Lennox EL296DF045XV36B, EL296DF110XV60C, EL296DF070XV48B, EL296DF090XV60C Unit Information

Service Literature
Corp. 1126-L5
Revised 01/2018
EL296DFV(X)
icomfort
EL296DFV(X) series units are 90% efficiency gas furnaces used for upflow or horizontal applications only, manufac tured with Lennox Duralok heat exchangers formed of aluminized steel. EL296DFV(X) units are available in heat ing capacities of 44,000 to 110,000 Btuh and cooling ap plications up to 5 tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. Kits are available for conversion to LPG operation. EL296DFV(X) model units are equipped with the icomfort
®
eLight EL296DFV(X) unit meets the California Nitrogen Oxides (NO quirements. All units use a redundant gas valve to assure safety shut-off as required by C.S.A.
All specifications in this manual are subject to change. Pro cedures outlined in this manual are presented as a recom mendation only and do not supersede or replace local or state codes. In the absence of local or state codes, the guidelines and procedures outlined in this manual (except where noted) are recommendations only and do not consti tute code.
Specifications Page 2.............................
I Unit Components Page 5........................
II Installation Page 31.............................
III Start Up Page 55..............................
IV Heating System Service Checks Page 56.........
V Typical Operating Characteristics Page 59.........
VI Maintenance Page 59..........................
VII Wiring and Sequence of Operation Page 62......
VIII Field Wiring and Jumper Settings Page 67.......
IX Program Unit Capacity Size Mode Page 71.......
X Troubleshooting Page 72........................
two-stage variable speed integrated control.
) Standards and California Seasonal Efficiency re
x
TABLE OF CONTENTS
- ENABLED EL296DFV(X) SERIES UNITS
®
enabled Sur
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person al injury or loss of life. Installation and service must be performed by a licensed professional HVAC in staller (or equivalent), service agency or the gas sup plier.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal in jury. Take care while handling this equipment and wear gloves and protective clothing.
Page 1
© 2018 Lennox Industries Inc.

SPECIFICATIONS

Gas Heating Performance
High Fire
Temperature rise range - °F 35-65 35-65 40-70 45-75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
Low Fire
Temperature rise range - °F 20 - 50 25 - 55 30 - 60 35 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static ­in. w.g.
Connections in.
Intake / Exhaust Pipe (PVC) 2 / 2 2 / 2 2 / 2 2 / 2
Gas pipe size IPS 1/2 1/2 1/2 1/2
Condensate Drain Trap (PVC pipe) - i.d. 1/2 1/2 1/2 1/2
with furnished 90° street elbow 1/2 slip x 1/2 Mipt 1/2 slip x 1/2 Mipt 1/2 slip x 1/2 Mipt 1/2 slip x 1/2 Mipt
with eld supplied (PVC coupling) - o.d. 1/2 slip x 1/2 NPT 1/2 slip x 1/2 NPT 1/2 slip x 1/2 NPT 1/2 slip x 1/2 NPT
Indoor
Wheel nom. diameter x width - in. 10 x 9 11 x 10 11 x 11 11 x 11
Blower
Tons of add-on cooling 2 - 3 2.5 - 4 3 - 5 3 - 5
Air Volume Range - cfm 545 - 1360 575 - 1800 890 - 2130 860 - 2180
Electrical
Data
Blower motor full load amps 7.7
Maximum overcurrent protection 15 20 20 20
Shipping Data lbs. - 1 package 131 136 164 176
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
Model No. EL296DF045XV36B EL296DF070XV48B EL296DF090XV60C EL296DF110XV60C
1
AFUE 96% 96% 96% 96%
Input - Btuh 44,000 66,000 88,000 110,000
Output - Btuh 43,000 64,000 85,000 106,000
3.5 / 10.0 3.5 / 10.0 3.5 / 10.0 3.5 / 10.0
Input - Btuh 29,000 43,000 57,000 72,000
Output - Btuh 28,000 42,000 56,000 70,000
1.7 / 4.9 1.7 / 4.9 1.7 / 4.9 1.7 / 4.9
Heating 0.8 0.8 0.8 0.8
Cooling 1.0 1.0 1.0 1.0
Motor output - hp 1/2 3/4 1 1
Voltage 120 volts - 60 hertz - 1 phase
10.1 12.8 12.8
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
furnaces.
INSTALLATION CLEARANCES
Sides
Rear 0 inches (0 mm)
Top/Plenum 1 inch (25 mm)
Front 0 inches (0 mm)
Front (service/alcove) 24 inches (610 mm)
Floor
NOTE - Air for combustion must conform to the methods outlined in the National Fuel Gas Code (NFPA 54/ANSI-
NOTE - In the U.S. ue sizing must conform to the methods outlined in the current National Fuel Gas Code (NFPA
2
Z223.1) or the National Standard of Canada CAN/CSA-B149.1 “Natural Gas and Propane Installation
54/ANSI-Z223.1) or applicable provisions of local building codes. In Canada ue sizing must conform to
1
Clearance for installation on combustible oor if Optional Downow Combustible Flooring Base is installed be-
tween furnace and combustible oor. Not required in add-on cooling applications if installed in accordance with
local codes or National Fuel Gas Code ANSI-Z223.1 or CAN/CGA-149.1,.2. Do not install the furnace directly on
the methods outlined in National Standard of Canada CAN/CSA-B149.1.
Allow proper clearances to accommodate condensate trap and vent pipe installation.
carpeting, tile, or other combustible materials other than wood ooring.
Code”.
Page 2
1
0 inches (0 mm)
2
Combustible
OPTIONAL ACCESSORIES - ORDER SEPARATELY
NOTE - FURNACES CANNOT BE TWINNED!
“B” Width Models “C” Width Models
CABINET ACCESSORIES
Downow Combustible Flooring Base 11M60 11M61
CONDENSATE DRAIN KITS
Condensate Drain Heat Cable 6 ft. 26K68 26K68
24 ft. 26K69 26K69
50 ft. 26K70 26K70
Heat Cable Tape Fiberglass - 1/2 in. x 66 ft. 36G53 36G53
Aluminum foil - 2 in. x 60 ft. 16P89 16P89
Crawl Space Vent Drain Kit US 51W18 51W18
Canada 51W19 51W19
CONTROLS
icomfort Touch® Communicating Thermostat 49W95 49W95
1
Remote Outdoor Temperature Sensor
(for dual fuel and Humiditrol®)
2
Discharge Temperature Sensor 88K38 88K38
®
ComfortSense
3
Remote Outdoor Temperature Sensor
7000 Thermostat Y2081 Y2081
(for dual fuel and Humiditrol)
FILTERS
4
Downow Filter Cabinet 51W07 51W08
No. and Size of lter - in. (2) 16 x 20 x 1 (2) 16 x 20 x 1
NIGHT SERVICE KITS
Night Service Kit 14C99 14C99
Universal Service Kit - Switches 89W20 89W20
TERMINATION KITS
See Installation Instructions for specic venting information.
