This is a safety alert symbol and should never be ignored.
When you see this symbol on labels or in manuals, be alert
to the potential for personal injury or death.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a licensed professional HVAC in
staller (or equivalent), service agency or the gas sup
plier.
DOWNFLOW
AIR FLOW
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
Table of Contents
Unit Dimensions2......................................
EL296DFV Gas Furnace3..............................
Shipping and Packing List3.............................
Program Unit Capacity Size Mode62.....................
Repair Parts List64....................................
®
7500 thermostat may be used, as
thermostat must be used in
Page 1
Page 2
EL296DFV Unit Dimensions - inches (mm)
COMBUSTION
EXHAUST AIR
AIR INTAKE
OUTLET
2−1/16 (52)
5
(127)
2−1/4
(57)
9/16
(14)
RETURN AIR
B
OPENING
9/16
(14)
TOP VIEW
3/4
(19)
AIR
C
A
B
FLOW
Supply
Air
9/16
(14)
3/4
(19)
33
(838)
1−1/2 (38)
Front Panel
1 (25)
1−7/8 (48)
5−3/16
(132)
2−1/16
(52)
2 (51)
Either Side
GAS PIPING INLET
(Either Side)
9−1/8 (232) Right
6−9/16 (167) Left
27−3/4
(705)
6−1/4
(157)
OPTIONAL LEFT SIDE
ELECTRICAL INLET
(Either Side)
ALTERNATE RIGHT SIDE
VENT LOCATION
(Parts Furnished)
ELECTRICAL INLET
(Either Side)
TRAP CONNECTION
6−7/16 (163)
Either Side
19−7/16
(494)
VENT LOCATION
(Kit Required)
CONDENSATE
(Either Side)
9 (229)
Either Side
(489)
Supply
Air
19−1/4
9/16
(14)
3/4
(19)
FRONT VIEWSIDE VIEW
Model No.
EL296DFXV045P36B
EL296DFXV070P48B
EL296DFXV090P60C
EL296DFXV110P60C
ABC
in.mmin.mmin.mm
17-1/244616-3/841616406
2153319-7/850519-1/2495
Page 2
Page 3
EL296DFV Gas Furnace
Shipping and Packing List
The EL296DFV Category IV gas furnace is shipped ready
for installation in the downflow position.
The furnace is equipped for installation in natural gas ap
plications. A conversion kit (ordered separately) is re
quired for use in propane/LP gas applications.
The EL296DFV can be installed as a Direct Vent or NonDirect Vent gas central furnace.
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors. In
Non-Direct Vent installations, combustion air is taken from
indoors or ventilated attic or crawlspace and flue gases are
discharged outdoors. See figures 1 and 2 for applications in
volving roof termination.
DIRECT VENT INSTALLATIONNON-DIRECT VENT
EXHAUST OUTLET
AIR INTAKE OUTSIDE
COMBUSTION
OF HOUSE
INSTALLATION
EXHAUST
OUTLET
COMBUSTION
AIR INTAKE
OF HOUSE
INSIDE
FIGURE 1
Package 1 of 1 contains
1 - Assembled EL296DFV unit
1 - Bag assembly containing the following:
1 - Snap bushing
1 - Snap plug
1 - Wire tie
1 - Condensate trap
1 - Condensate trap cap
1 - Condensate trap clamp
1 - 2” diameter Air intake screen
1 - 3/4” Threaded street elbow
2 - 2” Street elbows
2 - Side vent sealing plates
2 - Side vent sealing gaskets
6 - Sheet metal screws
DANGER
Danger of explosion.
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
The following items may also be ordered separately:
1 - Thermostat
1 - LP/Propane changeover kit
1 - High altitude pressure switch
Safety Information
NON-DIRECT VENT
INSTALLATION
EXHAUST
OUTLET
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
FIGURE 2
NON-DIRECT VENT
INSTALLATION
EXHAUST
OUTLET
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
EL296DFV units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with lo
cal building codes. In the absence of local codes, units must
Page 3
Page 4
be installed according to the current National Fuel Gas Code
(ANSI‐Z223.1/NFPA 54). The National Fuel Gas Code is
available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA‐B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
In order to ensure proper unit operation in non-direct vent
applications, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA‐B149 standard.
Locations and Clearances
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in figure 13. Accessibility and ser
vice clearances must take precedence over fire protection
clearances.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a haz
ardous atmosphere, the furnace must be installed accord
ing to recommended good practice requirements and cur
rent National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Failure
to do so may cause erratic limit operation and premature heat
exchanger failure.
This EL296DFV furnace must be installed so that its electri
cal components are protected from water.
Installation in Combination with a Cooling Coil
When this furnace is used with cooling units (figure 3), it
shall be installed in parallel with, or on the upstream side of,
cooling units to avoid condensation in the heating compart
ment. With a parallel flow arrangement, a damper (or other
means to control the flow of air) must adequately prevent
chilled air from entering the furnace. If the damper is manu
ally operated, it must be equipped to prevent operation of ei
ther the heating or the cooling unit, unless it is in the full
HEAT or COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Heating Unit Installed Parallell to Air Handler Unit
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 3
NOTE - This furnace is designed for a minimum continu
ous return air temperature of 60°F (16°C) or an intermit
tent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air tem
perature must not exceed 85°F (29°C) dry bulb.
The EL296DFV furnace may be installed in alcoves, clos
ets, attics, basements, garages, utility rooms and crawl
spaces.
This furnace design has not been CSA certified for installa
tion in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL296DFV units
as a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and op
eration of the unit with clogged or misplaced filters will dam
age the unit.
EL296DFV units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
• The return air duct must be provided and sealed to the
furnace.
Page 4
Page 5
• Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
• Air filters must be installed in the system and must be
maintained during construction.
• Air filters must be replaced upon construction comple
tion.
• The input rate and temperature rise must be set per the
furnace rating plate.
• One hundred percent (100%) outdoor air must be pro
vided for combustion air requirements during construc
tion. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
• The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean-up.
• All furnace operating conditions (including ignition, in
put rate, temperature rise and venting) must be verified
according to these installation instructions.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the fol
lowing general recommendations must be considered
when installing a EL296DFV furnace:
• Place the furnace as close to the center of the air dis
tribution system as possible. The furnace should also be
located close to the chimney or vent termination point.
• When the furnace is installed in non-direct vent applica
tions, do not install the furnace where drafts might blow
directly into it. This could cause improper combustion
and unsafe operation.
• When the furnace is installed in non-direct vent applica
tions, do not block the furnace combustion air opening
with clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other insu
lated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent freezing
of condensate drain system.
CAUTION
EL296DFV unit should not be installed in areas nor
mally subject to freezing temperatures.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
Combustion, Dilution & Ventilation Air
If the EL296DFV is installed as a Non-Direct Vent Fur
nace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air
is taken from indoors or ventilated attic or crawlspace
and flue gases are discharged out-doors.
WARNING
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rust
ing and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the com
bustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today's homes, tight construction
practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans, ap
pliance vents, chimneys, and fireplaces force additional
air that could be used for combustion out of the house.
Unless outside air is brought into the house for combus
tion, negative pressure (outside pressure is greater than
inside pressure) will build to the point that a downdraft
can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a po
tentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install EL296DFV furnaces to ensure effi
cient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
pip-ing. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI-
Page 5
Page 6
Z223.1/NFPA 54). This reprinted material is not the com
plete and official position of the ANSI on the referenced
subject, which is represented only by the standard in its
entirety.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami
nated atmosphere. Meet all combustion and ventila
tion air requirements, as well as all local codes.
All gas‐fired appliances require air for the combustion pro
cess. If sufficient combustion air is not available, the fur
nace or other appliance will operate inefficiently and un
safely. Enough air must be provided to meet the needs of all
fuel-burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, ex
haust fans, or clothes dryers are used at the same time as
the furnace, much more air is required to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air di
lutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace compo
nents.
The requirements for providing air for combustion and ven
tilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m
bined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be un
confined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic
3
) per 1,000 Btu (.29 kW) per hour of the com
feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This
definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con
taining the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space ei
ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm
2
) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm
2
). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 4.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE - Each opening shall have a free area of at least one square
inch per 1,000 Btu (645mm
rating of all equipment in the enclosure, but not less than 100 square
inches (64516mm.
2
per .29kW) per hour of the total input
2).
(To Adjacent
Unconfined
Space)
FIGURE 4
Page 6
Page 7
Air from Outside
If air from outside is brought in for combustion and ventila
tion, the confined space shall be provided with two perma
nent openings. One opening shall be within 12” (305mm)
of the top of the enclosure and one within 12” (305mm) of
the bottom. These openings must communicate directly
or by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a mini
mum free area of 1 square inch per 4,000 Btu (645mm
per 1.17kW) per hour of total input rating of all equipment
in the enclosure. When communicating with the outdoors
through horizontal ducts, each opening shall have a mini
mum free area of 1 square inch per 2,000 Btu (645mm
per .59kW) per total input rating of all equipment in the en
closure (See figure 5). It is also permissible to bring in air
for combustion from a ventilated attic (figure 6) or venti
lated crawl space (figure 7).
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
2
Ventilation
2
Louvers
(Crawl space)
EQUIPMENT IN CONFINED SPACE
Furnace
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
VENTILATION
LOUVERS
(For unheated
crawl space)
2
per 1.17kW) per
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
INLET
AIR
FIGURE 5
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
EQUIPMENT IN CONFINED SPACE
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
*Intake Debris
Screen
(Provided)
Furnace
* See table 9 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
2
per 1.17kW) per
FIGURE 6
* See table 9 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
2
per 1.17kW) per
FIGURE 7
If air from outside is brought in for combustion and ventila
tion, the confined space must have two permanent open
ings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communi
cate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indi
rectly through vertical ducts. Each opening shall have a
2
minimum free area of 1 square inch (645 mm
) per 4,000
Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See figures 5 and 8. When communicat
ing with the outdoors through horizontal ducts, each open
ing shall have a minimum free area of 1 square inch (645
2
) per 2,000 Btu (.56 kW) per total input rating of all
mm
equipment in the enclosure. See figure 9.
When ducts are used, they shall be of the same cross-sec
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protec
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be fixed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
Page 7
Page 8
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
EL296 Furnaces with
1/2 HP Blower Motor
ROOF TERMINATED
EXHAUST PIPE
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12” above
bottom)
2
per 1.17kW) per
FIGURE 8
EQUIPMENT IN CONFINED SPACE -
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645mm
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communi
cate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm
hour of the total input rating of all other equipment in the enclosure.
2
per .59kW) per hour of the total
INLET AIR
2
per 1.17kW) per
FIGURE 9
Shipping Bolt Removal
Units with 1/2 hp blower motor are equipped with three flex
ible legs and one rigid leg. The rigid leg is equipped with a
shipping bolt and a flat white plastic washer (rather than the
rubber mounting grommet used with a flexible mounting
leg). See figure 10. The bolt and washer must be removed before the furnace is placed into operation. Af
ter the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
RIGID LEG
(Remove shipping bolt
and washer)
FIGURE 10
Installation - Setting Equipment
WARNING
Do not install the furnace on its front, back or in the
horizontal position. See figure 12. Do not connect the
return air ducts to the back of the furnace. Doing so
will adversely affect the operation of the safety con
trol devices, which could result in personal injury or
death.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
condensate trap and drain connections, and installation
and service clearances [24 inches (610 mm) at unit
front]. The unit must be level from side to side. Unit may
be positioned from level to 1/2” toward the front to aid in
draining. See figure 11.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or al
cove installations are shown in figure 13.
WARNING
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
Page 8
Page 9
SETTING EQUIPMENT
AIR FLOW
FRONT VIEW
AIR FLOW
UNIT
FRONT
SIDE VIEW
UNIT
FRONT
Unit must be level side-to-side. Unit may be positioned
from level to 1/2” toward the front to aid in draining.
FIGURE 11
AIR FLOW
SIDE VIEW
1/2”
max.
Back
Front
NOTE - Do not install the furnace on its front, back or in the horizontal position
FIGURE 12
Page 9
Horizontal
Page 10
WARNING
Improper installation of the furnace can result in per
sonal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the fur
nace should be sealed airtight to the return air ple
num. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Al
low absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct sys
tems ever be connected to or from other heating de
vices such as a fireplace or stove, etc. Fire, explo
sion, carbon monoxide poisoning, personal injury
and/or property damage could result.
The unit may be installed three ways in downflow applica
tions: on non-combustible flooring, on combustible flooring
using an additive base, or on a reverse-flow cooling coil
cabinet. Do not drag the unit across the floor in the
downflow position. Floor and furnace flange damage
will result.
Refer to figure 13 for clearances in downflow applica
tions.
Installation on Non-Combustible Flooring Figure 14
1 - Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec
tions, electrical supply, flue and air intake connections
and sufficient installation and servicing clearances.
See table 1 for correct floor opening size.
2 - Flange warm air plenum and lower the plenum into the
opening.
3 - Set the unit over the plenum and seal the plenum to
the unit.
4 - Ensure that the seal is adequate.
