaust)
NOTE − Flue gas may be acidic and may adversely affect some building materials. If flue gases impinge on the building materials, a corrosion−resistant shield should be used to protect the wall surface. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
12” (305 mm) Min. 12” (305 mm) Min.
6” (152 mm) Min. 24” (610 mm) Max.
Per: Saskatchewan Code of Practice
6” (152 mm) Max.
3” (76MM)
Vent Pipe
6” (152 mm) Min. 24” (610 mm) Max.
6” (152 mm) Max.
Page 67
Loading...