Termination Kits ­Direct Vent Applications Only
Concentric US - 2 in. 71M80 69M29
3 in. - - - 60L46
Canada - 2 in. 44W92 44W92
3 in. - - - 44W93
Flush-Mount US - 2, 2-1/2 or 3 in. 51W11 51W11
Canada - 2, 2-1/2 or 3 in. 51W12 51W12
Wall - Close
Couple
Wall - Close
Couple WTK
Termination Kits ­Direct or Non-Direct vent
5
Roof Termination Flashing Kit - Direct or Non-Direct Vent
Wall Ring Kit 2 in. 15F74
Roof 2 in. 15F75 15F75
US - 2 in. 22G44 - - -
3 in. 44J40 44J40
Canada - 2 in. 30G28 - - -
3 in. 81J20 81J20
2 in. 44J41 44J41
(2 ashings)
VENTING
7
Left Side Vent Kit 2 or 3 in. 87W73 87W73
1
Remote Outdoor Sensor may be used with an icomfort®-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a conventional
2
3
Remote Outdoor Temperature Sensor for ComfortSense 7000 Thermostat must be connected directly to the thermostat, Do not connect it directly to the icomfort® control.
5
Kits contain enough parts for two, non-direct vent installations.
NOTE - The curved exhaust pipe furnished with the Left Side Vent Kit counts as one additional 2 in. diameter 90° elbow. When using 3 in. diameter pipe, the furnished
curved exhaust pipe and eld provided ttings to transition from 2 in. to 3 in. count as 20 feet of equivalent pipe on all units.
NOTE - Termination Kits 44W92, 44W93, 30G28, 51W12, 51W19, 81J20 are certied to ULC S636 standard for use in Canada only.
Optional for service diagnostics.
4
Cleanable polyurethane, frame-type lter.
outdoor unit.
6
Non-direct vent only.
X2658 X2658
X2658 X2658
6
15F74
Page 3
CONTROL BOX
(Includes integrated control,
transformer and door switch)
EL296DFV PARTS IDENTIFICATION
VARIABLE SPEED MOTOR
(hidden)
BAG ASSEMBLY (shipping location)
COMBUSTION AIR INDUCER
OUTER
ACCESS
PANEL
COMBUSTION AIR INDUCER
PRESSURE SWITCH
BURNER BOX ASSEMBLY
(includes sensor, rollout switches and ignitor)
GAS VALVE
FIGURE 1
COLD END HEADER BOX
PRIMARY LIMIT
BLOWER DECK
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
TM
Page 4
I-UNIT COMPONENTS
EL296DFV(X) unit components are shown in figure 1. The gas valve, combustion air inducer and burners can be ac cessed by removing the access panel. Electrical compo nents are in the control box (figure 2) found in the blower section.
CAUTION
Electrostatic discharge can affect elec tronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.
A- Control Box
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V sec ondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in se ries with line voltage. When the inner blower access panel is removed the unit will shut down.
CONTROL BOX EL296DFV
Transformer
Circuit Breaker
Interlock Switch
SureLight
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the trans former (T1). The breaker is rated 3A at 32V. If the current exceeds this limit the breaker will trip and all unit opera tion will shutdown. The breaker can be manually reset by pressing the button on the face. See figure 3.
®
Integrated Control
FIGURE 2
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
WARNING
Shock hazard. Disconnect power before servicing. Integrated
control is not field repairable. If control is inoper able, simply replace entire control.
Can cause injury or death. Unsafe operation will re sult if repair is attempted.
4. Integrated Control (A92)
Units are equipped with the icomfort two-stage, variable speed integrated control. This control is used with the icomfort Touch® thermostat as part of a communicating comfort system. The control can also oper ate with a non-communicating conventional single or two­stage thermostat. The system consists of a ignition / blow er control (figures 4 and 5) with control pin designations in tables 1, 2 and 3 and ignitor (figure 13). The control and ignitor work in combination to ensure furnace ignition and ignitor durability. The control provides gas ignition, safety checks and indoor blower control with two-stage gas heat ing. The furnace combustion air inducer, gas valve and in door blower are controlled in response to various system inputs such as thermostat signal, pressure and limit switch signal and flame signal. The control features a seven-seg ment LED display, indicating furnace status (including in door blower) and error codes. The LED flashes in single digits. For example using table 5 under LIMIT CODE, an “E” followed by “2” followed by “5” followed by “0”, the limit switch circuit is open. The control also has two unpowered (dry) 1/4” contacts for a humidifier and a 120 volt accessory terminal. Both rated at (1) one amp each.
Electronic Ignition
At the beginning of the heat cycle the integrated control monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by-passed). Likewise the integrated control will not begin the second stage heating cycle if the second stage prove switch is closed, and will remain in first stage heat. However, if the second stage prove switch closes during the first stage heat pre-purge, the control will allow second stage heat. Once the first stage prove switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15-second pre-purge begins.
NOTE - During abnormal conditions such as low supply voltage or low outdoor temperatures and the low fire pres sure switch does not close, the combustion air inducer will switch to high fire. After a 15 second pre-purge the high fire pressure switch will close and the unit will begin operation on high fire. After 10 to 20 seconds of high fire operation the unit will switch to low fire
After the 15-second pre-purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4-second trial for ignition. The ignitor remains ener gized during the trial until flame is sensed. If ignition is not
®
enabled SureLight
®
Page 5
proved during the 4-second period, the control will try four more times with an inter purge and warm-up time between trials of 35 seconds. After a total of five trials for ignition (in cluding the initial trial), the control goes into Watchguard­Flame Failure mode. After a 60-minute reset period, the control will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP Switch
The control can be utilized in two modes: SINGLE-STAGE thermostat or TWO-STAGE thermostat. The thermostat selection is made using a DIP switch and must be posi tioned for the particular application. DIP switch 1, labeled T”STAT HEAT STAGE is factory-set in the OFF position for use with a two-stage thermostat. Move the DIP switch to ON for use with a single stage thermostat. While in the single-stage thermostat mode, the burners will always fire on first-stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second stage heat after a "recognition period". DIP switch 2, labeled SECOND STAGE DELAY, is factory set in the OFF position for a 7 minute recognition period. The switch can be moved to the ON position for a 12 minute recognition period, after which time the unit will switch to secondstage heat. While in the two-stage thermostat mode, the burners will fire on first­stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second-stage heat on call from the indoor thermostat. If there is a simultaneous call for first and second stage heat, the unit will fire an first stage heat and switch to second stage heat after 30 seconds of opera tion. See Sequence of Operation flow charts in the back of this manual for more detail.