TABLE 1
NON-COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
B Cabinet (17.5”)19 - 3/450216 - 5/8422
C Cabinet (21”)19 - 3/450220-1/8511
NOTE - Floor opening dimensions listed are 1/4 inch (6 mm) larger than
the unit opening. See dimension drawing on page 2.
Front to RearSide to Side
in.mmin.mm
Downflow Application Installation Clearances
Top
Left SideRight Side
Bottom
Top0
*Front0
Back0
Sides0†
Vent0
FloorNC‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap and
vent pipe installation.
‡The furnace may be installed on a combustible wood floor if an op
tional additive base is installed between the furnace and the com
bustible floor.
FIGURE 13
FURNACE
PROPERLY
SIZED FLOOR
OPENING
SUPPLY AIR
PLENUM
FIGURE 14
Installation on Combustible Flooring Figure 15
1 - When unit is installed on a combustible floor, a down
flow combustible flooring base must be installed be
tween the furnace and the floor. The base must be or
dered separately. See table 2 for opening size to cut in
floor.
CAUTION
The furnace and combustible flooring base shall not
be installed directly on carpeting, tile, or other com
bustible material other than wood flooring.
Page 10
Page 11
TABLE 2
COMBUSTIBLE FLOORING BASE OPENING SIZE
Cabinet
Width
Catalog
Number
Front to RearSide to Side
in.mmin.mm
FURNACE
B Cabinet
(17.5”)
C Cabinet
(21”)
FURNACE
PROPERLY
SIZED FLOOR
OPENING
11M60
11M61
2255918 - 3/4476
2255922 - 3/4578
SUPPLY AIR
PLENUM
COMBUSTIBLE
FLOORING BASE
FIGURE 15
2 - After opening is cut, set the combustible flooring base
into opening.
3 - Check fiberglass strips on the combustible flooring
base to make sure they are properly glued and posi
tioned.
4 - Lower supply air plenum into the combustible flooring
base until plenum flanges seal against fiberglass
strips.
NOTE - Be careful not to damage fiberglass strips.
Check for a tight seal.
5 - Set the furnace over the plenum.
6 - Ensure that the seal between the furnace and plenum
is adequate.
Installation on Cooling Coil Cabinet Figure 16
NOTE - Downflow combustible flooring kit is not used.
1 - Refer to reverse-flow coil installation instructions for
correctly sized opening in floor and installation of cabi
net.
2 - When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided
with the cooling coil. Secure the furnace to the cabinet.
3 - Seal the cabinet and check for air leaks.
COOLING COIL
PROPERLY
SIZED FLOOR
OPENING
PLENUM
FIGURE 16
Return Air Opening -- Downflow Units
Return air may be brought in only through the top opening
of a furnace installed in the downflow position. The follow
ing steps should be taken when installing plenum:
1 - Bottom edge of plenum should be flanged with a
hemmed edge (See figure 17 or 18).
2 - Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 - In all cases, plenum should be secured to top of fur
nace using sheet metal screws.
4 - Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
Side View
FIGURE 17
PLENUM
(Field Provided)
SECURE FROM
INSIDE CABINET
Side View
SEALING STRIP
(Field Provided)
CABINET
SIDE PANEL
FIGURE 18
Page 11
Page 12
Filters
This unit is not equipped with a filter or rack. A field-pro
vided filter is required for the unit to operate properly. Table
3 lists recommended minimum filter size.
A filter must be in place whenever the unit is operating.
IMPORTANT
If a highefficiency filter is being installed as part of
this system to ensure better indoor air quality, the fil
ter must be properly sized. Highefficiency filters
have a higher static pressure drop than standardef
ficiency glass/foam filters. If the pressure drop is too
great, system capacity and performance may be re
duced. The pressure drop may also cause the limit to
trip more frequently during the winter and the indoor
coil to freeze in the summer, resulting in an increase
in the number of service calls.
Before using any filter with this system, check the
specifications provided by the filter manufacturer
against the data given in the appropriate Lennox
Product Specifications bulletin. Additional informa
tion is provided in Service and Application Note
ACC002 (August 2000).
TABLE 3
Furnace
Cabinet Width
17-1/2”
21”
Duct System
Use industry‐approved standards to size and install the
supply and return air duct system. Refer to ACCA Manual
D. This will result in a quiet and low‐static system that has
uniform air distribution.
NOTE - This furnace is not certified for operation in heating
mode (indoor blower operating at selected heating speed)
with an external static pressure which exceeds 0.8 inches
w.c. Operation at these conditions may result in improper
limit operation.
Minimum Filter Size
16 x 25 x 1 (1)
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel should be installed in the supply air duct. The
access panel should be large enough to permit inspection
of the heat exchanger. The furnace access panel must al
ways be in place when the furnace is operating and it must
not allow leaks into the supply air duct system.
Return Air Plenum
NOTE - Return air must not be drawn from a room
where this furnace, or any other gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing de
vice (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pres
sure is created in the room. If a gas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
re verse flow of the flue gas may result in incomplete com
bustion and the formation of carbon monoxide gas. This
raw gas or toxic fumes might then be distributed through
out the house by the furnace duct system.
Use fiberglass sealing strips, caulking, or equivalent seal
ing method between the plenum and the furnace cabinet to
ensure a tight seal. If a filter is installed, size the return air
duct to fit the filter frame.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri
can Society for Testing and Materials (ANSI/ASTM) stan
dards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that ad
versely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratifica
tion, or separation that cannot be removed by stirring. Re
fer to the table 4 below for approved piping and fitting ma
terials.
Page 12
Page 13
CAUTION
Solvent cements for plastic pipe are flammable liq
uids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of ce
ment with skin and eyes.
POLYPROPYLENE VENTING SYSTEMULC-S636
PolyPro® by DuraventULC-S636
InnoFlue® by CentrothermULC-S636
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3138
MARKING
ULCS636
IMPORTANT
EL296DFV exhaust and intake connections are made
of PVC. Use PVC primer and solvent cement when
using PVC vent pipe. When using ABS vent pipe, use
transitional solvent cement to make connections to
the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement
meeting ASTM specifications, refer to Table 4. As an alter
nate, use all purpose cement, to bond ABS, PVC, or CPVC
pipe when using fittings and pipe made of the same materi
als. Use transition solvent cement when bonding ABS to ei
ther PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean in
side socket surface of fitting and male end of pipe to depth
of fitting socket.
Canadian Applications Only - Pipe, fittings, primer
and solvent cement used to vent (exhaust) this ap
pliance must be certified to ULC S636 and supplied by a
single manufacturer as part of an approved vent (ex
haust) system. In addition, the first three feet of vent
pipe from the furnace flue collar must be accessible for
inspection.
Venting Options
The EL296DFV is shipped with vent exhaust / air intake
connection at the top cap. See figure 19. Using parts pro
vided, the furnace may be field modified to have these
connections on the right side of the furnace cabinet. See
figure 21 and follow the steps below. For left side venting
order kit 87W73.
1 - Remove inner blower door.
2 - Loosen hose clamps which attach rubber fittings to the
white PVC pipes inside the vestibule area. See figure
19.
3 - Loosen the clamp which secures the pipes at the blow
er deck. See figure 19.
4 - Remove white PVC pipes, slide up and out thru the top
cap.
5 - Remove the black plastic fitting in top cap which pre
viously aligned the PVC pipes.
6 - Remove the remaining parts of the pipe clamp at the
blower deck.
7 - Remove the sheet metal patch plate on the side of the
cabinet which covers the openings for side venting op
tion. Save screws for reuse.
8 - Re-use the patch plate to cover the hole in the top cap.
See figure 20. Remove the 2 screws which secure the
top cap to the furnace on the right side and re-install
securing the right edge of the patch plate and the right
side of the top cap to the furnace. Use 2 self-drilling
sheet metal screws (provided) to finish securing the
left edge of the patch plate on the left side.
9 - Use a utility knife to cut out the cabinet insulation for
the right side vent / air intake.
10 -Install the two 90° street elbows (provided) through the
side of the cabinet. The male side of each elbow
should extend down through the blower deck and con
nect to the rubber fittings below. Once the elbows are
properly positioned, tighten each clamp.
11 -Peel protective backing from side vent sealing gaskets
(2) and apply to side vent sealing plates (2) as shown
in figure 21.
Page 13
Page 14
12 -Install the side vent sealing plates and gaskets on the
exterior of the cabinet as shown in figure 21. Secure
with six mounting screws (four reused and two pro
vided from bag assembly). Holes are pre-punched in
the parts and cabinet, no drilling is required.
13 -Install sheet metal screws (provided) to seal extra two
holes in cabinet not used with side vent clamps.
IMPORTANT
Side vent sealing plates and side vent sealing gas
kets must be used when converting to right side
venting. Failure to use gaskets and plates may lead
to improper operation of unit.
Top Vent Configuration
Exhaust/Air
Intake Connections
Pipe Clamp
Patch Plate Top Cap
Sheet Metal
Patch Plate
FIGURE 20
FIGURE 19
Hose Clamp
Page 14
Page 15
Right Side Vent Configuration
Side Vent
Sealing Plate
Side Vent
Sealing Gaskets
Input Size
045
070
090
110
Exhaust
Street Elbows (2)
FIGURE 21
TABLE 5
OUTDOOR TERMINATION USAGE*
STANDARDCONCENTRIC
Flush
Vent
Pipe
Dia. in.
Mount
Kit
51W11
(US)
51W12
2 inch3 inch2 inch
22G44 (US)
4
30G28 (CA)
(CA)
2
2-1/2
3
2
2-1/2
3
2
2-1/2
3
3
YESYES
3
YESYES
3
YESYES
3
YESYES
3
YESYES
3
YESYES
3
YESYESYES
3
YESYESYES
3
YESYESYES
2YESYESYES
2-1/2YESYES
3YESYES
Wall KitWall Ring Kit
44J40
(US)
4
81J20 (CA)
1
YES
1
YES
1
YES
1
YES
1
YES
1
YES
15F74
1
YES
1
YES
1
YES
1
YES
1
YES
1
YES
Intake
1-1/2 inch2 inch3 inch
Field
Fabricated
5
YES
5
YES
5
YES
5
YES
5
YES
5
YES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYESYES
5
YESYESYES
71M80
(US)
4
44W92
(CA)
2
YES
2
YES
2
YES
2
YES
2
YES
2
YES
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See vent
length tables.
* Kits must be properly installed according to kit instructions.
Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
3
Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4
Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.
5
See table 10 for vent accelerator requirements.
Page 15
Page 16
Joint Cementing Procedure
Venting Practices
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
NOTE - A sheet metal screw may be used to secure
the intake pipe to the connector, if desired. Use a drill
or self tapping screw to make a pilot hole.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system
check. Allow fumes to dissipate for at least 5 minutes
before placing unit into operation.
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
NOTE - Check the inside of vent pipe thoroughly for
any obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 - Test fit joint and mark depth of fitting on outside of pipe.
5 - Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
6 - Promptly apply solvent cement to end of pipe and in
side socket surface of fitting. Cement should be ap
plied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply sec
ond coat to end of pipe.
NOTE - Time is critical at this stage. Do not allow prim
er to dry before applying cement.
7 - Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn dur
ing assembly (but not after pipe is fully inserted) to dis
tribute cement evenly. DO NOT turn ABS or cellular
core pipe.
NOTE - Assembly should be completed within 20 sec
onds after last application of cement. Hammer blows
should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indi
cate an improper assembly due to insufficient sol
vent.
9 - Handle joints carefully until completely set.
Piping Suspension Guidelines
SCHEDULE 40
PVC - 5'
all other pipe* - 3'
* See table 4 for allowable pipe.
NOTE - Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24” maximum
3/4” minimum
insideoutside
Wall
FIGURE 22
REPLACING FURNACE THAT
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by EL193)
If an EL296DFV furnace replaces a furnace which was
commonly vented with another gas appliance, the size of
the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue prod
ucts, the existing vent pipe is probably oversized for the
single water heater or other appliance. The vent should be
checked for proper draw with the remaining appliance.
WAS PART OF A COMMON
VENT SYSTEM
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 23
1 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on
all sides of pipe through center of hole using a hanger.
Page 16
Page 17
2 - When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining conden
sate collection trap and lines.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap
pliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operat
ing and the other appliances (which are not operating) re
main connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting re
quirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon mon
oxide poisoning or death.
The following steps shall be followed for each ap
pliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
1 - Seal any unused openings in the common venting sys
tem.
2 - Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 - Close all building doors and windows and all doors be
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper
ate at maximum speed. Do not operate a summer ex
haust fan. Close fireplace dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 - After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
6 - After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace damp
ers, and any other gas-burning appliances to their pre
vious mode of operation.
7 - If a venting problem is found during any of the preced
ing tests, the common venting system must be modi
fied to correct the problem.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan
dards of the National Fuel Gas Code ANSI Z223.1.
Exhaust Piping (Figures 25 and 26)
Route piping to outside of structure. Continue with installa
tion following instructions given in piping termination sec
tion.
WARNING
Carbon Monoxide Poisoning Hazard
Cutting or altering exhaust or air intake pipes, which
are located in the blower compartment, could result
in Carbon Monoxide Poisoning or Death.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If verti
cal discharge through an existing unused stack is re
quired, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres
sure and must be completely sealed to prevent leak
age of combustion products into the living space.