TABLE 1
®
SureLight
PIN # Function
Control 5 Pin Terminal Designation
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
TABLE 2
®
SureLight
Control 12 Pin Terminal Designation
PIN # Function
1 Gas Valve Second Stage
2 Second Stage Prove Switch
3 Rollout Switch In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve First Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 First Stage Prove Switch
TABLE 3
®
Control 6 Pin Terminal Designation
SureLight
PIN # Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6 Not Used
Page 6
HUM
LINE 1
7 SEGMENT LED
FLAME SENSE
DIAGNOSTIC
PUSH BUTTON
DIP SWITCHES
INTEGRATED CONTROL
ACC
HS/ CAI
INDOOR
BLOWER
CONNECTOR
NEUTRAL
OUTDOOR AIR
SENSOR
TERMINALS
DISCHARGE AIR
SENSOR
TERMINALS
TB83
icomfort
COMMUNICATING
OUTDOOR
EQUIPMENT
TB84
icomfort
COMMUNICATING
INDOOR
THERMOSTAT
I + I -CRI + I -
R
TB83 icomfort Communicating Outdoor Equipment
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
TB84 icomfort Communicating Indoor Thermostat
R = 24VAC I + = DATA HIGH CONNECTION I - = DATA LOW CONNECTION C = 24VAXC COMMON
1/4” QUICK CONNECT TERMINALS
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
XMFR = 120 VAC OUTPUT TO TRANSFORMER
LI = 120 VAC INPUT TO CONTROL
ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY
NEUTRALS = 120 VAC NEUTRAL
C
W1 W2 GY2Y1
NON-COMMUNICATING
24V TERMINALS
12 PIN LOW
VOLTAGE
CONNECTOR
W915 Y1 TO Y2
2 STAGE COMPR
W951 R TO O HEAT PUMP
W914 R TO DS
DEHUM OR
CC
RDHLODS
HARMONY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL W2 = HEAT DEMAND FROM 2ND STAGE T/STAT W1 = HEAT DEMAND FROM 1ST STAGE T/STAT
R = CLASS 2 VOLTAGE TO THERMOSTAT
G = MANUAL FAN FROM T'STAT
C = THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD (TR) & CHASIS GROUND (GRD)
Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL
Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL
O = THERMOSTAT SIGNAL TO HEAT PUMP
DH = DEHUMIDIFICATION OUTPUT COMMUNICATING
L = USE ONLY WITH A COMMUNICATING THERMOSTAT
AND A NON-COMMUNICATING OUTDOOR UNIT
REVERSING VALVE
THERMOSTAT ONLY
FIGURE 4
Page 7
THERMOSTAT SELECTION
1
2
3
*
TWO STAGE
THERMOSTAT
1STAGE
THERMOSTAT
(TIMED STAGING)
SEE SW #2
HEATING BLOWEROFF DELAY
*
90 SECOND
HTG BLOWER
OFF DELAY
60 SECOND
HTG BLOWER
OFF DELAY
120 SECOND
HTG BLOWER
OFF DELAY
180 SECOND
HTG BLOWER
OFF DELAY
BLOWER ON DELAY 30 SEC. FIXED
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
HEATING MODE BLOWER SPEED
9
11
10
+ 24%
+ 18%
+ 12%
INCREASE AIR HTG CFM
+ 6%
*
FACTORY
DEFAULT
6%
12%
DECREASE AIR HTG CFM
18%
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
5
6
7
5
6
7
5
6
7
5
6
7
5
6
7
5
6
7
13
12
13
12
13
12
13
12
13
12
13
12
13
12
13
121415
INTEGRATED CONTROL CONFIGURATION GUIDE
2ND STAGE HEAT ON DELAY
1
2
3
4
5
2
3
4
S1
7
8
15
14
INDOOR EQUIPMENT
1
6
5
6
HEAT PUMP LINK
(JUMPERS R to O)
7 MIN
UPSTAGE
DELAY
12 MIN
UPSTAGE
DELAY
FLAME
SENSE
123456
ON
S4S3
911
ON
OUTDOOR
SENSOR
DISCHARGE
AIR SENSOR
I+ I
OUTDOOR EQUIPMENT
ON
1
ON
DIAGNOSTIC
PUSH BUTTON
13
10
12
RI+ ICRI+ I− C
*
8
8
8
8
8
8
15
14
15
14
15
14
15
14
1STG COMPRESSOR
15
14
W915
2 STAGE
COMPR
DO NOT CUT
15
14
2STG COMPRESSOR
15
14
W915
2 STAGE
COMPR
CUT LINK
2STAGE
COMPRESSOR LINK
(JUMPERS Y1 to Y2)
W915
CLG BLOWER SPEED ADJUSTMENT
*
7
7
HUM
W1W2 G Y2 Y1 C C DH L O DSR
HEAT PUMP UNIT
DEFAULT
8
8
ACC
W1
W2GY2
ONBOARD LINK
OPTION SELECTION
A/C UNIT
W951
HEAT PUMP
DO NOT CUT
W951
HEAT PUMP
CUT LINK
1
W951
ON
ON
+ 10%
ON
10%
L1
DIAGNOSTIC
LED
SureLight
C
C
Y1
1
2
3
4
1
2
3
4
1
2
3
4
HSI/CAI
1
J3
IGN
CAI2
®
110
4 7
3
SELECTION
L
R
DH
NO HARMONY ZONING
OR
NO SIGNATURESTAT
W/ DS CONNECTION
DO NOT CUT
W914
DEHUM
or
HARMONY
HARMONY ZONING
SIGNATURESTAT W/
DS CONNECTION
CUT LINK
W914
DEHUM
or
HARMONY
DEHUMIDIFICATION
HARMONY LINK
(JUMPERS R to DS)
5
6
5
6
5
6
N
CAI1
14
3
CUT FOR
OPTION
W915
2 STAGE
COMPR
W951 HEAT
PUMP
W914 DEHUM
HARMONY
OR
1
W914
7
7
7
5
N
P79
6
12
8
CONTINUOUS FAN MODE BLOWER SPEED
8
8
NEUTRALS
MEDIUMLOW
*
SPEED
(38%)
MEDIUMHIGH
SPEED
(70%)
LOW
SPEED
(28%)
HIGH SPEED (100%)
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
COOLING MODE BLOWER SPEED
1
2
3
*
HIGH
SPEED
MEDIUMHIGH
J2
SPEED
MEDIUMLOW
SPEED
LOW
SPEED
COOLING MODE BLOWER RAMPING
*
OPTION A
OFF50%82%
100%50%OFF
OPTION B
OFF82%100%OFF
OPTION C
OFF100%100%OFF
OPTION D
OFF100%OFF
CUT ONBOARD LINK (SOLDER TRACE) COMPLETELY THROUGH
1
BOTH LAYERS ON THE CONTROL BOARD
LINKS CUT IN ERROR INSTALL A JUMPER ON THE APPROPRIATE
TERMINALS ON THE TERMINAL STRIP
PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE
REMOVED FOR EASE IN SETTING OF DIP SW.
* FACTORY DEFAULT
ON
1
2
3
ON
1
2
3
ON
1
2
3
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
9
11
10
ON
13
15
12
14
15
12
14
15
12
14
15
12
14
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
13
15
12
14
13
15
12
14
13
15
12
14
13
15
12
14
FIGURE 5
Page 8
TABLE 4

Integrated Control Diagnostic Modes

Display Action (when button released)
No change (idle)* Remain in idle mode
Solid “E” Enter diagnostic recall mode
Solid “F” Enter flame signal mode
Solid “P” (variable speed only) Program unit capacity/size (Unit Code)
__ Two horizontal bars __
Soft disable
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal, active error code, heat state, etc..)
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating status, target airflow, error codes and other information. The table beginning on Page 10 lists diagnostic LED codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the seven-segment diagnostic LED. This button is used to en able the Error Code Recall “E” mode, the Flame Signal “F” mode and “P” the Program Unit Capacity/Size mode. Press the button and hold it to cycle through a menu of options. Every five seconds a new menu item will be displayed. When the button is released, the displayed item will be se lected. Once all items in the menu have been displayed, the menu resumes from the beginning until the button is re
Program Unit Capacity/Size Mode
After the “P” is selected (by releasing the push button) the integrated control will start flashing the “P” on display for 90 seconds. If push button is pressed again and held during that time, the control will start to display characters corre sponding to different variable speed furnace models for 3 seconds each. While the wanted character-model is dis played push button has to be released. Selected option will flash display for 10 seconds and during that time push but ton has to be pressed and held for 5 seconds. Once control accepts new setting it will store data in non-volatile memory and reset itself. If 10 seconds expires or push button is held less than 5 seconds, control will exit field test mode and go into idle without changing programming the unit size.
leased.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 error codes. Select “c” from the Error Code Recall menu to clear all error codes. Button must be pressed a second time while “c” is flashing to confirm command to delete codes. Press the button until a solid “” is displayed to exit the Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the flame signal mode. The integrated control will display the flame current on seven-segment LED in in micro amps (uA).
Soft Disable
Soft disabling is when thermostat finds a device on the BUS that it does not recognize and the thermostat sends a the device a message to be in soft disabling mode until proper ly configured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying the soft disable code.
1- Confirm proper wiring between all devices (thermo stat, damper control module, indoor and outdoor).
2- Cycle power to the control that is displaying the soft disable code.
Flame signal mode is exited after any of the following:
Power is reset Pressing and holding push button until 3 horizontal
lines “≡” are displayed
10 minutes after entering the flame sense mode.
3- Put the room thermostat through set up.
4- Go to setup / system devices / thermostat / edit / then push reset.
5- Go to setup / system devices / thermostat / edit / then push resetAll.
Page 9
TABLE 5
Integrated Diagnostic Codes/Status of Equipment
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
.
Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF).
A
Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5 second OFF) / cfm setting for current mode displayed.
C
Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes).
d
Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting dis played / Pause / Repeat Codes).
h
Heat pump stage (1 second ON, 0.5 second OFF) / % of input rate dis played / Pause / cfm setting / Pause / Repeat codes.
H
Gas Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause / cfm setting displayed / Pause / Repeat codes. Blinking during ignition.
dF
Defrost mode.
U
Discharge Air Temperature
E 105
Device communication problem - No other devices on RS BUS (Commu nication system).
E 110
Low line voltage. Line Voltage Low (Voltage lower than nameplate
E 111
Line voltage polarity reversed. Reverse line power voltage wiring. System resumes
E 112
Ground not detected System shuts down. Provide proper earth ground.
E 113
High line voltage. Line Voltage High (Voltage higher than nameplate
E 114
Line voltage frequency out-of-range. No 60 Hertz Power. Check voltage and line power
E 115
Low 24V - Control will restart if the error recovers. 24-Volt Power Low (Range is 18 to 30 volts). Check
E 116
High 24V. 24 Volt Power High (Range is 18 to 30 volts). Check
E 117
Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper
E 120
Unresponsive device. Communication only. Usually caused by delay in outdoor unit responding
Equipment is unable to communicate. Indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis­wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high volt age source of noise close to the system. Fault clears after communication is restored.
rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.
normal operation 5 seconds after fault recovered.
System resumes normal operation 5 seconds after fault recovered.
rating). Provide power voltage within proper range. System resumes normal operation 5 seconds after fault recovered.
frequency. Correct voltage and frequency problems. System resumes normal operation 5 seconds after fault recovered.
and correct voltage. Check for additional power-rob bing equipment connected to system. May require installation of larger VA transformer to be installed in furnace / air handler. Clears after fault recovered.
and correct voltage. Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when con trol senses proper voltage.
earth ground to the system. Warning only will clear 30 seconds after fault recovered.
to indoor unit poling. Recycle power. Check all wir ing connections. Cleared after unresponsive device responds to any inquiry.
Page 10
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 124
Active communicating thermostat signal missing for more than 3 min utes.
E 125
Control failed self-check, internal error, failed hardware. Will restart if error recovers. Integrated control not communicating. Covers hardware errors (flame sense circuit faults, pin shorts, etc.).
E 126
Control internal communication problem. Hardware problem on the control. Cycle power on
E 131
Corrupted control parameters (Verify configuration of system). Communi cating only.
E 180
Outdoor air temperature sensor failure. Only shown if shorted or out-of­range.
E 200
Hard lockout - Rollout circuit open or previously open. Correct cause of rollout trip, or replace flame rollout
E 201
Indoor blower communication failure - Unable to communicate with blow er motor.
E 202
Indoor blower motor mis-match - Indoor motor horsepower does not match unit capacity. See Page 71.
E 203
Appliance capacity / size is NOT programmed. Invalid unit codes refer to configuration flow chart. See Page 71.
E 204
Gas valve mis-wired. Check gas valve operation and wiring. Clears when
E 205
Gas valve control relay contact shorted. Check wiring on control and gas valve. If wiring is
Equipment lost communication with the thermostat. Check four wiring connections, ohm wires and cycle power at the thermostat. Alert stops all services and waits for heartbeat message from thermostat (sub net controller). Cleared after valid thermostat (sub net controller) message is received.
Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Critical alert. Cleared 300 seconds after fault recovered.
control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recov ered.
Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode, not in startup. Exit from Com missioning and Execute 'Set Factory Default mode'. Control will still operate on default parameter set tings.
Compare outdoor sensor resistance to temperature/ resistance charts in unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s). If detected (reading in range), appropri ate feature will be set as 'installed' and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of set ting and alarm, redo configuration and make sure that temperature sensor is marked as 'not installed' in Indoor Unit 'About' screen. When Indoor unit con trol is replaced, thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.
switch. Test furnace operation. Cleared after fault recovered.
Indoor blower communication failure (including pow er outage). Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.
Incorrect appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air Handler on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove ther mostat from system while applying power and re programming.)
No appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Fur nace on configuration guide or in installation instruc tions. Critical Alert. Cleared after valid unit code is read following a reset. (Remove thermostat from system while applying power and reprogramming.)
repaired.
correct, replace control.
Page 11
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 206
Gas valve second-stage relay failure Furnace will operate on 1st stage for remainder of
the heating demand. Will clear after fault recovered. If unable to operate 2nd stage, replace control.
E 207
Hot surface ignitor sensed open - Refer to troubleshooting. See Page 72. Measure resistance of hot surface ignitor. Replace if
open or not within specified range found in IOM. Resumes normal operation after fault is cleared.
E 223
Low pressure switch failed open. Check pressure (inches w.c.) of low pressure switch
closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air in ducer for correct operation and restriction. Re sumes normal operation after fault is cleared
E 224
Low pressure switch failed closed - Refer to troubleshooting. See Page 72.
E 225
High pressure switch failed open - Refer to troubleshooting. See Page 72.
E 226
High pressure switch failed closed - Refer to troubleshooting. See Page 72.
E 227
Low pressure switch open during trial for ignition or run mode. Refer to troubleshooting. See Page 72.
E 228
Combustion air inducer calibration failure Unable to perform pressure switch calibration.
E 229
Ignition on High Fire - Information Only Code is displayed if 1) low pressure switch fails to
E 240
Low flame current - Run mode - Refer to troubleshooting. See Page 72. Check micro-amperes of flame sensor using control
E 241
Flame sensed out of sequence - Flame still present. Shut off gas. Check for gas valve leak. Replace, if
E 250
Limit switch circuit open - Refer to troubleshooting. See Page 72 Check for proper firing rate on furnace. Ensure
E 252
Discharge air temperature too high (gas heat only). Check temperature rise, air flow and input rate.
E 270
Soft lockout - Exceeded maximum number of retries. No flame current sensed.
Check operation of low pressure switch to see if it is stuck closed on heat call longer than 150 seconds. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct opera tion and restriction. Resumes normal operation after fault is cleared.
Check pressure (inches w.c.) of high pressure switch closing on heat call. Measure operating pres sure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Re sumes normal operation after fault is cleared.