Page 17
Page 18
Vent Piping Guidelines
NOTE - Lennox has approved the use of DuraVent
Centrotherm manufactured vent pipe and terminations as
an option to PVC. When using the PolyPro
InnoFlue
®
by Centrotherm venting system the vent pipe re
®
by DuraVent or
quirements stated in the unit installation instruction – min
imum & maximum vent lengths, termination clearances,
etc. – apply and must be followed. Follow the instructions
provided with PoyPro by DuraVent and InnoFlue by Cen
trotherm venting system for assembly or if requirements
are more restrictive. The PolyPro by Duravent and In
noFlue by Centrotherm venting system must also follow
the uninsulated and unconditioned space criteria listed in
table 8.
The EL296DFV can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE - In Non‐Direct Vent installations, combustion air is
taken from indoors or ventilated attic or crawlspace and flue
gases are discharged outdoors. In Direct Vent installations,
combustion air is taken from outdoors and flue gases are
discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 6 and 7. Count all elbows inside and outside the
home. Table 6 lists the minimum vent pipe lengths per
mitted. Table 7 lists the maximum pipe lengths permitted.
TABLE 6
MINIMUM VENT PIPE LENGTHS
EL296DFV
MODEL
045, 070, 090, 110
*Any approved termination may be added to the minimum length listed.
MIN. VENT LENGTH*
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust PipingTerminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to table 10.
In some applications which permit the use of several differ
ent sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox' Application Department for assis
tance in sizing vent pipe in these applications.
®
and
NOTE - Exhaust pipe MUST be glued to furnace exhaust
fittings.
NOTE - Exhaust piping should be checked carefully to
make sure there are no sags or low spots.
NOTE - If right side venting option is used, you must include
the elbow at the furnace in the elbow count. If transitioning
to 3” dia pipe, this elbow equates to 20' of equivalent vent
length for all models.
Use the following steps to correctly size vent pipe diameter.
Piping Size Process
What is the
furnace capacity?
1
045, 070, 090,
110 or 135?
Which style termination
2
being used?
Standard or concentric?
See table 5.
Which needs
3
most elbows?
Intake or
exhaust?
How many elbows?
Count all elbows inside
4
and outside house.
Desired pipe size?
5
6
2”, 2-1/2”, 3”
What is the altitude of
the furnace installation?
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups
and may block the terminations.
NOTE - It is acceptable to use any pipe size which fits within
the guidelines allowed in table 7.
NOTE toward unit. A minimum of 1/4” (6mm) drop for each 12”
(305mm) of horizontal run is mandatory for drainage.
All horizontal runs of exhaust pipe must slope back
Page 18
Use table 7 or 9 to find
max intake or exhaust pipe
7
length. Includes all vent
pipe and elbows inside
and outside the house.
FIGURE 24
Page 19
Maximum Allowable Intake or Exhaust Vent Length
TABLE 7
Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
FIGURE 25
INTAKE
EXHAUST
TOP VIEW
Pipe size determined in table 7.
TYPICAL INTAKE PIPE CONNECTIONS
2”
TRANSITION
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Intake pipe and exhaust pipe must be the same diameter.
2”
3”
*2”
2”
*2”
2”
or
TRANSITION
*2”
2”
3”
INTAKE
FIGURE 26
EXHAUST
TOP VIEW
Page 20
Page 21
TYPICAL EXHAUST CONNECTIONS WITH RIGHT SIDE VENT OPTION
Pipe Length
4” Maximum
2”
Street Ell
(Not Furnished)
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
(Not Furnished)
2”
NOTE Intake pipe and exhaust pipe must be the same diameter.
2”
TRANSITION
3
”
*2”
FIGURE 27
TYPICAL AIR INTAKE PIPE CONNECTIONS WITH RIGHT SIDE VENT OPTION
Plate
(Furnished)
TOP VIEW
3
2”
*2”
Street Ell
(Not Furnished)
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE Intake pipe and exhaust pipe must be the same diameter.
2”
TRANSITION
”
*2”
(Furnished)
FIGURE 28
Plate
TOP VIEW
Page 21
Page 22
Intake Piping
The EL296DFV furnace may be installed in either direct
vent or non-direct vent applications. In non-direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered. Guidelines listed in Combustion, Dilution and
Ventilation Air section must be followed.
Follow the next two steps when installing the unit in DirectVent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
1 - Use cement or a sheet metal screw to secure the in
take pipe to the inlet air connector.
2 - If intake air is drawn from a ventilated crawlspace (fig
ure 30) or ventilated attic (figure 29) the exhaust vent
length must not exceed those listed in table 9. If 3” di
ameter pipe is used, reduce to 2” diameter pipe to ac
commodate the debris screen.
3 - Route piping to outside of structure. Continue with
installation following instructions given in general
guide lines for piping terminations and intake and ex
haust piping terminations for direct vent sections. Re
fer to table
7 for pipe sizes.
CAUTION
If this unit is being installed in an application with
combustion air coming in from a space serviced by
an exhaust fan, power exhaust fan, or other device
which may create a negative pressure in the space,
take care when sizing the inlet air opening. The in
let air opening must be sized to accommodate the
maximum volume of exhausted air as well as the
maximum volume of combustion air required for
all gas appliances serviced by this space.
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl space)
(Field Provided)
EQUIPMENT IN CONFINED SPACE
Furnace
Coupling or
3 in. to 2 in.
Transition
12 in.(305mm)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
Above crawl
space floor)
* See table 9 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
2
per 1.17kW) per
FIGURE 29
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
EQUIPMENT IN CONFINED SPACE
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
*Intake Debris
Screen
(Provided)
Furnace
Page 22
* See table 9 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
hour of the total input rating of all equipment in the enclosure.
2
per 1.17kW) per
FIGURE 30
Page 23
TYPICAL AIR INTAKE PIPE CONNECTIONS
NON−DIRECT VENT APPLICATIONS
AIR
INTAKE
SCREEN
(Provided)
NOTE - Air intake screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
FIGURE 31
Follow the next two steps when installing the unit in Non‐
Direct Vent applications where combustion air is takenfrom indoors and flue gases are discharged outdoors.
1 - Use field-provided materials and the factory-provided
air intake screen to route the intake piping as shown in
figure 31. Maintain a minimum clearance of 3” (76mm)
around the air intake opening. The air intake opening
(with the protective screen) should always be directed
forward, or sideways.
2 - Use cement to secure the intake pipe to the connector,
if desired.
General Guidelines for Vent Terminations
In Non‐Direct Vent applications, combustion air is taken
from indoors and the flue gases are discharged to the out
doors. The EL296DFV is then classified as a non‐direct
vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the out
doors. The EL296DFV is then classified as a direct vent,
Category IV gas furnace.
In both Non‐Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the
absence of local codes, refer to the current National Fuel
Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current
CSA-B149 Natural Gas and Propane Installation Codes in
Canada for details.
Position termination according to location given in figure 33
or 34. In addition, position termination so it is free from any
obstructions and 12” above the average snow accumula
tion.
At vent termination, care must be taken to maintain
protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective
coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8m) of an outdoor AC unit because
the condensate can damage the painted coating.
NOTE - See table 8 for maximum allowed exhaust pipe
length without insulation in unconditioned space during
winter design temperatures below 32°F (0°C). If required
exhaust pipe should be insulated with 1/2” (13mm) Arma
flex or equivalent. In extreme cold climate areas, 3/4”
(19mm) Armaflex or equivalent may be necessary. Insula
tion must be protected from deterioration. Armaflex with
UV protection is permissable. Basements or other en
closed areas that are not exposed to the outdoor ambient
temperature and are above 32 degrees F (0°C) are to be
considered conditioned spaces.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze-ups and
may block the terminations.
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches
(305mm).
Page 23
Page 24
Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
TABLE 8
Winter Design Temperatures Two - Stage High Efficiency Furnace
Winter Design
Temperatures
32 to 21
(0 to -6)
1
°F (°C)
Vent Pipe
Diameter
045070090110
PVC
2
PPPVC
2 in.2118333046423030
2-1/2 in.16N/A26N/A37N/A36N/A
Unit Input Size
2
PPPVC
2
PPPVC
2
PP
3 in.1212212130302929
2 in119191728252724
20 to 1
(-7 to -17)
2-1/2 in.7N/A14N/A21N/A20N/A
3 in.N/AN/A9916161414
2 in.64121019161815
0 to -20
(-18 to -29)
2-1/2 in.N/AN/A7N/A13N/A12N/A
3 in.N/AN/AN/AN/A8877
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2
Poly-Propylene vent pipe (PP) by Duravent and Centrotherm.
NOTE - Concentric terminations are the equivalent of 5' and should be considered when measuring pipe length.
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the
maximum allowable intake or exhaust vent length listed in table 7 or 9 which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure32.
Conditioned
Space
Conditioned
Space
FIGURE 32
Pipe Insulation
Unconditioned
Space
Exhaust
Pipe
Intake
Pipe
Page 24
Page 25
Maximum Allowable Exhaust Vent Length Using Ventilated Attic or Crawl Space For Intake Air in Feet
TABLE 9
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
FOR NON-DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
B =
Clearance to window or
door that may be opened
C =
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
D =
located above the terminal within a
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
* 12”
* Equal to or greater than soffit depth.
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air
supply inlet to building or the com
bustion air inlet to any other ap
* Equal to or greater than soffit depth.
* No minimum to outside corner* No minimum to outside corner
**
3 feet (.9m) within a height 15 feet (4.5m)
*
above the meter / regulator assembly
* 3 feet (.9m)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
pliance
K =
L =
Clearance to mechanical air sup
ply inlet
Clearance above paved sidewalk or
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)†
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
M =
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open
on a minimum of two sides beneath the floor. Lennox recommends
avoiding this location if possible.
*12 inches (305mm)‡
FIGURE 33
H
B
Fixed
Closed
A
J
I
M
AREA WHERE TERMINAL
IS NOT PERMITTED
1
Canadian Installations
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these instal
lation instructions.”
K
2
Page 26
Page 27
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap
pliances > 50,000 Btuh (15kw)
C =
Clearance to permanently
* 12”
closed window
D =
Vertical clearance to ventilated soffit
located above the terminal within a
* Equal to or greater than soffit depth
horizontal distance of 2 feet (610mm)
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non-mechanical air
supply inlet to building or the com
bustion air inlet to any other ap
pliance
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
*
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap
pliances > 50,000 Btuh (15kw)
K =
Clearance to mechanical air sup
ply inlet
L =
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of
two sides beneath the floor. Lennox recommends avoiding this location if possible.
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)‡
FIGURE 34
H
B
Fixed
Closed
A
J
I
M
K
AREA WHERE TERMINAL
IS NOT PERMITTED
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these
installation instructions.”
Page 27
Page 28
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE - In Direct Vent installations, combustion air is tak
en from outdoors and flue gases are discharged to out
doors.
NOTE - Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gasses may impinge on the building ma
terial, a corrosion-resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommended.
The shield should be constructed using wood, plastic,
sheet metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
appropriate sealant. See figure 43.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In at
tic or closet installations, vertical termination through the
roof is preferred. Figures 35 through 42 show typical ter
minations.
1 - Vent terminations are not required to be in the same
pressure zone. You may exit the intake on one side of
the structure and the exhaust on another side (figure
36). You may exit the exhaust out the roof and the in
take out the side of the structure (figure 37).
2 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il
lustrations). Maximum separation is 3” (76mm) on roof
terminations and 6” (152mm) on side wall termina
tions.
NOTE - When venting in different pressure zones, the
maximum separation requirement of intake and ex
haust pipe DOES NOT apply.
3 - On roof terminations, the intake piping should termi
nate straight down using two 90° elbows (See figure
35).
4 - Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust pip
ing at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
See table 10.
TABLE 10
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL296
MODEL
*045 and *070
*0902” (51mm)
1102” (51mm)
*EL296DFV-045, -070 and -090 units with the flush-mount termina
tion must use the 1-1/2”accelerator supplied with the kit.
Termination
Pipe Size
1-1/2” (38mm)
5 - On field-supplied terminations for side wall exit, ex
haust piping may extend a maximum of 12 inches
(305mm) for 2” PVC and 20 inches (508mm) for 3”
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See figure 43.
NOTE - Care must be taken to avoid recirculation of
exhaust back into intake pipe.
6 - On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
figure 43.
Inches(mm)
8” (203mm) MIN
12” (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
3”(76mm) MAX.
(15F75 or 44J41)
SIZE TERMINATION
PIPE PER TABLE 10.
UNCONDITIONED
ATTIC SPACE
FIGURE 35
Exiting Exhaust and Intake Vent
(different pressure zone)
Inlet Air
Exhaust
Pipe
Furnace
(Minimum 12in.
(305 mm) Above
grade or snow
accumulation)
FIGURE 36
Exiting Exhaust and Intake Vent
(different pressure zone)
Roof T
erminated
Exhaust Pipe
Inlet Air
Furnace
(Minimum 12in.