Check operation of high pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal opera tion after fault is cleared.
Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air in ducer for correct operation and restriction. Re sumes normal operation after fault is cleared.
Check vent system and pressure switch wiring con nections. Resumes normal operation after fault is cleared.
close, then furnace will switch to high speed inducer to close both low and high pressure switches, then furnace lights on high fire, or 2) if continuous fan is active, furnace lights on high fire for 60 seconds to improve heat exchanger warm up time.
diagnostics or field-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Alert clears after current heat call has been completed.
necessary. Alert clears when fault is recovered.
there is no blockage in heater. Check for proper air flow. If limit not closed within 3 minutes, unit will go into 1-hour soft lockout. Resumes normal operation after fault is cleared.
Cleared when heat call is finished.
Check for proper gas flow. Ensure that ignitor is lighting burner. Check flame sensor current. Clears when heat call finishes successfully.
Page 12
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 271
Soft lockout - Exceeded maximum number of retries. Last retry failed due to the pressure switch opening.
E 272
Soft lockout - Exceeded maximum number of recycles. Last recycle due to the pressure switch opening.
E 273
Soft lockout - Exceeded maximum number of recycles. Last recycle due to flame failure.
E 274
Soft lockout - Exceeded maximum number of recycles. Last recycle failed due to the limit circuit opening or limit remained open longer than 3 minutes.
E 275
Soft lockout - Flame sensed out of sequence. Flame signal is gone. Shut off gas. Check for gas valve leak. 1-hour soft
E 276
Watchguard calibration failure. Unable to perform pressure switch calibration.
E 290
Ignitor circuit fault - Failed ignitor or triggering circuitry. Measure resistance of hot surface ignitor. Replace if
E 291
Heat air flow restricted below the minimum. Check for dirty filter and air flow restriction. Check
E 292
Indoor blower motor unable to start due to obstructed wheel, seized bearings.
E 294
Combustion air inducer over current. Check combustion blower bearings, wiring and
E 295
Indoor blower motor temperature is too high. Indoor blower motor over temperature (motor
E 310
Discharge error temperature sensor failure. Only shown if shorted or out of range.
E 311
Heat rate reduced to match indoor blower air flow. Warning Only. Furnace blower in cutback mode due
Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air in ducer for correct operation and restriction. Clears when heat call finishes successfully.
Check operation of low pressure switch to see if it is stuck closed on heat call. Check pressure (inches w.c.) of high pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct opera tion and restriction. Clears when heat call finishes successfully.
Check micro-amperes of flame sensor using control diagnostics or field-installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground. Clears when heat call finishes successfully.
Shut down system. 1-hour soft lockout. Check firing rate and air flow. Check for blockage. Clears when heat call finishes successfully.
lockout. Clears when flame has been proven stable.
Check vent system and pressure switch wiring con nections. 1-hour soft lockout. Clears when calibra tion has finished successfully.
open or not within specifications. 1-hour soft lock out. Clears when flame has been proven stable.
blower performance. 1-hour soft lockout. Cleared when heat call finishes successfully.
Indoor blower motor unable to start (seized bear ing, stuck wheel, etc.). Replace motor or wheel if assembly does not operate or meet performance standards. 1-hour soft lockout. Clears after circula tor successfully starts.
amps. Replace if does not operate or does not meet performance standards. Clears after inducer current is sensed to be in-range after the ignition following the soft lockout or reset.
tripped on internal protector). Check motor bearings and amps. Replace if necessary. Cleared after blower demand is satisfied.
Compare outdoor sensor resistance to temperature/ resistance charts in installation instructions. Re place sensor if necessary. Cleared in Communicat ing mode: 30 seconds after fault recovered. In Non­Communicating mode: Cleared after the current heat call is completed.
to restricted airflow. Reduce firing rate every 60 seconds to match available CFM. Check filter and duct system. To clear, replace filter if needed or re pair/add duct. 2-stage controls will reduce firing rate
st
stage. Clears when heat call finishes success
to 1 fully.
Page 13
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 312
E 313
E 331
E 334
E 347
E 348
E 349
E 370
E 400
E 401
E 402
E 403
E 404
E 405
Restricted air flow in cooling or continuous fan mode is lower than cfm setting.
Indoor or outdoor unit capacity mismatch. Communication only. Incorrect indoor/outdoor capacity code selected.
Global network connection - Communication link problem. For Future Use.
Relay “Y1” stuck on interated control. Replace integrated control.
No 24 Volt output on Y1 of ”integrated control” with non communicating outdoor unit.
No 24 Volt output on Y2 of ”integrated control” with non?communicating outdoor unit.
No 24 Volts between R & O on ”integrated control” with non communi cating outdoor unit (Dual fuel module required for heat pump applica tion).
Interlock switch sensed open for 2 minutes. Control sees the loss of 24VAC for 2 minutes .Ter
LSOM - Compressor internal overload tripped. Thermostat demand Y1 is present; but, compressor
LSOM Compressor long run cycle or low system pressure. Compressor ran more than 18 hours to satisfy a
LSOM - Outdoor unit system pressure trip. Discharge or suction pressure out-of-limits, or com
LSOM - Compressor short-cycling. .(Running less than 4 minutes). Out door unit pressure trip
LSOM - Compressor rotor locked. Compressor short-cycling. (Running less than 4 minutes).
LSOM - Compressor open circuit. Compressor circuit open (due to power disconnec
Warning Only. Restricted airflow - Indoor blower is running at a reduced CFM (Cutback Mode - The variable speed motor has pre-set speed and torque limiters to protect the motor from damage caused by operating outside of design parameters (0 to 0.8” W.C.. total external static pressure). Check filter and duct system. To clear, replace filter if needed or repair/add duct. Cleared after the current service demand is satisfied.
Check for proper configuring in installation instruc tions. Alarm is just a warning. The system will oper ate, but might not meet efficiency and capacity pa rameters. Alarm will clear when commissioning is exited. Cleared after commissioning is complete.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
Y2 relay / Stage 2 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
Configuration link R to O needs to be restored. Re place link or hard-wire. Applicable in non communi cating mode. Critical Alert.
minate all services and wait for interlock switch to close. The alarm will clear when 24VAC is continu ously sensed on DS terminal for a minimum of 10 seconds or on a power reset.
is not running. Check power to outdoor unit. Clears the error after current is sensed in both RUN and START sensors for at least 2 seconds, or after ser vice is removed, or after power reset.
single thermostat demand. Critical Alert. Clears the error after 30 consecutive normal run cycles or power reset. Also monitors low pressure switch trips.
pressor overloaded. Clears the error after 4 consec utive normal compressor run cycles.
Compressor runs less than 3 minutes to satisfy a thermostat demand. Clears the error after 4 consec utive normal run cycles or power reset.
Compressor rotor locked up due to run capacitor short, bearings are seized, excessive liquid refriger ant, etc. Clears the error after 4 consecutive normal run cycles or after power reset.
tion, open fuse, etc.) Clears the error after 1 normal compressor run cycle.
Page 14
TABLE 5 Continued
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E 406
E 407
E 408
E 409
LSOM - Compressor open start circuit. Required amount of current is not passing through
Start current transformer. Clears the error after cur rent is sensed in START sensor, or after power re set.
LSOM - Compressor open run circuit. Required amount of current is not passing through
Run current transformer. Clears the error after cur rent is sensed in RUN sensor, or 1 normal compres sor run cycle, or after power reset.
LSOM - Compressor contactor is welded. Compressor runs continuously. Clears the error
after 1 normal compressor run cycle or after power reset.
LSOM - Compressor low voltage. Secondary voltage is below 18VAC. After 10 min
utes, operation is discontinued. Clears the code after voltage is higher than 20 VAC for 2 seconds or after power reset.

DIP Switch Settings

NOTE - All icomfortt settings are set at the icomfort Wi-Fi thermostat. See icomfortt installation instruction. In icom fortt communication system all DIP switch and clippable link settings are ignored. For conventional thermostats pro ceed with DIP switch and clippable link settings as outlined in the following.
Heating Operation DIP Switch Settings Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat. The thermostat selection is made using a DIP switch which must be properly positioned for the particular application. The DIP switch is factory-positioned for use with a two­stage thermostat. If a single-stage thermostat is to be used, the DIP switch must be repositioned.
Select “OFF” for two-stage heating operation con
trolled by a two-stage heating thermostat (factory set ting);
b - Select “ON” for two-stage heating operation con
trolled by a single-stage heating thermostat. This set ting provides a timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with Single­Stage Thermostat Only) -- This switch is used to deter
mine the second stage on delay when a single-stage ther mostat is being used. The switch is factory-set in the OFF position, which provides a 7-minute delay before second­stage heat is initiated. If the switch is toggled to the ON position, it will provide a 12-minute delay before second­stage heat is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE­stage thermostat use.
Switches 3 and 4 -- Blower-Off Delay -- The blower-on delay of 30 seconds is not adjustable. The blower-off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 3 and 4 on the integrated control. The unit is shipped from the factory with a blower-off delay of 90 seconds. The blower
off delay affects comfort and is adjustable to satisfy individ
®
ual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de-energized. Longer off delay settings provide lower supply air temperatures; shorter set tings provide higher supply air temperatures.Table 6 pro vides the blower off timings that will result from different switch settings.
TABLE 6
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3 Switch 4
60 On Off
90 (Factory) Off Off
120 Off On 180 On On
Indoor Blower Operation DIP Switch Settings Switches 5 and 6 -- Cooling Mode Blower Speed -- The
unit is shipped from the factory with the dip switches posi tioned for high speed (4) indoor blower motor operation during the cooling mode. Table 7 provides the cooling mode blower speeds that will result from different switch settings. Switches 5 and 6 set the blower cfm for second­stage cool. The integrated control automatically ramps down to 70% of the second-stage cfm for first-stage cfm. Refer to tables for corresponding cfm values.
TABLE 7
Cooling Mode Blower Speeds
Speed
Switch 5 Switch 6
Low On On
Medium Low Off On
Medium High On Off
High (Factory) Off Off
Switches 7 and 8 -- Cooling Blower Speed Adjustment
-- The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or
Page 15
-10% to better suit the application. Table 8 below provides blower speed adjustments that will result from different switch settings. Refer to tables for corresponding cfm val ues.
TABLE 8
Cooling Blower Speed Adjustment
Adjustment
Switch 7 Switch 8
+10% (approx.) On Off Factory Default Off Off
-10% (approx.) Off On
Switches 9 and 10 -- Cooling Mode Blower Speed Ramping -- Blower speed ramping may be used to en
hance dehumidification performance. The switches are factory set at option A which has the greatest effect on de­humidification performance. Table 9 provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed below.
NOTE - In heat pump mode blower operation defaults to option c.
TABLE 9
Cooling Mode Blower Speed Ramping
Ramping Option
Switch 9 Switch 10
A (Factory) Off Off
B Off On C On Off D On On
Ramping Option A (Factory Selection)
Motor runs at 50% for 30 seconds. Motor then runs at 82% for approximately 7-1/2 minu
tes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 50% for 30 sec
onds then ramps down to stop.
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COMPRESSOR DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes, motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COMPRESSOR DEMAND
100% CFM
OFF
Ramping Option C
Motor runs at 100% until demand is satisfied.
Once demand is met, motor runs at 100% for 45 sec
onds then ramps down to stop.
OFF
100% CFM
COMPRESSOR
DEMAND
100% CFM
45 SEC.
OFF
Ramping Option D
Motor runs at 100% until demand is satisfied.
Once demand is met, motor ramps down to stop.
100% CFM
COMPRESSOR
DEMAND
OFFOFF
Switches 11, 12 and 13 -- Heating Mode Blower Speed --
The switches are factory set to the OFF position which pro vides factory default heat speed. Refer to table 10 for switches 11, 12 and 13 that provided the corresponding in creases or decrease to both high and low heat demand.
TABLE 10
Heating Mode Blower Speeds
Heat Speed
Switch11Switch12Switch
13
Increase 24% On On On
Increase 18% On On Off
Increase 12% On Off On
Increase 6% On Off Off
Factory Default Off Off Off
Decrease 6% Off Off On
Decrease 12% Off On Off
Decrease18% Off On On
Switches 14 and 15 -- Continuous Blower Speed --
Table 11 provides continuous blower speed adjustments that will result from different switch settings.
TABLE 11
Continuous Blower Speed
Continuous
Blower Speed
Switch 14 Switch 15
28% of High Cool Speed Off On
38% of High Cool Speed
(Factory)
Off Off
70% of High Cool Speed On Off
100% of High Cool Speed On On
Page 16

BLOWER DATA

EL296DF045XV36B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 910 1150
+18% 855 1095
+12% 820 1040
+6% 770 990
Factory Default 745 935
–6% 700 880
–12% 665 820
–18% 635 755
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 640 755 850 975 895 1050 1210 1360
Factory Default 580 695 780 880 805 965 1105 1250
545 645 720 795 735 865 1000 1130
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
NOTES - The effect of static pressure is included in air volumes shown.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 250 cfm.
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
First stage HEAT is approximately 91% of the same second stage HEAT.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 250 cfm.
tings.
Factory default setting.
2
High
EL296DF045XV36B BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Motor Watts @ Various External Static Pressures - in. wg.
+ Setting
Low 28 44 60 77 93 11 2 128 144 158 59 77 97 121 138 160 182 197 216 241 256
Cooling
Speed
Med-low 47 67 88 105 121 138 161 179 201 131 154 177 202 228 250 277 299 320 344 370
Med-High 69 91 11 3 132 160 183 204 220 246 199 215 248 275 308 340 360 390 407 431 445
High 100 11 7 153 172 192 215 240 260 286 292 313 363 379 419 452 488 5 11 526 523 524
Factory Default
Low 17 34 52 65 82 97 121 132 148 61 79 98 125
Cooling
Speed
Med-low 35 50 70 85 105 125 140 155 175 99 11 5 148 167 188 211 236 256 279 303 317
Med-High 54 72 95 113 131 148 173 189 210 147 170 197 223 252 278 301 330 355 373 398
High 74 96 11 8 141 168 190 212 233 252 216 229 258 303 325 356 390 410 426 448 465
– Setting
Low 17 31 49 61 75 91 107 123 136 46 64 82 101 115 134 155 174 196 205 221
Cooling
Speed
Med-low 28 45 61 77 93 11 2 129 144 159 72 92 114 133 160 184 204 221 247 263 282
Med-High 40 57 77 93 11 2 130 148 165 186 11 2 130 161 183 205 226 252 272
High 57 76 97 119 136 156 179 195 214 155 174 207 235 265 292 3 11 343 370 386 414
141 164 185 201 219 246 259
294 319 341
Page 17
BLOWER DATA
EL296DF070XV48B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1085 1635
+18% 1030 1525
+12% 950 1450
+6% 910 1365
Factory Default 850 1310
–6% 790 1225
–12% 740 1135
–18% 680 1060
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 740 915 1055 1255 1110 1340 1575 1800
Factory Default 660 820 940 1120 995 1230 1420 1650
575 735 850 995 880 1085 1290 1460
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
NOTES - The effect of static pressure is included in air volumes shown.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 380 cfm.