(305 mm) Above
grade or snow
accumulation)
FIGURE 37
Page 28
Page 29
7 - If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob
structions, piping must be supported. At least one
bracket must be used within 6” from the top of the el
bow and then every 24” (610mm) as shown in figure
43, to prevent any movement in any direction. When
exhaust and intake piping must be run up an outside
wall, the exhaust piping must be terminated with pipe
sized per table 10.The intake piping may be equipped
with a 90° elbow turndown. Using turndown will add 5
feet (1.5m) to the equivalent length of the pipe.
8 - A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 40.
1-1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for EL296DFV045P36B-
& 070P36B
12” (305mm)
Minimum
Above Average
Snow
Accumulation
INTAKE
FLASHING
(Not Furnished)
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
CLAMP
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIGURE 38
EXHAUST
VENT
5”
(127mm)
5-1/2”
(140mm)
12”
(305mm)
INTAKE
AIR
18” MAX.
(457mm)
Front View
EXHAUST VENT
12” (305mm) Min.
above grade or
Inches (mm)
INTAKE
average snow ac
cumulation.
AIR
optional intake elbow
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
FIGURE 40
2” EXTENSION FOR
2” PVC PIPE
1” EXTENSION FOR
3” PVC PIPE
4''
FURNACE
INTAKE
PIPE
(all-045, -070 and -090 units)
FLUSH-MOUNT SIDE WALL TERMINATION KIT
51W11 (US) or 51W12 (Canada)
FURNACE
EXHAUST
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
1-1/2” ACCELERATOR
FIGURE 41
EL296DFV DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
1-1/2” (38mm) accelerator
FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE
SIZE TO TERMINATION
EXHAUST
AIR
INTAKE
AIR
(Not Furnished)
OUTSIDE
WALL
CLAMP
provided on 71M80 &
EL296DFV045P36B- &
INTAKE
AIR
INTAKE
AIR
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIGURE 39
44W92 kits for
070P36B
EXHAUST
AIR
12” (305mm) Min.
above grade or
average snow ac
cumulation.
GRADE
Page 29
8” - 12”
(203mm - 305mm)
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
*SIZE TERMINATION
PIPE PER TABLE 10.
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
3” - 8”
(76mm203mm)
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8”
(76mm-
203mm)
ALTERNATE
INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
FIGURE 42
Page 30
NOTE − FIELD−PROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
C1
* WALL
SUPPORT
C1
REDUCER MAY BE
TO TERMINATION
A
E
D
B
STRAIGHT
APPPLICATION
D
B
A
EXTENDED
APPLICATION
FIELD FABRICATED WALL TERMINATION
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal
separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
distance from top of each
pipe (intake/exhaust)
D
B
See venting table 7 for maximum venting lengths
with this arrangement.
* Use wall support every 24” (610 mm). Use two
wall supports if extension is greater than
24” (610 mm) but less than 48” (1219 mm).
NOTE − One wall support must be within 6” (152 mm)
from top of each pipe (intake and exhaust) to prevent
movement in any direction.
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
3
B
C
Intake
Elbow
Do not use an accelerator in applications that include an exhaust termination tee.
The accelerator is not required.
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield
(24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield
is recommended. The shield should be constructed using wood, sheet metal or other suitable material.
All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust
away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
A
Front View of
Intake and Exhaust
Intake
Exhaust
D
3
Exhaust
A− Clearance above
grade or average snow
accumulation
B− Horizontal
separation between
intake and exhaust
C− Minimum from
end of exhaust to
inlet of intake
D− Exhaust pipe length
E− Wall support distance
from top of each pipe
(intake/exhaust)
Vent Pipe
12” (305 mm) Min. 12” (305 mm) Min.
6” (152 mm) Min.
24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min.
16” (405 mm) Max.
6” (152 mm) Max.
3” (76MM)
Vent Pipe
6” (152 mm) Min.
24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min.
20” (508 mm) Max.
6” (152 mm) Max.
FIGURE 43
Page 30
Page 31
Details of Exhaust Piping Terminations for Non‐Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is pre
ferred. Figures 45 through 44 show typical terminations.
1 -Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
table 10.The specified pipe size ensures proper ve
locity required to move the exhaust gases away from
the building.
2 -On field supplied terminations for side wall exit, ex
haust piping may extend a maximum of 12 inches
(305mm) for 2” PVC and 20 inches (508mm) for 3”
(76mm) PVC beyond the outside wall.
3 -If exhaust piping must be run up a side wall to posi
tion above snow accumulation or other obstructions,
piping must be supported every 24 inches (610mm).
When exhaust piping must be run up an outside wall,
any reduction in exhaust pipe size must be done after
the final elbow.
4 - Distance between exhaust pipe terminations on mul
tiple furnaces must meet local codes.
12” (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 45
SIZE TERMINATION
PIPE PER TABLE
10.
UNCONDITIONED
ATTIC SPACE
EL296DFV NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 10.
3” - 8”
(76mm-
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
METAL TOP
INSULATE
TO FORM
SEAL
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
203mm)
SHEET
PLATE
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8”
(76mm-
203mm)
EXTERIOR
PORTION OF
CHIMNEY
FIGURE 44
Page 31
Page 32
Condensate Piping
This unit is designed for either right‐ or left‐side exit of con
densate piping. Refer to figures 46 and 47 for condensate
trap locations.
NOTE - If necessary the condensate trap may be installed
up to 5’ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4” per ft. toward trap.
CONDENSATE TRAP AND PLUG LOCATIONS
Trap
(same
on right
side)
Plug
(same on left side)
1-1/2 in.
FIGURE 46
CONDENSATE TRAP LOCATION
(shown with right side exit of condensation)
1 - Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length of
PVC pipe required to reach available drain.
2 - Use a large flat head screw driver or a 1/2” drive socket
extension and remove plug (figure 46) from the cold
end header box at the appropriate location on the side
of the unit. Install provided 3/4 NPT street elbow fitting
into cold end header box. Use Teflon tape or appropri
ate pipe dope.
NOTE - Cold end header box drain plugs are factory in
stalled. Check the unused plug for tightness to prevent
leakage.
3 - Install the cap over the clean out opening at the base
of the trap. Secure with clamp. See figure 52.
4 - Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig
ure 52. Route the condensate line to an open drain.
5 - Figure 49 shows the furnace and evaporator coil using
a separate drain. If necessary, the condensate line
from the furnace and evaporator coil can drain togeth
er. See figures 50 and 51. The field provided vent must
be a minimum 1” to a maximum 2” length above the
condensate drain outlet connection.
NOTE - If necessary the condensate trap may be installed
up to 5 feet away from the furnace. Piping from furnace
must slope down a minimum of 1/4” per ft. toward trap.
NOTE - Appropriately sized tubing and barbed fitting may
be used for condensate drain. Attach to the drain on the
trap using a hose clamp. See figure 48.
Field Provided Drain Components
Trap can be installed a maximum
of 5ft. from furnace (*PVC only)
Field Provided Vent
1” min. 2” max. above
condensate drain.
1” min.
2” max.
5’ max.
to drain
*Piping from furnace must slope down a minimum of
1/4” per ft. toward trap.
FIGURE 47
Elbow
Barbed Fitting
Tubing
Hose Clamp
FIGURE 48
Page 32
Page 33
6 - If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start-Up section.
EL296DFV with Evaporator
Coil Using a Common Drain
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heat cable kit is avail
able from Lennox in various lengths; 6 ft. (1.8m) - kit
no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft.
(15.2m) - kit no. 26K70.
EL296DFV with Evaporator Coil
Using a Separate Drain
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate
Drain Connection
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate Drain
Connection
Evaporator Drain
Line
(vent required)
FIGURE 50
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
Field Provided Vent
1” min. 2” max. above
condensate drain.
Evaporator Drain Line
(vent required)
FIGURE 49
IMPORTANT
When combining the furnace and evaporator
coil drains together, the A/C condensate drain
outlet must be vented to relieve pressure in or
der for the furnace pressure switch to operate
properly.
FurnaceCondensate
DrainConnection
Optional
Drain
FIGURE 51
CAUTION
Donot use copper tubing or existing copper
condensate lines for drain line.
Page 33
Page 34
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
Optional Condensate Drain Connection
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow
3/4 inch PVC
(not furnished)
Condensate Drain
Connection In Unit
90° Street Elbow
3/4 inch PVC
( furnished)
To
Trap
Optional Drain Piping FromTrap
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
1 (25 mm) Min.
2 (50 mm) Max.
Above Top Of
Condensate Drain
Connection In Unit
Elbow 3/4 inch PVC
90°
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
V
ent
5 Feet
Maximum
3/4 inch PVC Pipe
(Not Furnished)
Coupling 3/4 inch slip X slip
Drain Trap
Assembly
(Furnished)
Condensate Drain
Connection In Unit
(Not Furnished)
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
DrainTrap Assembly
(Furnished)
7
(178)
Drain Trap
Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
T
o
Coupling 3/4 inch slip X slip
Drain
DrainTrap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
(Not Furnished)
Vent
1/2 inch
Condensate Drain
Connection In Unit
To
Drain
DrainTrap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
Vent
3/4 inch
Condensate Drain
Connection In Unit
To
Drain
FIGURE 52
Page 34
Page 35
Gas Piping
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
WARNING
Do not over torque (800 in-lbs) or under torque (350
in-lbs) when attaching the gas piping to the gas
valve.
1 - Gas piping may be routed into the unit through either
the left‐ or right‐hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
figure 54. The maximum torque is 800 in lbs and mini
mum torque is 350 in lbs when when attaching the gas
piping to the gas valve.
2 - When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be con
sidered to avoid excessive pressure drop. Table 11
lists recommended pipe sizes for typical applications.
NOTE - Use two wrenches when connecting gas pip
ing to avoid transferring torque to the manifold.
3 - Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or eleva
tor shafts. Center gas line through piping hole. Gas
line should not touch side of unit. See figures 54.
4 - Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, ev
ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers
or straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 60.
6 - In some localities, codes may require installation of a
manual main shut‐off valve and union (furnished by in
staller) external to the unit. Union must be of the
ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro
leum gases.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and field-installed) for gas leaks. Use
a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system
by closing its individual manual shut‐off valve during any
pressure testing of the gas supply system at pressures lessthan or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8” N.P.T. PLUGGED TAP
FIGURE 53
CAP
FURNACE
ISOLATE
GAS VALVE
IMPORTANT
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 53. Gas
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa).
WARNING
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to cer
tain metals. Carefully rinse piping thoroughly after
leak test has been completed.
FIRE OR EXPLOSION HAZARD
Page 35
Page 36
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Tap Shown)
GROUND
JOINT
UNION
Left Side Piping
(Standard)
AUTOMATIC
GAS VALVE
AUTOMATIC
GAS VALVE
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Tap
Shown)
GROUND
JOINT
UNION
DRIP LEG
FIELD
PROVIDED
DRIP LEG
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
AND INSTALLED
FIGURE 54
GAS PIPE CAPACITY - FT
TABLE 11
Nominal
Iron Pipe
Size
inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
NOTE - Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Electrostatic discharge can affect elec
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be properly
grounded in accordance with national
and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this
product may result in a fire, causing property dam
age, severe injury or death. Use copper wire only
with this product.
The unit is equipped with a field make-up box on the left
hand side of the cabinet. The make-up box may be moved
to the right side of the furnace to facilitate installation. If the
make-up box is moved to the right side, clip the wire ties
that bundle the wires together. The excess wire must be
pulled into the blower compartment. Secure the excess
wire to the existing harness to protect it from damage.
EXTERIOR MAKE-UP BOX
(FIELD PROVIDED RIGHT SIDE)
MAKE-UP
BOX
OUTSIDE
CABINET
Right Side
FIGURE 55
Refer to figure 58 for unit schematic and field wiring. See
figures 56 and 57 for icomfort Wi-Fi
communicating applications. Table 13 shows DIP switch
and on-board link settings for non-communicating thermo
stat applications. Typical wiring schematic is shown in fig
ure 58.
®
thermostat wiring in
CAUTION
Failure to use properly sized wiring and circuit
breaker may result in property damage. Size wiring
and circuit breaker(s) per Product Specifications
bulletin (EHB) and unit rating plate.
The power supply wiring must meet Class I restric
tions. Protected by either a fuse or circuit breaker, se
lect circuit protection and wire size according to unit
nameplate.
NOTE - Unit nameplate states maximum current draw.
Maximum over-current protection allowed is shown in table
12.
TABLE 12
EL296DFV Model
045V36B, 070V48B15
090V60C, 110V60C20
Holes are on both sides of the furnace cabinet to facili
tate wiring.
Install a separate (properly sized) disconnect switch
near the furnace so that power can be turned off for
servicing.
Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for
servicing at a later date. Remove the blower access
panel to check the length of the wire.
Complete the wiring connections to the equipment.
Use the provided unit wiring diagram and the field wir
ing diagrams shown in table 13 and figure 58. Use
18-gauge wire or larger that is suitable for Class II ra
ting for thermostat connections.
Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70). A green
ground wire is provided in the field make-up box.
NOTE - The EL296DFV furnace contains electronic
components that are polarity sensitive. Make sure
that the furnace is wired correctly and is properly
grounded.