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
First stage HEAT is approximately 91% of the same second stage HEAT.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 380 cfm.
tings.
Factory default setting.
2
High
EL296DF070XV48B BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Motor Watts @ Various External Static Pressures - in. wg.
+ Setting
Low 68 88 109 132 154 178 199 213 238 144 169 208 244 270 310 343 378 401 432 457
Cooling
Speed
Med-low 93 120 147 172 198 220 254 274 304 257 276 326 370 398 437 470 492 531 558 598
Med-High 120 152 180 220 254 281 318 344 380 390 428 472 526 574 611 659 706 745 788 820
High 214 237 284 324 352 390 424 456 474 627 604 663 721 775 825 869 908 915 881 864
Factory Default
Low 35 54 74 92 109 129 147 163 191 104 137 162 189
Cooling
Speed
Med-low 75 100 115 140 165 190 210 230 255 188 203 250 297 327 374 399 432 454 486 513
Med-High 99 129 159 179 209 236 270 293 329 304 340 376 418 450 495 533 567 613 637 674
High 157 184 232 264 285 335 365 406 419 454 469 537 589 634 669 724 770 818 833 840
– Setting
Low 27 49 63 73 98 11 6 135 155 168 86 111 135 162 186 206 236 257 283 306 339
Cooling
Speed
Med-low 67 87 109 132 154 177 199 212 238 129 156 187 226 258 288 325 353 385 409 441
Med-High 82 105 127 153 176 196 223 243 269 226 244 290 335 364 402 435 465
High 107 141 164 195 224 263 282 321 347 329 375 403 444 481 526 570 612 656 680 718
219 254 278 312 341 369 400
485 516 556
Page 18
BLOWER DATA
EL296DF090XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1425 1895
+18% 1355 1825
+12% 1280 1740
+6% 1215 1660
Factory Default 1160 1575
–6% 1055 1455
–12% 1010 1365
–18% 950 1265
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 1115 1265 1400 1600 1600 1750 1970 2130
Factory Default 1005 1150 1275 1450 1450 1630 1810 1975
890 1065 1150 1270 1270 1450 1645 1810
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
NOTES - The effect of static pressure is included in air volumes shown.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm.
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
First stage HEAT is approximately 91% of the same second stage HEAT.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 450 cfm.
tings.
Factory default setting.
2
High
EL296DF090XV60C BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Motor Watts @ Various External Static Pressures - in. wg.
+ Setting
Low 79 108 144 162 207 242 262 293 323 275 299 366 399 449 483 532 584 605 644 680
Cooling
Speed
Med-low 120 156 187 233 261 279 329 368 401 387 409 471 521 562 606 650 688 716 762 800
Med-High 155 202 235 293 317 369 407 453 502 547 577 622 667 744 795 835 872 910 950 963
High 268 299 366 399 449 483 532 584 605 780 775 8 11 898 942 994 1048 1071 1082 1080 1073
Factory Default
Low 56 86 111 140 170 200 232 259 282 186 219 270 308
Cooling
Speed
Med-low 93 11 8 152 195 223 254 283 306 344 278 304 365 420 450 510 544 592 640 665 698
Med-High 123 161 201 228 260 310 341 381 416 446 475 528 582 616 662 686 747 780 823 855
High 182 219 270 308 361 390 431 489 517 576 603 654 704 756 809 871 902 939 972 975
– Setting
Low 48 69 101 120 152 175 201 218 249 11 8 155 181 232 259 299 340 376 402 438 476
Cooling
Speed
Med-low 65 94 123 150 185 220 250 278 296 177 205 267 304 353 390 430 486 515 563 587
Med-High 93 118 152 195 223 254 283 306 344 301 322 392 439 468 531 568 599
High 116 155 181 232 259 299 340 376 402 446 475 528 582 616 662 686 747 780 823 855
361 390 431 489 517 555 590
647 678 721
Page 19
BLOWER DATA
EL296DF110XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
+24% 1535 2015
+18% 1445 1935
+12% 1370 1855
+6% 1300 1760
Factory Default 1220 1645
–6% 1135 1545
–12% 1070 1420
–18% 1000 1335
1
Cooling Speed
DIP Switch
Settings
Low Medium-Low Medium-High
+ 1095 1265 1395 1585 1585 1790 1990 2180
Factory Default 965 1130 1285 1440 1440 1630 1845 2005
860 1035 1130 1275 1275 1475 1655 1845
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic DIP Switch Set-
NOTES - The effect of static pressure is included in air volumes shown.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm.
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
COOLING
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
2
High Low Medium-Low Medium-High
2
First stage HEAT is approximately 91% of the same second stage HEAT.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 450 cfm.
tings.
Factory default setting.
2
High
EL296DF110XV60C BLOWER MOTOR WATTS (COOLING)
1
Cooling Speed
DIP Switch
Settings
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Motor Watts @ Various External Static Pressures - in. wg.
+ Setting
Low 71 99 147 166 202 240 271 302 337 248 280 333 374 429 469 511 548 594 619 677
Cooling
Speed
Med-low 127 159 198 225 256 301 325 365 390 409 427 496 531 587 632 665 721 742 781 805
Med-High 162 204 242 287 316 371 408 446 487 563 589 651 703 755 808 860 888 932 970 1007
High 243 280 333 374 429 469 511 548 594 866 850 915 963 1020 1056 1091 1127 1141 1136 1131
Factory Default
Low 57 88 117 140 165 196 232 259 283 167 214 244 291
Cooling
Speed
Med-low 77 11 2 147 172 209 250 283 317 345 275 321 348 418 447 505 546 597 632 668 716
Med-High 122 154 199 230 268 300 331 373 411 461 493 547 572 628 666 703 745 777 819 860
High 167 214 244 291 331 380 405 467 497 601 626 688 730 787 823 880 924 963 994 1011
– Setting
Low 44 67 99 11 5 144 167 197 215 245 126 165 201 232 262 305 334 373 417 451 479
Cooling
Speed
Med-low 66 97 123 153 186 216 247 275 303 187 219 272 308 360 391 432 479 514 559 588
Med-High 77 112 147 172 209 250 283 317 345 308 341 390 430 490 528 569 617
High 127 165 201 232 262 305 334 373 417 461 493 547 572 628 666 703 745 777 819 860
331 380 405 467 497 539 583
640 691 724
Page 20
On-Board Links
Note: In icomfortt systems with a conventional outdoor unit (non-communicating), the on-board clippable links must be set to properly configure the system.
damage. Refer to table 12 for operation sequence in ap plications including EL296DFV, a thermostat which fea tures humidity control and a single-speed outdoor unit. Table 13 gives the operation sequence in applications with a two-speed outdoor unit.
On-Board Link W951 Heat Pump (R to O)
WARNING
Carefully review all configuration information pro vided. Failure to properly set DIP switches, jumpers and on-board links can result in improper operation!