One line voltage “ACC” 1/4” spade terminal is provided
on the furnace integrated control. Any electronic air
cleaner or other accessory rated up to one amp can be
connected to this terminal with the neutral leg of the cir
cuit being connected to the one of the provided neutral
terminals. See figure 59 for control configuration. This
terminal is energized when the indoor blower is operat
ing.
An unpowered, normally open (dry) set of contacts
with a 1/4” spade terminal “HUM” are provided for hu
midifier connections and may be connected to 24V or
120V. Any humidifier rated up to one amp can be con
Maximum Over-Current
Protection (Amps)
Page 37
Page 38
nected to these terminals. In 120V humidifier applica
tions the neutral leg of the circuit can be connected to
one of the provided neutral terminals. This terminal is
energized in the heating mode.
Install the room thermostat according to the instruc
tions provided with the thermostat. See table 13 for
field wiring connections in varying applications. If the
furnace is being matched with a heat pump, refer to the
instruction packaged with the dual fuel thermostat.
Thermostat Selection
CAUTION
Field wiring for both communicating and non-com
municating applications is illustrated in diagrams,
which begin on Page 39.
Non-Communicating
In non-communicating applications the EL296DFV is de
signed to operate in a SINGLE-STAGE mode or TWOSTAGE mode using a conventional thermostat.
For optimal performance in non-communicating applica
tions, Lennox recommends use of a ComfortSense
high quality electronic digital thermostat or any other with
adjustable settings for 1st stage / 2nd stage on / off differen
tials and adjustable stage timers.
Communicating
In communicating applications the icomfort Wi-Fi® thermo
stat must be used. Refer to the instructions provided with
the thermostat for installation, set-up and operation. In
communicating system all unused thermostat wire in the
wire bundle needs to be terminated inside and out. The ex
tra wires can terminate on the 'C” terminal of the icomfort
communication terminal strip. (RSBus). Using an addition
al wire come off ”C” terminal and wire nut all the extra wires
together. Termination on the outdoor control must match
the indoor control.
®
7000
Indoor Blower Speeds
Non-Communicating
When the thermostat is set to “FAN ON,” the indoor
blower will run continuously at a field selectable per
centage of the second-stage cooling speed when there
is no cooling or heating demand. The factory default
setting is 38% of cool speed.
When the EL296DFV is running in the heating mode,
the indoor blower will run on the heating speed desig
nated by the positions of DIP switches 11, 12 and 13.
When there is a cooling demand, the indoor blower will
run on the cooling speed designated by the positions
of DIP switches 5 and 6. First stage cooling will run at
70% cool speed.
Communicating
NOTE - When the EL296DFV is used with icomfort
®
Touch
thermostat, proper indoor blower speed selec
tions are made by the communicating thermostat.
When the thermostat is set to “FAN ON,” the indoor
blower will run at setting determined during system
configuration.
When there is a heating demand the fan will run on
heating speeds for firing rate.
When there is a cooling demand, the fan will run on the
first stage and second stage cooling speed set using
the icomfort Wi-Fi
®
thermostat in the installer setup
mode. The factory default is based upon 400 CFM a
ton.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
The furnace requires 120 volts (Range: 102 volts to
132 volts)
The furnace operates at 60 Hz +
5% (Range: 57 Hz to
63 Hz)
The furnace integrated control requires both correct
polarity and proper ground. Both polarity and proper
grounding should be checked before attempting to op
erate the furnace on either permanent or temporary
power
Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion)
Page 38
Page 39
®
iComfort
Thermostat with a Non-
Communicating Outdoor Unit
iComfort® Thermostat with an
iComfortt-ENABLED Outdoor Unit
icCmforti® Thermostat
iComfort®-Enabled Indoor Furnace
Non-Communicating Outdoor Air Conditioner
icomfort®-
ENABLED
OPTIONAL
DISCHARGE
AIR SENSOR
iComfort®
THERMOSTAT
CLIP ON-BOARD LINK
W915 (Y1 TO Y2) FOR
TWO-STAGE OPERATION
FURNACE
NON-COMMUNICATING
OUTDOOR AIR
CONDITIONING UNIT -
1 OR 2 STAGE
OPTIONAL
OUTDOOR
AIR SENSOR
iComfort® Thermostat
iComfort®-Enabled Indoor Furnace
iComfort-Enabled Outdoor Air Conditioner or Heat Pump
icomfort®ENABLED
FURNACE
OPTIONAL
DISCHARGE
AIR SENSOR
OPTIONAL
OUTDOOR
AIR SENSOR
iComfort®
THERMOSTAT
®
iComfort
OUTDOOR AIR CONDITIONING
OR HEAT PUMP UNIT
- ENABLED
Outdoor Unit
Indoor Unit
Controller
Single wire to
Single wire to
terminal C
Unused wires
terminal C
Unused wires
Communicating systems using the IComfort® thermostat require four thermo
stat wires between the thermostat and the furnace/air handler control and four
wires between the outdoor unit and the furnace/air handler control. When a
thermostat cable with more than four wires is used, the extra wires must be
properly connected to avoid electrical noise. The wires must not be left discon
nected.
Use wire nuts to bundle the four unused wires at each end of the cable. A
single wire should then be connected to the indoor unit end of the wire bundle
and attached to the “C” terminals as shown above.
FIGURE 56
iComfort®
THERMOSTAT
Page 39
Page 40
Optional Accessories for use with any iComfort Touch® System
NOTE: IComfort® THERMOSTAT SENSES HUMIDITY & CON
TROLS HUM CONTACTS TO CYCLE HUMIDIFIER BASED ON
DEMAND. NO OTHER CONTROL OR HUMIDISTAT REQUIRED.
OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH HUMIDI
FIER (IF NOT ALREADY IN THE SYSTEM FOR OTHER FUNC
TIONS. BUILT INTO ALL iComfort by Lennox®OUTDOOR UNITS).
120V CONNECTIONS
“HUM” CONTACT IS
CLOSED ANYTIME
HUMIDITY DEMAND
IS PRESENT
icomfort® ENABLED
Discharge Air Sen
sor (Required for
even heat)
THERMOSTAT
EL296DFV FURNACE
®
IComfort
RSBus
Maximum total
length of all connec
tions on the RSBus
is limited to 1500ft.
Wire gauge of
RSBus wire is 18.
®
iComfort
ENABLED OUTDOOR AIR
CONDITIONING OR HEAT
PUMP UNIT
ENABLED
®
icomfort
EL296DFV FURNACE
(POWER COMPANY INTERRUPTION SYSTEMS ARE
WIRED SAME AS OVERFLOW SWITCH)
HEPA BYPASS FILTER X2680 HEPA INTERLOCK KIT
PASS INDOOR BLOWER MO
TOR COMMON WIRE
THROUGH CURRENT LOOP.
ENABLED
®
icomfort
EL296DFV FURNACE
SEE HEPA INTERLOCK KIT
FOR INSTALLATION DETAILS
LVCS VENTILATION CONTROL SYSTEM
SEE LVCS VENTILATION
INSTRUCTIONS FOR DAMPER &
SENSOR WIRING
NOTE: 24V UV LIGHT
APPLICATIONS
®
In an iComfort
by Lennox® sys
tem, neither furnace nor air handler
transformer will have adequate VA
to power 24V UV light applications.
An additional transformer for UV
light applications is required.
IComfort
THERMOSTAT
HVAC
EQUIPMENT
STANDARD 1 OR 2 STAGE
AC OR HP UNIT
2 STAGE FURNACE
24V HUMIDIFIER CONNECTIONS
CS 7000
THERMOSTAT
CONVENTIONAL NONCOMMUNICATING
SYSTEM
COMMUNICATING SYSTEM
*24V IN jumper not used in noncommunicating configuration
*24V IN
JUMPER
icomfort® ENABLED
EL296DFV FURNACE
®
DEHUMIDIFIER
CONTROL
RfWGhGsCf
HVAC EQUIP
DH
NON-COMMUNICATING
SYSTEM WIRING
ENABLED
®
icomfort
EL296DFV FURNACE
FIGURE 57
Page 40
CUT R-DS
W914
DS
COMMUNICATING
SYSTEM WIRING
R
Page 41
Thermostat
1 Heat / 1 Cool
NOTE - Use DIP
switch 2 to set
second-stage
heat ON delay.
OFF-7 minutes.
ON-12 minutes.
TABLE 13
EL296 Field Wiring Applications With Conventional Thermostat
DIP Switch Settings and On-Board Links (See figure 59)
DIP Switch 1
Thermostat
Heating
On Board Links Must Be Cut To Select
System Options
Stages
ON
DO NOT CUT ANY
ON-BOARD LINKS
Wiring Connections
S1
T'STAT
*Not required on all units
FURNACE
TERM. STRIP
OUTDOOR
UNIT
*
1 Heat / 2 Cool
NOTE - Use DIP
switch 2 to set
second-stage
heat ON delay.
OFF-7 minutes.
ON-12 minutes.
1 Heat / 2 Cool
with t'stat with
humidity control
NOTE - Use DIP
switch 2 to set
second-stage
heat ON delay.
OFF-7 minutes.
ON-12 minutes.
ON
ON
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
S1
T'STAT
*Not required on all units
S1
T'STAT
*Not required on all units
FURNACE
TERM. STRIP
*
FURNACE
TERM. STRIP
o
OUTDOOR
UNIT
OUTDOOR
UNIT
*
Page 41
Page 42
EL296 Field Wiring Applications With Conventional Thermostat (Continued)
DIP Switch Settings and On-Board Links (See figure 59)
DIP Switch 1
Thermostat
Thermostat
Heating
Stages
2 Heat / 2 CoolOFF
TABLE 13
On Board Links Must Be Cut To Select
System Options
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
Wiring Connections
S1
T'STAT
*Not required on all units
FURNACE
TERM. STRIP
OUTDOOR
*
UNIT
2 Heat / 2 Cool
with t'stat with
humidity control
2 Heat / 1 Cool
with t'stat with
humidity control
OFF
OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
S1
T'STAT
*Not required on all units
S1
T'STAT
*Not required on all units
FURNACE
TERM. STRIP
o
FURNACE
TERM. STRIP
o
OUTDOOR
UNIT
*
OUTDOOR
UNIT
*
2 Heat / 1 CoolOFF
DO NOT CUT ANY
ON-BOARD LINKS
Page 42
S1
T'STAT
*Not required on all units
FURNACE
TERM. STRIP
OUTDOOR
UNIT
*
Page 43
Thermostat
Dual Fuel
Single Stage
Heat Pump
ComfortSense
thermostat w/
dual fuel capa
bilities
Capable of 2
stage gas heat
control
TABLE 13
EL296 Field Wiring Applications With Conventional Thermostat (Continued)
DIP Switch Settings and On-Board Links (figure 59)
DIP Switch 1
Thermostat
Heating
On Board Links Must Be Cut To Select
System Options
Wiring Connections
Stages
FURNACE
TERM. STRIP
OFF
CUT ON-BOARD LINK
W951
HEAT
PUMP
T'STAT
H
L
Y2
D
B
HEAT PUMP
67M41*
L
Y
Y2
T
T
Dual Fuel
Two Stage
Heat Pump
ComfortSense
OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
T'STAT
H
FURNACE
TERM. STRIP
HEAT PUMP
67M41*
thermostat w/
dual fuel capa
bilities
Capable of 2
stage gas heat
control
CUT ON-BOARD LINK
W951
HEAT
PUMP
Y2
D
L
B
T
T
outdoor
sensor
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the EL296
integrated control.
outdoor
sensor
L
Y2
out blue
Page 43
Page 44
Thermostat
Dual Fuel
Single Stage
Heat Pump
ComfortSense
thermostat w/
dual fuel capa
bilities
Capable of 2
stage gas heat
control w/dehu
midification
control
TABLE 13
EL296 Field Wiring Applications With Conventional Thermostat (Continued)
DIP Switch Settings and On-Board Links (figure 59)
DIP Switch 1
Thermostat
Heating
On Board Links Must Be Cut To Select
System Options
Wiring Connections
Stages
FURNACE
TERM. STRIP
OFF
CUT ON-BOARD LINK
W951
HEAT
PUMP
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
T'STAT
H
L
Y2
D
B
HEAT PUMP
67M41*
L
Y
Y2
T
T
Dual Fuel
Two Stage
Heat Pump
ComfortSense
thermostat w/
dual fuel capa
bilities
Capable of 2
stage gas heat
control w/dehu
midification
OFF
CUT ON-BOARD LINK
W915
2 STAGE
COMPR
CUT ON-BOARD LINK
W951
HEAT
PUMP
CUT ON-BOARD LINK
W914
DEHUM
OR
HARMONY
T'STAT
H
L
Y2
D
B
T
T
FURNACE
TERM. STRIP
Y2
HEAT PUMP
67M41*
out blue
* Connect W1 to W1 ONLY if using defrost tempering kit 67M41
NOTE - Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the EL296
integrated control.
outdoor
sensor
L
Y2
outdoor
sensor
Page 44
Page 45
EL296DFV Schematic Wiring Diagram
FIGURE 58
Page 45
Page 46
Integrated Control
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
HUM
LINE 1
ACC
HS/ CAI
INDOOR
BLOWER
CONNECTOR
NEUTRAL
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
icomfortt
COMMUNICATING
OUTDOOR
EQUIPMENT
TB84
icomfortt
COMMUNICATING
INDOOR
THERMOSTAT
I + I -CRI + I -
R
TB82, future use
I+ = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
TB83 icomfortt Communicating Outdoor Equipment
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAXC COMMON
TB84 icomfortt Communicating Indoor Thermostat
R = 24VAC
I + = DATA HIGH CONNECTION
I - = DATA LOW CONNECTION
C = 24VAXC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
C
W1 W2 GY2Y1
NON-COMMUNICATING
24V TERMINALS
12 PIN LOW
VOLTAGE
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O
HEAT PUMP
W914 R TO DS
DEHUM OR
CC
RDHLODS
HARMONY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE T/STAT
W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
REVERSING VALVE
THERMOSTAT ONLY
.............
FIGURE 59
Page 46
Page 47
Integrated Control DIP Switch Settings Con
ventional Thermostat (non-communicating)
EL296DFV units are equipped with a two-stage, variable
speed integrated control. This control manages ignition
timing, heating mode fan off delays and indoor blower
speeds based on selections made using the control dip
switches and jumpers. The control includes an internal
watchguard feature which automatically resets the ignition
control when it has been locked out. After one hour of con
tinuous thermostat demand for heat, the watchguard will
break and remake thermostat demand to the furnace and
automatically reset the control to relight the furnace.
Note: All icomfortt settings are set at the icomfort Wi-Fi
thermostat. See icomfortt installation instruction. In icom
fortt communication system all DIP switch and clippable
link settings are ignored. For conventional thermostats pro
ceed with DIP switch and clippable link settings as outlined
in the following.
Heating Operation DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory-positioned for use with a twostage thermostat. If a single-stage thermostat is to be used,
the DIP switch must be repositioned.
Select “OFF” for two-stage heating operation con
trolled by a two-stage heating thermostat (factory set
ting);
b - Select “ON” for two-stage heating operation con
trolled by a single-stage heating thermostat. This set
ting provides a timed delay before second-stage heat
is initiated.
Switch 2 -- Second Stage Delay (Used with SingleStage Thermostat Only) -- This switch is used to deter
mine the second stage on delay when a single-stage ther
mostat is being used. The switch is factory-set in the OFF
position, which provides a 7-minute delay before secondstage heat is initiated. If the switch is toggled to the ON
position, it will provide a 12-minute delay before secondstage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLEstage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on
delay of 30 seconds is not adjustable. The blower-off delay
(time that the blower operates after the heating demand
has been satisfied) can be adjusted by moving switches 3
and 4 on the integrated control. The unit is shipped from the
factory with a blower-off delay of 90 seconds. The blower
off delay affects comfort and is adjustable to satisfy individ
ual applications. Adjust the blower off delay to achieve a
supply air temperature between 90° and 110°F at the exact
moment that the blower is de-energized. Longer off delay
settings provide lower supply air temperatures; shorter set
tings provide higher supply air temperatures.Table 14 pro
vides the blower off timings that will result from different
switch settings.
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
60OnOff
90 (Factory)OffOff
120OffOn
180OnOn
Indoor Blower Operation DIP Switch Settings
®
Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches posi
tioned for high speed (4) indoor blower motor operation
during the cooling mode. Table 15 provides the cooling
mode blower speeds that will result from different switch
settings. Switches 5 and 6 set the blower cfm for secondstage cool. The integrated control automatically ramps
down to 70% of the second-stage cfm for first-stage cfm.
Refer to tables for corresponding cfm values.
Cooling Mode Blower Speeds
Speed
LowOnOn
Medium LowOffOn
Medium HighOnOff
High (Factory)OffOff
Switches 7 and 8 -- Cooling Blower Speed Adjustment
-- The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches
may be positioned to adjust the blower speed by +10% or
-10% to better suit the application. Table 16 below provides
blower speed adjustments that will result from different
switch settings. Refer to tables for corresponding cfm val
ues.
Cooling Blower Speed Adjustment
Adjustment
+10% (approx.)OnOff
Factory DefaultOffOff
-10% (approx.)OffOn
Switches 9 and 10 -- Cooling Mode Blower Speed
Ramping -- Blower speed ramping may be used to en
hance dehumidification performance. The switches are
factory set at option A which has the greatest effect on dehumidification performance. Table 17 provides the cooling
mode blower speed ramping options that will result from
different switch settings. The cooling mode blower speed
ramping options are detailed on the next page.
NOTE - The off portion of the selected ramp profile also ap
plies during heat pump operation in dual fuel applications.
TABLE 14
Switch 3Switch 4
TABLE 15
Switch 5Switch 6
TABLE 16
Switch 7Switch 8
Page 47
Page 48
Cooling Mode Blower Speed Ramping
TABLE 17
Ramping Option
Switch 9Switch 10
A (Factory)OffOff
BOffOn
COnOff
DOnOn
Ramping Option D
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
OFFOFF
Ramping Option A (Factory Selection)
Motor runs at 50% for 30 seconds.
Motor then runs at 82% for approximately 7-1/2 minu
tes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 50% for 30 sec
onds then ramps down to stop.
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COMPRESSOR DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
S Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
OFF
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 45 sec
The switches are factory set to the OFF position which pro
vides factory default heat speed. Refer to table 18 for
switches 11, 12 and 13 that provided the corresponding in
creases or decrease to both high and low heat demand.
TABLE 18
Heating Mode Blower Speeds
Heat Speed
Switch11Switch12Switch
13
Increase 24%OnOnOn
Increase 18%OnOnOff
Increase 12%OnOffOn
Increase 6%OnOffOff
Factory DefaultOffOffOff
Decrease 6%OffOffOn
Decrease 12%OffOnOff
Decrease18%OffOnOn
Switches 14 and 15 -- Continuous Blower Speed --
Table 19 provides continuous blower speed adjustments
that will result from different switch settings.
TABLE 19
Continuous Blower Speed
Continuous
Blower Speed
Switch 14Switch 15
28% of High Cool SpeedOffOn
38% of High Cool Speed
(Factory)
OffOff
70% of High Cool SpeedOnOff
100% of High Cool SpeedOnOn
Page 48
Page 49
On-Board Links
Note: In icomfortt systems with a conventional outdoor
unit (non-communicating), the on-board clippable links
must be set to properly configure the system.
mony III control will be blocked and also lead to control
damage. Refer to table 20 for operation sequence in ap
plications including EL296DFV, a thermostat which fea
tures humidity control and a single-speed outdoor unit.
Table 21 gives the operation sequence in applications with
a two-speed outdoor unit.
On-Board Link W951 Heat Pump (R to O)
On-board link W951 is a clippable connection between ter
WARNING
Carefully review all configuration information pro
vided. Failure to properly set DIP switches, jumpers
and on-board links can result in improper operation!
On-Board Link W914 Dehum or Harmony (R to DS)
On-board link W914, is a clippable connection between ter
minals R and DS on the integrated control. W914 must be
cut when the furnace is installed with either the Harmony
III zone control or a thermostat which features humidity
control. If the link is left intact the PMW signal from the Har
minals R and O on the integrated control. W951 must be cut
when the furnace is installed in applications which include a
heat pump unit and a thermostat which features dual fuel
use. If the link is left intact, terminal “O” will remain ener
gized eliminating the HEAT MODE in the heat pump.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board link W915 is a clippable connection between ter
minals Y1 and Y2 on the integrated control. W915 must be
cut if two-stage cooling will be used. If the Y1 to Y2 link is
not cut the outdoor unit will operate in second-stage cool
ing only.
TABLE 20
OPERATING SEQUENCE
EL296DFV, Non-Communicating Thermostat with Humidity Control Feature and Single-Speed Outdoor Unit
OPERATING
SEQUENCE
System
Condition
NO CALL FOR DEHUMIDIFICATION
Normal Operation1On OnOnAcceptable
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation1On OnOnAcceptable
Dehumidification
Call
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1On OnOnAcceptable
Dehumidification
call
Dehumidification
call ONLY
Step
Jumpers at indoor unit with a single stage outdoor unit
With Condensing unit - Cut W914 (R to DS) on SureLight
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight
Thermostat DemandRelative Humidity
Y1OG
2On OnOnDemand
2On OnOnDemand
1On OnOnDemand
SYSTEM DEMANDSYSTEM RESPONSE
W
1
StatusD
24
VAC
24
VAC
0
VAC
24
VAC
0
VAC
0
VAC
Compres
sor
High100%
High100%
High70%*
High100%
High70%*
High70%*
®
control
®
Blower
CFM
(COOL)
control
Comments
Compressor and indoor
blower follow thermostat
demand
ComfortSense® 7500
thermostat energizes Y1
and de-energizes D on a
call for de-humidification
Dehumidification mode
begins when humidity is
greater than set point
ComfortSense
thermostat
maintain room humidity
setpoint by allowing the
room space to maintain a
cooler room thermostat
setpoint**
®
7500
will try to
Dave Lennox ComfortSense® 7000 thermostat to use for this application - Y2081 4 heat / 2 cool
*Dehumidification blower speed is 70% of COOL speed for all units .
**In Precision mode, ComfortSense
®
7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
Page 49
Page 50
TABLE 21
OPERATING SEQUENCE
EL296DFV, Non-Communicating Thermostat with Humidity Control Feature and Two-Speed Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMANDSYSTEM RESPONSE
Thermostat DemandRelative Humidity
System
Condition
Ste
p
Y1 Y2OG
W1W
2
StatusD
NO CALL FOR DEHUMIDIFICATION
Normal Opera
tion - Y1
Normal Opera
tion - Y2
1OnOnOnAcceptable
2On On OnOnAcceptable
24
VAC
24
VAC
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
Call
1OnOnOnAcceptable
2On On OnOnDemand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
call
Dehumidification
call ONLY
1OnOnOnAcceptable
2On On OnOnDemand
1On On OnOnDemand
24
VAC
0
VAC
0
VAC
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
Call
1On On OnOnAcceptable
2On On OnOnDemand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
call
1OnOnOnAcceptable
2On On OnOnDemand
24
VAC
0
VAC
Compressor
Low70%*
High100%
Low70%*
High70%**
Low70%*
High70%**
High70%**
High100%
High70%**
Low70%*
High70%**
Blower
CFM
(COOL)
Comments
Compressor and indoor
blower follow thermostat
demand
®
ComfortSense
7500
thermostat energizes Y2
and de-energizes D on a
call for de-humidification
Dehumidification mode
begins when humidity is
greater than set point
ComfortSense® 7500
thermostat will try to
maintain room humidity
setpoint by allowing the
room space to maintain
a cooler room thermostat
setpoint***
ComfortSense® 7500
thermostat energizes Y2
and de-energizes D on a
call for de-humidification
Dehumidification mode
begins when humidity is
greater than set point
Dehumidification
call ONLY
1On On OnOnDemand
0
VAC
Jumpers at indoor unit with a two stage outdoor unit
Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2)
With Condensing unit - Cut W914 (R to DS) on SureLight
®
control
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight
Dave Lennox ComfortSense® 7500 thermostat to use for this application - Y2081 4 heat / 2 cool
*Normal operation first stage cooling blower speed is 70% COOL speed.
**Dehumidification blower speed is, reduced to 70% of COOL.
***In Precision mode, ComfortSense
®
7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
Page 50
High70%**
®
control
ComfortSense® 7500
thermostat will try to
maintain room humidity
setpoint by allowing the
room space to maintain
a cooler room thermostat
setpoint***
Page 51
BLOWER DATA
EL296DF045XV36B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24%9101150
+18%8551095
+12%8201040
+6%770990
Factory Default745935
–6%700880
–12%665820
–18%635755
1
Cooling Speed
DIP Switch
Settings
LowMedium-Low Medium-High
+640755850975895105012101360
Factory Default58069578088080596511051250
–54564572079573586510001130
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
tings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 425 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24%10851635
+18%10301525
+12%9501450
+6%9101365
Factory Default8501310
–6%7901225
–12%7401135
–18%6801060
1
Cooling Speed
DIP Switch
Settings
LowMedium-LowMedium-High
+740915105512551110134015751800
Factory Default6608209401120995123014201650
–575735850995880108512901460
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
tings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 425 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24%14251895
+18%13551825
+12%12801740
+6%12151660
Factory Default11601575
–6%10551455
–12%10101365
–18%9501265
1
Cooling Speed
DIP Switch
Settings
LowMedium-LowMedium-High
+11151265140016001600175019702130
Factory Default10051150127514501450163018101975
–8901065115012701270145016451810
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
tings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 425 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24%15352015
+18%14451935
+12%13701855
+6%13001760
Factory Default12201645
–6%11351545
–12%10701420
–18%10001335
1
Cooling Speed
DIP Switch
Settings
LowMedium-LowMedium-High
+10951265139515851585179019902180
Factory Default9651130128514401440163018452005
–8601035113012751275147516551845
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
tings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 425 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.