On-board link W951 is a clippable connection between ter minals R and O on the integrated control. W951 must be cut when the furnace is installed in applications which include a heat pump unit and a thermostat which features dual fuel use. If the link is left intact, terminal “O” will remain ener
On-Board Link W914 Dehum or Harmony (R to DS)
On-board link W914, is a clippable connection between ter minals R and DS on the integrated control. W914 must be cut when the furnace is installed with either the Harmony III zone control or a thermostat which features humidity control. If the link is left intact the PMW signal from the Har mony III control will be blocked and also lead to control
gized eliminating the HEAT MODE in the heat pump.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board link W915 is a clippable connection between ter minals Y1 and Y2 on the integrated control. W915 must be cut if two-stage cooling will be used. If the Y1 to Y2 link is not cut the outdoor unit will operate in second-stage cool ing only.
TABLE 12
OPERATING SEQUENCE
EL296DFV, Non-Communicating Thermostat with Humidity Control Feature and Single-Speed Outdoor Unit
OPERATING SEQUENCE
System
Condition
NO CALL FOR DEHUMIDIFICATION
Normal Operation 1 On On On Acceptable
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidification
Call
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
Dehumidification
call
Dehumidification
call ONLY
Step
Jumpers at indoor unit with a single stage outdoor unit With Condensing unit - Cut W914 (R to DS) on SureLight With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight
Thermostat Demand Relative Humidity
Y1 O G
2 On On On Demand 0 VAC High 70%*
2 On On On Demand
1 On On On Demand
SYSTEM DEMAND SYSTEM RESPONSE
W
1
Status D
24
VAC
24
VAC
24
VAC
0
VAC
0
VAC
Compressor
High 100%
High 100%
High 100%
High 70%*
High 70%*
®
control
®
Blower
(COOL)
control
CFM
Comments
Compressor and indoor blower follow thermostat demand
ComfortSense® 7000 thermostat energizes Y1 and de-energizes D on a call for de-humidification
Dehumidification mode begins when humidity is greater than set point
®
ComfortSense thermostat maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint**
7000
will try to
Use Dave Lennox ComfortSense® 7000 thermostat Y2081 4 heat / 2 cool for this application *Dehumidification blower speed is 70% of COOL speed for all units . **In Precision mode, ComfortSense
®
7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
Page 21
TABLE 13
OPERATING SEQUENCE
EL296DFV, Non-Communicating Thermostat with Humidity Control Feature and Two-Speed Outdoor Unit
OPERATING
SEQUENCE
SYSTEM DEMAND SYSTEM RESPONSE
Thermostat Demand Relative Humidity
System
Condition
Ste
p
Y1 Y2 O G
W1W
2
Status D
NO CALL FOR DEHUMIDIFICATION
Normal Opera
tion - Y1
Normal Opera
tion - Y2
1 On On On Acceptable
2 On On On On Acceptable
24
VAC
24
VAC
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
Call
1 On On On Acceptable
2 On On On On Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
call
Dehumidification
call ONLY
1 On On On Acceptable
2 On On On On Demand
1 On On On On Demand
24
VAC
0
VAC
0
VAC
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
Call
1 On On On On Acceptable
2 On On On On Demand
24
VAC
0
VAC
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Opera
tion
Dehumidification
call
1 On On On Acceptable
2 On On On On Demand
24
VAC
0
VAC
Compressor
Low 70%*
High 100%
Low 70%*
High 70%**
Low 70%*
High 70%**
High 70%**
High 100%
High 70%**
Low 70%*
High 70%**
Blower
CFM
(COOL)
Comments
Compressor and indoor blower follow thermostat demand
ComfortSense
®
7000 thermostat energizes Y2 and de-energizes D on a call for de-humidification
Dehumidification mode begins when humidity is greater than set point
ComfortSense® 7000 thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint***
ComfortSense® 7000 thermostat energizes Y2 and de-energizes D on a call for de-humidification
Dehumidification mode begins when humidity is greater than set point
Dehumidification
call ONLY
1 On On On On Demand
0
VAC
Jumpers at indoor unit with a two stage outdoor unit Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2) With Condensing unit - Cut W914 (R to DS) on SureLight
®
control
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight
Use Dave Lennox ComfortSense® 7000 thermostat Y2081 4 heat / 2 cool for this application. *Normal operation first stage cooling blower speed is 70% COOL speed. **Dehumidification blower speed is, reduced to 70% of COOL. ***In Precision mode, ComfortSense
®
7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.
Page 22
High 70%**
®
control
ComfortSense® 7000 thermostat will try to maintain room humidity setpoint by allowing the room space to maintain a cooler room thermostat setpoint***
B- Indoor Blower Motor
Power Choke
(4 and 5 Ton Only)
To Remove Blower From Unit: Remove access panels,
Control box, Bolts and Wiring Jackplugs.
Blower Motor
(B3)
Then Slide Out Front of Unit.
FIGURE 6
WARNING
During blower operation, the ECM motor emits ener gy that may interfere with pacemaker operation. In terference is reduced by both the sheet metal cabinet and distance.
The motor communicates with the integrated control via a 2-way serial connection. The motor receives all necessary functional parameters from the integrated control and does not rely on a factory program like traditional variable speed motors. EL296DFV units use a three‐phase, electronically controlled D.C. brushless motor (controller converts single phase a.c. to three phase D.C.), with a permanent‐magnet‐ type rotor (figure 7). Because this motor has a permanent magnet rotor it does not need brushes like conventional D.C. motors. The stator windings are split into three poles which are electri cally connected to the controller. This arrangement allows motor windings to turn on and off in sequence by the con troller.
IMPORTANT
Earlier ECM motors used on other Lennox furnace models are not interchangeable with motors used on the EL296 furnace line.
A solid‐state controller is permanently attached to the motor. The controller is primarily an A.C. to D.C. con verter. Converted D.C. power is used to drive the motor. The controller contains a microprocessor which moni tors varying conditions inside the motor (such as motor workload).
BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
ROTOR
FIGURE 7
The controller uses sensing devices to sense what position the rotor is in at any given time. By sensing the position of the rotor and then switching the motor windings on and off in se quence, the rotor shaft turns the blower.
All EL296DFV blower motors use single phase power. An external run capacitor is not used. The motor uses permanently lubricated ball‐type bearings.
Internal Operation
The motor is controlled via serial communication between the integrated control on the furnace and the controller at tached to the motor shell. The messages sent back and forth between the two controls serve to communicate rota tional direction, demand, motor size, current draw, torque, and rpm, among other variables.
Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel. The control ler monitors the static work load on the motor and motor amp‐ draw to determine the amount of rpm adjustment. Blower rpm may be adjusted any amount in order to maintain a constant cfm as shown in Blower Ratings Tables. The cfm remains rel atively stable over a broad range of static pressure. Since the blower constantly adjusts rpm to maintain a specified cfm, mo tor rpm is not rated. Hence, the terms “cool speed”, “heat speed ” or “speed tap” in this manual, on the unit wiring dia gram and on blower B3, refer to blower cfm regardless of mo tor rpm.
Initial Power Up
When line voltage is applied to B3, there will be a large inrush of power lasting less than 1/4 second. This inrush charges a bank of DC filter capacitors inside the controller. If the discon nect switch is bounced when the disconnect is closed, the dis connect contacts may become welded. Try not to bounce the disconnect switch when applying power to the unit.
Page 23
Loading...
+ 53 hidden pages