Do not use this furnace if any part has been under
water. A flood-damaged furnace is extremely dan
gerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a qualified ser
vice technician to inspect the furnace and to replace
all gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace,
if deemed necessary.
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at dis
connect switch.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
BEFORE LIGHTING the unit, smell all around the fur
nace area for gas. Be sure to smell next to the floor be
cause some gas is heavier than air and will settle on the
floor.
The gas valve on the EL296DFV is equipped with a gas
control switch. Use only your hand to move switch. Never
use tools. If the switch will not move by hand, do not try to
repair it. Force or attempted repair may result in a fire or
explosion.
Placing the furnace into operation:
EL296DFV units are equipped with an automatic hot sur
face ignition system. Do not
burners on this furnace. Each time the thermostat calls
for heat, the burners will automatically light. The ignitor
does not get hot when there is no call for heat on these
units.
Priming Condensate Trap
The condensate trap should be primed with water prior to
start-up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 - Follow the lighting instructions to place the unit into op
eration.
2 - Set the thermostat to initiate a heating demand.
3 - Allow the burners to fire for approximately 3 minutes.
4 - Adjust the thermostat to deactivate the heating de
mand.
attempt to manually light
5 - Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al
low the burners to fire for approximately 3 minutes.
6 - Adjust the thermostat to deactivate the heating de
mand and wait for the combustion air inducer to stop.
At this point, the trap should be primed with sufficient
water to ensure proper condensate drain operation.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figure 60)
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 - Remove the access panel.
6 - Move gas valve switch to OFF. See figure 60.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instruc
tions. If you do not smell gas go to next step.
8 - Move gas valve switch to ON. See figure 60.
9 - Replace the access panel.
10- Turn on all electrical power to to the unit.
11- Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
INLET PRESSURE POST
GAS VALVE SHOWN IN ON POSITION
12- If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service techni
cian or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting.
2 - Turn off all electrical power to the unit if service is to be
performed.
3 - Remove the access panel.
MANIFOLD
PRESSURE POST
FIGURE 60
HIGH FIRE ADJUSTMENT
SCREW
(under cap)
Page 55
Page 56
4 - Move gas valve switch to OFF.
5 - Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat?
2 - Are access panels securely in place?
3 - Is the main disconnect switch closed?
4 - Is there a blown fuse or tripped breaker?
5 - Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 - Is gas turned on at the meter?
7 - Is the manual main shut‐off valve open?
8 - Is the internal manual shut‐off valve open?
9 - Is the unit ignition system in lockout? If the unit locks out
again, inspect the unit for blockages.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air inducer
starts.
2 - Combustion air pressure switch proves blower opera
tion. Switch is factory-set and requires no adjustment.
3 - After a 15-second prepurge, the hot surface ignitor en
ergizes.
4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second Trial for Ignition peri
od begins.”
5 - Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6 - If flame is not detected after first ignition trial, the igni
tion control will repeat steps 3 and 4 four more times
before locking out the gas valve (“WATCHGUARD”
flame failure mode). The ignition control will then auto
matically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60-minute “WATCHGUARD” period,
move thermostat from “Heat” to “OFF” then back to
“Heat”. Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 22
GAS METER CLOCKING CHART
Seconds for One Revolution
EL296
Unit
-04580160200400
-07055110136272
-0904182102204
-110336682164
Natural-1000 btu/cu ft LP-2500 btu/cu ft
NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
Furnace should operate at least 5 minutes before check
ing gas flow. Determine time in seconds for two revolu
tions of gas through the meter. (Two revolutions assures a
more accurate time). Divide by two and compare to time
in table 22. If manifold pressure matches table 24 and rate
is incorrect, check gas orifices for proper size and restric
tion. Remove temporary gas meter if installed.
Supply Pressure Measurement
An inlet pressure post located on the gas valve provides ac
cess to the supply pressure. See figure 60. Back out the
3/32 hex screw one turn, connect a piece of 5/16 tubing and
connect to a manometer to measure supply pressure. See
table 24 for supply line pressure.
Manifold Pressure Measurement
A manifold pressure post located on the gas valve provides
access to the manifold pressure. See figure 60. Back out
the 3/32 hex screw one turn, connect a piece of 5/16 tubing
and connect to a manometer to measure manifold pres
sure.
To correctly measure manifold pressure, the differential
pressure between the positive gas manifold and the nega
tive burner box must be considered.
NOTE - Pressure test adapter kit (10L34) is available from
Lennox to facilitate manifold pressure measurement.
1 - Connect the test gauge positive side “+“ to manifold
pressure tap on gas valve as noted above.
2 - Tee into the gas valve regulator vent hose and connect
to test gauge negative “-”.
3 - Ignite unit on low fire and let run for 5 minutes to allow
for steady state conditions.
4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
24.
5 - If necessary, make adjustments. Figure 60 shows
location of high fire and low fire adjustment screws.
6 - Repeat steps 3, 4 and 5 on high fire. See values in
table 24.
7 - Shut unit off and remove manometer as soon as an ac
curate reading has been obtained. Turn the supply
and manifold 3/32” hex screw one revolution back into
the gas valve.
8 - Start unit and perform leak check. Seal leaks if found.
Page 56
Page 57
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com
bustion. Take combustion sample beyond the flue outlet
and compare to the tables below. The maximum carbon
monoxide reading should not exceed 100 ppm.
TABLE 23
CO2%
EL296
Model
Low FireHigh FireLow FireHigh Fire
For Nat
0455.6 - 6.67.8 - 8.86.6 - 7.69.1 - 10.1
0705.5 - 6.57.3 - 8.36.5 - 7.58.6 - 9.6
0905.9 - 6.97.8 - 8.86.9 - 7.99.1 - 10.1
1106.3 - 7.38.2 - 9.27.3 - 8.39.5 - 10.5
The maximum carbon monoxide reading should not exceed 50 ppm.
Manifold and Supply Line Pressures at Varying Altitudes
CO2%
For L.P
TABLE 24
High Altitude Information
NOTE - In Canada, certification for installations at eleva
tions over 4500 feet (1372 m) is the jurisdiction of local au
thorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level without manifold adjustment. Units installed at al
titude of 4501 - 10,000 feet (1373 to 3048m) may require a
pressure switch change which can be ordered separately.
Table 25 lists conversion kit and pressure switch require
ments at varying altitudes.
The combustion air pressure switch is factory-set and re
quires no adjustment.
Manifold Pressure in. wg.
EL296
Unit
All
Sizes
NOTE -A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
EL296
Unit
-045
Natural to
LP/Propane
0 - 7500 ft
(0 - 2286m)
High Altitude
Natural Burner
Orifice Kit
7501 - 10,000 ft
(2286 - 3038m)
High Altitude
LP/Propane Burner
Orifice Kit
7501 - 10,000 ft
(2286 - 3038m)
High Altitude Pressure Switch
4501 - 7500 ft
(1373 - 2286m)
7501 -10,000 ft
(2286 - 3048m)
14A4714A50
-07014A5514A56
-09014A5414A53
*11K5173W37*11K46
-11014A4614A51
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
Page 57
Page 58
Testing of Non-Direct Vent Applications
for Proper Venting and Sufficient Combus
tion Air
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monox
ide poisoning or death.
The following steps shall be followed for each ap
pliance connected to the venting system being
placed into operation, while all other appliances con
nected to the venting system are not in operation.
After the EL296DFV gas furnace has been started, the fol
lowing test should be conducted to ensure proper venting
and sufficient combustion air has been provided to the
EL296DFV as well as to other gas‐fired appliances which
are separately vented.
If a EL296DFV furnace replaces a Category I furnace
which was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas appliance must
be checked. Without the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent should
be checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in
operation and those not in operation) are connected to the
venting system being tested. If the venting system has
been installed improperly, or if provisions have not been
made for sufficient amounts of combustion air, corrections
must be made as outlined in the previous section.
1 - Seal any unused openings in the venting system.
2 - Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re
striction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
3 - To the extent that it is practical, close all building doors
and windows and all doors between the space in which
the appliances connected to the venting system are lo
cated and other spaces of the building.
4 - Close fireplace dampers.
5 - Turn on clothes dryers and any appliances not con
nected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan.
6 - Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously.
7 - Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 min
utes of main burner operation.
8 - If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make‐up air must be provided.
The venting system should be re‐sized to approach
the minimum size as determined by using the ap
propriate tables in appendix G in the current standards
of the National Fuel Gas Code ANSI-Z223.1/NPFA 54
in the U.S.A., and the appropriate Natural Gas and
Propane appliances venting sizing tables in the cur
rent standard of the CSA-B149 Natural Gas and Pro
pane Installation Codes in Canada.
9 - After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, fireplace dampers
and any other gas‐burning appliance to their previous
condition of use.
Other Unit Adjustments
NOTE - See troubleshooting flow charts if any safety
switches are found to be open.
Primary Limit.
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and requires no ad
justment.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of
the burner box.
Pressure Switch
The pressure switch is located in the heating compartment
on the cold end header box. This switch checks for proper
combustion air inducer operation before allowing ignition
trial. The switch is factory-set and must not be adjusted.
Temperature Rise
Place the unit into operation with a second-stage heating
demand. After supply and return air temperatures have
stabilized, check the temperature rise. If necessary, adjust
the heating blower speed to maintain the temperature rise
within the range shown on the unit nameplate. Increase the
blower speed to decrease the temperature rise. Decrease
the blower speed to increase the temperature rise. Failure
to properly adjust the temperature rise may cause erratic
limit operation.
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC +
3 - Check amp-draw on the blower motor with blower ac
cess panel in place.
Motor Nameplate__________Actual__________
Exhaust and Air Intake Pipe
1 - Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 - Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check ter
mination for blockages.
3 - Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
10%
Page 58
Page 59
Heating Sequence of Operation
Electronic Ignition
The two-stage, variable speed integrated control used in
EL296DFV units has an added feature of an internal Watch
guard control. The feature serves as an automatic reset de
vice for ignition control lockout caused by ignition failure. Af
ter one hour of continuous thermostat demand for heat, the
Watchguard will break and remake thermostat demand to
the furnace and automatically reset the control to begin the
ignition sequence.
NOTE - The ignition control thermostat selection DIP switch is
factory-set in the “TWO-STAGE” position.
Applications Using a Two-Stage Thermostat
See figure 61 for ignition control sequence
A - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 OFF in “Two-Stage” Position
(Factory Setting)
1 - On a call for heat, thermostat first-stage contacts close
sending a signal to the integrated control. The inte
grated control runs a self‐diagnostic program and
checks high temperature limit switches for normally
closed contacts and pressure switches for normally
open contacts. The combustion air inducer is ener
gized at low speed.
2 - Once the control receives a signal that the low pres
sure switch has closed, the combustion air inducer be
gins a 15-second pre-purge in low speed.
NOTE - If the low fire pressure switch does not close
the combustion air inducer will switch to high fire. After
a 15 second pre-purge the high fire pressure switch
will close and the unit will begin operation on high fire.
After 10 to 20 seconds of high fire operation the unit
will switch to low fire..
3 - After the pre-purge is complete, a 20-second initial ig
nitor warm-up period begins. The combustion air in
ducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc
curs. At the same time, the control module sends a sig
nal to begin an indoor blower 30-second ON-delay.
When the delay ends, the indoor blower motor is ener
gized on the low fire heating speed, the HUM contacts
close energizing the humidifier and 120V ACC termi
nal is energized. The furnace will continue this opera
tion as long as the thermostat has a first-stage heating
demand.
5 - If second-stage heat is required, the thermostat sec
ond-stage heat contacts close and send a signal to the
integrated control. The integrated control initiates a
30-second second-stage recognition delay.
6 - At the end of the recognition delay, the integrated con
trol energizes the combustion air inducer at high
speed. The control also checks the high fire (second
stage) pressure switch to make sure it is closed. The
high fire (second stage) gas valve is energized and the
indoor blower motor is energized for operation at the
high fire heating speed.
7 - When the demand for high fire (second stage) heat is
satisfied, the combustion air inducer is switched to the
low-fire heating speed and the high-fire (second
stage) gas valve is de-energized. The low-fire (first
stage) gas valve continues operation. The indoor
blower motor is switched to the low-fire heating speed.
8 - When the thermostat demand for low-fire (first stage)
heat is satisfied, the gas valve is de-energized and the
field-selected indoor blower off delay begins. The
combustion air inducer begins a 5-second post-purge
period.
9 - When the combustion air post-purge period is com
plete, the inducer and the HUM contacts are de-ener
gized. The indoor blower is de-energized at the end of
the off delay as well as the 120V ACC terminals.
Applications Using A Single-Stage Thermostat
See figure 62 for ignition control sequence
B - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 ON in “Single-Stage” Position
NOTE - In these applications, two-stage heat will be initi
ated by the integrated control if heating demand has not
been satisfied after the field adjustable period (7 or 12 min
utes).
1 - On a call for heat, thermostat first-stage contacts close
sending a signal to the integrated control. The inte
grated control runs a self‐diagnostic program and
checks high temperature limit switches for normally
closed contacts and pressure switches for normally
open contacts. The combustion air inducer is ener
gized at low speed.
2 - Once the control receives a signal that the low pres
sure switch has closed, the combustion air inducer be
gins a 15-second pre-purge in low speed.
NOTE - If the low fire pressure switch does not close
the combustion air inducer will switch to high fire. After
a 15 second pre-purge the high fire pressure switch
will close and the unit will begin operation on high fire.
After 10 to 20 seconds of high fire operation the unit
will switch to low fire.
3 - After the pre-purge is complete, a 20-second initial ig
nitor warm-up period begins. The combustion air in
ducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended, the gas
valve is energized on low fire (first stage) and ignition oc
curs. At the same time, the control module sends a sig
nal to begin an indoor blower 30-second ON-delay.
When the delay ends, the indoor blower motor is ener
gized on the low fire heating speed, the HUM contacts
close energizing the humidifier and 120V ACC termi
nal is energized. The integrated control also initiates
a second-stage on delay (factory-set at 7 minutes; ad
justable to 12 minutes).
5 - If the heating demand continues beyond the second-
stage on delay, the integrated control energizes the
combustion air inducer at high speed. The control also
checks the high fire (second stage) pressure switch to
make sure it is closed. The high fire (second stage)
gas valve is energized and the indoor blower motor is
energized for operation at the high fire heating speed.
Page 59
Page 60
6 - When the thermostat heating demand is satisfied, the
combustion air inducer begins a 5-second low speed
post-purge. The field-selected indoor blower off delay
begins. The indoor blower operates at the low-fire
heating speed.
HEATING OPERATION WITH TWO-STAGE THERMOSTAT
ON
OFF
1 stg heat demand
low speed CAI
ignitor
low fire gas valve
indoor blower low heat
1
Pre-Purge
15
Ignitor Warm-up
35
Trial For
Ignition
7 - When the combustion air post-purge period is com
plete, the inducer and the HUM contacts are de-ener
gized. The indoor blower is de-energized at the end of
the off delay as well as the 120V ACC terminals.
39
30* second
“on” delay
blower
5 SEC80
Post
Purge
blower
“off”
delay
2 stg heat demand
high speed CAI
high fire gas valve
indoor blower high heat
* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.
30 seconds
FIGURE 61
HEATING OPERATION WITH SINGLE STAGE THERMOSTAT
351
Trial For
Ignition
ON
OFF
heat demand
low speed CAI
ignitor
low fire gas valve
indoor blower low heat
7 or 12 minutes after heating demand begins, furnace switches to high fire (depending on setting)
high speed CAI
high fire gas valve
indoor blower high heat
* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.
Pre-Purge
15
Ignitor Warm-up
FIGURE 62
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or
property damage.
Improper servicing could result in dangerous opera
tion, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to dis
connecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply
with the Lennox Limited Warranty, your system should be
checked as follows:
RECOGNITION PERIOD
39
30* second
blower
“on” delay
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal inju
ry or death.
1- Check wiring for loose connections, voltage at indoor
unit and amperage of indoor motor
2- Check the condition of the belt and shaft bearings if ap
plicable.
3- Inspect all gas pipe and connections for leaks
4- Check the cleanliness of filters and change if necessary
(monthly).
5 Check the condition and cleanliness of burners and
heat exchanger and clean if necessary.
WARNING
.
5 SEC80
Post
Purge
blower
“off”
delay
.
Page 60
Page 61
6 Check the cleanliness of blower assembly and clean
the housing, blower wheel and blower motor if neces
sary
.
7- Inspect the condensate drain and trap for leaks and
cracks. The drain and trap must also be cleaned and the
trap must be primed with water. Inspect the rubber
hoses connected to the pressure switches for cracks or
loose connections, replace as necessary. Remove the
rubber hoses from the cold end header box and inspect
for any blockage, clean as needed. If strainers are in
stalled in the hoses remember to remove and clean be
fore reinstalling the hoses.
8- Evaluate the heat exchanger integrity by inspecting the
heat exchanger per the AHRI heat exchanger inspec
tion procedure. This procedure can be viewed at
www.ahrinet.org
9- Ensure sufficient combustion air is available to the fur
nace. Fresh air grilles and louvers (on the unit and in the
room where the furnace is installed) must be properly
sized, open and unobstructed to provide combustion
air
.
10 Inspect the furnace intake and exhaust pipes to make
sure they are in place, structurally sound, without holes,
blockage or leakage and the exhaust pipe is sloped to
ward the furnace. Inspect terminations to ensure they
are free of obstructions and are structurally sound.
Inspect the furnace return air duct connection to ensure
the duct is sealed to the furnace. Check for air leaks on
supply and return ducts and seal where necessary
11 Inspect the furnace return air duct connection to ensure
the duct is sealed to the furnace. Check for air leaks on
supply and return ducts and seal where necessary
12 Check the condition of the furnace cabinet insulation
and repair if necessary.
13 Perform a complete combustion analysis during the fur
nace inspection to ensure proper combustion and oper
ation. Consult Service Literature for proper combustion
values.
14 Verify operation of CO detectors and replace batteries
as required.
Perform a general system test. Turn on the furnace to
check operating functions such as the start-up and shut-off
operation.
1 - Check the operation of the ignition system, inspect
and clean flame sensor. Check microamps before and
after. Check controls and safety devices (gas valve,
flame sensor, temperature limits). Consult Service
.
.
Manual for proper operating range. Thermal Limits
should be checked by restricting airflow and not dis
connecting the indoor blower. For additional details,
please see Service and Application Note H049.
2 - Verify that system total static pressure and airflow set
tings are within specific operating parameters.
3 - Clock gas meter to ensure that the unit is operating at
the specified firing rate for each stage of operation.
Check the supply pressure and the manifold pressure
on both low fire and high fire. If manifold pressure ad
justment is necessary, consult the Service Literature
for unit specific information on adjusting gas pressure.
Not all gas valves are adjustable. Verify correct tem
perature rise.
Winterizing and Condensate Trap Care
1 - Turn off power to the furnace.
2 - Have a shallow pan ready to empty condensate water.
3 - Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
drain plug.
Cleaning the Burner Assembly (if needed)
1 - Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 - Disconnect the 2-pin plug from the gas valve.
3 - Remove the burner box cover (if equipped).
4 - Disconnect the gas supply line from the gas valve. Re
move gas valve/manifold assembly.
5 - -Loosen clamps and remove combustion air intake
flexible connector (if equipped).
5 - Mark and disconnect sensor wire from the sensor. Dis
connect plug from the ignitor at the burner box.
6 - Remove four screws which secure burner box assem
bly to vest panel. Remove burner box from the unit.
7 - Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block
age caused by foreign matter. Remove any blockage.
8 - Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports.
9 - Reconnect the sensor wire and reconnect the 2-pin
plug to the ignitor wiring harness.
10 - Reinstall combustion air intake flexible connector (if
equipped), secure using existing clamps.
11 - Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn
er box cover.
12 - Reconnect plug to gas valve.
13 - Replace the blower compartment access panel.
14 - Refer to instruction on verifying gas and electrical con
nections when re-establishing supplies.
15 - Follow lighting instructions to light and operate fur
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly.
16 - Replace access panel.
Page 61
Page 62
Program Unit Capacity/Size Mode
Power-Up - Number displayed represents by integrated control unit size code (furnace model
and capacity). If three horizontal bars are displayed followed by continuous E203, furnace
control does not recognize unit size code. Configure per the following:
Yes
To enter Program UnitCapacity/Size: push
and hold button next to
7-segment LED display
until solid “P” symbol
appears. Release
button.
IMPORTANT: Field replacement controls may
need to be manually configured to validate
furnace unit size code.
Solid P starts
blinking on
7-Segment LED
P
Furnace control in IDLE mode
No heating, cooling or indoor fan
operation)
_
UNIT SIZE
CODE
−
−
−
No
Turn room thermostat to OFF
FURNACE MODEL
0
1
2
3
4
5
6
7
EL296UH045V36B
EL296UH070V36B
EL296UH090V36B
EL296UH09048C
EL296UH090V60C
EL296UH110V48C
EL296UH110V60C
EL296UH135V60D
UNIT SIZE
CODE
8
9
11
U
FURNACE MODEL
EL296DF0450V36A
EL296DF070V48B
EL296DF090V60C
EL296DF110V60C
Push and hold button. Integrated control will
display unit size code number for each
furnace model for three seconds.
When the correct unit size code is displayed, release
button. Selected code will flash for 10-second period.
During that period, press and hold push button for 5
seconds. Integrated control will store code in
memory and will automatically exit Program UnitCapacity/Size Mode and reset. (If second period
expires or push button is held less than five seconds,
control will automatically exit ProgramCapacity/Size Mode and go into IDLE mode without
storing unit size code. If this happens, programming
function must be repeated).
−
. If
−
−
Verify that the selected unit size code is correct
and stored in non-volatile memory by cycling
the 24 volt power to the furnace control. (At 24
volt power-up of the furnace control, the
7-segment LED will display a unit size code
three horizontal bars display, board does not
recognize unit size code
function must be repeated)
. Programming
FINISHED
Page 62
Page 63
Requirements for Commonwealth of Massachusetts
Modifications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following re
quirements:
For all side wall, horizontally vented, gas-fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the finished grade in the area of the venting, in
cluding but not limited to decks and porches, the following
requirements shall be satisfied:
1 - INSTALLATION OF CARBON MONOXIDE DETEC
TORS. At the time of installation of the side wall, hori
zontally vented, gas-fueled equipment, the installing
plumber or gasfitter shall observe that a hard-wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery-oper
ated or hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the dwell
ing, building or structure served by the side wall, hori
zontally vented, gas-fueled equipment. It shall be the
responsibility of the property owner to secure the ser
vices of qualified licensed professionals for the instal
lation of hard-wired carbon monoxide detectors.
a - In the event that the side wall, horizontally vented,
gas-fueled equipment is installed in a crawl space
or an attic, the hard-wired carbon monoxide detec
tor with alarm and battery back-up may be installed
on the next adjacent floor level.
b - In the event that the requirements of this subdivi
sion cannot be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery-operated carbon monoxide detec
tor with an alarm shall be installed.
2 - APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accor
dance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certi
fied.
3 - SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade di
rectly in line with the exhaust vent terminal for the hori
zontally vented, gas-fueled heating appliance or
equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECT
LY BELOW. KEEP CLEAR OF ALL OBSTRUC
TIONS.”
4 - INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas-fueled equipment
shall not approve the installation unless, upon inspec
tion, the inspector observes carbon monoxide detec
tors and signage installed in accordance with the pro
visions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1 - The equipment listed in Chapter 10 entitled “Equip
ment Not Required to Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2 - Product Approved side wall, horizontally vented, gas-
fueled equipment installed in a room or structure sepa
rate from the dwelling, building or structure used in
whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment provides a vent
ing system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
1 - Detailed instructions for the installation of the venting
system design or the venting system components:
and
2 - A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment does not pro
vide the parts for venting the flue gases, but identifies “spe
cial venting systems,” the following requirements shall be
satisfied by the manufacturer:
1 - The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2 The “special venting systems” shall be Product Ap
proved by the Board, and the instructions for that sys
tem shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instruc
tions shall remain with the appliance or equipment at
the completion of the installation.
Page 63
Page 64
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model
number listed on the CSA nameplate -- Example: EL296DFV04536B. All service must be performed by a licensed pro
fessional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Outer access panel
Blower access panel
Top Cap
Control Panel Parts
Transformer
Integrated control board
Door interlock switch
Blower Parts
Blower wheel
Motor
Motor mounting frame
Heating Parts
Flame Sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orifices
Pressure switch
Ignitor
Primary limit control
Flame rollout switches
Motor capacitor
Blower housing cutoff plate
FOR THE PROVINCE OF ONTARIO, HORIZONTAL SIDEWALL VENT APPLICATIONS ONLY
For exterior horizontal venting applications, the 2” X 1.5”
reducer for 2” venting at the point where the exhaust pipe
exits the structure is not required in direct or nondirect vent
applications in the Province of Ontario. In these applica
tions, the vent should be oriented such that the exhaust
plume is unobjectionable. If the installation requires more
separation between the flue gases and the building struc
ture, a reducer may be installed on the exhaust pipe to in
crease the flue gas velocity.
ADDENDUM FOR THE PROVINCE OF SASKATCHEWAN
See below for venting in the province of Saskatchewan.
Lennox approves the following termination for use in
Saskatchewan Canada.
3” (76MM)
Vent Pipe
6” (152 mm) Min.
24” (610 mm) Max.
6” (152 mm) Max.
A − Clearance above grade or
average snow accumulation
B − Horizontal separation between
intake and exhaust
C − Exhaust pipe length
D − Wall support distance from top
of each pipe (intake/exhaust)
NOTE − Flue gas may be acidic and may adversely affect some building materials. If flue gases impinge
on the building materials, a corrosion−resistant shield should be used to protect the wall surface. The
shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks,
etc. in affected area, should be sealed using an appropriate sealant.
2” (51MM)
Vent Pipe
12” (305 mm) Min. 12” (305 mm) Min.
6” (152 mm) Min.
24” (610 mm) Max.
Per: Saskatchewan Code of Practice
6” (152 mm) Max.
C
D
B
12”
A
Page 64
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.